SENGKANG LNG PRODUCTION PLANT & EXPORT TERMINAL

MECHANICAL DATA SHEET


COOLING TOWER PACKAGE
(L-561)

A Issued For Review CND ### KS ### AD ###

Rev Reason for Issue Author Date Checked Date Approver Date

STATUS CODE: A : Issued for Review (IFR)


B : Issued for Approval (IFC)
C : Approve for Construction (AFC)
D : As Built

DISTRIBUTION : DC : Original
All Engineer : Controlled Copy
QS : Controlled Copy

Document Number
! This document is copyright and shall not be reproduced without the
permission of PT. Slipform Indonesia
1103-DS-540-1000
Sengkang LNG Production Plant & Export Terminal
Mechanical Datasheet - Cooling Tower Package L-561

Revision History
Revision Amender
Amendment Date Amendment
Number Name
14-Mar-16 A CND Issued For Review

OMS References
Relevant Section of This
OMS Section Ref OMS Section Title
Document

Related Documents

Document Number Document Name Description of Content

09804-TS-000-103 LNG Plant Painting & Coating Specification


09804-TS-000-101 Rev 1 LNG Plant Piping Specification
1103-SP-540-1000 Specification for Cooling Tower Package

Stakeholders

Name Date Reviewed

List of Holds

Hold Description Comment

1103-DS-540-1000 Page : 2 of 10 Rev : A


PTSI Confidential
Sengkang LNG Production Plant & Export Terminal
Mechanical Datasheet - Cooling Tower Package L-561
Client : Energy World Corporation Location South Sulawesi, Indonesia
REVISION
1
2 Process unit : Sengkang LNG Facility Item No. L-561
3 Project No. : 1103 Manufacturer : VTA
4 Service of unit : Cooling Tower Package No. of units : 2 (Two) 2 x 100% (1 W + 1 S)
5 Applicable To: Proposal Purchase As Built
6 GENERAL DATA
7 Tower : Rectangular Package
8 Type : Induced Draft (MECHANICAL DRAFT)
9 : Wet cooling tower, counterflow
10 Heat Exchanged MMBTU/h : VTA
11 No. of cooling tower : 2 x 100%
12 Service For : 1 Liquefaction, Rubicon Cooling and BOG Compressor Lube Oil Skid
13
14 DESIGN CONDITIONS
15 Circulating Water Flow m³/h : 280 NOTE-4
16 Hot (Inlet) Water Temp. o
C : 37.2
17 Cold (Outlet) Water Temp. o
C : < 32
18 Design Pressure barg : waiting for information from Process team
19 Design Temperature o
C : waiting for information from Process team
20 Average Ambient Temperature o
C : 30.5
21 Tower Pump Head, Circulation ft : VTA
22 Air Flow ft3/h : VTA
23 Ambient Dry Bulb Temperature o
F : 91.6
24 Air Outlet Temperature o
F : VTA
25 Total Fan B.H.P (Driver Output) HP : VTA
26 Total Pumping Head Above Basin Curb ft : VTA
27 Drift Loss, % Of Circulating Flow : VTC
28 Evaporation Loss (At Design) m³/h : 4.5
29 Basin Water Retention min : VTA
30 Make Up Water Temperature o
C : 30
31 Make Up Water Required m³/h : VTA
32 Cooling Duty kW : VTA
33 Effectiveness : VTA
34 Approach o
C : VTA
35 COC : PTA
36 Air inlets/ Number of Sides : VTA
37 Air Inlet Height Above Curb (m) : VTA
38 Design L / G : VTA
39 Water Loading (m3/h/m2) : VTA
40 Slope of Characteristic Curve : VTA
41 Design KaV/L or KaY/L : VTA
42 Model : VTA
43 Chemical Consumption rate m³/h : VTA
44 Evaporation Loss % : VTA
45 Blowdown Rate m³/h : VTA
46 Blowdown Frequency : VTA
47
48 AVAILABLE UTILITIES
49 INSTRUMENT AIR OPERATING
50 min / max
51 Temperature C
o
82 / 100
52 Pressure barg 4 / 8.25
53 Dewpoint -60oC @ 7 barg
54
55 Electrical Supply 220V/1ph/50Hz and 380V/3ph/50Hz
56
57 SCOPE OF SUPPLY (NOTE 5, 11 & 18)
58 Cooling Tower Package shall consist of below equipments as a minimum:
59 - Cooling tower (2 x 100%)
60 - Chemical dosing system consisting of one tank and two dosing pumps for each system (NOTE 19)
61 - Instruments, valves and control valves including wiring and junction box at battery limit
62 - Skid and auxiliary piping and tubing within skid battery limit
63 - Other auxiliaries / equipments based on VENDOR's design
64
65
66
67
68
1103-DS-540-1000 Page : 3 of 10 Rev : A
PTSI Confidential
Sengkang LNG Production Plant & Export Terminal
Mechanical Datasheet - Cooling Tower Package L-561
Client : Energy World Corporation Location South Sulawesi, Indonesia
REVISION
1
2 Process unit : Sengkang LNG Facility Item No. L-561
3 Project No. : 1103 Manufacturer :VTA
4 Service of unit : Cooling Tower Package No. of units 2 (Two) 2 x 100% (1 W + 1 S)
5 SITE DATA
6 Location Sengkang - South Sulawesi Onshore, Outdoor
7 Maximum Temperature C : 37
o

