Sunteți pe pagina 1din 105

®

Gamewell-FCI
Control Panels
SLC Wiring Guide

Document 9021-60542
01/15/10 Rev:
P/N 9021-60542:A
A
ECN 09-403
Important Limitations Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
While a fire alarm system may lower insurance rates, matches (especially in bedrooms), smoking in bed, and
it is not a substitute for fire insurance! violent explosions (caused by escaping gas, improper
An automatic fire alarm system- typically made up of storage of flammable materials, etc.).
smoke detectors, heat detectors, manual pull stations, Heat detectors do not sense particles of combustion and
audible warning devices, and a fire alarm control panel with alarm only when heat on their sensors increases at a
remote notification capability - can provide early warning of predetermined rate or reaches a predetermined level.
a developing fire. Such a system, however, does not Rate-of-rise heat detectors may be subject to reduced
assure protection against property damage or loss of life sensitivity over time. For this reason, the rate-of-rise
resulting from a fire. feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Heat detectors
The Manufacturer recommends that smoke and/or heat
are designed to protect property, not life.
detectors be located throughout a protected premise
following the recommendations of the current edition of the IMPORTANT! Smoke detectors must be installed in the
National Fire Protection Association, Standard 72 (NFPA same room as the control panel and in rooms used by the
72), manufacturer’s recommendations, State and local system for the connection of alarm transmission wiring,
codes, and the recommendations contained in the Guide communications, signaling, and/or power. If detectors are
for Proper Use of System Smoke Detectors, which are not so located, a developing fire may damage the alarm
made available at no charge to all installing dealers. These system, crippling its ability to report a fire.
documents can be found at http://www.systemsensor.co/
Audible warning devices such as bells may not alert
html/applict.html. A study by the Federal Emergency people if these devices are located on the other side of
Management Agency (an agency of the United States closed or partly open doors or are located on another floor
government) indicated that smoke detectors may not go off of a building. Any warning device may fail to alert people
in as many as 35% of all fires. While fire alarm systems are with a disability or those who have recently consumed
designed to provide early warning against fire, they do not drugs, alcohol or medication. Please note that:
guarantee warning or protection against fire. A fire alarm • Strobes can, under certain circumstances, cause
system may not provide timely or adequate warning, or seizures in people with conditions such as epilepsy.
simply may not function, for a variety of reasons. • Studies have shown that certain people, even when
Smoke Detectors may not sense fire where smoke cannot they hear a fire alarm signal, do not respond or
reach the detectors such as in chimneys, in or behind comprehend the meaning of the signal. It is the
walls, on roofs, or on the other side of closed doors. Smoke property owner’s responsibility to conduct fire drills
detectors also may not sense a fire on another level or floor and other training exercise to make people aware of
of a building. A second-floor detector, for example, may not fire alarm signals and instruct them on the proper
sense a first-floor or basement fire. reaction to alarm signals.
• In rare instances, the sounding of a warning device
Particles of combustion or “smoke” from a developing
fire may not reach the sensing chambers of smoke can cause temporary or permanent hearing loss.
detectors because: A fire alarm system will not operate without any electrical
• Barriers such as closed or partially closed doors, power. If AC power fails the system will operate from
walls, or chimneys may inhibit particle or smoke flow. standby batteries only for a specified time and only if the
• Smoke particles may become “cold,” stratify, and not batteries have been properly maintained and replaced
reach the ceiling or upper walls where detectors are regularly.
located.
Equipment used in the system may not be technically
• Smoke particles may be blown away from detectors by
compatible with the control panel. It is essential to use only
air outlets.
equipment listed for service with your control panel.
• Smoke particles may be drawn into air returns before
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to premise to a central monitoring station may be out of
alarm smoke detectors. Smoke detectors are designed to service or temporarily disabled. For added protection
alarm at various levels of smoke density. If such density against telephone line failure, backup radio transmission
levels are not created by a developing fire at the location of systems are recommended.
detectors, the detectors will not go into alarm. The most common cause of fire alarm malfunction is
Smoke detectors, even when working properly, have inadequate maintenance. To keep the entire fire alarm
sensing limitations. Detectors that have photoelectronic system in excellent working order, ongoing maintenance is
sensing chambers tend to detect smoldering fires better required per the manufacturer’s recommendations, and UL
than flaming fires, which have little visible smoke. and NFPA standards. At a minimum, the requirements of
Detectors that have ionizing-type sensing chambers tend NFPA 72 shall be followed. Environments with large
to detect fast-flaming fires better than smoldering fires. amounts of dust, dirt or high air velocity require more
Because fires develop in different ways and are often frequent maintenance. A maintenance agreement should
unpredictable in their growth, neither type of detector is be arranged through the local manufacturer’s
necessarily best and a given type of detector may not representative. Maintenance should be scheduled monthly.
provide adequate warning of a fire.

2 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Installation Precautions Survivability
Per the National Fire Alarm Code, NFPA 72, all circuits
Adherence to the following will aid in problem-free necessary for the operation of the operation of the
installation with long-term reliability: notification appliances shall be protected until they enter
WARNING - Several different sources of power can be the evacuation signaling zone that they serve. Any of the
connected to the fire alarm control panel. Disconnect all following methods shall be considered acceptable as
sources of power before servicing. Control unit and meeting these requirements:
associated equipment may be damaged by removing 1) A 2-hour rated cable or cable system
and/or inserting cards, modules, or interconnecting 2) A 2-hour rated enclosure
cables while the unit is energized. Do not attempt to 3) Performance alternatives approved by Authority
install, service, or operate this unit until manuals are read Having Jurisdiction (AHJ).
and understood.
CAUTION - System Re-acceptance Test after Like all solid state electronic devices, this system
Software Changes: To ensure proper system operation, may operate erratically or can be damaged when
this product must be tested in accordance with NFPA 72 subjected to lightning induced transients. Although no
after any programming operation or change in site- system is completely immune from lightning transients
specific software. Reacceptance testing is required after and interference, proper grounding will reduce
any change, addition or deletion of system components, susceptibility. Overhead or outside aerial wiring is not
or after any modification, repair or adjustment to system recommended, due to an increased susceptibility to
hardware or wiring. All components, circuits, system nearby lightning strikes. Consult with the Technical
operations, or software functions known to be affected Services Department if any problems are anticipated or
by a change must be 100% tested. In addition, to ensure encountered.
that other operations are not inadvertently affected, at
least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, Disconnect AC power and batteries prior to removing
must also be tested and proper system operation or inserting circuit boards. Failure to do so can damage
verified. circuits.

This system meets NFPA requirements for operation at


0-49° C/32-120° F and at a relative humidity 93% ± 2% Remove all electronic assemblies prior to any drilling,
RH (non-condensing) at 32° C ± 2° C (90° F ± 3° F). filing, reaming, or punching of the enclosure. When
However, the useful life of the system’s standby batteries possible, make all cable entries from the sides or rear.
and the electronic components may be adversely Before making modifications, verify that they will not
affected by extreme temperature ranges and humidity. interfere with battery, transformer, or printed circuit board
Therefore, it is recommended that this system and its location.
peripherals be installed in an environment with a normal Do not tighten screw terminals more than 9 in-lbs.
room temperature of 15-27° C/60-80° F. Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with
Verify that wire sizes are adequate for all initiating and screw terminal removal.
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage. This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
Follow the instructions in the installation, operating, handling any circuits so that static charges are removed
and programming manuals. These instructions must be from the body. Use static suppressive packaging to
followed to avoid damage to the control panel and protect electronic assemblies removed from the unit.
associated equipment FACP operation and reliability
Precau-D2-8-2008
depend upon proper installation.

FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and Canadian Requirements
used in accordance with the instruction manual may This digital apparatus does not exceed the Class A limits
cause interference to radio communications. It has been for radiation noise emissions from digital apparatus set
tested and found to comply with the limits for Class A out in the Radio Interference Regulations of the
computing devices pursuant to Subpart B of Part 15 of Canadian Department of Communications.
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are Le present appareil numerique n’emet pas de bruits
operating in a commercial environment. Operation of this radioelectriques depassant les limites applicables aux
equipment in a residential area is likely to cause appareils numeriques de la Classe A prescrites dan le
interference, in which case the user will be required to Reglement sur le brouillage radioelectrique edicte par le
correct the interference at his or her own expense. ministere des Communications du Canada.

Gamewell-FCI® and SmartScan® are registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a
trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered
trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 3


Software Downloads
In order to supply the latest features and functionality in fire alarms and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for
a specific application.

Documentation Feedback
Your feedback helps us keep out documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services

4 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Table of Contents

Table of Contents
Section 1: Introduction............................................................................................................. 7
1.1: About This Manual ........................................................................................................................................7
1.1.1: CLIP and Velociti® Modes..................................................................................................................7
1.2: UL 864 Compliance.......................................................................................................................................8
1.2.1: Products Subject to AHJ Approval......................................................................................................8
1.3: Reference Documentation ............................................................................................................................9
1.4: SLC Overview .............................................................................................................................................10
1.5: Polling Protocols .........................................................................................................................................10
1.6: Devices .......................................................................................................................................................11
1.6.1: Monitor/Zone Interface Modules.......................................................................................................11
1.6.2: Control Modules ................................................................................................................................11
1.6.3: Isolator Modules ................................................................................................................................11
1.6.4: Relay Modules...................................................................................................................................11
1.6.5: Plug-in Detector Bases ......................................................................................................................11
1.6.6: Intelligent Detectors .........................................................................................................................12
1.6.7: Addressable Manual Pull Stations.....................................................................................................12
1.7: SLC Capacity...............................................................................................................................................12
1.8: SLC Performance.........................................................................................................................................13
Section 2: Wiring Requirements............................................................................................ 14
2.1: Recommended SLC Wiring.........................................................................................................................14
2.2: Two-Wire SLC - Style 4 (Class B) ..............................................................................................................15
2.2.1: Measuring SLC Resistance................................................................................................................15
2.2.2: Measuring Total Wire Length ...........................................................................................................15
2.3: Four-Wire SLC Style 6 & 7 (Class A).........................................................................................................16
2.3.1: Measuring SLC Resistance................................................................................................................16
2.3.2: Measuring Total Wire Length ...........................................................................................................16
2.4: Terminal Blocks...........................................................................................................................................16
Section 3: Shielded Wire Termination .................................................................................. 17
3.1: Overview......................................................................................................................................................17
3.2: Floating Shield ............................................................................................................................................17
Section 4: SLC Circuits without Isolators ............................................................................ 18
4.1: Overview......................................................................................................................................................18
4.2: NFPA Style 4 SLC .......................................................................................................................................18
4.3: NFPA Style 6 SLC .......................................................................................................................................19
Section 5: SLC Circuits with Isolators .................................................................................. 20
5.1: Overview......................................................................................................................................................20
5.2: Fault Isolator Module ..................................................................................................................................20
5.3: Isolator Detector Bases ................................................................................................................................21
5.3.1: How an Isolator Base Works .............................................................................................................21
5.4: NFPA Style 4 SLC Using Isolator Modules ................................................................................................22
5.5: NFPA Style 6 SLC Using Isolator Modules ................................................................................................23
5.6: NFPA Style 7 SLC Using an Isolating Device ............................................................................................24
Section 6: Monitor Modules ................................................................................................... 25
6.1: Description...................................................................................................................................................25
6.1.1: Addressable Monitor Module............................................................................................................25
6.1.2: Zone Interface Module ......................................................................................................................25
6.1.3: Dual Monitor Module........................................................................................................................26
6.1.4: Miniature Monitor Module................................................................................................................26
6.2: Setting an SLC Address for a Module .........................................................................................................27
6.3: NFPA Style B IDC Using Monitor Modules ...............................................................................................28
6.4: NFPA Style D IDC Using Monitor Modules ...............................................................................................29

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 5


Table of Contents

6.5: NFPA Style B IDC Using Dual Monitor Modules.......................................................................................30


6.6: NFPA Style B IDC Using Zone Interface Modules .....................................................................................31
6.7: NFPA Style D IDC Using Zone Interface Modules.....................................................................................32
Section 7: Control Modules ................................................................................................... 33
7.1: Description ...................................................................................................................................................33
7.2: Wiring a NAC with Addressable Control Modules .....................................................................................33
7.3: Wiring a Style Y NAC (Two-Wire) with Addressable Control Modules ....................................................34
7.4: Wiring a Style Z NAC (Four-Wire) with Addressable Control Modules ....................................................35
Section 8: Relay Module ........................................................................................................ 36
8.1: Description ...................................................................................................................................................36
8.2: Wiring the Addressable Relay Module (Form-C Relay) .............................................................................36
Section 9: Intelligent Detector Bases ................................................................................... 37
9.1: Description ...................................................................................................................................................37
9.2: Wiring a Detector Base ................................................................................................................................37
9.3: Wiring an Isolator Base................................................................................................................................38
9.4: Wiring a Relay Base.....................................................................................................................................38
9.5: Wiring a Sounder Base.................................................................................................................................39
Section 10: Addressable Manual Pull Station...................................................................... 41
10.1: Description .................................................................................................................................................41
10.2: Wiring a Manual Pull Station.....................................................................................................................41
Appendix A: Power Considerations...................................................................................... 42
A.1: Supplying Power to 24 VDC Detectors and NACs ....................................................................................42
A.2: Supervising 24 VDC Power ........................................................................................................................43
A.2.1: Power Supervision Relay..................................................................................................................43
A.2.2: Using the Addressable Control Module Without Relay ...................................................................45
Appendix B: SLC Surge Suppression .................................................................................. 48
B.1: Introduction .................................................................................................................................................48
B.2: Installation ...................................................................................................................................................49
B.2.1: 7100 Series and E3 Series .............................................................................................................49
Appendix C: Terminal Conversion Charts for V-type and H-type Devices ....................... 52
C.1: AOM-2RF ...................................................................................................................................................52
C.2: AOM-2SF and AMM-4F ............................................................................................................................53
C.3: AMM-2F .....................................................................................................................................................54
Index ........................................................................................................................................ 56

6 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Section 1: Introduction
1.1 About This Manual
This document describes the installation and wiring connections of various Signaling Line Circuit
(SLC) devices, when the SLC devices are used with the following systems:
• E3 Series® Fire Alarm Control Panel and E3 Series Networks
• 7100 Series Fire Alarm Control Panel
• E3 Series® Broadband
• NetSOLO® Broadband
This document also provides basic information that applies to SLC loops in general, such as the
branch resistance measurements.
See Section 2.1 for information on the basic panel-end SLC connections. For additional
information about each control panel, modules, detectors referenced in this document, and the part
numbers assigned to the the corresponding manuals, refer to the respective installation manual as
listed in Section 1.3, “Reference Documentation”.

1.1.1 CLIP and Velociti® Modes


There are two types of formats used with the SLC circuit modules. Depending on the date the
product was manufactured, the SLC circuit modules may appear in either of the following two
different formats. Figure 1.1.1.1 illustrates the CLIP and Velociti formats.
• CLIP Communication Protocol (Old Format)
The CLIP communication protocol allows backward compatibility with older fire alarm
control panel (FACP) systems (for example, 7200 and 7100 Systems). While the CLIP format
is no longer manufactured for these models (7200 and 7100 Systems), for additional
information, refer to the Appendix C, “Terminal Conversion Charts for V-type and H-type
Devices”. The SLC circuit modules that use the CLIP format have vertical rotary dials.
• Velociti® Protocol (New Format)
The faster Velociti protocol includes an increased device address count which is used with the
E3 Series Systems. SLC circuit modules that use the Velociti format have horizontal rotary
dials.

NOTE: The re-designed modules are capable of operating in both the CLIP communication
protocol and in the Velociti® protocol.

Appendix C contains terminal conversion charts that identify the old CLIP and new Velociti
formats. The model name does not indicate the format. In Appendix C, the following module
naming conventions are used to identify the two types of rotary switches.
• “h-type” rotary switches (uses the new Velociti format, which has horizontal rotary dials).
• “v-type” rotary switches (uses the old CLIP format, which has vertical rotary dials).
Figure 1.1.1.1 illustrates the modules’ formats.

CLIP Format
Vertical rotary dials.
Old-format .

Velociti Format
Horizontal rotary
dials. New-format .

Figure 1.1.1.1 Example of Old and New Module Formats

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 7


Introduction UL 864 Compliance

1.2 UL 864 Compliance


1.2.1 Products Subject to AHJ Approval
This SLC Wiring Manual accompanies installation, operation, and programming manuals for
various fire alarm control panels (FACPs), and has been certified to comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL® 864 9th Edition.

8 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Reference Documentation Introduction

1.3 Reference Documentation


Table 1.3.1.1 provides a list of documents referenced in this manual, as well as a list of documents
for other selected compatible devices. The document series chart provides the current document
revision. A copy of this document is included in every shipment.
Document
Model Description
Part Number
Reference Documentation
9000-0447 7100 Series 7100 Series Fire Alarm Control Panel
9000-0552 NetSOLO Broadband NetSOLO Broadband Network Emergency Voice
Evacuation System
9000-0574 E3 Series E3 Series Expandable Emergency Evacuation
System
9000-0575 E3 Series Broadband E3 Series Broadband Network Emergency Voice
Evacuation System
Gamewell-FCI Addressable Sensors & Modules
Velociti® Series Sensors and Bases
9000-0557 ASD-IL2F Analog Ionization Sensor
9000-0558 ASD-PL2F Analog Photoelectronic Sensor
9000-0472 ASD-PTL2F Analog Photoelectronic Sensor 135
9000-0470 ATD-RL2F Thermal Sensor ROR 15 / 135
9000-0192 ATD-HL2F Thermal Sensor 190
9000-0192 ATD-L2F Thermal Sensor 135
9000-0519 MCCS-ACCLIMATE2F Multi-Criteria Analog Sensor
9000-0531 ASD-LS Analog Laser Sensor, CLIP
I56-2747-000R (SS) ADPF Analog Duct Detector without Relay
I56-2747-000R (SS) ADPRF Analog Duct Detector with Relay
I56-2747-000R (SS) ADP-F-SB Duct Detector Board, Replacement
9000-0406 ADB-FLF Base, Flanged, For Use with Analog Sensor or
Velociti® Sensors
9000-0466 ASD-FILTREXF Analog ASD-FILTREX Sensor
9000-0466 ADB-FILTREXF Base, Flanged, For Use with ASD-FILTREX or
ASD-FILTREXF
9000-0188 ABD-2F Single-ended Reflected Beam Sensor
9000-0188 ABD-RT2F Single-ended Reflected Beam Sensor with Integral
Sensitivity Test
Velociti® Series Modules and Pull Station
9000-0590 AMM-2F Addressable Monitor Module, Class “B”
9000-0592 AMM-2IF Addressable Dual Monitor Module, 2 Circuit, Style B
9000-0479 AMM-4F Addressable Monitor Module, Class “A”
9000-0591 AMM-4SF Addressable Sub-Loop Module, Class “A”
9000-0594 AOM-2RF Addressable Output Relay Control Module
9000-0593 AOM-2SF Addressable Output Supervised Module
9000-0595 AOM-MUXF Multiplex Output Module
9000-0596 AOM-TELF Telephone Monitor Module
9000-0554 MMI-10F Multi-Module Input, 10 Input Module
9000-0556 MMI-6SF Multi-Module Input, Signal
Table 1.3.1.1 SLC Devices Reference Documentation

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 9


Introduction SLC Overview

Document
Model Description
Part Number
9000-0555 MMO-6RF Multi-Module 6 Zone Interface Module
9000-0553 MMO-6SF Multi-Module Output, Relay
9000-0518 MS-7AF Addressable Double Action Station
(AMM-2SF Mini Mod Incl)
I56-2763-00 (SS) MS-7ASF Addressable Single Action Station
(AMM-2SF Mini-Mod Incl)
Other Sensors, Bases and Modules
I56-0725-012R (SS) B224BI Base with Auxiliary Relay, Isolator for Style 7
Operation
I56-2815-000R (SS) B224RB Base with Auxiliary Relay
I56-3392-003R B200SR Intelligent Sounder Base
I56-0357-008R (SS) B501 Detector base without flange (European), 4-Inches
Diameter
I56-1382-001 (SS) M500X Fault Isolator Module
Table 1.3.1.1 SLC Devices Reference Documentation (Continued)

1.4 SLC Overview


Communication between the control panel and intelligent addressable monitor and control devices
takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of
the following:
• NFPA Class B, Style 4 • NFPA Class A, Style 6 • NFPA Class A, Style 7
At least one secondary surge protector must be used with each SLC wiring pair whenever the SLC
wiring runs outside the building. For detailed information, refer to Appendix B, “SLC Surge
Suppression”.

1.5 Polling Protocols


There are two (2) modes of polling protocols:
• Velociti® Mode
In the Velociti Mode, the number of Velociti devices are set to 159 detectors and 159 modules
per circuit. The total number of Velociti devices that can be used is 318 devices per circuit.
• CLIP Mode
In the CLIP Mode, the number of CLIP devices is limited to 99 detectors and 99 modules per
circuit. The total number of CLIP devices that can be used is 198 per circuit.

10 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Devices Introduction

1.6 Devices
1.6.1 Monitor/Zone Interface Modules
These addressable modules allow the control panel to monitor entire circuits of conventional alarm
initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and
supervisory devices. The following modules support Velociti or CLIP mode.
• AMM-2F Monitor Module
• AMM-2IF Dual Monitor Module
• AMM-2SF Addressable Mini-Monitor Module
• AMM-4F Zone Interface Module
• MMI-6F Multi-Module Input, Signal
The MMI-6F Module allows an intelligent alarm system to monitor six (6) zones of
conventional two-wire detectors.
• MMI-10F Multi-Module Input, 10 Input Module
The MMI-10F Module supervises ten (10) Class-B addressable Initiating Device Circuits
(IDC) which monitor normally open contact initiating devices.

