Sunteți pe pagina 1din 8

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO.

4, JULY/AUGUST 1998 697

Application Guidelines for Instantaneous-Trip


Circuit Breakers in Combination
Motor Starters
George D. Gregory, Senior Member, IEEE, and Lorraine K. Padden, Senior Member, IEEE

Abstract— This paper addresses the application of instan-


taneous-trip molded-case circuit breakers (MCCB’s) in combi-
nation motor starters. These circuit breakers have been widely
used in many industries for motor circuit protection. If they
are not properly applied, situations of false tripping on motor
starting and contact welding of contactors under low-level faults
may occur. Energy efficiency motors compound the issue of false
tripping on motor starting. This paper discusses the components
of combination starters, reviews testing requirements, and pro-
vides examples of coordination with analysis of application issues
and solution options.
Index Terms— Combination motor starter, instantaneous-trip
molded-case circuit breaker, low-voltage protection.

I. OUTLINE OF ISSUES
Fig. 1. Combination motor starter components.

T HE following questions will be discussed in this paper.


• What is a combination starter?
• How are components and the combination starter tested
an instantaneous-trip circuit breaker is used, contain at least an
overload relay, a controller (contactor), and the circuit breaker.
and rated? A combination motor controller is marked with ratings of
• What are selection factors for components? voltage and horsepower and will generally have a short-circuit
• What is the bandwidth of a circuit breaker setting? current rating. Different horsepower and short-circuit current
• How can false tripping during starting be avoided? ratings may be linked with different voltages.
• How can contact welding of contactors be mitigated?
III. COMPONENTS
II. DESCRIPTION OF A COMBINATION STARTER
It is helpful to understand the components as they are
ANSI/UL Standard 508-1993, Industrial Control Equip- outlined in the NEC. Fig. 1 diagrams components that may
ment, defines a combination controller as “an open or enclosed be in a combination motor starter unit. Fig. 430-1 of the NEC
device containing both a magnetic or solid-state controller and is also a convenient reference [2].
a disconnecting means. The controller may or may not contain Combination starters perform the following four basic func-
overload protection, short-circuit protection, or both. Where an tions:
individual controller is enclosed, it includes an external means
• conducting;
for operating the disconnecting means.” [1] Then, it defines
• switching (disconnecting and controlling);
a combination motor controller as “a combination controller
• overload (thermal) protection;
intended for motor service.” A combination starter is one
• short-circuit and ground-fault protection.
form of a combination motor controller and is supplied as
an individually enclosed unit or as an individual unit to be The components are discussed in terms of their functions.
installed in a motor control center.
Relating these definitions to Section 430-52(c)(3) of the Na- A. Conducting
tional Electrical Code (NEC), combination starters, in which Branch-circuit conductors supplying a single motor are
Paper ICPSD 97–39, presented at the 1997 Industry Applications Society required to have ampacity not less than 125% of the motor
Annual Meeting, New Orleans, LA, October 5–9, and approved for publication full-load current (FLC) rating under NEC Section 430-22 [2].
in the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS by the Power Systems
Protection Committee of the IEEE Industry Applications Society. Manuscript
released for publication February 23, 1998. B. Disconnecting Means
G. D. Gregory is with Square D Company, Cedar Rapids, IA 52404 USA.
L. K. Padden is with Padden Engineering, LLC, Katy, TX 77491 USA. The motor disconnecting means is a switching device. NEC
Publisher Item Identifier S 0093-9994(98)04922-6. Section 430-109 is quite specific concerning the devices that
0093–9994/98$10.00  1998 IEEE
698 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 4, JULY/AUGUST 1998

may serve this function, stating that it shall be a motor-


circuit switch rated in horsepower, a circuit breaker, or a
molded-case switch, and shall be a listed device [2]. A manual
motor controller is not permitted for this application. By
exception, an instantaneous-trip circuit breaker may serve as
the disconnecting means only if it is part of a listed combina-
tion motor controller. Other exceptions permit other devices
under specific conditions. NEC Section 430-110 requires the
disconnecting means to have a continuous current rating of at
least 115% of the FLC of the motor [2].

