Sunteți pe pagina 1din 2

M O D AL

The MODAL is a high efficiency Completely adjustable New heat exchange


pressurized steel boiler for
operation at a fixed temperature, door ratio for preventing
higher than 50°C. On all pressure-fired boilers it is condensation
The MODAL range is available in necessary that the door ensure the
10 models, with an output The development of this project
maximum gas soundness, as every has modified the ratio between the
from 64 to 291 kW. minimum opening could cause heat exchange guaranteed by the
The cylindrical furnace with a blind a high temperature gas leakage furnace’s surface and the one of
bottom plate, completely wet, and towards the ambient, causing: tube bundle.
with reversed flame combustion • heat dispersion By increasing heat exchange of
chamber guarantees: • structure deformation the tube bundle to over 60% of the
compact dimensions • air pollution with combustion total and placing it in the highest
heat exchange optimization residues in the room where the and hottest part of the boiler the
for short flame fuels, as for boiler is installed. possibility of condensation for
example oil and gas, thus the combustion gasses is notably
favouring heat exchange by Due to these reasons the reduced. Besides, the introduction
convection. door is particularly strong and of the “fin effect” technology, the
finely adjustable, vertically and extension of the smoke pipes
The furnace’s flat bottom plate has lengthwise, in order to achieve the
”C” profiles welded on the water over the rear tube plate, causes a
ideal gastight position. Normally temperature increase in the pipes
side in order to favour heat transfer hinged on the right hand side,
and to strengthen the structure. terminal part, protecting their
the opening can be reversed by welding seams from corrosion.
inverting the hinges. Moreover, for
reducing the thermal dispersions
towards the ambient, it is also Instruments and
fitted with a special ceramic fibre complementary
lining which, when compared to
refractory cement, improves the functions
insulation by 40% and remarkably Complete insulation
increases its life-span. of the boiler body
with 60 mm thick rock
wool material.
Steel turbulators
for combustion optimiziation
The control panel
Main fuse Burner switch

Illuminated main switch Summer/winter pump switch

High limit thermostat Boiler thermometer Working thermostat

Technical data
DIMENSIONS

Legend:
1 - Control panel
2 - Burner connection flange
3 - Maintenance/cleaning door
4 - Flame spy glass
T1 - C.H. flow
T2 - C.H. return
T3 - Chimney connection
T4 - Max dia. for burner tube
T5 - Boiler drain

model Output Input A B C E F G H T1-T2* T3 T4 T5 Combustion Water content Water side Smoke side Max Weight
chamber Boiler/DHW pressure pressure working
dimensions tank * losses** losses pressure***
Ø Ø
kW kW mm mm mm mm mm mm mm Rp mm mm Rp mm l m w.c. mm w.c. bar kg
MODAL
64 64 71 690 722 990 305 480 115 - 1½ 200 130 ¾ 330x670 86 0,10 1,5 5 195
76 76 84 690 722 990 305 480 115 - 1½ 200 130 ¾ 330x670 86 0,13 1,8 5 195
93 93 102 690 722 990 305 480 115 - 1½ 200 130 ¾ 330x670 86 0,16 2,5 5 195
Cod. 28665GB - Ed.1 - 09/12

105 105 115 760 812 1205 350 500 130 - 2 200 180 ¾ 390x850 126 0,10 3 5 280
116 116 128 760 812 1205 350 500 130 - 2 200 180 ¾ 390x850 126 0,10 3 5 280
140 140 155 760 812 1205 350 500 130 - 2 200 180 ¾ 390x850 126 0,14 5 5 280
163 163 180 760 812 1385 350 500 130 - 2 200 180 ¾ 390x1030 151 0,20 8 5 318
186 186 206 760 812 1385 350 500 130 - 2 200 180 ¾ 390x1030 151 0,25 14 5 318
233 233 258 860 937 1437 421 580 165 1482 DN 65 250 180 ¾ 470x1070 203 0,22 18 5 420
291 291 322 860 937 1687 421 580 165 1732 DN 65 250 180 ¾ 470x1320 247 0,30 22 5 480

*For the MODAL 233 and MODAL 291 the connections T1-T2 are flanged. **The pressure losses related to a flow rate for a Δt of 15 K. ***On request available also up to 10 bar.

AG S.p.A. 46033 casteldario - mantova - italy - tel. +39 0376 57001 - fax +39 0376 660556 - export@unical-ag.com - www.unical.eu
Unical AG declines any liability for the inaccuracies that may appear due to errors in transcription or printing. It also reserves the right to introduce
those modifications to its products that it considers necessary or useful, without compromising the essential characteristics of the said products.

S-ar putea să vă placă și