System of
Air Circuit Breakers
please go through this manual fully. U-POWER Omega System of ACBs have many
safety related as well as innovative features, which are explained herein.
This USERS’ Manual is a generic guide to normal site installation, operation and
maintenance. Omega System of ACBs and their accessories should only
U-POWER
LARSEN &TOUBRO
CAUTION
Ensure that deviations of the mains and control voltages do not exceed the
specified operating limits, as this may cause malfunction, dangerous
operation and damage to product.
LARSEN &TOUBRO
Contents:
8. Useful hints
LARSEN &TOUBRO
Section 1
On Receiving
System
LARSEN &TOUBRO
1.1 Visual Inspection
SYSTEM OF
A) Inspect the carton for any damage. In case of visible damage to the carton, contact nearest L&T
branch office before unpacking.
B) Verify the breaker version and rating written on the carton with your order.
Weights:
Before proceeding with unpacking, it is important to know the weight of the
breaker for proper selection of handling equipment.
50% N
Rating Specification Parameters
Frame I II III
Version N S H S H S H H V
Rated Uninterrupted current at 40deg.C In (A) 400-1600 2000-2500 400-3200 3200-5000
Weight Fixed 4P (50% N) 41 45 55 55 63 63 93 93
kg D/O 4P (50% N) 77 81 91 91 98 98 142 142
200% N
Rating Specification Parameters
Frame I II III
Version N S S H S H
Rated Uninterrupted current at 40deg.C In (A) 400 -1250 1600 2000 - 2500
Weight Fixed 4P (200% N) 52 52 65 65 72 72
kg D/O 4P (200% N) 84 84 102 102 110 110
LARSEN &TOUBRO
b) For Draw-out breakers:
LARSEN &TOUBRO 1-3
o
Temp. Range : -5 to 70 C.
LARSEN &TOUBRO
Section 2
Understanding
System
2.1 Identification
2.2 Exploring
2.3 Racking-out
2.4 Operating
2.5 Technical Data
LARSEN &TOUBRO
2.1 Identification:
J1
12
OFF O
29a
ON I 29g UW3-04H
In : 400A
29b
U imp : 12kV
29h Category : B
400/415 V~
Ics = Icu
80 kA
660/690 V~ 55 kA 29d
CHARGED 500/550 V~
660/690 V~
70 kA
55 kA
I cw 80 kA 0.5 s
0.5 s
I cw 80 kA
80 kA 1.0 s 80 kA 1.0 s
50 kA 3.0 s
50 / 60 Hz 50 kA 3.0 s
50 / 60 Hz
IS/IEC 60947 - 2
29j 29e
-2
60947
IEC 60947 - 2
IS/IEC
60947 - 2
EN EN 60947 - 2
Sr.No.: 60947 - 2
IEC
Suitable for 50°C
MADE IN INDIA
IS/IEC 60947 - 2
IEC 60947
IS/IEC 60947 - 2- 2 29f
EN EN 60947 - 2- 2
60947
Charging Device IEC
Sr.No.: 60947 - 2
240V~,240V Suitable for 50°C
MADE IN INDIA
(Microswitch)
TEST
DISCONNECTED
15
ocations
25 Withdrawal Rails
26 Door Racking Interlock
15 Racking Handle 27 Breaker Pull-out Handle
16 Smart Racking Shutter 34 Guide for
16
Keeping OFF button (11a) pressed, open the Racking Shutter (16). In case
Breaker is out of the panel or the panel door is open, gently press Racking
Interlock (26) to defeat it.
Insert the racking handle &
Note: Once racking shutter is opened, the breaker can not be closed, even by
rotate anti-clockwise
Frame I I II I III
Rating Specific Parameters Neutral Unit Symbol
Rated Uninterrupted Current at 40deg.C A In 400 -1600 2000 2500 400 - 3200 400 - 5000 6300
Version N S H S H S H S H H V H V
Rated ultimate 400/415V ~ 50/60 Hz kA 50 65 80 65 80 65 80 65 80 80 100 80 100
S.C. Breaking 500/550V ~ 50/60 Hz kA Icu 42 55 65 55 65 55 65 55 70 70 85 70 85
Capacity 660/690V ~ 50/60 Hz kA 36 50 55 50 55 50 55 50 55 55 75 55 75
Rated Service 400/415V ~ 50/60 Hz
S.C. Breaking 500/550V ~ 50/60 Hz kA Ics 100% Icu
660/690V ~ 50/60 Hz kA 76 105 121 105 121 105 121 105 121 121 165 121 165
Opening Time 40
ms
Closing Time 60
Width 3P mm W 347 447 647
Fixed Width 4P 100% mm W 447 581 847
ACB Depth mm D 324 324 334
Height mm H 430
Dimensions
Width 3P mm W 347 447 647
Drawout Width 4P 100% mm W 447 581 847
ACB Depth mm D 421 421 431
Height mm H 433
Mechanical Life- With Maintenance no. of cycles 20000 15000 10000
Frequency of Operation-Mechanical cycles/hour 60
200%N
Rating Specification Parameters Symbol
Frame I II III
Version N&S S&H H
Rated Uninterrupted Current at 40deg. C In (A) 400-1250 1600 2000-2500
Fixed ACB 200% W (mm) 447 581 647
Dimensions
Drawout ACB 200% W (mm) 447 581 647
Pitch Ph-N 200% N mm 100 133.3 200
Termination
Neutral 200% N mm 65 65 165
Width
Fixed 4P 200% N kg 52 65 72
Weight
D/O 4P 200% N kg 84 102 110
Understanding
System
LARSEN &TOUBRO
Mounting U-POWER Omega in a Panel
General Information:
2 U-POWER
Omega System of Breaker’s front
facia is Right aligned thereby giving uniform
panel appearance. This feature also leads to
optimum utilization of panel space, inside the
panel as well as on the door .
LARSEN &TOUBRO
Frame 1, 3 Pole U-POWER Omega System of
breaker can be fitted in a 400mm wide panel.
LARSEN &TOUBRO
Mounting
400A-1600A N & 400A-2500A S/H Fr.1 3P
142
324
DISCONNECTED
25.5
421
(250) (47.5)
(62.4)
(280)
324
DISCONNECTED
25.5
421
(280)
324
DISCONNECTED
(280)
324
DISCONNECTED
(280)
These 3 supports
are must
334
DISCONNECTED
35.5
431
(100) (250) (47.5)
(49.5)
(62.4)
These 3 supports
(250)
(280)
are must
3-7
Mounting
334
35.5
431
(49.5) (200) (100) (250) (47.5)
(62.4)
These 4 supports
are must
(250)
(280)
3-8
All Dimensions in mm FIXED ACB BEZEL
FIXING DRILLING PLAN
10.5
10.5
Cutout for Main Facia 171 171
181
181
8 HOLES-DIA.5
(Bezel overall Dims W=371XH=391; 25mm around the cutout)
D/O ACB BEZEL
Cutout for door Interlock device FIXING DRILLING PLAN
See Detail `z’
9.2 10.5
171 171
10.5
53.5
208.5
208.5
8 HOLES-DIA.5
(Bezel overall Dims W=371XH=446; 25mm around the cutout)
3 411.8
4 545.8
3 611.8
III 4 811.8
Installation: Fix the sealing (Bezel assy.) frame on the panel door
by provided M4x8mm length Screws at 8 places from the rear side
of panel door.
3-9
3.2 Termination
Terminal Adaptor:
If required, a Terminal adapter is available as an accessory.