8 Max / Min Avg. Temperature C : 37 / 32


o

9 Avg. Relative Humidity : 76 %


10 Design Relative Humidity for Equipment : 96  %
11 Barometric Pressure : 1006 mbar(a)
12 Maximum rainfall per hour : 35 mm
13 Maximum rainfall per day : 199 mm
14 Design Maximum Wind Speed : 35 m/s
15 Wind Gust Recorded-Makassar Airport - Sept 09 : 57 m/s
16 Design Seismic Code : SNI Zone 6, UBC Zone 4
17 Elevation Above Sea Level (m) (Grade) : Seal Level
18 Electrical Supply : Safe Area
19 Fan Deck Loading psig : VTA
20 Available Plot, L x W (m) : VTA
21 Miscelaneous (obstructions(m) : VTA
22 Tower Orientation : Refer to plot plan
23
24 PHYSICAL DETAILS
25 Number Of Cell : VTA
26 Flow Of Cells : VTA
27 Fans Per Cells : VTA
28 Total Number Of Fans : VTA
29 Nominal Cell Dimension, L X W X H (Centerline Of Columns) (m) : VTA
30 Fan Stack Height (m) : VTA
31 Overall Tower Dimension, L X W (Less Stairs) (m) : VTA
32 Height-Basin Curb To Fan Deck (m) : VTA
33 Overall Tower Height (m) : VTA
34 Required Inside Basin Dimensions L X W (m) : VTA
35 Depth Of Basin (m) : VTA
36 Column Extension Below Basin Curb, Perimeter / Interior : VTA
37 Number Of Concrete Perimeter Piers Requiired : VTA
38 Number Of Concrete Interior Piers Required : VTA
39 Distance. Top of Fill to Bottom of Drift Eliminators (DE's) (m) : VTA
40 Distance, Top of DE's to Fan Deck Bottom (m) : VTA
41 Access To Top Of Tower : Ladder
42 Stairways
43 Number Per Tower : VTA
44 Description : VTA
45 Materials : VTA
46 Hardware : VTA
47 Location : VTA
48 Ladders
49 Number Per Tower : VTA
50 Description : VTA
51 Location : VTA
52 Safety Cages Included Yes/No : YES
53
54 STRUCTURAL MATERIAL
55 Structural Hardware Material : VTA
56 Bolt, Nuts : A 193 Gr. B7 / A 194 Gr. 2H (cadmium plated)
57 Washers : Carbon Steel A 36 Galvanized
58 Nails : Carbon Steel A 36 Galvanized
59 Nail Type : VTA
60 Structural Connectors
61 Type : VTA
62 Materials : Carbon Steel A 36 Galvanized
63 Anchor Assemblies
64 Anchor Connector Material : VTA
65
66
67
68
1103-DS-540-1000 Page : 4 of 10 Rev : A
PTSI Confidential
Sengkang LNG Production Plant & Export Terminal
Mechanical Datasheet - Cooling Tower Package L-561
Client : Energy World Corporation Location : South Sulawesi, Indonesia
REVISION
1
2 Process unit : Sengkang LNG Facility Item No. : L-561
3 Project No. : 1103 Manufacturer : VTA
4 Service of unit : Cooling Tower Package No. of units : 2 (Two) 2 x 100% (1 W + 1 S)
5 STRUCTURAL MATERIAL (continue)
6 Anchor Assemblies
7 Anchor Bolt Material : A 307 gr B (cadmium plated)
8 Anchor Bolts / Grout Furnished By : VTA
9 Mechanical Drive Supports
10 Description : VTA
11 Materials : Carbon Steel A 36 Galvanized
12 Hardware Material : Carbon Steel A 36 Galvanized
13 Casing : VTA
14 Materials : VTA
15 Thickness or Weight : VTA
16 Fastener Material : VTA
17 Support Span (m) : VTA
18 Louvers
19 Materials : VTA
20 Thickness or Weight : VTA
21 Fastener Material : VTA
22 Support Span (m) : VTA
23 Method of Support : VTA
24 Vertical Spacing : VTA
25 Ice Retainer Bar Included : No
26
27 FRAMEWORK
28 Columns:
29 Material & Grade : Carbon Steel A 36 Galvanized
30 Size L x W (mm) (Nominal) : VTA
31 Spacing : VTA
32 Splice Type : VTA
33 Horizontal Ties:
34 Material & Grade : Carbon Steel A 36 Galvanized
35 Size L x W (mm) (Nominal) : VTA
36 Vertical Spacing : VTA
37 Splice Type : VTA
38 Diagonals
39 Material & Grade : Carbon Steel A 36 Galvanized
40 Size L x W (mm) (Nominal) : VTA
41
42 DECKING, BASINS & PARTITIONS
43 Fan Deck
44 Material & Grade : A 283 Gr C, Galvanized
45 Decking Thickness L x W (mm) (Nominal) : VTA
46 Joint Type : VTA
47 Joint size L x W (mm) (Nominal) : VTA
48 Joint Spacing (mm) : VTA
49 Joint Support L x W (mm) (Nominal) : VTA
50 Joint Support Spacing (mm) : VTA
51 Overlay : VTA
52 Crossflow Hot Water Distribution Basin
53 Material & Grade : A 283 Gr C, Galvanized
54 Decking Size (L x W (mm) (Nominal) : VTA
55 Joint Type : VTA
56 Joint size L x W (mm) (Nominal) : VTA
57 Joint Spacing (mm) : VTA
58 Joint Support L x W (mm) (Nominal) : VTA
59 Joint Support Spacing (mm) : VTA
60 Curb size L x W (mm) (Nominal) : VTA
61 Basin Cover Included : Yes
62 Description : VTA
63 Material : VTA
64
65
1103-DS-540-1000 Page : 5 of 10 Rev : A
PTSI Confidential
Sengkang LNG Production Plant & Export Terminal
Mechanical Datasheet - Cooling Tower Package L-561
Client : Energy World Corporation Location South Sulawesi, Indonesia
REVISION
1
2 Process unit : Sengkang LNG Facility Item No. L-561
3 Project No. : 1103 Manufacturer VTA
4 Service of unit : Cooling Tower Package No. of units 2 (Two) 2 x 100% (1 W + 1 S)
5 DECKING, BASINS & PARTITIONS (continue)
6 Parititions / Wind Baffles:
7 Material & Grade : A 283 Gr C, Galvanized
8 Size L x W (mm) (Nominal) : VTA
9 Weight or Thickness : VTA
10
11 FILL
12 Material : VTA
13 Designation or Trade Name : VTA
14 Manufacturer : VTA
15 Average Fill Height (m) : VTA
16 Fill Air Travel (m) : VTA
17 Fill Volume (m3/cell) : VTA
18 Net Fill Plan Area (m2) : VTA
19 Type (Splash fill / Film fill) : VTA
20 SPLASH FILL
21 Size
22 Width (mm) : VTA
23 Thickness (mm) : VTA
24 Spacing (Center to Center)
25 Horizontal (mm) : VTA
26 Vertical (mm) : VTA
27 Number of Vertical Rows : VTA
28 Fill Orientation to Air Flow : Parallel
29 Basin Curb to Bottom Fill Layer (mm) : VTA
30 Support: : VTA
31 Method : VTA
32 Material : VTA
33 Wire Gauge or sze : VTA
34 Type of Coating : VTA
35 Maximum Horizontal Fill Support Span (mm) : VTA
36 Vertical Fill Support Span (mm) : VTA
37 Maximum allowable Continuous Operating Temperature ( oF) : VTA
38 Total Spash Area (m2) : VTA
39 Other Information: : VTA
40
41 FILM FILL
42 Type (Modular, Sheet, Cellular) : VTA
43 Individual Fill Pack Dimensions (m) : VTA
44 Nominal Sheet Thickness After Forming (mm) : VTA
45 Material of Sheets : VTA
46 Sheet Spacing (mm) : VTA
47 Fill System Load Bearing capacity, (Support Included) (psig) : VTA
48 Surface Area (m2/m3) : VTA
