Sunteți pe pagina 1din 434

INSTITUTO POLITÉCNICO NACIONAL

ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA


UNIDAD ZACATENCO

MEMORIA DE EXPERIENCIA PROFESIONAL:

“Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de


Tratamiento de Aguas Residuales Atotonilco”

QUE PARA OBTENER EL TÍTULO DE:

INGENIERO CIVIL

PRESENTA:

MARTÍN VALOR MANRIQUE

ASESOR:

M. en I. ALFREDO ANTONIO PÁEZ ROBLES

FEBRERO/2016

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco i
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Índice.

Índice de figuras. iii

Introducción. v

Marco Teórico. x

CLASIFICACIÓN DE LA CONSTRUCCIÓN SEGÚN SU DESTINO ...................................... x


FACTOR DE COMPORTAMIENTO SÍSMICO Q .............................................................. xi
CONSIDERACIONES GENERALES PARA EL ANÁLISIS DE LA ESTRUCTURA .................... xii
DISEÑO POR DURABILIDAD. ................................................................................. xiii
REQUISITOS COMPLEMENTARIOS DEL ANÁLISIS DE LA ESTRUCTURA ....................... xiv
CAPÍTULO I. Consideraciones generales para el análisis de la estructura. 1

I.1. Cálculo del Factor de Reducción Q’. .................................................................1


I.2. Definición de cargas. .....................................................................................5
I.3. Análisis de cargas unitarias........................................................................... 11
I.4. Descripción del análisis. ............................................................................... 13
I.5. Resumen de materiales ................................................................................ 14
I.6. Cálculo de coeficiente de reacción vertical Kvs ................................................ 15
CAPÍTULO II. Análisis de la estructura. 16

II.1. Cálculo del centro de masa ........................................................................... 16


II.2. Análisis sísmico estático. .............................................................................. 17
II.3. Cálculo de empuje de reposo. ....................................................................... 19
II.4. Cálculo de empuje debido al sismo. ............................................................... 20
CAPÍTULO III. Topología del modelo tridimensional. 22

CAPÍTULO IV. Sismo. 28

IV.1. Cálculo de rigideces. .................................................................................... 28


IV.2. Distribución de fuerzas sísmicas. ................................................................... 34
CAPÍTULO V. Análisis de resultados. 46

V.1. Revisión de desplazamientos. ....................................................................... 46


V.2. Revisión de deflexiones en trabes por medio del RCDF NTC 2004. ..................... 58
V.3. Diseño de zapatas aisladas. .......................................................................... 62
V.4. Diseño de zapatas corridas. .......................................................................... 70
V.5. Diseño de losas de entrepiso y azoteas. ......................................................... 79
V.6. Diseño de castillos para muros de mampostería. ............................................. 89
V.7. Diseño de muros de concreto reforzado.......................................................... 92
V.8. Revisión de cortante en columnas. ................................................................ 95
Bibliografía. xix

ANEXO 1: Datos de entrada. xx

ANEXO 2: Reusltado de diseño. lvii

ANEXO 3: Planos cccv

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Índice de figuras.

Figura 1. Plano general de conjunto de la PTAR-Atotonilco. ...................................................................... v


Figura 2. Planta del edificio de Sub-Estación Derivada Número 8 ............................................................. vi
Figura 3. Planta de la Sub-Estación Derivada Número 8 ...........................................................................vii
Figura 4. Fachada eje A, de la Sub-Estación Derivada Número 8 ............................................................ viii
Figura 5. Longitud de desarrollo de barras con doblez .............................................................................xvi
Figura 6. Isométrico del modelo del edificio (imagen tomada directa del programa STAAD.Pro V8i) ..... 22
Figura 7. Planta y numeración de nodos donde se localizan las zapatas aisladas .................................. 23
Figura 8. Planta y numeración de nodos donde se localizan las zapatas corridas. ................................. 23
Figura 9. Isométrico y numeración de dados ............................................................................................ 24
Figura 10. Planta y numeración de Contratrabes ..................................................................................... 24
Figura 11. Planta y numeración de trabes principales y secundarias. Entrepiso ..................................... 25
Figura 12. Planta y numeración de trabes principales y secundarias. Cuarto de Aire Acondicionado .... 25
Figura 13. Planta y numeración de trabes principales y secundarias. Sótano ......................................... 26
Figura 14. Isométrico y numeración de columna Nivel 1 .......................................................................... 26
Figura 15. Isométrico y numeración de columnas Nivel 2 ........................................................................ 27
Figura 16. Ubicación y nomenclatura de marcos para el cálculo de rigideces Nivel 1 ............................ 28
Figura 17. Ubicación y nomenclatura de marcos para el cálculo de rigideces Nivel 2 ............................ 28
Figura 18. Numeración de nodos para revisión de desplazamientos horizontales Nivel 1. ..................... 46
Figura 19. Numeración de nodos para revisión de desplazamientos horizontales Nivel 2. ..................... 46
Figura 20. Diagrama de presiones ZA-1. .................................................................................................. 62
Figura 21. Carga Axial y momentos actuantes ZA-1. ............................................................................... 65
Figura 22. Bloque rectangular equivalente de esfuerzos ZA-1................................................................. 65
Figura 23. Sección crítica ZA-1. ................................................................................................................ 67

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco iii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Índice de tablas.

Tabla 1 Distribución de dirección X SX1 Nivel Azotea .............................................................................. 34


Tabla 2 Distribución de dirección Z SX1 Nivel Azotea............................................................................... 35
Tabla 3 Distribución de dirección X SX1 Nivel Entrepiso .......................................................................... 36
Tabla 4 Distribución de dirección Z SX1 Nivel Entrepiso .......................................................................... 36
Tabla 5 Distribución de dirección X SX3 Nivel Azotea .............................................................................. 37
Tabla 6 Distribución de dirección Z SX3 Nivel Azotea............................................................................... 38
Tabla 7 Distribución de dirección X SX3 Nivel Entrepiso .......................................................................... 39
Tabla 8 Distribución de dirección Z SX3 Nivel Entrepiso .......................................................................... 39
Tabla 9 Distribución de dirección X SZ1 Nivel Azotea............................................................................... 40
Tabla 10 Distribución de dirección Z SZ1 Nivel Azotea ............................................................................. 41
Tabla 11 Distribución de dirección X SZ1 Nivel Entrepiso ........................................................................ 42
Tabla 12 Distribución de dirección Z SZ1 Nivel Entrepiso ......................................................................... 42
Tabla 13 Distribución de dirección X SZ3 Nivel Azotea ............................................................................ 43
Tabla 14 Distribución de dirección Z SZ3 Nivel Azotea ............................................................................. 44
Tabla 15 Distribución de dirección X SZ3 Nivel Entrepiso ........................................................................ 45
Tabla 16 Distribución de dirección Z SZ3 Nivel Entrepiso ......................................................................... 45

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco iv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Introducción.
Como en todo proyecto de obra civil y atendiendo a su magnitud y especialización inherente, la Sub-Estación
Derivada Número 8 resulta ser un espacio necesario para el correcto funcionamiento de la Planta de Tratamiento
de Aguas Residuales Atotonilco ubicada en el Estado de Hidalgo, y está ubicada en el área que corresponde a
los edificios operativos y de servicio, que se encuentran al noreste de la Planta de Tratamientos de Aguas
Residuales. Está flanqueado al oeste por el Edificio de Deshidratación de Lodos, al este por el Tanque Tampón.
Se enlaza a los demás edificios por medio de la vialidad principal. Ver figura 1.

Figura 1. Plano general de conjunto de la PTAR-Atotonilco.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco v
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

La operación de la planta de tratamiento requiere del funcionamiento de motores, alumbrado, UPS, centros de
control de motores, etc. razón por la cual es indispensable contar con la infraestructura necesaria para la
transformación, control y derivación de energía eléctrica. En general el área de la Sub-Estación Derivada Número
8 se encuentra dividida en zonas de acometida eléctrica (área de transformadores), almacenamiento de
combustible, planta de emergencia, cuarto eléctrico (control de motores, tableros, UPS, etc.) y cárcamo de aceite.
Por lo que el área disponible para la Sub-Estación Derivada Número 8 se diseñó en función del equipamiento
que albergará, así como del área necesaria para su operación y mantenimiento. Ver figura 2.

Figura 2. Planta del edificio de Sub-Estación Derivada Número 8

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco vi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

La Sub-Estación Derivada Número 8 estará dividida en tres secciones, cuarto eléctrico, planta de emergencia y
zona de transformadores. Ver figura 3.

El acceso a las diferentes áreas es independiente uno del otro, se llega a este espacio por medio de una de las
vialidades principales. Su ubicación se pensó de tal modo que se pueda acceder a este edificio de manera fácil
y rápida, sin intervenir en las demás actividades de los otros edificios del conjunto.

La propuesta para la Sub-Estación Derivada Número 8 es muy sencilla y toma en cuenta para su diseño formas
geométricas regulares y simples, en este caso se divide este espacio en un cuarto eléctrico y un cuarto para
alojar las plantas de emergencia, estos en forma rectangular. Esta forma facilitará el acomodo de los equipos.
Cuenta con rampas y puertas abatibles para poder acceder en diferentes puntos al cuarto eléctrico y de forma
independiente a la zona de plantas de emergencia.

Se cuenta con muros cortafuego sobre los ejes 3, 4, C, D y E, con el fin de aislar al cuarto eléctrico y zona de
transformadores en caso de un siniestro, los muros del edificio son de mampostería, a excepción de los muros
que se encuentran entre los ejes 1-2, A-B y C-D, los cuales serán muros de concreto, ligados a la estructura
principal; tanto los muros de mampostería como los muros cortafuego, se diseñaron y especificaron para que se
encuentren separados de la estructura principal.

El acceso al cuarto de aire acondicionado es por fuera del cuarto eléctrico mediante una escalera marina con
jaula de protección.

Figura 3. Planta de la Sub-Estación Derivada Número 8

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco vii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

El edificio se desplanta sobre una superficie de 570 m² aproximadamente, alcanzando una altura total de 13.62
m. dejando definidas las alturas de entrepiso en 7.70 m para el cuarto eléctrico y las plantas de emergencia, y
5.0 m, este último correspondiente al cuarto de aire acondicionado. Ver figura 2.2.

Figura 4. Fachada eje A, de la Sub-Estación Derivada Número 8

El análisis y diseño de la Sub-Estación Derivada Número 8 estará regido bajo el marco del Reglamento de ACI-
318 (318, 2008), Construcciones del Distrito Federal publicado el 29 de enero del 2004 y sus Normas Técnicas
Complementarias de Concreto, Cimentaciones y Sismo cuando así se requieran.

“Todo Proyecto (Arquitectónico) debe contemplar la posibilidad de implementar sistemas estructurales que
sean eficientes para resistir las acciones permanentes y accidentales que puedan afectar a la estructura.
Poniendo especial atención a los efectos sísmicos, de preferencia concebir una estructuración regular que
cumpla con la mayoría de los requisitos que establecen las normas que aplican para tal efecto.”

La edificación debe contar con un sistema estructural que permita el flujo adecuado de las fuerzas que generan
las distintas acciones de diseño, para que dichas fuerzas puedan transmitirse de forma continua y eficiente hasta
la cimentación. Siendo esta la que garantice la correcta transmisión al suelo donde se desplante.

La estructuración se resolvió por marcos ortogonales formados por columnas y trabes de concreto reforzado de
sección rectangular, en ambas direcciones. El sistema de losa de cubierta resulto una losa maciza de 12 cm,
de espesor al igual que la losa de entrepiso, ver planos estructurales. La cimentación se resolvió con zapatas
aisladas y zapatas corridas de diferentes dimensiones (ver plano estructural correspondiente) conectadas entre
sí por contratrabes de concreto reforzado de sección rectangular. Los muros de mampostería se encuentran

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco viii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

ligados a la cimentación de la estructura principal, pero se desligan de los marcos ortogonales para que no
participen en la rigidez de la estructura. Los muros cortafuego se construyen de concreto reforzado, dichos
muros estarán ligados a la cimentación, pero desligados de los marcos ortogonales para que no participen en
la rigidez de la estructura, por último, los muros de cortante, serán de concreto reforzado, ligados a la estructura
para garantizar una rigidez mayor de la estructura.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Marco Teórico.

CLASIFICACIÓN DE LA CONSTRUCCIÓN SEGÚN SU DESTINO


El destino de las construcciones debe tomarse como referencia para determinar su importancia, y con ello, la
protección o seguridad que se les provea. Este criterio se consigna en la tabla 2.1. del manual de obras civiles
de la Comisión Federal de Electricidad.

Estructuras en que se requiere un grado de seguridad alto. Construcciones cuya


falla estructural causaría la pérdida de un número elevado de vidas o pérdidas
económicas o culturales de magnitud intensa o excepcionalmente alta, o que
constituyan un peligro significativo por contener sustancias tóxicas o inflamables,
así como construcciones cuyo funcionamiento sea esencial a raíz de un sismo. Tal
es el caso de puentes principales, sistemas de abastecimiento de agua potable,
subestaciones eléctricas, centrales telefónicas, estaciones de bomberos, archivos
y registros públicos, monumentos, museos, hospitales, escuelas, estadios, templos,
terminales de trasporte, salas de espectáculos y hoteles que tengan áreas de
reunión que pueden alojar un número elevado de personas, gasolineras, depósitos
de sustancias inflamables o tóxicas y locales que alojen equipo especialmente
costoso. Se incluyen también todas aquellas estructuras de plantas de generación
GRUPO A
de energía eléctrica cuya falla por movimiento sísmico pondría en peligro la
operación de la planta, así como las estructuras para la transmisión y distribución
de energía eléctrica.

CLASIFICACIÓN DE LA CONSTRUCCIÓN SEGÚN SU ESTRUCTURACIÓN

Estructuras de edificios: Estructuras comunes tales como edificios urbanos, naves


industriales típicas, salas de espectáculos y estructuras semejantes, en que las
fuerzas laterales se resisten en cada nivel por marcos continuos contra venteados
TIPO I
o no, por diafragmas o muros o por la combinación de estos.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco x
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

FACTOR DE COMPORTAMIENTO SÍSMICO Q


En la actualidad, la forma más adecuada de caracterizar las estructuras en función de su ductilidad consiste en
el empleo del factor de comportamiento sísmico Q, que en realidad no sólo está asociado a la ductilidad
estructural, sino también a la estructuración, al deterioro o efecto que puede llegar a contrarrestar gran parte de
la capacidad extra en resistencia que suministra la ductilidad y a reservas de capacidad ante carga sísmica que
los métodos convencionales de diseño no consideran. Para las distintas estructuras comprendidas dentro de la
clasificación por tipos considerada se adoptarán los siguientes valores del factor de comportamiento sísmico. En
la sección de recomendaciones, elaborada para cada uno de los tipos de estructuración considerados en la tabla
2.2, del manual CFE.

RESUMEN DE PARÁMETROS DE DISEÑO

ZONA SÍSMICA (CFE) “B”

COEFICIENTE SÍSMICO CS=0.207

ESTRUCTURA GRUPO “A”

FACTOR DE IMPORTANCIA FI=1.5

FACTOR DE COMPORTAMIENTO SÍSMICO Q=2

CAPACIDAD DE CARGA qa=200 kPa (Para Combinación CM+CV)

CAPACIDAD DE CARGA qa=300 kPa (Para Combinación CM+CV+CA)

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Para la capacidad de carga los datos se obtuvieron a partir de “Estudio de mecánica de suelos y de banco de
materiales para terracerías y agregados de concreto, para la Planta de Tratamiento de Aguas Residuales,
PTAR, en Atotonilco de Tula, Edo. de Hidalgo” por CONTRATISTAS DE ATOTONILCO, S. A. de C. V.
CATOSA

Espectro de Diseño Sísmico

Proyecto: PTAR Atotonilco CELDA 2A DEL MONORRELLENO


Elaborado por: ERN Ingenieros Consultores S.C.
Para: ISASA

PARÁMETROS SÍSMICOS
Tr ao c cTc Ta Tb Tc k r
500 AÑOS 0.075 0.207 0.036 0.050 0.450 4.500 1.600 0.760

CONSIDERACIONES GENERALES PARA EL ANÁLISIS DE LA ESTRUCTURA


En la presente memoria se presentan los comentarios empleados para diseñar la estructura de concreto.

Criterios de diseño.

Las fuerzas y momentos internos producidos por las acciones a que están sujetas las estructuras se determinarán
de acuerdo con los criterios prescritos en la sección 1.4. De las NTC. El dimensionamiento y el detallado se harán
de acuerdo con los criterios relativos a los estados límite de falla y de servicio, así como de durabilidad,
establecidos en el Título Sexto del Reglamento de construcciones y de sus respectivas Normas Técnicas
Complementarias-Estructuras de Concreto (NTC-EC),

Estados límite de falla.

Según el criterio de estados límite de falla, las estructuras deben dimensionarse de modo que la resistencia de
diseño de toda sección con respecto a cada fuerza o momento interno que en ella actúe, sea igual o mayor que
el valor de diseño de dicha fuerza o momento internos.

Las resistencias de diseño deben incluir el correspondiente factor de resistencia, FR, prescrito en la sección 1.7.
De las NTC-EC. Las fuerzas y momentos internos de diseño se obtienen multiplicando por el correspondiente
factor de carga los valores de dichas fuerzas y momentos internos calculados bajo las acciones especificadas
en el Título Sexto del Reglamento y en las Normas Técnicas Complementarias sobre Criterios y Acciones para
el Diseño Estructural de las Edificaciones.

Estados límite de servicio.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Se comprobó que las respuestas de la estructura (deformación, agrietamiento, etc.) quedaron limitadas a valores
tales que el funcionamiento en condiciones de servicio es satisfactorio.

DISEÑO POR DURABILIDAD.


La durabilidad fue tomada en cuenta en el diseño, mediante la determinación de la clasificación de exposición
de acuerdo con la sección 4.2 y, para esa clasificación, cumpliendo con los siguientes requisitos:

a) Calidad y curado del concreto, de acuerdo con las secciones 4.3 a 4.6. (NTC-EC).

Superficie de miembros en contacto con el terreno- Suelo no agresivo - A2.

Serán curados en forma continua bajo temperatura y presión del ambiente por al menos tres días a
partir del día de colado.

b) Superficies de miembros no en contacto con el terreno y expuestos a ambientes exteriores:

Ligeramente agresivos – B1

Serán curados en forma continua bajo condiciones de temperatura y presión del ambiente, por al menos siete
días a partir del colado. El concreto en el miembro tendrá una resistencia a compresión especificada, f’c , no
menor de 200 kg/cm² para clasificación B1.

c) Recubrimiento, de acuerdo con la sección 4.9. (NTC-EC).

Columnas y trabes, 25 mm.

Losas, 15 mm.

Zapatas dados y contratrabes 50 mm.

Este último en cumplimiento con 4.9.3 (NTC-EC). Para superficie en contacto con el terreno será:

75 mm, o 50 mm si se emplea plantilla o membrana impermeable entre el terreno y el concreto por colar.

Materiales.

Concreto.

El concreto utilizado para fines de análisis y diseño de la estructurales fue clase 1, con peso volumétrico de 2.4
t/m³.

Materiales componentes para concretos clase 1. En la fabricación de los concretos, se empleará cualquier tipo
de cemento que sea congruente con la finalidad y características de la estructura, que cumpla con los
requisitos especificados en la norma NMXC-414-ONNCCE.

Los agregados pétreos deberán cumplir con los requisitos de la norma NMX-C-111 con las modificaciones y
adiciones establecidas.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

El concreta clase 1 se fabricará con agregados gruesos calizo, con peso específico superior a 2.6 t/m³.

El agua de mezclado deberá ser limpia y cumplir con los requisitos de la norma NMX-C-122. Si contiene
sustancias en solución o en suspensión que la enturbien o le produzcan olor o sabor fuera de lo común, no
deberá emplearse.

Resistencia a compresión. Los concretos clase 1 tendrán una resistencia especificada, f’c, igual o mayor que 250
kg/cm².

Se deberá comprobarse que el nivel de resistencia del concreto estructural de toda construcción cumpla con la
resistencia especificada. Se admitirá que un concreto cumple con la resistencia especificada si satisface los
requisitos prescritos en la sección 14.3.4.1. (NTC-EC).

Acero.

Como refuerzo ordinario para concreto pueden usarse barras de acero corrugadas, con la salvedad que se indica
adelante, y deben cumplir con las normas NMX-C-407-ONNCCE, NMX-B-294. En el cálculo de resistencias se
usará el esfuerzo de fluencia, fy= 4200 kg/cm2, establecidos en las normas citadas.

REQUISITOS COMPLEMENTARIOS DEL ANÁLISIS DE LA ESTRUCTURA


Anclaje.

La fuerza de tensión o compresión que actúa en el acero de refuerzo en toda sección debe desarrollarse a cada
lado de la sección considerada por medio de adherencia en una longitud de desarrollo, suficiente de barra o de
algún dispositivo mecánico.

Longitud de desarrollo de barras a tensión.

5.1.2.1 (NTC-EC). Barras rectas La longitud de desarrollo, Ld, en la cual se considera que una barra a tensión
se ancla de modo que desarrolle su esfuerzo de fluencia, se obtendrá multiplicando la longitud básica, Ldb dada
por la ec 5.1 (NTC-EC)., por el factor o los factores indicados.

as  fy
Ldb  (5.1)
 
3 c  Ktr  f´c

d b  fy
Ldb  0.11
f´c

Donde:

as = área transversal de la barra;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

db = diámetro nominal de la barra;

c = separación o recubrimiento; úsese el menor de los valores siguientes:

1) distancia del centro de la barra a la superficie de concreto más próxima;

2) la mitad de la separación entre centros de

A tr fyv
Ktr 
100 s  n

Donde:

Atr = área total de las secciones rectas de todo el refuerzo transversal comprendido en la separación s, y que
cruza el plano potencial de agrietamiento entre las barras que se anclan.

fyv = esfuerzo especificado de fluencia de refuerzo transversal;

s = máxima separación centro a centro del refuerzo transversal, en una distancia igual a Ld .

n = número de barras longitudinales en el plano potencial de agrietamiento.

Por sencillez en el diseño, se permite suponer Ktr=0, aunque haya refuerzo transversal. En ningún caso Ld.
será menor que 300 mm.

Barras con dobleces en cumplimiento con la sección 5.5 seguidos de tramos rectos

Barras a tensión que terminan con dobleces a:

Grados tramo recto

90 12db

180 4db

En estas barras se toma como longitud de desarrollo la longitud paralela a la barra, comprendida entre la sección
crítica y el paño externo de la barra después del doblez. La longitud de desarrollo se obtendrá multiplicando la
longitud de desarrollo básica dada por la expresión:

0.76d b  fy

f´c

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Por el factor o los factores de la tabla abajo descrita que sean aplicables, pero sin que se tome menor que 150
mm ni que 8db.

Figura 5. Longitud de desarrollo de barras con doblez

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Longitud de desarrollo de barras a compresión.

La longitud de desarrollo de una barra a compresión será cuando menos el 60 por ciento de la que requeriría a
tensión y no se considerarán efectivas porciones dobladas. En ningún caso será menor de 200 mm.

Factores que modifican la longitud básica de desarrollo de barras con dobleces1

Condición del refuerzo Factor

Barras de diámetro no mayor que 34.9 mm


(número 11), con recubrimiento libre lateral
(normal al plano del doblez) no menor que 60
mm, y para barras con doblez a 90 grados, con
recubrimiento libre del tramo de barra recto
después del doblez no menor que 50 mm 0.7

Barras de diámetro no mayor que 34.9 mm


(número 11), confinadas en toda la longitud de
desarrollo con estribos verticales u horizontales
separados entre sí no más de 3db 0.8

En concreto ligero 1.3

Barras lisas 1.9

Barras cubiertas con resina epóxica, o con lodo bentonítico 1.2

Todos los otros casos 1.0

Si se aplican varias condiciones, se multiplican los factores correspondientes;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Los requisitos de la sección 5.1.1 (NTC-EC). Y del párrafo anterior se cumplen para el acero a tensión, si:

a) Las barras que dejan de ser necesarias por flexión se cortan o se doblan a una distancia no menor que un
peralte efectivo más allá del punto teórico donde, de acuerdo con el diagrama de momentos, ya no se requieren.

b) En las secciones donde, según el diagrama de momentos flexionantes, teóricamente ya no se requiere el


refuerzo que se corta o se dobla, la longitud que continúa de cada barra que no se corta ni se dobla es mayor o
igual que Ld+d. Este requisito no es necesario en las secciones teóricas de corte más próximas a los extremos
de vigas libremente apoyadas.

c) A cada lado de toda sección de momento máximo, la longitud de cada barra es mayor o igual que la longitud
de desarrollo, Ld, que se define en la sección 5.1.2. (NTC-EC)

d) Cada barra para momento positivo que llega a un extremo libremente apoyado, se prolonga más allá del centro
del apoyo y termina en un doblez de 90 ó 180 grados, seguido por un tramo recto de 12db o 4db, respectivamente.
El doblez debe cumplir con los requisitos de la sección 5.5. (NTC-EC). En caso de no contar con un espacio
suficiente para alojar el doblez, se empleará un anclaje mecánico equivalente al doblez.

Columnas.

En las intersecciones con vigas o losas las barras de las columnas serán continuas y en su caso cumplirán con
las disposiciones de las secciones 7.4.5 u 8.2.b.2. (NTC-EC). Las barras longitudinales de columnas de planta
baja se anclarán en la cimentación de manera que en la sección de la base de la columna puedan alcanzar un
esfuerzo igual al de fluencia en tensión multiplicado por 1.25. En columnas que deban resistir fuerzas laterales
accidentales, se supondrá que se cumple el requisito de la sección 5.1.1 (NTC-EC), si la longitud de desarrollo
de toda barra longitudinal no es mayor que dos tercios de la altura libre de la columna.

Refuerzo por cambios volumétricos.

En toda dirección en que la dimensión de un elemento estructural sea mayor que 1.5 m, el área de refuerzo
que se suministre no será menor que:

660 x1
as1 

fy  x1  100 
DISPOSICIONES COMPLEMENTARIAS PARA ELEMENTOS ESTRUCTURALES COMUNES.

Las disposiciones de esta sección se cumplirán, además de los requisitos generales de las secciones
precedentes.

Vigas Requisitos generales.

El claro se contará a partir del centro del apoyo, siempre que el ancho de éste no sea mayor que el peralte
efectivo

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

De la viga; en caso contrario, el claro se contará a partir de la sección que se halla a medio peralte efectivo del
paño

Interior del apoyo. En toda sección se dispondrá de refuerzo tanto en el lecho inferior como en el superior. En
cada lecho, el área de refuerzo no será menor que la obtenida de la ec. 2.2 (NTC-EC)y constará de por lo menos
dos barras corridas de 12.7 mm. De diámetro (número 4). La cuantía de acero longitudinal a tensión, p, no
excederá de lo indicado en la sección 2.2.2 (NTC-EC), con excepción de vigas de marcos dúctiles para las cuales
se respetará el inciso 7.2.2.a (NTC-EC). En el dimensionamiento de vigas continuas monolíticas con sus apoyos
puede usarse el momento en el paño del apoyo. Para calcular momentos flexionantes en vigas que soporten
losas de tableros rectangulares, se puede tomar la carga tributaria de la losa como si estuviera uniformemente
repartida a lo largo de la viga. La relación entre la altura y el ancho de la sección transversal, h/b, no debe
exceder de 6.

Columnas Geometría.

La relación entre la dimensión transversal mayor de una columna y la menor no excederá de 4. La dimensión
transversal menor será por lo menos igual a 200 mm.

Refuerzo mínimo y máximo.

La cuantía del refuerzo longitudinal de la sección no será menor que 2/fy (fy en MPa, o 20/fy, con fy en kg/cm²)
ni mayor que 0.06. El número mínimo de barras será seis en columnas circulares y cuatro en rectangulares.

Requisitos para refuerzo transversal.

Criterio general.

El refuerzo transversal de toda columna no será menor que el necesario por resistencia a fuerza cortante y
torsión, en

Su caso, y debe cumplir con los requisitos mínimos de los párrafos siguientes. Además, en los tramos donde se
prevean articulaciones plásticas no será inferior al prescrito en la sección 6.8. (NTC-EC).

Separación.

Todas las barras o paquetes de barras longitudinales deben restringirse contra el pandeo con estribos o zunchos
con

Separación no mayor que:

850
a) veces el diámetro de la barra o de la barra más delgada del paquete con fy en kg/cm²;
fy

b) 48 diámetros de la barra del estribo; ni que

c) La mitad de la menor dimensión de la columna


Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

La separación máxima de estribos se reducirá a la mitad de la antes indicada en una longitud no menor que:

a) la dimensión transversal máxima de la columna;

b) un sexto de su altura libre; ni que

c) 600 mm arriba y abajo de cada unión de columna con trabes o losas, medida a partir del respectivo plano de
intersección.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO
DEPARTAMENTO DE FORMACIÓN PROFESIONAL

EN INGENIERÍA APLICADA

CAPÍTULO I. Consideraciones generales para el análisis de la estructura.

I.1. Cálculo del Factor de Reducción Q’.


Para el cálculo de las fuerzas sísmicas para el análisis estático
se empleará un factor de reducción Q' que se calculará como sigue:

Q' = Q; si se desconoce T, o si T ≥ Ta

El período de la estructura se calculó a través del programa Staad Pro, considerando sólo cargas permanentes
de la estructura:

LOAD 1 CÁLCULO DE PERIODO DE VIBRACIÓN


SELFWEIGHT Y -1
FLOOR LOAD
YRANGE 7.35 7.35 FLOAD -0.597 XRANGE 0 7 ZRANGE 0 6 GY
YRANGE 7.35 7.35 FLOAD -0.597 XRANGE 7 25.95 GY
YRANGE 7.35 7.35 FLOAD -0.852 XRANGE 0 7 ZRANGE 6 12 GY
YRANGE 12.48 12.48 FLOAD -0.597 XRANGE 0 7 ZRANGE 6 12 GY
*
SELFWEIGHT X 1
FLOOR LOAD
YRANGE 7.35 7.35 FLOAD -0.597 XRANGE 0 7 ZRANGE 0 6 GX
YRANGE 7.35 7.35 FLOAD -0.597 XRANGE 7 25.95 GX
YRANGE 7.35 7.35 FLOAD -0.852 XRANGE 0 7 ZRANGE 6 12 GX
YRANGE 12.48 12.48 FLOAD -0.597 XRANGE 0 7 ZRANGE 6 12 GX
*
SELFWEIGHT Z 1
FLOOR LOAD
YRANGE 7.35 7.35 FLOAD -0.597 XRANGE 0 7 ZRANGE 0 6 GZ
YRANGE 7.35 7.35 FLOAD -0.597 XRANGE 7 25.95 GZ
YRANGE 7.35 7.35 FLOAD -0.852 XRANGE 0 7 ZRANGE 6 12 GZ
YRANGE 12.48 12.48 FLOAD -0.597 XRANGE 0 7 ZRANGE 6 12 GZ
*
MODAL CALCULATION REQUESTED

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 1
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

MODE FREQUENCY PERIOD


(CYCLES/SEC) (SEC)

1 2.61 0.38315
2 2.877 0.34753
3 3.313 0.30182
4 4.428 0.22585
5 4.902 0.20398
6 5.851 0.17093
7 6.523 0.15331
8 6.829 0.14643
9 7.427 0.13464
10 7.973 0.12542

Por lo tanto T = 0.38315 Seg y el valor Ta = 0.30 Seg Por lo que T > Ta, por lo tanto Q' = Q

FACTOR DE REDUCCIÓN Q' DEBIDO A CONDICIONES DE REGULARIDAD DE LA ESTRUCTURA

1) Su planta es sensiblemente simétrica con respecto a dos ejes ortogonales por lo que toca a masas,
así como a muros y otros elementos resistentes. Estos son además, sensiblemente paralelos a los ejes
ortogonales principales del edificio

No cumple

Para el edificio de la Sub-estación 8 se tomarón las siguientes consideraciones:

Lado mayor en planta (Lz) 25.00 m


Lado menor en planta (Lx) 28.00 m
Altura del edificio (H) 12.50 m

Dimensiones de la entrante o saliente:

En dirección X 18.75 m
En direccion Z 14.00 m

2) La relación de su altura a la dimensión menor en planta no pasa de 2.5

Altura total de la estructiura(H) = 7.70 H/B= 0.31 Si cumple


Lado menor (Lx) = 25.00

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 2
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

3) La relación de largo ancho de la base no excede de 2.5

Largo mayor (Lz) = 28.00 L/B= 1.12 Si cumple


Lado menor (Lx) = 25.00

4) En planta no tiene entrantes ni salientes cuya dimensión exceda de 20% de la dimensión de la planta
medida paralelamente a la dirección que se considera del entrante o saliente

Entrante o saliente:
Dirección X 18.75 C1 = 0.2 Lb 5 No cumple
Direccion Z 14 C2 = 0.2 La 5.6 No cumple

5) En cada nivel tiene un sistema de techo o piso rígido y resistente


Si cumple

6) No tiene aberturas en sus sistemas de techo o piso cuya dimensión exceda el 20% de la dimensión en
planta medida paralelamente a la abertura; las áreas huecas no ocasionan asimetrías significativas ni difie-
ren en posición de un piso a otro y el área total de aberturas no excede en ningún nivel del 20% del área
de planta

Si cumple

7) El peso de cada nivel, incluyendo la carga viva que debe considerarse para diseño sísmico, no es mayor
que 110% del correspondiente al piso inmediato inferior ni, excepción hecha del último nivel de la cosntruc-
ción, es menor que 70% de dicho peso

Si cumple

8) Ningún piso tiene un área, delimitada por los paños exteriores de sus elementos resisentes verticales,
mayor que 110% de la del piso inmediato inferior ni menos que 70% de ésta. Se exime de este último re-
quisito unicamente al último piso de la construcción. Además, el área de ningun entrepiso excede en más
de 50% a la menor de los pisos inferiores

Si cumple

9) Todas las columnas estan restringidas en todos los pisos en dos direcciones sensiblemente ortogonales
por diafragmas horizontales y por trabes o losas planas

Si cumple

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 3
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

10) Ni la rigidez ni la resistencia al corte de ningún entrepiso difieren en más de 50% de la del entrepiso
inmediatamente inferior. El último entrepiso queda excluido de este requisito

Si cumple

11) En ningún entrepiso la excentricidad torsional calculada estáticamente, e s , excede del 10% de la di-
mensión en planta de ese entrepiso medida paralelamente a la excentricidad mencionada

No cumple

ESTRUCTURA IRREGULAR

Toda estructura que no satisfaga uno o más de los requisitos de la sección anterior será considerada irregular.

Corrección por irregularidad El factor de reducción Q’, definido en la sección 4.1( de lasN.T.C.) se multiplicará
por 0.9 cuando no se cumpla con uno de los requisitos 1 a 11 de la sección 6.1 por 0.8 cuando no cumpla con
dos o más de dichos requisitos, y por 0.7 cuando la estructura sea fuertemente irregular según las condiciones
de la sección 6.3. .(de las N.T.C.) En ningún caso el factor Q’ se tomará menor que uno.
Factor de Correccion de Irregularidad Firregularidad = 0.70

Factor de Comportamiento Sísmico de la Estructura Q= 2.00

Factor de Comportamiento sísmico Corregido

Q' = Firregularidad x Q Q' = 1.40

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 4
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

I.2. Definición de cargas.


Las cargas que se consideraron para el análisis de la estructura son las siguientes:

 Carga muerta, la cual incluye: peso de propio de trabes principales, secundarias, columnas, peso del
sistema de piso y peso de equipos fijos.
 Carga viva máxima. Cabe hacer mención que de acuerdo a los criterios de diseño estipulados en el
Reglamento de Construcciones para el Distrito Federal (RCDF), se deben manejar tres conceptos de
carga viva: Carga Viva Máxima (Wm), la cual se deberá emplear para el diseño estructural por fuerzas
gravitacionales y para calcular asentamientos inmediatos en suelos, así como el diseño de las
cimentaciones ante cargas gravitacionales. Carga Viva Instantánea (Wa), la cual se deberá usar para
diseño sísmico y por viento, así mismo cuando se revisen distribuciones de carga más desfavorables que
la uniformemente repartida sobre toda el área. Carga Viva Media (W), la cual se deberá emplear en el
cálculo de asentamientos diferidos y para el cálculo de fechas diferidas.
 Carga Sísmica, evaluada de acuerdo al Manual de Diseño por Sismo de la Comisión Federal de
Electricidad (MDSCFE)
 Estas cargas serán afectadas por los factores de carga correspondientes, indicados en este documento.
 Peso propio de la estructura, inducido por el programa de cálculo.

Las cargas básicas que se consideraron para el análisis de los elementos estructurales (columnas, trabes y
contratrabes, etc.), fueron:

 CARGA MUERTA (incluye el peso propio)

 CARGA VIVA MÁXIMA

 CARGA VIVA INSTANTÁNEA

 CARGA SÍSMICA X

 CARGA SÍSMICA Z

 EMPUJE DEBIDO A RELLENO

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 5
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Para la seguridad de la estructura el Reglamento de Construcciones para el Distrito Federal, en su artículo 188,
establece que deberá verificarse para el efecto combinado de todas las acciones que tengan una probabilidad
no despreciable de ocurrir simultáneamente, considerándose dos categorías de combinaciones:

I. Combinaciones que incluyan acciones permanentes y acciones variables (cargas estáticas).


II. Combinaciones que incluyan acciones permanentes, variables y accidentales (cargas estáticas +
cargas sísmicas y/o de viento)

Bajo ésta consideración, las cargas básicas y las combinaciones de cargas que se consideraron para el diseño
de los elementos estructurales fueron las siguientes:

Cargas Básicas.

LOAD 1 CARGA PERMANENTE (CM)


* CARGA DEBIDA A MUROS DE PRETIL
* CARGA DEBIDA A MUROS DE BLOCK
* CARGA DEBIDA A MUROS DE CORTAFUEGO
* CARGA DEBIDA A MURO DE HVAC
* LOSA DE AZOTEA
* LOSA DE ENTREPISO
* LOSA DE SÓTANO
*******************************************************************************
LOAD 2 CARGA VIVA MÁXIMA (CVM)
* LOSA DE AZOTEA
* LOSA DE ENTREPISO
* LOSA DE SÓTANO
*******************************************************************************
LOAD 3 CARGA VIVA INSTANTÁNEA (CVI)
* LOSA DE AZOTEA
* LOSA DE ENTREPISO
* LOSA DE SÓTANO
******************************************************************************
LOAD 4 SISMO EN DIRECCIÓN SX1
* AZOTEA
* ENTREPISO
* EMPUJE DEBIDO A SISMO
*******************************************************************************
LOAD 5 SISMO EN DIRECCIÓN SX2
JOINT LOAD
* AZOTEA
* ENTREPISO
* EMPUJE DEBIDO A SISMO
*******************************************************************************
LOAD 6 SISMO EN DIRECCIÓN SX3
* AZOTEA
* ENTREPISO
* EMPUJE DEBIDO A SISMO
*******************************************************************************
LOAD 7 SISMO EN DIRECCIÓN SX4
* AZOTEA
* ENTREPISO
* EMPUJE DEBIDO A SISMO
*******************************************************************************
LOAD 8 SISMO EN DIRECCIÓN SZ1
* AZOTEA

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 6
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

* ENTREPISO
* EMPUJE DEBIDO A SISMO
*******************************************************************************
LOAD 9 SISMO EN DIRECCIÓN SZ2
* AZOTEA
* ENTREPISO
* EMPUJE DEBIDO A SISMO
*******************************************************************************
LOAD 10 SISMO EN DIRECCIÓN SZ3
* AZOTEA
* ENTREPISO
* EMPUJE DEBIDO A SISMO
*******************************************************************************
LOAD 11 SISMO EN DIRECCIÓN SZ4
* AZOTEA
* ENTREPISO
* EMPUJE DEBIDO A SISMO
*******************************************************************************
LOAD 12 EMPUJE DE REPOSO X+
*******************************************************************************
LOAD 13 EMPUJE DE REPOSO X-
*******************************************************************************
LOAD 14 EMPUJE DE REPOSO Z+

Combinaciones de carga.

* *******************************************

* ** COMBINACIONES DE CARGA PARA DISEÑO **

* ** POR RESISTENCIA DE LA ESTRUCTURA **

* *******************************************

LOAD COMB 100 U = 1.5 (CP + CVM)

LOAD COMB 101 U = 1.5 (CP + CVM + E1 + E2 + E3 + E4)

*******************************************************************************

* COMBINACIONES DE CARGA CON EL 100% DEL SISMO EN X Y EL 30% EN Z

LOAD COMB 102 U = 1.1 (CP + CVI + SX1 + 0.30 SZ1 + E2 + E4)

LOAD COMB 103 U = 1.1 (CP + CVI + SX1 + 0.30 SZ2 + E2 + E5)

LOAD COMB 104 U = 1.1 (CP + CVI + SX1 + 0.30 SZ3 + E2 + E4)

LOAD COMB 105 U = 1.1 (CP + CVI + SX1 + 0.30 SZ4 + E2 + E5)

*******************************************************************************

LOAD COMB 106 U = 1.1 (CP + CVI + SX2 + 0.30 SZ1 + E1 + E4)

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 7
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

LOAD COMB 107 U = 1.1 (CP + CVI + SX2 + 0.30 SZ2 + E1 + E3)

LOAD COMB 108 U = 1.1 (CP + CVI + SX2 + 0.30 SZ3 + E1 + E4)

LOAD COMB 109 U = 1.1 (CP + CVI + SX2 + 0.30 SZ4 + E1 + E3)

******************************************************************************

LOAD COMB 110 U = 1.1 (CP + CVI + SX3 + 0.30 SZ1 + E2 + E4)

LOAD COMB 111 U = 1.1 (CP + CVI + SX3 + 0.30 SZ2 + E2 + E3)

LOAD COMB 112 U = 1.1 (CP + CVI + SX3 + 0.30 SZ3 + E2 + E4)

LOAD COMB 113 U = 1.1 (CP + CVI + SX3 + 0.30 SZ4 + E2 + E3)

*******************************************************************************

LOAD COMB 114 U = 1.1 (CP + CVI + SX4 + 0.30 SZ1 + E1 + E4)

LOAD COMB 115 U = 1.1 (CP + CVI + SX4 + 0.30 SZ2 + E1 + E3)

LOAD COMB 116 U = 1.1 (CP + CVI + SX4 + 0.30 SZ3 + E1 + E4)

LOAD COMB 117 U = 1.1 (CP + CVI + SX4 + 0.30 SZ4 + E1 + E3)

*******************************************************************************

* COMBINACIONES DE CARGA CON EL 100% DEL SISMO EN Z Y EL 30% EN X

LOAD COMB 118 U = 1.1 (CP + CVI + SZ1 + 0.30 SX1 + E4 + E2)

LOAD COMB 119 U = 1.1 (CP + CVI + SZ1 + 0.30 SX2 + E4 + E1)

LOAD COMB 120 U = 1.1 (CP + CVI + SZ1 + 0.30 SX3 + E4 + E2)

LOAD COMB 121 U = 1.1 (CP + CVI + SZ1 + 0.30 SX4 + E4 + E1)

*******************************************************************************

LOAD COMB 122 U = 1.1 (CP + CVI + SZ2 + 0.30 SX1 + E3 + E2)

LOAD COMB 123 U = 1.1 (CP + CVI + SZ2 + 0.30 SX2 + E3 + E1)

LOAD COMB 124 U = 1.1 (CP + CVI + SZ2 + 0.30 SX3 + E3 + E2)

LOAD COMB 125 U = 1.1 (CP + CVI + SZ2 + 0.30 SX4 + E3 + E1)

*******************************************************************************

LOAD COMB 126 U = 1.1 (CP + CVI + SZ3 + 0.30 SX1 + E4 + E2)

LOAD COMB 127 U = 1.1 (CP + CVI + SZ3 + 0.30 SX2 + E4 + E1)

LOAD COMB 128 U = 1.1 (CP + CVI + SZ3 + 0.30 SX3 + E4 + E2)

LOAD COMB 129 U = 1.1 (CP + CVI + SZ3 + 0.30 SX4 + E4 + E1)

*******************************************************************************

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 8
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

LOAD COMB 130 U = 1.1 (CP + CVI + SZ4 + 0.30 SX1 + E3 + E2)

LOAD COMB 131 U = 1.1 (CP + CVI + SZ4 + 0.30 SX2 + E3 + E1)

LOAD COMB 132 U = 1.1 (CP + CVI + SZ4 + 0.30 SX3 + E3 + E2)

LOAD COMB 133 U = 1.1 (CP + CVI + SZ4 + 0.30 SX4 + E3 + E1)

*******************************************************************************

* ***********************************************

* ** COMBINACIONES DE CARGA PARA REVISISÓN **

* ** DE DESPLAZAMEINTOS Y CIMENTACIÓN **

* ***********************************************

* PARA LA REVISIÓN DE DESPLAZAMIENTOS SE DEBEN MULTIPLICAR LOS OBTENIDOS

* MEDIANTE EL ANÁLISIS DE ELEMENTO FINITO POR EL FACTOR DE REDUCCIÓN Q'

LOAD COMB 200 U = 1.0 (CP + CVM)

LOAD COMB 201 U = 1.0 (CP + CVM + E1 + E2 + E3 + E4)

*******************************************************************************

* COMBINACIONES DE CARGA CON EL 100% DEL SISMO EN X Y EL 30% EN Z

LOAD COMB 202 U = 1.0 (CP + CVI + SX1 + 0.30 SZ1 + E2 + E4)

LOAD COMB 203 U = 1.0 (CP + CVI + SX1 + 0.30 SZ2 + E2 + E3)

LOAD COMB 204 U = 1.0 (CP + CVI + SX1 + 0.30 SZ3 + E2 + E4)

LOAD COMB 205 U = 1.0 (CP + CVI + SX1 + 0.30 SZ4 + E2 + E3)

*******************************************************************************

LOAD COMB 206 U = 1.0 (CP + CVI + SX2 + 0.30 SZ1 + E1 + E4)

LOAD COMB 207 U = 1.0 (CP + CVI + SX2 + 0.30 SZ2 + E1 + E3)

LOAD COMB 208 U = 1.0 (CP + CVI + SX2 + 0.30 SZ3 + E1 + E4)

LOAD COMB 209 U = 1.0 (CP + CVI + SX2 + 0.30 SZ4 + E1 + E3)

*******************************************************************************

LOAD COMB 210 U = 1.0 (CP + CVI + SX3 + 0.30 SZ1 + E2 + E4)

LOAD COMB 211 U = 1.0 (CP + CVI + SX3 + 0.30 SZ2 + E2 + E3)

LOAD COMB 212 U = 1.0 (CP + CVI + SX3 + 0.30 SZ3 + E2 + E4)

LOAD COMB 213 U = 1.0 (CP + CVI + SX3 + 0.30 SZ4 + E2 + E3)

*******************************************************************************

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 9
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

LOAD COMB 214 U = 1.0 (CP + CVI + SX4 + 0.30 SZ1 + E1 + E4)

LOAD COMB 215 U = 1.0 (CP + CVI + SX4 + 0.30 SZ2 + E1 + E3)

LOAD COMB 216 U = 1.0 (CP + CVI + SX4 + 0.30 SZ3 + E1 + E4)

LOAD COMB 217 U = 1.0 (CP + CVI + SX4 + 0.30 SZ4 + E1 + E3)

******************************************************************************

* COMBINACIONES DE CARGA CON EL 100% DEL SISMO EN Z Y EL 30% EN X

LOAD COMB 218 U = 1.0 (CP + CVI + SZ1 + 0.30 SX1 + E4 + E2)

LOAD COMB 219 U = 1.0 (CP + CVI + SZ1 + 0.30 SX2 + E4 + E1)

LOAD COMB 220 U = 1.0 (CP + CVI + SZ1 + 0.30 SX3 + E4 + E2)

LOAD COMB 221 U = 1.0 (CP + CVI + SZ1 + 0.30 SX4 + E4 + E1)

*******************************************************************************

LOAD COMB 222 U = 1.0 (CP + CVI + SZ2 + 0.30 SX1 + E3 + E2)

LOAD COMB 223 U = 1.0 (CP + CVI + SZ2 + 0.30 SX2 + E3 + E1)

LOAD COMB 224 U = 1.0 (CP + CVI + SZ2 + 0.30 SX3 + E3 + E2)

LOAD COMB 225 U = 1.0 (CP + CVI + SZ2 + 0.30 SX4 + E3 + E1)

*******************************************************************************

LOAD COMB 226 U = 1.0 (CP + CVI + SZ3 + 0.30 SX1 + E4 + E2)

LOAD COMB 227 U = 1.0 (CP + CVI + SZ3 + 0.30 SX2 + E4 + E1)

LOAD COMB 228 U = 1.0 (CP + CVI + SZ3 + 0.30 SX3 + E4 + E2)

LOAD COMB 229 U = 1.0 (CP + CVI + SZ3 + 0.30 SX4 + E4 + E1)

*******************************************************************************

LOAD COMB 230 U = 1.0 (CP + CVI + SZ4 + 0.30 SX1 + E3 + E2)

LOAD COMB 231 U = 1.0 (CP + CVI + SZ4 + 0.30 SX2 + E3 + E1)

LOAD COMB 232 U = 1.0 (CP + CVI + SZ4 + 0.30 SX3 + E3 + E2)

LOAD COMB 233 U = 1.0 (CP + CVI + SZ4 + 0.30 SX4 + E3 + E1)

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 10
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

I.3. Análisis de cargas unitarias


A continuación se considerarán las diferentes cargas que actúan sobre las losas de la
estructura. Y que son:

Espesor P. Vol. C. Unit.


Ubicación de losa
(m) (ton/m3) (ton/m2)
Azotea (Losa maciza esp. = 12 cm.)
Impermeabilizante 0.005
Entortado de cemento 0.070 2.00 0.140
Relleno de tezontle ligero 0.150 0.65 0.098
Peso propio de losa maciza (esp. = 12 cm.) 0.120 2.40 0.288
Plafón 0.005 1.20 0.006
Instalaciones 0.020
Carga muerta adicional (NTC-5.1.2) 0.040
Carga permanente total, C.P. 0.597
Carga viva máxima, Wm (NTC-Tabla 6.1) 0.100
Carga viva media, W (NTC-Tabla 6.1) 0.015
Carga viva instantánea, Wa (NTC-Tabla 6.1) 0.070
Carga para diseño estático, Wdv = C.P. + Wm 0.697
Carga para diseño sísmico, Wda = C.P. + Wa 0.667

Espesor P. Vol. C. Unit.


Ubicación de losa
(m) (ton/m3) (ton/m2)
Entrepiso (Losa maciza esp. = 12 cm.)
Firme de concreto 0.120 2.00 0.240
Relleno de tezontle ligero 0.150 0.65 0.098
Peso propio de losa maciza (esp. = 12 cm.) 0.120 2.40 0.288
Plafón 0.005 1.20 0.006
Instalaciones. 0.020
Bases de concreto para equipos 0.060
Carga debida a equipos de aire acondicionado 0.100
Carga muerta adicional (NTC-5.1.2) 0.040
Carga permanente total, C.P. 0.852
Carga viva máxima, Wm (NTC-5.1.2) 0.250
Carga viva media, W (NTC-Tabla 6.1) 0.100
Carga viva instantánea, (NTC-5.1.2) 0.180
Carga para diseño estático, Wdv = C.P. + Wm 1.102
Carga para diseño sísmico, Wda = C.P. + Wa 1.032

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 11
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Especificaciones de cargas en muros

Espesor P. Vol. C. Unit.


Tipo de muro
(m) (ton/m3) (ton/m2)
Tipo 1

Aplanado (2 caras) 0.03 1.50 0.045


Muro de block hueco 20x20x40 0.216
Carga permanente total, C.P. 0.261

Tipo 2

Aplanado (2 caras) 0.03 1.50 0.045


Muro de concreto reforzado 0.15 2.40 0.360
Carga permanente total, C.P. 0.405

Descargas de muros

Descargas de muros

Altura Peso
Tipo de muro Ubicación
(m) (ton/m)
Tipo 1

Muro de block hueco 20x20x40 0.90 0.235 Pretil perimetral en azotea

4.10 1.070 Muro de cuarto de aire


acondicionado
7.00 1.827 Muro de planta baja

9.70 2.532 Muro de planta baja

Tipo 2

Muro de concreto reforzado 7.70 3.119 Muro de planta baja

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 12
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

I.4. Descripción del análisis.


En apego al cumplimiento de Art 147 del RCDF y las recomendaciones del ACI. Toda la estructura y cada una
de sus partes se diseñaron para cumplir con los requisitos básicos siguientes:

I. Tener seguridad adecuada contra la aparición de todo estado límite de falla posible ante las combinaciones de
acciones más desfavorables que puedan presentarse durante su vida esperada, y

II. No rebasar ningún estado límite de servicio ante combinaciones de acciones que corresponden a condiciones
normales de operación. Definiendo cada uno como sigue:

Se considerará como estado límite de falla cualquier situación que corresponda al agotamiento de la capacidad
de carga de la estructura o de cualquiera de sus componentes, incluyendo la cimentación, o al hecho de que
ocurran daños irreversibles que afecten significativamente su resistencia ante nuevas aplicaciones de carga. Las
Normas establecerán los estados límite de falla más importante para cada material y tipo de estructura.

La estructura se modeló como una estructura tridimensional; para el análisis y diseño de los elementos
principales (columnas, trabes), se usó el programa STAAD Pro for Windows v.2007 (Structural Analysis and
Design Software), propiedad de Research Engineers, Inc.

El diseño de los elementos estructurales (trabes, columnas) se realizó con los elementos mecánicos que resulten
del análisis y de la combinación más desfavorable.

La cimentación se diseñó con el método de resistencia última especificado en Las Normas Técnicas
Complementarias para Diseño y Construcción de Estructuras de Concreto del Reglamento de Construcciones
para el Distrito Federal.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 13
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

I.5. Resumen de materiales


 Concreto estructural y acero de refuerzo

Las características de los materiales que se especificaron para el análisis y diseño del proyecto son los siguientes:

CONCRETO f'c = 250 kg/cm2. Para elementos estructurales (Zapatas, contratrabes, dados, columnas, trabes, losas,
muros cortafuego y muros de cortante.

CONCRETO f'c = 200 kg/cm2. Para elementos no estructurales (castillos, dalas y firmes de concreto).

Peso Volumétrico = 2400 kg/m3.

ACERO DE REFUERZO Fy = 4200 kg/cm2.

ACERO DE REFUERZO Fy = 2520 kg/cm 2. (Alambrón).

ACERO DE ALTA RESISTENCIA Fy = 5000 kg/cm 2. (Malla electrosoldada).

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 14
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

I.6. Cálculo de coeficiente de reacción vertical Kvs


OBTENCIÓN DE CONSTANTE DE RESORTE Kvs
Para contratrab es de muros de 7.0m de longitud
Longitud de estudio L= 7.00 m
Ancho de la contratrabe B= 0.30 m
Para estructuras de ancho B< 10m, E = 60 Mpa De acuerdo al inciso 9.1 de Mecanica de Suelos de Geotec
L 7.00
Relacion = = 23.33
B 0.30
Factor de Forma para L / B = 23.33 I = 2.46

714.00
Kvs= = 967.48 kPa /cm
0.30 x 2.46

Modulo de reacciòn Kvs = 967.480 kPa/cm = 9872 Ton/m 2 /m

La rigidez de resorte por nudo se obtiene al multiplicar Kvs por el area tributaria que le corresponda
Área Tributaria : 0.70 m² Kv = 6910.10 Ton/m

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 15
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

CAPÍTULO II. Análisis de la estructura.

II.1. Cálculo del centro de masa


CÁLCULO DE CENTRO DE CARGAS EN NIVEL DE AZOTEA Y ENTREPISO. CONSIDERANDO CARGA
VIVA INSTANTÁNEA.

Cargas Puntuales (losa, p.p.estructura) Cargas Distribuidas (muros)

Carga(P) X Z P*X P*Z Carga(w) Long. Carga(P) X Z P*X P*Z


ton m m ton-m ton-m ton/m m ton m m ton-m ton-m
1.- 262.43 14.93 10.50 3918.30 2755.56 4.- 0.23 106.00 24.90 14.49 10.50 360.79 261.44
2.- 90.26 12.50 10.50 1128.20 947.69 5.- 0.54 39.00 20.87 12.50 10.50 260.84 219.10
3.- 357.58 14.01 10.50 5009.72 3754.61

S: 710.27 10056.23 7457.86 45.77 621.63 480.55


Xp = 10056.2 = 14.16 m Xw = 621.6 = 13.58 m
710.3 45.8
Zp = 7457.9 = 10.50 m Zw = 480.5 = 10.50 m
710.3 45.8

Coordenadas de Centro de Gravedad

Xcg = 10677.9 = 14.12 m


756.0
Zcg = 7938.4 = 10.50 m
756.0

1.- Carga de losa maciza de azotea (esp. = 12 cm.), incluyendo carga viva instantánea.
2.- Carga de losa maciza de entrepiso (esp. = 12 cm.), incluyendo carga viva instantánea.
3.- Peso propio de estructura (trabes principales, trabes secundarias y 1/2 columnas).
4.- Peso de pretil perimetral en azotea, h=0.90 m.
5.- 1/2 Peso de muros (Cuarto de aire acondicionado).

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 16
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

CÁLCULO DE CENTRO DE CARGAS EN NIVEL DE AZOTEA CUARTO DE MÁQUINAS.


CONSIDERANDO CARGA VIVA INSTANTÁNEA.

Cargas Puntuales (losa, p.p.estructura) Cargas Distribuidas (muros)

Carga(P) X Z P*X P*Z Carga(w) Long. Carga(P) X Z P*X P*Z


ton m m ton-m ton-m ton/m m ton m m ton-m ton-m
1.- 58.32 12.50 10.50 728.98 612.35 3.- 0.23 39.00 9.16 12.50 10.50 114.51 96.19
2.- 41.76 12.50 10.50 522.01 438.49 4.- 0.54 39.00 20.87 12.50 10.50 260.84 219.10

S: 100.08 1251.00 1050.84 30.03 375.35 315.29


Xp = 1251.0 = 12.50 m Xw = 375.4 = 12.50 m
100.1 30.0
Zp = 1050.8 = 10.50 m Zw = 315.3 = 10.50 m
100.1 30.0

Coordenadas de Centro de Gravedad

Xcg = 1626.3 = 12.50 m


130.1
Zcg = 1366.1 = 10.50 m
130.1

1.- Carga de losa maciza de azotea (esp. = 12 cm.), incluyendo carga viva instantánea.
2.- Peso propio de estructura (trabes principales, trabes secundarias y 1/2 columnas).
3.- Peso de pretil perimetral en azotea h=0.90 m. (Cuarto de aire acondicionado).
4.- 1/2 Peso de muros (Cuarto de aire acondicionado).

II.2. Análisis sísmico estático.


Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 17
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

CÁLCULO DE LAS FUERZAS SÍSMICAS POR EL MÉTODO ESTÁTICO

CÁLCULO DE LAS FUERZAS SÍSMICAS POR EL MÉTODO ESTÁTICO

Nivel W h hi W * hi F V X Z F*X S F*X F*Z S F*Z Xv Zv


T m m T-m T T m m T-m T-m T-m T-m m m

Azotea 130.1 4.80 12.50 1626.35 42.92 42.92 12.50 10.50 536.45 536.45 450.62 450.62 12.50 10.50
N-1 756.0 7.70 7.70 5821.50 153.62 196.53 14.12 10.50 2169.62 2706.07 1612.99 2063.61 13.77 10.50

S 886.15 7447.85

C = 0.207 Coeficiente sísmico


FR = 0.70 Factor de reducción por irregularidad.
Q = 2.00 Factor de ductilidad.
Q' = 1.40 Factor de ductilidad reducido = FR x Q
Grupo A Estructura según su importancia
FI = 1.50 Factor de importancia
Vb = 196.53 Ton Cortante basal

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 18
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

II.3. Cálculo de empuje de reposo.


CÁLCULO DE EMPUJES LATERALES SOBRE MUROS

PARA H= 3.20 M
a) Datos
Altura total del muro 3.20 m
Peso volumétrico del suelo γr = 1.90 ton/m 3

Coeficiente de empuje en reposo K0 = 0.50 (valor dado por estudio de mecánica de suelos)
Sobrecarga considerada q = 1.50 ton/m 2

b) Presión debida al relleno


σa= K 0 Υ r H = 0.50 x 1.90 x 3.20 = 3.04 Ton/m 2

c) Presión debida a la sobrecarga


σa= K 0 q = 0.50 x 1.50 = 0.75 Ton/m 2

Los diagramas de presión y la distribución a las placas del modelo, considerando que
tienen una altura h= 0.53 m, es:
y σ
m Ton/m 2
Relleno Sobrecarga 0.00 0.75
0.53 1.26
1.07 1.76
1.60 2.27
3.20

2.14 2.78
2.67 3.29
1.60
1.07

3.20 3.79

3.04 0.75

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 19
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

II.4. Cálculo de empuje debido al sismo.


Para el cálculo del empuje del terreno que produce el sismo se utilizó el método de Mononobe y Okabe, el cuál se
describe a continuación.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 20
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

PARA H=3.20 M
g= 1.90 ton/m3
H= 3.20 m Hplaca= 0.53 m
f= 32 ángulo de fricción interna del suelo
q= arc tan [ Kh / (1 - Kv ) ] = 8.53
d 0 ángulo de fricción del muro y terraplén
Kh= 0.15
Kv= 0.00 coeficiente de aceleración vertical
i= 0.00 ángulo de la pendiente del relleno con respecto a la horizontal
b= 0.00 pendiente de la cara del muro posterior
 f- q - b   23.47
cos ( f - q - b   0.92
cos 2 ( f - q - b   0.8464
cos q  0.99
cos f  0.85
cos b  1.00
cos 2 b  1.00 K AE= 0.8464 1
( d b  q   8.53 0.9801 2
cos ( d  b  q   0.99 1+ 0.2
( f d   32.00 1
sen ( f  d   0.53
 f- q - i   23.47
sen  f - q - i   0.4 K AE= 0.86 0.47
i-b 0.00
cos  i - b   1.00 K AE= 0.40 ( Coeficiente de presión sísmica activa )
EMPUJE TOTAL4.1
DEBIDO AL EMPUJE ACTIVO MÁS EMPUJE DEBIDO A SISMO
EAE = (1/2 ) g ( H ) 2
( 1- Kv ) KAE.
E AE = 3.89 ton/ml
EMPUJE ACTIVO ESTÁTICO EMPUJE DEBIDO AL SISMO
EA = (1/2 ) g ( H ) 2
( KA ) E AS = E AE - E A.
K A= tan (45 - f /2 )
2
EAS = 0.88 ton/ml
K A= 0.310 y σ

sA = 7.70 Ton/m2 m Ton/m 2

EA = 3.02 ton/ml 0.00 0.00


0.53 1.28
1.07 2.57
1.60 3.85 0.88
3.20

3.20

3.02 2.14 5.14


2.67 6.42
2.1
1.07

3.20 7.71

7.70

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 21
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

CAPÍTULO III. Topología del modelo tridimensional.


En este capítulo se muestran algunas imágenes del modelo tridimensional, para la ubicación y conceptualización de los
elementos estructurales que conforman a la Sub-estación Derivada No. 8.

Figura 6. Isométrico del modelo del edificio (imagen tomada directa del programa STAAD.Pro V8i)

. 43 . 44 . 45

. 50

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 22
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Figura 7. Planta y numeración de nodos donde se localizan las zapatas aisladas

Figura 8. Planta y numeración de nodos donde se localizan las zapatas corridas.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 23
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Figura 9. Isométrico y numeración de dados

Figura 10. Planta y numeración de Contratrabes

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 24
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Figura 11. Planta y numeración de trabes principales y secundarias. Entrepiso

Figura 12. Planta y numeración de trabes principales y secundarias. Cuarto de Aire Acondicionado

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 25
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Figura 13. Planta y numeración de trabes principales y secundarias. Sótano

Figura 14. Isométrico y numeración de columna Nivel 1

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 26
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Figura 15. Isométrico y numeración de columnas Nivel 2

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 27
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

CAPÍTULO IV. Sismo.

IV.1. Cálculo de rigideces.

Figura 16. Ubicación y nomenclatura de marcos para el cálculo de rigideces Nivel 1

Figura 17. Ubicación y nomenclatura de marcos para el cálculo de rigideces Nivel 2

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 28
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

NIVEL 1

MARCOS PARALELOS AL EJE "X" (1, 2, 3, 4, 5)

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN X (EJE 1)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS

T/Cm
Cm

T
19 6 0.078 0.000 0.000
20 6 0.065 0.021 0.000

RIGIDEZ 604.218
21 6 0.067 -0.022 -0.003

D PROM 0.081
22 6 0.092 0.000 -0.002

FUERZA 48.7
23 6 0.101 0.000 0.000

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN X (EJE 2)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS

T/Cm
Cm
24 7 0.685 0.002 -0.003 T
25 7 0.684 -0.003 -0.069
26 7 0.684 0.000 -0.010 RIGIDEZ 71.157
D PROM 0.684

27 7 0.684 0.003 0.046


FUERZA 48.7

28 7 0.685 -0.002 0.003

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN X (EJE 3)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS
T/Cm
Cm

29 8 0.082 0.001 0.000


30 8 0.068 0.021 -0.003
RIGIDEZ 611.809

31 8 0.066 -0.023 -0.012


D PROM 0.080

32 8 0.086 -0.001 -0.009


FUERZA 48.7

33 8 0.096 0.000 0.000

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 29
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN X (EJE 4)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS

T/Cm
Cm
T
34 9 1.040 0.006 0.043

RIGIDEZ 28.168
D PROM 1.037

FUERZA 29.22
35 9 1.040 0.000 -0.065
36 9 1.032 -0.006 0.002

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN X (EJE 5)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS

RIGIDEZ 590.303 T/Cm


Cm
T
D PROM 0.033

FUERZA 19.48
56 10 0.033 0.012 0.003
58 10 0.033 -0.012 0.000

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN Z (EJE A)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS
T/Cm
Cm
T

23 1 0.000 0.020 0.051


28 1 0.005 -0.021 0.064
RIGIDEZ 545.964

33 1 0.000 0.000 0.101


D PROM 0.089

36 1 0.002 0.000 0.123


FUERZA 48.7

58 1 -0.001 0.000 0.107

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 30
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN Z (EJE B)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS

T/Cm
Cm
T
22 2 -0.004 0.003 0.842
27 2 0.046 -0.002 0.840
32 2 -0.009 0.001 0.840

RIGIDEZ 59.159
D PROM 0.823
35 2 -0.104 0.000 0.845

FUERZA 48.7
56 2 0.006 0.001 0.749

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN Z (EJE C)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS

T/Cm
Cm
T
21 3 -0.002 0.002 0.847
26 4 -0.008 -0.002 0.856
RIGIDEZ 44.859
D PROM 0.869

FUERZA 38.96

31 5 -0.009 0.004 0.878


34 3 0.054 -0.005 0.893

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN Z (EJE D)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS
T/Cm
Cm
T

20 4 0.001 0.001 0.697


RIGIDEZ 42.043
D PROM 0.695

FUERZA 29.22

25 4 -0.042 -0.001 0.695


30 4 -0.002 -0.001 0.693

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 31
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN Z (EJE E)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS

T/Cm
Cm
T
RIGIDEZ 701.280
19 5 0.000 0.013 0.033

D PROM 0.042

FUERZA 29.22
24 5 -0.002 -0.013 0.039
29 5 0.000 -0.001 0.053

NIVEL 2

MARCOS PARALELOS AL EJE "X" (2, 3)

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN X (EJE 2)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS

T/Cm
Cm
T
61 14 0.429 0.006 -0.150
RIGIDEZ 63.624
D PROM 0.428

FUERZA 27.21

62 14 0.424 0.000 -0.011


63 14 0.430 -0.006 0.118

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN X (EJE 3)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS
T/Cm
Cm
T

64 15 0.410 0.019 0.056


RIGIDEZ 67.075
D PROM 0.406

FUERZA 27.21

65 15 0.406 -0.016 0.001


66 15 0.401 -0.007 -0.055

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 32
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

MARCOS PARALELOS AL EJE "Z" (B, C, D)

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN Z (EJE B)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS

RIGIDEZ 36.945 T/Cm


Cm
T
D PROM 0.491

FUERZA 18.14
63 11 0.079 0.007 0.490
66 11 -0.037 -0.007 0.492

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN Z (EJE C)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS

RIGIDEZ 45.693 T/Cm


Cm
T
D PROM 0.397

FUERZA 18.14
62 12 -0.007 0.006 0.397
65 12 0.000 -0.002 0.397

DESPLAZAMIENTOS PARA CALCULO DE RIGIDEZ EN Z (EJE D)


JOINT LOAD X-TRANS Y-TRANS Z-TRANS
RIGIDEZ 35.053 T/Cm
Cm
T
D PROM 0.518

FUERZA 18.14

61 13 -0.100 0.007 0.519


64 13 0.038 -0.005 0.516

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 33
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

IV.2. Distribución de fuerzas sísmicas.

SISMO DIRECCIÓN X1
NIVEL AZOTEA

CÁLCULO DE EXCENTRICIDADES ACCIDENTALES


X Z
Coordenadas del centro de cargas: 12.50 10.50
Coordenadas del centro de rigidez: 12.60 10.59
Excentricidad calculada : 0.10 m 0.09 m

Las excentricidades de diseño para cada dirección seran:

esx calc . = 0.10 m edx1. = 0.85 m edx2. = -0.60 m


esz calc . = 0.09 m edz1. = -1.11 m edz2. = 1.34 m

DISTRIBUCIÓN DE DIRECCIÓN X

Fx = 42.92 T edz1. = -1.11 m M= -47.70 T-m


Centro de Torsión Efectos de Vz
EJE Rix Zi Rix Zi Zit Rix Zit Rix Zit² Directo Torsión Total
T/m m T m T T-m T T T

2 6362 7.00 44537.0 -3.59 -22856.4 82109.3 20.892 2.472


3 6707 14.00 93904.7 3.41 22856.4 77885.5 22.025 -2.472

S  13069.91 138441.7 159994.8 42.92 0.000

Zct = 138441.7 = 10.59 m


13069.9

Tabla 1 Distribución de dirección X SX1 Nivel Azotea

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 34
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO
DISTRIBUCIÓN DE DIRECCIÓN Z

Fx = 42.92 T edz1. = -1.11 m M= -47.70 T-m


Centro de Torsión Efectos de Vx
EJE Riz Xi Riz Xi Xit Riz Xit Riz Xit² Directo Torsión Total
T/ m m T m T T-m T T T

B 3695 18.75 69271.9 6.15 22719.5 139714.0 -2.457


C 4569 12.50 57115.9 -0.10 -459.1 46.1 0.050
D 3505 6.25 21908.2 -6.35 -22260.4 141363.9 2.407

S  11769.08 148296.0 281124.0 0.000

Xct = 148296 = 12.60 m


11769.08

Tabla 2 Distribución de dirección Z SX1 Nivel Azotea

NIVEL ENTREPISO

CÁLCULO DE EXCENTRICIDADES ACCIDENTALES


X Z
Coordenadas del centro de cargas: 13.77 10.50
Coordenadas del centro de rigidez: 11.18 13.74
Excentricidad calculada : 2.59 m 3.24 m

Las excentricidades de diseño para cada dirección seran:

esx calc . = 2.59 m edx1. = 6.68 m edx2. = -0.21 m


esz calc . = 3.24 m edz1. = 2.36 m edz2. = 5.74 m

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 35
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Fx = 153.62 T edz1. = 2.36 m M= 362.51 T-m


Centro de Torsión Efectos de Vz
EJE Rix Zi Rix Zi Zit Rix Zit Rix Zit² Directo Torsión Total
T/m m T m T T-m T T T

1 60422 0.00 0.0 -13.74 -830187.6 11406661.74 48.71 -6.914


2 7116 7.00 49810.1 -6.74 -47959.0 323236.78 5.74 -0.399
3 61181 14.00 856532.7 0.26 15915.6 4140.27 49.32 0.133
4 2817 21.00 59153.6 7.26 20450.6 148474.48 2.27 0.170
5 59030 28.00 1652848.5 14.26 841780.4 12003905.39 47.59 7.010

S 190565.60 2618344.8 23886418.7 153.62 0.000

Zct = 2618344.8 = 13.74 m


190565.6

Tabla 3 Distribución de dirección X SX1 Nivel Entrepiso

Fx = 153.62 T edz1. = 2.36 m M = 362.51 T-m


Centro de Torsión Efectos de Vx
EJE Riz Xi Riz Xi Xit Riz Xit Riz Xit² Directo Torsión Total
T/ m m T m T T-m T T T

A 54596 25.00 1364910.3 13.82 754338.6 10422419.5 6.282


B 5916 18.75 110923.8 7.57 44763.7 338710.7 0.373
C 4486 12.50 56073.7 1.32 5906.3 7776.4 0.049
D 4204 6.25 26277.0 -4.93 -20741.4 102325.1 -0.173
E 70128 0.00 0.0 -11.18 -784267.2 8770747.6 -6.531

S 139330.56 1558184.8 19641979.3 0.000

Xct = 1558184.816 = 11.18 m


139330.5621

Tabla 4 Distribución de dirección Z SX1 Nivel Entrepiso

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 36
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

SISMO DIRECCIÓN X3
NIVEL AZOTEA

CÁLCULO DE EXCENTRICIDADES ACCIDENTALES

X Z
Coordenadas del centro de cargas: 12.50 10.50
Coordenadas del centro de rigidez: 12.60 10.59
Excentricidad calculada : 0.10 m 0.09 m

Las excentricidades de diseño para cada dirección seran:

esx calc . = 0.10 m edx1. = 0.85 m edx2. = -0.60 m


esz calc . = 0.09 m edz1. = -1.11 m edz2. = 1.34 m

Fx = 42.92 T edz2. = 1.34 m M= 57.61 T-m


Centro de Torsión Efectos de Vz
EJE Rix Zi Rix Zi Zit Rix Zit Rix Zit² Directo Torsión Total
T/ m m T m T T-m T T T

2 6362 7.0 44537.0 -3.59 -22856.4 82109.3 20.892 -2.985


3 6707 14.0 93904.7 3.41 22856.4 77885.5 22.025 2.985

S 13069.91 138441.7 159994.8 42.92 0.000

Xct = 138441.7 = 10.59 m


13069.9

Tabla 5 Distribución de dirección X SX3 Nivel Azotea

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 37
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Fx = 42.92 T edz2. = 1.34 m M= 57.61 T-m


Centro de Torsión Efectos de Vz
EJE Rix Zi Rix Zi Zit Rix Zit Rix Zit² Directo Torsión Total
T/ m m T m T T-m T T T

B 3695 18.75 69271.9 6.15 22719.5 139714.0 2.967


C 4569 12.50 57115.9 -0.10 -459.1 46.1 -0.060
D 3505 6.25 21908.2 -6.35 -22260.4 141363.9 -2.907

S 11769.08 148296.0 281124.0 0.000

Zct = 148296 = 12.60 m


11769.08

Tabla 6 Distribución de dirección Z SX3 Nivel Azotea

NIVEL ENTREPISO

CÁLCULO DE EXCENTRICIDADES ACCIDENTALES

X Z
Coordenadas del centro de cargas: 13.77 10.50
Coordenadas del centro de rigidez: 11.18 13.74
Excentricidad calculada : 2.59 m 3.24 m

Las excentricidades de diseño para cada dirección seran:

esx calc . = 2.59 m edx1. = 6.68 m edx2. = -0.21 m


esz calc . = 3.24 m edz1. = 2.36 m edz2. = 5.74 m

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 38
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Fx = 153.62 T edz2. = 5.74 m M = 881.748 T-m


Centro de Torsión Efectos de Vz
EJE Rix Zi Rix Zi Zit Rix Zit Rix Zit² Directo Torsión Total
T/ m m T m T T-m T T T

1 60422 0.0 0.0 -13.74 -830187.6 11406661.7 48.707 -16.817


2 7116 7.0 49810.1 -6.74 -47959.0 323236.8 5.736 -0.971
3 61181 14.0 856532.7 0.26 15915.6 4140.3 49.319 0.322
4 2817 21.0 59153.6 7.26 20450.6 148474.5 2.271 0.414
5 59030 28.0 1652848.5 14.26 841780.4 12003905.4 47.585 17.052

S 190565.60 2618344.8 23886418.7 153.62 0.000

Xct = 2618344.8 = 13.74 m


190565.6

Tabla 7 Distribución de dirección X SX3 Nivel Entrepiso

Fx = 153.62 T edz2. = 5.74 m M = 881.748 T-m


Centro de Torsión Efectos de Vx
EJE Riz Xi Riz Xi Xit Riz Xit Riz Xit² Directo Torsión Total
T/ m m T m T T-m T T T

A 54596 25.00 1364910.3 13.82 754338.6 10422419.5 15.281


B 5916 18.75 110923.8 7.57 44763.7 338710.7 0.907
C 4486 12.50 56073.7 1.32 5906.3 7776.4 0.120
D 4204 6.25 26277.0 -4.93 -20741.4 102325.1 -0.420
E 70128 0.00 0.0 -11.18 -784267.2 8770747.6 -15.887

S 139330.56 1558184.8 19641979.3 0.000

Zct = 1558184.816 = 11.18 m


139330.5621

Tabla 8 Distribución de dirección Z SX3 Nivel Entrepiso

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 39
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

SISMO DIRECCIÓN Z1
NIVEL AZOTEA

CÁLCULO DE EXCENTRICIDADES ACCIDENTALES

X Z
Coordenadas del centro de cargas: 12.50 10.50
Coordenadas del centro de rigidez: 12.60 10.59
Excentricidad calculada : 0.10 m 0.09 m

Las excentricidades de diseño para cada dirección seran:

esx calc . = 0.10 m edx1. = 0.85 m edx2. = -0.60 m


esz calc . = 0.09 m edz1. = -1.11 m edz2. = 1.34 m

Fz = 42.92 T edx1. = 0.851 m M= 36.51 T-m


Centro de Torsión Efectos de Vz
EJE Riz Xi Riz Xi Xit Riz Xit Riz Xit² Directo Torsión Total
T/ m m T m T T-m T T T

2 6362 7.00 44537.0 -3.59 -22856.4 82109.3 -1.892


3 6707 14.00 93904.7 3.41 22856.4 77885.5 1.892

S 13069.91 138441.7 159994.8 0.000

Xct = 138441.7 = 10.59 m


13069.9

Tabla 9 Distribución de dirección X SZ1 Nivel Azotea

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 40
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Fz = 42.92 T edx1. = 0.85 m M= 36.51 T-m


Centro de Torsión Efectos de Vx
EJE Rix Zi Rix Zi Zit Rix Zit Rix Zit² Directo Torsión Total
T/ m m T m T T-m T T T

B 3695 18.8 69271.9 6.15 22719.5 139714.0 13.472 1.880


C 4569 12.5 57115.9 -0.10 -459.1 46.1 16.662 -0.038
D 3505 6.3 21908.2 -6.35 -22260.4 141363.9 12.782 -1.842

S 11769.08 148296.0 281124.0 42.92 0.000

Zct = 148296 = 12.60 m


11769.08

Tabla 10 Distribución de dirección Z SZ1 Nivel Azotea

NIVEL ENTREPISO

CÁLCULO DE EXCENTRICIDADES ACCIDENTALES

X Z
Coordenadas del centro de cargas: 13.77 10.50
Coordenadas del centro de rigidez: 11.18 13.74
Excentricidad calculada : 2.59 m 3.24 m

Las excentricidades de diseño para cada dirección seran:

esx calc . = 2.59 m edx1. = 6.68 m edx2. = -0.21 m


esz calc . = 3.24 m edz1. = 2.36 m edz2. = 5.74 m

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 41
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Fz = 153.62 T edx1. = 6.68 m M = 1025.92 T-m


Centro de Torsión Efectos de Vz
EJE Riz Xi Riz Xi Xit Riz Xit Riz Xit² Directo Torsión Total
T/ m m T m T T-m T T T

1 60422 0.0 0.0 -13.74 -830187.6 11406661.7 -19.567


2 7116 7.0 49810.1 -6.74 -47959.0 323236.8 -1.130
3 61181 14.0 856532.7 0.26 15915.6 4140.3 0.375
4 2817 21.0 59153.6 7.26 20450.6 148474.5 0.482
5 59030 28.0 1652848.5 14.26 841780.4 12003905.4 19.840

S 190565.60 2618344.8 23886418.7 0.000

Xct = 2618344.8 = 13.74 m


190565.6

Tabla 11 Distribución de dirección X SZ1 Nivel Entrepiso

Fz = 153.62 T edx1. = 6.68 m M = 1025.92 T-m


Centro de Torsión Efectos de Vx
EJE Rix Zi Rix Zi Zit Rix Zit Rix Zit² Directo Torsión Total
T/ m m T m T T-m T T T

A 54596 25.0 1364910.3 13.82 754338.6 10422419.5 60.195 17.779


B 5916 18.8 110923.8 7.57 44763.7 338710.7 6.523 1.055
C 4486 12.5 56073.7 1.32 5906.3 7776.4 4.946 0.139
D 4204 6.3 26277.0 -4.93 -20741.4 102325.1 4.635 -0.489
E 70128 0.0 0.0 -11.18 -784267.2 8770747.6 77.319 -18.484

S 139330.56 1558184.8 19641979.3 153.62 0.000

Zct = 1558184.8 = 11.18 m


139330.56

Tabla 12 Distribución de dirección Z SZ1 Nivel Entrepiso

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 42
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

SISMO DIRECCIÓN Z3
NIVEL AZOTEA

CÁLCULO DE EXCENTRICIDADES ACCIDENTALES

X Z
Coordenadas del centro de cargas: 12.50 10.50
Coordenadas del centro de rigidez: 12.60 10.59
Excentricidad calculada : 0.10 m 0.09 m

Las excentricidades de diseño para cada dirección seran:

esx calc . = 0.10 m edx1. = 0.85 m edx2. = -0.60 m


esz calc . = 0.09 m edz1. = -1.11 m edz2. = 1.34 m

Fz = 42.92 T edx2. = -0.60 m M = -25.7297 T-m


Centro de Torsión Efectos de Vz
EJE Riz Xi Riz Xi Xit Riz Xit Riz Xit² Directo Torsión Total
T/ m m T m T T-m T T T

2 6362 7.00 44537.0 -3.59 -22856.4 82109.3 1.333


3 6707 14.00 93904.7 3.41 22856.4 77885.5 -1.333

S 13069.91 138441.7 159994.8 0.000

Xct = 138441.7 = 10.59 m


13069.9

Tabla 13 Distribución de dirección X SZ3 Nivel Azotea

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 43
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Fx = 42.92 T edx2. = -0.60 m M = -25.7297 T-m


Centro de Torsión Efectos de Vx
EJE Rix Zi Rix Zi Zit Rix Zit Rix Zit² Directo Torsión Total
T/ m m T m T T-m T T T

B 3695 18.75 69271.9 6.15 22719.5 139714.0 13.472 -1.325


C 4569 12.50 57115.9 -0.10 -459.1 46.1 16.662 0.027
D 3505 6.25 21908.2 -6.35 -22260.4 141363.9 12.782 1.298

S 11769.08 148296.0 281124.0 42.92 0.000

Zct = 148296 = 12.60 m


11769.08

Tabla 14 Distribución de dirección Z SZ3 Nivel Azotea

NIVEL ENTREPISO

CÁLCULO DE EXCENTRICIDADES ACCIDENTALES

X Z
Coordenadas del centro de cargas: 13.77 10.50
Coordenadas del centro de rigidez: 11.18 13.74
Excentricidad calculada : 2.59 m 3.24 m

Las excentricidades de diseño para cada dirección seran:

esx calc . = 2.59 m edx1. = 6.68 m edx2. = -0.21 m


esz calc . = 3.24 m edz1. = 2.36 m edz2. = 5.74 m

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 44
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Fz = 153.62 T edx2. = -0.21 m M= -32.942 T-m


Centro de Torsión Efectos de Vz
EJE Riz Xi Riz Xi Xit Riz Xit Riz Xit² Directo Torsión Total
T/ m m T m T T-m T T T

1 60422 0.0 0.0 -13.74 -830187.6 11406661.7 0.628


2 7116 7.0 49810.1 -6.74 -47959.0 323236.8 0.036
3 61181 14.0 856532.7 0.26 15915.6 4140.3 -0.012
4 2817 21.0 59153.6 7.26 20450.6 148474.5 -0.015
5 59030 28.0 1652848.5 14.26 841780.4 12003905.4 -0.637

S 190565.60 2618344.8 23886418.7 0.000

Xct = 2618344.8 = 13.74 m


190565.6

Tabla 15 Distribución de dirección X SZ3 Nivel Entrepiso

Fx = 153.62 T edx2. = -0.21 m M = -32.942 T-m


Centro de Torsión Efectos de Vx
EJE Rix Zi Rix Zi Zit Rix Zit Rix Zit² Directo Torsión Total
T/ m m T m T T-m T T T

A 54596 25.00 1364910.3 13.82 754338.6 10422419.5 60.195 -0.571


B 5916 18.75 110923.8 7.57 44763.7 338710.7 6.523 -0.034
C 4486 12.50 56073.7 1.32 5906.3 7776.4 4.946 -0.004
D 4204 6.25 26277.0 -4.93 -20741.4 102325.1 4.635 0.016
E 70128 0.00 0.0 -11.18 -784267.2 8770747.6 77.319 0.594

S 139330.56 1558184.8 19641979.3 153.62 0.000

Zct = 1558184.8 = 11.18 m


139330.56

Tabla 16 Distribución de dirección Z SZ3 Nivel Entrepiso

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 45
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

CAPÍTULO V. Análisis de resultados.

V.1. Revisión de desplazamientos.

Figura 18. Numeración de nodos para revisión de desplazamientos horizontales Nivel 1.

Figura 19. Numeración de nodos para revisión de desplazamientos horizontales Nivel 2.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 46
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

La revisión de los desplazamientos permisibles se realizará restando los desplazamientos de los nodos
inferiores a los nodos superiores (desplazamientos relativos), estos datos se obtienen directamente del
programa STAAD Pro.V8i. El resultado obtenido se multiplicará por el factor de reducción Q’ y se revisará, que
éste, sea menor al desplazamiento permisible d=h x Q’, donde h es la altura del entrepiso analizado.

REVISIÓN DE DESPLAZAMIENTOS PERMISIBLES PARA EL NIVEL 1

Altura de entrepiso
7.70 h =m Q' = 1.4
Desplazamiento permisible es δ=h x 0.006 δ= 4.62 cm

Los desplazamientos deben ser revisados con respecto al nodo inferior (desplazamiento del nodo superior respecto al nodo
inferior).