3-10
MAX.
3-11
Termination - Fixed Breakers
Flat Termination
C
400A-1600A N & 400A-2500A S/H Fr.1-3P 32
11
A
B
M10
105
A
B
32
122
FRAME 1 A B C C
41
Bolt length
400-1600A N 24 50 50 100 100
400-1600A S 24 50 65 347
15
2000-2500A S 30 55 65
Bolt length for mounting
link(s) on Flat Terminals 400-2500A H 30 55 65
M10 bolts to be used for link termination
to be cumulative link(s) Holes (on both sides) for Earthing Tightening torque: 3.0 kgfm
thickness + 15 mm. connections by M10/Equivalent BS bolt
40
69
108.8
19
Ø12.9 27
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm 100 100
3-12
Termination - Fixed Breakers
Vertical Terminals
BREAKER ADAPTOR
RATING CAT. No. 74
400A-1600A N/S Fr.1-3P 400-1600A N/S CL60967OOOO 19
2000A S/H Fr.1-3P 2000A S/H CL60968OOOO
65
27 40
65
Ø12.9
117.5
100 100
63
15
100 100
Vertical Terminals 72
2500A S/H Fr.1-3P 19
63
(Adaptor-CL60976OOOO)
27 27
100
45
100
Ø12.9
80.8
100 100
20
100 100
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm
3-13
Termination - Fixed Breakers
11
A
B
M10
105
B
122
41
27
Ø12.9 100 100 100
3-14
Termination - Fixed Breakers
Vertical Terminals
400A-1600A N/S Fr.1-4P & BREAKER
RATING
ADAPTOR
CAT. No. 74
400-1600A N/S CL60967OOOO 19
2000A S/H Fr.1-4P
2000A S/H CL60968OOOO
65
27 40
65
Ø12.9
117.5
100 100 100
15
100 100 100
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm
72
Vertical Terminals 63
2500A S/H Fr.1-4P 19
(Adaptor-CL60976OOOO)
23 27 27
100
45
100
Ø12.9
80.8
20
M12 / Equivalent BS bolts to be used for link termination
100 100 100
Tightening torque: 3.2 kgfm
3-15
Termination - Fixed Breakers
Flat Termination
Bolt length for mounting
400A-3200A S/H Fr.2-3P Bolt length
link(s) on Flat Terminals
to be cumulative link(s)
thickness + 15 mm.
98.4
32
M10
9
55
30
105
55
30
122
41
15 133.3 133.3 90
Holes (on both sides) for Earthing
connections by M10 / Equivalent BS bolt 447
Horizontal Termination
400A-3200A S/H Fr.2-3P 72
(Adaptor-CL60977OOOO) 63
20
74
48
74
103.8
19
27
20 54
133.3 133.3
M12 / Equivalent BS bolts to be used for links termination Details of 4P(200% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
3-16
Termination - Fixed Breakers
Vertical Termination
400A-3200A S/H Fr.2-3P
(Adaptor-CL60977OOOO)
72
63
19
100
133.3 133.3
54
27
53
100
133.3 133.3 20
77.2
M12 / Equivalent BS bolts to be used for links termination Details of 4P(200% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
3-17
Termination - Fixed Breakers
Flat Termination
98.4
400A-3200A S/H Fr.2-4P (100% N) 32
9
M10
30
55
105
30
55
122
41
Horizontal Termination
400A-3200A S/H Fr.2-4P (100% N) 72
(Adaptor - CL60977OOOO) 63
20
74
48
74
103.8
19
27 27 20
Ø12.9
100
133.3 133.3 133.3
3-18
Termination - Fixed Breakers
Vertical Termination
400A-3200A S/H Fr.2-4P (100% N)
(Adaptor-CL60977OOOO)
63
Ø 12.9 19
27
100
54
23
20
133.3 133.3 133.3
77.2
M12 / Equivalent BS bolts to be used for links termination Details of 4P(200% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
3-19
Termination - Fixed Breakers
M10
30
56
10
105
56
30
122
41
15 73.5
100 100 100 100 100
647
Holes (on both sides) for Earthing connections by
M10 / Equivalent BS bolt M10 to be used for links termination
Tightening torque: 3.0 kgfm
Horizontal Termination
400A-4000A H/V Fr.3-3P
& 5000A H/V Fr.3-3P
82
63
19
A
B
30
B
C
Cat. No.
400-4000A CL60968OOOO 15 69 108.8
M12 / Equivalent BS bolts to be used for links termination Details of 4P(50% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
3-20
Termination - Fixed Breakers
27
65
19
40
65
117.5
SEE
100 DETAIL
100 A 100 100 100
B
Vertical Termination
6300A H/V Fr.3-3P 82
A
(Adaptor-CL60976OOOO) 19
63
27 27
100
23
45
100
Ø12.9
80.8
20
100 100 100 100 100
M12 / Equivalent BS bolts to
be used for links termination Details of 4P(50% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
3-21
Termination - Fixed Breakers
65
32
M 10
9
56
30
10
105
56
30
122
41
Horizontal Termination
400A-5000A H/V Fr.3-4P(100% N)
82
63
19
A
B
30
B
C
27 65
100 100
100 100
100 100
100 100
100 100
100 100
100
M12 / Equivalent BS bolts to be used for links termination Details of 4P(50% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
3-22
Termination - Fixed Breakers
Vertical Termination
400A-4000A H/V Fr.3-4P (100% N)
& 5000A H/V Fr.3-4P (100% N)
82
63
19
65
27
19
40
65
117.5
100 100 100 100 100 100 100
Breaker Rating
Adaptor Dim. A
Cat. No.
