Documente Academic
Documente Profesional
Documente Cultură
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This publication was prepared in cooperation with TC 9.9, Mission Critical Facilities,
Technology Spaces, and Electronic Equipment.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
ISBN: 978-1-933742-20-5
ASHRAE has compiled this publication with care, but ASHRAE has not investigated, and ASHRAE
expressly disclaims any duty to investigate, any product, service, process, procedure, design, or the like
that may be described herein. The appearance of any technical data or editorial material in this publi-
cation does not constitute endorsement, warranty, or guaranty by ASHRAE of any product, service,
process, procedure, design, or the like. ASHRAE does not warrant that the information in the publi-
cation is free of errors, and ASHRAE does not necessarily agree with any statement or opinion in this
publication. The entire risk of the use of any information in this publication is assumed by the user.
No part of this book may be reproduced without permission in writing from ASHRAE, except by a
reviewer who may quote brief passages or reproduce illustrations in a review with appropriate credit;
nor may any part of this book be reproduced, stored in a retrieval system, or transmitted in any way
or by any means—electronic, photocopying, recording, or other—without permission in writing from
ASHRAE.
____________________________________________
Library of Congress Cataloging-in-Publication Data
Structural and vibration guidelines for datacom equipment centers.
p. cm. -- (ASHRAE datacom series)
Summary: "Provides basics for addressing the structural and vibration performance (resistance against wind,
snow, and seismic assault) of datacom equipment centers, focusing on the facility (envelope, beams, columns,
floor slabs, roof slabs), the building infrastructure (power, cooling, flooring, ceiling systems), and the datacom
equipment (servers, storage, tape drives, racks, network equipment)"--Provided by publisher.
Includes bibliographical references and index.
ISBN 978-1-933742-20-5 (softcover)
1. Structural design. 2. Data processing service centers--Design and construction. 3. Buildings--Vibration. 4.
Earthquake resistant design. 5. Data processing service centers--Protection. 6. Electronic digital computers--
Protection. I. American Society of Heating, Refrigerating and Air-Conditioning Engineers.
TH1094.S77 2007
725'.23--dc22
2007046368
ASHRAE STAFF
SPECIAL PUBLICATIONS PUBLISHING SERVICES
PUBLISHER
W. Stephen Comstock
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Contents
Acknowledgments................................................................................... ix
Chapter 1 Introduction......................................................................... 3
1.1 Overview of this Book............................................................ 3
1.2 Overview of the Datacom Industry ........................................ 5
1.3 Overview of ASHRAE Technical Committee 9.9 ................... 6
1.4 Overview of the ASHRAE Datacom Series ........................... 6
1.5 Document Flow ..................................................................... 7
1.6 Primary Users for This Document ......................................... 7
Chapter 2 Best Practices..................................................................... 9
2.2 Building Structures—New Buildings and Additions ............... 9
2.3 Building Structures—Renovations,
Relocations, and Changes .................................................. 10
2.4 Building Infrastructure ......................................................... 11
2.5 Datacom Equipment............................................................ 11
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
vi ⏐ Contents
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
viii ⏐ Contents
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Acknowledgments
The information in this guide was produced with the help and support of the
corporations listed below:
• Dr. Roger Schmidt, Dr. Budy Notohardjono, John Quick, and Shawn
Canfield of IBM, Don Beaty and Dan Dyer of DLB Associates Consulting
Engineers, Jeff Trower of Data Aire Inc., Jeffrey Soulages of Intel, Richard
C. Berger of VMC Group, Larry Wong of AT&T Services, Inc., and Bill
Perry of Tate Access Floors, Inc., for their participation as chapter leads,
which included numerous calls, writing, and review.
• Dr. Budy Notohardjono for his leadership in coordinating and leading the
overall development of this book.
• Don Beaty of DLB Associates Consulting Engineers and Dr. Roger Schmidt
of IBM, the past and present chairmen of TC 9.9, for their leadership, vision,
and encouragement for this book.
• Don Beaty of DLB Associates for his leadership on the building structure and
infrastructure portions of the book.
• Steve Felton and Tom Davidson of DLB Associates, Hubert Starzer and Tony
Fagan of Starzer Brady Fagan Associates, Bob Morris of Corgan Associates,
Jerry Estoup of JG Pierson, Elizabeth O’Neill of VMC Group, and Jack Glass
of Citigroup for their participation and improvements to the final document.
ix
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Part I
Introduction and
Best Practices
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Introduction
1.1 OVERVIEW OF THIS BOOK
Today’s datacom (data and communications) facility managers and operators
understand the importance of protecting their business’ critical data and information
technology (IT) equipment (or datacom equipment), which includes servers as well
as storage, communications, and networking equipment. Data center operators must
therefore implement standards and practices for ensuring the integrity and function-
ality of the equipment within the datacom environment.
High-performance data center facilities accommodate a variety of complex and
sensitive datacom equipment that is vulnerable to internal and external sources of
shock and vibration. Shock and vibration sources are unwanted forces found at some
level in most datacom facilities that over time can degrade both facilities and equip-
ment. The datacom equipment and infrastructure equipment can themselves be
vibration sources within the data center. Datacom equipment manufacturers can
control these vibration sources by reducing the internal vibrations that are transmit-
ted to the surroundings. External sources such as airports, trains, nearby mining
operations (quarry blasting), construction activities, and earthquake and weather
events are other sources of operational shock and vibration. These shock and vibra-
tion sources are transferred through the building structure to the data center and
finally to any operating server and supporting infrastructure equipment. The effect
of these disturbances on the function of the IT and telecommunications equipment
depends on the design or the robustness of the equipment itself. The best practice to
reduce and circumvent the potential disruptive effects of these shock and vibration
sources is to eliminate, minimize, and control the input shock and vibration levels.
The best place to manage shock and vibration is at the originating source, which may
not always be possible.
For users, manufacturers, and installers of servers and storage, telecommuni-
cation, and networking equipment, this publication provides design information and
criteria to allow for continuous data center equipment operation during vibration or
seismic events.
Datacom equipment centers require a focus on the structural and vibration
performance of the facility, the building infrastructure, and the contents (e.g., data-
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
4⏐ Introduction
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
designers but also owners and operators to have a general understanding of the struc-
tural and vibration basics. For example, unintentionally the structural or vibration
system could be seriously compromised by an operator’s not understanding the impor-
tance of the structural and vibration systems’ interactions within the building system.
The intent of this book is to provide some basics for addressing these highly
integrated topics of building structure, infrastructure, and datacom equipment. In
order to effectively address this holistic topic, the contributors to this book include
datacom equipment manufacturers, mechanical/electrical engineers, building archi-
tects, and building structural engineers.
1.2 OVERVIEW OF THE DATACOM INDUSTRY
The data center and telecommunications industry relies on a physical infra-
structure, including datacom equipment centers, for which there is a widely varying
range of size, capacity, level of resilience, configuration, use, staffing strategy, etc.
As a result, it is very important not to overgeneralize or use a cookbook/recipe
approach. Table 1.1 shows typical ranges of applications for various topics but is not
intended to show the absolute extremes.
Topic Range
Space size Small room to the entire building
Building size 500 to over 500,000 ft2 (46.45 to over 46,451.52 m2)
Building configuration Single building to an entire campus
Power and cooling density 5 to 500 W/ft2 (54 to 5382 W/m2)
Equipment weight 30 to 3600 lb (13.6 to 1634.4 kg)
Infrastructure performance/availability Tier 1 to Tier 4
Scope Minor renovation to a new building or campus
Operations staffing Lights out (unmanned) to full 7 × 24 staffing
Use Mixed use to dedicated use
Main function Telecommunications, call center, data center
Backup site No backup site to automatic failover backup site
Lifetime changes Minimal to extreme
Occupancy Owner occupied to tenant occupied
Code Barely meets code to significantly exceeds code
Stories Single story to high-rise
Below 0°F (–18°C), above 100°F (38°C),
Climate
dry/wet, hurricane, tornado prone
Soil type Sand, clay, organic, high water table
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
6⏐ Introduction
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Chapter 1—Introduction
Chapter 2—Best Practices
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
8⏐ Introduction
other infrastructure equipment will benefit from these guidelines. Specific examples
of users of this document include:
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Best Practices
2.1 BUILDING STRUCTURES—NEW BUILDINGS AND ADDITIONS
Careful forethought is needed in the early design phases for new buildings and
additions to existing buildings. Datacom equipment centers require a unique set of
design criteria as compared to more traditional spaces. Many services must be
supplied directly to the datacom equipment to meet cooling, power, and communi-
cations needs. These services require support systems that place increased loads on
the building structure.
In addition, the weight of the datacom equipment and its supporting infrastruc-
ture will create the need for special structural consideration, as will any structural
design requirements (such as resistance to hurricanes or explosions) that are above
and beyond code minimums.
Best practices for new buildings and additions to existing buildings are listed in
Table 2.1.
1 Balance the first cost of the building with the long-term adaptability of the structure.
2 Provide above-average clear height to the underside of overhead building structures.
3 Provide a reserve capacity in structural members for collateral loads.
4 Optimize column spacing for maximum adaptability.
Provide special structural inspections as outlined in Chapter 17 of the International
5
Building Code.
6 Consider the building’s structural system versus steel lead-time.
7 Consider the holistic impact of seismic design requirements.
8 Review the benefits of increased soil-bearing capacity.
9 Optimally locate shear walls and braced frames for maximum adaptability.
10 Reduce constraints on penetrations through wall, floor, and roof assemblies.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Expose the existing structure as much as possible (e.g., remove existing ceiling
2
systems).
Evaluate the current code requirements and upgrade the existing structural systems
4
as required.
7 Accurately locate the existing building columns and confirm that they are plumb.
Understand that buildings erected prior to 1975 typically require expensive structural
8
improvements to meet current seismic code requirements.
Recognize that concrete structures are very difficult to verify structurally, with or
9
without drawings.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Datacom equipment is the focus of the data center. The building and infrastruc-
ture designs should be integrated to assure that the reliability and availability of the
datacom equipment is maintained at the desired level. The design and installation of
datacom equipment that can weigh from 300–400 to 3600 lb (1335–1780 to
16,017 N) are key to achieving this goal.
Best practices for datacom equipment installation are listed in Table 2.4, and
best practices for datacom equipment design are listed in Table 2.5.
2 Locate larger systems outside the building in adjacent equipment yards if possible.
Install the raised-acess floor system at a temperature very close to the operational
6
temperature.
Secure all overhead cable trays to a rigid frame that carries the load either to the roof
8
structure or to the floor slab.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Check the building structure—can the building support the datacom equipment
2
loading?
3 Check the raised-access floor—can the it support the datacom equipment loading?
Investigate the installation/relocation route from the loading dock to the final
4
destination.
Consult the equipment manufacturer for unusual relocation routes or high opera-
7
tional shock and vibration.
10 Consult the equipment manufacturer when the need arises to relocate the equipment.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Part II
Building Structure
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
• foundations
• soil or sub-surface bearing elements
• floor slabs
• structural frames
• structural components of wall and roof systems
• structural connections
• other structural elements
The common saying that a building is only as strong as its foundation should not
be dismissed as mere cliché: foundations are critical. One might also say a founda-
tion is only as strong as the soil that supports it, as site selection and facility design
depend greatly on site soil conditions, which may vary over a single site for larger
structures.
Additional elements that are not direct structural elements, such as the building
envelope, skin, surfaces, and cladding, have also have an impact on the structure.
These elements are analogous to ship sails or surfaces that are directly impacted by
exterior forces such as wind, rain, and snow that in turn impact the loading of the
structural system.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
and determine the load requirements, the impact from natural occurrences, and the
expected design performance of the building now and in the future.
Gathering loading information is often a difficult task, especially when
members of various architectural and engineering disciplines are concurrently
designing the building components, including the mechanical, electrical, plumbing,
and fire protection systems. The owner or tenant and the facility operators also play
a part in the design process.
The required loads as defined by the building code may be sufficient in many
cases, but in every case the design professional must review the structural loading
for the entire project. Building codes are quick to address typical uses, such as office
spaces; however, they seldom, if ever, contain specific requirements for datacom
facilities or address the unique loading conditions imposed by datacom facility
systems and the need to resist threats posed by both man and nature. The designer
must consider the type of loads the facility will bear, as these will influence the
supporting structure, especially during vibratory events.
Loads from datacom equipment, battery or uninterruptible power supply (UPS)
systems, transformers and switchgear, chillers, boilers, large cooling water piping,
cooling towers, roof-mounted mechanical units attached to large ductwork, and fire
protection systems and their associated water distribution systems all greatly impact
the design of elevated floor or roof members. Architectural finishes such as ceilings,
lights, interior lateral wall supports, bearing walls, raised-access floors, large wall
openings, floor slopes, and underground drainage also impact the structural design.
Other elements designers must consider are deflection of members and struc-
ture drift, which vary with the type of structure selected. For financial reasons, pre-
engineered metal buildings are commonly used. Such buildings are typically frame
structures that are relatively flexible and dissipate energy by bending or deforming.
This type of structure requires that nonstructural elements and systems be designed
to accommodate the expected deformations.
Buildings utilizing moment-resisting frames (moment frames) for lateral stabil-
ity will likely have similar considerations. More rigid structures, such as those that
incorporate shear walls or braced frames, will deflect or drift less than a typical pre-
engineered or moment frame structure. If reduced levels of deflection and drift can
be predicted, connecting elements from partitions, exterior walls, and attached
equipment will cost less to construct.
Seismic and wind requirements vary from location to location and are based on
geological data and past damage reports in regions where seismic events have
occurred. A geological investigation called a site-specific seismic study is commonly
completed to determine the type of existing soil and the distance from the building
foundation to the supporting bedrock. These parameters, in combination with code-
prescribed criteria, provide guidance for establishing the percentage of structure
mass to be used in the lateral load analysis, sometimes leading to net savings in over-
all construction costs.
