Using Micrologic Trip Units

Description of the Micrologic 5 and 6 Trip Units

Trip Unit Front Face


Use the display screen and keypad on the trip unit to set the trip unit options and check system
measurements. Refer to the navigation principles for more information (see page 24).
Front face of a Micrologic 5.2 A trip unit for a 3-pole circuit breaker

A Indication LEDs
B Test port
C Dials for presetting protection functions and microswitch for locking protection setting
D LCD display
E Navigation keypad

Indication LEDs
Indication LEDs show the trip unit operational state.
Indication LEDs vary in meaning depending on the trip unit type.

Type of Micrologic trip unit Description


Distribution  Ready LED (green) blinks slowly when the standard protection functions of the
electronic trip unit are operational.
 Overload pre-alarm LED (orange) lights when the load exceeds 90% of the Ir
setting.
 Overload alarm LED (red) lights when the load exceeds 105% of the Ir setting.

Motor  Ready LED (green) blinks slowly when the standard protection functions of the
electronic trip unit are operational.
 Overload temperature alarm LED (red) lights when the motor thermal image
exceeds 95% of the Ir setting.

Test Port
Micrologic trip units feature a test port specifically for maintenance actions.
Use the test port to:
 Connect a pocket battery for local testing of the Micrologic trip unit
 Connect the USB maintenance interface for testing, setting the Micrologic trip unit, and for installation
diagnostics
For more information, refer to Compact NSX - Circuit Breakers and Switch-Disconnectors 100–630 A -
User Guide (see page 8).