1.6.2 Control Modules


Through the following addressable modules, the control panel can selectively activate Notification
Appliance Circuits (NAC). The following modules support Velociti or CLIP mode.
• AOM-2SF Control Module
• MMO-6SF Multi-Module Output, Relay
The MMO-6SF Module controls six (6) NAC or speaker/telephone circuits

1.6.3 Isolator Modules


Isolator Modules permit a short-circuited section of the SLC to be fault isolated from the remainder
of the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator
Modules are required to meet the requirements of an NFPA Style 7 circuit. The following module
supports Velociti or CLIP mode.
• M500X Fault Isolator Module

1.6.4 Relay Modules


This addressable module provides the control panel with a dry-contact output for activating a
variety of auxiliary devices. The following modules support Velociti or CLIP mode.
• AOM-2RF Relay Module
• MMO-6RF Controls six (6) Form-C Relays

1.6.5 Plug-in Detector Bases


Plug-in detector bases provide a connection between the SLC and a variety of intelligent detectors
which are snapped into place. Standard and isolator bases are used depending upon which NFPA
SLC style is required. Sounder and relay bases are similar to standard bases, but have sound or
relay capabilities.
• Standard Base Models
– B501(4 inch (10.16 cm) standard small diameter base, commonly used in European
installations)
– B710LP (6 inch (15.2 cm) standard large diameter base, commonly used in US installations)
• Isolator Base Model
– B224BI isolator base.
• Sounder Base Models
– B200SR (Intelligent Sounder Base)
• Relay Base Model
– B224RB relay base

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 11


Introduction SLC Capacity

1.6.6 Intelligent Detectors


The following list the Intelligent Detectors and supports both Velociti and CLIP modes.
• MCS-ACCLIMATE2F
Addressable, intelligent detector that combines a photoelectronic sensing chamber and a fixed
temperature heat detection 135° F (57.2°C).
• ASD-IL2F
Addressable, intelligent smoke detector that incorporates an ionization sensing chamber. This
detector is designed to provide an open area protection.
• ASD-PL2F
Analog, addressable intelligent smoke detector that uses a photoelectronic sensing chamber.
This detector is Listed for use in ducts. It is designed to provide an open area protection. The
ASD-PL2F adds thermal sensors that will go into alarm at a fixed temperature of 135° F
(57.2°C).
• ATD-RL2F
Intelligent thermistor sensing circuit for fast response. This detector is designed to provide an
open area protection with 50 foot spacing capability. A fixed temperature sensor with 135°F
(57.2°C) fixed temperature alarm. The ATD-RL2F incorporates a thermal rate-of-rise of 15°F
(8.3°C).
• ADP-RF
Photoelectronic Duct Detector.
• ADP-F
Low-flow Photoelectronic Duct Detector, with an extended speed range of 100–4000 FPM
(0.5 m/s to 20.3 m/s).
The following Intelligent Detector supports only CLIP mode.
• ASD-LS
An advanced intelligent photoelectronic detector that uses a laser diode, special optics, and
signal processing to obtain extremely high sensitivity. Although this detector supports CLIP
mode, it can operate in a Velociti System.

1.6.7 Addressable Manual Pull Stations


The following are the addressable manual pull stations that support both Velociti and CLIP mode.
• MS-7AF
The MS-7AF is a dual-action pull station that, when activated, provides an addressable
identification and its location to the control panel. An addressable monitor module is mounted
inside the pull station to facilitate servicing and replacement.
• MS-7ASF
The MS-7ASF is a Spanish/English labeled version.

1.7 SLC Capacity


The protocol selected for an SLC loop determines the maximum number of devices that can be
handled by the SLC loop (see Section 1.5, “Polling Protocols”). Within those limits, the individual
control panel may have additional restrictions. For additional information, refer to the specific the
panel installation manual.

12 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


SLC Performance Introduction

1.8 SLC Performance


SLC performance (Style 4, Style 6, or Style 7) depends on the configuration of the circuit and the
components on the circuit (for a list of see Table 1.3.1.1 for ). The SLC operation, that complies
with Style 7 requirements, isolates each addressable device on the SLC from faults that may occur
on the SLC.
Wiring style requirements are determined by the national and local codes. Consult with the
Authority Having Jurisdiction (AHJ) before wiring the SLC. The table (derived from NFPA 72-
2009) lists the trouble conditions that result when a fault exists on an SLC. Additional information
is identified in Section 2, “Wiring Requirements”, and Section 3, “Shielded Wire Termination”.

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 13


Section 2: Wiring Requirements
2.1 Recommended SLC Wiring
To maximize the distance on the SLC loop, use the recommended type of wire. Using other wiring
types makes the SLC circuit more susceptible to electrical interference and thus reduces its
maximum circuit length.
• Maximum allowable field wiring resistance is 40 ohms per circuit. Use unshielded, twisted-
pair cable.
• Maximum circuit capacitance is 0.5 µf.
Table 2.1 lists the recommended wiring requirements.
Distance
Circuit Type Circuit Function Wire Requirements Typical Wire Type*
(feet/meters)
SLC Connects to Twisted-unshielded pair, 12 to 18 AWG 10,000 ft. (3,000 m) 12 AWG (3.1 mm2)
(power-limited) intelligent and (3.1 to 0.78 mm2) 40 Ohms maximum 8,000 ft. (2,400 m) 14 AWG (2.00 mm2)
addressable per length of Style 6 & 7 loops. 40
modules. Ohms combined-branch circuits 4,875 ft. (1,450 m) 16 AWG (1.30 mm2)
maximum for Style 4 loop. 3,225 ft. (980 m) 18 AWG (0.78 mm2)
MC Cable with 2 conductor twisted.
Not Shielded wire, in conduit or outside of 1,000 ft. (304.8 m) 12 to 18 AWG
recommended conduit or MC cable. (3.1 to 0.78 mm2)
Note 1: Shielded wire is not
recommended for SLC use, unless the
AHJ requires the wiring.
MC Cable with 3 conductor twisted.
Note 2: Maximum total capacitance of
all SLC wiring (both between
conductors and from any conductor to
ground) should not exceed 0.5
microfarads.
EIA-485 Connects to Twisted-unshielded pair with a 3,000 ft .(maximum) 16 AWG (1.30 mm2)
(power-limited) LCD-E3, ASM-16, characteristic impedance of 120
and ANU-48 Ohms. 16 AWG (0.78 mm2) minimum.
modules
EIA-232 Connects to Twisted-unshielded pair. 18 AWG 10/50 ft. 16 AWG (1.30 mm2)
(power-limited) Printers, CRT, (0.78 mm2) minimum (without modem)
E3 or PC.
NAC E3 12-18 AWG (3.1 to 0.78 mm2). At To meet 1.2 V drop, or 12 to 18 AWG
Notification (power-limited) alarm current level, no more than a 1.2 sized to provide the (3.1 to 0.78 mm2)
Appliance V drop at the end of the circuit, or sized minimum rated
Circuit to provide the minimum rated operating voltage of
operating voltage of the appliances the appliances used.
used.
24 VDC Power To Transmitter 12-18 AWG (3.1 to 0.78 mm2). Size To meet 1.2 volt drop 12 to 18 AWG
Runs Annunciator wire so that no more than 1.2 V drop (3.1 to 0.78 mm2)
(power-limited) across wire run from supply source to
end of any branch.
CHG-120 External battery 12 AWG (3.1 mm2) in conduit 20/6.1 (maximum) 12 AWG (3.1 mm2)
charger
ARCNET Provides interface Twisted-unshielded pair, low 3,000 ft. (.914 m) 18 AWG (3.1 mm2)
(power-limited) between network capacitance 18 AWG
nodes.
ARCNET should
be installed in a
separate conduit.
Note: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL
1459.
Table 2.1 Wiring Requirements

14 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Two-Wire SLC - Style 4 (Class B) Wiring Requirements

2.2 Two-Wire SLC - Style 4 (Class B)


2.2.1 Measuring SLC Resistance
T-tapping of the SLC wiring is permitted for two-wire Style 4 configurations. The total DC
resistance from the control panel to each branch end cannot exceed 40 ohms.
Figure 2.2.1.1 illustrates the measure DC resistance of a two-wire SLC.
1. With power removed, short the termination point of one branch at a time and measure the DC
resistance from the beginning of the SLC to the end of that particular branch.
2. Repeat this procedure for all remaining branches in the SLC.
In Figure 2.2.1.1, Branches A, B, and C all begin at the SLC terminal, even though Branch B is
T-tapped.

Branch A Branch B Branch C

SLC Out
SLC-meas5.cdr

Branch

Short Point SLC Terminal


Block
B+ B–

Figure 2.2.1.1 Measuring DC Resistance of a Two-Wire SLC

2.2.2 Measuring Total Wire Length


The total wire length of all combined branches of one SLC cannot exceed the limits described in
each system’s instruction manual. To determine the total length in each SLC, you can add all wire
segments. In Figure 2.2.1.1 above, the picture on the right shows an SLC with 3 branches.
Figure 2.2.2.1 below shows the same SLC divided into segments. To calculate the total length of
the SLC, add the lengths of Segment 1 + Segment 2 + Segment 3 + Segment 4 + Segment 5. No
segment should be summed twice.

Branch A Branch B Branch C

Segment
Segment
Five
Four

Segment
SLC-meas2.cdr

Segment Segment Three


One Two

SLC Terminal Block

Figure 2.2.2.1 Measuring the Total Wire Length of a Two-wire SLC

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 15


Wiring Requirements Four-Wire SLC Style 6 & 7 (Class A)

2.3 Four-Wire SLC Style 6 & 7 (Class A)


2.3.1 Measuring SLC Resistance
The total DC resistance of the SLC pair should not exceed 40 ohms. Figure 2.3.1.1 illustrates the
measure DC resistance of a four-wire SLC:
1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.
2. Short the SLC at the last device and measure the resistance at SLC (Out). Record the resistance
and remove the short.
3. Short the SLC at the first device and measure the resistance at SLC (Return). Record the
resistance and remove the short.
The maximum DC resistance of the SLC is the higher of 2 and 3.

SLC Out First Device

STEP 2

Last Device
SLC Return

Short Point

SLC Out

SLC-meas5.cdr
First Device
STEP 3
SLC Return

Last Device

Figure 2.3.1.1 Measuring DC Resistance of a Four-Wire SLC

2.3.2 Measuring Total Wire Length


The total wire length in a four-wire SLC cannot exceed the limits defined in each system’s
instruction manual. Figure 2.3.2.1 identifies the output and return circuits from the SLC terminal on
the control panel.

SLC channel B SLC channel A


(output loop) (return loop)

SLC Terminal Block


B+ B- A+ A–

Figure 2.3.2.1 Measuring the Wire Length of a Four-Wire SLC

2.4 Terminal Blocks


For information on the terminal blocks, refer to the following manuals:
• E3 Series Expandable Emergency Evacuation System Installation/Operation Manual,
P/N: 9000-0574
• 7100 Series Fire Alarm Control Panel, P/N: 9000-0447.

16 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Overview Shielded Wire Termination

Section 3: Shielded Wire Termination

3.1 Overview
This section shows the proper termination of the shield, if used.
Shielding of the SLC is not recommended for use with all SLC circuit wiring. If twisted-shielded
wire is used in an installation, use a floating shield to terminate the wire as described in Section 3.2.

NOTE: Use good wiring practices in compliance with local electrical codes.

3.2 Floating Shield


„ If you use shielded wire:
Twisted-unshielded wire is recommended for the E3 Series and 7100 Series SLC circuits.

! CAUTION: If the twisted-shielded pair wire is used in an installation, use a floating shield to
terminate the wire. The following precautions must be met:
• If the SLC is more than 3,000 ft. (914.4 m), divide the shield into floating segments of less than
1,000 ft. (304.8 m).
• To divide the shield wire into floating segments, cut the shield even with a jacket and tape as
shown in Figure 3.2.1.1.

Tape

SLC-swterm4.cdr

NOTE: If you use shielded wire in applications, where it is not recommended, the shielded wire will
reduce the maximum SLC length and may cause system SLC circuit faults. If shielded wire must be
used, where it is not recommended, failing to float the ends will reduce the maximum SLC length
even further.

Figure 3.2.1.1 Floating the Shield

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 17


Section 4: SLC Circuits without Isolators

4.1 Overview
This chapter describes the two styles of circuits that do not require isolation devices:
• NFPA 72 Style 4
• NFPA 72 Style 6

4.2 NFPA Style 4 SLC


Figure 4.2.1.1 illustrates the SLC wiring in compliance with NFPA Style 4 requirements. The
following are the criteria.
• T-tapping of the SLC wiring is allowed for Style 4 configuration.

Two-wire Addressable Detector

Addressable Module

T-tapped Circuits

B+ B–
SLC-style4.cdr

Control Panel
SLC

Figure 4.2.1.1 Basic NFPA Style 4 SLC

18 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


NFPA Style 6 SLC SLC Circuits without Isolators

4.3 NFPA Style 6 SLC


Figure 4.3.1.1 illustrates the SLC wiring in compliance with NFPA Style 6 requirements..

Two-wire Addressable Detector

SLC Out

Addressable Module

SLC Return

B+ B– A– A+

SLC-style6.cdr
Control Panel
SLC

NOTE: T-tapping of the SLC wiring is NOT allowed for the Style 6 configuration.

Figure 4.3.1.1 Basic NFPA Style 6 SLC

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 19


Section 5: SLC Circuits with Isolators
5.1 Overview
There are two isolator devices used to protect critical elements of the Velociti mode or CLIP-mode
SLC circuit from faults on other SLC branches or segments.
• M500X Fault Isolator Module
• Isolator Detector Base B224BI
A Fault Isolator Module located on both sides of a device, or the combination of an Isolator Base
and Isolator Module are required to comply with NFPA Style 7 requirements.

CAUTION: Isolator Modules/Bases Connection Limitations


!
• If the relay or sounder bases are not used, a recovered limit of 20 devices or a maximum of
25 addressable devices can be connected between Isolator Modules and/or Bases.
• When the relay or sounder bases are used, the maximum number of addressable devices
that can be connected between the Isolators is reduced to seven. Isolator Modules will not
function properly when these limits are exceeded.
• When more than 100 Isolator Modules and/or Isolator Bases are connected from the
ILI-MB-E3, ILI-S-E3 or 7100 Series sub-assemblies to an SLC circuit, the address capacity
of the circuit is reduced by two (2) addresses for every Isolator device in excess of 100.
• The address capacity of the circuit is reduced by two (2) addresses for every Isolator device
in excess of 200 when the Isolator Modules and/or Isolator Bases are connected to the SLC
circuit from the ILI-MB-E3, ILI-S-E3 or 7100 Series sub-assemblies.

5.2 Fault Isolator Module


The M500X Module continuously monitors the circuit connected to terminals 3(–) and 4(+). Upon
power-up, an integral relay is latched on. The module periodically pulses the coil of this relay. A
short circuit on the SLC resets the relay. The module detects the short and disconnects the faulted
SLC branch or segment by opening the positive side of the SLC (terminal 4). This isolates the
faulted branch from the remainder of the circuit, and prevents a communication problem with all
other addressable devices on the remaining branches. During a fault condition, the control panel
registers a trouble condition for each addressable device which is isolated on the SLC segment or
branch. After the fault is removed, the module automatically reapplies the power to the SLC branch
or segment.

Figure 5.2.1.1 illustrates an example of the Style 4 wiring of an Isolator Module.


Continuation
of the SLC

IN
IN

OUT

OUT
SLC-isowire.cdr

SLC Isolated branch


of the SLC

Figure 5.2.1.1 Wiring the Module

20 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Isolator Detector Bases SLC Circuits with Isolators

5.3 Isolator Detector Bases


Isolator detector bases prevent an entire communications circuit from being disabled when a short
circuit occurs. This is accomplished by isolating that part of the circuit containing the short from
the remainder of the circuit. These bases also automatically restore the entire circuit when the cause
of the short circuit is corrected.
The B224BI intelligent isolator base is used with the Velociti detectors and most CLIP mode
detectors.

5.3.1 How an Isolator Base Works


If a short circuit fault occurs at point “X”, devices A, B, C & detector 2 will cease to function and
display a trouble warning at the control panel. Devices D, E, F & detectors 1, 3, 4, and 5 will
remain normal as they are served by the ‘SLC Return.’
If a short circuit fault occurs at point “Y,” all devices will continue to function.
If a short circuit fault occurs at point “Z,” only detector 4 will cease to function.
Figure 5.3.1.1 illustrates the Isolator Base wiring using Style 6.

Detector 1 X Detector 2

Y
Detector 5 Z

Detector 4 Detector 3
SLC Out SLC Return

SLC-isowork.wmf
Control Panel
Isolator Base Non-Isolating Device Short-circuit path

NOTE: For information on wiring an isolator base, refer to Figure 9.3.1.1, “Wiring an Isolator
Base”.

Figure 5.3.1.1 Isolator Base Circuit: Sample Style 6 Wiring

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 21


SLC Circuits with Isolators NFPA Style 4 SLC Using Isolator Modules

5.4 NFPA Style 4 SLC Using Isolator Modules


Figure 5.4.1.1 illustrates a variation of a Style 4 operation using Isolator Modules to protect each
branch of the SLC. Refer to Figure 5.2.1.1 on page 20 for M500X wiring and Section 5.1,
“Overview” for the limitations.

Isolator Module
Two-wire Addressable Detector
Isolated Branch

Isolator Module

Isolated Branch

Addressable Pull Station

Isolator Module

Isolated Branch

B– B+

SLC-style4iso.cdr
Control Panel
SLC

Figure 5.4.1.1 NFPA Style 4 SLC Using Modules

22 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


NFPA Style 6 SLC Using Isolator Modules SLC Circuits with Isolators

5.5 NFPA Style 6 SLC Using Isolator Modules


Figure 5.5.1.1 illustrates a variation of Style 6 operation using the Isolator Modules to protect a
section of the SLC. By flanking each group of devices with the M500X fault Isolator Modules,
each group is protected from faults that may occur in the other groups. For example, a fault in
Section B will not affect Sections A & C. The Isolator Modules on either side of Section B will
open the circuit. Section A will still operate from power on the SLC (Out) side and Section C will
operate from the SLC (Return) side. The following are the criteria.
• A combination of Isolator Modules and Isolator Bases may be used.
• T-tapping is NOT allowed within the Style 6 configuration.
• Isolator Modules shall be within 20 ft. (6.1 m) of the device and the wire must be enclosed in a
metal conduit.

Isolator Isolator
Module Module

Section B

Two-wire
Addressable Section C
Detector

Addressable
Pull Station

Section A

An Additional Isolator Module is required when the first


device in the section is more than 20 feet from the control
Isolator panel. Isolator
Module Module

The first Isolator Module on SLC (Out) and SLC (Return) is optional for the E3
Isolator Series and 7100 Series, because the panels provide the functionality. Isolator
Module Module

SLC Out SLC Return

E3 Series and 7100 Series:


SLC-style6iso.cdr

The first Isolator Module on SLC (Out) and


SLC (Return) must be contained within the
same enclosure as the FACP, or these Control Panel
Isolator Modules must be connected within
20 ft. (6.1 m) of the FACP enclosure in
conduit.

Figure 5.5.1.1 NFPA Style 6 SLC Using Isolator Modules

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 23


SLC Circuits with Isolators NFPA Style 7 SLC Using an Isolating Device

5.6 NFPA Style 7 SLC Using an Isolating Device


Style 7 operation requires using a combination of isolator detector bases and Isolator Modules or
Isolator Modules before and after a non-isolator device. Flanking each device with an isolator
provides fault protection to all the other devices on the circuit.
• T-tapping is NOT allowed within the Style 7 wiring configuration.
• When a non-isolator base or pull station is used, install Isolator Modules on both sides of the
devices.
• When an isolator base is used in conjunction with an Isolator Module, install the Isolator
Module as shown in Figure 9.3.1.1.
• There must be a close-nipple connection between a device and the isolator bases or modules
that protect it.
Figure 5.6.1.1 illustrates the NFPA Style 7 SLC Wiring.

Isolator
Module

Two-wire Isolator
Detector Base

Isolator Isolator
Module Module

Addressable
Pull Station
Addressable
Detector

Isolator Isolator
Module Module

The first Isolator Module on SLC (Out) and SLC (Return) is optional for the tE3
Series and 7100 Series, because the panels provide the functionality.(
Isolator Isolator
Module Module
SLC Out SLC Return

E3 Series and 7100 Series:


The first Isolator Module on SLC Out and
SLC Return must be contained within the
same enclosure as the FACP, or these
Isolator Modules must be connected
SLC-style7iso.cdr

within 20 ft. (6.1 m) of the FACP


enclosure in conduit.
Control Panel

Figure 5.6.1.1 NFPA Style 7 SLC

NOTE: For additional information, refer to Figure 9.3.1.1, “Wiring an Isolator Base”.

24 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Description Monitor Modules

Section 6: Monitor Modules

6.1 Description
These addressable modules monitor conventional contact-type alarm initiating devices. You can
configure module circuits as an NFPA Style B (Class B) or a Style D (Class A) Initiating Device
Circuits (IDC). There is no limit to the number of contact-type devices installed on a monitor
module IDC.
For more information on the individual module specifications, refer to the Installation Instructions
that are provided with this device. For information on transponders, refer to the specific
transponder manual.

6.1.1 Addressable Monitor Module


AMM-2F is an addressable module that monitor either a Style B (Class B) or Style D (Class A)
IDC of the dry-contact input devices. This module is capable of participating in degraded mode
where supported by the FACP. Figure 6.1.1.1 illustrates the Addressable Monitor Module.

SLC–
IDC Return – Rotary
SLC+
Switches
IDC Return +
IDC Out +
IDC Out –

FMMtpH.wmf
Areas used to record the device
address and SLC number.

Figure 6.1.1.1 AMM-2F Monitor Module

6.1.2 Zone Interface Module


AMM-4F is similar to the AMM-2F, except it is used to monitor compatible two-wire, 24 volt,
conventional (non-addressable) smoke detectors on a Style B (Class B) or Style D (Class A) IDC.
Figure 6.1.2.1 illustrates the AMM-4F Zone-Interface Module.