NODOS SUPERIORES NODOS INFERIORES DESPLAZAMIENTO COMPARACIÓN


Node L/C X-Trans cm Y-Trans Z-Trans cmNode L/C X-Trans cm Y-Trans Z-Trans cm X * Q' Z * Q' X Z
19 200 -0.006 -0.011 0.004 1 200 -0.001 -0.004 -0.001 0.007 0.004 OK OK
201 -0.006 -0.010 0.005 201 0.002 -0.003 0.001 0.006 0.006 OK OK
202 0.126 -0.003 0.024 202 0.006 -0.001 0.003 0.168 0.029 OK OK
203 0.101 -0.024 -0.037 203 0.003 -0.007 -0.004 0.137 0.046 OK OK
204 0.114 0.000 0.033 204 0.007 0.000 0.004 0.150 0.041 OK OK
205 0.113 -0.027 -0.046 205 0.003 -0.008 -0.005 0.154 0.057 OK OK
206 -0.113 0.003 0.047 206 0.001 0.000 0.005 0.157 0.059 OK OK
207 -0.138 -0.018 -0.014 207 -0.002 -0.006 -0.001 0.190 0.018 OK OK
208 -0.125 0.007 0.056 208 0.002 0.001 0.006 0.172 0.070 OK OK
209 -0.126 -0.021 -0.023 209 -0.002 -0.007 -0.002 0.174 0.029 OK OK
210 0.080 0.009 0.061 210 0.007 0.003 0.007 0.102 0.076 OK OK
211 0.055 -0.011 0.000 211 0.004 -0.003 0.001 0.071 -0.001 OK OK
212 0.068 0.013 0.070 212 0.008 0.004 0.008 0.084 0.087 OK OK
213 0.067 -0.015 -0.009 213 0.004 -0.004 0.000 0.088 0.013 OK OK
214 -0.068 -0.009 0.010 214 0.000 -0.003 0.000 0.095 0.014 OK OK
215 -0.092 -0.030 -0.051 215 -0.003 -0.009 -0.006 0.125 0.063 OK OK
216 -0.079 -0.006 0.019 216 0.001 -0.002 0.001 0.109 0.025 OK OK
217 -0.081 -0.033 -0.060 217 -0.003 -0.010 -0.007 0.109 0.074 OK OK
218 0.071 0.025 0.107 218 0.007 0.007 0.015 0.090 0.129 OK OK
219 0.001 0.027 0.114 219 0.008 0.008 0.016 -0.010 0.137 OK OK
220 0.057 0.029 0.118 220 0.008 0.008 0.016 0.069 0.143 OK OK
221 0.015 0.023 0.103 221 0.008 0.007 0.014 0.010 0.125 OK OK
222 -0.013 -0.047 -0.103 222 -0.006 -0.014 -0.013 0.010 0.126 OK OK
223 -0.083 -0.045 -0.096 223 -0.005 -0.014 -0.012 0.109 0.118 OK OK
224 -0.027 -0.044 -0.092 224 -0.005 -0.013 -0.011 0.031 0.113 OK OK
225 -0.069 -0.049 -0.107 225 -0.005 -0.015 -0.013 0.090 0.132 OK OK
226 0.033 0.035 0.138 226 0.008 0.010 0.018 0.035 0.168 OK OK
227 -0.037 0.037 0.145 227 0.009 0.011 0.019 0.039 0.176 OK OK
228 0.019 0.039 0.149 228 0.009 0.011 0.020 0.014 0.181 OK OK
229 -0.024 0.034 0.134 229 0.009 0.010 0.018 0.021 0.162 OK OK
230 0.025 -0.058 -0.135 230 -0.006 -0.017 -0.017 0.027 0.165 OK OK
231 -0.045 -0.056 -0.127 231 -0.006 -0.017 -0.016 0.055 0.155 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 47
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

232 0.012 -0.054 -0.124 232 -0.006 -0.016 -0.015 0.008 0.153 OK OK
233 -0.031 -0.059 -0.138 233 -0.006 -0.018 -0.017 0.035 0.169 OK OK
23 200 -0.004 -0.010 0.005 5 200 0.001 -0.004 0.000 0.004 0.007 OK OK
201 -0.004 -0.010 0.007 201 -0.002 -0.004 0.002 0.003 0.007 OK OK
202 0.159 0.006 0.055 202 -0.002 0.002 0.008 0.220 0.066 OK OK
203 0.136 -0.018 -0.016 203 0.002 -0.008 -0.003 0.188 0.018 OK OK
204 0.144 0.003 0.047 204 -0.002 0.001 0.007 0.199 0.056 OK OK
205 0.150 -0.015 -0.008 205 0.002 -0.007 -0.001 0.207 0.010 OK OK
206 -0.143 0.000 0.035 206 -0.008 0.000 0.005 0.189 0.042 OK OK
207 -0.166 -0.023 -0.036 207 -0.003 -0.010 -0.005 0.228 0.043 OK OK
208 -0.158 -0.003 0.027 208 -0.007 -0.001 0.004 0.211 0.032 OK OK
209 -0.152 -0.021 -0.028 209 -0.004 -0.009 -0.004 0.207 0.034 OK OK
210 0.101 -0.005 0.023 210 -0.001 -0.002 0.003 0.140 0.028 OK OK
211 0.078 -0.028 -0.048 211 0.004 -0.012 -0.008 0.104 0.056 OK OK
212 0.086 -0.007 0.015 212 -0.001 -0.003 0.002 0.119 0.018 OK OK
213 0.092 -0.025 -0.040 213 0.003 -0.011 -0.007 0.125 0.046 OK OK
214 -0.085 0.010 0.067 214 -0.009 0.004 0.011 0.106 0.078 OK OK
215 -0.108 -0.013 -0.004 215 -0.004 -0.005 0.000 0.146 0.006 OK OK
216 -0.100 0.008 0.059 216 -0.009 0.003 0.009 0.127 0.070 OK OK
217 -0.094 -0.010 0.004 217 -0.005 -0.004 0.001 0.125 0.004 OK OK
218 0.077 0.032 0.136 218 -0.010 0.013 0.024 0.094 0.157 OK OK
219 -0.012 0.030 0.130 219 -0.009 0.012 0.023 0.004 0.150 OK OK
220 0.060 0.029 0.127 220 -0.010 0.012 0.022 0.070 0.147 OK OK
221 0.006 0.033 0.139 221 -0.010 0.014 0.024 -0.006 0.161 OK OK
222 0.003 -0.048 -0.109 222 0.006 -0.020 -0.018 -0.004 0.127 OK OK
223 -0.085 -0.050 -0.116 223 0.007 -0.021 -0.019 0.109 0.136 OK OK
224 -0.014 -0.051 -0.119 224 0.007 -0.021 -0.020 0.010 0.139 OK OK
225 -0.068 -0.046 -0.106 225 0.007 -0.020 -0.018 0.085 0.123 OK OK
226 0.029 0.023 0.110 226 -0.009 0.010 0.020 0.028 0.126 OK OK
227 -0.060 0.022 0.103 227 -0.008 0.009 0.018 0.073 0.119 OK OK
228 0.011 0.020 0.100 228 -0.009 0.008 0.018 0.003 0.115 OK OK
229 -0.043 0.025 0.113 229 -0.009 0.010 0.020 0.048 0.130 OK OK
230 0.052 -0.039 -0.083 230 0.005 -0.017 -0.014 0.066 0.097 OK OK
231 -0.037 -0.041 -0.090 231 0.006 -0.018 -0.015 0.043 0.105 OK OK
232 0.034 -0.042 -0.093 232 0.006 -0.018 -0.016 0.039 0.108 OK OK
233 -0.020 -0.038 -0.080 233 0.006 -0.016 -0.013 0.020 0.094 OK OK
29 200 0.015 -0.019 0.006 11 200 -0.002 -0.005 0.003 0.018 0.004 OK OK
201 0.014 -0.019 0.007 201 -0.001 -0.005 0.002 0.018 0.007 OK OK
202 0.158 -0.016 0.028 202 0.005 -0.004 0.001 0.214 0.038 OK OK
203 0.165 -0.015 -0.053 203 0.005 -0.004 0.000 0.224 0.074 OK OK
204 0.159 -0.016 0.041 204 0.005 -0.004 0.001 0.216 0.056 OK OK
205 0.164 -0.015 -0.066 205 0.005 -0.004 0.000 0.223 0.092 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 48
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

206 -0.139 -0.022 0.066 206 -0.006 -0.006 0.003 0.186 0.088 OK OK
207 -0.132 -0.021 -0.015 207 -0.006 -0.006 0.003 0.176 0.017 OK OK
208 -0.139 -0.022 0.079 208 -0.006 -0.006 0.004 0.186 0.105 OK OK
209 -0.133 -0.021 -0.028 209 -0.006 -0.006 0.003 0.178 0.035 OK OK
210 0.163 -0.017 0.079 210 0.005 -0.004 0.002 0.221 0.108 OK OK
211 0.170 -0.016 -0.002 211 0.005 -0.004 0.002 0.231 0.000 OK OK
212 0.164 -0.017 0.092 212 0.005 -0.004 0.002 0.223 0.126 OK OK
213 0.170 -0.016 -0.015 213 0.005 -0.004 0.001 0.231 0.020 OK OK
214 -0.145 -0.021 0.015 214 -0.006 -0.006 0.002 0.195 0.018 OK OK
215 -0.138 -0.020 -0.066 215 -0.006 -0.006 0.002 0.185 0.090 OK OK
216 -0.144 -0.021 0.028 216 -0.006 -0.006 0.002 0.193 0.036 OK OK
217 -0.139 -0.020 -0.079 217 -0.006 -0.006 0.001 0.186 0.109 OK OK
218 0.040 -0.020 0.141 218 -0.002 -0.006 0.005 0.053 0.190 OK OK
219 -0.045 -0.021 0.153 219 -0.003 -0.006 0.006 0.059 0.206 OK OK
220 0.041 -0.020 0.157 220 -0.002 -0.006 0.006 0.055 0.211 OK OK
221 -0.046 -0.021 0.137 221 -0.003 -0.006 0.005 0.060 0.185 OK OK
222 0.071 -0.016 -0.139 222 0.001 -0.004 -0.004 0.098 0.189 OK OK
223 -0.014 -0.017 -0.128 223 -0.001 -0.004 -0.003 0.018 0.175 OK OK
224 0.072 -0.016 -0.124 224 0.001 -0.004 -0.003 0.099 0.169 OK OK
225 -0.015 -0.017 -0.143 225 -0.001 -0.004 -0.004 0.020 0.195 OK OK
226 0.043 -0.020 0.184 226 -0.002 -0.006 0.006 0.057 0.249 OK OK
227 -0.041 -0.021 0.195 227 -0.003 -0.006 0.007 0.053 0.263 OK OK
228 0.044 -0.020 0.199 228 -0.002 -0.006 0.007 0.059 0.269 OK OK
229 -0.043 -0.021 0.180 229 -0.003 -0.006 0.006 0.056 0.244 OK OK
230 0.067 -0.016 -0.182 230 0.001 -0.004 -0.005 0.092 0.248 OK OK
231 -0.017 -0.017 -0.170 231 -0.001 -0.004 -0.004 0.022 0.232 OK OK
232 0.069 -0.016 -0.166 232 0.001 -0.004 -0.004 0.095 0.227 OK OK
233 -0.018 -0.017 -0.186 233 -0.001 -0.004 -0.005 0.024 0.253 OK OK
31 200 0.025 -0.053 -0.002 13 200 0.004 -0.015 -0.010 0.029 -0.011 OK OK
201 0.025 -0.052 0.009 201 0.003 -0.015 -0.009 0.031 0.000 OK OK
202 0.162 -0.093 0.256 202 0.023 -0.029 -0.014 0.195 0.339 OK OK
203 0.168 -0.094 -0.290 203 0.023 -0.030 -0.020 0.203 0.378 OK OK
204 0.164 -0.094 0.257 204 0.023 -0.030 -0.014 0.197 0.340 OK OK
205 0.166 -0.093 -0.292 205 0.023 -0.030 -0.020 0.200 0.381 OK OK
206 -0.122 -0.007 0.307 206 -0.018 0.002 0.003 0.146 0.426 OK OK
207 -0.117 -0.007 -0.240 207 -0.017 0.001 -0.003 0.140 0.332 OK OK
208 -0.121 -0.007 0.308 208 -0.018 0.002 0.003 0.144 0.427 OK OK
209 -0.118 -0.007 -0.241 209 -0.018 0.001 -0.003 0.140 0.333 OK OK
210 0.169 -0.096 0.264 210 0.023 -0.030 -0.014 0.204 0.350 OK OK
211 0.174 -0.096 -0.283 211 0.024 -0.031 -0.020 0.210 0.368 OK OK
212 0.171 -0.096 0.265 212 0.023 -0.030 -0.014 0.207 0.351 OK OK
213 0.173 -0.096 -0.284 213 0.024 -0.031 -0.020 0.209 0.370 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 49
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

214 -0.129 -0.004 0.299 214 -0.019 0.003 0.003 0.154 0.414 OK OK
215 -0.124 -0.005 -0.248 215 -0.018 0.002 -0.003 0.148 0.343 OK OK
216 -0.128 -0.005 0.300 216 -0.019 0.003 0.003 0.153 0.416 OK OK
217 -0.125 -0.004 -0.249 217 -0.018 0.002 -0.003 0.150 0.344 OK OK
218 0.052 -0.060 1.017 218 0.005 -0.015 0.015 0.066 1.403 OK OK
219 -0.029 -0.035 1.031 219 -0.003 -0.006 0.020 0.036 1.415 OK OK
220 0.054 -0.061 1.019 220 0.005 -0.015 0.015 0.069 1.406 OK OK
221 -0.031 -0.035 1.029 221 -0.003 -0.006 0.020 0.039 1.413 OK OK
222 0.074 -0.065 -1.003 222 0.008 -0.022 -0.036 0.092 1.354 OK OK
223 -0.006 -0.040 -0.988 223 0.001 -0.013 -0.031 0.007 1.340 OK OK
224 0.077 -0.066 -1.000 224 0.009 -0.022 -0.036 0.095 1.350 OK OK
225 -0.008 -0.039 -0.990 225 0.001 -0.013 -0.031 0.010 1.343 OK OK
226 0.056 -0.062 1.021 226 0.005 -0.015 0.015 0.071 1.408 OK OK
227 -0.024 -0.037 1.035 227 -0.002 -0.006 0.020 0.031 1.421 OK OK
228 0.058 -0.062 1.023 228 0.006 -0.016 0.015 0.073 1.411 OK OK
229 -0.027 -0.036 1.033 229 -0.002 -0.006 0.020 0.035 1.418 OK OK
230 0.070 -0.063 -1.007 230 0.008 -0.022 -0.036 0.087 1.359 OK OK
231 -0.010 -0.039 -0.992 231 0.000 -0.013 -0.031 0.014 1.345 OK OK
232 0.072 -0.064 -1.004 232 0.008 -0.022 -0.036 0.090 1.355 OK OK
233 -0.012 -0.038 -0.994 233 0.000 -0.013 -0.031 0.017 1.348 OK OK
34 200 0.003 -0.017 -0.004 16 200 -0.002 -0.005 0.002 0.001 0.003 OK OK
201 0.003 -0.017 0.007 201 -0.001 -0.004 0.001 0.003 0.008 OK OK
202 0.118 -0.017 0.253 202 0.002 -0.004 0.002 0.162 0.351 OK OK
203 0.131 -0.014 -0.291 203 0.003 -0.003 -0.004 0.179 0.402 OK OK
204 0.131 -0.017 0.255 204 0.002 -0.004 0.002 0.181 0.354 OK OK
205 0.117 -0.014 -0.292 205 0.002 -0.003 -0.004 0.161 0.403 OK OK
206 -0.126 -0.019 0.303 206 -0.003 -0.006 0.006 0.172 0.416 OK OK
207 -0.113 -0.016 -0.241 207 -0.002 -0.004 0.000 0.155 0.337 OK OK
208 -0.113 -0.019 0.304 208 -0.003 -0.006 0.006 0.154 0.417 OK OK
209 -0.127 -0.016 -0.242 209 -0.002 -0.004 0.000 0.175 0.339 OK OK
210 0.179 -0.017 0.260 210 0.003 -0.004 0.002 0.246 0.361 OK OK
211 0.192 -0.013 -0.284 211 0.003 -0.003 -0.004 0.265 0.392 OK OK
212 0.192 -0.017 0.261 212 0.003 -0.004 0.002 0.265 0.363 OK OK
213 0.178 -0.013 -0.285 213 0.003 -0.003 -0.004 0.245 0.393 OK OK
214 -0.187 -0.019 0.296 214 -0.004 -0.006 0.006 0.256 0.406 OK OK
215 -0.174 -0.016 -0.248 215 -0.003 -0.004 0.000 0.239 0.347 OK OK
216 -0.174 -0.019 0.297 216 -0.004 -0.006 0.006 0.238 0.407 OK OK
217 -0.188 -0.016 -0.249 217 -0.003 -0.004 0.000 0.259 0.349 OK OK
218 0.014 -0.023 1.010 218 -0.004 -0.008 0.016 0.014 1.392 OK OK
219 -0.058 -0.024 1.025 219 -0.003 -0.008 0.017 0.077 1.411 OK OK
220 0.032 -0.023 1.012 220 -0.003 -0.008 0.016 0.041 1.394 OK OK
221 -0.076 -0.024 1.023 221 -0.003 -0.008 0.017 0.102 1.408 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 50
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

222 0.064 -0.009 -1.000 222 0.001 -0.001 -0.015 0.088 1.379 OK OK
223 -0.008 -0.010 -0.985 223 0.002 -0.001 -0.015 0.008 1.358 OK OK
224 0.082 -0.009 -0.998 224 0.001 -0.001 -0.015 0.113 1.376 OK OK
225 -0.027 -0.010 -0.987 225 0.001 -0.001 -0.015 0.036 1.361 OK OK
226 0.059 -0.023 1.014 226 -0.003 -0.007 0.016 0.078 1.397 OK OK
227 -0.013 -0.023 1.028 227 -0.002 -0.008 0.017 0.015 1.415 OK OK
228 0.077 -0.023 1.016 228 -0.003 -0.007 0.016 0.104 1.400 OK OK
229 -0.031 -0.023 1.026 229 -0.003 -0.008 0.017 0.039 1.413 OK OK
230 0.019 -0.010 -1.003 230 0.001 -0.001 -0.015 0.025 1.383 OK OK
231 -0.053 -0.010 -0.989 231 0.001 -0.001 -0.015 0.073 1.364 OK OK
232 0.037 -0.009 -1.001 232 0.001 -0.001 -0.015 0.050 1.380 OK OK
233 -0.071 -0.010 -0.991 233 0.001 -0.001 -0.015 0.098 1.366 OK OK
35 200 0.002 -0.048 -0.012 17 200 0.000 -0.010 -0.009 0.003 0.004 OK OK
201 0.002 -0.048 -0.005 201 0.000 -0.010 -0.022 0.003 -0.024 OK OK
202 0.116 -0.047 0.291 202 0.001 -0.010 -0.007 0.161 0.398 OK OK
203 0.130 -0.046 -0.157 203 0.001 -0.010 -0.012 0.181 0.203 OK OK
204 0.130 -0.047 0.263 204 0.001 -0.010 -0.010 0.181 0.354 OK OK
205 0.116 -0.046 -0.129 205 0.001 -0.010 -0.009 0.161 0.168 OK OK
206 -0.127 -0.047 0.150 206 -0.002 -0.010 -0.022 0.175 0.179 OK OK
207 -0.114 -0.046 -0.298 207 -0.002 -0.010 -0.027 0.157 0.379 OK OK
208 -0.114 -0.047 0.121 208 -0.002 -0.010 -0.025 0.157 0.134 OK OK
209 -0.127 -0.046 -0.270 209 -0.002 -0.010 -0.024 0.175 0.344 OK OK
210 0.177 -0.047 0.146 210 0.002 -0.010 -0.023 0.245 0.172 OK OK
211 0.191 -0.046 -0.302 211 0.002 -0.010 -0.028 0.265 0.384 OK OK
212 0.191 -0.047 0.118 212 0.002 -0.010 -0.026 0.265 0.129 OK OK
213 0.177 -0.046 -0.274 213 0.002 -0.010 -0.025 0.245 0.349 OK OK
214 -0.188 -0.047 0.295 214 -0.002 -0.010 -0.006 0.260 0.405 OK OK
215 -0.175 -0.046 -0.154 215 -0.002 -0.010 -0.011 0.242 0.200 OK OK
216 -0.175 -0.047 0.266 216 -0.002 -0.010 -0.009 0.242 0.360 OK OK
217 -0.188 -0.046 -0.125 217 -0.002 -0.010 -0.008 0.260 0.164 OK OK
218 0.012 -0.048 0.864 218 0.000 -0.010 0.110 0.017 1.056 OK OK
219 -0.059 -0.047 0.824 219 0.000 -0.010 0.106 0.083 1.005 OK OK
220 0.031 -0.047 0.820 220 0.000 -0.010 0.105 0.043 1.001 OK OK
221 -0.078 -0.048 0.867 221 -0.001 -0.010 0.111 0.108 1.058 OK OK
222 0.063 -0.046 -0.823 222 0.000 -0.009 -0.156 0.088 0.934 OK OK
223 -0.009 -0.045 -0.863 223 0.000 -0.009 -0.160 0.013 0.984 OK OK
224 0.081 -0.045 -0.866 224 0.000 -0.009 -0.160 0.113 0.988 OK OK
225 -0.027 -0.046 -0.819 225 0.000 -0.009 -0.155 0.038 0.930 OK OK
226 0.057 -0.047 0.769 226 0.000 -0.010 0.100 0.080 0.937 OK OK
227 -0.015 -0.047 0.730 227 0.000 -0.010 0.095 0.021 0.889 OK OK
228 0.075 -0.047 0.726 228 0.000 -0.010 0.095 0.105 0.883 OK OK
229 -0.033 -0.047 0.773 229 0.000 -0.010 0.100 0.046 0.942 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 51
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

230 0.018 -0.046 -0.729 230 0.000 -0.010 -0.145 0.025 0.818 OK OK
231 -0.054 -0.046 -0.769 231 0.000 -0.010 -0.149 0.076 0.868 OK OK
232 0.036 -0.046 -0.772 232 0.000 -0.010 -0.150 0.050 0.871 OK OK
233 -0.072 -0.046 -0.725 233 0.000 -0.010 -0.144 0.101 0.813 OK OK
56 200 0.000 -0.010 -0.013 55 200 -0.001 -0.004 0.008 -0.001 0.007 OK OK
201 0.000 -0.010 -0.006 201 -0.001 -0.004 0.010 -0.001 -0.006 OK OK
202 0.074 0.011 0.288 202 0.012 0.006 0.072 0.087 0.302 OK OK
203 0.096 0.018 -0.157 203 0.016 0.009 -0.022 0.112 0.189 OK OK
204 0.087 0.015 0.260 204 0.014 0.008 0.067 0.102 0.270 OK OK
205 0.084 0.014 -0.129 205 0.014 0.008 -0.017 0.098 0.157 OK OK
206 -0.096 -0.039 0.148 206 -0.017 -0.017 0.041 0.111 0.150 OK OK
207 -0.074 -0.032 -0.298 207 -0.013 -0.014 -0.053 0.085 0.343 OK OK
208 -0.083 -0.035 0.120 208 -0.015 -0.016 0.036 0.095 0.118 OK OK
209 -0.086 -0.036 -0.270 209 -0.015 -0.016 -0.048 0.099 0.311 OK OK
210 0.124 0.026 0.144 210 0.021 0.013 0.043 0.144 0.141 OK OK
211 0.146 0.033 -0.302 211 0.024 0.016 -0.052 0.171 0.350 OK OK
212 0.136 0.030 0.116 212 0.023 0.015 0.037 0.158 0.111 OK OK
213 0.133 0.029 -0.274 213 0.022 0.015 -0.046 0.155 0.319 OK OK
214 -0.146 -0.054 0.292 214 -0.026 -0.024 0.071 0.168 0.309 OK OK
215 -0.123 -0.047 -0.153 215 -0.022 -0.021 -0.024 0.141 0.181 OK OK
216 -0.133 -0.050 0.264 216 -0.023 -0.023 0.065 0.154 0.279 OK OK
217 -0.136 -0.051 -0.125 217 -0.024 -0.023 -0.018 0.157 0.150 OK OK
218 -0.011 -0.014 0.858 218 -0.002 -0.006 0.190 0.013 0.935 OK OK
219 -0.062 -0.029 0.818 219 -0.011 -0.013 0.181 0.071 0.892 OK OK
220 0.004 -0.010 0.814 220 0.000 -0.004 0.181 0.006 0.886 OK OK
221 -0.076 -0.034 0.861 221 -0.014 -0.015 0.190 0.087 0.939 OK OK
222 0.062 0.009 -0.819 222 0.010 0.005 -0.159 0.073 0.924 OK OK
223 0.011 -0.006 -0.859 223 0.001 -0.002 -0.168 0.014 0.967 OK OK
224 0.077 0.013 -0.863 224 0.012 0.007 -0.168 0.091 0.973 OK OK
225 -0.004 -0.011 -0.816 225 -0.001 -0.005 -0.159 0.004 0.920 OK OK
226 0.032 -0.002 0.764 226 0.005 0.000 0.171 0.038 0.830 OK OK
227 -0.019 -0.017 0.724 227 -0.004 -0.007 0.162 0.021 0.787 OK OK
228 0.047 0.003 0.720 228 0.007 0.002 0.162 0.056 0.781 OK OK
229 -0.034 -0.021 0.768 229 -0.006 -0.009 0.171 0.039 0.836 OK OK
230 0.020 -0.004 -0.726 230 0.003 -0.001 -0.141 0.024 0.819 OK OK
231 -0.031 -0.019 -0.765 231 -0.006 -0.008 -0.149 0.035 0.862 OK OK
232 0.034 0.001 -0.769 232 0.005 0.001 -0.149 0.041 0.868 OK OK
233 -0.046 -0.023 -0.722 233 -0.009 -0.010 -0.140 0.052 0.815 OK OK
58 200 0.000 -0.011 0.004 57 200 0.001 -0.004 0.014 -0.001 -0.014 OK OK
201 0.000 -0.011 0.006 201 0.001 -0.004 0.014 -0.001 -0.011 OK OK
202 0.074 -0.033 0.115 202 0.013 -0.014 0.034 0.085 0.113 OK OK
203 0.096 -0.039 -0.043 203 0.017 -0.017 0.003 0.111 0.056 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 52
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

204 0.087 -0.036 0.098 204 0.015 -0.016 0.030 0.101 0.095 OK OK
205 0.083 -0.035 -0.026 205 0.015 -0.016 0.007 0.095 0.027 OK OK
206 -0.096 0.018 0.062 206 -0.016 0.009 0.026 0.112 0.050 OK OK
207 -0.074 0.011 -0.097 207 -0.012 0.006 -0.005 0.087 0.129 OK OK
208 -0.083 0.014 0.044 208 -0.014 0.007 0.022 0.097 0.031 OK OK
209 -0.087 0.015 -0.079 209 -0.014 0.008 -0.001 0.102 0.109 OK OK
210 0.124 -0.047 0.044 210 0.022 -0.021 0.019 0.143 0.035 OK OK
211 0.146 -0.053 -0.115 211 0.026 -0.024 -0.012 0.168 0.144 OK OK
212 0.136 -0.051 0.026 212 0.024 -0.023 0.015 0.157 0.015 OK OK
213 0.133 -0.050 -0.097 213 0.023 -0.023 -0.008 0.154 0.125 OK OK
214 -0.146 0.032 0.133 214 -0.024 0.016 0.041 0.171 0.129 OK OK
215 -0.124 0.026 -0.025 215 -0.021 0.013 0.010 0.144 0.021 OK OK
216 -0.133 0.029 0.116 216 -0.022 0.014 0.037 0.155 0.111 OK OK
217 -0.136 0.030 -0.008 217 -0.023 0.015 0.014 0.158 -0.008 OK OK
218 -0.011 -0.008 0.290 218 -0.001 -0.003 0.067 0.014 0.312 OK OK
219 -0.062 0.007 0.274 219 -0.010 0.004 0.065 0.073 0.293 OK OK
220 0.004 -0.012 0.269 220 0.001 -0.005 0.063 0.004 0.288 OK OK
221 -0.076 0.012 0.296 221 -0.012 0.006 0.069 0.090 0.318 OK OK
222 0.062 -0.028 -0.254 222 0.011 -0.013 -0.036 0.071 0.305 OK OK
223 0.011 -0.013 -0.270 223 0.002 -0.005 -0.038 0.013 0.325 OK OK
224 0.076 -0.033 -0.276 224 0.014 -0.015 -0.041 0.087 0.329 OK OK
225 -0.004 -0.009 -0.249 225 0.000 -0.003 -0.034 0.006 0.301 OK OK
226 0.032 -0.020 0.232 226 0.006 -0.009 0.055 0.036 0.248 OK OK
227 -0.019 -0.005 0.216 227 -0.003 -0.002 0.053 0.022 0.228 OK OK
228 0.047 -0.025 0.210 228 0.009 -0.011 0.050 0.053 0.224 OK OK
229 -0.034 -0.001 0.237 229 -0.005 0.001 0.057 0.041 0.252 OK OK
230 0.019 -0.016 -0.196 230 0.004 -0.007 -0.024 0.021 0.241 OK OK
231 -0.032 -0.001 -0.212 231 -0.005 0.000 -0.026 0.038 0.260 OK OK
232 0.034 -0.020 -0.217 232 0.006 -0.009 -0.028 0.039 0.265 OK OK
233 -0.047 0.004 -0.190 233 -0.007 0.002 -0.021 0.056 0.237 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 53
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

REVISIÓN DE DESPLAZAMIENTOS PERMISIBLES PARA EL NIVEL 2

Altura de entrepiso
4.80 h =m Q' = 1.4
Desplazamiento permisible es δ=h x 0.006 δ= 2.88 cm

Los desplazamientos deben ser revisados con respecto al nodo inferior (desplazamiento del nodo superior respecto al nodo
inferior).

NODOS SUPERIORES NODOS INFERIORES DESPLAZAMIENTO COMPARACION


Node L/C X-Trans cm Y-Trans Z-Trans cmNode L/C X-Trans cm Y-Trans Z-Trans cm X * Q' Z * Q' X Z
61 200 0.025 -0.127 -0.086 25 200 0.013 -0.119 -0.002 0.017 0.118 OK OK
201 0.022 -0.126 -0.075 201 0.011 -0.119 0.010 0.015 0.091 OK OK
202 1.087 -0.114 0.053 202 0.636 -0.109 0.117 0.631 -0.090 OK OK
203 1.033 -0.119 -0.682 203 0.600 -0.112 -0.335 0.606 0.486 OK OK
204 1.040 -0.114 0.116 204 0.607 -0.109 0.150 0.606 -0.048 OK OK
205 1.081 -0.119 -0.745 205 0.629 -0.112 -0.368 0.633 0.528 OK OK
206 -0.976 -0.125 0.538 206 -0.588 -0.117 0.355 0.543 0.256 OK OK
207 -1.030 -0.129 -0.197 207 -0.624 -0.120 -0.098 0.568 0.139 OK OK
208 -1.024 -0.125 0.601 208 -0.617 -0.117 0.388 0.570 0.298 OK OK
209 -0.983 -0.130 -0.260 209 -0.595 -0.120 -0.131 0.543 0.181 OK OK
210 0.839 -0.113 0.395 210 0.492 -0.108 0.291 0.486 0.146 OK OK
211 0.785 -0.118 -0.340 211 0.456 -0.111 -0.162 0.461 0.249 OK OK
212 0.791 -0.113 0.459 212 0.463 -0.108 0.324 0.459 0.189 OK OK
213 0.833 -0.118 -0.403 213 0.485 -0.112 -0.195 0.487 0.291 OK OK
214 -0.728 -0.126 0.196 214 -0.444 -0.118 0.181 0.398 0.021 OK OK
215 -0.782 -0.130 -0.540 215 -0.481 -0.121 -0.271 0.421 0.377 OK OK
216 -0.775 -0.126 0.259 216 -0.473 -0.118 0.214 0.423 0.063 OK OK
217 -0.734 -0.131 -0.603 217 -0.452 -0.121 -0.304 0.395 0.419 OK OK
218 0.407 -0.113 1.208 218 0.228 -0.108 0.869 0.251 0.475 OK OK
219 -0.178 -0.116 1.349 219 -0.100 -0.110 0.938 0.109 0.575 OK OK
220 0.333 -0.113 1.311 220 0.185 -0.108 0.921 0.207 0.546 OK OK
221 -0.103 -0.116 1.246 221 -0.057 -0.111 0.886 0.064 0.504 OK OK
222 0.237 -0.128 -1.483 222 0.113 -0.119 -0.907 0.174 0.806 OK OK
223 -0.349 -0.131 -1.343 223 -0.215 -0.121 -0.838 0.188 0.707 OK OK
224 0.162 -0.127 -1.380 224 0.070 -0.119 -0.855 0.129 0.735 OK OK
225 -0.274 -0.131 -1.445 225 -0.172 -0.121 -0.890 0.143 0.777 OK OK
226 0.248 -0.112 1.419 226 0.132 -0.108 0.979 0.162 0.616 OK OK
227 -0.337 -0.116 1.559 227 -0.197 -0.110 1.048 0.196 0.715 OK OK
228 0.174 -0.112 1.522 228 0.088 -0.107 1.031 0.120 0.687 OK OK
229 -0.263 -0.116 1.456 229 -0.153 -0.110 0.996 0.154 0.644 OK OK
230 0.396 -0.128 -1.693 230 0.209 -0.119 -1.017 0.262 0.946 OK OK
231 -0.190 -0.131 -1.553 231 -0.119 -0.122 -0.948 0.099 0.847 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 54
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

232 0.321 -0.128 -1.590 232 0.166 -0.119 -0.964 0.217 0.876 OK OK
233 -0.115 -0.132 -1.656 233 -0.076 -0.122 -1.000 0.055 0.918 OK OK
63 200 0.018 -0.127 -0.021 27 200 0.013 -0.119 -0.011 0.007 0.014 OK OK
201 0.015 -0.126 -0.014 201 0.010 -0.119 -0.003 0.007 0.015 OK OK
202 1.081 -0.135 0.567 202 0.633 -0.127 0.297 0.627 0.378 OK OK
203 1.028 -0.140 -0.233 203 0.597 -0.131 -0.159 0.603 0.104 OK OK
204 1.034 -0.135 0.509 204 0.604 -0.127 0.269 0.602 0.336 OK OK
205 1.076 -0.140 -0.175 205 0.626 -0.131 -0.130 0.630 0.063 OK OK
206 -0.982 -0.125 0.205 206 -0.590 -0.120 0.152 0.549 0.074 OK OK
207 -1.036 -0.130 -0.594 207 -0.626 -0.123 -0.304 0.574 0.406 OK OK
208 -1.030 -0.125 0.148 208 -0.619 -0.120 0.123 0.575 0.035 OK OK
209 -0.988 -0.130 -0.537 209 -0.597 -0.123 -0.275 0.547 0.367 OK OK
210 0.833 -0.136 0.257 210 0.490 -0.128 0.150 0.480 0.150 OK OK
211 0.779 -0.141 -0.543 211 0.453 -0.131 -0.306 0.456 0.332 OK OK
212 0.785 -0.136 0.199 212 0.461 -0.128 0.121 0.454 0.109 OK OK
213 0.827 -0.141 -0.485 213 0.482 -0.131 -0.278 0.483 0.290 OK OK
214 -0.733 -0.124 0.515 214 -0.446 -0.119 0.300 0.402 0.301 OK OK
215 -0.787 -0.129 -0.285 215 -0.483 -0.123 -0.157 0.426 0.179 OK OK
216 -0.781 -0.124 0.457 216 -0.475 -0.119 0.271 0.428 0.260 OK OK
217 -0.739 -0.129 -0.227 217 -0.454 -0.122 -0.128 0.399 0.139 OK OK
218 0.401 -0.126 1.464 218 0.227 -0.120 0.879 0.244 0.819 OK OK
219 -0.185 -0.123 1.360 219 -0.101 -0.118 0.838 0.118 0.731 OK OK
220 0.326 -0.126 1.371 220 0.184 -0.121 0.835 0.199 0.750 OK OK
221 -0.110 -0.123 1.453 221 -0.057 -0.118 0.883 0.074 0.798 OK OK
222 0.232 -0.142 -1.380 222 0.110 -0.132 -0.837 0.171 0.760 OK OK
223 -0.354 -0.139 -1.483 223 -0.218 -0.130 -0.878 0.190 0.847 OK OK
224 0.157 -0.142 -1.473 224 0.067 -0.132 -0.881 0.126 0.829 OK OK
225 -0.279 -0.139 -1.390 225 -0.175 -0.130 -0.833 0.146 0.780 OK OK
226 0.242 -0.126 1.271 226 0.131 -0.121 0.783 0.155 0.683 OK OK
227 -0.344 -0.124 1.168 227 -0.197 -0.119 0.743 0.206 0.595 OK OK
228 0.167 -0.127 1.179 228 0.088 -0.121 0.739 0.111 0.616 OK OK
229 -0.269 -0.123 1.261 229 -0.154 -0.118 0.787 0.161 0.664 OK OK
230 0.391 -0.142 -1.187 230 0.206 -0.132 -0.741 0.259 0.624 OK OK
231 -0.195 -0.139 -1.291 231 -0.122 -0.130 -0.782 0.102 0.713 OK OK
232 0.316 -0.142 -1.280 232 0.163 -0.132 -0.785 0.214 0.693 OK OK
233 -0.120 -0.138 -1.198 233 -0.078 -0.129 -0.738 0.059 0.644 OK OK
64 200 0.045 -0.035 -0.093 30 200 0.014 -0.028 0.001 0.043 0.129 OK OK
201 0.044 -0.036 -0.082 201 0.013 -0.028 0.014 0.043 0.095 OK OK
202 0.576 0.008 0.046 202 0.145 0.014 0.120 0.603 -0.104 OK OK
203 0.595 0.013 -0.690 203 0.152 0.017 -0.334 0.620 0.498 OK OK
204 0.592 0.008 0.109 204 0.147 0.014 0.153 0.623 -0.062 OK OK
205 0.579 0.013 -0.753 205 0.151 0.017 -0.367 0.599 0.540 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 55
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

206 -0.489 -0.082 0.532 206 -0.128 -0.073 0.360 0.505 0.241 OK OK
207 -0.470 -0.078 -0.204 207 -0.122 -0.069 -0.093 0.487 0.155 OK OK
208 -0.473 -0.082 0.595 208 -0.127 -0.073 0.393 0.484 0.283 OK OK
209 -0.486 -0.078 -0.267 209 -0.123 -0.070 -0.126 0.508 0.197 OK OK
210 0.667 0.009 0.389 210 0.152 0.015 0.295 0.721 0.132 OK OK
211 0.687 0.014 -0.347 211 0.158 0.019 -0.159 0.741 0.263 OK OK
212 0.683 0.009 0.452 212 0.153 0.015 0.328 0.742 0.174 OK OK
213 0.670 0.014 -0.410 213 0.157 0.019 -0.192 0.718 0.305 OK OK
214 -0.581 -0.084 0.189 214 -0.134 -0.075 0.185 0.626 0.006 OK OK
215 -0.561 -0.079 -0.547 215 -0.128 -0.071 -0.268 0.606 0.391 OK OK
216 -0.564 -0.083 0.252 216 -0.133 -0.074 0.219 0.603 0.046 OK OK
217 -0.577 -0.079 -0.610 217 -0.129 -0.071 -0.301 0.627 0.433 OK OK
218 0.174 -0.030 1.203 218 0.037 -0.022 0.875 0.192 0.459 OK OK
219 -0.137 -0.056 1.343 219 -0.040 -0.047 0.945 0.136 0.557 OK OK
220 0.202 -0.030 1.306 220 0.039 -0.021 0.928 0.228 0.529 OK OK
221 -0.165 -0.057 1.240 221 -0.042 -0.048 0.892 0.172 0.487 OK OK
222 0.243 -0.013 -1.491 222 0.064 -0.009 -0.906 0.251 0.819 OK OK
223 -0.068 -0.039 -1.350 223 -0.013 -0.034 -0.836 0.077 0.720 OK OK
224 0.271 -0.013 -1.388 224 0.066 -0.008 -0.853 0.287 0.749 OK OK
225 -0.096 -0.040 -1.453 225 -0.015 -0.034 -0.889 0.113 0.790 OK OK
226 0.228 -0.029 1.413 226 0.041 -0.021 0.985 0.262 0.599 OK OK
227 -0.084 -0.056 1.554 227 -0.036 -0.046 1.055 0.067 0.699 OK OK
228 0.255 -0.029 1.516 228 0.043 -0.021 1.038 0.297 0.669 OK OK
229 -0.111 -0.056 1.451 229 -0.038 -0.047 1.002 0.102 0.629 OK OK
230 0.190 -0.014 -1.701 230 0.060 -0.009 -1.016 0.182 0.959 OK OK
231 -0.122 -0.040 -1.561 231 -0.017 -0.035 -0.947 0.147 0.860 OK OK
232 0.217 -0.013 -1.598 232 0.062 -0.009 -0.964 0.217 0.888 OK OK
233 -0.149 -0.041 -1.664 233 -0.019 -0.035 -0.999 0.182 0.931 OK OK
66 200 0.040 -0.126 -0.027 32 200 0.025 -0.119 -0.009 0.021 0.025 OK OK
201 0.040 -0.126 -0.020 201 0.024 -0.119 -0.002 0.022 0.025 OK OK
202 0.573 -0.145 0.561 202 0.193 -0.135 0.298 0.532 0.368 OK OK
203 0.592 -0.140 -0.239 203 0.198 -0.131 -0.156 0.552 0.116 OK OK
204 0.589 -0.145 0.503 204 0.194 -0.135 0.270 0.553 0.326 OK OK
205 0.576 -0.140 -0.181 205 0.197 -0.131 -0.127 0.531 0.076 OK OK
206 -0.492 -0.125 0.199 206 -0.156 -0.120 0.154 0.470 0.063 OK OK
207 -0.473 -0.120 -0.600 207 -0.151 -0.116 -0.301 0.451 0.419 OK OK
208 -0.476 -0.125 0.142 208 -0.154 -0.119 0.125 0.451 0.024 OK OK
209 -0.489 -0.120 -0.543 209 -0.152 -0.116 -0.272 0.472 0.379 OK OK
210 0.665 -0.144 0.251 210 0.201 -0.134 0.151 0.650 0.140 OK OK
211 0.683 -0.138 -0.549 211 0.206 -0.130 -0.303 0.668 0.344 OK OK
212 0.681 -0.144 0.193 212 0.202 -0.134 0.123 0.671 0.098 OK OK
213 0.667 -0.139 -0.491 213 0.205 -0.130 -0.274 0.647 0.304 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 56
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

214 -0.584 -0.126 0.509 214 -0.164 -0.120 0.301 0.588 0.291 OK OK
215 -0.565 -0.121 -0.290 215 -0.159 -0.116 -0.154 0.568 0.190 OK OK
216 -0.568 -0.126 0.451 216 -0.162 -0.120 0.272 0.568 0.251 OK OK
217 -0.581 -0.121 -0.233 217 -0.160 -0.117 -0.125 0.589 0.151 OK OK
218 0.173 -0.144 1.458 218 0.060 -0.134 0.878 0.158 0.812 OK OK
219 -0.139 -0.138 1.354 219 -0.039 -0.130 0.837 0.140 0.724 OK OK
220 0.200 -0.144 1.365 220 0.062 -0.134 0.833 0.193 0.745 OK OK
221 -0.166 -0.139 1.447 221 -0.042 -0.130 0.881 0.174 0.792 OK OK
222 0.239 -0.126 -1.386 222 0.082 -0.121 -0.831 0.220 0.777 OK OK
223 -0.073 -0.121 -1.489 223 -0.017 -0.116 -0.872 0.078 0.864 OK OK
224 0.266 -0.126 -1.479 224 0.084 -0.121 -0.875 0.255 0.846 OK OK
225 -0.101 -0.121 -1.396 225 -0.019 -0.117 -0.828 0.115 0.795 OK OK
226 0.227 -0.143 1.265 226 0.065 -0.134 0.782 0.227 0.676 OK OK
227 -0.085 -0.138 1.162 227 -0.034 -0.129 0.741 0.071 0.589 OK OK
228 0.254 -0.143 1.173 228 0.067 -0.134 0.738 0.262 0.609 OK OK
229 -0.113 -0.138 1.255 229 -0.037 -0.130 0.785 0.106 0.658 OK OK
230 0.185 -0.127 -1.193 230 0.077 -0.121 -0.735 0.151 0.641 OK OK
231 -0.127 -0.121 -1.297 231 -0.022 -0.117 -0.776 0.147 0.729 OK OK
232 0.212 -0.127 -1.286 232 0.080 -0.121 -0.779 0.185 0.710 OK OK
233 -0.154 -0.122 -1.204 233 -0.024 -0.117 -0.732 0.182 0.661 OK OK

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 57
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

V.2. Revisión de deflexiones en trabes por medio del RCDF NTC 2004.
Deflexiones permisibles

De acuerdo con el apartado 3.2 de las NTC para diseño en concreto, la deflexión total (suma de la deflexión
inmediata más la diferida), que se obtiene del análisis estructural bajo las condiciones de servicio y considerando
la carga viva media, debe de ser menor que las delfexiones permisibles indicadas en las Normas Técnicas
Complementarias sobre Criterios y Acciones para el Diseño Estructural de las Edificaciones. En trabes la
deflexción permisible se calcula mediante las: (1) cuando no se perjudican elementos no estructurales y (2)
cuando la delfexión puerde perjudicarlos.

D1Perm = (L/240) + 0.5 (cm) … (1)


D2Perm = (L/480) + 0.3 (cm) … (2)

Deflexiones inmediatas

Las deflexiones inmediatas se pueden calcular con el momento de inercia de la sección transformada agrietada
(Iag), la cual se calcula del siguiente modo:

n = Es/Ec Relación modular


At = nAs Área transformada de acero
Tomando momentos de área respecto a la posición del
E.N. de la sección transformada agrietada.

Bc2/2 = nAs(d-c) Bc2/2 + nAs c - nAs d = 0


La ec. anterior da la posición del eje neutro (c).

El momento de inercia de la sección transformada


respecto al E.N. es:
Iag = Bc3/3 + IAt + nAs(d-c) 2
Bc3/3 : Inercia del concreto a compresión respecto al eje neutro.
IAt : Inercia de la sección equivalente de concreto respecto a su propio eje (se desprecia).

Deflexiones diferidas

Según lo estipulado en las Normas Técnicas Complementarias para Diseño en Concreto, la deflexión diferida se
calcula multiplicando la flecha inmediata por el siguiente factor:

2
1  50' ….. Para concreto clase 1.
4
1  50' ….. Para concreto clase 2.
r' = As'/(Bd) ….. Porcentaje de acero en compresión.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 58
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Constantes de cálculo :
f'c = 250 kg/cm 2
f*c = 200 kg/cm 2
f"c = 170 kg/cm 2
B1 = 0.85

Ec = 221359 kg/cm 2
Es = 2039000 kg/cm 2
n = 9.21
r min. = 0.00264
r máx. est.= 0.01821
r máx. din.= 0.01518

NIVEL N+2109.36
NIVEL As r real As' B H r d L DE D E Real DTot.
UBICACIÓN TRABE
cm 2 cm 2 cm cm cm cm m cm cm cm
TRABES PRINCIPALES
T-1 (EJE A-B) S 8.55 0.0050 15.21 30 60 2.5 57.5 6.25 0.204 0.626 1.495
T-1 (EJE B-C) S 8.55 0.0050 15.21 30 60 2.5 57.5 6.25 0.202 0.620 1.480
T-1 (EJE C-D) S 8.55 0.0050 15.21 30 60 2.5 57.5 6.25 0.218 0.669 1.597
T-1 (EJE D-E) S 8.55 0.0050 15.21 30 60 2.5 57.5 6.25 0.199 0.611 1.458
T-1 (EJE 1-2) S 8.55 0.0050 15.21 30 60 2.5 57.5 7.00 0.243 0.746 1.780
T-1 (EJE 2-3) S 8.55 0.0050 15.21 30 60 2.5 57.5 7.00 0.21 0.644 1.539
T-1 (EJE 3-4) S 8.55 0.0050 15.21 30 60 2.5 57.5 7.00 0.261 0.801 1.912
T-2 (EJE A-B) N1 10.14 0.0050 10.14 30 70 2.5 67.5 6.25 0.152 0.454 1.180
T-2 (EJE B-C) N1 10.14 0.0050 10.14 30 70 2.5 67.5 6.25 0.171 0.511 1.328
T-2 (EJE D-E) N1 10.14 0.0050 10.14 30 70 2.5 67.5 6.25 0.098 0.293 0.761
T-3 (EJE 1-2) N1 10.14 0.0050 20.28 30 70 2.5 67.5 7.00 0.219 0.654 1.526
T-3 (EJE 2-3) N1 12.99 0.0064 20.28 30 70 2.5 67.5 7.00 0.286 0.701 1.635
T-4 (EJE 1-2) N1 12.99 0.0064 10.14 30 70 2.5 67.5 7.00 0.230 0.564 1.466
T-4 (EJE 2-3) N1 12.99 0.0064 20.28 30 70 2.5 67.5 7.00 0.244 0.598 1.395
T-4 (EJE 3-4) N1 12.99 0.0064 20.28 30 70 2.5 67.5 7.00 0.179 0.439 1.023
T-4 (EJE 4-5) N1 12.99 0.0064 10.14 30 70 2.5 67.5 7.00 0.118 0.289 0.752
T-5 (EJE A-B) N1 10.14 0.0050 15.21 30 70 2.5 67.5 6.25 0.157 0.469 1.151
T-5 (EJE B-C) N1 10.14 0.0050 15.21 30 70 2.5 67.5 6.25 0.174 0.520 1.275
T-5 (EJE C-D) N1 10.14 0.0050 15.21 30 70 2.5 67.5 6.25 0.173 0.517 1.268
T-5 (EJE D-E) N1 10.14 0.0050 15.21 30 70 2.5 67.5 6.25 0.162 0.484 1.187
T-6 (EJE A-B) N1 8.55 0.0042 8.55 30 70 2.5 67.5 6.25 0.197 0.676 1.793
T-6 (EJE B-C) N1 8.55 0.0042 8.55 30 70 2.5 67.5 6.25 0.07 0.240 0.637
T-7 (EJE 2-3) NA 10.14 0.0059 10.14 30 60 2.5 57.5 5.00 0.037 0.099 0.252

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 59
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

TRABES SECUNDARIAS
TS-1 (EJE A-B) S 3.96 0.0033 5.94 25 50 2.5 47.5 6.25 0.227 0.992 2.580
TS-1 (EJE B-C) S 3.96 0.0033 5.94 25 50 2.5 47.5 6.25 0.127 0.555 1.443
TS-1 (EJE C-D) S 3.96 0.0033 5.94 25 50 2.5 47.5 6.25 0.072 0.315 0.818
TS-1 (EJE D-E) S 3.96 0.0033 5.94 25 50 2.5 47.5 6.25 0.190 0.830 2.159
TS-2 (EJE 1-2) S 3.96 0.0033 8.55 25 50 2.5 47.5 7.00 0.044 0.192 0.475
TS-2 (EJE 2-3) S 3.96 0.0033 8.55 25 50 2.5 47.5 7.00 0.101 0.441 1.091
TS-3 (EJE C-D) S 3.96 0.0033 3.96 25 50 2.5 47.5 4.50 0.115 0.503 1.364
TS-4 (EJE A-B) N1 3.81 0.0032 5.94 25 50 2.5 47.5 6.25 0.204 0.921 2.395
TS-4 (EJE B-C) N1 3.81 0.0032 5.94 25 50 2.5 47.5 6.25 0.209 0.944 2.454
TS-5 (EJE A-B) N1 3.81 0.0032 6.97 25 50 2.5 47.5 6.25 0.175 0.790 2.012
TS-5 (EJE B-C) N1 3.8 0.0032 6.97 25 50 2.5 47.5 6.25 0.201 0.908 2.311
TS-5 (EJE C-D) N1 3.81 0.0032 6.97 25 50 2.5 47.5 6.25 0.165 0.745 1.897
TS-5 (EJE D-E) N1 3.81 0.0032 6.97 25 50 2.5 47.5 6.25 0.198 0.894 2.277
TS-6 (EJE 1-2) N1 5.7 0.0048 8.55 25 50 2.5 47.5 7.00 0.228 0.737 1.821
TS-6 (EJE 2-3) N1 5.7 0.0048 8.55 25 50 2.5 47.5 7.00 0.35 1.131 2.795
TS-7 (EJE 1-2) N1 2.54 0.0021 5.7 25 50 2.5 47.5 7.00 0.198 1.267 3.310
TS-7 (EJE 2-3) N1 2.54 0.0021 8.55 25 50 2.5 47.5 7.00 0.185 1.184 2.924
TS-7 (EJE 3-4) N1 2.54 0.0021 8.55 25 50 2.5 47.5 7.00 0.152 0.972 2.403
TS-7 (EJE 4-5) N1 2.54 0.0021 5.7 25 50 2.5 47.5 7.00 0.184 1.177 3.076
TS-8 (EJE B-C) NA 7.92 0.0067 3.96 25 50 2.5 47.5 6.25 0.238 0.592 1.606
TS-8 (EJE C-D) NA 7.92 0.0067 3.96 25 50 2.5 47.5 6.25 0.246 0.612 1.660
MURO D1Perm D2Perm Ig c d-c n As(d-c) 2 B c 3/3 Icr
UBICACIÓN TRABE REVISIÓN
cm cm cm 4 cm cm cm 4 cm 4 cm 4
TRABES PRINCIPALES
T-1 (EJE A-B) No 3.10 BIEN 540000 14.95 42.55 142607.20 33395.18 176002.4
T-1 (EJE B-C) No 3.10 BIEN 540000 14.95 42.55 142607.20 33395.18 176002.4
T-1 (EJE C-D) No 3.10 BIEN 540000 14.95 42.55 142607.20 33395.18 176002.4
T-1 (EJE D-E) No 3.10 BIEN 540000 14.95 42.55 142607.20 33395.18 176002.4
T-1 (EJE 1-2) No 3.42 BIEN 540000 14.95 42.55 142607.20 33395.18 176002.4
T-1 (EJE 2-3) No 3.42 BIEN 540000 14.95 42.55 142607.20 33395.18 176002.4
T-1 (EJE 3-4) No 3.42 BIEN 540000 14.95 42.55 142607.20 33395.18 176002.4
T-2 (EJE A-B) No 3.10 BIEN 857500 17.62 49.88 232357.36 54732.96 287090.3
T-2 (EJE B-C) No 3.10 BIEN 857500 17.62 49.88 232357.36 54732.96 287090.3
T-2 (EJE D-E) No 3.10 BIEN 857500 17.62 49.88 232357.36 54732.96 287090.3
T-3 (EJE 1-2) No 3.42 BIEN 857500 17.62 49.88 232357.36 54732.96 287090.3
T-3 (EJE 2-3) No 3.42 BIEN 857500 19.56 47.94 275038.57 74792.01 349830.6
T-4 (EJE 1-2) No 3.42 BIEN 857500 19.56 47.94 275038.57 74792.01 349830.6
T-4 (EJE 2-3) No 3.42 BIEN 857500 19.56 47.94 275038.57 74792.01 349830.6
T-4 (EJE 3-4) No 3.42 BIEN 857500 19.56 47.94 275038.57 74792.01 349830.6
T-4 (EJE 4-5) No 3.42 BIEN 857500 19.56 47.94 275038.57 74792.01 349830.6
T-5 (EJE A-B) No 3.10 BIEN 857500 17.62 49.88 232357.36 54732.96 287090.3
T-5 (EJE B-C) Si 1.60 BIEN 857500 17.62 49.88 232357.36 54732.96 287090.3
T-5 (EJE C-D) Si 1.60 BIEN 857500 17.62 49.88 232357.36 54732.96 287090.3
T-5 (EJE D-E) No 3.10 BIEN 857500 17.62 49.88 232357.36 54732.96 287090.3
T-6 (EJE A-B) No 3.10 BIEN 857500 16.38 51.12 205789.98 43968.93 249758.9
T-6 (EJE B-C) No 3.10 BIEN 857500 16.38 51.12 205789.98 43968.93 249758.9
T-7 (EJE 2-3) No 2.58 BIEN 540000 16.06 41.44 160374.03 41445.95 201820.0

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 60
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

TRABES SECUNDARIAS
TS-1 (EJE A-B) No 3.10 BIEN 260417 10.40 37.10 50195.13 9385.59 59580.7
TS-1 (EJE B-C) No 3.10 BIEN 260417 10.40 37.10 50195.13 9385.59 59580.7
TS-1 (EJE C-D) No 3.10 BIEN 260417 10.40 37.10 50195.13 9385.59 59580.7
TS-1 (EJE D-E) No 3.10 BIEN 260417 10.40 37.10 50195.13 9385.59 59580.7
TS-2 (EJE 1-2) No 3.42 BIEN 260417 10.40 37.10 50195.13 9385.59 59580.7
TS-2 (EJE 2-3) No 3.42 BIEN 260417 10.40 37.10 50195.13 9385.59 59580.7
TS-3 (EJE C-D) No 2.38 BIEN 260417 10.40 37.10 50195.13 9385.59 59580.7
TS-4 (EJE A-B) No 3.10 BIEN 260417 10.23 37.27 48750.33 8920.12 57670.4
TS-4 (EJE B-C) No 3.10 BIEN 260417 10.23 37.27 48750.33 8920.12 57670.4
TS-5 (EJE A-B) No 3.10 BIEN 260417 10.23 37.27 48750.33 8920.12 57670.4
TS-5 (EJE B-C) No 3.10 BIEN 260417 10.23 37.27 48750.33 8920.12 57670.4
TS-5 (EJE C-D) No 3.10 BIEN 260417 10.23 37.27 48750.33 8920.12 57670.4
TS-5 (EJE D-E) No 3.10 BIEN 260417 10.23 37.27 48750.33 8920.12 57670.4
TS-6 (EJE 1-2) No 3.42 BIEN 260417 12.18 35.32 65498.76 15058.26 80557.0
TS-6 (EJE 2-3) No 3.42 BIEN 260417 12.18 35.32 65498.76 15058.26 80557.0
TS-7 (EJE 1-2) No 3.42 BIEN 260417 8.54 38.96 35514.21 5189.44 40703.6
TS-7 (EJE 2-3) No 3.42 BIEN 260417 8.54 38.96 35514.21 5189.44 40703.6
TS-7 (EJE 3-4) No 3.42 BIEN 260417 8.54 38.96 35514.21 5189.44 40703.6
TS-7 (EJE 4-5) No 3.42 BIEN 260417 8.54 38.96 35514.21 5189.44 40703.6
TS-8 (EJE B-C) No 3.10 BIEN 260417 13.99 33.51 81942.00 22796.47 104738.5
TS-8 (EJE C-D) No 3.10 BIEN 260417 13.99 33.51 81942.00 22796.47 104738.5

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 61
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

V.3. Diseño de zapatas aisladas.


Elementos mecánicos en los apoyos para el diseño de zapatas ZA-1

Datos de zapata y dado.


Zapata Dado q= 17.11 
max P
Df LX LZ h cx cz qd = 24.01 Mx
m m m m m m A= 9.00 
min
3.45 3.00 3.00 0.45 0.60 0.60
My
Peso de Cimentación Terreno
x y
Zapata Dado Relleno Suma qadm wrell L
B

T T T T T/m2 T/m3
9.72 2.59 0.00 12.31 20.00 0.00 Distribución deesfuerzosen el suelo

Figura 20. Diagrama de presiones ZA-1.


Cargas y determinacion de presión de contacto. (Ton,m) MX MZ
JOINT LOAD FORCE-X FORCE-Y FORCE-Z MOM-X MOM-Y MOM Z (TOTAL) (TOTAL) ex ez LX' LZ' q qd
43 200 0.571 124.926 0.025 0.383 0 -0.422 0.38 -0.42 0.00 0.00 2.99 2.99 15.31 21.34 C.P.
201 0.047 124.362 -0.645 -0.89 0 0.564 -0.89 0.56 0.00 -0.01 2.99 2.99 15.29 21.32 C.P.
202 -2.949 114.756 0.684 1.106 0 7.851 1.11 7.85 0.06 0.01 2.88 2.98 14.81 15.10
203 -2.84 117.146 -1.029 -0.539 0 7.556 -0.54 7.56 0.06 0.00 2.88 2.99 15.01 15.32
204 -2.88 114.653 0.588 0.839 0 7.636 0.84 7.64 0.06 0.01 2.88 2.99 14.76 15.05
205 -2.91 117.249 -0.933 -0.272 0 7.772 -0.27 7.77 0.06 0.00 2.88 3.00 15.02 15.33
206 2.469 120.708 -0.027 -0.849 0 -5.662 -0.85 -5.66 -0.04 -0.01 2.91 2.99 15.28 15.62
207 2.578 123.099 -1.74 -2.494 0 -5.957 -2.49 -5.96 -0.04 -0.02 2.91 2.96 15.69 16.07
208 2.538 120.605 -0.123 -1.116 0 -5.877 -1.12 -5.88 -0.04 -0.01 2.91 2.98 15.30 15.65
209 2.508 123.201 -1.643 -2.227 0 -5.741 -2.23 -5.74 -0.04 -0.02 2.92 2.97 15.67 16.04
210 -2.599 114.138 0.19 -0.271 0 6.782 -0.27 6.78 0.05 0.00 2.89 3.00 14.59 14.86
211 -2.49 116.529 -1.523 -1.916 0 6.487 -1.92 6.49 0.05 -0.01 2.90 2.97 14.96 15.27
212 -2.53 114.036 0.093 -0.538 0 6.566 -0.54 6.57 0.05 0.00 2.90 2.99 14.58 14.85
213 -2.56 116.632 -1.427 -1.649 0 6.702 -1.65 6.70 0.05 -0.01 2.90 2.97 14.97 15.28
214 2.119 121.325 0.467 0.529 0 -4.592 0.53 -4.59 -0.03 0.00 2.93 2.99 15.24 15.57
215 2.228 123.716 -1.245 -1.116 0 -4.887 -1.12 -4.89 -0.04 -0.01 2.93 2.98 15.57 15.94
216 2.188 121.223 0.371 0.262 0 -4.807 0.26 -4.81 -0.04 0.00 2.93 3.00 15.22 15.56
217 2.158 123.819 -1.149 -0.849 0 -4.671 -0.85 -4.67 -0.03 -0.01 2.93 2.99 15.54 15.91
218 0.399 113.77 -5.253 -12.13 0 0.502 -12.13 0.50 0.00 -0.10 2.99 2.81 15.01 15.32
219 -0.461 115.563 -5.47 -12.71 0 1.073 -12.71 1.07 0.01 -0.10 2.98 2.80 15.30 15.64
220 0.504 113.585 -5.402 -12.54 0 0.181 -12.54 0.18 0.00 -0.10 3.00 2.80 15.00 15.31
221 -0.566 115.748 -5.322 -12.29 0 1.394 -12.29 1.39 0.01 -0.10 2.98 2.81 15.31 15.66
222 0.734 121.977 3.67 9.88 0 -0.404 9.88 -0.40 0.00 0.07 2.99 2.85 15.72 16.11
223 -0.126 123.77 3.453 9.299 0 0.167 9.30 0.17 0.00 0.07 3.00 2.86 15.85 16.25
224 0.839 121.792 3.522 9.467 0 -0.725 9.47 -0.73 -0.01 0.07 2.99 2.86 15.69 16.07
225 -0.231 123.955 3.601 9.713 0 0.488 9.71 0.49 0.00 0.07 2.99 2.86 15.93 16.34
226 0.629 113.427 -5.574 -13.01 0 -0.216 -13.01 -0.22 0.00 -0.10 3.00 2.79 15.02 15.34
227 -0.231 115.22 -5.791 -13.6 0 0.355 -13.60 0.36 0.00 -0.11 2.99 2.79 15.28 15.62
228 0.734 113.242 -5.722 -13.43 0 -0.537 -13.43 -0.54 0.00 -0.11 2.99 2.79 15.06 15.38
229 -0.336 115.405 -5.642 -13.18 0 0.675 -13.18 0.68 0.01 -0.10 2.99 2.79 15.29 15.63
230 0.504 122.32 3.99 10.77 0 0.315 10.77 0.32 0.00 0.08 3.00 2.84 15.83 16.22
231 -0.356 124.113 3.774 10.19 0 0.885 10.19 0.89 0.01 0.07 2.99 2.85 16.02 16.44
232 0.609 122.135 3.842 10.36 0 -0.006 10.36 -0.01 0.00 0.08 3.00 2.85 15.75 16.13

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 62
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

233 -0.461 124.298 3.922 10.6 0 1.206 10.60 1.21 0.01 0.08 2.98 2.84 16.10 16.52
44 200 -0.063 141.051 -0.065 0.339 0 0.147 0.34 0.15 0.00 0.00 3.00 3.00 17.08 23.99 C.P.
201 0.091 140.916 -0.591 -0.691 0 -0.126 -0.69 -0.13 0.00 0.00 3.00 2.99 17.09 24.01 C.P.
202 -2.573 134.018 0.708 0.792 0 6.608 0.79 6.61 0.05 0.01 2.91 2.99 16.82 17.32
203 -2.491 136.658 -0.866 -0.299 0 6.343 -0.30 6.34 0.04 0.00 2.91 3.00 17.06 17.58
204 -2.503 133.995 0.714 0.798 0 6.393 0.80 6.39 0.04 0.01 2.91 2.99 16.81 17.30
205 -2.561 136.681 -0.872 -0.306 0 6.558 -0.31 6.56 0.04 0.00 2.91 3.00 17.08 17.60
206 2.725 132.739 0.016 -0.568 0 -6.689 -0.57 -6.69 -0.05 0.00 2.91 2.99 16.67 17.15
207 2.807 135.379 -1.558 -1.66 0 -6.954 -1.66 -6.95 -0.05 -0.01 2.91 2.98 17.07 17.59
208 2.795 132.716 0.022 -0.562 0 -6.904 -0.56 -6.90 -0.05 0.00 2.90 2.99 16.69 17.17
209 2.737 135.402 -1.563 -1.666 0 -6.739 -1.67 -6.74 -0.05 -0.01 2.91 2.98 17.06 17.57
210 -2.223 133.918 0.739 0.823 0 5.544 0.82 5.54 0.04 0.01 2.92 2.99 16.73 17.22
211 -2.141 136.558 -0.835 -0.268 0 5.279 -0.27 5.28 0.04 0.00 2.93 3.00 16.96 17.47
212 -2.153 133.895 0.745 0.83 0 5.329 0.83 5.33 0.04 0.01 2.93 2.99 16.71 17.20
213 -2.211 136.581 -0.841 -0.275 0 5.495 -0.28 5.50 0.04 0.00 2.93 3.00 16.98 17.49
214 2.375 132.839 -0.015 -0.599 0 -5.626 -0.60 -5.63 -0.04 0.00 2.92 2.99 16.60 17.07
215 2.456 135.479 -1.589 -1.691 0 -5.89 -1.69 -5.89 -0.04 -0.01 2.92 2.98 17.00 17.51
216 2.445 132.816 -0.009 -0.593 0 -5.841 -0.59 -5.84 -0.04 0.00 2.92 2.99 16.62 17.09
217 2.386 135.502 -1.595 -1.697 0 -5.675 -1.70 -5.68 -0.04 -0.01 2.92 2.98 16.99 17.50
218 0.346 130.126 0.327 -2.384 0 0.112 -2.38 0.11 0.00 -0.02 3.00 2.97 16.01 16.43
219 -0.474 129.736 0.126 -2.779 0 0.61 -2.78 0.61 0.00 -0.02 2.99 2.96 16.04 16.45
220 0.452 130.096 0.336 -2.375 0 -0.207 -2.38 -0.21 0.00 -0.02 3.00 2.97 16.02 16.43
221 -0.579 129.766 0.117 -2.788 0 0.929 -2.79 0.93 0.01 -0.02 2.99 2.96 16.07 16.48
222 0.592 139.268 -1.544 0.79 0 -0.727 0.79 -0.73 0.00 0.01 2.99 2.99 16.96 17.46
223 -0.228 138.878 -1.744 0.395 0 -0.23 0.40 -0.23 0.00 0.00 3.00 2.99 16.85 17.34
224 0.697 139.238 -1.534 0.799 0 -1.046 0.80 -1.05 -0.01 0.01 2.99 2.99 16.98 17.49
225 -0.334 138.908 -1.754 0.386 0 0.089 0.39 0.09 0.00 0.00 3.00 2.99 16.84 17.33
226 0.58 130.05 0.347 -2.362 0 -0.605 -2.36 -0.61 0.00 -0.02 2.99 2.97 16.04 16.46
227 -0.241 129.66 0.146 -2.757 0 -0.108 -2.76 -0.11 0.00 -0.02 3.00 2.96 15.99 16.40
228 0.685 130.02 0.356 -2.353 0 -0.924 -2.35 -0.92 -0.01 -0.02 2.99 2.97 16.06 16.48
229 -0.346 129.69 0.136 -2.766 0 0.211 -2.77 0.21 0.00 -0.02 3.00 2.96 16.00 16.41
230 0.359 139.344 -1.564 0.769 0 -0.01 0.77 -0.01 0.00 0.01 3.00 2.99 16.91 17.41
231 -0.462 138.954 -1.764 0.374 0 0.488 0.37 0.49 0.00 0.00 2.99 3.00 16.87 17.37
232 0.464 139.314 -1.554 0.778 0 -0.329 0.78 -0.33 0.00 0.01 3.00 2.99 16.93 17.43
233 -0.567 138.984 -1.774 0.364 0 0.807 0.36 0.81 0.01 0.00 2.99 3.00 16.90 17.40
45 200 -0.612 124.909 -0.048 0.327 0 0.638 0.33 0.64 0.00 0.00 2.99 3.00 15.32 21.36 C.P.
201 0.157 124.563 -0.708 -0.983 0 -0.808 -0.98 -0.81 -0.01 -0.01 2.99 2.99 15.34 21.39 C.P.
202 -2.648 128.533 -0.245 -0.868 0 5.977 -0.87 5.98 0.04 -0.01 2.92 2.99 16.17 16.60
203 -2.606 131.065 -1.668 -2.044 0 5.76 -2.04 5.76 0.04 -0.01 2.92 2.97 16.53 16.99
204 -2.578 128.625 -0.165 -0.644 0 5.761 -0.64 5.76 0.04 0.00 2.92 2.99 16.15 16.57
205 -2.676 130.974 -1.747 -2.268 0 5.976 -2.27 5.98 0.04 -0.02 2.92 2.97 16.55 17.02
206 2.875 123.026 0.202 0.286 0 -7.683 0.29 -7.68 -0.06 0.00 2.89 3.00 15.65 16.03
207 2.916 125.558 -1.221 -0.89 0 -7.9 -0.89 -7.90 -0.06 -0.01 2.89 2.99 16.00 16.41
208 2.944 123.117 0.281 0.51 0 -7.899 0.51 -7.90 -0.06 0.00 2.88 2.99 15.70 16.08
209 2.846 125.467 -1.301 -1.114 0 -7.684 -1.11 -7.68 -0.06 -0.01 2.89 2.98 15.99 16.40
210 -2.296 129.069 0.162 0.269 0 4.906 0.27 4.91 0.03 0.00 2.93 3.00 16.10 16.52
211 -2.255 131.601 -1.261 -0.908 0 4.69 -0.91 4.69 0.03 -0.01 2.93 2.99 16.41 16.87
212 -2.226 129.16 0.242 0.493 0 4.69 0.49 4.69 0.03 0.00 2.93 2.99 16.11 16.53

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 63
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

213 -2.324 131.509 -1.34 -1.132 0 4.905 -1.13 4.91 0.03 -0.01 2.93 2.98 16.44 16.89
214 2.523 122.491 -0.205 -0.85 0 -6.612 -0.85 -6.61 -0.05 -0.01 2.90 2.99 15.55 15.92
215 2.564 125.023 -1.628 -2.027 0 -6.829 -2.03 -6.83 -0.05 -0.01 2.90 2.97 15.94 16.35
216 2.592 122.582 -0.125 -0.626 0 -6.828 -0.63 -6.83 -0.05 0.00 2.90 2.99 15.56 15.93
217 2.495 124.932 -1.707 -2.251 0 -6.613 -2.25 -6.61 -0.05 -0.02 2.90 2.97 15.93 16.33
218 0.046 123.52 -5.316 -12.08 0 -0.049 -12.08 -0.05 0.00 -0.09 3.00 2.82 16.05 16.46
219 -0.821 121.907 -5.255 -11.87 0 0.552 -11.87 0.55 0.00 -0.09 2.99 2.82 15.89 16.29
220 0.152 123.681 -5.194 -11.74 0 -0.37 -11.74 -0.37 0.00 -0.09 2.99 2.83 16.06 16.48
221 -0.926 121.746 -5.377 -12.21 0 0.874 -12.21 0.87 0.01 -0.09 2.99 2.82 15.93 16.33
222 0.231 132.201 3.007 8.525 0 -0.844 8.53 -0.84 -0.01 0.06 2.99 2.88 16.78 17.27
223 -0.636 130.587 3.068 8.731 0 -0.242 8.73 -0.24 0.00 0.06 3.00 2.88 16.57 17.04
224 0.336 132.362 3.129 8.866 0 -1.165 8.87 -1.17 -0.01 0.06 2.98 2.88 16.85 17.35
225 -0.742 130.427 2.946 8.39 0 0.079 8.39 0.08 0.00 0.06 3.00 2.88 16.51 16.98
226 0.278 123.825 -5.052 -11.33 0 -0.768 -11.33 -0.77 -0.01 -0.08 2.99 2.83 16.08 16.50
227 -0.589 122.211 -4.991 -11.13 0 -0.167 -11.13 -0.17 0.00 -0.08 3.00 2.83 15.83 16.23
228 0.384 123.985 -4.93 -10.99 0 -1.089 -10.99 -1.09 -0.01 -0.08 2.98 2.84 16.09 16.51
229 -0.695 122.05 -5.113 -11.47 0 0.155 -11.47 0.16 0.00 -0.09 3.00 2.83 15.84 16.24
230 -0.001 131.897 2.743 7.779 0 -0.125 7.78 -0.13 0.00 0.05 3.00 2.89 16.63 17.11
231 -0.868 130.283 2.804 7.985 0 0.477 7.99 0.48 0.00 0.06 2.99 2.89 16.50 16.96
232 0.105 132.057 2.865 8.12 0 -0.446 8.12 -0.45 0.00 0.06 2.99 2.89 16.70 17.18
233 -0.974 130.123 2.682 7.644 0 0.798 7.64 0.80 0.01 0.05 2.99 2.89 16.47 16.93
50 200 -0.808 126.687 0.916 1.351 0 0.932 1.35 0.93 0.01 0.01 2.99 2.98 15.61 21.80 C.P.
201 -0.324 126.124 0.881 1.381 0 0.01 1.38 0.01 0.00 0.01 3.00 2.98 15.49 21.61 C.P.
202 -1.478 135.98 1.384 1.321 0 2.218 1.32 2.22 0.01 0.01 2.97 2.98 16.74 17.23
203 -1.515 133.082 0.084 0.273 0 2.287 0.27 2.29 0.02 0.00 2.97 3.00 16.35 16.79
204 -1.494 135.876 1.469 1.549 0 2.238 1.55 2.24 0.02 0.01 2.97 2.98 16.75 17.24
205 -1.5 133.186 -0.001 0.046 0 2.268 0.05 2.27 0.02 0.00 2.97 3.00 16.34 16.79
206 0.75 124.266 1.871 2.507 0 -2.372 2.51 -2.37 -0.02 0.02 2.97 2.96 15.54 15.91
207 0.713 121.367 0.571 1.459 0 -2.303 1.46 -2.30 -0.02 0.01 2.97 2.98 15.14 15.46
208 0.734 124.161 1.956 2.735 0 -2.352 2.74 -2.35 -0.02 0.02 2.97 2.96 15.55 15.91
209 0.729 121.472 0.487 1.232 0 -2.322 1.23 -2.32 -0.02 0.01 2.97 2.98 15.13 15.46
210 -1.569 135.389 1.82 2.476 0 2.329 2.48 2.33 0.02 0.02 2.97 2.97 16.77 17.26
211 -1.607 132.491 0.52 1.428 0 2.397 1.43 2.40 0.02 0.01 2.97 2.98 16.38 16.83
212 -1.585 135.285 1.905 2.704 0 2.348 2.70 2.35 0.02 0.02 2.97 2.96 16.78 17.27
213 -1.591 132.595 0.435 1.201 0 2.378 1.20 2.38 0.02 0.01 2.97 2.98 16.37 16.82
214 0.841 124.857 1.436 1.352 0 -2.482 1.35 -2.48 -0.02 0.01 2.96 2.98 15.53 15.89
215 0.804 121.958 0.136 0.304 0 -2.413 0.30 -2.41 -0.02 0.00 2.96 3.00 15.12 15.45
216 0.825 124.752 1.521 1.58 0 -2.463 1.58 -2.46 -0.02 0.01 2.96 2.98 15.53 15.90
217 0.82 122.063 0.051 0.077 0 -2.433 0.08 -2.43 -0.02 0.00 2.96 3.00 15.12 15.44
218 -0.448 135.196 -3.516 -9.185 0 0.178 -9.19 0.18 0.00 -0.06 3.00 2.88 17.11 17.64
219 -0.647 131.84 -3.431 -8.948 0 0.399 -8.95 0.40 0.00 -0.06 2.99 2.88 16.74 17.23
220 -0.476 135.018 -3.385 -8.838 0 0.211 -8.84 0.21 0.00 -0.06 3.00 2.88 17.07 17.59
221 -0.62 132.018 -3.562 -9.294 0 0.366 -9.29 0.37 0.00 -0.06 2.99 2.87 16.78 17.27
222 -0.621 125.746 5.364 11.79 0 0.506 11.79 0.51 0.00 0.09 2.99 2.83 16.31 16.75
223 -0.82 122.391 5.448 12.02 0 0.726 12.02 0.73 0.01 0.09 2.99 2.82 15.97 16.38
224 -0.649 125.569 5.495 12.13 0 0.539 12.13 0.54 0.00 0.09 2.99 2.82 16.32 16.76
225 -0.793 122.568 5.318 11.68 0 0.693 11.68 0.69 0.01 0.09 2.99 2.83 15.96 16.37
226 -0.501 134.847 -3.233 -8.427 0 0.242 -8.43 0.24 0.00 -0.06 3.00 2.89 17.02 17.53

227 -0.7 131.491 -3.148 -8.19 0 0.463 -8.19 0.46 0.00 -0.06 2.99 2.89 16.64 17.12
228 -0.528 134.669 -3.102 -8.08 0 0.275 -8.08 0.28 0.00 -0.05 3.00 2.89 16.97 17.48
229 -0.673 131.668 -3.279 -8.536 0 0.43 -8.54 0.43 0.00 -0.06 2.99 2.88 16.69 17.17
230 -0.569 126.096 5.081 11.03 0 0.442 11.03 0.44 0.00 0.08 2.99 2.84 16.28 16.72
231 -0.768 122.74 5.165 11.26 0 0.662 11.26 0.66 0.00 0.08 2.99 2.83 15.94 16.35
232 -0.596 125.918 5.212 11.37 0 0.475 11.37 0.48 0.00 0.08 2.99 2.84 16.29 16.73
233 -0.74 122.917 5.035 10.92 0 0.629 10.92 0.63 0.00 0.08 2.99 2.84 15.93 16.33

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 64
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

DISEÑO DE ZAPATA AISLADA ZA-1

DATOS
DATOS DE ZAPATA Columna
Geometría Dado
Df LX LZ h r d cx cz
m m m m m m m m
3.45 3.00 3.00 0.45 0.050 0.40 0.60 0.60 dado
Acciones Peso de Cimentación
Ps Mz Mx Factor Zapata Dado Relleno Suma Zapata Acero paralelo a B
Df
T T-m T-m carga T T T T
Acero paralelo
135.17 0.18 9.19 1.1 9.72 2.59 0.00 12.31 d aL
Terreno Propiedades
qadm wrell f 'c f *c f ''c B1 P fy L h
2 3 2 2 2 2
T/m T/m Kg/cm Kg/cm Kg/cm T Kg/cm L
30.00 0.00 250 200 170 0.85 147.48 4200
REFUERZO Acero paralelo
aB
LX LZ
Var @  q Var @  q
# cm # cm
6 25 0.0029 0.0704 6 25 0.0029 0.07042 Acero
Mx y paralelo
 min  max  min  max B c1
a L
0.0026 0.0152 Bien 0.0026 0.0152 Bien
RELACIONES DE ESFUERZOS My
En Zapata As tem x
c2
Cortante Penetración Flexión #4 : @
L
0.62 0.97 0.76 34

EXCENTRICIDADES DISEÑO ESTRUCTURAL DE LA ZAPATA


Figura 21. Carga Axial y momentos actuantes ZA-1.
Se obtendrán las excentricidades para calcular la reacción rectangular
DISEÑO ESTRUCTURAL DE LA ZAPATA
equivalente a la reacción trapecial.
ex = Mz/P= 0.00 m LX' = LX - 2 ex = 3.00 m
Se obtendrán las excentricidades para calcular la reacción rectangular
ez = Mx/P = 0.06 m LZ' = LZ - 2 ez = 2.88 m
equivalente a la reacción trapecial.
ex = Mz/P= 0.00 m LX' = LX - 2 ex = 3.00 m q= P = 147.48 = 17.111 T/m2
L' ez = Mx/P = 0.06 m LZ'2 =ebLZ - 2 ez = 2.88 m (LX')(LZ') 8.62
Restando a la reacción del suelo el peso del alero de la zapata y el
q= P B'
147.48 2
2e = = 17.111 T/mrelleno sobre dicho alero.
(LX')(LZ') 8.62 W zapata = 1.08 T/m2
Restando a la reacción del suelo el peso del alero de la zapata y el W relleno = 0.00 T/m2
Bloque rectangular equivalente de esfuerzos
relleno sobre dicho alero. 1.08
W zapata = 1.08 T/m2 q= 17.11 - 1.08 = 16.03 T/m2
2 eb
W relleno = 0.00 T/m2 qu= 1.1 L' x 16.03 = 17.63 T/m
2

1.08
B'
q= 17.11 - 1.08 = 16.03 T/m2 2e
qu= 1.1 x 16.03 = 17.63 T/m2

Bloque rectangular equivalente de esfuerzos


Figura 22. Bloque rectangular equivalente de esfuerzos ZA-1.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 65
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

CORTANTE
La revisión se realiza para un ancho unitario (Ancho de un metro)
Dirección Z
Actuante
x= 0.8 m Mu= 5.64 T-m Vu = 14.11 T
Resistente
Si cumple como sección ancha
Vcr  0 .5 FR bd
*
f c

Si no cumple
Vcr  FRbd (0.2  30  ) f *c

Revisando si cumple como sección ancha


a) Ancho de zapata (la menor de LX y LZ) sea mayor que 4d
b= 3.00 > 1.6 m Cumple 1

b) Espesor de zapata sea menor que 60 cm


h= 0.45 < 0.60 m Cumple 1

c) La relación M / (V x d) no excede de 2
M
V d
< 2 Þ 5.64
5.6429
= 1.00 < 2 Cumple
1
3
Entonces:
Vcr = 22,627 Kg > Vu = 14,107 kg Bien

Dirección X
Actuante
x= 0.8 m Mu= 5.64 T-m Vu = 14.11 T
Resistente
Revisando si cumple como sección ancha
a) Ancho de zapata (la menor de LX y LZ) sea mayor que 4d
b= 3.00 > 1.6 m Cumple 1

b) Espesor de zapata sea menor que 60 cm


h= 0.45 < 0.60 m Cumple 1

c) La relación M / (V x d) no excede de 2
M
V d
< 2
5.64
5.64289
= Þ 1.00 < 2 Cumple
1
3
Entonces
Vcr = 22,627 Kg > Vu = 14,107 kg Bien

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 66
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

CORTANTE POR PENETRACIÓN


Esfuerzo Cortante Actuante
c2 + d
Sc= Sección Crítica
~
Sc

d/2 d
B c1 c1+ d

h d/2

L' 2e
c2 d/2
L
V MzcABx MxcABz
AB   x  z
Ac Jcx Jcz

Figura 23. Sección crítica ZA-1.


2

Sc cABy
A P
 Mx
cABx

AB

c1 y c1+ d My
x y
c2 + d
c1+ d

x B
c2

Figura 24. Perímetro efectivo. Figura 25. Diagrama de presiones.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 67
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

donde:
2
A c = 2d ( c 1 + c 2 + 2d ) = 1.600 m
c ABx = (c 1 +d)/2 = 0.500 m
c ABz = (c 2 +d)/2 = 0.500 m
1 0.401
x  1 - 
1  0.67 (c1  d)(c2  d)
1 0.401
z  1 - 
1  0.67 (c2  d)(c1  d)
3 3 2
d(c2  d) (c2  d)d d(c1  d)(c2  d) 0.277
Jcx    
6 6 2
3 3 2
d(c1  d) (c1  d)d d(c2  d)(c1  d) 0.277
Jcz    
6 6 2
Vu = Al qu = 8 x 17.63 = 141.1 T

141.072 0.04 2.028 96 T


uABu= + + =
1.600 0.277 0.277 m2

vABu= 9.6 kg/cm2

Esfuerzo Cortante Resistente

cr1  FR(0.5  g) f * c 
14.85 Kg/cm2

cr2  FR f * c 
9.899 Kg/cm2

2
Rige ucr = 9.899 Kg/cm

Comparando
2
cr = 9.9 Kg/cm > ABu 9.6 Kg/cm2 Bien

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 68
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

DISEÑO POR FLEXIÓN


Dirección X (Al paño del dado).
Mu = qu x 2 / 2 = 12.697 T-m
MR = FR bd2 f " c q(1-0.5q) = 16.631 T-m
Comparando
MR = 16.63 T-m > Mu = 12.70 T-m Bien
Dirección X (A 1 peralte efectivo del dado).
Mu = qu x 2 / 2 = 5.6429 T-m
MR = FR bd2 f " c q(1-0.5q) = 16.63 T-m con h= 0.45 m
Comparando
MR = 16.63 T-m > Mu = 5.64 T-m Bien

Dirección Z
Mu = qu z 2 / 2 = 12.697 T-m
2
MR = FR bd f " c q(1-0.5q) = 16.631 T-m
Comparando
MR = 16.63 T-m > Mu = 12.70 T-m Bien
Dirección Z (A 1 peralte efectivo del dado).
Mu = qu z 2 / 2 = 5.6429 T-m
MR = FR bd2 f " c q(1-0.5q) = 16.63 T-m con h= 0.45 m Sc= Sección Crítica
Comparando
MR = 16.63 T-m > Mu = 5.64 T-m Bien
x Sc
REFUERZO POR TEMPERATURA
d
660x1 [cm2 ] 0.0732 cm2
aS  1.5 
EN
 
f y ( x1  100) [cm] cm
h
Con var #4 : sep @ 17.00 cm En un lecho q
ó
Con var #4 : sep @ 34.00 cm En dos lechos
L' 2e

Figura 26. Sección crítica para el diseño por flexión ZA-1.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 69
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

V.4. Diseño de zapatas corridas.


