Documente Academic
Documente Profesional
Documente Cultură
Gamewell-FCI
Control Panels
SLC Wiring Guide
Document 9021-60542
01/15/10 Rev:
P/N 9021-60542:A
A
ECN 09-403
Important Limitations Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
While a fire alarm system may lower insurance rates, matches (especially in bedrooms), smoking in bed, and
it is not a substitute for fire insurance! violent explosions (caused by escaping gas, improper
An automatic fire alarm system- typically made up of storage of flammable materials, etc.).
smoke detectors, heat detectors, manual pull stations, Heat detectors do not sense particles of combustion and
audible warning devices, and a fire alarm control panel with alarm only when heat on their sensors increases at a
remote notification capability - can provide early warning of predetermined rate or reaches a predetermined level.
a developing fire. Such a system, however, does not Rate-of-rise heat detectors may be subject to reduced
assure protection against property damage or loss of life sensitivity over time. For this reason, the rate-of-rise
resulting from a fire. feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Heat detectors
The Manufacturer recommends that smoke and/or heat
are designed to protect property, not life.
detectors be located throughout a protected premise
following the recommendations of the current edition of the IMPORTANT! Smoke detectors must be installed in the
National Fire Protection Association, Standard 72 (NFPA same room as the control panel and in rooms used by the
72), manufacturer’s recommendations, State and local system for the connection of alarm transmission wiring,
codes, and the recommendations contained in the Guide communications, signaling, and/or power. If detectors are
for Proper Use of System Smoke Detectors, which are not so located, a developing fire may damage the alarm
made available at no charge to all installing dealers. These system, crippling its ability to report a fire.
documents can be found at http://www.systemsensor.co/
Audible warning devices such as bells may not alert
html/applict.html. A study by the Federal Emergency people if these devices are located on the other side of
Management Agency (an agency of the United States closed or partly open doors or are located on another floor
government) indicated that smoke detectors may not go off of a building. Any warning device may fail to alert people
in as many as 35% of all fires. While fire alarm systems are with a disability or those who have recently consumed
designed to provide early warning against fire, they do not drugs, alcohol or medication. Please note that:
guarantee warning or protection against fire. A fire alarm • Strobes can, under certain circumstances, cause
system may not provide timely or adequate warning, or seizures in people with conditions such as epilepsy.
simply may not function, for a variety of reasons. • Studies have shown that certain people, even when
Smoke Detectors may not sense fire where smoke cannot they hear a fire alarm signal, do not respond or
reach the detectors such as in chimneys, in or behind comprehend the meaning of the signal. It is the
walls, on roofs, or on the other side of closed doors. Smoke property owner’s responsibility to conduct fire drills
detectors also may not sense a fire on another level or floor and other training exercise to make people aware of
of a building. A second-floor detector, for example, may not fire alarm signals and instruct them on the proper
sense a first-floor or basement fire. reaction to alarm signals.
• In rare instances, the sounding of a warning device
Particles of combustion or “smoke” from a developing
fire may not reach the sensing chambers of smoke can cause temporary or permanent hearing loss.
detectors because: A fire alarm system will not operate without any electrical
• Barriers such as closed or partially closed doors, power. If AC power fails the system will operate from
walls, or chimneys may inhibit particle or smoke flow. standby batteries only for a specified time and only if the
• Smoke particles may become “cold,” stratify, and not batteries have been properly maintained and replaced
reach the ceiling or upper walls where detectors are regularly.
located.
Equipment used in the system may not be technically
• Smoke particles may be blown away from detectors by
compatible with the control panel. It is essential to use only
air outlets.
equipment listed for service with your control panel.
• Smoke particles may be drawn into air returns before
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to premise to a central monitoring station may be out of
alarm smoke detectors. Smoke detectors are designed to service or temporarily disabled. For added protection
alarm at various levels of smoke density. If such density against telephone line failure, backup radio transmission
levels are not created by a developing fire at the location of systems are recommended.
detectors, the detectors will not go into alarm. The most common cause of fire alarm malfunction is
Smoke detectors, even when working properly, have inadequate maintenance. To keep the entire fire alarm
sensing limitations. Detectors that have photoelectronic system in excellent working order, ongoing maintenance is
sensing chambers tend to detect smoldering fires better required per the manufacturer’s recommendations, and UL
than flaming fires, which have little visible smoke. and NFPA standards. At a minimum, the requirements of
Detectors that have ionizing-type sensing chambers tend NFPA 72 shall be followed. Environments with large
to detect fast-flaming fires better than smoldering fires. amounts of dust, dirt or high air velocity require more
Because fires develop in different ways and are often frequent maintenance. A maintenance agreement should
unpredictable in their growth, neither type of detector is be arranged through the local manufacturer’s
necessarily best and a given type of detector may not representative. Maintenance should be scheduled monthly.
provide adequate warning of a fire.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and Canadian Requirements
used in accordance with the instruction manual may This digital apparatus does not exceed the Class A limits
cause interference to radio communications. It has been for radiation noise emissions from digital apparatus set
tested and found to comply with the limits for Class A out in the Radio Interference Regulations of the
computing devices pursuant to Subpart B of Part 15 of Canadian Department of Communications.
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are Le present appareil numerique n’emet pas de bruits
operating in a commercial environment. Operation of this radioelectriques depassant les limites applicables aux
equipment in a residential area is likely to cause appareils numeriques de la Classe A prescrites dan le
interference, in which case the user will be required to Reglement sur le brouillage radioelectrique edicte par le
correct the interference at his or her own expense. ministere des Communications du Canada.
Gamewell-FCI® and SmartScan® are registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a
trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered
trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep out documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services
Table of Contents
Section 1: Introduction............................................................................................................. 7
1.1: About This Manual ........................................................................................................................................7
1.1.1: CLIP and Velociti® Modes..................................................................................................................7
1.2: UL 864 Compliance.......................................................................................................................................8
1.2.1: Products Subject to AHJ Approval......................................................................................................8
1.3: Reference Documentation ............................................................................................................................9
1.4: SLC Overview .............................................................................................................................................10
1.5: Polling Protocols .........................................................................................................................................10
1.6: Devices .......................................................................................................................................................11
1.6.1: Monitor/Zone Interface Modules.......................................................................................................11
1.6.2: Control Modules ................................................................................................................................11
1.6.3: Isolator Modules ................................................................................................................................11
1.6.4: Relay Modules...................................................................................................................................11
1.6.5: Plug-in Detector Bases ......................................................................................................................11
1.6.6: Intelligent Detectors .........................................................................................................................12
1.6.7: Addressable Manual Pull Stations.....................................................................................................12
1.7: SLC Capacity...............................................................................................................................................12
1.8: SLC Performance.........................................................................................................................................13
Section 2: Wiring Requirements............................................................................................ 14
2.1: Recommended SLC Wiring.........................................................................................................................14
2.2: Two-Wire SLC - Style 4 (Class B) ..............................................................................................................15
2.2.1: Measuring SLC Resistance................................................................................................................15
2.2.2: Measuring Total Wire Length ...........................................................................................................15
2.3: Four-Wire SLC Style 6 & 7 (Class A).........................................................................................................16
2.3.1: Measuring SLC Resistance................................................................................................................16
2.3.2: Measuring Total Wire Length ...........................................................................................................16
2.4: Terminal Blocks...........................................................................................................................................16
Section 3: Shielded Wire Termination .................................................................................. 17
3.1: Overview......................................................................................................................................................17
3.2: Floating Shield ............................................................................................................................................17
Section 4: SLC Circuits without Isolators ............................................................................ 18
4.1: Overview......................................................................................................................................................18
4.2: NFPA Style 4 SLC .......................................................................................................................................18
4.3: NFPA Style 6 SLC .......................................................................................................................................19
Section 5: SLC Circuits with Isolators .................................................................................. 20
5.1: Overview......................................................................................................................................................20
5.2: Fault Isolator Module ..................................................................................................................................20
5.3: Isolator Detector Bases ................................................................................................................................21
5.3.1: How an Isolator Base Works .............................................................................................................21
5.4: NFPA Style 4 SLC Using Isolator Modules ................................................................................................22
5.5: NFPA Style 6 SLC Using Isolator Modules ................................................................................................23
5.6: NFPA Style 7 SLC Using an Isolating Device ............................................................................................24
Section 6: Monitor Modules ................................................................................................... 25
6.1: Description...................................................................................................................................................25
6.1.1: Addressable Monitor Module............................................................................................................25
6.1.2: Zone Interface Module ......................................................................................................................25
6.1.3: Dual Monitor Module........................................................................................................................26
6.1.4: Miniature Monitor Module................................................................................................................26
6.2: Setting an SLC Address for a Module .........................................................................................................27
6.3: NFPA Style B IDC Using Monitor Modules ...............................................................................................28
6.4: NFPA Style D IDC Using Monitor Modules ...............................................................................................29
NOTE: The re-designed modules are capable of operating in both the CLIP communication
protocol and in the Velociti® protocol.