49 Maximum Allowable Continuous Operating Temperature (oF) : VTA
50 Nozzle Outlet Above Top of Fill (mm): : VTA
51 Fill Support: : VTA
52 Method : VTA
53 Material : A 283 Gr C, Galvanized
54 Size L x W (mm) (Nominal) : VTA
55 Maximum Fill Support Span (m) : VTA
56 Average Fill Air Velocity (m/min) : VTA
57 Other Information: : VTA
58
59 DRIFT ELIMINATOR
60 Material : A 283 Gr C, Galvanized
61 Designation or Trade Name: : VTA
62 Manufacturer : VTA
63 Type (Cellular, Wave, Blade, etc) : VTA
64
65
1103-DS-540-1000 Page : 6 of 10 Rev : A
PTSI Confidential
Sengkang LNG Production Plant & Export Terminal
Mechanical Datasheet - Cooling Tower Package L-561
Client : Energy World Corporation Location South Sulawesi, Indonesia
REVISION
1
2 Process unit : Sengkang LNG Facility Item No. L-561
3 Project No. : 1103 Manufacturer VTA
4 Service of unit : Cooling Tower Package No. of units 2 (Two) 2 x 100% (1 W + 1 S)
5 DRIFT ELIMINATOR (continue)
6 Number of Passes : VTA
7 Blade Spacing or Flute Size (mm) : VTA
8 Maximum Support Span (mm) : VTA
9 Support: : VTA
10 Method : VTA
11 Material : VTA
12 Thickness of Material : VTA
13 Size L x W (mm) (Nominal) : VTA
14 Exit Velocity (m/min) : VTA
15 Other Information (Drain Boards, etc) : VTA
16
17 WATER DISTRIBUTION - COUNTERFLOW TOWER
18 Upsray or Downspray : VTA
19 Headers
20 Number per Tower : VTA
21 Inlet Diameter (m) : VTA
22 Flange Rating & Type : VTA
23 Material & Schedule : VTA
24 Centerline Height Above Basin Curb (m) : VTA
25 Location : VTA
26 Support:
27 Method : VTA
28 Material : VTA
29 Size L x W (mm) (Nominal) : VTA
30 Maximum Support Span (m) : VTA
31 Distribution Laterals
32 Material & Schedule : VTA
33 Number per Cell : VTA
34 Diameter (s) (mm) : VTA
35 Fasteners to Structure : VTA
36 Method of Attachment to Main Header : VTA
37 Support:
38 Method : VTA
39 Material : VTA
40 Size L x W (mm) (Nominal) : VTA
41 Maximum support span (m) : VTA
42 Distribution Nozzles
43 Type (Cellular, Wave, Blade, etc) : VTA
44 Manufacturer : VTA
45 Material : VTA
46 Number per Cell : VTA
47 Orifice Diameter (mm) : VTA
48 Recommended Operating Depth (mm) : VTA
49 Nominal spacing (mm) : VTA
50 Operating Pressure (in H2O) : VTA
51
52 MECHANICAL EQUIPMENT
53 * Reverse Operation Required Yes / No : Yes
54 Fans
55 Number : VTA
56 Type or Model : VTA
57 Manufacturer : VTA
58 Diameter (m) : VTA
59 Number of Blades per fan : VTA
60 Fan Speed (RPM) : VTA
61 Tip Speed (RPM) : VTA
62 First Critical Speed (RPM) : VTA
63 Second Critical Speed (RPM) : VTA
64 Rater Power / Fan (Design at Motor Output Shaft) : VTA
65
66
67
68
1103-DS-540-1000 Page : 7 of 10 Rev : A
PTSI Confidential
Sengkang LNG Production Plant & Export Terminal
Mechanical Datasheet - Cooling Tower Package L-561
Client : Energy World Corporation Location South Sulawesi, Indonesia
REVISION
1
2 Process unit : Sengkang LNG Facility Item No. L-561
3 Project No. : 1103 Manufacturer VTA
4 Service of unit : Cooling Tower Package No. of units 2 (Two) 2 x 100% (1 W + 1 S)
5 MECHANICAL EQUIPMENT (continue)
6 Fans
7 kW (BHP) : VTA
8 Air delivery per fan (acfm) : VTA
9 Design Exit Air Temperature (oF) : VTA
10 Exit Air Density (kg/m3) : VTA
11 Fan Static Efficiency, Percent : VTA
12 Fan Total efficiency, percent : VTA
13 (Total) Static Pressure Drop (in H2O) : VTA
14 Velocity Pressure at Fan (in H2O) : VTA
15 Velocity Recovery (in H2O) : VTA
16 Net Total Pressure (in H2O) : VTA
17 Design Pitch setting, degrees : VTA
18 Maximum Pitch Setting, Degrees : VTA
19 Maximum / minimum Tip Clearance (mm) : VTA
20 Blade Material : VTA
21 Hub Material : VTA
22 Hardware Material : VTA
23 Hub Cover (seal Disc) Material : VTA
24 Hub Cover (seal Disc) Diameter (m) : VTA
25 hub Bore Straight / Tapered : Straight
26 Fan Moment of Inertia (WR2) (kg-m2) : VTA
27 FanStack
28 Manufacturer : VTA
29 Materials : VTA
30 Height (m) : VTA
31 Distance, Fan Above Fan Deck (mm) : VTA
32 Distance, Fan to Top of Stack (mm) : VTA
33 Stack Throat Diameter at Fan Level (m) : VTA
34 Inlet diameter (m) : VTA
35 Exit Diameter (m) : VTA
36 Method of Anchoring : VTA
37 Fan Stack Hardware : VTA
38 Fan Guard Screens Included Yes/ No : Yes
39 Materials : VTA
40 Hardware Material : VTA
41 Gear Speed Reducer
42 Manufacturer : VTA
43 Model number : VTA
44 Type or Model : VTA
45 Case Material : VTA
46 Gear Speed Reducer efficiency, percent : VTA
47 AGMA Service Factor, Base on Motor Nameplate : VTA
48 Gear Ratio : VTA
49 AGMA Rating Based on 2.5 service Factor (HP) : VTA
50 Number of Reductions : VTA
51 Type of Oil Lubrication System : VTA
52 Anchor Hardware Material : VTA
53 Case Protective Coating : VTA
54 Gear Speed Reducer
55 External Fill / Drain Line Included Yes/ No : Yes
56 If so, has Flexible Link Yes/ No : No
57 Drain Line Material : VTA
58 Vent External to Stack Included Yes/ No : Yes
59 Vent Line Material : VTA
60 Oil Gauge Included Gauge glass / Dipstick : Gauge Glass
61 Oil Gauge External to Fan Stack Yes/ No : VTA
62 Bearing Life (Minumum / Maximum B10) (hr) : VTA
63 Reversible Yes/ No : VTA
64
65
66
67
68
1103-DS-540-1000 Page : 8 of 10 Rev : A
PTSI Confidential
Sengkang LNG Production Plant & Export Terminal
Mechanical Datasheet - Cooling Tower Package L-561
Client : Energy World Corporation Location South Sulawesi, Indonesia
REVISION
1
2 Process unit : Sengkang LNG Facility Item No. L-561
3 Project No. : 1103 Manufacturer : VTA
4 Service of unit : Cooling Tower Package No. of units : 2 (Two) 2 x 100% (1 W + 1 S)
5 MECHANICAL EQUIPMENT (continue)
6 Drive Shaft Assembly : VTA
7 Manufacturer : VTA
8 Model Number : VTA
9 Nominal Tube Diameter (mm) : VTA
10 Rated at Motor Nameplate RPM & 2.5 Service Factor (HP) : VTA
11 Tube Materials : VTA
12 Coupling Materials : VTA
13 Type of Flexible Components/ Materials : VTA
14 Hardware Material : VTA
15 Drive shaft Guard Materials / Quantity : VTA
16 Motors (NOTE 21)
17
18 PACKAGE TIE IN SCHEDULE FOR PIPING
19 TIE-IN SIZE RATING Op. PRESS Op. TEMP MIN FLOW MAX FLOW