A continuación, se muestran las reacciones más desfavorables para el diseño de la zapata corrida ZC-1

REVISÓN DE PRESIÓN DE CONTACTO. ZC- 1


Datos de zapata y dados.
Zapata CT Dado
Df LX LZ h1 b h2 DZ DX q = 26.78 T/m2
m m m m m m m m qd = 22.13 T/m2
3.40 9.65 2.50 0.40 0.30 0.70 0.65 0.65 A = 24.13 m2
Peso de Cimentación Terreno
Zapata CT Dados Relleno Suma q adm w rell
T T T T T T/m 2 T/m 3 S = 6.25 m
23.16 0.00 0.00 135.86 159.02 30.00 1.90

LOAD ez' ex' P (TOTAL) MZ (TOTAL) MX (TOTAL) ex ez LX' LZ' q qd


200 0.00 0.00 -99.89 -0.26 -0.14 0.00 0.00 9.65 2.50 10.74 6.12 C.P.
201 0.00 0.00 -99.94 -0.42 -0.01 0.00 0.00 9.65 2.50 10.74 6.12 C.P.
202 0.00 3.70 -101.21 -374.07 3.34 -1.44 0.01 6.78 2.47 15.52 9.75
203 0.00 4.96 -98.44 -488.63 -1.81 -1.90 -0.01 5.85 2.49 17.69 12.13
204 0.00 4.34 -101.00 -438.52 2.95 -1.69 0.01 6.28 2.48 16.72 11.07
205 0.00 4.30 -98.65 -424.18 -1.42 -1.65 -0.01 6.36 2.49 16.28 10.59
206 0.00 -4.85 -100.46 487.73 1.69 1.88 0.01 5.89 2.49 17.71 12.16
207 0.00 -3.82 -97.69 373.16 -3.46 1.45 -0.01 6.74 2.47 15.40 9.61
208 0.00 -4.22 -100.26 423.27 1.30 1.63 0.01 6.38 2.49 16.31 10.61
209 0.00 -4.47 -97.90 437.61 -3.08 1.70 -0.01 6.24 2.48 16.62 10.96
210 0.00 6.24 -100.25 -626.06 1.51 -2.41 0.01 4.82 2.49 21.61 16.45
211 0.00 7.60 -97.49 -740.62 -3.65 -2.89 -0.01 3.88 2.47 26.78 22.13
212 0.00 6.90 -100.05 -690.51 1.12 -2.67 0.00 4.32 2.49 24.07 19.16
213 0.00 6.92 -97.69 -676.17 -3.26 -2.63 -0.01 4.38 2.47 23.67 18.71
214 0.00 -7.29 -101.42 739.72 3.53 2.84 0.01 3.97 2.47 26.53 21.86
215 0.00 -6.34 -98.65 625.15 -1.63 2.43 -0.01 4.80 2.49 21.59 16.43
216 0.00 -6.67 -101.22 675.27 3.14 2.59 0.01 4.46 2.48 23.57 18.60
217 0.00 -6.98 -98.86 689.60 -1.24 2.67 0.00 4.30 2.49 24.07 19.15
218 0.00 -0.55 -104.42 57.40 9.48 0.22 0.04 9.21 2.43 11.78 5.63
219 0.00 -3.03 -104.20 315.96 9.02 1.20 0.03 7.25 2.43 14.93 9.10
220 0.00 0.17 -104.13 -18.20 8.94 -0.07 0.03 9.51 2.43 11.38 5.19
221 0.00 -3.75 -104.49 391.56 9.57 1.49 0.04 6.68 2.43 16.26 10.56
222 0.00 3.34 -94.75 -316.83 -8.98 -1.25 -0.04 7.15 2.43 14.60 8.74
223 0.00 0.62 -94.54 -58.27 -9.44 -0.23 -0.04 9.19 2.43 11.37 5.19
224 0.00 4.15 -94.46 -392.43 -9.53 -1.55 -0.04 6.55 2.42 15.95 10.22
225 0.00 -0.18 -94.82 17.33 -8.89 0.07 -0.04 9.51 2.43 10.98 4.75
226 0.00 1.52 -103.74 -157.44 8.19 -0.60 0.03 8.45 2.44 12.75 6.70
227 0.00 -0.98 -103.52 101.12 7.73 0.39 0.03 8.88 2.44 12.11 6.00
228 0.00 2.25 -103.45 -233.04 7.64 -0.89 0.03 7.87 2.44 13.65 7.69
229 0.00 -1.70 -103.81 176.72 8.28 0.67 0.03 8.31 2.44 12.99 6.96
230 0.00 1.07 -95.44 -101.99 -7.68 -0.40 -0.03 8.85 2.44 11.79 5.64
231 0.00 -1.64 -95.22 156.57 -8.15 0.62 -0.03 8.42 2.44 12.40 6.31
232 0.00 1.87 -95.15 -177.59 -8.23 -0.70 -0.03 8.25 2.44 12.65 6.59
233 0.00 -2.43 -95.51 232.17 -7.60 0.91 -0.03 7.83 2.44 13.33 7.33

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 70
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

ZAPATA ZC-1

Datos de Zapata
Zapata Dado CT
Df LX LZ h1 DX DZ b h2
m m m m m m m m
3.40 9.65 2.50 0.40 0.65 0.65 0.30 0.70
Acciones (Cond. 211) Peso de Cimentación
Ps MZ MX Factor Relleno Zapata Dado CT Suma
T T-m T-m carga T T T T T
97.48 740.70 3.64 1.1 135.86 23.16 0.00 0.00 159.02
Terreno Propiedades
q adm w rell f'c f*c f''c P r d
2 3 2 2 2
T/m T/m Kg/cm Kg/cm Kg/cm T m m
20.00 1.90 250 200 170 256.5 0.05 0.35

Diseño Estructural de la zapata


Excentricidades
Se obtendrán las excentricidades para calcular la
reacción rectangular equivalente a la reacción trapecial.
ez = Mx/P = 0.01 m LZ'=LZ-2e z= 2.47 m
ex = Mz/P = 2.89 m LX'=LX-2ex= 3.87 m

q = P = 256.50 = 26.78437311 T/m2


(LX')( LZ') 9.58
2 eb Restando a la reacción del suelo el peso de la zapata
L'
y el relleno sobre la misma.
B' W zapata = 0.96 T/m 2
2e W relleno = 5.70 T/m 2
6.66
Bloque rectangular equivalente de esfuerzos q = 26.784 - 6.66 = 20.12 T/m 2
qu = 1.10 x 20.12 = 22.14 T/m 2

Constantes de cálculo
2
f'c = 250 kg/cm . FR = 0.9 (Flexión)
2
f*c = 200 kg/cm . FR = 0.8 (Cortante)
f"c = 170 kg/cm 2. F.C. = 1.1
2
fy = 4200 kg/cm . qD = 22.14 t/m 2 (Presión de diseño)
B1 = 0.85

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 71
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

La zapata se revisará como si fuera una zapata centrada

Diseño por flexión


La sección crítica se encuentra en el paño de la contratrabe
(NTC-6.4.1.a), considerando que la zapata se comporta como
una viga en voladizo.
M DF = 13.39 ton-m ( Momento de diseño por flexión)
El momento resistente es: MR  FR f¢¢c b d2 q  1-0.5q 
Sustituyendo valores: 1339277.0 = 18742500 q (1-0.5q)
Geometría 0.30 m Resolviendo : q = 0.07421
rTEORICO = q (f"c/fy) = 0.00300 RIGE
æ f ¢¢c 6000 Β1 ö
rMAX = 0.75 çç ÷÷  0.01518
è fy fy  6000 ø
f¢c
ρ MIN  0.7  0.00264 .
fy
As FLEXION = 10.51 cm
2
3.40 m
Con var #6 : Sep @ 27.11 c
cm
Revisión por tensión diagonal Bien
Considerando que la zapata actúa como una viga ancha de tal
0.40 m
forma que las grietas diagonales potenciales se extenderían
(d=0.35)
en todo el ancho de la zapata, la sección crítica se
encuentra a una distancia "d" del paño de la contratrabe
(NTC-2.5.4). Los elementos mecánicos en esta sección son:
B= 2.50 m
V DC = 16.60 ton ( Fuerza cortante de diseño )
B>4d Es elemento ancho
M DC = 6.23 ton-m ( Momento de diseño por cortante)
Revisando las condiciones :
Armado de zapata
M/Vd = 1.07 < 2,y h < 0.6 m
Entonces se aplicará la expresión (2.20) :
Si r< 0.015: Vcr= F R b d(0.2 + 20r) f*c ..... (2.19)
Si r> 0.015: Vcr= F R 0.5 b d f*c ..... (2.20)
Sustituyendo valores : 16,602.6 = 565.69 d
Resolviendo: d TEORICO = 29.3 cm, < d= 35.0 cm
Acero por temperatura
#4 @ 25 El área de refuerzo que se suministre no será menor que:
Con 1.5 x 660h
aS  var  0.0673 cm 2/cm (5.3)
fy h  100

r=0.05m Con var #4 : Sep1 @ 37.62 cm


O considerando un porcentaje mín. = 0.003
#6 @ 25.0 cm (RIGE) Con var #4 : Sep2 @ 24.13 cm
#4 @ 25.0 cm . Queda: #4 : Sep @ 24.13 cm

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 72
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

A continuación, se muestran las reacciones más desfavorables para el diseño de la zapata corrida ZC-2

REVISÓN DE PRESIÓN DE CONTACTO. ZC- 2


Datos de zapata y dados.
Zapata CT Dado
Df LX LZ h1 b h2 DZ DX q = 27.52 T/m2
m m m m m m m m qd = 23.08 T/m2
3.35 2.20 9.20 0.35 0.30 0.70 0.65 0.65 A = 20.24 m2
Peso de Cimentación Terreno
Zapata CT Dados Relleno Suma q adm w rell
T T T T T T/m 2 T/m 3 S = 7.02 m
17.00 0.00 0.00 56.77 73.77 30.00 1.90

LOAD ez' ex' P (TOTAL) MZ (TOTAL) MX (TOTAL) ex ez LX' LZ' q qd


200 -1.30 0.00 -138.52 2.46 -180.00 0.01 -0.85 2.18 7.50 13.00 9.68 C.P.
201 -1.48 0.00 -136.64 -11.49 -202.02 -0.05 -0.96 2.09 7.28 13.82 10.93 C.P.
202 -2.31 0.00 -227.31 -28.07 -524.35 -0.09 -1.74 2.01 5.72 26.16 21.58
203 -2.42 0.00 -225.68 -28.72 -546.18 -0.10 -1.82 2.01 5.55 26.86 22.35
204 -2.31 0.00 -227.96 -28.09 -527.60 -0.09 -1.75 2.01 5.70 26.27 21.71
205 -2.41 0.00 -225.04 -28.70 -542.93 -0.10 -1.82 2.01 5.57 26.74 22.22
206 3.99 0.00 -39.14 -8.97 156.20 -0.08 1.38 2.04 6.43 8.60 2.26
207 3.58 0.00 -37.52 -9.62 134.36 -0.09 1.21 2.03 6.79 8.09 1.71
208 3.84 0.00 -39.79 -8.99 152.94 -0.08 1.35 2.04 6.51 8.55 2.21
209 3.73 0.00 -36.87 -9.60 137.61 -0.09 1.24 2.03 6.71 8.13 1.75
210 -2.34 0.00 -231.09 -28.18 -541.84 -0.09 -1.78 2.02 5.65 26.80 22.28
211 -2.46 0.00 -229.47 -28.82 -563.67 -0.10 -1.86 2.01 5.48 27.52 23.08
212 -2.35 0.00 -231.74 -28.20 -545.09 -0.09 -1.78 2.02 5.63 26.92 22.41
213 -2.45 0.00 -228.82 -28.81 -560.41 -0.10 -1.85 2.01 5.50 27.40 22.94
214 4.91 0.00 -35.36 -8.87 173.68 -0.08 1.59 2.04 6.02 8.90 2.60
215 4.50 0.00 -33.73 -9.51 151.85 -0.09 1.41 2.02 6.37 8.34 1.98
216 4.73 0.00 -36.00 -8.89 170.42 -0.08 1.55 2.04 6.09 8.84 2.53
217 4.69 0.00 -33.09 -9.50 155.10 -0.09 1.45 2.02 6.30 8.39 2.04
218 -0.95 0.00 -167.00 -5.26 -158.09 -0.02 -0.66 2.16 7.89 14.16 8.38
219 0.05 0.00 -115.39 -13.88 5.56 -0.07 0.03 2.05 9.14 10.08 3.89
220 -0.97 0.00 -168.13 -5.29 -163.34 -0.02 -0.68 2.16 7.85 14.29 8.53
221 0.09 0.00 -114.26 -13.84 10.81 -0.07 0.06 2.05 9.08 10.08 3.90
222 -2.59 0.00 -151.88 -2.16 -393.14 -0.01 -1.74 2.18 5.72 18.10 12.72
223 -2.29 0.00 -100.28 -10.78 -229.48 -0.06 -1.32 2.08 6.56 12.77 6.86
224 -2.60 0.00 -153.02 -2.20 -398.38 -0.01 -1.76 2.18 5.69 18.29 12.92
225 -2.26 0.00 -99.15 -10.75 -224.23 -0.06 -1.30 2.08 6.61 12.61 6.68
226 -1.00 0.00 -169.15 -5.33 -168.93 -0.02 -0.70 2.16 7.81 14.43 8.68
227 -0.04 0.00 -117.55 -13.94 -5.27 -0.07 -0.03 2.05 9.14 10.18 4.01
228 -1.02 0.00 -170.29 -5.36 -174.18 -0.02 -0.71 2.16 7.77 14.56 8.83
229 0.00 0.00 -116.41 -13.91 -0.03 -0.07 0.00 2.05 9.20 10.07 3.88
230 -2.55 0.00 -149.73 -2.10 -382.30 -0.01 -1.71 2.18 5.78 17.73 12.31
231 -2.23 0.00 -98.13 -10.72 -218.64 -0.06 -1.27 2.08 6.66 12.44 6.49
232 -2.57 0.00 -150.86 -2.13 -387.54 -0.01 -1.73 2.18 5.75 17.91 12.51
233 -2.20 0.00 -96.99 -10.68 -213.39 -0.06 -1.25 2.07 6.70 12.28 6.32

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 73
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

ZAPATA ZC-2

Datos de Zapata
Zapata Dado CT
Df LX LZ h1 DX DZ b h2
m m m m m m m m
3.35 2.20 9.20 0.35 0.65 0.65 0.30 0.70
Acciones (Cond. 211) Peso de Cimentación
Ps MZ MX Factor Relleno Zapata Dado CT Suma
T T-m T-m carga T T T T T
229.47 28.82 563.67 1.1 56.77 17.00 0.00 0.00 73.77
Terreno Propiedades
q adm w rell f'c f*c f''c P r d
2 3 2 2 2
T/m T/m Kg/cm Kg/cm Kg/cm T m m
30.00 1.90 250 200 170 303.2 0.05 0.30

Diseño Estructural de la zapata


Excentricidades
Se obtendrán las excentricidades para calcular la
reacción rectangular equivalente a la reacción trapecial.
ez = Mx/P = 1.86 m LZ'=LZ-2e z= 5.48 m
ex = Mz/P = 0.10 m LX'=LX-2ex= 2.01 m

q = P = 303.24 = 27.51948653 T/m2


(LX')( LZ') 11.02
2 eb Restando a la reacción del suelo el peso de la zapata
L'
y el relleno sobre la misma.
B' W zapata = 0.84 T/m 2
2e W relleno = 5.70 T/m 2
6.54
Bloque rectangular equivalente de esfuerzos q = 27.519 - 6.54 = 20.98 T/m 2
qu = 1.10 x 20.98 = 23.08 T/m 2

Constantes de cálculo
2
f'c = 250 kg/cm . FR = 0.9 (Flexión)
2
f*c = 200 kg/cm . FR = 0.8 (Cortante)
f"c = 170 kg/cm 2. F.C. = 1.1
2
fy = 4200 kg/cm . qD = 23.08 t/m 2 (Presión de diseño)
B1 = 0.85

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 74
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

La zapata se revisará como si fuera una zapata centrada

Diseño por flexión


La sección crítica se encuentra en el paño de la contratrabe
(NTC-6.4.1.a), considerando que la zapata se comporta como
una viga en voladizo.
M DF = 10.41 ton-m ( Momento de diseño por flexión)
El momento resistente es: MR  FR f¢¢c b d2 q  1-0.5q 
Sustituyendo valores: 1041369.3 = 13770000 q (1-0.5q)
Geometría 0.30 m Resolviendo : q = 0.07872
rTEORICO = q (f"c/fy) = 0.00319 RIGE
æ f ¢¢c 6000 Β1 ö
rMAX = 0.75 çç ÷÷  0.01518
è fy fy  6000 ø
f¢c
ρ MIN  0.7  0.00264 .
fy
As FLEXION = 9.56 cm
2
3.35 m
Con var #6 : Sep @ 29.82 c
cm
Revisión por tensión diagonal Bien
Considerando que la zapata actúa como una viga ancha de tal
0.35 m
forma que las grietas diagonales potenciales se extenderían
(d=0.30)
en todo el ancho de la zapata, la sección crítica se
encuentra a una distancia "d" del paño de la contratrabe
(NTC-2.5.4). Los elementos mecánicos en esta sección son:
B= 2.20 m
V DC = 15.00 ton ( Fuerza cortante de diseño )
B>4d Es elemento ancho
M DC = 4.88 ton-m ( Momento de diseño por cortante)
Revisando las condiciones :
Armado de zapata
M/Vd = 1.08 < 2,y h < 0.6 m
Entonces se aplicará la expresión (2.20) :
Si r< 0.015: Vcr= F R b d(0.2 + 20r) f*c ..... (2.19)
Si r> 0.015: Vcr= F R 0.5 b d f*c ..... (2.20)
Sustituyendo valores : 15,000.3 = 565.69 d
Resolviendo: d TEORICO = 26.5 cm, < d= 30.0 cm
Acero por temperatura
#4 @ 25 El área de refuerzo que se suministre no será menor que:
Con 1.5 x 660h
aS  var  0.0611 cm 2/cm (5.3)
fy h  100

r=0.05m Con var #4 : Sep1 @ 41.46 cm


O considerando un porcentaje mín. = 0.003
#6 @ 30.0 cm (RIGE) Con var #4 : Sep2 @ 28.15 cm
#4 @ 25.0 cm . Queda: #4 : Sep @ 28.15 cm

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 75
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

A continuación, se muestran las reacciones más desfavorables para el diseño de la zapata corrida ZC-3

REVISIÓN DE PRESIÓN DE CONTACTO. ZC-3


Datos de zapata y dados.
Zapata Muro Relleno ext.
Df LX LZ h1 Int b1 esp b2 Ext b3 h3-Df q = 29.7 T/m2
m m m m m m m m qd = 25.1 T/m2
3.45 29.00 2.80 0.60 2.30 0.30 0.20 2.85 A = 81.20 m2
Peso de Cimentación Terreno
Zapata Muro Rell ext Relleno Suma q adm w rell
T T T T T T/m 2 T/m 3 S = 25.00 m
116.93 0.00 31.41 0.00 148.34 30.00 1.90

LOAD ez' ex' MZ(Volteo) MX(Volteo) P (TOTAL) MZ (TOTAL) MX (TOTAL) ex ez LX' LZ' q qd
200 0.00 0.13 0.00 407.21 -325.77 -43.70 402.55 -0.09 0.85 28.82 1.10 14.93 12.12 C.P.
201 0.00 0.12 0.00 401.03 -320.82 -39.92 445.03 -0.09 0.95 28.83 0.90 18.02 16.75 C.P.
202 0.00 1.55 0.00 327.87 -262.30 -407.66 349.35 -0.99 0.85 27.01 1.10 13.84 7.68
203 0.00 1.61 0.00 454.73 -363.78 -587.11 499.01 -1.15 0.97 26.71 0.85 22.53 17.24
204 0.00 1.89 0.00 329.03 -263.22 -497.81 350.50 -1.21 0.85 26.58 1.10 14.12 7.99
205 0.00 1.37 0.00 453.58 -362.86 -496.96 497.86 -0.97 0.97 27.06 0.85 22.17 16.85
206 0.00 -2.06 0.00 328.93 -263.15 540.84 352.41 1.31 0.86 26.37 1.09 14.35 8.25
207 0.00 -0.99 0.00 455.79 -364.63 361.38 502.07 0.70 0.98 27.59 0.84 22.07 16.73
208 0.00 -1.71 0.00 330.08 -264.07 450.67 353.56 1.09 0.86 26.81 1.09 14.17 8.05
209 0.00 -1.24 0.00 454.64 -363.71 451.52 500.92 0.88 0.98 27.24 0.84 22.29 16.98
210 0.00 2.92 0.00 332.70 -266.16 -777.52 354.18 -1.88 0.85 25.25 1.09 15.05 9.01
211 0.00 2.60 0.00 459.55 -367.64 -956.96 503.84 -1.85 0.98 25.29 0.85 24.09 18.95
212 0.00 3.25 0.00 333.85 -267.08 -867.66 355.33 -2.09 0.86 24.82 1.09 15.36 9.36
213 0.00 2.36 0.00 458.40 -366.72 -866.78 502.69 -1.68 0.98 25.63 0.85 23.69 18.52
214 0.00 -3.51 0.00 324.11 -259.29 910.67 347.58 2.23 0.85 24.53 1.09 15.18 9.16
215 0.00 -2.03 0.00 450.97 -360.77 731.22 497.24 1.44 0.98 26.13 0.85 23.02 17.78
216 0.00 -3.15 0.00 325.26 -260.21 820.52 348.72 2.01 0.85 24.98 1.09 14.96 8.92
217 0.00 -2.28 0.00 449.81 -359.85 821.36 496.10 1.62 0.98 25.77 0.85 23.27 18.06
218 0.00 -1.13 0.00 158.13 -126.50 143.13 267.33 0.52 0.97 27.96 0.85 11.50 5.11
219 0.00 -3.09 0.00 158.52 -126.81 391.73 268.60 1.42 0.98 26.15 0.85 12.41 6.11
220 0.00 -0.25 0.00 159.58 -127.66 32.19 268.78 0.12 0.97 28.77 0.85 11.26 4.84
221 0.00 -4.00 0.00 157.07 -125.66 502.68 267.15 1.83 0.98 25.33 0.85 12.73 6.46
222 0.00 0.90 0.00 616.95 -493.56 -441.90 643.39 -0.69 1.00 27.62 0.80 29.22 24.60
223 0.00 0.39 0.00 617.33 -493.86 -193.32 644.65 -0.30 1.00 28.40 0.79 28.54 23.85
224 0.00 1.12 0.00 618.40 -494.72 -552.87 644.84 -0.86 1.00 27.28 0.79 29.67 25.10
225 0.00 0.17 0.00 615.89 -492.71 -82.36 643.21 -0.13 1.00 28.74 0.79 28.12 23.39
226 0.00 1.21 0.00 161.97 -129.58 -157.37 271.15 -0.57 0.98 27.87 0.85 11.75 5.39
227 0.00 -0.70 0.00 162.36 -129.88 91.23 272.42 0.33 0.98 28.34 0.84 11.66 5.29
228 0.00 2.05 0.00 163.42 -130.74 -268.29 272.61 -0.96 0.98 27.08 0.85 12.18 5.86
229 0.00 -1.57 0.00 160.91 -128.73 202.19 270.97 0.73 0.98 27.54 0.84 11.92 5.57
230 0.00 0.29 0.00 613.11 -490.49 -141.39 639.57 -0.22 1.00 28.56 0.80 28.04 23.31
231 0.00 -0.22 0.00 613.49 -490.80 107.19 640.83 0.17 1.00 28.66 0.79 28.06 23.32
232 0.00 0.51 0.00 614.56 -491.65 -252.36 641.02 -0.39 1.00 28.21 0.80 28.47 23.78
233 0.00 -0.45 0.00 612.05 -489.64 218.13 639.38 0.34 1.00 28.32 0.80 28.32 23.61

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 76
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

ZAPATA ZC-3

Datos de Zapata
Zapata Relleno ext. Muro Factor r
Df LX LZ hprom Ext b3 h3-Df esp b2 Int b1 carga m
m m m m m m m m 1.1 0.05
3.45 29.00 2.80 0.60 0.20 2.85 0.30 2.30

Diseño Estructural de la zapata


Excentricidades

De la tabla anterior tenemos lo siguiente:

q = 29.67 T/m2

Restando a la reacción del suelo el peso de la zapata


2 eb
L' y el relleno sobre la misma.
B' W zapata = 1.44 T/m 2
2e W relleno = 5.42 T/m 2
6.86
Bloque rectangular equivalente de esfuerzos q = 29.670 - 6.86 = 22.82 T/m 2
qu = 1.10 x 22.82 = 25.10 T/m 2

Constantes de cálculo
2
f'c = 250 kg/cm . FR = 0.90 (Flexión)
f'c = 24.50 Mpa FR = 0.75 (Cortante)
F.C. = 1.0
2
fy = 4200 kg/cm . qD = 25.10 t/m 2 (Presión de diseño)
B1 = 0.850 Sflexion = 1.00
Scortante = 1.00

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 77
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Diseño por flexión


La sección crítica se encuentra en el paño de la contratrabe
(A.C.I. 350-06), considerando que la zapata se comporta como
una viga en voladizo.
M DF = 66.38 ton-m
( Momento de diseño por flexión)
Geometría 0.30 m El momento resistente es: M R  F R f¨c b d w  1 - 0.59 w 
2

Sustituyendo valores: 6638024.3 = 68062500 q (1-0.59q)


Resolviendo : q = 0.10390
rTEORICO = q (f`c/fy) = 0.00618 RIGE
æ 0.85f`c 6115 Β1 ö
rMAX = çç ÷
fy  6115 ÷ø
0.75 0.01912
3.45 m è fy
0.20 f ¢c 14
 MIN  0.80  0.00333 .
2.30 fy fy
As FLEXION = 34.01 cm2
0.60 m Con var #8 : Sep @ 14.90 c
cm
(d=0.55) Revisión por tensión diagonal Bien
Considerando que la zapata actúa como una viga ancha de tal
forma que las grietas diagonales potenciales se extenderían
B= 2.80 m en todo el ancho de la zapata, la sección crítica se
B>4d Es elemento ancho encuentra a una distancia "d" del paño de la contratrabe
(A.C.I. 350-06). Los elementos mecánicos en esta sección son:
Armado de zapata V DC = 38.27 ton ( Fuerza cortante de diseño )
M DC = 29.18 ton-m ( Momento de diseño por cortante)
Revisión por cortante
Para elementos sometidos únicamente a cortante y flexión,
la resistencia del concreto es: Vcr = b d(0.53) f`c
Sustituyendo valores : 38,272.2 = 838.00 d
Resolviendo: d TEORICO = 45.7 cm, < d= 55.0 cm
Acero por temperatura
#5 @ 20 El área de refuerzo que se suministre no será menor que:
 MINvar
Con  0.003333
As por una cara = 9.17 cm2
r=0.05m Con var #5 : Sep1 @ 21.59 cm
O considerando un porcentaje mín. = 0.003
#8 @ 15.0 cm (RIGE) Con var #5 : Sep2 @ 23.99 cm
#5 @ 20.0 cm . Queda: #5 : Sep @ 21.59 cm

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 78
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

V.5. Diseño de losas de entrepiso y azoteas.

Figura 27. Ubicación de tablero más desfavorable

El tablero más desfavorable para el diseño de la losa de entrepiso resultó ser el que se encuentra en la esquina
de la sub-estación, así mismo, el tablero de azotea más desfavorable, por las dimensiones de los claros resultó
ser el que se encuentra en el cuarto de HVAC.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 79
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

DISEÑO DE LOSA DE AZOTEA PARA SUB-ESTACIÓN DERIVADA NÚMERO 8


DATOS:
¿LOS ELEMENTOS SE CUELAN MONOLÍTICAMENTE CON LA LOSA? NO
DIMENSIONES DEL TABLERO MÁS GRANDE EN cm. 1.5
L1 = 300 CONTINUO 300.00
L2 = 300 DISCONTINUO 450.00
L3 = 312.5 DISCONTINUO 468.75
L4 = 312.5 CONTINUO 312.50

LADO CORTO a1: 3.00 m


LADO LARGO a2: 3.13 m

CARGAS CONSIDERADAS:

PESO VOLUMÉTRICO DEL CONCRETO = 2.400 T / m3


CARGA ADICIONAL RCDF = 0.040 T / m2
CARGAS (RELLENO, VIVA, ENLADRILLADO, ETC) = 0.339 T / m2
CARGA DE DISEÑO = 667.00 Kg/m2

CONSTANTES:
FR (V, M) = 0.8 0.9
FC = 1.5
f'c = 250 kg / cm2
CONCRETO CLASE: 1 250
fy = 4,200 kg / cm2
f*c = 200 kg / cm2
f''c = 170 kg / cm2
β1 = 0.85

CÁLCULO DE PORCENTAJE MÁXIMO DE REFUERZO.

fc'' 6000B1
Pb,máx  Pb, máx = 0.02024
fy fy  6000

CÁLCULO DEL PERALTE EFECTIVO MÍNIMO

EL PERALTE MÍNIMO SE CALCULARA CON ESTA EXPRESIÓN


Perímetro
d ...(1) SIEMPRE Y CUANDO SE CUMPLA QUE:
L
L  250 _ para _ clase _ 1_ y W  380(Kg / m 2 ) fs  2,520(Kg / cm 2 )
170 _ para _ clase _ 2

PARA COMBINACIONES DIFERENTES SE USARÁ: d


Coef . * Perímetro
...(2) Coef .  0.032 4 fs * W
L
fs  0.6fy

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 80
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

LA ECUACIÓN A UTILIZAR ES: 2

PERALTE PROPUESTO = 12 cm
PERALTE CALCULADO = 7.06 cm

RECUBRIMIENTO = 2.5 cm

PERALTE TOTAL = 10.00 cm

REVISIÓN POR FUERZA CORTANTE DEL PERALTE.

æ a1 öæ a1 ö CORTANTE ACTUANTE
V  ç - d ÷ ç 0.95 - 0.5 w
a2 ÷ø
VU = 757.08
è2 øè

CORTANTE RESISTENTE
0.5FR bd fc* VR = 5,656.85

SE ACEPTA EL PERALTE POR CORTANTE

REVISIÓN POR FLEXIÓN DEL PERALTE.

m = a1 / a2 = 0.96
PARA EL LADO CORTO.
PARA EL MOMENTO NEGATIVO: PARA EL MOMENTO POSITIVO.
Coef. = 443.20 1 Coef. = 227.80
MOMENTO = 266.05 Kg*m / m MOMENTO = 136.75 Kg*m / m

PARA EL LADO LARGO


PARA EL MOMENTO NEGATIVO: PARA EL MOMENTO POSITIVO.
Coef. = 438.20 1 Coef. = 155.20
MOMENTO = 263.05 Kg*m / m MOMENTO = 93.17 Kg*m / m

ACERO MÁXIMO PERMISIBLE = 10.12 cm2 / m


q= 0.5000

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 81
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

PARA EL LADO CORTO.


q(1-0.5q) = 0.069556 q(1-0.5q) = 0.015889
a b a b c
0.5 -1 0.069556 0.5 -1 0.015889
(-) (+) (-) (+)
q= 0.07216 1.92784 q= 0.01602 1.98398
p= 0.00292 p= 0.00065
EL PERALTE ES ADECUADO POR FLEXIÓN EL PERALTE ES ADECUADO POR FLEXIÓN

As = 1.46 cm2 / m As = 0.32 cm2 / m

PARA EL LADO LARGO


q(1-0.5q) = 0.068772 q(1-0.5q) = 0.010825
a b c a b c
0.5 -1 0.068772 0.5 -1 0.010825
(-) (+) (-) (+)
q= 0.07131 1.92869 q= 0.01088 1.98912
p= 0.00289 p= 0.00044
EL PERALTE ES ADECUADO POR FLEXIÓN EL PERALTE ES ADECUADO POR FLEXIÓN

As = 1.44 cm2 / m As = 0.22 cm2 / m

COLOCACIÓN ACERO REFUERZO

as, mín = 1.43 cm2 / m


660 X1
as1  SEPARACIÓN MÁXIMA
fy ( X1  100) 3.5X1 = 35 cm
50 cm
X1 = 10.00 cm

ACERO # = 3
as = 0.71 cm2

SEPARACIÓN TEÓRICA.

as * 100 SEPARACIÓN EN cm PARA:


S NEGATIVO POSITIVO
As 48.79 49.88 48.79
49.37 49.88 49.88

SEPARACIÓN DE VARILLAS

DIMENSIÓN DE FRANJAS
FRANJAS CENTRALES = 1.56 II AL CORTO 1.50 II AL LARGO
FRANJAS EXTREMAS = 0.78 II AL CORTO 0.75 II AL LARGO

SEPARACIÓN DE ACERO EN LAS FRANJAS


FRANJAS CENTRALES = 35.00 48.79
FRANJAS EXTREMAS = 35.00 49.88

SEPARACIÓN AL CENTRO DEL TABLERO = 35.00 cm


SEPARACIÓN EN LOS EXTREMOS DEL TABLERO = 35.00 cm

ACERO DE REFUERZO
RCDF. ING. CHACÓN.
BAYONETAS = 50 cm @ 35.00 60 cm
BASTONES = 60 cm @ 35.00 75 cm

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 82
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

DISEÑO DE LOSA DE ENTREPISO (AZOTEA) PARA SUB-ESTACIÓN DERIVADA NÚMERO 8


DATOS:
¿LOS ELEMENTOS SE CUELAN MONOLÍTICAMENTE CON LA LOSA? NO
DIMENSIONES DEL TABLERO MÁS GRANDE EN cm. 1.5
L1 = 300 DISCONTINUO 450.00
L2 = 300 CONTINUO 300.00
L3 = 312.5 CONTINUO 312.50
L4 = 312.5 CONTINUO 312.50

LADO CORTO a1: 3.00 m


LADO LARGO a2: 3.13 m

CARGAS CONSIDERADAS:

PESO VOLUMÉTRICO DEL CONCRETO = 2.400 T / m3


CARGA ADICIONAL RCDF = 0.040 T / m2
CARGAS (RELLENO, VIVA, ENLADRILLADO, ETC) = 0.704 T / m2
CARGA DE DISEÑO = 1,032.00 Kg/m2

CONSTANTES:
FR (V, M) = 0.8 0.9
FC = 1.5
f'c = 250 kg / cm2
CONCRETO CLASE: 1 250
fy = 4,200 kg / cm2
f*c = 200 kg / cm2
f''c = 170 kg / cm2
β1 = 0.85

CÁLCULO DE PORCENTAJE MÁXIMO DE REFUERZO.

fc'' 6000B1
Pb,máx  Pb, máx = 0.02024
fy fy  6000

CÁLCULO DEL PERALTE EFECTIVO MÍNIMO

EL PERALTE MÍNIMO SE CALCULARA CON ESTA EXPRESIÓN


Perímetro
d ...(1) SIEMPRE Y CUANDO SE CUMPLA QUE:
L
L  250 _ para _ clase _ 1_ y W  380(Kg / m 2 ) fs  2,520(Kg / cm 2 )
170 _ para _ clase _ 2

PARA COMBINACIONES DIFERENTES SE USARÁ: d


Coef . * Perímetro
...(2) Coef .  0.032 4 fs * W
L
fs  0.6fy

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 83
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

LA ECUACIÓN A UTILIZAR ES: 2

PERALTE PROPUESTO = 12 cm
PERALTE CALCULADO = 7.07 cm

RECUBRIMIENTO = 2.5 cm

PERALTE TOTAL = 9.57 cm

REVISIÓN POR FUERZA CORTANTE DEL PERALTE.

æ a1 öæ a1 ö CORTANTE ACTUANTE
V  ç - d ÷ ç 0.95 - 0.5 w
a2 ÷ø
VU = 1,174.99
è2 øè

CORTANTE RESISTENTE
0.5FR bd fc* VR = 5,412.35

SE ACEPTA EL PERALTE POR CORTANTE

REVISIÓN POR FLEXIÓN DEL PERALTE.

m = a1 / a2 = 0.96
PARA EL LADO CORTO.
PARA EL MOMENTO NEGATIVO: PARA EL MOMENTO POSITIVO.
Coef. = 790.40 1 Coef. = 600.30
MOMENTO = 734.12 Kg*m / m MOMENTO = 557.56 Kg*m / m

PARA EL LADO LARGO


PARA EL MOMENTO NEGATIVO: PARA EL MOMENTO POSITIVO.
Coef. = 0.00 1 Coef. = 520.00
MOMENTO = 0.00 Kg*m / m MOMENTO = 482.98 Kg*m / m

ACERO MÁXIMO PERMISIBLE = 9.24 cm2 / m


q= 0.5000

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 84
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

PARA EL LADO CORTO.


q(1-0.5q) = 0.229968 q(1-0.5q) = 0.072951
a b a b c
0.5 -1 0.229968 0.5 -1 0.072951
(-) (+) (-) (+)
q= 0.26511 1.73489 q= 0.07583 1.92417
p= 0.01073 p= 0.00307
EL PERALTE ES ADECUADO POR FLEXIÓN EL PERALTE ES ADECUADO POR FLEXIÓN

As = 4.90 cm2 / m As = 1.40 cm2 / m

PARA EL LADO LARGO


q(1-0.5q) = 0.000000 q(1-0.5q) = 0.063193
a b c a b c
0.5 -1 0.000000 0.5 -1 0.063193
(-) (+) (-) (+)
q= 0.00000 2.00000 q= 0.06533 1.93467
p= 0.00000 p= 0.00264
EL PERALTE ES ADECUADO POR FLEXIÓN EL PERALTE ES ADECUADO POR FLEXIÓN

As = 0.00 cm2 / m As = 1.21 cm2 / m

COLOCACIÓN ACERO REFUERZO

as, mín = 1.37 cm2 / m


660 X1
as1  SEPARACIÓN MÁXIMA
fy ( X1  100) 3.5X1 = 33.48721318 cm
50 cm
X1 = 9.57 cm

ACERO # = 3
as = 0.71 cm2

SEPARACIÓN TEÓRICA.

as * 100 SEPARACIÓN EN cm PARA:


S NEGATIVO POSITIVO
As 14.54 50.83 14.54
51.93 51.93 50.83

SEPARACIÓN DE VARILLAS

DIMENSIÓN DE FRANJAS
FRANJAS CENTRALES = 1.56 II AL CORTO 1.50 II AL LARGO
FRANJAS EXTREMAS = 0.78 II AL CORTO 0.75 II AL LARGO

SEPARACIÓN DE ACERO EN LAS FRANJAS


FRANJAS CENTRALES = 14.54 14.54
FRANJAS EXTREMAS = 33.49 50.00

SEPARACIÓN AL CENTRO DEL TABLERO = 14.00 cm


SEPARACIÓN EN LOS EXTREMOS DEL TABLERO = 33.00 cm

ACERO DE REFUERZO
RCDF. ING. CHACÓN.
BAYONETAS = 50 cm @ 14.00 60 cm
BASTONES = 60 cm @ 33.00 75 cm

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 85
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

DISEÑO DE LOSA DE AZOTEA PARA SUB-ESTACIÓN DERIVADA NÚMERO 8


DATOS:
¿LOS ELEMENTOS SE CUELAN MONOLÍTICAMENTE CON LA LOSA? NO
DIMENSIONES DEL TABLERO MÁS GRANDE EN cm. 1.5
L1 = 300 DISCONTINUO 450.00
L2 = 300 DISCONTINUO 450.00
L3 = 312.5 DISCONTINUO 468.75
L4 = 312.5 CONTINUO 312.50

LADO CORTO a1: 3.00 m


LADO LARGO a2: 3.13 m

CARGAS CONSIDERADAS:

PESO VOLUMÉTRICO DEL CONCRETO = 2.400 T / m3


CARGA ADICIONAL RCDF = 0.040 T / m2
CARGAS (RELLENO, VIVA, ENLADRILLADO, ETC) = 0.339 T / m2
CARGA DE DISEÑO = 667.00 Kg/m2

CONSTANTES:
FR (V, M) = 0.8 0.9
FC = 1.5
f'c = 250 kg / cm2
CONCRETO CLASE: 1 250
fy = 4,200 kg / cm2
f*c = 200 kg / cm2
f''c = 170 kg / cm2
β1 = 0.85

CÁLCULO DE PORCENTAJE MÁXIMO DE REFUERZO.

fc'' 6000B1
Pb,máx  Pb, máx = 0.02024
fy fy  6000

CÁLCULO DEL PERALTE EFECTIVO MÍNIMO

EL PERALTE MÍNIMO SE CALCULARA CON ESTA EXPRESIÓN


Perímetro
d ...(1) SIEMPRE Y CUANDO SE CUMPLA QUE:
L
L  250 _ para _ clase _ 1_ y W  380(Kg / m 2 ) fs  2,520(Kg / cm 2 )
170 _ para _ clase _ 2

PARA COMBINACIONES DIFERENTES SE USARÁ: d


Coef . * Perímetro
...(2) Coef .  0.032 4 fs * W
L
fs  0.6fy

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 86
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

LA ECUACIÓN A UTILIZAR ES: 2

PERALTE PROPUESTO = 12 cm
PERALTE CALCULADO = 7.75 cm

RECUBRIMIENTO = 2.5 cm

PERALTE TOTAL = 10.00 cm

REVISIÓN POR FUERZA CORTANTE DEL PERALTE.

æ a1 öæ a1 ö CORTANTE ACTUANTE
V  ç - d ÷ ç 0.95 - 0.5 w
a2 ÷ø
VU = 757.08
è2 øè

CORTANTE RESISTENTE
0.5FR bd fc* VR = 5,656.85

SE ACEPTA EL PERALTE POR CORTANTE

REVISIÓN POR FLEXIÓN DEL PERALTE.

m = a1 / a2 = 0.96
PARA EL LADO CORTO.
PARA EL MOMENTO NEGATIVO: PARA EL MOMENTO POSITIVO.
Coef. = 443.20 1 Coef. = 227.80
MOMENTO = 266.05 Kg*m / m MOMENTO = 136.75 Kg*m / m

PARA EL LADO LARGO


PARA EL MOMENTO NEGATIVO: PARA EL MOMENTO POSITIVO.
Coef. = 438.20 1 Coef. = 155.20
MOMENTO = 263.05 Kg*m / m MOMENTO = 93.17 Kg*m / m

ACERO MÁXIMO PERMISIBLE = 10.12 cm2 / m


q= 0.5000

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 87
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

PARA EL LADO CORTO.


q(1-0.5q) = 0.069556 q(1-0.5q) = 0.015889
a b a b c
0.5 -1 0.069556 0.5 -1 0.015889
(-) (+) (-) (+)
q= 0.07216 1.92784 q= 0.01602 1.98398
p= 0.00292 p= 0.00065
EL PERALTE ES ADECUADO POR FLEXIÓN EL PERALTE ES ADECUADO POR FLEXIÓN

As = 1.46 cm2 / m As = 0.32 cm2 / m

PARA EL LADO LARGO


q(1-0.5q) = 0.068772 q(1-0.5q) = 0.010825
a b c a b c
0.5 -1 0.068772 0.5 -1 0.010825
(-) (+) (-) (+)
q= 0.07131 1.92869 q= 0.01088 1.98912
p= 0.00289 p= 0.00044
EL PERALTE ES ADECUADO POR FLEXIÓN EL PERALTE ES ADECUADO POR FLEXIÓN

As = 1.44 cm2 / m As = 0.22 cm2 / m

COLOCACIÓN ACERO REFUERZO

as, mín = 1.43 cm2 / m


660 X1
as1  SEPARACIÓN MÁXIMA
fy ( X1  100) 3.5X1 = 35 cm
50 cm
X1 = 10.00 cm

ACERO # = 3
as = 0.71 cm2

SEPARACIÓN TEÓRICA.

as * 100 SEPARACIÓN EN cm PARA:


S NEGATIVO POSITIVO
As 48.79 49.88 48.79
49.37 49.88 49.88

SEPARACIÓN DE VARILLAS

DIMENSIÓN DE FRANJAS
FRANJAS CENTRALES = 1.56 II AL CORTO 1.50 II AL LARGO
FRANJAS EXTREMAS = 0.78 II AL CORTO 0.75 II AL LARGO

SEPARACIÓN DE ACERO EN LAS FRANJAS


FRANJAS CENTRALES = 35.00 48.79
FRANJAS EXTREMAS = 35.00 49.88

SEPARACIÓN AL CENTRO DEL TABLERO = 35.00 cm


SEPARACIÓN EN LOS EXTREMOS DEL TABLERO = 35.00 cm

ACERO DE REFUERZO
RCDF. ING. CHACÓN.
BAYONETAS = 50 cm @ 35.00 60 cm
BASTONES = 60 cm @ 35.00 75 cm

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 88
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

V.6. Diseño de castillos para muros de mampostería.


Los muros de mampostería se desplantarán sobre la contratrabe que conecta a los dados y en su parte superior
se apoyaran por medio del acero longitudinal en las trabes principales de la estructura. Por lo cual la
consideración para el diseño y análisis del castillo será simplemente apoyado en su parte superior y empotrado
en la base.

Se obtiene el tablero más grande de mampostería y se repartió por medio de su área tributaria al castillo
central y con ello se obtuvieron los elementos mecánicos de diseño.

DISEÑO Y REVISION ESTRUCTURAL DE CASTILLOS

Longitud

CASTILLO CASTILLO

CASTILLO

Altura MURO DE MURO DE


MAMPOSTERIA MAMPOSTERIA

NPT NPT

CONTRATRABE

DATOS:

Altura de muro de mampostería= 9.700 m Longitud Muro = 4.000 m


Peso del muro mamposteria = 0.261 Ton/m²
Longitud para diseño = 2.000 m (Área Tributaria castillo)

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 89
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Momento M0 = 2.39 Ton*m


Momento Md = 2.00 Ton*m
Cortante V 0 = 0.91 Ton
Cortante V d = 0.41 Ton

Revisión por sismo:


C= 0.207
FI = 1.5 Wi = 5.06 Ton
Q= 1.5 F= 1.05 Ton

REVISIÓN ESTRUCTURAL DE CASTILLOS Y CONECTOR A CORTANTE


DATOS:
Sección de castillo: Distancia entre castillos del área más desfavorable:
b= 20 cm D= 2m Vd = 0.91 Ton
h= 20 cm Área tributaria:
r= 2.5 cm A= 19.4 m² Md = 2.00 Ton*m
FC = 1.10
d= 17.5 Factores (FR)
f'c 200.00 Kg/cm² Flexión 0.90
fy 4,200.00 Kg/cm² Cortante 0.80

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 90
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Md = 2.20 Ton*m
Vd = 1.00 Ton

As min = 0.94 cm² ωmin = 0.056569 ρmin = 0.002694


cb = 10.29 cm As balanceado = 7.08 cm² As máximo = 5.313 cm²
ab = 8.75 cm ρb = 0.02024 ρb max = 0.01518
C= 29.75 Ton ωb = 0.42500 ωb max = 0.31875
β1 = 0.85 MRb = 3.51 Ton MR max = 2.85 Ton

Diseño a flexión: Diseño a cortante:


Simplemente armada
ω = 0.23043 Vs = 1.00 Ton Smax = 8.75 cm
ρ = 0.01097 Estribos con acero # 3
As = 3.84 cm² N° ramas del estribo: 2 2500 Armado propuesto :
MR = 2.20 Ton*m Av = 1.42 cm² 2 Var, # 6
S= 8.75 cm As = 5.74 cm²

Cortante para conectores: considerando la longitud total del muro


VU = 0.721 Ton
Conector; Var # 3 VR = 2,385.60 Kg Steorica = 331.06 cm

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 91
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

V.7. Diseño de muros de concreto reforzado.


Para el diseño de los muros de concreto que dividen el cuarto eléctrico de las plantas de emergencia se tomaron
las siguientes consideraciones.

El espesor del muro será por lo menos de 15 cm (división de plantas de emergencia y cuarto eléctrico). Dichos
muros se desplantarán sobre la contratrabe que conecta a los dados y en su parte superior se apoyarán por
medio del acero longitudinal en las trabes principales de la estructura. Por lo cual la consideración para el diseño
y análisis será simplemente apoyado en su parte superior y empotrado en la base.

DISEÑO Y REVISION ESTRUCTURAL DE MUROS DE CONCRETO (CORTA FUEGO).

DATOS:
Altura de muro de concreto = 7.00 m Df = 3 m
Espesor de muro de concreto = 0.15 m γ conc = 2.40 Ton/m³
Longitud para diseño = 7.00 m γ relleno = 1.90 Ton/m³
Peso del muro de concreto = 0.405 Ton/m²

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 92
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 93
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 94
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

V.8. Revisión de cortante en columnas.


La revisión por cortante de columnas se realizará comprobando que el cortante actuante de la columna sea
menor que el cortante resistente de la misma, como lo indican las Normas Técnicas Complementarias de
Concreto 2004.

REVISIÓN POR CORTANTE COLUMNAS C-1

B= 60 CM
H= 60 CM
f´c= 250 KG/CM2
fy = 4200 KG/CM2
f*c = 200 KG/CM2
f"c = 170 KG/CM2
E# 3
Ramas 4
As = 43.08 CM2
Barra long. # 8
p= 0.0120
Vcr = 17893.76 KG
0.8*(0.7*f*c*B*H+2000As) 472128.00
Vcrmáx = 101823.38 KG

E#3@... E#3@... E#3@... Armar con


Vcr Vu-Vcr
UNIT METER MTON S4 S5 S6 E#3@...
Beam L/C Node Fx Mton Fy Mton Fz Mton Mx MTon-m My MTon-m Mz MTon-m Kg Kg cm cm cm cm
4 100 4 44.33 -0.138 3.658 -0.014 -10.447 -0.383 19436.2 -15778 33 46 30 30
22 -34.804 0.138 -3.658 0.014 -16.436 -0.629 16682.8 -13025 33 46 30 30
101 4 44.306 -0.119 3.601 -0.174 -9.917 -0.313 19435.3 -15834 33 46 30 30
22 -34.78 0.119 -3.601 0.174 -16.553 -0.562 16683.6 -13083 33 46 30 30
102 4 30.25 0.932 1.178 -0.615 -1.955 3.329 18946.3 -17768 33 46 30 30
22 -23.264 -0.932 -1.178 0.615 -6.705 3.521 17084.3 -15906 33 46 30 30
103 4 32.577 0.739 3.176 -0.027 -9.613 2.7 19027.2 -15851 33 46 30 30
22 -25.591 -0.739 -3.176 0.027 -13.73 2.734 17003.4 -13827 33 46 30 30
104 4 30.37 0.838 1.286 -0.624 -2.343 3.003 18950.4 -17664 33 46 30 30
22 -23.385 -0.838 -1.286 0.624 -7.112 3.153 17080.1 -15794 33 46 30 30
105 4 32.456 0.834 3.068 -0.019 -9.225 3.025 19023.0 -15955 33 46 30 30
22 -25.471 -0.834 -3.068 0.019 -13.323 3.102 17007.5 -13940 33 46 30 30
106 4 30.377 -0.889 1.761 -0.269 -3.995 -3.079 18950.7 -17190 33 46 30 30
22 -23.391 0.889 -1.761 0.269 -8.951 -3.454 17079.9 -15319 33 46 30 30
107 4 32.704 -1.081 3.759 0.319 -11.652 -3.708 19031.6 -15273 33 46 30 30
22 -25.719 1.081 -3.759 -0.319 -15.976 -4.241 16998.9 -13240 33 46 30 30
108 4 30.498 -0.983 1.869 -0.278 -4.382 -3.405 18954.9 -17086 33 46 30 30
22 -23.512 0.983 -1.869 0.278 -9.358 -3.822 17075.7 -15207 33 46 30 30
109 4 32.583 -0.987 3.651 0.328 -11.265 -3.382 19027.4 -15376 33 46 30 30
22 -25.598 0.987 -3.651 -0.328 -15.569 -3.873 17003.1 -13352 33 46 30 30
110 4 30.903 0.555 1.741 -0.633 -3.967 2.027 18969.0 -17228 33 46 30 30
22 -23.918 -0.555 -1.741 0.633 -8.832 2.051 17061.6 -15321 33 46 30 30
111 4 33.231 0.362 3.739 -0.045 -11.624 1.398 19050.0 -15311 33 46 30 30
22 -26.245 -0.362 -3.739 0.045 -15.858 1.265 16980.6 -13242 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 95
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

112 4 31.024 0.461 1.85 -0.641 -4.355 1.702 18973.2 -17123 33 46 30 30


22 -24.039 -0.461 -1.85 0.641 -9.239 1.684 17057.4 -15207 33 46 30 30
113 4 33.11 0.457 3.631 -0.036 -11.237 1.724 19045.8 -15415 33 46 30 30
22 -26.124 -0.457 -3.631 0.036 -15.451 1.632 16984.8 -13354 33 46 30 30
114 4 29.723 -0.512 1.198 -0.252 -1.983 -1.778 18927.9 -17730 33 46 30 30
22 -22.737 0.512 -1.198 0.252 -6.823 -1.985 17102.7 -15905 33 46 30 30
115 4 32.05 -0.704 3.196 0.337 -9.641 -2.407 19008.9 -15813 33 46 30 30
22 -25.065 0.704 -3.196 -0.337 -13.849 -2.771 17021.7 -13826 33 46 30 30
116 4 29.844 -0.606 1.306 -0.26 -2.371 -2.103 18932.1 -17626 33 46 30 30
22 -22.858 0.606 -1.306 0.26 -7.23 -2.352 17098.5 -15792 33 46 30 30
117 4 31.929 -0.61 3.088 0.345 -9.253 -2.081 19004.7 -15917 33 46 30 30
22 -24.944 0.61 -3.088 -0.345 -13.442 -2.404 17025.9 -13938 33 46 30 30
118 4 27.832 0.508 -0.452 -1.273 3.858 1.768 18862.1 -18354 33 46 30 30
22 -20.847 -0.508 0.452 1.273 -0.539 1.965 17168.4 -16660 33 46 30 30
119 4 27.929 -0.039 -0.272 -1.119 3.217 -0.154 18865.5 -18594 33 46 30 30
22 -20.944 0.039 0.272 1.119 -1.217 -0.131 17165.0 -16893 33 46 30 30
120 4 28.029 0.395 -0.283 -1.279 3.254 1.378 18869.0 -18474 33 46 30 30
22 -21.043 -0.395 0.283 1.279 -1.177 1.524 17161.6 -16767 33 46 30 30
121 4 27.733 0.074 -0.441 -1.114 3.82 0.237 18858.7 -18418 33 46 30 30
22 -20.747 -0.074 0.441 1.114 -0.579 0.309 17171.9 -16731 33 46 30 30
122 4 35.094 -0.129 5.14 0.912 -16.209 -0.299 19114.8 -13975 33 46 30 30
22 -28.109 0.129 -5.14 -0.912 -21.572 -0.645 16915.8 -11776 33 46 30 30
123 4 35.191 -0.675 5.32 1.066 -16.85 -2.221 19118.2 -13798 33 46 30 30
22 -28.206 0.675 -5.32 -1.066 -22.251 -2.742 16912.4 -11592 33 46 30 30
124 4 35.291 -0.242 5.309 0.907 -16.813 -0.69 19121.7 -13813 33 46 30 30
22 -28.305 0.242 -5.309 -0.907 -22.21 -1.086 16908.9 -11600 33 46 30 30
125 4 34.995 -0.562 5.151 1.071 -16.247 -1.831 19111.4 -13960 33 46 30 30
22 -28.009 0.562 -5.151 -1.071 -21.613 -2.301 16919.2 -11768 33 46 30 30
126 4 28.235 0.194 -0.091 -1.302 2.566 0.682 18876.2 -18682 33 46 30 30
22 -21.25 -0.194 0.091 1.302 -1.896 0.74 17154.4 -16960 33 46 30 30
127 4 28.332 -0.353 0.088 -1.147 1.925 -1.24 18879.5 -18527 33 46 30 30
22 -21.347 0.353 -0.088 1.147 -2.575 -1.356 17151.0 -16798 33 46 30 30
128 4 28.432 0.081 0.078 -1.307 1.962 0.292 18883.0 -18802 33 46 30 30
22 -21.446 -0.081 -0.078 1.307 -2.534 0.3 17147.6 -17067 33 46 30 30
129 4 28.136 -0.24 -0.08 -1.142 2.528 -0.849 18872.7 -18633 33 46 30 30
22 -21.15 0.24 0.08 1.142 -1.936 -0.915 17157.9 -16918 33 46 30 30
130 4 34.691 0.186 4.78 0.94 -14.917 0.786 19100.8 -14321 33 46 30 30
22 -27.706 -0.186 -4.78 -0.94 -20.215 0.579 16929.8 -12150 33 46 30 30
131 4 34.788 -0.361 4.959 1.095 -15.558 -1.136 19104.2 -14145 33 46 30 30
22 -27.802 0.361 -4.959 -1.095 -20.894 -1.517 16926.4 -11967 33 46 30 30
132 4 34.887 0.073 4.949 0.935 -15.521 0.396 19107.6 -14159 33 46 30 30
22 -27.902 -0.073 -4.949 -0.935 -20.853 0.138 16923.0 -11974 33 46 30 30
133 4 34.592 -0.248 4.791 1.1 -14.955 -0.745 19097.3 -14306 33 46 30 30
22 -27.606 0.248 -4.791 -1.1 -20.256 -1.076 16933.3 -12142 33 46 30 30
11 100 11 27.038 -1.291 -1.703 0.018 3.585 -2.484 18834.5 -17132 33 46 30 30
29 -17.513 1.291 1.703 -0.018 8.929 -7.002 17284.4 -15581 33 46 30 30
101 11 27.068 -1.296 -1.719 0.086 3.64 -2.493 18835.5 -17117 33 46 30 30
29 -17.543 1.296 1.719 -0.086 8.992 -7.034 17283.4 -15564 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 96
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

102 11 18.077 -0.007 -1.337 0.583 3.05 1.407 18522.7 -17186 33 46 30 30


29 -11.091 0.007 1.337 -0.583 6.776 -1.456 17507.9 -16171 33 46 30 30
103 11 17.391 0.049 -0.924 -0.214 1.452 1.576 18498.9 -17575 33 46 30 30
29 -10.406 -0.049 0.924 0.214 5.338 -1.215 17531.7 -16608 33 46 30 30
104 11 18.141 0.004 -1.404 0.575 3.3 1.44 18524.9 -17121 33 46 30 30
29 -11.155 -0.004 1.404 -0.575 7.016 -1.41 17505.6 -16102 33 46 30 30
105 11 17.327 0.038 -0.857 -0.206 1.202 1.543 18496.6 -17640 33 46 30 30
29 -10.342 -0.038 0.857 0.206 5.099 -1.262 17533.9 -16677 33 46 30 30
106 11 21.716 -1.891 -1.521 0.062 3.703 -5.097 18649.3 -16758 33 46 30 30
29 -14.731 1.891 1.521 -0.062 7.479 -8.805 17381.2 -15490 33 46 30 30
107 11 21.031 -1.836 -1.108 -0.735 2.105 -4.927 18625.5 -16790 33 46 30 30
29 -14.046 1.836 1.108 0.735 6.041 -8.564 17405.1 -15569 33 46 30 30
108 11 21.78 -1.881 -1.588 0.053 3.953 -5.063 18651.6 -16771 33 46 30 30
29 -14.795 1.881 1.588 -0.053 7.718 -8.759 17379.0 -15498 33 46 30 30
109 11 20.967 -1.846 -1.042 -0.727 1.855 -4.961 18623.3 -16777 33 46 30 30
29 -13.982 1.846 1.042 0.727 5.801 -8.61 17407.3 -15561 33 46 30 30
110 11 18.31 0.052 -1.603 0.584 4.054 1.585 18530.8 -16928 33 46 30 30
29 -11.324 -0.052 1.603 -0.584 7.727 -1.205 17499.8 -15897 33 46 30 30
111 11 17.624 0.108 -1.19 -0.213 2.456 1.754 18507.0 -17317 33 46 30 30
29 -10.639 -0.108 1.19 0.213 6.29 -0.964 17523.6 -16334 33 46 30 30
112 11 18.374 0.063 -1.67 0.576 4.304 1.618 18533.1 -16863 33 46 30 30
29 -11.388 -0.063 1.67 -0.576 7.967 -1.159 17497.5 -15828 33 46 30 30
113 11 17.56 0.097 -1.123 -0.204 2.206 1.721 18504.7 -17382 33 46 30 30
29 -10.575 -0.097 1.123 0.204 6.05 -1.01 17525.8 -16403 33 46 30 30
114 11 21.483 -1.95 -1.255 0.06 2.699 -5.275 18641.2 -16691 33 46 30 30
29 -14.498 1.95 1.255 -0.06 6.527 -9.056 17389.3 -15439 33 46 30 30
115 11 20.798 -1.894 -0.842 -0.737 1.102 -5.105 18617.4 -16723 33 46 30 30
29 -13.813 1.894 0.842 0.737 5.09 -8.815 17413.2 -15519 33 46 30 30
116 11 21.547 -1.939 -1.322 0.052 2.95 -5.241 18643.5 -16704 33 46 30 30
29 -14.562 1.939 1.322 -0.052 6.767 -9.01 17387.1 -15448 33 46 30 30
117 11 20.734 -1.905 -0.776 -0.729 0.851 -5.139 18615.2 -16710 33 46 30 30
29 -13.749 1.905 0.776 0.729 4.85 -8.862 17415.4 -15510 33 46 30 30
118 11 20.172 -0.755 -1.886 1.359 5.118 -1.162 18595.6 -16710 33 46 30 30
29 -13.187 0.755 1.886 -1.359 8.742 -4.386 17434.9 -15549 33 46 30 30
119 11 21.249 -1.304 -1.943 0.972 5.32 -3.059 18633.1 -16690 33 46 30 30
29 -14.263 1.304 1.943 -0.972 8.964 -6.523 17397.5 -15455 33 46 30 30
120 11 20.242 -0.737 -1.965 1.359 5.419 -1.108 18598.0 -16633 33 46 30 30
29 -13.256 0.737 1.965 -1.359 9.027 -4.31 17432.5 -15468 33 46 30 30
121 11 21.179 -1.321 -1.864 0.972 5.019 -3.112 18630.7 -16767 33 46 30 30
29 -14.194 1.321 1.864 -0.972 8.679 -6.598 17399.9 -15536 33 46 30 30
122 11 17.858 -0.544 -0.507 -0.578 -0.153 -0.495 18515.1 -17971 33 46 30 30
29 -10.872 0.544 0.507 0.578 3.879 -3.502 17515.5 -16971 33 46 30 30
123 11 18.935 -1.093 -0.565 -0.964 0.049 -2.392 18552.6 -17460 33 46 30 30
29 -11.949 1.093 0.565 0.964 4.102 -5.638 17478.0 -16385 33 46 30 30
124 11 17.928 -0.526 -0.587 -0.577 0.148 -0.441 18517.5 -17931 33 46 30 30
29 -10.942 0.526 0.587 0.577 4.165 -3.426 17513.1 -16926 33 46 30 30
125 11 18.865 -1.11 -0.485 -0.965 -0.252 -2.445 18550.1 -17440 33 46 30 30
29 -11.879 1.11 0.485 0.965 3.816 -5.714 17480.5 -16370 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 97
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

126 11 20.385 -0.719 -2.108 1.331 5.952 -1.05 18603.0 -16495 33 46 30 30


29 -13.4 0.719 2.108 -1.331 9.541 -4.231 17427.5 -15320 33 46 30 30
127 11 21.462 -1.267 -2.166 0.945 6.155 -2.947 18640.5 -16474 33 46 30 30
29 -14.477 1.267 2.166 -0.945 9.763 -6.368 17390.1 -15224 33 46 30 30
128 11 20.455 -0.701 -2.188 1.332 6.253 -0.997 18605.5 -16417 33 46 30 30
29 -13.47 0.701 2.188 -1.332 9.826 -4.156 17425.1 -15237 33 46 30 30
129 11 21.392 -1.285 -2.086 0.945 5.854 -3.001 18638.1 -16552 33 46 30 30
29 -14.407 1.285 2.086 -0.945 9.477 -6.443 17392.5 -15306 33 46 30 30
130 11 17.644 -0.58 -0.285 -0.55 -0.987 -0.606 18507.7 -17928 33 46 30 30
29 -10.659 0.58 0.285 0.55 3.081 -3.656 17522.9 -16943 33 46 30 30
131 11 18.721 -1.129 -0.343 -0.937 -0.785 -2.503 18545.1 -17416 33 46 30 30
29 -11.736 1.129 0.343 0.937 3.303 -5.793 17485.4 -16356 33 46 30 30
132 11 17.714 -0.562 -0.365 -0.55 -0.686 -0.553 18510.1 -17948 33 46 30 30
29 -10.729 0.562 0.365 0.55 3.366 -3.581 17520.5 -16958 33 46 30 30
133 11 18.651 -1.146 -0.263 -0.937 -1.086 -2.557 18542.7 -17397 33 46 30 30
29 -11.666 1.146 0.263 0.937 3.018 -5.869 17487.9 -16342 33 46 30 30
15 100 15 44.012 3.197 -0.094 -0.027 0.191 9.124 19425.1 -16228 33 46 30 30
33 -34.487 -3.197 0.094 0.027 0.502 14.373 16693.8 -13497 33 46 30 30
101 15 44.073 3.221 -0.128 -0.171 0.341 9.09 19427.2 -16206 33 46 30 30
33 -34.547 -3.221 0.128 0.171 0.601 14.582 16691.8 -13471 33 46 30 30
102 15 40.745 3.662 -1.111 0.101 3.238 10.157 19311.4 -15649 33 46 30 30
33 -33.76 -3.662 1.111 -0.101 4.928 16.762 16719.1 -13057 33 46 30 30
103 15 40.35 3.668 -0.376 0.473 0.536 10.196 19297.7 -15630 33 46 30 30
33 -33.365 -3.668 0.376 -0.473 2.229 16.763 16732.9 -13065 33 46 30 30
104 15 40.73 3.674 -1.029 0.076 2.94 10.192 19310.9 -15637 33 46 30 30
33 -33.745 -3.674 1.029 -0.076 4.627 16.815 16719.7 -13046 33 46 30 30
105 15 40.365 3.656 -0.458 0.499 0.834 10.161 19298.2 -15642 33 46 30 30
33 -33.38 -3.656 0.458 -0.499 2.531 16.71 16732.4 -13076 33 46 30 30
106 15 37.647 2.06 -0.836 -0.658 2.272 4.736 19203.6 -17144 33 46 30 30
33 -30.661 -2.06 0.836 0.658 3.873 10.408 16827.0 -14767 33 46 30 30
107 15 37.251 2.066 -0.101 -0.286 -0.43 4.775 19189.9 -17124 33 46 30 30
33 -30.266 -2.066 0.101 0.286 1.173 10.409 16840.7 -14775 33 46 30 30
108 15 37.632 2.072 -0.754 -0.684 1.974 4.771 19203.1 -17131 33 46 30 30
33 -30.646 -2.072 0.754 0.684 3.571 10.461 16827.5 -14755 33 46 30 30
109 15 37.266 2.054 -0.183 -0.26 -0.132 4.74 19190.4 -17136 33 46 30 30
33 -30.281 -2.054 0.183 0.26 1.475 10.356 16840.2 -14786 33 46 30 30
110 15 40.735 3.73 -0.78 -0.002 2.026 10.351 19311.1 -15581 33 46 30 30
33 -33.75 -3.73 0.78 0.002 3.704 17.061 16719.5 -12989 33 46 30 30
111 15 40.34 3.735 -0.045 0.37 -0.676 10.391 19297.3 -15562 33 46 30 30
33 -33.354 -3.735 0.045 -0.37 1.005 17.063 16733.3 -12998 33 46 30 30
112 15 40.72 3.742 -0.698 -0.027 1.728 10.387 19310.5 -15569 33 46 30 30
33 -33.735 -3.742 0.698 0.027 3.402 17.115 16720.0 -12978 33 46 30 30
113 15 40.355 3.723 -0.126 0.396 -0.378 10.355 19297.9 -15575 33 46 30 30
33 -33.369 -3.723 0.126 -0.396 1.307 17.009 16732.7 -13010 33 46 30 30
114 15 37.657 1.993 -1.167 -0.555 3.484 4.541 19204.0 -17211 33 46 30 30
33 -30.672 -1.993 1.167 0.555 5.097 10.108 16826.6 -14834 33 46 30 30
115 15 37.262 1.999 -0.433 -0.183 0.782 4.58 19190.2 -17191 33 46 30 30
33 -30.276 -1.999 0.433 0.183 2.398 10.109 16840.4 -14841 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 98
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

116 15 37.642 2.005 -1.086 -0.581 3.186 4.576 19203.5 -17198 33 46 30 30


33 -30.657 -2.005 1.086 0.581 4.795 10.161 16827.1 -14822 33 46 30 30
117 15 37.277 1.986 -0.514 -0.157 1.08 4.545 19190.8 -17205 33 46 30 30
33 -30.291 -1.986 0.514 0.157 2.699 10.056 16839.8 -14854 33 46 30 30
118 15 40.166 3.149 -1.901 -0.565 6.146 8.532 19291.3 -16142 33 46 30 30
33 -33.18 -3.149 1.901 0.565 7.824 14.611 16739.3 -13590 33 46 30 30
119 15 39.162 2.57 -1.82 -0.776 5.869 6.478 19256.3 -16686 33 46 30 30
33 -32.176 -2.57 1.82 0.776 7.506 12.409 16774.2 -14204 33 46 30 30
120 15 40.163 3.169 -1.801 -0.596 5.782 8.59 19291.2 -16122 33 46 30 30
33 -33.177 -3.169 1.801 0.596 7.457 14.701 16739.4 -13570 33 46 30 30
121 15 39.165 2.549 -1.919 -0.746 6.232 6.42 19256.4 -16707 33 46 30 30
33 -32.18 -2.549 1.919 0.746 7.873 12.319 16774.1 -14225 33 46 30 30
122 15 38.789 3.171 0.585 0.47 -2.953 8.669 19243.4 -16072 33 46 30 30
33 -31.804 -3.171 -0.585 -0.47 -1.348 14.636 16787.2 -13616 33 46 30 30
123 15 37.785 2.592 0.666 0.258 -3.231 6.615 19208.4 -16616 33 46 30 30
33 -30.8 -2.592 -0.666 -0.258 -1.666 12.433 16822.1 -14230 33 46 30 30
124 15 38.786 3.191 0.685 0.439 -3.317 8.727 19243.3 -16052 33 46 30 30
33 -31.8 -3.191 -0.685 -0.439 -1.715 14.726 16787.3 -13596 33 46 30 30
125 15 37.788 2.571 0.567 0.289 -2.867 6.557 19208.5 -16638 33 46 30 30
33 -30.803 -2.571 -0.567 -0.289 -1.299 12.343 16822.0 -14251 33 46 30 30
126 15 40.116 3.189 -1.629 -0.65 5.152 8.649 19289.5 -16101 33 46 30 30
33 -33.13 -3.189 1.629 0.65 6.819 14.791 16741.1 -13552 33 46 30 30
127 15 39.112 2.61 -1.548 -0.862 4.875 6.595 19254.6 -16645 33 46 30 30
33 -32.126 -2.61 1.548 0.862 6.5 12.588 16776.0 -14166 33 46 30 30
128 15 40.113 3.209 -1.529 -0.681 4.788 8.707 19289.4 -16080 33 46 30 30
33 -33.127 -3.209 1.529 0.681 6.451 14.88 16741.2 -13532 33 46 30 30
129 15 39.115 2.59 -1.647 -0.831 5.239 6.537 19254.7 -16665 33 46 30 30
33 -32.129 -2.59 1.647 0.831 6.868 12.498 16775.9 -14186 33 46 30 30
130 15 38.839 3.13 0.313 0.556 -1.96 8.551 19245.1 -16115 33 46 30 30
33 -31.854 -3.13 -0.313 -0.556 -0.342 14.457 16785.5 -13655 33 46 30 30
131 15 37.835 2.551 0.394 0.344 -2.237 6.498 19210.2 -16659 33 46 30 30
33 -30.85 -2.551 -0.394 -0.344 -0.66 12.254 16820.4 -14269 33 46 30 30
132 15 38.836 3.151 0.413 0.525 -2.323 8.61 19245.0 -16094 33 46 30 30
33 -31.85 -3.151 -0.413 -0.525 -0.709 14.547 16785.6 -13635 33 46 30 30
133 15 37.838 2.531 0.295 0.375 -1.873 6.439 19210.3 -16679 33 46 30 30
33 -30.853 -2.531 -0.295 -0.375 -0.293 12.164 16820.3 -14289 33 46 30 30
16 100 16 24.824 -1.107 -1.51 0.054 3.128 -2.234 18757.5 -17247 33 46 30 30
34 -15.298 1.107 1.51 -0.054 7.973 -5.904 17361.5 -15851 33 46 30 30
101 16 24.872 -1.117 -1.572 -0.027 3.383 -2.269 18759.1 -17187 33 46 30 30
34 -15.346 1.117 1.572 0.027 8.174 -5.94 17359.8 -15788 33 46 30 30
102 16 18.908 -0.308 -2.386 0.007 7.282 0.438 18551.6 -16166 33 46 30 30
34 -11.922 0.308 2.386 -0.007 10.252 -2.7 17479.0 -15093 33 46 30 30
103 16 16.437 -0.252 0.115 -0.04 -2.773 0.612 18465.7 -18214 33 46 30 30
34 -9.452 0.252 -0.115 0.04 1.924 -2.466 17564.9 -17313 33 46 30 30
104 16 18.86 -0.247 -2.392 -0.052 7.307 0.683 18550.0 -16158 33 46 30 30
34 -11.874 0.247 2.392 0.052 10.275 -2.502 17480.6 -15089 33 46 30 30
105 16 16.486 -0.313 0.122 0.019 -2.799 0.366 18467.4 -18154 33 46 30 30
34 -9.5 0.313 -0.122 -0.019 1.901 -2.664 17563.2 -17250 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 99
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

106 16 19.596 -1.345 -2.357 -0.19 7.573 -3.854 18575.6 -16219 33 46 30 30


34 -12.611 1.345 2.357 0.19 9.752 -6.032 17455.0 -15098 33 46 30 30
107 16 17.126 -1.29 0.144 -0.238 -2.482 -3.68 18489.6 -17200 33 46 30 30
34 -10.14 1.29 -0.144 0.238 1.425 -5.799 17541.0 -16251 33 46 30 30
108 16 19.548 -1.285 -2.364 -0.25 7.599 -3.609 18573.9 -16210 33 46 30 30
34 -12.563 1.285 2.364 0.25 9.775 -5.834 17456.7 -15093 33 46 30 30
109 16 17.174 -1.35 0.15 -0.178 -2.507 -3.926 18491.3 -17141 33 46 30 30
34 -10.188 1.35 -0.15 0.178 1.402 -5.997 17539.3 -16189 33 46 30 30
110 16 18.698 -0.034 -2.426 -0.293 7.441 1.551 18544.3 -16118 33 46 30 30
34 -11.713 0.034 2.426 0.293 10.393 -1.799 17486.2 -15060 33 46 30 30
111 16 16.228 0.022 0.075 -0.341 -2.614 1.726 18458.4 -18383 33 46 30 30
34 -9.242 -0.022 -0.075 0.341 2.065 -1.566 17572.2 -17497 33 46 30 30
112 16 18.65 0.027 -2.433 -0.352 7.466 1.797 18542.7 -16110 33 46 30 30
34 -11.665 -0.027 2.433 0.352 10.416 -1.601 17487.9 -15055 33 46 30 30
113 16 16.276 -0.039 0.081 -0.281 -2.64 1.48 18460.1 -18379 33 46 30 30
34 -9.291 0.039 -0.081 0.281 2.042 -1.764 17570.5 -17489 33 46 30 30
114 16 19.806 -1.619 -2.316 0.11 7.414 -4.968 18582.9 -16267 33 46 30 30
34 -12.82 1.619 2.316 -0.11 9.611 -6.933 17447.7 -15132 33 46 30 30
115 16 17.335 -1.564 0.185 0.062 -2.64 -4.793 18496.9 -16933 33 46 30 30
34 -10.35 1.564 -0.185 -0.062 1.284 -6.699 17533.6 -15970 33 46 30 30
116 16 19.758 -1.559 -2.323 0.05 7.44 -4.722 18581.2 -16258 33 46 30 30
34 -12.772 1.559 2.323 -0.05 9.634 -6.735 17449.4 -15126 33 46 30 30
117 16 17.383 -1.624 0.191 0.122 -2.666 -5.039 18498.6 -16875 33 46 30 30
34 -10.398 1.624 -0.191 -0.122 1.26 -6.897 17532.0 -15908 33 46 30 30
118 16 22.288 -0.73 -5.69 -0.081 20.77 -1.241 18669.2 -12979 33 46 30 30
34 -15.302 0.73 5.69 0.081 21.049 -4.126 17361.4 -11671 33 46 30 30
119 16 22.504 -1.05 -5.687 -0.352 20.876 -2.574 18676.8 -12990 33 46 30 30
34 -15.519 1.05 5.687 0.352 20.92 -5.146 17353.8 -11667 33 46 30 30
120 16 22.225 -0.648 -5.702 -0.172 20.818 -0.907 18667.0 -12965 33 46 30 30
34 -15.239 0.648 5.702 0.172 21.091 -3.855 17363.5 -11662 33 46 30 30
121 16 22.567 -1.133 -5.674 -0.262 20.829 -2.908 18678.9 -13005 33 46 30 30
34 -15.582 1.133 5.674 0.262 20.877 -5.417 17351.6 -11678 33 46 30 30
122 16 13.547 -0.539 3.403 0.507 -15.91 -0.64 18365.1 -14962 33 46 30 30
34 -6.561 0.539 -3.403 -0.507 -9.102 -3.324 17665.5 -14262 33 46 30 30
123 16 13.763 -0.859 3.406 0.237 -15.803 -1.972 18372.6 -14967 33 46 30 30
34 -6.778 0.859 -3.406 -0.237 -9.231 -4.345 17657.9 -14252 33 46 30 30
124 16 13.484 -0.457 3.391 0.417 -15.862 -0.305 18362.9 -14972 33 46 30 30
34 -6.498 0.457 -3.391 -0.417 -9.06 -3.054 17667.7 -14277 33 46 30 30
125 16 13.826 -0.942 3.418 0.327 -15.851 -2.306 18374.8 -14957 33 46 30 30
34 -6.841 0.942 -3.418 -0.327 -9.274 -4.615 17655.7 -14238 33 46 30 30
126 16 22.127 -0.529 -5.712 -0.281 20.856 -0.422 18663.6 -12952 33 46 30 30
34 -15.141 0.529 5.712 0.281 21.126 -3.466 17367.0 -11655 33 46 30 30
127 16 22.343 -0.849 -5.709 -0.551 20.962 -1.755 18671.2 -12962 33 46 30 30
34 -15.358 0.849 5.709 0.551 20.997 -4.486 17359.4 -11650 33 46 30 30
128 16 22.064 -0.447 -5.724 -0.371 20.903 -0.088 18661.4 -12937 33 46 30 30
34 -15.078 0.447 5.724 0.371 21.168 -3.195 17369.1 -11645 33 46 30 30
129 16 22.406 -0.931 -5.696 -0.461 20.914 -2.089 18673.3 -12977 33 46 30 30
34 -15.421 0.931 5.696 0.461 20.954 -4.757 17357.2 -11661 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 100
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

130 16 13.708 -0.74 3.425 0.706 -15.995 -1.459 18370.7 -14946 33 46 30 30


34 -6.722 0.74 -3.425 -0.706 -9.179 -3.984 17659.9 -14235 33 46 30 30
131 16 13.924 -1.061 3.428 0.436 -15.889 -2.791 18378.2 -14950 33 46 30 30
34 -6.939 1.061 -3.428 -0.436 -9.308 -5.005 17652.3 -14224 33 46 30 30
132 16 13.645 -0.658 3.413 0.616 -15.948 -1.124 18368.5 -14956 33 46 30 30
34 -6.659 0.658 -3.413 -0.616 -9.137 -3.714 17662.1 -14249 33 46 30 30
133 16 13.987 -1.143 3.44 0.526 -15.937 -3.125 18380.4 -14940 33 46 30 30
34 -7.002 1.143 -3.44 -0.526 -9.351 -5.275 17650.1 -14210 33 46 30 30
17 100 17 66.612 -0.95 -1.851 -0.002 7.408 -2.119 20211.4 -18360 33 46 30 30
35 -57.086 0.95 1.851 0.002 6.196 -4.862 15907.5 -14057 33 46 30 30
101 17 66.595 -0.949 -1.76 -0.057 6.7 -2.116 20210.8 -18451 33 46 30 30
35 -57.069 0.949 1.76 0.057 6.238 -4.858 15908.1 -14148 33 46 30 30
102 17 47.725 0.004 -2.738 -0.179 10.031 0.989 19554.3 -16816 33 46 30 30
35 -40.74 -0.004 2.738 0.179 10.094 -0.96 16476.3 -13738 33 46 30 30
103 17 47.051 0.062 -0.406 0.22 1.604 1.236 19530.8 -19125 33 46 30 30
35 -40.066 -0.062 0.406 -0.22 1.383 -0.784 16499.7 -16094 33 46 30 30
104 17 47.663 0.081 -2.619 -0.194 9.622 1.277 19552.1 -16933 33 46 30 30
35 -40.678 -0.081 2.619 0.194 9.629 -0.683 16478.4 -13859 33 46 30 30
105 17 47.114 -0.015 -0.525 0.235 2.013 0.949 19533.0 -19008 33 46 30 30
35 -40.128 0.015 0.525 -0.235 1.849 -1.06 16497.6 -15973 33 46 30 30
106 17 47.403 -1.388 -1.957 -0.266 7.559 -4.205 19543.1 -17586 33 46 30 30
35 -40.418 1.388 1.957 0.266 6.823 -5.994 16487.5 -14530 33 46 30 30
107 17 46.729 -1.33 0.375 0.132 -0.868 -3.958 19519.6 -18190 33 46 30 30
35 -39.744 1.33 -0.375 -0.132 -1.888 -5.818 16510.9 -15181 33 46 30 30
108 17 47.341 -1.311 -1.838 -0.282 7.149 -3.917 19540.9 -17703 33 46 30 30
35 -40.355 1.311 1.838 0.282 6.358 -5.718 16489.7 -14652 33 46 30 30
109 17 46.792 -1.407 0.256 0.148 -0.459 -4.245 19521.8 -18115 33 46 30 30
35 -39.806 1.407 -0.256 -0.148 -1.422 -6.095 16508.8 -15102 33 46 30 30
110 17 47.401 0.351 -2.115 -0.24 7.899 2.289 19543.0 -17428 33 46 30 30
35 -40.416 -0.351 2.115 0.24 7.645 0.289 16487.6 -14373 33 46 30 30
111 17 46.727 0.408 0.217 0.158 -0.528 2.536 19519.6 -19112 33 46 30 30
35 -39.742 -0.408 -0.217 -0.158 -1.066 0.464 16511.0 -16103 33 46 30 30
112 17 47.339 0.427 -1.996 -0.255 7.49 2.576 19540.8 -17545 33 46 30 30
35 -40.353 -0.427 1.996 0.255 7.179 0.565 16489.7 -14494 33 46 30 30
113 17 46.79 0.332 0.098 0.174 -0.119 2.248 19521.7 -19190 33 46 30 30
35 -39.804 -0.332 -0.098 -0.174 -0.601 0.188 16508.8 -16177 33 46 30 30
114 17 47.727 -1.734 -2.58 -0.205 9.691 -5.504 19554.3 -16974 33 46 30 30
35 -40.742 1.734 2.58 0.205 9.273 -7.243 16476.2 -13896 33 46 30 30
115 17 47.053 -1.677 -0.248 0.193 1.264 -5.257 19530.9 -17854 33 46 30 30
35 -40.068 1.677 0.248 -0.193 0.562 -7.067 16499.7 -14823 33 46 30 30
116 17 47.665 -1.658 -2.461 -0.221 9.281 -5.217 19552.2 -17091 33 46 30 30
35 -40.68 1.658 2.461 0.221 8.807 -6.966 16478.4 -14017 33 46 30 30
117 17 47.116 -1.753 -0.367 0.209 1.673 -5.545 19533.1 -17780 33 46 30 30
35 -40.13 1.753 0.367 -0.209 1.027 -7.343 16497.5 -14745 33 46 30 30
118 17 48.109 -0.56 -4.517 -0.722 15.443 -1.16 19567.6 -15051 33 46 30 30
35 -41.123 0.56 4.517 0.722 17.759 -2.959 16463.0 -11946 33 46 30 30
119 17 48.019 -0.981 -4.293 -0.806 14.734 -2.731 19564.5 -15272 33 46 30 30
35 -41.034 0.981 4.293 0.806 16.822 -4.477 16466.0 -12173 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 101
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

120 17 48.011 -0.456 -4.33 -0.74 14.803 -0.77 19564.2 -15234 33 46 30 30


35 -41.026 0.456 4.33 0.74 17.024 -2.585 16466.3 -12136 33 46 30 30
121 17 48.116 -1.085 -4.48 -0.788 15.373 -3.121 19567.9 -15088 33 46 30 30
35 -41.131 1.085 4.48 0.788 17.557 -4.852 16462.7 -11983 33 46 30 30
122 17 46.452 -0.342 2.025 0.688 -6.279 -0.227 19510.0 -17485 33 46 30 30
35 -39.466 0.342 -2.025 -0.688 -8.601 -2.284 16520.6 -14496 33 46 30 30
123 17 46.363 -0.762 2.248 0.604 -6.988 -1.797 19506.9 -17259 33 46 30 30
35 -39.377 0.762 -2.248 -0.604 -9.537 -3.802 16523.7 -14276 33 46 30 30
124 17 46.355 -0.238 2.212 0.67 -6.919 0.163 19506.6 -17295 33 46 30 30
35 -39.369 0.238 -2.212 -0.67 -9.336 -1.909 16524.0 -14312 33 46 30 30
125 17 46.46 -0.866 2.061 0.622 -6.349 -2.187 19510.3 -17449 33 46 30 30
35 -39.474 0.866 -2.061 -0.622 -8.803 -4.176 16520.3 -14459 33 46 30 30
126 17 47.901 -0.305 -4.121 -0.775 14.078 -0.202 19560.4 -15439 33 46 30 30
35 -40.915 0.305 4.121 0.775 16.207 -2.038 16470.2 -12349 33 46 30 30
127 17 47.811 -0.725 -3.897 -0.859 13.369 -1.773 19557.3 -15660 33 46 30 30
35 -40.826 0.725 3.897 0.859 15.271 -3.556 16473.3 -12576 33 46 30 30
128 17 47.803 -0.201 -3.934 -0.793 13.439 0.188 19557.0 -15623 33 46 30 30
35 -40.818 0.201 3.934 0.793 15.473 -1.664 16473.6 -12540 33 46 30 30
129 17 47.909 -0.829 -4.084 -0.84 14.009 -2.162 19560.7 -15477 33 46 30 30
35 -40.923 0.829 4.084 0.84 16.006 -3.931 16469.9 -12386 33 46 30 30
130 17 46.66 -0.597 1.628 0.741 -4.915 -1.185 19517.2 -17889 33 46 30 30
35 -39.674 0.597 -1.628 -0.741 -7.049 -3.205 16513.4 -14885 33 46 30 30
131 17 46.57 -1.017 1.852 0.657 -5.624 -2.756 19514.1 -17662 33 46 30 30
35 -39.585 1.017 -1.852 -0.657 -7.986 -4.722 16516.5 -14664 33 46 30 30
132 17 46.563 -0.493 1.815 0.722 -5.555 -0.795 19513.8 -17699 33 46 30 30
35 -39.577 0.493 -1.815 -0.722 -7.784 -2.83 16516.7 -14702 33 46 30 30
133 17 46.668 -1.121 1.665 0.675 -4.984 -3.146 19517.5 -17853 33 46 30 30
35 -39.682 1.121 -1.665 -0.675 -7.251 -5.097 16513.1 -14848 33 46 30 30
18 100 18 45.822 2.444 0.287 0.042 -0.763 5.032 19488.1 -17044 33 46 30 30
36 -36.297 -2.444 -0.287 -0.042 -1.347 12.932 16630.9 -14187 33 46 30 30
101 18 45.847 2.456 0.269 0.107 -0.709 5.077 19488.9 -17033 33 46 30 30
36 -36.321 -2.456 -0.269 -0.107 -1.27 12.974 16630.0 -14174 33 46 30 30
102 18 32.786 2.246 -0.248 -0.039 1.304 5.644 19034.5 -16788 33 46 30 30
36 -25.801 -2.246 0.248 0.039 0.52 10.864 16996.1 -14750 33 46 30 30
103 18 33.057 2.307 0.553 0.242 -1.688 5.903 19043.9 -16737 33 46 30 30
36 -26.071 -2.307 -0.553 -0.242 -2.38 11.055 16986.7 -14680 33 46 30 30
104 18 32.883 2.306 -0.156 -0.047 0.965 5.889 19037.9 -16732 33 46 30 30
36 -25.897 -2.306 0.156 0.047 0.179 11.06 16992.7 -14687 33 46 30 30
105 18 32.96 2.247 0.461 0.25 -1.349 5.658 19040.6 -16794 33 46 30 30
36 -25.974 -2.247 -0.461 -0.25 -2.039 10.859 16990.0 -14743 33 46 30 30
106 18 31.522 1.157 -0.057 0.188 0.504 1.229 18990.5 -17834 33 46 30 30
36 -24.537 -1.157 0.057 -0.188 -0.087 7.272 17040.0 -15883 33 46 30 30
107 18 31.793 1.218 0.745 0.47 -2.487 1.488 18999.9 -17782 33 46 30 30
36 -24.807 -1.218 -0.745 -0.47 -2.987 7.463 17030.6 -15813 33 46 30 30
108 18 31.619 1.217 0.036 0.181 0.165 1.474 18993.9 -17777 33 46 30 30
36 -24.633 -1.217 -0.036 -0.181 -0.428 7.468 17036.7 -15820 33 46 30 30
109 18 31.696 1.158 0.652 0.478 -2.148 1.242 18996.6 -17839 33 46 30 30
36 -24.71 -1.158 -0.652 -0.478 -2.645 7.267 17034.0 -15876 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 102
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

110 18 33.199 2.517 0.128 -0.045 -0.076 6.751 19048.9 -16532 33 46 30 30


36 -26.214 -2.517 -0.128 0.045 -0.868 11.75 16981.7 -14465 33 46 30 30
111 18 33.47 2.578 0.93 0.236 -3.067 7.01 19058.3 -16480 33 46 30 30
36 -26.484 -2.578 -0.93 -0.236 -3.768 11.941 16972.3 -14394 33 46 30 30
112 18 33.296 2.577 0.221 -0.053 -0.415 6.997 19052.2 -16475 33 46 30 30
36 -26.311 -2.577 -0.221 0.053 -1.21 11.946 16978.3 -14401 33 46 30 30
113 18 33.373 2.518 0.837 0.244 -2.728 6.765 19054.9 -16537 33 46 30 30
36 -26.387 -2.518 -0.837 -0.244 -3.427 11.745 16975.7 -14458 33 46 30 30
114 18 31.109 0.885 -0.433 0.195 1.884 0.121 18976.2 -18091 33 46 30 30
36 -24.123 -0.885 0.433 -0.195 1.302 6.386 17054.4 -16169 33 46 30 30
115 18 31.379 0.947 0.368 0.476 -1.108 0.38 18985.5 -18039 33 46 30 30
36 -24.394 -0.947 -0.368 -0.476 -1.599 6.577 17045.0 -16098 33 46 30 30
116 18 31.206 0.945 -0.341 0.187 1.545 0.367 18979.5 -18035 33 46 30 30
36 -24.22 -0.945 0.341 -0.187 0.96 6.582 17051.1 -16106 33 46 30 30
117 18 31.283 0.887 0.276 0.484 -0.769 0.135 18982.2 -18095 33 46 30 30
36 -24.297 -0.887 -0.276 -0.484 -1.257 6.382 17048.4 -16161 33 46 30 30
118 18 31.98 1.777 -1.142 -0.054 4.59 3.747 19006.5 -17229 33 46 30 30
36 -24.995 -1.777 1.142 0.054 3.806 9.311 17024.1 -15247 33 46 30 30
119 18 31.591 1.443 -1.08 -0.249 4.329 2.385 18992.9 -17550 33 46 30 30
36 -24.606 -1.443 1.08 0.249 3.61 8.218 17037.6 -15595 33 46 30 30
120 18 32.104 1.858 -1.029 -0.056 4.176 4.079 19010.8 -17153 33 46 30 30
36 -25.119 -1.858 1.029 0.056 3.39 9.577 17019.8 -15162 33 46 30 30
121 18 31.467 1.361 -1.193 -0.247 4.742 2.053 18988.6 -17628 33 46 30 30
36 -24.482 -1.361 1.193 0.247 4.027 7.952 17041.9 -15681 33 46 30 30
122 18 32.988 2.023 1.576 0.126 -5.529 4.76 19041.5 -17019 33 46 30 30
36 -26.003 -2.023 -1.576 -0.126 -6.056 10.109 16989.0 -14966 33 46 30 30
123 18 32.599 1.689 1.638 -0.07 -5.79 3.398 19028.0 -17339 33 46 30 30
36 -25.614 -1.689 -1.638 0.07 -6.251 9.016 17002.6 -15314 33 46 30 30
124 18 33.112 2.104 1.689 0.124 -5.943 5.092 19045.8 -16942 33 46 30 30
36 -26.127 -2.104 -1.689 -0.124 -6.472 10.374 16984.7 -14881 33 46 30 30
125 18 32.475 1.608 1.525 -0.068 -5.376 3.065 19023.7 -17416 33 46 30 30
36 -25.49 -1.608 -1.525 0.068 -5.835 8.75 17006.9 -15399 33 46 30 30
126 18 32.303 1.977 -0.834 -0.08 3.46 4.564 19017.7 -17041 33 46 30 30
36 -25.318 -1.977 0.834 0.08 2.668 9.964 17012.9 -15036 33 46 30 30
127 18 31.914 1.643 -0.772 -0.275 3.199 3.202 19004.2 -17361 33 46 30 30
36 -24.929 -1.643 0.772 0.275 2.472 8.871 17026.4 -15383 33 46 30 30
128 18 32.427 2.058 -0.721 -0.082 3.046 4.897 19022.0 -16964 33 46 30 30
36 -25.442 -2.058 0.721 0.082 2.252 10.229 17008.5 -14951 33 46 30 30
129 18 31.79 1.561 -0.885 -0.274 3.612 2.87 18999.8 -17439 33 46 30 30
36 -24.805 -1.561 0.885 0.274 2.889 8.605 17030.7 -15470 33 46 30 30
130 18 32.665 1.823 1.268 0.152 -4.399 3.942 19030.3 -17207 33 46 30 30
36 -25.68 -1.823 -1.268 -0.152 -4.918 9.456 17000.3 -15177 33 46 30 30
131 18 32.276 1.489 1.33 -0.044 -4.66 2.58 19016.8 -17528 33 46 30 30
36 -25.291 -1.489 -1.33 0.044 -5.113 8.363 17013.8 -15525 33 46 30 30
132 18 32.789 1.904 1.38 0.15 -4.813 4.275 19034.6 -17131 33 46 30 30
36 -25.804 -1.904 -1.38 -0.15 -5.334 9.722 16996.0 -15092 33 46 30 30
133 18 32.152 1.408 1.217 -0.042 -4.246 2.248 19012.4 -17604 33 46 30 30
36 -25.167 -1.408 -1.217 0.042 -4.697 8.097 17018.1 -15610 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 103
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

REVISION POR CORTANTE COLUMNAS C-2

B= 60 CM
H= 60 CM
f´c= 250 KG/CM2
fy = 4200 KG/CM2
f*c = 200 KG/CM2
f"c = 170 KG/CM2
E# 3
Ramas 4
As = 51 CM2
Barra long. # 8
p= 0.0142
Vcr = 19685.85 KG
0.8*(0.7*f*c*B*H+2000As) 484800.00
Vcrmáx = 101823.38 KG

E#3@... E#3@... E#3@... Armar con


Vcr Vu-Vcr
UNIT METER MTON S4 S5 S6 E#3@...
Beam L/C Node Fx Mton Fy Mton Fz Mton Mx MTon-m My MTon-m Mz MTon-m Kg Kg cm cm cm cm
7 100 7 117.955 -0.396 -0.222 -0.04 1.059 -1.476 24200.9 -23805 33 46 30 30
25 -108.429 0.396 0.222 0.04 0.57 -1.438 15535.4 -15139 33 46 30 30
101 7 117.872 -0.58 -0.125 -0.113 0.558 -2.273 24197.8 -23618 33 46 30 30
25 -108.346 0.58 0.125 0.113 0.362 -1.988 15538.6 -14959 33 46 30 30
102 7 79.132 1.24 -0.851 0.187 3.303 5.185 22714.9 -21475 33 46 30 30
25 -72.147 -1.24 0.851 -0.187 2.95 3.927 16924.2 -15684 33 46 30 30
103 7 81.902 1.085 1.124 -0.125 -4.827 4.611 22820.9 -21697 33 46 30 30
25 -74.917 -1.085 -1.124 0.125 -3.431 3.361 16818.2 -15694 33 46 30 30
104 7 79.015 1.151 -0.934 0.144 3.682 4.817 22710.4 -21559 33 46 30 30
25 -72.029 -1.151 0.934 -0.144 3.184 3.64 16928.7 -15778 33 46 30 30
105 7 82.019 1.174 1.207 -0.082 -5.206 4.979 22825.4 -21618 33 46 30 30
25 -75.034 -1.174 -1.207 0.082 -3.665 3.648 16813.7 -15607 33 46 30 30
106 7 85.88 -2.099 -1.343 -0.081 5.77 -8.526 22973.2 -20874 33 46 30 30
25 -78.894 2.099 1.343 0.081 4.101 -6.903 16665.9 -14567 33 46 30 30
107 7 88.65 -2.254 0.631 -0.393 -2.36 -9.1 23079.2 -20825 33 46 30 30
25 -81.664 2.254 -0.631 0.393 -2.281 -7.469 16559.9 -14306 33 46 30 30
108 7 85.763 -2.188 -1.426 -0.124 6.149 -8.894 22968.7 -20781 33 46 30 30
25 -78.777 2.188 1.426 0.124 4.334 -7.19 16670.4 -14482 33 46 30 30
109 7 88.767 -2.165 0.715 -0.349 -2.739 -8.733 23083.7 -20919 33 46 30 30
25 -81.782 2.165 -0.715 0.349 -2.515 -7.182 16555.4 -14390 33 46 30 30
110 7 78.443 0.819 -1.268 -0.026 5.261 3.4 22688.5 -21420 33 46 30 30
25 -71.458 -0.819 1.268 0.026 4.059 2.622 16950.6 -15683 33 46 30 30
111 7 81.213 0.664 0.706 -0.338 -2.869 2.827 22794.5 -22089 33 46 30 30
25 -74.228 -0.664 -0.706 0.338 -2.323 2.056 16844.5 -16139 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 104
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

112 7 78.326 0.73 -1.351 -0.069 5.64 3.033 22684.0 -21333 33 46 30 30


25 -71.34 -0.73 1.351 0.069 4.292 2.335 16955.1 -15604 33 46 30 30
113 7 81.33 0.753 0.79 -0.295 -3.248 3.194 22799.0 -22009 33 46 30 30
25 -74.345 -0.753 -0.79 0.295 -2.557 2.343 16840.1 -16050 33 46 30 30
114 7 86.569 -1.679 -0.926 0.132 3.812 -6.742 22999.5 -21321 33 46 30 30
25 -79.584 1.679 0.926 -0.132 2.992 -5.598 16639.5 -14961 33 46 30 30
115 7 89.339 -1.834 1.049 -0.18 -4.318 -7.315 23105.6 -21272 33 46 30 30
25 -82.354 1.834 -1.049 0.18 -3.389 -6.164 16533.5 -14700 33 46 30 30
116 7 86.452 -1.768 -1.009 0.089 4.191 -7.109 22995.1 -21227 33 46 30 30
25 -79.466 1.768 1.009 -0.089 3.226 -5.885 16644.0 -14876 33 46 30 30
117 7 89.456 -1.745 1.132 -0.137 -4.697 -6.948 23110.1 -21365 33 46 30 30
25 -82.471 1.745 -1.132 0.137 -3.623 -5.877 16529.0 -14784 33 46 30 30
118 7 78.489 0.465 -2.586 0.663 9.762 2.068 22690.3 -20104 33 46 30 30
25 -71.503 -0.465 2.586 -0.663 9.244 1.347 16948.9 -14363 33 46 30 30
119 7 80.488 -0.796 -2.728 0.585 10.476 -3.353 22766.8 -20039 33 46 30 30
25 -73.503 0.796 2.728 -0.585 9.572 -2.5 16872.3 -14144 33 46 30 30
120 7 78.282 0.338 -2.711 0.599 10.35 1.532 22682.3 -19971 33 46 30 30
25 -71.297 -0.338 2.711 -0.599 9.577 0.955 16956.7 -14246 33 46 30 30
121 7 80.695 -0.67 -2.603 0.649 9.889 -2.818 22774.7 -20172 33 46 30 30
25 -73.71 0.67 2.603 -0.649 9.239 -2.109 16864.4 -14261 33 46 30 30
122 7 87.453 -0.054 2.604 -0.704 -10.03 0.156 23033.4 -20429 33 46 30 30
25 -80.468 0.054 -2.604 0.704 -9.111 -0.554 16605.7 -14002 33 46 30 30
123 7 89.453 -1.315 2.462 -0.782 -9.316 -5.265 23109.9 -20648 33 46 30 30
25 -82.467 1.315 -2.462 0.782 -8.783 -4.401 16529.2 -14067 33 46 30 30
124 7 87.246 -0.18 2.479 -0.768 -9.442 -0.38 23025.5 -20546 33 46 30 30
25 -80.261 0.18 -2.479 0.768 -8.779 -0.945 16613.6 -14135 33 46 30 30
125 7 89.659 -1.189 2.588 -0.718 -9.903 -4.73 23117.8 -20530 33 46 30 30
25 -82.674 1.189 -2.588 0.718 -9.116 -4.009 16521.3 -13933 33 46 30 30
126 7 78.098 0.168 -2.864 0.519 11.026 0.843 22675.3 -19811 33 46 30 30
25 -71.113 -0.168 2.864 -0.519 10.023 0.39 16963.8 -14100 33 46 30 30
127 7 80.097 -1.093 -3.006 0.441 11.74 -4.578 22751.8 -19746 33 46 30 30
25 -73.112 1.093 3.006 -0.441 10.351 -3.457 16887.3 -13881 33 46 30 30
128 7 77.891 0.042 -2.989 0.455 11.613 0.307 22667.4 -19678 33 46 30 30
25 -70.906 -0.042 2.989 -0.455 10.356 -0.001 16971.7 -13983 33 46 30 30
129 7 80.304 -0.967 -2.88 0.505 11.152 -4.043 22759.7 -19880 33 46 30 30
25 -73.319 0.967 2.88 -0.505 10.019 -3.065 16879.3 -13999 33 46 30 30
130 7 87.844 0.243 2.882 -0.56 -11.293 1.38 23048.3 -20166 33 46 30 30
25 -80.859 -0.243 -2.882 0.56 -9.89 0.403 16590.7 -13709 33 46 30 30
131 7 89.844 -1.018 2.74 -0.638 -10.579 -4.04 23124.9 -20385 33 46 30 30
25 -82.858 1.018 -2.74 0.638 -9.563 -3.444 16514.2 -13774 33 46 30 30
132 7 87.637 0.116 2.757 -0.624 -10.706 0.845 23040.4 -20283 33 46 30 30
25 -80.652 -0.116 -2.757 0.624 -9.558 0.011 16598.7 -13842 33 46 30 30
133 7 90.05 -0.892 2.866 -0.574 -11.166 -3.505 23132.8 -20267 33 46 30 30
25 -83.065 0.892 -2.866 0.574 -9.895 -3.053 16506.3 -13640 33 46 30 30
8 100 8 139.945 0.032 -0.458 -0.019 1.702 0.168 25042.7 -24585 33 46 30 30
26 -130.42 -0.032 0.458 0.019 1.667 0.069 14693.6 -14236 33 46 30 30
101 8 139.881 0.044 -0.38 0.02 1.277 0.23 25040.2 -24660 33 46 30 30
26 -130.356 -0.044 0.38 -0.02 1.513 0.092 14696.1 -14316 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 105
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