Appendix C contains terminal conversion charts that identify the old CLIP and new Velociti
formats. The model name does not indicate the format. In Appendix C, the following module
naming conventions are used to identify the two types of rotary switches.
• “h-type” rotary switches (uses the new Velociti format, which has horizontal rotary dials).
• “v-type” rotary switches (uses the old CLIP format, which has vertical rotary dials).
Figure 1.1.1.1 illustrates the modules’ formats.
CLIP Format
Vertical rotary dials.
Old-format .
Velociti Format
Horizontal rotary
dials. New-format .
Document
Model Description
Part Number
9000-0555 MMO-6RF Multi-Module 6 Zone Interface Module
9000-0553 MMO-6SF Multi-Module Output, Relay
9000-0518 MS-7AF Addressable Double Action Station
(AMM-2SF Mini Mod Incl)
I56-2763-00 (SS) MS-7ASF Addressable Single Action Station
(AMM-2SF Mini-Mod Incl)
Other Sensors, Bases and Modules
I56-0725-012R (SS) B224BI Base with Auxiliary Relay, Isolator for Style 7
Operation
I56-2815-000R (SS) B224RB Base with Auxiliary Relay
I56-3392-003R B200SR Intelligent Sounder Base
I56-0357-008R (SS) B501 Detector base without flange (European), 4-Inches
Diameter
I56-1382-001 (SS) M500X Fault Isolator Module
Table 1.3.1.1 SLC Devices Reference Documentation (Continued)
1.6 Devices
1.6.1 Monitor/Zone Interface Modules
These addressable modules allow the control panel to monitor entire circuits of conventional alarm
initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and
supervisory devices. The following modules support Velociti or CLIP mode.
• AMM-2F Monitor Module
• AMM-2IF Dual Monitor Module
• AMM-2SF Addressable Mini-Monitor Module
• AMM-4F Zone Interface Module
• MMI-6F Multi-Module Input, Signal
The MMI-6F Module allows an intelligent alarm system to monitor six (6) zones of
conventional two-wire detectors.
• MMI-10F Multi-Module Input, 10 Input Module
The MMI-10F Module supervises ten (10) Class-B addressable Initiating Device Circuits
(IDC) which monitor normally open contact initiating devices.
SLC Out
SLC-meas5.cdr
Branch
Segment
Segment
Five
Four
Segment
SLC-meas2.cdr
STEP 2
Last Device
SLC Return
Short Point
SLC Out
SLC-meas5.cdr
First Device
STEP 3
SLC Return
Last Device
3.1 Overview
This section shows the proper termination of the shield, if used.
Shielding of the SLC is not recommended for use with all SLC circuit wiring. If twisted-shielded
wire is used in an installation, use a floating shield to terminate the wire as described in Section 3.2.
NOTE: Use good wiring practices in compliance with local electrical codes.
! CAUTION: If the twisted-shielded pair wire is used in an installation, use a floating shield to
terminate the wire. The following precautions must be met:
• If the SLC is more than 3,000 ft. (914.4 m), divide the shield into floating segments of less than
1,000 ft. (304.8 m).
• To divide the shield wire into floating segments, cut the shield even with a jacket and tape as
shown in Figure 3.2.1.1.
Tape
SLC-swterm4.cdr
NOTE: If you use shielded wire in applications, where it is not recommended, the shielded wire will
reduce the maximum SLC length and may cause system SLC circuit faults. If shielded wire must be
used, where it is not recommended, failing to float the ends will reduce the maximum SLC length
even further.
4.1 Overview
This chapter describes the two styles of circuits that do not require isolation devices:
• NFPA 72 Style 4
• NFPA 72 Style 6
Addressable Module
T-tapped Circuits
B+ B–
SLC-style4.cdr
Control Panel
SLC
SLC Out
Addressable Module
SLC Return
B+ B– A– A+
SLC-style6.cdr
Control Panel
SLC
NOTE: T-tapping of the SLC wiring is NOT allowed for the Style 6 configuration.
IN
IN
OUT
OUT
SLC-isowire.cdr
Detector 1 X Detector 2
Y
Detector 5 Z
Detector 4 Detector 3
SLC Out SLC Return
SLC-isowork.wmf
Control Panel
Isolator Base Non-Isolating Device Short-circuit path
NOTE: For information on wiring an isolator base, refer to Figure 9.3.1.1, “Wiring an Isolator
Base”.
Isolator Module
Two-wire Addressable Detector
Isolated Branch
Isolator Module
Isolated Branch
Isolator Module
Isolated Branch
B– B+
SLC-style4iso.cdr
Control Panel
SLC
Isolator Isolator
Module Module
Section B
Two-wire
Addressable Section C
Detector
Addressable
Pull Station
Section A
The first Isolator Module on SLC (Out) and SLC (Return) is optional for the E3
Isolator Series and 7100 Series, because the panels provide the functionality. Isolator
Module Module
Isolator
Module
Two-wire Isolator
Detector Base
Isolator Isolator
Module Module
Addressable
Pull Station
Addressable
Detector
Isolator Isolator
Module Module
The first Isolator Module on SLC (Out) and SLC (Return) is optional for the tE3
Series and 7100 Series, because the panels provide the functionality.(
Isolator Isolator
Module Module
SLC Out SLC Return
NOTE: For additional information, refer to Figure 9.3.1.1, “Wiring an Isolator Base”.
6.1 Description
These addressable modules monitor conventional contact-type alarm initiating devices. You can
configure module circuits as an NFPA Style B (Class B) or a Style D (Class A) Initiating Device
Circuits (IDC). There is no limit to the number of contact-type devices installed on a monitor
module IDC.
For more information on the individual module specifications, refer to the Installation Instructions
that are provided with this device. For information on transponders, refer to the specific
transponder manual.
SLC–
IDC Return – Rotary
SLC+
Switches
IDC Return +
IDC Out +
IDC Out –
FMMtpH.wmf
Areas used to record the device
address and SLC number.
24 VDC –
24 VDC + SLC–
Rotary
IDC Return – SLC+ Switches
IDC Return +
IDC Out +
IDC Out –
FZMtpH.wmf
Rotary
Switches
Address +1{ 9 H–
8 H+ SLC–
SLCDualMod-simplified.wmf
7L+ SLC+
Base Address {
6L–
FMM-101.cdr
IDC (-) Yellow
Velociti-New Format
SLC-setadd.cdr,SLC-setaddtpH.wmf, SLCbrktabs.wmf
Breakaway Tab - Modules come
with a raised breakaway tab on the
TENS rotary switch. This tab must
be removed when the module is on
an FACP that uses more than 99
Type H Rotary addresses.
Switches
CLIP-Old Format
Type V Rotary
Switches
Dual monitor modules: On dual monitor modules, only even
numbers appear on the ONES rotary switch. The module takes
both the selected address and the next-higher address.