SERVICE
20 No. (in) FACING barg (°C) m³/h m³/h
21 TP-01 Outlet Cooling Water Circulation Pump 14 150# RF VTA VTA VTA VTA
22 TP-02 Inlet Hot Water Return 14 150# RF VTA VTA VTA VTA
23 TP-03 Inlet Make Up Water from Raw Water T 2 150# RF VTA VTA VTA VTA
24 TP-04 Drain connection to outfall VTA 150# RF VTA VTA VTA VTA
25 TP-05 Overflow 2 150# RF VTA VTA VTA VTA
26 WEIGHT DATA (kg)
27 UNIT EMPTY OPERATING TEST Max. Maint.
28 1 Cooling Tower VTA VTA VTA VTA
29 2 Chemical Dosing Skid VTA VTA VTA VTA
30
31
32 NOTES
33 1 VTA = Vendor to advise, VTC = Vendor to confirm
34 2 Vendor shall fill in all blank data whichever applicable
35 3 Materials to be selected based on 25 years lifetime. Grade of Material to be defined by VENDOR.
36 4 The value indicated is the maximum process requirement. The cooling water package to be designed with 10% margin
37 on flowrate for circulation pumps and make up water requirement. For area shall be sized based on governing scenario
38 between 10% on duty or 15% on required surface.
39 5 Vendor to propose and include Chemical Dosing System (as required by site conditions) in their bid
40 6 Vendor to calculate, guarantee and indicate the Cooling Water Circulation Rate, Make-Up Water Rate and Blowdown Rate
41 7 Vendor to guarantee the product quality as specified, capacity of the package unit including its turn-down and turn-up capacity,
42 maximum losses and make-up required for any solvent and other consumables (if any).
43 Vendor shall also indicate and guarantee amount of utility consumption.
44 8 All nozzle flanges shall be as per ASME B 16.5
45 9 The maximum value for the equipment noise limit (sound pressure level) shall be 85 dB(A) 1 m from the edge equipment.
46 10 Migas certificate to be provided. Vendor is responsible to provide all required document to obtain Migas approval.
47 11 VENDOR to refer to the following project documents:
48 - 09804-PI-500-561 "P&ID Cooling Water system"
49 - 1103-SP-540-1000 "Specification for Cooling Tower Package"
50 - 09804-TS-000-103 "LNG Plant Painting & Coating Specification"
51 - 09804-TS-000-101 Rev 1 "LNG Plant Piping Specification"
52
53 12 Motor shall be suitable for Safe Area. Eletric motor rating shall be IP 55 as a minimum
54 13 Each fan shall be provided with vibration switch.
55 14 All instrumention shall be certified for Zone 2, Group IIA, T3. Line- All external equipment shall be weatherproof to
56 IP 65 as a minimum
57 15 For detailed scope of supply, refer to Specification for Cooling Tower (1103-SP-540-1000)
58 16 Overall area / dimension required to include cooling tower and chemical dosing skid to be provided by VENDOR
59 17 Tie-in point connection shall terminate at the skid boundary limit with flanges and valved connection
60 18 Equipment shown on P&ID / Scope of supply are indicative only and state the minimum requirement for the package.
61 Vendor can provide additional equipments if required for the safe design and trouble free operation of the package
62 19 Vendor to propose and provide schematic diagram for the cooling tower package including schematic of the
63 chemical dosing system.
64
65
66
67
68
1103-DS-540-1000 Page : 9 of 10 Rev : A
PTSI Confidential
Sengkang LNG Production Plant & Export Terminal
Mechanical Datasheet - Cooling Tower Package L-561
Client : Energy World Corporation Location South Sulawesi, Indonesia
REVISION
1
2 Process unit : Sengkang LNG Facility Item No. L-561
3 Project No. : 1103 Manufacturer VTA
4 Service of unit : Cooling Tower Package No. of units 2 (Two) 2 x 100% (1 W + 1 S)
5 NOTES
6 20 Fresh Water Quality Data and Hot Water Return Quality Data
7 Parameter Unit
8 Total Dissolved Solid mg/L (HOLD)
9 Turbidity NTU (HOLD)
10 Suspended solids mg/L (HOLD)
11 Inorganic
12 pH (HOLD)
13 Iron (Fe) mg/L (HOLD)
14 Calcium Carbonate (CaCO3) mg/L (HOLD)
15 Nitrate (NO3-N) mg/L (HOLD)
16 Nitrite (NO2-N) mg/L (HOLD)
17 Manganese (Mn) mg/L (HOLD)
18 Chloride (Cl-) mg/L (HOLD)
19 Fluoride (F) mg/L (HOLD)
20 KMnO4 mg/L (HOLD)
21 Sulfate (SO4) mg/L (HOLD)
22 Free Chlorine mg/L (HOLD)
23 Microbiological
24 Faecal Coli form per 100 ml (HOLD)
25 Total Coli form per 100 ml (HOLD)
26 Organic Chemical
27 Surfactants Anionic as MBAS mg/L (HOLD)
28 The data shall be treated under "HOLD". Quality of the water as indicated may change based on further ongoing survey.
29 VENDOR to provide the proposal based on the presented quality information. Any further changes in the composition data
30 at later stage shall be considered and informed back to the vendor.
31 21 Vendor shall fill in the LV / MV Motor Datasheet provided (after PO).
32 22 VENDOR to refer to Process datasheet Doc No. 1103-DS-100-4059 latest revision for compliance
33 23 However, following testing plan shall be considered as minimum requirement:
34 - Casing: Visual inspection
35 - Fills: Visual inspection
36 - Structural: Visual inspection
37 - Pipes: Visual inspection, dimensional check, hydro test
38 - Valves: Visual inspection, dimensional check, hydro test
39 - Fan:
GearTip Clearance,
Box: Witness noStatic
loadBalancing, fanfor
running test running test,
bearing dynamic balancing,
temperature, hub static
after running test – balancing
visual
40 - inspection of gear teeth
41 - Shaft: Dynamic Balancing, review of material test certificates
42 - Motor: Routine & type test certificate
43 - Pump: material certificate, performance test report, visual dimension, conformity certificate
44 - Instrumentation: calibration test, CE certification, ATEX certification, material certificate
45 - Junction Box (electrical and instrument): CE certification, insulation test, dielectric test
46 - Flow/Pressure/Temperature indicator: Test supplier report, CE certificate, material certificate
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
1103-DS-540-1000 Page : 10 of 10 Rev : A
PTSI Confidential
MATINDOK GAS DEVELOPMENT PROJECT (MGDP)

MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)

2. COOLING WATER CIRCULATION PUMPS


(386-P-1001 A/B)
MATINDOK GAS DEVELOPMENT PROJECT (MGDP)

MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
SERVICE : Cooling Water Circulation Pumps TAG NUMBER : 386-P-1001 A/B

REVISION
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 2 x 100% (1W+1S)
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327

1 Note: Indicated Information Completed by Purchaser by Manufacturer by Purchaser or Manufacturer */ VTA : Vendor to Advice
2 Manufacturer VTA Model VTA Serial Number VTA
3 GENERAL
4 Number Motor Driven 2 (TWO) Number Turbine Driven N/A Gearbox Item Number N/A
5 Motor Item Number Turbine Item Number N/A Gearbox Provided By N/A
6 Motor Provided By VENDOR Turbine Provided By N/A Gearbox Mounted By N/A

7 Motor Mounted By VENDOR Turbine Mounted By N/A

8 OPERATING CONDITIONS (NOTE-2) PERFORMANCE (NOTE-2)


9 Rated Max. Normal Min. Performance Curve No VTA Speed (rpm) VTA
10 Capacity (gpm) NOTE-30 2228
11 Suction Pressure (psig) Measured at Capacity Rated Max. Normal Min.
12 Discharge Pressure (psig) VTA NPSH Req'd (ft) VTA VTA VTA
13 Differential Pressure (psi) 52.0 Total Differential Head @ Rated Impeller VTA (ft)
14 Differential head (ft) VTA @ Minimum SG Max. Differential Head @ Rated Impeller VTA (ft)
15 Hydraulic Power (hp) Minimum Continuous Flow VTA
16 At Designated Capacity Rated Max. Normal Min. Thermal (gpm) VTA Stable (gpm) VTA
17 Operating Time (hr./yr) Allowable Operating Region VTA To VTA (gpm)
18 NPSH Available (ft, at impeller) VTA VTA Best Efficiency point for Rated Impeller VTA (gpm)
19 System Design Suction Specific Speed Max./Actual VTA / VTA
20 Stand Alone Operation Parallel Operation Impeller Diameter Rated VTA Max. VTA Min. VTA (inch.)
21 Series operation with Item Number Pump Rated Power VTA (hp) Efficiency VTA (%)
22 Suction Pressure Min./max. / psig) Maximum Power @ Rated Impeller VTA (hp)
23 Service Rotation (Viewed from Coupling End) CW CCW
24 Continous Intermitent (Starts/Day)
25 System Control Method Case Pressure Rating
26 Speed Flow Level Temperature Max. Allowable Working Pressure VTA (psig)
27 Pressure Pipe Friction Resistance Only @ VTA (OF)

28 PUMPED FLUID Hydrostatic Test Pressure VTA (psig)

29 Pumped Fluid Cooling water + Raw Water SITE CONDITIONS


30 Rated Max. Normal Min. Location Indoor Outdoor
31 Pumping Temperature (oF) 99.15 94.65 81 Altitude 46 (ft.) above mean sea level 2
32 At Designated Temp. Rated Max. Normal Min. Range of Ambient Temperatures (Min./Max.) 71.06 / 91.58 (OF)
33 Specific Gravity VTA VTA 1 VTA Electrical Classification Zone Gr. Div. NOTE-10
34 Vapor Pressure (psia) VTA VTA VTA VTA Non Hazardous
35 Viscosity (cSt) VTA VTA VTA VTA GENERAL REMARKS
36 Specific Heat (Btu/lb.oF) VTA VTA VTA VTA Electrical motor rating : IP 55
37 Initial Boiling Point (OF) @ (psia)
38 Liquid Hazardous Flammable
39 Other Cooling water + raw water
40
41
42 Corrosion/Erosion Caused By

43 % Solid Max. Particle Size (inch.)

44 NOTES:
45 1 VTA : Vendor to advise, VTC : Vendor To Confirm
46 2 Vendor shall fill in all blank data whichever applicable
47 3 Materials to be selected based on 20 years lifetime. Grade of Material to be defined by VENDOR.
48 4 Design Margin between NPSHA & NPSHR shall be 3 ft at minimum.
49 5 Pumps are designed as per ANSI B73.1 and Project Specification MTDF-MR-300-SPE-3208 "Specification for ANSI Pumps" 2
50 6 Pump rated capacity with 10% design margin
51 7 All nozzle flanges shall be as per ASME B 16.5
52 8 The maximum value for the equipment noise limit (sound pressure level) shall be 85 dB(A) at 1m from the edge of the equipments
53 9 Migas certificate to be provided. VENDOR is responsible to provide all required documents to obtain Migas approval.
54 10 Motor shall be suitable for Non hazardous area (safe area) classification of zone 2, gas group IIA and temperature class T3.
55 Electrical motor rating shall be IP 55 as a minimum
56 11 All instrumention shall be certified for Zone 2, Group IIA, T3. Line- All external equipment shall be weatherproof to IP 65 as a minimum
57 12. Vendor shall fill in the LV / MV Motor Datasheet provided with the Material Requisition Document. 2
58 13. Design Pressure of closed cooling water circulation loop is 120 psig. Design temperature is 158 oF 2
59 14. VENDOR to perform Liquid Penetrant test to Manufacturer's Standard as a minimum

MTDF-MS-386-EDS-3327 | 7518-386-SP-0300-3327 Page 15 of 20


MATINDOK GAS DEVELOPMENT PROJECT (MGDP)

MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
SERVICE : Cooling Water Circulation Pumps TAG NUMBER : 386-P-1001 A/B

REVISION
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 2 x 100% (1W+1S)
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327

