ATLAS OF

POWER GRID OF
HPSEBL (66kV & Above)
1

INDEX
S.No. Description Page No. S.No. Description Page No.
1 List of Sub-Stations 2 6 Ghanvi 51
2 Detail/Status of Capacitor Banks Installed 5 7 Golthai 52
3 Network Diagram 6 8 Gumma 53
4 EHV Lines Detail 7 9 Khotkhai(Hulli) 54
5 Single Line Diagrams 10 Kumarsain 55
I 220kV Sub-Stations 8 11 Nalagarh 56
1 Baddi 9 12 Nathpa 57
2 Bhabha 10 13 Nogli 58
3 Giri 11 14 Parwanoo 59
4 Hamirpur-II 12 15 Sainj 60
5 Jassore 13 16 Sansarpur Terrace 61
6 Jeori(Kotla) 14 17 Smoli(Rohru) 62
7 Kangoo 15 18 Totu 63
8 Kunihar 16 6 Fibre Optic Details
9 Mandhala 17 I Proposed OFC Routing Diagram 64
10 Uperla Nangal 18 II Detail of OPGW Network 65
II 132kV Sub-Stations 19 III OLTE Detail 66
1 Amb 20 7 PLCC Details
2 Bagga 21 I PLCC Network Diagram 67
3 Bajaura 22 II PLCC Link/Channel Detail-48V 68
4 Barotiwala 23 III Exchange Detail 70
5 Bassi 24 IV SLDC Shimla MDF Detail 72
6 Bathri 25
7 Darlaghat 26
8 Dehan(Palampur) 27
9 Dehra 28
10 Gagret 29
11 Gaura 30
12 Gondpur(PoantaSahib) 31
13 Hamirpur-I 32
14 Jahoo 33
15 Jutogh 34
16 Kala-Amb 35
17 Kandrori 36
18 Kangra 37
19 Kurthala 38
20 Larji 39
21 Malana 40
22 Mandi 41
23 Rakkar(Una) 42
24 Solan 43
25 Tahliwala 44
III 66kV Sub-Stations 45
1 Akhanwali 46
2 Andhra 47
3 Anni 48
4 Batoli-Kalan 49
5 Davni 50
2

LIST OF EHV SUB-STATIONS/POWER-HOUSES IN HP (66 kV and above)


Name of Power House M/c Tap Changer 220V DC System 48V DC System
Date of
S.No. S/Stn/ Power Sub-Stn. Capacity Capacity & Generator Transformer Parameters Type
No of Normal Commissiong Battery Bank Battery Charger Battery Bank Battery Charger RTU Model Mode of Communication for RTU Remarks
Houses Transformer (GT) Taps Tap Capacity Status Rating Status Capacity Status Rating Status
I) 220 kV Sub-Stations/Power Houses
220/66 kV,100 MVA TFR. No.1 15% ON LTC 17 9b
220/66 kV,100 MVA TFR. No.2 14.80% ON LTC 17 9b
220/66 kV,100 MVA TFR. No.3 15.03% ON LTC 17 9b
220/33 KV,25/31.5 MVA TFR No. 04 12.06% ON LTC 17 7
Boost:2x40A Boost:2x60A Baddi to Kunihar on PLCC and Kunihar
1 Baddi 66/33 kV, 20MVA 12.07.2005 400Ah OK OK 400Ah OK OK Siemens
Float:2x40A Float:2x60A to Jutogh through OFC
66/11 KV 20MVA TFR 01 (66KV Side) 10% ON LTC 17 5
66/11 KV 20MVA TFR 02 (66KV Side) 10% ON LTC 17 5
66/11 KV 20MVA TFR 03 (66KV Side) 10% ON LTC 17 7
66/11 KV 20MVA TFR 04 (66KV Side) 9.93% ON LTC 17 7
M/c: 3x40 MW Bhabha to Kunihar on PLCC and Kunihar
2 Bhaba 220/11 kV, 1x10 MVA 20.05.1989 Alstom S-900
GT: 11/220 kV, 3x50 MVA to Jutogh through OFC
220/132 kV, 2x80/100 MVA M/c: 2x30 MW ON LTC 17 7
Boost:30A Boost:50A Giri to Kunihar on PLCC and Kunihar to
3 Girinagar 132/33 kV, 1x25/31.5 MVA GT:11/132 kV, 2x40 MVA ON LTC 17 7 16.04.1978 200Ah OK OK 400Ah OK OK Siemens
Float:10A Float:20A Jutogh through OFC
132/33 kV, 1x16/20 MVA ON LTC 17 7
Tap-1-11.87 %; Tap-13 B(N)-11.54 %; Tap 25-12.70 % 30V DC
Hamirpur-II 220/132 kV, 3x80/100 MVA(1-p) ON LTC 25 13b Boost:2x40A Boost:2x90A
4 Tap-1-12.35 %; Tap-13 (N)-12.12 %; Tap 25-12.80 % 01.08.2001 400Ah OK OK 600Ah OK OK Siemens Hamirpur-II to Jutogh through OFC System
(Mattansidh) Float:2x24A Float:2x60A
33/11 kV,2x3.15 MVA Tap-1-6.81 %; Tap-2 (N)-6.25 %; Tap 5-6.06 % 5 2 also in use
HV to LV-11.86% + IS tolerance at normal tap no. 13
220/132 kV,1x150 MVA HV to TV-32.40% + 20% tolerance at normal tap no. 13
LV to TV-19.32% + 20% tolerance
Jassore to Hamirpur-II on PLCC and
5 Jassore 220/132 kV,1x50/63 MVA 9.19 % normal tap 07.09.1985 400Ah OK 600Ah OK Siemens
Hamirpur-II to Jutogh through OFC
Tap-1-12.85 %; Tap-5 (N)-11.87 %; Tap 17-11.88 % ON LTC 17 5
220/33 kV, 2x25/31.5 MVA
Tap (N)-11.80 + 10%;
33/11 kV, 2x10 MVA Tap-1-8.44 %; Tap-5 (N)-8.30 %; Tap 17-8.00 % ON LTC 17 5
220/66 kV, 1x100MVA TRF(1-Ø BANK) Tap-1- 13.0 %; Tap-9- 12.5 %; Tap 17- 12.1 % ON LTC 17 9 1-Ø BANK
220/66 kV, 1x31.5 MVA Tap-1- 10.33 %; Tap-9- 9.94 %; Tap 17- 9.80 % ON LTC 17 9 Boost:40A Boost:7.7A Jeori to Kunihar on PLCC and Kunihar to
6 Jeori (Kotla) Mär.09 400Ah OK OK 200Ah OK OK Alstom S-900
66/22 kV, 1x31.5 MVA TRF Tap-1- 10.33 %; Tap-9- 9.94 %; Tap 17- 9.80 % ON LTC 17 5 Float:60A Float:9.1A Jutogh through OFC
66/22 kV, 1x10 MVA TRF Tap-1- 10.33 %; Tap-9- 9.94 %; Tap 17- 9.80 % ON LTC 17 5
220/132 kV,1x80/100 MVA Tap-Min-13.0692 %; Tap-13 (N)-13.0375 %; Tap Max-13.0062 %
Spare Tap- (N)-12.9432 %;
7 Kangoo 18.06.1999 Siemens Kangoo to Jutogh through OFC
Tap-Min-10.75 %; Tap-13 (N)-10.27 %; Tap Max-9.43%
132/33 kV, 2x25/31.5 MVA
Tap-Min-10.51 %; Tap-13 (N)-10.27 %; Tap Max-9.43%
R-Phase Y-Phase B-Phase
220/132kV,80/100MVA Tap-1-10.500 %; Tap-1-10.480 %; Tap-1-10.480 %;
ON LTC 17 5
Bank No.-I Tap-5-10.230 %; Tap-5-10.249 %; Tap-5-10.235 %;
Tap 17-10.100 % Tap 17-10.110 % Tap 17-10.130 %
Spare Tap-1- 10.500 %; Tap-5- 10.235 %; Tap 17- 10.130 % ON LTC 17 5
R-Phase Y-Phase B-Phase
Boost:
220/132kV,80/100MVA Tap-1-10.430 %; Tap-1-10.455 %; Tap-1-10.432 %;
ON LTC 17 5 40-60A Boost:60A
8 Kunihar Bank No. -II Tap-5-10.230 %; Tap-5-10.117 %; Tap-5-10.209 %; 17.01.1989 400Ah OK OK 400Ah OK OK Siemens Kunihar to Jutogh through OFC
Float: Float:60A
Tap 17-10.117 % Tap 17-10.025 % Tap 17-10.117 %
40-60A
R-Phase Y-Phase B-Phase
220/132kV,160/200MVA Tap-1-11.99 %; Tap-1-12.15 %; Tap-1-10.432 %;
ON LTC 17 9
Bank No. -III Tap-9-11.99 %; Tap-9-12.16 %; Tap-9-10.209 %;
Tap 17-12.53 % Tap 17-12.72 % Tap 17-12.71 %
Spare Tap-1- 12.09 %; Tap-5- 12.06 %; Tap 17- 12.53 % ON LTC 17 5
132/33 kV, 1x16 MVA Tap-1-10.409 %; Tap-5(N)-10.318 %; Tap 17-9.59% ON LTC 17 5
220/66 kV, 1x100 MVA ON LTC 17 9b Boost:2x40A
9 Mandhala 11.09.2015 400Ah OK OK 400Ah OK OK
66/11 kV, 4x20 MVA ON LTC 17 5 Float:2x40A
Uperla Nangal 220/66 kV 100 MVA TFR.1 (HV Side) T1-14.89%; T9b-14.55%; T17-13.98% ON LTC 17 9b Boost:2x60A Boost:2x40A Uperla Nangal to Kunihar on PLCC and ABB can be configured
10 02.07.2010 400Ah OK OK 400Ah OK OK ABB-560 CMU
(Nalagarh) 220/66 kV 100 MVA TFR.2 (HV Side) T1-15.05%; T9b-14.45%; T17-13.97% ON LTC 17 9b Float:2x60A Float:2x40A Kunihar to Jutogh through OFC for IEC-104 protocol
3

II) 132 kV Sub-Stations/Power Houses


Power House M/c
Name of Tap Changer 220V DC System 48V DC System
Capacity & Generator Date of
S.No. S/Stn/ Power Sub-Stn. Capacity Transformer Parameters RTU Model Mode of Communication for RTU Remarks
Houses
Transformer (GT) No of Normal Commissiong Battery Bank Battery Charger Battery Bank Battery Charger
Type
Capacity Taps Tap Capacity Status Rating Status Capacity Status Rating Status
132/33kV, 1x25/31.5MVA Tap-1-12.44 %; Tap-5 (N)-12.27 %; Tap 17-11.84 % ON LTC 17 5
Boost:60A Boost:60A
1 Amb 132/33kV, 1x16MVA Tap-1-10.45 %; Tap-5 (N)-10.27%; Tap 17-9.54 % ON LTC 17 5 31.05.1997 200Ah OK OK 400Ah OK OK
Float:40A Float:40A
33/11kV, 2x5MVA 7.15% Off LTC 5 3
Bagga to Kangoo on PLCC and Kangoo
2 Bagga Interlinking Sub-Station N.A. N.A. 25.11.2009 ABB-560 CMU
to Jutogh through OFC
Boost:30A Boost:30A Motorola ACE Bajaura to Kangoo on PLCC and Kangoo IEC-104 port can be
3 Bajaura 132/33 kV, 2x25/31.5 MVA ON LTC 17 5 Dez.98 200Ah OK OK 400Ah OK OK
Float:20A Float:15A 3600 to Jutogh through OFC configured in future
132/66 KV 25/31.5 MVA TFR No. 01 T1-11.20%, T5-11.668%, T17-12.40% ON LTC 17 5
132/66 KV 25/31.5MVA TFR No. 02 T1-11.16%, T5-11.592%, T17-12.30% ON LTC 17 5
132/66 KV 25/31.5MVA TFR No. 03 T1-12.512%, T5-12.422%, T17-11.478% ON LTC 17 5
Boost:2x40A Boost:2x60A Motorola ACE Barotiwala to Kunihar on PLCC and
4 Barotiwala 132/11 KV 25/31.5 MVA TFR No. 01 T1-12.303%, T5-12.273%, T17-11.572% ON LTC 17 5 19.05.89 400Ah OK OK 400Ah OK OK
Float:2x40A Float:2x60A 3600 Kunihar to Jutogh through OFC
132/11 KV 25/31.5 MVA TFR No. 02 T1-12.73%, T5-12.34%, T17-11.54% ON LTC 17 5
132/11 KV 16/20 MVA TFR No. 03 T1-10.23%, T5-09.73%, T17-9.19% ON LTC 17 5
132/11 KV 25/31.5 MVA TFR No. 04 T1-12.32%, T5-12.27%, T17-11.76% ON LTC 17 5

132/33 kV, 1x16 MVA M/c: 4x16.667 MW ON LTC 17 8 Motorola RTU as gateway for IEC-104
Non-
Boost:98A Boost:13A Motorola ACE Bassi to Hamirpur-II on PLCC and to IEC-101 conversion intalled at Bassi
5 Bassi 13.09.1970 200Ah Function OK 400Ah OK OK
Float:49A Float:13A 3600 Hamirpur-II to Jutogh through OFC and interfaced with SAS of Andritz
33/11 kV, 2x2.5 MVA GT:11/132, 4x20.4/22.5 MVA ON LTC 5 2 al
Hydro at Bassi
12.13% normal tap
132/33kV, 2x25/31.5MVA
12.07% normal tap
6 Bathri 12.05.1987
Tap-1-6.81 %; Tap-5 (N)-6.25 %; Tap 17-6.06 %
33/11kV, 2x1.6MVA

