1103-DS-540-1000
Sengkang LNG Production Plant & Export Terminal
Mechanical Datasheet - Cooling Tower Package L-561
Revision History
Revision Amender
Amendment Date Amendment
Number Name
14-Mar-16 A CND Issued For Review
OMS References
Relevant Section of This
OMS Section Ref OMS Section Title
Document
Related Documents
Stakeholders
List of Holds
MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
SERVICE : Cooling Water Circulation Pumps TAG NUMBER : 386-P-1001 A/B
REVISION
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 2 x 100% (1W+1S)
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327
1 Note: Indicated Information Completed by Purchaser by Manufacturer by Purchaser or Manufacturer */ VTA : Vendor to Advice
2 Manufacturer VTA Model VTA Serial Number VTA
3 GENERAL
4 Number Motor Driven 2 (TWO) Number Turbine Driven N/A Gearbox Item Number N/A
5 Motor Item Number Turbine Item Number N/A Gearbox Provided By N/A
6 Motor Provided By VENDOR Turbine Provided By N/A Gearbox Mounted By N/A
44 NOTES:
45 1 VTA : Vendor to advise, VTC : Vendor To Confirm
46 2 Vendor shall fill in all blank data whichever applicable
47 3 Materials to be selected based on 20 years lifetime. Grade of Material to be defined by VENDOR.
48 4 Design Margin between NPSHA & NPSHR shall be 3 ft at minimum.
49 5 Pumps are designed as per ANSI B73.1 and Project Specification MTDF-MR-300-SPE-3208 "Specification for ANSI Pumps" 2
50 6 Pump rated capacity with 10% design margin
51 7 All nozzle flanges shall be as per ASME B 16.5
52 8 The maximum value for the equipment noise limit (sound pressure level) shall be 85 dB(A) at 1m from the edge of the equipments
53 9 Migas certificate to be provided. VENDOR is responsible to provide all required documents to obtain Migas approval.
54 10 Motor shall be suitable for Non hazardous area (safe area) classification of zone 2, gas group IIA and temperature class T3.
55 Electrical motor rating shall be IP 55 as a minimum
56 11 All instrumention shall be certified for Zone 2, Group IIA, T3. Line- All external equipment shall be weatherproof to IP 65 as a minimum
57 12. Vendor shall fill in the LV / MV Motor Datasheet provided with the Material Requisition Document. 2
58 13. Design Pressure of closed cooling water circulation loop is 120 psig. Design temperature is 158 oF 2
59 14. VENDOR to perform Liquid Penetrant test to Manufacturer's Standard as a minimum
MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
SERVICE : Cooling Water Circulation Pumps TAG NUMBER : 386-P-1001 A/B
REVISION
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 2 x 100% (1W+1S)
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327
MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
SERVICE : Cooling Water Circulation Pumps TAG NUMBER : 386-P-1001 A/B
REVISION
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 2 x 100% (1W+1S)
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327
MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
REVISION
SERVICE : Chemical Treatment Package TAG NUMBER : -
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 1 x 100%
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327
1 INJECTION LIQUID
2 Injection System for: ✘ Water Treatment Pipeline Other :
3 Liquid Injected VTA
4 Injection Flow Normal: VTA L/hr Max. : VTA L/hr
5 Pressure Required at Injection Point (1) VTA psig Temperature: AMBIENT Specific Gravity: VTA
6 (2) VTA psig Viscosity @ Flowing Temperature: VTA
7 Concentration VTA %
8 CHEMICAL STORAGE TANK
9 Item No VTA
10 Service of Unit Chemical Storage Tank
11 No of Required 1 x 100% per Chemical
12 Capacity VTA Liter NOTE-9, 10 2
13 Design Pres.: VTA psig Design Temp.: VTA °F
14 Operating Pres.: ATM psig Operating Temp.: Ambient
15 Type VTA
16 Size (ID x T/F) VTA inch
17 Thickness VTA inch
18 Material VTA
19 Accessories ✘ Calibrated Level Gauge Measuring Cup ✘ Flame Arrestor
20 ✘ Level Transmitter ✘ Inner Basket Others,….
21 ✘ Cover ✘ Internal Baffles …………..
22 ✘ Low Point Drain Ladder …………..
23 MIXER (VTA)
24 Item No
25 Service of Unit
26 No. of Required
27 Type Mechanical with motor Pulsator
28 Hand-operation Vertical Mounted
29 Material
30
31 MOTOR FOR PUMPS (NOTE-12) MOTOR FOR MIXER (NOTE-12) 2
32 No. Required: 1+1 (Motor shall follow MTDF-EL-900-SPE-1007 ) No. Required:
33 Supplied By: VTA Supplied By:
34 Mounted By: VTA Mounted By:
35 Rated Output: VTA HP Rated Output: HP
36 Pole: 4 Speed: 1500 Pole: Speed:
37 Phase: 3 Hz: 50 Volt: 400 Phase: Hz: Volt:
38 ACCESSORIES
39 ✘ Local Control Panel, if required ✘ Automatic Control System ✘ Strainers ✘ Pressure Gauge
40 ✘ Piping on Common Baseplate ✘ Valves ✘ Relief Valves ✘ Pulsation Dampeners VTA
41 ✘ Anchor Bolts & Nuts ✘ Instruments ✘ Companion Flange Bolts & Nuts ✘ Calibration Gauge Glass / Column
42 INSTALLATION
43 ✘ Outdoor Under Roof Indoor Heated Unheated
44 Hazardous Area Classification Non-Hazardous
45 Site Ambient Temperature Minimum: 71.06 °F Normal: 81.43 °F Maximum: 91.58 °F
46 Mounted on: ✘ Skid (with Drip pan and Drain Con.) Structural Base
47 Total Weight of the System VTA kg
48 NOTES
49 1. VTA = Vendor to advise, VTC = Vendor to confirm
50 2. Vendor shall fill in all blank data whichever applicable
51 3. Materials to be selected based on 20 years lifetime. Grade of Material to be defined by VENDOR.
52 4. All nozzle flanges shall be as per ASME B 16.5
53 5. The maximum value for the equipment noise limit (sound pressure level) shall be 85 dB(A) 1 m from the edge equipment.
54 6. Migas certificate to be provided. Vendor is responsible to provide all required document to obtain Migas approval.
55 7. Motor shall be suitable for Zone 2, Group IIA, T3. Eletric motor rating shall be IP 55 as a minimum
56 8. All instrumention shall be certified for Zone 2, Group IIA, T3. Line- All external equipment shall be weatherproof to IP 65 as a minimum
57 9. Refer to Specification for Chemical Injection Package (MTDF-MS-300-SPE-3213)
58 10. 10% design margin on net working tank volume. Tank should be sized for storage volume of period of one week.
59 11. Vendor to propose and provide chemical storage tank drawing and detail
60 12. Vendor shall fill in the LV / MV Motor Datasheet provided with the Material Requisition Document. 2
MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
REVISION
SERVICE : Chemical Dosing Pumps TAG NUMBER : -
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 2 x 100% (1W + 1S)
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327
50 REMARKS
51
52
53
54
MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
REVISION
SERVICE : Chemical Dosing Pumps TAG NUMBER : -
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 2 x 100% (1W + 1S)
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327
55 REMARKS
56