The building design should be as symmetrical as possible to allow seismic
forces to flow more evenly across the structure. Forces induced on an asymmetri-
cally shaped building are considerably greater than those on symmetrically shaped
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
buildings. Deflections of the asymmetrical structures will also vary and require
greater study in the interconnections of the nonstructural components.
Wind load requirements are based on weather data compiled from sources such
as the National Weather Service. The codes or incorporated standards include maps
and guidance data, but working with the local building department is highly recom-
mended. Although building codes generally allow interpolation between wind speed
contours, some jurisdictions require a set minimum wind speed for the entire juris-
diction based on the highest minimum wind speed in that jurisdiction.
Wind load considerations are critical for not only the performance of a structure
during wind events but also for the performance of the nonstructural components.
Roof uplift and wall anchorage systems as well as equipment tie-downs on the roof
are of great importance and must be considered.
It should be noted that structures are typically designed based on meeting only
the minimum code requirements. Further, the codes are written for life safety and not
for the purpose of keeping data center facilities operational during and after a major
storm.
Facilities can be constructed to withstand wind loads from extremely high wind
forces, such as tornadoes, and wind-borne debris, etc., as shown in Figure 3.1, but
these provisions can be very costly. A cost-benefit analysis should be performed to
confirm the value of storm-resistant design. Such a study should assess structural
upgrades to meet multiple wind-speed conditions (and their associated costs) against
the historic statistical probability of the occurrence of those conditions. The owner
of the structure then can make an informed decision on the level of wind-threat resis-
tance to be incorporated into the project.
Historically, the codes have been prescriptive (cookbook- or recipe-like). The
trend in code content, however, has been toward increasing the complexity and
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
including more requirements. This trend is probably driven by events such as Legion-
naire’s disease outbreaks, New Orleans hurricane damage, global warming, etc.
In addition to becoming more complicated, the codes are gradually migrating
toward performance requirements rather than prescriptive requirements.
Appendix A includes details regarding recent code requirements.
Especially in older structures, it is quite common that the plans and specifica-
tions issued to construct the building are no longer available and therefore the design
load capacity of the structure is not known. This can be problematic (and often
costly) for planned datacom-related retrofits and even for seemingly minor building
infrastructure upgrade projects. In such cases, a licensed structural engineer should
review the structure in the field and determine the load carrying capacity of the exist-
ing structural system.
When constructing a datacom equipment center in a leased space, consideration
should be paid to the eventual exit strategy from the facility. Modifications to leased
structures should be kept to a minimum or designed so as to allow them to be
removed at lease termination without impacting the main structural systems.
Pits and trenches can be filled in and free-standing structures can be removed,
but when existing walls or other structural elements are modified such that the struc-
ture would no longer be sound without the added reinforcement, the modifications
must remain in place permanently. Therefore, the terms of a lease should be carefully
checked to determine potential consequences prior to making changes to the build-
ing structure.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
dead load: the combined weight of all the permanent construction materials, includ-
ing roofing, framing, and other structural components such as walls, floors, roofs,
ceilings, stairways, built-in partitions, finishes, cladding, and other similarly incor-
porated architectural and structural items and fixed service equipment, including
cranes. The dead load is determined in advance and is assigned a low factor of safety
in the overall building design. All dead loads are considered permanent loads.
collateral load: a type of dead load, the collateral load includes the weight of any
materials other than the permanent construction materials. The collateral load may
include electrical pipes, sprinkler systems, ceilings, lights, and other materials.
live load: the weight of building occupants, furniture, machines, equipment, and the
like. Since the live load is hard to quantify, it carries large factors of safety in the over-
all design of the building. Other live load sources that occur during construction and
maintenance, such as those from tool boxes, temporary generators, etc., must be
taken into consideration as well; these loads may be difficult to predict.
snow load: the maximum weight of snow that will collect on the roof of the building.
The snow load is highly dependant on the ultimate location of the building. The slope
(pitch) of the roof is a factor used to determine snow loads.
In addition to roof snow load, ground snow load must also be taken into consid-
eration. The roof snow load is usually less than the corresponding ground snow load
because snow is often removed from building roofs by melting and wind.
duration of load: the period of continuous application of a given load, or the aggre-
gate of periods of intermittent applications of the same load.
load factor: a factor that accounts for deviations of the actual load from the nominal
load, for uncertainties in the analysis that transforms the load into a load effect, and
for the probability that more than one extreme load will occur simultaneously.
impact load: the load resulting from moving machinery, such as elevators,
craneways, vehicles, and other similar forces, and kinetic loads, pressure, and possi-
ble surcharge from fixed or moving loads. Note: a craneway is the structure or struc-
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
tural members upon which a crane travels, which can include columns, support
girders, and rails.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
New Structures
4.1 INITIAL INVESTIGATION
Once a tract of land has been identified as a potential location for a new facility,
preliminary due-diligence activities such as those listed below should commence.
From a structural standpoint, the most important of these activities is the geotech-
nical investigation and its subsequent report.
The geotechnical report will provide information regarding the existing soil
conditions and will provide recommendations for site preparation or soil improve-
ment activities as well as recommended parameters for building foundation design.
As a minimum, it is suggested that the following information be provided in the
geotechnical report:
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
4.2 COORDINATION
All members of the design team must coordinate their documents with the docu-
ments of members from the other disciplines. A free flow of information through a
central management point works best so that a single entity is knowledgeable of
everything that is occurring, including what information has been requested, what
has been furnished, and what is still outstanding. Traditionally, this role is performed
by the architectural firm, but in design/build situations, it can be assigned to the
construction manager or to a contractor.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
4.3.1 Adaptability
When designing any aspect of a datacom equipment center, it is important to
have a clear understanding of how much value the owner places on the adaptability
of the systems being designed.
Datacom equipment has a “refresh rate” of between three and five years; this
means that in a maximum of five years, the cutting-edge datacom equipment of today
will be outdated and will potentially be scheduled for replacement.
The design and construction process for a typical facility is 12 to 18 months; the
anticipated life span of the mechanical and electrical infrastructure is 15 to 20 years;
and the anticipated life span of the building structure is 20 to 50 years. Consequently,
the building structural system may house five to ten vintages of datacom equipment
over its lifetime. It is impossible to predict the structural requirements that will be
imposed by datacom equipment and supporting building infrastructure of the future.
However, it is possible to adopt structural design criteria that will result in a building
structure that can be easily adapted to meet future requirements.
Some specific aspects of adaptability might include:
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Conversely, a clear height that is too high will lead to inefficiencies and an increase
in the cost of the installation of any MEP infrastructure that is supported from the
overhead structure as well as an increase in the cost of the structure itself, which will
require larger column members.
In addition to vertical zones over RAF areas, clear heights are critical for
mechanical and electrical equipment rooms. When designing mechanical and elec-
trical equipment rooms, consider more than the height of the equipment itself. Below
the equipment, account for the additional height of special foundations and house-
keeping pads. Above the equipment, consider radii for conduit and piping bends and
the additional height of pipe flanges and valve bodies. In generator rooms, bear in
mind the height required for exhaust mufflers if located in the room.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Within the datacom equipment area, if the configuration of the datacom equip-
ment is known, it may be possible to configure the column spacing to reduce the
disruption to the equipment.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
the system. The structure will deflect at the time the empty pipes, racks, and equip-
ment are suspended.
Another incremental deflection will occur when the system is loaded with water
or other liquids or, in the case of rack or cable tray systems, conduits, wires, or
cables. After each loading cycle, the installers must adjust their hangers. Depending
on span lengths, planned loads, installation sequencing, and maintenance issues, it
may be desirable that supporting members be sized so the structure under collateral
load (load from all other loads above the building weight, not including the live load)
deflects no more than L/500.
• Very high straight-line wind resistance of 140 to over 200 mph (225–322 km/h)
for hurricane and/or tornado resistance
• Very high snow and/or ice loads
• Excessive roof water loads should drains fail
• Setting a building Importance Factor (see Appendix E2 for a detailed explana-
tion of Importance Factor) exceeding the code minimum
• Structural resistance to blast, projectile, vehicle, or other threat force impacts
• Structural resistance to progressive column failure in the aftermath of an ini-
tial column failure due to structural overloading or impact
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Existing Structures
and Additions
5.1 INITIAL INVESTIGATION
5.1.1 Geotechnical
When a data center occupies an existing structure, the building owner and the
structure design professionals should obtain the subsurface soils investigation report
and foundation recommendations made for the original building. In addition, the
building owner should perform any additional geotechnical investigation to deter-
mine if subsoil conditions are suitable for a datacom equipment center application.
Specifically, the owner should discover whether the new imposed loads on the struc-
ture can be successfully carried by the foundations and whether new structures can
be properly supported by new foundations. In addition to the previously discussed
items, this investigation should include but not be limited to
• soil borings within the structure to determine water table and moisture in the
subgrade and
• bearing capacity at bottom of slab level and 1–6 ft (0.30–1.83 m) below slab.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
(3.05 m) of the building, but most of the equipment yard space for a data center
extends far beyond this 10 ft (3.05 m) range.
5.2.1 Headroom
Structural clearance is one of the most challenging aspects of converting exist-
ing buildings to data centers. Nowadays, raised-access floor heights are taller, as is
some of the new computer equipment. Thus, overhead clearances for new mechan-
ical and electrical infrastructure areas are often less than desirable. First, floor slabs
are often removed and rebuilt at a depressed level to accommodate the tall genera-
tors, electrical switchgear, and chillers.
When assessing structural clearances, look not only at the typical height to the
underside of typical beams or joists but also to the lower (and more restricting)
height of the deeper beams and joist girders that carry their loads back to the
columns.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Sprinkler system mains can be found or placed within the joist space but may
be located below the joists and girders, thus influencing the headroom available.
Interior roof drains, unit heaters, and other mechanical and electrical equipment can
also be located below the roof joists. All of these elements can be raised or relocated,
but this relocation will increase project cost and will take considerable time and
effort to complete.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
existing structures where the collateral loads are already 5 psf (239 N/m2), no new
loads may be introduced without the structure being reinforced or new support struc-
tures being added.
Earlier building codes allowed the reduction of live loads on roof members that
carry more than 200 ft2 (19 m2) and on elevated floor members carrying more than
150 ft2 (14 m2). However, newer building codes have revised and even placed restric-
tions on such reductions, and in some cases they have changed required load combi-
nations. Such changes can have substantial impacts on structural capacity.
Live-load reductions have been allowed by building codes that are based on the
presumption that while an area of a column bay may be loaded to the maximum live
load (psf), this uniform load will not actually occur over the entire bay at any single
point in time. This presumption is less true with the uniform loading of large
computer rooms. Structural assessments should look for the use of live-load reduc-
tions that actually lower the actual live-load capacity of the floor due to reductions
taken on some of the major supporting beams and girders.
Design live-load requirements for data centers vary but are often within the
ranges indicated in Table 5.1. Office areas in most buildings are designed for as little
as a 50 psf (2.39 kN/m2) live load plus a 20 psf (0.96 kN/m2) partition live load. The
building code may allow the 50 psf (2.39 kN/m2) live load to be reduced under
certain conditions. This relatively low allowable live load in combination with the
live-load reduction severely limits the possibility of placement of extensive data
centers on the elevated upper floors in most buildings. In existing buildings, care
should be taken to understand the worst-case load conditions of the datacom equip-
ment and the collateral suspended loads of the building infrastructure.
Additionally, the loads imposed by equipment moving into the facility should
be understood. When those loads exceed the structural capacity of the building floor
systems, structural reinforcing is required and/or equipment must be sufficiently
spaced so as not to exceed loads. When spacing is mandated, very clear and well-
documented spacing guidelines should be prepared and given to the owner for use
during equipment move-ins and installations.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
5.3.1 Introduction
Most new data centers have complex mechanical, electrical, plumbing, and fire
protection system requirements. These systems typically require underground and
above-ground installation of conduits and cable trays carrying conduits. The
mechanical plant requires that large overhead piping systems be supported from
structures overhead. Where overhead plumbing is required, the pipes may be
required to be isolated to prevent leaks from damaging equipment. Fire protection
systems vary greatly by type and layout. The existing system may require partial
replacement or even removal.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
5.4.1 Introduction
If the existing structure is occupied and the ceilings, ductwork, and sprinklers
are installed, then adding reinforcement in an existing structure is very difficult and
intrusive. The removal of the architectural and mechanical elements will need to be
carried out by a contractor. These removals will impact the schedule and will limit
the amount of other work that can be done in the same areas. If the existing structure
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
is empty and there is little overhead interference, the possibility of adding reinforce-
ment to joists, beams, joist girders, girders, and columns and reinforcing the foun-
dation, if required to provide sufficient collateral load capacity, is preferred.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
These types of buildings usually utilize typical design and framing methods and
are usually designed by a licensed structural engineering firm, an architectural/engi-
neering firm, or a design/build contractor’s engineer. Similar to pre-engineered
metal buildings, they are designed to support the code-required loads, but rather than
using special or proprietary members, they typically utilize standard steel framing
members.
Buildings utilizing concrete or CMU shear walls typically concentrate such
elements at the building perimeter. Where buildings are large, require expansion
joints, or require additional supports due to load or configuration issues, interior
shear walls may be used. However, because these require considerable space and
may interfere with building layout or equipment routing requirements, braced
frames utilizing X-bracing, diagonal bracing, any type of chevron bracing (“K”,
“V”, etc.), or other bracing may be used. Such bracing can be concentrically located
or eccentrically located depending on design requirements. Sample elevations of
common types of bracing systems are shown in Figures 6.2 through 6.6; a sample
shear wall elevation is shown in Figure 6.7.