From Supply
24 VDC
Four-wire
24 VDC Power
Detector Base
Filtered, Regulated,
Resettable
Manual pull
station
To Next IDC
or
47K ELR Supervision Device
(supplied
with module)
SLC
Heat
detector AMM-2F
SLC-idcB1tpH.wmf
IDC
From
Supply
24 VDC
Four-wire 24 VDC Power
Detector Base Filtered, Regulated,
Resettable
Manual pull
station
To Next IDC
or
Supervision Device
SLC
Heat AMM-2F
detector
SLC-idcD1tpH.wmf
IDC
Manual
Pull
Station
47K
47K ELR
ELR AMM-2IF
SLC-idcB3fdm1.wmf
Heat
Detector SLC
1. Connect the SLC wiring to the AMM-4F module terminals 1 (–) and 2 (+).
2. Use the rotary switches on the module to set it to the required SLC address.
Each module takes one address on the SLC.
Figure 6.6.1 shows typical wiring for a supervised and power-limited NFPA Style B (Class B) IDC
using the AMM-4F module.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
For information on compatible smoke detectors, refer to the Compatibility Addendum to
Gamewell-FCI Installation/Operating Manuals, P/N: 9000-0427.
Two-wire
smoke
detectors
3.9K ELR
(supplied with module)
SLC
IDC
SLC-idcB2tpH.wmf
1. Connect the SLC wiring to the AMM-4F module terminals 1 (–) and 2 (+).
2. Use the rotary switches on the module to set it to the required SLC address.
Each module takes one address on the SLC.
Figure 6.7.1 shows the typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using the AMM-4F zone interface module.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 micro amps
@ 24 VDC (nominal).
2. The IDC provides the following services (do not mix the services):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
For information on compatible smoke detectors, refer to the Compatibility Addendum to Gamewell-
FCI Installation/Operating Manuals, P/N: 9000-0427.
Two-wire
smoke
detectors
SLC
IDC
SLC-idcD2tpH.wmf
3.9K ELR
(supplied with module)
SLCModule-simplified.wmf
Style Y/Z NAC (+)
NOTE:
• Module polarities are shown in alarm condition.
Prying tool
FCMBackJump.wmf, FCMBackJumpcl.wmf
A power supervision
relay is required only on
the last module of the
ELR power run. If using one
24 VDC Notification of the Velociti type IDs
47K, 1/2-watt
Appliances that provide built-in
power supervision, no
relay is required.
SLC-nacY.wmf
NAC
AOM-2SF
24 VDC
notification
appliances
NAC Return
A power supervision relay
is required only on the last
NAC Out module of the power. If
using one of the Velociti
SLC-nacZtpH.wmf
type IDs that provide built-
in power supervision, no
relay is required).
Module polarities are shown in Alarm.
8.1 Description
The AOM-2RF module is an addressable module that provides two isolated sets of Form-C relay
contacts.
Ratings for the dry relay contacts on a Form-C module are listed below:
• Resistive – 2 amps @ 30 VDC (e.g. Electronic devices and strobes)
• Inductive – 1 amp @ 30 VDC (0.6pF) (e.g. Mechanical bells and horns)
• Pilot Duty – 0.5 amp @ 125 VAC (0.35pF) (e.g. Using a smaller relay to trip another relay)
For more information on the module specifications, refer to the Installation Instructions provided
with this device. For information on transponders, refer to the specific transponder manual.
SLC
AOM-2RF
C
NC
NO
C
NC NO
SLC-frmCtpH.wmf
9.1 Description
The following types of bases provide the connection between the SLC and a variety of intelligent
detectors:
• B501 and B710LP detector bases
• B224RB plug-in relay detector base
• B200SR sounder base
For more information, refer to the Installation Instructions documents provided with these devices.
SLC
To next device
on SLC
RA400Z
SLC-B501wire.wmf
Remote LED
Annunciator
(Optional)
NOTE: The base wiring is identical to the B710LP, except there is no shield terminal.
SLC Out
SLC In
Conduit
SLC-224BIwire.wmf
Isolator Module
To next device
on SLC
For connection of
cable shield
3 Relay Common
2 Normally Open
1 Normally Closed
SLC
b224rb.wmf
NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore
the groups can only be used as a supplementary evacuation system. It is not acceptable to group
horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are
grouped via software are not subject to this limitation and may be used as part of the primary
alarm signaling.
Figure 9.5.1.1 illustrates the wiring of grouped devices using terminal 6, Sounder Base
Interconnect, so that the bases are activated by the detector.
INTELLIGENT
MONITOR MODULE
CLASS A OPTIONAL WIRING (+) SLC
(-) SLC OPTIONAL SOUNDER (-) SLC
(+) SLC INTERCONNECT
SUP (+)
SUP (-)
UL LISTED
COMPATIBLE
CONTROL
PANEL
UL LISTED
EOL
RESISTOR
47X
END OF LINE
NOT SLC+ SLC- EXT+ EXT- RA NOT SLC+ SLC- EXT+ EXT- RA NOT SLC+ SLC- EXT+ EXT- RA RELAY
USED USED USED (EOLR-1 OR
EQUIVALENT)
NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore
the groups can only be used as a supplementary evacuation system. It is not acceptable to group
horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are
grouped via software are not subject to this limitation and may be used as part of the primary
alarm signaling.
Figure 9.5.1.2 illustrates the wiring of grouped devices using terminal 6, Sounder Base
Interconnect, so that the bases are activated by the panel.
INTELLIGENT
MONITOR MODULE
(+) SLC
OPTIONAL SOUNDER (-) SLC
(-) SLC INTERCONNECT
SUP (+)
SUP (-)
(+) SLC
UL LISTED INTELLIGENT
COMPATIBLE RELAY MODULE†
CONTROL
PANEL
COMM 2 (-) SLC
UL LISTED
EOL
NC 2 (+) SLC RESISTOR
47X
NO 2
END OF LINE
COMM 1
NOT SLC+ SLC- EXT+ EXT- RA NOT SLC+ SLC- EXT+ EXT- RA RELAY
USED USED (EOLR-1 OR
EQUIVALENT)
NC 1 NO 1
Figure 9.5.1.2 Wiring for Grouped or General Alarm B200SR Sounder Bases
10.1 Description
The MS-7AF is an addressable manual pull station with a key-lock reset feature. The MS-7ASF is a
Spanish/English labeled version. It supports Velociti or CLIP mode. Wiring is the same for the MS-
7AF manual pull station.
For more information, refer to the Installation Instructions provided with the devices.
–
To next device
+ on SLC
SLC +
–
US PAT 444 0991
SLC-nbg12.cdr
For NACs:
(Vms - Vom)
Rmax =
(Nb)(Ib)
Where:
NOTE: This simplified equation is based on the fact that the devices are located at the end of a
long wire run.
Table A.1.1 lists the minimum supply voltages produced by the Gamewell-FCI power supplies.
Power Supervision
Relay
(EOLR-1)
SLC-psrtpH.cdr
Supervised NAC or IDC
ELR
(Use 47K with
or 3.9K with )
Figure A.2.1.2 shows an alternate 2-address method for supervising a 24 VDC circuit.
24 VDC Power from
Control Panel or Power Supply
AOM-2SF
ELR 47K
Power Supervision
Relay
(EOLR-1)
AMM-2F
Circuit supervised
by control panel
AOM-2SF
SLC-nacY1tpH.wmf
NOTE: If the NAC is a coded output, the AOM-2SF output will be coded as well.
For information on compatible notification appliances and relays, refer to the Compatibility
Addendum to Gamewell-FCI Installation/Operating Manuals, P/N: 9000-0427.
The following list the requirements for Style Z NAC Power Wiring (alternate):
• The circuit is supervised and power-limited.
• In this circuit, an external ELR is not required at the end of the NAC circuit.
• Refer to the respective control panel installation manual for the NAC terminal block
connection information.