102 8 98.112 1.621 -1.367 0.318 5.443 6.929 23441.4 -21820 33 46 30 30


26 -91.127 -1.621 1.367 -0.318 4.605 4.984 16197.7 -14577 33 46 30 30
103 8 101.13 1.497 0.943 0.203 -4.015 6.439 23556.9 -22060 33 46 30 30
26 -94.144 -1.497 -0.943 -0.203 -2.918 4.564 16082.2 -14585 33 46 30 30
104 8 98.089 1.532 -1.37 0.237 5.46 6.559 23440.5 -21909 33 46 30 30
26 -91.104 -1.532 1.37 -0.237 4.609 4.703 16198.6 -14667 33 46 30 30
105 8 101.153 1.585 0.946 0.284 -4.031 6.808 23557.8 -21973 33 46 30 30
26 -94.167 -1.585 -0.946 -0.284 -2.922 4.845 16081.3 -14496 33 46 30 30
106 8 97.004 -1.506 -1.577 -0.119 6.074 -6.371 23399.0 -21822 33 46 30 30
26 -90.019 1.506 1.577 0.119 5.514 -4.702 16240.1 -14663 33 46 30 30
107 8 100.021 -1.63 0.734 -0.233 -3.384 -6.86 23514.5 -21884 33 46 30 30
26 -93.036 1.63 -0.734 0.233 -2.009 -5.122 16124.6 -14495 33 46 30 30
108 8 96.981 -1.595 -1.579 -0.2 6.091 -6.74 23398.1 -21803 33 46 30 30
26 -89.996 1.595 1.579 0.2 5.518 -4.983 16241.0 -14646 33 46 30 30
109 8 100.044 -1.542 0.737 -0.152 -3.401 -6.491 23515.3 -21973 33 46 30 30
26 -93.059 1.542 -0.737 0.152 -2.013 -4.841 16123.7 -14582 33 46 30 30
110 8 98.007 1.206 -1.392 -0.104 5.566 5.143 23437.4 -22045 33 46 30 30
26 -91.021 -1.206 1.392 0.104 4.668 3.722 16201.7 -14810 33 46 30 30
111 8 101.024 1.082 0.918 -0.218 -3.891 4.654 23552.9 -22471 33 46 30 30
26 -94.039 -1.082 -0.918 0.218 -2.855 3.301 16086.2 -15004 33 46 30 30
112 8 97.984 1.118 -1.395 -0.185 5.583 4.774 23436.5 -22041 33 46 30 30
26 -90.998 -1.118 1.395 0.185 4.672 3.441 16202.6 -14808 33 46 30 30
113 8 101.047 1.171 0.921 -0.138 -3.908 5.023 23553.7 -22383 33 46 30 30
26 -94.062 -1.171 -0.921 0.138 -2.859 3.583 16085.3 -14914 33 46 30 30
114 8 97.11 -1.092 -1.551 0.303 5.951 -4.586 23403.0 -21852 33 46 30 30
26 -90.124 1.092 1.551 -0.303 5.451 -3.439 16236.1 -14685 33 46 30 30
115 8 100.127 -1.216 0.759 0.189 -3.507 -5.075 23518.5 -22303 33 46 30 30
26 -93.142 1.216 -0.759 -0.189 -2.072 -3.86 16120.6 -14905 33 46 30 30
116 8 97.087 -1.18 -1.554 0.222 5.968 -4.955 23402.2 -21848 33 46 30 30
26 -90.101 1.18 1.554 -0.222 5.455 -3.721 16237.0 -14683 33 46 30 30
117 8 100.15 -1.127 0.762 0.27 -3.524 -4.706 23519.4 -22392 33 46 30 30
26 -93.165 1.127 -0.762 -0.27 -2.076 -3.579 16119.7 -14993 33 46 30 30
118 8 94.148 0.772 -4.265 0.211 16.853 3.37 23289.7 -19025 33 46 30 30
26 -87.163 -0.772 4.265 -0.211 14.495 2.303 16349.4 -12084 33 46 30 30
119 8 93.832 -0.402 -4.325 0.07 17.036 -1.842 23277.6 -18953 33 46 30 30
26 -86.847 0.402 4.325 -0.07 14.756 -1.114 16361.5 -12037 33 46 30 30
120 8 94.117 0.647 -4.273 0.084 16.89 2.834 23288.5 -19015 33 46 30 30
26 -87.131 -0.647 4.273 -0.084 14.514 1.925 16350.6 -12078 33 46 30 30
121 8 93.864 -0.278 -4.318 0.196 16.999 -1.306 23278.8 -18961 33 46 30 30
26 -86.879 0.278 4.318 -0.196 14.737 -0.735 16360.3 -12042 33 46 30 30
122 8 104.353 0.375 3.757 -0.091 -15.331 1.819 23680.3 -19923 33 46 30 30
26 -97.368 -0.375 -3.757 0.091 -12.283 0.937 15958.8 -12202 33 46 30 30
123 8 104.037 -0.799 3.697 -0.233 -15.149 -3.392 23668.2 -19971 33 46 30 30
26 -97.052 0.799 -3.697 0.233 -12.023 -2.48 15970.9 -12274 33 46 30 30
124 8 104.322 0.251 3.75 -0.218 -15.294 1.284 23679.1 -19929 33 46 30 30
26 -97.336 -0.251 -3.75 0.218 -12.264 0.558 15960.0 -12210 33 46 30 30
125 8 104.069 -0.675 3.704 -0.106 -15.186 -2.856 23669.4 -19965 33 46 30 30
26 -97.084 0.675 -3.704 0.106 -12.042 -2.101 15969.7 -12266 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 106
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

126 8 94.072 0.477 -4.275 -0.059 16.909 2.139 23286.7 -19012 33 46 30 30


26 -87.086 -0.477 4.275 0.059 14.509 1.365 16352.4 -12077 33 46 30 30
127 8 93.756 -0.697 -4.335 -0.2 17.091 -3.072 23274.6 -18940 33 46 30 30
26 -86.77 0.697 4.335 0.2 14.77 -2.052 16364.5 -12029 33 46 30 30
128 8 94.04 0.352 -4.282 -0.186 16.946 1.603 23285.5 -19004 33 46 30 30
26 -87.055 -0.352 4.282 0.186 14.528 0.986 16353.6 -12072 33 46 30 30
129 8 93.787 -0.573 -4.327 -0.074 17.055 -2.537 23275.8 -18949 33 46 30 30
26 -86.802 0.573 4.327 0.074 14.751 -1.673 16363.2 -12036 33 46 30 30
130 8 104.43 0.67 3.767 0.179 -15.387 3.05 23683.2 -19916 33 46 30 30
26 -97.445 -0.67 -3.767 -0.179 -12.297 1.875 15955.8 -12189 33 46 30 30
131 8 104.114 -0.504 3.706 0.037 -15.205 -2.161 23671.1 -19965 33 46 30 30
26 -97.129 0.504 -3.706 -0.037 -12.037 -1.542 15967.9 -12262 33 46 30 30
132 8 104.398 0.546 3.759 0.052 -15.35 2.515 23682.0 -19923 33 46 30 30
26 -97.413 -0.546 -3.759 -0.052 -12.279 1.496 15957.1 -12198 33 46 30 30
133 8 104.146 -0.379 3.714 0.164 -15.242 -1.625 23672.4 -19958 33 46 30 30
26 -97.16 0.379 -3.714 -0.164 -12.056 -1.163 15966.8 -12253 33 46 30 30
9 100 9 117.792 0.527 -0.073 -0.071 0.672 1.893 24194.7 -23668 33 46 30 30
27 -108.267 -0.527 0.073 0.071 -0.133 1.982 15541.6 -15015 33 46 30 30
101 9 117.629 0.738 0.104 -0.253 -0.179 2.838 24188.5 -23450 33 46 30 30
27 -108.103 -0.738 -0.104 0.253 -0.583 2.586 15547.9 -14810 33 46 30 30
102 9 94.204 1.914 -0.517 -0.204 3.565 8.461 23291.8 -21378 33 46 30 30
27 -87.218 -1.914 0.517 0.204 0.238 5.608 16347.3 -14433 33 46 30 30
103 9 97.181 1.813 1.207 0.12 -3.952 8.038 23405.8 -21593 33 46 30 30
27 -90.195 -1.813 -1.207 -0.12 -4.917 5.284 16233.4 -14420 33 46 30 30
104 9 94.314 1.824 -0.458 -0.245 3.264 8.092 23296.0 -21472 33 46 30 30
27 -87.328 -1.824 0.458 0.245 0.101 5.318 16343.1 -14519 33 46 30 30
105 9 97.071 1.902 1.147 0.161 -3.65 8.407 23401.5 -21500 33 46 30 30
27 -90.085 -1.902 -1.147 -0.161 -4.779 5.574 16237.6 -14336 33 46 30 30
106 9 88.05 -1.441 -0.413 -0.47 2.465 -5.291 23056.2 -21615 33 46 30 30
27 -81.065 1.441 0.413 0.47 0.57 -5.297 16582.8 -15142 33 46 30 30
107 9 91.027 -1.542 1.311 -0.146 -5.052 -5.715 23170.2 -21628 33 46 30 30
27 -84.042 1.542 -1.311 0.146 -4.585 -5.621 16468.9 -14927 33 46 30 30
108 9 88.16 -1.53 -0.353 -0.511 2.163 -5.661 23060.4 -21530 33 46 30 30
27 -81.175 1.53 0.353 0.511 0.432 -5.587 16578.6 -15049 33 46 30 30
109 9 90.917 -1.452 1.252 -0.105 -4.751 -5.345 23166.0 -21714 33 46 30 30
27 -83.932 1.452 -1.252 0.105 -4.448 -5.331 16473.1 -15021 33 46 30 30
110 9 94.837 1.491 -0.241 -0.406 2.074 6.668 23316.0 -21825 33 46 30 30
27 -87.851 -1.491 0.241 0.406 -0.304 4.289 16323.1 -14832 33 46 30 30
111 9 97.814 1.389 1.483 -0.082 -5.443 6.245 23430.0 -21947 33 46 30 30
27 -90.828 -1.389 -1.483 0.082 -5.459 3.965 16209.1 -14726 33 46 30 30
112 9 94.947 1.401 -0.181 -0.448 1.773 6.299 23320.2 -21919 33 46 30 30
27 -87.961 -1.401 0.181 0.448 -0.441 3.999 16318.9 -14918 33 46 30 30
113 9 97.704 1.479 1.423 -0.041 -5.141 6.614 23425.8 -21947 33 46 30 30
27 -90.718 -1.479 -1.423 0.041 -5.321 4.255 16213.3 -14734 33 46 30 30
114 9 87.417 -1.017 -0.689 -0.268 3.956 -3.498 23032.0 -22015 33 46 30 30
27 -80.432 1.017 0.689 0.268 1.112 -3.978 16607.1 -15590 33 46 30 30
115 9 90.394 -1.119 1.035 0.056 -3.561 -3.921 23146.0 -22027 33 46 30 30
27 -83.409 1.119 -1.035 -0.056 -4.043 -4.302 16493.1 -15374 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 107
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

116 9 87.527 -1.107 -0.63 -0.309 3.654 -3.868 23036.2 -21929 33 46 30 30


27 -80.542 1.107 0.63 0.309 0.974 -4.268 16602.9 -15496 33 46 30 30
117 9 90.284 -1.029 0.975 0.098 -3.26 -3.552 23141.7 -22113 33 46 30 30
27 -83.299 1.029 -0.975 -0.098 -3.906 -4.012 16497.3 -15468 33 46 30 30
118 9 88.572 0.884 -1.645 -0.772 7.735 4.334 23076.2 -21431 33 46 30 30
27 -81.587 -0.884 1.645 0.772 4.353 2.162 16562.9 -14918 33 46 30 30
119 9 86.754 -0.391 -1.608 -0.849 7.383 -1.142 23006.6 -21399 33 46 30 30
27 -79.768 0.391 1.608 0.849 4.436 -1.735 16632.5 -15024 33 46 30 30
120 9 88.762 0.757 -1.562 -0.832 7.288 3.796 23083.5 -21521 33 46 30 30
27 -81.776 -0.757 1.562 0.832 4.19 1.766 16555.6 -14994 33 46 30 30
121 9 86.564 -0.264 -1.691 -0.788 7.83 -0.604 22999.4 -21308 33 46 30 30
27 -79.578 0.264 1.691 0.788 4.598 -1.34 16639.8 -14949 33 46 30 30
122 9 98.569 0.574 2.571 0.461 -9.692 3.045 23458.9 -20888 33 46 30 30
27 -91.583 -0.574 -2.571 -0.461 -9.208 1.178 16180.2 -13609 33 46 30 30
123 9 96.75 -0.701 2.608 0.384 -10.044 -2.431 23389.3 -20781 33 46 30 30
27 -89.765 0.701 -2.608 -0.384 -9.125 -2.719 16249.8 -13642 33 46 30 30
124 9 98.759 0.447 2.654 0.4 -10.139 2.507 23466.2 -20812 33 46 30 30
27 -91.773 -0.447 -2.654 -0.4 -9.371 0.782 16173.0 -13519 33 46 30 30
125 9 96.56 -0.574 2.525 0.444 -9.597 -1.893 23382.0 -20857 33 46 30 30
27 -89.575 0.574 -2.525 -0.444 -8.963 -2.324 16257.1 -13732 33 46 30 30
126 9 88.939 0.585 -1.445 -0.909 6.73 3.103 23090.3 -21645 33 46 30 30
27 -81.953 -0.585 1.445 0.909 3.894 1.194 16548.9 -15104 33 46 30 30
127 9 87.12 -0.691 -1.409 -0.986 6.378 -2.373 23020.6 -21612 33 46 30 30
27 -80.135 0.691 1.409 0.986 3.977 -2.703 16618.4 -15209 33 46 30 30
128 9 89.129 0.458 -1.362 -0.97 6.283 2.565 23097.5 -21736 33 46 30 30
27 -82.143 -0.458 1.362 0.97 3.731 0.798 16541.6 -15180 33 46 30 30
129 9 86.93 -0.564 -1.492 -0.925 6.825 -1.836 23013.4 -21521 33 46 30 30
27 -79.945 0.564 1.492 0.925 4.139 -2.308 16625.7 -15134 33 46 30 30
130 9 98.202 0.874 2.372 0.598 -8.687 4.276 23444.8 -21073 33 46 30 30
27 -91.217 -0.874 -2.372 -0.598 -8.749 2.146 16194.2 -13822 33 46 30 30
131 9 96.383 -0.401 2.409 0.521 -9.039 -1.2 23375.2 -20966 33 46 30 30
27 -89.398 0.401 -2.409 -0.521 -8.667 -1.751 16263.9 -13855 33 46 30 30
132 9 98.392 0.747 2.455 0.537 -9.134 3.739 23452.1 -20997 33 46 30 30
27 -91.406 -0.747 -2.455 -0.537 -8.912 1.75 16187.0 -13732 33 46 30 30
133 9 96.194 -0.274 2.326 0.582 -8.592 -0.662 23368.0 -21042 33 46 30 30
27 -89.208 0.274 -2.326 -0.582 -8.504 -1.356 16271.1 -13945 33 46 30 30
14 100 14 116.615 0.494 -0.301 0.091 0.586 1.968 24149.6 -23656 33 46 30 30
32 -107.09 -0.494 0.301 -0.091 1.629 1.666 15586.7 -15093 33 46 30 30
101 14 116.547 0.639 -0.411 0.298 1.074 2.622 24147.0 -23508 33 46 30 30
32 -107.022 -0.639 0.411 -0.298 1.945 2.075 15589.3 -14950 33 46 30 30
102 14 100.184 0.145 -1.566 0.383 5.832 2.222 23520.7 -21955 33 46 30 30
32 -93.198 -0.145 1.566 -0.383 5.675 -1.155 16118.4 -14552 33 46 30 30
103 14 96.778 0.141 0.146 0.781 -1.701 2.247 23390.3 -23244 33 46 30 30
32 -89.793 -0.141 -0.146 -0.781 0.627 -1.207 16248.8 -16103 33 46 30 30
104 14 100.05 0.12 -1.504 0.329 5.521 2.181 23515.6 -22012 33 46 30 30
32 -93.065 -0.12 1.504 -0.329 5.532 -1.297 16123.5 -14620 33 46 30 30
105 14 96.912 0.166 0.084 0.835 -1.389 2.288 23395.5 -23229 33 46 30 30
32 -89.927 -0.166 -0.084 -0.835 0.77 -1.065 16243.6 -16078 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 108
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

106 14 87.249 0.116 -1.422 -0.386 4.607 0.225 23025.6 -21604 33 46 30 30


32 -80.263 -0.116 1.422 0.386 5.843 0.626 16613.5 -15192 33 46 30 30
107 14 83.843 0.112 0.29 0.011 -2.927 0.25 22895.2 -22605 33 46 30 30
32 -76.858 -0.112 -0.29 -0.011 0.795 0.574 16743.9 -16454 33 46 30 30
108 14 87.115 0.091 -1.36 -0.441 4.295 0.184 23020.4 -21660 33 46 30 30
32 -80.13 -0.091 1.36 0.441 5.7 0.484 16618.6 -15259 33 46 30 30
109 14 83.977 0.137 0.228 0.065 -2.615 0.291 22900.3 -22672 33 46 30 30
32 -76.992 -0.137 -0.228 -0.065 0.938 0.716 16738.7 -16511 33 46 30 30
110 14 99.435 0.002 -1.279 0.117 4.293 1.983 23492.0 -22213 33 46 30 30
32 -92.45 -0.002 1.279 -0.117 5.109 -1.969 16147.0 -14868 33 46 30 30
111 14 96.029 -0.002 0.433 0.515 -3.241 2.008 23361.7 -22929 33 46 30 30
32 -89.044 0.002 -0.433 -0.515 0.061 -2.021 16277.4 -15844 33 46 30 30
112 14 99.301 -0.023 -1.217 0.063 3.981 1.942 23486.9 -22270 33 46 30 30
32 -92.316 0.023 1.217 -0.063 4.966 -2.111 16152.2 -14935 33 46 30 30
113 14 96.163 0.023 0.371 0.569 -2.929 2.049 23366.8 -22996 33 46 30 30
32 -89.178 -0.023 -0.371 -0.569 0.204 -1.879 16272.3 -15901 33 46 30 30
114 14 87.998 0.259 -1.708 -0.12 6.146 0.464 23054.2 -21346 33 46 30 30
32 -81.012 -0.259 1.708 0.12 6.409 1.44 16584.9 -14877 33 46 30 30
115 14 84.592 0.255 0.003 0.277 -1.387 0.489 22923.9 -22669 33 46 30 30
32 -77.606 -0.255 -0.003 -0.277 1.361 1.389 16715.2 -16460 33 46 30 30
116 14 87.864 0.234 -1.646 -0.174 5.835 0.423 23049.1 -21403 33 46 30 30
32 -80.878 -0.234 1.646 0.174 6.266 1.298 16590.0 -14944 33 46 30 30
117 14 84.726 0.28 -0.058 0.332 -1.075 0.53 22929.0 -22649 33 46 30 30
32 -77.74 -0.28 0.058 -0.332 1.504 1.531 16710.1 -16430 33 46 30 30
118 14 99.558 0.128 -2.853 -0.455 10.888 1.466 23496.7 -20644 33 46 30 30
32 -92.573 -0.128 2.853 0.455 10.082 -0.525 16142.3 -13289 33 46 30 30
119 14 95.821 -0.026 -2.807 -0.696 10.509 0.22 23353.7 -20547 33 46 30 30
32 -88.836 0.026 2.807 0.696 10.123 -0.408 16285.4 -13478 33 46 30 30
120 14 99.334 0.085 -2.767 -0.535 10.427 1.394 23488.2 -20721 33 46 30 30
32 -92.348 -0.085 2.767 0.535 9.912 -0.77 16151.0 -13384 33 46 30 30
121 14 96.046 0.017 -2.893 -0.616 10.971 0.292 23362.3 -20469 33 46 30 30
32 -89.061 -0.017 2.893 0.616 10.293 -0.164 16276.8 -13384 33 46 30 30
122 14 88.211 0.153 1.439 1.181 -7.192 1.663 23062.4 -21623 33 46 30 30
32 -81.225 -0.153 -1.439 -1.181 -3.381 -0.54 16576.7 -15138 33 46 30 30
123 14 84.474 -0.001 1.485 0.941 -7.571 0.417 22919.4 -21434 33 46 30 30
32 -77.488 0.001 -1.485 -0.941 -3.341 -0.423 16719.8 -15235 33 46 30 30
124 14 87.986 0.11 1.525 1.102 -7.654 1.591 23053.8 -21529 33 46 30 30
32 -81.001 -0.11 -1.525 -1.102 -3.551 -0.784 16585.3 -15060 33 46 30 30
125 14 84.698 0.042 1.399 1.02 -7.11 0.489 22927.9 -21529 33 46 30 30
32 -77.713 -0.042 -1.399 -1.02 -3.171 -0.179 16711.2 -15312 33 46 30 30
126 14 99.112 0.045 -2.647 -0.636 9.85 1.329 23479.7 -20833 33 46 30 30
32 -92.127 -0.045 2.647 0.636 9.607 -0.999 16159.4 -13512 33 46 30 30
127 14 95.375 -0.109 -2.601 -0.877 9.47 0.083 23336.6 -20736 33 46 30 30
32 -88.39 0.109 2.601 0.877 9.647 -0.881 16302.5 -13701 33 46 30 30
128 14 98.888 0.002 -2.561 -0.716 9.388 1.257 23471.1 -20910 33 46 30 30
32 -91.902 -0.002 2.561 0.716 9.437 -1.243 16168.0 -13607 33 46 30 30
129 14 95.6 -0.066 -2.687 -0.797 9.932 0.155 23345.2 -20658 33 46 30 30
32 -88.615 0.066 2.687 0.797 9.817 -0.637 16293.8 -13607 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 109
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

130 14 88.657 0.236 1.233 1.362 -6.153 1.8 23079.5 -21846 33 46 30 30


32 -81.671 -0.236 -1.233 -1.362 -2.906 -0.067 16559.6 -15327 33 46 30 30
131 14 84.92 0.082 1.279 1.121 -6.533 0.554 22936.4 -21657 33 46 30 30
32 -77.934 -0.082 -1.279 -1.121 -2.865 0.05 16702.7 -15424 33 46 30 30
132 14 88.432 0.193 1.318 1.282 -6.615 1.728 23070.9 -21753 33 46 30 30
32 -81.447 -0.193 -1.318 -1.282 -3.076 -0.311 16568.2 -15250 33 46 30 30
133 14 85.144 0.125 1.193 1.201 -6.071 0.626 22945.0 -21752 33 46 30 30
32 -78.159 -0.125 -1.193 -1.201 -2.695 0.295 16694.1 -15501 33 46 30 30
85 100 25 24.346 -3.648 6.731 0.075 -12.588 -5.431 20617.8 -13887 33 46 30 30
61 -19.032 3.648 -6.731 -0.075 -15.009 -9.526 18957.3 -12226 33 46 30 30
101 25 24.351 -3.612 6.735 0.04 -12.575 -5.296 20618.0 -13883 33 46 30 30
61 -19.037 3.612 -6.735 -0.04 -15.038 -9.511 18957.2 -12222 33 46 30 30
102 25 13.364 4.743 4.455 1.311 -8.527 12.791 20197.4 -15454 33 46 30 30
61 -9.467 -4.743 -4.455 -1.311 -9.737 6.654 19323.5 -14580 33 46 30 30
103 25 15.834 4.368 8.853 1.343 -18.189 11.957 20291.9 -11439 33 46 30 30
61 -11.937 -4.368 -8.853 -1.343 -18.107 5.953 19228.9 -10376 33 46 30 30
104 25 13.263 4.441 3.932 1.107 -7.343 12.127 20193.5 -15753 33 46 30 30
61 -9.366 -4.441 -3.932 -1.107 -8.779 6.08 19327.3 -14886 33 46 30 30
105 25 15.935 4.67 9.375 1.547 -19.373 12.622 20295.8 -10921 33 46 30 30
61 -12.038 -4.67 -9.375 -1.547 -19.065 6.527 19225.1 -9850 33 46 30 30
106 25 18.893 -8.967 0.694 -1.312 0.45 -18.188 20409.0 -11442 33 46 30 30
61 -14.997 8.967 -0.694 1.312 -3.295 -18.575 19111.8 -10145 33 46 30 30
107 25 21.363 -9.341 5.092 -1.279 -9.212 -19.022 20503.6 -11163 33 46 30 30
61 -17.466 9.341 -5.092 1.279 -11.665 -19.276 19017.3 -9676 33 46 30 30
108 25 18.792 -9.269 0.172 -1.515 1.634 -18.852 20405.2 -11136 33 46 30 30
61 -14.895 9.269 -0.172 1.515 -2.337 -19.149 19115.7 -9847 33 46 30 30
109 25 21.464 -9.039 5.614 -1.076 -10.396 -18.358 20507.5 -11468 33 46 30 30
61 -17.567 9.039 -5.614 1.076 -12.623 -18.702 19013.4 -9974 33 46 30 30
110 25 12.799 3.022 1.526 0.194 -1.885 8.964 20175.8 -17154 33 46 30 30
61 -8.903 -3.022 -1.526 -0.194 -4.373 3.426 19345.1 -16323 33 46 30 30
111 25 15.269 2.648 5.924 0.226 -11.547 8.13 20270.3 -14346 33 46 30 30
61 -11.372 -2.648 -5.924 -0.226 -12.743 2.726 19250.6 -13327 33 46 30 30
112 25 12.698 2.72 1.004 -0.01 -0.7 8.3 20171.9 -17452 33 46 30 30
61 -8.801 -2.72 -1.004 0.01 -3.415 2.853 19349.0 -16629 33 46 30 30
113 25 15.37 2.95 6.447 0.429 -12.731 8.795 20274.2 -13827 33 46 30 30
61 -11.473 -2.95 -6.447 -0.429 -13.701 3.299 19246.7 -12800 33 46 30 30
114 25 19.458 -7.246 3.622 -0.195 -6.192 -14.361 20430.7 -13185 33 46 30 30
61 -15.561 7.246 -3.622 0.195 -8.659 -15.348 19090.2 -11844 33 46 30 30
115 25 21.928 -7.62 8.021 -0.162 -15.855 -15.195 20525.2 -12504 33 46 30 30
61 -18.031 7.62 -8.021 0.162 -17.03 -16.049 18995.7 -10975 33 46 30 30
116 25 19.357 -7.548 3.1 -0.398 -5.008 -15.025 20426.8 -12879 33 46 30 30
61 -15.46 7.548 -3.1 0.398 -7.701 -15.922 19094.1 -11546 33 46 30 30
117 25 22.029 -7.318 8.543 0.041 -17.039 -14.531 20529.1 -11986 33 46 30 30
61 -18.132 7.318 -8.543 -0.041 -17.987 -15.475 18991.8 -10449 33 46 30 30
118 25 12.491 0.362 -1.9 0.234 5.811 2.841 20164.0 -18264 33 46 30 30
61 -8.595 -0.362 1.9 -0.234 1.98 -1.357 19356.9 -17457 33 46 30 30
119 25 14.209 -3.807 -2.982 -0.505 8.392 -6.541 20229.7 -16423 33 46 30 30
61 -10.312 3.807 2.982 0.505 3.833 -9.07 19291.1 -15484 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 110
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

120 25 12.322 -0.154 -2.779 -0.101 7.803 1.693 20157.5 -17379 33 46 30 30


61 -8.425 0.154 2.779 0.101 3.589 -2.325 19363.4 -16584 33 46 30 30
121 25 14.378 -3.291 -2.103 -0.169 6.4 -5.393 20236.2 -16945 33 46 30 30
61 -10.482 3.291 2.103 0.169 2.224 -8.101 19284.6 -15994 33 46 30 30
122 25 20.535 -0.829 12.536 0.539 -26.119 0.18 20471.9 -7936 33 46 30 30
61 -16.638 0.829 -12.536 -0.539 -25.278 -3.579 19049.0 -6513 33 46 30 30
123 25 22.253 -4.998 11.454 -0.2 -23.537 -9.202 20537.7 -9084 33 46 30 30
61 -18.356 4.998 -11.454 0.2 -23.424 -11.291 18983.2 -7529 33 46 30 30
124 25 20.366 -1.345 11.657 0.204 -24.126 -0.968 20465.4 -8808 33 46 30 30
61 -16.469 1.345 -11.657 -0.204 -23.668 -4.547 19055.5 -7398 33 46 30 30
125 25 22.422 -4.482 12.333 0.135 -25.53 -8.054 20544.1 -8211 33 46 30 30
61 -18.525 4.482 -12.333 -0.135 -25.034 -10.323 18976.8 -6644 33 46 30 30
126 25 12.154 -0.644 -3.641 -0.444 9.758 0.627 20151.1 -16510 33 46 30 30
61 -8.257 0.644 3.641 0.444 5.172 -3.269 19369.8 -15729 33 46 30 30
127 25 13.871 -4.814 -4.723 -1.183 12.339 -8.756 20216.8 -15403 33 46 30 30
61 -9.975 4.814 4.723 1.183 7.025 -10.982 19304.0 -14490 33 46 30 30
128 25 11.984 -1.161 -4.52 -0.779 11.75 -0.521 20144.6 -15625 33 46 30 30
61 -8.088 1.161 4.52 0.779 6.781 -4.237 19376.3 -14856 33 46 30 30
129 25 14.041 -4.298 -3.845 -0.848 10.346 -7.608 20223.3 -15925 33 46 30 30
61 -10.144 4.298 3.845 0.848 5.416 -10.013 19297.6 -15000 33 46 30 30
130 25 20.873 0.178 14.277 1.217 -30.065 2.395 20484.8 -6208 33 46 30 30
61 -16.976 -0.178 -14.277 -1.217 -28.47 -1.667 19036.0 -4759 33 46 30 30
131 25 22.59 -3.992 13.195 0.479 -27.484 -6.987 20550.6 -7356 33 46 30 30
61 -18.693 3.992 -13.195 -0.479 -26.617 -9.38 18970.3 -5775 33 46 30 30
132 25 20.703 -0.339 13.398 0.882 -28.073 1.247 20478.3 -7080 33 46 30 30
61 -16.806 0.339 -13.398 -0.882 -26.86 -2.635 19042.6 -5645 33 46 30 30
133 25 22.759 -3.476 14.074 0.814 -29.477 -5.839 20557.0 -6483 33 46 30 30
61 -18.863 3.476 -14.074 -0.814 -28.226 -8.411 18963.8 -4890 33 46 30 30
86 100 26 43.381 0.204 8.814 0.139 -12.487 0.33 21346.4 -12532 33 46 30 30
62 -38.067 -0.204 -8.814 -0.139 -23.65 0.507 18228.7 -9415 33 46 30 30
101 26 43.392 0.203 8.815 0.148 -12.472 0.324 21346.8 -12532 33 46 30 30
62 -38.079 -0.203 -8.815 -0.148 -23.671 0.507 18228.3 -9413 33 46 30 30
102 26 29.964 9.968 3.736 1.226 -3.159 19.384 20832.8 -10865 33 46 30 30
62 -26.067 -9.968 -3.736 -1.226 -12.157 21.487 18688.1 -8720 33 46 30 30
103 26 32.781 9.603 8.788 1.082 -13.948 18.714 20940.6 -11338 33 46 30 30
62 -28.884 -9.603 -8.788 -1.082 -22.081 20.657 18580.2 -8977 33 46 30 30
104 26 29.958 9.548 3.726 1.041 -3.141 18.577 20832.6 -11285 33 46 30 30
62 -26.062 -9.548 -3.726 -1.041 -12.134 20.569 18688.3 -9140 33 46 30 30
105 26 32.786 10.023 8.797 1.267 -13.966 19.521 20940.8 -10918 33 46 30 30
62 -28.89 -10.023 -8.797 -1.267 -22.103 21.574 18580.0 -8557 33 46 30 30
106 26 29.706 -8.673 3.547 -0.875 -3.147 -16.602 20822.9 -12150 33 46 30 30
62 -25.81 8.673 -3.547 0.875 -11.396 -18.958 18697.9 -10025 33 46 30 30
107 26 32.524 -9.039 8.599 -1.019 -13.936 -17.271 20930.8 -11892 33 46 30 30
62 -28.627 9.039 -8.599 1.019 -21.32 -19.788 18590.1 -9551 33 46 30 30
108 26 29.701 -9.094 3.538 -1.06 -3.13 -17.408 20822.7 -11729 33 46 30 30
62 -25.804 9.094 -3.538 1.06 -11.374 -19.876 18698.1 -9604 33 46 30 30
109 26 32.529 -8.618 8.609 -0.834 -13.954 -16.465 20931.0 -12313 33 46 30 30
62 -28.632 8.618 -8.609 0.834 -21.343 -18.871 18589.9 -9972 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 111
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

110 26 29.931 7.587 3.67 0.204 -3.027 14.777 20831.6 -13245 33 46 30 30


62 -26.034 -7.587 -3.67 -0.204 -12.02 16.33 18689.3 -11102 33 46 30 30
111 26 32.748 7.221 8.722 0.059 -13.816 14.108 20939.4 -12217 33 46 30 30
62 -28.851 -7.221 -8.722 -0.059 -21.944 15.5 18581.5 -9859 33 46 30 30
112 26 29.925 7.167 3.66 0.018 -3.009 13.971 20831.3 -13664 33 46 30 30
62 -26.029 -7.167 -3.66 -0.018 -11.997 15.412 18689.5 -11523 33 46 30 30
113 26 32.753 7.642 8.732 0.245 -13.834 14.914 20939.6 -12208 33 46 30 30
62 -28.857 -7.642 -8.732 -0.245 -21.966 16.418 18581.3 -9849 33 46 30 30
114 26 29.739 -6.292 3.613 0.148 -3.279 -11.995 20824.2 -14532 33 46 30 30
62 -25.843 6.292 -3.613 -0.148 -11.533 -13.802 18696.6 -12405 33 46 30 30
115 26 32.557 -6.658 8.665 0.003 -14.069 -12.665 20932.1 -12267 33 46 30 30
62 -28.66 6.658 -8.665 -0.003 -21.457 -14.632 18588.8 -9924 33 46 30 30
116 26 29.734 -6.712 3.603 -0.038 -3.262 -12.802 20824.0 -14112 33 46 30 30
62 -25.837 6.712 -3.603 0.038 -11.511 -14.719 18696.9 -11985 33 46 30 30
117 26 32.562 -6.237 8.675 0.189 -14.086 -11.858 20932.3 -12257 33 46 30 30
62 -28.665 6.237 -8.675 -0.189 -21.48 -13.714 18588.6 -9914 33 46 30 30
118 26 26.562 3.857 -2.226 0.635 9.327 7.517 20702.6 -16846 33 46 30 30
62 -22.665 -3.857 2.226 -0.635 -0.2 8.295 18818.3 -14961 33 46 30 30
119 26 26.486 -1.805 -2.281 0.036 9.33 -3.352 20699.7 -18419 33 46 30 30
62 -22.59 1.805 2.281 -0.036 0.022 -4.049 18821.2 -16540 33 46 30 30
120 26 26.552 3.142 -2.246 0.328 9.367 6.135 20702.2 -17560 33 46 30 30
62 -22.655 -3.142 2.246 -0.328 -0.159 6.748 18818.7 -15677 33 46 30 30
121 26 26.496 -1.091 -2.261 0.343 9.291 -1.97 20700.1 -18439 33 46 30 30
62 -22.6 1.091 2.261 -0.343 -0.019 -2.502 18820.8 -16560 33 46 30 30
122 26 36.006 2.73 14.624 0.156 -26.427 5.462 21064.1 -6440 33 46 30 30
62 -32.11 -2.73 -14.624 -0.156 -33.533 5.731 18456.7 -3833 33 46 30 30
123 26 35.931 -2.932 14.569 -0.443 -26.424 -5.406 21061.2 -6492 33 46 30 30
62 -32.034 2.932 -14.569 0.443 -33.311 -6.614 18459.7 -3891 33 46 30 30
124 26 35.996 2.016 14.605 -0.151 -26.387 4.08 21063.7 -6459 33 46 30 30
62 -32.1 -2.016 -14.605 0.151 -33.492 4.184 18457.1 -3852 33 46 30 30
125 26 35.941 -2.217 14.589 -0.136 -26.463 -4.024 21061.6 -6473 33 46 30 30
62 -32.044 2.217 -14.589 0.136 -33.352 -5.067 18459.3 -3870 33 46 30 30
126 26 26.544 2.455 -2.259 0.016 9.386 4.829 20701.9 -18247 33 46 30 30
62 -22.648 -2.455 2.259 -0.016 -0.126 5.236 18818.9 -16364 33 46 30 30
127 26 26.469 -3.207 -2.313 -0.583 9.389 -6.039 20699.0 -17492 33 46 30 30
62 -22.572 3.207 2.313 0.583 0.097 -7.108 18821.8 -15615 33 46 30 30
128 26 26.534 1.741 -2.278 -0.291 9.425 3.447 20701.5 -18424 33 46 30 30
62 -22.638 -1.741 2.278 0.291 -0.085 3.689 18819.3 -16541 33 46 30 30
129 26 26.479 -2.492 -2.294 -0.276 9.349 -4.657 20699.4 -18207 33 46 30 30
62 -22.582 2.492 2.294 0.276 0.056 -5.562 18821.5 -16329 33 46 30 30
130 26 36.024 4.132 14.657 0.775 -26.485 8.15 21064.8 -6408 33 46 30 30
62 -32.127 -4.132 -14.657 -0.775 -33.607 8.79 18456.1 -3799 33 46 30 30
131 26 35.948 -1.53 14.602 0.176 -26.482 -2.719 21061.9 -6460 33 46 30 30
62 -32.052 1.53 -14.602 -0.176 -33.385 -3.555 18459.0 -3857 33 46 30 30
132 26 36.014 3.417 14.637 0.468 -26.445 6.768 21064.4 -6427 33 46 30 30
62 -32.117 -3.417 -14.637 -0.468 -33.566 7.243 18456.5 -3819 33 46 30 30
133 26 35.958 -0.816 14.621 0.483 -26.522 -1.337 21062.3 -6441 33 46 30 30
62 -32.062 0.816 -14.621 -0.483 -33.426 -2.008 18458.6 -3838 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 112
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

87 100 27 24.525 4.074 5.354 0.065 -8.066 6.56 20624.6 -15271 33 46 30 30


63 -19.212 -4.074 -5.354 -0.065 -13.886 10.144 18950.5 -13596 33 46 30 30
101 27 24.521 4.037 5.3 0.039 -7.873 6.423 20624.5 -15324 33 46 30 30
63 -19.207 -4.037 -5.3 -0.039 -13.857 10.13 18950.6 -13651 33 46 30 30
102 27 18.903 9.321 0.054 1.431 1.579 18.279 20409.4 -11088 33 46 30 30
63 -15.007 -9.321 -0.054 -1.431 -1.801 19.935 19111.4 -9790 33 46 30 30
103 27 21.747 9.167 5.502 1.086 -10.266 17.983 20518.3 -11351 33 46 30 30
63 -17.851 -9.167 -5.502 -1.086 -12.291 19.603 19002.6 -9836 33 46 30 30
104 27 18.999 9.016 0.548 1.228 0.477 17.608 20413.1 -11397 33 46 30 30
63 -15.102 -9.016 -0.548 -1.228 -2.723 19.359 19107.8 -10092 33 46 30 30
105 27 21.652 9.471 5.008 1.288 -9.164 18.654 20514.6 -11044 33 46 30 30
63 -17.755 -9.471 -5.008 -1.288 -11.369 20.179 19006.2 -9535 33 46 30 30
106 27 13.462 -4.557 3.616 -1.035 -6.596 -13.036 20201.2 -15644 33 46 30 30
63 -9.565 4.557 -3.616 1.035 -8.231 -5.649 19319.7 -14763 33 46 30 30
107 27 16.306 -4.711 9.064 -1.38 -18.44 -13.332 20310.0 -11246 33 46 30 30
63 -12.409 4.711 -9.064 1.38 -18.721 -5.981 19210.9 -10147 33 46 30 30
108 27 13.557 -4.861 4.11 -1.238 -7.698 -13.707 20204.8 -15344 33 46 30 30
63 -9.66 4.861 -4.11 1.238 -9.154 -6.225 19316.1 -14455 33 46 30 30
109 27 16.211 -4.406 8.57 -1.178 -17.339 -12.661 20306.4 -11736 33 46 30 30
63 -12.314 4.406 -8.57 1.178 -17.799 -5.405 19214.5 -10644 33 46 30 30
110 27 19.438 7.592 2.84 0.321 -4.662 14.425 20429.9 -12838 33 46 30 30
63 -15.541 -7.592 -2.84 -0.321 -6.982 16.7 19091.0 -11499 33 46 30 30
111 27 22.282 7.438 8.287 -0.023 -16.506 14.129 20538.8 -12252 33 46 30 30
63 -18.385 -7.438 -8.287 0.023 -17.472 16.368 18982.1 -10695 33 46 30 30
112 27 19.533 7.287 3.334 0.119 -5.763 13.754 20433.5 -13147 33 46 30 30
63 -15.636 -7.287 -3.334 -0.119 -7.905 16.124 19087.3 -11800 33 46 30 30
113 27 22.186 7.742 7.794 0.179 -15.404 14.8 20535.1 -12741 33 46 30 30
63 -18.29 -7.742 -7.794 -0.179 -16.55 16.944 18985.7 -11192 33 46 30 30
114 27 12.928 -2.828 0.831 0.074 -0.356 -9.182 20180.7 -17353 33 46 30 30
63 -9.031 2.828 -0.831 -0.074 -3.05 -2.414 19340.2 -16512 33 46 30 30
115 27 15.772 -2.982 6.278 -0.27 -12.2 -9.478 20289.6 -14012 33 46 30 30
63 -11.875 2.982 -6.278 0.27 -13.54 -2.746 19231.3 -12953 33 46 30 30
116 27 13.023 -3.132 1.325 -0.128 -1.458 -9.853 20184.3 -17052 33 46 30 30
63 -9.126 3.132 -1.325 0.128 -3.973 -2.99 19336.5 -16205 33 46 30 30
117 27 15.676 -2.677 5.784 -0.068 -11.098 -8.807 20285.9 -14502 33 46 30 30
63 -11.78 2.677 -5.784 0.068 -12.618 -2.17 19234.9 -13451 33 46 30 30
118 27 13.723 4.635 -5.094 0.99 12.85 7.644 20211.1 -15117 33 46 30 30
63 -9.826 -4.635 5.094 -0.99 8.034 11.36 19309.7 -14216 33 46 30 30
119 27 12.032 0.418 -4.067 0.299 10.496 -1.831 20146.4 -16079 33 46 30 30
63 -8.136 -0.418 4.067 -0.299 6.179 3.544 19374.4 -15307 33 46 30 30
120 27 13.883 4.116 -4.258 0.657 10.978 6.487 20217.3 -15959 33 46 30 30
63 -9.987 -4.116 4.258 -0.657 6.48 10.39 19303.6 -15046 33 46 30 30
121 27 11.872 0.936 -4.903 0.632 12.368 -0.675 20140.3 -15237 33 46 30 30
63 -7.975 -0.936 4.903 -0.632 7.733 4.515 19380.6 -14478 33 46 30 30
122 27 23.173 4.216 13.128 -0.253 -27.154 6.877 20572.9 -7445 33 46 30 30
63 -19.277 -4.216 -13.128 0.253 -26.67 10.41 18948.0 -5820 33 46 30 30
123 27 21.483 -0.001 14.155 -0.944 -29.508 -2.598 20508.2 -6353 33 46 30 30
63 -17.586 0.001 -14.155 0.944 -28.526 2.594 19012.7 -4858 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 113
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

124 27 23.333 3.698 13.964 -0.586 -29.026 5.721 20579.0 -6615 33 46 30 30


63 -19.437 -3.698 -13.964 0.586 -28.224 9.439 18941.8 -4978 33 46 30 30
125 27 21.322 0.518 13.319 -0.611 -27.636 -1.442 20502.0 -7183 33 46 30 30
63 -17.426 -0.518 -13.319 0.611 -26.971 3.564 19018.8 -5700 33 46 30 30
126 27 14.04 3.621 -3.448 0.315 9.177 5.407 20223.3 -16602 33 46 30 30
63 -10.144 -3.621 3.448 -0.315 4.959 9.441 19297.6 -15677 33 46 30 30
127 27 12.35 -0.596 -2.421 -0.375 6.823 -4.068 20158.6 -17738 33 46 30 30
63 -8.453 0.596 2.421 0.375 3.103 1.625 19362.3 -16941 33 46 30 30
128 27 14.201 3.103 -2.612 -0.017 7.305 4.251 20229.4 -17126 33 46 30 30
63 -10.304 -3.103 2.612 0.017 3.404 8.471 19291.4 -16188 33 46 30 30
129 27 12.189 -0.077 -3.257 -0.042 8.695 -2.912 20152.4 -16895 33 46 30 30
63 -8.293 0.077 3.257 0.042 4.657 2.595 19368.4 -16111 33 46 30 30
130 27 22.856 5.23 11.482 0.421 -23.481 9.114 20560.7 -9079 33 46 30 30
63 -18.959 -5.23 -11.482 -0.421 -23.594 12.329 18960.1 -7478 33 46 30 30
131 27 21.165 1.013 12.509 -0.27 -25.835 -0.361 20496.0 -7987 33 46 30 30
63 -17.269 -1.013 -12.509 0.27 -25.45 4.513 19024.8 -6516 33 46 30 30
132 27 23.016 4.711 12.317 0.088 -25.353 7.958 20566.9 -8250 33 46 30 30
63 -19.119 -4.711 -12.317 -0.088 -25.148 11.358 18954.0 -6637 33 46 30 30
133 27 21.005 1.531 11.673 0.063 -23.963 0.795 20489.9 -8817 33 46 30 30
63 -17.108 -1.531 -11.673 -0.063 -23.895 5.483 19031.0 -7358 33 46 30 30
90 100 32 23.317 3.258 -4.982 0.03 7.447 5.297 20578.4 -15596 33 46 30 30
66 -18.004 -3.258 4.982 -0.03 12.981 8.061 18996.7 -14015 33 46 30 30
101 32 23.317 3.226 -4.941 0.058 7.293 5.179 20578.4 -15637 33 46 30 30
66 -18.003 -3.226 4.941 -0.058 12.967 8.049 18996.7 -14056 33 46 30 30
102 32 22.881 8.605 -8.95 1.163 18.262 17.505 20561.7 -11612 33 46 30 30
66 -18.984 -8.605 8.95 -1.163 18.433 17.778 18959.2 -10009 33 46 30 30
103 32 20.073 8.858 -3.508 0.697 6.466 18.119 20454.2 -11596 33 46 30 30
66 -16.177 -8.858 3.508 -0.697 7.917 18.199 19066.6 -10209 33 46 30 30
104 32 22.767 8.889 -8.454 0.973 17.154 18.171 20557.3 -11668 33 46 30 30
66 -18.87 -8.889 8.454 -0.973 17.508 18.276 18963.5 -10075 33 46 30 30
105 32 20.187 8.574 -4.004 0.887 7.574 17.452 20458.6 -11885 33 46 30 30
66 -16.291 -8.574 4.004 -0.887 8.842 17.701 19062.3 -10488 33 46 30 30
106 32 13.389 -5.432 -5.073 -0.648 9.536 -15.004 20198.4 -14766 33 46 30 30
66 -9.492 5.432 5.073 0.648 11.264 -7.267 19322.5 -13891 33 46 30 30
107 32 10.581 -5.179 0.369 -1.114 -2.26 -14.39 20090.9 -14912 33 46 30 30
66 -6.685 5.179 -0.369 1.114 0.747 -6.846 19430.0 -14251 33 46 30 30
108 32 13.275 -5.148 -4.577 -0.838 8.427 -14.338 20194.0 -15046 33 46 30 30
66 -9.378 5.148 4.577 0.838 10.338 -6.769 19326.9 -14179 33 46 30 30
109 32 10.696 -5.463 -0.127 -0.924 -1.152 -15.056 20095.3 -14632 33 46 30 30
66 -6.799 5.463 0.127 0.924 1.673 -7.344 19425.6 -13963 33 46 30 30
110 32 22.248 10.218 -6.153 0.112 11.989 21.286 20537.5 -10319 33 46 30 30
66 -18.352 -10.218 6.153 -0.112 13.238 20.607 18983.4 -8765 33 46 30 30
111 32 19.441 10.47 -0.711 -0.354 0.193 21.9 20430.0 -9960 33 46 30 30
66 -15.544 -10.47 0.711 0.354 2.721 21.028 19090.9 -8621 33 46 30 30
112 32 22.134 10.502 -5.657 -0.078 10.881 21.952 20533.1 -10031 33 46 30 30
66 -18.237 -10.502 5.657 0.078 12.312 21.105 18987.8 -8486 33 46 30 30
113 32 19.555 10.186 -1.207 -0.163 1.301 21.234 20434.4 -10248 33 46 30 30
66 -15.658 -10.186 1.207 0.163 3.647 20.53 19086.5 -8900 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 114
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

114 32 14.021 -7.044 -7.87 0.403 15.809 -18.785 20222.5 -12353 33 46 30 30


66 -10.125 7.044 7.87 -0.403 16.459 -10.096 19298.3 -11428 33 46 30 30
115 32 11.214 -6.792 -2.428 -0.063 4.013 -18.171 20115.1 -13323 33 46 30 30
66 -7.317 6.792 2.428 0.063 5.942 -9.674 19405.8 -12614 33 46 30 30
116 32 13.907 -6.76 -7.374 0.213 14.7 -18.119 20218.2 -12844 33 46 30 30
66 -10.01 6.76 7.374 -0.213 15.533 -9.598 19302.7 -11929 33 46 30 30
117 32 11.328 -7.076 -2.924 0.127 5.121 -18.837 20119.5 -13043 33 46 30 30
66 -7.431 7.076 2.924 -0.127 6.868 -10.172 19401.4 -12325 33 46 30 30
118 32 22.772 3.379 -13.922 1.139 29.065 5.378 20557.5 -6636 33 46 30 30
66 -18.876 -3.379 13.922 -1.139 28.016 8.475 18963.3 -5041 33 46 30 30
119 32 19.978 -0.747 -12.801 0.625 26.545 -4.143 20450.6 -7650 33 46 30 30
66 -16.082 0.747 12.801 -0.625 25.938 1.079 19070.3 -6269 33 46 30 30
120 32 22.583 3.862 -13.083 0.824 27.183 6.512 20550.3 -7467 33 46 30 30
66 -18.686 -3.862 13.083 -0.824 26.457 9.323 18970.6 -5888 33 46 30 30
121 32 20.168 -1.231 -13.64 0.94 28.427 -5.278 20457.8 -6818 33 46 30 30
66 -16.271 1.231 13.64 -0.94 27.497 0.23 19063.0 -5423 33 46 30 30
122 32 13.488 4.204 4.254 -0.556 -10.672 7.369 20202.1 -15948 33 46 30 30
66 -9.591 -4.204 -4.254 0.556 -6.768 9.866 19318.7 -15065 33 46 30 30
123 32 10.694 0.077 5.375 -1.07 -13.193 -2.152 20095.2 -14720 33 46 30 30
66 -6.797 -0.077 -5.375 1.07 -8.846 2.47 19425.7 -14051 33 46 30 30
124 32 13.298 4.687 5.093 -0.871 -12.554 8.504 20194.9 -15102 33 46 30 30
66 -9.402 -4.687 -5.093 0.871 -8.327 10.715 19326.0 -14233 33 46 30 30
125 32 10.884 -0.406 4.536 -0.755 -11.311 -3.287 20102.5 -15566 33 46 30 30
66 -6.987 0.406 -4.536 0.755 -7.287 1.621 19418.4 -14882 33 46 30 30
126 32 22.391 4.325 -12.269 0.505 25.371 7.598 20542.9 -8274 33 46 30 30
66 -18.495 -4.325 12.269 -0.505 24.931 10.135 18977.9 -6709 33 46 30 30
127 32 19.597 0.199 -11.147 -0.009 22.851 -1.923 20436.0 -9289 33 46 30 30
66 -15.701 -0.199 11.147 0.009 22.853 2.739 19084.8 -7938 33 46 30 30
128 32 22.202 4.809 -11.43 0.19 23.489 8.733 20535.7 -9106 33 46 30 30
66 -18.305 -4.809 11.43 -0.19 23.372 10.983 18985.2 -7555 33 46 30 30
129 32 19.787 -0.285 -11.986 0.306 24.732 -3.058 20443.3 -8457 33 46 30 30
66 -15.89 0.285 11.986 -0.306 24.412 1.89 19077.6 -7092 33 46 30 30
130 32 13.869 3.257 2.6 0.078 -6.978 5.149 20216.7 -16960 33 46 30 30
66 -9.973 -3.257 -2.6 -0.078 -3.683 8.206 19304.1 -16047 33 46 30 30
131 32 11.075 -0.869 3.722 -0.436 -9.499 -4.373 20109.8 -16388 33 46 30 30
66 -7.178 0.869 -3.722 0.436 -5.76 0.81 19411.1 -15689 33 46 30 30
132 32 13.68 3.741 3.439 -0.237 -8.86 6.283 20209.5 -16468 33 46 30 30
66 -9.783 -3.741 -3.439 0.237 -5.242 9.055 19311.4 -15570 33 46 30 30
133 32 11.265 -1.353 2.883 -0.121 -7.617 -5.507 20117.1 -17234 33 46 30 30
66 -7.368 1.353 -2.883 0.121 -4.202 -0.039 19403.8 -16521 33 46 30 30

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco 115
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO
DEPARTAMENTO DE FORMACIÓN PROFESIONAL

EN INGENIERÍA APLICADA

Bibliografía.

318, C. A. (2008). Requisitos de Reglamento para Concreto Estructural (ACI 318S-08) y Comentarios. Farmington Hills:
American Concrete Institute.

RCDF, México D.F. (2004). Reglamento de Construcciones para el Distrito Federal y sus Normas Técnicas v
Complementarias. Gobierno del Distrito Federal.

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

ANEXO 1: Datos de entrada.


STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 25-Apr-13
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER MTON
JOINT COORDINATES
1 0 0 0; 2 6.25 0 0; 3 12.5 0 0; 4 18.75 0 0; 5 25 0 0; 6 0 0 7; 7 6.25 0 7;
8 12.5 0 7; 9 18.75 0 7; 10 25 0 7; 11 0 0 14; 12 6.25 0 14; 13 12.5 0 14;
14 18.75 0 14; 15 25 0 14; 16 12.5 0 21; 17 18.75 0 21; 18 25 0 21;
19 0 7.35 0; 20 6.25 7.35 0; 21 12.5 7.35 0; 22 18.75 7.35 0; 23 25 7.35 0;
24 0 7.35 7; 25 6.25 7.35 7; 26 12.5 7.35 7; 27 18.75 7.35 7; 28 25 7.35 7;
29 0 7.35 14; 30 6.25 7.35 14; 31 12.5 7.35 14; 32 18.75 7.35 14;
33 25 7.35 14; 34 12.5 7.35 21; 35 18.75 7.35 21; 36 25 7.35 21; 37 0 -3.2 0;
38 6.25 -3.2 0; 39 12.5 -3.2 0; 40 18.75 -3.2 0; 41 25 -3.2 0; 42 0 -3.2 7;
43 6.25 -3.2 7; 44 12.5 -3.2 7; 45 18.75 -3.2 7; 46 25 -3.2 7; 47 0 -3.2 14;
48 6.25 -3.2 14; 49 12.5 -3.2 14; 50 18.75 -3.2 14; 51 25 -3.2 14;
52 12.5 -3.2 21; 53 18.75 -3.2 21; 54 25 -3.2 21; 55 18.75 0 28;
56 18.75 7.35 28; 57 25 0 28; 58 25 7.35 28; 59 18.75 -3.2 28; 60 25 -3.2 28;
61 6.25 11.45 7; 62 12.5 11.45 7; 63 18.75 11.45 7; 64 6.25 11.45 14;
65 12.5 11.45 14; 66 18.75 11.45 14; 67 0 7.35 0.777778; 68 0 6.825 0.777778;
69 0 6.825 0; 70 0 7.35 1.55556; 71 0 6.825 1.55556; 72 0 7.35 2.33333;
73 0 6.825 2.33333; 74 0 7.35 3.11111; 75 0 6.825 3.11111; 76 0 7.35 3.88889;
77 0 6.825 3.88889; 78 0 7.35 4.66667; 79 0 6.825 4.66667; 80 0 7.35 5.44444;
81 0 6.825 5.44444; 82 0 7.35 6.22222; 83 0 6.825 6.22222; 84 0 6.825 7;
85 0 6.3 0.777778; 86 0 6.3 0; 87 0 6.3 1.55556; 88 0 6.3 2.33333;
89 0 6.3 3.11111; 90 0 6.3 3.88889; 91 0 6.3 4.66667; 92 0 6.3 5.44444;
93 0 6.3 6.22222; 94 0 6.3 7; 95 0 5.775 0.777778; 96 0 5.775 0;
97 0 5.775 1.55556; 98 0 5.775 2.33333; 99 0 5.775 3.11111;
100 0 5.775 3.88889; 101 0 5.775 4.66667; 102 0 5.775 5.44444;
103 0 5.775 6.22222; 104 0 5.775 7; 105 0 5.25 0.777778; 106 0 5.25 0;
107 0 5.25 1.55556; 108 0 5.25 2.33333; 109 0 5.25 3.11111; 110 0 5.25 3.88889;
111 0 5.25 4.66667; 112 0 5.25 5.44444; 113 0 5.25 6.22222; 114 0 5.25 7;
115 0 4.725 0.777778; 116 0 4.725 0; 117 0 4.725 1.55556; 118 0 4.725 2.33333;
119 0 4.725 3.11111; 120 0 4.725 3.88889; 121 0 4.725 4.66667;
122 0 4.725 5.44444; 123 0 4.725 6.22222; 124 0 4.725 7; 125 0 4.2 0.777778;
126 0 4.2 0; 127 0 4.2 1.55556; 128 0 4.2 2.33333; 129 0 4.2 3.11111;
130 0 4.2 3.88889; 131 0 4.2 4.66667; 132 0 4.2 5.44444; 133 0 4.2 6.22222;
134 0 4.2 7; 135 0 3.675 0.777778; 136 0 3.675 0; 137 0 3.675 1.55556;
138 0 3.675 2.33333; 139 0 3.675 3.11111; 140 0 3.675 3.88889;
141 0 3.675 4.66667; 142 0 3.675 5.44444; 143 0 3.675 6.22222; 144 0 3.675 7;
145 0 3.15 0.777778; 146 0 3.15 0; 147 0 3.15 1.55556; 148 0 3.15 2.33333;
149 0 3.15 3.11111; 150 0 3.15 3.88889; 151 0 3.15 4.66667; 152 0 3.15 5.44444;
153 0 3.15 6.22222; 154 0 3.15 7; 155 0 2.625 0.777778; 156 0 2.625 0;
157 0 2.625 1.55556; 158 0 2.625 2.33333; 159 0 2.625 3.11111;
160 0 2.625 3.88889; 161 0 2.625 4.66667; 162 0 2.625 5.44444;
163 0 2.625 6.22222; 164 0 2.625 7; 166 0 2.1 0; 167 0 2.1 1.55556;
168 0 2.1 2.33333; 169 0 2.1 3.11111; 170 0 2.1 3.88889; 171 0 2.1 4.66667;
172 0 2.1 5.44444; 173 0 2.1 6.22222; 174 0 2.1 7; 176 0 1.575 0;
177 0 1.575 1.55556; 178 0 1.575 2.33333; 179 0 1.575 3.11111;
180 0 1.575 3.88889; 181 0 1.575 4.66667; 182 0 1.575 5.44444;
183 0 1.575 6.22222; 184 0 1.575 7; 186 0 1.05 0; 187 0 1.05 1.55556;
188 0 1.05 2.33333; 189 0 1.05 3.11111; 190 0 1.05 3.88889; 191 0 1.05 4.66667;
192 0 1.05 5.44444; 193 0 1.05 6.22222; 194 0 1.05 7; 196 0 0.524999 0;
197 0 0.524999 1.55556; 198 0 0.524999 2.33333; 199 0 0.524999 3.11111;
200 0 0.524999 3.88889; 201 0 0.524999 4.66667; 202 0 0.524999 5.44444;
203 0 0.524999 6.22222; 204 0 0.524999 7; 205 0 0 0.777778; 206 0 0 1.55556;
207 0 0 2.33333; 208 0 0 3.11111; 209 0 0 3.88889; 210 0 0 4.66667;
211 0 0 5.44444; 212 0 0 6.22222; 213 6.94444 7.35 0; 214 6.94444 6.825 0;
215 6.25 6.825 0; 216 7.63889 7.35 0; 217 7.63889 6.825 0; 218 8.33333 7.35 0;
219 8.33333 6.825 0; 220 9.02778 7.35 0; 221 9.02778 6.825 0;
222 9.72222 7.35 0; 223 9.72222 6.825 0; 224 10.4167 7.35 0;
225 10.4167 6.825 0; 226 11.1111 7.35 0; 227 11.1111 6.825 0;
228 11.8056 7.35 0; 229 11.8056 6.825 0; 230 12.5 6.825 0; 231 6.94444 6.3 0;
232 6.25 6.3 0; 233 7.63889 6.3 0; 234 8.33333 6.3 0; 235 9.02778 6.3 0;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

236 9.72222 6.3 0; 237 10.4167 6.3 0; 238 11.1111 6.3 0; 239 11.8056 6.3 0;
240 12.5 6.3 0; 241 6.94444 5.775 0; 242 6.25 5.775 0; 243 7.63889 5.775 0;
244 8.33333 5.775 0; 245 9.02778 5.775 0; 246 9.72222 5.775 0;
247 10.4167 5.775 0; 248 11.1111 5.775 0; 249 11.8056 5.775 0;
250 12.5 5.775 0; 251 6.94444 5.25 0; 252 6.25 5.25 0; 253 7.63889 5.25 0;
254 8.33333 5.25 0; 255 9.02778 5.25 0; 256 9.72222 5.25 0; 257 10.4167 5.25 0;
258 11.1111 5.25 0; 259 11.8056 5.25 0; 260 12.5 5.25 0; 261 6.94444 4.725 0;
262 6.25 4.725 0; 263 7.63889 4.725 0; 264 8.33333 4.725 0;
265 9.02778 4.725 0; 266 9.72222 4.725 0; 267 10.4167 4.725 0;
268 11.1111 4.725 0; 269 11.8056 4.725 0; 270 12.5 4.725 0; 271 6.94444 4.2 0;
272 6.25 4.2 0; 273 7.63889 4.2 0; 274 8.33333 4.2 0; 275 9.02778 4.2 0;
276 9.72222 4.2 0; 277 10.4167 4.2 0; 278 11.1111 4.2 0; 279 11.8056 4.2 0;
280 12.5 4.2 0; 281 6.94444 3.675 0; 282 6.25 3.675 0; 283 7.63889 3.675 0;
284 8.33333 3.675 0; 285 9.02778 3.675 0; 286 9.72222 3.675 0;
287 10.4167 3.675 0; 288 11.1111 3.675 0; 289 11.8056 3.675 0;
290 12.5 3.675 0; 291 6.94444 3.15 0; 292 6.25 3.15 0; 293 7.63889 3.15 0;
294 8.33333 3.15 0; 295 9.02778 3.15 0; 296 9.72222 3.15 0; 297 10.4167 3.15 0;
298 11.1111 3.15 0; 299 11.8056 3.15 0; 300 12.5 3.15 0; 301 6.94444 2.625 0;
302 6.25 2.625 0; 303 7.63889 2.625 0; 304 8.33333 2.625 0;
305 9.02778 2.625 0; 306 9.72222 2.625 0; 307 10.4167 2.625 0;
308 11.1111 2.625 0; 309 11.8056 2.625 0; 310 12.5 2.625 0; 311 6.94444 2.1 0;
312 6.25 2.1 0; 313 7.63889 2.1 0; 314 8.33333 2.1 0; 315 9.02778 2.1 0;
316 9.72222 2.1 0; 317 10.4167 2.1 0; 318 11.1111 2.1 0; 319 11.8056 2.1 0;
320 12.5 2.1 0; 321 6.94444 1.575 0; 322 6.25 1.575 0; 323 7.63889 1.575 0;
324 8.33333 1.575 0; 325 9.02778 1.575 0; 326 9.72222 1.575 0;
327 10.4167 1.575 0; 328 11.1111 1.575 0; 329 11.8056 1.575 0;
330 12.5 1.575 0; 331 6.94444 1.05 0; 332 6.25 1.05 0; 333 7.63889 1.05 0;
334 8.33333 1.05 0; 335 9.02778 1.05 0; 336 9.72222 1.05 0; 337 10.4167 1.05 0;
338 11.1111 1.05 0; 339 11.8056 1.05 0; 340 12.5 1.05 0;
341 6.94444 0.524999 0; 342 6.25 0.524999 0; 343 7.63889 0.524999 0;
344 8.33333 0.524999 0; 345 9.02778 0.524999 0; 346 9.72222 0.524999 0;
347 10.4167 0.524999 0; 348 11.1111 0.524999 0; 349 11.8056 0.524999 0;
350 12.5 0.524999 0; 351 6.94444 0 0; 352 7.63889 0 0; 353 8.33333 0 0;
354 9.02778 0 0; 355 9.72222 0 0; 356 10.4167 0 0; 357 11.1111 0 0;
358 11.8056 0 0; 359 6.94444 7.35 14; 360 6.94444 6.825 14; 361 6.25 6.825 14;
362 7.63889 7.35 14; 363 7.63889 6.825 14; 364 8.33333 7.35 14;
365 8.33333 6.825 14; 366 9.02778 7.35 14; 367 9.02778 6.825 14;
368 9.72222 7.35 14; 369 9.72222 6.825 14; 370 10.4167 7.35 14;
371 10.4167 6.825 14; 372 11.1111 7.35 14; 373 11.1111 6.825 14;
374 11.8056 7.35 14; 375 11.8056 6.825 14; 376 12.5 6.825 14;
377 6.94444 6.3 14; 378 6.25 6.3 14; 379 7.63889 6.3 14; 380 8.33333 6.3 14;
381 9.02778 6.3 14; 382 9.72222 6.3 14; 383 10.4167 6.3 14; 384 11.1111 6.3 14;
385 11.8056 6.3 14; 386 12.5 6.3 14; 387 6.94444 5.775 14; 388 6.25 5.775 14;
389 7.63889 5.775 14; 390 8.33333 5.775 14; 391 9.02778 5.775 14;
392 9.72222 5.775 14; 393 10.4167 5.775 14; 394 11.1111 5.775 14;
395 11.8056 5.775 14; 396 12.5 5.775 14; 397 6.94444 5.25 14; 398 6.25 5.25 14;
399 7.63889 5.25 14; 400 8.33333 5.25 14; 401 9.02778 5.25 14;
402 9.72222 5.25 14; 403 10.4167 5.25 14; 404 11.1111 5.25 14;
405 11.8056 5.25 14; 406 12.5 5.25 14; 407 6.94444 4.725 14; 408 6.25 4.725 14;
409 7.63889 4.725 14; 410 8.33333 4.725 14; 411 9.02778 4.725 14;
412 9.72222 4.725 14; 413 10.4167 4.725 14; 414 11.1111 4.725 14;
415 11.8056 4.725 14; 416 12.5 4.725 14; 417 6.94444 4.2 14; 418 6.25 4.2 14;
419 7.63889 4.2 14; 420 8.33333 4.2 14; 421 9.02778 4.2 14; 422 9.72222 4.2 14;
423 10.4167 4.2 14; 424 11.1111 4.2 14; 425 11.8056 4.2 14; 426 12.5 4.2 14;
427 6.94444 3.675 14; 428 6.25 3.675 14; 429 7.63889 3.675 14;
430 8.33333 3.675 14; 431 9.02778 3.675 14; 432 9.72222 3.675 14;
433 10.4167 3.675 14; 434 11.1111 3.675 14; 435 11.8056 3.675 14;
436 12.5 3.675 14; 437 6.94444 3.15 14; 438 6.25 3.15 14; 439 7.63889 3.15 14;
440 8.33333 3.15 14; 441 9.02778 3.15 14; 442 9.72222 3.15 14;
443 10.4167 3.15 14; 444 11.1111 3.15 14; 445 11.8056 3.15 14;
446 12.5 3.15 14; 447 6.94444 2.625 14; 448 6.25 2.625 14;
449 7.63889 2.625 14; 450 8.33333 2.625 14; 451 9.02778 2.625 14;
452 9.72222 2.625 14; 453 10.4167 2.625 14; 454 11.1111 2.625 14;
455 11.8056 2.625 14; 456 12.5 2.625 14; 457 6.94444 2.1 14; 458 6.25 2.1 14;
459 7.63889 2.1 14; 460 8.33333 2.1 14; 461 9.02778 2.1 14; 462 9.72222 2.1 14;
463 10.4167 2.1 14; 464 11.1111 2.1 14; 465 11.8056 2.1 14; 466 12.5 2.1 14;
467 6.94444 1.575 14; 468 6.25 1.575 14; 469 7.63889 1.575 14;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

470 8.33333 1.575 14; 471 9.02778 1.575 14; 472 9.72222 1.575 14;
473 10.4167 1.575 14; 474 11.1111 1.575 14; 475 11.8056 1.575 14;
476 12.5 1.575 14; 477 6.94444 1.05 14; 478 6.25 1.05 14; 479 7.63889 1.05 14;
480 8.33333 1.05 14; 481 9.02778 1.05 14; 482 9.72222 1.05 14;
483 10.4167 1.05 14; 484 11.1111 1.05 14; 485 11.8056 1.05 14;
486 12.5 1.05 14; 487 6.94444 0.524999 14; 488 6.25 0.524999 14;
489 7.63889 0.524999 14; 490 8.33333 0.524999 14; 491 9.02778 0.524999 14;
492 9.72222 0.524999 14; 493 10.4167 0.524999 14; 494 11.1111 0.524999 14;
495 11.8056 0.524999 14; 496 12.5 0.524999 14; 497 6.94444 0 14;
498 7.63889 0 14; 499 8.33333 0 14; 500 9.02778 0 14; 501 9.72222 0 14;
502 10.4167 0 14; 503 11.1111 0 14; 504 11.8056 0 14; 505 25 7.35 0.777778;
506 25 6.825 0.777778; 507 25 6.825 0; 508 25 7.35 1.55556;
509 25 6.825 1.55556; 510 25 7.35 2.33333; 511 25 6.825 2.33333;
512 25 7.35 3.11111; 513 25 6.825 3.11111; 514 25 7.35 3.88889;
515 25 6.825 3.88889; 516 25 7.35 4.66667; 517 25 6.825 4.66667;
518 25 7.35 5.44444; 519 25 6.825 5.44444; 520 25 7.35 6.22222;
521 25 6.825 6.22222; 522 25 6.825 7; 523 25 6.3 0.777778; 524 25 6.3 0;
525 25 6.3 1.55556; 526 25 6.3 2.33333; 527 25 6.3 3.11111; 528 25 6.3 3.88889;
529 25 6.3 4.66667; 530 25 6.3 5.44444; 531 25 6.3 6.22222; 532 25 6.3 7;
533 25 5.775 0.777778; 534 25 5.775 0; 535 25 5.775 1.55556;
536 25 5.775 2.33333; 537 25 5.775 3.11111; 538 25 5.775 3.88889;
539 25 5.775 4.66667; 540 25 5.775 5.44444; 541 25 5.775 6.22222;
542 25 5.775 7; 543 25 5.25 0.777778; 544 25 5.25 0; 545 25 5.25 1.55556;
546 25 5.25 2.33333; 547 25 5.25 3.11111; 548 25 5.25 3.88889;
549 25 5.25 4.66667; 550 25 5.25 5.44444; 551 25 5.25 6.22222; 552 25 5.25 7;
553 25 4.725 0.777778; 554 25 4.725 0; 555 25 4.725 1.55556;
556 25 4.725 2.33333; 557 25 4.725 3.11111; 558 25 4.725 3.88889;
559 25 4.725 4.66667; 560 25 4.725 5.44444; 561 25 4.725 6.22222;
562 25 4.725 7; 563 25 4.2 0.777778; 564 25 4.2 0; 565 25 4.2 1.55556;
566 25 4.2 2.33333; 567 25 4.2 3.11111; 568 25 4.2 3.88889; 569 25 4.2 4.66667;
570 25 4.2 5.44444; 571 25 4.2 6.22222; 572 25 4.2 7; 573 25 3.675 0.777778;
574 25 3.675 0; 575 25 3.675 1.55556; 576 25 3.675 2.33333;
577 25 3.675 3.11111; 578 25 3.675 3.88889; 579 25 3.675 4.66667;
580 25 3.675 5.44444; 581 25 3.675 6.22222; 582 25 3.675 7;
583 25 3.15 0.777778; 584 25 3.15 0; 585 25 3.15 1.55556; 586 25 3.15 2.33333;
587 25 3.15 3.11111; 588 25 3.15 3.88889; 589 25 3.15 4.66667;
590 25 3.15 5.44444; 591 25 3.15 6.22222; 592 25 3.15 7; 593 25 2.625 0.777778;
594 25 2.625 0; 595 25 2.625 1.55556; 596 25 2.625 2.33333;
597 25 2.625 3.11111; 598 25 2.625 3.88889; 599 25 2.625 4.66667;
600 25 2.625 5.44444; 601 25 2.625 6.22222; 602 25 2.625 7;
603 25 2.1 0.777778; 604 25 2.1 0; 605 25 2.1 1.55556; 606 25 2.1 2.33333;
607 25 2.1 3.11111; 608 25 2.1 3.88889; 609 25 2.1 4.66667; 610 25 2.1 5.44444;
611 25 2.1 6.22222; 612 25 2.1 7; 613 25 1.575 0.777778; 614 25 1.575 0;
615 25 1.575 1.55556; 616 25 1.575 2.33333; 617 25 1.575 3.11111;
618 25 1.575 3.88889; 619 25 1.575 4.66667; 620 25 1.575 5.44444;
621 25 1.575 6.22222; 622 25 1.575 7; 623 25 1.05 0.777778; 624 25 1.05 0;
625 25 1.05 1.55556; 626 25 1.05 2.33333; 627 25 1.05 3.11111;
628 25 1.05 3.88889; 629 25 1.05 4.66667; 630 25 1.05 5.44444;
631 25 1.05 6.22222; 632 25 1.05 7; 633 25 0.524999 0.777778;
634 25 0.524999 0; 635 25 0.524999 1.55556; 636 25 0.524999 2.33333;
637 25 0.524999 3.11111; 638 25 0.524999 3.88889; 639 25 0.524999 4.66667;
640 25 0.524999 5.44444; 641 25 0.524999 6.22222; 642 25 0.524999 7;
643 25 0 0.777778; 644 25 0 1.55556; 645 25 0 2.33333; 646 25 0 3.11111;
647 25 0 3.88889; 648 25 0 4.66667; 649 25 0 5.44444; 650 25 0 6.22222;
651 19.4444 7.35 28; 652 19.4444 6.825 28; 653 18.75 6.825 28;
654 20.1389 7.35 28; 655 20.1389 6.825 28; 656 20.8333 7.35 28;
657 20.8333 6.825 28; 658 21.5278 7.35 28; 659 21.5278 6.825 28;
660 22.2222 7.35 28; 661 22.2222 6.825 28; 662 22.9167 7.35 28;
663 22.9167 6.825 28; 664 23.6111 7.35 28; 665 23.6111 6.825 28;
666 24.3056 7.35 28; 667 24.3056 6.825 28; 668 25 6.825 28; 669 19.4444 6.3 28;
670 18.75 6.3 28; 671 20.1389 6.3 28; 672 20.8333 6.3 28; 673 21.5278 6.3 28;
674 22.2222 6.3 28; 675 22.9167 6.3 28; 676 23.6111 6.3 28; 677 24.3056 6.3 28;
678 25 6.3 28; 679 19.4444 5.775 28; 680 18.75 5.775 28; 681 20.1389 5.775 28;
682 20.8333 5.775 28; 683 21.5278 5.775 28; 684 22.2222 5.775 28;
685 22.9167 5.775 28; 686 23.6111 5.775 28; 687 24.3056 5.775 28;
688 25 5.775 28; 689 19.4444 5.25 28; 690 18.75 5.25 28; 691 20.1389 5.25 28;
692 20.8333 5.25 28; 693 21.5278 5.25 28; 694 22.2222 5.25 28;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

695 22.9167 5.25 28; 696 23.6111 5.25 28; 697 24.3056 5.25 28; 698 25 5.25 28;
699 19.4444 4.725 28; 700 18.75 4.725 28; 701 20.1389 4.725 28;
702 20.8333 4.725 28; 703 21.5278 4.725 28; 704 22.2222 4.725 28;
705 22.9167 4.725 28; 706 23.6111 4.725 28; 707 24.3056 4.725 28;
708 25 4.725 28; 709 19.4444 4.2 28; 710 18.75 4.2 28; 711 20.1389 4.2 28;
712 20.8333 4.2 28; 713 21.5278 4.2 28; 714 22.2222 4.2 28; 715 22.9167 4.2 28;
716 23.6111 4.2 28; 717 24.3056 4.2 28; 718 25 4.2 28; 719 19.4444 3.675 28;
720 18.75 3.675 28; 721 20.1389 3.675 28; 722 20.8333 3.675 28;
723 21.5278 3.675 28; 724 22.2222 3.675 28; 725 22.9167 3.675 28;
726 23.6111 3.675 28; 727 24.3056 3.675 28; 728 25 3.675 28;
729 19.4444 3.15 28; 730 18.75 3.15 28; 731 20.1389 3.15 28;
732 20.8333 3.15 28; 733 21.5278 3.15 28; 734 22.2222 3.15 28;
735 22.9167 3.15 28; 736 23.6111 3.15 28; 737 24.3056 3.15 28; 738 25 3.15 28;
739 19.4444 2.625 28; 740 18.75 2.625 28; 741 20.1389 2.625 28;
742 20.8333 2.625 28; 743 21.5278 2.625 28; 744 22.2222 2.625 28;
745 22.9167 2.625 28; 746 23.6111 2.625 28; 747 24.3056 2.625 28;
748 25 2.625 28; 749 19.4444 2.1 28; 750 18.75 2.1 28; 751 20.1389 2.1 28;
752 20.8333 2.1 28; 753 21.5278 2.1 28; 754 22.2222 2.1 28; 755 22.9167 2.1 28;
756 23.6111 2.1 28; 757 24.3056 2.1 28; 758 25 2.1 28; 759 19.4444 1.575 28;
760 18.75 1.575 28; 761 20.1389 1.575 28; 762 20.8333 1.575 28;
763 21.5278 1.575 28; 764 22.2222 1.575 28; 765 22.9167 1.575 28;
766 23.6111 1.575 28; 767 24.3056 1.575 28; 768 25 1.575 28;
769 19.4444 1.05 28; 770 18.75 1.05 28; 771 20.1389 1.05 28;
772 20.8333 1.05 28; 773 21.5278 1.05 28; 774 22.2222 1.05 28;
775 22.9167 1.05 28; 776 23.6111 1.05 28; 777 24.3056 1.05 28; 778 25 1.05 28;
779 19.4444 0.524999 28; 780 18.75 0.524999 28; 781 20.1389 0.524999 28;
782 20.8333 0.524999 28; 783 21.5278 0.524999 28; 784 22.2222 0.524999 28;
785 22.9167 0.524999 28; 786 23.6111 0.524999 28; 787 24.3056 0.524999 28;
788 25 0.524999 28; 789 19.4444 -8.76188e-007 28; 790 20.1389 -8.76188e-007 28;
791 20.8333 -8.76188e-007 28; 792 21.5278 -8.76188e-007 28;
793 22.2222 -8.76188e-007 28; 794 22.9167 -8.76188e-007 28;
795 23.6111 -8.76188e-007 28; 796 24.3056 -8.76188e-007 28;
797 0 -0.533333 0.777778; 798 0 -0.533333 0; 799 0 -0.533333 1.55556;
800 0 -0.533333 2.33333; 801 0 -0.533333 3.11111; 802 0 -0.533333 3.88889;
803 0 -0.533333 4.66667; 804 0 -0.533333 5.44444; 805 0 -0.533333 6.22222;
806 0 -0.533333 7; 807 0 -1.06667 0.777778; 808 0 -1.06667 0;
809 0 -1.06667 1.55556; 810 0 -1.06667 2.33333; 811 0 -1.06667 3.11111;
812 0 -1.06667 3.88889; 813 0 -1.06667 4.66667; 814 0 -1.06667 5.44444;
815 0 -1.06667 6.22222; 816 0 -1.06667 7; 817 0 -1.6 0.777778; 818 0 -1.6 0;
819 0 -1.6 1.55556; 820 0 -1.6 2.33333; 821 0 -1.6 3.11111; 822 0 -1.6 3.88889;
823 0 -1.6 4.66667; 824 0 -1.6 5.44444; 825 0 -1.6 6.22222; 826 0 -1.6 7;
827 0 -2.13333 0.777778; 828 0 -2.13333 0; 829 0 -2.13333 1.55556;
830 0 -2.13333 2.33333; 831 0 -2.13333 3.11111; 832 0 -2.13333 3.88889;
833 0 -2.13333 4.66667; 834 0 -2.13333 5.44444; 835 0 -2.13333 6.22222;
836 0 -2.13333 7; 837 0 -2.66667 0.777778; 838 0 -2.66667 0;
839 0 -2.66667 1.55556; 840 0 -2.66667 2.33333; 841 0 -2.66667 3.11111;
842 0 -2.66667 3.88889; 843 0 -2.66667 4.66667; 844 0 -2.66667 5.44444;
845 0 -2.66667 6.22222; 846 0 -2.66667 7; 847 0 -3.2 0.777778;
848 0 -3.2 1.55556; 849 0 -3.2 2.33333; 850 0 -3.2 3.11111; 851 0 -3.2 3.88889;
852 0 -3.2 4.66667; 853 0 -3.2 5.44444; 854 0 -3.2 6.22222; 855 0 0 7.77778;
856 0 -0.533333 7.77778; 857 0 0 8.55556; 858 0 -0.533333 8.55556;
859 0 0 9.33333; 860 0 -0.533333 9.33333; 861 0 0 10.1111;
862 0 -0.533333 10.1111; 863 0 0 10.8889; 864 0 -0.533333 10.8889;
865 0 0 11.6667; 866 0 -0.533333 11.6667; 867 0 0 12.4444;
868 0 -0.533333 12.4444; 869 0 0 13.2222; 870 0 -0.533333 13.2222;
871 0 -0.533333 14; 872 0 -1.06667 7.77778; 873 0 -1.06667 8.55556;
874 0 -1.06667 9.33333; 875 0 -1.06667 10.1111; 876 0 -1.06667 10.8889;
877 0 -1.06667 11.6667; 878 0 -1.06667 12.4444; 879 0 -1.06667 13.2222;
880 0 -1.06667 14; 881 0 -1.6 7.77778; 882 0 -1.6 8.55556; 883 0 -1.6 9.33333;
884 0 -1.6 10.1111; 885 0 -1.6 10.8889; 886 0 -1.6 11.6667; 887 0 -1.6 12.4444;
888 0 -1.6 13.2222; 889 0 -1.6 14; 890 0 -2.13333 7.77778;
891 0 -2.13333 8.55556; 892 0 -2.13333 9.33333; 893 0 -2.13333 10.1111;
894 0 -2.13333 10.8889; 895 0 -2.13333 11.6667; 896 0 -2.13333 12.4444;
897 0 -2.13333 13.2222; 898 0 -2.13333 14; 899 0 -2.66667 7.77778;
900 0 -2.66667 8.55556; 901 0 -2.66667 9.33333; 902 0 -2.66667 10.1111;
903 0 -2.66667 10.8889; 904 0 -2.66667 11.6667; 905 0 -2.66667 12.4444;
906 0 -2.66667 13.2222; 907 0 -2.66667 14; 908 0 -3.2 7.77778;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

909 0 -3.2 8.55556; 910 0 -3.2 9.33333; 911 0 -3.2 10.1111; 912 0 -3.2 10.8889;
913 0 -3.2 11.6667; 914 0 -3.2 12.4444; 915 0 -3.2 13.2222; 916 0.694444 0 14;
917 0.694444 -0.533333 14; 918 1.38889 0 14; 919 1.38889 -0.533333 14;
920 2.08333 0 14; 921 2.08333 -0.533333 14; 922 2.77778 0 14;
923 2.77778 -0.533333 14; 924 3.47222 0 14; 925 3.47222 -0.533333 14;
926 4.16667 0 14; 927 4.16667 -0.533333 14; 928 4.86111 0 14;
929 4.86111 -0.533333 14; 930 5.55556 0 14; 931 5.55556 -0.533333 14;
932 6.25 -0.533333 14; 933 0.694444 -1.06667 14; 934 1.38889 -1.06667 14;
935 2.08333 -1.06667 14; 936 2.77778 -1.06667 14; 937 3.47222 -1.06667 14;
938 4.16667 -1.06667 14; 939 4.86111 -1.06667 14; 940 5.55556 -1.06667 14;
941 6.25 -1.06667 14; 942 0.694444 -1.6 14; 943 1.38889 -1.6 14;
944 2.08333 -1.6 14; 945 2.77778 -1.6 14; 946 3.47222 -1.6 14;
947 4.16667 -1.6 14; 948 4.86111 -1.6 14; 949 5.55556 -1.6 14;
950 6.25 -1.6 14; 951 0.694444 -2.13333 14; 952 1.38889 -2.13333 14;
953 2.08333 -2.13333 14; 954 2.77778 -2.13333 14; 955 3.47222 -2.13333 14;
956 4.16667 -2.13333 14; 957 4.86111 -2.13333 14; 958 5.55556 -2.13333 14;
959 6.25 -2.13333 14; 960 0.694444 -2.66667 14; 961 1.38889 -2.66667 14;
962 2.08333 -2.66667 14; 963 2.77778 -2.66667 14; 964 3.47222 -2.66667 14;
965 4.16667 -2.66667 14; 966 4.86111 -2.66667 14; 967 5.55556 -2.66667 14;
968 6.25 -2.66667 14; 969 0.694444 -3.2 14; 970 1.38889 -3.2 14;
971 2.08333 -3.2 14; 972 2.77778 -3.2 14; 973 3.47222 -3.2 14;
974 4.16667 -3.2 14; 975 4.86111 -3.2 14; 976 5.55556 -3.2 14;
977 6.94444 -0.533333 14; 978 7.63889 -0.533333 14; 979 8.33333 -0.533333 14;
980 9.02778 -0.533333 14; 981 9.72222 -0.533333 14; 982 10.4167 -0.533333 14;
983 11.1111 -0.533333 14; 984 11.8056 -0.533333 14; 985 12.5 -0.533333 14;
986 6.94444 -1.06667 14; 987 7.63889 -1.06667 14; 988 8.33333 -1.06667 14;
989 9.02778 -1.06667 14; 990 9.72222 -1.06667 14; 991 10.4167 -1.06667 14;
992 11.1111 -1.06667 14; 993 11.8056 -1.06667 14; 994 12.5 -1.06667 14;
995 6.94444 -1.6 14; 996 7.63889 -1.6 14; 997 8.33333 -1.6 14;
998 9.02778 -1.6 14; 999 9.72222 -1.6 14; 1000 10.4167 -1.6 14;
1001 11.1111 -1.6 14; 1002 11.8056 -1.6 14; 1003 12.5 -1.6 14;
1004 6.94444 -2.13333 14; 1005 7.63889 -2.13333 14; 1006 8.33333 -2.13333 14;
1007 9.02778 -2.13333 14; 1008 9.72222 -2.13333 14; 1009 10.4167 -2.13333 14;
1010 11.1111 -2.13333 14; 1011 11.8056 -2.13333 14; 1012 12.5 -2.13333 14;
1013 6.94444 -2.66667 14; 1014 7.63889 -2.66667 14; 1015 8.33333 -2.66667 14;
1016 9.02778 -2.66667 14; 1017 9.72222 -2.66667 14; 1018 10.4167 -2.66667 14;
1019 11.1111 -2.66667 14; 1020 11.8056 -2.66667 14; 1021 12.5 -2.66667 14;
1022 6.94444 -3.2 14; 1023 7.63889 -3.2 14; 1024 8.33333 -3.2 14;
1025 9.02778 -3.2 14; 1026 9.72222 -3.2 14; 1027 10.4167 -3.2 14;
1028 11.1111 -3.2 14; 1029 11.8056 -3.2 14; 1030 12.5 0 14.7778;
1031 12.5 -0.533333 14.7778; 1032 12.5 0 15.5556; 1033 12.5 -0.533333 15.5556;
1034 12.5 0 16.3333; 1035 12.5 -0.533333 16.3333; 1036 12.5 0 17.1111;
1037 12.5 -0.533333 17.1111; 1038 12.5 0 17.8889; 1039 12.5 -0.533333 17.8889;
1040 12.5 0 18.6667; 1041 12.5 -0.533333 18.6667; 1042 12.5 0 19.4444;
1043 12.5 -0.533333 19.4444; 1044 12.5 0 20.2222; 1045 12.5 -0.533333 20.2222;
1046 12.5 -0.533333 21; 1047 12.5 -1.06667 14.7778; 1048 12.5 -1.06667 15.5556;
1049 12.5 -1.06667 16.3333; 1050 12.5 -1.06667 17.1111;
1051 12.5 -1.06667 17.8889; 1052 12.5 -1.06667 18.6667;
1053 12.5 -1.06667 19.4444; 1054 12.5 -1.06667 20.2222; 1055 12.5 -1.06667 21;
1056 12.5 -1.6 14.7778; 1057 12.5 -1.6 15.5556; 1058 12.5 -1.6 16.3333;
1059 12.5 -1.6 17.1111; 1060 12.5 -1.6 17.8889; 1061 12.5 -1.6 18.6667;
1062 12.5 -1.6 19.4444; 1063 12.5 -1.6 20.2222; 1064 12.5 -1.6 21;
1065 12.5 -2.13333 14.7778; 1066 12.5 -2.13333 15.5556;
1067 12.5 -2.13333 16.3333; 1068 12.5 -2.13333 17.1111;
1069 12.5 -2.13333 17.8889; 1070 12.5 -2.13333 18.6667;
1071 12.5 -2.13333 19.4444; 1072 12.5 -2.13333 20.2222; 1073 12.5 -2.13333 21;
1074 12.5 -2.66667 14.7778; 1075 12.5 -2.66667 15.5556;
1076 12.5 -2.66667 16.3333; 1077 12.5 -2.66667 17.1111;
1078 12.5 -2.66667 17.8889; 1079 12.5 -2.66667 18.6667;
1080 12.5 -2.66667 19.4444; 1081 12.5 -2.66667 20.2222; 1082 12.5 -2.66667 21;
1083 12.5 -3.2 14.7778; 1084 12.5 -3.2 15.5556; 1085 12.5 -3.2 16.3333;
1086 12.5 -3.2 17.1111; 1087 12.5 -3.2 17.8889; 1088 12.5 -3.2 18.6667;
1089 12.5 -3.2 19.4444; 1090 12.5 -3.2 20.2222; 1091 13.1944 0 21;
1092 13.1944 -0.533333 21; 1093 13.8889 0 21; 1094 13.8889 -0.533333 21;
1095 14.5833 0 21; 1096 14.5833 -0.533333 21; 1097 15.2778 0 21;
1098 15.2778 -0.533333 21; 1099 15.9722 0 21; 1100 15.9722 -0.533333 21;
1101 16.6667 0 21; 1102 16.6667 -0.533333 21; 1103 17.3611 0 21;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1104 17.3611 -0.533333 21; 1105 18.0556 0 21; 1106 18.0556 -0.533333 21;
1107 18.75 -0.533333 21; 1108 13.1944 -1.06667 21; 1109 13.8889 -1.06667 21;
1110 14.5833 -1.06667 21; 1111 15.2778 -1.06667 21; 1112 15.9722 -1.06667 21;
1113 16.6667 -1.06667 21; 1114 17.3611 -1.06667 21; 1115 18.0556 -1.06667 21;
1116 18.75 -1.06667 21; 1117 13.1944 -1.6 21; 1118 13.8889 -1.6 21;
1119 14.5833 -1.6 21; 1120 15.2778 -1.6 21; 1121 15.9722 -1.6 21;
1122 16.6667 -1.6 21; 1123 17.3611 -1.6 21; 1124 18.0556 -1.6 21;
1125 18.75 -1.6 21; 1126 13.1944 -2.13333 21; 1127 13.8889 -2.13333 21;
1128 14.5833 -2.13333 21; 1129 15.2778 -2.13333 21; 1130 15.9722 -2.13333 21;
1131 16.6667 -2.13333 21; 1132 17.3611 -2.13333 21; 1133 18.0556 -2.13333 21;
1134 18.75 -2.13333 21; 1135 13.1944 -2.66667 21; 1136 13.8889 -2.66667 21;
1137 14.5833 -2.66667 21; 1138 15.2778 -2.66667 21; 1139 15.9722 -2.66667 21;
1140 16.6667 -2.66667 21; 1141 17.3611 -2.66667 21; 1142 18.0556 -2.66667 21;
1143 18.75 -2.66667 21; 1144 13.1944 -3.2 21; 1145 13.8889 -3.2 21;
1146 14.5833 -3.2 21; 1147 15.2778 -3.2 21; 1148 15.9722 -3.2 21;
1149 16.6667 -3.2 21; 1150 17.3611 -3.2 21; 1151 18.0556 -3.2 21;
1152 19.4444 0 21; 1153 19.4444 -0.533333 21; 1154 20.1389 0 21;
1155 20.1389 -0.533333 21; 1156 20.8333 0 21; 1157 20.8333 -0.533333 21;
1158 21.5278 0 21; 1159 21.5278 -0.533333 21; 1160 22.2222 0 21;
1161 22.2222 -0.533333 21; 1162 22.9167 0 21; 1163 22.9167 -0.533333 21;
1164 23.6111 0 21; 1165 23.6111 -0.533333 21; 1166 24.3056 0 21;
1167 24.3056 -0.533333 21; 1168 25 -0.533333 21; 1169 19.4444 -1.06667 21;
1170 20.1389 -1.06667 21; 1171 20.8333 -1.06667 21; 1172 21.5278 -1.06667 21;
1173 22.2222 -1.06667 21; 1174 22.9167 -1.06667 21; 1175 23.6111 -1.06667 21;
1176 24.3056 -1.06667 21; 1177 25 -1.06667 21; 1178 19.4444 -1.6 21;
1179 20.1389 -1.6 21; 1180 20.8333 -1.6 21; 1181 21.5278 -1.6 21;
1182 22.2222 -1.6 21; 1183 22.9167 -1.6 21; 1184 23.6111 -1.6 21;
1185 24.3056 -1.6 21; 1186 25 -1.6 21; 1187 19.4444 -2.13333 21;
1188 20.1389 -2.13333 21; 1189 20.8333 -2.13333 21; 1190 21.5278 -2.13333 21;
1191 22.2222 -2.13333 21; 1192 22.9167 -2.13333 21; 1193 23.6111 -2.13333 21;
1194 24.3056 -2.13333 21; 1195 25 -2.13333 21; 1196 19.4444 -2.66667 21;
1197 20.1389 -2.66667 21; 1198 20.8333 -2.66667 21; 1199 21.5278 -2.66667 21;
1200 22.2222 -2.66667 21; 1201 22.9167 -2.66667 21; 1202 23.6111 -2.66667 21;
1203 24.3056 -2.66667 21; 1204 25 -2.66667 21; 1205 19.4444 -3.2 21;
1206 20.1389 -3.2 21; 1207 20.8333 -3.2 21; 1208 21.5278 -3.2 21;
1209 22.2222 -3.2 21; 1210 22.9167 -3.2 21; 1211 23.6111 -3.2 21;
1212 24.3056 -3.2 21; 1213 0.694444 0 0; 1214 0.694444 -0.533333 0;
1215 1.38889 0 0; 1216 1.38889 -0.533333 0; 1217 2.08333 0 0;
1218 2.08333 -0.533333 0; 1219 2.77778 0 0; 1220 2.77778 -0.533333 0;
1221 3.47222 0 0; 1222 3.47222 -0.533333 0; 1223 4.16667 0 0;
1224 4.16667 -0.533333 0; 1225 4.86111 0 0; 1226 4.86111 -0.533333 0;
1227 5.55556 0 0; 1228 5.55556 -0.533333 0; 1229 6.25 -0.533333 0;
1230 0.694444 -1.06667 0; 1231 1.38889 -1.06667 0; 1232 2.08333 -1.06667 0;
1233 2.77778 -1.06667 0; 1234 3.47222 -1.06667 0; 1235 4.16667 -1.06667 0;
1236 4.86111 -1.06667 0; 1237 5.55556 -1.06667 0; 1238 6.25 -1.06667 0;
1239 0.694444 -1.6 0; 1240 1.38889 -1.6 0; 1241 2.08333 -1.6 0;
1242 2.77778 -1.6 0; 1243 3.47222 -1.6 0; 1244 4.16667 -1.6 0;
1245 4.86111 -1.6 0; 1246 5.55556 -1.6 0; 1247 6.25 -1.6 0;
1248 0.694444 -2.13333 0; 1249 1.38889 -2.13333 0; 1250 2.08333 -2.13333 0;
1251 2.77778 -2.13333 0; 1252 3.47222 -2.13333 0; 1253 4.16667 -2.13333 0;
1254 4.86111 -2.13333 0; 1255 5.55556 -2.13333 0; 1256 6.25 -2.13333 0;
1257 0.694444 -2.66667 0; 1258 1.38889 -2.66667 0; 1259 2.08333 -2.66667 0;
1260 2.77778 -2.66667 0; 1261 3.47222 -2.66667 0; 1262 4.16667 -2.66667 0;
1263 4.86111 -2.66667 0; 1264 5.55556 -2.66667 0; 1265 6.25 -2.66667 0;
1266 0.694444 -3.2 0; 1267 1.38889 -3.2 0; 1268 2.08333 -3.2 0;
1269 2.77778 -3.2 0; 1270 3.47222 -3.2 0; 1271 4.16667 -3.2 0;
1272 4.86111 -3.2 0; 1273 5.55556 -3.2 0; 1274 6.94444 -0.533333 0;
1275 7.63889 -0.533333 0; 1276 8.33333 -0.533333 0; 1277 9.02778 -0.533333 0;
1278 9.72222 -0.533333 0; 1279 10.4167 -0.533333 0; 1280 11.1111 -0.533333 0;
1281 11.8056 -0.533333 0; 1282 12.5 -0.533333 0; 1283 6.94444 -1.06667 0;
1284 7.63889 -1.06667 0; 1285 8.33333 -1.06667 0; 1286 9.02778 -1.06667 0;
1287 9.72222 -1.06667 0; 1288 10.4167 -1.06667 0; 1289 11.1111 -1.06667 0;
1290 11.8056 -1.06667 0; 1291 12.5 -1.06667 0; 1292 6.94444 -1.6 0;
1293 7.63889 -1.6 0; 1294 8.33333 -1.6 0; 1295 9.02778 -1.6 0;
1296 9.72222 -1.6 0; 1297 10.4167 -1.6 0; 1298 11.1111 -1.6 0;
1299 11.8056 -1.6 0; 1300 12.5 -1.6 0; 1301 6.94444 -2.13333 0;
1302 7.63889 -2.13333 0; 1303 8.33333 -2.13333 0; 1304 9.02778 -2.13333 0;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1305 9.72222 -2.13333 0; 1306 10.4167 -2.13333 0; 1307 11.1111 -2.13333 0;