400-4000A CL60968OOOO 15
5000A CL60982OOOO 20
A
100 100 100 100 100 100 100
Vertical Termination
6300A H/V Fr.3-4P (100% N)
Adaptor-CL60976OOOO
82
19 Ø12.9
27 27
100
23
45
100
80.8
M12 / Equivalent BS bolts to be used for links termination Details of 4P(50% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
3-23
Termination - Draw-out Breakers
65
Flat Terminals
SEE DETAIL A
DETAIL A
56.8
14.5
10.4
105
36
Ø12.5
150
36
25.5
Bolt length
100 100 73.5
15
16
347
Bolt length for mounting link(s) on Flat Terminals M12 bolts to be used for link termination
to be cumulative link(s) thickness +20 min to 25 max
Tightening torque: 3.2 kgfm
36 65
Horizontal Terminals*
400A-2000A N/S/H Ø12.9
17.5
Adaptor - CL60963OOOO
15
105 36
Ø12.9
36
150
15
100 100
16
83.5 347 73.5
36 15 65
Vertical Terminals
400A - 2000A N/S/H
Ø12.9
Adaptor - CL60963OOOO
17.5
**FOR 2500A REFER PAGE 3-25 36
27
65
105
Ø12.9
36
150
15
100 100
16 73.5
83.5 347
17.5
36
441
394
36
15
65.7
16
M12 / Equivalent BS bolts to be used 100
100 73.5
for links termination Tightening torque: 3.2 kgfm 347
All Dimensions in mm
3-24
Termination - Draw-out Breakers
2500A, S/H, 3P & 4P (Fr.1)
Vertical Terminals
** FOR 2500A - 3P S/H
Adapter - CL60964OOOO
65 20 36
90.5
65
15 Ø12.9
36
27 27
98
105
Ø12.9
140
15
100 100
16 73.5
347
Vertical Terminals
** FOR 2500A - 4P S/H
Adapter - CL60964OOOO
20 65 36
90.5
65
15 Ø 12.9
27 27
98
36
105
Ø12.9
140
15
16 73.5
447
3-25
Termination - Draw-out Breakers
400A-2500A, N/S/H, Fr.1-4P (100%N)
M12 bolts to be used for link termination
Tightening torque: 3.2 kgfm
Flat Terminals
SEE DETAIL A
65
14.5 36
M12
(Ø 12.5)
56.8
36
105
Bolt length
10.4
150
25.5
Bolt length for mounting link(s) on Flat 100 100 100
Terminals to be cumulative link(s)
15
thickness +20 min to 25 max. 16 73.5
447
65 36
Horizontal Terminals
400A - 2000A N/S/H
Adaptor - CL60963OOOO
Ø12.9 Ø12.9
36
15
105
17.5
36
150
83.5
100 100 100
15
16 447 73.5
15 65 36
Vertical Terminals
400A - 2000A N/S/H Ø12.9
Adaptor - CL60963OOOO 17.5
For 2500A REFER PAGE 3-25
27
65
36
105
Ø12.9
150
36
83.5
100 100 100
15
16 73.5
447
15 65 27 Ø 12.9
Front Terminals
48
36
36
441
394
15
65.5
All Dimensions in mm
3-26
Termination - Draw-out Breakers
M12 bolts to be used for link termination
400A-3200A, S/H Fr.2-3P Tightening torque: 3.2 kgfm
65
36
Flat Terminals
M12
77.2
36
105
Bolt length
77.2
36
140
Bolt length for mounting 25.5
link(s) on Flat Terminals
to be cumulative link(s)
15
16 133.3 133.3 90
thickness+20 min to 25 max
447
98
Horizontal Terminals
90.5
Adaptor - CL60964OOOO
15
20
65
105
36
Ø12.9
140
133.3 133.3 90
15
16 447
36 20 20
Vertical Terminals
Adaptor - CL60964OOOO 90.5
15
Ø12.9
27 27
98
36
105
98
36
140
36
36
133.3 133.3 90
447
15
16
27 27 98
45.6 Ø12.9
Front Terminals
20
17.5
48
23.5
42
36
36
481
15
16
133.34 133.34 90
M12 / Equivalent BS bolts to be used for links termination 447
Tightening torque: 3.2 kgfm All Dimensions in mm
3-27
Termination - Draw-out Breakers
400A-3200A, S/H, Fr.2-4P (100% N)
65
36
M12
Flat Terminals
Bolt length
77.2
36
105
77.2
Bolt length for mounting
36
link(s) on Flat Terminals
140
to be cumulative link(s)
25.5
thickness+20 min to 25 max
90 133.3
15
16 133.3 133.3
581
98 36
Horizontal Terminals
Adaptor - CL60964OOOO 90.5 N
15
20
65
36
105
36
Ø12.9
140
15
Vertical Terminals 20 36 65
Ø 12.9 15
27 27
98
36
105
98
36 140
581
17.5
Ø12.9 27 27 98
Front Terminals 45.6
23.5
48
20
42
36
36
481
15
16
M12 / Equivalent BS bolts to be used for links termination. Details of 4P(200% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
3-28
Termination - Draw-out Breakers
400A-4000A, H/V Fr.3-3P, & 5000A, H/V Fr.3-3P M12 bolts to be used for link termination
Tightening torque: 3.2 kgfm
& 6300A, H/V Fr.3-3P
165
36
Flat Terminals
400A-5000A H/V
56
36
ø12.9
Bolt length
36
56
179
25.5
Bolt length for mounting
link(s) on Flat Terminals
15
to be cumulative link(s) 100 100 100 100 100 73.5
16 Hole (on both sides)
647
thickness+20 min to 25 max for Earthing connections
by M10 / Equivalent BS bolt
36 Ø12.9 165
Flat Terminals
6300A H/V
36 36
11229
76
36
179
35.5
M12 bolts to be used for
15
Horizontal Terminals 65
165
Ø12.9
400A-4000A H/V 36
Adaptor - CL90747OOOO
2 HOLES - Ø12.9
PITCH 27 mm.
65
40
15
36
183
58 35.5
15
165
36 Ø12.9
Horizontal Terminals
5000A H/V 90.5
Adaptor - CL60966OOOO
6 HOLES- Ø 12.9
PITCH 27 mm
65
15
40
20
36
183
65
25.5
15
16
74.4 100 100 100 100 100
647
M12 / Equivalent BS bolts to be used for links termination.
Tightening torque: 3.2 kgfm
All Dimensions in mm
3-29
Termination - Draw-out Breakers
400A-4000A, H/V Fr.3-3P, & 5000A, H/V Fr.3-3P
& 6300A, H/V Fr.3-3P 165
36 Ø12.9 15
Vertical Terminals
400A-4000A H/V
Adaptor - Ø12.9
CL90747OOOO
19 27
65
40
Bolt length
36
183
58
Bolt length for mounting 35.5
link(s) on Flat Terminals
to be cumulative link(s)
15
16 Hole (on both sides) 74.4 100 100 100 100 100
thickness+20 min to 25 max for Earthing connections 647
by M10 / Equivalent BS bolt
165
Vertical Terminals 36 Ø12.9 20
5000A H/V
Adaptor -
CL60964OOOO Ø12.9
98
22 27 27
28.5
22 27 27
36
189
15
65 35.5
15
16 647
Vertical Terminals 36
165
20
Ø12.9
6300A H/V
Adaptor -
CL60965OOOO Ø12.9
27 27 27
125
36 36
15
29
27 27 27
36 36
125
179
65 35.5
17.5
15
16 27
74.4 65
100 100 100 100 100
647
Front Terminals
36
36
495
Ø12.9
40
16
15
93
30
66
100 100 100 100 100 73.5
M12 / Equivalent BS bolts to be used for links termination. 647
3-30
Termination - Draw-out Breakers
M12 bolts to be used for link termination
400A-4000A H/V Fr.3-4P (100% N),5000A H/V Fr.3-4P (100% N) Tightening torque: 3.2 kgfm
& 6300A H/V Fr.3-4P (100% N)
165
36 HOLE - o 12.9
Flat Terminals
11
400A-5000A H/V
56
36
105
Bolt length
56
179
31.7
Bolt length for mounting
link(s) on Flat Terminals
15
16
to be cumulative link(s) Hole (on both sides) 100 100 100 100 100 100 100 73.5
thickness+20 min to 25 max for Earthing connections
by M10 / Equivalent BS bolt
847
11
36
118
36
29
76
36
179
35.5
15
Horizontal Terminals 65
Ø12.9 165
36
400A-4000A H/V
Adaptor -
CL90747OOOO
2 HOLES- Ø 12.9
PITCH 27 mm
65
40
20
36
183
58 35.5
15
6 HOLES - Ø 12.9
PITCH 27 mm
65
15
40
20
36
65
183
25.5
15
16 100
73.5 100 100 100 100 100 100
M12 / Equivalent BS bolts to be used for links termination.