1 MECHANICAL DATA (NOTE-2) COUPLING BETWEEN PUMP AND DRIVER


2 Impeller Type Manufacturer VTA
3 Closed Open Type SPACER
4 Semi-open Other Size VTA
5 Casing Mounting Model VTA
6 Foot Centerline Spacer Length (in.) VTA
7 Vertical Line Close-coupled Coupling Guard Type
8 Bearings Manufacturer's Standard
9 Bearing Manufacturer VTA Baseplate Mounted
10 Radial Bearing Type VTA No. VTA Non-Spark Coupling Guard Required
11 Thrust Bearing Type VTA No. VTA Remarks
12 Bearing Isolator VTA
13 Shaft Stiffness Ratio (L3/D4) VTA
14 Lubrication
15 Flood Pure Mist Shielded (Grease) BASE PLATE
16 Grease Purge Mist Sealed (Grease) Remarks Grounded Free Standing
17 Constant Level Oiler Required Centerline of Pump to Stilt Bottom (in.)
18 Housing Vent Required Pedestal
19 Magnetic Drain Plug in Housing Required Design PIP Standard RESP002
20 Oil Cooler Required Manufacturer's Standard
21 Seal Spray Guard Required Remarks:
22 Oil Viscosity ISO Grade VTA
23 Other PAINT AND SHIPMENT PREPARATION
24 Nozzle Connections Size Rating Facing Pump Baseplate
25 Suction VTA 150# RF Manufacturer's Standard Manufacturer's Standard
26 Discharge VTA 150# RF Other MTDF-PP-300-SPE-1012 Other MTDF-PP-300-SPE-1012 2
27 Aux. Case Connection Drain Vent Shipment
28 Size VTA (in.) Domestic Export Export Boxing Required
29 Threaded Welded and Flanged Number of Months of Storage 12 months outdoor

30 MATERIALS (NOTE-2, 3) Total Weight VTA (lbs)

31 Material Class Code INSPECTION AND TESTING


32 Casing Cast Iron Final Inspection Required Days Notification Required
33 Impeller Bronze Test Non-Witnessed Witnessed Certificated
34 Cover VTA Hydrostatic
35 Shaft VTA Performance
36 Shaft Sleeve VTA NPSHR
37 Baseplate VTA Vibration
38 Casing Gasket VTA Mech. run test with job driver
39 Impeller Gasket VTA Dismantle and Inspect After test
40 Casing Fasteners VTA Casting Repair Procedure Approval Required
41 Bearing Housing VTA Material Certification Required
42 Bearing Housing Adapter VTA Casing Cover Impeller Shaft
43 Bearing Housing End Seals VTA Other gaskets and O-rings
44 Coupling Guard NON SPARKING Inspection Required for Connection Welds
45 Mechanical Seal Gland VTA Manufacturer's Standard Visual Inspection NOTE-14 2
46 Mechanical Seal Gland Fasteners VTA Inspection Required for Castings
47 Manufacturer's Standard Visual Inspection

48 DRIVER (NOTE-12) Other 2


49 Horsepowering Rating VTA (hp) Speed VTA (rpm) MANUFACTURER DOCUMENTATION REQUIREMENTS
50 Drive HP Selected or Max. S. G. VTA & Max. Visc. VTA (cp) For Vendor Data Requirements Refer to: MTDF-MS-386-SOW-3319
51 Rated Voltage/Frequency Remarks
52 Service Condition
53 Remarks as per MTDF-EL-300-SPE-1007 "Specification for LV Induction Motor" 2
54
55
56
57
58
59
60
61

MTDF-MS-386-EDS-3327 | 7518-386-SP-0300-3327 Page 16 of 20


MATINDOK GAS DEVELOPMENT PROJECT (MGDP)

MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)
SERVICE : Cooling Water Circulation Pumps TAG NUMBER : 386-P-1001 A/B

REVISION
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 2 x 100% (1W+1S)
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327

1 MECHANICAL SEAL BARRIER/BUFFER FLUSH SYSTEM


2 Supplied By Pump Manufacturer Purchaser Barrier Flush Plan
3 Mounted By Pump Manufacturer Purchaser Barrier Flush Liquid
4 Seal Classification Code VTA Temperature Min./Max. / (oF)
5 Manufacturer VTA Specific Grafity
6 Model VTA Specific Heat (BTU/lb oF)
7 Manufacturer Code VTA Vapor Pressure (psia) @ (oF)
8 Seal Type Cartridge Component Pressure Required Min./Max. / (psig)
9 Seal Design Single Dual Dry Gas MAWP of Secondary Seal System (psig)
10 Pressurized Unpressurized Temperature Required Min.Max. / (oF)
11 Seal Chamber Taper Bore Cylindrical Bore Secondary Seal Flush Piping Tubing Pipe
12 Seal Chamber Size Oversized Standard Material 316SS Carbon Steel
13 Other
14 Pumping Ring Required Piping/Tubing Size (in.)
15 Throat Bushing Required Materials Piping Assembly Threaded Unions Flanged
16 Remarks Tube Type Fittings Socket Welded 2
17 Remarks
18
19 SEAL GLAND SEAL SYSTEM INSTRUMENTATION
20 Taps Required Quench Flush Drain Primary Seal Gauges Switches
21 Other Flow
22 Throtle Bushing Materials Temperature
23 SEAL FLUSHING Pressure
24 Primary Flush Plan No. Secondary Seal
25 External Flush Liquid Flow
26 Supply Temperature Min./Max. / (oF) Temperature
27 Specific Gravity Pressure
28 Specific Heat (BTU/lb. oF) Remarks
29 Vapor Pressure (psia) @ (oF)
30 Flow Rate Required Min./Max. / (gpm)
31 Presure Required Min./Max. / (psig)
32 Temperature Required Min./Max. / (oF) COOLING OR HEATING PIPING CLASS
33 Primary Seal Flush piping Piping Plan No.
34 Tubing Pipe Other Name of Fluid
35 Material 316SS Carbon Steel Inlet Temperature (oF)
36 Other Outlet Temperature (oF)
37 Piping/Tubing Size (in) Rated Flow (gpm)
38 Piping Assembly Threaded Unions Flanged Supply Pressure (psig)
39 Tube Type Fittings Socket Welded Max. Allowable ∆P (psi)
40 Remarks
41 Galvanized Pipe SS Tubing
42 Sight Flow Indicator
43 Outlet Shut-Off Valve
44 Remarks
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60

MTDF-MS-386-EDS-3327 | 7518-386-SP-0300-3327 Page 17 of 20


MATINDOK GAS DEVELOPMENT PROJECT (MGDP)

MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)

3. CHEMICAL TREATMENT PACKAGE (….)


MATINDOK GAS DEVELOPMENT PROJECT (MGDP)

MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)

REVISION
SERVICE : Chemical Treatment Package TAG NUMBER : -
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 1 x 100%
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327