The various load paths, or means of transferring the loads through the structure,
should be clearly indicated on the drawings. Of particular importance are bracing
system locations where the horizontal forces from all of the contributing elements
must be collected and transferred to the foundation system. Since such systems must
sometimes be modified due to building usage changes, original design parameters
should always be listed on the project documents.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Figure 6.6 Eccentrically braced frame using diagonal bracing with link
beams.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Part III
Building Infrastructure
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Building Infrastructure
Overview
7.1 OVERVIEW
Within the context of this book, building infrastructure includes power systems,
cooling systems, and communications systems, including the structural support of
these systems.
There is both interior building infrastructure and exterior building infrastruc-
ture. The interior infrastructure may be located above the datacom equipment (e.g.,
in the ceiling cavity), in the raised-access floor cavity, on the raised-access floor, in
chases, on walls, or on the structural floor slab. The exterior infrastructure may be
located on grade, on elevated platforms, or on the roof of the building itself.
The building infrastructure is one of the more challenging aspects of a build-
ing’s structural design, especially with the significant trend toward 50% to 80% of
the total construction cost being mechanical and electrical. One of the building infra-
structure challenges is the fact that often multiple trades, systems, or subsystems
cohabitate the same area. This complicates load projections and building support
systems. From a structural perspective, the infrastructure can be broken down into
support, anchoring, and expansion and contraction.
Table 7.1 provides an overview of various building infrastructure components
and their associated weights. This table is far from comprehensive, but it neverthe-
less demonstrates the wide range of elements that can exist within the building and
the wide range in structural load capacities that may be required. Tables 7.2 and 7.3
provide some insight into the possible mechanical and electrical equipment loads.
The loads in all three of these tables are general ranges; actual loads should be
obtained for each piece of equipment. In addition, it is important to include the “wet
load” of the equipment (e.g., the load when the equipment is filled with water in the
case of piping and hydronic systems).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Mechanical
HVAC piping 10–50 (0.48–2.39)
Electrical
Cable and conduit 2–10 (0.10–0.48)
General
Suspended ceiling 1–2 (0.05–0.10)
1
Range is a general range and does not include the far extremes.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
infrastructure (piping, conduits, etc.) passes through the exterior wall or roof of the
building, an understanding of the interactions from building drift and deflection is
also important. If designed incorrectly, water intrusion or even physical damage may
occur at these interfaces.
From a structural standpoint, equipment located on grade is most easily handled
and, with the exception of water storage tanks, the load requirements associated with
the building infrastructure are easily achievable through standard soil preparation
techniques. For example, most soils can be improved to allow them to support a bear-
ing pressure of 1,000–1,500 psf (47.88–71.82 kN/m2). However, the load transmit-
ted from vertical water storage tanks may exceed this amount, in which case deep
foundations (piles, piers, etc.) may be required.
Whenever infrastructure is located on the roof of an existing building, an eval-
uation of the existing structure is required to determine if there is sufficient residual
capacity within the existing structural members or if new beams, columns, and foot-
ings need to be engineered and constructed. Figures 7.8 through 7.12) provide some
insight into the exterior building infrastructure components that may need to be
structurally supported.
Like the building itself, all exterior equipment is subject to wind loading of vary-
ing magnitudes and from varying directions (see Figure 3.1). In various regions of the
country there is a higher likelihood of strong wind or storm events such as tornadoes
and hurricanes. In these instances, the structural system and the connections to the
building infrastructure should be evaluated carefully, and consideration should be paid
to enhancing the structural system so that it exceeds the minimum code requirements.
Similarly, the equipment itself should be evaluated to ensure that it is sufficiently
robust; oftentimes, specific equipment components are designed based on maximum
wind speeds (e.g., acoustical enclosures for generators, cooling tower fill, etc.).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Structural Considerations
for Infrastructure
8.1 OVERVIEW
Chapter 8 focuses primarily on the building infrastructure that is located within
the datacom equipment room itself. From a structural perspective, the infrastructure
can be broken down into support, anchoring, and expansion and contraction.
8.2 SUPPORT
Experience has shown that within a datacom equipment room, the minimum
clear height requirement under the lowest structural member is typically between
16 and 24 ft (4.88 and 7.32 m). In these rooms, a 2–4 ft (0.61–1.22 m) tall RAF
system is often installed, the datacom equipment itself is typically between 7 and 9 ft
(2.13 and 2.74 m) tall, and distribution systems for power, cooling, and communi-
cations are routed above the equipment.
Within the datacom equipment room, building infrastructure support systems,
which could be in the form of threaded rods, cabling, strut systems, etc., are often
designed and installed in a somewhat haphazard manner. Each subcontractor basi-
cally fastens and supports its infrastructure using whatever is available. This often
leads to unanticipated point loads and complex reactions. The support systems
become even more complicated when the facility is located in a seismic zone.
Figures 8.1 and 8.2 provide some insight into interior building infrastructure compo-
nents that may be installed within a datacom equipment room.
The collateral load capacity is especially important for the installation of build-
ing infrastructure since the different subcontractors are required to coordinate the
suspended loads from the structure and must ensure that the capacity of the structure
is not exceeded.
Traditionally, cable tray systems have caused the most concern in regard to
understanding the allowable load capacity. Cable trays may either be hung from the
overhead structure, supported on the datacom equipment racks, or supported from
a strut system where stanchions are installed through the RAF to transmit the result-
ant loads the structural slab below. Cable trays are predominantly utilized for the
distribution of communications systems (which require copper twisted-pair cabling
or fiber cabling) and DC power cabling (which is typically far heavier than cabling
for AC power systems).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Cable tray systems are utilized because they allow good flexibility for the instal-
lation of cabling both during the initial construction and for future cabling. It is not
uncommon for the quantity of cabling ultimately installed to be 2 to 4 times more
than what was initially conceived and, consequently, the requirements of the struc-
tural support system must be carefully reviewed. It is good practice to identify and
permanently record both the design load and quantity of cables or approximate cable
fill percentages for all cable tray systems.
When considering a new datacom equipment center, a large increase in overall
construction costs is not required to provide for increased structural capacity at the
roof or floor level or in the columns, foundations, and bracing systems. Unfortu-
nately, speculative buildings and often build-to-suit or owner-occupied buildings are
designed precisely to the minimum code and any increased future capacity require-
ments are not accounted for.
Sometimes both cost and schedule benefit from the assignment of specific areas
within the datacom equipment center for the routing of heavy building infrastructure
distribution systems. Within these areas, floor-mounted structural frames may be
utilized to carry the structural loads rather than engineers trying to anticipate or
broadly overdesign the overhead structure.
8.3 ANCHORING
Anchorage of building infrastructure equipment that is not supported on the
RAF but is instead supported directly by a concrete slab (either suspended or on
grade) is quite straightforward. It should be understood that all equipment larger than
400 lb (180 kg) should be securely anchored to the floor per the IBC (ICC 2006).
Examples of equipment that may be located within the datacom equipment room and
that require anchorage are computer room air-conditioning (CRAC) units, power
distribution units (PDUs), and UPSs. In general, such heavy fixed equipment does
not have overturning issues. Of course, this assumption should be confirmed by a
qualified structural engineer.
As lateral loads are the primary concern for anchoring, a direct fastening system
using concrete anchors is the most direct approach. Anchorage to concrete should
use the provisions defined in ACI 318, Building Code Requirementts for Structural
Concrete (ACI 2001). Shot-in anchors, also commonly referred to as powder-driven
fasteners, are hardened steel pins that are driven into masonry or concrete by means
of a powder-actuated tool. Several anchor styles and lengths are produced for differ-
ent fastening requirements. Shot-in anchors should not be used due to their poor
performance in seismic applications. It may be desirable to use anchors that can be
removed and replaced (e.g., concrete screw anchors) if the configuration of the data-
com equipment center will change over time.
There are many standards that include typical details for the anchorage of
mechanical and electrical equipment that can be consulted for additional guidance,
such as ASCE Standard 7-05 (ASCE 2005) and the IBC (ICC 2006). Two special situ-
ations in data centers deserve additional discussion. One is CRAC units that sit on top
of frames to raise them to the level of the RAF, and the other is mechanical or electrical
equipment that requires vibration isolation.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
such as a compressor or a fan. Consequently, the anchoring methods for such equip-
ment must be configured to ensure that any vibratory energy is not transmitted to the
building structure. In general, anchoring means will utilize vibration isolators.
(Refer to Chapter 10 for a more in-depth discussion on this topic.)
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
In addition to the thermal expansion loop, there are several other types of pipe
shapes that can be used to provide for expansion and contraction, including L-bends
and Z-bends. While computer programs are typically used for detailed thermal
stress analysis, ASHRAE (2004) provides basic equations for loops, L-bends, and
Z-bends in Chapter 41, “Pipes, Tubes and Fittings.” In general, use of bends and
loops to absorb the deflection of the piping system is the preferred method, but in
many cases there is insufficient space to accommodate this expansion, especially
if the design temperature difference is high. In these cases, mechanical expansion
joints can be used.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Raised-Access
Floor Systems
9.1 OVERVIEW
Raised-access floors (RAFs) are often installed within datacom equipment
centers. The RAF directly supports all of the datacom equipment racks and several
elements of the building infrastructure; further, it protects and gives access to all of
the underfloor utilities. Collapse or major failure of the RAF would cause extensive
damage to the datacom equipment and building infrastructure and would certainly
impede egress for any personnel trying to get out. Consequently, the RAF is one of
the most critical elements in any datacom facility.
The RAF systems most prevalent within datacom facilities consist of four main
parts:
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
On some systems, the four corners of the head have separate tabs for attachment of
the stringers. Attached to the underside of the head is a threaded rod stem that sits
inside the pedestal base. A nut is used to adjust the height of the head when the floor
is leveled. The stem portion of the pedestal head can either be cast aluminum or solid
steel threaded rod.
The pedestal base is a tube with a collar on the top to accept the pedestal head
stem and a base plate on the bottom with holes that are used when the base must be
mechanically fastened to the structural floor. They come in many different heights
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
from 6 to 48 in. (150 to 1.2 m); currently, the most common finished floor heights
for datacom facilities are 18 and 24 in. (450 and 600 mm). The pedestal head often
rests on the base with no mechanical attachment.
The stringers are attached directly to adjacent pedestal heads either by “snap-
ping” them onto the pedestal heads or by screwing them in. They sometimes are U-
shaped or tube shaped and can be either 24 or 48 in. (600 or 1200 mm) long. Gener-
ally, the stringers are installed to provide lateral stability, but some flooring systems
require the stringers to increase the load bearing capacity at the edges of the RAF
panels.
The RAF panels are placed on top of the stringers and may be gravity-held,
which allows fast access to the underfloor space, or bolted to the stringer system.
Stringerless systems, also referred to as bolt-down or cornerlock systems since
they require that each RAF panel be bolted at every corner to the pedestals directly
below them, are also available, but they are generally restricted to RAFheights of 3 to
24 in. (0.08 to 0.61 m) and typically represent an unsuitable solution for datacom
equipment areas.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
1. Fixed-Base Pedestals: The lateral load is resisted simply by the base pedestal
cantilevering off of the structural floor. Figure 9.2 illustrates an installation that
utilizes fixed-base pedestals.
2. Underfloor Bracing: Supplemental lateral load resistance is provided by the
addition of diagonal braces to transfer lateral load directly to the structural
floor. Figure 9.3 illustrates an installation of underfloor bracing.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
(rather than a detailed analysis of the individual loads of every component located
on the RAF).
However, the main resistance to lateral loading remains the cantilever aspect of
the pedestals. Although theoretically the lateral loading can be transferred to the
perimeter of the RAF area and picked up by structural elements at those locations,
this is usually not the most practical approach because the floor areas of many data-
com equipment rooms are so large that the cumulative force would be massive.
It is important to note that the stringers themselves typically have a small cross-
sectional area and therefore have a limited resistance to bending. When the RAF
panels are installed, the panels and stringers interlock to form a structural
diaphragm. During the construction and installation of the building infrastructure
below the RAF, there may be a number of RAF panels removed and the diaphrag-
matic action may therefore be compromised.
Although it is rare for structural failure of the RAF system to occur as a result
of too many RAF panels being removed, it is quite common for the understructure
to shift slightly, or “rack.” When this racking occurs, it becomes difficult to properly
replace the RAF panels that were removed. Underfloor bracing systems can help
eliminate the potential for racking.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
appear to have been subjected to ground motions that would be characterized as the
“design-level” earthquake. There were, however, some interesting observations. Of
the 25 cases reported, only 7 had “significant” damage and the other 18 had only
“minor” damage. Damage to RAF panels was reported in several cases, but no
damage was reported to pedestal bases or anchorage. Most of the damage was the
result of shifting contents on top of the floor (in some cases up to 36 in. [0.9 m]) fall-
ing or damaging other equipment or the floor. Much of this equipment was on casters
that were unrestrained (EERI 1990).
A number of laboratory tests on RAFs and their attached components were
conducted utilizing a computer-controlled dynamic shake table by the Finance,
Insurance and Monetary Services (FIMS) Committee of the Federal Emergency
Management Agency (FEMA). These tests showed that the RAF can have a brittle
(not ductile) quality and may not have additional reserve capacity beyond yielding
or fracture of the first element (FIMS 1987). Several other tests have shown that
panels can “pop out” of the floor system during strong motion.
• The pedestal base plate should be anchored to the concrete floor with drilled-
in or cast-in-place anchors; lateral forces should not be transferred by friction,
shot-in anchors, or adhesive mastics.
• Avoid stringerless systems, as they often do not have a verifiable load path.