847
Tightening torque: 3.2 kgfm
3-31
Termination - Draw-out Breakers
400A-4000A H/V Fr.3-4P (100% N), & 5000A H/V Fr.3-4P (100% N)
& 6300A H/V Fr.3-4P (100% N)
36 Ø12.9 165 15
Vertical Terminals
400-4000A H/V
Adaptor - Ø12.9
CL90747OOOO 19 27
65
40
19 27
36
Bolt length
183
58
35.5
15
36 Ø12.9 165 20
Vertical Terminals
5000A H/V
Adaptor -
Ø12.9
CL60964OOOO
22 27 27
98
28.5
15
22 27 27
36
189
65
35.5
15
16
73.5 100 100 100 100 100 100 100
847
165
Vertical Terminals 36 Ø12.9 20
6300A H/V
Adaptor -
CL60965OOOO Ø12.9
27 27 27
36 36
125
15
29
27 27 27
36 36
179
65 35.5
16
15
Front Terminals
17.5
27 65
Ø12.9
48
36
36
495
40
16
15
93
48
30
65.5 100 100 100 100 100 100 100 73.5
847
M12 / Equivalent BS bolts to be used for links termination. Details of 4P(200% N) on request
Tightening torque: 3.2 kgfm All Dimensions in mm
For Earth fault protection and protection of Neutral against overloads, Neutral
CT is required. For 4-Pole breakers, the CT is provided inside the breaker, to
be used on 4 wire system whereas for 3-pole breakers, external CT is
available separately.
It is important that with U-POWER Omega System of breaker, special neutral CTs
supplied by L&T are used.
19
42
(ref. Page 2-6 for Frame size details)
72
TERMINAL THICKNESS 15 mm.
19
Frame Size Rating
12.5
1 2000/2500
19
45.5
details)
72
TERMINAL THICKNESS 30 mm.
2&3 2000/2500/
3200/4000
19
(ref. Page 2-6 for Frame size details)
45.5
72
65
Frame Size Rating
12.5 40 40 13
3 5000/6300
19
Cradle terminal supports (35) provide specific slots for the installation.
USERS can make their own phase barriers of suitable height using insulating
sheets of 1.5mm thick for Fixed and 4mm thick for Draw-out Breakers .
Two holes are required to be drilled in the insulating sheet as detailed in the
adjoining sketch.
5.2
ø7
54.3
128.4
95
SEE DETAIL A
27.5
130#0.5
130
.1
#0
R5
10
6.2
#0.13
13.8
2
6.2
DETAIL A
SCALE 1:1
Position Indication:
1
2
3
4
5
6
7
8
Disconnected Test Connected
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
11
31
21
V1
42
41
43
44
X
D-
12
13
14
24
32
23
V3
V0
A1
22
34
V2
33
D+
D1
C1
A2
C2
N1
D2
N2
X1
Z-L
X2
AL-
C-L
CN
131
Z-H
134
101
AL+
132
AS-
C-H
104
102
RR-
AS+
C-G
M-G
RR+
EC1
TST
TCS
DCN
EC2
CMN
CH1
CH2
Legend
Control
circuit
equipment
Ref. No.
LARSEN &TOUBRO
The above diagram gives a generic conguration for control termination on the breaker. For specic details, refer Connection diagram
(pages 3-38 to 3-44) specic to the P&C unit installed in the breaker.
3-37
# For using electrical accessories with dc Control Supply, it is recommended to connect D1/A1/C1 to +ve and D2/A2/C2 to -ve.
# m indicates micro switch
Connection Details
(UW-MTX 1.0)
41
21
31
11
33
43
A1
D1
13
23
N R Y B
C1
CN
134
TST
RR+
132
122
112
124
104
114
102
CH1
EC1
DCN
TCS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
UW-MTX 1.0
.4
.4
.4
.4
.2
.2
.2
.2
LOAD
34
44
EC2
D2
CH2
22
12
14
CMN
24
A2
C2
32
42
RR-
111
121
131
101
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
LARSEN &TOUBRO
3-38
Connection Details
(UW-MTX 1G)
41
21
31
11
33
43
A1
D1
13
23
N R Y B
C1
CN
134
TST
RR+
132
122
112
124
104
114
102
CH1
EC1
DCN
TCS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
UW-MTX 1G
.4
.4
.4
.4
.2
.2
.2
.2
N1
N2
LOAD
34
44
EC2
D2
22
12
14
CMN
24
A2
C2
32
42
RR-
CH2
111
121
131
101
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
LARSEN &TOUBRO
3-39
Connection Details
(UW-MTX 1.5G)
41
21
31
11
33
43
A1
D1
13
23
N R Y B
C1
CN
134
TST
RR+
132
122
112
124
104
114
102
CH1
EC1
DCN
TCS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
UW-MTX 1.5G
.4
.4
.4
.4
.2
.2
.2
.2
N1
N2
LOAD
34
44
EC2
D2
22
12
14
CMN
24
A2
C2
32
42
RR-
CH2
111
121
131
101
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
LARSEN &TOUBRO
3-40
Connection Details
(UW-MTX 2.5)
41
21
31
11
33
43
A1
D1
13
23
N R Y B
C1
CN
134
TST
RR+
132
122
112
124
104
114
102
AL+
CH1
AS+
EC1
DCN
TCS
ACB STATUS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
UW-MTX 2.5
.4
.4
.4
.4
.2
.2
.2
.2
LOAD
34
44
EC2
D2
22
12
14
CMN
24
A2
C2
AL-
32
42
AS-
RR-
CH2
111
121
131
101
ACB STATUS
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
LARSEN &TOUBRO
This output can be connected
to 5V-30 V dc 150 mA Relay
or any other indicating device
which can give alarm for Short
3-41
circuit and Earth Fault trip.
Connection Details
(UW-MTX 2.5G)
41
21
31
11
33
43
A1
D1
13
23
N R Y B
C1
CN
134
TST
RR+
132
122
112
124
104
114
CH1
102
AL+
AS+
EC1
DCN
TCS
ACB STATUS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
UW-MTX 2.5G
.4
.4
.4
.4
.2
.2
.2
.2
N1
N2
LOAD
34
44
EC2
D2
22
12
14
CMN
24
A2
C2
AL-
32
42
AS-
RR-
CH2
111
121
131
101
ACB STATUS
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
LARSEN &TOUBRO
This output can be connected
to 5V-30 V dc 150 mA Relay
or any other indicating device
which can give alarm for Short
3-42
circuit and Earth Fault trip.
N1,N2 : External Neutral C.T.
Connection Details
(UW-MTX 3.5)
N R Y B
41
21
31
11
33
43
A1
D1
13
23
C1
AS+
Z-H
CN
V3
V1
AL+
C-H
D+
M-G
134
TST
RR+
132
122
112
124
104
114
CH1
102
EC1
DCN
TCS
ACB STATUS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
UW-MTX 3.5 CFM PI
.4
.4
.4
.4
.2
.2
.2
.2
N1
N2
LOAD
V2
V0
AL-
AS-
Z-L
34
44
EC2
C-G
D2
C-L
22
12
14
D-
CMN
24
A2
C2
32
42
RR-
CH2
111
121
131
101
ACB STATUS
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
LARSEN &TOUBRO
to 5V-30 V dc 150 mA Relay N2 : External Neutral CT
or any other indicating device Z-L : ZSI CAN-Low
Z-H : ZSI CAN-High
which can give alarm for Short
circuit and Earth Fault trip .
3-43
C-L : CAN-Low
C-H : CAN-High
M-G : MOD-GND
C-G : CAN-GND
V0,V1,V2,V3 :N ,R,Y,B, VOLTAGE I/P.