• Remove the internal resistor on each AOM-2SF. (See instructions in Section 7.2, “Wiring a
NAC with Addressable Control Modules”).
Figure A.2.2.2 illustrates the wiring in compliance with NFPA Style Z NAC power alternate.
NAC Terminal Block
(24 VDC)
AOM-2SF
Circuit supervised
by control panel
AOM-2SF
SLC-nacZ1tpH.wmf
Notes
B.1 Introduction
There are one primary and three secondary UL–Listed surge protectors approved for use with the
FACPs listed in this appendix.
Primary Surge Protector:
• 326-2M TII Station Protector
Secondary Surge Protectors:
• DTK-2LVLP-F: Diversified Technology Group, Inc. (DITEK) 1720 Starkey Rd. Largo, FL
33771 (800) 753-2345.
• SLCP-30: EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029
• PLP-42N: Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019
(800) 727-9119
NOTE: For detailed information, refer to the installation documentation supplied with the unit.
Whenever the SLC wiring runs outside the building, one primary surge protector must be used with
each SLC wiring pair.
• Install the primary protection only as shown in this document.
• Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional
suppressors in series with the SLC wiring at the building entry/exit.
Figure B.1.1 illustrates the wiring connected to the surge suppressor output that must remain within
the building, while wiring connected to the surge suppressor input may be routed outside the
building.
Building #2 Building #1
P P
FACP
P = Primary
S = Secondary S
P P S
SLC-ssbuild1.cdr
Surge Suppressor
B.2 Installation
Mounting the secondary surge suppressor must be connected inside the FACP enclosure or
connected in a separate enclosure that is Listed for fire protective signaling use. To install, do the
following:
1. Locate an available stud and secure with the nut.
2. To protect the Control Panel, connect the unit in series with the SLC Circuit.
3. Provide a common ground to eliminate the possibility of a differential in ground potentials.
B.2.1 7100 Series and E3 Series
DTK-2LVLP-F Connections
Figure B.2.1.1 illustrates the DTK-2LVLP-F wiring connections.
2LVLP-F
IN OUT
SLC Terminal Block
2LVLP-F
–
+
SLC-lvlp1.cdr
SLC Loop
IN OUT
PLP-42N
GRND
L4
Style 6 (Class A)
L3
INPUT
L3
L2
L2
L1
L1
–
GRND
L4
L4
+
OUTPUT
L3
INPUT
L3
L2
SLC-plpn1.cdr
L2
SLC Loop
L1
L1
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to connect
the unit’s ground terminal to equipment ground. Wire length must be minimized to provide best
protection.
SLCP-30 Connections
Figure B.2.1.3 illustrates the SLCP-30 wiring connections.
SLCP-30
IN OUT
SLC Terminal Block
SLCP-30
SLC Loop
–
+
SLC-slcp1.cdr
IN OUT
Notes
C.1 AOM-2RF
Figure C.1.1 illustrates the AOM-2RF H-type format for rotary switches using the new Velociti
format.
Common 2 SLC -
Closed 2 SLC - Common 2
Closed 2 SLC +
Open 2 SLC +
Common 1 Open 2
Closed 1 Common 1
Open 1 Closed 1 Open 1
Type V Type H
Table C.1.1 lists the AOM-2RF terminal conversions. Column one lists the V-type (Clip format)
numbers, column two provides the terminal function and column three lists the H-type (Velociti
format) numbers.
1 SLC - 1
2 SLC + 2
3 Unused 3
N/A Unused 4
N/A Unused 11
Solenoid A- VDC -
Solenoid A+ SLC - VDC + SLC -
SLC + Solenoid A- SLC +
Solenoid B/A +
VDC - Solenoid A+
Solenoid B/A - Solenoid B/A +
VDC + Solenoid B/A -
Type V Type H
Table C.2.1 lists the AOM-2SF and AMM-4F terminal conversions. Column one lists the V-type
(Clip format) numbers, column two provides the terminal function and column three lists the H-
type (Velociti format) numbers.
1 SLC - 1
2 SLC + 2
3 VDC - 11
4 VDC + 10
5 Unused 5
6 Solenoid B/A - 6
7 Solenoid B/A + 7
8 Solenoid A + 8
9 Solenoid A - 9
N/A Unused 3
N/A Unused 4
C.3 AMM-2F
Figure C.3.1 illustrates the AMM-2F H-type format for rotary switches using the new Velociti
format.
Class A Supervision -
Class A Supervision+ SLC - SLC -
Class A/B Supervision + SLC + Class A Supervision - SLC +
Class A/B Supervision - Class A Supervision+
Class A/B Supervision +
Class A/B Supervision -
Type V Type H
Table C.3.1 lists the AMM-2F terminal conversions. Column one lists the V-type (Clip format)
numbers, column two provides the terminal function and column three lists the H-type (Velociti
format) numbers.
1 SLC - 1
2 SLC + 2
3 Unused 3
4 Unused 4
5 Unused 5
8 Class A Supervision + 8
9 Class A Supervision - 9
N/A Unused 10
N/A Unused 11
Notes
N S
NAC power 33, 46
Security service 28, 29, 30, 31, 32
wiring 45
shield-termination 17
NAC terminal block 45
short circuit 20, 21
NC-100 35
Signaling Line Circuit 10
NEC Article 800 48 see also SLC
NFPA Style 6 SLC
wiring 19 capacity of devices 12
with isolator modules 23 performance 13
NFPA Style 7 20 setting an SLC address 27
with isolator device 24 trouble conditions 13
T
terminal block, NAC 46
termination of shield 17
trouble conditions 13, 20
trouble warning 21
T-tapping 15, 18, 19, 23, 24
two-wire configuration 34
two-wire detectors 43
V
Velociti Mode
Setting an SLC Address 27
Velociti® 7
W
Waterflow alarm service, automatic and manual
28, 29, 30, 31, 32
wire length
four-wire SLC 16
two-wire SLC 15
Wiring
DTK-2LVLP-F 49
PLP-42N 49
SLCP-30 50
Style Y NAC 45
Style Z NAC Power 46
wiring
isolator bases 38
isolator modules 20
NACs 45
pull stations 41
relay modules 36
SLCs 28, 29, 30, 31, 32
wiring pair 48
wiring style requirements 13
Z
zone interface module 11, 25, 31, 32
Warn-HL-08-2009.fm
www.gamewell-fci.com
ILI-MB-E3
Intelligent Loop Interface - Main Board
Installation Instructions
12 Clintonville Road Northford, CT 06472-1610 USA PN 9000-0579:E 09/03/09 ECN 08-924
203-484-7161 • FAX 203-484-7118 • www.gamewell-fci.com
Section 1: Description
The ILI-MB-E3 is the main operating board for the E3 Series® control. It provides terminals for the connection of all of
the sub-assemblies. This sub-assembly can support the LCD-E3, DACT-E3, and up to a total of sixteen (16)
ASM-16 sub-assemblies and/or ANU-48 Remote LED Driver Modules.
TB3 TB4
TB5
TB 2
TB1 TB6
NOTE: For Installation Instructions, refer to the E3 Series® Expandable Emergency Evacuation Installation/
Operation Manual, P/N 9000-0574.
