Documente Academic
Documente Profesional
Documente Cultură
CHAPTER 3
EXPERIMENTAL PROGRAMME
3.1 INTRODUCTION
Figure 3.1a and Figure 3.1b show the details of the lipped cold
formed I- hw
bf bl tf
tl o centre of the upper and lower flanges;
d d
a
b c
tw
dmax
31
17 TCAR-1800-300-100-5 240 42.42 60.00 21.21 45 1.2 300 100 2 15 2 1800 4.0
Aspect
Sl. a b c d t h b t b t L
Specimen ID Ratio
No. mm mm mm mm mm mm mm mm mm mm mm
Aspect
Sl. a b c d t h b t b t L b /t
Specimen ID Ratio
No. mm mm mm mm mm mm mm mm mm mm mm Ratio
1 TCL-1000-400-150-1 60 42.42 60 21.21 45 1.2 400 150 2 15 2 1000 1.0 75
2 TCL-2000-400-150-2 60 42.42 60 21.21 45 1.2 400 150 2 15 2 2000 1.0 75
3 TCL-3000-400-150-3 60 42.42 60 21.21 45 1.2 400 150 2 15 2 3000 1.0 75
36
Tensile specimens were taken from the steel sheets and tested
according to IS 1663 1960 part I.
Totally six specimens were fabricated (Figure 3.3). Tensile test was
conducted in a universal tensile machine of 400 kN capacity. Test setup is
shown in the Figure 3.4. Stress Vs Strain plots are drawn (Figure 3.7 to Figure
3.12). The test results are presented in Table 3.6.
38
Figure 3.3 Specimens for Coupon Test Figure 3.4 Tensile Test Setup
Figure 3.5 Specimen before Test Figure 3.6 Specimen after Test
Figure 3.7 Stress Vs Strain curve for 1.2mm thickness plate C-1.2-1
39
Figure 3.8 Stress Vs Strain curve for 1.2mm thickness plate C-1.2-2
Figure 3.9 Stress Vs Strain curve for 1.2mm thickness plate C-1.2-3
40
Figure 3.10 Stress Vs Strain curve for 2.0mm thickness plate C-2-1
Figure 3.11 Stress Vs Strain curve for 2.0mm thickness plate C-2-2
41
Figure 3.12 Stress Vs Strain curve for 2.0mm thickness plate C-2-3
Average
Average
Specimen Yield Stress
Modulus Yield Stress
Details Modulus
2 2
( N/mm ) ( N/mm ) (N/mm2 ) (N/mm2 )
C-1.2-1 1.99 × 105 269
C-1.2-2 1.97 × 105 240 2.04 × 105 252.00
C-1.2-3 2.15 × 105 247
C-2-1 2.03 × 105 262
C-2-2 1.98 × 105 238 2.11 × 105 247.00
C-2-3 2.31 × 105 241
500 kN loading frame. The test set up and schematic diagram are shown in
Figure 3.13 and Figure 3.14 respectively. A load cell was used to monitor the
applied load. Two point loads were applied at l/3 distance from each end. To
avoid the lateral displacement and tilting of the specimen, lateral clamping of
web was made at the supports of the specimen. The beams were tested with
hinged support at one end and roller support at the other end. To measure the
displacements, , at mid span, at loading point under bottom flange,
and at mid span of top flange laterally on the lip, were positioned. The load
specimens were loaded till the specimen became unstable and load started
decreasing. The results are presented in Table 3.7 to Table 3.11.
The test results for TCAR series are presented in Table 3.7. In the
TCAR series aspect ratio is varied. Aspect ratio is the ratio between
horizontal panel to the inclined panel of trapezoidal corrugation.
40
30
Load (kN)
20
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCAR-3000-300-100-1 TCAR-3000-300-100-2
TCAR-3000-300-100-4 TCAR-3000-300-100-3
60
50
40
Load (kN)
30
20
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCAR-3600-400-150-1 TCAR-3600-400-150-2
TCAR-3600-400-150-4 TCAR-3600-400-150-3
50
40
30
Load (kN)
20
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCAR-1800-200-100-1 TCAR-1800-200-100-2
TCAR-1800-200-100-3 TCAR-1800-200-100-4
buckling of the flange occurs earlier in that zone. But, when the aspect ratio is
1, the inclined panel and the horizontal panel width are same and the flange
out-stand area is the least and the flange is more stiffened than the other, the
effective width is more and the local buckling in the compression flange is
delayed. From the Load versus mid span deflections of all TCAR series, it is
observed that when the aspect ratio is 1, it has more stiffness.
