DCPD7/DCPD7A Power Distribution Unit

Functions >>

The DCPD7/DCPD7A power distribution unit is applicable to a low-voltage DC power distribution system. Connected in serial between the DC power supply and system
devices, it protects devices from surge pulses and transient over-voltage due to external causes (for example, lightning and electromagnetic radiation interference) or internal
causes (for example, system effect of opening and closing breakers, starting and stopping of inductive loads and capacitive loads).

The DCPD7/DCPD7A power distribution unit functions as the power distribution unit for an indoor/outdoor distributed base station system (BBU+RRU). It has the following
features:

• Implements two-input and 10-output power distribution.

• Provides a large discharge current and a low residual voltage.

• Contains a built-in lightning protection board, which provides lightning protection and surge protection for the LLVD1 output side when the first power-down is implemented.

• Provides a telesignaling alarm interface (dry contact signals).

• Uses a metal shell, and provides a protection rating of IP2X. It is installed indoors, providing a sound fire-retardant capability.

• Uses the front-cabling method, with which the cabling does not require additional space.

The DCPD7 and the DCPD7A have the same external view. They differ in the maximum current of the input and output circuits. Planning personnel can perform configurations
as needed. For detailed information, refer to Table 1.

Table 1 DCPD7/DCPD7A Power Distribution Unit Specification

Type Application Scenario Description

DCPD7 It is applicable to distributed base stations,


• Two DC inputs, and the rated current is 160 A.
providing power supply for BBUs and RRUs.
• 10 DC outputs, equipped with 25 A circuit breakers.

• 10 DC outputs, providing the lightning protection function.

DCPD7A It is applicable to outdoor distributed base


• One DC input for the first power-down, and the rated current is 100 A.
stations, providing power supply for the devices
inside the BC cabinet of the . One DC input for the second power-down, and the rated current is 50 A.

• Two DC outputs, equipped with 10 A circuit breakers, used for the second power-down.

Two DC outputs, equipped with 25 A circuit breakers, used for the second power-down.

Six DC outputs, equipped with 25 A circuit breakers, used for the first power-down.

• Six DC outputs for the first power-down, providing the lightning protection function.

Four DC outputs for the second power-down, not providing the lightning protection
function.

External View >>

Figure 1 shows the external views of a DCPD7 and a DCPD7A.

Figure 1 DCPD7/DCPD7A Power Distribution Unit

Interfaces >>

For a description of the interfaces on the DCPD7 panel, refer to Figure 2.

Figure 2 Interfaces on the DCPD7 Panel

http://127.0.0.1:8890/document?channelid=2&record=2&resultid=4&presearchword=DocB... 7/2/2018
DCPD7/DCPD7A Power Distribution Unit Page 4 of 5

Position Name Description

1 PWR1 External DC input (dual DC input terminals are connected in parallel, and the rated current
PWR2 is 160 A)

2 Control switch (circuit breaker 10 × 25 A) Controls the DC output on the right side

3 DC output 1 (BBU/RRU) Outputs power supply to the power distribution unit of the indoor BBU or an outdoor RRU.

DC output 2 (BBU/RRU) Outputs power supply to the power distribution unit of the indoor BBU or an outdoor RRU.

DC output 3 (BBU/RRU) Outputs power supply to the power distribution unit of the indoor BBU or an outdoor RRU.

DC output 4 (BBU/RRU) Outputs power supply to the power distribution unit of the indoor BBU or an outdoor RRU.

DC output 5 (BBU/RRU) Outputs power supply to the power distribution unit of the indoor BBU or an outdoor RRU.

DC output 6 (BBU/RRU) Outputs power supply to the power distribution unit of the indoor BBU or an outdoor RRU.

DC output 7 (BBU/RRU) Outputs power supply to the power distribution unit of the indoor BBU or an outdoor RRU.

DC output 8 (BBU/RRU) Outputs power supply to the power distribution unit of the indoor BBU or an outdoor RRU.

DC output 9 (BBU/RRU) Outputs power supply to the power distribution unit of the indoor BBU or an outdoor RRU.

DC output 10 (BBU/RRU) Outputs power supply to the power distribution unit of the indoor BBU or an outdoor RRU.