GFLT
W4 J4 DIS ENA
W5 9 1 9 1 J2 15 1
OFF ON OFF ON SLC1 CLASS "B", STYLE 4 (+)
AUX TERM
10 2 10 2 16 2
ARCNET W9
TERM
485A 485B
J5 BSEL
TB4 SLC1 CLASS "B", STYLE 4 (-)
W2 NOTE: IF ONLY ONE SLC IS SLC1 CLASS "A", STYLE 6 (+)
W1
FACTORY BSEL
RESETTABLE PWR OUT USED STYLE 6 (CLASS "A") SLC1 CLASS "A", STYLE 6 (-)
USE
W3
SYSTEM GROUND TB3 USE CABLE P/N: 75645 (20") TO THE UNUSED SLC TERMINALS SLC2 CLASS "B", STYLE 4 (+)
NON-RESET PWR OUT MB PR
CONNECT TO J5 SOCKET OF NEXT MUST BE JUMPERED STYLE 6 SLC2 CLASS "B", STYLE 4 (-)
SYSTEM GROUND W7 ILI-MB-E3 PCB OR ILI-S-E3 TO PREVENT LOOP FAULT SLC2 CLASS "A", STYLE 6 (+)
MUNICIPAL CKT (+) PCB IN SAME CABINET (UP TO 8 SLC2 CLASS "A", STYLE 6 (-)
1 2 3 4 5 6 78 9
W8
NAC1 CLASS B OUT (-) SET FOR MUNICIPAL CKT/RELEASE OR TROUBLE NORMALLY CLOSED
RESISTIVE SUPV COMMON
NAC1 CLASS A RETURN (+) REVERSE POLARITY OUTPUT NOTE: TROUBLE DRY
NAC1 CLASS A RETURN (-) MB = MUNICIPAL CKT/RELEASE TB5 SUPV NORMALLY OPEN
RELAYS CONTACTS
NAC2 CLASS B OUT (+) TB2 (MIDDLE & LEFT PINS OF W7 & W8) SUPV NORMALLY CLOSED
TRANSFER UPON ALARM,
NAC2 CLASS B OUT (-) PR = REVERSE POLARITY ALARM COMMON
SUPERVISORY, TROUBLE
NAC2 CLASS A RETURN (+) (MIDDLE & RIGHT PINS OF W7 & W8) OR SYSTEM POWER LOSS ALARM NORMALLY OPEN
NAC2 CLASS A RETURN (-) ALARM NORMALLY CLOSED
10 9
TB1 TB6-4 RXD TO PIN 3 OF DB9
PM-9G, +24VDC (+) +24VDC TB6
PM-9G, GND (-) LED LED LED LED LED LED LED LED LED LED LED LED SW2 SW1 J1 TB6-3 SUPV TO PIN 9 OF DB9
GND ON 8 765432 1
1 2 3 4 5 6 7 8 9 10 11 12
OPT. MOD. (+) +24VDC + TB6-2 TXD TO PIN 2 OF DB9
REC MRC DUP TX RX RST DG ALRM SUPV TRBL PWR GND 2 1
1 2 34 5 6 7 8 1 2 3 4
4 3 2 1 4 3 2 1 9 8 76 5 4 3 2 1 4 32 1
Figure 3.1 illustrates the wiring connections for the ILI-MB-E3 sub-assembly.
OPT. MOD. (-) GND FLT 12345 ARCNET ADDRESS TB6-1 GND TO PIN 5 OF DB9
NOTE:
USE SWITCH SW1 TO TO PM9G DOWNLOAD CABLE
5
Section 3: Wiring (Continued)
Table 3.2 lists the wiring requirements for the ILI-MB-E3 sub-assembly.
Circuit Type Circuit Function Wire Requirements Distance Typical Wire Type*
SLC Connects to intelligent Twisted-unshielded pair, 12 to 10,000 ft. (3,000 m) 12 AWG (3.1 mm2)
(power-limited) and addressable 18 AWG (3.1 to 0.78 mm2) 8,000 ft. (2,400 m) 14 AWG (2.00 mm2)
modules. 40 Ohms maximum per length 4,875 ft. (1,450 m)
of Style 6 & 7 loops. 16 AWG (1.30 mm2)
40 Ohms combined-branch 3,225 ft. (980 m) 18 AWG (0.78 mm2)
circuits maximum for Style 4
loop.
MC cable with 2 conductor
twisted.
Or Shielded wire, in conduit or 1,000 ft. (304.8 m) 12 to 18 AWG
outside of conduit or MC cable.. (3.1 to 0.78 mm2)
MC cable with 3 conductor
twisted.
Note: Maximum total
capacitance of all SLC wiring
(both between conductors and
from any conductor to ground)
should not exceed 0.5
microfarads.
EIA-485 Connects to LCD-E3, Twisted-unshielded pair with a 3,000 ft. (.914 m) 16 AWG (1.30 mm2)
(power-limited) ASM-16 and ANU-48 characteristic impedance of (maximum)
modules. 120 Ohms. 18 AWG
(0.78 mm2) minimum.
EIA-232 Connects to Printers, Twisted-unshielded pair. 18 50/15.24 16 AWG (1.30 mm2)
(power-limited) CRT, or PC. 2
AWG (0.78 mm ) minimum (without modem)
NAC Notification E3 (power-limited) 12-18 AWG (3.1 to 0.78 mm2) To meet 1.2 V drop, 12 to 18 AWG
Appliance Circuit At alarm current level, no more or sized to provide (3.1 to 0.78 mm2)
than a 1.2 V drop at the end of the minimum rated
the circuit, or sized to provide operating voltage of
the minimum rated operating the appliances
voltage of the appliances used. used.
24 VDC Power To Transmitter 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 volt 12 to 18 AWG
Runs Annunciator Size wire so that no more than drop (3.1 to 0.78 mm2)
(power-limited) 1.2 V drop across wire run from
supply source to end of any
branch.
ARCNET Provides interface Twisted-unshielded pair low 3,000 ft. (.914 m) 18 AWG (3.1 mm2)
(power-limited) between network capacitance 18 AWG
nodes.
ARCNET should be
installed in a separate
conduit.
NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL 1459.
Table 3.2 Wiring Requirements
STANDALONE
8 76 54 3 2 1
=0
on 8 76 54 3 2 1
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=1 =10 =19 =28 =37 =46 =55
on on on on on on on
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=2 =11 =20 =29 =38 =47 =56
on on on on on on on
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=3 =12 =21 =30 =39 =48 =57
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=8 =17 =26 =35 =44 =53 =62
on on on on on on on
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
=9 =18 =27 =36 =45 =54 =63
on on on on on on on
8 76 54 3 2 1
=64
on
Set the address using the switch, SW1. Figure 4.1 illustrates the programming address switch settings for the ILI-MB-E3.
7
Section 5: Specifications
The following list the electrical specifications for the ILI-MB-E3.
Section 1: Description
The NGA LCD Graphic Annunciator is a software programmable touchscreen interface for the Gamewell-FCI emergency
voice evacuation systems. It provides an LCD display of system events, together with system status indicating LEDs, and
touch-screen switches for the following conditions:
• Alarm Acknowledge • Signal Silence
• Trouble Acknowledge • System Reset
The background display can be programmed to be labeled as, “Command Center in Control” if required. The NGA
mounts in the E3 Series® enclosure or it may be installed in a remote location. It occupies one (1), node on the Broadband
network.
NOTE: For a new installation, it is recommended that you work on a flat surface when you remove the inner
door of the enclosure and install all the sub-assemblies and/or blank panels.
2. Remove the unit from its static-shield bag, observing proper static protection measures.
3. Visually inspect the unit for damage.
4. Use the Hardware Kit provided with the unit.
For additional information on the installation, refer to the E3 Series® Expandable Emergency Evacuation
Installation/Operation Manual, P/N 9000-0574.
J3
TAG
CONNECT THE NGA TO THE
IMPORTANT NOTE: ARCNET REPEATER J4 OR
FOR NGA REVS 1-4 WIRE TO THE DIFFERENTIAL
INSTALL THE SHUNT ARCNET
ACROSS J4 PINS 13 & 14 COM A & COMB B
WHEN USING THE W1 DO NOT CONNECT THE NGA BOTH
FACTORY
DIFFERENTIAL ARCNET USE AT THE SAME TIME.
TERMS TB1-3 & 4 DO NOT
OR TB1-7 & 8 INSTALL
DO NOT CONNECT TO
J1
THE EXTERNAL POWER
TO OVERLAY
SUPPLY WHEN THE NGA
INSTALL W2 & W3 ACROSS THE J4 IS USED.