Connection Details
(UW-MTX 3.5EC/3.5H)
N R Y B
41
21
31
11
33
43
A1
D1
13
23
C1
AS+
Z-H
CN
V3
V1
AL+
C-H
D+
M-G
134
TST
RR+
132
122
112
124
104
114
102
CH1
EC1
DCN
TCS
ACB STATUS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
UW-MTX 3.5EC/3.5H CFM PI
.4
.4
.4
.4
.2
.2
.2
.2
N1
N2
LOAD
V2
V0
AL-
AS-
Z-L
34
44
EC2
C-G
D2
C-L
22
12
14
D-
CMN
24
A2
C2
32
42
RR-
CH2
111
121
131
101
ACB STATUS
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
LARSEN &TOUBRO
or any other indicating device Z-L : ZSI CAN-Low
Z-H : ZSI CAN-High
which can give alarm for Short
circuit and Earth Fault trip .
C-L : CAN-Low
3-44
C-H : CAN-High
M-G : MOD-GND
C-G : CAN-GND
V0,V1,V2,V3 :N ,R,Y,B, VOLTAGE I/P.
Section 4
System of ACB’s
Accessories: Features & Mounting
4.1 Cradle Mounted Accessories
4.2 Breaker Mounted Accessories
LARSEN &TOUBRO
4.1 Cradle Mounted Accessories
Tools required: Screw Driver (Blade length 300 mm, Tip width 8 mm)
Tools required: Philip head Screw driver (Tip no.2), Ring spanner
(size 13)
Cut-out for
Door Interlock
Assemble the Interlock as shown. Rest the rear end of the torsion Also assemble panel-door mounted
spring on the SIC bridge, as shown. part of door-interlock.
Features: It can interlock upto 3 U-POWER Omega breakers of Fixed / Drawout / Mixed versions. The
breakers can be interlocked in Vertical or Horizontal configuration.
Cable length: 2 meters/3 meters/5 meters
min. radius of cable bend: 70mm
Type of Interlock Typical Circuit Interlocks possible Schematic diagram
Two Incomers A B
(2 I/C)
Three Incomers A B C
(3 I/C)
G
Two Incomers &
One Standby
A B C
(2 I/C + 1 S/B)
Tools required: Screw Drivers (Tip widths 8 mm & 6 mm), Open spanner (10/11)
a. Mounting actuator
(Common for Fixed & Draw-out breakers)
Remove facia. Provide a cut in the facia Install the actuator on the main
along the guides shown inside the facia. shaft using 2 screws as shown.
b. Fixing the Mechanical Interlock plate Draw-out Breaker
Fixed Breaker
3
2
For 2I/C+1B/C:
4 i. Adjust the Screw (1) till Actuator link (2) is
1 horizontal and is in lowermost position
ii. Tighten Nut & locknut (4).
R>70mm
Installation:1) Insert lever ‘A’ in the slot on front bend of base Plate ‘F’.
S
2) Align Screw ‘S’ with the axis of NutInsert on Base plate. A
3) Press arm ‘B’ of the spring to trap against Screw
support ‘C’.
4) Tighten screw with the help of Screw Driver.
e. Safety Cover: 1
DETAILS OF HOLES TO BE
DRILLEDON PANEL DOOR
FOR REMOVABLE SAFETY
COVER
Function: To provide Ingress Protection.
30
30
Features: It can be mounted with Left Hinge / Right Hinge / Removable / Non- Ø5.3
removable combinations. 8 HOLES
396
300
300
Tools required: Screw Driver (Tip width 5 mm / 3 mm)
30
30
Installation: 1) Drill holes on Door as shown.
2) Assemble “Latching Bracket”, “Hinge A” & Hardware as shown.
29
29
3) Assemble “Locking Lever’, “Hinge B” & Hardware as shown 19.7
321 19.7
2 3 4
HINGE ‘B’
HINGE ‘A’
LOCKING
LEVER
LATCHING
BRACKET
OPERATION:-
Installation:
Lock Type Lock Components for ‘Locking Arrangement’ Assembly on the Lock
Adaptor Actuator Arrester
Castell
Ronis
Kirk
Profalux
1. Remove the Front Racking shield 2. Remove 3 bolts to take off cradle facia
4-6
3. Remove knock-out as shown.
4-7
4.2 Breaker Mounted Accessories
Removing facia
12 OFF O
DISCHARGED
13
Facia can be taken out by removing 2 screws This is true even for higher frame sizes,
(32) on either side of the facia. where side covers need not be removed for
taking out the facia.
After removing the screws on both sides, pull down Take out the facia by tilting it upwards as
the charging handle (14) half-way. shown.
4-8
Auxiliary Contact Undervoltage Closing Shunt
Block (3a) Release (4) Release (5) Release (6)
Common Fault
12 34 5 Indication
6
Several Breaker-mounted accessories are located on the
front top side of the breaker and have specific positions.
Undervoltage
release
controller (4c)
Operation
Undervoltage
Shunt Trip Counter (10)
Trip Indication
Indication
Installation: Drop fit the Shunt release in the assigned slot and slide
backwards to lock. Also, fix the pre-wired Auxiliary Contact Block.
4-9
c. Closing Release UN-CR (5):
Installation: Drop fit the Closing release in the assigned slot and slide
backwards to lock.
Features: Undervoltage releases are available with the following control voltages,
Installation: Drop fit the Undervoltage release in the assigned slot and slide backwards UV Release
Breakers equipped with Undervoltage release cannot be normally closed unless the
release is energized.
To return the release to normal state, energize the release and then disconnect the
control supply.
4-10
e. Electrical Charging Device UN-EC (2): To avoid possibility of personal injury,
CAUTION ensure that before opening the facia,
Function: To charge the main spring electrically. breaker is OFF and Spring is discharged.
Installation:
4-11
g. Common Fault Indication:
Tools required: Screw driver (Tip width 8 mm) or Philip head (Tip No. 2)
Installation:
Click-fit Undervoltage release trip indication assembly as shown Click-fit Shunt release Trip Indication assembly
and route connecting wires as shown
4-12
After fixing accessories:
Accessories a-f
4-13
j. Locking ‘OFF’ Button (18):
Installation:
Lock Type Lock Components for ‘Locking Arrangement’ Assembly on the Lock
Actuator Lock plate Adaptors & Plugs
Castell
Ronis
Kirk
Profalux
Remove knock-out and drill 2 holes Ensure that lock is in ‘Locked’ position.