1308 11.8056 -2.13333 0; 1309 12.5 -2.13333 0; 1310 6.94444 -2.66667 0;
1311 7.63889 -2.66667 0; 1312 8.33333 -2.66667 0; 1313 9.02778 -2.66667 0;
1314 9.72222 -2.66667 0; 1315 10.4167 -2.66667 0; 1316 11.1111 -2.66667 0;
1317 11.8056 -2.66667 0; 1318 12.5 -2.66667 0; 1319 6.94444 -3.2 0;
1320 7.63889 -3.2 0; 1321 8.33333 -3.2 0; 1322 9.02778 -3.2 0;
1323 9.72222 -3.2 0; 1324 10.4167 -3.2 0; 1325 11.1111 -3.2 0;
1326 11.8056 -3.2 0; 1327 13.1944 0 0; 1328 13.1944 -0.533333 0;
1329 13.8889 0 0; 1330 13.8889 -0.533333 0; 1331 14.5833 0 0;
1332 14.5833 -0.533333 0; 1333 15.2778 0 0; 1334 15.2778 -0.533333 0;
1335 15.9722 0 0; 1336 15.9722 -0.533333 0; 1337 16.6667 0 0;
1338 16.6667 -0.533333 0; 1339 17.3611 0 0; 1340 17.3611 -0.533333 0;
1341 18.0556 0 0; 1342 18.0556 -0.533333 0; 1343 18.75 -0.533333 0;
1344 13.1944 -1.06667 0; 1345 13.8889 -1.06667 0; 1346 14.5833 -1.06667 0;
1347 15.2778 -1.06667 0; 1348 15.9722 -1.06667 0; 1349 16.6667 -1.06667 0;
1350 17.3611 -1.06667 0; 1351 18.0556 -1.06667 0; 1352 18.75 -1.06667 0;
1353 13.1944 -1.6 0; 1354 13.8889 -1.6 0; 1355 14.5833 -1.6 0;
1356 15.2778 -1.6 0; 1357 15.9722 -1.6 0; 1358 16.6667 -1.6 0;
1359 17.3611 -1.6 0; 1360 18.0556 -1.6 0; 1361 18.75 -1.6 0;
1362 13.1944 -2.13333 0; 1363 13.8889 -2.13333 0; 1364 14.5833 -2.13333 0;
1365 15.2778 -2.13333 0; 1366 15.9722 -2.13333 0; 1367 16.6667 -2.13333 0;
1368 17.3611 -2.13333 0; 1369 18.0556 -2.13333 0; 1370 18.75 -2.13333 0;
1371 13.1944 -2.66667 0; 1372 13.8889 -2.66667 0; 1373 14.5833 -2.66667 0;
1374 15.2778 -2.66667 0; 1375 15.9722 -2.66667 0; 1376 16.6667 -2.66667 0;
1377 17.3611 -2.66667 0; 1378 18.0556 -2.66667 0; 1379 18.75 -2.66667 0;
1380 13.1944 -3.2 0; 1381 13.8889 -3.2 0; 1382 14.5833 -3.2 0;
1383 15.2778 -3.2 0; 1384 15.9722 -3.2 0; 1385 16.6667 -3.2 0;
1386 17.3611 -3.2 0; 1387 18.0556 -3.2 0; 1388 19.4444 0 0;
1389 19.4444 -0.533333 0; 1390 20.1389 0 0; 1391 20.1389 -0.533333 0;
1392 20.8333 0 0; 1393 20.8333 -0.533333 0; 1394 21.5278 0 0;
1395 21.5278 -0.533333 0; 1396 22.2222 0 0; 1397 22.2222 -0.533333 0;
1398 22.9167 0 0; 1399 22.9167 -0.533333 0; 1400 23.6111 0 0;
1401 23.6111 -0.533333 0; 1402 24.3056 0 0; 1403 24.3056 -0.533333 0;
1404 25 -0.533333 0; 1405 19.4444 -1.06667 0; 1406 20.1389 -1.06667 0;
1407 20.8333 -1.06667 0; 1408 21.5278 -1.06667 0; 1409 22.2222 -1.06667 0;
1410 22.9167 -1.06667 0; 1411 23.6111 -1.06667 0; 1412 24.3056 -1.06667 0;
1413 25 -1.06667 0; 1414 19.4444 -1.6 0; 1415 20.1389 -1.6 0;
1416 20.8333 -1.6 0; 1417 21.5278 -1.6 0; 1418 22.2222 -1.6 0;
1419 22.9167 -1.6 0; 1420 23.6111 -1.6 0; 1421 24.3056 -1.6 0; 1422 25 -1.6 0;
1423 19.4444 -2.13333 0; 1424 20.1389 -2.13333 0; 1425 20.8333 -2.13333 0;
1426 21.5278 -2.13333 0; 1427 22.2222 -2.13333 0; 1428 22.9167 -2.13333 0;
1429 23.6111 -2.13333 0; 1430 24.3056 -2.13333 0; 1431 25 -2.13333 0;
1432 19.4444 -2.66667 0; 1433 20.1389 -2.66667 0; 1434 20.8333 -2.66667 0;
1435 21.5278 -2.66667 0; 1436 22.2222 -2.66667 0; 1437 22.9167 -2.66667 0;
1438 23.6111 -2.66667 0; 1439 24.3056 -2.66667 0; 1440 25 -2.66667 0;
1441 19.4444 -3.2 0; 1442 20.1389 -3.2 0; 1443 20.8333 -3.2 0;
1444 21.5278 -3.2 0; 1445 22.2222 -3.2 0; 1446 22.9167 -3.2 0;
1447 23.6111 -3.2 0; 1448 24.3056 -3.2 0; 1449 25 -0.533333 0.777778;
1450 25 -0.533333 1.55556; 1451 25 -0.533333 2.33333;
1452 25 -0.533333 3.11111; 1453 25 -0.533333 3.88889;
1454 25 -0.533333 4.66667; 1455 25 -0.533333 5.44444;
1456 25 -0.533333 6.22222; 1457 25 -0.533333 7; 1458 25 -1.06667 0.777778;
1459 25 -1.06667 1.55556; 1460 25 -1.06667 2.33333; 1461 25 -1.06667 3.11111;
1462 25 -1.06667 3.88889; 1463 25 -1.06667 4.66667; 1464 25 -1.06667 5.44444;
1465 25 -1.06667 6.22222; 1466 25 -1.06667 7; 1467 25 -1.6 0.777778;
1468 25 -1.6 1.55556; 1469 25 -1.6 2.33333; 1470 25 -1.6 3.11111;
1471 25 -1.6 3.88889; 1472 25 -1.6 4.66667; 1473 25 -1.6 5.44444;
1474 25 -1.6 6.22222; 1475 25 -1.6 7; 1476 25 -2.13333 0.777778;
1477 25 -2.13333 1.55556; 1478 25 -2.13333 2.33333; 1479 25 -2.13333 3.11111;
1480 25 -2.13333 3.88889; 1481 25 -2.13333 4.66667; 1482 25 -2.13333 5.44444;
1483 25 -2.13333 6.22222; 1484 25 -2.13333 7; 1485 25 -2.66667 0.777778;
1486 25 -2.66667 1.55556; 1487 25 -2.66667 2.33333; 1488 25 -2.66667 3.11111;
1489 25 -2.66667 3.88889; 1490 25 -2.66667 4.66667; 1491 25 -2.66667 5.44444;
1492 25 -2.66667 6.22222; 1493 25 -2.66667 7; 1494 25 -3.2 0.777778;
1495 25 -3.2 1.55556; 1496 25 -3.2 2.33333; 1497 25 -3.2 3.11111;
1498 25 -3.2 3.88889; 1499 25 -3.2 4.66667; 1500 25 -3.2 5.44444;
1501 25 -3.2 6.22222; 1502 25 0 7.77778; 1503 25 -0.533333 7.77778;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1504 25 0 8.55556; 1505 25 -0.533333 8.55556; 1506 25 0 9.33333;


1507 25 -0.533333 9.33333; 1508 25 0 10.1111; 1509 25 -0.533333 10.1111;
1510 25 0 10.8889; 1511 25 -0.533333 10.8889; 1512 25 0 11.6667;
1513 25 -0.533333 11.6667; 1514 25 0 12.4444; 1515 25 -0.533333 12.4444;
1516 25 0 13.2222; 1517 25 -0.533333 13.2222; 1518 25 -0.533333 14;
1519 25 -1.06667 7.77778; 1520 25 -1.06667 8.55556; 1521 25 -1.06667 9.33333;
1522 25 -1.06667 10.1111; 1523 25 -1.06667 10.8889; 1524 25 -1.06667 11.6667;
1525 25 -1.06667 12.4444; 1526 25 -1.06667 13.2222; 1527 25 -1.06667 14;
1528 25 -1.6 7.77778; 1529 25 -1.6 8.55556; 1530 25 -1.6 9.33333;
1531 25 -1.6 10.1111; 1532 25 -1.6 10.8889; 1533 25 -1.6 11.6667;
1534 25 -1.6 12.4444; 1535 25 -1.6 13.2222; 1536 25 -1.6 14;
1537 25 -2.13333 7.77778; 1538 25 -2.13333 8.55556; 1539 25 -2.13333 9.33333;
1540 25 -2.13333 10.1111; 1541 25 -2.13333 10.8889; 1542 25 -2.13333 11.6667;
1543 25 -2.13333 12.4444; 1544 25 -2.13333 13.2222; 1545 25 -2.13333 14;
1546 25 -2.66667 7.77778; 1547 25 -2.66667 8.55556; 1548 25 -2.66667 9.33333;
1549 25 -2.66667 10.1111; 1550 25 -2.66667 10.8889; 1551 25 -2.66667 11.6667;
1552 25 -2.66667 12.4444; 1553 25 -2.66667 13.2222; 1554 25 -2.66667 14;
1555 25 -3.2 7.77778; 1556 25 -3.2 8.55556; 1557 25 -3.2 9.33333;
1558 25 -3.2 10.1111; 1559 25 -3.2 10.8889; 1560 25 -3.2 11.6667;
1561 25 -3.2 12.4444; 1562 25 -3.2 13.2222; 1563 25 0 14.7778;
1564 25 -0.533333 14.7778; 1565 25 0 15.5556; 1566 25 -0.533333 15.5556;
1567 25 0 16.3333; 1568 25 -0.533333 16.3333; 1569 25 0 17.1111;
1570 25 -0.533333 17.1111; 1571 25 0 17.8889; 1572 25 -0.533333 17.8889;
1573 25 0 18.6667; 1574 25 -0.533333 18.6667; 1575 25 0 19.4444;
1576 25 -0.533333 19.4444; 1577 25 0 20.2222; 1578 25 -0.533333 20.2222;
1579 25 -1.06667 14.7778; 1580 25 -1.06667 15.5556; 1581 25 -1.06667 16.3333;
1582 25 -1.06667 17.1111; 1583 25 -1.06667 17.8889; 1584 25 -1.06667 18.6667;
1585 25 -1.06667 19.4444; 1586 25 -1.06667 20.2222; 1587 25 -1.6 14.7778;
1588 25 -1.6 15.5556; 1589 25 -1.6 16.3333; 1590 25 -1.6 17.1111;
1591 25 -1.6 17.8889; 1592 25 -1.6 18.6667; 1593 25 -1.6 19.4444;
1594 25 -1.6 20.2222; 1595 25 -2.13333 14.7778; 1596 25 -2.13333 15.5556;
1597 25 -2.13333 16.3333; 1598 25 -2.13333 17.1111; 1599 25 -2.13333 17.8889;
1600 25 -2.13333 18.6667; 1601 25 -2.13333 19.4444; 1602 25 -2.13333 20.2222;
1603 25 -2.66667 14.7778; 1604 25 -2.66667 15.5556; 1605 25 -2.66667 16.3333;
1606 25 -2.66667 17.1111; 1607 25 -2.66667 17.8889; 1608 25 -2.66667 18.6667;
1609 25 -2.66667 19.4444; 1610 25 -2.66667 20.2222; 1611 25 -3.2 14.7778;
1612 25 -3.2 15.5556; 1613 25 -3.2 16.3333; 1614 25 -3.2 17.1111;
1615 25 -3.2 17.8889; 1616 25 -3.2 18.6667; 1617 25 -3.2 19.4444;
1618 25 -3.2 20.2222; 1619 18.75 -2.66667 28; 1620 19.4444 -2.66667 28;
1621 19.4444 -3.2 28; 1622 18.75 -2.13333 28; 1623 19.4444 -2.13333 28;
1624 18.75 -1.6 28; 1625 19.4444 -1.6 28; 1626 18.75 -1.06667 28;
1627 19.4444 -1.06667 28; 1628 18.75 -0.533333 28; 1629 19.4444 -0.533333 28;
1630 20.1389 -2.66667 28; 1631 20.1389 -3.2 28; 1632 20.1389 -2.13333 28;
1633 20.1389 -1.6 28; 1634 20.1389 -1.06667 28; 1635 20.1389 -0.533333 28;
1636 20.8333 -2.66667 28; 1637 20.8333 -3.2 28; 1638 20.8333 -2.13333 28;
1639 20.8333 -1.6 28; 1640 20.8333 -1.06667 28; 1641 20.8333 -0.533333 28;
1642 21.5278 -2.66667 28; 1643 21.5278 -3.2 28; 1644 21.5278 -2.13333 28;
1645 21.5278 -1.6 28; 1646 21.5278 -1.06667 28; 1647 21.5278 -0.533333 28;
1648 22.2222 -2.66667 28; 1649 22.2222 -3.2 28; 1650 22.2222 -2.13333 28;
1651 22.2222 -1.6 28; 1652 22.2222 -1.06667 28; 1653 22.2222 -0.533333 28;
1654 22.9167 -2.66667 28; 1655 22.9167 -3.2 28; 1656 22.9167 -2.13333 28;
1657 22.9167 -1.6 28; 1658 22.9167 -1.06667 28; 1659 22.9167 -0.533333 28;
1660 23.6111 -2.66667 28; 1661 23.6111 -3.2 28; 1662 23.6111 -2.13333 28;
1663 23.6111 -1.6 28; 1664 23.6111 -1.06667 28; 1665 23.6111 -0.533333 28;
1666 24.3056 -2.66667 28; 1667 24.3056 -3.2 28; 1668 24.3056 -2.13333 28;
1669 24.3056 -1.6 28; 1670 24.3056 -1.06667 28; 1671 24.3056 -0.533333 28;
1672 25 -2.66667 28; 1673 25 -2.13333 28; 1674 25 -1.6 28; 1675 25 -1.06667 28;
1676 25 -0.533333 28; 1677 0 7.35 3.5; 1678 0 6.825 3.5; 1679 0 6.3 3.5;
1680 0 5.775 3.5; 1681 0 5.25 3.5; 1682 0 4.725 3.5; 1683 0 4.2 3.5;
1684 0 3.675 3.5; 1685 0 3.15 3.5; 1686 0 2.625 3.5; 1687 0 2.1 3.5;
1688 0 1.575 3.5; 1689 0 1.05 3.5; 1690 0 0.524999 3.5; 1691 0 0 3.5;
1692 9.375 7.35 0; 1693 9.375 6.825 0; 1694 9.375 6.3 0; 1695 9.375 5.775 0;
1696 9.375 5.25 0; 1697 9.375 4.725 0; 1698 9.375 4.2 0; 1699 9.375 3.675 0;
1700 9.375 3.15 0; 1701 9.375 2.625 0; 1702 9.375 2.1 0; 1703 9.375 1.575 0;
1704 9.375 1.05 0; 1705 9.375 0.524999 0; 1706 9.375 0 0; 1707 9.375 7.35 14;
1708 9.375 6.825 14; 1709 9.375 6.3 14; 1710 9.375 5.775 14;
1711 9.375 5.25 14; 1712 9.375 4.725 14; 1713 9.375 4.2 14;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1714 9.375 3.675 14; 1715 9.375 3.15 14; 1716 9.375 2.625 14;
1717 9.375 2.1 14; 1718 9.375 1.575 14; 1719 9.375 1.05 14;
1720 9.375 0.524999 14; 1721 9.375 0 14; 1722 25 7.35 3.5; 1723 25 6.825 3.5;
1724 25 6.3 3.5; 1725 25 5.775 3.5; 1726 25 5.25 3.5; 1727 25 4.725 3.5;
1728 25 4.2 3.5; 1729 25 3.675 3.5; 1730 25 3.15 3.5; 1731 25 2.625 3.5;
1732 25 2.1 3.5; 1733 25 1.575 3.5; 1734 25 1.05 3.5; 1735 25 0.524999 3.5;
1736 25 0 3.5; 1737 21.875 7.35 28; 1738 21.875 6.825 28; 1739 21.875 6.3 28;
1740 21.875 5.775 28; 1741 21.875 5.25 28; 1742 21.875 4.725 28;
1743 21.875 4.2 28; 1744 21.875 3.675 28; 1745 21.875 3.15 28;
1746 21.875 2.625 28; 1747 21.875 2.1 28; 1748 21.875 1.575 28;
1749 21.875 1.05 28; 1750 21.875 0.524999 28; 1751 21.875 -8.85129e-007 28;
1752 0 -0.533333 3.5; 1753 0 -1.06667 3.5; 1754 0 -1.6 3.5;
1755 0 -2.13333 3.5; 1756 0 -2.66667 3.5; 1757 0 -3.2 3.5; 1758 0 0 10.5;
1759 0 -0.533333 10.5; 1760 0 -1.06667 10.5; 1761 0 -1.6 10.5;
1762 0 -2.13333 10.5; 1763 0 -2.66667 10.5; 1764 0 -3.2 10.5; 1765 3.125 0 14;
1766 3.125 -0.533333 14; 1767 3.125 -1.06667 14; 1768 3.125 -1.6 14;
1769 3.125 -2.13333 14; 1770 3.125 -2.66667 14; 1771 3.125 -3.2 14;
1772 9.375 -0.533333 14; 1773 9.375 -1.06667 14; 1774 9.375 -1.6 14;
1775 9.375 -2.13333 14; 1776 9.375 -2.66667 14; 1777 9.375 -3.2 14;
1778 12.5 0 17.5; 1779 12.5 -0.533333 17.5; 1780 12.5 -1.06667 17.5;
1781 12.5 -1.6 17.5; 1782 12.5 -2.13333 17.5; 1783 12.5 -2.66667 17.5;
1784 12.5 -3.2 17.5; 1785 15.625 0 21; 1786 15.625 -0.533333 21;
1787 15.625 -1.06667 21; 1788 15.625 -1.6 21; 1789 15.625 -2.13333 21;
1790 15.625 -2.66667 21; 1791 15.625 -3.2 21; 1792 21.875 0 21;
1793 21.875 -0.533333 21; 1794 21.875 -1.06667 21; 1795 21.875 -1.6 21;
1796 21.875 -2.13333 21; 1797 21.875 -2.66667 21; 1798 21.875 -3.2 21;
1799 3.125 0 0; 1800 3.125 -0.533333 0; 1801 3.125 -1.06667 0;
1802 3.125 -1.6 0; 1803 3.125 -2.13333 0; 1804 3.125 -2.66667 0;
1805 3.125 -3.2 0; 1806 9.375 -0.533333 0; 1807 9.375 -1.06667 0;
1808 9.375 -1.6 0; 1809 9.375 -2.13333 0; 1810 9.375 -2.66667 0;
1811 9.375 -3.2 0; 1812 15.625 0 0; 1813 15.625 -0.533333 0;
1814 15.625 -1.06667 0; 1815 15.625 -1.6 0; 1816 15.625 -2.13333 0;
1817 15.625 -2.66667 0; 1818 15.625 -3.2 0; 1819 21.875 0 0;
1820 21.875 -0.533333 0; 1821 21.875 -1.06667 0; 1822 21.875 -1.6 0;
1823 21.875 -2.13333 0; 1824 21.875 -2.66667 0; 1825 21.875 -3.2 0;
1826 25 -0.533333 3.5; 1827 25 -1.06667 3.5; 1828 25 -1.6 3.5;
1829 25 -2.13333 3.5; 1830 25 -2.66667 3.5; 1831 25 -3.2 3.5; 1832 25 0 10.5;
1833 25 -0.533333 10.5; 1834 25 -1.06667 10.5; 1835 25 -1.6 10.5;
1836 25 -2.13333 10.5; 1837 25 -2.66667 10.5; 1838 25 -3.2 10.5;
1839 25 0 17.5; 1840 25 -0.533333 17.5; 1841 25 -1.06667 17.5;
1842 25 -1.6 17.5; 1843 25 -2.13333 17.5; 1844 25 -2.66667 17.5;
1845 25 -3.2 17.5; 1846 21.875 -0.533334 28; 1847 21.875 -1.06667 28;
1848 21.875 -1.6 28; 1849 21.875 -2.13333 28; 1850 21.875 -2.66667 28;
1851 21.875 -3.2 28; 1852 3.125 7.35 0; 1853 15.625 7.35 0; 1854 21.875 7.35 0;
1855 3.125 7.35 7; 1856 9.375 7.35 7; 1857 15.625 7.35 7; 1858 21.875 7.35 7;
1859 3.125 7.35 14; 1860 15.625 7.35 14; 1861 21.875 7.35 14;
1862 15.625 7.35 21; 1863 21.875 7.35 21; 1864 25 7.35 10.5; 1865 25 7.35 17.5;
1866 18.75 7.35 3.5; 1867 18.75 7.35 10.5; 1868 18.75 7.35 17.5;
1869 12.5 7.35 3.5; 1870 12.5 7.35 10.5; 1871 12.5 7.35 17.5;
1872 6.25 7.35 3.5; 1873 6.25 7.35 10.5; 1874 0 7.35 10.5; 1875 25 7.35 24.5;
1876 18.75 7.35 24.5; 1877 9.375 11.45 7; 1878 15.625 11.45 7;
1879 9.375 11.45 14; 1880 15.625 11.45 14; 1881 18.75 11.45 10.5;
1882 12.5 11.45 10.5; 1883 6.25 11.45 10.5; 1884 3.125 0 7; 1886 15.625 0 7;
1887 21.875 0 7; 1888 15.625 0 14; 1889 21.875 0 14; 1890 18.75 0 4.18;
1891 18.75 0 11.67; 1892 18.75 0 17.5; 1893 12.5 0 4.18; 1894 12.5 0 11.67;
1895 6.25 0 3.11111; 1896 6.25 0 11.67; 1897 9.375 11.45 10.5;
1898 15.625 11.45 10.5; 1899 3.125 7.35 3.5; 1900 9.375 7.35 3.5;
1901 15.625 7.35 3.5; 1902 21.875 7.35 3.5; 1903 3.125 7.35 10.5;
1904 9.375 7.35 10.5; 1905 15.625 7.35 10.5; 1906 21.875 7.35 10.5;
1907 15.625 7.35 17.5; 1908 21.875 7.35 17.5; 1909 21.875 7.35 24.5;
1910 3.125 0 3.5; 1911 9.375 0 3.11111; 1912 15.625 0 4.18; 1914 3.125 0 11.67;
1916 15.625 0 11.67; 1917 21.875 0 11.67; 1918 15.625 0 17.5;
1919 21.875 0 17.5; 1920 18.75 -3.2 23.3333; 1921 18.75 -3.2 25.6667;
1922 25 -3.2 23.3333; 1923 25 -3.2 25.6667; 1924 18.75 0 3.11111;
1925 21.875 0 3.11111; 1926 12.5 0 3.11111; 1927 6.25 0 3.5;
1928 3.47222 0 3.5; 1929 8.33 0 7; 1930 8.33 0 3.11111; 1931 8.33 0 11.67;
1932 8.33 0 14; 1933 10.4167 0 7; 1934 10.4167 0 11.67; 1935 10.4167 0 3.11111;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1936 13.8889 0 14; 1937 13.8889 0 17.5; 1938 16.983 0 14; 1939 16.983 0 17.5;
1940 19.4444 0 14; 1941 19.4444 0 17.5; 1942 23.6111 0 14; 1943 23.6111 0 17.5;
1944 19.4444 0 15.75; 1945 19.4444 0 19.25; 1946 23.6111 0 15.75;
1947 23.6111 0 19.25; 1948 14.425 0 4.18; 1949 14.425 0 7; 1950 14.425 0 11.67;
1951 14.425 0 14; 1952 16.825 0 4.18; 1953 16.825 0 7; 1954 16.825 0 11.67;
1955 16.825 0 14;
*******************************************************************************
MEMBER INCIDENCES
1 1 196; 2 2 342; 3 3 350; 4 4 22; 5 5 634; 6 6 204; 7 7 25; 8 8 26; 9 9 27;
10 10 642; 11 11 29; 12 12 488; 13 13 496; 14 14 32; 15 15 33; 16 16 34;
17 17 35; 18 18 36; 19 37 838; 20 38 1265; 21 39 1318; 22 40 1379; 23 41 1440;
24 42 846; 25 43 7; 26 44 8; 27 45 9; 28 46 1493; 29 47 907; 30 48 968;
31 49 1021; 32 50 14; 33 51 1554; 34 52 1082; 35 53 1143; 36 54 1204;
37 19 1852; 38 20 213; 39 21 1853; 40 22 1854; 41 24 1855; 42 25 1856;
43 26 1857; 44 27 1858; 45 29 1859; 46 30 359; 47 31 1860; 48 32 1861;
49 34 1862; 50 35 1863; 51 23 505; 52 28 1864; 53 33 1865; 54 22 1866;
55 27 1867; 56 32 1868; 57 21 1869; 58 26 1870; 59 31 1871; 60 20 1872;
61 25 1873; 62 19 67; 63 24 1874; 64 1 1213; 65 2 351; 66 3 1327; 67 4 1388;
68 11 916; 69 12 497; 70 16 1091; 71 17 1152; 72 5 643; 73 10 1502; 74 15 1563;
75 13 1030; 76 1 205; 77 6 855; 78 55 780; 79 57 788; 80 56 651; 81 36 1875;
82 35 1876; 83 59 1619; 84 60 1672; 85 25 61; 86 26 62; 87 27 63; 88 30 64;
89 31 65; 90 32 66; 91 61 1877; 92 62 1878; 93 64 1879; 94 65 1880; 95 63 1881;
96 62 1882; 97 61 1883; 112 53 1920; 113 54 1922; 121 67 70; 122 69 19;
124 70 72; 126 72 74; 128 74 1677; 130 76 78; 132 78 80; 134 80 82; 136 82 24;
138 84 24; 140 86 69; 149 94 84; 151 96 86; 160 104 94; 162 106 96;
171 114 104; 173 116 106; 182 124 114; 184 126 116; 193 134 124; 195 136 126;
204 144 134; 206 146 136; 215 154 144; 217 156 146; 226 164 154; 228 166 156;
237 174 164; 239 176 166; 248 184 174; 250 186 176; 259 194 184; 261 196 186;
270 204 194; 272 205 206; 274 206 207; 276 207 208; 278 208 1691; 280 209 210;
282 210 211; 284 211 212; 286 212 6; 289 213 216; 290 215 20; 292 216 218;
294 218 220; 296 220 1692; 298 222 224; 300 224 226; 302 226 228; 304 228 21;
306 230 21; 308 232 215; 317 240 230; 319 242 232; 328 250 240; 330 252 242;
339 260 250; 341 262 252; 350 270 260; 352 272 262; 361 280 270; 363 282 272;
372 290 280; 374 292 282; 383 300 290; 385 302 292; 394 310 300; 396 312 302;
405 320 310; 407 322 312; 416 330 320; 418 332 322; 427 340 330; 429 342 332;
438 350 340; 440 351 352; 442 352 353; 444 353 354; 446 354 1706; 448 355 356;
450 356 357; 452 357 358; 454 358 3; 457 359 362; 458 361 30; 460 362 364;
462 364 366; 464 366 1707; 466 368 370; 468 370 372; 470 372 374; 472 374 31;
474 376 31; 476 378 361; 485 386 376; 487 388 378; 496 396 386; 498 398 388;
507 406 396; 509 408 398; 518 416 406; 520 418 408; 529 426 416; 531 428 418;
540 436 426; 542 438 428; 551 446 436; 553 448 438; 562 456 446; 564 458 448;
573 466 456; 575 468 458; 584 476 466; 586 478 468; 595 486 476; 597 488 478;
606 496 486; 608 497 498; 610 498 1932; 612 499 500; 614 500 1721; 616 501 502;
618 502 503; 620 503 504; 622 504 13; 625 505 508; 626 507 23; 628 508 510;
630 510 512; 632 512 1722; 634 514 516; 636 516 518; 638 518 520; 640 520 28;
642 522 28; 644 524 507; 653 532 522; 655 534 524; 664 542 532; 666 544 534;
675 552 542; 677 554 544; 686 562 552; 688 564 554; 697 572 562; 699 574 564;
708 582 572; 710 584 574; 719 592 582; 721 594 584; 730 602 592; 732 604 594;
741 612 602; 743 614 604; 752 622 612; 754 624 614; 763 632 622; 765 634 624;
774 642 632; 776 643 644; 778 644 645; 780 645 646; 782 646 1736; 784 647 648;
786 648 649; 788 649 650; 790 650 10; 793 651 654; 794 653 56; 796 654 656;
798 656 658; 800 658 1737; 802 660 662; 804 662 664; 806 664 666; 808 666 58;
810 668 58; 812 670 653; 821 678 668; 823 680 670; 832 688 678; 834 690 680;
843 698 688; 845 700 690; 854 708 698; 856 710 700; 865 718 708; 867 720 710;
876 728 718; 878 730 720; 887 738 728; 889 740 730; 898 748 738; 900 750 740;
909 758 748; 911 760 750; 920 768 758; 922 770 760; 931 778 768; 933 780 770;
942 788 778; 953 798 1; 962 806 6; 964 808 798; 973 816 806; 975 818 808;
984 826 816; 986 828 818; 995 836 826; 997 838 828; 1006 846 836; 1017 855 857;
1019 857 859; 1021 859 861; 1023 861 1758; 1025 863 865; 1027 865 867;
1029 867 869; 1031 869 11; 1033 871 11; 1043 880 871; 1053 889 880;
1063 898 889; 1073 907 898; 1084 916 918; 1086 918 920; 1088 920 922;
1090 922 1765; 1092 924 926; 1094 926 928; 1096 928 930; 1098 930 12;
1100 932 12; 1110 941 932; 1120 950 941; 1130 959 950; 1140 968 959;
1159 985 13; 1169 994 985; 1179 1003 994; 1189 1012 1003; 1199 1021 1012;
1210 1030 1032; 1212 1032 1034; 1214 1034 1036; 1216 1036 1778; 1218 1038 1040;
1220 1040 1042; 1222 1042 1044; 1224 1044 16; 1226 1046 16; 1236 1055 1046;
1246 1064 1055; 1256 1073 1064; 1266 1082 1073; 1277 1091 1093; 1279 1093 1095;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1281 1095 1097; 1283 1097 1785; 1285 1099 1101; 1287 1101 1103; 1289 1103 1105;
1291 1105 17; 1293 1107 17; 1303 1116 1107; 1313 1125 1116; 1323 1134 1125;
1333 1143 1134; 1344 1152 1154; 1346 1154 1156; 1348 1156 1158; 1350 1158 1792;
1352 1160 1162; 1354 1162 1164; 1356 1164 1166; 1358 1166 18; 1360 1168 18;
1370 1177 1168; 1380 1186 1177; 1390 1195 1186; 1400 1204 1195; 1411 1213 1215;
1413 1215 1217; 1415 1217 1219; 1417 1219 1799; 1419 1221 1223; 1421 1223 1225;
1423 1225 1227; 1425 1227 2; 1427 1229 2; 1437 1238 1229; 1447 1247 1238;
1457 1256 1247; 1467 1265 1256; 1486 1282 3; 1496 1291 1282; 1506 1300 1291;
1516 1309 1300; 1526 1318 1309; 1537 1327 1329; 1539 1329 1331; 1541 1331 1333;
1543 1333 1812; 1545 1335 1337; 1547 1337 1339; 1549 1339 1341; 1551 1341 4;
1553 1343 4; 1563 1352 1343; 1573 1361 1352; 1583 1370 1361; 1593 1379 1370;
1604 1388 1390; 1606 1390 1392; 1608 1392 1394; 1610 1394 1819; 1612 1396 1398;
1614 1398 1400; 1616 1400 1402; 1618 1402 5; 1620 1404 5; 1630 1413 1404;
1640 1422 1413; 1650 1431 1422; 1660 1440 1431; 1679 1457 10; 1689 1466 1457;
1699 1475 1466; 1709 1484 1475; 1719 1493 1484; 1730 1502 1504; 1732 1504 1506;
1734 1506 1508; 1736 1508 1832; 1738 1510 1512; 1740 1512 1514; 1742 1514 1516;
1744 1516 15; 1746 1518 15; 1756 1527 1518; 1766 1536 1527; 1776 1545 1536;
1786 1554 1545; 1797 1563 1565; 1799 1565 1567; 1801 1567 1569; 1803 1569 1839;
1805 1571 1573; 1807 1573 1575; 1809 1575 1577; 1811 1577 18; 1859 1619 1622;
1861 1622 1624; 1863 1624 1626; 1865 1626 1628; 1867 1628 55; 1912 1672 1673;
1914 1673 1674; 1916 1674 1675; 1918 1675 1676; 1920 1676 57; 1923 6 1884;
1924 7 1929; 1925 8 1949; 1926 9 1887; 1927 13 1936; 1928 14 1940; 1930 4 1924;
1931 9 1891; 1932 14 1892; 1933 3 1926; 1934 8 1894; 1935 2 1895; 1936 7 1896;
1937 1677 76; 1964 1691 209; 1967 1692 222; 1994 1706 355; 1997 1707 368;
2024 1721 501; 2027 1722 514; 2054 1736 647; 2057 1737 660; 2098 1758 863;
2111 1765 924; 2136 1778 1038; 2149 1785 1099; 2162 1792 1160; 2176 1799 1221;
2201 1812 1335; 2214 1819 1396; 2239 1832 1510; 2252 1839 1571; 2277 1852 20;
2278 1853 22; 2279 1854 23; 2280 1855 25; 2281 1856 26; 2282 1857 27;
2283 1858 28; 2284 1859 30; 2285 1860 32; 2286 1861 33; 2287 1862 35;
2288 1863 36; 2289 1864 33; 2290 1865 36; 2291 1866 27; 2292 1867 32;
2293 1868 35; 2294 1869 26; 2295 1870 31; 2296 1871 34; 2297 1872 25;
2298 1873 30; 2299 1874 29; 2300 1875 58; 2301 1876 56; 2302 1877 62;
2303 1878 63; 2304 1879 65; 2305 1880 66; 2306 1881 66; 2307 1882 65;
2308 1883 64; 2309 1884 7; 2311 1886 1953; 2312 1887 10; 2313 1888 1955;
2314 1889 1942; 2315 1890 9; 2316 1891 14; 2317 1892 17; 2318 1893 8;
2319 1894 13; 2320 1895 1927; 2321 1896 12; 2322 1877 1897; 2323 1897 1879;
2324 1878 1898; 2325 1898 1880; 2326 1883 1897; 2327 1882 1898; 2328 1897 1882;
2329 1898 1881; 2330 1677 1899; 2331 1872 1900; 2332 1869 1901; 2333 1866 1902;
2334 1899 1872; 2335 1900 1869; 2336 1901 1866; 2337 1902 1722; 2338 1874 1903;
2339 1873 1904; 2340 1870 1905; 2341 1867 1906; 2342 1903 1873; 2343 1904 1870;
2344 1905 1867; 2345 1906 1864; 2346 1852 1899; 2347 1855 1903; 2348 1899 1855;
2349 1903 1859; 2350 1692 1900; 2351 1856 1904; 2352 1900 1856; 2353 1904 1707;
2354 1853 1901; 2355 1857 1905; 2356 1860 1907; 2357 1901 1857; 2358 1905 1860;
2359 1907 1862; 2360 1854 1902; 2361 1858 1906; 2362 1861 1908; 2363 1902 1858;
2364 1906 1861; 2365 1908 1863; 2366 1863 1909; 2367 1909 1737; 2368 1691 1910;
2369 1895 1930; 2370 1893 1948; 2372 1910 1928; 2373 1911 1935; 2374 1912 1952;
2376 865 1914; 2377 1896 1931; 2378 1894 1950; 2379 1891 1917; 2380 1914 1896;
2382 1916 1954; 2383 1917 1512; 2384 1221 1928; 2385 1884 1914; 2386 1910 1884;
2387 1914 1765; 2388 1706 1911; 2392 1812 1912; 2396 1819 1925; 2397 1887 1917;
2399 1917 1889; 2404 1920 1921; 2405 1921 59; 2406 1922 1923; 2407 1923 60;
2408 1778 1937; 2409 1892 1941; 2410 1918 1939; 2411 1919 1943; 2412 1871 1907;
2413 1868 1908; 2414 1907 1868; 2415 1908 1865; 2416 1876 1909; 2417 1909 1875;
2418 1924 1890; 2419 1925 1887; 2420 1924 1925; 2421 1925 646; 2430 1926 1893;
2431 1927 7; 2432 1928 1927; 2433 1929 1933; 2434 1930 1911; 2435 1931 1934;
2436 1929 1931; 2437 1930 1929; 2438 1932 499; 2439 1931 1932; 2440 1933 8;
2441 1934 1894; 2442 1933 1934; 2443 1935 1926; 2444 1935 1933; 2445 1934 502;
2446 1936 1951; 2447 1937 1918; 2448 1936 1937; 2449 1937 1093; 2450 1888 1918;
2451 1918 1785; 2452 1938 14; 2453 1939 1892; 2454 1938 1939; 2455 1940 1889;
2456 1941 1919; 2457 1940 1944; 2458 1941 1945; 2459 1942 15; 2460 1943 1839;
2461 1942 1946; 2462 1943 1947; 2463 1944 1941; 2464 1945 1152; 2465 1946 1943;
2466 1947 1164; 2467 1944 1946; 2468 1945 1947; 2469 1948 1912; 2470 1949 1886;
2471 1950 1916; 2472 1949 1950; 2473 1948 1949; 2474 1951 1888; 2475 1950 1951;
2476 1952 1890; 2477 1953 9; 2478 1954 1891; 2479 1953 1954; 2480 1952 1953;
2481 1955 1938; 2482 1954 1955;
*******************************************************************************
ELEMENT INCIDENCES SHELL
123 19 67 68 69; 125 67 70 71 68; 127 70 72 73 71; 129 72 74 75 73;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

133 76 78 79 77; 135 78 80 81 79; 137 80 82 83 81; 139 82 24 84 83;


141 69 68 85 86; 142 68 71 87 85; 143 71 73 88 87; 144 73 75 89 88;
146 77 79 91 90; 147 79 81 92 91; 148 81 83 93 92; 150 83 84 94 93;
152 86 85 95 96; 153 85 87 97 95; 154 87 88 98 97; 155 88 89 99 98;
157 90 91 101 100; 158 91 92 102 101; 159 92 93 103 102; 161 93 94 104 103;
163 96 95 105 106; 164 95 97 107 105; 165 97 98 108 107; 166 98 99 109 108;
168 100 101 111 110; 169 101 102 112 111; 170 102 103 113 112;
172 103 104 114 113; 174 106 105 115 116; 175 105 107 117 115;
176 107 108 118 117; 177 108 109 119 118; 179 110 111 121 120;
180 111 112 122 121; 181 112 113 123 122; 183 113 114 124 123;
185 116 115 125 126; 186 115 117 127 125; 187 117 118 128 127;
188 118 119 129 128; 190 120 121 131 130; 191 121 122 132 131;
192 122 123 133 132; 194 123 124 134 133; 196 126 125 135 136;
197 125 127 137 135; 198 127 128 138 137; 199 128 129 139 138;
201 130 131 141 140; 202 131 132 142 141; 203 132 133 143 142;
205 133 134 144 143; 207 136 135 145 146; 208 135 137 147 145;
209 137 138 148 147; 210 138 139 149 148; 212 140 141 151 150;
213 141 142 152 151; 214 142 143 153 152; 216 143 144 154 153;
218 146 145 155 156; 219 145 147 157 155; 220 147 148 158 157;
221 148 149 159 158; 223 150 151 161 160; 224 151 152 162 161;
225 152 153 163 162; 227 153 154 164 163; 231 157 158 168 167;
232 158 159 169 168; 234 160 161 171 170; 235 161 162 172 171;
236 162 163 173 172; 238 163 164 174 173; 242 167 168 178 177;
243 168 169 179 178; 245 170 171 181 180; 246 171 172 182 181;
247 172 173 183 182; 249 173 174 184 183; 253 177 178 188 187;
254 178 179 189 188; 256 180 181 191 190; 257 181 182 192 191;
258 182 183 193 192; 260 183 184 194 193; 264 187 188 198 197;
265 188 189 199 198; 267 190 191 201 200; 268 191 192 202 201;
269 192 193 203 202; 271 193 194 204 203; 277 197 198 207 206;
279 198 199 208 207; 283 200 201 210 209; 285 201 202 211 210;
287 202 203 212 211; 288 203 204 6 212; 291 20 213 214 215;
293 213 216 217 214; 295 216 218 219 217; 297 218 220 221 219;
301 222 224 225 223; 303 224 226 227 225; 305 226 228 229 227;
307 228 21 230 229; 309 215 214 231 232; 310 214 217 233 231;
311 217 219 234 233; 312 219 221 235 234; 314 223 225 237 236;
315 225 227 238 237; 316 227 229 239 238; 318 229 230 240 239;
320 232 231 241 242; 321 231 233 243 241; 322 233 234 244 243;
323 234 235 245 244; 325 236 237 247 246; 326 237 238 248 247;
327 238 239 249 248; 329 239 240 250 249; 331 242 241 251 252;
332 241 243 253 251; 333 243 244 254 253; 334 244 245 255 254;
336 246 247 257 256; 337 247 248 258 257; 338 248 249 259 258;
340 249 250 260 259; 342 252 251 261 262; 343 251 253 263 261;
344 253 254 264 263; 345 254 255 265 264; 347 256 257 267 266;
348 257 258 268 267; 349 258 259 269 268; 351 259 260 270 269;
353 262 261 271 272; 354 261 263 273 271; 355 263 264 274 273;
356 264 265 275 274; 358 266 267 277 276; 359 267 268 278 277;
360 268 269 279 278; 362 269 270 280 279; 364 272 271 281 282;
365 271 273 283 281; 366 273 274 284 283; 367 274 275 285 284;
369 276 277 287 286; 370 277 278 288 287; 371 278 279 289 288;
373 279 280 290 289; 375 282 281 291 292; 376 281 283 293 291;
377 283 284 294 293; 378 284 285 295 294; 380 286 287 297 296;
381 287 288 298 297; 382 288 289 299 298; 384 289 290 300 299;
386 292 291 301 302; 387 291 293 303 301; 388 293 294 304 303;
389 294 295 305 304; 391 296 297 307 306; 392 297 298 308 307;
393 298 299 309 308; 395 299 300 310 309; 397 302 301 311 312;
398 301 303 313 311; 399 303 304 314 313; 400 304 305 315 314;
402 306 307 317 316; 403 307 308 318 317; 404 308 309 319 318;
406 309 310 320 319; 408 312 311 321 322; 409 311 313 323 321;
410 313 314 324 323; 411 314 315 325 324; 413 316 317 327 326;
414 317 318 328 327; 415 318 319 329 328; 417 319 320 330 329;
419 322 321 331 332; 420 321 323 333 331; 421 323 324 334 333;
422 324 325 335 334; 424 326 327 337 336; 425 327 328 338 337;
426 328 329 339 338; 428 329 330 340 339; 430 332 331 341 342;
431 331 333 343 341; 432 333 334 344 343; 433 334 335 345 344;
435 336 337 347 346; 436 337 338 348 347; 437 338 339 349 348;
439 339 340 350 349; 441 342 341 351 2; 443 341 343 352 351;
445 343 344 353 352; 447 344 345 354 353; 451 346 347 356 355;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

453 347 348 357 356; 455 348 349 358 357; 456 349 350 3 358;
459 30 359 360 361; 461 359 362 363 360; 463 362 364 365 363;
465 364 366 367 365; 469 368 370 371 369; 471 370 372 373 371;
473 372 374 375 373; 475 374 31 376 375; 477 361 360 377 378;
478 360 363 379 377; 479 363 365 380 379; 480 365 367 381 380;
482 369 371 383 382; 483 371 373 384 383; 484 373 375 385 384;
486 375 376 386 385; 488 378 377 387 388; 489 377 379 389 387;
490 379 380 390 389; 491 380 381 391 390; 493 382 383 393 392;
494 383 384 394 393; 495 384 385 395 394; 497 385 386 396 395;
499 388 387 397 398; 500 387 389 399 397; 501 389 390 400 399;
502 390 391 401 400; 504 392 393 403 402; 505 393 394 404 403;
506 394 395 405 404; 508 395 396 406 405; 510 398 397 407 408;
511 397 399 409 407; 512 399 400 410 409; 513 400 401 411 410;
515 402 403 413 412; 516 403 404 414 413; 517 404 405 415 414;
519 405 406 416 415; 521 408 407 417 418; 522 407 409 419 417;
523 409 410 420 419; 524 410 411 421 420; 526 412 413 423 422;
527 413 414 424 423; 528 414 415 425 424; 530 415 416 426 425;
532 418 417 427 428; 533 417 419 429 427; 534 419 420 430 429;
535 420 421 431 430; 537 422 423 433 432; 538 423 424 434 433;
539 424 425 435 434; 541 425 426 436 435; 543 428 427 437 438;
544 427 429 439 437; 545 429 430 440 439; 546 430 431 441 440;
548 432 433 443 442; 549 433 434 444 443; 550 434 435 445 444;
552 435 436 446 445; 554 438 437 447 448; 555 437 439 449 447;
556 439 440 450 449; 557 440 441 451 450; 559 442 443 453 452;
560 443 444 454 453; 561 444 445 455 454; 563 445 446 456 455;
565 448 447 457 458; 566 447 449 459 457; 567 449 450 460 459;
568 450 451 461 460; 570 452 453 463 462; 571 453 454 464 463;
572 454 455 465 464; 574 455 456 466 465; 576 458 457 467 468;
577 457 459 469 467; 578 459 460 470 469; 579 460 461 471 470;
581 462 463 473 472; 582 463 464 474 473; 583 464 465 475 474;
585 465 466 476 475; 587 468 467 477 478; 588 467 469 479 477;
589 469 470 480 479; 590 470 471 481 480; 592 472 473 483 482;
593 473 474 484 483; 594 474 475 485 484; 596 475 476 486 485;
598 478 477 487 488; 599 477 479 489 487; 600 479 480 490 489;
601 480 481 491 490; 603 482 483 493 492; 604 483 484 494 493;
605 484 485 495 494; 607 485 486 496 495; 609 488 487 497 12;
611 487 489 498 497; 613 489 490 499 498; 615 490 491 500 499;
619 492 493 502 501; 621 493 494 503 502; 623 494 495 504 503;
624 495 496 13 504; 627 23 505 506 507; 629 505 508 509 506;
631 508 510 511 509; 633 510 512 513 511; 637 514 516 517 515;
639 516 518 519 517; 641 518 520 521 519; 643 520 28 522 521;
645 507 506 523 524; 646 506 509 525 523; 647 509 511 526 525;
648 511 513 527 526; 650 515 517 529 528; 651 517 519 530 529;
652 519 521 531 530; 654 521 522 532 531; 656 524 523 533 534;
657 523 525 535 533; 658 525 526 536 535; 659 526 527 537 536;
661 528 529 539 538; 662 529 530 540 539; 663 530 531 541 540;
665 531 532 542 541; 667 534 533 543 544; 668 533 535 545 543;
669 535 536 546 545; 670 536 537 547 546; 672 538 539 549 548;
673 539 540 550 549; 674 540 541 551 550; 676 541 542 552 551;
678 544 543 553 554; 679 543 545 555 553; 680 545 546 556 555;
681 546 547 557 556; 683 548 549 559 558; 684 549 550 560 559;
685 550 551 561 560; 687 551 552 562 561; 689 554 553 563 564;
690 553 555 565 563; 691 555 556 566 565; 692 556 557 567 566;
694 558 559 569 568; 695 559 560 570 569; 696 560 561 571 570;
698 561 562 572 571; 700 564 563 573 574; 701 563 565 575 573;
702 565 566 576 575; 703 566 567 577 576; 705 568 569 579 578;
706 569 570 580 579; 707 570 571 581 580; 709 571 572 582 581;
711 574 573 583 584; 712 573 575 585 583; 713 575 576 586 585;
714 576 577 587 586; 716 578 579 589 588; 717 579 580 590 589;
718 580 581 591 590; 720 581 582 592 591; 722 584 583 593 594;
723 583 585 595 593; 724 585 586 596 595; 725 586 587 597 596;
727 588 589 599 598; 728 589 590 600 599; 729 590 591 601 600;
731 591 592 602 601; 733 594 593 603 604; 734 593 595 605 603;
735 595 596 606 605; 736 596 597 607 606; 738 598 599 609 608;
739 599 600 610 609; 740 600 601 611 610; 742 601 602 612 611;
744 604 603 613 614; 745 603 605 615 613; 746 605 606 616 615;
747 606 607 617 616; 749 608 609 619 618; 750 609 610 620 619;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

751 610 611 621 620; 753 611 612 622 621; 755 614 613 623 624;
756 613 615 625 623; 757 615 616 626 625; 758 616 617 627 626;
760 618 619 629 628; 761 619 620 630 629; 762 620 621 631 630;
764 621 622 632 631; 766 624 623 633 634; 767 623 625 635 633;
768 625 626 636 635; 769 626 627 637 636; 771 628 629 639 638;
772 629 630 640 639; 773 630 631 641 640; 775 631 632 642 641;
777 634 633 643 5; 779 633 635 644 643; 781 635 636 645 644;
783 636 637 646 645; 787 638 639 648 647; 789 639 640 649 648;
791 640 641 650 649; 792 641 642 10 650; 795 56 651 652 653;
797 651 654 655 652; 799 654 656 657 655; 801 656 658 659 657;
805 660 662 663 661; 807 662 664 665 663; 809 664 666 667 665;
811 666 58 668 667; 813 653 652 669 670; 814 652 655 671 669;
815 655 657 672 671; 816 657 659 673 672; 818 661 663 675 674;
819 663 665 676 675; 820 665 667 677 676; 822 667 668 678 677;
824 670 669 679 680; 825 669 671 681 679; 826 671 672 682 681;
827 672 673 683 682; 829 674 675 685 684; 830 675 676 686 685;
831 676 677 687 686; 833 677 678 688 687; 835 680 679 689 690;
836 679 681 691 689; 837 681 682 692 691; 838 682 683 693 692;
840 684 685 695 694; 841 685 686 696 695; 842 686 687 697 696;
844 687 688 698 697; 846 690 689 699 700; 847 689 691 701 699;
848 691 692 702 701; 849 692 693 703 702; 851 694 695 705 704;
852 695 696 706 705; 853 696 697 707 706; 855 697 698 708 707;
857 700 699 709 710; 858 699 701 711 709; 859 701 702 712 711;
860 702 703 713 712; 862 704 705 715 714; 863 705 706 716 715;
864 706 707 717 716; 866 707 708 718 717; 868 710 709 719 720;
869 709 711 721 719; 870 711 712 722 721; 871 712 713 723 722;
873 714 715 725 724; 874 715 716 726 725; 875 716 717 727 726;
877 717 718 728 727; 879 720 719 729 730; 880 719 721 731 729;
881 721 722 732 731; 882 722 723 733 732; 884 724 725 735 734;
885 725 726 736 735; 886 726 727 737 736; 888 727 728 738 737;
890 730 729 739 740; 891 729 731 741 739; 892 731 732 742 741;
893 732 733 743 742; 895 734 735 745 744; 896 735 736 746 745;
897 736 737 747 746; 899 737 738 748 747; 901 740 739 749 750;
902 739 741 751 749; 903 741 742 752 751; 904 742 743 753 752;
906 744 745 755 754; 907 745 746 756 755; 908 746 747 757 756;
910 747 748 758 757; 912 750 749 759 760; 913 749 751 761 759;
914 751 752 762 761; 915 752 753 763 762; 917 754 755 765 764;
918 755 756 766 765; 919 756 757 767 766; 921 757 758 768 767;
923 760 759 769 770; 924 759 761 771 769; 925 761 762 772 771;
926 762 763 773 772; 928 764 765 775 774; 929 765 766 776 775;
930 766 767 777 776; 932 767 768 778 777; 934 770 769 779 780;
935 769 771 781 779; 936 771 772 782 781; 937 772 773 783 782;
939 774 775 785 784; 940 775 776 786 785; 941 776 777 787 786;
943 777 778 788 787; 944 780 779 789 55; 945 779 781 790 789;
946 781 782 791 790; 947 782 783 792 791; 949 784 785 794 793;
950 785 786 795 794; 951 786 787 796 795; 952 787 788 57 796;
954 1 205 797 798; 955 205 206 799 797; 956 206 207 800 799;
957 207 208 801 800; 959 209 210 803 802; 960 210 211 804 803;
961 211 212 805 804; 963 212 6 806 805; 965 798 797 807 808;
966 797 799 809 807; 967 799 800 810 809; 968 800 801 811 810;
970 802 803 813 812; 971 803 804 814 813; 972 804 805 815 814;
974 805 806 816 815; 976 808 807 817 818; 977 807 809 819 817;
978 809 810 820 819; 979 810 811 821 820; 981 812 813 823 822;
982 813 814 824 823; 983 814 815 825 824; 985 815 816 826 825;
987 818 817 827 828; 988 817 819 829 827; 989 819 820 830 829;
990 820 821 831 830; 992 822 823 833 832; 993 823 824 834 833;
994 824 825 835 834; 996 825 826 836 835; 998 828 827 837 838;
999 827 829 839 837; 1000 829 830 840 839; 1001 830 831 841 840;
1003 832 833 843 842; 1004 833 834 844 843; 1005 834 835 845 844;
1007 835 836 846 845; 1008 838 837 847 37; 1009 837 839 848 847;
1010 839 840 849 848; 1011 840 841 850 849; 1013 842 843 852 851;
1014 843 844 853 852; 1015 844 845 854 853; 1016 845 846 42 854;
1018 6 855 856 806; 1020 855 857 858 856; 1022 857 859 860 858;
1024 859 861 862 860; 1028 863 865 866 864; 1030 865 867 868 866;
1032 867 869 870 868; 1034 869 11 871 870; 1035 806 856 872 816;
1036 856 858 873 872; 1037 858 860 874 873; 1038 860 862 875 874;
1040 864 866 877 876; 1041 866 868 878 877; 1042 868 870 879 878;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1044 870 871 880 879; 1045 816 872 881 826; 1046 872 873 882 881;
1047 873 874 883 882; 1048 874 875 884 883; 1050 876 877 886 885;
1051 877 878 887 886; 1052 878 879 888 887; 1054 879 880 889 888;
1055 826 881 890 836; 1056 881 882 891 890; 1057 882 883 892 891;
1058 883 884 893 892; 1060 885 886 895 894; 1061 886 887 896 895;
1062 887 888 897 896; 1064 888 889 898 897; 1065 836 890 899 846;
1066 890 891 900 899; 1067 891 892 901 900; 1068 892 893 902 901;
1070 894 895 904 903; 1071 895 896 905 904; 1072 896 897 906 905;
1074 897 898 907 906; 1075 846 899 908 42; 1076 899 900 909 908;
1077 900 901 910 909; 1078 901 902 911 910; 1080 903 904 913 912;
1081 904 905 914 913; 1082 905 906 915 914; 1083 906 907 47 915;
1085 11 916 917 871; 1087 916 918 919 917; 1089 918 920 921 919;
1091 920 922 923 921; 1095 924 926 927 925; 1097 926 928 929 927;
1099 928 930 931 929; 1101 930 12 932 931; 1102 871 917 933 880;
1103 917 919 934 933; 1104 919 921 935 934; 1105 921 923 936 935;
1107 925 927 938 937; 1108 927 929 939 938; 1109 929 931 940 939;
1111 931 932 941 940; 1112 880 933 942 889; 1113 933 934 943 942;
1114 934 935 944 943; 1115 935 936 945 944; 1117 937 938 947 946;
1118 938 939 948 947; 1119 939 940 949 948; 1121 940 941 950 949;
1122 889 942 951 898; 1123 942 943 952 951; 1124 943 944 953 952;
1125 944 945 954 953; 1127 946 947 956 955; 1128 947 948 957 956;
1129 948 949 958 957; 1131 949 950 959 958; 1132 898 951 960 907;
1133 951 952 961 960; 1134 952 953 962 961; 1135 953 954 963 962;
1137 955 956 965 964; 1138 956 957 966 965; 1139 957 958 967 966;
1141 958 959 968 967; 1142 907 960 969 47; 1143 960 961 970 969;
1144 961 962 971 970; 1145 962 963 972 971; 1147 964 965 974 973;
1148 965 966 975 974; 1149 966 967 976 975; 1150 967 968 48 976;
1151 12 497 977 932; 1152 497 498 978 977; 1153 498 499 979 978;
1154 499 500 980 979; 1156 501 502 982 981; 1157 502 503 983 982;
1158 503 504 984 983; 1160 504 13 985 984; 1161 932 977 986 941;
1162 977 978 987 986; 1163 978 979 988 987; 1164 979 980 989 988;
1166 981 982 991 990; 1167 982 983 992 991; 1168 983 984 993 992;
1170 984 985 994 993; 1171 941 986 995 950; 1172 986 987 996 995;
1173 987 988 997 996; 1174 988 989 998 997; 1176 990 991 1000 999;
1177 991 992 1001 1000; 1178 992 993 1002 1001; 1180 993 994 1003 1002;
1181 950 995 1004 959; 1182 995 996 1005 1004; 1183 996 997 1006 1005;
1184 997 998 1007 1006; 1186 999 1000 1009 1008; 1187 1000 1001 1010 1009;
1188 1001 1002 1011 1010; 1190 1002 1003 1012 1011; 1191 959 1004 1013 968;
1192 1004 1005 1014 1013; 1193 1005 1006 1015 1014; 1194 1006 1007 1016 1015;
1196 1008 1009 1018 1017; 1197 1009 1010 1019 1018; 1198 1010 1011 1020 1019;
1200 1011 1012 1021 1020; 1201 968 1013 1022 48; 1202 1013 1014 1023 1022;
1203 1014 1015 1024 1023; 1204 1015 1016 1025 1024; 1206 1017 1018 1027 1026;
1207 1018 1019 1028 1027; 1208 1019 1020 1029 1028; 1209 1020 1021 49 1029;
1211 13 1030 1031 985; 1213 1030 1032 1033 1031; 1215 1032 1034 1035 1033;
1217 1034 1036 1037 1035; 1221 1038 1040 1041 1039; 1223 1040 1042 1043 1041;
1225 1042 1044 1045 1043; 1227 1044 16 1046 1045; 1228 985 1031 1047 994;
1229 1031 1033 1048 1047; 1230 1033 1035 1049 1048; 1231 1035 1037 1050 1049;
1233 1039 1041 1052 1051; 1234 1041 1043 1053 1052; 1235 1043 1045 1054 1053;
1237 1045 1046 1055 1054; 1238 994 1047 1056 1003; 1239 1047 1048 1057 1056;
1240 1048 1049 1058 1057; 1241 1049 1050 1059 1058; 1243 1051 1052 1061 1060;
1244 1052 1053 1062 1061; 1245 1053 1054 1063 1062; 1247 1054 1055 1064 1063;
1248 1003 1056 1065 1012; 1249 1056 1057 1066 1065; 1250 1057 1058 1067 1066;
1251 1058 1059 1068 1067; 1253 1060 1061 1070 1069; 1254 1061 1062 1071 1070;
1255 1062 1063 1072 1071; 1257 1063 1064 1073 1072; 1258 1012 1065 1074 1021;
1259 1065 1066 1075 1074; 1260 1066 1067 1076 1075; 1261 1067 1068 1077 1076;
1263 1069 1070 1079 1078; 1264 1070 1071 1080 1079; 1265 1071 1072 1081 1080;
1267 1072 1073 1082 1081; 1268 1021 1074 1083 49; 1269 1074 1075 1084 1083;
1270 1075 1076 1085 1084; 1271 1076 1077 1086 1085; 1273 1078 1079 1088 1087;
1274 1079 1080 1089 1088; 1275 1080 1081 1090 1089; 1276 1081 1082 52 1090;
1278 16 1091 1092 1046; 1280 1091 1093 1094 1092; 1282 1093 1095 1096 1094;
1284 1095 1097 1098 1096; 1288 1099 1101 1102 1100; 1290 1101 1103 1104 1102;
1292 1103 1105 1106 1104; 1294 1105 17 1107 1106; 1295 1046 1092 1108 1055;
1296 1092 1094 1109 1108; 1297 1094 1096 1110 1109; 1298 1096 1098 1111 1110;
1300 1100 1102 1113 1112; 1301 1102 1104 1114 1113; 1302 1104 1106 1115 1114;
1304 1106 1107 1116 1115; 1305 1055 1108 1117 1064; 1306 1108 1109 1118 1117;
1307 1109 1110 1119 1118; 1308 1110 1111 1120 1119; 1310 1112 1113 1122 1121;
1311 1113 1114 1123 1122; 1312 1114 1115 1124 1123; 1314 1115 1116 1125 1124;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1315 1064 1117 1126 1073; 1316 1117 1118 1127 1126; 1317 1118 1119 1128 1127;
1318 1119 1120 1129 1128; 1320 1121 1122 1131 1130; 1321 1122 1123 1132 1131;
1322 1123 1124 1133 1132; 1324 1124 1125 1134 1133; 1325 1073 1126 1135 1082;
1326 1126 1127 1136 1135; 1327 1127 1128 1137 1136; 1328 1128 1129 1138 1137;
1330 1130 1131 1140 1139; 1331 1131 1132 1141 1140; 1332 1132 1133 1142 1141;
1334 1133 1134 1143 1142; 1335 1082 1135 1144 52; 1336 1135 1136 1145 1144;
1337 1136 1137 1146 1145; 1338 1137 1138 1147 1146; 1340 1139 1140 1149 1148;
1341 1140 1141 1150 1149; 1342 1141 1142 1151 1150; 1343 1142 1143 53 1151;
1345 17 1152 1153 1107; 1347 1152 1154 1155 1153; 1349 1154 1156 1157 1155;
1351 1156 1158 1159 1157; 1355 1160 1162 1163 1161; 1357 1162 1164 1165 1163;
1359 1164 1166 1167 1165; 1361 1166 18 1168 1167; 1362 1107 1153 1169 1116;
1363 1153 1155 1170 1169; 1364 1155 1157 1171 1170; 1365 1157 1159 1172 1171;
1367 1161 1163 1174 1173; 1368 1163 1165 1175 1174; 1369 1165 1167 1176 1175;
1371 1167 1168 1177 1176; 1372 1116 1169 1178 1125; 1373 1169 1170 1179 1178;
1374 1170 1171 1180 1179; 1375 1171 1172 1181 1180; 1377 1173 1174 1183 1182;
1378 1174 1175 1184 1183; 1379 1175 1176 1185 1184; 1381 1176 1177 1186 1185;
1382 1125 1178 1187 1134; 1383 1178 1179 1188 1187; 1384 1179 1180 1189 1188;
1385 1180 1181 1190 1189; 1387 1182 1183 1192 1191; 1388 1183 1184 1193 1192;
1389 1184 1185 1194 1193; 1391 1185 1186 1195 1194; 1392 1134 1187 1196 1143;
1393 1187 1188 1197 1196; 1394 1188 1189 1198 1197; 1395 1189 1190 1199 1198;
1397 1191 1192 1201 1200; 1398 1192 1193 1202 1201; 1399 1193 1194 1203 1202;
1401 1194 1195 1204 1203; 1402 1143 1196 1205 53; 1403 1196 1197 1206 1205;
1404 1197 1198 1207 1206; 1405 1198 1199 1208 1207; 1407 1200 1201 1210 1209;
1408 1201 1202 1211 1210; 1409 1202 1203 1212 1211; 1410 1203 1204 54 1212;
1412 1 1213 1214 798; 1414 1213 1215 1216 1214; 1416 1215 1217 1218 1216;
1418 1217 1219 1220 1218; 1422 1221 1223 1224 1222; 1424 1223 1225 1226 1224;
1426 1225 1227 1228 1226; 1428 1227 2 1229 1228; 1429 798 1214 1230 808;
1430 1214 1216 1231 1230; 1431 1216 1218 1232 1231; 1432 1218 1220 1233 1232;
1434 1222 1224 1235 1234; 1435 1224 1226 1236 1235; 1436 1226 1228 1237 1236;
1438 1228 1229 1238 1237; 1439 808 1230 1239 818; 1440 1230 1231 1240 1239;
1441 1231 1232 1241 1240; 1442 1232 1233 1242 1241; 1444 1234 1235 1244 1243;
1445 1235 1236 1245 1244; 1446 1236 1237 1246 1245; 1448 1237 1238 1247 1246;
1449 818 1239 1248 828; 1450 1239 1240 1249 1248; 1451 1240 1241 1250 1249;
1452 1241 1242 1251 1250; 1454 1243 1244 1253 1252; 1455 1244 1245 1254 1253;
1456 1245 1246 1255 1254; 1458 1246 1247 1256 1255; 1459 828 1248 1257 838;
1460 1248 1249 1258 1257; 1461 1249 1250 1259 1258; 1462 1250 1251 1260 1259;
1464 1252 1253 1262 1261; 1465 1253 1254 1263 1262; 1466 1254 1255 1264 1263;
1468 1255 1256 1265 1264; 1469 838 1257 1266 37; 1470 1257 1258 1267 1266;
1471 1258 1259 1268 1267; 1472 1259 1260 1269 1268; 1474 1261 1262 1271 1270;
1475 1262 1263 1272 1271; 1476 1263 1264 1273 1272; 1477 1264 1265 38 1273;
1478 2 351 1274 1229; 1479 351 352 1275 1274; 1480 352 353 1276 1275;
1481 353 354 1277 1276; 1483 355 356 1279 1278; 1484 356 357 1280 1279;
1485 357 358 1281 1280; 1487 358 3 1282 1281; 1488 1229 1274 1283 1238;
1489 1274 1275 1284 1283; 1490 1275 1276 1285 1284; 1491 1276 1277 1286 1285;
1493 1278 1279 1288 1287; 1494 1279 1280 1289 1288; 1495 1280 1281 1290 1289;
1497 1281 1282 1291 1290; 1498 1238 1283 1292 1247; 1499 1283 1284 1293 1292;
1500 1284 1285 1294 1293; 1501 1285 1286 1295 1294; 1503 1287 1288 1297 1296;
1504 1288 1289 1298 1297; 1505 1289 1290 1299 1298; 1507 1290 1291 1300 1299;
1508 1247 1292 1301 1256; 1509 1292 1293 1302 1301; 1510 1293 1294 1303 1302;
1511 1294 1295 1304 1303; 1513 1296 1297 1306 1305; 1514 1297 1298 1307 1306;
1515 1298 1299 1308 1307; 1517 1299 1300 1309 1308; 1518 1256 1301 1310 1265;
1519 1301 1302 1311 1310; 1520 1302 1303 1312 1311; 1521 1303 1304 1313 1312;
1523 1305 1306 1315 1314; 1524 1306 1307 1316 1315; 1525 1307 1308 1317 1316;
1527 1308 1309 1318 1317; 1528 1265 1310 1319 38; 1529 1310 1311 1320 1319;
1530 1311 1312 1321 1320; 1531 1312 1313 1322 1321; 1533 1314 1315 1324 1323;
1534 1315 1316 1325 1324; 1535 1316 1317 1326 1325; 1536 1317 1318 39 1326;
1538 3 1327 1328 1282; 1540 1327 1329 1330 1328; 1542 1329 1331 1332 1330;
1544 1331 1333 1334 1332; 1548 1335 1337 1338 1336; 1550 1337 1339 1340 1338;
1552 1339 1341 1342 1340; 1554 1341 4 1343 1342; 1555 1282 1328 1344 1291;
1556 1328 1330 1345 1344; 1557 1330 1332 1346 1345; 1558 1332 1334 1347 1346;
1560 1336 1338 1349 1348; 1561 1338 1340 1350 1349; 1562 1340 1342 1351 1350;
1564 1342 1343 1352 1351; 1565 1291 1344 1353 1300; 1566 1344 1345 1354 1353;
1567 1345 1346 1355 1354; 1568 1346 1347 1356 1355; 1570 1348 1349 1358 1357;
1571 1349 1350 1359 1358; 1572 1350 1351 1360 1359; 1574 1351 1352 1361 1360;
1575 1300 1353 1362 1309; 1576 1353 1354 1363 1362; 1577 1354 1355 1364 1363;
1578 1355 1356 1365 1364; 1580 1357 1358 1367 1366; 1581 1358 1359 1368 1367;
1582 1359 1360 1369 1368; 1584 1360 1361 1370 1369; 1585 1309 1362 1371 1318;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1586 1362 1363 1372 1371; 1587 1363 1364 1373 1372; 1588 1364 1365 1374 1373;
1590 1366 1367 1376 1375; 1591 1367 1368 1377 1376; 1592 1368 1369 1378 1377;
1594 1369 1370 1379 1378; 1595 1318 1371 1380 39; 1596 1371 1372 1381 1380;
1597 1372 1373 1382 1381; 1598 1373 1374 1383 1382; 1600 1375 1376 1385 1384;
1601 1376 1377 1386 1385; 1602 1377 1378 1387 1386; 1603 1378 1379 40 1387;
1605 4 1388 1389 1343; 1607 1388 1390 1391 1389; 1609 1390 1392 1393 1391;
1611 1392 1394 1395 1393; 1615 1396 1398 1399 1397; 1617 1398 1400 1401 1399;
1619 1400 1402 1403 1401; 1621 1402 5 1404 1403; 1622 1343 1389 1405 1352;
1623 1389 1391 1406 1405; 1624 1391 1393 1407 1406; 1625 1393 1395 1408 1407;
1627 1397 1399 1410 1409; 1628 1399 1401 1411 1410; 1629 1401 1403 1412 1411;
1631 1403 1404 1413 1412; 1632 1352 1405 1414 1361; 1633 1405 1406 1415 1414;
1634 1406 1407 1416 1415; 1635 1407 1408 1417 1416; 1637 1409 1410 1419 1418;
1638 1410 1411 1420 1419; 1639 1411 1412 1421 1420; 1641 1412 1413 1422 1421;
1642 1361 1414 1423 1370; 1643 1414 1415 1424 1423; 1644 1415 1416 1425 1424;
1645 1416 1417 1426 1425; 1647 1418 1419 1428 1427; 1648 1419 1420 1429 1428;
1649 1420 1421 1430 1429; 1651 1421 1422 1431 1430; 1652 1370 1423 1432 1379;
1653 1423 1424 1433 1432; 1654 1424 1425 1434 1433; 1655 1425 1426 1435 1434;
1657 1427 1428 1437 1436; 1658 1428 1429 1438 1437; 1659 1429 1430 1439 1438;
1661 1430 1431 1440 1439; 1662 1379 1432 1441 40; 1663 1432 1433 1442 1441;
1664 1433 1434 1443 1442; 1665 1434 1435 1444 1443; 1667 1436 1437 1446 1445;
1668 1437 1438 1447 1446; 1669 1438 1439 1448 1447; 1670 1439 1440 41 1448;
1671 5 643 1449 1404; 1672 643 644 1450 1449; 1673 644 645 1451 1450;
1674 645 646 1452 1451; 1676 647 648 1454 1453; 1677 648 649 1455 1454;
1678 649 650 1456 1455; 1680 650 10 1457 1456; 1681 1404 1449 1458 1413;
1682 1449 1450 1459 1458; 1683 1450 1451 1460 1459; 1684 1451 1452 1461 1460;
1686 1453 1454 1463 1462; 1687 1454 1455 1464 1463; 1688 1455 1456 1465 1464;
1690 1456 1457 1466 1465; 1691 1413 1458 1467 1422; 1692 1458 1459 1468 1467;
1693 1459 1460 1469 1468; 1694 1460 1461 1470 1469; 1696 1462 1463 1472 1471;
1697 1463 1464 1473 1472; 1698 1464 1465 1474 1473; 1700 1465 1466 1475 1474;
1701 1422 1467 1476 1431; 1702 1467 1468 1477 1476; 1703 1468 1469 1478 1477;
1704 1469 1470 1479 1478; 1706 1471 1472 1481 1480; 1707 1472 1473 1482 1481;
1708 1473 1474 1483 1482; 1710 1474 1475 1484 1483; 1711 1431 1476 1485 1440;
1712 1476 1477 1486 1485; 1713 1477 1478 1487 1486; 1714 1478 1479 1488 1487;
1716 1480 1481 1490 1489; 1717 1481 1482 1491 1490; 1718 1482 1483 1492 1491;
1720 1483 1484 1493 1492; 1721 1440 1485 1494 41; 1722 1485 1486 1495 1494;
1723 1486 1487 1496 1495; 1724 1487 1488 1497 1496; 1726 1489 1490 1499 1498;
1727 1490 1491 1500 1499; 1728 1491 1492 1501 1500; 1729 1492 1493 46 1501;
1731 10 1502 1503 1457; 1733 1502 1504 1505 1503; 1735 1504 1506 1507 1505;
1737 1506 1508 1509 1507; 1741 1510 1512 1513 1511; 1743 1512 1514 1515 1513;
1745 1514 1516 1517 1515; 1747 1516 15 1518 1517; 1748 1457 1503 1519 1466;
1749 1503 1505 1520 1519; 1750 1505 1507 1521 1520; 1751 1507 1509 1522 1521;
1753 1511 1513 1524 1523; 1754 1513 1515 1525 1524; 1755 1515 1517 1526 1525;
1757 1517 1518 1527 1526; 1758 1466 1519 1528 1475; 1759 1519 1520 1529 1528;
1760 1520 1521 1530 1529; 1761 1521 1522 1531 1530; 1763 1523 1524 1533 1532;
1764 1524 1525 1534 1533; 1765 1525 1526 1535 1534; 1767 1526 1527 1536 1535;
1768 1475 1528 1537 1484; 1769 1528 1529 1538 1537; 1770 1529 1530 1539 1538;
1771 1530 1531 1540 1539; 1773 1532 1533 1542 1541; 1774 1533 1534 1543 1542;
1775 1534 1535 1544 1543; 1777 1535 1536 1545 1544; 1778 1484 1537 1546 1493;
1779 1537 1538 1547 1546; 1780 1538 1539 1548 1547; 1781 1539 1540 1549 1548;
1783 1541 1542 1551 1550; 1784 1542 1543 1552 1551; 1785 1543 1544 1553 1552;
1787 1544 1545 1554 1553; 1788 1493 1546 1555 46; 1789 1546 1547 1556 1555;
1790 1547 1548 1557 1556; 1791 1548 1549 1558 1557; 1793 1550 1551 1560 1559;
1794 1551 1552 1561 1560; 1795 1552 1553 1562 1561; 1796 1553 1554 51 1562;
1798 15 1563 1564 1518; 1800 1563 1565 1566 1564; 1802 1565 1567 1568 1566;
1804 1567 1569 1570 1568; 1808 1571 1573 1574 1572; 1810 1573 1575 1576 1574;
1812 1575 1577 1578 1576; 1813 1577 18 1168 1578; 1814 1518 1564 1579 1527;
1815 1564 1566 1580 1579; 1816 1566 1568 1581 1580; 1817 1568 1570 1582 1581;
1819 1572 1574 1584 1583; 1820 1574 1576 1585 1584; 1821 1576 1578 1586 1585;
1822 1578 1168 1177 1586; 1823 1527 1579 1587 1536; 1824 1579 1580 1588 1587;
1825 1580 1581 1589 1588; 1826 1581 1582 1590 1589; 1828 1583 1584 1592 1591;
1829 1584 1585 1593 1592; 1830 1585 1586 1594 1593; 1831 1586 1177 1186 1594;
1832 1536 1587 1595 1545; 1833 1587 1588 1596 1595; 1834 1588 1589 1597 1596;
1835 1589 1590 1598 1597; 1837 1591 1592 1600 1599; 1838 1592 1593 1601 1600;
1839 1593 1594 1602 1601; 1840 1594 1186 1195 1602; 1841 1545 1595 1603 1554;
1842 1595 1596 1604 1603; 1843 1596 1597 1605 1604; 1844 1597 1598 1606 1605;
1846 1599 1600 1608 1607; 1847 1600 1601 1609 1608; 1848 1601 1602 1610 1609;
1849 1602 1195 1204 1610; 1850 1554 1603 1611 51; 1851 1603 1604 1612 1611;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1852 1604 1605 1613 1612; 1853 1605 1606 1614 1613; 1855 1607 1608 1616 1615;
1856 1608 1609 1617 1616; 1857 1609 1610 1618 1617; 1858 1610 1204 54 1618;
1860 59 1619 1620 1621; 1862 1619 1622 1623 1620; 1864 1622 1624 1625 1623;
1866 1624 1626 1627 1625; 1868 1626 1628 1629 1627; 1869 1628 55 789 1629;
1870 1621 1620 1630 1631; 1871 1620 1623 1632 1630; 1872 1623 1625 1633 1632;
1873 1625 1627 1634 1633; 1874 1627 1629 1635 1634; 1875 1629 789 790 1635;
1876 1631 1630 1636 1637; 1877 1630 1632 1638 1636; 1878 1632 1633 1639 1638;
1879 1633 1634 1640 1639; 1880 1634 1635 1641 1640; 1881 1635 790 791 1641;
1882 1637 1636 1642 1643; 1883 1636 1638 1644 1642; 1884 1638 1639 1645 1644;
1885 1639 1640 1646 1645; 1886 1640 1641 1647 1646; 1887 1641 791 792 1647;
1894 1649 1648 1654 1655; 1895 1648 1650 1656 1654; 1896 1650 1651 1657 1656;
1897 1651 1652 1658 1657; 1898 1652 1653 1659 1658; 1899 1653 793 794 1659;
1900 1655 1654 1660 1661; 1901 1654 1656 1662 1660; 1902 1656 1657 1663 1662;
1903 1657 1658 1664 1663; 1904 1658 1659 1665 1664; 1905 1659 794 795 1665;
1906 1661 1660 1666 1667; 1907 1660 1662 1668 1666; 1908 1662 1663 1669 1668;
1909 1663 1664 1670 1669; 1910 1664 1665 1671 1670; 1911 1665 795 796 1671;
1913 1667 1666 1672 60; 1915 1666 1668 1673 1672; 1917 1668 1669 1674 1673;
1919 1669 1670 1675 1674; 1921 1670 1671 1676 1675; 1922 1671 796 57 1676;
1938 74 1677 1678 75; 1939 1677 76 77 1678; 1940 75 1678 1679 89;
1941 1678 77 90 1679; 1942 89 1679 1680 99; 1943 1679 90 100 1680;
1944 99 1680 1681 109; 1945 1680 100 110 1681; 1946 109 1681 1682 119;
1947 1681 110 120 1682; 1948 119 1682 1683 129; 1949 1682 120 130 1683;
1950 129 1683 1684 139; 1951 1683 130 140 1684; 1952 139 1684 1685 149;
1953 1684 140 150 1685; 1954 149 1685 1686 159; 1955 1685 150 160 1686;
1956 159 1686 1687 169; 1957 1686 160 170 1687; 1958 169 1687 1688 179;
1959 1687 170 180 1688; 1960 179 1688 1689 189; 1961 1688 180 190 1689;
1962 189 1689 1690 199; 1963 1689 190 200 1690; 1965 199 1690 1691 208;
1966 1690 200 209 1691; 1968 220 1692 1693 221; 1969 1692 222 223 1693;
1970 221 1693 1694 235; 1971 1693 223 236 1694; 1972 235 1694 1695 245;
1973 1694 236 246 1695; 1974 245 1695 1696 255; 1975 1695 246 256 1696;
1976 255 1696 1697 265; 1977 1696 256 266 1697; 1978 265 1697 1698 275;
1979 1697 266 276 1698; 1980 275 1698 1699 285; 1981 1698 276 286 1699;
1982 285 1699 1700 295; 1983 1699 286 296 1700; 1984 295 1700 1701 305;
1985 1700 296 306 1701; 1986 305 1701 1702 315; 1987 1701 306 316 1702;
1988 315 1702 1703 325; 1989 1702 316 326 1703; 1990 325 1703 1704 335;
1991 1703 326 336 1704; 1992 335 1704 1705 345; 1993 1704 336 346 1705;
1995 345 1705 1706 354; 1996 1705 346 355 1706; 1998 366 1707 1708 367;
1999 1707 368 369 1708; 2000 367 1708 1709 381; 2001 1708 369 382 1709;
2002 381 1709 1710 391; 2003 1709 382 392 1710; 2004 391 1710 1711 401;
2005 1710 392 402 1711; 2006 401 1711 1712 411; 2007 1711 402 412 1712;
2008 411 1712 1713 421; 2009 1712 412 422 1713; 2010 421 1713 1714 431;
2011 1713 422 432 1714; 2012 431 1714 1715 441; 2013 1714 432 442 1715;
2014 441 1715 1716 451; 2015 1715 442 452 1716; 2016 451 1716 1717 461;
2017 1716 452 462 1717; 2018 461 1717 1718 471; 2019 1717 462 472 1718;
2020 471 1718 1719 481; 2021 1718 472 482 1719; 2022 481 1719 1720 491;
2023 1719 482 492 1720; 2025 491 1720 1721 500; 2026 1720 492 501 1721;
2028 512 1722 1723 513; 2029 1722 514 515 1723; 2030 513 1723 1724 527;
2031 1723 515 528 1724; 2032 527 1724 1725 537; 2033 1724 528 538 1725;
2034 537 1725 1726 547; 2035 1725 538 548 1726; 2036 547 1726 1727 557;
2037 1726 548 558 1727; 2038 557 1727 1728 567; 2039 1727 558 568 1728;
2040 567 1728 1729 577; 2041 1728 568 578 1729; 2042 577 1729 1730 587;
2043 1729 578 588 1730; 2044 587 1730 1731 597; 2045 1730 588 598 1731;
2046 597 1731 1732 607; 2047 1731 598 608 1732; 2048 607 1732 1733 617;
2049 1732 608 618 1733; 2050 617 1733 1734 627; 2051 1733 618 628 1734;
2052 627 1734 1735 637; 2053 1734 628 638 1735; 2055 637 1735 1736 646;
2056 1735 638 647 1736; 2058 658 1737 1738 659; 2059 1737 660 661 1738;
2060 659 1738 1739 673; 2061 1738 661 674 1739; 2062 673 1739 1740 683;
2063 1739 674 684 1740; 2064 683 1740 1741 693; 2065 1740 684 694 1741;
2066 693 1741 1742 703; 2067 1741 694 704 1742; 2068 703 1742 1743 713;
2069 1742 704 714 1743; 2070 713 1743 1744 723; 2071 1743 714 724 1744;
2072 723 1744 1745 733; 2073 1744 724 734 1745; 2074 733 1745 1746 743;
2075 1745 734 744 1746; 2076 743 1746 1747 753; 2077 1746 744 754 1747;
2078 753 1747 1748 763; 2079 1747 754 764 1748; 2080 763 1748 1749 773;
2081 1748 764 774 1749; 2082 773 1749 1750 783; 2083 1749 774 784 1750;
2084 783 1750 1751 792; 2085 1750 784 793 1751; 2086 208 1691 1752 801;
2087 1691 209 802 1752; 2088 801 1752 1753 811; 2089 1752 802 812 1753;
2090 811 1753 1754 821; 2091 1753 812 822 1754; 2092 821 1754 1755 831;