• Floor stringers should be designed to carry axial seismic loads (for at least
one panel) and should be mechanically fastened to the pedestal heads.
• Bracing (if used) should be designed to avoid a buckling mode of failure and
should utilize structural or piping shapes and not electrical conduit.
• If it is constructed of steel, the pedestal riser should be welded to the pedestal
base plate with regular welds and not brittle resistance welds; the user should
also consider requiring physical tests of the pedestal riser for a minimum lat-
eral load.
• All floor panels with equipment attached directly that transmit shear to the
panel should be corner locked with screws to the pedestal head.
• All floor panels with equipment attached directly that transmit overturning to
the floor system (i.e., equipment that does not have its own system holding it
down to the concrete) should not utilize “slip-on” pedestal heads but rather
should have a mechanism to transfer uplift to the pedestal base.
• Pedestals should have maximum deflection limits.
• Adding corner lock screws to all panels in egress pathways should be con-
sidered.
These recommendations are mostly directed toward ensuring that lateral loads
generated by equipment resting on and attached to the RAF floor gets transmitted
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
to the concrete floor below using a verifiable and sufficient load path. It should be
noted that the above recommendations are good practice even in areas of moderate
or low seismicity. Many of the above recommendations came out of the FIMS guide-
line published in 1987 (FIMS 1987). This document was important because it was
one of the first to go beyond what had been typical industry practice at the time.
Several of these recommendations have been incorporated into building codes as a
better performing alternative to standard RAFs (see the Special Access Floors
section below).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
10
Vibration Sources
and Control
10.1 OVERVIEW OF VIBRATION SOURCES
The building infrastructure includes equipment that is a potential source of trou-
blesome vibration. Chapter 10 provides an overview of sources of vibration and the
control of vibration.
Within a datacom equipment center, some representative vibratory sources
include standby generators, cooling towers, air-handling units, chillers, and CRAC
units. In fact, any equipment that includes a rotary component such as a compressor
or a fan is a potential source of vibration.
Although there is the potential for vibration caused by a component of the build-
ing infrastructure to be transmitted to the datacom equipment room, most datacom
equipment is fairly tolerant to vibratory loads and there is generally little risk of fail-
ure being caused in this manner. Of more concern is the impact that uncontrolled
vibrations will have on the equipment that is the vibratory source and any distribu-
tion systems that are directly connected to this equipment. The building infrastruc-
ture is by its very nature critical to the successful operation of the datacom
equipment, and any failure in the building infrastructure, such as the loss of power
or cooling, will directly impact the datacom equipment.
It is therefore important to address the vibration isolation of building infrastruc-
ture equipment within a datacom equipment center. Fortunately, the means of vibra-
tion isolation are fairly well known in the industry and there are several publications,
such as the ASHRAE Handbooks, that provide a more in-depth study of this topic.
For the purposes of this publication, we only consider vibration isolation for building
infrastructure equipment, which is located within or immediately adjacent to the
datacom equipment room.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
should be used often has much to do with the dynamics of the isolated component
and where it is located within the building.
The component’s location—grade or above, indoor or outdoor—enters into
isolator selection. An isolator’s ability to isolate is a function of the rigidity or stiff-
ness of the mass that it is being supported by (e.g., the structural floor system).
For isolators intended for use in above-grade applications, the intrinsic live-load
deflection of the floor must be added to a selected spring deflection that is properly
sized for the component’s disturbed frequency to overcome the lack of stiffness
inherent by design. This relationship is clearly defined in Chapter 47 of ASHRAE
Handbook—HVAC Applications (ASHRAE 2003).
Vibration isolators must not only isolate and restrain equipment but also must
have the ability to accept high transient dynamic loads. These transient loads can be
induced by seismic events, wind, or man-made sources.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
energy from reaching the floor below, it is recommended to universally select 2 in.
(51 mm) of isolator static deflection for all components except the boiler, if appli-
cable, where 1 in. (25 mm) will suffice.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Part IV
Datacom Equipment
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
11
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
root mean square (rms): a value of a set of numbers that is the square root of the
average of their squared values; a technique to determine the average magnitude of
a dynamic signal, giving the effective energy or power level of that signal.
transient vibration: a vibration that has a high amplitude and is of short duration,
typically only a few cycles, and unlikely to produce resonance.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
following intermittent and temporary operational sources may also exist and can
have harmful effects on equipment.
Any one of these activities can generate a great deal of ground motion with
disturbances that can travel and be sensed over great distances. The State of Cali-
fornia Department of Transportation (CalTrans) conducted a study (Eagan et al.
2001) between June 1999 and May 2000 to record and document dynamite blast
ground movements. CalTrans established the safe level for ground movement at a
peak particle velocity of 50 mm/s when blasting in urban area. In the CalTrans study,
two recorded events exceeded the established level, with levels at 70 mm/s peak
particle velocities recorded at distances of 18 and 30 m from the blast site.
The effects of vibration transmitted through the building floor can be even more
severe if the floor is excited at resonant frequencies of the equipment or building. For
example, vibratory pile drivers drive their piles at 1600 vibrations per minute and are
very likely to excite nearby buildings. Pile driving works by liquefying the soil next
to the pile. This allows the pile to move easily down into the ground. The amplitude
of the building’s floor can be multiplied to a level where data center equipment walks
across floors, equipment shakes to levels at which soldered joints crack, components
are caused to separate from holders, or heavier power components fail.
In addition to equipment component damage from severe vibration levels, there
are other risks associated with the equipment. The displacement of racked equip-
ment can separate cables from their connectors or disengage power cords from the
equipment. Datacom equipment on RAFs can move across the surface and result in
a rack foot catching or falling into a cable cutout or even tipping over. Even the very
heaviest of datacom equipment and infrastructure equipment can move under
continuous vibratory conditions.
Although not directly related to shock and vibration, a rack tipping over is an
issue that can impact service within the data center. Equipment racks can also over-
turn from unbalanced weight within the cabinet. It is common for telecommunica-
tions equipment, networking equipment, routers, or UPS equipment to weigh 300–
400 lb (1335–1780 N) per shelf, and a larger server can weigh up to 3600 lb (16,017
N). With the majority of the equipment weight supported by the front set of mounting
rails, the cabinet becomes front weight biased, which increases its chances for
tipping over. Large overhead loads that some equipment racks support also add to
the problem. Cables or cooling equipment placed over the racks moves the center of
gravity of these cabinets to an unstable configuration. An accidental bump or an
inadvertent push tips over these cabinets more easily.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
agencies. For most commercial enterprises, however, the practices for securing
equipment for natural and man-made risks should be satisfactory.
Considerations for reducing shock and vibration risks within the data center
should focus on securing cabinets as the primary defense against vibratory effects.
Shock and vibration isolation, shock absorption, or other mitigation techniques may
be considered but are generally more costly and more difficult to design. Isolation
design and techniques typically require assumptions on ground motion amplitudes,
frequencies, and providing additional space for the device displacement. The device
becomes less effective working outside of these assumed conditions. In very dense
telecom environments, the space necessary for the movement of an isolator may not
be easily provided. The equipment must be permitted to move freely in all horizontal
directions, which will be summarized in later chapters. In nonisolated installations,
cabinets that have been secured from tipping over or impacting adjacent objects at
least permit the equipment to operate up to its designed ambient vibration levels or
Network Equipment-Building System (NEBS) environmental vibration conditions.
It has been demonstrated using shake table tests that equipment will remain func-
tional up to its design conditions when properly installed.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Datacom products are designed in sizes ranging from a small desktop box to
multiple shelves filling a cabinet. Datacom equipment can weigh from as little as a
few pounds to several thousand pounds per shelf space. Shock and vibration testing
is more difficult to determine and test since these days the norm is to mix and match
products from various manufacturers to form a system that provides specific
services. Not all equipment frames are designed alike, and the installation of data-
com products in an open relay rack versus a closed cabinet will have an effect on
shock and vibration performance. Even among open relay racks, there are designs
with very light gauge aluminum uprights in addition to much stronger welded steel
designs. These differences have a direct effect on how well a product performs when
subjected to shock and vibration tests. Cabinets with side panels and doors will
perform better than open cabinets; lightly loaded datacom equipment frames will
perform better than heavily weighted frames.
Unfortunately, there are no established industry standards that provide product
testing guidance. Therefore, datacom equipment testing parameters must be devel-
oped that address all the configurations of the datacom equipment that may exist.
The question to consider is: Will the end user be content with individual product
testing, or will the end user need overall system testing with all of the components
working together? The datacom equipment designer will need to determine the
users’ requirements for demonstrating the datacom equipment’s capabilities and
establish an agreement on how the tests will be conducted with the pass/fail criteria
clearly defined.
Larger mechanical equipment such as HVAC equipment is much more difficult
to test. There are limited test laboratories with large shock and shaker tables avail-
able to conduct tests on large, heavy equipment. There may also be less need to test
mechanical equipment because of the design of these products. The major compo-
nents of these products are much more robust steel assemblies designed to operate
at high hydraulic or air pressures. One area where tests should be required and
performed on large mechanical equipment is the testing of equipment controls,
which includes circuit panels, monitoring equipment, gauge sets, and other electrical
devices governing the operation of the equipment.
Shock and vibration tests should be conducted to demonstrate the products’
capacity to sustain shock levels associated with transportation from the manufac-
turer’s factory, receiving the product at the user’s facility, and installation and oper-
ation in the user’s equipment room. Therefore, several tests need to be designed for
all datacom products. For transportation purposes, boxed and unboxed product
conditions must be able to tolerate shock and vibration loads related to moving the
product from the storage site onto a truck or train. The product will need testing to
simulate being transported across the country on rough roads with very little cush-
ioning provided by the suspension of a truck or train. At many points during its life-
time, the product may be dropped or mishandled (when arriving at its destination,
for example, or when being transported from one floor of the building to another)—
consequently, the product will need to tolerate all movement expected at the data
center. When the datacom equipment is installed within an equipment framework,
the product will live out its life either in a calm, gentle existence or subjected to low-
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
level steady ground movement with an occasional larger bump from an earthquake
or accidental impact on the frame.
Shock and vibration tests are usually broken down into four conditions: 1) oper-
ational shock and vibration, 2) seismic simulation, 3) ruggedness or fragility, and 4)
transportation shock and vibration. Each test has specific levels and defined param-
eters unrelated to the others. For example, office vibration levels are usually lower
than transportation vibration levels; office tests are run with equipment powered
while transportation testing does not require powering equipment. The seismic
simulation test, which can be categorized as an operational vibration test, has differ-
ent frequency content requirements and significantly higher amplitudes at a
frequency below 10Hz than do operational office tests.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
structure. The waveform contains a short period of very strong motions with periods
at lower levels of ground motion. Peak ground acceleration approaches 1.6g at the
test table, and when taller equipment is mounted to the test table, acceleration levels
could be amplified to much higher levels. Based on studies of seismic events in Japan
(IBM 1992b), IBM Corp. developed seismic simulation testing parameters for IT
equipment.
Seismic simulation testing is performed similar to the operational shock and
vibration testing. The product to be tested should be configured with similar loads
and cabled as if installed in users’ datacom facilities. For telecommunications equip-
ment, the test parameters are defined in NEBS GR-63-CORE (Telcordia 2006). This
document and the ANSI T1.329 (ANSI 2002) documents also contain specific tests
for earthquake conditions and can be used for reference. Most major test laboratories
are familiar with these test specifications and should be able to conduct the tests on
any product. The earthquake tests in these two documents have optional parameters
for zone intensities that product designers should consult for the earthquake zone
designation of the user’s site. It is always safe to assume worst-case conditions and
test to zone 4 parameters, which envelop all other zones if earthquake tests are
required. The International Code Council Evaluation Service (ICC-ES), a subsidiary
corporation of the International Conference of Building Officials (ICBO), published
AC-156, Acceptance Criteria for Seismic Qualification by Shake Table Testing of
Nonstructural Components and Systems, (ICC-ES 2007) and defined the required
response spectrum for equipment. Plots of seismic test parameters for different test
specifications are shown in Figure 11.2 Chapter 13 discusses the analysis of data-
com equipment and seismic anchorage systems.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
should limit the shock transmitted to the critical component to levels below the
fragility limit of the components when mounted in the rack. Typical drop tests for
racks weighing more than 1000 lb (4450 N) are done by performing two tests at 4 in.
(102 mm) free-fall equivalent drop heights followed by 10 drop tests at 2 in. (51 mm)
free-fall equivalent drop heights. Typical vibration tests are a sine sweep at 0.5g for
30 min followed by a random vibration test for 15 min at 0.8 grms, as shown in
Figure 11.3 (Notohardjono et al. 2004).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
(76.2 mm) compared to 12 in. (304.8 mm). The product mass will also determine the
drop height, with heavier equipment dropped from a shorter distance.
Although end users have some interest in transportation tests because the
replacement equipment process could delay in-service dates, these tests are more
important to the equipment manufacturer than they are to the end user. The product
manufacturer must ensure that the datacom equipment arrives at the user’s site with-
out damage and in working condition, because if the product is received damaged
it will have to be replaced at the manufacturer’s expense. Given these conditions,
equipment manufacturers should focus on transportation testing.
Transportation vibration tests consist of frequency sweeps of approximately 2–
200 Hz. Typical transportation test parameters are shown in Figure 11.3. Typical
drop tests for racks weighing more than 1000 lb (4450 N) are done by performing
two tests at 3 in. (76 mm) free-fall equivalent drop heights followed by 10 drop tests
at 1 in. (25 mm) free-fall equivalent drop heights. In documents such as Telcordia’s
NEBS GR-63-CORE (2006), there are two test parameters that cover transportation
using smooth or normal means of transport contrasting to rough means of transport
such as aircraft with reciprocating engines. Product designers should determine the
worst-case situation for their products.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
one is now in place: NEBS (Telcordia 2006). Should any major component within
the cooling system fail, an environmentally hostile environment will result within
the datacom equipment room. The datacom equipment that the cooling compo-
nents support will also undoubtedly have reduced reliability and shortened life
expectancy.