1
MIDDLE AND BOTTOM PINS. 24VDC IN(+) FROM ILI/ILI95-MB TB3-6 OR RPT-E3 TB4-3
Figure 3.1 illustrates the wiring connections for the NGA.
2
SYS GND IN(-) FROM ILI/ILI95-MB TB3-7 OR RPT-E3 TB4-4
3
DIFFERENTIAL ARCNET COM A IN FROM RPT-E3 TB3-3
J7
4
W2
W3
DIFFERENTIAL ARCNET COM B IN FROM RPT-E3 TB3-4
Section 3: Wiring Connections (Continued)
5
24VDC OUT (+) TO NEXT DEVICE
BSEL1
BSEL0
6
SYS GND OUT (-) TO NEXT DEVICE
BACKLIGHT
7
DIFFERENTIAL ARCNET COM A OUT TO NEXT DEVICE
W4
TERM
TERM
RS485
W5
SUPV TO COMPUTER DB9 PIN 9 OR PRINTER DB25 PIN 20
TX
RX
DG
RST
REC
DUP
MRC
PWR
TxD TO COMPUTER DB9 PIN 2 OR PRINTER DB25 PIN 3
TRBL
SUPV
ALRM
10 11 12
RS232 Supv
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
LED9
LED10
LED11
J2 P/N 75267
RS232 TxD BLK
RS232 Gnd RED
9 10 11 12
RS232 PORT: 15 VDC MAX., 0.05 AMP MAX. UP TO 115.2 K BAUD. 115.2K BAUD REQUIRED FOR
CONFIGURATION DOWNLOADS VIA NGA, 8 DATA BITS, 1 STOP BIT, NO PARITY
Distance
Circuit Type Circuit Function Wire Requirements (feet/meters) Typical Wire Type*
SLC Connects to Twisted-unshielded pair, 12 to 18 AWG 10,000 ft. (3,000 m) 12 AWG (3.1 mm2)
(power-limited) intelligent and (3.1 to 0.78 mm2) 40 Ohms maximum 8,000 ft. (2,400 m) 14 AWG (2.00 mm2)
addressable modules. per length of Style 6 & 7 loops.
4,875 ft. (1,450 m) 16 AWG (1.30 mm2)
40 Ohms combined-branch circuits
3,225 ft. (980 m) 18 AWG (0.78 mm2)
maximum for Style 4 loop.
MC cable with 2 conductor twisted.
Or Shielded wire, in conduit or outside of 1,000 ft. (304.8 m) 12 to 18 AWG
conduit or MC cable. (3.1 to 0.78 mm2)
MC cable with 3 conductor twisted.
Note: Maximum total capacitance of all
SLC wiring (both between conductors
and from any conductor to ground)
should not exceed 0.5 microfarads.
EIA-485 Connects to LCD-E3, Twisted-unshielded pair with a 3,000 ft (maximum) 16 AWG (1.30 mm2)
(power-limited) ASM-16 and ANU-48 characteristic impedance of 120
modules Ohms. 18 AWG (0.78 mm2) minimum.
EIA-232 Connects to Printers, Twisted-unshielded pair. 18 AWG 50/15.24 16 AWG (1.30 mm2)
(power-limited) CRT, E3or PC. (0.78 mm2) minimum (without modem)
NAC E3 (power-limited) 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 V drop, or 12 to 18 AWG
Notification 2
At alarm current level, no more than a sized to provide the (3.1 to 0.78 mm )
Appliance 1.2 V drop at the end of the circuit, or minimum rated
Circuit sized to provide the minimum rated operating voltage of
operating voltage of the appliances the appliances used.
used.
24 VDC Power To Transmitter 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 volt drop 12 to 18 AWG
Runs Annunciator Size wire so that no more than 1.2 V (3.1 to 0.78 mm2)
(power-limited) drop across wire run from supply
source to end of any branch.
CHG-120 External battery 12 AWG (3.1 mm2) in conduit 20/6.1 (maximum) 12 AWG (3.1 mm2)
charger
ARCNET Provides interface Twisted-unshielded pair, low 3,000 ft. (.914 m) 18 AWG (3.1 mm2)
(power-limited) wiring capacitance 18 AWG
ARCNET should be
installed in a separate
conduit.
Note: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL 1459.
Table 4.1 NGA Wiring Requirements
Section 6: Specifications
The following are the NGA specifications.
Operating Voltage: 24 VDC (from PM-9/PM-9G power supply)
Operating Current: 0.200 amp* (See Note)
Alarm Current: 0.200 amp
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93%, non-condensing at 90° F (32° C)
Supervised
Power-limited:
*NOTE: Normal operating current. During a power failure, the current drops to 0.045 amp, since the backlight is
extinguished.
Section1: Description
The Repeater Module (RPT-E3) provides the remote interface between the ILI-MB-E3 or ILI95-MB-E3 and the
Broadband Network. The Repeater Module (RPT-E3) can also be used with the NGA. The unit is available for use with
unshielded twisted-pair wire or fiber-optic cable (RPT-E3-FO), or unshielded twisted-pair only (RPT-E3-UTP).
NOTE: For additional information on the installation, refer to the E3 Series® Expandable Emergency
Evacuation Installation/Operation Manual, P/N 9000-0574.
TERM
16 2 COM B OUT TO NGA TB1-4
1 2 3 4
ARCNET
ARCNET LEAVE OPEN COM A OUT TO NGA TB1-3
J1
TB3
COM B IN
TB4 HARD-WIRED POWER COM A IN
1
CONNECTIONS NOT
GND(-) OUT TO NGA TB1-2
1 2 3 4
REQUIRED WHEN J10 USED
+24VDC OUT TO NGA TB1-1
TB4 GND(-) IN FROM TB3-7 ILI-MB-E3/
ILI95-MB-E3
1 +24VDC IN FROM TB3-6 ILI-MB-E3/
ILI95-MB-E3
1 2 3 4
ARCNET PORT 2B
D12 TB1 ARCNET PORT 2A
J2 SHORT TO
RX2 ENABLE ARCNET PORT 1B
D11 GROUND FAULT 1 ARCNET PORT 1A
RX1 DETECTION
J2 U5 FROM PREVIOUS NODE
D10 GFI (RX2) TX1 CONNECTOR
TX J7
D18 J8 U7 FROM PREVIOUS NODE
(TX2) RX1 CONNECTOR
PWR J9
See Table 3.1: RPT-E3 Wiring
Connections and Table 3.2: U4 TO NEXT NODE
Transmitter Output Settings (RX1) TX2 CONNECTOR
J4
J5 U6 TO NEXT NODE
(TX1) RX2 CONNECTOR
J6
LEDS
D12 ON = RECEIVING NETWORK TRANSMISSIONS INTO ARCNET PORT 2 OR U5
OFF OR BLINKING = NOT RECEIVING NETWORK TRANSMISSIONS INTO ARCNET PORT 2 OR U5
D11 ON = RECEIVING NETWORK TRANSMISSIONS INTO ARCNET PORT 1 OR U4
OFF OR BLINKING = NOT RECEIVING NETWORK TRANSMISSIONS INTO ARCNET PORT 1 OR U4
D10 ON = TRANSMITTING TO NETWORK
OFF = NOT TRANSMITTING TO NETWORK
D18 ON = POWERED
OFF = NOT POWERED
OPEN SHORTED
NOTE: 2-PIN SHUNT
PLACED OVER PINS
Section 1: Description
The ASM-16 sub-assembly is a configurable switch input sub-assembly that includes sixteen (16), switches and forty-
eight (48), status LEDs. This sub-assembly may be remotely located via the RS-485 serial interface. Each switch address
is fully software programmable to serve as:
• A System Control Switch, Reset, Silence, Alarm and Trouble Acknowledge, etc.
• A Voice Evacuation Speaker Circuit control switch
• An Auxiliary Control Circuit switch
• A status indicating LED, (red, green, and yellow)
• A status indicating LED, labeled to display, "Command Center in Control.”