4 LP_ALM Reports lightning protection alarms (dry contact output)

For a description of the interfaces on the DCPD7A panel, refer to Figure 3.

Figure 3 Interfaces on the DCPD7A Panel

Position Name Description

1 LLVD1 External DC input (the first power-down, the rate current is 100 A)

LLVD2 External DC input (the second power-down, the rate current is 50 A)

2 Control switch for the LLVD1 output (circuit breaker 6 Controls the DC output for the first power-down on the right side
× 25 A) Controls the DC output for the second power-down on the right side
Control switch for the LLVD2 output (circuit breaker 2
× 25 A + 2 × 10 A)

3 LLVD2 DC output 1 Outputs power supply to the power distribution module of the BC cabinet of BS8900A
series products (the second power-down).

LLVD2 DC output 2 Outputs power supply to the power distribution module of the BC cabinet of BS8900A
series products (the second power-down).

LLVD2 DC output 3 Outputs power supply to the power distribution module of the BC cabinet of BS8900A
series products (the second power-down).

LLVD2 DC output 4 Outputs power supply to the power distribution module of the BC cabinet of BS8900A
series products (the second power-down).

LLVD1 DC output 5 Outputs power supply to the power distribution module of an RRU (the first power-down)

LLVD1 DC output 6 Outputs power supply to the power distribution module of an RRU (the first power-down)

LLVD1 DC output 7 Outputs power supply to the power distribution module of an RRU (the first power-down)

LLVD1 DC output 8 Outputs power supply to the power distribution module of an RRU (the first power-down)

LLVD1 DC output 9 Outputs power supply to the power distribution module of an RRU (the first power-down)

LLVD1 DC output 10 Outputs power supply to the power distribution module of an RRU (the first power-down)

4 LP_ALM Reports lightning protection alarms (dry contact output)

Technical Specifications >>

http://127.0.0.1:8890/document?channelid=2&record=2&resultid=4&presearchword=DocB... 7/2/2018
DCPD7/DCPD7A Power Distribution Unit Page 5 of 5

Table 2 DCPD7/DCPD7A Specifications

Item Specification

W×H×D (mm) 482.6×43.6×118

Installation Requirement
• It is installed in a standard 19-inch rack, occupying a 1-U space.

• It uses the front-cabling method, with which the cabling does not require additional space. The installation height of DCPD7
series products is not higher than 2 m and not lower than 60 cm. If the equipment is installed in the basement, an additional
installation height must be left.

• It does not provide the waterproof function, thus dripping water, splash, and moisture must be avoided.

• It must be strictly grounded in accordance with the specification, and the grounding cable must be as short as possible.

Input voltage –48 V DC

Input current DCPD7: 160 A


DCPD7A:

• 100 A (the first power-down LLVD1)

• 50 A (the second power-down LLVD2)

Output voltage –48 V DC

Output current DCPD7:

• Circuit breaker configuration: 10 DC outputs, equipped with 25 A circuit breakers.

• Lightning protection configuration: 10 DC outputs, providing the lightning protection function.

DCPD7A:

• Circuit breaker configuration:

→ Two DC outputs, equipped with 10 A circuit breakers, used for the second power-down.

→ Two DC outputs, equipped with 25 A circuit breakers, used for the second power-down.

→ Six DC outputs, equipped with 25 A circuit breakers, used for the first power-down.

• Lightning protection configuration:

→ Six DC outputs for the first power-down, providing the lightning protection function.

→ Four DC outputs for the second power-down, not providing the lightning protection function.

Surge The surge protection capability at the DC output end:

• Line-line 10 kA (8/20 us)

• Line-ground 15 kA (8/20 us)

Monitoring The DCPD7 series products provide a pair of dry contact outputs for monitoring the status of the Lightning Protection Unit (LPU).
The dry contact status is defined as follows:

• Connected: The LPU is operating properly.

• Disconnected: The LPU fails.

Waterproof and dustproof protection IP20


rating

Operating environment
• Operating temperature: –40℃ to +65 ℃

• Storage temperature: –40 ℃ to +70 ℃

• Relative humidity: 5%–95% (25℃)