C. Controller
As defined in NEC Section 430-81(a), “a controller is any
switch or device normally used to start and stop a motor by
making and breaking the motor-circuit current.” [2] It is a
switching device capable of starting and stopping the motor
it controls and capable of interrupting the locked-rotor current
(LRC) of the motor. In many cases, the controller is a contactor
rated in horsepower. An inverse-time circuit breaker is also
permitted to serve as a controller, but an instantaneous-trip Fig. 2. Time–current characteristic for a 150-A adjustable trip ther-
circuit breaker is not, under the present NEC [2]. mal-magnetic MCCB.

D. Overload Protection can provide the thermal overload protection if sized in ac-
cordance with NEC Section 430, Part C, but, in most cases,
Motor overload protection is required to protect motors, provides backup protection for a thermal overload relay, such
motor-control apparatus, and branch-circuit conductors against as that shown in Fig. 1 [2]. Smaller current rated thermal-
excessive heating (thermal protection) due to motor overloads magnetic MCCB’s typically have fixed instantaneous-trip set-
and failure to start. Permanently installed motors are protected tings at about 10–20 rated current, whereas the larger cur-
by either an overload relay or by a thermal protector or rent rated thermal-magnetic breakers may have the adjustable
protective device integral with the motor. Overload relays instantaneous-trip settings that typically range from 5–10
are installed in the combination motor starter units when the continuous current rating of the MCCB. The availability
instantaneous-trip circuit breakers are used. of the adjustable features depends on the manufacturer.
Like the instantaneous-trip breaker, the thermal-magnetic
E. Short-Circuit and Ground-Fault Protection breaker can be used as the disconnect and as the short-
The branch-circuit short-circuit and ground-fault protection circuit protection, but, in addition, can also provide overload
is intended to protect the branch-circuit conductor, the motor protection.
control apparatus, and the motor against overcurrent due to
short circuits or ground faults. The device may be a listed C. Instantaneous-Trip Characteristic
fuse or a listed inverse-time circuit breaker. An instantaneous- The instantaneous-trip circuit breaker is essentially a
trip circuit breaker is permitted only if adjustable and if part thermal-magnetic circuit breaker with the thermal sensing
of a listed combination motor controller. Overload protection element removed. Its characteristic appears in Fig. 3. The
is provided by other components in the circuit. instantaneous sensing element, usually an electromagnet, has
an adjustable setting that can be adjusted to the needed trip
IV. INSTANTANEOUS-TRIP CIRCUIT BREAKERS value.
MCCB’s exhibit a band of tripping current for any given
instantaneous-trip setting. According to UL Standard 489,
A. Circuit Breaker Function
Molded-Case Circuit Breakers, Molded-Case Switches, and
In the above discussion, it is clear that a circuit breaker in Circuit-Breaker Enclosures, the trip range tolerance is as
a motor branch circuit serves the dual functions of disconnect indicated in Table I [3]. A considerably tighter degree of
switch and short-circuit protection. Other devices provide precision exists with electronic trip units; however, there is
thermal overload protection. no industry standard for a tolerance closer than that in Table I.

B. Thermal-Magnetic Molded-Case Circuit D. Ratings


Breaker (MCCB) Contrast Instantaneous-trip MCCB’s are available in continuous cur-
The most commonly available MCCB is thermal-magnetic. rent ratings from 3 to 1200 A. The instantaneous setting can
A typical thermal-magnetic MCCB characteristic appears in typically be adjusted in fixed steps to between about 3–11
Fig. 2. A thermal-magnetic breaker’s inverse-time function the continuous current rating. The settings are calibrated
GREGORY AND PADDEN: INSTANTANEOUS-TRIP CIRCUIT BREAKERS IN COMBINATION MOTOR STARTERS 699

instantaneous-trip MCCB’s. However, manufacturers may be


able to provide interrupting rating information about these
products, if it is needed.

