Sunteți pe pagina 1din 6

GRX-TVI Control Interface

Phase Control to 0-10V

English
Installation and Operation Instructions
Read Before Installing
Occupant Copy 100-127V and 220-240V/CE
Mounting
GRX-TVI Find a suitable location for mounting.
n Decide on the proper location for the GRX-TVI (NEMA Type 1
®
0-10V INTERFACE CONTROL
Control Input:
100-120V, 220-240V 50/60Hz
COOPERSBURG, PA 18036 U.S.A. Switched Output: 100-277
G 2 CB
144-317 Rev. 1.9

Ratings ®

Load Type Switched


Incandescent
Fluorescent
16A
5A
Control
GRX-TVI Input Rating enclosure, indoor use only). See System Wiring Layout below.
n The environment where the GRX-TVI is placed must have an
Magnetic Low-voltage 16A IH2 0.02A
IDH2 0.1A
Electronic Low-voltage 16A
Neon/Cold Cathode 16A 0-10V Output Rating
Motor 1/4 HP@120V Max. 0.3A Class 2
1/2 HP@277V

Ratings ✔ ACN

Load Type Switched


Switched µ
003 715 277

Control
GRX-TVI Input Rating
ambient temperature range of 32—104 °F (0—40 °C).
n Mount the enclosure vertically on a wall (screws not provided). See
10A
IH2 0.02A
5AX IDH2 0.1A
10A
0-10V Output Rating
10A
Max. 0.3A PELV
10A

Mounting Diagram below.


n Mounting method must be able to support weight and forces
applied during installation.
n Iinternal relays will click while in operation — mount where
audible noise is acceptable.

Description
The GRX-TVI provides 0-10V control and ballast switching capabili- System Wiring Layout
ties in one enclosure. The GRX-TVI gives GRAFIK Eye 3000 Series 0-10V Control Fluorescent Zone/Load 1
Control Units the ability to control any 0-10V ballasts powered by
0-10V Ballast
100V-277V (ballast must provide 0-10V sourcing of current) 0-10V Control Fluorescent Zone/Load 1
and provides switching relays that can handle the in-rush current for a
0-10V Ballast
circuit of ballasts. The GRX-TVI gives a GRAFIK Eye 3000 Series
Control Unit the ability to both dim and switch electronic ballasts, Ballast
such as Lutron's Eco-10 ™ (TVE models). The GRX-TVI can also be Switched Fluorescent Zone/Load 2
used to switch any of the load types listed below.
GRX- GRX-
TVI TVI

Product Specifications Incandescent Zone/Load 3

FEATURES.....................Provides a Class 2/PELV isolated 0-10V output signal that


conforms to EN60929 and IEC60929 Power from
Accepts a constant-gate drive fluorescent signal (100-127V, Distribution
Panel
220-240V, 50/60Hz) LUTRON
LUTRON LUTRON

INPUT POWER RATING ................100-127/220-240V, 50/60Hz Control Unit Class 2/PELV Accessory Controls

H2/L2 TERMINAL.........................20mA
INPUT RATING
Note: When using a Control Unit, a GRX-TVI is required for each 0-10V
DH2/DL2 TERMINAL.....................100mA fluorescent zone. (A 3-zone Control Unit with two fluorescent zones
INPUT RATING and one incandescent zone is shown as an example.)
0-10V OUTPUT RATING ...............10µA-300mA - Sinks current only (maximum 150
ballasts)
Mounting Diagram
100-127V/
Source/Load Type 230V (CE) Four Mounting Holes Four Screws
200-277V
FourDiameter
Mounting- Holes
0.25 in. (6mm) Secure Cover
Four Screws Secure Cover
Fluorescent: Diameter: 0.25 in. (6 mm)

Lutron Eco-10T 16A
(TVE Series)
Electronic Capacitive 10A 16A
Non-Dim ®
GRX-TVI
0-10V INTERFACE CONTROL
Control Input:

10A
100-120V, 220-240V 50/60Hz

Other Manufacturer’s 0-10V


COOPERSBURG, PA 18036 U.S.A. Switched Output: 100-277

16A
G 2 CB
144-317 Rev. 1.9

Ratings
Ballasts (0-10V source only)
®

Load Type Switched


Incandescent 16A Control
GRX-TVI Input Rating

Incandescent 10A 16A


Fluorescent
Magnetic Low-voltage
Electronic Low-voltage
Neon/Cold Cathode
5A
16A
16A
16A
IH2 0.02A
IDH2 0.1A

0-10V Output Rating


Motor 1/4 HP@120V Max. 0.3A Class 2
1/2 HP@277V

Low-Voltage 10A 16A Ratings ✔ ACN


003 715 277
Load Type Switched
Switched µ Control

Metal Halide 10A 11.75 in.