(dia 7mm), at depressed locations Mount the lock using LOPB rivets
4-14
Section 5
UW-MTX1.0 UW-MTX 1G
Power ON LED
UW-MTX 1.5G
UW-MTX 1.5G
UW - MTX1.5G
OLED Display
5 4 3 2 1
5-1
5.1 Identification
Identification Label
Power ON LED
OLED Display
Fault Indication LEDs
}
Navigation Keys Escape key
Query key Self Test key
UW - MTX 3.5H
Configurator
Metering Module
5-2
2.Feature List
5-3
5.3 Detailed Overview
400
630 800
800
1000
1250 1600
1600
ON
2000 OFF
2500 3200
3200 Note: This symbol indicates that DIP Switch is ON and indicates that DIP Switch is OFF.
5000
6300
6300
5-4
Protection Settings for UW-MTX2.5/2.5G/3.5/3.5EC/3.5H
5-5
Parameter UW-MTX2.5 UW-MTX2.5G UW-MTX3.5 UW-MTX3.5EC UW-MTX3.5H Factory Settings
5-6
Protection Characteristics
2
Overload I T (for UW-MTX1.0)
10000
ĈĆĆĆĆ
1000
ĈĆĆĆ
100
ĈĆĆ
Trip Time (s)
10
ĈĆ
Tolerance
Trip Time: ±20%
10s
1Ĉ
0.1
ĆBĈ
1.2 2 3 4 5 6 7 8 9 10
Current Multiples (x Ir)
5-7
Protection Characteristics
2
Overload I T (for MTX1G/1.5G/2.5/2.5G/3.5/3.5EC/3.5H)
10000
ĈĆĆĆĆ
1000
ĈĆĆĆ
100
ĈĆĆ
Trip Time (s)
30 s
ĈĆ
10 24 s
18 s Tolerance
Trip Time: ±20%
12 s
6s
4s
1Ĉ
2s
1s
0.5 s
0.1
ĆBĈ
1
Ĉ 1.2 Č2 Ċ3 Ç4 D
5 Ď
6 Đ
7 Ð
8 E9 10
ĈĆ
Current Multiples (x Ir)
5-8
Protection Characteristics
4
Overload I T for (UW-MTX2.5/2.5G/3.5/3.5EC/3.5H)
ĈĆĆĆĆĆ
100000
10000
ĈĆĆĆĆ
1000
ĈĆĆĆ
(s) (s)
ĈĆĆ
100
TimeTime
Trip Trip
10
ĈĆ
30 s
24 s
18 s
12 s
1Ĉ
6s
4s
2s
Tolerance
1s
ĆBĈ
0.1 Trip Time: ±20%
0.5 s
ĆBĆĈ
0.01
1
Ĉ 1.2
1.2 2 3 4 55 6 77 88 99 10
10
5-9
Protection Characteristics
ĈĆĆĆĆ
10000
1000
ĈĆĆĆ
100
ĈĆĆ
(s) (s)
Time
Time
30s
Trip
24s
Trip
18s
12s
10
ĈĆ
6s
4s
2s
Tolerance
Trip Time: ±20%
1Ĉ 1s
0.5s
0.1
ĆBĈ
1 1.2 2 3 4 5 6 7 8 9 10
5-10
Protection Characteristics
10000
ĈĆĆĆĆ
ĈĆĆĆ
1000
100
Trip Time (s)
ĈĆĆ
30s
Trip Time (s)
24s
ĈĆ
10 18s
12s
6s
4s
2s
1Ĉ
Tolerance
Trip Time: ±20%
1s
0.5s
ĆBĈ
0.1
1 1.2 2 3 4 5 6 7 8 9 10
Current Multiples (x Ir)
5-11
Protection Characteristics
10000
ĈĆĆĆĆ
1000
ĈĆĆĆ
0.6 12
100
ĈĆĆ
Trip Time (s)
10
ĈĆ
Trip Time (s)
1Ĉ
0.4
0.3
0.2
ĆBĈ
0.1
0.1
0.02
ĆBĆĈ
0.01
ĆBĆĈ 0.1
ĆBĈ 1Ĉ ĈĆ
10 DĆ
50
Current Multiples (x In)
5-12
Protection Characteristics
ĈĆĆĆĆ
10000
ĈĆĆĆ
1000
0.6
ĈĆĆ
100
0.6 12
Trip Time (s)
ĈĆ
10
Trip Time (s)
1Ĉ
0.4
0.3
0.2
ĆBĈ
0.1 0.1
0.02
ĆBĆĈ
0.01
0.1
ĆBĈ Ĉ1 ĈĆ
10 D
50Ć
Current Multiples (x In)
5-13
Protection Characteristics
100
ĈĆĆ
ĈĆ
10
Trip Time (s) Trip Time (s)
1.5 15
1Ĉ
ĆBĈ
0.1
0.01
ĆBĆĈ
ĆBĆĈ
0.01 ĆB
01Ĉ Ĉ1 ĈĆ
10
Current Multiples (x In)
5-14
Protection Characteristics
ĈĆĆĆĆ
10000
ĈĆĆĆ
1000
0.2
0.3
ĈĆĆ
100
0.4
0.5
Trip Time (s)
0.6
0.8 2.4
ĈĆ
10
Trip Time (s)
1Ĉ
0.4 s
ĆBĈ
0.1 0.1 s
0.01
ĆBĆĈ
0.8 2.4
ĆBĆĈ 0.1
ĆBĈ Ĉ1 ĈĆ
10 DĆ50
Current Multiples (x In)
5-15
Protection Characteristics
2
Earth Fault I T OFF(UW-MTX1G/1.5G/2.5G/3.5/3.5EC/3.5H)
ĈĆĆ
100
0.2 0.6
ĈĆ
10
Trip Time (s)
Trip Time (s)
1
1Ĉ 0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
ĆB
0.1Ĉ
0.01
ĆBĆĈ
ĆBĈ
0.1 Ĉ1 ĈĆ
10 DĆ
50
Current Multiples (x In)
5-16
Section 6
Putting System Of
Breakers in Operation
6.1 Re-loading in panel
6.2 Checking ON-OFF operation
6.3 Testing
6.4 Setting P&C unit
6.5 Trip simulation of P&C unit
6.6 ACB’s in Connected
6.7 Securing
6.1 Re-loading in panel:
6-1
6.2. Checking ON-OFF Operation:
I
DISCHARGED
Now, the breaker is ON and spring has
6-2
6.3 Testing (Control circuit & Interlocks):
• Trace the Control circuit wiring based on panel wiring diagrams given by the
panel builder and breaker connections given on pages 3-37 to 3-44.
• Based on the accessories fitted on the breaker, carry-out the following tests,
• If breaker is equipped with Electrical Charging Device UN-EC (2), main spring
will get charged as soon as breaker reaches ‘Test’ position and Control supply
is switched ON. If breaker is not equipped with Electrical Charging Device,
charge the spring manually.
• If Undervoltage release UN-UR (4) is installed, but not energized, it will not
allow the breaker to Close. However, you can continue the testing by defeating
the Undervoltage release (Ref. Page 4-10)
• Ensure that all arc chutes are fitted and secured properly.
• Give supply to Closing release UN-CR (5) to close the breaker. In case not
equipped with closing release, manually close the breaker by pushing the ON
button (11b).
• Trip the breaker by giving supply to Shunt release UN-SR (6). In case not
equipped with shunt release, manually trip the breaker by pushing the OFF
button.
• After tripping through Shunt release, also check tripping through Undervoltage
release, if it is energized.
• After checking the voltmetric releases, verify the functioning of other electrical
interlocks and indications wherein breaker’s auxiliary contacts or SICs are
used.
6-3
6.4 Configuring P&C Unit
Configuring UW-MTX1.0/1G/1.5G
Overload PICK-UP (Ir) DELAY (Tr)(s) Ir is now set at 0.5x1600 i.e. 800A, with Overload delay (Tr)
OFF 0.5
1.0 0.4 1 set for 18 seconds.
0.95 0.5 30 2
0.9 0.6 24 4
0.85 0.7 18 6
0.8 x In 12 @ 6 x Ir
Short Circuit PICK-UP (Is) DELAY (Ts)(ms) With knob at 4, Is is set at 4x1600 i.e. 6,400A. For this
10
0.6
1 400
20
100 ON
I2 t setting, select suitable time delay in ‘I2t OFF’ mode.
9 1.5 300 200
2 200 300
‘I2t ON’ mode offers inverse characteristics to help co-
8
I2 t 100
ordinate with fuses (refer page 5-12).