60
50
40
Load (kN)
30
20
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCAR-1800-300-100-2 TCAR-1800-300-100-3
TCAR-1800-300-100-4 TCAR-1800-300-100-1
TCAR-1800-300-100-5
The test results for TCA series are given in Table 3.8. In the TCA
series corrugation angle is varied. Corrugation angle is the angle made by the
inclined panel with horizontal panel. For TCA-3000-300-100 series, the
corrugation ratio varies from 15º to 60º with an increment of 15º. TCA-3000-
300-100-1 specimen failed under local buckling in top flange nearer to the
loading point in shear zone and finally interaction between local and flexure
buckling occurred. TCA-3000-300-100-2 and TCA-3000-300-100-3
specimens failed with a initiation of local buckling of top flange nearer to
loading in the pure bending zone and then led to lateral buckling of top flange
at failure.
52
Corrug
Test ation MExp
Specimen ID Failure Mode
No. angle in kNm
degrees
Local Buckling in the top compression
1 TCA-3000-300-100-1 15º 14.90 flange near the loading point+ Flexural
buckling
Local Buckling in top compression
2 TCR-3000-300-100-2 30º 16.20 flange nearer to the loading point +
Lateral Buckling
Local Buckling nearer to loading point
3 TCR-3000-300-100-3 45º 16.82 in top compression flange + Lateral
Buckling
Local Buckling nearer to loading point
4 TCR-3000-300-100-4 60º 18.05 in top compression flange + Lateral
Buckling
Local Buckling in the web at shear
5 TCR-3600-400-150-1 0º 25.06
Zone + Lateral Buckling
Local Buckling in middle of top
6 TCR-3600-400-150-2 15º 26.24 compression flange + Lateral Buckling
of Compression Flange
Local Buckling in middle of top
7 TCR-3600-400-150-3 30º 27.14 compression flange + Lateral Buckling
of Compression Flange
Local Buckling in top compression
8 TCR-3600-400-150-4 45º 28.71 flange nearer to loading point + Lateral
Buckling of Compression Flange
Local Buckling in top compression
TCR-3600-400-150-5 60º 31.32 flange nearer to loading point + Lateral
9
Buckling of Compression Flange
Local Buckling in top compression
flange at middle of the shear zone +
10 TCR-3600-400-150-6 75º 32.36
Lateral Buckling of Compression
Flange
Local Buckling at top compression
11 TCR-3600-400-150-7 90º 32.89 flange nearer to the support + Flexural
Buckling of Compression Flange
53
40
35
30
25
Load (kN)
20
15
10
5
0
0 5 10 15 20
Midspan Deflection (mm)
TCA-3000-300-100-1 TCA-3000-300-100-2
TCA-3000-300-100-3 TCA-3000-300-100-4
corrugation angle increases the flange out-sand on one side which decreases
the effective width of the flange. Therefore, further improvement in moment
capacity is less. So, increase in corrugation angle beyond 60º does not show
any notable increase in the moment capacity. The increase in corrugation
angle increases the depth of corrugation or the flange out-stand on one side,
which in turn increases the moment of inertia about the minor axis(I y). This
increase in moment of inertia about the minor axis (Iy) increases the resistance
to the lateral torsional buckling;that is why, the moment capacity increases
with increase in corrugation angle. Load Vs mid span deflection curves are
plotted for the TCA-3000-300-100 series specimen (Figure 3.42). The failure
shapes are shown in Figures 3.43 to 3.49.
60
50
40
Load ( kN)
30
20
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCA-3600-400-150-3 TCA-3600-400-150-4 TCA-3600-400-150-2
TCA-3600-400-150-1 TCA-3600-400-150-5 TCA-3600-400-150-6
TCA-3600-400-150-7
The test results for TCDW series are given in Table 3.9. In the
TCDW series, web slenderness is varied. Web slenderness is the ratio
between depth of web hw to thickness of web tw. For TCDW-1800 series, the
web slenderness (h w/tw ratio) varies from 104.17 to 166.67. TCDW-1800-125-
100-1 and TCDW-1800-150-100-2 specimens failed with initiation of local
buckling in top flange in pure bending zone and finally failed under flexure
buckling. TCDW-1800-175-100-3 and TCDW-1800-200-100-4 specimen
failed initially with local buckling in top flange in the middle of the pure
bending zone and finally led to lateral buckling of the top flange. The
specimen without corrugation TCDW-1800-200-100-5 specimen failed
initially with local buckling of web in shear zone and finally failed with
lateral buckling of compression flange. It is found that the moment carrying
capacity of corrugated web is 20 % more than flat web. It is known that as
the depth of web increases, the moment of inertia also increases. Hence, there
was a significant increase in moment capacity was noted with increase in web
slenderness.