E. Testing of Instantaneous-Trip Circuit Breakers


Under UL Standard 489, an instantaneous-trip circuit
breaker is required to complete overload, temperature, and
endurance testing identical to that to which a “Listed” circuit
breaker is subjected and with identical performance criteria
[3]. Calibration testing is done on each pole of each tested
sample before and after each test sequence to verify tripping
within Table I tolerances. Dielectric withstand testing is also
done following each test sequence.
A short-circuit interrupting test is done as for the “Listed”
circuit breaker at standard-level limited available current. In
this test a trip coil is permitted to burn out. However, if a trip
coil burns out, a second set of samples is subjected to a repeat
of the short-circuit test with an impedance equivalent to that
of an overload relay, in which test the trip coil may not burn
Fig. 3. Time–current characteristic for a 150-A instantaneous-trip MCCB. out. For three-pole circuit breakers up to 800 A rated 480 or
600 V, this test consists of two short circuits on each pole
TABLE I with 8660 A available at line-to-line voltage and a common
TRIP TOLERANCES FOR INSTANTANEOUS OPERATION three-phase short circuit with 10 000 A available. These seven
short-circuit operations are followed by a calibration and a
dielectric withstand test.

V. COMBINATION MOTOR CONTROLLER TESTS


Refer to Fig. 1 for components. Component tests of the
circuit breaker were discussed above. The contactor and relay
will each be tested as a component under ANSI/UL Standard
and marked in rms terms, although the sensing mechanism
508 [1]. Then, the combination is subjected to the following
is usually an electromagnet, which is actually sensing peak
tests:
current.
An instantaneous-trip circuit breaker is rated in continuous • temperature;
current and volts. It is not permitted to have a marked • dielectric withstand;
interrupting rating as a means of distinguishing it from the • current withstand;
listed circuit breaker intended for branch-circuit protection. • contactor overload;
The instantaneous-trip circuit breaker is “Component Rec- • combination short circuit;
ognized” by Underwriters Laboratories (UL), rather than being • high available short-circuit current.
“Listed.” The optional marking of a backward “UR” symbol For the current withstand test and all short-circuit tests, a
on the product may indicate this recognition. “Component wide range of combination controller samples are tested to
Recognition” indicates that the product is incomplete in some cover the possible combinations of overload relays, current
condition, a condition that will be completed when the product elements, and instantaneous-trip circuit breaker trip coils.
is installed in “Listed” equipment for which use it has been in-
vestigated. In this case, the instantaneous-trip circuit breaker is A. Temperature Test
made complete by installing it in a “Listed” combination motor
The combination controller is required to carry FLC contin-
controller in compliance with NEC Section 430-52(c)(3). [2]
uously and retain temperatures compatible with materials and
This NEC section requires that the combination have coordi-
components used in its construction.
nated overload, short-circuit, and ground-fault protection in
each conductor. Combination starter units and combination
motor control units used in motor control centers are two B. Current Withstand Test
examples of combination motor controllers. The combination controller is required to carry 600%, and
As a component recognized device intended for use in a then 1000%, of FLC without damage to parts or connected
combination unit, the only short-circuit current rating applied wire that would impair their function. The test is continued
is the rating applied to the combination unit. Because of mis- until the circuit is opened by the overload relay. The circuit
application occurrences of instantaneous-trip circuit breakers, breaker trip setting is adjusted to maximum or its mechanism
the industry has been reluctant to add interrupting ratings on is impaired to prevent tripping during the test.
700 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 4, JULY/AUGUST 1998

TABLE II Let us clarify that a contactor is tested in an overload test up


COMBINATION SHORT-CIRCUIT TESTS to 10 FLC in which it must clear the circuit. For coordination
purposes, be aware that contacts may weld under current levels
above 10 FLC.