As mentioned previously, the IBC requirements are primarily for components
located in geographically charted seismic locations. The maximum considered
earthquake ground motion charts (see Figure 1615 of IBC [ICC 2003]) encompass
nearly 40% of the United States. Additional IBC requirements now include coastal
and inland locations from Maine to Texas that are subjected to hurricane-force
winds; fragility requirements remain optional in all other locations. Considering the
meaning of the term mission critical—a system that is absolutely necessary for
continued operation—this topic needs further consideration. Designing for “mission
critical” equipment should cause a relatively minor cost increase to improve and
move a product line to ”compliant” status.
Unlike the shipping hold-down philosophy but similar to Telcordia’s practices,
the IBC established a series of test procedures. These procedures are based on reso-
nance at various frequency levels and the responses of the component and its
subcomponent assemblies to various input frequencies. Through stiffening the
casing, structural members, and internal components, the unit’s natural frequency
moves high enough to place space between the lower frequencies generated by an
earthquake and the passage of some resulting frequencies to the mounted compo-
nents. The ultimate goal is to establish the “on-line” capability of a component
before and after a seismic event.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
The unit under test, or UUT, must clearly demonstrate the following:
• that the unit will not pose a safety hazard to personnel due to collapse, anchor-
age failure, or the dislodgement of subassemblies;
• that the unit containing hazardous or flammable materials will not release
those materials that could pose a danger to humans or the environment; and
• that the unit deemed essential either by code or by owner requirements for
“mission critical” status satisfies all functional and operational tests.
The “shake test” option is undoubtedly the most practical test method to prove
the component’s real capabilities. Frequently, components are too large or cumber-
some or the manufacturer’s time constraints make it impractical to carry out this
form of testing, however. In these instances, finite element analysis becomes the next
sensible choice.
Finite element analysis or computer modeling create a replica of the component
and examine both material and fastenings. AC-156 (ICC-ES 2007) is also used as the
performance template for finite element analysis modeling, which has the same
requirements as shake table testing. Again, representative component samples are
utilized for the UUT to accelerate the process and to minimize costs. Finite element
analysis analyses are most effective and mainly used to model the unit’s structure.
Performance testing of subcomponents such as motors, compressors, and panel
boards are more efficient using shaker tests than using generated computer model-
ing. The shortcomings of finite element analysis are the accuracy of the modeling
and whether complex assemblies have been reflected properly.
The final compliance option available to manufacturers of components is
referred to as “The Experience Data Alternative,” which means learning from user-
reported data. If it can be proved that an identical unit survived an identical event in
an identical structure, that product will comply with the building code requirements.
To demonstrate this, it requires a manufacturer to use “nationally recognized proce-
dures” for the design and evaluation requirements to validate the component’s seis-
mic capacities. Capacities must meet or exceed the seismic demands established by
the IBC. The main legal issue linked with this form of compliance is the absence of
“nationally recognized procedures.”
Manufacturers that use and successfully meet or exceed the AC-156 seismic
program requirements will display evidence of testing and compliance. The manu-
facturer will rigidly affix a compliance data label (Figure 11.5) to the shipped
component for use by construction and building officials. The identification label
lists, among other things, the testing agency, function, and performance character-
istics of the component and the representative samples utilized as the test basis.
Keep in mind that “online requirements” for a component include all hardware,
accessories, options, and attachments that enable that component to perform its
“intended function.” The obvious items that fall within this category are pipes, ducts,
and electrical connections. Not-so-obvious items that fall into this category are floor
stands, vibration isolation components, and control panels. Any component that the
manufacturer supplies as an accessory or option must therefore be included in the
analysis to have or withstand the same level of vibration as the component itself.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
If an owner is truly eager for a datacom space that will “continue to perform,”
there must be a validation of those desires specifying a series of products that will
do just that. For some datacom facilities such as Emergency 911 call centers, hospi-
tals, or government installations, there is no option, it’s the law! A seismic floor stand
as shown in Figure 11.6 may be installed to satisfy the desire to have datacom cool-
ing equipment and infrastructure “continue to perform”.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
12
Seismic Anchorage
of Datacom Equipment
12.1 OVERVIEW
There are datacom equipment centers located throughout the world, many in
areas where there can be significant earthquakes. Some areas within the United
States, such as most of California, the Pacific Northwest, and Salt Lake City, are
areas that have well-known high seismic risks, but the fact is that all 50 states have
recorded earthquakes. Damage from earthquakes due to falling objects can induce
bodily injury and can seriously impair occupants’ ability to evacuate a building once
the shaking has stopped. In addition, the financial losses due to heavily damaged
equipment or loss of service can be devastating.
This chapter gives an overview of seismic anchoring and lists several key
aspects of protecting data center equipment from the damaging effects of earth-
quakes. This information is not meant to be a substitute for the building code or to
replace the services of a qualified structural engineer that is licensed to perform the
required calculations. Rather, it is meant to give the owner or engineer a general
background in the seismic requirements for nonstructural components as well as to
explore some particular topics in detail with commentary and guidance where appro-
priate.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
contours. For owners, this will be a significant challenge because where before one
could simply use “zone 4” datacom racks, there is no longer one design level that
covers every corner of a geographical area.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
It should also be understood that many codes, including the IBC, require the
addition of vertical seismic forces to the horizontal forces in order to quantify the
entire effect of the earthquake on a component. Equations 12.4-1 and 12.4-2 of
ASCE Standard 7-05 (ASCE 2005) should be used for this purpose.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
of equipment. The effects on the equipment cabinet from the two horizontal direc-
tions of earthquake motion are the most obvious and are often effectively resisted
using clips at the bottom of the cabinet feet, attached directly to the cabinet frame,
to resist the horizontal shear in each direction. If these clips are attached directly to
the RAF panel, corner lock screws are needed to transfer this shear load to the pedes-
tal head.
When the equipment cabinet is much taller than it is wide, it is prone to over-
turning (forces attempting to tip the cabinet over). Datacom equipment cabinets are
often ganged together using bolts in the longitudinal direction (down-aisle) so that
the cabinets act as one much larger unit. This greatly reduces the impact of over-
turning forces in the down-aisle direction. However, the transverse (or cross-aisle)
direction still needs to be managed because it produces forces coupled to the legs at
the bottom of the cabinet where one is in tension and the other is in compression. The
load path of both the down-aisle and the cross-aisle configurations must be consid-
ered. Tension forces can be handled in a number of different ways and will be
explored in the next section, but the compression force should not be overlooked. A
tall equipment cabinet with a large horizontal force and a narrow width can produce
a large compression force that must be resisted by the RAF panel and understructure
system. It is possible for the small hard castors supporting the equipment cabinet to
punch through or break a floor panel as a result of overturning compression.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
floor underneath the rack at each side to allow better positioning of the rod side
to side. These anchor rods do not resist horizontal shear without a special addi-
tional feature such as an additional clip to prevent horizontal movement; there-
fore, they are often used in conjunction with clips for this purpose. Another
improvement is to use a turnbuckle to achieve easy tensioning of the rod and to
induce a compressive load to resist the horizontal force. Schematic details of
this technique are shown in Figures 12.2 and 12.3 and photographs of this
installation method are shown in Figures 12.4 and 12.5. The improved detail
using slotted metal framing is shown in Figure 12.6.
2. Splay Cables: Another common anchoring option is to use wire rope cables,
called splay cables, to restrain the cabinet in all directions. Splay cables have
the added benefit of resisting loads in horizontal shear as well as in vertical
overturning. The disadvantage of this method is that since the wire rope only
resists tension, four cables are needed, one in each direction at each corner of
the cabinet. Wire rope can be easily threaded through the holes in the corners
of server cabinets and can be secured with wire rope clamps (three minimum
each end). In general, the wire should be located 45° to vertical and horizontal
(hence the term splayed). Wire rope has the benefit that it can be worked
through existing obstacles and does not have to be perfectly located in order to
be effective. Wire rope installs can also utilize turnbuckles to ensure each rope
is tight, but this is often not necessary, as the slack in each rope will tighten as
the cabinet shifts on the RAF during an earthquake. Photos of this installation
method are shown in Figures 12.7 and 12.8
3. Rigid Platforms: Similar to air-conditioning equipment that is placed on RAFs,
some datacom equipment cabinet vendors manufacture a rigid steel base that
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Figure 12.2 Vertical anchor rod detail at server cabinet. Reproduced with
permission from Notohardjono (2003).
Figure 12.3 Vertical anchor rod detail at floor. Reproduced with permission
from Notohardjono (2003).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Figure 12.6 Vertical anchor rod detail at floor using slotted metal framing.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
can support the equipment cabinet directly so that it does not sit directly on the
RAF. Although this makes bracing the datacom equipment cabinet much easier
and ensures excellent performance, there are a few drawbacks. First, if the data-
com equipment is not located exactly at the edges of a RAF panel, the RAF
panels must be cut and the new free edges supported by either edge angles or
additional RAF stanchions. Second, the datacom equipment cannot be easily
moved in the future, as the datacom equipment platform would have to be
moved as well.
4. Top Cabinet Snubber: Sometimes it is not possible to anchor the server cabinets
to the floor below. When this happens, another option is to add “snubbers” to the
top of the equipment cabinets to help restrain them from overturning. There are
several specific considerations with this method. First, the bracing must be stiff
and strong enough to resist the often large overturning forces on the cabinets.
Second, these large forces must be transferred to the structure somewhere, and
often the ceiling is not nearly adequate for this purpose—in some cases, the ceil-
ing must be greatly reinforced or the bracing must continue up through the ceil-
ing to the floor or roof structure above. Third, above-server bracing makes
moving the servers difficult in the future and makes running cables in raceways
above the datacom equipment very difficult. For a heavy datacom equipment
cabinet, the top cabinet snubber can be combined with one of the three anchoring
methods above. A schematic detail of this technique is shown in Figure 12.9, and
a photograph of this installation method is shown in Figure 12.10.
5. Isolation Platforms: A new way to anchor datacom equipment cabinets to the
RAF is to not anchor them at all but rather place them on an isolation platform.
These platforms, using similar techniques as base isolation bearings used in
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
buildings though on a much smaller scale, use the same technique to decouple
the motion of the ground from the item being isolated by shifting the funda-
mental resonance frequency. These platforms have the added benefit of being
able to be “tuned” so that the datacom equipment on top of the platform expe-
riences only a specified acceleration level and, thus, the probability that the
datacom equipment will remain operational is improved. There are two impor-
tant details to keep in mind with these systems, however. First, the isolation
bearings in the platform lengthen the period of the cabinet by displacing a large
amount (up to 8 in. [200 mm] in every direction), so an adequate amount of
empty space is needed around the cabinet for the system to work properly and
be unobstructed. Second, the isolation bearings have a discrete amount of
displacement capability, which may not be adequate in larger seismic zones or
for installations many levels above grade. A nonlinear analysis conducted by a
qualified structural engineer should be undertaken to ensure adequate displace-
ment capacity of the bearing being considered. Note that when specifically
detailed, equipment cabinets can still be ganged together side-to-side in a row
using these systems. A photograph of the platforms installed is shown in
Figure 12.11.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
13
Analysis of
Datacom Equipment and
Seismic Anchorage Systems
13.1 OVERVIEW
Guyan reduction solver and Lanczos method solver: numerical procedures used by
finite element analysis as iterative algorithms that are adaptations of power methods
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
to find eigenvalues and the eigenvector of a square matrix. They are particularly
useful for finding decompositions of very large sparse matrices.
parabolic shell element: a type of element used in finite element analysis to repre-
sent a surface.
rigid element: a type of element used in finite element analysis that will not deform
under loading.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
at the joint. The complete frame model consists of approximately 110,000 parabolic
shell elements (see Figure 13.1).
The finite element model was then solved using a normal-mode dynamics
solver to verify that it indeed accurately can predict the vibration behavior of our
real-world structure. The numerical analysis was conducted using a Lanczos method
solver. The advantage here is that this method is much faster than a traditional Guyan
reduction solver (Golub et al. 1972).
The result from the normal-mode dynamics solver provides a good correlation
with the experimental frame test. Examinations of the resulting mode shapes reveal
that the first and second modes of vibration correspond to the first lateral swaying
mode (6.9 Hz) and first torsional mode (36.35 Hz), shown in Figure 13.2. Corre-
spondingly, the experimental modes were found to occur at 5 and 38 Hz. Therefore,
the analysis results can be said to be a good predictor of the actual structural
response.
Now that correlation has been established between the finite element model and
reality, a series of design scenarios can be evaluated to investigate various earth-
quake anchorage systems as well as in-frame stiffening concepts for this datacom
equipment frame.
Figure 13.1 Finite element model of frame with vertical anchors subjected to
the maximum seismic horizontal design force Fp (defined by
Equation 13.1). Reproduced with permission from
Notohardjono and Canfield (2007).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Figure 13.2 Mode shapes of the frame: (a) lateral sway mode, 6.9 Hz, and
(b) torsional mode, 34.2 Hz. Reproduced with permission from
Canfield and Notohardjono (2004).
Some of the most important components in the datacom center that need to be
anchored are the datacom equipment frames. There are many different techniques
for anchoring frames to RAF systems to prevent overturning of the equipment. Many
of these anchorage system solutions are discussed and illustrated in Chapter 12. One
common anchoring system used to secure datacom equipment frames is vertical
steel rods that attach to the frame and to the concrete subfloor (depicted as a finite
element model in Figure 13.1). These anchors are located at each corner of the frame
and transfer the large inertial forces of datacom equipment down to the subfloor.