1 INJECTION LIQUID
2 Injection System for: ✘ Water Treatment Pipeline Other :
3 Liquid Injected VTA
4 Injection Flow Normal: VTA L/hr Max. : VTA L/hr
5 Pressure Required at Injection Point (1) VTA psig Temperature: AMBIENT Specific Gravity: VTA
6 (2) VTA psig Viscosity @ Flowing Temperature: VTA
7 Concentration VTA %
8 CHEMICAL STORAGE TANK
9 Item No VTA
10 Service of Unit Chemical Storage Tank
11 No of Required 1 x 100% per Chemical
12 Capacity VTA Liter NOTE-9, 10 2
13 Design Pres.: VTA psig Design Temp.: VTA °F
14 Operating Pres.: ATM psig Operating Temp.: Ambient
15 Type VTA
16 Size (ID x T/F) VTA inch
17 Thickness VTA inch
18 Material VTA
19 Accessories ✘ Calibrated Level Gauge Measuring Cup ✘ Flame Arrestor
20 ✘ Level Transmitter ✘ Inner Basket Others,….
21 ✘ Cover ✘ Internal Baffles …………..
22 ✘ Low Point Drain Ladder …………..
23 MIXER (VTA)
24 Item No
25 Service of Unit
26 No. of Required
27 Type Mechanical with motor Pulsator
28 Hand-operation Vertical Mounted
29 Material
30
31 MOTOR FOR PUMPS (NOTE-12) MOTOR FOR MIXER (NOTE-12) 2
32 No. Required: 1+1 (Motor shall follow MTDF-EL-900-SPE-1007 ) No. Required:
33 Supplied By: VTA Supplied By:
34 Mounted By: VTA Mounted By:
35 Rated Output: VTA HP Rated Output: HP
36 Pole: 4 Speed: 1500 Pole: Speed:
37 Phase: 3 Hz: 50 Volt: 400 Phase: Hz: Volt:
38 ACCESSORIES
39 ✘ Local Control Panel, if required ✘ Automatic Control System ✘ Strainers ✘ Pressure Gauge
40 ✘ Piping on Common Baseplate ✘ Valves ✘ Relief Valves ✘ Pulsation Dampeners VTA
41 ✘ Anchor Bolts & Nuts ✘ Instruments ✘ Companion Flange Bolts & Nuts ✘ Calibration Gauge Glass / Column
42 INSTALLATION
43 ✘ Outdoor Under Roof Indoor Heated Unheated
44 Hazardous Area Classification Non-Hazardous
45 Site Ambient Temperature Minimum: 71.06 °F Normal: 81.43 °F Maximum: 91.58 °F
46 Mounted on: ✘ Skid (with Drip pan and Drain Con.) Structural Base
47 Total Weight of the System VTA kg
48 NOTES
49 1. VTA = Vendor to advise, VTC = Vendor to confirm
50 2. Vendor shall fill in all blank data whichever applicable
51 3. Materials to be selected based on 20 years lifetime. Grade of Material to be defined by VENDOR.
52 4. All nozzle flanges shall be as per ASME B 16.5
53 5. The maximum value for the equipment noise limit (sound pressure level) shall be 85 dB(A) 1 m from the edge equipment.
54 6. Migas certificate to be provided. Vendor is responsible to provide all required document to obtain Migas approval.
55 7. Motor shall be suitable for Zone 2, Group IIA, T3. Eletric motor rating shall be IP 55 as a minimum
56 8. All instrumention shall be certified for Zone 2, Group IIA, T3. Line- All external equipment shall be weatherproof to IP 65 as a minimum
57 9. Refer to Specification for Chemical Injection Package (MTDF-MS-300-SPE-3213)
58 10. 10% design margin on net working tank volume. Tank should be sized for storage volume of period of one week.
59 11. Vendor to propose and provide chemical storage tank drawing and detail
60 12. Vendor shall fill in the LV / MV Motor Datasheet provided with the Material Requisition Document. 2

MTDF-MS-386-EDS-3327 | 7518-386-SP-0300-3327 Page 18 of 20


MATINDOK GAS DEVELOPMENT PROJECT (MGDP)

MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)

REVISION
SERVICE : Chemical Dosing Pumps TAG NUMBER : -
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 2 x 100% (1W + 1S)
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327

1 APPLICABLE TO: PROPOSAL PURCHASE AS BUILT


2 FOR PT PERTAMINA EP UNIT COOLING TOWER PACKAGE
3 SITE BANGGAI - SULAWESI TENGAH NO. OF PUMPS REQUIRED 1 OPERATING + 1 STANDBY (2 x 100%)
4 SERVICE CHEMICAL DOSING PUMPS MODEL SIZE AND TYPE
5 MANUFACTURER SERIAL NO.

6 NOTE: INDICATES INFORMATION TO BE COMPLETED BY PURCHASER BY MANUFACTURER


7 GENERAL
8 NO. MOTORS DRIVEN 2 (TWO) UNITS OTHER DRIVER TYPE
9 PUMP ITEM NO'S 0 PUMP ITEM NO'S
10 MOTOR ITEM NO'S DRIVER ITEM NO'S GEAR ITEM NO'S
11 MOTOR PROVIDED BY PUMP'S VENDOR DRIVER PROVIDED BY GEAR PROVIDED BY
12 MOTOR MOUNTED BY PUMP'S VENDOR DRIVER MOUNTED BY GEAR MOUNTED BY
13 MOTOR DATA SHEET NO. DRIVER DATA SHEET NO. GEAR DATA SHEET NO.

14 OPERATING CONDITIONS LIQUID


15 CAPACITY @ PT (GPM) : TYPE OR NAME OF LIQUID VTA
16 MAXIMUM VTA MINIMUM VTA RATED VTA PUMPING TEMPERATURE (°F):
17 DISCHARGE PRESSURE (PSIG) : NORMAL AMB MAX MIN
18 MAXIMUM VTA MINIMUM VTA SPECIFIC GRAVITY VTA MAXIMUM MINIMUM
19 SUCTION PRESSURE (PSIG) : SPECIFIC HEAT cP (BTU/lb °F)
20 MAXIMUM VTA MINIMUM VTA VISCOSITY (cP) VTA MINIMUM MAXIMUM
21 DIFFERENTIAL PRESSURE (PSI) : VAPOR PRESSURE (PSIA) VTA
22 MAXIMUM VTA MINIMUM VTA CORROSIVE/EROSIVE AGENTS VTA
23 NPSH AVAILABLE (FT) VTA CHLORIDE CONCENTRATION (PPM) VTA
24 WITHOUT ACCELERATION HEAD ACTUAL H2S CONCENTRATION (PPM) VTA
25 TURNDOWN RATIO VTA LIQUID TOXIC FLAMMABLE OTHER VTA

26 PERFORMANCE SITE AND UTILITY DATA


27 NUMBER OF FEEDS RATED CAPACITY (GPM) LOCATION INDOOR OUTDOOR
28 NPSH REQUIRED (FT) VTA HEATED UNHEATED UNDER ROOF
29 BHP RATED VTA AT RELIEF SETTING VTA ELECTRICAL AREA CLASS NOTE-7
30 PLUNGER SPEED (strokes/min) VTA DESIGN MAX VTA WINTERIZATION REQD TROPICALIZATION REQD
31 DIAMETER (IN.) VTA LENGTH OF STROKE (IN.) SITE DATA
32 PUMP HEAD: VTA RANGE OF AMBIENT TEMPS:MIN/MAX 80 / 91 °F
33 MAXIMUM PRESSURE (PSIG) VTA UNUSUAL CONDITIONS
34 HYDRO TEST PRESSURE (PSIG) VTA DUST FUMES SALT ATMOSPHERE
35 MAX DISCH PRESS. W/ JOB DRIVER (PSIG) VTA OTHER
36 MAX BHP BASIS GEAR STRENGTH VTA UTILITY CONDITIONS