Figure 1.2 Front View
Figure 1.2
Figure 1.2
Figure 1.2
Figure 1.2
Figure 1.2
Figure 1.2
Figure 1.2
Figure 1.2
Figure 1.2
Figure 1.2
NOTE: For a new installation, it is recommended that you work on a flat surface, while you remove the inner
door of the enclosure and install all the sub-assemblies and/or blank panels.
3. Remove the unit from its static-shield bag, observing proper static protection measures.
4. Visually inspect the unit for damage. If the switch identifying paper label is available at this time, install the label by
sliding the label down into the pocket that is located between the faceplate overlay and the steel backer plate. This
will prevent the need to remove the unit at later date.
5. Place the unit into position in the rear of the inner door, centered in the opening, and secure the unit with the nuts
provided.
NOTE 1: If other units are installed into the inner door at this time, do not tighten the nuts until the adjacent unit
or blank panel is in place. Use the nuts to connect and retain more than one unit.
NOTE 2: Use the wiring connections in Table 2.1 and refer to Notes A-F in Figure 2.1 for the installation of the
ribbon cable and hardwire locations for the following sub-assemblies:
• ASM-16 • LCD-E3
• ILI-E3 or ILI95 Series • Remote enclosure installation
• INI-VG Series
6. Install the short ribbon cables interconnecting the cables from board to board as shown in Figure 2.1.
7. Connect the long ribbon cables interconnecting the cables from row to row starting from the first row connecting to
the following sub-assemblies:
• INCC
• ILI-MB-E3
• ILI95-MB-E3
J3 A J3 J3
J1 J2 J1 J2 J1 J2
A A A A C NOTE C and F:
F From local INI-VG or LCD-E3 J1
SW 17 SW 17
(RS-485 Local)
JMP 1 JMP 1 JMP 1
NOTE A:
ASM-16 or ANU-48 to B NOTE B, D and E:
ASM-16 or ANU-48 wiring D HARDWARE RS-485 Port
ASM-16/ANU-48 to TB 1 TB 1 E TB 1
ASM-16/ANU-48 RS-485
REMOTE REMOTE REMOTE (to/from module in
connection Different INCC cabinet)
J3 J3 J3
From ILI-MB-E3 or IL95-MB-E3
A TB3-1, TB3-2, TB1-3 and TB1-4
J1 J2 J1 J2 J1 J2
A A A A RS-485 RIBBON CABLE
Connector (to/from module)
In same INCC Cabinet)
SW 17 SW 17 SW 17
JMP 1 JMP 1 JMP 1
B NOTE B:
TB 1 TB 1 TB 1 To next ASM-16 or ANU-48
REMOTE REMOTE REMOTE
TB1 remote in next INCC
cabinet
NOTE A:
ASM-16 or ANU-48 to
ASM-16 or ANU-48 wiring
ASM-16/ANU-48 to ASM-16/
ANU-48 RS-485 connection
S e t th is s w itc h 6 U P w h e n c o n n e c te d
to th e IL I-M B -E 3 o r IL I9 5 -M B -E 3 .
S e t th is s w itc h 6 D O W N w h e n
c o n n e c te d to th e IN I-V G C .
J32 10
J3 RS-232 PORT
1 9 CONNECTIONS
- ANU-48-C OR J2
- ASM-C SERIES
J1, J2, OR J3, AND
J1 - INI-VG-C J3
10
9
J1 RS-232 PORT
J2 RS-232 PORT
J2
10
9
CONNECTIONS
CONNECTORS
- ANU-48-C J1 OR J2
- ANU-48-C J1 OR J2
- ASM-C SERIES
- ASM-C SERIES
J1, J2, OR J3, AND
J1, J2 OR J3, AND
1
2
- INI-VG-C J3
- INI-VG-C J3
2
1
SW1
ON
1 2 3 4 5 6 7 8
REMOTE
JMP4
Distance
Circuit Type Circuit Function Wire Requirements (feet/meters) Typical Wire Type*
SLC Connects to Twisted-unshielded pair, 12 to 18 AWG 10,000 ft. (3,000 m) 12 AWG (3.1 mm2)
(power-limited) intelligent and (3.1 to 0.78 mm2) 40 Ohms maximum 8,000 ft. (2,400 m) 14 AWG (2.00 mm2)
addressable modules. per length of Style 6 & 7 loops.
4,875 ft. (1,450 m) 16 AWG (1.30 mm2)
40 Ohms combined-branch circuits
3,225 ft. (980 m) 18 AWG (0.78 mm2)
maximum for Style 4 loop.
MC cable with 2 conductor twisted.
Or Shielded wire, in conduit or outside of 1,000 ft. (304.8 m) 12 to 18 AWG
conduit or MC cable. (3.1 to 0.78 mm2)
MC cable with 3 conductor twisted.
Note: Maximum total capacitance of all
SLC wiring (both between conductors
and from any conductor to ground)
should not exceed 0.5 microfarads.
EIA-485 Connects to LCD-E3, Twisted-unshielded pair with a 3,000 ft (maximum) 16 AWG (1.30 mm2)
(power-limited) ASM-16 and ANU-48 characteristic impedance of 120
modules Ohms. 18 AWG (0.78 mm2) minimum.
EIA-232 Connects to Printers, Twisted-unshielded pair. 18 AWG 50/15.24 16 AWG (1.30 mm2)
(power-limited) CRT, E3or PC. 2
(0.78 mm ) minimum (without modem)
NAC E3 (power-limited) 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 V drop, or 12 to 18 AWG
Notification 2
At alarm current level, no more than a sized to provide the (3.1 to 0.78 mm )
Appliance 1.2 V drop at the end of the circuit, or minimum rated
Circuit sized to provide the minimum rated operating voltage of
operating voltage of the appliances the appliances used.
used.
24 VDC Power To Transmitter 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 volt drop 12 to 18 AWG
Runs Annunciator Size wire so that no more than 1.2 V (3.1 to 0.78 mm2)
(power-limited) drop across wire run from supply
source to end of any branch.
CHG-120 External battery 12 AWG (3.1 mm2) in conduit 20/6.1 (maximum) 12 AWG (3.1 mm2)
charger
ARCNET Provides interface Twisted-unshielded pair, low 3,000 ft. (.914 m) 18 AWG (3.1 mm2)
(power-limited) wiring capacitance 18 AWG
ARCNET should be
installed in a separate
conduit.
Note: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL 1459.
Table 5.1 ASM-16 Wiring Requirements
Section 1: Description
The PM-9 power supply supplies 24 VDC at 9 Amperes (max.) and is designed for use with the Gamewell-FCI distributed
audio networks. It can also be used to maintain and supervise batteries up to 55 A/H in size. The PM-9 can be
"hard-wired" or can communicate with the main panel via an RS-485 for status and diagnostics.
NOTE: For Installation Instructions, refer to the E3 Series® Expandable Emergency Evacuation Installation/
Operating Manual, P/N 9000-0574.
Section 3: Wiring
1. Wire the AC power connections, but do not apply power until all wiring is completed and checked. Wiring is to be in
conformance with local and national codes.
2. Connect the wires for the batteries to the battery terminal block, but do not connect the battery at this time.
3. A) For use with the E3 Broadband INX:
1. Determine the number of AM-50-25VRMS amplifier modules that will be connected to the PM-9 and pre-wire a
pair of wires of adequate length, including the service loop, for each module as shown in Figure 3.1.
TB4
TO AM-50 #1 TB1-2 (RED)
2. Install the 10-conductor ribbon cable (supplied) from the INI-VGX into Connector J1.
3. If the INI-VGX-FO or INI-VGX-UTP and AM-50 modules have not been installed on the sub-chassis,
Gamewell-FCI recommends installing the INI-VGX-FO, INI-VGX-UTP and AM-50 modules before the sub-
chassis is re-mounted in the INX cabinet.