To build an analysis model, first we need to define the model and then the load-
ing and the boundary conditions. For illustration purposes, a generic server with a
total height of 78.7 in. (2 m) is represented as a simple lumped mass suspended in
its frame. We assume that the RAF will support the static weight of the IT equipment
cabinet and that the anchors, with one end connected to the frame and the other ends
fixed to the floor or to the ceiling, will resist the forces that would try to overturn the
frame.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
For this load case, let us assume the datacom equipment is installed in a data-
com center in California. The maximum seismic horizontal design force Fp per
Equation 13.3.2 in ASCE Standard 07-05 (ASCE 2005) is given as follows:
where
SDS = short period spectral acceleration at 1 s period = 2.48g in a high seismic
zone
Ip = component importance factor = 1.5 when the datacom equipment is
required to function after an earthquake
Wp = equipment weight
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Figure 13.3 Evaluation of four vertical bottom anchor rods for various
equipment configurations. Reproduced with permission from
Notohardjono and Canfield (2007).
Figure 13.4 Evaluation of eight vertical anchor bottom and top rods for
various equipment configurations. Reproduced with
permission from Notohardjono and Canfield (2007).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Structural add-on supports are another area of investigation and design study for
various types of earthquake retrofit kits that use different classes of structural
elements. Each element is examined and then compared based on its effectiveness
in increasing datacom frame rigidity.
To limit lateral motion during earthquake events, one stiffening concept uses a
triangular support brace in combination with two other support bars (see
Figure 13.5a). This triangular brace is installed with hinged pins on one corner post
of the frame and is restrained on the opposite side by a latch and fastener. In this
configuration, the triangular brace with its hinged pivots provide easy access to the
rack-mounted components when they are installed in the frame.
An alternate option is to use an array of rear support trays (see Figure 13.5b).
In this scenario, seven trays all grouped together are examined. Each support tray is
bolted separately to the frame. The geometry of these support trays allows for instal-
lation without hindering the routing of cables, which are typically spread throughout
the rear of a datacom equipment cabinet.
The section that follows evaluates the variation of these two structural add-on
supports.
Figure 13.5 (a) Triangular brace and support bars and (b) group of support
trays. Reproduced with permission from Canfield and
Notohardjono (2004).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
1. bare frame
2. single set of tray supports (Figure 13.5b)
3. double set of tray supports (at frame’s front and back)
4. single triangular support (Figure 13.5a)
5. double triangular supports
6. triangular and tray supports
Each variation of the finite element analysis model was solved using the
Lanczos normal mode dynamics solver in ANSYS (ANSYS 2006).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
first harmonic to a higher frequency. On the other hand, all design scenarios using
triangular supports successfully shifted the occurrence of the first mode to 45.0 Hz
and higher. Figure 13.7 depicts the mode shapes of the least effective and most effec-
tive design changes to the frame’s geometry. This evaluation demonstrates that the
cross-bracing provided by the triangular supports is much more successful in
increasing the harmonic frequency or the overall lateral rigidity of the system. In
other words, the harmonic frequency of the frame increases as a result of the
increased frame rigidity. The increased harmonic frequency will lead to a reduced
lateral sway of top of the datacom equipment.
First
Harmonic 6.93 12.34 14.8 45 45.3 53.27
(Hz)
Second
Harmonic 35.66 36 36.35 56.3 57.08 61.37
(Hz.)
Figure 13.7 (a) Double tray support design, first mode shape (14.8 Hz) and
(b) double triangular support design, 1st mode shape (53.3 Hz).
Reproduced with permission from Canfield and Notohardjono
(2004).
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Olson, R.A. 1992. Earthquake protection for data systems. Disaster Recovery
Journal 5(2):35–42.
Pekcan, G. 2007. Private communication, University of Reno at Nevada, Reno,
Nevada.
SBCCI. 1997. Standard Building Code. Southern Building Code Congress Inter-
national, Inc. (now International Code Council), Washington, DC.
Tate. 2003. Bolted stringer understructure for concore and all steel access floor
panels-24 in. type 6A. Jessup, MD: Tate Access Floors, Inc.
Telcordia. 2006. Network Equipment-Building System (NEBS) Requirements:
Physical Protection, Generic Requirements. GR-63-Core. Piscataway, NJ:
Telcordia Technologies, Inc.
US Army. 1992. Tri-Service Manual TM 5-809-10, Seismic Design for Buildings.
Washington, DC: Department of Army (Corps of Engineers). www.usace.
army.mil/publications/armytm/tm5-809-10.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Appendix A
Codes for
Building Structures and
Structural Components
The primary purpose of the United States building codes has been to protect the
life and safety of the building occupants and those who are immediately outside of
the building. Building code requirements generally apply to new construction and
to existing structures undergoing significant additions or alterations.
The intent of such codes is to ensure that buildings are capable of supporting
specified gravity loads without structural or architectural distress and that buildings
do not experience structural collapse during major earthquake or wind events at or
exceeding the minimum design level specified by the code. However, it is assumed
that such buildings may experience structural distortions or damage and moderate
to even severe cosmetic damage.
As the result of several natural and man-initiated disasters in the early 2000s,
other considerations have become more important, such as keeping exits open to
allow escape from the building and keeping essential facilities, such as hospitals and
communication centers through which emergency calls are routed, functional after
such events. The economic impacts of any occurrences on the structural and nonstruc-
tural elements of the building are also starting to receive more focused attention.
The use of building codes to establish minimum acceptable design standards
has been common practice since the early 1900s. Since that time, several regional
organizations have developed model building codes that varied across the United
States. In 1994, these regional organizations—Building Officials and Code Admin-
istrators International, Inc. (BOCA), International Conference of Building Officials
(ICBO), and Southern Building Code Congress International, Inc. (SBCCI)—
decided to combine their efforts and formed the International Code Council (ICC),
which published its first major code editions in 2000.
At the time of writing this book, most US states, counties, cities, and govern-
ment agencies have adopted one of the model codes, adapted one of the model codes,
or, in some cases, written their own building codes. In addition, some states adopt
a specific building code (or, often, a group or set of codes covering various functions)
for statewide use, sometimes with state amendments but usually leaving it up to the
local governing agencies to adapt this code and choose how compliance is to be
enforced. Local agencies usually have the prerogative to amend the state-ratified
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
code or insert their own additional requirements. This may result in significantly
different requirements in adjacent or nearby jurisdictions.
To ensure code compliance, local governmental agencies require that builders
bring their projects through the building plan review process. The plan review
process typically considers the site where the structure will be built, the structure
itself, and all of the building functions, such as electrical, mechanical, plumbing, fire
protection, etc. Small municipalities, such as rural towns and counties, may not be
able to provide these services; therefore, code compliance may be done at the
regional or state level. Larger metropolitan areas have local planning boards that
review, approve, and issue building permits and, upon project completion, issue
certificates of occupancy.
Some states delegate their code adoption and enforcement authority to the
subordinate local jurisdictions but may exempt their own buildings from compliance
with local building codes or local amendments in favor of a statewide building code.
Additional nongovernmental reviews may be required in some instances, such as
lending institutions requiring conformance to local codes and insurance companies
sometimes encouraging conformance to specific codes or guidelines by offering
premium incentives for such compliance.
However, despite these various reviews and approvals that may be required, in
all cases, the design professional bears the ultimate responsibility to ensure that his
or her design meets the applicable building codes, that the design intent is under-
stood by the construction team, and that the structure in its final form is constructed
in general accordance with the contract documents.
The major codes used in the United States today are based on the International
Building Code (IBC), the model code published by the International Code Council.
This model code, now in its third edition (with editions dated 2000, 2003, and 2006),
was based largely on three earlier model codes: The BOCA National Building Code
(BOCA), the Standard Building Code (SBC), and the Uniform Building Code (UBC),
all of which were published in numerous editions.
Some jurisdictions still utilize one or more of these earlier codes. In addition,
the National Fire Protection Association (NFPA) produces a number of codes and
model codes, including NFPA 5000, Building Construction and Safety Code (NFPA
2003), which may be utilized by some jurisdictions. Guidelines, methodologies, and
supportive standards are also developed and provided by various technical societies.
Some of the guidelines and publications from such societies are listed below.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
DOD—Department of Defense
UFC 4-023-03, Design of Buildings to Resist Progressive Collapse
FM—Factory Mutual
FM Global has produced property loss prevention data sheets for many building
issues or components, including:
1-28, Design Wind Loads
1-29, Roof Deck Securement and Above-Deck Roof Components
1-54, Roof Loads for New Construction
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Appendix B
Weights of Materials
Table B.1 Minimum Dead Loads
Loads shown below are approximate. Many materials have variable weights. When in
doubt, consult the manufacturer or supplier.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Concrete (Reinforced)
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Appendix C
Raised-Access Floor
Calculations
C.1 RAISED-ACCESS FLOOR PANEL LOADING DEFINITIONS
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
C.2.1 Definitions
For the purpose of floor loading calculation, the following definitions will be
used in this chapter.
machine area: the area directly beneath the datacom equipment defined by the
length and width dimensions representing the equipment’s perimeter. The machine
area is represented as A in the formulas in the next section.
service clearance area: the area around the datacom equipment. Service clearance
areas of adjacent data equipment may overlap. The size of the service clearance area
depends on the application of the equipment and the expected environment in which
the equipment will be installed. When the equipment is installed against a wall, the
service clearance area should permit front-end servicing or adequate provisions
should be made to facilitate movement of the equipment as required.
weight distribution area: the area around the datacom equipment. Weight distribu-
tion areas may not overlap. Given that service clearance areas can overlap but weight
distribution areas cannot, when two pieces of equipment are installed next to one
another, only half the area between the equipment can be used for weight distribution
for either equipment. If the result is not sufficient for proper weight distribution, the
distance x between the machines has to be increased until the proper distribution is
achieved. The weight distribution area is represented as S in the formulas in the next
section.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
+ ( K1 × S ) + K2 × ( S + A )
FL = M
---------------------------------------------------------------------- , (C.1)
S+A
where
FLR = maximum floor load rating in N/m2
FL = floor loading in N/m2
M = datacom equipment weight in N
K1 = live load in the weight distribution area at 718 N/m2
K2 = RAF/cable load for the area at 478 N/m2
A = machine area in m2
S = weight distribution area in m2
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
In this example, the floor loading is less than the allowable 3450 N/m2.
Example 2
A multiple-frame machine configuration is to be installed as a group (four
frames total).
Service clearance:
Front and rear: 1.2 m
Between frames: 0 m
Left and right of group of frames: 1 m
Use half the service clearance dimensions (1.2/2 = 0.6 m and 1/2 = 0.5 m) for
calculating the weight distribution area.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Check whether the weight distribution area based solely on the service clear-
ance will result in an FL that is less than 3450 N/m2. (Half of the service clearance
area distance is used assuming additional groups of frame systems could be placed
with only the service clearance between them and this group.)
First check the four-frame system as a whole:
M = 6000 × 4 = 24,000 N
A = (0.75 × 1) × 4 = 3 m2
S + A = 5.8 m2 + 3 m2 = 8.8 m2
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
except that Fp shall not be less than Fp = 0.3 SDSIpWp and where
ap = component amplification factor (Table 13.5-1 of ASCE Standard 7-05,
given as 1.0 for access floors
SDS = design spectral response acceleration
Wp = component operating weight
Rp = component response modification factor, which is either 1.5 or 2.5
depending on whether the pedestals are fastened to the subfloor by
adhesive or mechanical fasteners (Table 13.5-1 of ASCE Standard 7-05)
Ip = component importance factor
z = height in the structure where the access floor is attached to the building
h = roof height of the building with respect to the base
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
The IBC designates minimum uniformly distributed live loads of 100 psf for data-
com rooms and 50 psf for offices. Other load values may be substituted at the user’s
discretion.
The component operating weight of a typical datacom RAF with its loads is
calculated using the following:
Wp = [(100.0 psf × 25%) + 10.0 psf + 10.0 psf] = 45.0 psf = 2154 N/m2
where
equipment live load = 100.0 psf = 4788 N/m2
access floor dead load = 10.0 psf = 479 N/m2
partition dead load = 10.0 psf = 479 N/m2
Seismic Use Group I: Ip = 1.0 (for all other occupancies not noted below)
Seismic Use Group II: Ip = 1.25 (for structures that have a substantial public
hazard due to occupancy or use)
Seismic Use Group III: Ip = 1.5 (for essential facilities that must function after
an earthquake)
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Appendix D
Data Center
Vibration Measurement
D.1 OVERVIEW
This appendix presents an overview of typical operational shock and vibration
test profiles for datacom and cooling equipment. The test profiles can also be used
as the limits, the acceptable vibration levels for a datacom center. The effect of this
shock and vibration on the functional performance of the datacom equipment
depends on how the equipment cabinet transmits this shock and vibration to critical
components. The acceptable level of shock and vibration can normally be obtained
from the datacom equipment manufacturer. However, the actual level of floor vibra-
tion in a datacom room is not readily available. This appendix is intended to provide
information on how to record the data and what kind of data is needed to evaluate
the effect of vibration on the operation or functionality of the datacom equipment.
In addition, this appendix informs the datacom center operator what vibration
magnitudes are considered normal or high.
D.2 INTRODUCTION
Datacom equipment such as high-performance computer servers, storage serv-
ers, networking equipment, rack-mounted equipment, and cooling equipment can
induce and transmit vibration to surrounding datacom equipment. As the datacom
equipment gets more powerful, more cooling is required, which translates to higher
blower or pump speeds. As a result, higher levels of vibration magnitude will be
transmitted to the floor and to the datacom equipment.