24 VDC –
24 VDC + SLC–
Rotary
IDC Return – SLC+ Switches
IDC Return +
IDC Out +
IDC Out –
FZMtpH.wmf

Areas used to record the device


address and SLC number.

Figure 6.1.2.1 AMM-4F Zone-interface Module

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 25


Monitor Modules Description

6.1.3 Dual Monitor Module


AMM-2IF is similar to the AMM-2F, except it is intended for use in intelligent two-wire systems
providing two independent Style B (Class B) IDCs at two separate, consecutive addresses.
Figure 6.1.3.1 illustrates the AMM-2IF Dual Monitor Module.

Rotary
Switches

Address +1{ 9 H–
8 H+ SLC–

SLCDualMod-simplified.wmf
7L+ SLC+
Base Address {
6L–

Areas used to record the device


address and SLC number.

Figure 6.1.3.1 AMM-2IF Dual Monitor Module

6.1.4 Miniature Monitor Module


AMM-2SF is intended to monitor a Style B (Class B) IDC; it is offered in a smaller package for
mounting directly in the electrical box of the device being monitored. Figure 6.1.4.1 illustrates the
AMM-2SF Miniature Monitor Module.

Rotary 14 15 0 1 ADDRESS 0 1 Label – Use to record the


Switches
13
12
2
3
2
3
device address and SLC
LOOP
11 4 4 number.
10 5 5
9 8 7 6 9 8 7 6
TENS ONES

IDC (+) Violet SLC (+) Red

SLC (-) Black

FMM-101.cdr
IDC (-) Yellow

Figure 6.1.4.1 AMM-2SF Miniature Monitor Module

26 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Setting an SLC Address for a Module Monitor Modules

6.2 Setting an SLC Address for a Module


The following list the two types of modes to set the SLC addresses.
Velociti Mode
The Velociti capable control or relay modules, as well as detectors, can be set to one of 159
addresses (01-159) and are factory preset with an address of “00.”
CLIP Mode
The CLIP mode detectors and panels are limited to addresses 01-99.
Setting an SLC Address
1. To set an SLC address, use a common screwdriver to adjust the rotary switches on the module
to the desired address.
Figure 6.2.1 illustrates the unit set at address “35.”
2. When finished, mark the address on the module face in the place provided.

Velociti-New Format

SLC-setadd.cdr,SLC-setaddtpH.wmf, SLCbrktabs.wmf
Breakaway Tab - Modules come
with a raised breakaway tab on the
TENS rotary switch. This tab must
be removed when the module is on
an FACP that uses more than 99
Type H Rotary addresses.
Switches

CLIP-Old Format
Type V Rotary
Switches
Dual monitor modules: On dual monitor modules, only even
numbers appear on the ONES rotary switch. The module takes
both the selected address and the next-higher address.

Figure 6.2.1 Setting SLC Address on Module

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 27


Monitor Modules NFPA Style B IDC Using Monitor Modules

6.3 NFPA Style B IDC Using Monitor Modules


To wire the SLC in compliance with NFPA Style B IDC using monitor modules, do the following:
1. Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
2. Use the rotary switches on the module to set it to the required SLC address.
Each AMM-2F module takes one address on the SLC.
Figure 6.3.1 shows the typical wiring for a supervised and power-limited NFPA Style B (Class B)
Initiating Device Circuit using the AMM-2F monitor module.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 micro amps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix the services.)
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
For information on compatible smoke detectors, refer to the Compatibility Addendum to Gamewell-
FCI Installation/Operating Manuals, P/N: 9000-0427.
For information on the documents that reference supervising 24 VDC, refer to Table 1.3.1.1 (SLC
Devices Reference Documents).

From Supply

24 VDC
Four-wire
24 VDC Power
Detector Base
Filtered, Regulated,
Resettable

Manual pull
station

To Next IDC
or
47K ELR Supervision Device
(supplied
with module)
SLC
Heat
detector AMM-2F
SLC-idcB1tpH.wmf

IDC

Figure 6.3.1 Typical Style B IDC Wiring with AMM-2F

28 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


NFPA Style D IDC Using Monitor Modules Monitor Modules

6.4 NFPA Style D IDC Using Monitor Modules


To wire the SLC in compliance with NFPA Style D IDC using monitor modules, do the following:
1. Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
2. Use the rotary switches to set it to the required SLC address.
Each AMM-2F module takes one address on the SLC.
Figure 6.4.1 shows the typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using the AMM-2F module.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 micro amps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix the services):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
For information on compatible smoke detectors, refer to the Compatibility Addendum to Gamewell-
FCI Installation/Operating Manuals, P/N: 9000-0427.
For information on the documents that reference supervising 24 VDC, refer to Table 1.3.1.1 (SLC
Devices Reference Documentation.)

From
Supply

24 VDC
Four-wire 24 VDC Power
Detector Base Filtered, Regulated,
Resettable

Manual pull
station
To Next IDC
or
Supervision Device

SLC
Heat AMM-2F
detector
SLC-idcD1tpH.wmf

IDC

Figure 6.4.1 Typical Style D IDC Wiring with AMM-2F

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 29


Monitor Modules NFPA Style B IDC Using Dual Monitor Modules

6.5 NFPA Style B IDC Using Dual Monitor Modules


To wire the SLC in compliance with NFPA Style B IDC, using monitor modules, do the following:
1. Connect the SLC wiring to the AMM-2IF module terminals 1 (–) and 2 (+).
2. Use the rotary switches on the module to set the module to the required SLC address.
Each dual module takes two addresses on the SLC.
Table 6.5.1 lists the circuit addresses.
Circuit Description Base Address
Circuit L Circuit L corresponds to the address The “base address” is always an even number.
set on rotary switches The lowest possible address is 02.
Circuit H Circuit H automatically responds at the The base + 1” address is always odd.
next higher address
Table 6.5.1 Circuit Addresses
3. Use caution to avoid duplicate addressing of modules on the system.
4. Each IDC (H & L) is power-limited to 230 micro amps @ 24 VDC.
Figure 6.5.1 shows the typical wiring for a supervised and power-limited NFPA Style B (Class B)
Initiating Device Circuit using the AMM-2IF dual monitor.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 micro amps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix the services):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
For information on the compatible smoke detectors, refer to the Compatibility Addendum to
Gamewell-FCI Installation/Operating Manuals, P/N: 9000-0427.

Manual
Pull
Station

47K
47K ELR
ELR AMM-2IF
SLC-idcB3fdm1.wmf

Heat
Detector SLC

Base Address Base +1 Address


(IDC Circuit L) (IDC Circuit H)

Figure 6.5.1 Typical Style B IDC Wiring with AMM-2IF

30 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


NFPA Style B IDC Using Zone Interface Modules Monitor Modules

6.6 NFPA Style B IDC Using Zone Interface Modules


To wire the SLC in compliance with NFPA Style B IDC using Zone Interface Modules, do the
following:

1. Connect the SLC wiring to the AMM-4F module terminals 1 (–) and 2 (+).
2. Use the rotary switches on the module to set it to the required SLC address.
Each module takes one address on the SLC.
Figure 6.6.1 shows typical wiring for a supervised and power-limited NFPA Style B (Class B) IDC
using the AMM-4F module.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
For information on compatible smoke detectors, refer to the Compatibility Addendum to
Gamewell-FCI Installation/Operating Manuals, P/N: 9000-0427.

24 VDC Resettable power.


90 mA External 24 volt supply required

Two-wire
smoke
detectors
3.9K ELR
(supplied with module)
SLC

IDC
SLC-idcB2tpH.wmf

Figure 6.6.1 Typical Style B IDC Wiring with AMM-4F

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 31


Monitor Modules NFPA Style D IDC Using Zone Interface Modules

6.7 NFPA Style D IDC Using Zone Interface Modules


To wire the SLC in compliance with NFPA Style D IDC using Zone Interface Modules, do the
following:

1. Connect the SLC wiring to the AMM-4F module terminals 1 (–) and 2 (+).
2. Use the rotary switches on the module to set it to the required SLC address.
Each module takes one address on the SLC.
Figure 6.7.1 shows the typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using the AMM-4F zone interface module.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 micro amps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix the services):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
For information on compatible smoke detectors, refer to the Compatibility Addendum to Gamewell-
FCI Installation/Operating Manuals, P/N: 9000-0427.

24 VDC Resettable power.


90 mA External 24 volt supply required

Two-wire
smoke
detectors

SLC

IDC
SLC-idcD2tpH.wmf

3.9K ELR
(supplied with module)

Figure 6.7.1 Typical Style D IDC Wiring with the AMM-4F

32 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Description Control Modules

Section 7: Control Modules


7.1 Description
The AOM-2SF Module is an addressable module that can be used for monitoring and switching 24
VDC Notification Appliance Circuit (NAC) power for NFPA Style Y (Class B) and NFPA Style Z
(Class A) circuits. It can also be used for audio/voice applications and firefighter’s telephone.
There are two types of applications that are documented separately. For information on UL 9th
Edition audio applications, refer to the following documents:
• E3 Series Broadband Emergency Voice Evacuation System Installation/Operation Manual,
P/N: 9000-0575
• E3 Series Classic Installation/Operation Manual, P/N: 9000-0577.
„ Setting an SLC Address
Each module is factory preset with an address of “00.” For information on how to set an SLC
address, refer to Section 6.2 on page 27.

7.2 Wiring a NAC with Addressable Control Modules


Figure 7.2.1.1 and Figure 7.3.1.1 show the connections to wire the AOM-2SF module for powering
a 24 VDC NAC.

24 VDC Nonresettable Power (–)


24 VDC Nonresettable Power (+) SLC (–)
Style Z NAC (+) SLC (+)
Style Z NAC (–)
Style Y/Z NAC (–)

SLCModule-simplified.wmf
Style Y/Z NAC (+)

NOTE:
• Module polarities are shown in alarm condition.

Figure 7.2.1.1 AOM-2SF Wiring Connections

Rear View Jumper J1 must be removed when using the AOM-2SF


and supervising 24VDC NAC power using the no-relay
alternative wiring.

Prying tool
FCMBackJump.wmf, FCMBackJumpcl.wmf

To remove J1 from the AOM-2SF:


1. Insert a small prying tool, such
as a screwdriver or probe,
behind J1.
2. Using the tip of the prying tool,
slide J1 toward the rear of the
J1 AOM-2SF so that it exits from
the slot in the back.

Figure 7.3.1.1 AOM-2SF Top and Rear View - Jumper Location

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 33


Control Modules Wiring a Style Y NAC (Two-Wire) with Addressable Control Modules

7.3 Wiring a Style Y NAC (Two-Wire) with Addressable


Control Modules
Figure 7.3.1.1 illustrates a supervised and power-limited NFPA Style Y (Class B) Notification
Appliance Circuit (NAC), using the AOM-2SF module. It also shows the polarized alarm
notification appliances connected to the module in a two-wire configuration.
1. For information on the documents that describe how to monitor 24 VDC, refer to Table 1.3.1.1
(SLC Devices Reference Documentation).
2. Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns), 67 watts DC only.
3. A power supervision relay is required only on the last module of the power run.
4. Do not Tap or branch a Style Y circuit.
5. Terminate the circuit across the last device using a UL-Listed End-of-Line Resistor 47K,
1/2-watt, SSD P/N A2143-00 (ELR-47K in Canada).
6. Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.
For information on the compatible notification appliances and relays, refer to the Compatibility
Addendum to Gamewell-FCI Installation/Operating Manuals, P/N: 9000-0427.
SLC
24 VDC Nonresettable power

A power supervision
relay is required only on
the last module of the
ELR power run. If using one
24 VDC Notification of the Velociti type IDs
47K, 1/2-watt
Appliances that provide built-in
power supervision, no
relay is required.

SLC-nacY.wmf
NAC

Module polarities are shown in alarm condition.

Figure 7.3.1.1 NFPA Style Y Notification Appliance Circuit

34 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Wiring a Style Z NAC (Four-Wire) with Addressable Control Modules Control Modules

7.4 Wiring a Style Z NAC (Four-Wire) with Addressable


Control Modules
Figure 7.4.1.1 illustrates a supervised and power-limited NFPA Style Z (Class A) Notification
Appliance Circuit (NAC) using the AOM-2SF module. It also shows the polarized alarm
notification appliances connected to the module in a four-wire configuration.
1. For information on the documents that describe how to supervise 24 VDC, refer to
Table 1.3.1.1 (SLC Devices Reference Documentation).
2. Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns), maximum 67 watts DC only.
3. A power supervision relay is required only on the last module of the power run.
4. Do not T-Tap or branch a Style Z circuit.
5. Do not loop wiring under the screw terminals of any notification appliance.
6. To maintain supervision, break the wire run at each device.
For information on the compatible notification appliances and relays, refer to the Compatibility
Addendum to Gamewell-FCI Installation/Operating Manuals, P/N: 9000-0427.

24 VDC Nonresettable power SLC

AOM-2SF
24 VDC
notification
appliances

NAC Return
A power supervision relay
is required only on the last
NAC Out module of the power. If
using one of the Velociti

SLC-nacZtpH.wmf
type IDs that provide built-
in power supervision, no
relay is required).
Module polarities are shown in Alarm.

Figure 7.4.1.1 NFPA Style Z Notification Appliance Circuit

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 35


Section 8: Relay Module

8.1 Description
The AOM-2RF module is an addressable module that provides two isolated sets of Form-C relay
contacts.
Ratings for the dry relay contacts on a Form-C module are listed below:
• Resistive – 2 amps @ 30 VDC (e.g. Electronic devices and strobes)
• Inductive – 1 amp @ 30 VDC (0.6pF) (e.g. Mechanical bells and horns)
• Pilot Duty – 0.5 amp @ 125 VAC (0.35pF) (e.g. Using a smaller relay to trip another relay)
For more information on the module specifications, refer to the Installation Instructions provided
with this device. For information on transponders, refer to the specific transponder manual.

„ Setting an SLC Address


Each relay module is factory preset with an address of “00.” For information on how to set an SLC
address refer, to Section 6.2, “Setting an SLC Address for a Module”.

8.2 Wiring the Addressable Relay Module (Form-C Relay)


Figure 8.2.1.1 illustrates the AOM-2RF module wired to the Control Panel.

SLC

AOM-2RF

C
NC
NO
C
NC NO
SLC-frmCtpH.wmf

Figure 8.2.1.1 Relay Module Wiring Connections

36 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Description Intelligent Detector Bases

Section 9: Intelligent Detector Bases

9.1 Description
The following types of bases provide the connection between the SLC and a variety of intelligent
detectors:
• B501 and B710LP detector bases
• B224RB plug-in relay detector base
• B200SR sounder base
For more information, refer to the Installation Instructions documents provided with these devices.

„ Setting the Detector Address


Each intelligent detector head is factory preset with an address of “00.” For information on how to
set an SLC address, refer to Section 6.2, “Setting an SLC Address for a Module”.

9.2 Wiring a Detector Base


Figure 9.2.1.1 shows the typical wiring of the B710LP or B501 detector base connected to an SLC.
An optional RA400Z Remote LED Annunciator is shown connected to the base.

SLC

Use a female disconnect


to wire the RA400Z (–) to
Terminal 1 (–).

To next device
on SLC

B501 only: For connection of


cable shield

RA400Z
SLC-B501wire.wmf

Remote LED
Annunciator
(Optional)

NOTE: The base wiring is identical to the B710LP, except there is no shield terminal.

Figure 9.2.1.1 Wiring of the Detector Base

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 37


Intelligent Detector Bases Wiring an Isolator Base

9.3 Wiring an Isolator Base


The Isolator Base will isolate its detector from short circuits that occur on the SLC connected at
terminals 3 and 2. It will not isolate its installed detector from short circuits that occur on the SLC
connected at terminals 1 and 2. In Style 7 applications, the loss of a single detector during a short
circuit is not acceptable, and an Isolator Module must be installed as shown in Figure 9.3.1.1.

SLC Out

SLC In

Conduit

SLC-224BIwire.wmf
Isolator Module

Figure 9.3.1.1 Wiring an Isolator Base

9.4 Wiring a Relay Base


Figure 9.4.1.1 illustrates the typical wiring of the B224RB plug-in relay detector base connected to
an SLC.

To next device
on SLC
For connection of
cable shield

3 Relay Common
2 Normally Open
1 Normally Closed
SLC
b224rb.wmf

Figure 9.4.1.1 Wiring of the B224RB Plug-in Relay Detector Base

38 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Wiring a Sounder Base Intelligent Detector Bases

9.5 Wiring a Sounder Base


Figure 9.5.1.1 Wiring Diagram
Detector Activates Sounder Base(s) - (Complies with UL268)
UL has approved the grouping for up to six (6) B200SR sounder bases. You can group a maximum
of six (6) sounder bases using the Optional Sounder Interconnect. Some Fire Alarm Control Panels
(FACP) support the grouping of sounder bases via software in lieu of the Sounder Base
Interconnect. This interconnect can also be used to attach B200SR devices to System Sensor B501-
Series sounder bases. When the sounder bases are wired as a group, any detector in the group that
has been activated by the panel, will cause other B200SR units in the group to sound. This type of
“local” grouping is accomplished by wiring the grouped devices using Terminal 6, Sounder Base
Interconnect.

NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore
the groups can only be used as a supplementary evacuation system. It is not acceptable to group
horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are
grouped via software are not subject to this limitation and may be used as part of the primary
alarm signaling.

Figure 9.5.1.1 illustrates the wiring of grouped devices using terminal 6, Sounder Base
Interconnect, so that the bases are activated by the detector.

INTELLIGENT
MONITOR MODULE
CLASS A OPTIONAL WIRING (+) SLC
(-) SLC OPTIONAL SOUNDER (-) SLC
(+) SLC INTERCONNECT

SUP (+)
SUP (-)
UL LISTED
COMPATIBLE
CONTROL
PANEL
UL LISTED
EOL
RESISTOR
47X

END OF LINE
NOT SLC+ SLC- EXT+ EXT- RA NOT SLC+ SLC- EXT+ EXT- RA NOT SLC+ SLC- EXT+ EXT- RA RELAY
USED USED USED (EOLR-1 OR
EQUIVALENT)

FIRST SECOND LAST


(+) POWER SOUNDER SOUNDER SOUNDER
BASE BASE BASE

UL LISTED (-) POWER


24V
POWER
CLASS A OPTIONAL WIRING
SUPPLY

* GROUPING OF UP TO 6 MODEL B200SR SOUNDER BASES

Figure 9.5.1.1 Wiring for Individual B200SR Sounder Bases

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 39


Intelligent Detector Bases Wiring a Sounder Base

Figure 9.5.1.2: Wiring Diagram


Panel Activates Sounder Base(s);
Intelligent Relay Module Activates Al Sounder Bases - (Complies with UL 268
and UL 464) ADITIONAL AUDIBLE VISIBLE DEVICES ARE SYNCHRONIZED
TO THE SOUNDER BASE OUTPUT
UL has approved grouping for up to six (6) B200SR sounder bases. You can group a maximum of
six (6) sounder bases using the Optional Sounder Interconnect. Some Fire Alarm Control Panels
support the grouping of sounder bases via software in lieu of the Sounder Base Interconnect. When
the sounder bases are wired as a group, any detector in the group that has been activated by the
panel will cause other B200SR units in the group to sound. This type of “local” grouping is
accomplished by wiring the grouped devices using Terminal 6, Sounder Base Interconnect.

NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore
the groups can only be used as a supplementary evacuation system. It is not acceptable to group
horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are
grouped via software are not subject to this limitation and may be used as part of the primary
alarm signaling.

Figure 9.5.1.2 illustrates the wiring of grouped devices using terminal 6, Sounder Base
Interconnect, so that the bases are activated by the panel.
INTELLIGENT
MONITOR MODULE

(+) SLC
OPTIONAL SOUNDER (-) SLC
(-) SLC INTERCONNECT

SUP (+)
SUP (-)
(+) SLC
UL LISTED INTELLIGENT
COMPATIBLE RELAY MODULE†
CONTROL
PANEL
COMM 2 (-) SLC
UL LISTED
EOL
NC 2 (+) SLC RESISTOR
47X
NO 2

END OF LINE
COMM 1
NOT SLC+ SLC- EXT+ EXT- RA NOT SLC+ SLC- EXT+ EXT- RA RELAY
USED USED (EOLR-1 OR
EQUIVALENT)
NC 1 NO 1

(+) POWER FIRST LAST


SOUNDER SOUNDER
BASE BASE

UL LISTED (-) POWER


24V
POWER
SUPPLY

* GROUPING OF UP TO 6 MODEL B200SR SOUNDER BASES

Figure 9.5.1.2 Wiring for Grouped or General Alarm B200SR Sounder Bases

40 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Description Addressable Manual Pull Station

Section 10: Addressable Manual Pull Station

10.1 Description
The MS-7AF is an addressable manual pull station with a key-lock reset feature. The MS-7ASF is a
Spanish/English labeled version. It supports Velociti or CLIP mode. Wiring is the same for the MS-
7AF manual pull station.
For more information, refer to the Installation Instructions provided with the devices.

„ Setting an SLC address


Each unit is factory preset with an address of “00.” For information on how to set an SLC address
refer to Section 6.2, “Setting an SLC Address for a Module”.

10.2 Wiring a Manual Pull Station


Figure 10.2.1.1 illustrates the typical wiring for the MS-7AF Manual Pull Station to an SLC.