Boost:50A Boost:50A Motorola ACE Darlaghat to Kunihar on PLCC and IEC-104 port can be
7 Darlaghat 132/11 kV, 7.5 MVA ON LTC 17 7 23.06.2006 200Ah OK OK 100Ah OK Ageing
Float:50A Float:50A 3600 Kunihar to Jutogh through OFC configured in future
Tap-1-13.28 %; Tap-5 (N)-12.85 %; Tap 17-11.93 % ON LTC 17 5
132/33KV, 2x25/31.5 MVA Palampur to Bassi on PLCC, Hamirpur-I
Tap-1-13.02 %; Tap-5 (N)-12.65 %; Tap 17-11.77 % ON LTC 17 5 Boost:2x40A
8 Dehan, Palampur 19.12.1997 400Ah OK OK 100Ah OK OK Alstom S-900 to Hamirpur-II on PLCC and Hamirpur-II
7.37% ON LTC 17 7 Float:2x40A
33/11KV, 2x4 MVA to Jutogh through OFC
7.59% ON LTC 17 7
132/33kV, 2x16/20MVA 10.68% ON LTC 17 5 Boost:30A Boost:60A Dehra to Hamirpur-II on PLCC and
9 Dehra 21.12.1993 200Ah OK OK 400Ah OK OK Alstom S-900
33/11kV, 2x4MVA 7.28% Off LTC 5 2 Float:20A Float:40A Hamirpur-II to Jutogh through OFC
132/33kV, 25/31.5MVA Tap-1-13.13 %; Tap-5 (N)-12.78 %; Tap 17-11.85 % ON LTC 17 5 Boost:60A Boost:60A
10 Gagret Dez.09 400Ah OK OK 400Ah OK OK
132/11kV, 25/31.5 MVA Tap-1-13.26 %; Tap-5 (N)-12.42 %; Tap 17-10.26 % ON LTC 17 5 Float:40A Float:40A
Tap-1-10.09 %; Tap-5 (N)-9.76 %; Tap 17-9.06 %
132/33kV, 16MVA(1-p) Tap-1-10.16 %; Tap-5 (N)-9.86 %; Tap 17-9.18 % Float cum Float cum
11 Gaura ON LTC 17 5 09.09.2014 200Ah OK OK 400Ah OK OK
+1 as Stand-By 1-phase Tap-1-10.17 %; Tap-5 (N)-9.85 %; Tap 17-9.13 % Boost: 30A Boost: 60A
Tap-1-10.15 %; Tap-5 (N)-9.84 %; Tap 17-9.12 % 1-Ø BANK
Tap-1-13.17 %; Tap-5 (N)-12.84 %; Tap 11.92 % ON LTC 17 5
Gondpur 132/33 kV, 2x25/31.5 MVA Boost:2x40A Boost:2x40A Non
12 Tap-1-12.44 %; Tap-5 (N)-12.27 %; Tap 11.76 % ON LTC 17 5 21.10.2007 200Ah OK OK 200Ah OK
(Paonta Sahib) Float:2x20A Float:2x20A Functional
132/11 kV,1x25/31.5 MVA Tap-1-12.51 %; Tap-5 (N)-12.13 %; Tap 11.77 % ON LTC 17 5
Tap-1-12.44 %; Tap-5 (N)-12.20 %; Tap 17-11.76 % ON LTC 17 5
132/33KV, 2x25/31.5MVA 3-phase
Tap-1-12.41 %; Tap-5 (N)-12.33 %; Tap 17-11.76 % ON LTC 17 5 Boost:2x40A Boost:2x60A Hamirpur-I to Hamirpur-II on PLCC and
13 Hamirpur-I (Anu) 1979 200Ah OK OK 400Ah OK OK Alstom S-900
7.37% ON LTC 17 5 Float:2x40A Float:2x60A Hamirpur-II to Jutogh through OFC
33/11KV, 2x5 MVA
7.42% ON LTC 17 5
14 Jahoo 132/33 kV, 1x25/31.5 MVA ON LTC 17
132/66 KV 50/63 MVA TFR No. 01(1-p) Tap-1-9.972 %; Tap-5 (N)-9.794 %; Tap 9.547 % ON LTC 17 5
132/66 KV 25/31.5MVA TFR No. 02(3-p) Tap-1-12.49 %; Tap-5 (N)-12.23 %; Tap 11.94 % ON LTC 17 5 1-Ø BANK
Boost:50A Jutogh to CFE Modem through Twisted
15 Jutogh 132/33 KV 31.5MVA TFR No. 01(1-p) Tap-1-9.81 %; Tap-5 (N)-10.079 %; Tap 11.45 % ON LTC 17 5 17.05.1981 200Ah OK OK Being fed from SLDC System Alstom S-900 1-Ø BANK
Float:30A Pair Cable
132/33 KV 31.5MVA TFR No. 02(3-p) Tap-1-10.67 %; Tap-5 (N)-10.43 %; Tap 9.49 % ON LTC 17 5
66/33 KV 20 MVA TFR No. 01 Tap-1-10.25 %; Tap-5 (N)-10.80 %; Tap 9.45 % ON LTC 17 5
Tap-1-12.41 %; Tap-5 (N)-12.349 %; Tap 11.765 % ON LTC 17 5
132/33 kV, 3x25/31.5 MVA Tap-1-12.41 %; Tap-5 (N)-12.349 %; Tap 11.765 % ON LTC 17 5 Boost:2x30A Boost:2x30A Motorola ACE Kala Amb to Jutogh on GPRS and IEC-
16 Kala-Amb 30.11.2006 200Ah OK OK 200Ah OK OK
Tap-1-12.41 %; Tap-5 (N)-12.122 %; Tap 11.765 % ON LTC 17 5 Float:2x20A Float:2x20A 3600 101 converter installed at Jutogh
132/11 kV, 1x25/31.5 MVA Tap-1-12.70 %; Tap-5 (N)-12.33 %; Tap 11.43 % ON LTC 17 5
Tap-Min-10.45 %; Tap- (N)-10.27 %; Tap Max-9.55 % ON LTC 17
132/33kV, 3x16MVA Tap-Min-10.45 %; Tap- (N)-10.22 %; Tap Max-9.46 % ON LTC 17
17 Kandrori Tap-Min-10.36 %; Tap- (N)-10.18 %; Tap Max-9.45 % ON LTC 17 28.08.1996 200Ah OK 200Ah OK
7.15 Normal tap ON LTC 17
33/11kV , 2x6.3MVA
Tap-Min-7.79 %; Tap-(N)-7.15 %; Tap Max-6.94 % ON LTC 17
Tap-1-12.56 %; Tap-5 (N)-12.00 %; Tap 17-11.60 % ON LTC 17 5
132/33kV, 2x25/31.5MVA
Tap-1-12.32 %; Tap-5 (N)-12.13 %; Tap 17-11.76 % ON LTC 17 5 Kangra to Hamirpur-II on PLCC and
18 Kangra Feb.78 200Ah OK OK 400Ah OK OK Alstom S-900
ON LTC 17 Hamirpur-II to Jutogh through OFC
33/11kV, 2x10MVA Tap-Min-9.60 %; Tap- (N)-8.35 %; Tap Max-7.95 %
ON LTC 17
19 Kurthala 33/132 kV, 1x50/63 MVA ON LTC 17 30.08.2014 400Ah OK 400Ah OK
M/c: 3x42 MW ON LTC 17 Motorola ACE Larji to Kangoo on PLCC and Kangoo to Provisions already made for IEC-104
20 Larji 132/11 kV, 1x6.3 MVA 28.09.2006
GT:11/132 kV, 3x52 MVA ON LTC 17 3600 Jutogh through OFC communication
Boost:30A Malana to Kangoo on PLCC and Kangoo
21 Malana 33/132kV, 25/31.5MVA Tap-1-13.01 %; Tap-5 (N)-12.66 %; Tap 17-11.75 % ON LTC 17 5 11.08.2009 200Ah OK OK N.A. Alstom S-900
Float:20A to Jutogh through OFC
132/33kV, 16/20MVA Tap-1-9.936 %; Tap-5 (N)-9.842 %; Tap 17-9.148 % ON LTC 17 5
132/33kV, 25/31.5MVA Tap-1-13.03 %; Tap-5 (N)-12.67 %; Tap 17-11.73 % ON LTC 17 5
Boost:30A Boost:60A Mandi to Kangoo on PLCC and Kangoo
22 Mandi (Bijni) 66/33kV, 1x20MVA Tap-1-1017 %; Tap-5 (N)-9.93 %; Tap 17-9.33 % ON LTC 17 5 26.10.1979 200Ah OK OK 400Ah OK OK Alstom S-900
Float:20A Float:40A to Jutogh through OFC
6.25% Off LTC 5 2
33/11 kV, 2x3.15 MVA
Off LTC 5 2
Tap-1-12.32 %; Tap-5 (N)-12.13 %; Tap 17-11.77 %
132/33kV, 2x25/31.5MVA ON LTC 17 5
12.28%
30V DC
8.50% Boost:60A Boost:60A
23 Rakkar (Una) 66/33kV, 2x10MVA Off LTC 5 2 30.12.1985 200Ah OK OK 400Ah OK OK System
Float:40A Float:40A
also in use
66/11kV, 1x20MVA Tap-1-10.25 %; Tap-5 (N)-9.93 %; Tap 17-9.18 % Off LTC 5 2
33/11kV, 2x6.3MVA Tap-Lowest-7.79 %; Tap-(N)-7.15 %; Tap Highest-6.94 % Off LTC 5 2
132/66 KV, 1x25/31.5 MVA Tap-1-12.32 %; Tap-5 (N)-12.20 %; Tap 11.69 % ON LTC 17 5
Tap-1-12.534 %; Tap-5 (N)-12.174 %; Tap 11.088 % ON LTC 17 5
Solan to Kunihar on PLCC and Kunihar
24 Solan 132/33 KV, 1x50MVA(1-p) Tap-1-12.192 %; Tap-5 (N)-12.046 %; Tap 11.914 % ON LTC 17 5 31.08.1993 Alstom S-900
to Jutogh through OFC
+1 as Stand-by Tap-1-12.406 %; Tap-5 (N)-12.050 %; Tap 11.054 % ON LTC 17 5
Tap-1-12.471 %; Tap-5 (N)-12.124 %; Tap 11.101 % ON LTC 17 5

Tap-1-13.00 %; Tap-5 (N)-12.50 %; Tap 17-12.00 %(Guaranteed ON LTC 17 5 Boost:30A Boost:60A


25 Tahliwala 132/33kV, 2x25/31.5MVA 25.08.2014 200Ah OK OK 400Ah OK OK
Tap-1-12.48 %; Tap-5 (N)-12.24 %; Tap 17-11.69 %(Major) Float:20A Float:40A
ON LTC 17 5
4

III) 66 kV Sub-Stations/Power Houses


Power House M/c
Name of Tap Changer 220V DC System 48V DC System
Capacity & Generator Date of
S.No. S/Stn/ Power Sub-Stn. Capacity Transformer Parameters RTU Model Mode of Communication for RTU Remarks
Houses
Transformer (GT) No of Normal Commissiong Battery Bank Battery Charger Battery Bank Battery Charger
Type
Capacity Taps Tap Capacity Status Rating Status Capacity Status Rating Status
66/33 KV 2x20MVA 10% ON LTC 17 7 Boost:2x40A Boost:2x60A
1 Akanwali 24.10.2007 200Ah OK OK 400Ah OK OK
66/11 KV 20MVA 10% ON LTC 17 7 Float:2x40A Float:2x60A
M/c: 3x5.65 MW ON LTC 17
GT:11/66 kV, 2x6.67 MVA ON LTC 17 Andhra to Kunihar on PLCC and Kunihar
2 Andhra 66/22 kV, 1x6.67 MVA 29.09.1987 Alstom S-900
GT:11/22 kV, 1x6.67 MVA ON LTC 17 to Jutogh through OFC
ON LTC 17
Boost:30A
3 Ani (Nagan) 66/22 kV, 2x10 MVA ON LTC 17 5 15.04.2015 200Ah OK OK N.A.
Float:30A
Boost:2x20A Boost:2x20A
4 Batoli-Kalan 66/11 kV, 2x20 MVA ON LTC 17 7 08.06.2015 200Ah OK OK 200Ah OK OK
Float:2x20A Float:2x20A
66/11 KV 20MVA TFR No. 01 T1-10.5%; T5-10.0%; T17-9.5% ON LTC 17 5 Boost:2x20A Boost:2x20A Motorola ACE
5 Davni 03.05.2014 200Ah OK OK 200Ah OK OK Davni to Jutogh through GPRS Proposed Unmanned
66/11 KV 20MVA TFR No. 02 T1-10.5%; T5-10.0%; T17-9.5% ON LTC 17 5 Float:2x20A Float:2x20A 3600
Substation
M/c: 2x11.25 MW ON LTC 17 Communication link is yet to
6 Ghanvi 16.10.2000 Siemens
GT:11/66 kV, 2x13.75 MVA ON LTC 17 be established
Boost:30A Boost:40A
7 Golthai 66/11kV, 6.3MVA Tap-1-8.508 %; Tap-5 (N)-8.336%; Tap 17-8.235 % ON LTC 17 5 31.03.2006 200Ah OK OK 400Ah OK OK
Float:20A Float:55A
66/22 KV 6.3MVA TFR No. 01 T1-8.17%; T5-8.37%; T17-8.62% ON LTC 17 5
Boost:50A
8 Gumma 66/22 KV 10MVA TFR No. 02 T1-9.33%; T5-8.51%; T17-8.51% ON LTC 17 5 12.07.1983 200Ah OK OK N.A.
Float:30A
66/22 KV 6.3MVA TFR No. 03 T1-8.35%; T5-8.50%; T17-8.82% ON LTC 17 5

9 Khotkhai (Hulli) 66/22 kV, 2x10 MVA ON LTC 17 7 22.12.2008 200Ah OK 40A OK N.A.

66/22 kV, 1x10 MVA T1-8.05%; T5-8.35%; T17-8.00% ON LTC 17 5 Boost:30A Boost:30A
10 Kumarsain Jul.84 200Ah OK OK 200Ah OK OK
66/22 kV, 1x6.3 MVA T1-8.35%; T5-8.50%; T17-8.82% ON LTC 17 5 Float:20A Float:20A
66/11 KV 20MVA TFR No. 01 T1-10.39%; T5-9.93%; T17-9.36% ON LTC 17 5
66/11 KV 20MVA TFR No. 02 T1-10.39%; T5-9.93%; T17-9.36% ON LTC 17 5
66/33 KV 20MVA TFR No. 03 T1-10.24%; T5-9.84%; T17-9.18% ON LTC 17 5 Boost:50A Boost:30A
11 Nalagarh 26.12.2005 200Ah OK OK 400Ah OK OK
66/33 KV 20MVA TFR No. 04 T1-10.25%; T5-9.85%; T17-9.09% ON LTC 17 5 Float:50A Float:30A
66/33 KV 10MVA TFR No. 05 8.50% ON LTC 17 5
33/11 kV, 1x3.15 MVA
66/22 kV, 1x10 MVA TFR No. 01 T1-8.11%; T5-8.36%; T17-9.41% Off LTC 17 5
12 Nathpa 31.01.2009 200Ah OK 20A OK 200Ah OK 16A OK
66/22 kV, 1x20 MVA TFR No. 02 T1-10.2%; T5-9.88%; T17-9.24% ON LTC 17 5
66/22 kV, 1x10 MVA M/c: 2x 250 kW+4x500 kW ON LTC 17
13 Nogli GT:0.4/22 kV, 2x300 kVA ON LTC 17 Dez.63
GT: 0.4/22 kV, 2x1250 kVA ON LTC 17
Non-
66/11kV, 1x20MVA, TR-1 Tap-1-10.13 %; Tap-5 (N)-9.955 %; Tap 17-9.147 % ON LTC 17 5 Boost:30A Boost:30A Non-
14 Parwanoo 02.11.2001 200Ah OK OK 200Ah Functiona
66/11kV, 1x20MVA, TR-2 Tap-1-10.390 %; Tap-5 (N)-10.111 %; Tap 17-9.366 % ON LTC 17 5 Float:20A Float:20A Functional
l
66/11 kV, 2x6.3 MVA ON LTC 17 8 Boost:40A
15 Sainj 21.11.2007 200Ah OK OK N.A.
66/22 kV, 1x6.3 MVA ON LTC 17 8 Float:24A
7.73% Off LTC 5 2 Boost:30A Boost:30A
16 Sansarpur Terrace 66/11kV, 2x10MVA 08.10.1990 200Ah OK OK 200Ah OK OK
7.87% Off LTC 5 2 Float:20A Float:20A
66/22 kV, 1x10 MVA T1-8.37%; T5-8.33%; T17-7.04% ON LTC 17 5 Boost:30A Boost:15A
17 Smoli (Rohru) 17.12.2008 200Ah OK OK 200Ah OK OK
66/22 kV, 1x16 MVA (1-p) 10.15% ON LTC 17 5 Float:20A Float:10A
66/11 kV, 20 MVA ON LTC 17 5 Boost:60A
18 Totu 16.07.1995 200Ah OK OK N.A.
66/11 kV, 3x6.3MVA(to be dismantled) Off LTC 5 2 Float:40A