VI. COMPONENT SELECTION

A. Overload Relay Selection


To comply with NEC 430-32(a)(1) and (c)(1), an overload
relay is selected to trip at no more than the following percent
of nameplate full-load rating:
• motors with a marked service factor not less than 1.15,
C. Contactor Overload Test 125%;
A magnetic or a vacuum contactor is required to break • motors with a marked temperature rise not over 40 C,
1000% of maximum FLC at maximum rated voltage and 125%;
50% power factor for three operations under conditions of • other motors, 115%.
maximum voltage, power, and current for each rating of When used in a combination controller, the relay’s short-
the combination controller. During the test, the contactor is circuit current rating is the integrated rating of the combination
required to break the circuit without mechanical or electrical unit.
breakdown and without contact weld. The most common practice is for the overload relay to
be wired such that the contactor opens during an overload
condition.
D. Combination Short-Circuit Test
Each combination controller is subjected to a specified B. Circuit Breaker Selection
short-circuit level corresponding to its horsepower rating.
The following three factors must be considered when se-
These are shown in Table II. Connection wire is sized to
lecting an instantaneous-trip circuit breaker.
at least 125% of the FLC rating of the current element. On
the supply side, 4 ft of wire connect the unit to test station • The continuous current rating must be 115% or greater
terminals, and an additional 4 ft of wire on the load side of motor FLC to comply with NEC Section 430-110(a)
connect the unit to the short-circuit point. The circuit breaker when the breaker is also used as the disconnect.
is adjusted to its maximum setting. The number of short-circuit • The adjustable trip range must comply with Table 430-
operations varies and is shown in Table II. 152 of the NEC, that is, it must be no more than 800%
Criteria for acceptance include the following points. The of FLC for other than Design E motors and 1100% of
circuit breaker or contactor must clear the circuit. The circuit FLC for Design E motors. Further, if starting current will
breaker must retain its integrity and demonstrate compliance cause it to trip at these settings, it may be adjusted to a
with calibration and dielectric withstand testing following all higher setting to avoid nuisance operation, as long as the
short-circuit operations. The contactor and overload relay may need has been demonstrated by engineering evaluations.
be inoperative, but insulating material must remain intact, such The maximum permissible adjustment to avoid nuisance
that live parts are not exposed and parts may not be expelled operation under NEC Section 430-52(c)(3) is 1300% of
from the housing. Contacts of a contactor may weld or may FLC for other than Design E motors or 1700% of FLC for
disintegrate. Conductors may not be damaged and may not Design E motors [2]. The NEC does not allow for higher
pull out of connectors. The unit must satisfactorily complete settings, even if the motor still experiences nuisance
a dielectric withstand test following short-circuit testing. tripping. The instantaneous-trip breaker design will not
block settings above that allowed by the NEC. Therefore,
it is important to convey to operators/electricians what
E. High Available Short-Circuit Current Test the maximum setting is for each application.
This is an optional test for units to obtain a short-circuit • Wire connectors must be suitable for the conductors to
current rating above that in the combination short-circuit which they will be connected, if wire is to be connected.
test. The test procedure is quite similar. Two short-circuit Using the example of the motor circuit for the 100-hp
operations are conducted on each unit: 1) an “O” (open) 460-V motor as above, the instantaneous-trip circuit breaker’s
operation in which the test circuit is closed on the unit under continuous current rating must be 115% of FLC (115% of
test by a test station device on the supply side of the unit and 2) 124 A) or 143 A minimum. The next standard current rating
a “CO” (close–open) operation in which the instantaneous-trip is 150 A. It must have an adjustable setting of no greater
circuit breaker is closed on the test circuit. The contactor will than 800% of FLC (992 A) if other than a Design E motor
be closed prior to the test in each case using a separate supply. and 1100% of FLC (1364 A) if a Design E motor to comply
Criteria for acceptance is the same as in the combination with NEC Table 430-152. It may need higher settings if the
short-circuit test. asymmetrical starting current is determined to be greater than
GREGORY AND PADDEN: INSTANTANEOUS-TRIP CIRCUIT BREAKERS IN COMBINATION MOTOR STARTERS 701