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

2093 1754 822 832 1755; 2094 831 1755 1756 841; 2095 1755 832 842 1756;
2096 841 1756 1757 850; 2097 1756 842 851 1757; 2099 861 1758 1759 862;
2100 1758 863 864 1759; 2101 862 1759 1760 875; 2102 1759 864 876 1760;
2103 875 1760 1761 884; 2104 1760 876 885 1761; 2105 884 1761 1762 893;
2106 1761 885 894 1762; 2107 893 1762 1763 902; 2108 1762 894 903 1763;
2109 902 1763 1764 911; 2110 1763 903 912 1764; 2112 922 1765 1766 923;
2113 1765 924 925 1766; 2114 923 1766 1767 936; 2115 1766 925 937 1767;
2116 936 1767 1768 945; 2117 1767 937 946 1768; 2118 945 1768 1769 954;
2119 1768 946 955 1769; 2120 954 1769 1770 963; 2121 1769 955 964 1770;
2122 963 1770 1771 972; 2123 1770 964 973 1771; 2124 500 1721 1772 980;
2125 1721 501 981 1772; 2126 980 1772 1773 989; 2127 1772 981 990 1773;
2128 989 1773 1774 998; 2129 1773 990 999 1774; 2130 998 1774 1775 1007;
2131 1774 999 1008 1775; 2132 1007 1775 1776 1016; 2133 1775 1008 1017 1776;
2134 1016 1776 1777 1025; 2135 1776 1017 1026 1777; 2137 1036 1778 1779 1037;
2138 1778 1038 1039 1779; 2139 1037 1779 1780 1050; 2140 1779 1039 1051 1780;
2141 1050 1780 1781 1059; 2142 1780 1051 1060 1781; 2143 1059 1781 1782 1068;
2144 1781 1060 1069 1782; 2145 1068 1782 1783 1077; 2146 1782 1069 1078 1783;
2147 1077 1783 1784 1086; 2148 1783 1078 1087 1784; 2150 1097 1785 1786 1098;
2151 1785 1099 1100 1786; 2152 1098 1786 1787 1111; 2153 1786 1100 1112 1787;
2154 1111 1787 1788 1120; 2155 1787 1112 1121 1788; 2156 1120 1788 1789 1129;
2157 1788 1121 1130 1789; 2158 1129 1789 1790 1138; 2159 1789 1130 1139 1790;
2160 1138 1790 1791 1147; 2161 1790 1139 1148 1791; 2164 1158 1792 1793 1159;
2165 1792 1160 1161 1793; 2166 1159 1793 1794 1172; 2167 1793 1161 1173 1794;
2168 1172 1794 1795 1181; 2169 1794 1173 1182 1795; 2170 1181 1795 1796 1190;
2171 1795 1182 1191 1796; 2172 1190 1796 1797 1199; 2173 1796 1191 1200 1797;
2174 1199 1797 1798 1208; 2175 1797 1200 1209 1798; 2177 1219 1799 1800 1220;
2178 1799 1221 1222 1800; 2179 1220 1800 1801 1233; 2180 1800 1222 1234 1801;
2181 1233 1801 1802 1242; 2182 1801 1234 1243 1802; 2183 1242 1802 1803 1251;
2184 1802 1243 1252 1803; 2185 1251 1803 1804 1260; 2186 1803 1252 1261 1804;
2187 1260 1804 1805 1269; 2188 1804 1261 1270 1805; 2189 354 1706 1806 1277;
2190 1706 355 1278 1806; 2191 1277 1806 1807 1286; 2192 1806 1278 1287 1807;
2193 1286 1807 1808 1295; 2194 1807 1287 1296 1808; 2195 1295 1808 1809 1304;
2196 1808 1296 1305 1809; 2197 1304 1809 1810 1313; 2198 1809 1305 1314 1810;
2199 1313 1810 1811 1322; 2200 1810 1314 1323 1811; 2202 1333 1812 1813 1334;
2203 1812 1335 1336 1813; 2204 1334 1813 1814 1347; 2205 1813 1336 1348 1814;
2206 1347 1814 1815 1356; 2207 1814 1348 1357 1815; 2208 1356 1815 1816 1365;
2209 1815 1357 1366 1816; 2210 1365 1816 1817 1374; 2211 1816 1366 1375 1817;
2212 1374 1817 1818 1383; 2213 1817 1375 1384 1818; 2215 1394 1819 1820 1395;
2216 1819 1396 1397 1820; 2217 1395 1820 1821 1408; 2218 1820 1397 1409 1821;
2219 1408 1821 1822 1417; 2220 1821 1409 1418 1822; 2221 1417 1822 1823 1426;
2222 1822 1418 1427 1823; 2223 1426 1823 1824 1435; 2224 1823 1427 1436 1824;
2225 1435 1824 1825 1444; 2226 1824 1436 1445 1825; 2227 646 1736 1826 1452;
2228 1736 647 1453 1826; 2229 1452 1826 1827 1461; 2230 1826 1453 1462 1827;
2231 1461 1827 1828 1470; 2232 1827 1462 1471 1828; 2233 1470 1828 1829 1479;
2234 1828 1471 1480 1829; 2235 1479 1829 1830 1488; 2236 1829 1480 1489 1830;
2237 1488 1830 1831 1497; 2238 1830 1489 1498 1831; 2240 1508 1832 1833 1509;
2241 1832 1510 1511 1833; 2242 1509 1833 1834 1522; 2243 1833 1511 1523 1834;
2244 1522 1834 1835 1531; 2245 1834 1523 1532 1835; 2246 1531 1835 1836 1540;
2247 1835 1532 1541 1836; 2248 1540 1836 1837 1549; 2249 1836 1541 1550 1837;
2250 1549 1837 1838 1558; 2251 1837 1550 1559 1838; 2253 1569 1839 1840 1570;
2254 1839 1571 1572 1840; 2255 1570 1840 1841 1582; 2256 1840 1572 1583 1841;
2257 1582 1841 1842 1590; 2258 1841 1583 1591 1842; 2259 1590 1842 1843 1598;
2260 1842 1591 1599 1843; 2261 1598 1843 1844 1606; 2262 1843 1599 1607 1844;
2263 1606 1844 1845 1614; 2264 1844 1607 1615 1845; 2265 792 1751 1846 1647;
2266 1751 793 1653 1846; 2267 1647 1846 1847 1646; 2268 1846 1653 1652 1847;
2269 1646 1847 1848 1645; 2270 1847 1652 1651 1848; 2271 1645 1848 1849 1644;
2272 1848 1651 1650 1849; 2273 1644 1849 1850 1642; 2274 1849 1650 1648 1850;
2275 1642 1850 1851 1643; 2276 1850 1648 1649 1851;
*******************************************************************************
START GROUP DEFINITION
MEMBER
_COL 1 TO 18 78 79 85 TO 90 122 138 140 149 151 160 162 171 173 182 184 193 -
195 204 206 215 217 226 228 237 239 248 250 259 261 270 290 306 308 317 319 -
328 330 339 341 350 352 361 363 372 374 383 385 394 396 405 407 416 418 427 -
429 438 458 474 476 485 487 496 498 507 509 518 520 529 531 540 542 551 553 -
562 564 573 575 584 586 595 597 606 626 642 644 653 655 664 666 675 677 686 -
688 697 699 708 710 719 721 730 732 741 743 752 754 763 765 774 794 810 812 -

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

821 823 832 834 843 845 854 856 865 867 876 878 887 889 898 900 909 911 920 -
922 931 933 942
_COL_N1 4 7 TO 9 11 14 TO 18
_COL_N1_MUROS 1 TO 3 5 6 10 12 13 78 79 122 138 140 149 151 160 162 171 173 -
182 184 193 195 204 206 215 217 226 228 237 239 248 250 259 261 270 290 306 -
308 317 319 328 330 339 341 350 352 361 363 372 374 383 385 394 396 405 407 -
416 418 427 429 438 458 474 476 485 487 496 498 507 509 518 520 529 531 540 -
542 551 553 562 564 573 575 584 586 595 597 606 626 642 644 653 655 664 666 -
675 677 686 688 697 699 708 710 719 721 730 732 741 743 752 754 763 765 774 -
794 810 812 821 823 832 834 843 845 854 856 865 867 876 878 887 889 898 900 -
909 911 920 922 931 933 942
_COL_N2 85 TO 90
_DADOS 19 TO 36 83 84 953 962 964 973 975 984 986 995 997 1006 1033 1043 1053 -
1063 1073 1100 1110 1120 1130 1140 1159 1169 1179 1189 1199 1226 1236 1246 -
1256 1266 1293 1303 1313 1323 1333 1360 1370 1380 1390 1400 1427 1437 1447 -
1457 1467 1486 1496 1506 1516 1526 1553 1563 1573 1583 1593 1620 1630 1640 -
1650 1660 1679 1689 1699 1709 1719 1746 1756 1766 1776 1786 1859 1861 1863 -
1865 1867 1912 1914 1916 1918 1920
_DADOS_DISEÑO 25 TO 27 32
_DADOS_MUROS 19 TO 24 28 TO 31 33 TO 36 83 84 953 962 964 973 975 984 986 -
995 997 1006 1033 1043 1053 1063 1073 1100 1110 1120 1130 1140 1159 1169 -
1179 1189 1199 1226 1236 1246 1256 1266 1293 1303 1313 1323 1333 1360 1370 -
1380 1390 1400 1427 1437 1447 1457 1467 1486 1496 1506 1516 1526 1553 1563 -
1573 1583 1593 1620 1630 1640 1650 1660 1679 1689 1699 1709 1719 1746 1756 -
1766 1776 1786 1859 1861 1863 1865 1867 1912 1914 1916 1918 1920
_CT 112 113 2404 TO 2407
_TRABES_SÓTANO 32 64 TO 77 272 274 276 278 280 282 284 286 440 442 444 446 -
448 450 452 454 608 610 612 614 616 618 620 622 776 778 780 782 784 786 788 -
790 1017 1019 1021 1023 1025 1027 1029 1031 1084 1086 1088 1090 1092 1094 -
1096 1098 1210 1212 1214 1216 1218 1220 1222 1224 1277 1279 1281 1283 1285 -
1287 1289 1291 1344 1346 1348 1350 1352 1354 1356 1358 1411 1413 1415 1417 -
1419 1421 1423 1425 1537 1539 1541 1543 1545 1547 1549 1551 1604 1606 1608 -
1610 1612 1614 1616 1618 1730 1732 1734 1736 1738 1740 1742 1744 1797 1799 -
1801 1803 1805 1807 1809 1811 1923 TO 1928 1930 TO 1936 1964 1994 2024 2054 -
2098 2111 2136 2149 2162 2176 2201 2214 2239 2252 2309 2311 TO 2321 2368 -
2369 TO 2370 2372 TO 2374 2376 TO 2380 2382 TO 2388 2392 2396 2397 2399 2408 -
2409 TO 2411 2418 TO 2421 2430 TO 2458 2460 TO 2482
_T_PER_S 64 TO 77 272 274 276 278 280 282 284 286 440 442 444 446 448 450 -
452 454 608 610 612 614 616 618 620 622 776 778 780 782 784 786 788 790 1017 -
1019 1021 1023 1025 1027 1029 1031 1084 1086 1088 1090 1092 1094 1096 1098 -
1210 1212 1214 1216 1218 1220 1222 1224 1277 1279 1281 1283 1285 1287 1289 -
1291 1344 1346 1348 1350 1352 1354 1356 1358 1411 1413 1415 1417 1419 1421 -
1423 1425 1537 1539 1541 1543 1545 1547 1549 1551 1604 1606 1608 1610 1612 -
1614 1616 1618 1730 1732 1734 1736 1738 1740 1742 1744 1797 1799 1801 1803 -
1805 1807 1809 1811 1964 1994 2024 2054 2098 2111 2136 2149 2162 2176 2201 -
2214 2239 2252 2438
_T_PRIN_SOT 1923 TO 1928 1930 TO 1936 2309 2311 TO 2321 2418 2430 2431 2433 -
2440 2446 2452 2455 2459 2470 2474 2477 2481
_T_SEC_SOT 2368 TO 2370 2372 TO 2374 2376 TO 2380 2382 TO 2388 2392 2396 2397 -
2399 2408 TO 2411 2419 TO 2421 2432 2434 TO 2437 2439 2441 TO 2445 -
2447 TO 2451 2453 2454 2456 TO 2458 2460 TO 2469 2471 TO 2473 2475 2476 2478 -
2479 TO 2480 2482
_TRABES_1N 37 TO 63 80 TO 82 121 124 126 128 130 132 134 136 289 292 294 296 -
298 300 302 304 457 460 462 464 466 468 470 472 625 628 630 632 634 636 638 -
640 793 796 798 800 802 804 806 808 1937 1967 1997 2027 2057 2277 TO 2301 -
2330 TO 2367 2412 TO 2417
_T_MUROS_1N 37 TO 40 45 TO 48 51 TO 53 62 63 80 81 121 124 126 128 130 132 -
134 136 289 292 294 296 298 300 302 304 457 460 462 464 466 468 470 472 625 -
628 630 632 634 636 638 640 793 796 798 800 802 804 806 808 1937 1967 1997 -
2027 2057 2277 TO 2279 2284 TO 2286 2289 2290 2299 2300
_T_PRIN_1N 41 TO 44 49 50 54 TO 61 82 2280 TO 2283 2287 2288 2291 TO 2298 2301
_T_SEC_1N 2330 TO 2367 2412 TO 2417
_T_DIS_1N 37 39 TO 45 47 TO 50 52 TO 61 63 81 82 2277 TO 2301
_T_PRIN_NA 91 TO 97 2302 TO 2308
_T_SEC_NA 2322 TO 2329
_REC_25 1 TO 18 25 TO 27 32 37 TO 82 85 TO 97 121 122 124 126 128 130 132 -
134 136 138 140 149 151 160 162 171 173 182 184 193 195 204 206 215 217 226 -

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

228 237 239 248 250 259 261 270 272 274 276 278 280 282 284 286 289 290 292 -
294 296 298 300 302 304 306 308 317 319 328 330 339 341 350 352 361 363 372 -
374 383 385 394 396 405 407 416 418 427 429 438 440 442 444 446 448 450 452 -
454 457 458 460 462 464 466 468 470 472 474 476 485 487 496 498 507 509 518 -
520 529 531 540 542 551 553 562 564 573 575 584 586 595 597 606 608 610 612 -
614 616 618 620 622 625 626 628 630 632 634 636 638 640 642 644 653 655 664 -
666 675 677 686 688 697 699 708 710 719 721 730 732 741 743 752 754 763 765 -
774 776 778 780 782 784 786 788 790 793 794 796 798 800 802 804 806 808 810 -
812 821 823 832 834 843 845 854 856 865 867 876 878 887 889 898 900 909 911 -
920 922 931 933 942 1017 1019 1021 1023 1025 1027 1029 1031 1084 1086 1088 -
1090 1092 1094 1096 1098 1210 1212 1214 1216 1218 1220 1222 1224 1277 1279 -
1281 1283 1285 1287 1289 1291 1344 1346 1348 1350 1352 1354 1356 1358 1411 -
1413 1415 1417 1419 1421 1423 1425 1537 1539 1541 1543 1545 1547 1549 1551 -
1604 1606 1608 1610 1612 1614 1616 1618 1730
_REC_25 1732 1734 1736 1738 1740 1742 1744 1797 1799 1801 1803 1805 1807 1809 -
1811 1923 TO 1928 1930 TO 1937 1964 1967 1994 1997 2024 2027 2054 2057 2098 -
2111 2136 2149 2162 2176 2201 2214 2239 2252 2277 TO 2309 2311 TO 2370 2372 -
2373 TO 2374 2376 TO 2380 2382 TO 2388 2392 2396 2397 2399 2408 TO 2421 2430 -
2431 TO 2482
_REC_50 19 TO 24 28 TO 31 33 TO 36 83 84 112 113 953 962 964 973 975 984 986 -
995 997 1006 1033 1043 1053 1063 1073 1100 1110 1120 1130 1140 1159 1169 -
1179 1189 1199 1226 1236 1246 1256 1266 1293 1303 1313 1323 1333 1360 1370 -
1380 1390 1400 1427 1437 1447 1457 1467 1486 1496 1506 1516 1526 1553 1563 -
1573 1583 1593 1620 1630 1640 1650 1660 1679 1689 1699 1709 1719 1746 1756 -
1766 1776 1786 1859 1861 1863 1865 1867 1912 1914 1916 1918 1920 -
2404 TO 2407
_DADOS_MUROS_D 22 29 33 TO 36 1033 1043 1053 1063 1073 1226 1236 1246 1256 -
1266 1293 1303 1313 1323 1333 1360 1370 1380 1390 1400 1553 1563 1573 1583 -
1593 1746 1756 1766 1776 1786
ELEMENT
_MC-1 123 125 127 129 133 135 137 139 141 TO 144 146 TO 148 150 152 TO 155 -
157 TO 159 161 163 TO 166 168 TO 170 172 174 TO 177 179 TO 181 183 -
185 TO 188 190 TO 192 194 196 TO 199 201 TO 203 205 207 TO 210 212 TO 214 -
216 218 TO 221 223 TO 225 227 231 232 234 TO 236 238 242 243 245 TO 247 249 -
253 254 256 TO 258 260 264 265 267 TO 269 271 277 279 283 285 287 288 1938 -
1939 TO 1963 1965 1966
_MC-1' 955 TO 957 959 TO 961 963 966 TO 968 970 TO 972 974 977 TO 979 981 -
982 TO 983 985 988 TO 990 992 TO 994 996 999 TO 1001 1003 TO 1005 1007 1018 -
1020 1022 1024 1028 1030 1032 1035 TO 1038 1040 TO 1042 1045 TO 1048 1050 -
1051 TO 1052 1055 TO 1058 1060 TO 1062 1065 TO 1068 1070 TO 1072 2086 TO 2095 -
2099 TO 2108
_MC-2 459 461 463 465 469 471 473 475 477 TO 480 482 TO 484 486 488 TO 491 -
493 TO 495 497 499 TO 502 504 TO 506 508 510 TO 513 515 TO 517 519 -
521 TO 524 526 TO 528 530 532 TO 535 537 TO 539 541 543 TO 546 548 TO 550 -
552 554 TO 557 559 TO 561 563 565 TO 568 570 TO 572 574 576 TO 579 -
581 TO 583 585 587 TO 590 592 TO 594 596 598 TO 601 603 TO 605 607 609 611 -
613 615 619 621 623 624 1998 TO 2023 2025 2026
_MC-2' 1087 1089 1091 1095 1097 1099 1101 1103 TO 1105 1107 TO 1109 1111 1113 -
1114 TO 1115 1117 TO 1119 1121 1123 TO 1125 1127 TO 1129 1131 1133 TO 1135 -
1137 TO 1139 1141 1151 TO 1154 1156 TO 1158 1161 TO 1164 1166 TO 1168 1171 -
1172 TO 1174 1176 TO 1178 1181 TO 1184 1186 TO 1188 1191 TO 1194 1196 TO 1198 -
2112 TO 2121 2124 TO 2133
_MC-3' 1213 1215 1217 1221 1223 1225 1229 TO 1231 1233 TO 1235 1239 TO 1241 -
1243 TO 1245 1249 TO 1251 1253 TO 1255 1259 TO 1261 1263 TO 1265 -
2137 TO 2146
_MC-4' 1280 1282 1284 1288 1290 1292 1294 1296 TO 1298 1300 TO 1302 1304 1306 -
1307 TO 1308 1310 TO 1312 1314 1316 TO 1318 1320 TO 1322 1324 1326 TO 1328 -
1330 TO 1332 1334 1345 1347 1349 1351 1355 1357 1359 1362 TO 1365 -
1367 TO 1369 1372 TO 1375 1377 TO 1379 1382 TO 1385 1387 TO 1389 -
1392 TO 1395 1397 TO 1399 2150 TO 2159 2164 TO 2173
_MC-5 627 629 631 633 637 639 641 643 645 TO 648 650 TO 652 654 656 TO 659 -
661 TO 663 665 667 TO 670 672 TO 674 676 678 TO 681 683 TO 685 687 -
689 TO 692 694 TO 696 698 700 TO 703 705 TO 707 709 711 TO 714 716 TO 718 -
720 722 TO 725 727 TO 729 731 733 TO 736 738 TO 740 742 744 TO 747 -
749 TO 751 753 755 TO 758 760 TO 762 764 766 TO 769 771 TO 773 775 777 779 -
781 783 787 789 791 792 2028 TO 2053 2055 2056
_MC-5' 1672 TO 1674 1676 TO 1678 1680 1682 TO 1684 1686 TO 1688 1690 1692 -

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xl
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1693 TO 1694 1696 TO 1698 1700 1702 TO 1704 1706 TO 1708 1710 1712 TO 1714 -
1716 TO 1718 1720 1731 1733 1735 1737 1741 1743 1745 1747 TO 1751 -
1753 TO 1755 1757 TO 1761 1763 TO 1765 1767 TO 1771 1773 TO 1775 -
1777 TO 1781 1783 TO 1785 1787 1798 1800 1802 1804 1808 1810 1812 -
1814 TO 1817 1819 TO 1821 1823 TO 1826 1828 TO 1830 1832 TO 1835 -
1837 TO 1839 1841 TO 1844 1846 TO 1848 2227 TO 2236 2240 TO 2249 -
2253 TO 2262
_MC-6 291 293 295 297 301 303 305 307 309 TO 312 314 TO 316 318 320 TO 323 -
325 TO 327 329 331 TO 334 336 TO 338 340 342 TO 345 347 TO 349 351 -
353 TO 356 358 TO 360 362 364 TO 367 369 TO 371 373 375 TO 378 380 TO 382 -
384 386 TO 389 391 TO 393 395 397 TO 400 402 TO 404 406 408 TO 411 -
413 TO 415 417 419 TO 422 424 TO 426 428 430 TO 433 435 TO 437 439 441 443 -
445 447 451 453 455 456 1968 TO 1993 1995 1996
_MC-6' 1414 1416 1418 1422 1424 1426 1428 1430 TO 1432 1434 TO 1436 1438 1440 -
1441 TO 1442 1444 TO 1446 1448 1450 TO 1452 1454 TO 1456 1458 1460 TO 1462 -
1464 TO 1466 1468 1478 TO 1481 1483 TO 1485 1487 TO 1491 1493 TO 1495 1497 -
1498 TO 1501 1503 TO 1505 1507 TO 1511 1513 TO 1515 1517 TO 1521 1523 TO 1525 -
1527 1538 1540 1542 1544 1548 1550 1552 1554 TO 1558 1560 TO 1562 -
1564 TO 1568 1570 TO 1572 1574 TO 1578 1580 TO 1582 1584 TO 1588 -
1590 TO 1592 1594 1605 1607 1609 1611 1615 1617 1619 1622 TO 1625 -
1627 TO 1629 1632 TO 1635 1637 TO 1639 1642 TO 1645 1647 TO 1649 -
1652 TO 1655 1657 TO 1659 2177 TO 2186 2189 TO 2198 2202 TO 2211 -
2215 TO 2224
_MC-7 795 797 799 801 805 807 809 811 813 TO 816 818 TO 820 822 824 TO 827 -
829 TO 831 833 835 TO 838 840 TO 842 844 846 TO 849 851 TO 853 855 -
857 TO 860 862 TO 864 866 868 TO 871 873 TO 875 877 879 TO 882 884 TO 886 -
888 890 TO 893 895 TO 897 899 901 TO 904 906 TO 908 910 912 TO 915 -
917 TO 919 921 923 TO 926 928 TO 930 932 934 TO 937 939 TO 941 943 TO 947 -
949 TO 952 2058 TO 2085
_MC-7' 1860 1862 1864 1866 1868 TO 1887 1894 TO 1911 1913 1915 1917 1919 1921 -
1922 2265 TO 2276
END GROUP DEFINITION
*******************************************************************************
ELEMENT PROPERTY
* MUROS DE CORTANTE
123 125 127 129 133 135 137 139 141 TO 144 146 TO 148 150 152 TO 155 -
157 TO 159 161 163 TO 166 168 TO 170 172 174 TO 177 179 TO 181 183 -
185 TO 188 190 TO 192 194 196 TO 199 201 TO 203 205 207 TO 210 212 TO 214 -
216 218 TO 221 223 TO 225 227 231 232 234 TO 236 238 242 243 245 TO 247 249 -
253 254 256 TO 258 260 264 265 267 TO 269 271 277 279 283 285 287 288 291 -
293 295 297 301 303 305 307 309 TO 312 314 TO 316 318 320 TO 323 325 TO 327 -
329 331 TO 334 336 TO 338 340 342 TO 345 347 TO 349 351 353 TO 356 -
358 TO 360 362 364 TO 367 369 TO 371 373 375 TO 378 380 TO 382 384 -
386 TO 389 391 TO 393 395 397 TO 400 402 TO 404 406 408 TO 411 413 TO 415 -
417 419 TO 422 424 TO 426 428 430 TO 433 435 TO 437 439 441 443 445 447 451 -
453 455 456 459 461 463 465 469 471 473 475 477 TO 480 482 TO 484 486 488 -
489 TO 491 493 TO 495 497 499 TO 502 504 TO 506 508 510 TO 513 515 TO 517 -
519 521 TO 524 526 TO 528 530 532 TO 535 537 TO 539 541 543 TO 546 -
548 TO 550 552 554 TO 557 559 TO 561 563 565 TO 568 570 TO 572 574 -
576 TO 579 581 TO 583 585 587 THICKNESS 0.25
588 TO 590 592 TO 594 596 598 TO 601 603 TO 605 607 609 611 613 615 619 621 -
623 624 627 629 631 633 637 639 641 643 645 TO 648 650 TO 652 654 -
656 TO 659 661 TO 663 665 667 TO 670 672 TO 674 676 678 TO 681 683 TO 685 -
687 689 TO 692 694 TO 696 698 700 TO 703 705 TO 707 709 711 TO 714 -
716 TO 718 720 722 TO 725 727 TO 729 731 733 TO 736 738 TO 740 742 -
744 TO 747 749 TO 751 753 755 TO 758 760 TO 762 764 766 TO 769 771 TO 773 -
775 777 779 781 783 787 789 791 792 795 797 799 801 805 807 809 811 -
813 TO 816 818 TO 820 822 824 TO 827 829 TO 831 833 835 TO 838 840 TO 842 -
844 846 TO 849 851 TO 853 855 857 TO 860 862 TO 864 866 868 TO 871 -
873 TO 875 877 879 TO 882 884 TO 886 888 890 TO 893 895 TO 897 899 -
901 TO 904 906 TO 908 910 912 TO 915 917 TO 919 921 923 TO 926 928 TO 930 -
932 934 TO 937 939 TO 941 943 TO 947 949 TO 952 1938 TO 1963 1965 1966 1968 -
1969 TO 1993 1995 1996 1998 TO 2023 2025 2026 2028 TO 2053 2055 2056 2058 -
2059 TO 2085 THICKNESS 0.25
* MUROS DE SÓTANO
954 TO 957 959 TO 961 963 965 TO 968 970 TO 972 974 976 TO 979 981 TO 983 -
985 987 TO 990 992 TO 994 996 998 TO 1001 1003 TO 1005 1007 TO 1011 1013 -

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xli
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1014 TO 1016 1018 1020 1022 1024 1028 1030 1032 1034 TO 1038 1040 TO 1042 -
1044 TO 1048 1050 TO 1052 1054 TO 1058 1060 TO 1062 1064 TO 1068 -
1070 TO 1072 1074 TO 1078 1080 TO 1083 1085 1087 1089 1091 1095 1097 1099 -
1101 TO 1105 1107 TO 1109 1111 TO 1115 1117 TO 1119 1121 TO 1125 -
1127 TO 1129 1131 TO 1135 1137 TO 1139 1141 TO 1145 1147 TO 1154 -
1156 TO 1158 1160 TO 1164 1166 TO 1168 1170 TO 1174 1176 TO 1178 -
1180 TO 1184 1186 TO 1188 1190 TO 1194 1196 TO 1198 1200 TO 1204 -
1206 TO 1209 1211 1213 1215 1217 1221 1223 1225 1227 TO 1231 1233 TO 1235 -
1237 TO 1241 1243 TO 1245 1247 TO 1251 1253 TO 1255 1257 TO 1261 -
1263 TO 1265 1267 TO 1271 1273 TO 1276 1278 1280 1282 1284 1288 1290 1292 -
1294 TO 1298 1300 TO 1302 1304 TO 1308 1310 TO 1312 1314 TO 1318 -
1320 TO 1322 1324 TO 1328 1330 TO 1332 1334 TO 1338 1340 TO 1343 1345 1347 -
1349 1351 1355 1357 1359 1361 TO 1365 1367 TO 1369 1371 TO 1375 1377 TO 1379 -
1381 TO 1385 1387 TO 1389 1391 TO 1395 1397 TO 1399 1401 TO 1405 -
1407 TO 1410 1412 1414 1416 1418 1422 1424 1426 1428 TO 1432 1434 TO 1436 -
1438 TO 1442 1444 TO 1446 1448 TO 1452 THICKNESS 0.3
1454 TO 1456 1458 TO 1462 1464 TO 1466 1468 TO 1472 1474 TO 1481 1483 TO 1485 -
1487 TO 1491 1493 TO 1495 1497 TO 1501 1503 TO 1505 1507 TO 1511 -
1513 TO 1515 1517 TO 1521 1523 TO 1525 1527 TO 1531 1533 TO 1536 1538 1540 -
1542 1544 1548 1550 1552 1554 TO 1558 1560 TO 1562 1564 TO 1568 1570 TO 1572 -
1574 TO 1578 1580 TO 1582 1584 TO 1588 1590 TO 1592 1594 TO 1598 -
1600 TO 1603 1605 1607 1609 1611 1615 1617 1619 1621 TO 1625 1627 TO 1629 -
1631 TO 1635 1637 TO 1639 1641 TO 1645 1647 TO 1649 1651 TO 1655 -
1657 TO 1659 1661 TO 1665 1667 TO 1674 1676 TO 1678 1680 TO 1684 -
1686 TO 1688 1690 TO 1694 1696 TO 1698 1700 TO 1704 1706 TO 1708 -
1710 TO 1714 1716 TO 1718 1720 TO 1724 1726 TO 1729 1731 1733 1735 1737 1741 -
1743 1745 1747 TO 1751 1753 TO 1755 1757 TO 1761 1763 TO 1765 1767 TO 1771 -
1773 TO 1775 1777 TO 1781 1783 TO 1785 1787 TO 1791 1793 TO 1796 1798 1800 -
1802 1804 1808 1810 1812 TO 1817 1819 TO 1826 1828 TO 1835 1837 TO 1844 1846 -
1847 TO 1853 1855 TO 1858 1860 1862 1864 1866 1868 TO 1887 1894 TO 1911 1913 -
1915 1917 1919 1921 1922 2086 TO 2097 2099 TO 2110 2112 TO 2135 2137 TO 2148 -
2150 TO 2161 2164 TO 2175 2177 TO 2200 2202 TO 2213 2215 TO 2238 -
2240 TO 2251 2253 TO 2276 THICKNESS 0.3
*******************************************************************************
DEFINE MATERIAL START
ISOTROPIC CONC_250
E 2.21359e+006
POISSON 0.17
DENSITY 2.4
ISOTROPIC CONC_250_S/P
E 2.21359e+006
POISSON 0.17
END DEFINE MATERIAL
*******************************************************************************
MEMBER PROPERTY AMERICAN
* COLUMNAS
1 TO 18 25 TO 27 32 78 79 85 TO 90 122 138 140 149 151 160 162 171 173 182 -
184 193 195 204 206 215 217 226 228 237 239 248 250 259 261 270 290 306 308 -
317 319 328 330 339 341 350 352 361 363 372 374 383 385 394 396 405 407 416 -
418 427 429 438 458 474 476 485 487 496 498 507 509 518 520 529 531 540 542 -
551 553 562 564 573 575 584 586 595 597 606 626 642 644 653 655 664 666 675 -
677 686 688 697 699 708 710 719 721 730 732 741 743 752 754 763 765 774 794 -
810 812 821 823 832 834 843 845 854 856 865 867 876 878 887 889 898 900 909 -
911 920 922 931 933 942 PRIS YD 0.6 ZD 0.6
* DADOS
19 TO 24 28 TO 31 33 TO 36 83 84 953 962 964 973 975 984 986 995 997 1006 -
1033 1043 1053 1063 1073 1100 1110 1120 1130 1140 1159 1169 1179 1189 1199 -
1226 1236 1246 1256 1266 1293 1303 1313 1323 1333 1360 1370 1380 1390 1400 -
1427 1437 1447 1457 1467 1486 1496 1506 1516 1526 1553 1563 1573 1583 1593 -
1620 1630 1640 1650 1660 1679 1689 1699 1709 1719 1746 1756 1766 1776 1786 -
1859 1861 1863 1865 1867 1912 1914 1916 1918 1920 PRIS YD 0.65 ZD 0.65
* CONTRATRABES
112 113 2404 TO 2407 PRIS YD 0.7 ZD 0.3
* TRABES QUE SÓLO SIRVEN PARA EL COMANDO FLOOR LOAD
64 TO 77 272 274 276 278 280 282 284 286 440 442 444 446 448 450 452 454 608 -
610 612 614 616 618 620 622 776 778 780 782 784 786 788 790 1017 1019 1021 -
1023 1025 1027 1029 1031 1084 1086 1088 1090 1092 1094 1096 1098 1210 1212 -

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xlii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1214 1216 1218 1220 1222 1224 1277 1279 1281 1283 1285 1287 1289 1291 1344 -
1346 1348 1350 1352 1354 1356 1358 1411 1413 1415 1417 1419 1421 1423 1425 -
1537 1539 1541 1543 1545 1547 1549 1551 1604 1606 1608 1610 1612 1614 1616 -
1618 1730 1732 1734 1736 1738 1740 1742 1744 1797 1799 1801 1803 1805 1807 -
1809 1811 1964 1994 2024 2054 2098 2111 2136 2149 2162 2176 2201 2214 2239 -
2252 2438 PRIS YD 0.1 ZD 0.1
* TRABES PRINCIPALES EN SÓTANO
1923 TO 1928 1930 TO 1936 2309 2311 TO 2321 2418 2430 2431 2433 2440 2446 -
2452 2455 2459 2470 2474 2477 2481 PRIS YD 0.6 ZD 0.3
* TRABES SECUNDARIAS EN SÓTANO
2368 TO 2370 2372 TO 2374 2376 TO 2380 2382 TO 2388 2392 2396 2397 2399 2408 -
2409 TO 2411 2419 TO 2421 2432 2434 TO 2437 2439 2441 TO 2445 2447 TO 2451 -
2453 2454 2456 TO 2458 2460 TO 2469 2471 TO 2473 2475 2476 2478 TO 2480 -
2482 PRIS YD 0.5 ZD 0.25
* TRAES PRINCIPALES ENTREPISO (ANCHO MAYOR POR MUROS DE CORTANTWE)
37 TO 40 45 TO 48 51 TO 53 62 63 80 81 121 124 126 128 130 132 134 136 289 -
292 294 296 298 300 302 304 457 460 462 464 466 468 470 472 625 628 630 632 -
634 636 638 640 793 796 798 800 802 804 806 808 1937 1967 1997 2027 2057 -
2277 TO 2279 2284 TO 2286 2289 2290 2299 2300 PRIS YD 0.7 ZD 0.35
* TRABES PRINCIPALES ENTREPISO
41 TO 44 49 50 54 TO 61 82 2280 TO 2283 2287 2288 2291 TO 2298 -
2301 PRIS YD 0.7 ZD 0.3
* TRABES SECUNDARIAS ENTREPISO
2330 TO 2367 2412 TO 2417 PRIS YD 0.5 ZD 0.25
* TRABES PRINCPALES AZOTEA
91 TO 97 2302 TO 2308 PRIS YD 0.7 ZD 0.3
* TRABES SECUNDARIAS AZOTEA
2322 TO 2329 PRIS YD 0.5 ZD 0.25
CONSTANTS
MATERIAL CONC_250 MEMB 1 TO 63 78 TO 97 112 113 121 TO 130 132 TO 144 146 -
147 TO 155 157 TO 166 168 TO 177 179 TO 188 190 TO 199 201 TO 210 212 TO 221 -
223 TO 228 231 232 234 TO 239 242 243 245 TO 250 253 254 256 TO 261 264 265 -
267 TO 271 277 279 283 285 287 TO 298 300 TO 312 314 TO 323 325 TO 334 336 -
337 TO 345 347 TO 356 358 TO 367 369 TO 378 380 TO 389 391 TO 400 402 TO 411 -
413 TO 422 424 TO 433 435 TO 439 441 443 445 447 451 453 455 TO 466 -
468 TO 480 482 TO 491 493 TO 502 504 TO 513 515 TO 524 526 TO 535 -
537 TO 546 548 TO 557 559 TO 568 570 TO 579 581 TO 590 592 TO 601 -
603 TO 607 609 611 613 615 619 621 623 TO 634 636 TO 648 650 TO 659 -
661 TO 670 672 TO 681 683 TO 692 694 TO 703 705 TO 714 716 TO 725 -
727 TO 736 738 TO 747 749 TO 758 760 TO 769 771 TO 775 777 779 781 783 787 -
789 791 TO 802 804 TO 816 818 TO 827 829 TO 838 840 TO 849 851 TO 860 862 -
863 TO 871 873 TO 882 884 TO 893 895 TO 904 906 TO 915 917 TO 926 928 TO 937 -
939 TO 947 949 TO 957 959 TO 968 970 TO 979 981 TO 990 992 TO 1001 -
1003 TO 1011 1013 TO 1016 1018 1020 1022 1024 1028 1030 1032 TO 1038 1040 -
1041
MATERIAL CONC_250 MEMB 1042 TO 1048 1050 TO 1058 1060 TO 1068 1070 TO 1078 -
1080 TO 1083 1085 1087 1089 1091 1095 1097 1099 TO 1105 1107 TO 1115 1117 -
1118 TO 1125 1127 TO 1135 1137 TO 1145 1147 TO 1154 1156 TO 1164 1166 TO 1174 -
1176 TO 1184 1186 TO 1194 1196 TO 1204 1206 TO 1209 1211 1213 1215 1217 1221 -
1223 1225 TO 1231 1233 TO 1241 1243 TO 1251 1253 TO 1261 1263 TO 1271 1273 -
1274 TO 1276 1278 1280 1282 1284 1288 1290 1292 TO 1298 1300 TO 1308 1310 -
1311 TO 1318 1320 TO 1328 1330 TO 1338 1340 TO 1343 1345 1347 1349 1351 1355 -
1357 1359 TO 1365 1367 TO 1375 1377 TO 1385 1387 TO 1395 1397 TO 1405 1407 -
1408 TO 1410 1412 1414 1416 1418 1422 1424 1426 TO 1432 1434 TO 1442 1444 -
1445 TO 1452 1454 TO 1462 1464 TO 1472 1474 TO 1481 1483 TO 1491 1493 TO 1501 -
1503 TO 1511 1513 TO 1521 1523 TO 1531 1533 TO 1536 1538 1540 1542 1544 1548 -
1550 1552 TO 1558 1560 TO 1568 1570 TO 1578 1580 TO 1588 1590 TO 1598 1600 -
1601 TO 1603 1605 1607 1609 1611 1615 1617 1619 TO 1625 1627 TO 1635 1637 -
1638 TO 1645 1647 TO 1655 1657 TO 1665 1667 TO 1674 1676 TO 1684 1686 TO 1694 -
1696 TO 1704 1706 TO 1714 1716 TO 1724 1726 TO 1729 1731 1733 1735 1737 1741 -
1743 1745 TO 1751 1753 TO 1761 1763 TO 1771 1773 TO 1781 1783 TO 1791 1793 -
1794 TO 1796 1798 1800 1802 1804 1808 1810 1812 TO 1817 1819 TO 1826 1828 -
1829 TO 1835 1837 TO 1844 1846
MATERIAL CONC_250 MEMB 1847 TO 1853 1855 TO 1887 1894 TO 1928 1930 TO 1963 -
1965 TO 1993 1995 TO 2023 2025 TO 2053 2055 TO 2097 2099 TO 2110 -
2112 TO 2135 2137 TO 2148 2150 TO 2161 2164 TO 2175 2177 TO 2200 -
2202 TO 2213 2215 TO 2238 2240 TO 2251 2253 TO 2309 2311 TO 2370 -

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xliii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

2372 TO 2374 2376 TO 2380 2382 TO 2388 2392 2396 2397 2399 2404 TO 2421 2430 -
2431 TO 2437 2439 TO 2482
MATERIAL CONC_250_S/P MEMB 64 TO 77 272 274 276 278 280 282 284 286 440 442 -
444 446 448 450 452 454 608 610 612 614 616 618 620 622 776 778 780 782 784 -
786 788 790 1017 1019 1021 1023 1025 1027 1029 1031 1084 1086 1088 1090 1092 -
1094 1096 1098 1210 1212 1214 1216 1218 1220 1222 1224 1277 1279 1281 1283 -
1285 1287 1289 1291 1344 1346 1348 1350 1352 1354 1356 1358 1411 1413 1415 -
1417 1419 1421 1423 1425 1537 1539 1541 1543 1545 1547 1549 1551 1604 1606 -
1608 1610 1612 1614 1616 1618 1730 1732 1734 1736 1738 1740 1742 1744 1797 -
1799 1801 1803 1805 1807 1809 1811 1964 1994 2024 2054 2098 2111 2136 2149 -
2162 2176 2201 2214 2239 2252 2438
*******************************************************************************
SUPPORTS
* SOPORTES EN COLUMNAS
37 41 47 49 52 TO 54 59 60 PINNED
* SOPORTES EN COLUMNAS DE SÓTANO
43 TO 45 50 FIXED BUT MY
* SOPORTE EN MUROS DE CONCRETO
42 46 51 847 TO 854 909 911 913 915 1083 TO 1090 1494 1497 1499 1500 1557 -
1560 1612 1613 1615 1616 1618 1784 FIXED BUT MX MY
39 48 969 971 973 975 1022 TO 1029 1144 TO 1146 1148 1149 1151 1205 1207 1208 -
1210 TO 1212 1266 1269 1272 1319 1322 1325 1381 1384 1387 1442 1445 1448 -
1621 1631 1637 1643 1649 1655 1661 1667 FIXED BUT MY MZ
* SOPORTE EN CONTRATRABES
1920 TO 1923 FIXED BUT FX FZ MX MY MZ KFY 6910.1
*******************************************************************************
*
* CARGAS BÁSICAS DE DISEÑO
*
*
LOAD 1 CARGA PERMANENTE (CM)
SELFWEIGHT Y -1
* CARGA DEBIDA A MUROS DE PRETIL
MEMBER LOAD
37 TO 40 45 49 51 TO 53 59 62 63 80 TO 82 91 TO 95 97 121 124 126 128 130 -
132 134 136 289 292 294 296 298 300 302 304 625 628 630 632 634 636 638 640 -
793 796 798 800 802 804 806 808 1937 1967 2027 2057 2277 TO 2279 2284 2287 -
2289 2290 2296 2299 TO 2306 2308 UNI GY -0.235
* CARGA DEBIDA A MUROS DE BLOCK
MEMBER LOAD
64 66 67 70 73 74 77 1017 1019 1021 1023 1025 1027 1029 1031 1277 1279 1281 -
1283 1285 1287 1289 1291 1411 1413 1415 1417 1419 1421 1423 1425 1537 1539 -
1541 1543 1545 1547 1549 1551 1604 1606 1608 1610 1612 1614 1616 1618 1730 -
1732 1734 1736 1738 1740 1742 1744 1797 1799 1801 1803 1805 1807 1809 1811 -
2098 2149 2176 2201 2214 2239 2252 UNI GY -1.827
112 113 2404 TO 2407 UNI GY -2.532
* CARGA DEBIDA A MUROS DE CORTAFUEGO
68 71 75 1084 1086 1088 1090 1092 1094 1096 1098 1210 1212 1214 1216 1218 -
1220 1222 1224 1344 1346 1348 1350 1352 1354 1356 1358 2111 2136 -
2162 UNI GY -3.119
* CARGA DEBIDA A MURO DE HVAC
42 43 46 47 55 61 457 460 462 464 466 468 470 472 1997 2281 2282 2285 2292 -
2298 UNI GY -1.07
FLOOR LOAD
* LOSA DE AZOTEA
YRANGE 11.45 11.45 FLOAD -0.597 GY
YRANGE 7.35 7.35 FLOAD -0.597 XRANGE 0 25 ZRANGE 0 7 GY
YRANGE 7.35 7.35 FLOAD -0.597 XRANGE 0 6.25 ZRANGE 7 14 GY
YRANGE 7.35 7.35 FLOAD -0.597 XRANGE 18.75 25 ZRANGE 7 14 GY
YRANGE 7.35 7.35 FLOAD -0.597 XRANGE 12.5 25 ZRANGE 14 28 GY
* LOSA DE ENTREPISO
YRANGE 7.35 7.35 FLOAD -0.852 XRANGE 6.25 18.75 ZRANGE 7 14 GY
* LOSA DE SÓTANO
YRANGE 0 0 FLOAD -0.5 GY
*MOMENTO DEBIDO A EMPUJE DE RELLENO EXTERIOR EN ZAPATA DE LINDERO
JOINT LOAD
37 MX 0.09975

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xliv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1266 MX 0.39615
1269 MX 0.5928
1272 MX 0.5928
1319 MX 0.5928
1322 MX 0.5928
1325 MX 0.4959
39 MX 0.399
1381 MX 0.4959
1384 MX 0.5928
1387 MX 0.5928
1442 MX 0.5928
1445 MX 0.5928
1448 MX 0.39615
41 MX 0.09975
*******************************************************************************
LOAD 2 CARGA VIVA MÁXIMA (CVM)
FLOOR LOAD
* LOSA DE AZOTEA
YRANGE 11.45 11.45 FLOAD -0.1 GY
YRANGE 7.35 7.35 FLOAD -0.1 XRANGE 0 25 ZRANGE 0 7 GY
YRANGE 7.35 7.35 FLOAD -0.1 XRANGE 0 6.25 ZRANGE 7 14 GY
YRANGE 7.35 7.35 FLOAD -0.1 XRANGE 18.75 25 ZRANGE 7 14 GY
YRANGE 7.35 7.35 FLOAD -0.1 XRANGE 12.5 25 ZRANGE 14 28 GY
* LOSA DE ENTREPISO
YRANGE 7.35 7.35 FLOAD -0.25 XRANGE 6.25 18.75 ZRANGE 7 14 GY
* LOSA DE SÓTANO
YRANGE 0 0 FLOAD -0.25 GY
*******************************************************************************
LOAD 3 CARGA VIVA INSTANTÁNEA (CVI)
FLOOR LOAD
* LOSA DE AZOTEA
YRANGE 11.45 11.45 FLOAD -0.07 GY
YRANGE 7.35 7.35 FLOAD -0.07 XRANGE 0 25 ZRANGE 0 7 GY
YRANGE 7.35 7.35 FLOAD -0.07 XRANGE 0 6.25 ZRANGE 7 14 GY
YRANGE 7.35 7.35 FLOAD -0.7 XRANGE 18.75 25 ZRANGE 7 14 GY
YRANGE 7.35 7.35 FLOAD -0.07 XRANGE 12.5 25 ZRANGE 14 28 GY
* LOSA DE ENTREPISO
YRANGE 7.35 7.35 FLOAD -0.18 XRANGE 6.25 18.75 ZRANGE 7 14 GY
* LOSA DE SÓTANO
YRANGE 0 0 FLOAD -0.18 GY
*******************************************************************************
LOAD 4 SISMO EN DIRECCIÓN SX1
JOINT LOAD
* AZOTEA
61 TO 63 FX 6.96
64 TO 66 FX 7.34
61 TO 63 FX 0.824
64 TO 66 FX -0.824
63 66 FZ 1.228
62 65 FZ -0.025
61 64 FZ -1.203
* ENTREPISO
19 TO 23 FX 9.74
24 TO 28 FX 1.15
29 TO 33 FX 9.86
34 TO 36 FX 0.76
56 58 FX 23.79
19 TO 23 FX 1.38
24 TO 28 FX 0.08
29 TO 33 FX -0.03
34 TO 36 FX -0.06
56 58 FX -3.51
23 28 33 36 58 FZ 1.26
22 27 32 35 56 FZ 0.07
21 26 31 34 FZ 0.01
20 25 30 FZ -0.06
24 29 67 FZ -2.18

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xlv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

* EMPUJE DEBIDO A SISMO


ELEMENT LOAD
965 TO 968 970 TO 972 974 1035 TO 1038 1040 TO 1042 1044 1228 TO 1231 1233 -
1234 TO 1235 1237 2088 2089 2101 2102 2139 -
2140 TRAP GX JT 1.28583 1.28583 2.57067 2.57067
976 TO 979 981 TO 983 985 1045 TO 1048 1050 TO 1052 1054 1238 TO 1241 1243 -
1244 TO 1245 1247 2090 2091 2103 2104 2141 -
2142 TRAP GX JT 2.57067 2.57067 3.8555 3.8555
987 TO 990 992 TO 994 996 1055 TO 1058 1060 TO 1062 1064 1248 TO 1251 1253 -
1254 TO 1255 1257 2092 2093 2105 2106 2143 -
2144 TRAP GX JT 3.8555 3.8555 5.14033 5.14033
998 TO 1001 1003 TO 1005 1007 1065 TO 1068 1070 TO 1072 1074 1258 TO 1261 -
1263 TO 1265 1267 2094 2095 2107 2108 2145 -
2146 TRAP GX JT 5.14033 5.14033 6.42518 6.42518
1008 TO 1011 1013 TO 1016 1075 TO 1078 1080 TO 1083 1268 TO 1271 1273 TO 1276 -
2096 2097 2109 2110 2147 2148 TRAP GX JT 6.42518 6.42518 7.71 7.71
954 TO 957 959 TO 961 963 1018 1020 1022 1024 1028 1030 1032 1034 1211 1213 -
1215 1217 1221 1223 1225 1227 2086 2087 2099 2100 2137 -
2138 TRAP GX JT 0.000999707 0.000999707 1.28583 1.28583
976 TO 979 981 TO 983 985 1045 TO 1048 1050 TO 1052 1054 1238 TO 1241 1243 -
1244 TO 1245 2090 2091 2103 2104 2141 2142 PR GX 0.88 0 0
*******************************************************************************
LOAD 5 SISMO EN DIRECCIÓN SX2
JOINT LOAD
* AZOTEA
61 TO 63 FX -6.96
64 TO 66 FX -7.34
61 TO 63 FX -0.824
64 TO 66 FX 0.824
63 66 FZ -1.228
62 65 FZ 0.025
61 64 FZ 1.203
* ENTREPISO
19 TO 23 FX -9.74
24 TO 28 FX -1.15
29 TO 33 FX -9.86
34 TO 36 FX -0.76
56 58 FX -23.79
19 TO 23 FX -1.38
24 TO 28 FX -0.08
29 TO 33 FX 0.03
34 TO 36 FX 0.06
56 58 FX 3.51
23 28 33 36 58 FZ -1.26
22 27 32 35 56 FZ -0.07
21 26 31 34 FZ -0.01
20 25 30 FZ 0.06
24 29 67 FZ 2.18
* EMPUJE DEBIDO A SISMO
ELEMENT LOAD
1681 TO 1684 1686 TO 1688 1690 1748 TO 1751 1753 TO 1755 1757 1814 TO 1817 -
1819 TO 1822 2229 2230 2242 2243 2255 -
2256 TRAP GX JT -1.28583 -1.28583 -2.57067 -2.57067
1691 TO 1694 1696 TO 1698 1700 1758 TO 1761 1763 TO 1765 1767 1823 TO 1826 -
1828 TO 1831 2231 2232 2244 2245 2257 -
2258 TRAP GX JT -2.57067 -2.57067 -3.8555 -3.8555
1701 TO 1704 1706 TO 1708 1710 1768 TO 1771 1773 TO 1775 1777 1832 TO 1835 -
1837 TO 1840 2233 2234 2246 2247 2259 -
2260 TRAP GX JT -3.8555 -3.8555 -5.14033 -5.14033
1711 TO 1714 1716 TO 1718 1720 1778 TO 1781 1783 TO 1785 1787 1841 TO 1844 -
1846 TO 1849 2235 2236 2248 2249 2261 -
2262 TRAP GX JT -5.14033 -5.14033 -6.42518 -6.42518
1721 TO 1724 1726 TO 1729 1788 TO 1791 1793 TO 1796 1850 TO 1853 1855 TO 1858 -
2237 2238 2250 2251 2263 2264 TRAP GX JT -6.42518 -6.42518 -7.71 -7.71
1671 TO 1674 1676 TO 1678 1680 1731 1733 1735 1737 1741 1743 1745 1747 1798 -
1800 1802 1804 1808 1810 1812 1813 2227 2228 2240 2241 2253 -
2254 TRAP GX JT -0.000999707 -0.000999707 -1.28583 -1.28583

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xlvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1691 TO 1694 1696 TO 1698 1700 1758 TO 1761 1763 TO 1765 1767 1823 TO 1826 -
1828 TO 1831 2231 2232 2244 2245 2257 2258 PR GX -0.88 0 0
*******************************************************************************
LOAD 6 SISMO EN DIRECCIÓN SX3
JOINT LOAD
* AZOTEA
61 TO 63 FX 6.96
64 TO 66 FX 7.34
61 TO 63 FX -0.995
64 TO 66 FX 0.995
63 66 FZ -1.484
62 65 FZ 0.03
61 64 FZ 1.454
* ENTREPISO
19 TO 23 FX 9.74
24 TO 28 FX 1.15
29 TO 33 FX 9.86
34 TO 36 FX 0.76
56 58 FX 23.79
19 TO 23 FX -3.36
24 TO 28 FX -0.19
29 TO 33 FX 0.06
34 TO 36 FX 0.14
56 58 FX 8.53
23 28 33 36 58 FZ -3.06
22 27 32 35 56 FZ -0.23
21 26 31 34 FZ -0.03
20 25 30 FZ 0.14
24 29 67 FZ 5.3
* EMPUJE DEBIDO A SISMO
ELEMENT LOAD
965 TO 968 970 TO 972 974 1035 TO 1038 1040 TO 1042 1044 1228 TO 1231 1233 -
1234 TO 1235 1237 2088 2089 2101 2102 2139 -
2140 TRAP GX JT 1.28583 1.28583 2.57067 2.57067
976 TO 979 981 TO 983 985 1045 TO 1048 1050 TO 1052 1054 1238 TO 1241 1243 -
1244 TO 1245 1247 2090 2091 2103 2104 2141 -
2142 TRAP GX JT 2.57067 2.57067 3.8555 3.8555
987 TO 990 992 TO 994 996 1055 TO 1058 1060 TO 1062 1064 1248 TO 1251 1253 -
1254 TO 1255 1257 2092 2093 2105 2106 2143 -
2144 TRAP GX JT 3.8555 3.8555 5.14033 5.14033
998 TO 1001 1003 TO 1005 1007 1065 TO 1068 1070 TO 1072 1074 1258 TO 1261 -
1263 TO 1265 1267 2094 2095 2107 2108 2145 -
2146 TRAP GX JT 5.14033 5.14033 6.42518 6.42518
1008 TO 1011 1013 TO 1016 1075 TO 1078 1080 TO 1083 1268 TO 1271 1273 TO 1276 -
2096 2097 2109 2110 2147 2148 TRAP GX JT 6.42518 6.42518 7.71 7.71
954 TO 957 959 TO 961 963 1018 1020 1022 1024 1028 1030 1032 1034 1211 1213 -
1215 1217 1221 1223 1225 1227 2086 2087 2099 2100 2137 -
2138 TRAP GX JT 0.000999707 0.000999707 1.28583 1.28583
976 TO 979 981 TO 983 985 1045 TO 1048 1050 TO 1052 1054 1238 TO 1241 1243 -
1244 TO 1245 2090 2091 2103 2104 2141 2142 PR GX 0.88 0 0
*******************************************************************************
LOAD 7 SISMO EN DIRECCIÓN SX4
JOINT LOAD
* AZOTEA
61 TO 63 FX -6.96
64 TO 66 FX -7.34
61 TO 63 FX 0.995
64 TO 66 FX -0.995
63 66 FZ 1.484
62 65 FZ -0.03
61 64 FZ -1.454
* ENTREPISO
19 TO 23 FX -9.74
24 TO 28 FX -1.15
29 TO 33 FX -9.86
34 TO 36 FX -0.76
56 58 FX -23.79

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xlvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

19 TO 23 FX 3.36
24 TO 28 FX 0.19
29 TO 33 FX -0.06
34 TO 36 FX -0.14
56 58 FX -8.53
23 28 33 36 58 FZ 3.06
22 27 32 35 56 FZ 0.23
21 26 31 34 FZ 0.03
20 25 30 FZ -0.14
24 29 67 FZ -5.3
* EMPUJE DEBIDO A SISMO
ELEMENT LOAD
1681 TO 1684 1686 TO 1688 1690 1748 TO 1751 1753 TO 1755 1757 1814 TO 1817 -
1819 TO 1822 2229 2230 2242 2243 2255 -
2256 TRAP GX JT -1.28583 -1.28583 -2.57067 -2.57067
1691 TO 1694 1696 TO 1698 1700 1758 TO 1761 1763 TO 1765 1767 1823 TO 1826 -
1828 TO 1831 2231 2232 2244 2245 2257 -
2258 TRAP GX JT -2.57067 -2.57067 -3.8555 -3.8555
1701 TO 1704 1706 TO 1708 1710 1768 TO 1771 1773 TO 1775 1777 1832 TO 1835 -
1837 TO 1840 2233 2234 2246 2247 2259 -
2260 TRAP GX JT -3.8555 -3.8555 -5.14033 -5.14033
1711 TO 1714 1716 TO 1718 1720 1778 TO 1781 1783 TO 1785 1787 1841 TO 1844 -
1846 TO 1849 2235 2236 2248 2249 2261 -
2262 TRAP GX JT -5.14033 -5.14033 -6.42518 -6.42518
1721 TO 1724 1726 TO 1729 1788 TO 1791 1793 TO 1796 1850 TO 1853 1855 TO 1858 -
2237 2238 2250 2251 2263 2264 TRAP GX JT -6.42518 -6.42518 -7.71 -7.71
1671 TO 1674 1676 TO 1678 1680 1731 1733 1735 1737 1741 1743 1745 1747 1798 -
1800 1802 1804 1808 1810 1812 1813 2227 2228 2240 2241 2253 -
2254 TRAP GX JT -0.000999707 -0.000999707 -1.28583 -1.28583
1691 TO 1694 1696 TO 1698 1700 1758 TO 1761 1763 TO 1765 1767 1823 TO 1826 -
1828 TO 1831 2231 2232 2244 2245 2257 2258 PR GX -0.88 0 0
*******************************************************************************
LOAD 8 SISMO EN DIRECCIÓN SZ1
JOINT LOAD
* AZOTEA
63 66 FZ 6.74
62 65 FZ 8.33
61 64 FZ 6.39
63 66 FZ 0.94
62 65 FZ -0.02
61 64 FZ -0.92
61 TO 63 FX 0.631
64 TO 66 FX -0.631
* ENTREPISO
23 28 33 36 58 FZ 12.04
22 27 32 35 56 FZ 1.3
21 26 31 34 FZ 1.24
20 25 30 FZ 1.55
19 24 29 FZ 25.77
23 28 33 36 58 FZ 3.56
22 27 32 35 56 FZ 0.21
21 26 31 34 FZ 0.03
20 25 30 FZ -0.16
19 24 29 FZ -6.16
19 TO 23 FX 3.91
24 TO 28 FX 0.23
29 TO 33 FX -0.08
34 TO 36 FX -0.16
56 58 FX -9.92
* EMPUJE DEBIDO A SISMO
ELEMENT LOAD
1429 TO 1432 1434 TO 1436 1438 1488 TO 1491 1493 TO 1495 1497 1555 TO 1558 -
1560 TO 1562 1564 1622 TO 1625 1627 TO 1629 1631 2179 2180 2191 2192 2204 -
2205 2217 2218 TRAP GZ JT 1.28583 1.28583 2.57067 2.57067
1439 TO 1442 1444 TO 1446 1448 1498 TO 1501 1503 TO 1505 1507 1565 TO 1568 -
1570 TO 1572 1574 1632 TO 1635 1637 TO 1639 1641 2181 2182 2193 2194 2206 -
2207 2219 2220 TRAP GZ JT 2.57067 2.57067 3.8555 3.8555

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xlviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1449 TO 1452 1454 TO 1456 1458 1508 TO 1511 1513 TO 1515 1517 1575 TO 1578 -
1580 TO 1582 1584 1642 TO 1645 1647 TO 1649 1651 2183 2184 2195 2196 2208 -
2209 2221 2222 TRAP GZ JT 3.8555 3.8555 5.14033 5.14033
1459 TO 1462 1464 TO 1466 1468 1518 TO 1521 1523 TO 1525 1527 1585 TO 1588 -
1590 TO 1592 1594 1652 TO 1655 1657 TO 1659 1661 2185 2186 2197 2198 2210 -
2211 2223 2224 TRAP GZ JT 5.14033 5.14033 6.42518 6.42518
1469 TO 1472 1474 TO 1477 1528 TO 1531 1533 TO 1536 1595 TO 1598 1600 TO 1603 -
1662 TO 1665 1667 TO 1670 2187 2188 2199 2200 2212 2213 2225 -
2226 TRAP GZ JT 6.42518 6.42518 7.71 7.71
1412 1414 1416 1418 1422 1424 1426 1428 1478 TO 1481 1483 TO 1485 1487 1538 -
1540 1542 1544 1548 1550 1552 1554 1605 1607 1609 1611 1615 1617 1619 1621 -
2177 2178 2189 2190 2202 2203 2215 -
2216 TRAP GZ JT 0.000999707 0.000999707 1.28583 1.28583
1439 TO 1442 1444 TO 1446 1448 1498 TO 1501 1503 TO 1505 1507 1565 TO 1568 -
1570 TO 1572 1574 1632 TO 1635 1637 TO 1639 1641 2181 2182 2193 2194 2206 -
2207 2219 2220 PR GZ 0.88 0 0
*******************************************************************************
LOAD 9 SISMO EN DIRECCIÓN SZ2
JOINT LOAD
* AZOTEA
63 66 FZ -6.74
62 65 FZ -8.33
61 64 FZ -6.39
63 66 FZ -0.94
62 65 FZ 0.02
61 64 FZ 0.92
61 TO 63 FX -0.631
64 TO 66 FX 0.631
* ENTREPISO
23 28 33 36 58 FZ -12.04
22 27 32 35 56 FZ -1.3
21 26 31 34 FZ -1.24
20 25 30 FZ -1.55
19 24 29 FZ -25.77
23 28 33 36 58 FZ -3.56
22 27 32 35 56 FZ -0.21
21 26 31 34 FZ -0.03
20 25 30 FZ 0.16
19 24 29 FZ 6.16
19 TO 23 FX -3.91
24 TO 28 FX -0.23
29 TO 33 FX 0.08
34 TO 36 FX 0.16
56 58 FX 9.92
* EMPUJE DEBIDO A SISMO
ELEMENT LOAD
1102 TO 1105 1107 TO 1109 1111 1161 TO 1164 1166 TO 1168 1170 1295 TO 1298 -
1300 TO 1302 1304 1362 TO 1365 1367 TO 1369 1371 2114 2115 2126 2127 2152 -
2153 2166 2167 TRAP GZ JT -1.28583 -1.28583 -2.57067 -2.57067
1112 TO 1115 1117 TO 1119 1121 1171 TO 1174 1176 TO 1178 1180 1305 TO 1308 -
1310 TO 1312 1314 1372 TO 1375 1377 TO 1379 1381 2116 2117 2128 2129 2154 -
2155 2168 2169 TRAP GZ JT -2.57067 -2.57067 -3.8555 -3.8555
1122 TO 1125 1127 TO 1129 1131 1181 TO 1184 1186 TO 1188 1190 1315 TO 1318 -
1320 TO 1322 1324 1382 TO 1385 1387 TO 1389 1391 2118 2119 2130 2131 2156 -
2157 2170 2171 TRAP GZ JT -3.8555 -3.8555 -5.14033 -5.14033
1132 TO 1135 1137 TO 1139 1141 1191 TO 1194 1196 TO 1198 1200 1325 TO 1328 -
1330 TO 1332 1334 1392 TO 1395 1397 TO 1399 1401 2120 2121 2132 2133 2158 -
2159 2172 2173 TRAP GZ JT -5.14033 -5.14033 -6.42518 -6.42518
1142 TO 1145 1147 TO 1150 1201 TO 1204 1206 TO 1209 1335 TO 1338 1340 TO 1343 -
1402 TO 1405 1407 TO 1410 2122 2123 2134 2135 2160 2161 2174 -
2175 TRAP GZ JT -6.42518 -6.42518 -7.71 -7.71
1085 1087 1089 1091 1095 1097 1099 1101 1151 TO 1154 1156 TO 1158 1160 1278 -
1280 1282 1284 1288 1290 1292 1294 1345 1347 1349 1351 1355 1357 1359 1361 -
2112 2113 2124 2125 2150 2151 2164 -
2165 TRAP GZ JT -0.000999707 -0.000999707 -1.28583 -1.28583
1112 TO 1115 1117 TO 1119 1121 1171 TO 1174 1176 TO 1178 1180 1305 TO 1308 -
1310 TO 1312 1314 1372 TO 1375 1377 TO 1379 1381 2116 2117 2128 2129 2154 -

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xlix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

2155 2168 2169 PR GZ -0.88 0 0


*******************************************************************************
LOAD 10 SISMO EN DIRECCIÓN SZ3
JOINT LOAD
* AZOTEA
63 66 FZ 6.74
62 65 FZ 8.33
61 64 FZ 6.39
63 66 FZ -0.66
62 65 FZ 0.01
61 64 FZ 0.65
61 TO 63 FX -0.444
64 TO 66 FX 0.444
* ENTREPISO
23 28 33 36 58 FZ 12.04
22 27 32 35 56 FZ 1.3
21 26 31 34 FZ 1.24
20 25 30 FZ 1.55
19 24 29 FZ 25.77
23 28 33 36 58 FZ -0.11
22 27 32 35 56 FZ -0.01
21 26 31 34 FZ -0.001
20 25 30 FZ 0.01
19 24 29 FZ 0.2
19 TO 23 FX -0.13
24 TO 28 FX -0.01
29 TO 33 FX 0.002
34 TO 36 FX 0.01
56 58 FX 0.32
* EMPUJE DEBIDO A SISMO
ELEMENT LOAD
1429 TO 1432 1434 TO 1436 1438 1488 TO 1491 1493 TO 1495 1497 1555 TO 1558 -
1560 TO 1562 1564 1622 TO 1625 1627 TO 1629 1631 2179 2180 2191 2192 2204 -
2205 2217 2218 TRAP GZ JT 1.28583 1.28583 2.57067 2.57067
1439 TO 1442 1444 TO 1446 1448 1498 TO 1501 1503 TO 1505 1507 1565 TO 1568 -
1570 TO 1572 1574 1632 TO 1635 1637 TO 1639 1641 2181 2182 2193 2194 2206 -
2207 2219 2220 TRAP GZ JT 2.57067 2.57067 3.8555 3.8555
1449 TO 1452 1454 TO 1456 1458 1508 TO 1511 1513 TO 1515 1517 1575 TO 1578 -
1580 TO 1582 1584 1642 TO 1645 1647 TO 1649 1651 2183 2184 2195 2196 2208 -
2209 2221 2222 TRAP GZ JT 3.8555 3.8555 5.14033 5.14033
1459 TO 1462 1464 TO 1466 1468 1518 TO 1521 1523 TO 1525 1527 1585 TO 1588 -
1590 TO 1592 1594 1652 TO 1655 1657 TO 1659 1661 2185 2186 2197 2198 2210 -
2211 2223 2224 TRAP GZ JT 5.14033 5.14033 6.42518 6.42518
1469 TO 1472 1474 TO 1477 1528 TO 1531 1533 TO 1536 1595 TO 1598 1600 TO 1603 -
1662 TO 1665 1667 TO 1670 2187 2188 2199 2200 2212 2213 2225 -
2226 TRAP GZ JT 6.42518 6.42518 7.71 7.71
1412 1414 1416 1418 1422 1424 1426 1428 1478 TO 1481 1483 TO 1485 1487 1538 -
1540 1542 1544 1548 1550 1552 1554 1605 1607 1609 1611 1615 1617 1619 1621 -
2177 2178 2189 2190 2202 2203 2215 -
2216 TRAP GZ JT 0.000999707 0.000999707 1.28583 1.28583
1439 TO 1442 1444 TO 1446 1448 1498 TO 1501 1503 TO 1505 1507 1565 TO 1568 -
1570 TO 1572 1574 1632 TO 1635 1637 TO 1639 1641 2181 2182 2193 2194 2206 -
2207 2219 2220 PR GZ 0.88 0 0
*******************************************************************************
LOAD 11 SISMO EN DIRECCIÓN SZ4
JOINT LOAD
* AZOTEA
63 66 FZ -6.74
62 65 FZ -8.33
61 64 FZ -6.39
63 66 FZ 0.66
62 65 FZ -0.01
61 64 FZ -0.65
61 TO 63 FX 0.444
64 TO 66 FX -0.444
* ENTREPISO
23 28 33 36 58 FZ -12.04

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco l
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

22 27 32 35 56 FZ -1.3
21 26 31 34 FZ -1.24
20 25 30 FZ -1.55
19 24 29 FZ -25.77
23 28 33 36 58 FZ 0.11
22 27 32 35 56 FZ 0.01
21 26 31 34 FZ 0.001
20 25 30 FZ -0.01
19 24 29 FZ -0.2
19 TO 23 FX 0.13
24 TO 28 FX 0.01
29 TO 33 FX -0.002
34 TO 36 FX -0.01
56 58 FX -0.32
* EMPUJE DEBIDO A SISMO
ELEMENT LOAD
1102 TO 1105 1107 TO 1109 1111 1161 TO 1164 1166 TO 1168 1170 1295 TO 1298 -
1300 TO 1302 1304 1362 TO 1365 1367 TO 1369 1371 2114 2115 2126 2127 2152 -
2153 2166 2167 TRAP GZ JT -1.28583 -1.28583 -2.57067 -2.57067
1112 TO 1115 1117 TO 1119 1121 1171 TO 1174 1176 TO 1178 1180 1305 TO 1308 -
1310 TO 1312 1314 1372 TO 1375 1377 TO 1379 1381 2116 2117 2128 2129 2154 -
2155 2168 2169 TRAP GZ JT -2.57067 -2.57067 -3.8555 -3.8555
1122 TO 1125 1127 TO 1129 1131 1181 TO 1184 1186 TO 1188 1190 1315 TO 1318 -
1320 TO 1322 1324 1382 TO 1385 1387 TO 1389 1391 2118 2119 2130 2131 2156 -
2157 2170 2171 TRAP GZ JT -3.8555 -3.8555 -5.14033 -5.14033
1132 TO 1135 1137 TO 1139 1141 1191 TO 1194 1196 TO 1198 1200 1325 TO 1328 -
1330 TO 1332 1334 1392 TO 1395 1397 TO 1399 1401 2120 2121 2132 2133 2158 -
2159 2172 2173 TRAP GZ JT -5.14033 -5.14033 -6.42518 -6.42518
1142 TO 1145 1147 TO 1150 1201 TO 1204 1206 TO 1209 1335 TO 1338 1340 TO 1343 -
1402 TO 1405 1407 TO 1410 2122 2123 2134 2135 2160 2161 2174 -
2175 TRAP GZ JT -6.42518 -6.42518 -7.71 -7.71
1085 1087 1089 1091 1095 1097 1099 1101 1151 TO 1154 1156 TO 1158 1160 1278 -
1280 1282 1284 1288 1290 1292 1294 1345 1347 1349 1351 1355 1357 1359 1361 -
2112 2113 2124 2125 2150 2151 2164 -
2165 TRAP GZ JT -0.000999707 -0.000999707 -1.28583 -1.28583
1112 TO 1115 1117 TO 1119 1121 1171 TO 1174 1176 TO 1178 1180 1305 TO 1308 -
1310 TO 1312 1314 1372 TO 1375 1377 TO 1379 1381 2116 2117 2128 2129 2154 -
2155 2168 2169 PR GZ -0.88 0 0
*******************************************************************************
LOAD 12 EMPUJE DE REPOSO X+
ELEMENT LOAD
965 TO 968 970 TO 972 974 1035 TO 1038 1040 TO 1042 1044 1228 TO 1231 1233 -
1234 TO 1235 1237 2088 2089 2101 2102 2139 -
2140 TRAP GX JT 1.25667 1.25667 1.76334 1.76334
976 TO 979 981 TO 983 985 1045 TO 1048 1050 TO 1052 1054 1238 TO 1241 1243 -
1244 TO 1245 1247 2090 2091 2103 2104 2141 -
2142 TRAP GX JT 1.76334 1.76334 2.27 2.27
987 TO 990 992 TO 994 996 1055 TO 1058 1060 TO 1062 1064 1248 TO 1251 1253 -
1254 TO 1255 1257 2092 2093 2105 2106 2143 -
2144 TRAP GX JT 2.27 2.27 2.77666 2.77666
998 TO 1001 1003 TO 1005 1007 1065 TO 1068 1070 TO 1072 1074 1258 TO 1261 -
1263 TO 1265 1267 2094 2095 2107 2108 2145 -
2146 TRAP GX JT 2.77666 2.77666 3.28334 3.28334
1008 TO 1011 1013 TO 1016 1075 TO 1078 1080 TO 1083 1268 TO 1271 1273 TO 1276 -
2096 2097 2109 2110 2147 2148 TRAP GX JT 3.28334 3.28334 3.79 3.79
954 TO 957 959 TO 961 963 1018 1020 1022 1024 1028 1030 1032 1034 1211 1213 -
1215 1217 1221 1223 1225 1227 2086 2087 2099 2100 2137 -
2138 TRAP GX JT 0.75 0.75 1.25667 1.25667
*******************************************************************************
LOAD 13 EMPUJE DE REPOSO X-
ELEMENT LOAD
1681 TO 1684 1686 TO 1688 1690 1748 TO 1751 1753 TO 1755 1757 1814 TO 1817 -
1819 TO 1822 2229 2230 2242 2243 2255 -
2256 TRAP GX JT -1.25667 -1.25667 -1.76334 -1.76334
1691 TO 1694 1696 TO 1698 1700 1758 TO 1761 1763 TO 1765 1767 1823 TO 1826 -
1828 TO 1831 2231 2232 2244 2245 2257 -
2258 TRAP GX JT -1.76334 -1.76334 -2.27 -2.27

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco li
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1701 TO 1704 1706 TO 1708 1710 1768 TO 1771 1773 TO 1775 1777 1832 TO 1835 -
1837 TO 1840 2233 2234 2246 2247 2259 -
2260 TRAP GX JT -2.27 -2.27 -2.77666 -2.77666
1711 TO 1714 1716 TO 1718 1720 1778 TO 1781 1783 TO 1785 1787 1841 TO 1844 -
1846 TO 1849 2235 2236 2248 2249 2261 -
2262 TRAP GX JT -2.77666 -2.77666 -3.28334 -3.28334
1721 TO 1724 1726 TO 1729 1788 TO 1791 1793 TO 1796 1850 TO 1853 1855 TO 1858 -
2237 2238 2250 2251 2263 2264 TRAP GX JT -3.28334 -3.28334 -3.79 -3.79
1671 TO 1674 1676 TO 1678 1680 1731 1733 1735 1737 1741 1743 1745 1747 1798 -
1800 1802 1804 1808 1810 1812 1813 2227 2228 2240 2241 2253 -
2254 TRAP GX JT -0.75 -0.75 -1.25667 -1.25667
*******************************************************************************
LOAD 14 EMPUJE DE REPOSO Z+
ELEMENT LOAD
1429 TO 1432 1434 TO 1436 1438 1488 TO 1491 1493 TO 1495 1497 1555 TO 1558 -
1560 TO 1562 1564 1622 TO 1625 1627 TO 1629 1631 2179 2180 2191 2192 2204 -
2205 2217 2218 TRAP GZ JT 1.25667 1.25667 1.76334 1.76334
1439 TO 1442 1444 TO 1446 1448 1498 TO 1501 1503 TO 1505 1507 1565 TO 1568 -
1570 TO 1572 1574 1632 TO 1635 1637 TO 1639 1641 2181 2182 2193 2194 2206 -
2207 2219 2220 TRAP GZ JT 1.76334 1.76334 2.27 2.27
1449 TO 1452 1454 TO 1456 1458 1508 TO 1511 1513 TO 1515 1517 1575 TO 1578 -
1580 TO 1582 1584 1642 TO 1645 1647 TO 1649 1651 2183 2184 2195 2196 2208 -
2209 2221 2222 TRAP GZ JT 2.27 2.27 2.77666 2.77666
1459 TO 1462 1464 TO 1466 1468 1518 TO 1521 1523 TO 1525 1527 1585 TO 1588 -
1590 TO 1592 1594 1652 TO 1655 1657 TO 1659 1661 2185 2186 2197 2198 2210 -
2211 2223 2224 TRAP GZ JT 2.77666 2.77666 3.28334 3.28334
1469 TO 1472 1474 TO 1477 1528 TO 1531 1533 TO 1536 1595 TO 1598 1600 TO 1603 -
1662 TO 1665 1667 TO 1670 2187 2188 2199 2200 2212 2213 2225 -
2226 TRAP GZ JT 3.28334 3.28334 3.79 3.79
1412 1414 1416 1418 1422 1424 1426 1428 1478 TO 1481 1483 TO 1485 1487 1538 -
1540 1542 1544 1548 1550 1552 1554 1605 1607 1609 1611 1615 1617 1619 1621 -
2177 2178 2189 2190 2202 2203 2215 -
2216 TRAP GZ JT 0.75 0.75 1.25667 1.25667
*******************************************************************************
LOAD 15 EMPUJE DE REPOSO Z-
ELEMENT LOAD
1102 TO 1105 1107 TO 1109 1111 1161 TO 1164 1166 TO 1168 1170 1295 TO 1298 -
1300 TO 1302 1304 1362 TO 1365 1367 TO 1369 1371 2114 2115 2126 2127 2152 -
2153 2166 2167 TRAP GZ JT -1.25667 -1.25667 -1.76334 -1.76334
1112 TO 1115 1117 TO 1119 1121 1171 TO 1174 1176 TO 1178 1180 1305 TO 1308 -
1310 TO 1312 1314 1372 TO 1375 1377 TO 1379 1381 2116 2117 2128 2129 2154 -
2155 2168 2169 TRAP GZ JT -1.76334 -1.76334 -2.27 -2.27
1122 TO 1125 1127 TO 1129 1131 1181 TO 1184 1186 TO 1188 1190 1315 TO 1318 -
1320 TO 1322 1324 1382 TO 1385 1387 TO 1389 1391 2118 2119 2130 2131 2156 -
2157 2170 2171 TRAP GZ JT -2.27 -2.27 -2.77666 -2.77666
1132 TO 1135 1137 TO 1139 1141 1191 TO 1194 1196 TO 1198 1200 1325 TO 1328 -
1330 TO 1332 1334 1392 TO 1395 1397 TO 1399 1401 2120 2121 2132 2133 2158 -
2159 2172 2173 TRAP GZ JT -2.77666 -2.77666 -3.28334 -3.28334
1142 TO 1145 1147 TO 1150 1201 TO 1204 1206 TO 1209 1335 TO 1338 1340 TO 1343 -
1402 TO 1405 1407 TO 1410 2122 2123 2134 2135 2160 2161 2174 -
2175 TRAP GZ JT -3.28334 -3.28334 -3.79 -3.79
1085 1087 1089 1091 1095 1097 1099 1101 1151 TO 1154 1156 TO 1158 1160 1278 -
1280 1282 1284 1288 1290 1292 1294 1345 1347 1349 1351 1355 1357 1359 1361 -
2112 2113 2124 2125 2150 2151 2164 -
2165 TRAP GZ JT -0.75 -0.75 -1.25667 -1.25667
*******************************************************************************
*
* *******************************************
* ** COMBINACIONES DE CARGA PARA DISEÑO **
* ** POR RESISTENCIA DE LA ESTRUCTURA **
* *******************************************
*
LOAD COMB 100 U = 1.5 (CP + CVM)
1 1.5 2 1.5
LOAD COMB 101 U = 1.5 (CP + CVM + E1 + E2 + E3 + E4)
1 1.5 2 1.5 12 1.5 13 1.5 14 1.5 15 1.5
*******************************************************************************

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

*
* COMBINACIONES DE CARGA CON EL 100% DEL SISMO EN X Y EL 30% EN Z
*
LOAD COMB 102 U = 1.1 (CP + CVI + SX1 + 0.30 SZ1 + E2 + E4)
1 1.1 3 1.1 4 1.1 8 0.33 13 1.1 15 1.1
LOAD COMB 103 U = 1.1 (CP + CVI + SX1 + 0.30 SZ2 + E2 + E5)
1 1.1 3 1.1 4 1.1 9 0.33 13 1.1 14 1.1
LOAD COMB 104 U = 1.1 (CP + CVI + SX1 + 0.30 SZ3 + E2 + E4)
1 1.1 3 1.1 4 1.1 10 0.33 13 1.1 15 1.1
LOAD COMB 105 U = 1.1 (CP + CVI + SX1 + 0.30 SZ4 + E2 + E5)
1 1.1 3 1.1 4 1.1 11 0.33 13 1.1 14 1.1
*******************************************************************************
LOAD COMB 106 U = 1.1 (CP + CVI + SX2 + 0.30 SZ1 + E1 + E4)
1 1.1 3 1.1 5 1.1 8 0.33 12 1.1 15 1.1
LOAD COMB 107 U = 1.1 (CP + CVI + SX2 + 0.30 SZ2 + E1 + E3)
1 1.1 3 1.1 5 1.1 9 0.33 12 1.1 14 1.1
LOAD COMB 108 U = 1.1 (CP + CVI + SX2 + 0.30 SZ3 + E1 + E4)
1 1.1 3 1.1 5 1.1 10 0.33 12 1.1 15 1.1
LOAD COMB 109 U = 1.1 (CP + CVI + SX2 + 0.30 SZ4 + E1 + E3)
1 1.1 3 1.1 5 1.1 11 0.33 12 1.1 14 1.1
*******************************************************************************
LOAD COMB 110 U = 1.1 (CP + CVI + SX3 + 0.30 SZ1 + E2 + E4)
1 1.1 3 1.1 6 1.1 8 0.33 13 1.1 15 1.1
LOAD COMB 111 U = 1.1 (CP + CVI + SX3 + 0.30 SZ2 + E2 + E3)
1 1.1 3 1.1 6 1.1 9 0.33 13 1.1 14 1.1
LOAD COMB 112 U = 1.1 (CP + CVI + SX3 + 0.30 SZ3 + E2 + E4)
1 1.1 3 1.1 6 1.1 10 0.33 13 1.1 15 1.1
LOAD COMB 113 U = 1.1 (CP + CVI + SX3 + 0.30 SZ4 + E2 + E3)
1 1.1 3 1.1 6 1.1 11 0.33 13 1.1 14 1.1
*******************************************************************************
LOAD COMB 114 U = 1.1 (CP + CVI + SX4 + 0.30 SZ1 + E1 + E4)
1 1.1 3 1.1 7 1.1 8 0.33 12 1.1 15 1.1
LOAD COMB 115 U = 1.1 (CP + CVI + SX4 + 0.30 SZ2 + E1 + E3)
1 1.1 3 1.1 7 1.1 9 0.33 12 1.1 14 1.1
LOAD COMB 116 U = 1.1 (CP + CVI + SX4 + 0.30 SZ3 + E1 + E4)
1 1.1 3 1.1 7 1.1 10 0.33 12 1.1 15 1.1
LOAD COMB 117 U = 1.1 (CP + CVI + SX4 + 0.30 SZ4 + E1 + E3)
1 1.1 3 1.1 7 1.1 11 0.33 12 1.1 14 1.1
*******************************************************************************
*
* COMBINACIONES DE CARGA CON EL 100% DEL SISMO EN Z Y EL 30% EN X
*
LOAD COMB 118 U = 1.1 (CP + CVI + SZ1 + 0.30 SX1 + E4 + E2)
1 1.1 3 1.1 8 1.1 4 0.33 15 1.1 13 1.1
LOAD COMB 119 U = 1.1 (CP + CVI + SZ1 + 0.30 SX2 + E4 + E1)
1 1.1 3 1.1 8 1.1 5 0.33 15 1.1 12 1.1
LOAD COMB 120 U = 1.1 (CP + CVI + SZ1 + 0.30 SX3 + E4 + E2)
1 1.1 3 1.1 8 1.1 6 0.33 15 1.1 13 1.1
LOAD COMB 121 U = 1.1 (CP + CVI + SZ1 + 0.30 SX4 + E4 + E1)
1 1.1 3 1.1 8 1.1 7 0.33 15 1.1 12 1.1
*******************************************************************************
LOAD COMB 122 U = 1.1 (CP + CVI + SZ2 + 0.30 SX1 + E3 + E2)
1 1.1 3 1.1 9 1.1 4 0.33 14 1.1 13 1.1
LOAD COMB 123 U = 1.1 (CP + CVI + SZ2 + 0.30 SX2 + E3 + E1)
1 1.1 3 1.1 9 1.1 5 0.33 14 1.1 12 1.1
LOAD COMB 124 U = 1.1 (CP + CVI + SZ2 + 0.30 SX3 + E3 + E2)
1 1.1 3 1.1 9 1.1 6 0.33 14 1.1 13 1.1
LOAD COMB 125 U = 1.1 (CP + CVI + SZ2 + 0.30 SX4 + E3 + E1)
1 1.1 3 1.1 9 1.1 7 0.33 14 1.1 12 1.1
*******************************************************************************
LOAD COMB 126 U = 1.1 (CP + CVI + SZ3 + 0.30 SX1 + E4 + E2)
1 1.1 3 1.1 10 1.1 4 0.33 15 1.1 13 1.1
LOAD COMB 127 U = 1.1 (CP + CVI + SZ3 + 0.30 SX2 + E4 + E1)
1 1.1 3 1.1 10 1.1 5 0.33 15 1.1 12 1.1
LOAD COMB 128 U = 1.1 (CP + CVI + SZ3 + 0.30 SX3 + E4 + E2)
1 1.1 3 1.1 10 1.1 6 0.33 15 1.1 13 1.1
LOAD COMB 129 U = 1.1 (CP + CVI + SZ3 + 0.30 SX4 + E4 + E1)

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco liii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

1 1.1 3 1.1 10 1.1 7 0.33 15 1.1 12 1.1


*******************************************************************************
LOAD COMB 130 U = 1.1 (CP + CVI + SZ4 + 0.30 SX1 + E3 + E2)
1 1.1 3 1.1 11 1.1 4 0.33 14 1.1 13 1.1
LOAD COMB 131 U = 1.1 (CP + CVI + SZ4 + 0.30 SX2 + E3 + E1)
1 1.1 3 1.1 11 1.1 5 0.33 14 1.1 12 1.1
LOAD COMB 132 U = 1.1 (CP + CVI + SZ4 + 0.30 SX3 + E3 + E2)
1 1.1 3 1.1 11 1.1 6 0.33 14 1.1 13 1.1
LOAD COMB 133 U = 1.1 (CP + CVI + SZ4 + 0.30 SX4 + E3 + E1)
1 1.1 3 1.1 11 1.1 7 0.33 14 1.1 12 1.1
*******************************************************************************
*
* ***********************************************
* ** COMBINACIONES DE CARGA PARA REVISISÓN **
* ** DE DESPLAZAMEINTOS Y CIMENTACIÓN **
* ***********************************************
*
* PARA LA REVISIÓN DE DESPLAZAMIENTOS SE DEBEN MULTIPLICAR LOS OBTENIDOS
* MEDIANTE EL ANÁLISIS DE ELEMENTO FINITO POR EL FACTOR DE REDUCCIÓN Q'
*
LOAD COMB 200 U = 1.0 (CP + CVM)
1 1.0 2 1.0
LOAD COMB 201 U = 1.0 (CP + CVM + E1 + E2 + E3 + E4)
1 1.0 2 1.0 12 1.0 13 1.0 14 1.0 15 1.0
*******************************************************************************
*
* COMBINACIONES DE CARGA CON EL 100% DEL SISMO EN X Y EL 30% EN Z
*
LOAD COMB 202 U = 1.0 (CP + CVI + SX1 + 0.30 SZ1 + E2 + E4)
1 1.0 3 1.0 4 1.0 8 0.3 13 1.0 15 1.0
LOAD COMB 203 U = 1.0 (CP + CVI + SX1 + 0.30 SZ2 + E2 + E3)
1 1.0 3 1.0 4 1.0 9 0.3 13 1.0 14 1.0
LOAD COMB 204 U = 1.0 (CP + CVI + SX1 + 0.30 SZ3 + E2 + E4)
1 1.0 3 1.0 4 1.0 10 0.3 13 1.0 15 1.0
LOAD COMB 205 U = 1.0 (CP + CVI + SX1 + 0.30 SZ4 + E2 + E3)
1 1.0 3 1.0 4 1.0 11 0.3 13 1.0 14 1.0
*******************************************************************************
LOAD COMB 206 U = 1.0 (CP + CVI + SX2 + 0.30 SZ1 + E1 + E4)
1 1.0 3 1.0 5 1.0 8 0.3 12 1.0 15 1.0
LOAD COMB 207 U = 1.0 (CP + CVI + SX2 + 0.30 SZ2 + E1 + E3)
1 1.0 3 1.0 5 1.0 9 0.3 12 1.0 14 1.0
LOAD COMB 208 U = 1.0 (CP + CVI + SX2 + 0.30 SZ3 + E1 + E4)
1 1.0 3 1.0 5 1.0 10 0.3 12 1.0 15 1.0
LOAD COMB 209 U = 1.0 (CP + CVI + SX2 + 0.30 SZ4 + E1 + E3)
1 1.0 3 1.0 5 1.0 11 0.3 12 1.0 14 1.0
*******************************************************************************
LOAD COMB 210 U = 1.0 (CP + CVI + SX3 + 0.30 SZ1 + E2 + E4)
1 1.0 3 1.0 6 1.0 8 0.3 13 1.0 15 1.0
LOAD COMB 211 U = 1.0 (CP + CVI + SX3 + 0.30 SZ2 + E2 + E3)
1 1.0 3 1.0 6 1.0 9 0.3 13 1.0 14 1.0
LOAD COMB 212 U = 1.0 (CP + CVI + SX3 + 0.30 SZ3 + E2 + E4)
1 1.0 3 1.0 6 1.0 10 0.3 13 1.0 15 1.0
LOAD COMB 213 U = 1.0 (CP + CVI + SX3 + 0.30 SZ4 + E2 + E3)
1 1.0 3 1.0 6 1.0 11 0.3 13 1.0 14 1.0
*******************************************************************************
LOAD COMB 214 U = 1.0 (CP + CVI + SX4 + 0.30 SZ1 + E1 + E4)
1 1.0 3 1.0 7 1.0 8 0.3 12 1.0 15 1.0
LOAD COMB 215 U = 1.0 (CP + CVI + SX4 + 0.30 SZ2 + E1 + E3)
1 1.0 3 1.0 7 1.0 9 0.3 12 1.0 14 1.0
LOAD COMB 216 U = 1.0 (CP + CVI + SX4 + 0.30 SZ3 + E1 + E4)
1 1.0 3 1.0 7 1.0 10 0.3 12 1.0 15 1.0
LOAD COMB 217 U = 1.0 (CP + CVI + SX4 + 0.30 SZ4 + E1 + E3)
1 1.0 3 1.0 7 1.0 11 0.3 12 1.0 14 1.0
*******************************************************************************
*
* COMBINACIONES DE CARGA CON EL 100% DEL SISMO EN Z Y EL 30% EN X
*

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco liv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

LOAD COMB 218 U = 1.0 (CP + CVI + SZ1 + 0.30 SX1 + E4 + E2)
1 1.0 3 1.0 8 1.0 4 0.3 15 1.0 13 1.0
LOAD COMB 219 U = 1.0 (CP + CVI + SZ1 + 0.30 SX2 + E4 + E1)
1 1.0 3 1.0 8 1.0 5 0.3 15 1.0 12 1.0
LOAD COMB 220 U = 1.0 (CP + CVI + SZ1 + 0.30 SX3 + E4 + E2)
1 1.0 3 1.0 8 1.0 6 0.3 15 1.0 13 1.0
LOAD COMB 221 U = 1.0 (CP + CVI + SZ1 + 0.30 SX4 + E4 + E1)
1 1.0 3 1.0 8 1.0 7 0.3 15 1.0 12 1.0
*******************************************************************************
LOAD COMB 222 U = 1.0 (CP + CVI + SZ2 + 0.30 SX1 + E3 + E2)
1 1.0 3 1.0 9 1.0 4 0.3 14 1.0 13 1.0
LOAD COMB 223 U = 1.0 (CP + CVI + SZ2 + 0.30 SX2 + E3 + E1)
1 1.0 3 1.0 9 1.0 5 0.3 14 1.0 12 1.0
LOAD COMB 224 U = 1.0 (CP + CVI + SZ2 + 0.30 SX3 + E3 + E2)
1 1.0 3 1.0 9 1.0 6 0.3 14 1.0 13 1.0
LOAD COMB 225 U = 1.0 (CP + CVI + SZ2 + 0.30 SX4 + E3 + E1)
1 1.0 3 1.0 9 1.0 7 0.3 14 1.0 12 1.0
*******************************************************************************
LOAD COMB 226 U = 1.0 (CP + CVI + SZ3 + 0.30 SX1 + E4 + E2)
1 1.0 3 1.0 10 1.0 4 0.3 15 1.0 13 1.0
LOAD COMB 227 U = 1.0 (CP + CVI + SZ3 + 0.30 SX2 + E4 + E1)
1 1.0 3 1.0 10 1.0 5 0.3 15 1.0 12 1.0
LOAD COMB 228 U = 1.0 (CP + CVI + SZ3 + 0.30 SX3 + E4 + E2)
1 1.0 3 1.0 10 1.0 6 0.3 15 1.0 13 1.0
LOAD COMB 229 U = 1.0 (CP + CVI + SZ3 + 0.30 SX4 + E4 + E1)
1 1.0 3 1.0 10 1.0 7 0.3 15 1.0 12 1.0
*******************************************************************************
LOAD COMB 230 U = 1.0 (CP + CVI + SZ4 + 0.30 SX1 + E3 + E2)
1 1.0 3 1.0 11 1.0 4 0.3 14 1.0 13 1.0
LOAD COMB 231 U = 1.0 (CP + CVI + SZ4 + 0.30 SX2 + E3 + E1)
1 1.0 3 1.0 11 1.0 5 0.3 14 1.0 12 1.0
LOAD COMB 232 U = 1.0 (CP + CVI + SZ4 + 0.30 SX3 + E3 + E2)
1 1.0 3 1.0 11 1.0 6 0.3 14 1.0 13 1.0
LOAD COMB 233 U = 1.0 (CP + CVI + SZ4 + 0.30 SX4 + E3 + E1)
1 1.0 3 1.0 11 1.0 7 0.3 14 1.0 12 1.0
*******************************************************************************
PERFORM ANALYSIS
LOAD LIST 100 TO 133
START CONCRETE DESIGN
CODE ACI
*
CLB 0.025 MEMB _REC_25
CLB 0.05 MEMB _REC_50
*
CLT 0.025 MEMB _REC_25
CLT 0.05 MEMB _REC_50
*
CLS 0.025 MEMB _COL
CLS 0.05 MEMB _DADOS
*
FC 2500 ALL
FYMAIN 42000 ALL
FYSEC 42000 ALL
*
MAXMAIN 25 ALL
MINMAIN 10 ALL
MINSEC 10 ALL
*
* DISEÑO DE COLUMNAS
DESIGN COLUMN _COL_N1
DESIGN COLUMN _COL_N2
* DISEÑO DE DADOS
DESIGN COLUMN _DADOS_DISEÑO
DESIGN COLUMN _DADOS_MUROS_D
* DISEÑO DE CONTRATRABES
DESIGN BEAM _CT
* DISEÑO DE TRABES PRINCIPALES

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

DESIGN BEAM _T_DIS_1N


DESIGN BEAM _T_PRIN_NA
* DISEÑO DE TRABES SECUNDARIAS
DESIGN BEAM _T_SEC_1N
DESIGN BEAM _T_SEC_NA
* DISEÑO DE TRABES DE SÓTANO
DESIGN BEAM _T_PRIN_SOT
DESIGN BEAM _T_SEC_SOT
*
END CONCRETE DESIGN
FINISH

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

ANEXO 2: Reusltado de diseño.