ABSTRACT
S.No. Voltage level No. of Sub-Station/Power Houses
1 220 kV 10
2 132 kV 25
3 66 kV 18
Total (66 & above) 53

Sub-Stations/Power Houses (IPPs):


Power House M/c
Name of Tap Changer 220V DC System 48V DC System
Capacity & Generator Date of
S.No. S/Stn/ Power Sub-Stn. Capacity Transformer Parameters RTU Model Mode of Communication for RTU Remarks
Houses
Transformer (GT) No of Normal Commissiong Battery Bank Battery Charger Battery Bank Battery Charger
Type
Capacity Taps Tap Capacity Status Rating Status Capacity Status Rating Status
M/c: 2x43 MW
1 Malana 05.07.2001
GT: 11/132 kV, 2x58 MVA
M/c: 3x100 MW Motorola ACE IEC-104 port can be
2 Baspa 24.05.2003 Baspa to Jutogh on GPRS
3600 configured in future
GT: 13.8/400 kV, 3x123 MVA
5

DETAIL/STATUS OF CAPACITOR BANKS INSTALLED IN HPSEBL NETWORK(66kV & Above)


Power House M/c Capacity & Voltage Level at Power House M/c Capacity & Voltage Level at
Name of S/Stn/ Capacitor Bank Capacitor Bank
S.No. Sub-Stn. Capacity Generator Transformer (GT) which Capacitor Status Remarks S.No. Name of S/Stn/ Power Houses Sub-Stn. Capacity Generator Transformer (GT) which Capacitor Status Remarks
Power Houses Capacity Capacity
Capacity Bank Installed Capacity Bank Installed
I) 220 kV Sub-Stations/Power Houses II) 132 kV Sub-Stations/Power Houses
220/66 kV,3x80/100 MVA 10 MVAR Functional 132/33 kV, 3x25/31.5 MVA 33kV 4x3.6 MVAR All Non-Functional
66kV 16 Kala-Amb
220/33 kV, 1x25/31.5 MVA 2x14.4 MVAR Functional 132/11 kV, 1x25/31.5 MVA 11kV 2x2.5 MVAR All Functional
1 Baddi
66/33 kV,1x20 MVA 33kV 2x3.6 MVAR Functional 132/33 kV, 3x16 MVA 33kV 2x3.6 MVAR
17 Kandrori
66/11 kV, 4x20 MVA 11kV 2x3 MVAR Functional 33/11 kV,2x6.3 MVA
M/c: 3x40 MW 132/33 kV, 2x25/31.5 MVA 11kV 1.2+1.8 MVAR
2 Bhaba 220/11 kV, 1x10 MVA 18 Kangra
GT: 11/220 kV, 3x50 MVA 33/11 kV,2x10 MVA
220/132 kV, 2x80/100 MVA M/c: 2x30 MW 19 Kurthala 33/132 kV, 1x50/63 MVA
3 Girinagar 132/33 kV, 1x25/31.5 MVA GT:11/132 kV, 2x40 MVA 33kV 4x2.5 MVAR All Functional M/c: 3x42 MW
20 Larji 132/11 kV, 1x6.3 MVA
132/33 kV, 1x16/20 MVA GT:11/132 kV, 3x52 MVA
Hamirpur-II 220/132 kV, 3x80/100 MVA 21 Malana 33/132 kV, 1x25/31.5 MVA
4
(Mattansidh) 33/11 kV,2x3.15 MVA 132/33 kV, 1x16 MVA 33kV 2x3.6 MVAR Both Functional
220/132 kV,1x150 MVA 33kV 2x3.6 MVAR 132/33 kV, 1x25/31.5 MVA
22 Mandi (Bijni)
220/132 kV,1x50/63 MVA 3 MVAR 66/33 kV,1x20 MVA
5 Jassore
220/33 kV, 2x25/31.5 MVA 11kV 33/11 kV, 2x3.15 MVA
1.8+1.2 MVAR
33/11 kV, 2x10 MVA 132/33 kV, 2x25/31.5 MVA 33kV 2x3.6 MVAR Both Functional
220/66 kV, 1x100 MVA 1-Ø BANK 66/33 kV, 2x10 MVA 11kV 1.2+1.8 MVAR Both Functional
23 Rakkar (Una)
220/66 kV, 1x31.5 MVA 66/11 kV, 1x20 MVA
6 Jeori (Kotla) 66kV 2x7.2 MVAR Non-Functional
66/22 kV,1x10 MVA 33/11 kV, 2x6.3 MVA
66/22 kV,1x31.5 MVA 132/66 kV, 1x25/31.5 MVA 11kV 2x2.5 MVAR Both Functional
24 Solan
220/132 kV,1x80/100 MVA 132/33 kV,1x50 MVA 1-Ø BANK
7 Kangoo 33kV 2x3.6 MVAR
132/33 kV, 2x25/31.5 MVA 25 Tahliwala 132/33 kV, 2x25/31.5 MVA
220/132 kV, 2x80/100 MVA
220/132 kV, 1x160/200 MVA III) 66 kV Sub-Stations/Power Houses
8 Kunihar 33kV 2x2.5 kVAR Both Functional Power House M/c Capacity & Voltage Level at
Capacitor Bank
132/33 kV, 1x16 MVA S.No. Name of S/Stn/ Power Houses Sub-Stn. Capacity Generator Transformer (GT) which Capacitor Status Remarks
Capacity
Capacity Bank Installed
220/66 kV, 1x100 MVA 66/33 kV, 2x20 MVA
9 Mandhala 1 Akanwali
66/11 kV, 4x20 MVA 66/11 kV,1x20 MVA
Uperla Nangal 220/66 kV, 2x100MVA M/c: 3x5.65 MW
10
(Nalagarh) 220/33 kV, 1x25/31.5 MVA GT:11/66 kV, 2x6.67 MVA
2 Andhra 66/22 kV, 1x6.67 MVA GT:11/22 kV, 1x6.67 MVA
II) 132 kV Sub-Stations/Power Houses
Power House M/c Capacity & Voltage Level at
Name of S/Stn/ Capacitor Bank
S.No. Sub-Stn. Capacity Generator Transformer (GT) which Capacitor Status Remarks 3 Ani 66/22 kV, 2x10 MVA
Power Houses Capacity
Capacity Bank Installed
132/33 kV, 1x25/31.5 MVA 33kV 2x2.5 MVAR Functional 4 Batoli-Kalan 66/11 kV, 2x20 MVA
1 Amb 132/33 kV, 1x16 MVA 11kV 1.2+1.8 MVAR Functional 5 Davni 66/11 kV,2x20 MVA
33/11 kV,2x5 MVA M/c: 2x11.25 MW
6 Ghanvi
GT:11/66 kV, 2x13.75 MVA
2 Bagga Interlinking Sub-Station
7 Golthai 66/11 kV, 1x6.3 MVA
Functional
3 Bajaura 132/33 kV, 2x25/31.5 MVA 33kV 2x3.6 MVAR
Functional 66/22 kV, 2x6.3 MVA 22kV 2x2.6 MVAR Both Non-Functional
8 Gumma
132/66 kV, 3x31.5 MVA 66kV 10 MVAR Functional 66/22 kV, 1x10 MVA
2 Banks Functional,
4 Barotiwala 132/11 kV,1x16 MVA 3X3 MVAR 9 Khotkhai (Hulli) 66/22 kV, 2x10 MVA 22kV 2x2.4 MVAR Both Non-Functional
11kV 1 Bank Non-Functional
132/11 kV, 3x25/31.5 MVA 5 MVAR Non-Functional 66/22 kV, 1x10 MVA 1 Bank Functional,
10 Kumarsain 22kV 2x2.4 MVAR
132/33 kV, 1x16 MVA M/c: 4x16.667 MW(1-p) 11kV 0.6 MVAR Functional 66/22 kV, 1x6.3 MVA 1 Bank Non-Functional
5 Bassi
33/11 kV,2x2.5 MVA GT:11/132, 4x20.4/22.5 MVA 66/33 kV, 2x20 MVA 1 Bank Functional,
33kV 2x7.2 MVAR
132/33 kV, 2x25/31.5 MVA 33kV 2x3.6 MVAR 66/33 kV, 10 MVA 1 Bank Non-Functional
6 Bathri 11 Nalagarh
33/11 kV, 2x1.6 MVA 66/11 kV,2x20 MVA 1 Bank Functional,
11kV 2x(1.2+1.8)MVAR
7 Darlaghat 132/11 kV, 7.5 MVA 33/11 kV, 1x3.15 MVA 1 Bank Non-Functional
132/33 kV, 2x25/31.5 MVA 33kV 2x2.5 MVAR Non-Functional 66/22 kV, 1x10 MVA 22kV 2x2.4 MVAR Both Functional
8 Dehan, Palampur 12 Nathpa
33/11 kV,2x4 MVA 11kV 1.2+1.8 MVAR Functional 66/22 kV, 1x20 MVA
132/33 kV, 2x16/20 MVA 33kV 2x3.6 MVAR Functional 66/22 kV, 1x10 MVA M/c: 2x 250 kW+4x500 kW 22kV 2x2.4 MVAR
9 Dehra 1 Bank Functional,
33/11 kV,2x4 MVA 11kV 2x3 MVAR 13 Nogli GT:0.4/22 kV, 2x300 kVA
1 Bank Non-Functional
132/33 kV, 1x25/31.5 MVA 11kV 2x2.5 MVAR Functional GT: 0.4/22 kV, 2x1250 kVA
10 Gagret
132/11 kV, 1x25/31.5 MVA 22kV 4x2 MVAR 2 Banks Functional,
14 Parwanoo 66/11 kV, 2x20 MVA
11 Gaura 132/33 kV, 1x16 MVA 1-Ø BANK 2 Banks Non-
1 Bank Functional,
Gondpur 132/33 kV, 2x25/31.5 MVA 33kV 4x3.6 MVAR 66/11 kV, 2x6.3 MVA
12 1 Bank Non-Functional 15 Sainj
(Paonta Sahib)
132/11 kV,1x25/31.5 MVA 11kV 2x3.6 MVAR Functional 66/22 kV, 1x6.3 MVA
132/33 kV, 2x25/31.5 MVA 33kV 2x3.6 MVAR Functional 16 Sansarpur Terrace 66/11 kV, 2x10 MVA
13 Hamirpur-I (Anu)
33/11 kV,2x5 MVA 66/22 kV, 1x16 MVA 22kV 2x2.4 MVAR Both Non-Functional
17 Smoli (Rohru)
14 Jahoo 132/33 kV, 1x25/31.5 MVA 66/22 kV, 1x10 MVA
132/66 kV, 1x25/31.5 MVA 33kV 2x3.6 MVAR Both Non-Functional 66/11 kV, 1x20 MVA
18 Totu
132/66 kV, 1x50/63 MVA 1-Ø BANK 66/11 kV, 3x6.3 MVA To be dismantled
15 Jutogh 132/33kV, 1x31.5 MVA 1-Ø BANK
132/33 kV, 1x25/31.5 MVA
66/33 kV, 1x20MVA
SINGLE LINE NETWORK DIAGRAM OF HPSEBL (66KV and above) AS ON: 11-05-2016 6

JOINER TARELA-I TARELA-II TEJUS SJVNL BASPA ANDHRA


MALANA GHANVI-II NALAGARH (1500 MW) (300 MW) (16.95 MW)
(5MW) (5MW) (5MW) (12 MW) JOGNI
GAJ KHAULI SHANAN BASSI BINWA BANER CHULLA THRIOT (86 MW) LARJI BHABA GHANVI-I (10 MW) (PGCIL) NOGLI GIRI KHODRI(UA)
(10.5 MW) (12 MW) (110 MW) (60 MW) (6 MW) (12 MW) (100 MW) (4.5 MW) (126 MW) (120 MW) (22.5 MW) (2.5 MW) ( MW) (60 MW)
BAIRA(NHPC) E13 E14
(190 MW) KULHAL(UA)

6.6 E16
C42 C13
6.6 kV Visco D44
Andhra-2 C17 GIRI
kV KANGRA(PSEB) C19 NOGLI

D10 D12 D14 MALANA E8 Hisar ROHROO C18


E17 E18
Nathpa (SAMOLI) C16 D41 D42 D43
Pathankot D11 D37 UPERLA NANGAL Abdullapur Jeori
KURTHALA
JEORI
C1 D13 E19 NALAGARH (PGCIL) Jagadhari Poanta
D56 D57 C15
D39 D38 JP AMBUJA Sahib
KANGRA(HP) PALAMPUR V/man
BATHRI D9 DEHRA Mandi D52 C21 C20 KALA-AMB
E1 Tal (PG) BAJAURA UPERLA NANGAL C41 C40 GPIL
D5 D6 HAMIRPUR-I (ANU) D40 D50 D51
D2 E7 E9
D17 C31 C32 NALAGARH (HP) C22 KUMARSAIN
PONG-BBMB E4 E5 MANDI (BIJNI)
E2 JASSORE AMB D15 D16
360MW C18 C3 C35 C14 HM steel JBRolling
E23 C23
Chohal-PSEB BADDI
D3 D48 D7 D8 HAMIRPUR-II(HP) ANNI
E3 D4 D46 D47 Nogli AKHANWALI
D53 Kunihar
Thein-PSEB C30 C5
Gagret D36 D35 C4 C37 C24
Pong D54 Mandala C27
HAMIRPUR-II PNG Birla
E20 E21 C33 D30 D29 GUMMA
KUNIHAR Alkem Davni C39
33 kV D1 JASSORE C1 JUTOG
D45 D18 D19 Batoli-Kalan
Dasuya Shanan E11 BADDI C28
E10 E22
Kandrori C12
E12 Vardhman
RAKKAR JAHOO C2 C7
C25 D32 C36
Jallandhar Panchkula SAINJ
D55 D61 BAROTIWALA
Sansarpur Terrace D31 JUTOGH
RAKKAR D59 C29
(UNA) KUNIHAR TOTU
KANGOO Inox
Tahliwala C11 Hulli
GOLTHAI BAROTIWALA PARWANOO
D29 D30 C38
C44 C43 C8
SOLAN C6
C26 Cadbury
SPS Suraj Pinjore
C34 KANGOO Jutogh C9
Ind. Ind. GAURA
BHAKHRA-1200MW D25 D27 D28 C10
E15
D22
Rauri D24 SOLAN
E6
DEHAR Dehar D34 D58
D23 D23A D26
33 KV BILASPUR
D33
BAGGA DARLAGHAT
D20 D21
D60 D49
F (400 kV)
ACC Jaypee Cement SUB-STNS./POWER HOUSES(IPPs) E (220 kV)
Ambuja Cement
GANGUWAL 1.Malana D (132 kV)
2.Baspa
132/33 kV,1x16 MVA M/c:3x100 MW C (66 kV)
M/c:2x43 MW GT:13.8/400kV,3x123MVA DOUBLE BUS
GT:11/132kV, 2x58MVA
SINGLE BUS