To next device
+ on SLC
SLC +

US PAT 444 0991

SLC-nbg12.cdr

Figure 10.2.1.1 Wiring the MS-7AF Pull Station to an SLC

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 41


Power Considerations Supplying Power to 24 VDC Detectors and NACs

Appendix A: Power Considerations

A.1 Supplying Power to 24 VDC Detectors and NACs


Resistance and Size
To determine the maximum allowable resistance that can be tolerated in supplying power to
24 VDC four-wire devices and NACs, use the calculations below. These simplified equations are
based on the fact that the devices are located at the end of a long wire run. With the computed
resistance and using the manufacturers’ specifications for the desired wire, select the proper gauge
wire for the power run.
For Four-Wire Detectors:
(Vms - Vom)
Rmax =
(N)(Is) + (Na)(Ia) + (Ir)

For NACs:
(Vms - Vom)
Rmax =
(Nb)(Ib)

Where:

Rmax = maximum resistance of the 24 VDC wires


Vms = minimum supply voltage (see Table A.1)
Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater,
in volts
N = total number of detectors on the 24 VDC supply circuit
Is = detector current in standby
Na = number of detectors on the 24 VDC power circuit which must function at the same
time in alarm
Ia = detector current in alarm
Ir = end-of-line relay current
Nb = number of Notification Appliance Devices
Ib = Notification Appliance current when activated

NOTE: This simplified equation is based on the fact that the devices are located at the end of a
long wire run.

Table A.1.1 lists the minimum supply voltages produced by the Gamewell-FCI power supplies.

FACP AC Vms Power Supply Battery Vms


E3 Series® 27.3V ± 0.1V PM-9/PM-9G 20.4 (min.)
7100 Series 28.2V ± 0.4V BSM 20.4 (min.)

Table A.1.1 Minimum Supply Voltage

42 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Supervising 24 VDC Power Power Considerations

A.2 Supervising 24 VDC Power


The following are the options available for supervising 24 VDC power.
• Using Velociti Type Codes with Built-In Power Supervision
• Power Supervision Relay
• Using the AOM-2SF module without relay

A.2.1 Power Supervision Relay


Power used to supply 24 VDC detectors, notification appliances (using the AOM-2SF) and two
wire detectors (using the AMM-4F) can be supervised with a power supervision relay. This relay,
energized by the 24 VDC power itself, is installed at the end of each respective power run and
wired in line with the supervised circuit of any intelligent module.
When power is removed from the relay, the normally closed contacts open the supervised circuit,
generating a trouble condition. Therefore, the relay needs to be installed at the end of the
supervised circuit, so that it does not disrupt the operating capability of all the devices on that
circuit. The relay can be installed in line with any leg (+ or –) of the supervised NAC or IDC
circuit, either a two or a four-wire style.
See Figure A.2.1.1 and Figure A.2.1.2.
For information on compatible notification appliances and relays, refer to the Compatibility
Addendum to Gamewell-FCI Installation/Operating Manuals, P/N: 9000-0427.
24 VDC Power from
Control Panel or
Power Supply
Last device on the SLC loop
(AOM-2SF or AMM-4F)

Power Supervision
Relay
(EOLR-1)

SLC-psrtpH.cdr
Supervised NAC or IDC
ELR
(Use 47K with
or 3.9K with )

Figure A.2.1.1 Supervised 24 VDC Circuit

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 43


Power Considerations Supervising 24 VDC Power

Figure A.2.1.2 shows an alternate 2-address method for supervising a 24 VDC circuit.
24 VDC Power from
Control Panel or Power Supply
AOM-2SF
ELR 47K

Power Supervision
Relay
(EOLR-1)

ELR 47K Supervised NAC or IDC

AMM-2F

Figure A.2.1.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit

44 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Supervising 24 VDC Power Power Considerations

A.2.2 Using the Addressable Control Module Without Relay


An alternate method of supervising 24 VDC power, fed to the Notification Appliance Circuit of the
AOM-2SF module, eliminates the need for a power supervision relay. This method uses a
Notification Appliance Circuit from the control panel or uses a power supply to supply power to the
AOM-2SF modules. The control panel supervises this circuit, which can be either a Style Y or Style
Z.
Style Y NAC Power Wiring
Program the NAC from the control panel for general alarm. (For instructions, refer to the
programming manual or programming section of the FACP documentation). Note that if the NAC
is a coded output, the AOM-2SF output will be coded as well.
For information on the compatible notification appliances, refer to the Compatibility Addendum to
Gamewell-FCI Installation/Operating Manuals, P/N: 9000-0427.
The following list the requirements for Style Y NAC Power Wiring:
• The circuit is supervised and power-limited.
• In this circuit, an external ELR is required at the end of the NAC circuit.
• Refer to the respective control panel installation manual for NAC terminal block connection
information and ELR value.
• Remove the internal resistor on each AOM-2SF. (For additional information, refer to the
instructions in Section 7.2, “Wiring a NAC with Addressable Control Modules”).
Figure A.2.2.1 illustrates the wiring in compliance with NFPA Style Y NAC power alternate.
NAC Terminal Block (24 VDC)
AOM-2SF

Circuit supervised
by control panel

AOM-2SF
SLC-nacY1tpH.wmf

Note: Drawing shows power wiring


only; SLC Wiring is not shown.

Figure A.2.2.1 NFPA Style Y NAC Power (Alternate)

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 45


Power Considerations Supervising 24 VDC Power

Style Z NAC Power Wiring (Alternate)


Program the NAC from the control panel for general alarm. (For instructions, refer to the
Programming Manual or Programming Section of the FACP documentation).

NOTE: If the NAC is a coded output, the AOM-2SF output will be coded as well.

For information on compatible notification appliances and relays, refer to the Compatibility
Addendum to Gamewell-FCI Installation/Operating Manuals, P/N: 9000-0427.
The following list the requirements for Style Z NAC Power Wiring (alternate):
• The circuit is supervised and power-limited.
• In this circuit, an external ELR is not required at the end of the NAC circuit.
• Refer to the respective control panel installation manual for the NAC terminal block
connection information.
• Remove the internal resistor on each AOM-2SF. (See instructions in Section 7.2, “Wiring a
NAC with Addressable Control Modules”).
Figure A.2.2.2 illustrates the wiring in compliance with NFPA Style Z NAC power alternate.
NAC Terminal Block
(24 VDC)

AOM-2SF

Circuit supervised
by control panel

AOM-2SF

SLC-nacZ1tpH.wmf

Note: Drawing shows power wiring


only; SLC Wiring is not shown.

Figure A.2.2.2 NFPA Style Z NAC Power (Alternate)

46 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Supervising 24 VDC Power Power Considerations

Notes

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 47


Appendix B: SLC Surge Suppression

B.1 Introduction
There are one primary and three secondary UL–Listed surge protectors approved for use with the
FACPs listed in this appendix.
Primary Surge Protector:
• 326-2M TII Station Protector
Secondary Surge Protectors:
• DTK-2LVLP-F: Diversified Technology Group, Inc. (DITEK) 1720 Starkey Rd. Largo, FL
33771 (800) 753-2345.
• SLCP-30: EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029
• PLP-42N: Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019
(800) 727-9119

NOTE: For detailed information, refer to the installation documentation supplied with the unit.

Whenever the SLC wiring runs outside the building, one primary surge protector must be used with
each SLC wiring pair.
• Install the primary protection only as shown in this document.
• Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional
suppressors in series with the SLC wiring at the building entry/exit.
Figure B.1.1 illustrates the wiring connected to the surge suppressor output that must remain within
the building, while wiring connected to the surge suppressor input may be routed outside the
building.

Building #2 Building #1

P P
FACP
P = Primary
S = Secondary S

P P S
SLC-ssbuild1.cdr

Surge Suppressor

Figure B.1.1 Wiring Connection

48 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Installation SLC Surge Suppression

B.2 Installation
Mounting the secondary surge suppressor must be connected inside the FACP enclosure or
connected in a separate enclosure that is Listed for fire protective signaling use. To install, do the
following:
1. Locate an available stud and secure with the nut.
2. To protect the Control Panel, connect the unit in series with the SLC Circuit.
3. Provide a common ground to eliminate the possibility of a differential in ground potentials.
B.2.1 7100 Series and E3 Series
DTK-2LVLP-F Connections
Figure B.2.1.1 illustrates the DTK-2LVLP-F wiring connections.

2LVLP-F

Optional Four-wire Return Loop


Style 6 (Class A)

IN OUT
SLC Terminal Block

2LVLP-F


+

SLC-lvlp1.cdr
SLC Loop
IN OUT

Figure B.2.1.1 DTK-2LVLP-F Wiring Connections


PLP-42N Connections
Figure B.2.1.2 illustrates the PLP-42N wiring connections.

PLP-42N
GRND
L4

Optional Four-wire Return Loop


L4
OUTPUT

Style 6 (Class A)
L3
INPUT

L3
L2

L2
L1

L1

SLC Terminal Block


PLP-42N


GRND
L4

L4

+
OUTPUT
L3
INPUT

L3
L2

SLC-plpn1.cdr
L2

SLC Loop
L1

L1

Figure B.2.1.2 PLP-42N Wiring Connections

NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to connect
the unit’s ground terminal to equipment ground. Wire length must be minimized to provide best
protection.

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 49


SLC Surge Suppression Installation

SLCP-30 Connections
Figure B.2.1.3 illustrates the SLCP-30 wiring connections.

SLCP-30

Optional Four-wire Return Loop


Style 6 (Class A)

IN OUT
SLC Terminal Block
SLCP-30
SLC Loop

+

SLC-slcp1.cdr
IN OUT

Figure B.2.1.3 SLCP-30 Wiring Connections

50 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Installation SLC Surge Suppression

Notes

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 51


Appendix C: Terminal Conversion Charts for V-type
and H-type Devices

C.1 AOM-2RF
Figure C.1.1 illustrates the AOM-2RF H-type format for rotary switches using the new Velociti
format.

Common 2 SLC -
Closed 2 SLC - Common 2
Closed 2 SLC +
Open 2 SLC +
Common 1 Open 2
Closed 1 Common 1
Open 1 Closed 1 Open 1

Type V Type H

Figure C.1.1 AOM-2RF H-type Format

Table C.1.1 lists the AOM-2RF terminal conversions. Column one lists the V-type (Clip format)
numbers, column two provides the terminal function and column three lists the H-type (Velociti
format) numbers.

V-type Terminal Number Terminal Function H-type Terminal Number

1 SLC - 1

2 SLC + 2

3 Unused 3

4 Normally Open (1) 5

5 Normally Closed (1) 6

6 Relay Common (1) 7

7 Normally Open (2) 8

8 Normally Closed (2) 9

9 Relay Common (2) 10

N/A Unused 4

N/A Unused 11

Table C.1.1 AOM-2RF Terminal Conversions

52 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


AOM-2SF and AMM-4F Terminal Conversion Charts for V-type and H-type Devices

C.2 AOM-2SF and AMM-4F


Table C.2.1 illustrates the AOM-2SF and AMM-4F H-type format for rotary switches using the
new Velociti format.

Solenoid A- VDC -
Solenoid A+ SLC - VDC + SLC -
SLC + Solenoid A- SLC +
Solenoid B/A +
VDC - Solenoid A+
Solenoid B/A - Solenoid B/A +
VDC + Solenoid B/A -

Type V Type H

Figure C.2.1 AOM-2SF and AMM-4F H-type Format

Table C.2.1 lists the AOM-2SF and AMM-4F terminal conversions. Column one lists the V-type
(Clip format) numbers, column two provides the terminal function and column three lists the H-
type (Velociti format) numbers.

V-type Terminal Number Terminal Function H-type Terminal Number

1 SLC - 1

2 SLC + 2

3 VDC - 11

4 VDC + 10

5 Unused 5

6 Solenoid B/A - 6

7 Solenoid B/A + 7

8 Solenoid A + 8

9 Solenoid A - 9

N/A Unused 3

N/A Unused 4

Table C.2.1 AOM-2SF and AMM-4F Terminal Conversions

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 53


Terminal Conversion Charts for V-type and H-type Devices AMM-2F

C.3 AMM-2F
Figure C.3.1 illustrates the AMM-2F H-type format for rotary switches using the new Velociti
format.

Class A Supervision -
Class A Supervision+ SLC - SLC -
Class A/B Supervision + SLC + Class A Supervision - SLC +
Class A/B Supervision - Class A Supervision+
Class A/B Supervision +
Class A/B Supervision -

Type V Type H

Figure C.3.1 AMM-2F H-type Format

Table C.3.1 lists the AMM-2F terminal conversions. Column one lists the V-type (Clip format)
numbers, column two provides the terminal function and column three lists the H-type (Velociti
format) numbers.

V-type Terminal Number Terminal Function H-type Terminal Number

1 SLC - 1

2 SLC + 2

3 Unused 3

4 Unused 4

5 Unused 5

6 Class A/B Supervision - 6

7 Class A/B Supervision + 7

8 Class A Supervision + 8

9 Class A Supervision - 9

N/A Unused 10

N/A Unused 11

Table C.3.1 AMM-2F Terminal Conversions

54 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


AMM-2F Terminal Conversion Charts for V-type and H-type Devices

Notes

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 55


Index
Numerics Documentation
SLC Devices 9
24 VDC power 42–45
dry contact ratings 36
alternate method of supervising 45
dry-contact 11
monitoring and switching NAC power 33
DTK-2LVLP-F 48
dual monitor module 11, 26, 30
A
A77-716B E
Replaced by EOLR-1
See power supervision relay electrical interference 14
addressable devices 20 End-of-Line-Resistor 34, 45, 46
EOLR-1 See power supervision relay
Addressable Manual Pull Stations
MS-7AF 12
MS-7ASF 12 F
addressable modules 11, 25 FACP, see Fire Alarm Control Panels
auxiliary devices 11 fault 13, 21, 23
fault condition 20
B Fault Isolator Module, see isolator module
Fire Alarm Control Panels 48
B224BI, see isolator bases
Fire alarm service 28, 29, 30, 31, 32
bases 11
floating segments 17
building entry/exit 48
Form-C contacts 36
four-wire configuration 35
C
circuit fault 11 G
CLIP 7
CLIP Mode general alarm 45, 46
Setting an SLC Address 27
coded output 45, 46 I
common ground 49 IDC, see Initiating Device Circuits
communications loop 21 Initiating Device Circuits 25
Control Modules integral relay 20
AOM-2SF 11 Intelligent Baes Wiring
MMO-6SF 11 Relay Base 38
control modules 11 Intelligent Bases
B200SR 37
D B224RB 37
B501 37
DC resistance 15
B710LP 37
degraded mode 25
Intelligent Bases Wiring
detector bases
Detector Bases 37
list of 11
Isolator Bases 38
see also isolator bases
detectors Sounder Base 39
24 VDC 43 Intelligent Detectors
ADP-F 12
listing 12
ADP-RF 12
devices
addressable 20 ASD-IL2F 12
auxiliary 11 ASD-LS 12
isolator 20 ASD-PL2F 12
maximum number between isolators 20 ATD-RL2F 12
SLC capacity 12 MCS-ACCLIMATE2F 12
supervised 43 isolator bases 11, 20, 21, 24
how they work 21

56 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


wiring 38 NFPA Style B
isolator devices 20 IDC wiring 28, 30, 31
Isolator Module NFPA Style D
M500X 11 IDC wiring 29, 32
isolator modules 11, 23, 24 NFPA Style Y 33
how they work 20 wiring 34
wiring of 20 NFPA Style Z 33
wiring 35
K normally closed contacts 43
Notification Appliance Circuit 11, 45
key-lock reset 41 see also NAC
notification appliances 43
L
LED Annunciator, remote 37 P
LED operation 13
PLP-42N 48
local building code 48
Plug-in Detector Bases
Loop Resistance
B224B 11
Style 6 & 7 16
B224RB 11
loops 16
B501 11
B710LP 11
M Polling Protocols 10
metal conduit 23 CLIP Mode 10
Miniature monitor module 26 Velociti® Mode 10
module circuits, configuring 25 power run 42, 43
modules power supervision relay 34, 35, 43
addressable 11 power supplies 42
control 11 power-limited 45
h-type 54 proper gauge wire 42
isolator 11 pull stations 12, 24
monitor 11 addressable manual, wiring 41
relay 11
v-type 54 R
monitor module 11, 25, 28
RA400Z 37
dual see dual monitor module
ratings, dry contact 36
miniature, see miniature monitor module
relay bases 11, 20
zone interface see zone interface module
relay module 11, 36
Monitor/Zone Interface Modules
wiring 36
AMM-2F 11
Relay Modules
AMM-2IF 11
AOM-2RF 11
AMM-2SF 11
MMO-6RF 11
AMM-4F 11
Releasing Device
MMI-10F 11
NC-100 35
MMI-6F 11
rotary switches 7, 27, 30, 31, 32

N S
NAC power 33, 46
Security service 28, 29, 30, 31, 32
wiring 45
shield-termination 17
NAC terminal block 45
short circuit 20, 21
NC-100 35
Signaling Line Circuit 10
NEC Article 800 48 see also SLC
NFPA Style 6 SLC
wiring 19 capacity of devices 12
with isolator modules 23 performance 13
NFPA Style 7 20 setting an SLC address 27
with isolator device 24 trouble conditions 13

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 57


wiring 28, 29, 30, 31, 32
SLC Resistance 15
SLCP-30 48
Sounder Base Model
B200SR 11
sounder bases 11, 20
Sprinkler supervision 28, 29, 30, 31, 32
standard bases 11
Style 4, Style 6, Style 7, Style B, Style D, Style Y,
Style Z see NFPA Style 18
supervised circuits 43, 45
supervised devices 43
suppressors, surge 48
surge protector 10, 48

T
terminal block, NAC 46
termination of shield 17
trouble conditions 13, 20
trouble warning 21
T-tapping 15, 18, 19, 23, 24
two-wire configuration 34
two-wire detectors 43

V
Velociti Mode
Setting an SLC Address 27
Velociti® 7

W
Waterflow alarm service, automatic and manual
28, 29, 30, 31, 32
wire length
four-wire SLC 16
two-wire SLC 15
Wiring
DTK-2LVLP-F 49
PLP-42N 49
SLCP-30 50
Style Y NAC 45
Style Z NAC Power 46
wiring
isolator bases 38
isolator modules 20
NACs 45
pull stations 41
relay modules 36
SLCs 28, 29, 30, 31, 32
wiring pair 48
wiring style requirements 13

Z
zone interface module 11, 25, 31, 32

58 Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10


Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein,
Manufacturer warrants that the Products manufactured by it in its
Northford, Connecticut facility and sold by it to its authorized
Distributors shall be free, under normal use and service, from defects
in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The
Products manufactured and sold by Manufacturer are date stamped at
the time of production. Manufacturer does not warrant Products that
are not manufactured by it in its Northford, Connecticut facility but
assigns to its Distributor, to the extent possible, any warranty offered
by the manufacturer of such product. This warranty shall be void if a
Product is altered, serviced or repaired by anyone other than
Manufacturer or its authorized Distributors. This warranty shall also
be void if there is a failure to maintain the Products and the systems in
which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND
DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER
EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS,
TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY
MANUFACTURER INCLUDING WITHOUT LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR
ANY PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE
LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY
ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,
COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer
with respect to its products and replaces all previous warranties and is
the only warranty made by Manufacturer. No increase or alteration,
written or verbal, of the obligation of this warranty is authorized.
Manufacturer does not represent that its products will prevent any loss
by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at
Manufacturer's discretion, each part returned by its authorized
Distributor and acknowledged by Manufacturer to be defective,
provided that such part shall have been returned to Manufacturer with
all charges prepaid and the authorized Distributor has completed
Manufacturer's Return Material Authorization form. The replacement
part shall come from Manufacturer's stock and may be new or
refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND
EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.

Warn-HL-08-2009.fm

Gamewell-FCI Control Panels SLC Wiring Guide — P/N 9021-60542:A 01/15/10 59


Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118

www.gamewell-fci.com
ILI-MB-E3
Intelligent Loop Interface - Main Board
Installation Instructions
12 Clintonville Road Northford, CT 06472-1610 USA PN 9000-0579:E 09/03/09 ECN 08-924
203-484-7161 • FAX 203-484-7118 • www.gamewell-fci.com

! CAUTION: STATIC SENSITIVE EQUIPMENT


THIS EQUIPMENT IS SENSITIVE TO STATIC ELECTRICITY. IT MAY BE DAMAGED IF NOT PROPERLY
HANDLED. TRANSPORT AND STORE THIS UNIT IN A STATIC-SHIELDING BAG.
FAILURE TO OBSERVE THIS REQUIREMENT COULD CAUSE LATENT DAMAGE TO THE EQUIPMENT
WHICH MIGHT NOT MANIFEST ITSELF UNTIL AFTER THE EQUIPMENT IS PLACED IN SERVICE.

! CAUTION: DISCONNECT ALL POWER


REMOVE ALL SOURCES OF POWER BEFORE SERVICING, REMOVING OR INSTALLING ANY UNITS.

Section 1: Description
The ILI-MB-E3 is the main operating board for the E3 Series® control. It provides terminals for the connection of all of
the sub-assemblies. This sub-assembly can support the LCD-E3, DACT-E3, and up to a total of sixteen (16)
ASM-16 sub-assemblies and/or ANU-48 Remote LED Driver Modules.

Figure 1.1 ILI-MB-E3 Signaling Line Circuit Sub-Assembly

TB3 TB4

TB5
TB 2

TB1 TB6

Figure 1.2 ILI-MB-E3 Signaling Line Circuit Sub-Assembly


E3 Series® is a registered trademark and CAMWorks™ is a trademark of Honeywell International Inc.
©2009 Copyright by Honeywell International, Inc. All rights reserved.
Section 2: Installation
1. Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that
could cause condensation. Equipment must be securely mounted on rigid, permanent walls.
2. Remove the ILI-MB-E3 sub-assembly from its static-shield bag, observing proper static protection measures.
3. Visually inspect the unit for damage.
4. Use the Hardware Kit provided with the unit.

NOTE: For Installation Instructions, refer to the E3 Series® Expandable Emergency Evacuation Installation/
Operation Manual, P/N 9000-0574.