6 3 400
4 x In OFF 20 @ 10 x In
Thermal THERMAL
REFLECTIVITY
Reflectivity ON ON N1 N2
6-4
6.4 Configuring UW-MTX2.5/2.5G/3.5/3.5EC
1. System Settings
Setting Breaker Rating (UW-MTX-2.5/2.5G/3.5/3.5EC):
Follow the mentioned steps for configuration of breaker rating
Save Settings ?
Rest of the parameters under System settings should be set in same manner.
After programming the settings, press key to escape from menu and
Yes No confirm the changes in Save Settings.
Note: To apply any parameter change in System settings in P&C unit , reset the power supply
once settings are saved.
6-5
2. Unit Settings
Unit settings can be programmed following menu navigation Sequence given below
I1
I2
I3
Current
: 0A
: 0A
: 0A
Menu
Settings
View Records
Metering
Settings
Config Mode
View Mode
Password
****
Select “Settings” by Select “Config” Mode” Enter the password “0000”
Press “SEL” key SEL key (Factory set: default)
Date & Time :Current date & time to be entered. Helpful for fault history time stamping.
Communication :Total 126 Device Ids are provided along with Parity option, Baud Type,
Baud rate with wide range up to 19.2kbps.
Event Recorder :To capture an event viz alarm, pick-up, trip ,module connect/disconnect
and maintenance.
Max Demand :Maximum demand of energy integration and refreshing interval can be
selected.
Settings P/W: :The factory default settings password is “0000” which can be modified
to new password by user.
Command password :The factory default command password is “0000”. This password is valid for
following commands enlisted in “Restore settings” menu, namely
Maint. operation ,Clear MD ,Set Group ,Factory Setting, Clear Max I, Clear
Max V, Clear Energies and Earth Fault test of the P&C Unit. It is configurable.
Contrast :Screen contrast can be adjusted.
Auto set GRP: :As per the factory load requirements, protections can be configured using
time based set groups. Active set group will switch over to dormant set group
after the set time elapsed.
Day Light Saving :Day light saving can be programmed through this option. Enable the
Day light saving option, using “DST Mode” Enable and set the Start
and End DST dates and the time which is required to add.
6-6
3. Protection
Set the protection settings as per the following menu navigation Sequence.
Press “SEL” key in the Select “Settings” by Select “Config” Mode” Enter the password “0000”
overlay SEL key (Factory Set: default)
Set Group 1 * Two interchangeable protection set groups are provided to meet different load
requirements in plant.
I Protection Set group 1 is Default active Set group. Time based set group can be programmed
V Protection through “AUTO SET GRP”.
Freq Protection
Overload :It’s a protection against over current. The characteristics provided are I2t, I4t
LI, SI, VI with Thermal memory. Thermal memory help to reduce the trip time of the
unit in case of recursions of overload.
Short Circuit :Excessive currents though the conductors can cause circuit damage ,fire ,explosion .
This protection prevents such conditions.
Directional SC :The protection is a short circuit protection with the ability to recognize the direction of the
phases current during the fault period. The current direction makes it possible to determine
whether the fault is on the supply or load side of the circuit-breaker. Particularly in ring
distribution systems, this makes it possible to identify and disconnect the distribution
feeder where the fault has occurred, whilst keeping the rest of the system running.
Instantaneous :This protection works as short circuit protection with no intentional time delay
which means release operates in 20milliseconds as soon as the fault current
exceeds the set pick-up.
Note: Refer UW-MTX Release manual for the programming of further protections in detail.
6-7
3. Protection....continued
Earth Fault :When fault current flows from phase to earth due to rupturing of insulation,
this can lead to arc flash events and electric shock. This causes more damage to
the distribution system. This feature provides protection against earth fault current.
Neutral Overload :This provides protection against neutral overload at 50%, 100% & 200% of rated
current. It follows overload characteristics.
Restricted EF :It works in the restricted zone of source side. It functions similar to normal earth
fault protection
Earth Leakage :Earth leakage current is harmful to human body. Sensing of fault current & communicating
occurrence of fault signal to the main release is being done by an earth leakage module.
Under current :Decrease in any phase current below threshold leads to under current.
Current Unbalance :It provides protection against any unbalance in phase currents .
Enable O/L protection Select O/L char. from the Select delay from drop down list
drop down list.
Save Settings ? After programming the settings, press key to escape from menu and
confirm the changes in Save Settings. After doing all the settings Save the
Yes No Set Group by pressing the escape key . “Save in Progress” message
confirms the Set Group has saved.
Note: Refer UW-MTX Release manual for the programming of further protections in detail.
6-8
Protections under V- protection:
Under voltage :When the voltage in one of the phases reduces than threshold, this
protection gets activated.
Over voltage :When the voltage in one of the phases increases above threshold, this
protection gets activated.
Voltage unbalance :Voltage unbalance creates damage to the distribution system. This protection
checks voltage unbalance in all three phases.
Residual voltage :Give protection against the residual voltage present in the system.
Under frequency
Over frequency
} applicable for both control frequencies 50Hz & 60Hz.
Reverse power : When the direction of the total active power reverses to that of
the set direction, this protection gets activated. The direction of power depends on
that of the current flowing.
Leading PF : It checks whether the power factor is dropping down the set value when load is
capacitive.
Lagging PF : When the power factor for inductive load goes below the set value, this protection
gets activated. It’s important for any plant to maintain the power factor to unity.
MD active
MD reactive
MD apparent
} When max. demand of active, reactive & apparent power exceeds the set
value, then this protection gets activated.
Phase sequence :Mostly used for motor applications where phase reversal can be seen.
Breaker failure : In case if the breaker fails to open under fault condition (mechanism jam,
FSD malfunctions etc.) release issues one more trip command to FSD to operate
the breaker as per the set delay through this protection.
Note: Refer UW-MTX Release manual for the programming of further protections in detail.
6-9
6.5 Trip Simulation of P & C Unit :
6-10
6.6 U-POWER Omega ACB’s in Connected:
“Click”
5 6 “Click”
CONNECTED
TEST
c DISCONNECTED
b
a
Keeping the OFF button (11a) pressed, open the Rack-in the breaker to Connected position.
Racking Shutter (16). In case panel door is open, Two almost-simultaneous ‘Click’ sounds
also gently depress Racking Interlock (26). confirm ‘Connected’ position.
Carry-out Racking operation only Excessive forceful racking-in
CAUTION when Panel door is closed. CAUTION beyond Connected position may
lead to product damage.
6-11
6.7 Securing your Breaker:
U-POWER Omega offers several security features to prevent unauthorized access and inadvertent operation.
Press the ‘OFF’ button (11a) and turn the key. When key is removed, the
breaker remains locked in OFF position. For switching the breaker ‘ON’,
reinsert the key & turn to release OFF button.
6-12
Section 7
Regular maintenance of U-POWER Omega Series of breaker will help ensure proper operation,
reliable protection and enhanced product life.
Nature of
Schedule/Frequency Actions Reference
Maintenance
7-1
Door Racking Interlock defeat (26):
Tools required: None
Door Racking interlock prevents opening of smart racking
shutter (16) and thus, racking in/out of the breaker when
panel door is open.
U-power Omega ACB poles are equipped with an
indicator for contact condition.
7.1h Greasing of Mechanism:
Non-adherence to greasing schedule
Greasing schedule Mechanism : 1 Year or 500 operations, or using other-than-specified grease
whichever is earlier Grease to be used: MobilithSHC-100 of Mobill. may lead to malfunction.