the setting allowed by Table 430-152 (including the device tions. For example, circuit breakers, contactors, and overload
bandwidth). Wire connectors must be suitable for the no. 2/0 relays are not suitable for connection of 90 C conductors at
AWG conductors if they are brought to the circuit breaker. 90 C ampacity. The equipment will be marked to identify
The instantaneous-trip circuit breaker will not have an inter- suitable conductors by wire size, conductor metal (Cu or Al),
rupting rating. A short-circuit current rating is instead applied and insulation temperature, which will not be over 75 C.
to and marked on the combination starter unit containing the Conductors rated 90 C may be used as long as their ampacity
circuit breaker. The design engineer must determine that the at 75 C or 60 C, as marked on the product terminals, meets
combination starter short-circuit current rating is adequate for the NEC current requirements. Note that conductor correction
the system in which it is used. The combination starter is short- factors and deration factors are applied to the ampacity based
circuit retested every two years under UL’s Follow-Up Service on the insulation rating (e.g., 90 C). The conductor must also
to ensure that the rating is retained by all components [1]. fit the wire connector provided on the equipment [5].
The “80% rule” and the “100% rating” applied to certain When a power factor correction capacitor is provided,
thermal-magnetic and electronic circuit breakers does not as indicated in Fig. 1, its effect is to be disregarded when
apply to motor circuits. The “80% rule” comes from NEC determining the ampacity of the motor-circuit conductors.
Sections 210-22(c), 220-3(a), and 220-10(b) which contain the Ampacity of the conductors to the capacitor are to be the
requirement that an overcurrent protective device be rated not larger of 135% of the rated current of the capacitor or 1/3 of
less than the noncontinuous load plus 125% of the continuous the ampacity of the motor circuit conductors.
load. In other words, the continuous load will be no more than Consider a 100-hp 460-V motor example. FLC is 124 A
80% of the rating of the device. For branch and feeder circuits from NEC Table 430-150. The required ampacity is 125% of
other than motor circuits, this 100% rating is permitted by 124 A, or 155 A. Using Table 310-16 , a no. 2/0 AWG copper
exceptions to the same NEC sections. The 100% rating implies cable with a 175-A ampacity is required, assuming a 75 C
that the circuit breaker is capable of continuous operation at termination rating (no correction factors or deration factors
100% of its rated current while enclosed, without operating are applied). A coordination plot shows the thermal damage
automatically to open the circuit and without experiencing an curve of the conductor. The conductor must be protected by
excessive temperature condition. the overload and short-circuit devices.

C. Contactor Selection VII. COORDINATION DISCUSSION


A contactor used as the motor controller is required to have The two components of coordination are as follows:
a horsepower rating at the application voltage not less than • protection;
the horsepower rating of the motor. For a Design E motor, • selectivity.
the contactor must either be marked as suitable for Design E NEC Section 110-10 addresses the protection requirements:
motors or have a horsepower rating 1.4 that of a 1–100-hp “The overcurrent protective devices, the total impedance, the
motor or 1.3 that of a motor over 100 hp. The reader is component short-circuit withstand ratings, and other charac-
referred to NEMA Standard ICS-2 for a tabulation of various teristics of the circuit to be protected shall be selected and
types and sizes of contactors [4]. coordinated to permit the circuit protective devices used to
When used in a combination controller, the contactor’s clear a fault to do so without extensive damage to the electrical
short-circuit current rating is the integrated rating of the components of the circuit.” [1] The combination motor starter
combination unit. protective devices should also be selective with devices on
If the overload relay is wired such that the contactor the supply side.
opens on overload conditions, the make/break capability of According to ANSI/UL Standard 508, the phrase
the contactor should be reviewed for coordination with the “ without extensive damage ” means that the circuit
short-circuit protection device. is cleared without fire or shock hazard. Components must
retain structural integrity, such that live electrical parts are
D. Conductor Selection not exposed and will pass a dielectric withstand test following
Conductors are selected in accordance with the motor cir- a short-circuit test [1].
cuit ampacity by applying NEC Sections 430-22–430-24 [2].
Where a single motor is involved, the conductors are required A. Coordination Example
to have an ampacity of not less than 125% of FLC using NEC Refer to Fig. 4 for the time–current plot of a coordination
Tables 430-148–430-150 and not the nameplate FLC (unless example.
the nameplate FLC is higher than the Table values, such as The parameters are as follows:
1200-r/min motors). Conductors are then selected for their motor—100 hp, 460 V, Design B;
ampacity, using NEC Section 310-15. The most commonly MCCB—175 A instantaneous trip;
applied ampacity table is Table 310-16. Correction factors for MCCB setting—12 FLC 1500 A;
ambient temperature and deration factors for the number of overload—class 10;
conductors in a cable or raceway may need to be applied [5]. contactor—NEMA size 4;
When determining the correct cable ampacity, it is essential conductor—no. 2/0 AWG XHHW, Cu;
to be aware of equipment wire connector temperature limita- available short circuit—20 000 A.
702 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 4, JULY/AUGUST 1998