11.75 in. 10A
GRX-TVI Input Rating
IH2 0.02A
12.5 in.
12.50 in. Wall
16A
5AX IDH2 0.1A

(318 mm)
mm)
10A

(298 mm)
(298 mm) 10A
0-10V
Max. 0.3A
Output Rating
PELV (318
WALL
10A

Neon/Cold Cathode 10A 16A


Motors 1/4HP @ 100-120V
1/2HP @ 200-277V
1/2HP @ 230V CE

TERMINALS Two #12-20AWG (0.5-2.5 mm2) conductors per terminal.


MOUNTING NEMA Type 1 enclosure, indoor use only.
Italiano

ENVIRONMENTAL 32—104 ˚F (0—40 ˚C). 4.0 in.


4.0 in. 3.30 in.
3.30 in.
(102 mm)
(102 mm) (84 mm)
WEIGHT 4.25 lb. (2kg) (84 mm)
6.10 in.
6.10
(155 mm)
(155 mm)
220-240V/CE Control Interface
Important Installation Information
 Install in accordance with all national and local electrical codes.
 Check for short circuited loads during new installations before wiring the GRX-TVI.
Caution: Multiple feeds may enter this enclosure. Locate and lock each feed circuit breaker/MCB in the OFF position
before wiring the Interface.

 Proper short circuit and overload protection must be provided at the distribution panel. You can use up to a 20A (16A for CE)
maximum circuit breaker/MCB or equivalent (tripping curve C according to IEC 898/EN60898 is recommended) with adequate
short circuit breaking capacity for your installation.
 Terminal blocks are rated for two #12-22 AWG (0.5-2.5 mm2) wires per terminal.
 Strip 3/8 in. (10 mm) of insulation from wires.
 Wiring Diagram A shows a GRX-TVI wired from one distribution panel. If the 10mm
power requirement of the complete system is less than an MCB/circuit (3/8in.)
breaker rating, one feed can be jumpered inside the enclosure (as shown).
 Wiring Diagram B shows a GRX-TVI wired from two separate distribution panels that may be different phases or voltages.
 Use the internal terminal block label to see where to land wires.

L2/H2 220-240V/CE
L2/H2 100-127V

L1/H1 100-277V
— The label shows two separate Hot/Live terminals (L1/H1 & L2/H2).

0-10 Volt
L1/H1 is the Hot/Live feed to power the lighting load.

DL2/DH2

SL1/SH1
L2/H2 is the Hot/Live feed that powers internal circuitry of the GRX-
TVI.
L2/H2 has a 100-127V connection and a 220-240V connection - use

N2

N1
N1
Use only if
only the one corresponding to line voltage for your application. your
line/mains
Note 1: Not all terminal blocks receive a connection. voltage is
220-240V. Input from distribution
Note 2: The power feed to the Control Unit and L2/H2 of the GRX- panel.
TVI must be the same phase! Use only if your line/mains voltage is
Class 2/PELV, 0-10V wiring from a ballast to the GRX-TVI- 120-127V.
CE must be separated from the power wiring. Enter the
Class 2/PELV wires through the knockout adjacent to the 0-10V terminal blocks. The Nomex® barrier ensures
separation and is flexible to allow access to the terminals. The barrier must be in place when installation is
complete.

GRX-TVI Internal Terminal Block Label Definitions

Use only one input according to Input Voltage:


L2/H2 240V Power input for GRX-TVI control (line/mains voltage must be 220-240V)
L2/H2 127V Power input for GRX-TVI control (line/mains voltage must be 100-127V)
N2 Neutral for GRX-TVI control
DL2/DH GRAFIK Eye 3000 Series Control Unit Lighting Zone connection (Phase Control Input to GRX-TVI)
L1/H1 Power input for lighting load
N1 Neutral for lighting load (2 terminals provided and internally tied together — one for input neutral and one
for load neutral)
SL1/SH1 Switched output to power lighting load
+ - 0-10V control signal wires (ballast must provide a 0-10V source only)

2
Wiring Diagram A: 220-240V/CE GRX-TVI — 1 Distribution Panel
GRX-TVI

Line/Mains Voltage:
220-240V

L2/H2 100-120V
L2/H2 220-240V

0-10 Volt
DL2/DH2

SL1/SH1
L1/H1
N2

N1
N1
220- 100- N2 DL2/DH2 L1/H1 N1 N1 SL1/SH1 + –
240V 127V 100-
L2/H2 277V 0-10V
Control Inputs Load Switched Max 0.3A

L2/H2 220-240V/CE
L2/H2 100-127V

L1/H1 100-277V
NEUTRAL

0-10 Volt
EARTH/GROUND

L2/H2 is the Hot/Live feed that powers


CONNECTIONS

0-10V Control Signal Wires - DO NOT

DL2/DH2

SL1/SH1
the internal circuitry of the GRX-TVI. CONNECT TO LINE VOLTAGE. Lutron is not
liable for damage due to miswiring.
Use L2/H2 220-240V/CE only if your

N2

N1
N1
line/mains voltage is 220-240V.