Line Length Line Length Line Length Line Length Line Length Line Length 220 kV SUB-STNS./POWER HOUSES 9. Mandhala 9. Dehra 20. Larji 7. Golthai
220/66kV, 1x100 MVA 132/33 kV, 2x16/20 MVA 132/11 kV, 1x6.3 MVA 66/11 kV,1x6.3 MVA
code km. code km. code km. code km. code km. code km. 1.Baddi
33/11 kV,2x4 MVA M/c: 3x42 MW
220/66 kV,3x80/100 MVA 66/11kV, 4x20 MVA 8. Gumma
E1 57.00 D1 024.234 D22 002.90 D42 31.960 C1 35.00 C22 01.545 10. Gagret GT:11/132 kV, 3x52 MVA
220/33 kV, 1x25/31.5 MVA 66/22 kV,2x6.3 MVA,1x10 MVA
E2 040.00 D2 038.390 D23 016.205 D43 16.390 C2 03.820 C23 016.739 66/33 kV,1x20 MVA 10.Uparla Nangal(Nalagarh) 132/33 kV, 1x25/31.5 MVA 21.Malana 33/132 kV, 1x25/31.5 MVA
132/11 kV, 1x25/31.5 MVA 9.Khotkhai(Hulli)
E3 025.602 D3 060.639 D23A 013.563 D44 017.60 C3 14.507 C24 40.304 66/11 kV, 4x20 MVA 220/66 kV, 2x100 MVA 22. Mandi (Bijni) 66/22 kV, 2x10 MVA
2. Bhaba 220/33 kV, 1x25/31.5 MVA 11.Gaura 132/33 kV, 1x16 MVA,1x25/31.5 MVA
E4 9.50 D4 060.639 D24 046.00 D45 031.330 C4 0.425 C25 006.40 10. Kumarsain
9.50 D5 C26
220/11 kV,1x10 MVA Mc:3x40 MW 132kV SUB-STNS/POWER HOUSES 132/33 kV,1x16 MVA(1-Ø) 66/33 kV,1x20 MVA 66/22 kV, 1x6.3MVA,1x10MVA
E5 027.492 D25 047.039 D46 055.83 C5 1.740 15.980 GT:11/220 kV,3x50MVA 33/11 kV, 2x3.15 MVA
1. Amb 12.Gondpur(Poanta) 11. Nalagarh
E6 03.177 D6 027.492 D26 022.301 D47 055.83 C6 017.210 C27 10.172 3. Girinagar 132/33 kV, 2x25/31.5 MVA 23. Una (Rakkar)
132/33 kV, 1x25/31.5 MVA 66/33 kV, 2x20 MVA,10 MVA
220/132 kV, 2x80/100 MVA 132/33 kV, 1x16 MVA 132/11 kV,1x25/31.5 MVA 132/33 kV, 2x25/31.5 MVA 66/11 kV,2x20 MVA
E7 130.90 D7 043.123 D27 022.00 D48 7.80 C7 03.256 C28 21.029 66/33 kV, 2x10 MVA
132/33 kV, 1x25/31.5 MVA 33/11 kV,2x5 MVA 13. Hamirpur-I (Anu) 33/11 kV, 1x3.15 MVA
E8 D8 043.123 D28 020.00 D49 1.918 C8 008.230 C29 009.992 132/33 kV, 1x16/20 MVA 66/11 kV, 1x20 MVA
024.70 132/33 kV, 2x25/31.5 MVA
M/c: 2x30 MW 2.Bagga Interlinking S/Stn 33/11 kV, 2x6.3 MVA 12. Nathpa
E9 106.72 D9 029.935 D29 015.34 D50 0.080 C9 018.50 C30 02.40 33/11 kV,2x5 MVA
GT:11/132 kV, 2x40 MVA 24. Solan 66/22kV,1x10MVA,1x20MVA
3. Bajaura
E10 67.5 D10 00.135 D30 016.00 D51 0.043 C10 025.27 C31 3.510 132/33 kV, 2x25/31.5 MVA 14. Jutogh 132/66 kV,1x25/31.5 MVA 13. Nogli
4. Hamirpur-II (Mattansidh) 132/66kV,25/31.5MVA,50/63MVA 132/33 kV,1x50 MVA 66/22 kV, 1x10 MVA
E11 031.091 D11 005.25 D31 026.03 D52 16.94 C11 01.555 C32 3.510 220/132 kV, 3x80/100 MVA 4. Barotiwala 132/33kV,31.5MVA,25/31.5MVA M/c: 2x250kW + 4x500kW
E12 042.764 D12 005.25 D32 026.03 D53 35.699 C12 015.49 C33 33/11kV, 2x3.15 MVA 132/66 kV, 3x25/31.5 MVA 66/33kV,1x20MVA 25.Tahliwala132/33 kV,2x25/31.5MVA
02.00 GT:0.4/22 kV, 2x300 kVA
132/11 kV,1x16 MVA 66 kV SUB-STNS./POWER HOUSES GT: 0.4/22 kV, 2x1250 kVA
E13 035.06 D13 049.75 D33 063.99 D54 35.699 C13 007.30 C34 1.813 5.Jassore 132/11 kV, 3x25/31.5 MVA 15. Jahoo
220/132 kV,1x150MVA,1x50/63MVA 132/33 kV,1x25/31.5 MVA 1. Akanwali
E14 035.06 D14 032.00 D34 20.662 D55 16.949 C14 017.3 C35 014.507 220/33 kV, 2x25/31.5 MVA 5. Bassi 66/33 kV, 2x20 MVA 14. Parwanoo
D56 45.510 132/33 kV, 1x16 MVA 66/11 kV,1x20 MVA 66/11 kV, 2x20 MVA
E15 024.115 D15 004.95 D35 060.70 C15 025.694 C36 019.995 16. Kala-Amb
6.Jeori (Kotla) 33/11 kV,2x2.5 MVA 132/33 kV, 3x25/31.5 MVA 2. Andhraa
E16 002.65 D16 004.95 D36 073.199 D57 45.510 C16 34.408 C37 002.11 220/66 kV, 1x100 MVA(1-Ø BANK) M/c: 4x16.667 MW 66/22 kV, 1x6.67 MVA 15. Sainj
132/11 kV, 1x25/31.5 MVA 66/11 kV, 2x6.3 MVA
003.569 D58 60.491 C38 0.72 220/66 kV, 1x31.5 MVA GT:11/132, 4x20.4/22.5 MVA M/c: 3x5.65 MW
E17 D17 076.00 D37 020.196 C17 013.10 66/22 kV,1x10 MVA,1x31.5 MVA 66/22 kV, 1x6.3 MVA
17. Kandrori GT:11/66 kV, 2x6.67 MVA
E18 003.569 D18 042.139 D38 024.11 D59 1.00 C18 024.71 C39 010.172 6. Bathri GT:11/22 kV, 1x6.67 MVA
7.Kangoo 132/33 kV, 2x25/31.5 MVA 132/33 kV, 3x16 MVA 16. Sansarpur Terrace
E19 0.300 D19 24.836 D39 024.11 D60 C19 26.270 C40 09.837 220/132 kV,1x80/100 MVA 33/11 kV,2x1.6 MVA 33/11 kV,2x6.3 MVA 66/11 kV, 2x10 MVA
3. Anni 66/22 kV,2x10MVA
132/33 kV, 2x25/31.5 MVA
E20 7.80 D20 001.65 D40 020.00 D61 29.403 C20 06.952 C41 21.078 7. Darlaghat 18.Kangra 17. Samauli(Rohru)
8. Kunihar 4. Batoli Kalan 66/11 kV,2x20MVA
E21 C21 5.750 C42 3.280 132/11 kV, 7.5 MVA 132/33 kV, 2x25/31.5 MVA 66/22kV, 1x16MVA,1x10MVA
24.562 D21 001.65 D41 050.00 220/132 kV, 2x80/100 MVA 33/11 kV,2x10 MVA
8. Dehan(Palampur) 5. Davni 66/11 kV,2x20MVA
E22 0.804 C43 0.260 220/132 kV, 1x160/200 MVA 18. Totu
132/33 kV, 1x16 MVA 132/33 kV, 2x25/31.5 MVA 19.Kurthala 6.Ghanvi M/c: 2x11.25 MW
30.253 C44 0.400 33/11 kV,2x4 MVA 33/132 kV,1x50/63MVA GT:11/66 kV, 2x13.75 MVA 66/11 kV,1x10MVA,3x6.3 MVA
E23
7

EHV LINES DETAIL


LINE LENGTH CIRCUIT LENGTH TYPE OF CONDUCTOR LINE LENGTH CIRCUIT LENGTH TYPE OF CONDUCTOR
CODE LINE NAME TYPE CODE LINE NAME TYPE
(in kms) (in kms) CONDUCTOR USED SIZE (in kms) (in kms) CONDUCTOR USED SIZE
E1 Jassore-Baira-Siul(NHPC) 57.000 Zebra 54/7/3.18mm D42 Giri-Kala Amb Single Circuit Line 31.960 31.960 Panther 30/7/3.00mm
E2 Jassore-Pong(BBMB) 40.000 Zebra 54/7/3.18mm D43 Giri-Poanta Sahib Single Circuit Line 16.390 16.390 Panther 30/7/3.00mm
E3 Jassore-Thein(PSEB) 25.602 Zebra 54/7/3.18mm D44 Giri-Kulhal Single Circuit Line 17.600 17.600 Panther 30/7/3.00mm
E4 Hamirpur-II-Tal(PGCIL)-1 Double Circuit Line 9.500 19 Zebra 54/7/3.18mm D45 Una(Rakkar)-Amb Single Circuit Line 31.330 31.330 Panther 30/7/3.00mm
E5 Hamirpur-II-Tal(PGCIL)-2 Double Circuit Line 9.500 19 Zebra 54/7/3.18mm D46 Kangoo-Larji-1 55.830 Panther 30/7/3.00mm
E6 Kangoo-Dehar Single Circuit Line 3.177 3.177 Zebra 54/7/3.18mm D47 Kangoo-Larji-2 55.830 Panther 30/7/3.00mm
E7 Kunihar-Bhabha Double Circuit Line 130.900 261.8 Zebra 54/7/3.18mm D48 Amb-Gagret Single Circuit Line 7.800 7.800 Panther 30/7/3.00mm
E8 Bhabha-Jeori Double Circuit Line 24.700 49.4 Zebra 54/7/3.18mm D49 Darlaghat-Ambuja Cement Single Circuit Line 1.918 1.918 Panther 30/7/3.00mm
E9 Jeori-Kunihar Double Circuit Line 106.720 213.44 Zebra 54/7/3.18mm D50 Kala Amb-HM Steel Single Circuit Line 0.080 0.080 Panther 30/7/3.00mm
E10 Kunihar-Panchkula Double Circuit Line 67.500 135 Zebra 54/7/3.18mm D51 Kala Amb-JB Rolling Single Circuit Line 0.043 0.043 Panther 30/7/3.00mm
E11 Kunihar-Baddi Double Circuit Line 31.091 62.182 Zebra 54/7/3.18mm D52 Bassi-Chulla Single Circuit Line 16.940 16.940 Panther 30/7/3.00mm
E12 Baddi-Panchkula Double Circuit Line 42.764 85.528 Zebra 54/7/3.18mm D53 Chulla-Hamirpur-II-1 Double Circuit Line 35.699 71.398 Panther 30/7/3.00mm
E13 Giri-Khodri-1 Double Circuit Line 35.060 70.12 Zebra 54/7/3.18mm D54 Chulla-Hamirpur-II-2 Double Circuit Line 35.699 71.398 Panther 30/7/3.00mm
E14 Giri-Khodri-2 Double Circuit Line 35.060 70.12 Zebra 54/7/3.18mm D55 Una(Rakkar)-Tahliwala Single Circuit Line 16.949 16.949 Panther 30/7/3.00mm
E15 Kangoo-Rauri Single Circuit Line 24.115 24.115 Zebra 54/7/3.18mm D56 Kurthala-Bathri-1 Double Circuit Line 45.510 91.020 Panther 30/7/3.00mm
E16 Giri-Visco Single Circuit Line 2.650 2.650 Zebra 54/7/3.18mm D57 Kurthala-Bathri-2 Double Circuit Line 45.510 91.020 Panther 30/7/3.00mm
E17 Uperla-Nangal-Nalagarh(PGCIL)-1 Double Circuit Line 3.569 7.138 Zebra 54/7/3.18mm D58 Giri-Gaura Single Circuit Line 60.491 60.491 Panther 30/7/3.00mm
E18 Uperla-Nangal-Nalagarh(PGCIL)-2 Double Circuit Line 3.569 7.138 Zebra 54/7/3.18mm D59 Barotiwla-Inox Single Circuit Line 1.000 1.000 Panther 30/7/3.00mm
E19 Uperla-Nangal-Vardhman Single Circuit Line 0.300 0.300 Zebra 54/7/3.18mm D60 Bagga-JP Cement Single Circuit Line Panther 30/7/3.00mm
E20 Baddi-Mandhala Double Circuit Line 7.800 15.6 Zebra 54/7/3.18mm D61 Kangoo-Jahoo LILO 29.403 29.403 Panther 30/7/3.00mm
E21 Baddi-Uperla-Nangal Double Circuit Line 24.562 49.124 Zebra 54/7/3.18mm TOTAL= 1739.984 2175.339
E22 Baddi-Vardhman Single Circuit Line 0.804 0.804 Zebra 54/7/3.18mm
LINE LENGTH CIRCUIT LENGTH TYPE OF CONDUCTOR
E23 Mandhala-Uperla-Nangal Double Circuit Line 30.253 60.506 Zebra 54/7/3.18mm CODE LINE NAME TYPE
(in kms) (in kms) CONDUCTOR USED SIZE
TOTAL= 716.196 1156.142 C1 Mandi-Shanan Single Circuit Line 35.000 35.000 Wolf 30/7/2.59mm
C2 Baddi-Barotiwala-1 Single Circuit Line 3.820 3.820 AAAC-Poplar-I 37/2.88mm
LINE LENGTH CIRCUIT LENGTH TYPE OF CONDUCTOR
CODE LINE NAME TYPE C3 Nalagarh-Akhanwali-2 Double Circuit Line 14.507 29.014 Panther & Wolf 30/7/3.00mm & 30/7/2.59mm
(in kms) (in kms) CONDUCTOR USED SIZE
D1 Jassore-Kandrori 24.234 Panther 30/7/3.00mm C4 Akhanwali-Alkem Single Circuit Line 0.425 0.425 Panther 30/7/3.00mm
D2 Jassore-Bathri 38.390 Panther 30/7/3.00mm C5 Baddi-Birla Single Circuit Line 1.740 1.740 Panther 30/7/3.00mm
D3 Jassore-Dehra-1 Double Circuit Line 60.639 121.278 Panther 30/7/3.00mm C6 Barotiwala-Parwanoo Single Circuit Line 17.210 17.210 AAAC-Poplar-I 37/2.88mm
D4 Jassore-Dehra-2 Double Circuit Line 60.639 121.278 Panther 30/7/3.00mm C7 Baddi-Barotiwala-2 Single Circuit Line 3.256 3.256 Wolf & AAAC-Poplar-I 30/7/2.59mm & 37/3.2.88mm
D5 Dehra-Amb-1 Double Circuit Line 27.492 54.984 Panther 30/7/3.00mm C8 Parwanoo-Pinjore Single Circuit Line 8.230 8.230 Dotterel 12/7/3.08mm
D6 Dehra-Amb-2 Double Circuit Line 27.492 54.984 Panther 30/7/3.00mm C9 Solan-Parwanoo Single Circuit Line 18.500 18.500 Dotterel 12/7/3.08mm
D7 Dehra-Hamirpur-II-1 Double Circuit Line 43.123 86.246 Panther 30/7/3.00mm C10 Solan-Totu 25.270 Dotterel 12/7/3.08mm
D8 Dehra-Hamirpur-II-2 Double Circuit Line 43.123 86.246 Panther 30/7/3.00mm C11 Jutogh-Totu Single Circuit Line 1.555 1.555 Panther 30/7/3.00mm
D9 Dehra-Kangra Single Circuit Line 29.935 29.935 Panther 30/7/3.00mm C12 Jutogh-Gumma Single Circuit Line 15.490 15.490 Panther 30/7/3.00mm
D10 Kangra-Kangra(PSPCL) 0.135 Panther 30/7/3.00mm C13 Andhra-Andhra-II 7.300
D11 Bassi-Shanan-1 Double Circuit Line 5.250 10.500 Panther 30/7/3.00mm C14 Kumarsain-Anni(Nagan) Single Circuit Line 17.300 17.300 Wolf 30/7/2.59mm
D12 Bassi-Shanan-2 Double Circuit Line 5.250 10.500 Panther 30/7/3.00mm C15 Kumarsain-Nogli Single Circuit Line 25.694 25.694 Wolf 30/7/2.59mm
D13 Bassi-Hamirpur-I(Anu) Single Circuit Line 49.750 49.750 Panther 30/7/3.00mm C16 Nogli-Smoli Single Circuit Line 34.408 34.408 Wolf 30/7/2.59mm
D14 Bassi-Palampur Single Circuit Line 32.000 32.000 Panther 30/7/3.00mm C17 Smoli-Andhra Single Circuit Line 13.100 13.100 Wolf 30/7/2.59mm
D15 Hamirpur-I(Anu)-Hamirpur-II-1 Double Circuit Line 4.950 9.900 Panther 30/7/3.00mm C18 Nogli-Jeori Single Circuit Line 24.710 24.710 Wolf 30/7/2.59mm
D16 Hamirpur-I(Anu)-Hamirpur-II-2 Double Circuit Line 4.950 9.900 Panther 30/7/3.00mm C19 Ghanvi-Nathpa Single Circuit Line 26.270 26.270 Wolf 30/7/2.59mm
D17 Hamirpur-I(Anu)-Chohal(PSEB) 76.000 Panther 30/7/3.00mm C20 Ghanvi-II-Jeori Single Circuit Line 6.952 6.952 Panther & Wolf 30/7/3.00mm & 30/7/2.59mm
D18 Hamirpur-II-kangoo-2 Double Circuit Line 42.139 84.278 Panther 30/7/3.00mm C21 Ghanvi-I-Jeori Single Circuit Line 5.750 5.750 Wolf 30/7/2.59mm
D19 Hamirpur-II-Jahoo Double Circuit Line 24.836 49.672 Panther 30/7/3.00mm C22 Nalagarh-GPIL Single Circuit Line 1.545 1.545 Panther 30/7/3.00mm
D20 Kangoo-ACC-1 1.650 Panther 30/7/3.00mm C23 Baddi-Nalagarh Single Circuit Line 16.739 16.739 AAAC-Poplar-II 37/3.05mm
D21 Kangoo-ACC-2 1.650 Panther 30/7/3.00mm C24 Gumma-Anni(Nagan) Single Circuit Line 40.304 40.304 Wolf 30/7/2.59mm
D22 Kangoo-Dehar 2.900 Panther 30/7/3.00mm C25 Sansarpur Terrace-Pong(BBMB) Single Circuit Line 6.400 6.4 Wolf 30/7/2.59mm
D23 Kangoo-Bagga 16.205 Panther 30/7/3.00mm C26 Rakkar(Una)-Golthai Single Circuit Line 15.980 15.980 Panther 30/7/3.00mm
D23A Bagga-Darlaghat Double Circuit Line 13.563 27.126 Panther 30/7/3.00mm C27 Baddi-Akhanwali-1 Double Circuit Line 10.172 20.344 Panther 30/7/3.00mm
D24 Kangoo-Kunihar-1 Single Circuit Line 46.000 46.000 Panther 30/7/3.00mm C28 Gumma-Sainj Single Circuit Line 21.029 21.029 Wolf 30/7/2.59mm
D25 Kangoo-Kunihar-2 Double Circuit Line 47.039 94.078 Panther 30/7/3.00mm C29 Sainj-Hulli Single Circuit Line 9.992 9.992 Wolf 30/7/2.59mm
D26 Kunihar-Darlaghat Double Circuit Line 22.301 44.602 Panther 30/7/3.00mm C30 Baddi-PNG Single Circuit Line 2.400 2.400 XLPE Cable 300mm^2
D27 Kunihar-Solan-1 Single Circuit Line 22.000 22.000 Panther 30/7/3.00mm C31 Nalagarh-Uperla Nangal-1 Double Circuit Line 3.510 Zebra 54/7/3.18mm
D28 Kunihar-Solan-2 Single Circuit Line 20.000 20.000 Panther 30/7/3.00mm C32 Nalagarh-Uperla Nangal-2 Double Circuit Line 3.510 Zebra 54/7/3.18mm
D29 Kunihar-Jutogh-1 Single Circuit Line 15.340 15.340 Panther 30/7/3.00mm C33 Baddi-Batolikalan Single Circuit Line 2.000 2.000 Panther 30/7/3.00mm
D30 Kunihar-Jutogh-2 Single Circuit Line 16.000 16.000 Panther 30/7/3.00mm C34 Golthai-Bhakhra Single Circuit Line 1.813 1.813 Panther 30/7/3.00mm
D31 Kunihar-Barotiwala-1 Double Circuit Line 26.030 52.060 Panther 30/7/3.00mm C35 Nalagarh-Akhanwali-1 Double Circuit Line 14.507 29.014 Panther & Wolf 30/7/3.00mm & 30/7/2.59mm
D32 Kunihar-Barotiwala-2 Double Circuit Line 26.030 52.060 Panther 30/7/3.00mm C36 Nalagarh-Barotiwala 19.995 AAAC-Poplar-I 37/2.88mm
D33 Giri-Solan Mixed Line 63.990 63.990 Panther 30/7/3.00mm C37 Akhanwali-Davni Single Circuit Line 2.110 2.110 Panther 30/7/3.00mm
D34 Solan-Gaura Mixed Line 20.662 20.662 Panther 30/7/3.00mm C38 Barotiwala-Cadbury Single Circuit Line 0.720 0.720 AAAC-Poplar-I 37/2.88mm
D35 Kangoo-Mandi 60.700 Panther 30/7/3.00mm C39 Baddi-Akhanwali-2 Double Circuit Line 10.172 20.344 Panther 30/7/3.00mm
D36 Kangoo-Bajaura Double Circuit Line 73.199 146.398 Panther 30/7/3.00mm C40 Uperla Nangal-Ambuja Single Circuit Line 9.837 9.837 Panther 30/7/3.00mm
D37 Bajaura-Larji Double Circuit Line 20.196 40.392 Panther 30/7/3.00mm C41 Uperla Nangal-JP Single Circuit Line 21.078 21.078 Panther 30/7/3.00mm
D38 Bajaura-Malana-1 Double Circuit Line 24.110 48.220 Panther 30/7/3.00mm C42 Ghanvi-II-Ghanvi-I Single Circuit Line 3.280 3.280
D39 Bajaura-Malana-2 Double Circuit Line 24.110 48.220 Panther 30/7/3.00mm C43 Golthai-Suraj Fabricates Single Circuit Line 0.260 0.260 Panther 30/7/3.00mm
D40 Mandi-Larji 20.000 Panther 30/7/3.00mm C44 Golthai-SPS Industries Single Circuit Line 0.4 0.4 Panther 30/7/3.00mm
D41 Giri-Jagadhari Single Circuit Line 50.000 50.000 Panther 30/7/3.00mm TOTAL= 524.240 514.013
8