1040–1690 A. Operation at the low end of the band could see


false tripping on starting. At the high end, the contactor might
open above its tested break current on a high-impedance fault,
and a contact weld is possible.
A setting of 1500 A was selected for Fig. 4 to illustrate a
high setting available on a typical breaker without exceeding
the NEC limit. This selection still leaves a gap in which the
contactor is unprotected and overlaps a small range in which
the breaker could trip during motor start.
An asymmetrical starting value of 1.76 the LRC is a
typical value used for industrial applications [5]–[8]. This
condition illustrates the coordination issues that arise for
industrial applications. In some cases, the multiplier will be
lower. However, with the advent of energy-efficient motors,
high starting current issues are increasing.

C. Potential Solutions
If false tripping during start still occurs when the
instantaneous-trip setting is at the maximum allowed by the
NEC, several options should be considered.
• Use a thermal-magnetic MCCB or fuse in place of the
Fig. 4. Time–current coordination plot for a 480-V 100-hp motor showing instantaneous-trip MCCB. Fixed-trip thermal-magnetic
the unprotected area of the contactor. MCCB’s have an instantaneous-trip range higher than
the instantaneous-trip MCCB, thereby allowing the mo-
tor to start. Ratings of the contactor and other compo-
For the circuit breaker setting, the following analysis is used. nents should be reviewed for protection. Adjustable-trip
thermal-magnetic breakers may provide the best of both
• Consider the maximum permissible setting for a Design
worlds, allowing a higher instantaneous setting within
B motor of 800% of FLC (8 124 A 992 A) in NEC
the NEC requirements, while providing the maximum
Table 430-152.
possible protection for other components, such as the
• Determine whether false tripping is expected when start-
contactor. As the design engineer would expect, the
ing. A typical asymmetrical starting current is assumed
instantaneous-trip devices are the least expensive, the
and calculated as follows: 1.76 LRC (1.76 725
fixed-trip thermal-magnetic breakers are more expensive,
1276 A) in rms terms [5]–[8]. This indicates false tripping
and the adjustable-trip thermal-magnetic breakers are the
will occur with the 800% setting.
most expensive.
• Using NEC Section 430-53(c)(3) Ex 1, it is permissible
• Use an MCCB with time delay or damping to override
to adjust the setting higher than 800%, but no higher than
starting current.
1300% (13 124 A 1612 A) for the Design B motor.
• Use a reduced-voltage starter, such as an autotransformer,
• A setting of 12 FLC was chosen for this example to
during starting to reduce the starting current.
review possible false tripping and view interaction with
other components. An option to avoid applying the contactor at levels above
those for which it has been tested to break is to specify a
larger contactor which has a higher current rating. Contactors
B. Coordination Issues are tested to break current at 10 their continuous rating.
1) False Tripping and Contactor Rating: Finding an ap- Therefore, the contactor would be protected with a higher
propriate circuit breaker setting that will permit starting current setting of the instantaneous-trip MCCB (within the NEC
to flow while providing protection for the contactor may be requirements).
a challenge. Asymmetrical starting current can be several If space is a factor in upsizing the contactor, vacuum
times LRC. Recall that the circuit breaker settings are marked contactors should be considered. They are manufactured with
in rms terms. For this example, the asymmetrical starting FLC ratings of 160, 320, 600, and 720 A and have a break
current was calculated at 1276 A, which would occur in rating of 10 FLC. These are generally smaller in size than
the first half cycle. The size-4 contactor has been tested to the comparable magnetic contactor, but are more expensive. A
break up to 10 its continuous current rating of 135 A, or cost/benefit analysis may be needed to determine the contactor
1350 A. It would seem that a setting of 1300 A would be type.
satisfactory to permit starting current to flow while protecting Fig. 5 explores one of these solution options. A size-5
the contactor. contactor is illustrated with an instantaneous-trip setting of
The circuit breaker tripping band must be considered. Using 1610 A. Note that the NEC permits 13 FLC for the setting,
Table I, the tripping band for a setting of 1300 A would be which would be 1612 A. The maximum trip is 1610 130%,
GREGORY AND PADDEN: INSTANTANEOUS-TRIP CIRCUIT BREAKERS IN COMBINATION MOTOR STARTERS 703