+
SL1/SH1 0-10V Ballast
N1

220-240V Earth/Ground
GRX-3000
Switched Hot/Live
Dimmed Hot/Live
Neutral

Neutral
+
LUTRON Hot/Live EARTH/GROUND SL1/SH1 0-10V Ballast
N1
CONNNECTIONS
Earth/Ground
Hot/Live
Use 20A (16A CE) maximum
circuit breaker/MCB To additional ballasts
Distribution Neutral
N
Panel
Earth/Ground

Wiring Diagram B: 220-240V/CE GRX-TVI — 2 Distribution Panels


GRX-TVI

Line/Mains Voltage:
220-240V
L2/H2 100-120V
L2/H2 220-240V

0-10 Volt
DL2/DH2

SL1/SH1
L1/H1
N2

N1
N1

220- 100- N2 DL2/DH2 L1/H1 N1 N1 SL1/SH1 + –


240V 127V 100-
L2/H2 277V 0-10V
Control Inputs Load Switched Max 0.3A
L2/H2 220-240V/CE
L2/H2 100-127V

L1/H1 100-277V

NEUTRAL
0-10 Volt

EARTH/GROUND
CONNECTIONS

L2/H2 is the Hot/Live feed that powers 0-10V Control Signal Wires - DO NOT
DL2/DH2

SL1/SH1

CONNECT TO LINE VOLTAGE. Lutron is not


the internal circuitry of the GRX-TVI. liable for damage due to miswiring.
Use L2/H2 220-240V/CE only if your
N2

N1
N1

line/mains voltage is 220-240V.



+
SL1/SH1 0-10V Ballast
N1

220-240V Earth/Ground
GRX-3000 Switched Hot/Live
Dimmed Hot/Live
Neutral
Neutral –
+
LUTRON
Hot/Live EARTH/GROUND SL1/SH1 0-10V Ballast
N1
CONNNECTIONS
Earth/Ground
Hot/Live
Use 20A (16A CE) maximum
circuit breaker/MCB To additional ballasts
Distribution Neutral
N
Panel
Earth/Ground Note: Ballast must provide a 0-10V
source only!
Hot/Live
Distribution Neutral
N
Panel
Earth/Ground

3
100-127V Control Interface
Important Installation Information
 Install in accordance with all national and local electrical codes.
 Check for short circuited loads during new installations before wiring the GRX-TVI.
Caution: Multiple feeds may enter this enclosure. Locate and lock each feed circuit breaker/MCB in the OFF position
before wiring the Interface.

 Proper short circuit and overload protection must be provided at the distribution panel. You can use up to a 20A (16A for CE)
maximum circuit breaker/MCB or equivalent (tripping curve C according to IEC 898/EN60898 is recommended) with adequate
short circuit breaking capacity for your installation.
 Terminal blocks are rated for two #12-22 AWG (0.5-2.5 mm2) wires per terminal.
 Strip 3/8 in. (10 mm) of insulation from wires.
 Wiring Diagram C shows a GRX-TVI wired from one distribution panel. If the
10mm
power requirement of the complete system is less than an MCB/circuit (3/8in.)
breaker rating, one feed can be jumpered inside the enclosure (as shown).
 Wiring Diagram D shows a GRX-TVI wired from two separate distribution panels that may be different phases or voltages.
 Use the internal terminal block label to see where to land wires.

L2/H2 220-240V/CE
L2/H2 100-127V

L1/H1 100-277V
— The label shows two separate Hot/Live terminals (L1/H1 & L2/H2).

0-10 Volt
L1/H1 is the Hot/Live feed to power the lighting load.

DL2/DH2

SL1/SH1
L2/H2 is the Hot/Live feed that powers internal circuitry of the GRX-
TVI.
L2/H2 has a 100-127V connection and a 220-240V connection - use

N2

N1
N1
Use only if
only the one corresponding to line voltage for your application. your
line/mains
Note 1: Not all terminal blocks receive a connection. voltage is
220-240V. Input from distribution
Note 2: The power feed to the Control Unit and L2/H2 of the GRX- panel.
TVI must be the same phase! Use only if your line/mains voltage is
Class 2/PELV, 0-10V wiring from a ballast to the GRX-TVI- 120-127V.
CE must be separated from the power wiring. Enter the
Class 2/PELV wires through the knockout adjacent to the 0-10V terminal blocks. The Nomex® barrier ensures
separation and is flexible to allow access to the terminals. The barrier must be in place when installation is
complete.

