Documente Academic
Documente Profesional
Documente Cultură
This technical note tells how to set transmitter failure levels within CCC
controllers for projects which use “smart” transmitters.
Smart transmitters use a diagnostic routine to monitor themselves during
normal operation. If a fault is detected, the transmitter can indicate the
condition by setting the output current to a configurable value beyond the
Technical Note
normal operating range. The controller can then detect the transmitter
fault and take appropriate control action.
Each smart transmitter can be configured to indicate a fault with either a
high or low output, and the controller must be configured for the proper
A/D failure limits and fallback action.
The operational range and fault levels for smart transmitters vary by man-
ufacturer. Alarm levels for various Standard and Namur transmitters are
shown in Figure 1 on page 2. Note the unique low and high fail detec-
tion thresholds for standard Yokogawa and Rosemount smart
transmitters.
A saturated output from a transmitter should not be considered as failure
as a saturated output can represent a real process condition.
AM CCC controllers test each transmitter input against a configured range,
as discussed in the following sections:
• “Series 3 Plus” on page 2
• “Series 3++” on page 3
• “Series 4” on page 3
• “Series 5 and 5M” on page 5
• “Prodigy” on page 6
The failure level threshold settings should be set in both primary and sec-
ondary controllers:
• Series 5: primary IOC and secondary IOC
• Prodigy: primary IOP and secondary IOP)
Rosemount Smart
3.80
Standard
< 3.75 > 3.90 4 - 20 < 20.90 > 21.75
NAMUR
< 3.60 > 3.80 4 - 20 < 20.50 > 22.50
Honeywell Smart
Standard
< 3.60 > 3.80 4 - 20 < 20.90 > 21.00
NAMUR
< 3.60 > 3.80 4 - 20 < 20.50 > 21.00
Foxboro HART
Standard
< 3.60 > 3.80 4 - 20 < 20.50 > 21.00
Series 3 Plus The maximum current that can be read within Series 3 Plus controllers is
20.48 mA. Since this value is typically within the saturation range of a
smart transmitter, the controller cannot tell the difference between a
transmitter that is saturated and a smart transmitter that is producing a
high-fault signal. Therefore, the smart transmitter must be configured to
produce a low signal upon failure, and the controller should be configured
as follows:
• The MODE:D ANIN # LOW parameter defines a minimum value
below which an input is considered to have failed. To detect a smart
transmitter fault and not a saturation level, it should be set to a value
between the highest low-fault signal and the lowest saturation level.
A setting of 18.5% (3.70 mA) is recommended for all projects, which
will also cover open wire or fuse failures.
Note:
Rosemount Standard = 19.0% (3.80 mA) recommended
Yokogawa Standard = 17.5% (3.50 mA) recommended
++ ++
Series 3 The maximum current that can be read within Series 3 controllers is
23.2 mA. Therefore, the controller can tell if a transmitter is saturated or a
smart transmitter is producing a high fault signal. The controller should be
configured as follows:
• A MODE:D ANIN # LOW parameter setting of 18.5% (3.70 mA) is
recommended for all projects, which will also cover open wire or
fuse failures.
Note:
Rosemount Standard = 19.0% (3.80 mA) recommended
Yokogawa Standard = 17.5% (3.50 mA) recommended
• The MODE:D ANIN # HIGH parameter should be set to 21.0 mA. A
setting of 102.3% (entered as A2.3) is specifically coded within a
++
Series 3 controller to correspond to a current of 21.0 mA.
Note:
Yokogawa Standard = 108.0% (21.6 mA) recommended
++
For Series 3 controllers, 0.0 mA corresponds to 0% and 20.0 mA to
100%. For more information on transmitter configuration and testing in
++
Series 3 controllers, refer to Input/Output Features in Chapter 3 of
UM3301.
Series 4 The maximum transmitter current that can be read within Series 4 con-
trollers can vary depending on hardware configuration. Therefore, a “low-
fault” smart transmitter configuration may be required in some projects,
while a “low-fault” or “high-fault” configuration may be possible in others.
The _sys_ani_failure_low, _sys_ani_failure_high system parameters set
the low and high alarms for each transmitter input. A failure will be trig-
gered if a transmitter input exceeds an alarm level for longer than the
number of scans configured with the _sys_ani_fail_limit parameter.
• _sys_ani_failure_low has a range of -4095 to 4095 counts. Setting it
to -4095 counts will mask low alarms
• _sys_ani_failure_high has a range of 0 to 4095 counts. Setting it to
4095 will mask high alarms
Table 1 gives the recommended low and high transmitter alarm settings
for each type of Series 4 daughter card for all types of smart transmitters
except Rosemount Standard (see Table 2) and Yokogawa Standard (see
Table 3 on page 5). The recommended settings correspond to a low
alarm level of 3.70 mA and a high alarm level of 21.0 mA.