NOTE: To complete the wiring to the AM-50, INI-VGX-FO and INI-VGX-UTP modules, refer to the
AM-50 Installation Instructions (P/N 9000-0544) and INI-VG Series Installation Instructions
(P/N 9000-0549).
24VOUT
RED
GND
B LK
T1
12
1
TB3
BATT+
PS3
+
1
+ +
1 1
PS2
+
PS1
BATT-
TB4
1
+
24 VOUT GND 24 VOUT GND 24 VOUT GND
TB1
1
1 1
1
+
+ 1
J1
JMP1
1
6.25A 250V
SLO BLO
F1
W1
TB3
(NON-PWR LIMITED) L1
Q1
T1
12
BACKUP
1
BATTERY (+) POS +C11 D6
BACKUP
BATTERY (-) NEG
BATT-
+ C12 See
Note 1:
Section 3: Wiring (Continued)
6
7
TB4
TB1
OUTPUT GND (-) BATTERY FAULT D3 YELLOW LED GROUND (GREEN) AND MECHANICALLY PROTECTED.
EXTERNAL POWER ALL MEANS OF DISCONNECTING
GROUND FAULT YELLOW LED
OUTPUT 24VDC (+) D4 120VAC HOT (BLACK) THIS CIRCUIT MUST BE CLEARLY
NEUT/ WHT GND/ GRN HOT/ BLK
EXTERNAL POWER MARKED “FIRE ALARM CONTROL”
OUTPUT GND (-) NOTE:
SLO BLOW
F1 6.25A 256V
See Note 1:
AND BE ACCESSIBLE TO
9
J4 CONNECTOR
5
Section 4:Specifications
The following are the electrical specifications for the PM-9.
Input Voltage: 120 VAC, 60 Hz
Input Current: 4.6 amps max. @ 120 VAC 60 Hz
Output Voltage: 24 VDC FWR
Output Current: 9 amperes Alarm max. continuous
Output Current: 5 amperes Standby max. continuous (See Note 1)
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93%, non-condensing at 90° F (32° C)
Supervised
Non Power-Limited
NOTE 1: Continuous standby loads in excess of .560 Amps up to 5 Amps may require Generator Backup or load
shedding during an AC power failure. See Section 3.14 Standby Battery Calculations in the E3 Series Installation/
Operation Manual P/N 9000-0574.
! CAUTION: This equipment is sensitive to static electricity. It may be damaged if not properly handled. Use a
ground wrist strap and anti-static mat, when handling this equipment. Transport this unit in a static-shielding
bag.
Failure to observe this requirement could cause latent damage to the equipment which might not
manifest itself until after the equipment is placed in service.
Remove all source of power before removing or installing any units.
Section 1: Description
The E3 Series® Cabinet Trim Rings are metal frames or brackets used for supporting the E3 Series Cabinet backbox
installations. The E3 Trim Rings can be used as an optional accessory when installing the following E3 Series Cabinets:
• E3 Cabinet A or AA • E3 Cabinet A2 • E3 Cabinet C
• E3 Cabinet A1 • E3 Cabinet B • E3 Cabinet D
The E3 Series Trim Rings package includes the following interchangeable components.
• E3 Trim Ring Top/Bottom • E3 Trim Ring Left/Right
NOTE: Use the Trim Ring Hardware Kit provided. The top/bottom and left/right trim rings are interchangeable.
KNOCKOUTS
LEFT/RIGHT LEFT/RIGHT
TRIM RING TRIM RING KNOCKOUTS
(LEFT) (RIGHT)
R IG H T S ID E
TOP/BOTTOM TRIM RING BOTTOM T R IM R IN G
(BOTTOM) T R IM R IN G
Figure 1.1 E3 Cabinet Trim Ring (Front View) Figure 1.2 E3 Cabinet Trim Ring (Side View)
E3 Cabinet A or
AA, Trim Top
7
1
E3 Cabinet A
or AA, Trim Left
2
8 #6
KE H E X 3
( 10 P S N ,
P L UT
A C S, 9
ES
4 )
5
E3 Cabinet A
6 or AA, Trim Righ
10
E3 Cabinet A
or AA, Trim Bottom
E3 CABINET A and AA
21 3/4”
55.25 cm
1 2
12 1/2” 10 1/8"
32 cm 25.86 cm
3 4
(SEE NOTE)
19 3/8"
49.22 cm
NOTE:
E3 CABINET A DEPTH= 1 11/16" (2.92 cm)
E3 CABINET AA DEPTH= 3 11/64" (7.91 cm)
5 1
E3 Cabinet A1, 2
Left Trim Ring
7
6
NOTE:
E3 Cabinet A1,
#6 HEX,
3 Right Trim Ring
KEPS NUTS, 8
(8 PLACES) 4
E3 Cabinet A1,
Bottom Trim Ring
E3 Cabinet A2,
Top Trim Ring
5 1
E3 Cabinet A2,
Left Trim Ring 2
6
7
NOTE:
#6 HEX,
3
KEPS NUTS,
E3 Cabinet A2,
(8 PLACES)
8 Right Trim Ring
4
E3 Cabinet A2,
Bottom Trim Ring
E3 C A BIN ET A 1
11 1/4”
28.60 cm
1 2
12 1/2” 10 1/8"
31.75 cm 25.86 cm
3 4
1 3/4”
4.44 cm
1 11/16”
2.82 cm
8 7/8"
22.30 cm
Figure 2.4.1 E3 Cabinet A1, Flush-Mounting Installation
E3 CABINET A2
15.75"
40.00 cm
1 2
12.5"
31.75 cm 10 1/8"
25.86 cm
3 4
1 11/16"
2.82 cm
1 11/16"
2.82 cm
13.3/8"
33.99 cm
Figure 2.4.2 E3 Cabinet A2, Flush-Mounting Installation
E3 Cabinet B,
7 Top Trim Ring
1
E3 Cabinet B, 3
8
Left Trim Ring
10
11
NOTES:
#6 HEX, 4 E3 Cabinet B,
KEPS NUTS Right Trim Ring
5
(12 PLACES)
6 12
E3 Cabinet B,
Bottom Trim Ring
E 3 C a b in e t C ,
7 T o p T rim R in g
1
3
8
10
E 3 C a b in e t C ,
L e ft T rim R in g
9
12
10 E 3 C a b in e t C ,
13 R ig h t T rim R in g
NO TE:
#6 HEX, 4
KEPS NUTS, 5
(1 4 P L A C E S )
6 14
E 3 C a b in e t C ,
B o tto m T rim R in g
3.1/8"
E 3 C A B IN E T B
21.7/8" 8.1 cm
55.32 cm
1 2
21.7/8" 19 1/2”
55.32 cm 49.52 cm
3 4
3 1/8"
8.1 cm
19 1/2”
49.52 cm
Figure 2.6.1 E3 Cabinet B, Flush-Mounting Installation
E 3 C A B IN ET C
21 7/8" 3 1/8"
55.32 cm 8.07 cm
1 2
32 1/2" 30 1/8"
82.55 cm 76.66 cm
3 4
3 1/8"
8.07 cm
19 1/2"
49.52 cm
Figure 2.6.2 E3 Cabinet C, Flush-Mounting Installation
E3 Cabinet D,
Top Trim Ring
71
2
3
8
12
E3 Cabinet D,
9
Left Trim Ring 13
10
14
E3 Cabinet D,
Right Trim Ring
11
15
NOTE: 4
#6 HEX,
KEPS NUTS 5
(16 PLACES)
16
6
E3 Cabinet D,
Bottom Trim Ring
Figure 2.7.1 E3 Cabinet D, Trim Rings Installation
E3 CABINET D
21 7/8" 3 1/8"
55.32 cm 8.072 cm
1 2
43 ½” 41 1/8"
110.49 cm 105.41 cm
3 4
3 1/8"
8.072 cm
19 1/2"
49.52 cm