2 ILI-MB-E3 Installation Instructions — P/N 9000-0579:E 09/03/09


Section 3: Wiring
Field wiring connections for the ILI-MB-E3 are shown in Table 3.1 and Figure 3.1.
Designation Description Comments
TB1-1, TB1-3 +24 V IN +24 VDC Input from PM-9/PM-9G TB4-1
TB1-2, TB1-4 GND Common negative from PM-9/PM-9G TB4-2
TB2-1 NAC 1 B+ Notification Appliance Circuit 1 (See Note 6)
TB2-2 NAC 1 B - Notification Appliance Circuit 1 (See Note 6)
TB2-3 NAC 1 A+ Notification Appliance Circuit 1 (See Note 6)
TB2-4 NAC 1 A- Notification Appliance Circuit 1 (See Note 6)
TB2-5 NAC 2 B+ Notification Appliance Circuit 2 (See Note 6)
TB2-6 NAC 2 B- Notification Appliance Circuit 2 (See Note 6)
TB2-7 NAC 2 A+ Notification Appliance Circuit 2 (See Note 6)
TB2-8 NAC 2 A- Notification Appliance Circuit 2 (See Note 6)
TB3-1 AUX RS485 A Output to LCD-E3, ASM-16, ANU-48, LCD-7100, DACT-E3
(See Note 3)
TB3-2 AUX RS485 B Output to LCD-E3, ASM-16, ANU-48, LCD-7100, DACT-E3
(See Note 3)
TB3-3 Earth Ground Connect to water pipe ground
TB3-4 Resettable B+ Auxiliary resettable 24 VDC power
TB3-5 GND Common negative
TB3-6 Non-resettable B+ Auxiliary non-resettable 24 VDC power
TB3-7 GND Common negative
TB3-8 Municipal Ckt+ Output to Local Energy City Box, Remote Station or Releasing
Solenoid - Non Power-limited (See Note 7)
TB3-9 Municipal Ckt - Output to Local Energy City Box or Remote Station or Releasing
Solenoid - Non Power-limited (See Note 7)
TB4-1 SLC 2 A- SLC 2 Style 6 / 7 Return (See Note 5)
TB4-2 SLC 2 A+ SLC 2 Style 6 / 7 Return (See Note 5)
TB4-3 SLC 2 B- SLC 2 Style 4 / 6 / 7 Out (See Note 5)
TB4-4 SLC 2 B+ SLC 2 Style 4 / 6 / 7 Out (See Note 5)
TB4-5 SLC 1 A- SLC 1 Style 6 / 7 Return (See Note 5)
TB4-6 SLC 1 A+ SLC 1 Style 6 / 7 Return (See Note 5)
TB4-7 SLC 1 B- SLC 1 Style 4 / 6 / 7 Out (See Note 5)
TB4-8 SLC 1 B+ SLC 1 Style 4 / 6 / 7 Out (See Note 5)
TB5-1 Alarm DC NC Alarm relay contact, N/C
TB5-2 Alarm DC NO Alarm relay contact, N/O
TB5-3 Alarm DC Common Alarm relay contact, Common
TB5-4 Supv DC NC Supervisory relay contact, N/C
TB5-5 Supv DC NO Supervisory relay contact, N/O
TB5-6 Supv DC Common Supervisory relay contact, Common
TB5-7 Trbl DC NC Trouble relay contact, N/C
TB5-8 Trbl DC NO Trouble relay contact, N/O
TB5-9 Trbl DC Common Trouble relay contact, Common
TB6-1 RS232 GND To red lead on download cable P/N 75267
TB6-2 RS232 TxD To black lead on download cable P/N 75267 RS-232 Download
TB6-3 RS232 Supervision Optional Printer Supervision or Printer Port
TB6-4 RS232 RxD To green lead on download cable P/N 75267
W1, W2, W3 Factory Jumpers Factory Use Only (Default OUT)
W4 ARCNET Term OPEN = Normal Operation.
SHORT = If the ILI-MB-E3 is located at the end of the ARCNET bus.

Table 3.1 ILI-MB- E3 Field Wiring Connections

ILI-MB-E3 Installation Instructions — P/N 9000-0579:E 09/03/09 3


Designation Description Comments
W7, W8 Municipal Jumpers “MB” = For Master Box / Releasing
“PR” = For Polarity Reversal (See Note 7)
W9 Ground Fault Detection IN = ENABLE
OUT = DISABLE (See Note 1)
SW2-1 Switch 1 ON = SLC 1 DISABLED
(OFF = SLC 1 ENABLED)
SW2-2 Switch 2 ON = SLC 2 DISABLED
(OFF = SLC 2 ENABLED)
SW2-3 Switch 3 ON = NAC 1 & 2 DISABLED
(OFF = NAC 1 & 2 ENABLED)
SW2-4 Switch 4 ON = BUZZER DISABLED
(OFF = BUZZER ENABLED)
SW2-5 Switch 5 ON = RS232 115.2 K BAUD
(OFF = defined by CAMWorks™)
J1 ILI to PM-9/PM-9G Connects to PM-9/PM-9G J1. (See Note 1 & 2)
COMM Port
J2 Local ARCNET Connects to J5 of the next ILI-E3 or ILI95-E3 Series sub-assembly.
J5 Local ARCNET Connects to J2 from the previous ILI-E3 or ILI95-E3 Series
sub-assembly.
J4 ARCNET Repeater Connects to INI-VG J7 or J10 of the RPT-E3 (See Note 4)
Connector
NOTE 1: Must be IN when connected via ribbon cable from this ILI95-MB-E3 at J1 to a PM-9/PM-9G
connector J1. Requires the removal of the JMP-1 on the PM-9/PM-9G.
Must be OUT when a ribbon cable is not installed in J1 and the ground fault detection is being provided by
another ILI95-MB-E3, ILI-MB-E3 or an INI-VG Series node that is being powered from a common
PM-9/PM-9G.
NOTE 2: Connect J1 to PM-9/PM-9G J1 only when the PM-9/PM-9G is NOT powering an INI-VG Series sub-
assembly in addition to an ILI95-MB-E3, ILI95-S-E3 or an ILI-MB-E3 or ILI-S-E3 sub-assembly.
NOTE 3: Use ILI95-MB-E3 Auxiliary RS485 Port (TB3-1 COM A & TB3-2 COM B) to connect to
LCD-E3 (E3 annunciator module) LCD-7100 (7100 Remote Annunciator Module) ASM-16 (Addressable
Switch Module) ANU-48 (LED Annunciator Driver Module) DACT-E3 (E3 Digital Communicator Transmitter).
NOTE 4: RPT-E3 (E3 Repeater Module) is required when this ILI-MB-E3 is networked via ARCNET to an
INI-VGE, INI-VGC, INI-VGX, or another RPT-E3 equipped node. Not required for LOCAL ARCNET
communication within a single enclosure. (J2 or J5).
NOTE 5: For Style 4 use terminals B+ and B- only. For Style 6 use terminals B+ and B- and connect return
wires to A+ and A-. For Style 7 wire as for Style 6 and use Isolator Modules and or Isolator Detectors per
recommendations as required.
NOTE 6: NAC1 and NAC2 are rated as Special Application.
NOTE 7: When used for Releasing, must be configured in CAMWorks™ for Releasing in the General
Settings Section.
Table 3.1 ILI-MB- E3 Field Wiring Connections (Continued)

4 ILI-MB-E3 Installation Instructions — P/N 9000-0579:E 09/03/09


UNSUPERVISED & NON PWR-LIMITED CONNECT TO EARTH GROUND PER ARTICLE 780 DISABLE GROUND FAULT DETECTION CIRCUIT:
WHEN SET FOR MUNICIPAL CKT. OF THE NATIONAL ELECTRICAL CODE. FAILURE 1. ON THE PM-9G WHEN LOCATED IN THE SAME
UNSUPERVISED WHEN SET FOR TO CONNECT TO A METALLIC GROUND WATER CABINET WITH A SINGLE ILI-MB-E3 PCB.
REVERSE POLARITY PIPE OR GROUND DRIVEN ROD WILL RESULT IN 2. WHEN THE CABINET CONTAINS MULTIPLE ILI-MB-E3
2.0 AMPS MAX. OUT OF EACH LOSS OF LIGHTNING PROTECTION, REDUCED PCBS, SELECT JUST ONE ILI-MB-E3 PCB TO
EXT PWR OUTPUT. NOTE: PROTECTION AGAINST TRANSIENTS AND COULD SUPERVISE FOR GROUND FAULT. DISABLE
DO NOT EXCEED 2.5 AMPS TOTAL ADVERSELY AFFECT PROPER SYSTEM OPERATION. GROUND FAULT DETECTION ON THE REMAINING ILI-E3 PCBS.
BOTH OUTPUTS COMBINED PANEL NEUTRAL OR CONDUIT GROUND IS NOT
ACCEPTABLE. USE 14 AWG WIRE MINIMUM.
TO RPT-E3 GROUND FAULT GROUND FAULT
TO: LCD-E3 TB1-3, ASM-16 TB1-1,
ARCNET DETECTION ENABLED DETECTION DISABLED
ANU-48 TB1-1, LCD-7100 TB1-2, DACT-E3 TB1-1
TO: LCD-E3 TB1-4, ASM-16 TB1-2, LEAVE W1, W2, W3, CONNECTOR (MIDDLE TO RIGHT PIN) (MIDDLE TO LEFT PIN)
ANU-48 TB1-2, LCD-7100 TB1-1, DACT-E3 TB1-2 W4 & W5 OPEN J10

GFLT
W4 J4 DIS ENA
W5 9 1 9 1 J2 15 1
OFF ON OFF ON SLC1 CLASS "B", STYLE 4 (+)
AUX TERM
10 2 10 2 16 2
ARCNET W9
TERM

485A 485B
J5 BSEL
TB4 SLC1 CLASS "B", STYLE 4 (-)
W2 NOTE: IF ONLY ONE SLC IS SLC1 CLASS "A", STYLE 6 (+)
W1
FACTORY BSEL
RESETTABLE PWR OUT USED STYLE 6 (CLASS "A") SLC1 CLASS "A", STYLE 6 (-)
USE
W3
SYSTEM GROUND TB3 USE CABLE P/N: 75645 (20") TO THE UNUSED SLC TERMINALS SLC2 CLASS "B", STYLE 4 (+)
NON-RESET PWR OUT MB PR
CONNECT TO J5 SOCKET OF NEXT MUST BE JUMPERED STYLE 6 SLC2 CLASS "B", STYLE 4 (-)
SYSTEM GROUND W7 ILI-MB-E3 PCB OR ILI-S-E3 TO PREVENT LOOP FAULT SLC2 CLASS "A", STYLE 6 (+)
MUNICIPAL CKT (+) PCB IN SAME CABINET (UP TO 8 SLC2 CLASS "A", STYLE 6 (-)

1 2 3 4 5 6 78 9
W8

RB+ GND AB+ GND MU+ MU-


MUNICIPAL CKT (-) ILI-E3 PCBS MOUNTED IN SAME
MB PR ALL RELAYS RATED TROUBLE COMMON
NAC1 CLASS B OUT (+) CABINET CAN BE CONNECTED) TROUBLE NORMALLY OPEN
AT 2.0 AMPS @ 30 VDC

ILI-MB-E3 Installation Instructions — P/N 9000-0579:E 09/03/09


Section 3: Wiring (Continued)

NAC1 CLASS B OUT (-) SET FOR MUNICIPAL CKT/RELEASE OR TROUBLE NORMALLY CLOSED
RESISTIVE SUPV COMMON
NAC1 CLASS A RETURN (+) REVERSE POLARITY OUTPUT NOTE: TROUBLE DRY
NAC1 CLASS A RETURN (-) MB = MUNICIPAL CKT/RELEASE TB5 SUPV NORMALLY OPEN
RELAYS CONTACTS
NAC2 CLASS B OUT (+) TB2 (MIDDLE & LEFT PINS OF W7 & W8) SUPV NORMALLY CLOSED
TRANSFER UPON ALARM,
NAC2 CLASS B OUT (-) PR = REVERSE POLARITY ALARM COMMON
SUPERVISORY, TROUBLE
NAC2 CLASS A RETURN (+) (MIDDLE & RIGHT PINS OF W7 & W8) OR SYSTEM POWER LOSS ALARM NORMALLY OPEN
NAC2 CLASS A RETURN (-) ALARM NORMALLY CLOSED
10 9
TB1 TB6-4 RXD TO PIN 3 OF DB9
PM-9G, +24VDC (+) +24VDC TB6
PM-9G, GND (-) LED LED LED LED LED LED LED LED LED LED LED LED SW2 SW1 J1 TB6-3 SUPV TO PIN 9 OF DB9
GND ON 8 765432 1
1 2 3 4 5 6 7 8 9 10 11 12
OPT. MOD. (+) +24VDC + TB6-2 TXD TO PIN 2 OF DB9
REC MRC DUP TX RX RST DG ALRM SUPV TRBL PWR GND 2 1

1 2 34 5 6 7 8 1 2 3 4
4 3 2 1 4 3 2 1 9 8 76 5 4 3 2 1 4 32 1
Figure 3.1 illustrates the wiring connections for the ILI-MB-E3 sub-assembly.

OPT. MOD. (-) GND FLT 12345 ARCNET ADDRESS TB6-1 GND TO PIN 5 OF DB9
NOTE:
USE SWITCH SW1 TO TO PM9G DOWNLOAD CABLE

Figure 3.1 ILI-MB-E3 Wiring Diagram


NAC1 & NAC2
TYPICAL STYLE Y NOTE: POWER CONNECTION SET ILI-MB-E3 PCB CONNECTOR J1 P/N: 75267
CLASS "B" NAC, FROM PM-9G IS NETWORK ADDRESS (1 - 64)
RS232 PORT: 15 VDC MAXIMUM
USE 33KOHM, NON-POWER LIMITED SET TO 0 (ZERO) FOR
0.05 AMP MAXIMUM
STANDALONE MODE
1/2 W EOL RESISTOR UP TO 115.2 K BAUD (DEFAULT)
- OR - 8 DATA BITS, 1 STOP BIT, NO PARITY
TYPICAL STYLE Z LED1 = REC (NETWORK RECONFIGURATION)
CLASS "A" NAC, LED2 = MRC (NETWORK RECONFIGURATION ORIGINATING FROM THIS NODE) SLC WIRE SELECTION:
NO EOL RESISTOR LED3 = DUP (NODE'S NETWORK ADRESS IS DUPLICATED AT ANOTHER NODE) UNSHIELDED, TWISTED-PAIR
REQUIRED LED4 = TX (NODE IS TRANSMITTING DATA TO THE NETWORK) 18 AWG MIN. 40 OHMS MAX. WIRE
NAC RATINGS (EACH): LED5 = RX (NODE IS RECEIVING DATA FROM THE NETWORK) RESISTANCE PER LOOP
24VDC (NOMINAL) FWR LED6 = RST (NODE IS RESETTING) 0.5µF MAX. CAPACITANCE
MAX. ALARM LOAD: LED7 = DG (GENERAL NETWORK FAULT) PER LOOP
2.0 AMPS PER CKT LED8 = ALRM (ALARM CONDITION) SW2 POS 1 ON = SL1 DISABLED (OFF = SLC1 ENABLED)
LED9 = SUPV (SUPERVISORY OFF-NORMAL) SW2 POS 2 ON = SL2 DISABLED (OFF = SLC2 ENABLED)
SUPERVISED &
LED10 = TRBL (TROUBLE CONDITION) SW2 POS 3 ON = NAC1 & 2 DISABLED (OFF = NAC1 & 2 ENABLED)
POWER-LIMITED
LED11 = PWR (DC POWER GOOD) SW2 POS 4 ON = BUZZER DISABLED (OFF = BUZZER ENABLED)
18 AWG WIRE MIN. LED12 = GND FLT (GROUND FAULT) SW2 POS 5 ON = RS232 115.2K BAUD (OFF = DEFINED BY CamWorks™)
NOTE: NAC1 & NAC2 ARE RATED AS SPECIAL APPLICATION.

5
Section 3: Wiring (Continued)
Table 3.2 lists the wiring requirements for the ILI-MB-E3 sub-assembly.

Circuit Type Circuit Function Wire Requirements Distance Typical Wire Type*
SLC Connects to intelligent Twisted-unshielded pair, 12 to 10,000 ft. (3,000 m) 12 AWG (3.1 mm2)
(power-limited) and addressable 18 AWG (3.1 to 0.78 mm2) 8,000 ft. (2,400 m) 14 AWG (2.00 mm2)
modules. 40 Ohms maximum per length 4,875 ft. (1,450 m)
of Style 6 & 7 loops. 16 AWG (1.30 mm2)
40 Ohms combined-branch 3,225 ft. (980 m) 18 AWG (0.78 mm2)
circuits maximum for Style 4
loop.
MC cable with 2 conductor
twisted.
Or Shielded wire, in conduit or 1,000 ft. (304.8 m) 12 to 18 AWG
outside of conduit or MC cable.. (3.1 to 0.78 mm2)
MC cable with 3 conductor
twisted.
Note: Maximum total
capacitance of all SLC wiring
(both between conductors and
from any conductor to ground)
should not exceed 0.5
microfarads.
EIA-485 Connects to LCD-E3, Twisted-unshielded pair with a 3,000 ft. (.914 m) 16 AWG (1.30 mm2)
(power-limited) ASM-16 and ANU-48 characteristic impedance of (maximum)
modules. 120 Ohms. 18 AWG
(0.78 mm2) minimum.
EIA-232 Connects to Printers, Twisted-unshielded pair. 18 50/15.24 16 AWG (1.30 mm2)
(power-limited) CRT, or PC. 2
AWG (0.78 mm ) minimum (without modem)
NAC Notification E3 (power-limited) 12-18 AWG (3.1 to 0.78 mm2) To meet 1.2 V drop, 12 to 18 AWG
Appliance Circuit At alarm current level, no more or sized to provide (3.1 to 0.78 mm2)
than a 1.2 V drop at the end of the minimum rated
the circuit, or sized to provide operating voltage of
the minimum rated operating the appliances
voltage of the appliances used. used.
24 VDC Power To Transmitter 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 volt 12 to 18 AWG
Runs Annunciator Size wire so that no more than drop (3.1 to 0.78 mm2)
(power-limited) 1.2 V drop across wire run from
supply source to end of any
branch.
ARCNET Provides interface Twisted-unshielded pair low 3,000 ft. (.914 m) 18 AWG (3.1 mm2)
(power-limited) between network capacitance 18 AWG
nodes.
ARCNET should be
installed in a separate
conduit.
NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL 1459.
Table 3.2 Wiring Requirements

6 ILI-MB-E3 Installation Instructions — P/N 9000-0579:E 09/03/09


ADDRESS SWITCH SETTINGS
SWITCH DOWN (ON) SWITCH UP (OFF)

STANDALONE
8 76 54 3 2 1
=0
on 8 76 54 3 2 1
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=1 =10 =19 =28 =37 =46 =55
on on on on on on on
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=2 =11 =20 =29 =38 =47 =56
on on on on on on on
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=3 =12 =21 =30 =39 =48 =57

ILI-MB-E3 Installation Instructions — P/N 9000-0579:E 09/03/09


on on on on on on on
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=4 =13 =22 =31 =40 =49 =58
on on on on on on on
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=5 =14 =23 =32 =41 =50 =59
on on on on on on on
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=6 =15 =24 =33 =42 =51 =60
on on on on on on on
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1

Figure 4.1 ILI-MB-E3 Address Switch Settings


=7 =16 =25 =34 =43 =52 =61
on on on on on on on
Section 4: Programming Address Switch Settings

8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=8 =17 =26 =35 =44 =53 =62
on on on on on on on
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=9 =18 =27 =36 =45 =54 =63
on on on on on on on
8 76 54 3 2 1
=64
on
Set the address using the switch, SW1. Figure 4.1 illustrates the programming address switch settings for the ILI-MB-E3.

7
Section 5: Specifications
The following list the electrical specifications for the ILI-MB-E3.

Operating Voltage 24 VDC (from PM-9/PM-9G power supply)


Operating Current: 0.081 amp
Alarm Current: 0.150 amp
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93%, non-condensing at 90° F (32° C)
Supervised
Power-limited

Section 6: Minimum Configuration


The minimum configuration for use as a working system is as follows:
A) ILI-MB-E3
B) PM-9/PM-9G Power Supply
C) LCD-E3/NGA Display Module (only one (1) is required per Networked System)
Optional modules for use with the ILI-MB-E3 are as follows:
A) RPT-E3 Repeater Module (Required for Distributed Network Systems)
B) LCD-E3 LCD Display Module
C) DACT-E3 Digital Alarm Communicator Transmitter
D) INI-VG Series Voice Gateway Modules
E) ASM-16 Auxiliary Switch Module

8 ILI-MB-E3 Installation Instructions — P/N 9000-0579:E 09/03/09


NGA
Network LCD Annunciator
Installation Instructions
12 Clintonville Road Northford, CT 06472-1610 USA PN 9000-0568:D 09/03/09 ECN 08-924
203-484-7161 • FAX 203-484-7118 • www.gamewell-fci.com

! CAUTION: STATIC SENSITIVE EQUIPMENT


THIS EQUIPMENT IS SENSITIVE TO STATIC ELECTRICITY. IT MAY BE DAMAGED IF NOT PROPERLY
HANDLED. TRANSPORT AND STORE THIS UNIT IN A STATIC-SHIELDING BAG.
FAILURE TO OBSERVE THIS REQUIREMENT COULD CAUSE LATENT DAMAGE TO THE EQUIPMENT
WHICH MIGHT NOT MANIFEST ITSELF UNTIL AFTER THE EQUIPMENT IS PLACED IN SERVICE.

! CAUTION: DISCONNECT ALL POWER


REMOVE ALL SOURCES OF POWER BEFORE SERVICING, REMOVING OR INSTALLING ANY UNITS.

Section 1: Description
The NGA LCD Graphic Annunciator is a software programmable touchscreen interface for the Gamewell-FCI emergency
voice evacuation systems. It provides an LCD display of system events, together with system status indicating LEDs, and
touch-screen switches for the following conditions:
• Alarm Acknowledge • Signal Silence
• Trouble Acknowledge • System Reset
The background display can be programmed to be labeled as, “Command Center in Control” if required. The NGA
mounts in the E3 Series® enclosure or it may be installed in a remote location. It occupies one (1), node on the Broadband
network.