220 kV Sub-Stations/
Power Houses
SINGLE LINE DIAGRAM OF 220/66/33/11 SUB-STATION, BADDI
AS ON: 06-01-2016 9

CONDUCTOR/EARTH-WIRE DETAIL
LEGEND
(D/C LINE) (D/C LINE) (D/C LINE) (D/C LINE) (S/C LINE)
220 kV BUS TWIN AAAC TARANTULA (33/5.23 mm) [42.764 km] [31.191 km] [24.562 km] [7.80 km] [0.804 km]
TWIN ACSR MOOSE (54/7/3.53mm) PANCHKULA KUNIHAR-1 UPEARLA NANGAL MANDHALA VARDHMAN LIGHTENING ARRESTOR
220 kV LINE ACSR - ZEBRA (54/7/3.18 mm)
TWIN ZEBRA TWIN ZEBRA XLPE-630mm2
EARTH-WIRE GSS - (7/3.15 mm) CIRCUIT BREAKER

66 kV BUS TARANTULA (33/5.23 mm) CURRENT TRANSFORMER


ACSR 1. PANTHER (30/7/3.00 mm)
66 kV LINE 2. WOLF (30/7/2.59mm) ISOLATOR WITHOUT
AAAC 1. POPLAR-I (37/2.88 mm) EARTH SWITCH
2. POPLAR-II (37/3.05mm)
[25.75 km] [13.00 km]
33 kV BUS ACSR - ZEBRA (54/7/3.18 mm) Industrial feeder1 Industrial feeder2 feeder03 ISOLATOR WITH
EARTH SWITCH
33 kV LINE AAAC- (30/2.59 mm)

11 kV BUS (CTR:1200-600/ (CTR:1200-600/ (CTR:2000-1000/ (CTR:2000-1000/ (CTR:250-125/ WAVE TRAP


INDOOR COPPER STRIP
1-1-1-1-1) 1-1-1-1-1) 1-1-1-1-1) 1-1-1-1-1) 1-1-1-1-1)
SF6
11 kV LINE AAAC- (7/4.26 mm) SF6 SF6 SF6 SF6 POTENTIAL TRANSFORMER
VCB VCB VCB

(CTR: 400-200/ (CTR: 400-200/ (CTR: 300-150/


1-1-1A) 1-1-1A) 1-1-1A)
POWER TRANSFORMER
220 kV Bus B1
(PTR:
220kV/110V 33 kV Bus CAPACITOR VOLTAGE
(PTR: TRANSFORMER
SF6
33kV/110V
B2 (PTR:
220kV/110V

VCB CAPACITOR BANK


SF6 (CTR:1200-600/ SF6 SF6 SF6 VCB
(CTR:150-75/ (CTR: 1000-500/1-0.577) (FUNCTIONAL)
(CTR:300-150/ 1-1-1A) (CTR:300-150/ (CTR:300-150/ 1-1-1-1-0.577A)
1-1-1-1-0.577A) 1-1-1-1-0.577A) 1-1-1-1-0.577A) T4
Y (20 MVA)
Y Y (66/33) KV (2x3.6 MVAR)
T1 (100 MVA) T2 (100 MVA) Y T3 (100 MVA)
Y Y (220/66)KV (CTR:400-200/
(220/66)KV (220/66)KV Y
TC: ON LOAD TC: ON LOAD TC: ON LOAD T4 1-1-1)
DC SYSTEM STATUS
Y No.of Taps:17 Y No.of Taps:17 Y No.of Taps:17 (25/31.5 MVA)
NormalTap:9b NormalTap:9b NormalTap:9b (220/33)KV
TC: ON LOAD
(CTR:200-100/1-1-1-0.577) BATTERY BANK BATTERY CHARGER
DC VOLTAGE
(CTR:1800-900/ (CTR:1800-900/ (CTR:1000-500/ No.of Taps:17 SF6
1-1-1-1-0.577) 1-1-1-1-0.577A) NormalTap:7 CAPACITY STATUS RATING STATUS
1-1-1-1-0.577)
SF6 SF6 SF6
Boost:2x40A Functional
220 V 400Ah Functional
Float:2x40A

48 V 400Ah Functional Boost:2x60A Functional


Float:2x60A
66 kV Bus B1
(PTR:
66kV/110V

B2 (PTR:
66kV/110V

SF6

(CTR:400-200/1-1-1) SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6
(CTR:200-100/ (CTR:500-250/ (CTR:500-250/ (CTR:800-400/ (CTR:400-200/ (CTR:200-100/ (CTR:200-100/ (CTR:400-200/ (CTR: SF6 SF6 SF6 SF6
1-1-1-1A) 1-1-1-1A) 1-1-1-1A) 1-1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1-1A) 300-150/1) (CTR: 200-100/ (CTR: 200-100/ (CTR: 200-100/ (CTR: 200-100/
1-1-1-1-0.577) 1-1-1-1-0.577) 1-1-1-1-0.577) 1-1-1-1-0.577)
Y T1 Y T2 Y T3 Y T4
66/11 kV 66/11 kV 66/11 kV 66/11 kV
20 MVA 20 MVA 20 MVA 20 MVA
Y Y Y Y
(PANTHER) TC: ON LOAD TC: ON LOAD TC: ON LOAD
TC: ON LOAD No.of Taps:17 No.of Taps:17
(AAA) (AAA) (AAA) (AAA) (PANTHER) (PANTHER) (PANTHER) No.of Taps:17 No.of Taps:17
C2 NormalTap:5 NormalTap:7 NormalTap:7
C1 NormalTap:5
14.4 MVAR 14.4 MVAR
(AAAC-1 & (ACSR-1) (XLPE-
(ACSR-1) (ACSR-1) (ACSR-1) (AAAC-1) (AAAC-2)
ACSR-2) 300mm2)
(CTR:1200-600 (CTR:1200-600 (CTR:1200-600 (CTR:1200-600
Birla Taxtiles Akanwali-I Akanwali-II P&G (Functional) /1-1-0.577A) /1-1-0.577A) /1-1-0.577A)
Barotiwala-II/ Barotiwala-I Batoli Kalan Nalagarh /1-1-0.577A)
10MVAR (1.74 km) (10.172 km) (10.172 km) Winsom from T14 (3.82 km) (2.00 km) (2.40 km) (16.739 km)
(S/C LINE) (S/C LINE) (S/C LINE) (S/C LINE) VCB VCB VCB VCB
CAPACITOR BANK (D/C LINE) (D/C LINE) (3.256 km.) (S/C LINE)
(Functional) (S/C LINE)
11 kV Bus

VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB

(CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR:
200-100/1) 400-200/1) 400-200/1) 200-100/1) 400-200/1) 200-100/1) 400-200/1) 200-100/1) 400-200/1) 400-200/1) 400-200/1) 400-200/1) 400-200/1) 400-200/1)

FEEDER-1 FEEDER-2 FEEDER-3 FEEDER-6 FEEDER-9 FEEDER-10 FEEDER-11 FEEDER-12 FEEDER-13 FEEDER-14 FEEDER-16 FEEDER-21 FEEDER-22 FEEDER-23
(3.5 km.) (10.0 km.) (11.0 km.) (2.0 km.) (12.0 km.) (2.0 km.) (14.00 km.) (0.4 km.) (12.50 km.) (0.80 km.) (28.00 km.) (4.5 km.) (4.0 km.) (3.5 km.)