Fig. 5. Time–current plot for a 480-V 100-hp motor showing the protected Fig. 6. Backup protection using a thermal-magnetic MCCB.
contactor.

motors. Energy-efficient motors are among those with which


or 2093 A. The minimum trip is 1610 80%, or 1288 A. For low power factor, high starting currents can be expected. In
this case, the size-5 contactor is protected using a trip setting many cases, starting current for the Design B energy-efficient
of 1610 A, because the contactor break rating of 2700 A is not motors will exceed the maximum permissible setting of 1300%
exceeded. Also, the circuit breaker should not trip on motor of FLC permitted by the NEC. In these cases, an instantaneous-
start, because the minimum trip is 1288 A, which is above the trip circuit breaker will not be suitable, and an inverse-time
asymmetrical starting current of 1276 A. circuit breaker, a fuse, or reduced voltage starting may be a
This solution satisfies the protection criteria. Because of solution.
high starting current, protection of the motor is not as close
as might be desired. Also, selective coordination with devices VIII. CONCLUSIONS
on the supply side will be more of a challenge than with a
lower setting. 1) A “Listed” combination starter meets the requirements
of the NEC and is tested such that the combination of
components protects the motor and is self protecting as
D. Backup Protection a system. A system designer selecting components must
The design engineer should evaluate the need for backup be aware of NEC requirements, as well as being aware
protection in the overload region. First, the overload device of the meaning of the ratings of the combination and its
is normally the only line of protection from overloads and components.
high impedance faults when using instantaneous-trip circuit 2) The combination starter must have a short-circuit current
breakers. A failure of the overload device, the overload wiring, rating adequate for the available short-circuit current on
or the contactor can prevent the circuit from being isolated due its supply side.
to overload or high-impedance fault conditions. Where backup 3) False tripping of instantaneous-trip circuit breakers is
protection is desired for these abnormal conditions, an inverse- an occasional problem when motors are starting. The
time circuit breaker or fuses should be selected. Fig. 6 shows asymmetrical starting current causes the breaker to trip
a thermal-magnetic breaker with a 100-hp motor to illustrate without a fault condition. In some cases, the maximum
the backup protection provided in the overload region. setting permitted by the NEC is not high enough to
allow the starting current to flow without tripping the
instantaneous-trip circuit breaker. Inverse-time circuit
E. Energy Efficient Motors breakers (thermal-magnetic or electronic-trip), fuses, or
To comply with the Energy Policy Act of 1992, certain reduced voltage starters may be required to satisfy NEC
motors manufactured after October 24, 1997 must meet new requirements.
efficiency standards. Design E motors comply with these 4) Coordination plots that simply show a straight line
standards. However, the most commonly available motors to for an instantaneous-trip breaker should be modified
meet these standards are energy-efficient Design B motors. to include the manufacturing tolerance around the set
The 1996 NEC permits especially high circuit breaker settings point, as given in Table I. To avoid false tripping,
for the Design E motors, and the 1999 NEC is considering the asymmetrical starting current should be below the
higher circuit breaker settings for energy-efficient Design B minimum Table I tolerances of the set point.
704 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 4, JULY/AUGUST 1998