Figure 1.1 NGA Sub-Assembly


E3 Series® is a registered trademark of Honeywell International Inc.
©2009 Copyright by Honeywell International, Inc. All rights reserved.
Section 2: Installation
1. Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that
could cause condensation. Equipment must be securely mounted on rigid, permanent walls.

NOTE: For a new installation, it is recommended that you work on a flat surface when you remove the inner
door of the enclosure and install all the sub-assemblies and/or blank panels.

2. Remove the unit from its static-shield bag, observing proper static protection measures.
3. Visually inspect the unit for damage.
4. Use the Hardware Kit provided with the unit.
For additional information on the installation, refer to the E3 Series® Expandable Emergency Evacuation
Installation/Operation Manual, P/N 9000-0574.

NOTE: WIRING REQUIREMENTS


To connect the ribbon cable, plug the ARCNET interconnect ribbon cable into J4 of the NGA. Plug the other end
of the ribbon cable into the INI-VG connector J7, or connect to J10 of the RPT-E3 sub-assembly. Do not
connect to J3. Plug the other end into J4 of the NGA.

2 NGA Installation Instructions — P/N 9000-0568:D 09/03/09


Section 3: Wiring Connections
Table 3.1, Table 3.2, and Figure 3.1 illustrate the NGA electrical connections.

Designation Description Comments


TB1-1 NGA TB1-1 24 VDC IN (+) from ILI/ILI95-MB TB3-6 or RPT-E3 TB4-3
TB1-2 NGA TB1-2 SYS GND IN (-) from ILI/ILI95-MB TB3-7 or RPT-E3 TB4-4
TB1-3 NGA TB1-3 Differential ARCNET COM A IN from RPT-E3 TB3-3
TB1-4 NGA TB1-4 Differential ARCNET COM B IN from RPT-E3 TB3-4
TB1-5 24 VDC OUT (+) to next device
TB1-6 SYS GND OUT (-) to next device
TB1-7 Differential ARCNET COM A OUT to next device
TB1-8 Differential ARCNET COM B OUT to next device
TB1-9 RxD RxD to computer DB9 PIN 3, Printer DB25 PIN 2, or RS232 RxD GRN
download cable
TB1-10 Supervision SUPV to computer DB9 PIN 9, Printer DB25 PIN 20, or RS232 Supv download
cable
TB1-11 TxD TxD to computer DB9 PIN 2, Printer DB25 PIN 3, or RS232 TxD BLK download
cable
TB1-12 GND GND to computer DB9 PIN 5, Printer DB25 PIN 7, or RS232 GND RED
download cable

J1 Internal use To overlay


J2 Factory use only
J3 Program Factory use only
J4 RS-485 Connects to J7 of INI-VG
J5 Internal use To overlay
J6 Internal use
J7 Internal use

W1 Factory use only


W2 Factory use only
W3 Factory use only
W4 ARCNET TERM OFF
W5 RS-485 TERM OFF
Table 3.1 NGA Wiring Connections

Designation Description Comments


LED1 REC Network is reconfiguring
LED2 MRC This node is initiating a network reconfiguration
LED3 DUP Duplicate node address or switch error
LED4 TX The sub-assembly is transmitting network data
LED5 RX The sub-assembly is receiving network data
LED6 RST Firmware fault
LED7 DG Trouble condition
Table 3.2 NGA LED Designations

NGA Installation Instructions — P/N 9000-0568:D 09/03/09 3


4
REAR VIEW PIN 1 CONNECTS TO LOCAL INI-VG ARCNET REPEATER
J7 CONNECTOR – CABLE ASSEMBLY PN 75618
ARCNET (MAX. DISTANCE 36")
REPEATER
J4

J3
TAG
CONNECT THE NGA TO THE
IMPORTANT NOTE: ARCNET REPEATER J4 OR
FOR NGA REVS 1-4 WIRE TO THE DIFFERENTIAL
INSTALL THE SHUNT ARCNET
ACROSS J4 PINS 13 & 14 COM A & COMB B
WHEN USING THE W1 DO NOT CONNECT THE NGA BOTH
FACTORY
DIFFERENTIAL ARCNET USE AT THE SAME TIME.
TERMS TB1-3 & 4 DO NOT
OR TB1-7 & 8 INSTALL
DO NOT CONNECT TO

J1
THE EXTERNAL POWER

TO OVERLAY
SUPPLY WHEN THE NGA
INSTALL W2 & W3 ACROSS THE J4 IS USED.

1
MIDDLE AND BOTTOM PINS. 24VDC IN(+) FROM ILI/ILI95-MB TB3-6 OR RPT-E3 TB4-3
Figure 3.1 illustrates the wiring connections for the NGA.

2
SYS GND IN(-) FROM ILI/ILI95-MB TB3-7 OR RPT-E3 TB4-4

3
DIFFERENTIAL ARCNET COM A IN FROM RPT-E3 TB3-3

J7
4

W2
W3
DIFFERENTIAL ARCNET COM B IN FROM RPT-E3 TB3-4
Section 3: Wiring Connections (Continued)

5
24VDC OUT (+) TO NEXT DEVICE

BSEL1

BSEL0
6
SYS GND OUT (-) TO NEXT DEVICE

BACKLIGHT
7
DIFFERENTIAL ARCNET COM A OUT TO NEXT DEVICE

W4
TERM

Figure 3.1 NGA Wiring Connections


ARCNET
8
+ DIFFERENTIAL ARCNET COM B OUT TO NEXT DEVICE
9
RxD TO COMPUTER DB9 PIN 3 OR PRINTER DB25 PIN 2

TERM
RS485

W5
SUPV TO COMPUTER DB9 PIN 9 OR PRINTER DB25 PIN 20

TX
RX
DG
RST

REC
DUP
MRC
PWR
TxD TO COMPUTER DB9 PIN 2 OR PRINTER DB25 PIN 3

TRBL
SUPV
ALRM
10 11 12

GND TO COMPUTER DB9 PIN 5 OR PRINTER DB25 PIN 7


LOCAL RS485 RS232 RxD GRN DOWNLOAD CABLE
J6
TB1

RS232 Supv

LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
LED9
LED10
LED11
J2 P/N 75267
RS232 TxD BLK
RS232 Gnd RED
9 10 11 12

RS232 PORT: 15 VDC MAX., 0.05 AMP MAX. UP TO 115.2 K BAUD. 115.2K BAUD REQUIRED FOR
CONFIGURATION DOWNLOADS VIA NGA, 8 DATA BITS, 1 STOP BIT, NO PARITY

NGA Installation Instructions — P/N 9000-0568:D 09/03/09


Section 4: Circuit Wiring Requirements
Table 4.1 provides the circuit wiring requirements for the NGA sub-assembly

Distance
Circuit Type Circuit Function Wire Requirements (feet/meters) Typical Wire Type*
SLC Connects to Twisted-unshielded pair, 12 to 18 AWG 10,000 ft. (3,000 m) 12 AWG (3.1 mm2)
(power-limited) intelligent and (3.1 to 0.78 mm2) 40 Ohms maximum 8,000 ft. (2,400 m) 14 AWG (2.00 mm2)
addressable modules. per length of Style 6 & 7 loops.
4,875 ft. (1,450 m) 16 AWG (1.30 mm2)
40 Ohms combined-branch circuits
3,225 ft. (980 m) 18 AWG (0.78 mm2)
maximum for Style 4 loop.
MC cable with 2 conductor twisted.
Or Shielded wire, in conduit or outside of 1,000 ft. (304.8 m) 12 to 18 AWG
conduit or MC cable. (3.1 to 0.78 mm2)
MC cable with 3 conductor twisted.
Note: Maximum total capacitance of all
SLC wiring (both between conductors
and from any conductor to ground)
should not exceed 0.5 microfarads.
EIA-485 Connects to LCD-E3, Twisted-unshielded pair with a 3,000 ft (maximum) 16 AWG (1.30 mm2)
(power-limited) ASM-16 and ANU-48 characteristic impedance of 120
modules Ohms. 18 AWG (0.78 mm2) minimum.
EIA-232 Connects to Printers, Twisted-unshielded pair. 18 AWG 50/15.24 16 AWG (1.30 mm2)
(power-limited) CRT, E3or PC. (0.78 mm2) minimum (without modem)
NAC E3 (power-limited) 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 V drop, or 12 to 18 AWG
Notification 2
At alarm current level, no more than a sized to provide the (3.1 to 0.78 mm )
Appliance 1.2 V drop at the end of the circuit, or minimum rated
Circuit sized to provide the minimum rated operating voltage of
operating voltage of the appliances the appliances used.
used.
24 VDC Power To Transmitter 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 volt drop 12 to 18 AWG
Runs Annunciator Size wire so that no more than 1.2 V (3.1 to 0.78 mm2)
(power-limited) drop across wire run from supply
source to end of any branch.
CHG-120 External battery 12 AWG (3.1 mm2) in conduit 20/6.1 (maximum) 12 AWG (3.1 mm2)
charger
ARCNET Provides interface Twisted-unshielded pair, low 3,000 ft. (.914 m) 18 AWG (3.1 mm2)
(power-limited) wiring capacitance 18 AWG
ARCNET should be
installed in a separate
conduit.
Note: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL 1459.
Table 4.1 NGA Wiring Requirements

NGA Installation Instructions — P/N 9000-0568:D 09/03/09 5


Section 5: Programming Address Switch Settings
To set the address for the NGA sub-assembly, use the menu on the touchscreen. If the menu is not used to set the address,
the address defaults to 64.

Section 6: Specifications
The following are the NGA specifications.
Operating Voltage: 24 VDC (from PM-9/PM-9G power supply)
Operating Current: 0.200 amp* (See Note)
Alarm Current: 0.200 amp
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93%, non-condensing at 90° F (32° C)
Supervised
Power-limited:
*NOTE: Normal operating current. During a power failure, the current drops to 0.045 amp, since the backlight is
extinguished.

6 NGA Installation Instructions — P/N 9000-0568:D 09/03/09


RPT-E3
Repeater Module
Installation Instructions
12 Clintonville Road Northford, CT 06472-1610 USA PN 9000-0580:D 09/03/09 ECN 08-924
203-484-7161 • FAX 203-484-7118 • www.gamewell-fci.com

! CAUTION: STATIC SENSITIVE EQUIPMENT


THIS EQUIPMENT IS SENSITIVE TO STATIC ELECTRICITY. IT MAY BE DAMAGED IF NOT PROPERLY
HANDLED. TRANSPORT AND STORE THIS UNIT IN A STATIC-SHIELDING BAG.
FAILURE TO OBSERVE THIS REQUIREMENT COULD CAUSE LATENT DAMAGE TO THE EQUIPMENT
WHICH MIGHT NOT MANIFEST ITSELF UNTIL AFTER THE EQUIPMENT IS PLACED IN SERVICE.

! CAUTION: DISCONNECT ALL POWER


REMOVE ALL SOURCES OF POWER BEFORE SERVICING, REMOVING OR INSTALLING ANY UNITS.

Section1: Description
The Repeater Module (RPT-E3) provides the remote interface between the ILI-MB-E3 or ILI95-MB-E3 and the
Broadband Network. The Repeater Module (RPT-E3) can also be used with the NGA. The unit is available for use with
unshielded twisted-pair wire or fiber-optic cable (RPT-E3-FO), or unshielded twisted-pair only (RPT-E3-UTP).

Figure 1.1 RPT-E3 Repeater Sub-Assembly Figure 1.2 RPT-E3 Sub-Assembly

E3 Series® is a registered trademark and CAMWorks™ is a trademark of Honeywell International Inc.


©2009 Copyright by Honeywell International, Inc. All rights reserved.
Section 2: Installation
1. Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that
could cause condensation. Equipment must be securely mounted on rigid, permanent walls.
2. Remove the RPT-E3 Repeater Module from its static-shield bag, observing proper static protection measures.
3. Visually inspect the unit for damage.
4. Use the Hardware Kit provided with the unit.

NOTE: For additional information on the installation, refer to the E3 Series® Expandable Emergency
Evacuation Installation/Operation Manual, P/N 9000-0574.

2 RPT-E3 Installation Instructions — P/N 9000-0580:D 09/03/09


Section 3: Wiring
The RPT-E3 wiring connections are shown in Table 3.1 and Figure 3.1.
Designation Description Comments
TB1-1 ARCNET PORT 1A Broadband Network (See Note 1)
TB1-2 ARCNET PORT 1B Broadband Network (See Note 1)
TB1-3 ARCNET PORT 2A Broadband Network (See Note 1)
TB1-4 ARCNET PORT 2B Broadband Network (See Note 1)
TB2 Earth Ground Local Differential ARCNET (See Note 2)
TB3-1 COM A IN Local Differential ARCNET (See Note 3)
TB3-2 COM B IN Local Differential ARCNET (See Note 3)
TB3-3 COM A OUT Local Differential ARCNET Connect to NGA TB1-3. (See Note 3)
TB3-4 COM B OUT Local Differential ARCNET Connect to NGA TB1-4. (See Note 3)
TB4-1 + 24V IN Do not use, if J10 is used.
(+24 VDC IN from TB3-6 ILI-MB-E3/ILI95-MB-E3)
TB4-2 Common – IN Do not use, if J10 is used.
(-GND IN from TB3-7 ILI-MB-E3/ILI95-MB-E3)
TB4-3 + 24 V OUT Do not use, if J10 is used.
TB4-4 Common – OUT Do not use, if J10 is used.
J10 ARCNET Connector to ILI-MB-E3/ILI95-MB-E3 or ILI-S-E3/ILI95-S-E3, J4
(See Note 4)
U5 Fiber Port 2 IN (See Note 5)
U7 Fiber Port 2 OUT (See Note 5)
U4 Fiber Port 1 IN (See Note 5)
U6 Fiber Port 1 OUT (See Note 5)
J1 ARCNET Term Short when using the Local Differential ARCNET wiring to Terminal
TB3. This is the first and last device on the local net.
Note: If the first and last devices are CLOSED, then the device
between the two must be OPEN. If the ILI-E3 Series is the first
device and the NGA is the last device, then the J1 would be OPEN.
J2 GFI Short to enable Ground Fault Detection on the ARCNET Network
when using copper wiring.
J3 GND FLT Short to enable Ground Fault Detection when remotely connected to
a Listed power source that does not provide earth detection.
OPEN when connected to DC power supplied from an ILI-MB-E3,
ILI95-MB-E3, PM-9/PM-9G or INI-7100.
J4 Transmitter Light Comm port 1 fiber-optic transmitter drive current
Output Control Jumper contributes to drive current when closed.
Contributes 12.5% of maximum drive
J4, J5 & J6 OPEN - minimum drive, 12.5% of maximum.
J4, J5 & J6 CLOSED - maximum drive, 100%
To match drive used on INI boards: SHORT J4, J5 and J6.
J5 Transmitter Light Comm port 1 fiber-optic transmitter drive current
Output Control Jumper contributes to drive current when CLOSED.
Contributes 25% of maximum drive
J4, J5 & J6 OPEN - minimum drive, 12.5% of maximum.
J4, J5 & J6 CLOSED - maximum drive, 100%
To match drive used on INI boards: SHORT J4, J5 and J6.
J6 Transmitter Light Comm port 1 fiber-optic transmitter drive current
Output Control Jumper contributes to drive current when CLOSED.
Contributes 50% of maximum drive
J4, J5 & J6 OPEN - minimum drive, 12.5% of maximum.
J4, J5 & J6 CLOSED - maximum drive, 100%
To match drive used on INI boards: SHORT J4, J5 and J6.

Table 3.1 Repeater-E3 Wiring Connections

RPT-E3 Installation Instructions — P/N 9000-0580:D 09/03/09 3


Designation Description Comments
J7 Transmitter Light Comm port 2 fiber-optic transmitter drive current
Output Control Jumper contributes to drive current when CLOSED.
Contributes 12.5% of maximum drive.
J7, J8 & J9 OPEN - minimum drive, 12.5% of maximum.
J7, J8 & J9 CLOSED - maximum drive, 100%
To match drive used on INI boards: SHORT J7, J8 and J9.
J8 Transmitter Light Comm port 2 fiber-optic transmitter drive current
Output Control Jumper contributes to drive current when CLOSED.
Contributes 25% of maximum drive.
J7, J8 & J9 OPEN - minimum drive, 12.5% of maximum.
J7, J8 & J9 CLOSED - maximum drive, 100%
To match drive used on INI boards: SHORT J7, J8 and J9.
J9 Transmitter Light Comm port 2 fiber-optic transmitter drive current
Output Control Jumper contributes to drive current when CLOSED.
Contributes 50% of maximum drive.
J7 J8 & J9 OPEN - minimum drive, 12.5% of maximum.
J7, J8 & J9 CLOSED - maximum drive, 100%
To match drive used on INI boards: SHORT J7, J8 and J9.
NOTE 1: TB1 - RPT-E3 UTP Network Connections using unshielded, twisted-pair 18 AWG min. 3,000’
(914.4 m) maximum between the following nodes:
– RPT-E3 TB1-1 (COM1A) to: INI-7100 TB1-3 INI-VG TB1-3 or another RPT-E3 TB1-3
– RPT-E3 TB1-2 (COM1B) to: INI-7100 TB1-4 INI-VG TB1-4 or another RPT-E3 TB1-4
– RPT-E3 TB1-3 (COM2A) to: INI-7100 TB1-1 INI-VG TB1-1 or another RPT-E3 TB1-1
– RPT-E3 TB1-4 (COM2B) to: INI-7100 TB1-2 INI-VG TB1-2 or another RPT-E3 TB1-2
NOTE 2: TB2 must be used when the RPT-E3 is used remotely from a main system cabinet such as in a
remote network display. Connect to a local cold water earth or via an additional conductor connected to TB3-7
of the ILI-MB-E3 or ILI95-MB-E3 or Terminal TB4-4 of an INI-7100.
NOTE 3: Use TB3 (differential ARCNET) to connect an NGA to the RPT-E3.
NOTE 4: When J10 is used to connect the RPT-E3 to the ILI-E3 or ILI95-E3 Series, do not use TB4.
NOTE 5: U4, U5, U6 and U7 are omitted on the RPT-E3-UTP.
U5, U7, U4 & U6 - RPT-E3 FO Network Connections using standard ST connector fiber-optic cable, multi-
node, up to 200 µ (optimized for 62.5/125 u). Signal loss up to 8 dB maximum between the following nodes:
– RPT-E3 U6 (TX1) to: INI-7100 J7 (RX2) INI-VG J8 (RX2) or another RPT-E3 U5 (RX2)
– RPT-E3 U4 (RX1) to: INI-7100 J6 (TX2) INI-VG J6 (RX2) or another RPT-E3 U7 (TX2)
– RPT-E3 U7 (TX2) to: INI-7100 J4 (RX1) INI-VG J5 (RX1) or another RPT-E3 U4 (RX1)
– RPT-E3 U5 (RX2) to: INI-7100 J1 (TX1) INI-VG J2 (TX1) or another RPT-E3 U6 (TX1)
Network Connections using fiber-optic cable (available on RPT-E3 FO only). The RPT-E3 FO can support both
unshielded, twisted pair and fiber-optic network connections.
Table 3.1 Repeater-E3 Wiring Connections (Continued)

4 RPT-E3 Installation Instructions — P/N 9000-0580:D 09/03/09


Transmit
Port 1 Port 2 Power
J4 J5 J6 J7 J8 J9
OPEN OPEN OPEN OPEN OPEN OPEN 12.5%
SHORT OPEN OPEN SHORT OPEN OPEN 25.0%
OPEN SHORT OPEN OPEN SHORT OPEN 37.5%
SHORT SHORT OPEN SHORT SHORT OPEN 50.0%
OPEN OPEN SHORT OPEN OPEN SHORT 67.5%
SHORT OPEN SHORT SHORT OPEN SHORT 75.0%
OPEN SHORT SHORT OPEN SHORT SHORT 87.5%
SHORT SHORT SHORT SHORT SHORT SHORT 100.0%
Table 3.2 Transmitter Output Power Jumper Settings

RPT-E3 Installation Instructions — P/N 9000-0580:D 09/03/09 5


Section 3: Wiring (Continued)
Figure 3.1 illustrates the wiring connections for the RPT-E3 sub-assembly.
CONNECT TO EARTH GROUND AND ENABLE
J10 CONNECT TO GROUND DETECTION WHEN REMOTELY
LOCAL ILI-MB-E3 OR ILI95-MB-E3 MOUNTED
J4 ARCNET CONNECTOR (NOTE: NOT APPLICABLE WHEN USING
(NOTE PIN 1 POSITION) FIBER-OPTIC CONNECTIONS)
ARCNET
LOCAL DIFFERENTIAL
15 1 J10 J3 TB2

TERM
16 2 COM B OUT TO NGA TB1-4

1 2 3 4
ARCNET
ARCNET LEAVE OPEN COM A OUT TO NGA TB1-3

J1
TB3
COM B IN
TB4 HARD-WIRED POWER COM A IN
1
CONNECTIONS NOT
GND(-) OUT TO NGA TB1-2

1 2 3 4
REQUIRED WHEN J10 USED
+24VDC OUT TO NGA TB1-1
TB4 GND(-) IN FROM TB3-7 ILI-MB-E3/
ILI95-MB-E3
1 +24VDC IN FROM TB3-6 ILI-MB-E3/
ILI95-MB-E3