_sys_ani_failure_low _sys_ani_failure_high
Daughter Card
(counts) (counts)
DC5100 546 4335
DC5200 548 4357
DC5201 545 4319
DC5412 539 4287
_sys_ani_failure_low _sys_ani_failure_high
Daughter Card
(counts) (counts)
DC5100 568 4335
DC5200 570 4357
DC5201 567 4319
DC5412 560 4287
_sys_ani_failure_low _sys_ani_failure_high
Daughter Card
(counts) (counts)
DC5100 502 4467
DC5200 504 4489
DC5201 501 4450
DC5412 495 4417
Series 5 and The maximum transmitter current that can be read within Series 5 and
5M 5M controllers can vary depending on hardware configuration. Therefore,
a “low-fault” smart transmitter configuration may be required in some
projects, while a “low-fault” or “high-fault” configuration may be possible
in others.
The failure level threshold settings should be set in both primary and sec-
ondary controllers (primary IOC and secondary IOC).
The _LIO.IOC#_Config.ANI.ani_##.ani_alarm_Low and ani_alarm_High
parameters set the transmitter input low and high values for each analog
input, beyond which an LL or HH out-of-range error and alarm are
indicated:
• ani_alarm_Low can be set between a range of -50% (-4 mA) and
25% (8 mA), and has a default setting of -10% (2.4 mA). A setting of
-1.875% (3.70 mA) is recommended for all projects.
Note:
Rosemount Standard = -1.250% (3.80 mA) recommended
Yokogawa Standard = -3.125% (3.50 mA) recommended
• ani_alarm_High can be set between a range of 25% (8 mA) and
150% (28 mA), and has a default setting of 110% (21.6 mA). A set-
ting of 106.25% (21.0 mA) is recommended for all projects.
Note:
Yokogawa Standard = 110.0% (21.6 mA) recommended
An analog input signal greater than 100% (20 mA) but below 110% (21.6
mA) will result in a constant 100% signal within the control application.
Similarly, a signal between 0% (4 mA) and -10% (2.4 mA) will result in a
constant 0% signal in the application. An analog input signal above 110%
or below -10% will produce an input signal failure within the control
application.
For Series 5 controllers, 4.0 mA corresponds to 0% and 20.0 mA to
100%.
Prodigy The maximum transmitter current that can be read within Prodigy control-
lers can vary depending on hardware configuration. Therefore, a “low-
fault” smart transmitter configuration may be required in some projects,
while a “low-fault” or “high-fault” configuration may be possible in others.
The failure level threshold settings should be set in both primary and sec-
ondary controllers (primary IOP and secondary IOP).
The _LIO.IOP_#_config.ANI.ani[#].lowLimit and highLimit parameters set
the transmitter input low and high values for each analog input, beyond
which an LL or HH out-of-range error and alarm are indicated:
• lowLimit can be set between a range of -50% (-4 mA) and 25% (8
mA), and has a default setting of -10% (2.4 mA). A setting of -1.875%
(3.70 mA) is recommended for all projects.
Note:
Rosemount Standard = -1.250% (3.80 mA) recommended
Yokogawa Standard = -3.125% (3.50 mA) recommended
• highLimit can be set between a range of 25% (8 mA) and 150% (28
mA), and has a default setting of 110% (21.6 mA). A setting of
106.25% (21.0 mA) is recommended for all projects.
Note:
Yokogawa Standard = 110.0% (21.6 mA) recommended
An analog input signal greater than 100% (20 mA) but below 110% (21.6
mA) will result in a constant 100% signal within the control application.
Similarly, a signal between 0% (4 mA) and -10% (2.4 mA) will result in a
constant 0% signal in the application. An analog input signal above 110%
or below -10% will produce an input signal failure within the control
application.
For Prodigy controllers, 4.0 mA corresponds to 0% and 20.0 mA to 100%.
Non-Smart For other analog input signals, such as from non-smart analog transmit-
ters, DCS (RLC, remote set point), motor current, valve position feedback
signals etc., a setting not to exceed 3 mA is recommended since those
signals often drift significantly.
The TTC and impeller logos, Air Miser, Guardian, Prodigy, Recycle Trip, Reliant, Safety On, SureLink, TTC, Total Train Control, TrainTools, TrainView,
++
TrainWare, Vanguard, Vantage, Vibrant, and WOIS are registered trademarks; and the Series 3 and Series 5 logos, COMMAND, and TrainPanel are
trademarks of Compressor Controls Corp. © 2016