Documente Academic
Documente Profesional
Documente Cultură
net/publication/275463636
CITATIONS READS
0 1,525
4 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Pankaj Kumar on 26 April 2015.
IJEEMF
www.ijeemf.com
1
International Journal of Electronics, Electrical and Mechanical Fundamentals, (Vol. 16, Issue 01), August 2014
www.ijeemf.com (An Indexed, Referred and Impact Factor Journal) ISSN: 2278-3989
protection. At 11kV voltage level, there are magnitude of generated third harmonic voltage
equipment like generators, motors, transformers [2] is
and feeders along with a large network of 11kV U3=1.44+4.22 (Ia/In) – 2.72 (If/Ifn)
cable length, spread to different plate forms, Where U3 (%) – is the measured third
introducing significant capacitive charging harmonic voltage,
current, which could be of the order of 20A to Ia (Amp)-Armature current
200A [1]. Thus, low resistance grounding is an In (Amp) – Rated armature current,
option, considered for further analysis. If – is calculated field current
Ifn – is the calculated field current at rated output
2.1 Winding Pitch of Generator power
In off-shore installation, space and weight of
The winding pitch of generator could be 2/3rd or equipment are important for plate form design,
5/6th; however both contribute to 3rd harmonic unlike the onshore plant where horizontal
voltage, displaced by 3600 (electrical placement of sub-system is not a concern.
degrees). Industry always prefers a proven designed
generator. Reducing the winding pitch to 2/3rd
reduces 3rd harmonic, however rotor pole surface
loss is increased by 6 times approx. and
generator output reduced by 15%. Therefore for
same output, generator size needs to be
increased, which requires more space & weight
at plate form, having impact on the overall plate
form design. For a typical 32MVA generator
with 5/6th winding pitch, the 3rd harmonic
content is as follows:-
Phase to neutral Voltage is 2.97% and
Phase to phase voltage is 0.06%.
Hence, for proven standard generator, the
manufacturer offers an optimum designed
generator with 5/6th winding pitch.
IJEEMF
www.ijeemf.com
2
International Journal of Electronics, Electrical and Mechanical Fundamentals, (Vol. 16, Issue 01), August 2014
www.ijeemf.com (An Indexed, Referred and Impact Factor Journal) ISSN: 2278-3989
IJEEMF
www.ijeemf.com
3
International Journal of Electronics, Electrical and Mechanical Fundamentals, (Vol. 16, Issue 01), August 2014
www.ijeemf.com (An Indexed, Referred and Impact Factor Journal) ISSN: 2278-3989
core damage by using NER of 10A, 10sec cannot be achieved due to temperature class
however, low resistance grounding (LRG) is also limitation (T4=2000C), while NER temperature
used in off-shore installation where Ico is high. can be up to 7600C [6]. In that scenario, 3 no
Due to 60A capacitive charging current, HRG is NER along with 2 no NET are to be placed in
not recommended. safe area. Generator neutral is earthed through
Low resistance grounding (LRG) through NER - 10A, 10sec NER with breaker for NER switch-
Higher fault current is good for sensitive & in/off (fig-3). During normal operation, only one
selective relaying, limiting transient over- NET with loading resistor has to be kept in
voltages to moderate values, and a potential cost service while Generator NERs are kept switched-
savings over other grounding methods. However, off.
the main drawback is the possibility of
significant burning of the generator stator core
(Refer Fig-2). In addition, because of IP54 and
generator core guarantee for 60A fault current,
this scheme is found not suitable as illustrated
above (Refer 2.2). There are a certain issues,
which needs a particular attention-
1. While using low resistance grounding it is
recommended to have single NET/NER in
service at a time, to reduce 3rd harmonic
circulating current flow. So, with bus-
coupler in closed condition (refer fig-1),
only one NET should be in service and Fig-3 – Earthing scheme with LRG & HRG
others in switch-off condition. When bus-
coupler is off, then both NET should be in
service. In addition, there should not be
parallel grounding of generators. Parallel
grounding means generators shown in fig-1
are having their NERs in service.
2. Even though there is no parallel grounding,
there will still be capacitive leakage currents
at 11kV voltage level due to generators and
large network of 11kV cable length to
motors, service transformers and feeders,
spread to various plate forms. This current Fig-4 Earthing scheme with NET & loading
will flow through the generator neutral resistor at 11kV
earthing resistor. Thus, for a ground fault in
the stator winding occurring together with Under bus-coupler closed condition, second NET
low resistance grounding, the stator core should be off (fig-1 & fig-4). Prior to
will be severely damaged (fig-2). synchronization or under complete load throw
In view of above, Hybrid grounding is a better scenario of a generator, the corresponding NER
option, combining best features of both low should be put into service (refer fig-3) as GCB is
resistance and high resistance grounding opened to check the over-voltage condition due
methods [2]. This requires 3 no NER (HRG) to fault.
with degree of protection defined to IP23 & 2 no Neutral earthing transformer is connected in
Neutral Earthing Transformer (LRG), which star/broken delta (fig-4). The primary winding is
means more space & weight, however is solidly earthed and secondary in broken delta
insignificant and can be accommodated at Utility having loading resistor with Over-Voltage relay
plate form. For Industrial generator, NER can be (59N) [8]. The loading resistor is designed to
installed within main terminal box of the limit the zero-sequence current in secondary to
generator. For ExnA generator [9], NER cannot limit the earth fault current to 75A. Earthing
be placed within Main terminal box or Line side transformer/loading resistor is designed to
cubicle of generator otherwise Exn certification
IJEEMF
www.ijeemf.com
4
International Journal of Electronics, Electrical and Mechanical Fundamentals, (Vol. 16, Issue 01), August 2014
www.ijeemf.com (An Indexed, Referred and Impact Factor Journal) ISSN: 2278-3989
IJEEMF
www.ijeemf.com
5
International Journal of Electronics, Electrical and Mechanical Fundamentals, (Vol. 16, Issue 01), August 2014
www.ijeemf.com (An Indexed, Referred and Impact Factor Journal) ISSN: 2278-3989
IJEEMF
www.ijeemf.com