Consumption figures for a Naphtha based Steamreformer 

with 1500 Nm³/h hydrogen capacityx 
 
A typical Naphtha: 

  Composition (mol.%)  

Cut Point ‐ Liq.V%     ASTM D86 [C] 
  10      56.2 
  30      80.5 
  50      97.6 
  70    120.2 
  90    156 
 
Density @15 C  kg/mc    723.5 
 
H2S content    ppmwt  40 
Mercaptan sulphur  ppmwt  10 
Sulfur, total    ppmwt  50 
Note: Less Sulphur is better of course. 
 
Paraffins    wt%  52.6 
Naphthenes     wt%  36.5 
Aromatics     wt%  11.1 
n‐ Paraffins    wt%  23.3 
 
Temperature 
Normal    °C   40 
Design    °C  50 
Pressure     
Normal    bar(abs)  5 
Design    bar(abs)  9 
 
LHV        10.600 kcal/kg (assumed) 
 
Remark:   If a naphtha with a slight different specification is available, this 
would not influence the design of the plant. The main criteria have to 
be considered: 
 
a) content of olefines: none 
 
b) S‐content: if a naphtha with a lower S‐content than stated above 
would be used, the absorption capacity respectively running time 
of the zincoxide bed(s) will be enlarged accordingly. 
 
d.) no particles or dust expected in naphtha 
 
Naphtha consumption: 
feed + fuel:  550‐560 kg/h (expected) for 1500 Nm³/h Hydrogen 
 
   
 
Cooling water        approx. 75 m³/h 
 
Demineralized water  approx. 2200– 2500 kg/h 
(without recycling the process condensate) 

  approx. 1400  – 1.550 kg/h  
(with recycling the process condensate) 
 
approx.2800 kg/h (design) 

Instrument air        40‐50 Nm³/h 

Atomizer air In case liquid naphtha fuel will be used atomizer air for spraying naphtha might be 
required.        Approx.25 – 30 Nm3/h 
 
Electric energy        approx.  60 kW  
Plus electric energy for naphtha pumps (?) and electric 
energy for heaters required during start‐up of the plant to 
preheat the nitrogen/naphtha feed stream for heating‐up of 
the desulphurization rectors(s) to operating temperatures 
(approx. 20 ‐25 kW). 
 
Dosing chemicals for demin. water – depending on water quality 
 
Nitrogen for purging analysers or header system 
 
Utilities required during normal start‐up and shut‐down : 
    Nitrogen       approx. 250 Nm³/h 

    H2 from bottles or storage   approx. 12 Nm3/h 

 
 
 
 