GRX-TVI Internal Terminal Block Label Definitions

Use only one input according to Input Voltage:


L2/H2 240V Power input for GRX-TVI control (line/mains voltage must be 220-240V)
L2/H2 127V Power input for GRX-TVI control (line/mains voltage must be 100-127V)
N2 Neutral for GRX-TVI control
DL2/DH GRAFIK Eye 3000 Series Control Unit Lighting Zone connection (Phase Control Input to GRX-TVI)
L1/H1 Power input for lighting load
N1 Neutral for lighting load (2 terminals provided and internally tied together — one for input neutral and one
for load neutral)
SL1/SH1 Switched output to power lighting load
+ - 0-10V control signal wires (ballast must provide a 0-10V source only)

4
Wiring Diagram C: 100-127V GRX-TVI — 1 Distribution Panel
GRX-TVI

Line/Mains Voltage:
120-127V

L2/H2 100-120V
L2/H2 220-240V

0-10 Volt
DL2/DH2

SL1/SH1
L1/H1
N2

N1
N1
220- 100- N2 DL2/DH2 L1/H1 N1 N1 SL1/SH1 + –
240V 127V 100-
L2/H2 277V 0-10V
Control Inputs Load Switched Max 0.3A

L2/H2 220-240V/CE
L2/H2 100-127V

L1/H1 100-277V
NEUTRAL

L2/H2 is the Hot/Live feed that powers

0-10 Volt
EARTH/GROUND
CONNECTIONS

the internal circuitry of the GRX-TVI. 0-10V Control Signal Wires - DO NOT

DL2/DH2

SL1/SH1
CONNECT TO LINE VOLTAGE. Lutron is not
Use L2/H2 100-127V only if your liable for damage due to miswiring.
line/mains voltage is 120-127V.

N2

N1
N1

+
SL1/SH1 0-10V Ballast
N1

120-127V Earth/Ground
GRX-3000
Switched Hot/Live
Dimmed Hot/Live
Neutral

Neutral
+
LUTRON Hot/Live EARTH/GROUND SL1/SH1 0-10V Ballast
N1
CONNNECTIONS
Earth/Ground
Hot/Live
Use 20A (16A CE) maximum
circuit breaker/MCB To additional ballasts
Distribution Neutral
N
Panel
Earth/Ground Note: Ballast must provide a 0-10V
source only!

Wiring Diagram D: 100-127V GRX-TVI — 2 Distribution Panels


GRX-TVI

Chinese
Line/Mains Voltage:
120-127V
L2/H2 100-120V
L2/H2 220-240V

0-10 Volt
DL2/DH2

SL1/SH1
L1/H1
N2

N1
N1

220- 100- N2 DL2/DH2 L1/H1 N1 N1 SL1/SH1 + –


240V 127V 100-
L2/H2 277V 0-10V
Control Inputs Load Switched Max 0.3A
L2/H2 220-240V/CE
L2/H2 100-127V

L1/H1 100-277V

NEUTRAL

L2/H2 is the Hot/Live feed that powers


0-10 Volt

EARTH/GROUND
CONNECTIONS

0-10V Control Signal Wires - DO NOT


the internal circuitry of the GRX-TVI.
DL2/DH2

SL1/SH1

CONNECT TO LINE VOLTAGE. Lutron is not


Use L2/H2 100-127V only if your liable for damage due to miswiring.
line/mains voltage is 120-127V.
N2

N1
N1


+
SL1/SH1 0-10V Ballast
N1

120-127V Earth/Ground
GRX-3000 Switched Hot/Live
Dimmed Hot/Live
Neutral
Neutral –
+
LUTRON
Hot/Live EARTH/GROUND SL1/SH1 0-10V Ballast
N1
CONNNECTIONS
Earth/Ground
Hot/Live
Use 20A (16A CE) maximum
circuit breaker/MCB To additional ballasts
Distribution Neutral
N
Panel
Earth/Ground

Hot/Live
Distribution Neutral
N
Panel
Earth/Ground

5
Operation
After wiring is complete, supply power to the GRX-TVI to check for proper operation.
■ With the cover removed, an LED will provide visual feedback about the operation of the system.