Total - 23 Feeders Connected - 14 Feeders

(2x3 MVAR)
CAPACITOR BANK
(Functional)
10
SINGLE LINE DIAGRAM OF BHABA
CONDUCTOR/EARTH-WIRE DETAIL
[130.90 km] [24.70 km]
KUNIHAR(HP) JEORI(HP)
132 kV BUS

132 kV LINE

EARTH-WIRE

33 kV BUS-1

33 kV BUS-2

33kV LINE

Connected Connected
(CTR: 600/1) (CTR: 600/1)

LEGEND

LIGHTENING ARRESTOR

Bus B2 B4
CIRCUIT BREAKER

CURRENT TRANSFORMER
B3
ISOLATOR WITHOUT
220 kV
Bus B1 EARTH SWITCH

ISOLATOR WITH
EARTH SWITCH

Connected WAVE TRAP


(CTR: 100/1)

POTENTIAL TRANSFORMER
T1
(220/11 KV)
GT1 GT2 GT3
(50 MVA) (50 MVA) (50 MVA) POWER TRANSFORMER
(11/220 KV) (11/220 KV) (11/220 KV)
TC: ON/Off LOAD TC: ON/Off LOAD TC: ON/Off LOAD
No.of Taps:17 No.of Taps:17 No.of Taps:17
Connected NormalTap:7 Connected NormalTap:7 Connected NormalTap:7 CAPACITOR VOLTAGE
(CTR: A) (CTR: A) (CTR: A) TRANSFORMER

PTR: PTR: PTR:


[11 kV/110V] [11 kV/110V] [11 kV/110V] DC SYSTEM STATUS

11kV Bus B1 BATTERY BANK BATTERY CHARGER


DC VOLTAGE
UNIT-I UNIT-II UNIT-III
(40 MW) (40 MW) (40 MW) CAPACITY STATUS RATING STATUS

220 V

48 V
SINGLE LINE DIAGRAM OF 220/132/33 kV SUB-STATION, GIRI AND 60 MW POWER HOUSE, GIRI
AS ON: 20-01-2016 11
(S/C LINE) (D/C LINE) (D/C LINE)
[2.65 km] [35.06 km] [35.06 km]
VISCO KHODRI-2 KHODRI-1

LEGEND
CONDUCTOR/EARTH-WIRE DETAIL DC SYSTEM STATUS

LIGHTENING ARRESTOR BATTERY BANK BATTERY CHARGER


220 kV BUS MOOSE (54/7/3.53mm) DC VOLTAGE
CAPACITY STATUS RATING STATUS
CIRCUIT BREAKER 220 kV LINE ZEBRA (54/7/3.15mm)
Functional Boost:30A
220 V 200Ah Float:10A Functional
CURRENT TRANSFORMER 132 kV BUS GOAT (30/7/3.71mm)
400Ah Functional Boost:50A Functional
48 V Float:20A Connected Connected
ISOLATOR WITHOUT 132 kV LINE PANTHER (30/7/3.00mm) (CTR: 800/1) (CTR: 800/1)
EARTH SWITCH
SF6 SF6 SF6
EARTH-WIRE GSS (7/3.15mm)
ISOLATOR WITH
EARTH SWITCH 33 kV BUS MOOSE (54/7/3.53mm)

220 kV BUS B1
WAVE TRAP 33kV LINE ACSR (6/1/4.72mm)
Bus PTR:
(S/C LINE) (S/C LINE)
[220kV/110V]
POTENTIAL TRANSFORMER [17.6 km] [16.39 km]
KULHAL POANTA

Bus PTR: B2
POWER TRANSFORMER [220kV/110V]
SF6

CAPACITOR VOLTAGE
TRANSFORMER SF6 SF6 (CTR:800/1)
(CTR:300/1) (CTR:300/1)

T2(80/100MVA) T1 (80/100MVA)
Y Y (220/132kV)
(220/132kV)
TC: ON LOAD
TC: ON LOAD
Y Y No.of Taps:17
No.of Taps:17
NormalTap:7 NormalTap:7
Connected Connected
(CTR: 400/1) (CTR: 500/1)
(CTR:500/1) (CTR:500/1)
ABCB SF6
SF6 SF6

132 kV Bus B1
Bus PTR:
[132kV/110V]

B2
Bus PTR:
[132kV/110V]

ABCB

SF6 SF6 ABCB ABCB Connected


ABCB ABCB Connected Connected
(CTR: 500/1) (CTR: 200/1) (CTR: 200/1)
Connected Connected Connected Connected Connected Connected
(CTR:500/1) (CTR: 500/1) (CTR:500/1) (CTR: 600/1) (CTR: 150/1) (CTR: 150/1) SF6 SF6

T3 T4
(16/20 MVA) (25/31.5 MVA)
(132/33 KV) (132/33 KV)
GT2 GT1
TC: ON/Off LOAD TC: ON/Off LOAD (40 MVA)
No.of Taps:17
(40 MVA)
No.of Taps:17 (11/132 kV)
NormalTap:7 NormalTap:7 (11/132 kV)
TC: ON/Off LOAD TC: ON/Off LOAD
No.of Taps:17 No.of Taps:17
NormalTap:7 NormalTap:7
Connected Connected
(CTR: 600/1) (CTR: 600/1)
(CTR: 2000/5) (CTR: 2000/5)
VCB VCB
PTR: PTR:
[11kV/110V] [11kV/110V]
SOLAN-2 SOLAN-1 JAGADHARI KALA AMB
[63.99 km] [65.758 km] [50 km] [31.96 km] UNIT-II UNIT-I
(S/C LINE) (S/C LINE) (S/C LINE) (S/C LINE) (30 MW) (30 MW)
33 KV BUS

SF6 SF6 SF6 MOCB VCB VCB VCB VCB

(CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR:


300/1) 150/1) 300/1) 20/5) 200/1) 300/1) 200/1) 300/5A)
VCB VCB

450 kVA
33/11 kV

AAS.L VIZ ENGINEERS VALLEY IRON Nahan Dhaulakuan IT


Paonta
[2.92 km] [8 MW] ST. Aux. [11 MW] [14 MW] [11 MW] [10 MW]
[2.221 km] Xmer
Cells Cells

Series Series Series Series


Reactor Reactor Reactor Reactor
(2*2.5 MVAR Cap. bank) (2*2.5 MVAR Cap. bank)
(FUNCTIONAL) (FUNCTIONAL)
SINGLE LINE DIAGRAM OF 220/132 SUB-STATION HAMIRPUR-II
AS ON: 11-05-2016
12
(D/C LINE) (D/C LINE)
[9.50 km] [9.50 km]
TAL (PGCIL) TAL (PGCIL)
LEGEND CONDUCTOR/EARTH-WIRE DETAIL DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


220 kV BUS MOOSE (54/7/3.53mm) DC VOLTAGE
LIGHTENING ARRESTOR
CAPACITY STATUS RATING STATUS
220 kV LINE ZEBRA (54/7/3.18mm)
Boost:2x40A
220 V 400Ah Functional Float:2x24A Functional
CIRCUIT BREAKER
EARTH-WIRE GSS - (7/3.15 mm) Boost:2x90A
CURRENT TRANSFORMER 48 V 600Ah Functional
Float:2x60A Functional

132 kV BUS AAAC TARANTULA(37/5.23mm) Boost:40A


30 V 100Ah Functional Float:35A Functional
ISOLATOR WITHOUT
EARTH SWITCH 132 kV LINE PANTHER (30/7/3.00mm)

ISOLATOR WITH 33 kV BUS WOLF (30/7/2.59mm)


(CTR:1600-800/1-1-1-1-1A) (CTR:1600-800/1-1-1-1-1A)
EARTH SWITCH
33 kV LINE DOG (6/1/4.72mm)
SF6-CB SF6-CB
WAVE TRAP
11 kV BUS

POTENTIAL TRANSFORMER 11 kV LINE DOG (6/1/4.72mm)


220 kV BUS-I

POWER TRANSFORMER (D/C LINE) (D/C LINE) (LILO) (D/C LINE)


[4.95 km] [4.95 km] [24.836 km] [42.139 km]
(PTR:220 kV/110 V)
HAMIRPUR-1 HAMIRPUR-2 JAHOO KANGOO-2 220 kV BUS-II
CAPACITOR VOLTAGE
TRANSFORMER

(PTR:220 kV/110 V) SF6-CB

SF6-CB (CTR: SF6-CB SF6-CB


1200-600/1-1)
(CTR:600-300/1-1-1-1-1A) (CTR:600-300/1-1-1-1-1A) (CTR:300-150/1-1-1-1-1A)

T1 (80/100 MVA) T2 (80/100 MVA) T3 (80/100 MVA)


(220/132 KV) (220/132 KV) (220/132 KV)
TC: ON LOAD TC: ON LOAD TC: ON LOAD
No.of Taps:25 No.of Taps:25 No.of Taps:25
NormalTap:13b NormalTap:13b NormalTap:13b
(CTR:500-250/ (CTR:500-250/ (CTR:500-250/ (CTR:500-250/
1-1-1-.577A) 1-1-1-.577A) 1-1-1-.577A) 1-1-1-.577A) (CTR:1200-600/1-1-1-.577A) (CTR:600-300/1-1-1-1A)
(CTR:1200-600/1-1-1-.577A)
SF6-CB SF6-CB SF6-CB SF6-CB
SF6-CB SF6-CB SF6-CB

(PTR:132 kV/110 V) 132 kV BUS-I

132 kV BUS-II

(PTR: SF6-CB [4.950 km] [4.950 km]


132 kV/110 V) BARSAR LADRAUR
SF6-CB SF6-CB SF6-CB SF6-CB
(CTR:500-250/
1-1-1-.577A)
(CTR:500-250/1-1-1-1A) (CTR:500-250/1-1-1-1A)
(CTR:500-250/ (CTR:500-250/
1-1-1-.577A) 1-1-1-.577A)

VCB VCB

(CTR:200-100/1-1-1A) (CTR:200-100/1-1-1A)

33 kV BUS

(PTR: (PTR: (PTR:


33 kV/110 V) 33 kV/110 V) 33 kV/110 V)

DEHRA-2 DEHRA-1 VCB VCB CHULLA-I CHULLA-II


[43.123 km] [43.123 km] [35.699Kms] [35.699Kms]
(D/C LINE) (CTR:100-50/1-1) (CTR:100-50/1-1) (D/C LINE)
(D/C LINE) (D/C LINE)

T1 33/11 kV T2 33/11 kV
3.15 MVA 3.15 MVA

Y Y

VCB VCB 400-200/5-5A VCB

400-200/5-5A
200-100/5-5A 200-100/5-5A 200-100/5-5A 200-100/5-5A 200-100/5-5A

VCB VCB VCB VCB VCB

TAPAN HAMIRPUR LAMBLOO TIKKAR INDUSTRIAL AREA


[1.00 km] [6.440 km] [33.80 km] [28.171 km] [9.466 km]
SINGLE LINE DIAGRAM OF 220/132/33/11 kV SUB-STTION AT JASSORE
AS ON: 11-02-2016 LEGEND 13
(40 km) (57 km) (25.602 km)
PONG-BBMB BAIRASUIL(NHPC) THEIN(RSDPH)-PSEB
LIGHTENING ARRESTOR
CONDUCTOR/EARTH-WIRE DETAIL

220 kV BUS ACSR - MOOSE (54/7/3.54 mm) CIRCUIT BREAKER

220 kV LINE ACSR - ZEBRA (54/7/3.18 mm) CURRENT TRANSFORMER

EARTH-WIRE GSS - (7/3.15 mm) ISOLATOR WITHOUT


EARTH SWITCH

132 kV BUS ACSR - ZEBRA (54/7/3.18 mm)


ISOLATOR WITH
EARTH SWITCH
132 kV LINE ACSR - PANTHER (30/7/3.00 mm)
(CTR:800-400/ (CTR:800-400/ (CTR:800-400/
1-1-1-1-1) 1-1-1-1-1) 1-1-1-1-1) 33 kV BUS ACSR - PANTHER (54/7/3.00 mm) WAVE TRAP

SF6 SF6 SF6


33 kV LINE ACSR - DOG (6/1/4.72 mm)
POTENTIAL TRANSFORMER

220 kV BUS-I POWER TRANSFORMER

(PTR: CAPACITOR VOLTAGE


220 kV/110 V) TRANSFORMER

220 kV BUS-II

(PTR: CTR:
SF6 300-150/1-1A
220 kV/110 V)
SF6
SF6 (CTR:800-400/ SF6 SF6
(CTR:800-400/ 1-1-1-1-1)
(CTR:800-400/ (CTR:150-75/ (CTR:150-75/
1-1-1-1A)
1-1-1-1-1) 1-1-0.577A) 1-1-1-1-1A)
T4 220/132 KV T3 220/132 KV
Y T1 220/33 KV T2 220/33 KV
Y (50/63 MVA) Y (150 MVA) (25/31.5 MVA)
Y (25/31.5 MVA)
TC: ON LOAD TC: ON LOAD TC: ON LOAD TC: ON LOAD
Y No.of Taps:17
NormalTap:5 Y No.of Taps:17 Y No.of Taps:17 Y No.of Taps:17
NormalTap:13 NormalTap:5 NormalTap:5
(CTR:600-300/ (CTR:1600-800/ (CTR:1000-500/ (CTR:1200-600/
1-1-1-1-1A) 1-1-1-1-1) 1-1-0.577A) 1-1-1-1-0.577A)
SF6 SF6 MOCB MOCB

(CTR:1000-500/ 33kV
(CTR:1500-750/1-1-1) 1-1-1-1-0.577A) (2x3.6 MVAR)
132 kV BUS 33 kV Bus B1 PTR:33kV/110V CAPACITOR BANK
[BOTH FUNCTIONAL]
SF6
PTR: PTR:
132kV/110V 132kV/110V
(CTR: (CTR:300-150/ (CTR: (CTR: (CTR:400-200/ (CTR:200-100/
(CTR:400-200/ (CTR:10-5/ (CTR:400-200/
400-200/1-1) 1-1-1A) 200-100/1-1) 400-200/1-1) 1-1-1A) 1-1A)
SF6 SF6 SF6 SF6 1-1-1-0.577) 1-1A) 1-1-1-0.577)
MOCB MOCB MOCB MOCB MOCB MOCB
MOCB
(CTR:500-250/ (CTR:300-150/ (CTR:600-300/ (CTR:500-250/ MOCB MOCB
1-1-1-1A) 1-1-1A) 1-1-1-1A) 1-1-1-1A)
(CTR:
200/1)
T2 10 MVA T1 10 MVA
Y 33/11 kV 33/11 kV
TC: ON LOAD TC: ON LOAD
No.of Taps:17 No.of Taps:17
Y NormalTap:5 NormalTap:5

(CTR:1200-600/ (CTR:1200-600/
1-1-1-.577A) 1-1-1-.577A)
Bakloh Shahpur Raja ka VCB Kandrori VCB Bharmar Raja ka
(22.417)km Bag-I 33/0.4kV (16.20)km
(23.34+ (27=20+7)km Bag-II
400kVA
11.00)km

BATHRI KANDRORI DEHRA-II DEHRA-I Stn-Tfr


[60.379 km] [60.379 km] (CTR:1200-600/
[38.540 km] [24.334 km] 1-1A)
[Panther] 11 kV Bus B1 PTR:11kV/110V

PTR:
VCB
DC SYSTEM STATUS 11kV/110V VCB

BATTERY BANK BATTERY CHARGER VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB
DC VOLTAGE
CAPACITY STATUS RATING STATUS (CTR:100-50/ (CTR:100-50/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:100-50/ (CTR:100-50/
(CTR:200-100/ (CTR:200-100/
1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A)
Boost:2x60A
220 V 400Ah Functional
Float:2x40A Functional

Boost:2x100A
48 V 600Ah Functional Float:2x60A Functional

Spare Spare Gangath Kotla Aund Nurpur Suliali Agro Jassore Colony Stn X-frmr

(3 MVAR) (1.8+1.2 MVAR)


