BEMS POINT SCHEDULE & MCC LOAD DIAGRAM

Utilities Compound, Laundry

Load Item Power Kw


Starting Gear Rating
Control Cable Cores

Starting Gear Type


Analouge or Digital

Compartment #

Cable Cores
Nr of Points

Cable Type

Cable Size

Load Item
Location
Device

[X-G-AH2-01] [X-G-AH2-01]

X-1-MCC-02
Duct RA temp. detector [AHU] 1 A 2 SD 25 5 7 4 4.0kW Supply fan
Duct SA temp detector [AHU] 1 A 2 1
Duct FA temp detector [AHU] 1 A 2 INV 16 5 4 2.5 3.0kW Extract fan Variable to suit laundry exhaust
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator [AHU] 1 D 2
Extract fan isolator [AHU] 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2

[X-G-AH2-02]
Duct RA temp. detector [AHU] 1 A 2 [X-G-AH2-02]
Duct SA temp detector [AHU] 1 A 2 SD 25 5 7 4 4.0kW Supply fan
Duct FA temp detector [AHU] 1 A 2 2
Mixing damper 1 [AHU] 1 A 3 DOL 16 5 4 2.5 3.0kW Extract fan Variable to suit laundry exhaust
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator [AHU] 1 D 2
Extract fan isolator [AHU] 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2

[X-G-AH2-03]
Duct RA temp. detector [AHU] 1 A 2 [X-G-AH2-03]
Duct SA temp detector [AHU] 1 A 2 SD 25 5 7 4 4.0kW Supply fan
Duct FA temp detector [AHU] 1 A 2 3
Mixing damper 1 [AHU] 1 A 3 DOL 16 5 4 2.5 3.0kW Extract fan Variable to suit laundry exhaust
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator [AHU] 1 D 2
Extract fan isolator [AHU] 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
[X-R-EF-01]
Main Filter DP switch [AHU] 1 D 2
DOL 4 fhp Extract fan
4
[X-R-EF-01]
Extract fan starter [MCC] 3 D 5

[X-R-EF-02]
[X-R-EF-02]
Extract fan starter [MCC] 3 D 5
DOL 4 fhp Extract fan
5
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2

1. A = Analogue; D = Digital; C = Communication


2. Starters: DOL = Direct On Line; SD = Star/Delta; AT = Auto Transformer; Inv = Inverter
3 Cable Type :1 = Xlpe/Swa/LSF, T3 Cable Type :1 = Xlpe/Swa/LSF
4. Numbers of Points and control cable cores are given for guidance. Tenderer to review against written specified requirements and make due allowance for what is required

RE6309/D1361 Rev 0/2003 15910/1 BEMS Point Schedule