FactoryTalk View Studio: Manually Removing an Application from Existing


Application List
24950 | Date Created: 05/07/2003 | Last Updated: 02/14/2018
Access Level: TechConnect

Question
How do I manually delete or remove an application from the Project List if you are having
trouble removing it with the Application Manager?
Unable to delete FactoryTalk View Site Edition application using the Application Manager.

Environment
FactoryTalk View SE
FactoryTalk View ME

Answer
Do the following steps:

Note: Version 8.0 FactoryTalk View ME and greater requires only step 3.

1. Navigate to the Services and find the Rockwell Application Services

2. Right click and select Properties and change the Startup Type to Disabled and reboot the
computer.
Note: You may also have to disable Rockwell Directory Multiplexer and Rockwell
Directory Server if the above service does not stop.

3. Delete the project folder (application folder) from the following directory - Depending on if it is
ME or SE:

mhtml:file://C:\Users\acupello\AppData\Local\Microsoft\Windows\INetCache\Conte... 26/01/2019
24950 - FactoryTalk View Studio: Manually Removing an Application from Existing ... Page 2 of 3

In Windows 7

ME: C:\Users\Public\Public Documents\RSView


Enterprise\ME\HMI Projects\ProjectName
SE: C:\Users\Public\Public Documents\RSView
Enterprise\SE\HMI Projects\ProjectName

In Windows XP

ME: C:\Documents and Settings\Shared Documents\RSView


Enterprise\ME\HMI Projects\ProjectName
SE: C:\Documents and Settings\Shared Documents\RSView
Enterprise\SE\HMI Projects\ProjectName

4. Then delete the <ApplicationName>.RnaD files from the following directories - Note: The file
will not be in all of them:

In Windows 7
Note: ProgramData is a normally hidden folder in Windows 7.
C:\ProgramData\Rockwell\RNAClient\Local
C:\ProgramData\Rockwell\RNAClient\Local\RNAStore
C:\ProgramData\Rockwell\RNAServer\Local
C:\ProgramData\Rockwell\RNAServer\Local\RNAStore

In Windows XP

C:\Documents and Settings\All Users\Application


Data\Rockwell\RNAClient\Local
C:\Documents and Settings\All Users\Application
Data\Rockwell\RNAClient\Local\RNAStore
C:\Documents and Settings\All Users\Application
Data\Rockwell\RNAServer\Local
C:\Documents and Settings\All Users\Application
Data\Rockwell\RNAServer\Local\RNAStore

5. Once done, ensure that you set the startup types of the services that were disabled in step 2
back are set back to Automatic then, reboot the PC.

Notes:

mhtml:file://C:\Users\acupello\AppData\Local\Microsoft\Windows\INetCache\Conte... 26/01/2019
24950 - FactoryTalk View Studio: Manually Removing an Application from Existing ... Page 3 of 3

Replace \Local with \Global in file path for SE Networked applications


The procedure can be done in Safe Mode (F8 at start of WINDOWS), in place of stopping the
services in step 1 and 2

DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular
subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information
in this web site is not intended to constitute application, design, software or other professional
engineering advice or services. Before making any decision or taking any action, which might affect
your equipment, you should consult a qualified professional advisor.

ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR


ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE
CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER,
ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT
SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT,
INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF
ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR


IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY,
INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE,
MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not
countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.

If you have a problem with this page, please use this link
(mailto:rockwellautomation@custhelp.com?Subject=Problems%20with%20web%20page%20%
2Fapp%2Fanswers%2Fdetail%2Fa_id%2F24950&Body=%28Please%20include%20steps%20to%
20reproduce%20and%20a%20screenshot%20of%20the%20entire%20browser%20window%
20including%20the%20URL%20and%20error%20message.%0AFor%20chat%20problems%2C%
20specify%20which%20chat%20option%20you%20are%20selecting.%29%0A%0Ahttp%3A%2F%
2Frockwellautomation.custhelp.com%2Fapp%2Fanswers%2Fdetail%2Fa_id%2F24950%0A%
0AReferer:%20%0A%0A1) to report it to us by email.

This page is best viewed in Internet Explorer 11, Edge, Firefox 41, Chrome 46, Safari 9 or newer.

mhtml:file://C:\Users\acupello\AppData\Local\Microsoft\Windows\INetCache\Conte... 26/01/2019

S-ar putea să vă placă și