STAAD SPACE -- PAGE NO. 46

====================================================================

COLUMN NO. 4 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 7 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 8 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 47

====================================================================

COLUMN NO. 9 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 11 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 14 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 48

====================================================================

COLUMN NO. 15 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 16 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 17 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 49

====================================================================

COLUMN NO. 18 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

********************END OF COLUMN DESIGN RESULTS********************

2404. DESIGN COLUMN _COL_N2

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 50

====================================================================

COLUMN NO. 85 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


AREA OF STEEL REQUIRED = 4104.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.257 133 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 86 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


AREA OF STEEL REQUIRED = 4608.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

24 - 16 MM 1.340 105 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 87 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


AREA OF STEEL REQUIRED = 4104.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.257 122 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 51

====================================================================

COLUMN NO. 88 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


AREA OF STEEL REQUIRED = 4608.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

24 - 16 MM 1.340 112 STA 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 89 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


AREA OF STEEL REQUIRED = 5112.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

28 - 16 MM 1.564 114 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 90 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


AREA OF STEEL REQUIRED = 4104.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.257 118 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

********************END OF COLUMN DESIGN RESULTS********************

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 52

2405. * DISEムO DE DADOS


2406. DESIGN COLUMN _DADOS_DISEムO

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 53

====================================================================

COLUMN NO. 25 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 26 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 27 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 54

====================================================================

COLUMN NO. 32 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 600.0 X 600.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 3600.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

32 - 12 MM 1.005 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

********************END OF COLUMN DESIGN RESULTS********************

2407. DESIGN COLUMN _DADOS_MUROS_D

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 55

====================================================================

COLUMN NO. 22 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.900


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 29 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 33 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 56

====================================================================

COLUMN NO. 34 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 35 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 36 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 57

====================================================================

COLUMN NO. 1033 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1043 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1053 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 58

====================================================================

COLUMN NO. 1063 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1073 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1226 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 59

====================================================================

COLUMN NO. 1236 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1246 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1256 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 60

====================================================================

COLUMN NO. 1266 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1293 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1303 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 61

====================================================================

COLUMN NO. 1313 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1323 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1333 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 62

====================================================================

COLUMN NO. 1360 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1370 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1380 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 63

====================================================================

COLUMN NO. 1390 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1400 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1553 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 64

====================================================================

COLUMN NO. 1563 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1573 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1583 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 65

====================================================================

COLUMN NO. 1593 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1746 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1756 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 66

====================================================================

COLUMN NO. 1766 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1776 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

====================================================================

COLUMN NO. 1786 DESIGN PER ACI 318-05 - AXIAL + BENDING

FY - 411.9 FC - 24.5 MPA, SQRE SIZE - 650.0 X 650.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 4225.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

40 - 12 MM 1.071 100 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 10 SPACING 192.00 MM

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 68

=====================================================================

BEAM NO. 112 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2333. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 66. 6 - 12MM 342. 2333. NO YES


2 634. 6 - 12MM 0. 2333. YES YES

B E A M N O. 112 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 64.90 KNS Vc= 159.55 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 317. MM C/C FOR 537. MM

AT END SUPPORT - Vu= 16.97 KNS Vc= 153.44 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___ 53J____________________ 2333X 300X 700_____________________1920J____


| |
||=========================================================================||
| 6No12 H 634. 0.TO 2333 |
| 3*10c/c317| | |
| 6No12 H 66.|342.TO 2333 |
| ================================================================||
| |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
| | | | | | | | | | | | | | | | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 69

=====================================================================

BEAM NO. 113 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2333. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 66. 6 - 12MM 925. 2333. NO YES


2 634. 6 - 12MM 0. 1635. YES NO

B E A M N O. 113 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 73.55 KNS Vc= 159.55 KNS Vs= 0.00 KNS
Tu= 0.02 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 317. MM C/C FOR 537. MM

AT END SUPPORT - Vu= 25.61 KNS Vc= 159.55 KNS Vs= 0.00 KNS
Tu= 0.02 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___ 54J____________________ 2333X 300X 700_____________________1922J____


| |
||==================================================== |
| 6No12 H 634. 0.TO 1635 |
| 3*10c/c317 |
| 6No12 H 66. 925.TO 2333 |
| =============================================||
| |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
| | | | | | | | | | | | | | | | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 70

=====================================================================

BEAM NO. 2404 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2333. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 66. 6 - 12MM 0. 2333. YES YES

B E A M N O. 2404 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 23.21 KNS Vc= 151.84 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 24.73 KNS Vc= 152.11 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1920J____________________ 2333X 300X 700_____________________1921J____


| |
| |
| |
| |
| 6No12 H 66. 0.TO 2333 |
||=========================================================================||
| |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
| | | | | | | | | | | | | | | | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 71

=====================================================================

BEAM NO. 2405 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2333. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 66. 6 - 12MM 0. 2333. YES YES


2 634. 6 - 12MM 17. 2333. NO YES

B E A M N O. 2405 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 20.00 KNS Vc= 155.34 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 67.94 KNS Vc= 159.55 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 317. MM C/C FOR 537. MM

___1921J____________________ 2333X 300X 700_____________________ 59J____


| |
|==========================================================================||
| 6No12 H 634. 17.TO 2333 | | | |
| | 3*10c/c317 | |
| 6No12 H 66. 0.TO 2333 | | | |
||=========================================================================||
| |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | | | | | | | | | | | | | | | | |
| | |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
| | | | | | | | | | | | | | | | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 72

=====================================================================

BEAM NO. 2406 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2333. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 66. 6 - 12MM 0. 2333. YES YES

B E A M N O. 2406 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 25.10 KNS Vc= 152.24 KNS Vs= 0.00 KNS
Tu= 0.02 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 22.84 KNS Vc= 151.82 KNS Vs= 0.00 KNS
Tu= 0.02 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1922J____________________ 2333X 300X 700_____________________1923J____


| |
| |
| |
| |
| 6No12 H 66. 0.TO 2333 |
||=========================================================================||
| |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
| | | | | | | | | | | | | | | | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 73

=====================================================================

BEAM NO. 2407 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2333. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 66. 6 - 12MM 0. 1700. YES NO


2 634. 6 - 12MM 601. 2333. NO YES

B E A M N O. 2407 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 21.09 KNS Vc= 155.47 KNS Vs= 0.00 KNS
Tu= 0.02 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 69.03 KNS Vc= 159.55 KNS Vs= 0.00 KNS
Tu= 0.02 KN-MET Tc= 6.8 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 317. MM C/C FOR 537. MM

___1923J____________________ 2333X 300X 700_____________________ 60J____


| |
| ========================================================||
| 6No12 H 634. 601.TO 2333 | |
| | 3*10c/c317 |
| 6No12 H 66. 0.TO 1700 | |
||====================================================== |
| |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | | | | | | | | | | | | | | | | |
| | | | | | |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| | | | | | |
| | | | | | | | | | | | | | | | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

********************END OF BEAM DESIGN**************************

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 74

=====================================================================

BEAM NO. 37 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 39. 3125. NO YES


2 659. 7 - 12MM 0. 1510. YES NO

B E A M N O. 37 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 71.46 KNS Vc= 290.08 KNS Vs= 0.00 KNS
Tu= 28.65 KN-MET Tc= 8.9 KN-MET Ts= 38.2 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.84 SQ.CM.

AT END SUPPORT - Vu= 29.39 KNS Vc= 183.43 KNS Vs= 0.00 KNS
Tu= 28.65 KN-MET Tc= 8.9 KN-MET Ts= 38.2 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.84 SQ.CM.

___ 19J____________________ 3125X 350X 700_____________________1852J____


||=================================== |
| 7No12 H 659.| 0.TO 1510| | |
| | | | | | | |
| 6*10c/c226 | | | | 6*10c/c226 |
| | | | | | | |
| 7No12 H 41.| 39.TO 3125| | |
|==========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
|ooooooo| |ooooooo| |ooooooo| | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 75

=====================================================================

BEAM NO. 39 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 299. 3125. NO YES


2 659. 7 - 12MM 0. 2031. YES NO

B E A M N O. 39 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 56.13 KNS Vc= 161.72 KNS Vs= 0.00 KNS
Tu= 24.66 KN-MET Tc= 7.3 KN-MET Ts= 32.9 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.03 SQ.CM.

AT END SUPPORT - Vu= 25.91 KNS Vc= 161.72 KNS Vs= 0.00 KNS
Tu= 24.66 KN-MET Tc= 7.3 KN-MET Ts= 32.9 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.03 SQ.CM.

___ 21J____________________ 3125X 350X 700_____________________1853J____


||================================================ |
| 7No12 H 659.| 0.TO 2031| | | |
| | | | | | | |
| 6*10c/c226 | | | | | 6*10c/c226 |
| | | | | | | |
| 7No12 H 41.|299.TO 3125| | |
| ====================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
|ooooooo| |ooooooo| |ooooooo| |ooooooo| | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 76

=====================================================================

BEAM NO. 40 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 820. 3125. NO YES


2 659. 7 - 12MM 0. 1771. YES NO

B E A M N O. 40 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 93.35 KNS Vc= 193.39 KNS Vs= 0.00 KNS
Tu= 6.50 KN-MET Tc= 8.9 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 330. MM C/C FOR 908. MM

AT END SUPPORT - Vu= 40.16 KNS Vc= 183.53 KNS Vs= 0.00 KNS
Tu= 10.80 KN-MET Tc= 8.5 KN-MET Ts= 14.4 KN-MET LOAD 122
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.20 SQ.CM.

___ 22J____________________ 3125X 350X 700_____________________1854J____


||========================================== |
| 7No12 H 659. 0.TO 1771 | |
| | | |
| 4*10c/c330 | | 6*10c/c226 |
| | | |
| 7No12 H 41. 820.TO 3125 |
| ========================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
|ooooooo| |ooooooo| |ooooooo| |ooooooo| | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 77

=====================================================================

BEAM NO. 41 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 0. 3125. YES YES


2 657. 4 - 16MM 0. 1927. YES NO

B E A M N O. 41 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 125.45 KNS Vc= 185.30 KNS Vs= 0.00 KNS
Tu= 0.70 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 908. MM

AT END SUPPORT - Vu= 71.79 KNS Vc= 158.85 KNS Vs= 0.00 KNS
Tu= 0.70 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 908. MM

___ 24J____________________ 3125X 300X 700_____________________1855J____


||============================================= |
| 4No16 H 657. 0.TO 1927 | |
| | | | | |
| 4*10c/c329 | | 4*10c/c329 |
| | | | | |
| 4No16 H 43. 0.TO 3125 | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | | | | | | |
| 4#16| | 4#16| | 4#16| | 4#16| | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16|
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 78

=====================================================================

BEAM NO. 42 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 47. 2 - 25MM 167. 3125. NO YES


2 653. 3 - 25MM 0. 2972. YES NO

B E A M N O. 42 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 153.71 KNS Vc= 167.65 KNS Vs= 37.30 KNS
Tu= 13.82 KN-MET Tc= 6.9 KN-MET Ts= 18.4 KN-MET LOAD 133
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.28 SQ.CM.

AT END SUPPORT - Vu= 68.65 KNS Vc= 159.29 KNS Vs= 0.00 KNS
Tu= 14.22 KN-MET Tc= 6.8 KN-MET Ts= 19.0 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.38 SQ.CM.

___ 25J____________________ 3125X 300X 700_____________________1856J____


||======================================================================= |
| 3No25 H 653.| 0.TO 2972| | | | | | | |
| | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 |
| | | | | | | | | | | |
| 2No25 H 47. 167.TO 3125 | | | | | | |
| =======================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | |
| 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 2#25| | 2#25| | 2#25| | 2#25| | 2#25| | 2#25|
| | | oo | | oo | | oo | | oo | | oo | | oo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 79

=====================================================================

BEAM NO. 43 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 51. 3125. NO YES


2 653. 3 - 25MM 0. 2972. YES NO

B E A M N O. 43 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 157.55 KNS Vc= 166.30 KNS Vs= 43.76 KNS
Tu= 13.50 KN-MET Tc= 6.8 KN-MET Ts= 18.0 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.21 SQ.CM.

AT END SUPPORT - Vu= 64.56 KNS Vc= 160.04 KNS Vs= 0.00 KNS
Tu= 13.96 KN-MET Tc= 7.1 KN-MET Ts= 18.6 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.32 SQ.CM.

___ 26J____________________ 3125X 300X 700_____________________1857J____


||======================================================================= |
| 3No25 H 653.| 0.TO 2972| | | | | | | |
| | | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 |
| | | | | | | | | | | | |
| 3No20 H 45.| 51.TO 3125| | | | | | | |
|==========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | |
| 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20|
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco lxxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 80

=====================================================================

BEAM NO. 44 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 451. 3125. NO YES


2 653. 3 - 25MM 0. 2972. YES NO

B E A M N O. 44 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 155.95 KNS Vc= 165.53 KNS Vs= 42.41 KNS
Tu= 17.96 KN-MET Tc= 6.9 KN-MET Ts= 24.0 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.27 SQ.CM.

AT END SUPPORT - Vu= 87.63 KNS Vc= 160.70 KNS Vs= 0.00 KNS
Tu= 18.07 KN-MET Tc= 7.3 KN-MET Ts= 24.1 KN-MET LOAD 124
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.29 SQ.CM.

___ 27J____________________ 3125X 300X 700_____________________1858J____


||======================================================================= |
| 3No25 H 653.| 0.TO 2972| | | | | | | |
| | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 |
| | | | | | | | | | |
| 4No16 H 43. 451.TO 3125 | | | | | |
| =================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | |
| 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16|
| | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xc
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 81

=====================================================================

BEAM NO. 45 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 0. 3125. YES YES


2 659. 7 - 12MM 0. 1510. YES NO

B E A M N O. 45 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 71.45 KNS Vc= 334.44 KNS Vs= 0.00 KNS
Tu= 23.24 KN-MET Tc= 9.0 KN-MET Ts= 31.0 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.74 SQ.CM.

AT END SUPPORT - Vu= 29.37 KNS Vc= 183.04 KNS Vs= 0.00 KNS
Tu= 23.24 KN-MET Tc= 9.0 KN-MET Ts= 31.0 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.74 SQ.CM.

___ 29J____________________ 3125X 350X 700_____________________1859J____


||=================================== |
| 7No12 H 659.| 0.TO 1510| | |
| | | | | | | |
| 6*10c/c226 | | | | 6*10c/c226 |
| | | | | | | |
| 7No12 H 41.| 0.TO 3125| | |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
|ooooooo| |ooooooo| |ooooooo| | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
|ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xci
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 82

=====================================================================

BEAM NO. 47 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 6 - 16MM 120. 3125. NO YES


2 653. 3 - 25MM 0. 2569. YES NO

B E A M N O. 47 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 136.64 KNS Vc= 169.92 KNS Vs= 12.27 KNS
Tu= 16.99 KN-MET Tc= 7.8 KN-MET Ts= 22.6 KN-MET LOAD 128
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.46 SQ.CM.

AT END SUPPORT - Vu= 86.43 KNS Vc= 191.27 KNS Vs= 0.00 KNS
Tu= 17.07 KN-MET Tc= 9.8 KN-MET Ts= 22.8 KN-MET LOAD 127
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.48 SQ.CM.

___ 31J____________________ 3125X 350X 700_____________________1860J____


||============================================================= |
| 3No25 H 653.| 0.TO 2569| | | | | | |
| | | | | | | | | | | |
| 6*10c/c226 | | | | | | | 6*10c/c226 |
| | | | | | | | | | | |
| |6No16|H 43. 120.TO 3125 | | | | | |
| =========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooo | | ooo | | ooo | | ooo | | ooo | | | | |
| 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 6#16 | | 6#16 | | 6#16 | | 6#16 | | 6#16 | | 6#16 |
| | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xcii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 83

=====================================================================

BEAM NO. 48 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 359. 3125. NO YES


2 655. 4 - 20MM 0. 2464. YES NO

B E A M N O. 48 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 162.36 KNS Vc= 193.44 KNS Vs= 23.04 KNS
Tu= 24.16 KN-MET Tc= 9.4 KN-MET Ts= 32.2 KN-MET LOAD 121
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.93 SQ.CM.

AT END SUPPORT - Vu= 98.65 KNS Vc= 186.83 KNS Vs= 0.00 KNS
Tu= 24.45 KN-MET Tc= 8.7 KN-MET Ts= 32.6 KN-MET LOAD 118
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.99 SQ.CM.

___ 32J____________________ 3125X 350X 700_____________________1861J____


||========================================================== |
| 4No20 H 655.| 0.TO 2464| | | | | |
| | | | | | | | | |
| 6*10c/c226 | | | | | | | 6*10c/c226 |
| | | | | | | | | |
| |3No20|H 45. 359.TO 3125 | | | |
| ===================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | | | |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 |
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xciii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 84

=====================================================================

BEAM NO. 49 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3125. YES YES


2 659. 6 - 12MM 0. 1510. YES NO

B E A M N O. 49 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 47.00 KNS Vc= 206.76 KNS Vs= 0.00 KNS
Tu= 20.96 KN-MET Tc= 6.9 KN-MET Ts= 28.0 KN-MET LOAD 121
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.98 SQ.CM.

AT END SUPPORT - Vu= 18.43 KNS Vc= 157.30 KNS Vs= 0.00 KNS
Tu= 20.96 KN-MET Tc= 6.9 KN-MET Ts= 28.0 KN-MET LOAD 121
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.98 SQ.CM.

___ 34J____________________ 3125X 300X 700_____________________1862J____


||=================================== |
| 6No12 H 659.| 0.TO 1510| | |
| | | | | | | |
| 6*10c/c213 | | | | 6*10c/c213 |
| | | | | | | |
| 6No12 H 41.| 0.TO 3125| | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
|ooooo| |ooooo| |ooooo| | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xciv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 85

=====================================================================

BEAM NO. 50 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 614. 3125. NO YES


2 655. 3 - 20MM 0. 2083. YES NO

B E A M N O. 50 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 159.55 KNS Vc= 169.62 KNS Vs= 43.12 KNS
Tu= 4.94 KN-MET Tc= 7.0 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 908. MM

AT END SUPPORT - Vu= 105.90 KNS Vc= 161.45 KNS Vs= 0.00 KNS
Tu= 4.94 KN-MET Tc= 7.0 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 908. MM

___ 35J____________________ 3125X 300X 700_____________________1863J____


||================================================= |
| 3No20 H 655. 0.TO 2083| | |
| | | | |
| 4*10c/c328 | | | 4*10c/c328 |
| | | | |
| 3No20 H 45. 614.TO 3125 | |
| =============================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 3#20| | 3#20| | 3#20| | 3#20| | 3#20|
| | | | | ooo | | ooo | | ooo | | ooo | | ooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xcv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 86

=====================================================================

BEAM NO. 52 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 669. 3500. NO YES


2 655. 3 - 20MM 0. 2531. YES NO

B E A M N O. 52 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 92.48 KNS Vc= 61.74 KNS Vs= 61.56 KNS
Tu= 26.06 KN-MET Tc= NaN KN-MET Ts= 34.7 KN-MET LOAD 118
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 193. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.31 SQ.CM.

AT END SUPPORT - Vu= 44.42 KNS Vc= 140.49 KNS Vs= 0.00 KNS
Tu= 30.23 KN-MET Tc= 6.0 KN-MET Ts= 40.3 KN-MET LOAD 102
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.16 SQ.CM.

___ 28J____________________ 3500X 350X 700_____________________1864J____


||===================================================== |
| 3No20 H 655. 0.TO 2531 | | | | |
| | | | | | | |
| 7*10c/c193 | | | | | | 6*10c/c226 |
| | | | | | | |
| 7No12 H| 41.|669.TO 3500 | | |
| =============================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooo | | ooo | | ooo | | ooo | | ooo | | | | |
| 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xcvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 87

=====================================================================

BEAM NO. 53 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 1252. 3500. NO YES


2 659. 7 - 12MM 0. 2219. YES NO

B E A M N O. 53 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 89.74 KNS Vc= 191.55 KNS Vs= 0.00 KNS
Tu= 15.35 KN-MET Tc= 8.9 KN-MET Ts= 20.5 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.13 SQ.CM.

AT END SUPPORT - Vu= 36.38 KNS Vc= 185.27 KNS Vs= 0.00 KNS
Tu= 15.35 KN-MET Tc= 8.9 KN-MET Ts= 20.5 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.13 SQ.CM.

___ 33J____________________ 3500X 350X 700_____________________1865J____


||=============================================== |
| 7No12 H 659. 0.TO 2219 | |
| | |
| 6*10c/c226 | 6*10c/c226 |
| | |
| |7No12 H 41.1252.TO 3500 |
| ================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
|ooooooo| |ooooooo| |ooooooo| |ooooooo| | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo|
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xcvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 88

=====================================================================

BEAM NO. 54 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 3500. YES YES


2 655. 3 - 20MM 0. 2240. YES NO

B E A M N O. 54 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 131.84 KNS Vc= 187.58 KNS Vs= 0.00 KNS
Tu= 1.73 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 61.91 KNS Vc= 157.41 KNS Vs= 0.00 KNS
Tu= 1.73 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___ 22J____________________ 3499X 300X 700_____________________1866J____


||=============================================== |
| 3No20 H 655. 0.TO 2240| | | |
| | | | | | | |
| 5*10c/c328 | | | | 5*10c/c328 |
| | | | | | | |
| 3No20 H |45. 0.TO 3500| | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20|
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xcviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 89

=====================================================================

BEAM NO. 55 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 4 - 20MM 443. 3500. NO YES


2 655. 5 - 20MM 0. 3039. YES NO
3 615. 2 - 20MM 0. 3039. YES NO

B E A M N O. 55 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 216.81 KNS Vc= 155.46 KNS Vs= 133.62 KNS
Tu= 9.87 KN-MET Tc= 6.5 KN-MET Ts= 13.2 KN-MET LOAD 107
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 204. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.35 SQ.CM.

AT END SUPPORT - Vu= 92.24 KNS Vc= 158.98 KNS Vs= 0.00 KNS
Tu= 9.96 KN-MET Tc= 6.7 KN-MET Ts= 13.3 KN-MET LOAD 108
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.37 SQ.CM.

___ 27J____________________ 3500X 300X 700_____________________1867J____


||================================================================ |
||5No20=H=655.===0.TO=3039======================================== |
| 2No20 H 615. 0.TO 3039 | | | | | | | |
| 7*10c/c204 | | | | | | | | 7*10c/c213 |
| | | | | | | | | | | |
| 4No20 H| 45.|443.TO 3500 | | | | | |
| ==================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| | |
| 5#20| | 5#20| | 5#20| | 5#20| | 5#20| | 5#20| | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20|
| | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco xcix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 90

=====================================================================

BEAM NO. 56 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 261. 3500. NO YES


2 653. 3 - 25MM 0. 3451. YES NO

B E A M N O. 56 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 157.28 KNS Vc= 164.60 KNS Vs= 45.10 KNS
Tu= 0.11 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 87.35 KNS Vc= 160.33 KNS Vs= 0.00 KNS
Tu= 0.11 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___ 32J____________________ 3500X 300X 700_____________________1868J____


||========================================================================= |
| 3No25 H 653. 0.TO 3451| | | | | | | |
| | | | | | | | | | |
| 5*10c/c329 | | | | | | 5*10c/c329 | |
| | | | | | | | | | |
| 4No16 H 43.|261.TO 3500 | | | | | | |
| ======================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | |
| 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16|
| | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco c
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 91

=====================================================================

BEAM NO. 57 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 3500. YES YES


2 655. 4 - 20MM 0. 2652. YES NO

B E A M N O. 57 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 133.72 KNS Vc= 177.89 KNS Vs= 0.40 KNS
Tu= 0.44 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 63.79 KNS Vc= 157.61 KNS Vs= 0.00 KNS
Tu= 0.44 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___ 21J____________________ 3499X 300X 700_____________________1869J____


||======================================================== |
| 4No20 H 655. 0.TO 2652| | | | |
| | | | | | | | |
| 5*10c/c328 | | | | | 5*10c/c328 |
| | | | | | | | |
| 3No20 H |45. 0.TO 3500| | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | | | | |
| 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20|
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ci
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 92

=====================================================================

BEAM NO. 58 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 4 - 20MM 129. 3500. NO YES


2 653. 4 - 25MM 0. 3500. YES YES

B E A M N O. 58 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 214.44 KNS Vc= 149.18 KNS Vs= 136.74 KNS
Tu= 1.48 KN-MET Tc= 6.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 310. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 113.31 KNS Vc= 149.18 KNS Vs= 1.91 KNS
Tu= 1.48 KN-MET Tc= 6.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___ 26J____________________ 3500X 300X 700_____________________1870J____


||=========================================================================||
| 4No25 H|653. |0.TO 3500 | | | | | | |
| | | | | | | | | | | |
| 5*10c/c310 | | | | | | 5*10c/c328 | |
| | | | | | | | | | | |
| |4No20 H 45. 129.TO 3500 | | | | | | |
| =========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| 4#25| | 4#25| | 4#25| | 4#25| | 4#25| | 4#25| | 4#25|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20|
| | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 93

=====================================================================

BEAM NO. 59 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3500. YES YES


2 655. 4 - 20MM 0. 3500. YES YES

B E A M N O. 59 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 106.14 KNS Vc= 161.98 KNS Vs= 0.00 KNS
Tu= 15.84 KN-MET Tc= 7.0 KN-MET Ts= 21.1 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.76 SQ.CM.

AT END SUPPORT - Vu= 55.49 KNS Vc= 161.16 KNS Vs= 0.00 KNS
Tu= 15.84 KN-MET Tc= 7.0 KN-MET Ts= 21.1 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.76 SQ.CM.

___ 31J____________________ 3500X 300X 700_____________________1871J____


||=========================================================================||
| 4No20|H 655. 0.TO 3500 | | | | | | | | | |
| | | | | | | | | | | | | | | |
| 7*10c/c213 | | | | | | | | 7*10c/c213 | |
| | | | | | | | | | | | | | | |
| 6No12|H 41. 0.TO 3500 | | | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ciii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 94

=====================================================================

BEAM NO. 60 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 3500. YES YES


2 653. 2 - 25MM 0. 2757. YES NO

B E A M N O. 60 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 132.69 KNS Vc= 177.90 KNS Vs= 0.00 KNS
Tu= 1.33 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 62.76 KNS Vc= 157.53 KNS Vs= 0.00 KNS
Tu= 1.33 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___ 20J____________________ 3499X 300X 700_____________________1872J____


||========================================================== |
| 2No25 H 653. 0.TO 2757| | | | | |
| | | | | | | | | |
| 5*10c/c328 | | | | | | 5*10c/c328 |
| | | | | | | | | |
| 3No20 H |45. 0.TO 3500| | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| oo | | oo | | oo | | oo | | oo | | | | |
| 2#25| | 2#25| | 2#25| | 2#25| | 2#25| | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20|
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco civ
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 95

=====================================================================

BEAM NO. 61 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 4 - 20MM 101. 3500. NO YES


2 653. 4 - 25MM 0. 3500. YES YES

B E A M N O. 61 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 236.46 KNS Vc= 153.55 KNS Vs= 161.74 KNS
Tu= 1.57 KN-MET Tc= 6.4 KN-MET Ts= 0.0 KN-MET LOAD 101
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 262. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 116.20 KNS Vc= 153.87 KNS Vs= 1.06 KNS
Tu= 1.47 KN-MET Tc= 6.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___ 25J____________________ 3500X 300X 700_____________________1873J____


||=========================================================================||
| 4No25 H 653.| 0.TO 3500| | | | | | | |
| | | | | | | | | | | | |
| 6*10c/c262 | | | | | | | 5*10c/c328 | |
| | | | | | | | | | | | |
| |4No20|H 45. 101.TO 3500 | | | | | | |
| =========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| 4#25| | 4#25| | 4#25| | 4#25| | 4#25| | 4#25| | 4#25|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20|
| | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 96

=====================================================================

BEAM NO. 63 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 669. 3500. NO YES


2 659. 7 - 12MM 0. 2219. YES NO

B E A M N O. 63 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 79.05 KNS Vc= 192.24 KNS Vs= 0.00 KNS
Tu= 18.23 KN-MET Tc= 9.1 KN-MET Ts= 24.3 KN-MET LOAD 107
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.72 SQ.CM.

AT END SUPPORT - Vu= 40.77 KNS Vc= 186.42 KNS Vs= 0.00 KNS
Tu= 18.23 KN-MET Tc= 9.1 KN-MET Ts= 24.3 KN-MET LOAD 107
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.72 SQ.CM.

___ 24J____________________ 3500X 350X 700_____________________1874J____


||=============================================== |
| 7No12 H 659. 0.TO 2219 | |
| | | | |
| 6*10c/c226 | | | 6*10c/c226 |
| | | | |
| 7No12 H| 41.|669.TO 3500 |
| =============================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
|ooooooo| |ooooooo| |ooooooo| |ooooooo| | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 97

=====================================================================

BEAM NO. 81 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 961. 3500. NO YES


2 659. 7 - 12MM 0. 2219. YES NO

B E A M N O. 81 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 107.20 KNS Vc= 191.23 KNS Vs= 0.00 KNS
Tu= 8.28 KN-MET Tc= 9.0 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 330. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 53.85 KNS Vc= 185.79 KNS Vs= 0.00 KNS
Tu= 8.28 KN-MET Tc= 9.0 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___ 36J____________________ 3500X 350X 700_____________________1875J____


||=============================================== |
| 7No12 H 659. 0.TO 2219| | |
| | | |
| 5*10c/c330 | | |
| | | |
| 7No12|H 41. 961.TO 3500 |
| =======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
|ooooooo| |ooooooo| |ooooooo| |ooooooo| | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 98

=====================================================================

BEAM NO. 82 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 961. 3500. NO YES


2 655. 3 - 20MM 0. 2823. YES NO

B E A M N O. 82 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 107.61 KNS Vc= 161.84 KNS Vs= 0.00 KNS
Tu= 14.64 KN-MET Tc= 6.9 KN-MET Ts= 19.5 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.48 SQ.CM.

AT END SUPPORT - Vu= 56.96 KNS Vc= 160.99 KNS Vs= 0.00 KNS
Tu= 14.64 KN-MET Tc= 6.9 KN-MET Ts= 19.5 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.48 SQ.CM.

___ 35J____________________ 3500X 300X 700_____________________1876J____


||============================================================ |
| 3No20 H 655. 0.TO 2823 | | | | | | |
| | | | | | | | |
| 7*10c/c213 | | | | | | | 7*10c/c213 |
| | | | | | | | |
| 6No12 H 41. 961.TO 3500 | | | |
| =======================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 99

=====================================================================

BEAM NO. 2277 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 0. 2435. YES NO


2 659. 7 - 12MM 963. 3125. NO YES

B E A M N O. 2277 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 43.95 KNS Vc= 188.53 KNS Vs= 0.00 KNS
Tu= 16.32 KN-MET Tc= 8.9 KN-MET Ts= 21.8 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.33 SQ.CM.

AT END SUPPORT - Vu= 74.17 KNS Vc= 192.06 KNS Vs= 0.00 KNS
Tu= 16.32 KN-MET Tc= 8.9 KN-MET Ts= 21.8 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.33 SQ.CM.

___1852J____________________ 3125X 350X 700_____________________ 20J____


| ====================================================||
| 7No12 H 659. 963.TO 3125 | | |
| | | | | | |
| 6*10c/c226 | | | | | 6*10c/c226 |
| | | | | | |
| 7No12 H 41. 0.TO 2435| | | | | |
||========================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
| | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | | | |
|ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 100

=====================================================================

BEAM NO. 2278 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 0. 2175. YES NO


2 659. 7 - 12MM 963. 3125. NO YES

B E A M N O. 2278 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 44.17 KNS Vc= 187.16 KNS Vs= 0.00 KNS
Tu= 17.81 KN-MET Tc= 8.9 KN-MET Ts= 23.7 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.63 SQ.CM.

AT END SUPPORT - Vu= 86.25 KNS Vc= 193.04 KNS Vs= 0.00 KNS
Tu= 17.81 KN-MET Tc= 8.9 KN-MET Ts= 23.7 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.63 SQ.CM.

___1853J____________________ 3125X 350X 700_____________________ 22J____


| ====================================================||
| 7No12 H 659. 963.TO 3125 | |
| | | | | |
| 6*10c/c226 | | | | 6*10c/c226 |
| | | | | |
| 7No12 H 41. 0.TO 2175| | | | |
||=================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
| | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | | | |
|ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 101

=====================================================================

BEAM NO. 2279 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 0. 2956. YES NO


2 659. 7 - 12MM 1484. 3125. NO YES

B E A M N O. 2279 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 27.03 KNS Vc= 183.25 KNS Vs= 0.00 KNS
Tu= 29.37 KN-MET Tc= 8.9 KN-MET Ts= 39.2 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.99 SQ.CM.

AT END SUPPORT - Vu= 69.11 KNS Vc= 296.18 KNS Vs= 0.00 KNS
Tu= 29.37 KN-MET Tc= 8.9 KN-MET Ts= 39.2 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.99 SQ.CM.

___1854J____________________ 3125X 350X 700_____________________ 23J____


| =======================================||
| 7No12 H|659.1484.TO|3125 | | |
| | | | | | |
| 6*10c/c226 | | | 6*10c/c226 |
| | | | | | |
| 7No12 H 41. 0.TO 2956 | | | | | |
||====================================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo|
| | | | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | |
|ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 102

=====================================================================

BEAM NO. 2280 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 0. 2809. YES NO


2 655. 4 - 20MM 270. 3125. NO YES

B E A M N O. 2280 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 82.29 KNS Vc= 163.38 KNS Vs= 0.00 KNS
Tu= 12.41 KN-MET Tc= 6.9 KN-MET Ts= 16.5 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.95 SQ.CM.

AT END SUPPORT - Vu= 120.37 KNS Vc= 164.24 KNS Vs= 0.00 KNS
Tu= 12.41 KN-MET Tc= 6.9 KN-MET Ts= 16.5 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.95 SQ.CM.

___1855J____________________ 3125X 300X 700_____________________ 25J____


| =====================================================================||
| 4No20 H|655. 270.TO|3125 | | | | | | |
| | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 |
| | | | | | | | | | | |
| 4No16 H 43.| 0.TO 2809| | | | | | | |
||=================================================================== |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| | | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | |
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 103

=====================================================================

BEAM NO. 2281 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 2683. YES NO


2 653. 3 - 25MM 0. 3125. YES YES

B E A M N O. 2281 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 69.95 KNS Vc= 160.36 KNS Vs= 0.00 KNS
Tu= 15.65 KN-MET Tc= 7.0 KN-MET Ts= 20.9 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.72 SQ.CM.

AT END SUPPORT - Vu= 163.42 KNS Vc= 160.97 KNS Vs= 56.92 KNS
Tu= 15.53 KN-MET Tc= 6.8 KN-MET Ts= 20.7 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.69 SQ.CM.

___1856J____________________ 3125X 300X 700_____________________ 26J____


||=========================================================================||
| 3No25 H 653.| 0.TO 3125| | | | | | |
| | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 |
| | | | | | | | | | | |
| 3No20 H 45.| 0.TO 2683| | | | | | |
||================================================================ |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 104

=====================================================================

BEAM NO. 2282 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 47. 2 - 25MM 0. 2830. YES NO


2 653. 3 - 25MM 0. 3125. YES YES

B E A M N O. 2282 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 72.55 KNS Vc= 160.24 KNS Vs= 0.00 KNS
Tu= 10.14 KN-MET Tc= 6.9 KN-MET Ts= 13.5 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.41 SQ.CM.

AT END SUPPORT - Vu= 157.77 KNS Vc= 166.41 KNS Vs= 43.95 KNS
Tu= 10.00 KN-MET Tc= 7.0 KN-MET Ts= 13.3 KN-MET LOAD 124
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.38 SQ.CM.

___1857J____________________ 3125X 300X 700_____________________ 27J____


||=========================================================================||
| 3No25 H 653.| 0.TO 3125| | | | | | | |
| | | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 |
| | | | | | | | | | | | |
| 2No25 H 47.| 0.TO 2830| | | | | | | |
||=================================================================== |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 2#25| | 2#25| | 2#25| | 2#25| | 2#25| | 2#25| | |
| oo | | oo | | oo | | oo | | oo | | oo | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 105

=====================================================================

BEAM NO. 2283 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 0. 3061. YES NO


2 655. 3 - 20MM 911. 3125. NO YES

B E A M N O. 2283 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 70.31 KNS Vc= 158.94 KNS Vs= 0.00 KNS
Tu= 0.20 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 908. MM

AT END SUPPORT - Vu= 149.34 KNS Vc= 169.24 KNS Vs= 29.87 KNS
Tu= 8.63 KN-MET Tc= 7.6 KN-MET Ts= 11.5 KN-MET LOAD 105
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.05 SQ.CM.

___1858J____________________ 3125X 300X 700_____________________ 28J____


| =====================================================||
| 3No20 H 655. 911.TO 3125 | | | | | |
| | | | | | | | |
| 4*10c/c329 | | | | 6*10c/c213 | |
| | | | | | | | |
| 4No16 H 43. 0.TO 3061 | | | | | | | |
||========================================================================= |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| | | | | ooo | | ooo | | ooo | | ooo | | ooo |
| | | | | 3#20| | 3#20| | 3#20| | 3#20| | 3#20|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | |
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 106

=====================================================================

BEAM NO. 2284 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 0. 2956. YES NO


2 659. 7 - 12MM 703. 3125. NO YES

B E A M N O. 2284 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 36.93 KNS Vc= 176.42 KNS Vs= 0.00 KNS
Tu= 32.39 KN-MET Tc= 8.1 KN-MET Ts= 43.2 KN-MET LOAD 127
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 215. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.60 SQ.CM.

AT END SUPPORT - Vu= 67.15 KNS Vc= 176.42 KNS Vs= 0.00 KNS
Tu= 32.39 KN-MET Tc= 8.1 KN-MET Ts= 43.2 KN-MET LOAD 127
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 215. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.60 SQ.CM.

___1859J____________________ 3125X 350X 700_____________________ 30J____


| ==========================================================||
| 7No12 H 659. 703.TO 3125 | | | | | |
| | | | | | | | | |
| 6*10c/c215 | | | | | | 6*10c/c215 |
| | | | | | | | | |
| 7No12 H 41. 0.TO 2956| | | | | | | |
||====================================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
| | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | |
|ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 107

=====================================================================

BEAM NO. 2285 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 6 - 16MM 0. 2613. YES NO


2 653. 3 - 25MM 165. 3125. NO YES

B E A M N O. 2285 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 120.70 KNS Vc= 188.16 KNS Vs= 0.00 KNS
Tu= 6.30 KN-MET Tc= 8.9 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 908. MM

AT END SUPPORT - Vu= 184.70 KNS Vc= 125.82 KNS Vs= 120.44 KNS
Tu= 6.79 KN-MET Tc= 4.8 KN-MET Ts= 9.1 KN-MET LOAD 102
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.38 SQ.CM.

___1860J____________________ 3125X 350X 700_____________________ 32J____


| =======================================================================||
| 3No25 H 653. 165.TO 3125| | | | | |
| | | | | | | | |
| 4*10c/c329 | | | | | 6*10c/c226 |
| | | | | | | | |
| 6No16 H 43. 0.TO 2613 | | | | | |
||============================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 6#16 | | 6#16 | | 6#16 | | 6#16 | | 6#16 | | 6#16 | | |
|oooooo | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 108

=====================================================================

BEAM NO. 2286 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 2895. YES NO


2 659. 7 - 12MM 1745. 3125. NO YES

B E A M N O. 2286 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 80.61 KNS Vc= 171.10 KNS Vs= 0.00 KNS
Tu= 9.01 KN-MET Tc= 7.9 KN-MET Ts= 12.0 KN-MET LOAD 102
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.84 SQ.CM.

AT END SUPPORT - Vu= 124.07 KNS Vc= 249.12 KNS Vs= 0.00 KNS
Tu= 1.22 KN-MET Tc= 9.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 908. MM

___1861J____________________ 3125X 350X 700_____________________ 33J____


| =================================||
| 7No12 H|659.1745.TO 3125 |
| | | | |
| 6*10c/c226 | | 4*10c/c328 |
| | | | |
| 3No20 H 45. 0.TO 2895 | | | |
||===================================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | |ooooooo| |ooooooo| |ooooooo|
| | | | | | | | | 7#12 | | 7#12 | | 7#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 109

=====================================================================

BEAM NO. 2287 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 1654. YES NO


2 657. 4 - 16MM 547. 3125. NO YES

B E A M N O. 2287 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 61.52 KNS Vc= 165.77 KNS Vs= 0.00 KNS
Tu= 21.47 KN-MET Tc= 6.9 KN-MET Ts= 28.6 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.10 SQ.CM.

AT END SUPPORT - Vu= 101.35 KNS Vc= 162.01 KNS Vs= 0.00 KNS
Tu= 21.47 KN-MET Tc= 6.9 KN-MET Ts= 28.6 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.10 SQ.CM.

___1862J____________________ 3125X 300X 700_____________________ 35J____


| ==============================================================||
| 4No16 H 657.|547.TO 3125 |
| | | | | |
| 6*10c/c213 | | | | 6*10c/c213 |
| | | | | |
| 6No12 H 41.| 0.TO 1654| | |
||======================================= |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| | | | |oooo | |oooo | |oooo | |oooo | |oooo |
| | | | | 4#16| | 4#16| | 4#16| | 4#16| | 4#16|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| | | | | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 110

=====================================================================

BEAM NO. 2288 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 2897. YES NO


2 659. 6 - 12MM 1745. 3125. NO YES

B E A M N O. 2288 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 71.37 KNS Vc= 158.09 KNS Vs= 0.00 KNS
Tu= 0.14 KN-MET Tc= 7.0 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 908. MM

AT END SUPPORT - Vu= 125.03 KNS Vc= 242.77 KNS Vs= 0.00 KNS
Tu= 0.14 KN-MET Tc= 7.0 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 908. MM

___1863J____________________ 3125X 300X 700_____________________ 36J____


| =================================||
| 6No12 H|659.1745.TO 3125 |
| | | | |
| 4*10c/c328 | | 4*10c/c328 |
| | | | |
| 3No20 H 45. 0.TO 2897 | | | |
||===================================================================== |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| | | | | | | | |ooooo| |ooooo| |ooooo|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 111

=====================================================================

BEAM NO. 2289 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 0. 2685. YES NO


2 659. 7 - 12MM 1427. 3500. NO YES

B E A M N O. 2289 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 33.45 KNS Vc= 431.40 KNS Vs= 0.00 KNS
Tu= 23.47 KN-MET Tc= 13.8 KN-MET Ts= 31.3 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.79 SQ.CM.

AT END SUPPORT - Vu= 111.53 KNS Vc= 63.48 KNS Vs= 85.24 KNS
Tu= 20.44 KN-MET Tc= NaN KN-MET Ts= 27.3 KN-MET LOAD 121
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 203. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.17 SQ.CM.

___1864J____________________ 3499X 350X 700_____________________ 33J____


| =============================================||
| 7No12 H 659.1427.TO 3500 |
| | | | |
| 6*10c/c226 | | | 7*10c/c203 |
| | | | |
| 7No12 H 41. 0.TO 2685 | | | |
||========================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo|
| | | | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | | | |
|ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 112

=====================================================================

BEAM NO. 2290 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 0. 2393. YES NO


2 659. 7 - 12MM 1135. 3500. NO YES

B E A M N O. 2290 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 25.95 KNS Vc= 186.39 KNS Vs= 0.00 KNS
Tu= 13.30 KN-MET Tc= 8.7 KN-MET Ts= 17.7 KN-MET LOAD 112
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.71 SQ.CM.

AT END SUPPORT - Vu= 64.23 KNS Vc= 186.39 KNS Vs= 0.00 KNS
Tu= 13.30 KN-MET Tc= 8.7 KN-MET Ts= 17.7 KN-MET LOAD 112
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.71 SQ.CM.

___1865J____________________ 3500X 350X 700_____________________ 36J____


| ===================================================||
| 7No12 H 659.1135.TO 3500| |
| | | |
| 6*10c/c226 | | 6*10c/c226 |
| | | |
| 7No12 H 41. 0.TO 2393 | | |
||================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
| | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | | | |
|ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 113

=====================================================================

BEAM NO. 2291 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 2890. YES NO


2 653. 3 - 25MM 0. 3500. YES YES

B E A M N O. 2291 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 87.05 KNS Vc= 164.21 KNS Vs= 0.00 KNS
Tu= 9.26 KN-MET Tc= 6.8 KN-MET Ts= 12.3 KN-MET LOAD 102
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.20 SQ.CM.

AT END SUPPORT - Vu= 136.63 KNS Vc= 161.75 KNS Vs= 20.43 KNS
Tu= 9.26 KN-MET Tc= 6.8 KN-MET Ts= 12.3 KN-MET LOAD 102
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.20 SQ.CM.

___1866J____________________ 3499X 300X 700_____________________ 27J____


||=========================================================================||
| 3No25|H 653. 0.TO 3500 | | | | | | |
| | | | | | | | | | | | |
| 7*10c/c213 | | | | | | | | 7*10c/c213 |
| | | | | | | | | | | | |
| 3No20|H 45. 0.TO 2890 | | | | | | |
||============================================================= |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 114

=====================================================================

BEAM NO. 2292 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 4 - 20MM 0. 2908. YES NO


2 653. 4 - 25MM 0. 3500. YES YES

B E A M N O. 2292 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 102.35 KNS Vc= 157.65 KNS Vs= 0.00 KNS
Tu= 5.17 KN-MET Tc= 6.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 210.68 KNS Vc= 159.37 KNS Vs= 121.54 KNS
Tu= 8.10 KN-MET Tc= 6.7 KN-MET Ts= 10.8 KN-MET LOAD 114
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.93 SQ.CM.

___1867J____________________ 3499X 300X 700_____________________ 32J____


||=========================================================================||
| 4No25 H 653. 0.TO 3500| | | | | | |
| | | | | | | | | | |
| 5*10c/c328 | | | | | | | 7*10c/c213 |
| | | | | | | | | | |
| 4No20 H |45. 0.TO 2908| | | | | | |
||============================================================== |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| 4#25| | 4#25| | 4#25| | 4#25| | 4#25| | 4#25| | 4#25|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | | | |
|oooo | |oooo | |oooo | |oooo | |oooo | | | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 115

=====================================================================

BEAM NO. 2293 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 0. 2806. YES NO


2 657. 5 - 16MM 779. 3500. NO YES

B E A M N O. 2293 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 83.62 KNS Vc= 159.92 KNS Vs= 0.00 KNS
Tu= 5.28 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 153.55 KNS Vc= 165.54 KNS Vs= 39.19 KNS
Tu= 5.28 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___1868J____________________ 3500X 300X 700_____________________ 35J____


| ===========================================================||
| 5No16 H 657. 779.TO 3500 | | | |
| | | | | | | |
| 5*10c/c329 | | | | | | 5*10c/c329 |
| | | | | | | |
| 4No16 H 43. 0.TO 2806| | | | | |
||=========================================================== |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| | | | |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
| | | | | 5#16| | 5#16| | 5#16| | 5#16| | 5#16|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | | | |
|oooo | |oooo | |oooo | |oooo | |oooo | | | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 116

=====================================================================

BEAM NO. 2294 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 3500. YES YES


2 653. 3 - 25MM 0. 3500. YES YES

B E A M N O. 2294 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 86.92 KNS Vc= 159.74 KNS Vs= 0.00 KNS
Tu= 1.75 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 156.85 KNS Vc= 166.31 KNS Vs= 42.82 KNS
Tu= 1.75 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___1869J____________________ 3499X 300X 700_____________________ 26J____


||=========================================================================||
| 3No25 H 653. 0.TO 3500| | | | | | | |
| | | | | | | | | | | |
| 5*10c/c328 | | | | | | 5*10c/c328 | |
| | | | | | | | | | | |
| 3No20 H |45. 0.TO 3500| | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20|
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 117

=====================================================================

BEAM NO. 2295 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 4 - 20MM 0. 3221. YES NO


2 653. 4 - 25MM 0. 3500. YES YES

B E A M N O. 2295 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 113.88 KNS Vc= 149.09 KNS Vs= 2.75 KNS
Tu= 3.30 KN-MET Tc= 6.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 215.01 KNS Vc= 149.09 KNS Vs= 137.58 KNS
Tu= 3.30 KN-MET Tc= 6.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 308. MM C/C FOR 1095. MM

___1870J____________________ 3499X 300X 700_____________________ 31J____


||=========================================================================||
| 4No25 H 653. 0.TO 3500| | | | | | |
| | | | | | | | | | |
| 5*10c/c328 | | | | | | 5*10c/c308 |
| | | | | | | | | | |
| 4No20 H |45. 0.TO 3221| | | | | | |
||==================================================================== |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| 4#25| | 4#25| | 4#25| | 4#25| | 4#25| | 4#25| | 4#25|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | |
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 118

=====================================================================

BEAM NO. 2296 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3500. YES YES


2 657. 4 - 16MM 687. 3500. NO YES

B E A M N O. 2296 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 21.45 KNS Vc= 156.35 KNS Vs= 0.00 KNS
Tu= 14.75 KN-MET Tc= 7.0 KN-MET Ts= 19.7 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.51 SQ.CM.

AT END SUPPORT - Vu= 72.10 KNS Vc= 211.72 KNS Vs= 0.00 KNS
Tu= 14.75 KN-MET Tc= 7.0 KN-MET Ts= 19.7 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.51 SQ.CM.

___1871J____________________ 3500X 300X 700_____________________ 34J____


| =============================================================||
| 4No16 H|657.|687.TO 3500 | | | | | | | |
| | | | | | | | | | | | |
| 7*10c/c213 | | | | | | | | 7*10c/c213 | |
| | | | | | | | | | | | |
| 6No12 H 41. 0.TO 3500 | | | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| | | | |oooo | |oooo | |oooo | |oooo | |oooo |
| | | | | 4#16| | 4#16| | 4#16| | 4#16| | 4#16|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 119

=====================================================================

BEAM NO. 2297 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 3448. YES NO


2 653. 3 - 25MM 0. 3500. YES YES

B E A M N O. 2297 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 91.21 KNS Vc= 160.19 KNS Vs= 0.00 KNS
Tu= 1.82 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 161.13 KNS Vc= 165.15 KNS Vs= 49.69 KNS
Tu= 1.82 KN-MET Tc= 7.1 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___1872J____________________ 3499X 300X 700_____________________ 25J____


||=========================================================================||
| 3No25 H 653. 0.TO 3500| | | | | | | |
| | | | | | | | | | | |
| 5*10c/c328 | | | | | | 5*10c/c328 | |
| | | | | | | | | | | |
| 3No20 H |45. 0.TO 3448| | | | | | | |
||========================================================================= |
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 120

=====================================================================

BEAM NO. 2298 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 4 - 20MM 0. 3500. YES YES


2 653. 4 - 25MM 0. 3500. YES YES

B E A M N O. 2298 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 93.41 KNS Vc= 153.79 KNS Vs= 0.00 KNS
Tu= 4.61 KN-MET Tc= 6.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 213.41 KNS Vc= 153.79 KNS Vs= 130.76 KNS
Tu= 4.61 KN-MET Tc= 6.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 324. MM C/C FOR 1095. MM

___1873J____________________ 3499X 300X 700_____________________ 30J____


||=========================================================================||
| 4No25 H 653. 0.TO 3500| | | | | | | |
| | | | | | | | | | | |
| 5*10c/c328 | | | | | | 5*10c/c324 | |
| | | | | | | | | | | |
| 4No20 H |45. 0.TO 3500| | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| 4#25| | 4#25| | 4#25| | 4#25| | 4#25| | 4#25| | 4#25|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20|
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 121

=====================================================================

BEAM NO. 2299 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 0. 3500. YES YES


2 659. 7 - 12MM 1719. 3500. NO YES

B E A M N O. 2299 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 26.64 KNS Vc= 182.43 KNS Vs= 0.00 KNS
Tu= 20.70 KN-MET Tc= 9.0 KN-MET Ts= 27.6 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.22 SQ.CM.

AT END SUPPORT - Vu= 80.00 KNS Vc= 335.26 KNS Vs= 0.00 KNS
Tu= 20.70 KN-MET Tc= 9.0 KN-MET Ts= 27.6 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.22 SQ.CM.

___1874J____________________ 3499X 350X 700_____________________ 29J____


| ======================================||
| 7No12 H 659.1719.TO 3500 | | | |
| | | | | | | |
| 6*10c/c226 | | | 6*10c/c226 | |
| | | | | | | |
| 7No12 H 41. 0.TO 3500 | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo|
| | | | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
|ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo|
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 122

=====================================================================

BEAM NO. 2300 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 350. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 7 - 12MM 0. 3268. YES NO


2 659. 7 - 12MM 1719. 3500. NO YES

B E A M N O. 2300 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 26.24 KNS Vc= 182.47 KNS Vs= 0.00 KNS
Tu= 27.56 KN-MET Tc= 8.9 KN-MET Ts= 36.7 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.62 SQ.CM.

AT END SUPPORT - Vu= 79.60 KNS Vc= 256.86 KNS Vs= 0.00 KNS
Tu= 27.56 KN-MET Tc= 8.9 KN-MET Ts= 36.7 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 226. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.62 SQ.CM.

___1875J____________________ 3499X 350X 700_____________________ 58J____


| ======================================||
| 7No12 H 659.1719.TO 3500 | | |
| | | | | | |
| 6*10c/c226 | | | 6*10c/c226 |
| | | | | | |
| 7No12 H 41. 0.TO 3268 | | | | | |
||===================================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | |ooooooo| |ooooooo| |ooooooo| |ooooooo|
| | | | | | | 7#12 | | 7#12 | | 7#12 | | 7#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | 7#12 | | |
|ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| |ooooooo| | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 123

=====================================================================

BEAM NO. 2301 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3500. YES YES


2 659. 6 - 12MM 1135. 3500. NO YES

B E A M N O. 2301 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 20.65 KNS Vc= 156.22 KNS Vs= 0.00 KNS
Tu= 19.26 KN-MET Tc= 6.9 KN-MET Ts= 25.7 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.58 SQ.CM.

AT END SUPPORT - Vu= 71.30 KNS Vc= 217.61 KNS Vs= 0.00 KNS
Tu= 19.26 KN-MET Tc= 6.9 KN-MET Ts= 25.7 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.58 SQ.CM.

___1876J____________________ 3499X 300X 700_____________________ 56J____


| ===================================================||
| 6No12 H|659.1135.TO|3500| | | | | | |
| | | | | | | | | | |
| 7*10c/c213 | | | | | | 7*10c/c213 | |
| | | | | | | | | | |
| 6No12 H 41. 0.TO 3500 | | | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____
| | | | |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 125

=====================================================================

BEAM NO. 91 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3125. YES YES


2 657. 4 - 16MM 0. 2709. YES NO

B E A M N O. 91 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 39.51 KNS Vc= 171.88 KNS Vs= 0.00 KNS
Tu= 27.24 KN-MET Tc= 7.0 KN-MET Ts= 36.3 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 207. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.47 SQ.CM.

AT END SUPPORT - Vu= 10.93 KNS Vc= 155.75 KNS Vs= 0.00 KNS
Tu= 27.24 KN-MET Tc= 7.0 KN-MET Ts= 36.3 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 207. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.47 SQ.CM.

___ 61J____________________ 3125X 300X 700_____________________1877J____


||================================================================ |
| 4No16 H 657.| 0.TO 2709| | | | | | |
| | | | | | | | | | | |
| 6*10c/c207 | | | | | | | 6*10c/c207 |
| | | | | | | | | | | |
| 6No12 H 41.| 0.TO 3125| | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | | | | |
| 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 126

=====================================================================

BEAM NO. 92 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3125. YES YES


2 655. 3 - 20MM 0. 2604. YES NO

B E A M N O. 92 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 52.94 KNS Vc= 182.60 KNS Vs= 0.00 KNS
Tu= 20.69 KN-MET Tc= 6.9 KN-MET Ts= 27.6 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.92 SQ.CM.

AT END SUPPORT - Vu= 24.36 KNS Vc= 158.18 KNS Vs= 0.00 KNS
Tu= 20.69 KN-MET Tc= 6.9 KN-MET Ts= 27.6 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.92 SQ.CM.

___ 62J____________________ 3125X 300X 700_____________________1878J____


||============================================================== |
| 3No20 H 655.| 0.TO 2604| | | | | | |
| | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 |
| | | | | | | | | | | |
| 6No12 H 41.| 0.TO 3125| | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | | | |
| 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 127

=====================================================================

BEAM NO. 93 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3125. YES YES


2 657. 4 - 16MM 0. 2709. YES NO

B E A M N O. 93 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 56.28 KNS Vc= 174.64 KNS Vs= 0.00 KNS
Tu= 25.04 KN-MET Tc= 6.8 KN-MET Ts= 33.4 KN-MET LOAD 127
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.95 SQ.CM.

AT END SUPPORT - Vu= 27.71 KNS Vc= 158.22 KNS Vs= 0.00 KNS
Tu= 25.04 KN-MET Tc= 6.8 KN-MET Ts= 33.4 KN-MET LOAD 127
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.95 SQ.CM.

___ 64J____________________ 3125X 300X 700_____________________1879J____


||================================================================ |
| 4No16 H 657.| 0.TO 2709| | | | | | |
| | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 |
| | | | | | | | | | | |
| 6No12 H 41.| 0.TO 3125| | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | | | | |
| 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 128

=====================================================================

BEAM NO. 94 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3125. YES YES


2 655. 4 - 20MM 0. 2985. YES NO

B E A M N O. 94 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 58.09 KNS Vc= 168.92 KNS Vs= 0.00 KNS
Tu= 18.81 KN-MET Tc= 6.9 KN-MET Ts= 25.1 KN-MET LOAD 128
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.47 SQ.CM.

AT END SUPPORT - Vu= 29.51 KNS Vc= 159.20 KNS Vs= 0.00 KNS
Tu= 18.81 KN-MET Tc= 6.9 KN-MET Ts= 25.1 KN-MET LOAD 128
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.47 SQ.CM.

___ 65J____________________ 3125X 300X 700_____________________1880J____


||======================================================================= |
| 4No20 H 655.| 0.TO 2985| | | | | | | |
| | | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 |
| | | | | | | | | | | | |
| 6No12 H 41.| 0.TO 3125| | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | | |
| 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 129

=====================================================================

BEAM NO. 95 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3500. YES YES


2 655. 4 - 20MM 0. 3235. YES NO

B E A M N O. 95 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 70.83 KNS Vc= 169.55 KNS Vs= 0.00 KNS
Tu= 19.37 KN-MET Tc= 7.2 KN-MET Ts= 25.8 KN-MET LOAD 105
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.60 SQ.CM.

AT END SUPPORT - Vu= 34.53 KNS Vc= 158.93 KNS Vs= 0.00 KNS
Tu= 19.37 KN-MET Tc= 7.2 KN-MET Ts= 25.8 KN-MET LOAD 105
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.60 SQ.CM.

___ 63J____________________ 3500X 300X 700_____________________1881J____


||===================================================================== |
| 4No20|H 655. 0.TO 3235 | | | | | | | | |
| | | | | | | | | | | | | | |
| 7*10c/c213 | | | | | | | | 7*10c/c213 |
| | | | | | | | | | | | | | |
| 6No12|H 41. 0.TO 3500 | | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | | |
| 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 130

=====================================================================

BEAM NO. 96 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 4 - 20MM 0. 3500. YES YES


2 653. 3 - 25MM 0. 3159. YES NO

B E A M N O. 96 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 163.53 KNS Vc= 184.24 KNS Vs= 33.80 KNS
Tu= 0.34 KN-MET Tc= 7.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 93.60 KNS Vc= 160.29 KNS Vs= 0.00 KNS
Tu= 0.34 KN-MET Tc= 7.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___ 62J____________________ 3500X 300X 700_____________________1882J____


||=================================================================== |
| 3No25 H 653. 0.TO 3159| | | | | | |
| | | | | | | | | | |
| 5*10c/c328 | | | | | | 5*10c/c328 |
| | | | | | | | | | |
| 4No20 H |45. 0.TO 3500| | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | |
| 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20|
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 131

=====================================================================

BEAM NO. 97 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3500. YES YES


2 655. 4 - 20MM 0. 3235. YES NO

B E A M N O. 97 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 94.39 KNS Vc= 172.28 KNS Vs= 0.00 KNS
Tu= 19.70 KN-MET Tc= 7.4 KN-MET Ts= 26.3 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.68 SQ.CM.

AT END SUPPORT - Vu= 43.74 KNS Vc= 158.78 KNS Vs= 0.00 KNS
Tu= 19.70 KN-MET Tc= 7.4 KN-MET Ts= 26.3 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.68 SQ.CM.

___ 61J____________________ 3500X 300X 700_____________________1883J____


||===================================================================== |
| 4No20|H 655. 0.TO 3235 | | | | | | | | |
| | | | | | | | | | | | | | |
| 7*10c/c213 | | | | | | | | 7*10c/c213 |
| | | | | | | | | | | | | | |
| 6No12|H 41. 0.TO 3500 | | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | | |
| 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxl
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 132

=====================================================================

BEAM NO. 2302 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3125. YES YES


2 655. 3 - 20MM 390. 3125. NO YES

B E A M N O. 2302 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 27.68 KNS Vc= 159.01 KNS Vs= 0.00 KNS
Tu= 19.56 KN-MET Tc= 7.0 KN-MET Ts= 26.1 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.65 SQ.CM.

AT END SUPPORT - Vu= 56.26 KNS Vc= 173.84 KNS Vs= 0.00 KNS
Tu= 19.56 KN-MET Tc= 7.0 KN-MET Ts= 26.1 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.65 SQ.CM.

___1877J____________________ 3125X 300X 700_____________________ 62J____


| ==================================================================||
| 3No20 H 655. 390.TO 3125 | | | | | | |
| | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 | |
| | | | | | | | | | | |
| 6No12 H 41.| 0.TO 3125| | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| | | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20|
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxli
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 133

=====================================================================

BEAM NO. 2303 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3125. YES YES


2 657. 4 - 16MM 286. 3125. NO YES

B E A M N O. 2303 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 14.52 KNS Vc= 156.22 KNS Vs= 0.00 KNS
Tu= 25.46 KN-MET Tc= 7.0 KN-MET Ts= 33.9 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.05 SQ.CM.

AT END SUPPORT - Vu= 43.09 KNS Vc= 191.35 KNS Vs= 0.00 KNS
Tu= 25.46 KN-MET Tc= 7.0 KN-MET Ts= 33.9 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.05 SQ.CM.

___1878J____________________ 3125X 300X 700_____________________ 63J____


| =====================================================================||
| 4No16 H|657. 286.TO|3125 | | | | | | | |
| | | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 | |
| | | | | | | | | | | | |
| 6No12 H 41.| 0.TO 3125| | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| | | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16|
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxlii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 134

=====================================================================

BEAM NO. 2304 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3125. YES YES


2 655. 3 - 20MM 390. 3125. NO YES

B E A M N O. 2304 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 50.45 KNS Vc= 162.73 KNS Vs= 0.00 KNS
Tu= 19.77 KN-MET Tc= 6.8 KN-MET Ts= 26.4 KN-MET LOAD 118
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.70 SQ.CM.

AT END SUPPORT - Vu= 79.02 KNS Vc= 162.79 KNS Vs= 0.00 KNS
Tu= 19.77 KN-MET Tc= 6.8 KN-MET Ts= 26.4 KN-MET LOAD 118
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.70 SQ.CM.

___1879J____________________ 3125X 300X 700_____________________ 65J____


| ==================================================================||
| 3No20 H 655. 390.TO 3125 | | | | | | |
| | | | | | | | | | | |
| 6*10c/c213 | | | | | | | 6*10c/c213 | |
| | | | | | | | | | | |
| 6No12 H 41.| 0.TO 3125| | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| | | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20| | 3#20|
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxliii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 135

=====================================================================

BEAM NO. 2305 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3125. YES YES


2 657. 4 - 16MM 286. 3125. NO YES

B E A M N O. 2305 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 28.85 KNS Vc= 159.11 KNS Vs= 0.00 KNS
Tu= 27.12 KN-MET Tc= 6.9 KN-MET Ts= 36.2 KN-MET LOAD 118
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 208. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.44 SQ.CM.

AT END SUPPORT - Vu= 57.42 KNS Vc= 171.56 KNS Vs= 0.00 KNS
Tu= 27.12 KN-MET Tc= 6.9 KN-MET Ts= 36.2 KN-MET LOAD 118
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 208. MM C/C FOR 908. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.44 SQ.CM.

___1880J____________________ 3125X 300X 700_____________________ 66J____


| =====================================================================||
| 4No16 H|657. 286.TO|3125 | | | | | | | |
| | | | | | | | | | | | |
| 6*10c/c208 | | | | | | | 6*10c/c208 | |
| | | | | | | | | | | | |
| 6No12 H 41.| 0.TO 3125| | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| | | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16| | 4#16|
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxliv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 136

=====================================================================

BEAM NO. 2306 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3500. YES YES


2 655. 4 - 20MM 119. 3500. NO YES

B E A M N O. 2306 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 11.12 KNS Vc= 155.60 KNS Vs= 0.00 KNS
Tu= 20.91 KN-MET Tc= 7.2 KN-MET Ts= 27.9 KN-MET LOAD 111
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.97 SQ.CM.

AT END SUPPORT - Vu= 47.41 KNS Vc= 200.58 KNS Vs= 0.00 KNS
Tu= 20.91 KN-MET Tc= 7.2 KN-MET Ts= 27.9 KN-MET LOAD 111
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.97 SQ.CM.

___1881J____________________ 3499X 300X 700_____________________ 66J____


| =========================================================================||
| |4No20 H 655. 119.TO|3500| | | | | | | | | |
| | | | | | | | | | | | | | | |
| 7*10c/c213 | | | | | | | | 7*10c/c213 | |
| | | | | | | | | | | | | | | |
| 6No12|H 41. 0.TO 3500 | | | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| | | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20|
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxlv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 137

=====================================================================

BEAM NO. 2307 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 4 - 20MM 0. 3500. YES YES


2 653. 3 - 25MM 195. 3500. NO YES

B E A M N O. 2307 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 94.20 KNS Vc= 160.34 KNS Vs= 0.00 KNS
Tu= 0.51 KN-MET Tc= 7.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

AT END SUPPORT - Vu= 164.13 KNS Vc= 183.85 KNS Vs= 35.00 KNS
Tu= 0.51 KN-MET Tc= 7.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 328. MM C/C FOR 1095. MM

___1882J____________________ 3499X 300X 700_____________________ 65J____


| =======================================================================||
| 3No25|H 653. 195.TO 3500 | | | | | | |
| | | | | | | | | | |
| 5*10c/c328 | | | | | | 5*10c/c328 | |
| | | | | | | | | | |
| 4No20 H |45. 0.TO 3500| | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| | | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25| | 3#25|
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20|
|oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxlvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 138

=====================================================================

BEAM NO. 2308 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 700. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 3500. YES YES


2 655. 4 - 20MM 411. 3500. NO YES

B E A M N O. 2308 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 10.45 KNS Vc= 155.63 KNS Vs= 0.00 KNS
Tu= 20.81 KN-MET Tc= 7.3 KN-MET Ts= 27.7 KN-MET LOAD 117
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.95 SQ.CM.

AT END SUPPORT - Vu= 46.75 KNS Vc= 258.82 KNS Vs= 0.00 KNS
Tu= 20.81 KN-MET Tc= 7.3 KN-MET Ts= 27.7 KN-MET LOAD 117
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 213. MM C/C FOR 1095. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.95 SQ.CM.

___1883J____________________ 3499X 300X 700_____________________ 64J____


| ===================================================================||
| 4No20 H 655. 411.TO 3500 | | | | | | | |
| | | | | | | | | | | | | |
| 7*10c/c213 | | | | | | | | 7*10c/c213 | |
| | | | | | | | | | | | | |
| 6No12 H 41. 0.TO 3500 | | | | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_____ _____ _____ _____ _____ _____ _____ _____ _____
| | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo | |oooo |
| | | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20| | 4#20|
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | |
|ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo| |ooooo|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxlvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 140

=====================================================================

BEAM NO. 2330 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 617. 3125. NO YES


2 457. 3 - 16MM 0. 1927. YES NO

B E A M N O. 2330 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 73.39 KNS Vc= 94.97 KNS Vs= 2.88 KNS
Tu= 0.09 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 19.01 KNS Vc= 90.96 KNS Vs= 0.00 KNS
Tu= 0.09 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1677J____________________ 3125X 250X 500_____________________1899J____


| |
||============================================= |
| 3No16 H 457. 0.TO 1927| | |
| 6*10c/c230 | | | |
| | | | |
| 5No10 H 40. 617.TO 3125 |
| ============================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxlviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 141

=====================================================================

BEAM NO. 2331 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 877. 3125. NO YES


2 459. 4 - 12MM 0. 1771. YES NO

B E A M N O. 2331 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 58.42 KNS Vc= 94.39 KNS Vs= 0.00 KNS
Tu= 2.01 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 4.04 KNS Vc= 90.36 KNS Vs= 0.00 KNS
Tu= 2.01 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1872J____________________ 3125X 250X 500_____________________1900J____


||========================================== |
| 4No12 H 459. 0.TO 1771| | |
| | | |
| 6*10c/c230 | | |
| | | |
| 5No10 H 40. 877.TO 3125 |
| ======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | | | | | |
| 4#12 | | 4#12 | | 4#12 | | 4#12 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxlix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 142

=====================================================================

BEAM NO. 2332 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 877. 3125. NO YES


2 457. 3 - 16MM 0. 1927. YES NO

B E A M N O. 2332 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 64.11 KNS Vc= 94.65 KNS Vs= 0.00 KNS
Tu= 0.23 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 9.73 KNS Vc= 90.69 KNS Vs= 0.00 KNS
Tu= 0.23 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1869J____________________ 3125X 250X 500_____________________1901J____


| |
||============================================= |
| 3No16 H 457. 0.TO 1927| | |
| 6*10c/c230 | | |
| | | |
| 5No10 H 40. 877.TO 3125 |
| ======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cl
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 143

=====================================================================

BEAM NO. 2333 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 877. 3125. NO YES


2 457. 3 - 16MM 0. 1667. YES NO

B E A M N O. 2333 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 69.31 KNS Vc= 95.28 KNS Vs= 0.00 KNS
Tu= 0.04 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 14.93 KNS Vc= 90.80 KNS Vs= 0.00 KNS
Tu= 0.04 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1866J____________________ 3125X 250X 500_____________________1902J____


| |
||======================================= |
| 3No16 H 457. 0.TO 1667| | |
| 6*10c/c230 | | |
| | | |
| 5No10 H 40. 877.TO 3125 |
| ======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cli
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 144

=====================================================================

BEAM NO. 2334 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2378. YES NO


2 459. 4 - 12MM 1484. 3125. NO YES

B E A M N O. 2334 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 13.60 KNS Vc= 90.69 KNS Vs= 0.00 KNS
Tu= 0.39 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 67.97 KNS Vc= 95.75 KNS Vs= 0.00 KNS
Tu= 0.39 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1899J____________________ 3125X 250X 500_____________________1872J____


| =======================================||
| 4No12 H|459.1484.TO|3125 |
| | | | |
| | | | 6*10c/c230 |
| | | | |
| 5No10 H 40. 0.TO 2378 | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | oooo | | oooo | | oooo | | oooo |
| | | | | | | 4#12 | | 4#12 | | 4#12 | | 4#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 145

=====================================================================

BEAM NO. 2335 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2118. YES NO


2 459. 4 - 12MM 1224. 3125. NO YES

B E A M N O. 2335 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 4.65 KNS Vc= 90.44 KNS Vs= 0.00 KNS
Tu= 1.60 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 59.03 KNS Vc= 94.24 KNS Vs= 0.00 KNS
Tu= 1.60 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1900J____________________ 3125X 250X 500_____________________1869J____


| ==============================================||
| 4No12 H 459.1224.TO 3125 |
| | | |
| | | 6*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2118 | | |
||================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | oooo | | oooo | | oooo | | oooo |
| | | | | | | 4#12 | | 4#12 | | 4#12 | | 4#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cliii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 146

=====================================================================

BEAM NO. 2336 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2118. YES NO


2 457. 3 - 16MM 1068. 3125. NO YES

B E A M N O. 2336 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 10.60 KNS Vc= 90.79 KNS Vs= 0.00 KNS
Tu= 0.63 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 64.98 KNS Vc= 94.45 KNS Vs= 0.00 KNS
Tu= 0.63 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1901J____________________ 3125X 250X 500_____________________1866J____


| |
| ==================================================||
| 3No16 H 457.1068.TO 3125| |
| | | 6*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2118 | | |
||================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cliv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 147

=====================================================================

BEAM NO. 2337 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2378. YES NO


2 457. 3 - 16MM 1068. 3125. NO YES

B E A M N O. 2337 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 19.21 KNS Vc= 90.98 KNS Vs= 0.00 KNS
Tu= 0.11 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 73.59 KNS Vc= 94.91 KNS Vs= 3.21 KNS
Tu= 0.11 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1902J____________________ 3125X 250X 500_____________________1722J____


| |
| ==================================================||
| 3No16 H 457.1068.TO 3125| | |
| | | | 6*10c/c230 |
| | | | |
| 5No10 H 40. 0.TO 2378 | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 148

=====================================================================

BEAM NO. 2338 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 96. 3125. NO YES


2 460. 5 - 10MM 0. 912. YES NO

B E A M N O. 2338 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 55.25 KNS Vc= 94.40 KNS Vs= 0.00 KNS
Tu= 0.41 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 0.87 KNS Vc= 94.40 KNS Vs= 0.00 KNS
Tu= 0.41 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1874J____________________ 3125X 250X 500_____________________1903J____


||===================== |
| 5No10 H 460.| 0.TO 912 |
| | | | | |
| 6*10c/c230 | | |
| | | | | |
| |5No10|H 40. 96.TO 3125 |
| =========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | | | | | | | | | |
| 5#10 | | 5#10 | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 149

=====================================================================

BEAM NO. 2339 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 877. 3125. NO YES


2 457. 3 - 16MM 0. 1667. YES NO

B E A M N O. 2339 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 86.02 KNS Vc= 94.09 KNS Vs= 20.60 KNS
Tu= 2.60 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 5.73 KNS Vc= 94.09 KNS Vs= 0.00 KNS
Tu= 2.60 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1873J____________________ 3125X 250X 500_____________________1904J____


| |
||======================================= |
| 3No16 H 457. 0.TO 1667| | |
| 6*10c/c230 | | |
| | | |
| 5No10 H 40. 877.TO 3125 |
| ======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 150

=====================================================================

BEAM NO. 2340 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 877. 3125. NO YES


2 457. 4 - 16MM 0. 2127. YES NO

B E A M N O. 2340 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 96.88 KNS Vc= 94.17 KNS Vs= 35.00 KNS
Tu= 0.37 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 16.58 KNS Vc= 94.17 KNS Vs= 0.00 KNS
Tu= 0.37 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1870J____________________ 3125X 250X 500_____________________1905J____


| |
||================================================== |
| 4No16 H 457. 0.TO 2127| | |
| 6*10c/c230 | | |
| | | |
| 5No10 H 40. 877.TO 3125 |
| ======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oooo | | oooo | | oooo | | oooo | | oooo | | | | |
| 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 151

=====================================================================

BEAM NO. 2341 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 4 - 12MM 843. 3125. NO YES


2 457. 3 - 16MM 0. 1927. YES NO

B E A M N O. 2341 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 67.83 KNS Vc= 94.12 KNS Vs= 0.00 KNS
Tu= 0.16 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 13.45 KNS Vc= 94.12 KNS Vs= 0.00 KNS
Tu= 0.16 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1867J____________________ 3125X 250X 500_____________________1906J____


| |
||============================================= |
| 3No16 H 457. 0.TO 1927| | |
| 6*10c/c230 | | | |
| | | | |
| |4No12|H 41. 843.TO 3125 |
| =======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 |
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 152

=====================================================================

BEAM NO. 2342 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2118. YES NO


2 457. 3 - 16MM 1068. 3125. NO YES

B E A M N O. 2342 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 17.00 KNS Vc= 94.38 KNS Vs= 0.00 KNS
Tu= 0.65 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 71.38 KNS Vc= 94.38 KNS Vs= 0.79 KNS
Tu= 0.65 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1903J____________________ 3125X 250X 500_____________________1873J____


| |
| ==================================================||
| 3No16 H 457.1068.TO 3125| |
| | | 6*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2118 | | |
||================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 153

=====================================================================

BEAM NO. 2343 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1857. YES NO


2 457. 4 - 16MM 868. 3125. NO YES

B E A M N O. 2343 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 14.40 KNS Vc= 94.08 KNS Vs= 0.00 KNS
Tu= 2.01 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 94.70 KNS Vc= 94.08 KNS Vs= 32.19 KNS
Tu= 2.01 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1904J____________________ 3125X 250X 500_____________________1870J____


| |
| ======================================================||
| 4No16 H 457. 868.TO 3125 |
| | 6*10c/c230 |
| | |
| 5No10 H 40. 0.TO 1857 | |
||============================================ |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 154

=====================================================================

BEAM NO. 2344 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2118. YES NO


2 457. 3 - 16MM 1068. 3125. NO YES

B E A M N O. 2344 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 8.94 KNS Vc= 94.22 KNS Vs= 0.00 KNS
Tu= 0.78 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 89.24 KNS Vc= 94.22 KNS Vs= 24.77 KNS
Tu= 0.78 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1905J____________________ 3125X 250X 500_____________________1867J____


| |
| ==================================================||
| 3No16 H 457.1068.TO 3125| |
| | | 6*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2118 | | |
||================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 155

=====================================================================

BEAM NO. 2345 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 4 - 12MM 0. 2677. YES NO


2 460. 5 - 10MM 2083. 3125. NO YES

B E A M N O. 2345 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 3.36 KNS Vc= 94.12 KNS Vs= 0.00 KNS
Tu= 0.09 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 51.02 KNS Vc= 94.12 KNS Vs= 0.00 KNS
Tu= 0.09 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1906J____________________ 3125X 250X 500_____________________1864J____


| =========================||
| |5No10|H 460.2083.TO 3125 |
| | | | |
| | | 6*10c/c230 |
| | | | |
| 4No12 H 41. 0.TO 2677 | | | |
||================================================================ |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | ooooo | | ooooo | | ooooo |
| | | | | | | | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | |
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 156

=====================================================================

BEAM NO. 2346 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 143. 3500. NO YES


2 460. 5 - 10MM 0. 974. YES NO

B E A M N O. 2346 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 53.70 KNS Vc= 94.35 KNS Vs= 0.00 KNS
Tu= 3.25 KN-MET Tc= 3.2 KN-MET Ts= 4.3 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1295. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.04 SQ.CM.

AT END SUPPORT - Vu= 15.52 KNS Vc= 94.35 KNS Vs= 0.00 KNS
Tu= 3.25 KN-MET Tc= 3.2 KN-MET Ts= 4.3 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1295. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.04 SQ.CM.

___1852J____________________ 3499X 250X 500_____________________1899J____


||==================== |
| 5No10 H 460.| 0.TO 974 |
| | | | | |
| 10*10c/c151 | | 10*10c/c151 |
| | | | | |
| 5No10 H 40. 143.TO 3500 |
| ========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | | | | | | | | | |
| 5#10 | | 5#10 | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 157

=====================================================================

BEAM NO. 2347 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1018. 3500. NO YES


2 455. 2 - 20MM 0. 2240. YES NO

B E A M N O. 2347 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 76.98 KNS Vc= 94.32 KNS Vs= 8.32 KNS
Tu= 0.54 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 7.76 KNS Vc= 94.32 KNS Vs= 0.00 KNS
Tu= 0.54 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1855J____________________ 3500X 250X 500_____________________1903J____


| |
||=============================================== |
| 2No20 H 455. 0.TO 2240 | | |
| 7*10c/c230 | | | |
| | | | |
| |5No10 H 40.1018.TO 3500 |
| =====================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oo | | oo | | oo | | oo | | | | | | |
| 2#20 | | 2#20 | | 2#20 | | 2#20 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 158

=====================================================================

BEAM NO. 2348 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2336. YES NO


2 457. 3 - 16MM 1271. 3500. NO YES

B E A M N O. 2348 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.69 KNS Vc= 94.31 KNS Vs= 0.00 KNS
Tu= 2.54 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 69.91 KNS Vc= 94.31 KNS Vs= 0.00 KNS
Tu= 2.54 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1899J____________________ 3499X 250X 500_____________________1855J____


| |
| ================================================||
| 3No16 H 457.1271.TO 3500 |
| | | 7*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2336 | | |
||================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 159

=====================================================================

BEAM NO. 2349 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 3211. YES NO


2 460. 5 - 10MM 2088. 3500. NO YES

B E A M N O. 2349 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 7.85 KNS Vc= 94.32 KNS Vs= 0.00 KNS
Tu= 1.46 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 61.37 KNS Vc= 94.32 KNS Vs= 0.00 KNS
Tu= 1.46 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1903J____________________ 3499X 250X 500_____________________1859J____


| ==============================||
| 5No10 H 460.2088.TO 3500 |
| | | | | | |
| | | | 7*10c/c230 |
| | | | | | |
| 5No10 H 40. 0.TO 3211 | | | | | |
||==================================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | ooooo | | ooooo | | ooooo |
| | | | | | | | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 160

=====================================================================

BEAM NO. 2350 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 143. 3500. NO YES


2 457. 3 - 16MM 0. 2084. YES NO

B E A M N O. 2350 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 70.66 KNS Vc= 95.45 KNS Vs= 0.00 KNS
Tu= 0.17 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 1.44 KNS Vc= 89.93 KNS Vs= 0.00 KNS
Tu= 0.17 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1692J____________________ 3499X 250X 500_____________________1900J____


| |
||============================================ |
| 3No16|H 457. 0.TO 2084 | | |
| 7*10c/c230 | | | | |
| | | | | | | |
| 5No10 H |40. 143.TO 3500 | |
| ========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 161

=====================================================================

BEAM NO. 2351 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 4 - 12MM 693. 3500. NO YES


2 457. 4 - 16MM 0. 1992. YES NO

B E A M N O. 2351 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 102.88 KNS Vc= 95.05 KNS Vs= 42.11 KNS
Tu= 0.90 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 101
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 0.02 KNS Vc= 89.64 KNS Vs= 0.00 KNS
Tu= 0.89 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1856J____________________ 3500X 250X 500_____________________1904J____


| |
||========================================== |
| 4No16 H 457. 0.TO 1992 | | |
| 7*10c/c230 | | | | |
| | | | | |
| 4No12 H 41. 693.TO 3500 |
| ============================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oooo | | oooo | | oooo | | oooo | | | | | | |
| 4#16 | | 4#16 | | 4#16 | | 4#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 |
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 162

=====================================================================

BEAM NO. 2352 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2336. YES NO


2 457. 4 - 16MM 1071. 3500. NO YES

B E A M N O. 2352 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 7.65 KNS Vc= 90.41 KNS Vs= 0.00 KNS
Tu= 0.07 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 76.87 KNS Vc= 93.69 KNS Vs= 8.81 KNS
Tu= 0.07 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1900J____________________ 3499X 250X 500_____________________1856J____


| |
| ====================================================||
| 4No16 H 457.1071.TO 3500 | |
| | | 7*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2336 | | |
||================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 163

=====================================================================

BEAM NO. 2353 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 4 - 12MM 0. 2971. YES NO


2 457. 4 - 16MM 1071. 3500. NO YES

B E A M N O. 2353 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 3.29 KNS Vc= 89.81 KNS Vs= 0.00 KNS
Tu= 0.88 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 106.09 KNS Vc= 95.09 KNS Vs= 46.37 KNS
Tu= 0.88 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1904J____________________ 3499X 250X 500_____________________1707J____


| |
| ====================================================||
| 4No16 H 457.1071.TO 3500 | | | | |
| | | | | 7*10c/c230 |
| | | | | | |
| 4No12 H 41. 0.TO 2971 | | | | | |
||=============================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | |
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 164

=====================================================================

BEAM NO. 2354 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 3500. YES YES


2 460. 5 - 10MM 0. 1266. YES NO

B E A M N O. 2354 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 57.87 KNS Vc= 108.85 KNS Vs= 0.00 KNS
Tu= 0.14 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 11.35 KNS Vc= 90.51 KNS Vs= 0.00 KNS
Tu= 0.14 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1853J____________________ 3499X 250X 500_____________________1901J____


||========================== |
| 5No10|H 460. 0.TO 1266 | |
| | | | | | | |
| 7*10c/c230 | | | |
| | | | | | | |
| 5No10|H 40. 0.TO 3500 | |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 165

=====================================================================

BEAM NO. 2355 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 726. 3500. NO YES


2 457. 4 - 16MM 0. 1992. YES NO

B E A M N O. 2355 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 100.78 KNS Vc= 94.33 KNS Vs= 40.03 KNS
Tu= 0.97 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 101
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 2.03 KNS Vc= 94.44 KNS Vs= 0.00 KNS
Tu= 0.97 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1857J____________________ 3500X 250X 500_____________________1905J____


| |
||========================================== |
| 4No16 H 457. 0.TO 1992 | | |
| 7*10c/c230 | | | | |
| | | | | |
| 5No10 H 40. 726.TO 3500 |
| ============================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oooo | | oooo | | oooo | | oooo | | | | | | |
| 4#16 | | 4#16 | | 4#16 | | 4#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 166

=====================================================================

BEAM NO. 2356 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1018. 3500. NO YES


2 457. 4 - 16MM 0. 2575. YES NO

B E A M N O. 2356 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 80.19 KNS Vc= 93.00 KNS Vs= 13.92 KNS
Tu= 0.66 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 10.96 KNS Vc= 90.66 KNS Vs= 0.00 KNS
Tu= 0.66 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1860J____________________ 3500X 250X 500_____________________1907J____


| |
||====================================================== |
| 4No16 H 457. 0.TO 2575 | | |
| 7*10c/c230 | | | |
| | | | |
| |5No10 H 40.1018.TO 3500 |
| =====================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oooo | | oooo | | oooo | | oooo | | oooo | | | | |
| 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 167

=====================================================================

BEAM NO. 2357 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2336. YES NO


2 457. 4 - 16MM 1071. 3500. NO YES

B E A M N O. 2357 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 8.81 KNS Vc= 90.48 KNS Vs= 0.00 KNS
Tu= 0.22 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 78.03 KNS Vc= 93.19 KNS Vs= 10.85 KNS
Tu= 0.22 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1901J____________________ 3499X 250X 500_____________________1857J____


| |
| ====================================================||
| 4No16 H 457.1071.TO 3500 | |
| | | 7*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2336 | | |
||================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 168

=====================================================================

BEAM NO. 2358 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2628. YES NO


2 457. 4 - 16MM 1071. 3500. NO YES

B E A M N O. 2358 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.06 KNS Vc= 94.43 KNS Vs= 0.00 KNS
Tu= 0.03 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 102.74 KNS Vc= 94.33 KNS Vs= 42.65 KNS
Tu= 0.03 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 101
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1905J____________________ 3499X 250X 500_____________________1860J____


| |
| ====================================================||
| 4No16 H 457.1071.TO 3500 | | |
| | | | 7*10c/c230 |
| | | | |
| 5No10 H 40. 0.TO 2628 | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 169

=====================================================================

BEAM NO. 2359 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 3211. YES NO


2 460. 5 - 10MM 2380. 3500. NO YES

B E A M N O. 2359 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 11.35 KNS Vc= 90.53 KNS Vs= 0.00 KNS
Tu= 0.46 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 57.87 KNS Vc= 107.50 KNS Vs= 0.00 KNS
Tu= 0.46 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1907J____________________ 3500X 250X 500_____________________1862J____


| ========================||
| 5No10 H 460.2380.TO 3500 |
| | | | | |
| | | 7*10c/c230 |
| | | | | |
| 5No10 H 40. 0.TO 3211 | | | | |
||==================================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | ooooo | | ooooo |
| | | | | | | | | | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 170

=====================================================================

BEAM NO. 2360 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 143. 3500. NO YES


2 460. 5 - 10MM 0. 974. YES NO

B E A M N O. 2360 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 53.37 KNS Vc= 105.94 KNS Vs= 0.00 KNS
Tu= 3.29 KN-MET Tc= 3.2 KN-MET Ts= 4.4 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1295. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.05 SQ.CM.

AT END SUPPORT - Vu= 15.85 KNS Vc= 91.12 KNS Vs= 0.00 KNS
Tu= 3.29 KN-MET Tc= 3.2 KN-MET Ts= 4.4 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1295. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.05 SQ.CM.