In certain cases, the operator of the datacom equipment can feel the vibration
and express concern as to the effect of this vibration on the operation of the datacom
equipment in the building. Another datacom center operator may be concerned that
the datacom equipment room has excessive vibration from forklift vehicles and
trucks operating in the warehouse that is close to the equipment room. In another
location, the datacom equipment room is on twelfth floor of a 26-story building. The
adjacent building physically attached to the main structure has electrical power
generators that produce levels of vibration that can be felt anywhere inside the build-
ing. All of these examples have vibration environments that may effect the datacom
equipment’s operation. To evaluate the effect of these operational vibration levels,
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
one needs to know what level of vibration the datacom equipment can tolerate and
the vibration magnitude transmitted to the datacom equipment. The first piece of
information can be obtained from the datacom equipment manufacturer, but each
type of datacom equipment may have different specifications, such as a maximum
g-force level at any frequency range or a certain PSD profile. The second piece of
information is the data center vibration, which may not be readily available. In this
appendix, the typical levels to which datacom equipment can be tested are discussed.
Next, the tests on datacom equipment, the criteria for an acceptable datacom equip-
ment room, and the methodology for datacom equipment room measurements are
presented. Then some actual measurements on datacom equipment rooms are
presented.
In this appendix, no attempts are made to evaluate the effect of operational
vibration (which is dominantly in the vertical direction) on the functional perfor-
mance of the datacom equipment. The datacom equipment manufacturer can eval-
uate the effect of the vibration on their datacom equipment based on the testing and
design of the datacom equipment. Typical operational testing is given for guidance
purposes only.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
component is installed while the system is running. During this operation, a shock
magnitude up to 30g with 3 ms pulse width in the vertical direction and about 15 g
with 3 ms pulse width can occur (IBM 1990).
The shock and vibration levels in the previous section were determined by
conducting actual vibration measurements in datacom equipment rooms. The
magnitudes given are an envelope of the peak amplitudes. These values can also be
used as typical limits of vibration amplitude produced by datacom or cooling equip-
ment. Therefore, the limits can also be used as the acceptable datacom equipment
room vibration levels since datacom equipment is tested to meet these limits. Actu-
ally, most datacom equipment can withstand higher magnitudes of operational shock
and vibration. However, datacom equipment manufacturers may not test above the
level indicated in the previous section.
The solid line in Figure D.3 shows the level of vibration shown in Figure D.2.
The dotted line shows the threshold where people start to feel the vibration (Harris
and Piersol 2001), and the dashed line represents a vibration level that is unpleas-
ant to people. Generally, as long as people do not feel the unpleasant vibration
level, the level of datacom equipment room vibration is within the allowable or
acceptable level.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Figures D.1 and D.2 depict the expected vibration magnitude in a data center.
Datacom manufacturers require not only the magnitude but also the frequency
related to this magnitude as key information for evaluating the effect of vibration on
the datacom equipment. Generally, recording vibration amplitude data alone,
whether it is in g-force or velocity, requires lower-cost measurement instrumentation
than collecting data in order to produce magnitude and frequency content. However,
it is critical that g or PSD versus frequency data be recorded. The frequency range
of the data should be between 5–500 Hz. Accomplishing this task may require two
sets of data collection; one between 2 and 50 Hz to capture the low frequency content
and the second between 50 and 500 Hz to capture frequencies higher than 50 Hz.
One data center layout is shown in Figure D.4. The cooling units are shown as
A/C boxes; the datacom equipment is shown as S boxes. Vibration was monitored
at nine locations, denoted as I-1, I-2, I-3, II-1, ... III-3.
Figure D.5 illustrates typical acceleration in g for a frequency range from
2–50 Hz, and Figure D.6 shows similar information but at a frequency range
from 5–500 Hz. The maximum g is 0.002g at 220 Hz. This value is an order of
magnitude lower than the limit given in Figure D.2 (0.035). The areas near the
cooling units have higher vibration than the other areas. Figures D.7 and D.8
show the data in a different format. Here, the vibration magnitude is given in the
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
vertical axis as g2/Hz vs. Hz. At 220 Hz, the vertical axis is 5.4 × 10E–5 g2/Hz,
which is somewhat higher than Level 1 but is still below Level 2 (see Figure D.1).
1. Level 1 (see Figure D.1) is the appropriate vibration input test level for a heavy
datacom equipment cabinet. This level is intended to mimic the datacom equip-
ment room floor vibration and to test that the functionality of the system is not
affected during the test. For a small and relatively light equipment cabinet,
Level 2 can be used as a typical test level.
2. Vibration amplitudes at 0.07g are most likely the upper limit of vibration at the
base of the datacom equipment. This level can be considered normal data center
vibration and most likely will not induce any functional degradation to datacom
equipment.
3. When a concern arises as to whether the data center’s floor vibration is too high,
an actual measurement of data center vibration is warranted. Both PSD vs.
frequency and g vs. frequency plots are the information needed to evaluate this
concern.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Appendix E
Component
Anchorage Forces
The horizontal seismic design force is calculated in accordance with the follow-
ing three formulas included in ASCE Standard 7-05 (ASCE 2005):
0.4a p S DS W p
F p = ------------------------------- ⎛⎝ 1 + 2 ---⎞⎠
z
(E.1)
Rp h
Fp
max
= 1.6S DS I p W p (E.2)
Fp
min
= 0.3S DS I p W p (E.3)
where
Fp = horizontal design seismic force
ap = component amplification factor
SDS = design spectral response at short periods
Wp = component operating weight
Rp = component response modification factor
Ip = component importance factor
z = component elevation above grade in the building
h = average roof height of the structure above grade
The above formula for the calculation of lateral forces has changed quite a bit
in the last decade. It is instructive to review a number of the variables that go into
this equation in more detail in order to better understand their impact.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
its linear elastic force provisions. A triangular distribution of forces with the largest
force at the roof is assumed by the code because the forces at the roof are higher than
those at the lower floors. This story force is also imparted on all the nonstructural
components attached to the building at each floor.
The relative location factor is used to scale the seismic coefficient at grade to
approximate the dynamic amplification felt by the component when it is located
much higher in the building. The factor ranges from 1.0 (component at grade) to
3.0 (component at roof).
In previous versions of the building code, this factor was (1 + 3z/h), and thus the
maximum multiplier went up to 4.0 for roof-mounted locations. However, subse-
quent research showed that this was too conservative, and the coefficient was
lowered to 2.
It should be noted that the best location for a high-performance datacom equip-
ment center would be on the ground floor, as the seismic forces there would be the
lowest of any location in the building.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
the ground, the amplification due to the support would be negligible and the compo-
nent would be subjected to only the same force as the floor itself. However, if the
component is supported on a flimsy steel platform, the component would experience
additional force due to the “whipping” of the support directly below it—much like
the end of a snapping bullwhip.
Traditionally, the code has defined ap as a step function between fully rigid and
fully flexible even though neither of these cases really exists in real life. The code
definition of a fully “rigid” support is one with a fundamental period of less than or
equal to 0.06 s. With this stiff of a support, it is assumed that no dynamic amplifi-
cation occurs and the ap can be taken as 1.0. If the fundamental period is greater than
0.06 s (the frequency of the oscillation is lower than 16.7 Hz), the support is consid-
ered flexible and the ap is taken as 2.5. Tables 13.5-1 and 13.6-1 of ASCE
Standard 7-05 (ASCE 2005) list ap values for many common architectural, mechan-
ical, and electrical components.
In real life a support is never really “fully” rigid or flexible but somewhere in
between. Also, the much larger bracing forces required by the code for “flexible”
supports often are quite extensive and expensive. In these cases, the code allows a
more accurate determination of the component amplification factor based on
dynamic analysis, if desired. This can be calculated when reasonably accurate values
for both the fundamental period of the component and the structure are known. The
accurate representation of ap is the ratio of these two periods. The NEHRP Commen-
tary (BSSC 2003) has an excellent discussion of this procedure based on the provi-
sions included in Tri-Service Manual TM 5-809-10, Seismic Design for Buildings
(US Army 1992).
Of special discussion for datacom equipment rooms is the determination of the
component amplification factor for equipment such as equipment cabinets anchored
directly to a RAF.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
It should be noted that the values of Rp in Table 13.6-1 of ASCE Standard 7-05
have increased dramatically for many components in the latest edition of the code.
These increases acknowledge recent analysis work to develop less conservative
values as well as the good past seismic performance of many of these systems. Also,
many systems are listed with a relatively high Rp factor but, in order to achieve this
good performance, specific seismic detailing is required. Owners should note that
some of the component systems used in high performance datacom equipment
rooms are not specifically listed in the table (except a generic mechanical or elec-
trical component). The owner should decide in advance on the values to be used for
specific datacom equipment room components.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Glossary of Terms
acceleration of gravity (g or G): g is the acceleration produced by gravity at the
surface of the earth and has an international standard value of 9.807 m/s2. Measured
accelerations are often expressed as a ratio of the measured acceleration divided by
gravitational acceleration; this unitless ratio is expressed as a G value.
ACI: American Concrete Institute.
AHJ: the local authority having jurisdiction.
amplitude or magnitude: the maximum value of a measured vibration. Amplitude
may be measured in values of displacement, velocity, or acceleration.
ANSI: American National Standards Institute.
ap : component amplification factor. See Section E.3 of Appendix E for further
discussion.
ASCE: American Society of Civil Engineers.
ASHRAE: American Society of Heating, Refrigerating and Air-Conditioning Engi-
neers, Inc.
ASTM International: formerly the American Society for Testing and Materials
(ASTM).
augered cast-in-place pile: see pile.
availability: a percentage value representing the degree to which a system or compo-
nent is operational and accessible when required for use.
ballasted roof: a roof system where the waterproof membrane or the multiple layers
of roof felts are held in place by the weight of ballast stone or concrete pavers.
base fixity: a number from 0 to 1 used to quantify how well the base of a frame is
attached to the ground (1 being a perfectly rigid connection, 0 being no connection).
BOCA: Building Officials and Code Administrators International, Inc.; now Inter-
national Code Council.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
building loads:
collateral load: a type of dead load, the collateral load includes the weight of
any materials other than the permanent construction materials. The collateral
load may include electrical pipes, sprinkler systems, ceilings, lights, and other
materials.
dead load: the combined weight of all the permanent construction materials,
including roofing, framing, and other structural components such as walls,
floors, roofs, ceilings, stairways, built-in partitions, finishes, cladding, and
other similarly incorporated architectural and structural items and fixed service
equipment, including cranes. The dead load is determined in advance and is
assigned a low factor of safety in the overall building design. All dead loads are
considered permanent loads.
duration of load: the period of continuous application of a given load, or the
aggregate of periods of intermittent applications of the same load.
impact load: the load resulting from moving machinery, such as elevators,
craneways, vehicles, and other similar forces, and kinetic loads, pressure, and
possible surcharge from fixed or moving loads.
live load: the weight of building occupants, furniture, machines, equipment,
and the like. Since the live load is hard to quantify, it carries large factors of
safety in the overall design of the building. Other live load sources that occur
during construction and maintenance, such as those from tool boxes, temporary
generators, etc., must be taken into consideration as well; these loads may be
difficult to predict.
load factor: a factor that accounts for deviations of the actual load from the
nominal load, for uncertainties in the analysis that transforms the load into a
load effect, and for the probability that more than one extreme load will occur
simultaneously.
partition live load: the load carried by a wall that is one story or less in height
used to subdivide the interior space in a building. The loads accounted for are
produced only by the use and occupancy of the structure and not by external
forces such as weather, wind, or seismic loads.
seismic load: the force exerted on a structure due to seismic activity.
snow load: the maximum weight of snow that will collect on the roof of the
building. The snow load is highly dependant on the ultimate location of the
building. The slope (pitch) of the roof is a factor used to determine snow loads.
wind load: the force exerted on a structure by strong winds.
built-up roof: a roof constructed of multiple layers of roof felts laminated together
with a hot or cold applied bitumen, tar, etc., and often finished with a coating of rocks
or aggregate. It is called a built-up roof because it is made (or built up) at a job site.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
cabinet: frame for housing electronic equipment that is enclosed by doors and is
stand-alone; this is generally found with high-end datacom equipment.
CDU: cooling distribution unit.
chase: building element within which building infrastructure (ductwork, piping,
etc.) is routed; vertical chases may also be referred to as risers or shafts.
chevron bracing: structural bracing members that start out wide at two points on
top of a component and then gradually converge to the bottom of another (see
Figure 6.5).
CISCA: Ceilings & Interior Systems Construction Association.
clear height: also headroom; refers to the distance from the top of the structural floor
slab to the lowest point of the overhead structural system (which may support a roof
system or a building floor above).
CMU: concrete masonry unit.
collateral load: see building loads.
combined footing: see footing.
component amplification factor: ap . See Section E.3 of Appendix E for further
discussion.
component importance factor: Ip . See Section E.2 of Appendix E for further
discussion.
component operating weight: Wp . See Section C.4.1 of Appendix C for further
discussion.
component response modification factor: Rp . See Section E.4 of Appendix E for
further discussion.
constraint element: a general class of elements that apply kinematic constraints
(rigid link, slider, revolute, point-in-plane, translational) between nodes.
CRAC: computer room air-conditioning unit.
craneway: the structure or structural members upon which a crane travels, which can
include columns, support girders, and rails.
data center: a building or portion of a building whose primary function is to house
a computer room and its support areas. Data centers typically contain high-end serv-
ers and storage products with mission-critical functions.
datacom: an abbreviation for the data and communications industry.
datacom equipment: refers to, but is not limited to, servers, storage products, work-
stations, personal computers, and transportable computers; may also be referred to
as electronic equipment or IT equipment.
dead load: see building loads.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
design spectral response acceleration: SDS . See Section C.4.2 of Appendix C for
further discussion.
diaphragmatic action: the resistance to in-plane shear forces (such as from wind)
offered by roof decks or floor slabs that are rigid enough to transfer the forces to the
structural framing system.
drilled pier: see pier.
driven pile: see pile.
duration of load: see building loads.