CAPACITOR BANK CAPACITOR BANK
[FUNCTIONAL] [FUNCTIONAL]
SINGLE LINE DIAGRAM OF 220/66/22 kV SUB-STATION, JEORI
AS ON: 07-01-2016
14
(D/C LINE) (D/C LINE)
(24.70 km) (106.72 km)
BHABHA (HP) KUNIHAR (HP)
LEGEND

LIGHTENING ARRESTOR

CIRCUIT BREAKER

CURRENT TRANSFORMER

ISOLATOR WITHOUT
EARTH SWITCH

(CTR: 600-300-150/
1-1-1-1) (CTR: 1200-600/1-1-1-1-1) ISOLATOR WITH
EARTH SWITCH

(PTR: 220kV/110V) SF6-CB SF6-CB


WAVE TRAP

POTENTIAL TRANSFORMER
220 kV BUS

POWER TRANSFORMER

SF6-CB SF6-CB CAPACITOR VOLTAGE


TRANSFORMER
(CTR:600-300/1-1-1-1-0.577A) (CTR: 200-100/1-1-1-0.577 A)

T1, (3x33.33 MVA) T2, (31.5 MVA)


Y (220/66 KV) Y (220/66 KV)
TC: ON LOAD TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17 CONDUCTOR/EARTH-WIRE DETAIL
NormalTap:9 NormalTap:9
220 kV BUS TARANTULA (37/5.23mm)
(CTR:2000-1000/1-1-1-1-1A) (CTR:600-300/1-1-1-1-0.577 A)
SF6-CB SF6-CB 220 kV LINE ZEBRA(54/7/3.18mm)
(PTR: 66kV/110V) (PTR: 66kV/110V) EARTH-WIRE GSS (7/3.15mm)

ACSR-1. TARANTULA(37/5.23mm)
66 kV BUS 2. WOLF(30/7/2.59mm)

66 kV BUS 66 kV LINE ACSR-1. PANTHER(30/7/3.00mm)


2. WOLF(30/7/2.59mm)
(CTR:300-150/1-1A) (CTR:600-300/ INDOOR COPPER STRIP
1-1-1-1-0.577A) 22 kV BUS
(80x6mm)
SF6-CB
(CTR:500-250/ (CTR:600/ (CTR:500-250/ ACSR-1. 6/1/4.72mm
1-1-1 A) SF6-CB 1-1-1 A) 22kV LINE 2. 6/1/2.59mm
1-1-1-1-1A) 3. 7/1/4.72mm
(Mtr Core NA) SF6-CB
SF6-CB SF6-CB SF6-CB 4. 6/1/3.35mm
(CTR:600-300/ (CTR: 200-100/
1-1-1-1A) 1-0.577A) (Mtr Core NA)
T3 T4
Y (31.5 MVA) Y (10 MVA)
(66/22 KV) (66/22 KV) DC SYSTEM STATUS
Y Y
TC: ON LOAD TC: ON LOAD BATTERY BANK BATTERY CHARGER
No.of Taps:17 No.of Taps:17 DC
NormalTap:5 NormalTap:5 VOLTAGE
CAPACITY STATUS RATING STATUS
(CTR:600-300/ (CTR:600-300/
1-0.577A) 1-0.577 A) Float:40A
220 V 400Ah Functional Functional
Capacitor Bank VCB-CB VCB-CB Boost:60A
(ACSR-1&2)
(2x7.2 MVAR)
(NON FUNCTIONAL) 200Ah Boost:7.7A Functional
48 V Functional Float:9.1A
GHANVI-II GHANVI-I NOGLI
(6.952km) (5.750km) (PTR: (24.71 km)
(ACSR-1&2) (ACSR-2) CTR: 22kV/110V)
(PTR: (ACSR-2)
1000-500/1-1
22 KV BUS 22kV/110V)

VCB-CB
VCB-CB VCB-CB VCB-CB VCB-CB VCB-CB VCB-CB VCB-CB VCB-CB VCB-CB VCB-CB VCB-CB

CTR: 200-100/ 200-100/ 200-100/ 200-100/ CTR: CTR: CTR: CTR:


1-1A CTR: CTR:
150/1A 1-1A 1-1A 1-1A 200-100/1-1 200-100/1-1 200-100/1-1 200-100/1-1 200-100/1-1 20/10/1-1

250 kVA
22/0.4kV
Y

MANGLAD Spare Jhakri-II Kinnaur Manglad Wadhal-I Wadhal-II Daj Rampur Sarahan Ghanvi
ST.Xmer (5.00km) (20.0km)
SHEP (7.50km) (30.72km) (7.50km) (7.5km) (24.0km) (39.90km) (7.910 km)
(ACSR-1) (ACSR-2&4) (ACSR-1) (ACSR-1) (ACSR-1) (ACSR-1) (ACSR-1&2) (ACSR-2&4) (ACSR-1&4)
(4.50km)
(ACSR-1)
SINGLE LINE DIAGRAM OF 220/132/33 kV SUB-STATION AT KANGOO
[24.115 km] [3.177 km] 15
RAURI DEHAR-BBMB
LEGEND CONDUCTOR/EARTH-WIRE DETAIL

220 kV BUS ACSR - MOOSE (54/7/3.54 mm)


LIGHTENING ARRESTOR

220 kV LINE ACSR - ZEBRA (54/7/3.18 mm)


CIRCUIT BREAKER
EARTH-WIRE GSS - (7/3.15 mm)
CURRENT TRANSFORMER
132 kV BUS ACSR - MOOSE (54/7/3.54 mm)
ISOLATOR WITHOUT
EARTH SWITCH 132 kV LINE ACSR - PANTHER (30/7/3.00 mm)

(CTR:600-300-100/1-1-1-1-1) (CTR:600-300/1-1)
ISOLATOR WITH 33 kV BUS ACSR - ZEBRA (54/7/3.18 mm)
EARTH SWITCH
SF6 SF6 33 kV LINE ACSR - DOG (6/1/4.72 mm)
AAA - (7/4.26 mm)
WAVE TRAP

220 KV BUS B1 POTENTIAL TRANSFORMER

POWER TRANSFORMER
(PTR:220 kV/110 V)

SF6
CAPACITOR VOLTAGE
(CTR:1200-600-300/ TRANSFORMER
1-1-1-1-1)
Y T1
(80/100 MVA)
Y 220/132 KV
(CTR:600-300/
1-1-1-0.577)
SF6

(PTR:132 kV/110 V) 132 kV Bus B1 B2

B3 B4

SF6 (PTR:132 kV/


110 V)
SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6 SF6
SF6 SF6
(CTR:500-250/ (CTR:500-250/ (CTR:150-75/ (CTR:150-75/ (CTR:500-250/ (CTR:500-250/ (CTR:500-250/ (CTR:500-250/ (CTR:500-250/ (CTR:500-250/ (CTR:500-250/ (CTR:500-250/ (CTR:500-250/ (CTR:500-250/
1-1-1-1) 1-1-1-1) 1-1-1-1-0.577) 1-1-1-1-0.577) 1-1-1-1) 1-1-1-1) 1-1-1-1) 1-1-1-1) 1-1-1-1) 1-1-1-1) 1-1-1-1) 1-1-1-1) 1-1-1-1) 1-1-1-1)
2x3.6 MVAR
Cap. bank Y T2 Y T3
(31.5 MVA) (31.5 MVA)
Y 132/33 KV Y 132/33 KV

(CTR:600-300/ (CTR:600-300/
1-0.577) 1-0.577)
VCB VCB

(CTR:200-100/
1-1)

VCB LARJI-I LARJI-II JAHOO HAMIRPUR-II-2 KUNIHAR-II BAGGA ACC-II ACC-I KUNIHAR-I DEHAR-BBMB MANDI BAJAURA
[55.83 km] [55.83 km] [29.403 km] [42.139 km] [48.95 km] [16.205 km] [1.65 km] [1.65 km] [46 km] [2.90 km.] [62.70 km] [77.199 km]
33kV BUS [42.90 km upto Pandoh +[57.00 km upto Larji+
33 kV Bus 19.80 km Pandoh to Bijni]
20.00 km Larji to Bajaura]

(PTR:
33 kV/110 V)

VCB
VCB VCB VCB (CTR:10-5/ VCB VCB VCB VCB
1-1)
(CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/
1-1) 1-1) 1-1) 1-1) 250 kVA 1-1) 1-1) 1-1) 1-1)
33/0.4 KV
Y

ACSR ACSR AAA AAA ACSR ACSR AAA AAA


ST. Aux.
Xmer-I
SUNDERNAGAR-I SUNDERNAGAR-II KOLDAM-I KANDROR-II BILASPUR-I BILASPUR-II KOLDAM-II KANDROR-I
[16.437 km.] [15.785 km.] [5.5 km.] [11.25 km.] [20.505 km.] [19.895 km.] [5.5 km.] [11.5 km.]
SINGLE LINE DIAGRAM OF 220/132/33 kV SUB-STATION, KUNIHAR
AS ON: 05-01-2016 16
(D/C LINE) (D/C LILO) (D/C LILO) (D/C LINE)
[67.5 km] [31.091 km] [106.72 km] [130.90 km]
LEGEND CONDUCTOR/EARTH-WIRE DETAIL PANCHKULLA-2 BADDI-1 JEORI BHABHA

220 kV BUS ACSR - MOOSE (54/7/3.54 mm)


LIGHTENING ARRESTOR

220 kV LINE ACSR - ZEBRA (54/7/3.18 mm)


CIRCUIT BREAKER
EARTH-WIRE GSS - (7/3.15 mm)
CURRENT TRANSFORMER
132 kV BUS ACSR - ZEBRA (54/7/3.18 mm)
ISOLATOR WITHOUT
EARTH SWITCH 132 kV LINE ACSR - PANTHER (30/7/3.00 mm)

ISOLATOR WITH 33 kV BUS ACSR - PANTHER (30/7/3.00 mm)


EARTH SWITCH (CTR:600-300-150/ (CTR:600-300-150/ (CTR:600-300-150/ (CTR:600-300-150/
33 kV LINE ACSR - DOG (6/1/4.72 mm) 1-1-1-1) 1-1-1-1) 1-1-1-1) 1-1-1-1)
WAVE TRAP SF6-CB SF6-CB SF6-CB SF6-CB

POTENTIAL TRANSFORMER

220 kV
Bus B2
POWER TRANSFORMER

(PTR:220 kV/110 V)
CAPACITOR VOLTAGE
TRANSFORMER Bus B1

DC SYSTEM STATUS
SF6-CB (PTR:220 kV/110 V)
BATTERY BANK BATTERY CHARGER
DC (CTR:600-300-150/
VOLTAGE SF6-CB SF6-CB 1-1-1-1-1) SF6-CB
CAPACITY STATUS RATING STATUS (CTR:600-300-150/1-1-1-1-1) (CTR:600-300-150/1-1-1-1-1) (CTR:600-300/1-1-1-1-1)
220 V 400Ah Functional Float:40-60A Functional T1, (80/100 MVA) T3, (160/200 MVA)
T2, (80/100 MVA)
Boost:40-60A Y (220/132 KV) Y Y (220/132 KV)
(220/132 KV)
48 V Boost:60A Functional TC: Off LOAD TC: Off LOAD TC: ON LOAD
400Ah Functional Float:60A No.of Taps:17 No.of Taps:17
Y NormalTap:5 Y No.of Taps:17 Y NormalTap:9
NormalTap:5

(CTR:1000-500 (CTR:1000-500-250/1-1-1-1) (CTR:1200-600/1-1-1-1-1)


-250/1-1-1-1)
SF6-CB SF6-CB
SF6-CB

132 kV
Bus B2

B1 (PTR:132 kV/110 V)

SF6-CB
(PTR:132 kV/110 V)

SF6-CB SF6-CB SF6-CB SF6-CB SF6-CB SF6-CB SF6-CB SF6-CB SF6-CB (CTR:1000-500-250/1-1-1-1)
SF6-CB
(CTR:500-250/ (CTR:500-250/ (CTR:400-200/ (CTR:400-200/ (CTR:500-250/ (CTR:500-250/ (CTR:400-200/ (CTR:500-250/ (CTR:400-200/ (CTR:100-50/1-1-0.577)
1-1-1-1-1) 1-1-1-1-1) 1-1-1-1-1) 1-1-1) 1-1-1-1-1) 1-1-1-1-1) 1-1-1) 1-1-1) 1-1-1)
T5, (16 MVA)
Y (132/33 KV)
TC: ON LOAD
No.of Taps:17
Y NormalTap:5

(CTR:400-200/1-1-0.577)

MOCB

KANGOO-II DARLAGHAT KANGOO-I JUTOGH-I JUTOGH-II SOLAN-II SOLAN-I BAROTIWALA-I BAROTIWALA-II


[D/C LINE] [S/C LINE] [S/C LINE] [S/C LINE] [S/C LINE] [S/C LINE] [D/C LINE] [D/C LINE]
[D/C LILO] [26.03 km.]
[46.00 km.] [16.00 km.] [20.00 km.] [22.00 km.] [26.03 km.]
[47.039 km.] [22.301 km.] [15.34 km.] 33kV BUS B1

(PTR:33 kV/110 V)

MOCB MOCB
ACB MOCB VCB
(CTR:15-7.5/1) (CTR:15-7.5/1)
(CTR:150-750/ (CTR:150-750/ (CTR:300-150/1)
1-1) 1-1) 33/0.4 kV
33/0.4 kV
Y 630 KVA Y 200 KVA

SUBATHU KUNIHAR CAPACITOR BANK


[13.98 km.] [4.0 km.] [2X2.5 kVAR]
ST. Aux. ST. Aux. (FUNCTIONAL)
Xmer-I Xmer-II
SINGLE LINE DIAGRAM OF 220/66/11 KV SUB-STATION, MANDHALA
AS ON: 06.01.2016
17
(D/C LINE) (D/C LINE)
[30.253km] [9.909km]
UPERLA NANGAL BADDI BAY-3 (LINE) BAY-1 (LINE)

LEGEND

LIGHTENING ARRESTOR

CIRCUIT BREAKER

CURRENT TRANSFORMER

ISOLATOR WITHOUT
EARTH SWITCH
(CTR:2000-1000/1-1-1-1-1A) (CTR: (CTR:2000-1000/1-1-1-1-1A) (CTR:2000-1000/1-1-1-1-1A)
2000-1000/1-1-1-1-1A)
ISOLATOR WITH
EARTH SWITCH

WAVE TRAP

220 kV Bus B1
(PTR: POTENTIAL TRANSFORMER
220kV/110V

220 kV Bus B2
POWER TRANSFORMER
(PTR:
220kV/110V
CAPACITOR VOLTAGE
TRANSFORMER

CONDUCTOR/EARTH-WIRE DETAIL

220 kV BUS TWIN MOOSE (54/7/3.53mm)

(CTR:2000-1000/1-1-1-1-1A) 220 kV LINE TWIN ZEBRA (54/7/3.18mm)


(CTR:300-150/1-1-1-1-.577A)
T1 EARTH-WIRE GSS (7/3.15mm)
(100 MVA)
Y QUAD MOOSE (54/7/3.53mm)
(220/66)KV 66 kV BUS
TC: ON LOAD
Y No.of Taps:17
NormalTap:9b 66 kV LINE

(CTR:1000-500/1-1-1-1-1A)
11 kV BUS

11 kV LINE

66 kV Bus B1
(PTR:
66kV/110V

DC SYSTEM STATUS
B2 (PTR:
66kV/110V BATTERY BANK BATTERY CHARGER
DC VOLTAGE
CAPACITY STATUS RATING STATUS

(CTR:2000-1000/1-1-1-1-1A) 220 V 400Ah Functional Functional

(CTR: (CTR: (CTR: Boost:2x40A


(CTR: 48 V 400Ah Functional Functional
200-100/1-1-1-1-.577A) 200-100/1-1-1-1-.577A) 200-100/1-1-1-1-.577A) Float:2x40A
200-100/1-1-1-1-.577A)