1 2 3 4
ARCNET PORT 2B
D12 TB1 ARCNET PORT 2A
J2 SHORT TO
RX2 ENABLE ARCNET PORT 1B
D11 GROUND FAULT 1 ARCNET PORT 1A
RX1 DETECTION
J2 U5 FROM PREVIOUS NODE
D10 GFI (RX2) TX1 CONNECTOR
TX J7
D18 J8 U7 FROM PREVIOUS NODE
(TX2) RX1 CONNECTOR
PWR J9
See Table 3.1: RPT-E3 Wiring
Connections and Table 3.2: U4 TO NEXT NODE
Transmitter Output Settings (RX1) TX2 CONNECTOR
J4
J5 U6 TO NEXT NODE
(TX1) RX2 CONNECTOR
J6

LEDS
D12 ON = RECEIVING NETWORK TRANSMISSIONS INTO ARCNET PORT 2 OR U5
OFF OR BLINKING = NOT RECEIVING NETWORK TRANSMISSIONS INTO ARCNET PORT 2 OR U5
D11 ON = RECEIVING NETWORK TRANSMISSIONS INTO ARCNET PORT 1 OR U4
OFF OR BLINKING = NOT RECEIVING NETWORK TRANSMISSIONS INTO ARCNET PORT 1 OR U4
D10 ON = TRANSMITTING TO NETWORK
OFF = NOT TRANSMITTING TO NETWORK
D18 ON = POWERED
OFF = NOT POWERED

OPEN SHORTED
NOTE: 2-PIN SHUNT
PLACED OVER PINS

Figure 3.1 RPT-E3 Wiring Diagram

6 RPT-E3 Installation Instructions — P/N 9000-0580:D 09/03/09


Section 3: Wiring (Continued)
Table 3.3 lists the wiring requirements for the RPT-E3.
Circuit Type Circuit Function Wire Requirements Distance Typical Wire Type*
SLC (power-limited) Connects to intelligent Twisted-unshielded pair, 12 to 10,000 ft. (3,000 m) 12 AWG (3.1 mm2)
and addressable 18 AWG (3.1 to 0.78 mm2) 8,000 ft. (2,400 m) 14 AWG (2.00 mm2)
modules. 40 Ohms maximum per length 4,875 ft. (1,450 m)
of Style 6 & 7 loops. 16 AWG (1.30 mm2)
40 Ohms combined-branch 3,225 ft. (980 m) 18 AWG (0.78 mm2)
circuits maximum for Style 4
loop.
MC cable with 2 conductor
twisted.
Or Shielded wire, in conduit or 1,000 ft. (304.8 m) 12 to 18 AWG
outside of conduit or MC cable. (3.1 to 0.78 mm2)
MC cable with 3 conductor
twisted.
Note: Maximum total
capacitance of all SLC wiring
(both between conductors and
from any conductor to ground)
should not exceed 0.5
microfarads.
EIA-485 Connects to LCD-E3, Twisted-unshielded pair with a 3,000 ft. (.914 m) 16 AWG (1.30 mm2)
(power-limited) ASM-16 and ANU-48 characteristic impedance of (maximum)
modules. 120 Ohms. 18 AWG
(0.78 mm2) minimum.
EIA-232 Connects to Printers, Twisted-unshielded pair. 50/15.24 16 AWG (1.30 mm2)
(power-limited) CRT, or PC. 18 AWG (0.78 mm2) minimum (without modem)
NAC Notification E3 (power-limited) 12-18 AWG (3.1 to 0.78 mm2) To meet 1.2 V drop, 12 to 18 AWG
Appliance Circuit At alarm current level, no more or sized to provide (3.1 to 0.78 mm2)
than a 1.2 V drop at the end of the minimum rated
the circuit, or sized to provide operating voltage of
the minimum rated operating the appliances
voltage of the appliances used. used.
24 VDC Power To Transmitter 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 volt 12 to 18 AWG
Runs Annunciator Size wire so that no more than drop (3.1 to 0.78 mm2)
(power-limited) 1.2 V drop across wire run from
supply source to end of any
branch.
CHG-120 External battery 12 AWG (3.1 mm2) in conduit 20/6.1 (max) 12 AWG (3.1 mm2)
charger
ARCNET Provides interface Twisted-unshielded pair low 3,000 ft. (.914 m) 18 AWG (3.1 mm2)
(power-limited) between network capacitance 18 AWG
nodes.
ARCNET should be
installed in a separate
conduit.
NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL 1459.

Table 3.3 Wiring Requirements

RPT-E3 Installation Instructions — P/N 9000-0580:D 09/03/09 7


Section 4: Specifications
The following list the electrical specifications for the RPT-E3 sub-assembly.
Operating Voltage: 24 VDC FWR (from PM-9/PM-9G power supply)
Operating Current: 0.013 amp
Operating Temperature: 32° to 120° F (0° to 49°C)
Relative Humidity: 0° to 93%, non-condensing at 90° F (32°C)
Supervised
Power-limited

8 RPT-E3 Installation Instructions — P/N 9000-0580:D 09/03/09


ASM-16
Annunciator Switch Assembly
Installation Instructions
12 Clintonville Road Northford, CT 06472-1610 USA PN 9000-0550:F 09/03/09 ECN 08-924
203-484-7161 • FAX 203-484-7118 • www.gamewell-fci.com

! CAUTION: STATIC SENSITIVE EQUIPMENT


THIS EQUIPMENT IS SENSITIVE TO STATIC ELECTRICITY. IT MAY BE DAMAGED IF NOT PROPERLY
HANDLED. TRANSPORT AND STORE THIS UNIT IN A STATIC-SHIELDING BAG.
FAILURE TO OBSERVE THIS REQUIREMENT COULD CAUSE LATENT DAMAGE TO THE EQUIPMENT
WHICH MIGHT NOT MANIFEST ITSELF UNTIL AFTER THE EQUIPMENT IS PLACED IN SERVICE.

! CAUTION: DISCONNECT ALL POWER


REMOVE ALL SOURCES OF POWER BEFORE SERVICING, REMOVING OR INSTALLING ANY UNITS.

Section 1: Description
The ASM-16 sub-assembly is a configurable switch input sub-assembly that includes sixteen (16), switches and forty-
eight (48), status LEDs. This sub-assembly may be remotely located via the RS-485 serial interface. Each switch address
is fully software programmable to serve as:
• A System Control Switch, Reset, Silence, Alarm and Trouble Acknowledge, etc.
• A Voice Evacuation Speaker Circuit control switch
• An Auxiliary Control Circuit switch
• A status indicating LED, (red, green, and yellow)
• A status indicating LED, labeled to display, "Command Center in Control.”
Figure 1.2 Front View

Figure 1.2

Figure 1.2

Figure 1.2

Figure 1.2

Figure 1.2

Figure 1.2

Figure 1.2

Figure 1.2

Figure 1.2

Figure 1.2

Figure 1.1 Rear View Figure 1.2 Front View

E3 Series® is a registered trademark of Honeywell International Inc.


©2009 Copyright by Honeywell International, Inc. All rights reserved.
Section 2: Installation
1. Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that
could cause condensation. Equipment must be securely mounted on rigid, permanent walls.
2. Use the Hardware Kit provided with the unit.
For additional information on the ASM-16 installation, refer to the E3 Series® Expandable Emergency Evacuation
Installation/Operation Manual, P/N 9000-0574. For instructions on the connection to additional or remote enclosures,
refer to the E3 Series® Broadband Installation/Operation Manual, P/N 9000-0575.

NOTE: For a new installation, it is recommended that you work on a flat surface, while you remove the inner
door of the enclosure and install all the sub-assemblies and/or blank panels.

3. Remove the unit from its static-shield bag, observing proper static protection measures.
4. Visually inspect the unit for damage. If the switch identifying paper label is available at this time, install the label by
sliding the label down into the pocket that is located between the faceplate overlay and the steel backer plate. This
will prevent the need to remove the unit at later date.
5. Place the unit into position in the rear of the inner door, centered in the opening, and secure the unit with the nuts
provided.

NOTE 1: If other units are installed into the inner door at this time, do not tighten the nuts until the adjacent unit
or blank panel is in place. Use the nuts to connect and retain more than one unit.

NOTE 2: Use the wiring connections in Table 2.1 and refer to Notes A-F in Figure 2.1 for the installation of the
ribbon cable and hardwire locations for the following sub-assemblies:
• ASM-16 • LCD-E3
• ILI-E3 or ILI95 Series • Remote enclosure installation
• INI-VG Series

6. Install the short ribbon cables interconnecting the cables from board to board as shown in Figure 2.1.
7. Connect the long ribbon cables interconnecting the cables from row to row starting from the first row connecting to
the following sub-assemblies:
• INCC
• ILI-MB-E3
• ILI95-MB-E3

2 ASM-16 Installation Instructions — P/N 9000-0550:F 09/03/09


Section 2: Installation (Continued)
The ASM-16 wiring connections are shown in Table 2.1, Figure 2.1, and Figure 4.1.
ASM-16 or ANU-48 to ASM-16 or ANU-48 Wiring
Designation Description Comments
From ASM-16 or ANU-48 Ribbon Cable To ASM-16 or ANU-48
J1 Ribbon Cable Connect To:
J1 - LCD-E3
J1,J2 - ANU-48
J3 - INI-VGC, INI-VGX, INI-VGE
J1,J2,J3 - ASM-16
J2 Ribbon Cable Connect To:
J1 - LCD-E3
J1,J2 - ANU-48
J3 - INI-VGC, INI-VGX, INI-VGE
J1,J2,J3 - ASM-16
J3 Ribbon Cable Connect To:
J1 - LCD-E3
J1,J2 - ANU-48
J3 - INI-VGC, INI-VGX, INI-VGE
J1,J2,J3 - ASM-16
J4 Emulator Factory Use Only
J5 Factory Use Only
JMP1 Termination Install Jumper only if the last device is on RS-485 bus.
Note: See Note A in Figure 2.1 for the ribbon cable connection.
ASM-16 or ANU-48 to ASM-16 or ANU-48 Wiring
From ASM-16 or ANU-48 RS-485 COM A from previous device/to next device.
Connect To:
TB1-1 COMM A Single Discrete Wire TB3-1 ILI-MB-E3/ILI95-MB-E3
TB6-3 INI-VGC, INI-VGX, INI-VGE
TB1-3 DACT-E3
TB1-1 ASM-16, ANU-48
TB1-5 LCD-E3
TB1-1 LCD-7100
TB1-2 COMM B Single Discrete Wire RS-485 COM B from previous device/to next device.
Connect To:
TB3-2 ILI-MB-E3/ILI95-MB-E3
TB6-2 INI-VGC, INI-VGX, INI-VGE
TB1-4 DACT-E3
TB1-2 ASM-16, ANU-48
TB1-6 LCD-E3
TB1-2 LCD-7100
TB1-3 +24V Single Discrete Wire Connect To:
TB1-3 +24V
TB3-6 ILI-MB-E3/ILI95-MB-E3
TB6-1 INI-VGC, INI-VGX, INI-VGE
TB1-4 GND Single Discrete Wire Connect To:
Common
TB1-4 GND
TB3-5 or TB3-7 ILI-MB-E3/ILI95-MB-E3
TB6-4 INI-VGC, INI-VGX, INI-VGE
Note: See Note B in Figure 2.1 for the hardwire connection.
Table 2.1 ASM-16 Wiring Connections

ASM-16 Installation Instructions — P/N 9000-0550:F 09/03/09 3


INI-VGC, INI-VGX or INI-VGE Wiring
Designation Description Comments
From INI-VGC, INI-VGX or INI-VGE To ASM-16 or ANU-48
J3 RS-485 Local Ribbon Cable J1, J2 or J3
Note: See Note C in Figure 2.1 for the ribbon cable connection.
From INI-VGC, INI-VGX or INI-VGE To ASM-16 or ANU-48
ASM-16 or ANU-48 to ASM-16 or ANU-48 Wiring
Designation Description Comments
TB6 RS-485 Remote ASM-16 or ANU-48 TB-1
TB6-1+24V Single Discrete Wire TB1-3 + 24V
TB6-2 COMM B Single Discrete Wire TB1-2 COMM B
TB6-3 COMM A Single Discrete Wire TB1-1 COMM A
TB6-4 GND Single Discrete Wire TB1-4 GND
Note: See Note D in Figure 2.1 for the hardwire connection.
ILI-MB-E3/ILI95-MB-E3 Wiring
From ILI-MB-E3/ILI95-MB-E3 To ASM-16 or ANU-48
TB3-1 COMM A Single Discrete Wire TB1-1 COMM A
TB3-2 COMM B Single Discrete Wire TB1-2 COMM B
TB1-3 +24V Single Discrete Wire TB1-3 +24V
TB1-4 GND Single Discrete Wire TB1-4 GND
Note: See Note E in Figure 2.1 for the hardwire connection.
LCD-E3 Wiring
From LCD-E3 To ASM-16 or ANU-48
J1 Ribbon Cable J1, J2, or J3
Note1: See Note F in Figure 2.1 for the ribbon cable connection.
Note2:
JMP1 - Termination leave out.
JMP2 - Factory programming leave in.
JMP3 - Factory programming leave in.
JMP4 - External Buzzer Connector.
Table 2.1 ASM-16 Wiring Connections (Continued)

4 ASM-16 Installation Instructions — P/N 9000-0550:F 09/03/09


Section 2: Installation (Continued)
Figure 2.1 illustrates the ASM-16 wiring connections.
NOTE A:
ASM-16 or ANU-48 to ASM-16 or ANU-48 wiring
ASM-16/ANU-48 to ASM-16/ANU-48
RS-485 Connection

J3 A J3 J3

J1 J2 J1 J2 J1 J2
A A A A C NOTE C and F:
F From local INI-VG or LCD-E3 J1
SW 17 SW 17
(RS-485 Local)
JMP 1 JMP 1 JMP 1
NOTE A:
ASM-16 or ANU-48 to B NOTE B, D and E:
ASM-16 or ANU-48 wiring D HARDWARE RS-485 Port
ASM-16/ANU-48 to TB 1 TB 1 E TB 1

ASM-16/ANU-48 RS-485
REMOTE REMOTE REMOTE (to/from module in
connection Different INCC cabinet)
J3 J3 J3
From ILI-MB-E3 or IL95-MB-E3
A TB3-1, TB3-2, TB1-3 and TB1-4
J1 J2 J1 J2 J1 J2
A A A A RS-485 RIBBON CABLE
Connector (to/from module)
In same INCC Cabinet)
SW 17 SW 17 SW 17
JMP 1 JMP 1 JMP 1

B NOTE B:
TB 1 TB 1 TB 1 To next ASM-16 or ANU-48
REMOTE REMOTE REMOTE
TB1 remote in next INCC
cabinet

NOTE A:
ASM-16 or ANU-48 to
ASM-16 or ANU-48 wiring
ASM-16/ANU-48 to ASM-16/
ANU-48 RS-485 connection

Figure 2.1 ASM-16 Wiring Connections

ASM-16 Installation Instructions — P/N 9000-0550:F 09/03/09 5


Section3: Programming Address Switch Settings
Figure 3.1 illustrates the programming address switch settings for the ASM-16 sub-assembly. To set the addresses for
either the E3 Series Broadband or E3 Series Systems, see A or B.
A) E3 Series Broadband System:
1. Set the address for each ASM-16, starting with the address that is closest to the INCC sub-assembly.
Set this address to Number 1.
2. To sequentially number the remaining ASM-16 units up to the maximum of 16 units, set the switches as shown
in Figure 3.1. Do not duplicate an address.
B) E3 Series Expandable Emergency Evacuation System:
1. Up to sixteen (16), ASM-16 sub-assemblies can be installed. Set the first address to Number 32.
2. Remove the shorting jumper from all sub-assemblies (if installed) except for the last sub-assembly in the
series.
3. On the last sub-assembly in the series, install a shorting jumper on J1.

S e t th is s w itc h 6 U P w h e n c o n n e c te d
to th e IL I-M B -E 3 o r IL I9 5 -M B -E 3 .

S e t th is s w itc h 6 D O W N w h e n
c o n n e c te d to th e IN I-V G C .

Figure 3.1 ASM-16 Address Switch Settings

6 ASM-16 Installation Instructions — P/N 9000-0550:F 09/03/09


Section 4: Wiring
Figure 4.1 illustrates the field wiring connections for the ASM-16 sub-assembly.
J1, J2 AND J3 ARE RS-485 RIBBON CABLE
“IN” AND/OR “OUT” CONNECTIONS
TO NEXT/PREVIOUS MODULE
(NOTE POSITION PIN 1)

J32 10
J3 RS-232 PORT
1 9 CONNECTIONS
- ANU-48-C OR J2
- ASM-C SERIES
J1, J2, OR J3, AND
J1 - INI-VG-C J3
10
9

J1 RS-232 PORT
J2 RS-232 PORT
J2

10
9
CONNECTIONS
CONNECTORS
- ANU-48-C J1 OR J2
- ANU-48-C J1 OR J2
- ASM-C SERIES
- ASM-C SERIES
J1, J2, OR J3, AND
J1, J2 OR J3, AND
1
2

- INI-VG-C J3
- INI-VG-C J3

2
1
SW1
ON

1 2 3 4 5 6 7 8

FACTORY JMP1 TB1 RS-485 PORT


CONNECTS TO THE
USE ONLY JMP3 JMP2 INI-VG-C
J5
TB1 TO INI-VG-C
4
SYSTEM GND (-) 4 TO TB6-4
4 3 2 1

24 VDC (+) 3 TO TB6-1


RS-485 COM B 2 TO TB6-2
RS-485 COM A 1 TO TB6-3
1

REMOTE

JMP4

REAR SIDE VIEW JMP4


REMOVE SHUNT AND
PLACE SA-C CONNECTOR
FOR EXTERNAL SOUNDER
Figure 4.1 ASM-16 Rear Side Wiring Diagram

ASM-16 Installation Instructions — P/N 9000-0550:F 09/03/09 7


Section5: Circuit Wiring Requirements
Table 5.1 provides the circuit wiring requirements for the ASM-16 sub-assembly.

Distance
Circuit Type Circuit Function Wire Requirements (feet/meters) Typical Wire Type*
SLC Connects to Twisted-unshielded pair, 12 to 18 AWG 10,000 ft. (3,000 m) 12 AWG (3.1 mm2)
(power-limited) intelligent and (3.1 to 0.78 mm2) 40 Ohms maximum 8,000 ft. (2,400 m) 14 AWG (2.00 mm2)
addressable modules. per length of Style 6 & 7 loops.
4,875 ft. (1,450 m) 16 AWG (1.30 mm2)
40 Ohms combined-branch circuits
3,225 ft. (980 m) 18 AWG (0.78 mm2)
maximum for Style 4 loop.
MC cable with 2 conductor twisted.
Or Shielded wire, in conduit or outside of 1,000 ft. (304.8 m) 12 to 18 AWG
conduit or MC cable. (3.1 to 0.78 mm2)
MC cable with 3 conductor twisted.
Note: Maximum total capacitance of all
SLC wiring (both between conductors
and from any conductor to ground)
should not exceed 0.5 microfarads.
EIA-485 Connects to LCD-E3, Twisted-unshielded pair with a 3,000 ft (maximum) 16 AWG (1.30 mm2)
(power-limited) ASM-16 and ANU-48 characteristic impedance of 120
modules Ohms. 18 AWG (0.78 mm2) minimum.
EIA-232 Connects to Printers, Twisted-unshielded pair. 18 AWG 50/15.24 16 AWG (1.30 mm2)
(power-limited) CRT, E3or PC. 2
(0.78 mm ) minimum (without modem)
NAC E3 (power-limited) 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 V drop, or 12 to 18 AWG
Notification 2
At alarm current level, no more than a sized to provide the (3.1 to 0.78 mm )
Appliance 1.2 V drop at the end of the circuit, or minimum rated
Circuit sized to provide the minimum rated operating voltage of
operating voltage of the appliances the appliances used.
used.
24 VDC Power To Transmitter 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 volt drop 12 to 18 AWG
Runs Annunciator Size wire so that no more than 1.2 V (3.1 to 0.78 mm2)
(power-limited) drop across wire run from supply
source to end of any branch.
CHG-120 External battery 12 AWG (3.1 mm2) in conduit 20/6.1 (maximum) 12 AWG (3.1 mm2)
charger
ARCNET Provides interface Twisted-unshielded pair, low 3,000 ft. (.914 m) 18 AWG (3.1 mm2)
(power-limited) wiring capacitance 18 AWG
ARCNET should be
installed in a separate
conduit.
Note: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL 1459.
Table 5.1 ASM-16 Wiring Requirements

8 ASM-16 Installation Instructions — P/N 9000-0550:F 09/03/09


Section 6: Specifications:
The following are the electrical specifications for the ASM-16.
Operating Voltage: 24 VDC (from PM-9/PM-9G Power Supply)
Operating Current: 0.011 amp (with no LEDs lit)
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93%, non-condensing at 90° F (32° C)
Supervised
Power-limited

ASM-16 Installation Instructions — P/N 9000-0550:F 09/03/09 9


PM-9
Power Supply and Battery Charger
Installation Instructions
12 Clintonville Road Northford, CT 06472-1610 USA PN 9000-0548:E 09/03/09 ECN 08-924
203-484-7161 • FAX 203-484-7118 • www.gamewell-fci.com

! CAUTION: STATIC SENSITIVE EQUIPMENT


THIS EQUIPMENT IS SENSITIVE TO STATIC ELECTRICITY. IT MAY BE DAMAGED IF NOT PROPERLY
HANDLED. USE AN ESD (ELECTROSTATIC DISCHARGE). TRANSPORT THIS UNIT IN A STATIC-
SHIELDING BAG.
FAILURE TO OBSERVE THIS REQUIREMENT COULD CAUSE LATENT DAMAGE TO THE EQUIPMENT
WHICH MIGHT NOT MANIFEST ITSELF UNTIL AFTER THE EQUIPMENT IS PLACED IN SERVICE.

! CAUTION: DISCONNECT ALL POWER


REMOVE ALL SOURCES OF POWER BEFORE REMOVING OR INSTALLING ANY UNITS.