EERI: Earthquake Engineering Research Institute.
EIA: Electronic Industry Alliance.
EJMA: Expansion Joint Manufacturers Association.
electronic equipment: see datacom equipment.
equipment support: those structural members or assemblies of members or manu-
factured elements, including braces, frames, lugs, hangers, or saddles, that transmit
gravity load and operating load between the equipment and the structure.
FEMA: Federal Emergency Management Agency.
finite element analysis: a numerical technique of solving a wide range of engineer-
ing problems. Finite element analysis is used to determine the stresses and displace-
ments of a mechanical structure. The first step in the analysis is to approximate the
actual geometry by a mesh of small elements bounded by points called nodes. The
next step is to define the boundary conditions, the applied load, and/or the displace-
ment on the elements and nodes.
footing: essentially a base in the ground that will support the weight (load) of the
building structure imposed upon it. The dimensions of a footing vary according to
the soil conditions under the building, the load placed on the footing, and the
construction style of the structure being supported.
combined footing: a type of footing that supports two or more columns.
monolithic footing: concrete footing poured and cast in one piece without
joints.
spread footing: supports the weight (load) from the exterior or foundation walls
of a building.
foundation: the connecting structure between the footing and the structural system
above.
mat foundation: a raft or floating foundation; a continuous footing that
supports a reinforced concrete slab covering a minimum of 75% of the total area
within the exterior walls of a building. It is normally only used when the subsoil
is poor.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
ribbed slab foundation: a concrete slab on grade that is continuously cast with
deepened perimeter and interior beams placed in a grid pattern within the foot-
print of the slab.
Fp : seismic horizontal force. See Section C.4.1 of Appendix C for further discussion.
frame drift: the horizontal displacement of the structure at a floor or roof level with
respect to its original position; is a very important part of the structural design. Drift
limitation requirements can greatly impact the type of structure that is selected.
free-fall drop heights: the equivalent velocity change due to free-fall drop from a
certain height (h):
velocity change ΔV = (1 + e) ( 2gh )
where e is the coefficient of restitution and is the ratio of velocities after and before
an impact.
frequency: the reciprocal of a period in cycles per second, sometimes expressed as
Hertz (Hz).
grms: the root mean square value of the acceleration of gravity, g.
Guyan reduction solver: a numerical procedure used by finite element analysis as
an iterative algorithm that is an adaptation of power methods to find eigenvalues and
the eigenvector of a square matrix. It is particularly useful for finding decomposi-
tions of very large sparse matrices.
half-sine shock pulse: an ideal shock pulse for which the acceleration/time relation
has the shape of the positive (or negative) section of one cycle of a sine wave.
harmonic frequency, normal mode, natural frequency, resonance frequency: the
frequency at which a deformable structure will oscillate when disturbed.
headroom: see clear height.
HVAC: heating, ventilating, and air conditioning.
IBC: International Building Code.
ICBO: International Conference of Building Officials.
ICC: International Code Council.
impact load: see building loads.
Ip : component importance factor. See Section E.2 of Appendix E for further
discussion.
IT: information technology.
IT equipment: see datacom equipment.
Lanczos method solver: a numerical procedure used by finite element analysis as an
iterative algorithm that is an adaptation of power methods to find eigenvalues and the
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
(NIST is the lead NEHRP agency), 3) National Science Foundation (NSF), and 4)
United States Geological Survey (USGS) of the Department of the Interior.
NFPA: National Fire Protection Association.
NIBS: National Institute of Building Sciences.
nonstructural components: all those items in a data center that are attached to the
structure but are not part of the building structure itself. Typically this includes archi-
tectural components such as the exterior building cladding, interior partition walls,
hung ceiling, raised-access flooring, and storage cabinets. It also includes mechan-
ical and electrical components such as HVAC units, pumps and compressors, eleva-
tors, motor control units, transformers, computers, server racks, and all associated
piping, ductwork, conduit, bus duct, and cable trays. And, most importantly, it
includes all of the servers on the data center floor.
normal mode, harmonic frequency, natural frequency, resonance frequency: the
frequency at which a deformable structure will oscillate when disturbed.
parabolic shell element: a type of element used in finite element analysis to repre-
sent a surface.
partition live load: see building loads.
PDU: power distribution unit; the junction point between the uninterruptible power
supply and the cabinets containing equipment.
perforated floor tile: a tile as part of a raised-access flooring system that is engi-
neered to provide airflow from the cavity underneath the floor to the space. Tiles may
be with or without volume dampers.
pier: a vertical load-bearing member often used as a foundation. See also pile.
drilled pier: a deep foundation system that is constructed by placing fresh
concrete and reinforcing steel into a drilled shaft. Typical shaft diameters range
from 18 to 144 in.
rammed aggregate pier: a foundation soil improvement technique that is
achieved by boring holes in the soil and filling them with a compacted aggre-
gate, thereby strengthening the soil.
pile: a vertical structural shaft that transfers load through weak layers of soil to those
that are capable of supporting such loads. See also pier.
augered cast-in-place pile: a support that is created by removing a column of
soil to a certain depth through the use of an auger and filling the void with
concrete.
driven pile: a support that is driven into the ground by means of a hydraulic ram,
press, or some other means until the support reaches stable solid soil or bedrock.
power spectral density (PSD): a measure of the power content with respect to the
frequency for random vibration. The units are g2/Hz and represent the power present
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
in a 1-Hz-wide square filter. The square root of the integration of the PSD curve with
respect to frequency gives the overall root mean square level of the vibration.
PSD: see power spectral density.
pulse width: half of the period of a sinusoidal wave expressed in milliseconds (ms).
purlin: horizontal structural roof members used to support roof decking.
rack: a cabinet or frame for housing electronic equipment.
rack-mounted equipment: equipment mounted in an Electronic Industry Alliance
(EIA) or similar cabinet; these systems are generally specified in EIA units, such as
1U, 2U, 3U, etc., where 1U = 1.75 in. (44 mm).
raised-access floor (RAF): a platform with removable panels where equipment is
installed, with the intervening space between it and the main building floor used to
house the interconnecting cables and at times used as a means for supplying condi-
tioned air to the datacom equipment and the room.
RAF: raised-access floor; a platform with removable panels where equipment is
installed, with the intervening space between it and the main building floor used to
house the interconnecting cables and at times used as a means for supplying condi-
tioned air to the datacom equipment and the room.
rammed aggregate pier: see pier.
random vibration: a vibration having randomly varying amplitude and frequency
content within specified limits. It is typical of the vibration to which products are
exposed in the operating environment.
relative location factor (1 + 2z / h): adjusts the design seismic force for dynamic
amplification due to the position of a component in the height of the building. The
factor ranges from 1.0 (component at grade) to 3.0 (component at roof). See
Section E.1 in Appendix E for further discussion.
reliability: a percentage value representing the probability that a piece of equipment
or system will be operable throughout its mission duration. Values of 99.9% and
higher are common in datacom equipment areas. For individual components, the
reliability is often determined through testing. For assemblies and systems, reliabil-
ity is often the result of a mathematical evaluation based on the reliability of indi-
vidual components and any redundancy or diversity that may be employed.
resilience: ability of a system or component to recover and maintain its function
from both expected and unexpected events.
resonance: the point at which the natural frequency (resonance frequency) of an
element is equal to the excitation frequency and the point that produces the peak
amplification of input amplitude; a condition caused by excitation with an input
frequency that is at or very near an element’s natural frequency. The resonance
frequency causes a maximum output or element amplitude response.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
Index
A
acceleration of gravity 79, 153, 157
amplitude 12, 25, 27, 51, 63–64, 74, 79–83, 85, 91, 116, 137, 141–46, 153, 158, 160–62
ap 98, 138, 149–51, 153, 155
augered cast-in-place pile 33, 153, 159
authority having jurisdiction (AHJ) 18, 153, 158
availability 4, 11, 97, 99, 153
B
ballasted roof 153
base fixity 153
braced frame 9, 16, 25
built-up roof 154
C
cabinet 81–82, 84, 87, 99–102, 104–106, 110, 160, 162
CalTrans 81
chase 155
chevron bracing 26, 38, 40, 155
clear height 155
collateral load 19, 154
combined footing 1586
component amplification factor (ap) 98, 138, 149–51, 153, 155
component importance factor (Ip) 90, 111, 138–39, 149–50, 155, 157
component operating weight (Wp) 68, 111, 138–39, 149, 155, 162
component response modification factor (Rp) 69, 138, 149, 151, 155, 161
computer room air-conditioning unit (CRAC) 46, 57–58, 71, 73–74, 80, 155
concentrated load/concentrated load capacity 37, 63–64, 133–34
concrete masonry unit (CMU) 26, 34, 38, 128, 155
constraint element 155
cooling distribution unit (CDU) 155
craneway 155
D
data center 3–6, 11, 17, 22, 26, 29–33, 35, 37, 57–58, 67–68, 73, 80–84, 86, 95, 97, 98–99,
107, 110, 141–47, 150, 152, 155, 159
datacom 3–7, 9, 11–12, 16–17, 22–26, 29, 32, 37, 45, 47, 51, 55, 57, 61, 63–64, 66, 71, 73–
75, 80–81, 83–87, 89–90, 93, 135, 139
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
164⏐ Index
datacom equipment 9, 11–12, 16–18, 23, 45, 47, 55, 57, 61, 63–64, 66, 71, 73–75, 80–81, 85–
86, 89–90, 95, 98–100, 104, 106–11, 113, 116, 134–35, 141–46, 150–52, 155, 158, 160–62
dead load 19, 154
design spectral response acceleration (SDS) 111, 138, 149, 156, 161
diaphragmatic action 156
drift, frame 157
drift, structure 16, 25
drilled pier 159
driven pile 159
duration of load 19, 154
E
earthquake 3, 10, 18, 66–68, 80, 82, 85–86, 90, 95–96, 98–100, 109–11, 113, 116, 119, 121,
138–39, 149–51, 156, 158, 161
electronic equipment 156
element, constraint 155
element, rigid 161
equipment support 20, 156
F
finite element analysis 90, 92, 107–108, 114, 116, 119, 156–57, 159, 161
floor load/floor loading 66, 134–37
footing, combined 156
footing, monolithic 156
footing, spread 156
foundation, mat 156
foundation, ribbed slab 157
Fp 68, 137, 139, 149, 157, 161
fragility 12, 85, 87–88, 90
frame drift 157
free-fall drop height 79, 157
frequency, harmonic 157, 160
frequency, natural 157, 160
G
grms 157
Guyan reduction solver 107, 109, 157
H
half-sine shock pulse 79, 157
handling 83, 87–88
harmonic frequency 157, 160
headroom 155
horizontal design seismic force 68, 137, 139, 149, 157, 161
horizontal force 38, 64, 68, 98–100, 137, 139, 157, 161
HVAC 6, 46, 75, 84, 95, 157, 159
I
impact load 19, 154
infrastructure 3–6, 8–9, 11–12, 18, 22–26, 30, 32, 45–47, 51, 55, 57, 80, 89
International Building Code (IBC) 9, 26, 57, 69, 74–75, 89–90, 92, 96–98, 119, 122, 137–39,
149–51, 157
International Code Council (ICC) 86, 90, 119, 121, 137, 157
Ip 90, 111, 138–39, 149–50, 155, 157
isolation 58, 71, 83, 92, 104, 106
IT/IT equipment 8, 81–82, 86, 110, 155, 157
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
L
Lanczos method solver 107, 109, 114, 157
live load 19, 23, 26–27, 32, 47, 68, 135, 138–39, 154
load, collateral 19, 154
load, concentrated 37, 63–64, 133–34
load, dead 19, 154
load, duration of 19, 154
load factor 19, 154
load, impact 19, 154
load, live 19, 23, 26–27, 32, 47, 68, 135, 138–39, 154
load, partition live 154
load, rolling 63, 134
load, seismic 19, 154
load, snow 19, 154
load, ultimate 133
load, uniform 32, 34, 63, 133, 138
M
machine area 158
magnitude 12, 25, 27, 51, 63–64, 74, 79–83, 85, 91, 116, 137, 141–46, 153, 158, 160–62
mat foundation 156
minipiles 158
mission critical 82, 90, 92, 97, 158
moment frame 16, 26, 39, 158
N
Network Equipment-Building System (NEBS) 83, 158
nonstructural components 159
normal mode 157, 160
P
parabolic shell element 108–109, 159
partition live load 154
pedestal 11, 58, 61–69, 99, 137–39, 162
pier, drilled 159
pier, rammed aggregate 159
pile 33, 153, 158–59
pile, augered cast-in-place 33, 153, 159
pile, driven 159
power distribution unit (PDU) 159
power spectral density (PSD) 79, 86, 142, 147, 159
pulse width 79, 160
purlin 160
R
rack/rack-mounted equipment 160
raised-access floor (RAF) 11–12, 16, 23–24, 30, 37, 45, 55, 57–58, 61–69, 81, 95, 98–100,
104, 107, 110, 129, 133, 135, 137–39, 150–51, 159–60, 162
raised-access floor panel 11, 61, 63–64, 66–67, 99, 104, 133, 162
rammed aggregate pier 159
random vibration 79, 160
relative location factor 149, 160
reliability 97, 160
resilience 160
resonance/resonance frequency 79, 157, 160
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
© 2007, American Society of Heating, refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only.
Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
166⏐ Index
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012
This file is licensed to sergio torres morales (retos@correoinfinitum.com). License Date: 9-26-2012