■ When power is first applied, the LED will turn on for 8 seconds to indicate start-up mode and then start to flash in one of two ways to
indicate the status of the system:
1. Standard Operation
■ The LED will flash at a rate of twice per second to signify proper communication between the Control Unit and the Interface.

2. Incorrect Operation - No Active Input


■ The LED will repeatedly turn on for 1 second then off for 1 second to indicate that there is not an active phase control input to the GRX-
TVI. Make sure that the phase control dimmer is ON and connected to the GRX-TVI at the terminal block marked DL2/DH2. Check that
the corresponding zone for the DL2/DH2 terminal is ON and the light level is not set at the minimum output.
■ When the LED indicates proper input of a phase control signal, then the output can be checked by looking at the load and checking operation
from the Control Unit.
■ For non-dimming ballasts, select non-dim load type on the GRAFIK Eye Control Unit and do not connect ballasts to 0-10V terminals.

Make sure that the Control Unit is set for Fluorescent Load Type. (Refer to GRAFIK Eye 3000 Series Installer's Guide.) If the load
type is not set correctly, proper dimming will not occur.

Troubleshooting
Symptom Possible Cause Solution
0-10V Ballast does not dim or control Miswire Verify that LED pulses twice per second. If not, check wiring from phase control unit to the Interface.
unit to the Interface.
Power is OFF Make sure that the GRAFIK Eye 3000 Series Control Unit is ON.

Miswire Check for proper polarity of 0-10V signals at terminal blocks. Does it match what is at every ballast? A
miswire at any ballast will cause all ballasts to go to the low end.

Incorrect Control Setup GRAFIK Eye 3000 Series Control Unit is not configured for fluorescent load type.

Light does not switch on Miswire Check that the SL1/SH1 connection goes to the ballasts.

Miswire Check that the DL2/DH2 connection is actually wired to a phase control input.

Light does not switch off Miswire Load is not connected to SH (SL) terminal.

Miswire Check that the DL2/DH2 connection is actually wired to a phase control input.

LED is not illuminated No Power Input Check that power is applied to the Interface.

Internet: www.lutron.com FRANCE LIMITED WARRANTY


E-mail: product@lutron.com Lutron LTC Lutron will, at its option, repair or replace any unit that is defective in materials or
International +33-1-44-70-72-00 manufacture within one year after purchase. For warranty service, return unit to place of
WORLD HEADQUARTERS Int’l Fax: +33-1-44-70-00-19 purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-
Lutron Electronics Co. Inc., paid.
TOLL FREE: (800) 523-9466 ASIAN HEADQUARTERS This warranty is in lieu of all other express warranties, and the implied
(U.S.A., Canada, Caribbean) Lutron Asuka Corporation (Japan) warranty of merchantability is limited to one year from purchase. This
Tel: (610) 282-3800; Tel:(03)-5575-8411; warranty does not cover the cost of installation, removal or reinstallation, or
International (03)-5575-8411 damage resulting from misuse, abuse, or improper or incorrect repair, or
International +1- 610-282-3800
damage from improper wiring or installation. This warranty does not cover
Fax: (610) 282-1243; Fax: +(03) -5575-8420; incidental or consequential damages. Lutron’s liability on any claim for
International +1-610-282-1243 International +81-3-5575-8420 damages arising out of or in connection with the manufacture, sale,
HONG KONG SALES OFFICE installation, delivery, or use of the unit shall never exceed the purchase price
EUROPEAN HEADQUARTERS of the unit.
Lutron EA Ltd., Lutron GL (Hong Kong) This warranty gives you specific legal rights, and you may also have other rights which vary
Tel: (207) 702-0657; Tel: 2104-7733; from state to state. Some states do not allow limitations on how long an implied warranty
International +44-207-702-0657 International +852-2104-7733 lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or
Fax: (207) 480-6899; Fax: 2104-7633; limitation of incidental or consequential damages, so the above limitation or exclusion may
International +44-207-480-6899 International +852-2104-7633 not apply to you.
Nomex is a registered trademark of E.I. Du Pont de Nemours and Company.
GERMANY SINGAPORE Lutron and GRAFIK Eye are registered trademarks; Eco-10 is a trademark of Lutron
Lutron Electronics GmbH Lutron GL (Singapore) Electronics Co., Inc.
Tel: (309) 710-4590; Tel: +65-6220-4666 © 2003 Lutron Electronics Co., Inc.
International +49-309-710-4590 Fax: +65-6220-4333
Fax: (309) 710-4591;
International +49-309-710-4591

Lutron Electronics Co., Inc.


Made and printed in U.S.A. 8/03
P/N 032-119 Rev. B

S-ar putea să vă placă și