5) The contactor should be tested to break high-impedance George D. Gregory (S’69–M’70–SM’97) earned
fault conditions it may see and to withstand the motor’s the B.S.E.E. and M.S.E.E. degrees from the Illinois
Institute of Technology, Chicago.
LRC. Any condition at or below the maximum Table He is presently Manager, Industry Standards,
I tolerances of the set point of the breaker should be Square D Company, Cedar Rapids, IA. Since joining
within the tested break value of the contactor. Magnetic Square D Company in 1985, he has held a variety
of positions, including Chief Engineer, and Product
or vacuum contactors that have adequate break values Manager for Molded-Case Circuit Breakers. Prior
may be applied to avoid welding of contacts. to 1985, he served as Design Manager for Circuit
Breakers with GTE Products, Puerto Rico, and
as Engineering Group Leader with Underwriters
ACKNOWLEDGMENT Laboratories, Chicago, IL. He is currently Chair of the NEMA Circuit Breaker
Section, Deputy Technical Advisor to the IEC 17B Subcommittee, and a
This paper was the result of considerable work and dis- member of National Electrical Code Panel 10 (representing NEMA).
Mr. Gregory is Vice Chair of the IEEE Industry Applications Society Power
cussion by members of the Molded-Case Circuit Breaker Systems Protection Committee, Chair of the Blue Book Working Group, a
Applications Working Group of the IEEE Industry Appli- Chapter Chairman in the Buff Book Working Group, and a contributor to the
cations Society Power Systems Protection Committee. The Battery Systems Protection Working Group. He is a Registered Professional
Engineer in Illinois, Iowa, and Puerto Rico.
authors thank J. Andrews, B. Bailey, R. Clark, K. Cooper,
J. Fischer, W. Hall, G. Irvine, D. Love, Don McCullough,
Alan Pierce, Vince Saporita, and Ray Valentine, members of
the Working Group, for their contributions to this paper as
well as to nonworking group members who provided support. Lorraine K. Padden (S’81–M’83–SM’94) received
the B.S. degree in electrical engineering in 1983
from the South Dakota School of Mines and Tech-
nology, Rapid City.
REFERENCES Following graduation, she was with Shell Oil
Company and subsidiaries in Houston, TX, and Bak-
[1] Industrial Control Equipment, ANSI/UL Standard 508-1993.
[2] ANSI/NFPA 70, 1996 National Electrical Code, National Fire Protection ersfield, CA. As a Facilities Engineer, she designed
Association, Quincy, MA, 1996. and managed production facilities projects from
[3] Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit- conception to completion. In 1992, she founded
Breaker Enclosures, ANSI/UL Standard 489-1996. Padden Engineering, LLC, Katy, TX, a consulting
[4] Industrial Control and Systems Controllers, Contactors, and Overload company, of which she is President. She has been
Relays Rated Not More Than 2000 Volts AC or 750 Volts DC, NEMA providing electrical engineering services to the petrochemical industry since
Standard ICS-2-1993. 1983, specializing in power system design and analysis and coordination
[5] L. K. Padden and P. Pillai, “A flow chart methodology for performing studies, including plants up to 700 MW.
low-voltage three-phase motor coordination studies,” in Conf. Rec. IEEE Ms. Padden is a member of the IEEE Industry Applications (IAS) and
PCIC Conf., 1997, pp. 11–23. IEEE Power Engineering Societies and has served on several committees,
[6] R. R. Burke and W. R. Finley, “Trouble shooting motor problems,” in including a term as Chair of the IAS Petroleum and Chemical Industry
Conf. Rec. IEEE PCIC Conf., 1993, pp. 303–316. Committee Production Subcommittee. She is also a member of the American
[7] R. L. Nailen, “Motor inrush current: What does it really mean?,” Elect. Petroleum Institute, National Fire Protection Association, Society of Petroleum
App. Mag., pp. 56–60, June 1986. Engineers, International Society for Measurement and Control, and National
[8] H. L. Bradfield and D. W. Heath, “Short-circuit protection of energy Society of Professional Engineers, and an affiliate member of the International
efficient motors,” IEEE Ind. Applicat. Mag., vol. 3, pp. 41–44, Jan./Feb. Electrical Testing Association. She is a Licensed Professional Engineer in the
1997. States of Texas, California, and Washington.

S-ar putea să vă placă și