Section 1: Description
The PM-9 power supply supplies 24 VDC at 9 Amperes (max.) and is designed for use with the Gamewell-FCI distributed
audio networks. It can also be used to maintain and supervise batteries up to 55 A/H in size. The PM-9 can be
"hard-wired" or can communicate with the main panel via an RS-485 for status and diagnostics.

Figure 1.1 PM-9 Power Supply Board

E3 Series® is a registered trademark and CamWorks™ is a trademark of Honeywell International Inc.


©
2009Copyright by Honeywell International, Inc. All rights reserved.
Section 2: Installation
1. Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that
could cause condensation. Equipment must be securely mounted on rigid, permanent walls.
2. Use the Hardware Kit provided with the unit.
3. Remove the inner chassis from the enclosure and set aside.
4. Remove the PM-9 power supply sub-assembly from its static-shield bag, observing proper static protection measures.
5. Visually inspect the unit for damage.

NOTE: For Installation Instructions, refer to the E3 Series® Expandable Emergency Evacuation Installation/
Operating Manual, P/N 9000-0574.

Section 3: Wiring
1. Wire the AC power connections, but do not apply power until all wiring is completed and checked. Wiring is to be in
conformance with local and national codes.
2. Connect the wires for the batteries to the battery terminal block, but do not connect the battery at this time.
3. A) For use with the E3 Broadband INX:
1. Determine the number of AM-50-25VRMS amplifier modules that will be connected to the PM-9 and pre-wire a
pair of wires of adequate length, including the service loop, for each module as shown in Figure 3.1.

TB4
TO AM-50 #1 TB1-2 (RED)

24VOUT GND 24VOUT GND 24VOUT GND


TO AM-50 #3 TB1-2 (RED)

TO AM-50 #1 TB1-1 (BLACK)

TO AM-50 #3 TB1-1 (BLACK)

TO AM-50 #2 TB1-2 (RED)

TO AM-50 #4 TB1-2 (RED)


TO AM-50 #2 TB1-1 (BLACK)

TO AM-50 #4 TB1-1 (BLACK)

NOTE: Wire all connections


before applying the AC power
or connecting the Batteries.

Figure 3.1 Output to Terminal Wiring for INX Installation

2. Install the 10-conductor ribbon cable (supplied) from the INI-VGX into Connector J1.
3. If the INI-VGX-FO or INI-VGX-UTP and AM-50 modules have not been installed on the sub-chassis,
Gamewell-FCI recommends installing the INI-VGX-FO, INI-VGX-UTP and AM-50 modules before the sub-
chassis is re-mounted in the INX cabinet.

NOTE: To complete the wiring to the AM-50, INI-VGX-FO and INI-VGX-UTP modules, refer to the
AM-50 Installation Instructions (P/N 9000-0544) and INI-VG Series Installation Instructions
(P/N 9000-0549).

4. Re-install the sub-chassis.

2 PM-9 Installation Instructions — P/N 9000-0548:E 09/03/09


Section 3: Wiring (Continued)
3. B) For use with the ILI-MB-E3 or ILI95-MB-E3:
1. Connect from the PM-9, TB4-1 to the ILI-MB-E3 or ILI95-MB-E3, Terminals: TB1-1 or TB-1-3. Connect from
the PM-9, TB4-2 to the ILI-MB-E3 or ILI95-MB-E3, Terminals: TB1-2 or TB1-4.
TB 4
ILI-M B -E 3 or IL I95-M B -E 3 TB 1-1

24VOUT
RED

ILI-M B -E 3 or IL I95-M B -E 3 TB 1-2

GND
B LK

Figure 3.2 Output Terminal Wiring for ILI-MB-E3 or ILI95-MB-E3 Installation

T1

12
1
TB3
BATT+

PS3
+
1

+ +
1 1
PS2
+
PS1
BATT-

TB4
1

+
24 VOUT GND 24 VOUT GND 24 VOUT GND

HOT/BLK GND/GRN NEUT/WHT


GNDSIG
+

TB1
1

1 1

1
+

+ 1

J1
JMP1

1
6.25A 250V
SLO BLO
F1
W1

Figure 3.3 PM-9 Board Sub-Assembly


Table 3.1 lists the PM-9 terminals, jumpers, and LEDs.
Designation Description Comments
TB1-1 HOT/BLK Connect to hot, 120VAC, 60Hz - Non Power-limited
TB1-2 GND/GRN Connect to ground and isolated earth ground - Non Power-limited
TB1-3 NEUT/WHT Connect to neutral 120VAC, 60Hz
TB3-1 BATT+ Battery positive input - Non Power-limited
TB3-2 BATT - Battery negative input - Non Power-limited
TB4-1 24VOUT +24 VDC FWR Output to AM-50 amplifiers or ILI95-E3/ILI-E3 Series, TB1-2:
used to power two (2), AM-50 amplifiers or the ILI95-E3/ILI-E3 Series
TB4-2 GND GND (-) Output to AM-50 amplifiers or ILI95-E3/ILI-E3 Series, TB1-1: used to
power two (2), AM-50 amplifiers or the ILI95-E3/ILI-E3 Series
TB4-3 24VOUT +24 VDC FWR Output to AM-50 amplifiers or ILI95-E3/ILI-E3 Series, TB1-2:
used to power 2nd pair of AM-50 amplifiers, ILI95-E3/ILI-E3 Series, and INI-VG
TB4-4 GND GND (-) Output to AM-50 amplifiers or ILI95-E3/ILI-E3 Series: TB1-1: to
second pair of AM-50 amplifiers, ILI95-E3/ILI-E3 Series, INI-VGC
TB4-5 24VOUT +24 VDC FWR Output to other sub-assemblies: INI-VG or ILI95-E3/ILI-E3
Series
TB4-6 GND GND (-) Output to INI-VG or ILI95-E3/ILI-E3 Series
JMP1 IN for GND Fault Detection (See Note 1)
J1 10-PIN Ribbon Cable Connect to the ILI95-MB-E3 or ILI-MB-E3 Connector J1,
or INI-VG Connector J4
JMP2 Factory Use Only
LED 2 Green Lights to indicate AC power
LED 3 Yellow Lights to indicate no or low battery fault
LED 4 Yellow Lights to indicate ground fault
NOTE: AC “Brown Out” condition indicated by:
LED 2 (grn) OFF
LED 3 (yel) LIT
LED 4 (yel) LIT
NOTE 1: Must be OUT if this sub-assembly is monitoring the ILI95-MB-E3/ILI-MB-E3 Series.
Table 3.1 PM-9 Terminals, Jumpers and LEDs

PM-9 Installation Instructions — P/N 9000-0548:E 09/03/09 3


Section 3: Wiring (Continued)
Table 3.2 lists the details for the Ground Fault supervision and settings.
Designation Description Comments
Ground Fault Supervision Jumper Settings CamWorks™ Settings
ILI-MB-E3, ILI95-MB-E3 W9 shorted on ILI, ILI Supervision of PM-9 enabled.
JMP1 OPEN on PM-9
INI-VGX JMP1 shorted on PM-9, VGX Supervision of PM-9 enabled
W9 OPEN on ILI
Table 3.2 Ground Fault Supervision

4 PM-9 Installation Instructions — P/N 9000-0548:E 09/03/09


55 AH BATTERIES
MAXIMUM
BATT+

TB3
(NON-PWR LIMITED) L1

Q1
T1

12
BACKUP

1
BATTERY (+) POS +C11 D6
BACKUP
BATTERY (-) NEG
BATT-
+ C12 See
Note 1:
Section 3: Wiring (Continued)

6
7

TB4
TB1

PM-9 Installation Instructions — P/N 9000-0548:E 09/03/09


EXTERNAL POWER NOTE:
CB1
OUTPUT 24VDC (+) CONNECTION MUST BE TO A 120VAC NEUTRAL
D2 CB DEDICATED BRANCH CIRCUIT (WHITE)
EXTERNAL POWER AC POWER GREEN LED
Figure 3.4 illustrates the wiring connections for the PM-9.

OUTPUT GND (-) BATTERY FAULT D3 YELLOW LED GROUND (GREEN) AND MECHANICALLY PROTECTED.
EXTERNAL POWER ALL MEANS OF DISCONNECTING
GROUND FAULT YELLOW LED
OUTPUT 24VDC (+) D4 120VAC HOT (BLACK) THIS CIRCUIT MUST BE CLEARLY
NEUT/ WHT GND/ GRN HOT/ BLK
EXTERNAL POWER MARKED “FIRE ALARM CONTROL”
OUTPUT GND (-) NOTE:

SLO BLOW
F1 6.25A 256V
See Note 1:
AND BE ACCESSIBLE TO
9

EXTERNAL POWER AC BROWNOUT D2 LED OFF 10


TO ILI-MB-E3/ILI95-MB-E3 AUTHORIZED PERSONNEL ONLY
OUTPUT 24VDC (+) BATTERY FAULT D3 LED OFF
J1 CONNECTOR (NON-PWR LIMITED).
J1

EXTERNAL POWER GROUND FAULT D4 LED OFF


OR INI-VG
OUTPUT GND (-) JMP1
2
1

J4 CONNECTOR

24VOUT GND 24VOUT GND 24VOUT GND


L2

Figure 3.4 PM-9 Wiring Connections


NOTE: DISABLE THE GROUND
24VDC @ 9 AMPS PIN1
FAULT DETECTION CKT WHEN
FROM ANY EXT.
THE PM-9 IS LOCATED IN THE
PWR OUTPUT NOTE1:
GROUND FAULT GROUND FAULT SAME CABINET AS THE
9 AMPS TOTAL EITHER CB1 OR F1 ARE
ENABLED DISABLED ILI-MB-E3 OR ILI95-MB-E3
FROM PM-9 OPTIONAL FORMS OF AC
(MIDDLE TO TOP PIN) (MIDDLE TO BOTTOM PIN)
(NON-PWR-LIMITED) POWER PROTECTION.

5
Section 4:Specifications
The following are the electrical specifications for the PM-9.
Input Voltage: 120 VAC, 60 Hz
Input Current: 4.6 amps max. @ 120 VAC 60 Hz
Output Voltage: 24 VDC FWR
Output Current: 9 amperes Alarm max. continuous
Output Current: 5 amperes Standby max. continuous (See Note 1)
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93%, non-condensing at 90° F (32° C)
Supervised
Non Power-Limited
NOTE 1: Continuous standby loads in excess of .560 Amps up to 5 Amps may require Generator Backup or load
shedding during an AC power failure. See Section 3.14 Standby Battery Calculations in the E3 Series Installation/
Operation Manual P/N 9000-0574.

6 PM-9 Installation Instructions — P/N 9000-0548:E 09/03/09


E3 Series® Cabinet Trim Rings
Installation Instructions

12 Clintonville Road Northford, CT 06472-1610 USA PN 9001-0058:A 09/17/08 ECN 08-651


203-484-7161 • FAX 203-484-7118 • www.gamewell-fci.com

! CAUTION: This equipment is sensitive to static electricity. It may be damaged if not properly handled. Use a
ground wrist strap and anti-static mat, when handling this equipment. Transport this unit in a static-shielding
bag.
Failure to observe this requirement could cause latent damage to the equipment which might not
manifest itself until after the equipment is placed in service.
Remove all source of power before removing or installing any units.

Section 1: Description
The E3 Series® Cabinet Trim Rings are metal frames or brackets used for supporting the E3 Series Cabinet backbox
installations. The E3 Trim Rings can be used as an optional accessory when installing the following E3 Series Cabinets:
• E3 Cabinet A or AA • E3 Cabinet A2 • E3 Cabinet C
• E3 Cabinet A1 • E3 Cabinet B • E3 Cabinet D
The E3 Series Trim Rings package includes the following interchangeable components.
• E3 Trim Ring Top/Bottom • E3 Trim Ring Left/Right

NOTE: Use the Trim Ring Hardware Kit provided. The top/bottom and left/right trim rings are interchangeable.

TOP/BOTTOM TRIM RING FRONT


(TOP) T R IM R IN G

KNOCKOUTS

LEFT/RIGHT LEFT/RIGHT
TRIM RING TRIM RING KNOCKOUTS
(LEFT) (RIGHT)

R IG H T S ID E
TOP/BOTTOM TRIM RING BOTTOM T R IM R IN G
(BOTTOM) T R IM R IN G

Figure 1.1 E3 Cabinet Trim Ring (Front View) Figure 1.2 E3 Cabinet Trim Ring (Side View)

E3 Series® is a registered trademark of Honeywell International Inc.


Section 2: Installation
Sections 2.1 thru 2.8 provide the installation instructions for the E3 Series Cabinet Trim Rings. For additional information
on the E3 Cabinet Trim Rings installation, refer to the E3 Series® Installation/Operating Manual, P/N 9000-0574.
2.1: E3 Cabinet A and AA, Trim Rings Installation
1. Insert the E3 Cabinet A or AA, top and bottom trim rings over the top and bottom three-hole mounting patterns.
2. Secure with six (6), #6 nuts in the three-hole mounting patterns. (See Figure 2.1.1, Locations 1 thru 6).
3. Insert the E3 Cabinet A or AA, left and right trim rings in the two-hole mounting patterns on the left and right sides.
4. Secure with four (4), #6 nuts in the two-hole mounting patterns. (See Figure 2.1.1, Locations 7 thru 10).

E3 Cabinet A or
AA, Trim Top
7

1
E3 Cabinet A
or AA, Trim Left
2
8 #6
KE H E X 3
( 10 P S N ,
P L UT
A C S, 9
ES
4 )

5
E3 Cabinet A
6 or AA, Trim Righ
10

E3 Cabinet A
or AA, Trim Bottom

Figure 2.1.1 E3 Cabinet A and AA, Trim Rings Installation

2.2: E3 Cabinet A and AA, Flush-Mounting Installation


1. Prepare a hole in the wall according to the dimensions shown in Figure 2.2.1.
2. To mount the backbox, secure with four (4), #10 screws. (See Figure 2.2.1, Locations 1 thru 4).

NOTE: Use existing knockouts provided. Existing knockouts may be enlarged.

E3 CABINET A and AA
21 3/4”
55.25 cm

1 2
12 1/2” 10 1/8"
32 cm 25.86 cm

3 4

(SEE NOTE)
19 3/8"
49.22 cm
NOTE:
E3 CABINET A DEPTH= 1 11/16" (2.92 cm)
E3 CABINET AA DEPTH= 3 11/64" (7.91 cm)

Figure 2.2.1 E3 Cabinet A and AA, Flush-Mounting Installation

2 E3 Series Cabinet Trim Rings Installation Instructions — P/N 9001-0058:A 09/17/08


2.3: E3 Cabinet A1 and A2, Trim Rings Installation
1. Insert the E3 Cabinet A1 or A2, top and bottom trim rings over the top and bottom two-hole mounting patterns.
2. Secure with four (4), #6 nuts in the two-hole mounting patterns.(See Figure 2.3.1 or Figure 2.3.2, Locations 1 thru 4).
3. Insert the E3 Cabinet A1 or A2, left and right trim rings in the two-hole mounting patterns on the left and right sides.
4. Secure with four (4), #6 nuts in the two-hole mounting patterns. (See Figure 2.3.1 or Figure 2.3.2, Locations 5 thru 8).
E3 Cabinet A1,
Top Trim Ring

5 1
E3 Cabinet A1, 2
Left Trim Ring

7
6

NOTE:
E3 Cabinet A1,
#6 HEX,
3 Right Trim Ring
KEPS NUTS, 8
(8 PLACES) 4

E3 Cabinet A1,
Bottom Trim Ring

Figure 2.3.1 E3 Cabinet A1, Trim Rings Installation

E3 Cabinet A2,
Top Trim Ring
5 1
E3 Cabinet A2,
Left Trim Ring 2

6
7
NOTE:
#6 HEX,
3
KEPS NUTS,
E3 Cabinet A2,
(8 PLACES)
8 Right Trim Ring
4
E3 Cabinet A2,
Bottom Trim Ring

Figure 2.3.2 E3 Cabinet A2, Trim Rings Installation

E3 Series Cabinet Trim Rings Installation Instructions — P/N 9001-0058:A 09/17/08 3


2.4: E3 Cabinet A1 and A2, Flush-Mounting Installation
1. Prepare a hole in the wall according to the dimensions shown in Figure 2.4.1 and Figure 2.4.2.
2. To mount the backbox, secure with four (4), #10 screws. (See Figure 2.4.1 and Figure 2.4.2, Locations 1 thru 4).

NOTE: Use existing knockouts provided. Existing knockouts may be enlarged.

E3 C A BIN ET A 1
11 1/4”
28.60 cm

1 2

12 1/2” 10 1/8"
31.75 cm 25.86 cm

3 4

1 3/4”
4.44 cm
1 11/16”
2.82 cm
8 7/8"
22.30 cm
Figure 2.4.1 E3 Cabinet A1, Flush-Mounting Installation

E3 CABINET A2
15.75"
40.00 cm

1 2

12.5"
31.75 cm 10 1/8"
25.86 cm

3 4

1 11/16"
2.82 cm
1 11/16"
2.82 cm
13.3/8"
33.99 cm
Figure 2.4.2 E3 Cabinet A2, Flush-Mounting Installation

4 E3 Series Cabinet Trim Rings Installation Instructions — P/N 9001-0058:A 09/17/08


2.5: E3 Cabinet B and C, Trim Rings Installation
1. Insert the E3 Cabinet B or C, top and bottom trim rings over the top and bottom three-hole mounting patterns.
2. Secure with six (6), #6 nuts in the top and bottom three-hole mounting patterns. (See Figure 2.5.1 or Figure 2.5.2,
Locations 1 thru 6).
3. Insert the E3 Cabinet B, left and right trim rings in the three-hole mounting patterns on the left and right sides.
4. Secure with six (6), #6 nuts in the left and right three-hole mounting patterns. (See Figure 2.5.1, Locations 7 thru 12).
5. Insert the E3 Cabinet C, left and right trim rings in the four-hole mounting patterns on the left and right sides.
6. Secure with six (6), #6 nuts in the left and right four-hole mounting patterns. (See Figure 2.5.2, Locations 7 thru 14).

E3 Cabinet B,
7 Top Trim Ring
1

E3 Cabinet B, 3
8
Left Trim Ring
10

11
NOTES:
#6 HEX, 4 E3 Cabinet B,
KEPS NUTS Right Trim Ring
5
(12 PLACES)
6 12
E3 Cabinet B,
Bottom Trim Ring

Figure 2.5.1 E3 Cabinet B, Trim Rings Installation

E 3 C a b in e t C ,
7 T o p T rim R in g
1

3
8
10
E 3 C a b in e t C ,
L e ft T rim R in g

9
12

10 E 3 C a b in e t C ,
13 R ig h t T rim R in g
NO TE:
#6 HEX, 4
KEPS NUTS, 5
(1 4 P L A C E S )
6 14
E 3 C a b in e t C ,
B o tto m T rim R in g

Figure 2.5.2 E3 Cabinet C, Trim Rings Installation

E3 Series Cabinet Trim Rings Installation Instructions — P/N 9001-0058:A 09/17/08 5


2.6: E3 Cabinet B and C, Flush-Mounting Installation
1. Prepare a hole in the wall according to the dimensions shown in Figure 2.6.1 or Figure 2.6.2.
2. To mount the backbox, secure with four (4), #10 screws. (See Figure 2.6.1 or Figure 2.6.2, Locations 1 thru 4).

NOTE: Use existing knockouts provided. Existing knockouts may be enlarged.

3.1/8"
E 3 C A B IN E T B
21.7/8" 8.1 cm
55.32 cm

1 2

21.7/8" 19 1/2”
55.32 cm 49.52 cm

3 4

3 1/8"
8.1 cm
19 1/2”
49.52 cm
Figure 2.6.1 E3 Cabinet B, Flush-Mounting Installation

E 3 C A B IN ET C
21 7/8" 3 1/8"
55.32 cm 8.07 cm

1 2

32 1/2" 30 1/8"
82.55 cm 76.66 cm

3 4

3 1/8"
8.07 cm
19 1/2"
49.52 cm
Figure 2.6.2 E3 Cabinet C, Flush-Mounting Installation

6 E3 Series Cabinet Trim Rings Installation Instructions — P/N 9001-0058:A 09/17/08


2.7 E3 Cabinet D, Trim Rings Installation
1. Insert the E3 Cabinet D, top and bottom trim rings over the top and bottom three-hole mounting patterns.
2. Secure with six (6), #6 nuts in the three-hole mounting patterns. (See Figure 2.7.1, Locations 1 thru 6).
3. Insert the E3 Cabinet D, left and right trim rings in the five-hole mounting patterns on the left and right sides.
Secure with ten (10), #6 nuts in the five-hole mounting patterns on the left and right sides.
(See Figure 2.7.1, Locations 7 thru 16).

E3 Cabinet D,
Top Trim Ring
71
2
3
8

12
E3 Cabinet D,
9
Left Trim Ring 13

10
14
E3 Cabinet D,
Right Trim Ring
11
15
NOTE: 4
#6 HEX,
KEPS NUTS 5
(16 PLACES)
16
6
E3 Cabinet D,
Bottom Trim Ring
Figure 2.7.1 E3 Cabinet D, Trim Rings Installation

E3 Series Cabinet Trim Rings Installation Instructions — P/N 9001-0058:A 09/17/08 7


2.8 E3 Cabinet D, Flush-Mounting Installation
1. Prepare a hole in the wall according to the dimensions shown in Figure 2.8.1.
2. To mount the backbox, secure with four (4), #10 screws. (See Figure 2.8.1, Locations 1 thru 4).

NOTE: Use existing knockouts provided. Existing knockouts may be enlarged.

E3 CABINET D
21 7/8" 3 1/8"
55.32 cm 8.072 cm

1 2

43 ½” 41 1/8"
110.49 cm 105.41 cm

3 4

3 1/8"
8.072 cm
19 1/2"
49.52 cm

Figure 2.8.1 E3 Cabinet D, Flush-Mounting Installation

8 E3 Series Cabinet Trim Rings Installation Instructions — P/N 9001-0058:A 09/17/08

S-ar putea să vă placă și