37 CONSTRUCTION ELECTRICITY DRIVERS HEATING CONTROL SHUTDOWN


38 SIZE ANSI FACING POSITION VOLTAGE 400
39 CONNECTIONS RATING HERTZ 50
40 SUCTION VTA #150 RF SIDE PHASE 3
41 DISCHARGE VTA #150 RF SIDE COOLING WATER INLET RETURN DESIGN MAX D
42 FLUSH TEMP °F N/A MAX N/A
43 PRESS. (PSIG) N/A MIN N/A N/A N/A
44 LIQUID END JACKET REQ'D SOURCE N/A
45 TYPE DIAPHRAGM PLUNGER INSTRUMENT AIR MIN / NOR / MAX
46 DIAPHRAGM DIA (IN) NO REQ. PRESSURE (PSIG) VTA

47 VALVES/FEED SUCTION DISCHARGE APPLICABLE SPECIFICATIONS:


48 TYPE Ball Ball API 675 POSITIVE DISPLACEMENT PUMPS - CONTROLLED VOLUME
49 NUMBER 1 1 GOVERNING SPECIFICATION (IF DIFFERENT): MTDF-MR-300-SPE-3213

50 REMARKS
51
52
53
54

MTDF-MS-386-EDS-3327 | 7518-386-SP-0300-3327 Page 19 of 20


55

MTDF-MS-386-EDS-3327 | 7518-386-SP-0300-3327 Page 19 of 20


MATINDOK GAS DEVELOPMENT PROJECT (MGDP)

MECHANICAL DATASHEET
COOLING TOWER PACKAGE (386-V-1001)

REVISION
SERVICE : Chemical Dosing Pumps TAG NUMBER : -
LOCATION : MATINDOK Gas Production Facility NO. QUANTITY : 2 x 100% (1W + 1S)
P&ID NUMBER : MTDF-PR-386-PID-1001 DOC. NO. : MTDF-MS-386-EDS-3327

1 MATERIALS (NOTE-2, 3) CONTROLS


2 LIQUID END TEFLON (VTA) TYPE: SIGNAL:
3 CONTOUR PLATE VTA MANUAL REMOTE PNEUMATIC
4 HYDRAULIC DIAPHRAGM VTA AUTOMATIC LOCAL ELECTRONIC
5 PROCESS DIAPHRAGM TEFLON (VTA) STROKE CONTROL:
6 PLUNGER VTA PNEUMATIC (PSIG):
7 LANTERN RING VTA MINIMUM MAXIMUM
8 PACKING GLAND VTA ELECTRONIC (mA):
9 PACKING VTA MINIMUM MAXIMUM

10 VALVE TEFLON / VITON (VTA) OTHER PURCHASE REQUIREMENTS


11 VALVE SEAT VTA NAMEPLATE UNITS U.S. CUSTOMARY SI
12 VALVE GUIDE VTA VENDOR FURNISHED PROCESS PIPING
13 VALVE BODY VTA
14 VALVE GASKET VTA VENDOR REVIEW PIPING DRAWINGS
15 FRAME VTA VENDOR FURNISHED PULSATION SUPRESSION DEVICES VTA
16 SPECIAL MATERIAL TESTS (2.13.1.3) VTA VENDOR FURNISHED RELIEF VALVE
17 INTERNAL EXTERNAL
18 LOW AMBIENT TEMPERATURE MATERIALS TESTS (2.13.5) RELIEF VALVE SETTING (PSIG) VTA
19 VENDOR FURNISHED BACK-PRESSURE VALVE

20 QA INSPECTION AND TEST DOUBLE CHECK VALVES REQUIRED


21 COMPLIANCE WITH INSPECTORS CHECK LIST OIL-FILLED PRESSURE GAUGES REQUIRED
22 CERTIFICATION OF MATERIALS VENDOR FURNISHED CONTROL PANEL
23 FINAL ASSEMBLY CLEARANCES BASEPLATE PREPARED FOR EPOXY GROUT
24 SURFACE AND SUBSURFACE EXAMINATIONS PROVIDE TECHNICAL DATA MANUAL
25 RADIOGRAPHY PAINTING as per MTDF-PP-300-SPE-1012 2
26 ULTRASONIC

27 MAGNETIC PARTICLE PREPARATION FOR SHIPMENT


28 LIQUID PENETRANT DOMESTIC EXPORT EXPORT BOXING 2
29 CLEANLINESS PRIOR TO FINAL ASSEMBLY OUTDOOR STORAGE MORE THAN 6 MONTHS
30 HARDNESS OF PARTS, WELDS & HEAT AFFECTED ZONES WEIGHTS (LBS) NOTE-2
31 FURNISH PROCEDURES FOR OPTIONAL TESTS PUMP BASE GEAR DRIVER

32 TESTS REQ'D WIT OBS DRIVERS (NOTE-12) 2


33 HYDROSTATIC MOTOR:
34 STEADY STATE ACCURACY MANUFACTURER
35 REPEATABILITY TYPE Squirrel Cage Induction Motor
36 LINEARITY FRAME NO.
37 PERFORMANCE (8.3.4) CONSTANT SPEED
38 MECHANICAL RUN (8.3.5)
39 NPIP (8.3.7.1)
40 COMPLETE UNIT (8.3.7.2)
41 SOUND LEVEL (8.3.7.3)
42 HIGH DISCHARGE PRES (8.3.7.4)
43 FACTORY ACCEPTANCE (8.3.8) VARIABLE SPEED

44 LUBRICATION FLUID HP RPM


45 CRANKCASE INTERMEDIATE VOLTS 400 PHASE 3
46 HYDRAULIC FLUID HERTZ 50 SERVICE FACTOR
47 ACCESSORIES ENCLOSURE
48 SPEED REDUCER MANUFACTURER OTHER (SEE SEPARATE DATA SHEETS)
49 INTEGRAL SEPARATE GAS DRIVEN
50 MODEL STEAM TURBINE
51 RATIO OTHER Motor shall be suitable for Zone 2, Group IIA, T3. 2
52 BASEPLATE UNDER Eletric motor rating shall be IP 55 as a minimum 2
53 COUPLING MANUFACTURER Refer to MTDF-EL-300-SPE-1007 "Specification for LV Induction Motor" 2
54 TYPE

55 REMARKS
56