___1854J____________________ 3499X 250X 500_____________________1902J____


||==================== |
| 5No10 H 460.| 0.TO 974 |
| | | | | |
| 10*10c/c151 | | 10*10c/c151 |
| | | | | |
| 5No10 H 40. 143.TO 3500 |
| ========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | | | | | | | | | |
| 5#10 | | 5#10 | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 171

=====================================================================

BEAM NO. 2361 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 726. 3500. NO YES


2 457. 4 - 16MM 0. 1992. YES NO

B E A M N O. 2361 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 72.58 KNS Vc= 93.81 KNS Vs= 2.96 KNS
Tu= 0.92 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 3.35 KNS Vc= 90.09 KNS Vs= 0.00 KNS
Tu= 0.92 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1858J____________________ 3500X 250X 500_____________________1906J____


| |
||========================================== |
| 4No16 H 457. 0.TO 1992 | | |
| 7*10c/c230 | | | | |
| | | | | |
| 5No10 H 40. 726.TO 3500 |
| ============================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oooo | | oooo | | oooo | | oooo | | | | | | |
| 4#16 | | 4#16 | | 4#16 | | 4#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 172

=====================================================================

BEAM NO. 2362 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1018. 3500. NO YES


2 457. 3 - 16MM 0. 2375. YES NO

B E A M N O. 2362 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 71.70 KNS Vc= 93.58 KNS Vs= 2.02 KNS
Tu= 0.17 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 2.48 KNS Vc= 90.06 KNS Vs= 0.00 KNS
Tu= 0.17 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1861J____________________ 3500X 250X 500_____________________1908J____


| |
||================================================== |
| 3No16 H 457. 0.TO 2375 | | |
| 7*10c/c230 | | | |
| | | | |
| |5No10 H 40.1018.TO 3500 |
| =====================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 173

=====================================================================

BEAM NO. 2363 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2336. YES NO


2 457. 3 - 16MM 979. 3500. NO YES

B E A M N O. 2363 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.52 KNS Vc= 89.89 KNS Vs= 0.00 KNS
Tu= 2.59 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 68.70 KNS Vc= 93.54 KNS Vs= 0.00 KNS
Tu= 2.59 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1902J____________________ 3499X 250X 500_____________________1858J____


| |
| ======================================================||
| 3No16 H 457. 979.TO 3500 | |
| | | 7*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2336 | | |
||================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | ooo | | ooo | | ooo | | ooo | | ooo |
| | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 174

=====================================================================

BEAM NO. 2364 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2628. YES NO


2 457. 4 - 16MM 1363. 3500. NO YES

B E A M N O. 2364 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 4.34 KNS Vc= 90.17 KNS Vs= 0.00 KNS
Tu= 1.19 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 73.56 KNS Vc= 93.69 KNS Vs= 4.39 KNS
Tu= 1.19 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1906J____________________ 3499X 250X 500_____________________1861J____


| |
| ==============================================||
| 4No16 H 457.1363.TO|3500| |
| | | | 7*10c/c230 |
| | | | |
| 5No10 H 40. 0.TO 2628 | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | oooo | | oooo | | oooo | | oooo |
| | | | | | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 175

=====================================================================

BEAM NO. 2365 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2336. YES NO


2 457. 3 - 16MM 1271. 3500. NO YES

B E A M N O. 2365 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 1.60 KNS Vc= 89.98 KNS Vs= 0.00 KNS
Tu= 1.00 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 70.82 KNS Vc= 93.66 KNS Vs= 0.77 KNS
Tu= 1.00 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1908J____________________ 3500X 250X 500_____________________1863J____


| |
| ================================================||
| 3No16 H 457.1271.TO 3500 |
| | | 7*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2336 | | |
||================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 176

=====================================================================

BEAM NO. 2366 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1018. 3500. NO YES


2 455. 2 - 20MM 0. 1948. YES NO

B E A M N O. 2366 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 78.57 KNS Vc= 94.01 KNS Vs= 10.75 KNS
Tu= 0.42 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 9.35 KNS Vc= 90.38 KNS Vs= 0.00 KNS
Tu= 0.42 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1863J____________________ 3500X 250X 500_____________________1909J____


| |
||========================================= |
| 2No20 H 455. 0.TO 1948 | | |
| 7*10c/c230 | | | |
| | | | |
| |5No10 H 40.1018.TO 3500 |
| =====================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oo | | oo | | oo | | oo | | | | | | |
| 2#20 | | 2#20 | | 2#20 | | 2#20 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 177

=====================================================================

BEAM NO. 2367 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2628. YES NO


2 457. 3 - 16MM 1562. 3500. NO YES

B E A M N O. 2367 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 7.33 KNS Vc= 90.22 KNS Vs= 0.00 KNS
Tu= 0.03 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 76.55 KNS Vc= 94.88 KNS Vs= 7.19 KNS
Tu= 0.03 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1909J____________________ 3499X 250X 500_____________________1737J____


| |
| ==========================================||
| 3No16 H 457.1562.TO 3500 |
| | | | 7*10c/c230 |
| | | | |
| 5No10 H 40. 0.TO 2628 | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 178

=====================================================================

BEAM NO. 2412 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 96. 3125. NO YES


2 460. 5 - 10MM 0. 912. YES NO

B E A M N O. 2412 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 53.73 KNS Vc= 125.16 KNS Vs= 0.00 KNS
Tu= 0.29 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 0.65 KNS Vc= 89.87 KNS Vs= 0.00 KNS
Tu= 0.29 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1871J____________________ 3125X 250X 500_____________________1907J____


||===================== |
| 5No10 H 460.| 0.TO 912 |
| | | | | |
| 6*10c/c230 | | |
| | | | | |
| |5No10|H 40. 96.TO 3125 |
| =========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | | | | | | | | | |
| 5#10 | | 5#10 | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 179

=====================================================================

BEAM NO. 2413 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 877. 3125. NO YES


2 457. 3 - 16MM 0. 1927. YES NO

B E A M N O. 2413 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 70.21 KNS Vc= 93.93 KNS Vs= 0.00 KNS
Tu= 0.77 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 15.83 KNS Vc= 90.97 KNS Vs= 0.00 KNS
Tu= 0.77 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1868J____________________ 3125X 250X 500_____________________1908J____


| |
||============================================= |
| 3No16 H 457. 0.TO 1927| | |
| 6*10c/c230 | | |
| | | |
| 5No10 H 40. 877.TO 3125 |
| ======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 180

=====================================================================

BEAM NO. 2414 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2118. YES NO


2 457. 3 - 16MM 1068. 3125. NO YES

B E A M N O. 2414 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 18.81 KNS Vc= 91.10 KNS Vs= 0.00 KNS
Tu= 0.91 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 73.18 KNS Vc= 93.80 KNS Vs= 3.78 KNS
Tu= 0.91 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1907J____________________ 3125X 250X 500_____________________1868J____


| |
| ==================================================||
| 3No16 H 457.1068.TO 3125| |
| | | 6*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2118 | | |
||================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 181

=====================================================================

BEAM NO. 2415 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2899. YES NO


2 460. 5 - 10MM 2083. 3125. NO YES

B E A M N O. 2415 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 2.14 KNS Vc= 89.96 KNS Vs= 0.00 KNS
Tu= 0.20 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 52.29 KNS Vc= 139.26 KNS Vs= 0.00 KNS
Tu= 0.21 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 101
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1908J____________________ 3125X 250X 500_____________________1865J____


| =========================||
| |5No10|H 460.2083.TO 3125 |
| | | | | |
| | | 6*10c/c230 |
| | | | | |
| 5No10 H 40. 0.TO 2899 | | | | |
||===================================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | ooooo | | ooooo | | ooooo |
| | | | | | | | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco clxxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 182

=====================================================================

BEAM NO. 2416 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 356. 3125. NO YES


2 460. 5 - 10MM 0. 912. YES NO

B E A M N O. 2416 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 54.56 KNS Vc= 111.49 KNS Vs= 0.00 KNS
Tu= 2.49 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 0.18 KNS Vc= 89.84 KNS Vs= 0.00 KNS
Tu= 2.49 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1876J____________________ 3125X 250X 500_____________________1909J____


||===================== |
| 5No10 H 460.| 0.TO 912 |
| | | | |
| 6*10c/c230 | | |
| | | | |
| |5No10|H 40. 356.TO 3125 |
| ===================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | | | | | | | | | |
| 5#10 | | 5#10 | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxc
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 183

=====================================================================

BEAM NO. 2417 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2638. YES NO


2 460. 5 - 10MM 2083. 3125. NO YES

B E A M N O. 2417 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.92 KNS Vc= 89.89 KNS Vs= 0.00 KNS
Tu= 2.33 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 55.30 KNS Vc= 108.02 KNS Vs= 0.00 KNS
Tu= 2.33 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

___1909J____________________ 3125X 250X 500_____________________1875J____


| =========================||
| |5No10|H 460.2083.TO 3125 |
| | | | |
| | | 6*10c/c230 |
| | | | |
| 5No10 H 40. 0.TO 2638 | | | |
||=============================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | ooooo | | ooooo | | ooooo |
| | | | | | | | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

********************END OF BEAM DESIGN**************************

2415. DESIGN BEAM _T_SEC_NA


STAAD SPACE -- PAGE NO. 184

=====================================================================

BEAM NO. 2322 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxci
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 3500. YES YES


2 460. 5 - 10MM 0. 1266. YES NO

B E A M N O. 2322 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 62.30 KNS Vc= 107.62 KNS Vs= 0.00 KNS
Tu= 0.76 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 6.92 KNS Vc= 90.18 KNS Vs= 0.00 KNS
Tu= 0.76 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1877J____________________ 3500X 250X 500_____________________1897J____


||========================== |
| 5No10|H 460. 0.TO 1266 | |
| | | | | | | |
| 7*10c/c230 | | | |
| | | | | | | |
| 5No10|H 40. 0.TO 3500 | |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxcii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 185

=====================================================================

BEAM NO. 2323 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 3500. YES YES


2 460. 5 - 10MM 2088. 3500. NO YES

B E A M N O. 2323 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 7.34 KNS Vc= 90.20 KNS Vs= 0.00 KNS
Tu= 0.83 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 61.88 KNS Vc= 109.63 KNS Vs= 0.00 KNS
Tu= 0.83 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1897J____________________ 3499X 250X 500_____________________1879J____


| ==============================||
| 5No10 H 460.2088.TO 3500 | |
| | | | | | | |
| | | | 7*10c/c230 | |
| | | | | | | |
| 5No10 H 40. 0.TO 3500 | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | ooooo | | ooooo | | ooooo |
| | | | | | | | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxciii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 186

=====================================================================

BEAM NO. 2324 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 3500. YES YES


2 460. 5 - 10MM 0. 1266. YES NO

B E A M N O. 2324 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 62.51 KNS Vc= 109.59 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 6.71 KNS Vc= 90.17 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1878J____________________ 3500X 250X 500_____________________1898J____


||========================== |
| 5No10|H 460. 0.TO 1266 | |
| | | | | | | |
| 7*10c/c230 | | | |
| | | | | | | |
| 5No10|H 40. 0.TO 3500 | |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxciv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 187

=====================================================================

BEAM NO. 2325 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 3500. YES YES


2 460. 5 - 10MM 2088. 3500. NO YES

B E A M N O. 2325 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 6.63 KNS Vc= 90.16 KNS Vs= 0.00 KNS
Tu= 1.29 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 62.59 KNS Vc= 109.59 KNS Vs= 0.00 KNS
Tu= 1.29 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

___1898J____________________ 3499X 250X 500_____________________1880J____


| ==============================||
| 5No10 H 460.2088.TO 3500 | |
| | | | | | | |
| | | | 7*10c/c230 | |
| | | | | | | |
| 5No10 H 40. 0.TO 3500 | | | | | | |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | ooooo | | ooooo | | ooooo |
| | | | | | | | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxcv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 188

=====================================================================

BEAM NO. 2326 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 4 - 12MM 67. 3125. NO YES


2 460. 5 - 10MM 0. 1172. YES NO

B E A M N O. 2326 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 60.55 KNS Vc= 112.39 KNS Vs= 0.00 KNS
Tu= 0.05 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 6.17 KNS Vc= 89.94 KNS Vs= 0.00 KNS
Tu= 0.05 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1883J____________________ 3125X 250X 500_____________________1897J____


||=========================== |
| 5No10 H 460.| 0.TO 1172| |
| | | | | | |
| 6*10c/c230 | | | |
| | | | | | |
| 4No12 H 41.| 67.TO 3125| |
|==========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 |
| | | oooo | | oooo | | oooo | | oooo | | oooo | | oooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxcvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 189

=====================================================================

BEAM NO. 2327 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 875. 3125. NO YES


2 457. 4 - 16MM 0. 2127. YES NO

B E A M N O. 2327 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 79.98 KNS Vc= 93.69 KNS Vs= 12.96 KNS
Tu= 0.42 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 25.61 KNS Vc= 91.32 KNS Vs= 0.00 KNS
Tu= 0.42 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1882J____________________ 3125X 250X 500_____________________1898J____


| |
||================================================== |
| 4No16 H 457. 0.TO 2127| | |
| 6*10c/c230 | | |
| | | |
| 5No10 H 40. 875.TO 3125 |
| ======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oooo | | oooo | | oooo | | oooo | | oooo | | | | |
| 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxcvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 190

=====================================================================

BEAM NO. 2328 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 2 - 16MM 0. 2036. YES NO


2 457. 4 - 16MM 868. 3125. NO YES

B E A M N O. 2328 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 25.87 KNS Vc= 90.73 KNS Vs= 0.00 KNS
Tu= 0.10 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 80.25 KNS Vc= 93.24 KNS Vs= 13.76 KNS
Tu= 0.10 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 228. MM C/C FOR 1108. MM

___1897J____________________ 3125X 250X 500_____________________1882J____


| |
| ======================================================||
| 4No16 H 457. 868.TO 3125 |
| | 6*10c/c229 |
| 2No16 H 43. 0.TO 2036 | |
||================================================ |
| |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| | | | | | | | | | | | | |
| 2#16 | | 2#16 | | 2#16 | | 2#16 | | | | | | |
| oo | | oo | | oo | | oo | | | | | | |
| | | | | | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxcviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 191

=====================================================================

BEAM NO. 2329 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 2 - 16MM 0. 3077. YES NO


2 460. 5 - 10MM 1823. 3125. NO YES

B E A M N O. 2329 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 5.51 KNS Vc= 89.52 KNS Vs= 0.00 KNS
Tu= 0.64 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 59.89 KNS Vc= 110.54 KNS Vs= 0.00 KNS
Tu= 0.64 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 228. MM C/C FOR 1108. MM

___1898J____________________ 3125X 250X 500_____________________1881J____


| ===============================||
| |5No10|H 460.1823.TO 3125 | |
| | | | | | | |
| | | | 6*10c/c229 | |
| 2No16 H 43. 0.TO 3077 | | | | | | |
||========================================================================= |
| |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | ooooo | | ooooo | | ooooo |
| | | | | | | | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 2#16 | | 2#16 | | 2#16 | | 2#16 | | 2#16 | | 2#16 | | |
| oo | | oo | | oo | | oo | | oo | | oo | | |
| | | | | | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

********************END OF BEAM DESIGN**************************

2416. * DISEムO DE TRABES DE SモTANO

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cxcix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 192

=====================================================================

BEAM NO. 1923 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 630. 3125. NO YES


2 555. 4 - 20MM 0. 2464. YES NO

B E A M N O. 1923 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 145.89 KNS Vc= 140.55 KNS Vs= 53.97 KNS
Tu= 3.03 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1007. MM

AT END SUPPORT - Vu= 87.56 KNS Vc= 136.11 KNS Vs= 0.00 KNS
Tu= 3.03 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1007. MM

___ 6J____________________ 3125X 300X 600_____________________1884J____


||========================================================== |
| 4No20 H 555. |0.TO 2464 | | | |
| | | | | | |
| 5*10c/c278 | | | | | 5*10c/c278 |
| | | | | | |
| 3No20 H| 45. 630.TO 3125 | | |
| ============================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | | | |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 |
| | | | | ooo | | ooo | | ooo | | ooo | | ooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cc
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 193

=====================================================================

BEAM NO. 1924 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2080. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 793. 2080. NO YES


2 553. 3 - 25MM 0. 2080. YES YES

B E A M N O. 1924 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 195.35 KNS Vc= 139.29 KNS Vs= 121.18 KNS
Tu= 0.89 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 485. MM

AT END SUPPORT - Vu= 113.94 KNS Vc= 196.32 KNS Vs= 0.00 KNS
Tu= 10.63 KN-MET Tc= 6.2 KN-MET Ts= 14.2 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 485. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.64 SQ.CM.

___ 7J____________________ 2080X 300X 600_____________________1929J____


||=========================================================================||
| 3No25 H 553. 0.TO 2080 | | | | |
| | | | | |
| 3*10c/c280 | | 4*10c/c188 | |
| | | | | |
| 6No12 H 41. 793.TO 2080| | | | |
| ===============================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | 6#12 | | 6#12 | | 6#12 | | 6#12 |
| | | | | | |oooooo | |oooooo | |oooooo | |oooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cci
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 194

=====================================================================

BEAM NO. 1925 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1925. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 5 - 12MM 845. 1925. NO YES


2 553. 3 - 25MM 0. 1925. YES YES

B E A M N O. 1925 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 193.08 KNS Vc= 138.53 KNS Vs= 118.91 KNS
Tu= 0.75 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 408. MM

AT END SUPPORT - Vu= 173.89 KNS Vc= 244.02 KNS Vs= 0.00 KNS
Tu= 0.75 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 408. MM

___ 8J____________________ 1925X 300X 600_____________________1949J____


||=========================================================================||
| 3No25 H 553. 0.TO 1925 | | | |
| | | | |
| 3*10c/c280 | 3*10c/c280 | |
| | | | |
| 5No12 H 41. 845.TO 1925 | | |
| ==========================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | 5#12 | | 5#12 | | 5#12 | | 5#12 |
| | | | | | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 195

=====================================================================

BEAM NO. 1926 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 598. 3125. NO YES


2 555. 4 - 20MM 0. 2464. YES NO

B E A M N O. 1926 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 155.17 KNS Vc= 140.52 KNS Vs= 66.37 KNS
Tu= 2.58 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1007. MM

AT END SUPPORT - Vu= 96.84 KNS Vc= 136.90 KNS Vs= 0.00 KNS
Tu= 2.58 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1007. MM

___ 9J____________________ 3125X 300X 600_____________________1887J____


||========================================================== |
| 4No20 H 555. |0.TO 2464 | | | |
| | | | | | |
| 5*10c/c278 | | | | | 5*10c/c278 |
| | | | | | |
| 3No20 H |45. 598.TO 3125 | | |
| =============================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | | | |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 |
| | | | | ooo | | ooo | | ooo | | ooo | | ooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cciii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 196

=====================================================================

BEAM NO. 1927 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1389. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 5 - 12MM 857. 1389. NO YES


2 555. 4 - 20MM 0. 1389. YES YES

B E A M N O. 1927 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 175.33 KNS Vc= 138.80 KNS Vs= 94.97 KNS
Tu= 10.62 KN-MET Tc= 5.7 KN-MET Ts= 14.2 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 139. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.64 SQ.CM.

AT END SUPPORT - Vu= 169.59 KNS Vc= 143.50 KNS Vs= 82.62 KNS
Tu= 10.62 KN-MET Tc= 5.7 KN-MET Ts= 14.2 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 139. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.64 SQ.CM.

___ 13J____________________ 1388X 300X 600_____________________1936J____


||=========================================================================||
| 4No20 H 555. 0.TO 1389 | | |
| | | |
| 2*10c/c188 2*10c/c188 | |
| | | |
| 5No12 H 41. 857.TO 1389 | |
| =============================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | oooo |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | 5#12 | | 5#12 | | 5#12 |
| | | | | | | | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cciv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 197

=====================================================================

BEAM NO. 1928 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 694. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 555. 3 - 20MM 0. 694. YES YES

B E A M N O. 1928 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 1928 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 1928 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 14J____________________ 694X 300X 600_____________________1940J____


||=========================================================================||
| 3No20 H 555. 0.TO 694 |
| |
| |
| |
| |
| |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 198

=====================================================================

BEAM NO. 1930 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3111. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 756. 3111. NO YES


2 555. 4 - 20MM 0. 2717. YES NO

B E A M N O. 1930 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 141.67 KNS Vc= 137.96 KNS Vs= 50.94 KNS
Tu= 5.00 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1001. MM

AT END SUPPORT - Vu= 77.93 KNS Vc= 135.90 KNS Vs= 0.00 KNS
Tu= 5.00 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1001. MM

___ 4J____________________ 3111X 300X 600_____________________1924J____


||================================================================= |
| 4No20 H 555. 0.TO 2717 | | | | |
| | | | | | |
| 5*10c/c279 | | | | | 5*10c/c279 |
| | | | | | |
| 4No16 H 43. 756.TO 3111 | | | |
| =========================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 199

=====================================================================

BEAM NO. 1931 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4670. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 637. 4670. NO YES


2 557. 5 - 16MM 0. 2771. YES NO

B E A M N O. 1931 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 122.46 KNS Vc= 137.18 KNS Vs= 26.11 KNS
Tu= 1.49 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 1780. MM

AT END SUPPORT - Vu= 14.01 KNS Vc= 131.72 KNS Vs= 0.00 KNS
Tu= 1.49 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___ 9J____________________ 4670X 300X 600_____________________1891J____


||============================================ |
| 5No16 H 557. 0.TO 2771 | | | |
| | | | | | | |
| 8*10c/c280 | | | | | |
| | | | | | | |
| 6No12 H 41. 637.TO 4670 | |
| =================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
| 5#16 | | 5#16 | | 5#16 | | 5#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 |
| | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 200

=====================================================================

BEAM NO. 1932 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 454. 3500. NO YES


2 555. 4 - 20MM 0. 2652. YES NO

B E A M N O. 1932 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 132.75 KNS Vc= 138.59 KNS Vs= 38.40 KNS
Tu= 1.90 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1195. MM

AT END SUPPORT - Vu= 86.06 KNS Vc= 135.87 KNS Vs= 0.00 KNS
Tu= 1.90 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1195. MM

___ 14J____________________ 3500X 300X 600_____________________1892J____


||======================================================== |
| 4No20 H|555. |0.TO 2652 | | | | |
| | | | | | | | |
| 6*10c/c278 | | | | | | 6*10c/c278 |
| | | | | | | | |
| |3No20 H 45. 454.TO 3500 | | | |
| ==================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | | | |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 |
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 201

=====================================================================

BEAM NO. 1933 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3111. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 807. 3111. NO YES


2 555. 4 - 20MM 0. 2717. YES NO

B E A M N O. 1933 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 141.73 KNS Vc= 138.37 KNS Vs= 50.61 KNS
Tu= 7.36 KN-MET Tc= 5.7 KN-MET Ts= 9.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 1001. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.83 SQ.CM.

AT END SUPPORT - Vu= 77.99 KNS Vc= 136.58 KNS Vs= 0.00 KNS
Tu= 7.36 KN-MET Tc= 5.7 KN-MET Ts= 9.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 1001. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.83 SQ.CM.

___ 3J____________________ 3111X 300X 600_____________________1926J____


||================================================================= |
| 4No20 H 555. 0.TO 2717 | | | | | | | |
| | | | | | | | | |
| 7*10c/c188 | | | | | | | 7*10c/c188 |
| | | | | | | | | |
| 6No12 H| 41.|807.TO 3111| | | | | |
| ========================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 |
| | | | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 202

=====================================================================

BEAM NO. 1934 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4670. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 3 - 16MM 513. 4670. NO YES


2 555. 3 - 20MM 0. 2727. YES NO

B E A M N O. 1934 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 109.24 KNS Vc= 136.39 KNS Vs= 9.26 KNS
Tu= 1.84 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1780. MM

AT END SUPPORT - Vu= 12.66 KNS Vc= 131.19 KNS Vs= 0.00 KNS
Tu= 1.84 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___ 8J____________________ 4670X 300X 600_____________________1894J____


||=========================================== |
| 3No20 H 555. 0.TO 2727 | | | |
| | | | | | | |
| 8*10c/c279 | | | | | |
| | | | | | | |
| 3No16 H |43. 513.TO 4670 | |
| ===================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#20 | | 3#20 | | 3#20 | | 3#20 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 203

=====================================================================

BEAM NO. 1935 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3111. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 707. 3111. NO YES


2 555. 4 - 20MM 0. 2717. YES NO

B E A M N O. 1935 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 148.88 KNS Vc= 138.84 KNS Vs= 59.66 KNS
Tu= 4.95 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1001. MM

AT END SUPPORT - Vu= 87.69 KNS Vc= 136.67 KNS Vs= 0.00 KNS
Tu= 4.95 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1001. MM

___ 2J____________________ 3111X 300X 600_____________________1895J____


||================================================================= |
| 4No20 H 555. 0.TO 2717 | | | | |
| | | | | | |
| 5*10c/c279 | | | | | 5*10c/c279 |
| | | | | | |
| 4No16|H 43.|707.TO 3111 | | | |
| ==========================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 204

=====================================================================

BEAM NO. 1936 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4670. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 634. 4670. NO YES


2 553. 2 - 25MM 0. 2953. YES NO

B E A M N O. 1936 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 122.95 KNS Vc= 137.40 KNS Vs= 26.54 KNS
Tu= 1.76 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 1780. MM

AT END SUPPORT - Vu= 12.77 KNS Vc= 131.65 KNS Vs= 0.00 KNS
Tu= 1.76 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___ 7J____________________ 4670X 300X 600_____________________1896J____


||=============================================== |
| 2No25 H 553. 0.TO 2953 | | | |
| | | | | | | |
| 8*10c/c280 | | | | | |
| | | | | | | |
| 6No12 H 41. 634.TO 4670 | |
| =================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oo | | oo | | oo | | oo | | | | | | |
| 2#25 | | 2#25 | | 2#25 | | 2#25 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 |
| | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 205

=====================================================================

BEAM NO. 2309 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 2381. YES NO


2 555. 4 - 20MM 530. 3125. NO YES

B E A M N O. 2309 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 66.02 KNS Vc= 138.43 KNS Vs= 0.00 KNS
Tu= 8.48 KN-MET Tc= 6.1 KN-MET Ts= 11.3 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 1007. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.11 SQ.CM.

AT END SUPPORT - Vu= 153.17 KNS Vc= 140.14 KNS Vs= 64.09 KNS
Tu= 3.82 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1007. MM

___1884J____________________ 3125X 300X 600_____________________ 7J____


| ===============================================================||
| |4No20 H 555. 530.TO|3125 | | |
| | | | | | | | |
| 7*10c/c188 | | | | | | 5*10c/c278 |
| | | | | | | | |
| 3No20 H 45. 0.TO 2381 | | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 206

=====================================================================

BEAM NO. 2311 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1200. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 3 - 16MM 0. 1200. YES YES

B E A M N O. 2311 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 13.93 KNS Vc= 131.25 KNS Vs= 0.00 KNS
Tu= 0.18 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 16.28 KNS Vc= 131.38 KNS Vs= 0.00 KNS
Tu= 0.18 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1886J____________________ 1199X 300X 600_____________________1953J____


| |
| |
| |
| |
| |
| 3No16 H 43. 0.TO 1200 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 207

=====================================================================

BEAM NO. 2312 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 2381. YES NO


2 555. 4 - 20MM 530. 3125. NO YES

B E A M N O. 2312 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 91.35 KNS Vc= 136.41 KNS Vs= 0.00 KNS
Tu= 1.66 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1007. MM

AT END SUPPORT - Vu= 149.68 KNS Vc= 140.68 KNS Vs= 58.89 KNS
Tu= 1.66 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1007. MM

___1887J____________________ 3125X 300X 600_____________________ 10J____


| ===============================================================||
| 4No20 H 555. 530.TO 3125 | | |
| | | | | | |
| 5*10c/c278 | | | | | 5*10c/c278 |
| | | | | | |
| 3No20 H 45. |0.TO 2381 | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 208

=====================================================================

BEAM NO. 2313 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1200. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 1200. YES YES

B E A M N O. 2313 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 32.21 KNS Vc= 132.80 KNS Vs= 0.00 KNS
Tu= 16.73 KN-MET Tc= 5.7 KN-MET Ts= 22.3 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 45. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.16 SQ.CM.

AT END SUPPORT - Vu= 34.13 KNS Vc= 132.97 KNS Vs= 0.00 KNS
Tu= 16.73 KN-MET Tc= 5.7 KN-MET Ts= 22.3 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 45. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.16 SQ.CM.

___1888J____________________ 1199X 300X 600_____________________1955J____


| |
| |
| |
| 2*10c/c188 2*10c/c188 |
| |
| 6No12 H 41. 0.TO 1200 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 |
|oooooo | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 209

=====================================================================

BEAM NO. 2314 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1736. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 5 - 12MM 0. 1736. YES YES

B E A M N O. 2314 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 30.49 KNS Vc= 137.46 KNS Vs= 0.00 KNS
Tu= 29.00 KN-MET Tc= 5.5 KN-MET Ts= 38.7 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 164. MM C/C FOR 313. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 7.21 SQ.CM.

AT END SUPPORT - Vu= 46.14 KNS Vc= 137.46 KNS Vs= 0.00 KNS
Tu= 29.00 KN-MET Tc= 5.5 KN-MET Ts= 38.7 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 164. MM C/C FOR 313. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 7.21 SQ.CM.

___1889J____________________ 1736X 300X 600_____________________1942J____


| |
| |
| |
| 3*10c/c164 3*10c/c164 |
| |
| 5No12 H 41. 0.TO 1736 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 210

=====================================================================

BEAM NO. 2315 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2820. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 2 - 20MM 0. 2235. YES NO


2 555. 4 - 20MM 156. 2820. NO YES

B E A M N O. 2315 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 65.00 KNS Vc= 142.17 KNS Vs= 0.00 KNS
Tu= 9.75 KN-MET Tc= 6.1 KN-MET Ts= 13.0 KN-MET LOAD 102
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 855. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.42 SQ.CM.

AT END SUPPORT - Vu= 142.47 KNS Vc= 136.68 KNS Vs= 53.27 KNS
Tu= 9.44 KN-MET Tc= 5.6 KN-MET Ts= 12.6 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 855. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.35 SQ.CM.

___1890J____________________ 2820X 300X 600_____________________ 9J____


| =======================================================================||
| 4No20 H 555. 156.TO 2820 | | | | |
| | | | | | | | | |
| 6*10c/c188 | | | | | | | 6*10c/c188 |
| | | | | | | | | |
| 2No20 H 45.| 0.TO 2235| | | | | |
||=========================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | oooo | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 | | | | |
| oo | | oo | | oo | | oo | | oo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 211

=====================================================================

BEAM NO. 2316 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2330. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 1502. YES NO


2 553. 3 - 25MM 0. 2330. YES YES

B E A M N O. 2316 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 143.76 KNS Vc= 149.75 KNS Vs= 41.93 KNS
Tu= 3.05 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 610. MM

AT END SUPPORT - Vu= 173.86 KNS Vc= 138.43 KNS Vs= 93.39 KNS
Tu= 3.05 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 610. MM

___1891J____________________ 2329X 300X 600_____________________ 14J____


||=========================================================================||
| 3No25 H 553. 0.TO 2330 | | |
| | | | | | |
| 4*10c/c280 | | | 4*10c/c280 |
| | | | | | |
| 6No12 H 41. 0.TO 1502 | | |
||=============================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 6#12 | | 6#12 | | 6#12 | | 6#12 | | | | | | |
|oooooo | |oooooo | |oooooo | |oooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 212

=====================================================================

BEAM NO. 2317 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 3 - 20MM 0. 2906. YES NO


2 555. 4 - 20MM 702. 3500. NO YES

B E A M N O. 2317 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 77.05 KNS Vc= 135.86 KNS Vs= 0.00 KNS
Tu= 1.42 KN-MET Tc= 5.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1195. MM

AT END SUPPORT - Vu= 131.32 KNS Vc= 135.86 KNS Vs= 39.23 KNS
Tu= 1.42 KN-MET Tc= 5.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1195. MM

___1892J____________________ 3500X 300X 600_____________________ 17J____


| ============================================================||
| 4No20 H|555. 702.TO 3500 | | | |
| | | | | | | | |
| 6*10c/c278 | | | | | | | 6*10c/c278 |
| | | | | | | | |
| 3No20 H 45. |0.TO 2906 | | | | | |
||============================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 213

=====================================================================

BEAM NO. 2318 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2820. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 3 - 16MM 0. 2119. YES NO


2 555. 4 - 20MM 156. 2820. NO YES

B E A M N O. 2318 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 57.56 KNS Vc= 138.74 KNS Vs= 0.00 KNS
Tu= 10.11 KN-MET Tc= 6.0 KN-MET Ts= 13.5 KN-MET LOAD 107
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 855. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.52 SQ.CM.

AT END SUPPORT - Vu= 134.12 KNS Vc= 137.11 KNS Vs= 41.72 KNS
Tu= 9.40 KN-MET Tc= 5.7 KN-MET Ts= 12.5 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 855. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.34 SQ.CM.

___1893J____________________ 2820X 300X 600_____________________ 8J____


| =======================================================================||
| 4No20 H 555. 156.TO 2820 | | | | |
| | | | | | | | | |
| 6*10c/c188 | | | | | | | 6*10c/c188 |
| | | | | | | | | |
| 3No16 H 43.| 0.TO 2119| | | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | oooo | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 214

=====================================================================

BEAM NO. 2319 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2330. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 5 - 12MM 0. 1522. YES NO


2 555. 4 - 20MM 0. 2330. YES YES

B E A M N O. 2319 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 116.56 KNS Vc= 144.74 KNS Vs= 10.68 KNS
Tu= 1.10 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 610. MM

AT END SUPPORT - Vu= 147.20 KNS Vc= 138.31 KNS Vs= 57.96 KNS
Tu= 1.10 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 610. MM

___1894J____________________ 2329X 300X 600_____________________ 13J____


||=========================================================================||
| 4No20 H 555. 0.TO 2330 | | |
| | | | | | |
| 4*10c/c280 | | | 4*10c/c280 |
| | | | | | |
| 5No12 H 41. 0.TO 1522 | | |
||================================================ |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | oooo |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#12 | | 5#12 | | 5#12 | | 5#12 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 215

=====================================================================

BEAM NO. 2320 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 389. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 0. 389. YES YES

B E A M N O. 2320 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 2320 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 2320 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___1895J____________________ 388X 300X 600_____________________1927J____


| |
| |
| |
| |
| |
| 4No16 H 43. 0.TO 389 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | oooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 216

=====================================================================

BEAM NO. 2321 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2330. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 2 - 20MM 0. 1947. YES NO


2 555. 4 - 20MM 0. 2330. YES YES

B E A M N O. 2321 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 130.22 KNS Vc= 145.25 KNS Vs= 28.38 KNS
Tu= 2.31 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 610. MM

AT END SUPPORT - Vu= 161.44 KNS Vc= 137.65 KNS Vs= 77.60 KNS
Tu= 2.31 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 610. MM

___1896J____________________ 2329X 300X 600_____________________ 12J____


||=========================================================================||
| 4No20 H 555. 0.TO 2330 | | | |
| | | | | | | |
| 4*10c/c278 | | | | 4*10c/c278 |
| | | | | | | |
| 2No20 H 45. 0.TO 1947 | | | |
||============================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | oooo |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 | | |
| oo | | oo | | oo | | oo | | oo | | oo | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 217

=====================================================================

BEAM NO. 2418 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1069. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 0. 1069. YES YES

B E A M N O. 2418 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 2418 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 2418 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___1924J____________________ 1068X 300X 600_____________________1890J____


| |
| |
| |
| |
| |
| 4No16 H 43. 0.TO 1069 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 |
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | oooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 218

=====================================================================

BEAM NO. 2430 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1069. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 1069. YES YES

B E A M N O. 2430 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 2430 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 2430 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___1926J____________________ 1068X 300X 600_____________________1893J____


| |
| |
| |
| |
| |
| 6No12 H 41. 0.TO 1069 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 |
|oooooo | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 219

=====================================================================

BEAM NO. 2431 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 4 - 16MM 0. 2810. YES NO


2 555. 4 - 20MM 702. 3500. NO YES

B E A M N O. 2431 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 68.64 KNS Vc= 134.90 KNS Vs= 0.00 KNS
Tu= 2.95 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1195. MM

AT END SUPPORT - Vu= 140.22 KNS Vc= 138.89 KNS Vs= 48.08 KNS
Tu= 2.95 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 1195. MM

___1927J____________________ 3499X 300X 600_____________________ 7J____


| ============================================================||
| 4No20 H|555. 702.TO 3500 | | | |
| | | | | | | | |
| 6*10c/c279 | | | | | | | 6*10c/c279 |
| | | | | | | | |
| 4No16 H 43. |0.TO 2810 | | | | | |
||============================================================ |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | | | |
| oooo | | oooo | | oooo | | oooo | | oooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 220

=====================================================================

BEAM NO. 2433 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2087. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 6 - 12MM 0. 2087. YES YES

B E A M N O. 2433 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 10.68 KNS Vc= 131.54 KNS Vs= 0.00 KNS
Tu= 0.20 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 12.90 KNS Vc= 131.66 KNS Vs= 0.00 KNS
Tu= 0.20 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1929J____________________ 2086X 300X 600_____________________1933J____


| |
| |
| |
| |
| |
| 6No12 H 41. 0.TO 2087 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 | | 6#12 |
|oooooo | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo | |oooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 221

=====================================================================

BEAM NO. 2440 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2083. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 2 - 20MM 0. 1458. YES NO


2 553. 3 - 25MM 0. 2083. YES YES

B E A M N O. 2440 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 121.77 KNS Vc= 252.53 KNS Vs= 0.00 KNS
Tu= 8.02 KN-MET Tc= 6.2 KN-MET Ts= 10.7 KN-MET LOAD 130
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 487. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.99 SQ.CM.

AT END SUPPORT - Vu= 197.49 KNS Vc= 137.85 KNS Vs= 125.47 KNS
Tu= 1.02 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 278. MM C/C FOR 487. MM

___1933J____________________ 2083X 300X 600_____________________ 8J____


||=========================================================================||
| 3No25 H|553. |0.TO 2083 | |
| | | | | | |
| 4*10c/c188 | | | 3*10c/c278 |
| | | | | | |
| 2No20 H| 45. |0.TO 1458 | |
||==================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 | | | | |
| oo | | oo | | oo | | oo | | oo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 222

=====================================================================

BEAM NO. 2446 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 536. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 5 - 12MM 0. 536. YES YES

B E A M N O. 2446 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 2446 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 2446 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___1936J____________________ 536X 300X 600_____________________1951J____


| |
| |
| |
| |
| |
| 5No12 H 41. 0.TO 536 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 223

=====================================================================

BEAM NO. 2452 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1767. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 5 - 12MM 0. 800. YES NO


2 555. 4 - 20MM 0. 1767. YES YES

B E A M N O. 2452 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 110.85 KNS Vc= 245.92 KNS Vs= 0.00 KNS
Tu= 9.81 KN-MET Tc= 5.8 KN-MET Ts= 13.1 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 328. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.44 SQ.CM.

AT END SUPPORT - Vu= 177.46 KNS Vc= 138.99 KNS Vs= 97.62 KNS
Tu= 3.88 KN-MET Tc= 5.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 328. MM

___1938J____________________ 1766X 300X 600_____________________ 14J____


||=========================================================================||
| 4No20 H 555. 0.TO 1767 |
| | | | |
| 3*10c/c188 | 3*10c/c280 |
| | | | |
| 5No12 H 41. 0.TO 800 |
||================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | oooo |
| 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 | | 4#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#12 | | 5#12 | | 5#12 | | | | | | | | |
| ooooo | | ooooo | | ooooo | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 224

=====================================================================

BEAM NO. 2455 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2431. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 5 - 12MM 148. 2431. NO YES


2 559. 5 - 12MM 0. 1076. YES NO

B E A M N O. 2455 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 77.47 KNS Vc= 137.70 KNS Vs= 0.00 KNS
Tu= 24.62 KN-MET Tc= 5.5 KN-MET Ts= 32.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 660. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.12 SQ.CM.

AT END SUPPORT - Vu= 42.29 KNS Vc= 137.70 KNS Vs= 0.00 KNS
Tu= 24.62 KN-MET Tc= 5.5 KN-MET Ts= 32.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 660. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.12 SQ.CM.

___1940J____________________ 2430X 300X 600_____________________1889J____


||================================ |
| 5No12 H 559.| 0.TO 1076| |
| | | | | |
| 5*10c/c188 | | | 5*10c/c188 |
| | | | | |
| 5No12 H 41. 148.TO 2431 |
| =======================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | | | | | | | |
| 5#12 | | 5#12 | | 5#12 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 225

=====================================================================

BEAM NO. 2459 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1389. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 5 - 12MM 0. 474. YES NO


2 555. 3 - 20MM 0. 1389. YES YES

B E A M N O. 2459 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 130.60 KNS Vc= 137.30 KNS Vs= 36.83 KNS
Tu= 17.09 KN-MET Tc= 5.5 KN-MET Ts= 22.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 139. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.25 SQ.CM.

AT END SUPPORT - Vu= 136.54 KNS Vc= 137.30 KNS Vs= 44.75 KNS
Tu= 17.09 KN-MET Tc= 5.5 KN-MET Ts= 22.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 139. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 4.25 SQ.CM.

___1942J____________________ 1388X 300X 600_____________________ 15J____


||=========================================================================||
| 3No20 H 555. 0.TO 1389 |
| | | |
| 2*10c/c188| 2*10c/c188 |
| | | |
| 5No12 H 41. 0.TO 474 |
||======================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 | | 3#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#12 | | 5#12 | | 5#12 | | | | | | | | |
| ooooo | | ooooo | | ooooo | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 226

=====================================================================

BEAM NO. 2470 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1200. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 3 - 16MM 0. 1200. YES YES

B E A M N O. 2470 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 17.31 KNS Vc= 131.44 KNS Vs= 0.00 KNS
Tu= 0.18 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 14.95 KNS Vc= 131.31 KNS Vs= 0.00 KNS
Tu= 0.18 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1949J____________________ 1199X 300X 600_____________________1886J____


| |
| |
| |
| |
| |
| 3No16 H 43. 0.TO 1200 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 227

=====================================================================

BEAM NO. 2474 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1200. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 45. 2 - 20MM 0. 1200. YES YES

B E A M N O. 2474 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 43.88 KNS Vc= 132.74 KNS Vs= 0.00 KNS
Tu= 26.36 KN-MET Tc= 5.6 KN-MET Ts= 35.1 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 181. MM C/C FOR 45. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.55 SQ.CM.

AT END SUPPORT - Vu= 42.14 KNS Vc= 132.53 KNS Vs= 0.00 KNS
Tu= 26.36 KN-MET Tc= 5.6 KN-MET Ts= 35.1 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 181. MM C/C FOR 45. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 6.55 SQ.CM.

___1951J____________________ 1199X 300X 600_____________________1888J____


| |
| |
| |
| 2*10c/c181 2*10c/c181 |
| |
| 2No20 H 45. 0.TO 1200 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 |
| oo | | oo | | oo | | oo | | oo | | oo | | oo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 228

=====================================================================

BEAM NO. 2477 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1925. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 5 - 12MM 0. 1160. YES NO


2 553. 3 - 25MM 0. 1925. YES YES

B E A M N O. 2477 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 117.95 KNS Vc= 255.10 KNS Vs= 0.00 KNS
Tu= 8.57 KN-MET Tc= 6.2 KN-MET Ts= 11.4 KN-MET LOAD 124
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 188. MM C/C FOR 408. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.13 SQ.CM.

AT END SUPPORT - Vu= 192.83 KNS Vc= 138.65 KNS Vs= 118.46 KNS
Tu= 0.38 KN-MET Tc= 5.7 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 280. MM C/C FOR 408. MM

___1953J____________________ 1925X 300X 600_____________________ 9J____


||=========================================================================||
| 3No25 H 553. 0.TO 1925| |
| | | | | |
| 4*10c/c188 | | 3*10c/c280 |
| | | | | |
| 5No12 H |41. 0.TO 1160| |
||============================================ |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 | | 3#25 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#12 | | 5#12 | | 5#12 | | 5#12 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 229

=====================================================================

BEAM NO. 2481 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 158. MM FY - 412. FC - 25. MPA, SIZE - 300. X 600. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 5 - 12MM 0. 158. YES YES

B E A M N O. 2481 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 2481 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 2481 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___1955J____________________ 158X 300X 600_____________________1938J____


| |
| |
| |
| |
| |
| 5No12 H 41. 0.TO 158 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 | | 5#12 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

********************END OF BEAM DESIGN**************************

2418. DESIGN BEAM _T_SEC_SOT

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 230

=====================================================================

BEAM NO. 2368 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 877. 3125. NO YES


2 455. 2 - 20MM 0. 2083. YES NO

B E A M N O. 2368 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 80.70 KNS Vc= 94.00 KNS Vs= 13.60 KNS
Tu= 0.21 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 18.00 KNS Vc= 90.94 KNS Vs= 0.00 KNS
Tu= 0.21 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1691J____________________ 3125X 250X 500_____________________1910J____


| |
||================================================= |
| 2No20 H 455. 0.TO 2083| | |
| 6*10c/c230 | | |
| | | |
| 5No10 H 40. 877.TO 3125 |
| ======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oo | | oo | | oo | | oo | | oo | | | | |
| 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 231

=====================================================================

BEAM NO. 2369 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2080. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 832. 2080. NO YES


2 460. 5 - 10MM 0. 1431. YES NO

B E A M N O. 2369 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 59.17 KNS Vc= 95.36 KNS Vs= 0.00 KNS
Tu= 3.70 KN-MET Tc= 3.3 KN-MET Ts= 4.9 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 585. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.18 SQ.CM.

AT END SUPPORT - Vu= 31.41 KNS Vc= 94.65 KNS Vs= 0.00 KNS
Tu= 3.70 KN-MET Tc= 3.3 KN-MET Ts= 4.9 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 585. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.18 SQ.CM.

___1895J____________________ 2080X 250X 500_____________________1930J____


||=================================================== |
| 5No10 H 460. 0.TO 1431 | |
| | |
| 5*10c/c151 | 5*10c/c151 |
| | |
| 5No10 H 40. 832.TO|2080 |
| =============================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 232

=====================================================================

BEAM NO. 2370 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1925. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 588. 1925. NO YES


2 460. 5 - 10MM 0. 1514. YES NO

B E A M N O. 2370 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 37.52 KNS Vc= 97.35 KNS Vs= 0.00 KNS
Tu= 4.12 KN-MET Tc= 3.4 KN-MET Ts= 5.5 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 508. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.31 SQ.CM.

AT END SUPPORT - Vu= 22.29 KNS Vc= 101.56 KNS Vs= 0.00 KNS
Tu= 4.12 KN-MET Tc= 3.4 KN-MET Ts= 5.5 KN-MET LOAD 123
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 508. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.31 SQ.CM.

___1893J____________________ 1925X 250X 500_____________________1948J____


||========================================================== |
| 5No10 H 460. 0.TO 1514| | | |
| | | | |
| 5*10c/c151 | | | 5*10c/c151 |
| | | | |
| 5No10 H 40. 588.TO 1925 | | |
| ====================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxl
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 233

=====================================================================

BEAM NO. 2372 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 347. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 347. YES YES

B E A M N O. 2372 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 2372 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 2372 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___1910J____________________ 347X 250X 500_____________________1928J____


| |
| |
| |
| |
| |
| 5No10 H 40. 0.TO 347 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxli
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

STAAD SPACE -- PAGE NO. 235

B E A M N O. 2374 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 20.88 KNS Vc= 91.10 KNS Vs= 0.00 KNS
Tu= 16.80 KN-MET Tc= 3.3 KN-MET Ts= 22.4 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 145. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.36 SQ.CM.

AT END SUPPORT - Vu= 26.13 KNS Vc= 91.66 KNS Vs= 0.00 KNS
Tu= 16.80 KN-MET Tc= 3.3 KN-MET Ts= 22.4 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 145. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.36 SQ.CM.

___1912J____________________ 1199X 250X 500_____________________1952J____


| |
| |
| |
| 2*10c/c151 2*10c/c151 |
| |
| 5No10 H 40. 0.TO 1200 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxlii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2376 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 877. 3125. NO YES


2 457. 3 - 16MM 0. 1927. YES NO

B E A M N O. 2376 D E S I G N R E S U L T S - SHEAR

STAAD SPACE -- PAGE NO. 236

AT START SUPPORT - Vu= 67.16 KNS Vc= 96.60 KNS Vs= 0.00 KNS
Tu= 7.81 KN-MET Tc= 3.5 KN-MET Ts= 10.4 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1108. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.49 SQ.CM.

AT END SUPPORT - Vu= 11.20 KNS Vc= 90.63 KNS Vs= 0.00 KNS
Tu= 7.81 KN-MET Tc= 3.5 KN-MET Ts= 10.4 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1108. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.49 SQ.CM.

___ 865J____________________ 3125X 250X 500_____________________1914J____


| |
||============================================= |
| 3No16 H 457. 0.TO 1927| | | | | |
| 9*10c/c151 | | | | | | 9*10c/c151 |
| | | | | | | |
| 5No10 H |40.|877.TO 3125| |
| ======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxliii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2377 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2080. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 832. 2080. NO YES


2 460. 5 - 10MM 0. 1604. YES NO

B E A M N O. 2377 D E S I G N R E S U L T S - SHEAR

STAAD SPACE -- PAGE NO. 237

AT START SUPPORT - Vu= 53.94 KNS Vc= 94.96 KNS Vs= 0.00 KNS
Tu= 2.42 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 585. MM

AT END SUPPORT - Vu= 29.90 KNS Vc= 108.91 KNS Vs= 0.00 KNS
Tu= 2.42 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1896J____________________ 2080X 250X 500_____________________1931J____


||========================================================= |
| 5No10 H 460. 0.TO 1604 |
| |
| 4*10c/c230 |
| |
| 5No10 H 40. 832.TO 2080 |
| =============================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxliv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2378 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1925. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 908. 1925. NO YES


2 459. 4 - 12MM 0. 1752. YES NO

B E A M N O. 2378 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 58.54 KNS Vc= 95.13 KNS Vs= 0.00 KNS
Tu= 0.68 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 508. MM

STAAD SPACE -- PAGE NO. 238

AT END SUPPORT - Vu= 38.37 KNS Vc= 125.93 KNS Vs= 0.00 KNS
Tu= 0.68 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

___1894J____________________ 1925X 250X 500_____________________1950J____


||==================================================================== |
| 4No12 H 459. 0.TO 1752 |
| |
| 4*10c/c230 |
| |
| 5No10 H 40. 908.TO 1925 |
| ========================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | |
| 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxlv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2379 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 873. 3125. NO YES


2 457. 3 - 16MM 0. 1667. YES NO

B E A M N O. 2379 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 74.75 KNS Vc= 95.59 KNS Vs= 4.07 KNS
Tu= 0.67 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 18.82 KNS Vc= 91.00 KNS Vs= 0.00 KNS
Tu= 0.67 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 239

___1891J____________________ 3125X 250X 500_____________________1917J____


| |
||======================================= |
| 3No16 H 457. 0.TO 1667| | |
| 6*10c/c230 | | |
| | | |
| 5No10 H 40. 873.TO 3125 |
| ======================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxlvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2380 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2378. YES NO


2 459. 4 - 12MM 1484. 3125. NO YES

B E A M N O. 2380 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 9.59 KNS Vc= 90.57 KNS Vs= 0.00 KNS
Tu= 2.96 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 65.52 KNS Vc= 96.42 KNS Vs= 0.00 KNS
Tu= 2.96 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

STAAD SPACE -- PAGE NO. 240

___1914J____________________ 3125X 250X 500_____________________1896J____


| =======================================||
| 4No12 H|459.1484.TO|3125 |
| | | | |
| | | | 6*10c/c230 |
| | | | |
| 5No10 H 40. 0.TO 2378 | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | oooo | | oooo | | oooo | | oooo |
| | | | | | | 4#12 | | 4#12 | | 4#12 | | 4#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxlvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2382 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1200. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1200. YES YES

B E A M N O. 2382 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 15.51 KNS Vc= 91.39 KNS Vs= 0.00 KNS
Tu= 0.12 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 20.65 KNS Vc= 92.34 KNS Vs= 0.00 KNS
Tu= 0.12 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 241

___1916J____________________ 1199X 250X 500_____________________1954J____


| |
| |
| |
| |
| |
| 5No10 H 40. 0.TO 1200 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxlviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2383 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 41. 4 - 12MM 0. 2155. YES NO


2 457. 3 - 16MM 1328. 3125. NO YES

B E A M N O. 2383 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 18.78 KNS Vc= 90.78 KNS Vs= 0.00 KNS
Tu= 5.13 KN-MET Tc= 3.5 KN-MET Ts= 6.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1108. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.64 SQ.CM.

AT END SUPPORT - Vu= 78.46 KNS Vc= 99.18 KNS Vs= 5.44 KNS
Tu= 5.07 KN-MET Tc= 4.1 KN-MET Ts= 6.8 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1108. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.62 SQ.CM.

STAAD SPACE -- PAGE NO. 242

___1917J____________________ 3125X 250X 500_____________________1512J____


| |
| ===========================================||
| 3No16 H 457.1328.TO 3125 |
| 9*10c/c151 | | | | 9*10c/c151 |
| | | | | |
| 4No12 H 41. 0.TO 2155 | | | | |
||=================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | | | |
| oooo | | oooo | | oooo | | oooo | | oooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxlix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2384 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 726. 3500. NO YES


2 457. 3 - 16MM 0. 1792. YES NO

B E A M N O. 2384 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 64.98 KNS Vc= 96.13 KNS Vs= 0.00 KNS
Tu= 1.97 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 7.47 KNS Vc= 90.59 KNS Vs= 0.00 KNS
Tu= 1.97 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 243

___1221J____________________ 3499X 250X 500_____________________1928J____


| |
||===================================== |
| 3No16 H 457. 0.TO 1792 | | |
| 7*10c/c230 | | | | |
| | | | | |
| 5No10 H 40. 726.TO 3500 |
| ============================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccl
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2385 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4670. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 43. 2 - 16MM 497. 4670. NO YES


2 455. 2 - 20MM 0. 1949. YES NO

B E A M N O. 2385 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 86.69 KNS Vc= 94.37 KNS Vs= 21.22 KNS
Tu= 1.38 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 228. MM C/C FOR 1880. MM

AT END SUPPORT - Vu= 31.95 KNS Vc= 91.95 KNS Vs= 0.00 KNS
Tu= 1.38 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 244

___1884J____________________ 4670X 250X 500_____________________1914J____


| |
||============================== |
| 2No20 H 455.| 0.TO 1949| | |
| 10*10c/c229 | | | | | |
| 2No16|H 43. 497.TO 4670 |
| ===================================================================||
| |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oo | | oo | | oo | | | | | | | | |
| 2#20 | | 2#20 | | 2#20 | | | | | | | | |
| | | | | | | | | | | | | |
| | | 2#16 | | 2#16 | | 2#16 | | 2#16 | | 2#16 | | 2#16 |
| | | oo | | oo | | oo | | oo | | oo | | oo |
| | | | | | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccli
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2386 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2336. YES NO


2 457. 3 - 16MM 1562. 3500. NO YES

B E A M N O. 2386 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 2.17 KNS Vc= 90.11 KNS Vs= 0.00 KNS
Tu= 3.30 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 71.45 KNS Vc= 93.92 KNS Vs= 1.34 KNS
Tu= 3.30 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

STAAD SPACE -- PAGE NO. 245

___1910J____________________ 3499X 250X 500_____________________1884J____


| |
| ==========================================||
| 3No16 H 457.1562.TO 3500 |
| | | 7*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2336 | | |
||================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2387 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2330. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1265. YES NO


2 457. 3 - 16MM 54. 2330. NO YES

B E A M N O. 2387 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 30.38 KNS Vc= 94.57 KNS Vs= 0.00 KNS
Tu= 2.78 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 61.25 KNS Vc= 95.59 KNS Vs= 0.00 KNS
Tu= 2.78 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 710. MM

STAAD SPACE -- PAGE NO. 246

___1914J____________________ 2329X 250X 500_____________________1765J____


| |
|==========================================================================||
| 3No16 H 457. 54.TO 2330 |
| 5*10c/c230 |
| |
| 5No10 H 40. 0.TO 1265 |
||======================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccliii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2388 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3111. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1131. 3111. NO YES


2 457. 4 - 16MM 0. 2640. YES NO

B E A M N O. 2388 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 78.18 KNS Vc= 93.29 KNS Vs= 10.95 KNS
Tu= 0.02 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1101. MM

AT END SUPPORT - Vu= 20.95 KNS Vc= 91.58 KNS Vs= 0.00 KNS
Tu= 0.02 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 247

___1706J____________________ 3111X 250X 500_____________________1911J____


| |
||=============================================================== |
| 4No16 H 457. 0.TO 2640 | |
| 6*10c/c230 | |
| | |
| 5No10 H 40.1131.TO 3111 |
| ================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | |
| 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | 4#16 | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccliv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2392 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4180. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 925. 4180. NO YES


2 457. 3 - 16MM 0. 1670. YES NO

B E A M N O. 2392 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 76.16 KNS Vc= 95.90 KNS Vs= 5.64 KNS
Tu= 0.09 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1635. MM

AT END SUPPORT - Vu= 22.05 KNS Vc= 91.57 KNS Vs= 0.00 KNS
Tu= 0.09 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 248

___1812J____________________ 4180X 250X 500_____________________1912J____


| |
||============================= |
| 3No16 H 457. 0.TO 1670 | |
| 9*10c/c230 | | | |
| | | | |
| 5No10|H 40. 925.TO 4180 |
| ===========================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2396 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3111. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 613. 3111. NO YES


2 459. 4 - 12MM 0. 1506. YES NO

B E A M N O. 2396 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 63.20 KNS Vc= 96.56 KNS Vs= 0.00 KNS
Tu= 3.60 KN-MET Tc= 3.4 KN-MET Ts= 4.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1101. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.15 SQ.CM.

AT END SUPPORT - Vu= 5.97 KNS Vc= 90.31 KNS Vs= 0.00 KNS
Tu= 3.60 KN-MET Tc= 3.4 KN-MET Ts= 4.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1101. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.15 SQ.CM.

STAAD SPACE -- PAGE NO. 249

___1819J____________________ 3111X 250X 500_____________________1925J____


||=================================== |
| 4No12 H 459.| 0.TO 1506| | | |
| | | | | | | |
| 9*10c/c151 | | | | | | 9*10c/c151 |
| | | | | | | |
| |5No10 H| 40. 613.TO|3111 |
| =============================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | | | | | | | |
| 4#12 | | 4#12 | | 4#12 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2397 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4670. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1067. 4670. NO YES


2 457. 4 - 16MM 0. 1992. YES NO

B E A M N O. 2397 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 84.21 KNS Vc= 94.17 KNS Vs= 18.12 KNS
Tu= 1.40 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1880. MM

AT END SUPPORT - Vu= 34.43 KNS Vc= 93.72 KNS Vs= 0.00 KNS
Tu= 1.40 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 250

___1887J____________________ 4670X 250X 500_____________________1917J____


| |
||=============================== |
| 4No16 H 457. 0.TO 1992| | |
| 10*10c/c230 | | | | |
| | | | | |
| 5No10 H |40.1067.TO 4670 |
| ==========================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oooo | | oooo | | oooo | | | | | | | | |
| 4#16 | | 4#16 | | 4#16 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2399 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2330. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1460. YES NO


2 460. 5 - 10MM 483. 2330. NO YES

B E A M N O. 2399 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 16.05 KNS Vc= 94.52 KNS Vs= 0.00 KNS
Tu= 2.98 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 46.94 KNS Vc= 95.00 KNS Vs= 0.00 KNS
Tu= 2.98 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 710. MM

STAAD SPACE -- PAGE NO. 251

___1917J____________________ 2329X 250X 500_____________________1889J____


| ============================================================||
| 5No10 H 460. 483.TO 2330 | |
| | |
| | 5*10c/c230 |
| | |
| 5No10 H 40. 0.TO 1460 | |
||============================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2408 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1389. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 689. 1389. NO YES


2 457. 3 - 16MM 0. 1389. YES YES

B E A M N O. 2408 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 78.26 KNS Vc= 98.01 KNS Vs= 6.33 KNS
Tu= 1.97 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 239. MM

AT END SUPPORT - Vu= 69.56 KNS Vc= 173.46 KNS Vs= 0.00 KNS
Tu= 1.97 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 239. MM

STAAD SPACE -- PAGE NO. 252

___1778J____________________ 1388X 250X 500_____________________1937J____


| |
||=========================================================================||
| 3No16 H 457. 0.TO 1389 | | | |
| 3*10c/c230 | 3*10c/c230 | |
| | | | |
| 5No10 H 40. 689.TO 1389 | |
| ======================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2409 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 694. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 457. 3 - 16MM 0. 694. YES YES

B E A M N O. 2409 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 2409 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 2409 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

STAAD SPACE -- PAGE NO. 253

___1892J____________________ 694X 250X 500_____________________1941J____


| |
||=========================================================================||
| 3No16 H 457. 0.TO 694 |
| |
| |
| |
| |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2410 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1358. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1358. YES YES

B E A M N O. 2410 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 10.81 KNS Vc= 90.67 KNS Vs= 0.00 KNS
Tu= 9.75 KN-MET Tc= 3.5 KN-MET Ts= 13.0 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 224. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.11 SQ.CM.

AT END SUPPORT - Vu= 18.40 KNS Vc= 91.53 KNS Vs= 0.00 KNS
Tu= 9.75 KN-MET Tc= 3.5 KN-MET Ts= 13.0 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 224. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.11 SQ.CM.

STAAD SPACE -- PAGE NO. 254

___1918J____________________ 1358X 250X 500_____________________1939J____


| |
| |
| |
| 3*10c/c151 3*10c/c151 |
| |
| 5No10 H 40. 0.TO 1358 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2411 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1736. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1736. YES YES

B E A M N O. 2411 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 6.18 KNS Vc= 90.21 KNS Vs= 0.00 KNS
Tu= 0.31 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 23.83 KNS Vc= 91.80 KNS Vs= 0.00 KNS
Tu= 0.31 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 255

___1919J____________________ 1736X 250X 500_____________________1943J____


| |
| |
| |
| |
| |
| 5No10 H 40. 0.TO 1736 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2419 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3889. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2887. YES NO


2 455. 2 - 20MM 1649. 3889. NO YES

B E A M N O. 2419 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 8.80 KNS Vc= 90.50 KNS Vs= 0.00 KNS
Tu= 2.98 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 79.48 KNS Vc= 94.13 KNS Vs= 11.85 KNS
Tu= 2.98 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1489. MM

STAAD SPACE -- PAGE NO. 256

___1925J____________________ 3888X 250X 500_____________________1887J____


| |
| ===========================================||
| 2No20 H 455.1649.TO 3889 |
| | | | | 8*10c/c230 |
| | | | | |
| 5No10 H 40. 0.TO 2887 | | | | |
||======================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | oo | | oo | | oo | | oo |
| | | | | | | 2#20 | | 2#20 | | 2#20 | | 2#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2420 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 356. 3125. NO YES


2 460. 5 - 10MM 0. 1172. YES NO

B E A M N O. 2420 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 59.65 KNS Vc= 100.44 KNS Vs= 0.00 KNS
Tu= 1.05 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1108. MM

AT END SUPPORT - Vu= 1.85 KNS Vc= 89.95 KNS Vs= 0.00 KNS
Tu= 1.05 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 257

___1924J____________________ 3125X 250X 500_____________________1925J____


||=========================== |
| 5No10 H 460.| 0.TO 1172| |
| | | | | |
| 6*10c/c230 | | | |
| | | | | |
| |5No10|H 40. 356.TO 3125 |
| ===================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2421 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3125. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2118. YES NO


2 455. 2 - 20MM 911. 3125. NO YES

B E A M N O. 2421 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 20.33 KNS Vc= 91.15 KNS Vs= 0.00 KNS
Tu= 3.63 KN-MET Tc= 3.3 KN-MET Ts= 4.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1108. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.16 SQ.CM.

AT END SUPPORT - Vu= 78.58 KNS Vc= 94.44 KNS Vs= 10.33 KNS
Tu= 3.68 KN-MET Tc= 3.6 KN-MET Ts= 4.9 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR SHEAR AND TORSION.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1108. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.18 SQ.CM.

STAAD SPACE -- PAGE NO. 258

___1925J____________________ 3125X 250X 500_____________________ 646J____


| |
| =====================================================||
| |2No20 H|455. 911.TO|3125 | |
| 9*10c/c151 | | | | | | | 9*10c/c151 |
| | | | | | | | |
| 5No10 H 40. 0.TO 2118| | | | | | |
||================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | oo | | oo | | oo | | oo | | oo |
| | | | | 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2432 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2778. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2147. YES NO


2 460. 5 - 10MM 1345. 2778. NO YES

B E A M N O. 2432 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 9.95 KNS Vc= 91.05 KNS Vs= 0.00 KNS
Tu= 4.29 KN-MET Tc= 3.5 KN-MET Ts= 5.7 KN-MET LOAD 127
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 934. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.37 SQ.CM.

AT END SUPPORT - Vu= 43.24 KNS Vc= 99.73 KNS Vs= 0.00 KNS
Tu= 4.29 KN-MET Tc= 3.5 KN-MET Ts= 5.7 KN-MET LOAD 127
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 934. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.37 SQ.CM.

STAAD SPACE -- PAGE NO. 259

___1928J____________________ 2777X 250X 500_____________________1927J____


| =======================================||
| 5No10|H 460.1345.TO 2778 |
| | | | | | |
| 8*10c/c151 | | | | | 8*10c/c151 |
| | | | | | |
| 5No10 H 40. 0.TO 2147 | | | | | |
||========================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | ooooo | | ooooo | | ooooo | | ooooo |
| | | | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2435 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2087. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2087. YES YES

B E A M N O. 2435 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 4.79 KNS Vc= 90.52 KNS Vs= 0.00 KNS
Tu= 0.78 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 19.42 KNS Vc= 94.47 KNS Vs= 0.00 KNS
Tu= 0.78 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 261

___1931J____________________ 2086X 250X 500_____________________1934J____


| |
| |
| |
| |
| |
| 5No10 H 40. 0.TO 2087 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2436 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4670. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1067. 4670. NO YES


2 457. 3 - 16MM 0. 1793. YES NO

B E A M N O. 2436 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 72.41 KNS Vc= 93.98 KNS Vs= 2.57 KNS
Tu= 2.75 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1880. MM

AT END SUPPORT - Vu= 22.50 KNS Vc= 91.59 KNS Vs= 0.00 KNS
Tu= 2.75 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 262

___1929J____________________ 4670X 250X 500_____________________1931J____


| |
||============================ |
| 3No16 H 457. 0.TO 1793| |
| 10*10c/c230 | | | |
| | | | |
| 5No10 H |40.1067.TO 4670 |
| ==========================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2437 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3889. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2563. YES NO


2 457. 3 - 16MM 1805. 3889. NO YES

B E A M N O. 2437 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 7.63 KNS Vc= 90.59 KNS Vs= 0.00 KNS
Tu= 1.94 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 66.29 KNS Vc= 93.51 KNS Vs= 0.00 KNS
Tu= 1.94 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1489. MM

STAAD SPACE -- PAGE NO. 263

___1930J____________________ 3888X 250X 500_____________________1929J____


| |
| ========================================||
| 3No16 H 457.1805.TO 3889 |
| | | 8*10c/c230 |
| | | |
| 5No10 H 40. 0.TO 2563 | | |
||================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2439 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2330. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1848. YES NO


2 460. 5 - 10MM 483. 2330. NO YES

B E A M N O. 2439 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 15.09 KNS Vc= 91.79 KNS Vs= 0.00 KNS
Tu= 2.03 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 46.70 KNS Vc= 97.37 KNS Vs= 0.00 KNS
Tu= 2.03 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 710. MM

STAAD SPACE -- PAGE NO. 264

___1931J____________________ 2329X 250X 500_____________________1932J____


| ============================================================||
| 5No10 H 460. 483.TO 2330 | | | |
| | | | |
| | | | 5*10c/c230 |
| | | | |
| 5No10 H 40. 0.TO 1848 | | | |
||=========================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2441 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2083. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 815. YES NO


2 457. 2 - 16MM 0. 2083. YES YES

B E A M N O. 2441 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 22.73 KNS Vc= 187.22 KNS Vs= 0.00 KNS
Tu= 4.20 KN-MET Tc= 4.0 KN-MET Ts= 5.6 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 587. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.34 SQ.CM.

AT END SUPPORT - Vu= 46.86 KNS Vc= 97.66 KNS Vs= 0.00 KNS
Tu= 4.20 KN-MET Tc= 4.0 KN-MET Ts= 5.6 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 587. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.34 SQ.CM.

STAAD SPACE -- PAGE NO. 265

___1934J____________________ 2083X 250X 500_____________________1894J____


| |
||=========================================================================||
| 2No16 H 457.| 0.TO 2083| |
| 5*10c/c151 | | | 5*10c/c151 |
| | | | | | |
| 5No10 H 40.| 0.TO 815| |
||============================ |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oo | | oo | | oo | | oo | | oo | | oo | | oo |
| 2#16 | | 2#16 | | 2#16 | | 2#16 | | 2#16 | | 2#16 | | 2#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| ooooo | | ooooo | | ooooo | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2442 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4670. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1067. 4670. NO YES


2 457. 3 - 16MM 0. 1793. YES NO

B E A M N O. 2442 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 72.42 KNS Vc= 94.12 KNS Vs= 2.45 KNS
Tu= 2.23 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1880. MM

AT END SUPPORT - Vu= 22.53 KNS Vc= 91.58 KNS Vs= 0.00 KNS
Tu= 2.23 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 266

___1933J____________________ 4670X 250X 500_____________________1934J____


| |
||============================ |
| 3No16 H 457. 0.TO 1793| |
| 10*10c/c230 | | | |
| | | | |
| 5No10 H |40.1067.TO 4670 |
| ==========================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2443 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2083. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1336. YES NO


2 460. 5 - 10MM 738. 2083. NO YES

B E A M N O. 2443 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 29.02 KNS Vc= 93.53 KNS Vs= 0.00 KNS
Tu= 3.84 KN-MET Tc= 3.3 KN-MET Ts= 5.1 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 587. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.22 SQ.CM.

AT END SUPPORT - Vu= 56.88 KNS Vc= 96.46 KNS Vs= 0.00 KNS
Tu= 3.84 KN-MET Tc= 3.3 KN-MET Ts= 5.1 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 587. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.22 SQ.CM.

STAAD SPACE -- PAGE NO. 267

___1935J____________________ 2083X 250X 500_____________________1926J____


| =================================================||
| |5No10 H 460. 738.TO 2083 |
| | |
| 5*10c/c151 | 5*10c/c151 |
| | |
| 5No10 H 40. 0.TO 1336| |
||=============================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | ooooo | | ooooo | | ooooo | | ooooo |
| | | | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2444 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3889. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2563. YES NO


2 457. 3 - 16MM 1805. 3889. NO YES

B E A M N O. 2444 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 7.85 KNS Vc= 90.62 KNS Vs= 0.00 KNS
Tu= 1.73 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 66.10 KNS Vc= 93.57 KNS Vs= 0.00 KNS
Tu= 1.73 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1489. MM

STAAD SPACE -- PAGE NO. 268

___1935J____________________ 3888X 250X 500_____________________1933J____


| |
| ========================================||
| 3No16 H 457.1805.TO 3889 |
| | | | 8*10c/c230 |
| | | | |
| 5No10 H 40. 0.TO 2563 | | | |
||================================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | ooo | | ooo | | ooo | | ooo |
| | | | | | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2445 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2330. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1265. YES NO


2 457. 3 - 16MM 0. 2330. YES YES

B E A M N O. 2445 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 35.82 KNS Vc= 96.08 KNS Vs= 0.00 KNS
Tu= 3.60 KN-MET Tc= 3.3 KN-MET Ts= 4.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 710. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.15 SQ.CM.

AT END SUPPORT - Vu= 67.43 KNS Vc= 93.75 KNS Vs= 0.00 KNS
Tu= 3.60 KN-MET Tc= 3.3 KN-MET Ts= 4.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 710. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.15 SQ.CM.

STAAD SPACE -- PAGE NO. 269

___1934J____________________ 2329X 250X 500_____________________ 502J____


| |
||=========================================================================||
| 3No16|H 457. 0.TO 2330 | |
| 6*10c/c151 | | | 6*10c/c151 |
| | | | | | | |
| 5No10|H 40. 0.TO 1265 | |
||======================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2447 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1736. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1736. YES YES

B E A M N O. 2447 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 30.03 KNS Vc= 93.56 KNS Vs= 0.00 KNS
Tu= 1.52 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 14.25 KNS Vc= 90.85 KNS Vs= 0.00 KNS
Tu= 1.52 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

STAAD SPACE -- PAGE NO. 270

___1937J____________________ 1736X 250X 500_____________________1918J____


| |
| |
| |
| |
| |
| 5No10 H 40. 0.TO 1736 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2448 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 435. 3500. NO YES


2 460. 5 - 10MM 0. 1557. YES NO

B E A M N O. 2448 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 42.79 KNS Vc= 96.20 KNS Vs= 0.00 KNS
Tu= 2.43 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 10.40 KNS Vc= 91.68 KNS Vs= 0.00 KNS
Tu= 2.43 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

STAAD SPACE -- PAGE NO. 271

___1936J____________________ 3500X 250X 500_____________________1937J____


||================================ |
| 5No10 H 460. 0.TO 1557 | | |
| | | | | | |
| 7*10c/c230 | | | | |
| | | | | | |
| 5No10 H| 40.|435.TO 3500 |
| ==================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2449 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2628. YES NO


2 460. 5 - 10MM 1797. 3500. NO YES

B E A M N O. 2449 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 11.88 KNS Vc= 91.88 KNS Vs= 0.00 KNS
Tu= 8.28 KN-MET Tc= 3.3 KN-MET Ts= 11.0 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1295. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.64 SQ.CM.

AT END SUPPORT - Vu= 41.30 KNS Vc= 98.26 KNS Vs= 0.00 KNS
Tu= 8.28 KN-MET Tc= 3.3 KN-MET Ts= 11.0 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1295. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.64 SQ.CM.

STAAD SPACE -- PAGE NO. 272

___1937J____________________ 3500X 250X 500_____________________1093J____


| ====================================||
| 5No10 H 460.1797.TO 3500 |
| | | | | |
| 10*10c/c151 | | | | 10*10c/c151 |
| | | | | |
| 5No10 H 40. 0.TO 2628 | | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | ooooo | | ooooo | | ooooo |
| | | | | | | | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2450 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 435. 3500. NO YES


2 460. 5 - 10MM 0. 1266. YES NO

B E A M N O. 2450 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 47.96 KNS Vc= 98.77 KNS Vs= 0.00 KNS
Tu= 2.36 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 4.97 KNS Vc= 90.31 KNS Vs= 0.00 KNS
Tu= 2.36 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

STAAD SPACE -- PAGE NO. 273

___1888J____________________ 3500X 250X 500_____________________1918J____


||========================== |
| 5No10 H 460. 0.TO 1266 | |
| | | | | |
| 7*10c/c230 | | | |
| | | | | |
| 5No10 H| 40.|435.TO 3500 |
| ==================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2451 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 2628. YES NO


2 459. 4 - 12MM 1719. 3500. NO YES

B E A M N O. 2451 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 2.64 KNS Vc= 90.03 KNS Vs= 0.00 KNS
Tu= 2.53 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 62.76 KNS Vc= 96.83 KNS Vs= 0.00 KNS
Tu= 2.53 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

STAAD SPACE -- PAGE NO. 274

___1918J____________________ 3500X 250X 500_____________________1785J____


| ======================================||
| 4No12 H 459.1719.TO 3500 |
| | | | |
| | | | 7*10c/c230 |
| | | | |
| 5No10 H 40. 0.TO 2628 | | | |
||======================================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | oooo | | oooo | | oooo | | oooo |
| | | | | | | 4#12 | | 4#12 | | 4#12 | | 4#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxx
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2453 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1767. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 884. YES NO


2 459. 4 - 12MM 194. 1767. NO YES

B E A M N O. 2453 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 31.17 KNS Vc= 179.49 KNS Vs= 0.00 KNS
Tu= 4.06 KN-MET Tc= 3.8 KN-MET Ts= 5.4 KN-MET LOAD 121
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 428. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.29 SQ.CM.

AT END SUPPORT - Vu= 44.23 KNS Vc= 101.42 KNS Vs= 0.00 KNS
Tu= 4.06 KN-MET Tc= 3.8 KN-MET Ts= 5.4 KN-MET LOAD 121
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 428. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.29 SQ.CM.

STAAD SPACE -- PAGE NO. 275

___1939J____________________ 1766X 250X 500_____________________1892J____


| ===================================================================||
| 4No12 H|459. 194.TO 1767 |
| | | | |
| 4*10c/c151 | | 4*10c/c151 |
| | | | |
| 5No10 H| 40. |0.TO 884 |
||===================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | oooo | | oooo | | oooo | | oooo | | oooo | | oooo |
| | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxxi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2454 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 3500. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1018. 3500. NO YES


2 460. 5 - 10MM 0. 1849. YES NO

B E A M N O. 2454 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 47.95 KNS Vc= 93.76 KNS Vs= 0.00 KNS
Tu= 3.23 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1295. MM

AT END SUPPORT - Vu= 5.66 KNS Vc= 91.16 KNS Vs= 0.00 KNS
Tu= 3.37 KN-MET Tc= 3.4 KN-MET Ts= 4.5 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 1295. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.08 SQ.CM.

STAAD SPACE -- PAGE NO. 276

___1938J____________________ 3500X 250X 500_____________________1939J____


||======================================= |
| 5No10 H 460. 0.TO 1849 | | | |
| | | | | |
| 7*10c/c230 | | | | 10*10c/c151 |
| | | | | |
| |5No10 H 40.1018.TO 3500 |
| =====================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxxii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2456 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2431. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 9. 2431. NO YES


2 460. 5 - 10MM 0. 593. YES NO

B E A M N O. 2456 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 49.05 KNS Vc= 173.55 KNS Vs= 0.00 KNS
Tu= 0.31 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 15.40 KNS Vc= 90.86 KNS Vs= 0.00 KNS
Tu= 0.31 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
STAAD SPACE -- PAGE NO. 277

___1941J____________________ 2430X 250X 500_____________________1919J____


||================= |
| 5No10 H 460. 0.TO 593 |
| |
| |
| |
| 5No10 H 40. 9.TO 2431 |
|==========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | | | | | | | | | |
| 5#10 | | 5#10 | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxxiii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2457 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1750. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 507. 1750. NO YES


2 459. 4 - 12MM 0. 1635. YES NO

B E A M N O. 2457 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 73.10 KNS Vc= 96.60 KNS Vs= 0.87 KNS
Tu= 3.07 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 420. MM

AT END SUPPORT - Vu= 59.99 KNS Vc= 103.88 KNS Vs= 0.00 KNS
Tu= 3.07 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 420. MM

STAAD SPACE -- PAGE NO. 278

___1940J____________________ 1750X 250X 500_____________________1944J____


||====================================================================== |
| 4No12 H 459. 0.TO 1635 | | |
| | | | |
| 3*10c/c230 | | 3*10c/c230 |
| | | | |
| |5No10 H 40. 507.TO 1750 | | |
| =====================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| oooo | | oooo | | oooo | | oooo | | oooo | | oooo | | |
| 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | 4#12 | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxxiv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2458 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1750. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1750. YES YES

B E A M N O. 2458 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 5.49 KNS Vc= 90.24 KNS Vs= 0.00 KNS
Tu= 0.41 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 7.62 KNS Vc= 90.41 KNS Vs= 0.00 KNS
Tu= 0.41 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

STAAD SPACE -- PAGE NO. 279

___1941J____________________ 1750X 250X 500_____________________1945J____


| |
| |
| |
| |
| |
| 5No10 H 40. 0.TO 1750 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxxv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2460 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1389. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 758. YES NO


2 455. 2 - 20MM 0. 1389. YES YES

B E A M N O. 2460 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 93.76 KNS Vc= 174.02 KNS Vs= 0.00 KNS
Tu= 1.68 KN-MET Tc= 3.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 239. MM

AT END SUPPORT - Vu= 102.46 KNS Vc= 99.83 KNS Vs= 36.77 KNS
Tu= 1.68 KN-MET Tc= 3.6 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 239. MM

STAAD SPACE -- PAGE NO. 280

___1943J____________________ 1388X 250X 500_____________________1839J____


| |
||=========================================================================||
| 2No20 H 455. | 0.TO 1389 | |
| 3*10c/c230 | | 3*10c/c230 |
| | | | |
| 5No10 H 40. | 0.TO 758 | |
||======================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| oo | | oo | | oo | | oo | | oo | | oo | | oo |
| 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 | | 2#20 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxxvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2461 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1750. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 507. 1750. NO YES


2 460. 5 - 10MM 0. 1120. YES NO

B E A M N O. 2461 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 56.54 KNS Vc= 101.14 KNS Vs= 0.00 KNS
Tu= 3.63 KN-MET Tc= 3.4 KN-MET Ts= 4.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 420. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.16 SQ.CM.

AT END SUPPORT - Vu= 40.54 KNS Vc= 96.83 KNS Vs= 0.00 KNS
Tu= 3.63 KN-MET Tc= 3.4 KN-MET Ts= 4.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 420. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.16 SQ.CM.

STAAD SPACE -- PAGE NO. 281

___1942J____________________ 1750X 250X 500_____________________1946J____


||=============================================== |
| 5No10 H 460. 0.TO 1120 |
| | |
| 4*10c/c151 | 4*10c/c151 |
| | |
| 5No10 H 40. 507.TO 1750 |
| =====================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxxvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2462 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1750. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1750. YES YES

B E A M N O. 2462 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 25.39 KNS Vc= 94.45 KNS Vs= 0.00 KNS
Tu= 8.11 KN-MET Tc= 3.4 KN-MET Ts= 10.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 420. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.59 SQ.CM.

AT END SUPPORT - Vu= 9.39 KNS Vc= 90.74 KNS Vs= 0.00 KNS
Tu= 8.11 KN-MET Tc= 3.4 KN-MET Ts= 10.8 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 420. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.59 SQ.CM.

STAAD SPACE -- PAGE NO. 282

___1943J____________________ 1750X 250X 500_____________________1947J____


| |
| |
| |
| 4*10c/c151 4*10c/c151 |
| |
| 5No10 H 40. 0.TO 1750 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxxviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2463 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1750. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1750. YES YES

B E A M N O. 2463 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 7.21 KNS Vc= 90.37 KNS Vs= 0.00 KNS
Tu= 1.99 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 5.91 KNS Vc= 90.27 KNS Vs= 0.00 KNS
Tu= 1.99 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

STAAD SPACE -- PAGE NO. 283

___1944J____________________ 1750X 250X 500_____________________1941J____


| |
| |
| |
| |
| |
| 5No10 H 40. 0.TO 1750 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cclxxxix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2464 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1750. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1024. YES NO


2 457. 3 - 16MM 0. 1750. YES YES

B E A M N O. 2464 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 59.39 KNS Vc= 104.93 KNS Vs= 0.00 KNS
Tu= 6.22 KN-MET Tc= 3.5 KN-MET Ts= 8.3 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 420. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.98 SQ.CM.

AT END SUPPORT - Vu= 72.51 KNS Vc= 97.51 KNS Vs= 0.00 KNS
Tu= 6.22 KN-MET Tc= 3.5 KN-MET Ts= 8.3 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 420. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.98 SQ.CM.

STAAD SPACE -- PAGE NO. 284

___1945J____________________ 1750X 250X 500_____________________1152J____


| |
||=========================================================================||
| 3No16 H|457. |0.TO 1750 |
| 4*10c/c151 | | 4*10c/c151 |
| | | | | |
| 5No10 H| 40. |0.TO 1024 |
||=========================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxc
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2465 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1750. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1750. YES YES

B E A M N O. 2465 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 11.62 KNS Vc= 90.90 KNS Vs= 0.00 KNS
Tu= 7.12 KN-MET Tc= 3.4 KN-MET Ts= 9.5 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 420. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.27 SQ.CM.

AT END SUPPORT - Vu= 27.62 KNS Vc= 94.89 KNS Vs= 0.00 KNS
Tu= 7.12 KN-MET Tc= 3.4 KN-MET Ts= 9.5 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 420. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 2.27 SQ.CM.

STAAD SPACE -- PAGE NO. 285

___1946J____________________ 1750X 250X 500_____________________1943J____


| |
| |
| |
| 4*10c/c151 4*10c/c151 |
| |
| 5No10 H 40. 0.TO 1750 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxci
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2466 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1750. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1024. YES NO


2 460. 5 - 10MM 266. 1750. NO YES

B E A M N O. 2466 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 43.79 KNS Vc= 99.46 KNS Vs= 0.00 KNS
Tu= 10.41 KN-MET Tc= 3.4 KN-MET Ts= 13.9 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 420. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.32 SQ.CM.

AT END SUPPORT - Vu= 59.79 KNS Vc= 98.88 KNS Vs= 0.00 KNS
Tu= 10.41 KN-MET Tc= 3.4 KN-MET Ts= 13.9 KN-MET LOAD 100
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 420. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 3.32 SQ.CM.

STAAD SPACE -- PAGE NO. 286

___1947J____________________ 1750X 250X 500_____________________1164J____


| ================================================================||
| 5No10 H 460. 266.TO 1750 |
| | | |
| 4*10c/c151 | | 4*10c/c151 |
| | | |
| 5No10 H 40. |0.TO 1024 |
||=========================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
| | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxcii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2467 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4167. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 4167. YES YES


2 460. 5 - 10MM 0. 391. YES NO

B E A M N O. 2467 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 38.72 KNS Vc= 94.42 KNS Vs= 0.00 KNS
Tu= 2.46 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1628. MM

AT END SUPPORT - Vu= 34.62 KNS Vc= 94.42 KNS Vs= 0.00 KNS
Tu= 2.46 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

STAAD SPACE -- PAGE NO. 287

___1944J____________________ 4166X 250X 500_____________________1946J____


||====== |
| 5No10|H 460. 0.TO 391 |
| | | |
| 9*10c/c230 |
| | | |
| 5No10|H 40. 0.TO 4167 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | | | | | | | | | | | |
| 5#10 | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxciii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2468 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4167. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 4114. YES NO


2 460. 5 - 10MM 0. 391. YES NO
3 460. 5 - 10MM 3602. 4167. NO YES

B E A M N O. 2468 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 37.71 KNS Vc= 100.30 KNS Vs= 0.00 KNS
Tu= 2.06 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1628. MM

AT END SUPPORT - Vu= 35.74 KNS Vc= 94.40 KNS Vs= 0.00 KNS
Tu= 2.16 KN-MET Tc= 3.2 KN-MET Ts= 0.0 KN-MET LOAD 101
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1628. MM

STAAD SPACE -- PAGE NO. 288

___1945J____________________ 4166X 250X 500_____________________1947J____


||====== ==========||
| 5No10|H 460. 0.TO 391 5No10 H 460.3602.TO 4167 |
| | | | | |
| 9*10c/c230 9*10c/c230| |
| | | | | |
| 5No10|H 40. 0.TO 4114 | | |
||==========================================================================|
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| ooooo | | | | | | | | | | | | ooooo |
| 5#10 | | | | | | | | | | | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxciv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2469 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1200. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1200. YES YES

B E A M N O. 2469 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 27.00 KNS Vc= 92.26 KNS Vs= 0.00 KNS
Tu= 16.30 KN-MET Tc= 3.6 KN-MET Ts= 21.7 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 145. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.20 SQ.CM.

AT END SUPPORT - Vu= 21.75 KNS Vc= 91.45 KNS Vs= 0.00 KNS
Tu= 16.30 KN-MET Tc= 3.6 KN-MET Ts= 21.7 KN-MET LOAD 101
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 145. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 5.20 SQ.CM.

STAAD SPACE -- PAGE NO. 289

___1948J____________________ 1199X 250X 500_____________________1912J____


| |
| |
| |
| 2*10c/c151 2*10c/c151 |
| |
| 5No10 H 40. 0.TO 1200 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxcv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2471 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1200. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1200. YES YES

B E A M N O. 2471 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 13.35 KNS Vc= 91.17 KNS Vs= 0.00 KNS
Tu= 0.12 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 8.21 KNS Vc= 90.58 KNS Vs= 0.00 KNS
Tu= 0.12 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

STAAD SPACE -- PAGE NO. 290

___1950J____________________ 1199X 250X 500_____________________1916J____


| |
| |
| |
| |
| |
| 5No10 H 40. 0.TO 1200 |
||=========================================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxcvi
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2472 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4670. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1067. 4670. NO YES


2 457. 3 - 16MM 0. 1793. YES NO

B E A M N O. 2472 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 72.08 KNS Vc= 93.82 KNS Vs= 2.28 KNS
Tu= 1.23 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1880. MM

AT END SUPPORT - Vu= 24.75 KNS Vc= 92.66 KNS Vs= 0.00 KNS
Tu= 1.23 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

STAAD SPACE -- PAGE NO. 291

___1949J____________________ 4670X 250X 500_____________________1950J____


| |
||============================ |
| 3No16 H 457. 0.TO 1793| |
| 10*10c/c230 | | | |
| | | | |
| 5No10 H |40.1067.TO 4670 |
| ==========================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxcvii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2473 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2820. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1235. YES NO


2 457. 3 - 16MM 432. 2820. NO YES

B E A M N O. 2473 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 17.19 KNS Vc= 95.03 KNS Vs= 0.00 KNS
Tu= 0.65 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 62.20 KNS Vc= 93.07 KNS Vs= 0.00 KNS
Tu= 0.65 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 955. MM

STAAD SPACE -- PAGE NO. 292

___1948J____________________ 2820X 250X 500_____________________1949J____


| |
| ================================================================||
| 3No16 H 457. 432.TO 2820 |
| 6*10c/c230 |
| |
| 5No10 H 40. 0.TO 1235 |
||================================ |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| ooooo | | ooooo | | ooooo | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxcviii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2475 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2330. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1265. YES NO


2 460. 5 - 10MM 483. 2330. NO YES

B E A M N O. 2475 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 17.34 KNS Vc= 97.39 KNS Vs= 0.00 KNS
Tu= 2.72 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 48.11 KNS Vc= 94.40 KNS Vs= 0.00 KNS
Tu= 2.72 KN-MET Tc= 3.4 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 710. MM

STAAD SPACE -- PAGE NO. 293

___1950J____________________ 2329X 250X 500_____________________1951J____


| ============================================================||
| 5No10 H 460. 483.TO 2330 |
| |
| 5*10c/c230 |
| |
| 5No10 H 40. 0.TO 1265 |
||======================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccxcix
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2476 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1925. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1257. YES NO


2 460. 5 - 10MM 492. 1925. NO YES

B E A M N O. 2476 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 20.80 KNS Vc= 97.90 KNS Vs= 0.00 KNS
Tu= 4.15 KN-MET Tc= 3.4 KN-MET Ts= 5.5 KN-MET LOAD 124
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 508. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.32 SQ.CM.

AT END SUPPORT - Vu= 36.03 KNS Vc= 99.42 KNS Vs= 0.00 KNS
Tu= 4.15 KN-MET Tc= 3.4 KN-MET Ts= 5.5 KN-MET LOAD 124
STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 151. MM C/C FOR 508. MM
ADDITIONAL LONGITUDINAL STEEL REQD. FOR TORSIONAL RESISTANCE = 1.32 SQ.CM.

STAAD SPACE -- PAGE NO. 294

___1952J____________________ 1925X 250X 500_____________________1890J____


| ========================================================||
| 5No10 H 460. 492.TO 1925 |
| | | |
| 5*10c/c151 | | 5*10c/c151 |
| | | |
| 5No10 H 40. 0.TO 1257| |
||================================================ |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccc
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2478 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 1925. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 776. YES NO


2 457. 3 - 16MM 0. 1925. YES YES

B E A M N O. 2478 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 39.29 KNS Vc= 171.83 KNS Vs= 0.00 KNS
Tu= 0.90 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 59.47 KNS Vc= 94.05 KNS Vs= 0.00 KNS
Tu= 0.90 KN-MET Tc= 3.5 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 508. MM

STAAD SPACE -- PAGE NO. 295

___1954J____________________ 1925X 250X 500_____________________1891J____


| |
||=========================================================================||
| 3No16 H 457. 0.TO 1925 |
| 4*10c/c230 |
| |
| 5No10 H 40. 0.TO 776 |
||============================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| ooooo | | ooooo | | ooooo | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccci
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2479 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 4670. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 1067. 4670. NO YES


2 457. 3 - 16MM 0. 1793. YES NO

B E A M N O. 2479 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 72.21 KNS Vc= 93.74 KNS Vs= 2.55 KNS
Tu= 1.58 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT IS REQUIRED FOR SHEAR.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 1880. MM

AT END SUPPORT - Vu= 24.61 KNS Vc= 92.59 KNS Vs= 0.00 KNS
Tu= 1.58 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.

STAAD SPACE -- PAGE NO. 296

___1953J____________________ 4670X 250X 500_____________________1954J____


| |
||============================ |
| 3No16 H 457. 0.TO 1793| |
| 10*10c/c230 | | | |
| | | | |
| 5No10 H |40.1067.TO 4670 |
| ==========================================================||
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| ooo | | ooo | | ooo | | | | | | | | |
| 3#16 | | 3#16 | | 3#16 | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| | | | | 5#10 | | 5#10 | | 5#10 | | 5#10 | | 5#10 |
| | | | | ooooo | | ooooo | | ooooo | | ooooo | | ooooo |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cccii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2480 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2820. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1470. YES NO


2 457. 3 - 16MM 197. 2820. NO YES

B E A M N O. 2480 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 17.82 KNS Vc= 95.11 KNS Vs= 0.00 KNS
Tu= 1.07 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 62.84 KNS Vc= 93.03 KNS Vs= 0.00 KNS
Tu= 1.07 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 955. MM

STAAD SPACE -- PAGE NO. 297

___1952J____________________ 2820X 250X 500_____________________1953J____


| |
| ======================================================================||
| 3No16 H 457. 197.TO 2820 |
| 6*10c/c230 |
| |
| 5No10 H 40. 0.TO 1470 |
||====================================== |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | 5#10 | | | | | | |
| ooooo | | ooooo | | ooooo | | ooooo | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccciii
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

=====================================================================

BEAM NO. 2482 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05

LEN - 2330. MM FY - 412. FC - 25. MPA, SIZE - 250. X 500. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 40. 5 - 10MM 0. 1071. YES NO


2 457. 3 - 16MM 54. 2330. NO YES

B E A M N O. 2482 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 23.57 KNS Vc= 105.82 KNS Vs= 0.00 KNS
Tu= 1.98 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
STIRRUPS ARE NOT REQUIRED.
AT END SUPPORT - Vu= 54.35 KNS Vc= 93.51 KNS Vs= 0.00 KNS
Tu= 1.98 KN-MET Tc= 3.3 KN-MET Ts= 0.0 KN-MET LOAD 100
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 10 MM 2-LEGGED STIRRUPS AT 230. MM C/C FOR 710. MM

STAAD SPACE -- PAGE NO. 298

___1954J____________________ 2329X 250X 500_____________________1955J____


| |
|==========================================================================||
| 3No16 H 457. 54.TO 2330 |
| 5*10c/c230 |
| |
| 5No10 H 40. 0.TO 1071 |
||================================= |
|___________________________________________________________________________|
_______ _______ _______ _______ _______ _______ _______
| | | | | | | | | | | | | |
| | | ooo | | ooo | | ooo | | ooo | | ooo | | ooo |
| | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 | | 3#16 |
| | | | | | | | | | | | | |
| | | | | | | | | | | | | |
| 5#10 | | 5#10 | | 5#10 | | | | | | | | |
| ooooo | | ooooo | | ooooo | | | | | | | | |
|_______| |_______| |_______| |_______| |_______| |_______| |_______|

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco ccciv
INSTITUTO POLITÉCNICO NACIONAL
ESCUELA SUPERIOR DE INGENIERÍA Y ARQUITECTURA
UNIDAD ZACATENCO

ANEXO 3: Planos

Diseño estructural para la Sub-estación Derivada No. 8 de la Planta de Tratamiento de Aguas Residuales Atotonilco cccv

S-ar putea să vă placă și