Greasing schedule Cradle : 1 Year or 50 operations, whichever is
earlier Grease to be used: MobilithSHC-100 of Mobill. CAUTION Ensure that ACB is OFF and Spring is
Discharged, before commencing
The following components can be greased, without dismantling any greasing operation.
accessory or component, using a brush.
1 : Pole shaft bearing (all) 1 : Racking Screw
2 : Bearings (both sides of mechanism) 2 : Racking Cam & Drop Pin joint
3 : Cam Profile 3 : Base Plate
4 : Top surface of links (2) 4 : Rail Sliding surface on Side plate
5 : Top surface of link 5 : Racking Cam & Service Latch follower
6 : Rubbing surface of link 6 : Gear Teeth & Rack Slots
7 : Bottom & side Sliding Surfaces of Rails on Side Plate
8 : Service Latch on Side Plates
9 : Guiding surface of cradle SIC Bridge
8
2
1
7
3
6
Apply grease to the specified components at Simplified diagram for identification of Simplified diagram for identification of
rubbing surfaces components to be greased. components to be greased.
Fault identification:
3) Select versions of UW-MTX 2.5 & 2.5G (Ref. page 5-2) provide separate
remote indication of fault type, when auxiliary supply is available..
4
Reclosing the breaker:
7-4
Fault diagnosis in UW-MTX1.0/1.0+/2.0/2.0+ Units
P&C unit stores 5 Trip Records and 10 Event records which can be read
when auxiliary supply(24 dc) is present. Trip Record contains current, voltage
frequency levels of the system when the fault occured. Event Record records
the events like pick-up,alarm and trip.
e
Releas
Shunt
220V.
240V~,
Moving part of the pole can now
be removed
To take out fixed part of the pole, remove 1 screw from rear side
and 2 screws from top as shown.
Depress Arc-chute Interlock lever to defeat the Refix the connector pin, followed by CTs and CT
interlock and close the breaker. covers. After verifying closing of poles through
few ON-OFF operations, refix the arc chutes.
Jaws can be replaced without using any tool. Slightly rotate the jaw
left or right to remove it.
B A B
Remove screws ‘A’ and loosen screws Pull out the cradle terminal Now you can replace the cradle
‘B’. As a result, Removing of Safety Shutter, assembly using projections terminals & Jaw Cluster assemblies.
jaws and Terminal support clamp will drop down. on the terminal support.
7-7
7.2 Accessories & Spares
7-8
Sr. Component Cat No. Units per Units per
No. Cat No. ACB*
5 Protection&Control Units UW-MTX1.0 CL91966OOOO
UW-MTX1.0G CL91971OOOO
UW-MTX1.5G CL91965OOOO
UW-MTX 2.5 CL90112OOOO
UW-MTX 2.5G CL90610OOOO
UW-MTX 3.5 CL90113OOOO 1 1
UW-MTX 3.5EC CL90700OOOO
UW-MTX 3.5H CL91975OOOO
UW-MTX 4.5 CL90611OOOO
Power Supply Module UN-PS CL90722OOOO 1 1
6 External Simulation kit Matrix CL90724OOOO 1 1
7 Terminal Adaptor for one side Frame-1 3 for 3 Pole
(Incoming or Outgoing) 400-2000A Horiz./Vert. CL60963OOOO 4 for 4 Pole
Drawout ACB 2500A Vertical CL60964OOOO
Frame-2 3 for 3 Pole
400-3200A Horiz./Vert. CL60964OOOO 1 4 for 4 Pole
Frame-3
400-4000A Horiz./Vert. CL90747OOOO 6 for 3 Pole
Vertical CL90748OOOO 8 for 4 Pole
5000A
Horizontal CL60966OOOO 3/4 for 3/4 Pole
6300A Vertical CL60965OOOO 6/8 for 3/4 Pole
Fixed ACB Fr-1 N & S 400-1600A Horiz./Vert. CL60967OOOO
3 for 3 Pole
400-1600A H
Horiz./Vert. CL60968OOOO
Fr-1 2000A S/H 4 for 4 Pole
2500A S/H Vertical CL60976OOOO
Fr-2 400-3200A Horiz./Vert. CL60977OOOO 1 3/4 for 3/4 Pole
Fr-3 400-4000A Horiz./Vert. CL90668OOOO 6 for 3 Pole
5000A Horiz./Vert. CL60982OOOO 8 for 4 Pole
6300A Vertical CL90669OOOO
8 Auxiliary contacts
(4NO+4NC) CL90745OOOO 1 1
7-9
Sr. Component Cat No. Units per Units per
No. Cat No. ACB*
7-10
Units per Units per
Sr.No. Component Cat. No. ACB*
Cat. No.
2 Incomers (2m) CL90810OOOO
23 Mechanical Interlock
(2 metre, 3 metre & 5 metre) 3 Incomers (2m) CL90811OOOO 1 set 1 set
2 Incomers & 1 Standby (2m) CL90812OOOO per scheme
Frame 1 - 3P CL00687OOOO
30 C.T. Wire Harness
For Matrix Frame 1 - 4P CL00688OOOO
Frame 2 - 3P CL00689OOOO
Frame 2 - 4P CL00690OOOO 1 1
Frame 3 - 3P CL00691OOOO
Frame 3 - 4P CL00692OOOO
7-11
Sr. Component Cat No. Units per Units per
No. Cat No. ACB*
31 Current Transformer 400/630/800A CL00700OOOO
(Internal) Frame 1 1000/1250/1600A CL00701OOOO
2000/2500A CL00702OOOO
3 for 3 pole
Frame 2 400/630/800A CL00725OOOO
4 for 4 pole
1000/1250/1600A CL00703OOOO
2000A/2500A/ 1
CL00704OOOO
3200A
Frame 3 400/630/800A CL00726OOOO
1000/1250/1600A CL00727OOOO 6 for 3 pole
2000A/2500A/ 8 for 4 pole
CL00705OOOO
3200A/4000A
5000A/6300A CL00706OOOO
32 Current Transformer for Frame 400/630/800A CL00717OOOO
External Neutral 1,2,3 1000/1250/1600A CL00718OOOO
Frame 1 2000/2500A CL00719OOOO
1 1
Frame 2000A/2500A/
CL00720OOOO
2,3 3200A/4000A
Frame 3 5000A/6300A CL00721OOOO
33 Trip Indication for Undervoltage release CL90947OOOO 1 1
Shunt release CL90951OOOO 1 1
Common fault indication CL90949OOOO 1 1
Ready-to-Close indication CL90953OOOO 1 1
7-12
Section 8
Useful Hints
Useful Hints
Smart Racking Shutter is open Close the Smart Racking Shutter (Insert
Racking Handle once & pull back)
close
the breaker
Smart Racking Shutter does not Breaker is in-between Rack-in or out the
re-close automatically after Connected/Test/Disconnected breaker to any of the
racking handle is pulled out position. Position Indicator distinct positions
is not aligned with any of
the positions
8-1
Unique pole design and Voltmetric releases lead to Energy conservation
Extra safe engineering plastic chosen carefully to meet glow wire test
requirement as per IEC 60695-2-1
Single material used for moulded components for easy disposal
Avoiding use of harmful materials in electrical contact system
Use of easily disposable packing material and avoiding use of thermocole
Special Pigments used to avoid lead content
Bar code