58
Table 3.9(Continued)
Stiffness of corrugated web is more than the flat web. Load Vs mid
span deflection curves are plotted for the TCDW-1800 series specimen
(Figure 3.50). The failure shapes are shown in Figures 3.51 to 3.55.
Figure 3.50 shows that as the depth of the web increases, the initial stiffness
of the member also increases.
60
30
25
20
Load (kN)
15
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCDW-1800-125-100-5 TCDW-1800-150-100-4
TCDW-1800-175-100-3 TCDW-1800-200-100-2
TCDW-1800-200-100-1
Figure 3.50 Load Vs Deflection curves at mid span for TCDW-1800 series
60
50
40
Load (kN)
30
20
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCDW-2000-200-100-1 TCDW-2000-250-100-2
TCDW-2000-300-100-3 TCDW-2000-350-100-4
Figure 3.56 Load Vs Deflection curves at mid span for TCDW-2000 series
62
70
60
50
Load (kN)
40
30
20
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCDW-3000-200-100-1 TCDW-3000-300-100-2
TCDW-3000-350-100-3 TCDW-3000-400-100-4
TCDW-3000-450-100-5 TCDW-3000-500-100-6
TCDW-3000-550-100-7 TCDW-3000-600-100-8
Figure 3.61 Load Vs Deflection curves at mid span for TCDW-3000 series
but after 500, the stiffness of the specimen is lesser compared to the specimen
with web slenderness 583.33.
80
70
60
50
Load (KN)
40
30
20
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCDW-3600-400-100-1 TCDW-3600-500-100-2
TCDW-3600-600-100-3 TCDW-3600-700-100-4
Figure 3.70 Load Vs Deflection curves at mid span for TCDW-3600 series
The test results for TCFW series are given in Table 3.10. In the
TCFW series flange width to thickness ratio (b f/tf) is varied.
25
20
15
Load (kN)
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCFW-1800-150-60-1 TCFW-1800-150-75-2
TCFW-1800-150-90-3 TCFW-1800-150-105-4
Figure 3.75 Load Vs Deflection curves at mid span for TCFW-1800 series
68
lateral buckling. As the flange width ratio increases, the flange area increases
or value of Iy also increases. Due to this, lateral buckling of top compression
flange is eliminated and moment capacity also increases with increase in
flange width ratio.
30
25
20
Load (kN)
15
10
0
0 5 10 15 20
Midspan Deflection (mm)
TCFW-1050-100-80-2 TCFW-1050-100-100-3
TCFW-1050-100-120-4 TCFW-1050-100-70-1
Figure 3.80 Load Vs Deflection curves at mid span for TCFW-1050 series
The test results for TCL series are given in Table 3.11. In the TCL
series, length of the beam is varied from 1000 to 3600. TCL-1000-400-150-1
and TCL-2000-400-150-2 specimens failed due to initiation of local buckling
in top flange in the mid span of pure bending zone and led to flexural
buckling.TCL-3000-400-150-3 specimen failed due to initiation of local
buckling in top flange in middle of the pure bending zone and then led to
lateral buckling of top flange.
140
120
100
Load (kN)
80
60
40
20
0
0 5 10 15 20
Midspan Deflection (mm)
TCL-2000-400-150-2 TCL-3000-400-150-3
TCL-3600-400-150-4 TCL-1000-400-150-1
Figure 3.85 Load Vs Deflection curves at mid span for TCL series
The moment capacities have also been predicted using the current
specifications of the Australian/New Zealand standard AS/NZS-4600:2005
for cold-formed steel structures and North American Specification AISI-
S100:2007 for the design of Cold-Formed steel structural members
specifications
Table 3.12 compares the moment capacity from the tests and
various design standards. The mean and Standard deviation for the ratios of
test results to the predicted results were also calculated.
A comparison was carried out between the test results (MExp) and
the predicted moment capacity using IS method (IS-801:1975) (MIS). The
mean and standard deviation of the experiment to IS moment capacity are
73
From Table 3.12, it can be seen that the ultimate moment capacity
calculated using the AS/NZ specification and AISI specification are
unconservative for all specimens except TCAR-3000-300-100-4, TCDW-
1800-200-100-4, TCDW-2000-200-100-1, TCFW-1050-100-100-3 and TCL-
3600-400-150-4. The ultimate moment capacity calculated using the IS-
801:1975 specification is unconservative for all series and also it is more
unconservative thanAS/NZ specification and AISI specification.
3.8 CONCLUSION