T2 T3 T4
T1 66/11 kV
66/11 kV 66/11 kV
66/11 kV 20 MVA
20 MVA 20 MVA
20 MVA
TC: ON LOAD TC: ON LOAD
TC: ON LOAD TC: ON LOAD No.of Taps:17
No.of Taps:17 No.of Taps:17
No.of Taps:17 NormalTap:5 NormalTap:5
NormalTap:5 NormalTap:5

11 kV BOARD 11 kV BOARD 11 kV BOARD 11 kV BOARD


SINGLE LINE DIAGRAM OF 220/66 KV SUB-STATION, UPERELA NANGAL 18
AS ON: 06-01-2016

(D/C LINE) (D/C LINE) (D/C LINE) (D/C LINE) (S/C LINE)
[3.569 km] [3.569 km] [24.562km] [7.80km] [0.30km]
PGCIL REHRU-I PGCIL REHRU-II BADDI MANDHALA VARDHMAN

SINGLE ZEBRA
LEGEND

LIGHTENING ARRESTOR

CIRCUIT BREAKER

CURRENT TRANSFORMER

ISOLATOR WITHOUT
(CTR:2000-1000/ (CTR:2000-1000/ (CTR:2000-1000/ (CTR:100-50/ EARTH SWITCH
(CTR:2000-1000/
1-1-1-1-1A) 1-1-1-1-1A) 1-1-1-1-1A) 1-1-1-1-1A)
1-1-1-1-1A)
ISOLATOR WITH
EARTH SWITCH

WAVE TRAP
220 kV Bus B1
(PTR: POTENTIAL TRANSFORMER
220kV/110V

220 kV Bus B2
POWER TRANSFORMER
(PTR:
220kV/110V
CAPACITOR VOLTAGE
TRANSFORMER

(CTR:1500-750/1-1-1-1-1A)
CONDUCTOR/EARTH-WIRE DETAIL
(CTR:300-150/1-1-1-1-.577) (CTR:300-150/1-1-1-1-.577)
220 kV BUS TWIN MOOSE(54/7/3.53 mm)
T1 (100 MVA)
T2 (100 MVA)
Y (220/66)KV Y (220/66)KV
TC: ON LOAD 220 kV LINE TWIN ZEBRA (54/7/3.18 mm)
No.of Taps:17 TC: ON LOAD
Y NormalTap:9b Y No.of Taps:17
NormalTap:9b EARTH-WIRE GSS - (7/3.15 mm)
(CTR:1000-500/ (CTR:1000-500/
1-1-1-1-.577A) 1-1-1-1-.577A) 66 kV BUS QUAD MOOSE(54/7/3.53 mm)

66 kV LINE ACSR 1. ZEBRA(54/7/3.18 mm)


2. PANTHER(30/7/3.00mm)

66 kV Bus B1 DC SYSTEM STATUS


(PTR: BATTERY BANK BATTERY CHARGER
66kV/110V DC VOLTAGE
CAPACITY STATUS RATING STATUS

220 V 400 Ah Functional Boost:2x60A Functional


B2 (PTR: Float:2x60A
66kV/110V
48 V Boost:2x40A
400 Ah Functional Functional
Float:2x40A

(CTR: )

(CTR:500-250-125/ (CTR:1200-600/ (CTR:1200-600/


(CTR:200-100/ 1-1-1-1A)
1-1-1-1A) 1-1-1-1A)
1-1-1-1A)

(ACSR-2) (ACSR-2) (ACSR-1) (ACSR-1)

JP AMBUJA Nalagarh-I Nalagarh-II


[21.078 km] [3.510 km] [3.510 km]
[9.837 km]
(S/C LINE) (D/C LINE) (D/C LINE)
(S/C LINE)
19

132 kV Sub-Stations/
Power Houses
SINGLE LINE DIAGRAM OF 132/33/11KV SUBSTATION AMB 20
AS ON: 21-01-2016

(D/C LINE) (D/C LINE)


LEGEND (S/C LINE) (S/C LINE) CONDUCTOR/EARTH-WIRE DETAIL
[27.49 km] [27.49 km]
[31.33 km] [7.8 km]
DEHRA-2 DEHRA-1 Una Outgoing Feeder Gagret Outgoing Feeder
132 kV BUS ACSR- ZEBRA(54/7/3.18mm)
LIGHTENING ARRESTOR

132 kV LINE ACSR-PANTHER (30/7/3.00 mm)


CIRCUIT BREAKER
EARTH-WIRE GSS-(7/3.15 mm)
CURRENT TRANSFORMER
33 kV BUS ACSR- ZEBRA(54/7/3.18mm)
ISOLATOR WITHOUT
EARTH SWITCH AAAC-7/4.26mm
33kV LINE ACSR-6/1/4.09mm

ISOLATOR WITH 11 kV BUS INDOOR COPPER STRIP


EARTH SWITCH
AAAC-1. 7/4.26mm
2. 7/3.81mm
WAVE TRAP (CTR: 500-250/1-1-1) (CTR: 500-250/1-1-1) (CTR: 500-250/1-1-1) (CTR: 500-250/1-1-1) ACSR-1. 6/1/4.72mm
11kV LINE
2. 6/1/2.59mm
SF6 SF6 SF6 SF6 3. 6/1/3.35mm
4. 6/1/2.11mm
POTENTIAL TRANSFORMER

POWER TRANSFORMER 132 kV Bus


DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


DC VOLTAGE
CAPACITOR VOLTAGE (PTR:132 kV/110 V)
TRANSFORMER CAPACITY STATUS RATING STATUS
SF6 SF6
220 V 200Ah Boost:60A
(CTR:150-75/1-1-1-0.577) Functional Functional
(CTR:150-75/1-1-1-0.577) Float:40A

T2 T1 48 V 400Ah Boost:60A
(25/31.5 MVA) Functional Float:40A Functional
(16 MVA)
Y (132/33 kV) Y (132/33 kV)
TC: ON LOAD TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17
NormalTap:5 NormalTap:5

(CTR:600-300/1-1-1-0.577) (CTR:600-300/1-1-1-0.577)

VCB VCB

VCB
33 kV Bus

(CTR:600-300/1-1) VCB
VCB VCB (CTR:
(PTR:33 kV/110 V) 300-150/1-1)
(CTR:200-100/1-1) (CTR:200-100/1-1)
VCB
Y 33/11 kV Y 33/11 kV (CTR:
VCB VCB T2,5 MVA T1,5 MVA VCB VCB 10-5/1-1) VCB
Y TC: Off LOAD Y TC: Off LOAD (CTR:
(CTR: (CTR: No.of Taps:5
(CTR: (CTR:
150-75/1-1) 200-100/1-1) No.of Taps:5 400-200/1-1) 400-200/1-1) 300-150/1-1)
NormalTap:3 NormalTap:3 33/0.4 kV
(CTR:1200-600/ (CTR:1200-600/ 250 KVA
5-5-.577A) 5-5-.577A)
VCB VCB
Stn. Xfmr
Bharwain Daulatpur Baruhi Gagret Him Alloy
[14.838km] [17.30km] [15.50km] [7.355km] [0.380km]
(AAAC) (AAAC) (ACSR) (AAAC) (AAAC)
VCB
11 kV Bus

(CTR:1200-600/ (2x2.5 MVAR)


VCB VCB VCB VCB VCB VCB VCB VCB Capacitor Bank
5-5A)
(FUNCTIONAL)
CTR:300-150/1A

(CTR:400-200/ (CTR:400-200/ (CTR:200-100/ (CTR:200-100/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/


5-5A) 5-5A) 1-1A) 1-1A) 5-5A) 5-5A) 5-5A)

KOHAR CHHAN SIDHPUR DHUSARA PANJOA SONALIKA AMB JAWAR


[32km] [20.0km] [7.40km] [52.295km] [7.14km] [50.150km]
[1.480km]
(AAAC-1&2 (AAAC-1& (AAAC-1) (AAAC-1&2 (ACSR-3&4) (AAAC-1&2
(ACSR-3)
ACSR-2) ACSR-2) ACSR-4) ACSR-4)
(1.8+1.2 MVAR)
CAPACITOR BANK
(FUNCTIONAL)
21

SINGLE LINE DIAGRAM OF 132 kV SUB-STATION BAGGA CONDUCTOR/EARTH-WIRE DETAIL

132 kV BUS ACSR - MOOSE (54/7/3.54 mm)


(16.205 km) (13.563 km)
KANGOO DARLAGHAT 132 kV LINE ACSR - PANTHER (30/7/3.00 mm)

EARTH-WIRE GSS - (7/3.15 mm)

LEGEND

LIGHTENING ARRESTOR

CIRCUIT BREAKER

CURRENT TRANSFORMER
(CTR:500/1) (CTR:500/1)
ISOLATOR WITHOUT
EARTH SWITCH

ISOLATOR WITH
EARTH SWITCH
132kV BUS
B1
WAVE TRAP

POTENTIAL TRANSFORMER

(CTR:500/1) POWER TRANSFORMER

CAPACITOR VOLTAGE
TRANSFORMER

DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


DC VOLTAGE
CAPACITY STATUS RATING STATUS

220 V

48 V
JPCCL
SINGLE LINE DIAGRAM OF 132/33 kV SUB-STATION BAJAURA, KULLU(H.P.)
AS ON: 12-01-2016 22
(D/C LINE) (D/C LINE) (D/C LINE) (D/C LINE)
[24.11 km] [24.11 km] [73.199 km] [20.196 km]
MALANA CKT-I MALANA CKT-II KANGOO LARJI

CONDUCTOR/EARTH-WIRE DETAIL

132 kV BUS ZEBRA (54/7/3.18mm)

132 kV LINE PANTHER (30/7/3.00mm)

EARTH-WIRE GSS (7/3.15mm)

33 kV BUS ZEBRA (54/7/3.18mm)

33kV LINE ACSR- DOG(6/1/4.72mm)


(CTR:600-300/ (CTR:600-300/ (CTR:500-250/ (CTR:500-250/ AAAC- 7/4.26mm
1-1-1-1-1A) 1-1-1-1-1A) 1-1-1-1A) 1-1-1-1A)
SF6 SF6 SF6 SF6
PTR:
(132kV/110V)

Y
Y

132 kV Bus B1 LEGEND


PTR:
Y Y (132kV/110V)
Y LIGHTENING ARRESTOR

B2
CIRCUIT BREAKER

SF6 CURRENT TRANSFORMER

SF6 (CTR:500-250/1-1-1) SF6 ISOLATOR WITHOUT


EARTH SWITCH
(CTR:150-75/1-1-1-1-.577A) (CTR:150-75/1-1-1-1-.577A)

ISOLATOR WITH
EARTH SWITCH

WAVE TRAP
T2 (25/31.5 MVA) T1 (25/31.5 MVA)
(132/33 KV) (132/33 KV)
TC: ON LOAD TC: ON LOAD POTENTIAL TRANSFORMER
No.of Taps:17 No.of Taps:17
NormalTap:5 NormalTap:5

(CTR:600-300/1-1-1-.577A) (CTR:600-300/1-1-1-.577A) POWER TRANSFORMER


PTR: VCB VCB PTR:
(33kV/110V) (33kV/110V)
CAPACITOR VOLTAGE
Y Y Y TRANSFORMER
Y VCB Y
33 kV Bus B1

(CTR:600-300/1-1A) DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


DC VOLTAGE
VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB CAPACITY STATUS RATING STATUS
(CTR:400-200/
(CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR: 1-1-1A) (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ 220 V 200Ah Functional
Boost:30A
Functional
1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) Float:20A
10-5/1-1-1A)
48 V Boost:30A
400Ah Functional Float:15A
Functional

33/0.415 kV
250kVA Cells

Series Series
Bhuntar Kullu Manali Mani-karan Reactor Reactor
Spare Bay Gadsa Thalout-I Thalout-II Spare Bay
[4.00km] [16.00km] [31.10km] [27.840km] (2*3.6 MVAR Cap. bank) [12.015km] [20.0km] [20.0km]
Stn. Xfmr
(ACSR) (ACSR) (ACSR) (AAAC) (BOTH BANKS FUNCTIONAL) (AAAC) (ACSR) (ACSR)
SINGLE LINE DIAGRAM OF 132/66/11 kV SUB-STATION, BAROTIWALA 23
AS ON: 06-01-2016

(D/C LINE) (D/C LINE) (S/C LINE)


[26.03km] [26.03km] [1.0km]
KUNIHAR-I KUNIHAR-II INOX

(CTR:500-250/1-1-1-1-1A) (CTR:400-200/1-1-1-1-1A) (CTR: 150-75/1-1-1-1A)

SF6 SF6 SF6

132KV BUS B1
PT
132 kV/110 V

132KV BUS B2

PT
132 kV/110 V
St. Xmer SF6
11/0.4kV
(CTR: (CTR:
400-200/1-1) 400-200/1-1)
Baddi-1 U.T. SRForging SF6 OPTEC SF6 Baddi2 SF6 SF6 SF6 (CTR:300-150/ SF6 SF6
(CTR:300-150/ (CTR:300-150/
(CTR:150-75/ 1-1-1-1-.577A) 1-1-1-1-.577A)
(CTR:150-75/ (CTR:150-75/ 1-1-1-1-.577A) (CTR:150-75/
1-1-1-1-.577) 1-1-1-1-.577) 1-1-1-1-.577) B/wala 4 EPIP5 T2 132/66 kV B/Wala2 B/Wala5 B/Wala7 1-1-1-1-.577) B/wala 8
T3 132/11 kV
Y T1 132/66 kV Y 25/31.5 MVA
Y T3 132/66 kV
T1, 132/11 kV 25/31.5 MVA 25/31.5 MVA T4 132/11 kV
Y T2 132/11 kV Y 25/31.5 MVA Y 16/20 MVA TC: ON LOAD
Y 25/31.5 MVA
25/31.5 MVA
TC: ON LOAD TC: ON LOAD Y TC: ON LOAD Y No.of Taps:17 Y TC: ON LOAD
No.of Taps:17 TC: ON LOAD
No.of Taps:17
Y TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17 NormalTap:5
NormalTap:5 NormalTap:5 Y No.of Taps:17
No.of Taps:17 NormalTap:5 CTR: NormalTap:5 NormalTap:5
CTR: CTR: CTR: NormalTap:5 CTR: CTR: 50-25/1 CTR: CTR: (CTR:600-300/ (CTR:600-300/ CTR: CTR: CTR: CTR:
400-200/1 400-200/1 400-200/1 500-250/5-5 (CTR:600-300/ 400-200/1 400-200/1 400-200/1 200-100/1
200-100/1 400-200/1 500-250/5-5 1-1-1-1.577A) 1-1-1-1.577A) 1-1-1-1.577A)
(CTR:2400-1200/ (CTR:1800-900/ (CTR:1100/5-5-.577) MOCB MOCB MOCB CTR:1800/
1-1-1-.577A) 1-1.577A) 1-1-1-.577A
VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB
VCB VCB VCB
VCB VCB (CTR:
11KV BUS 11 kV Bus
600-300/1)
VCB 66 kV Bus
VCB VCB VCB
VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB
(DAMAGED)
PT CTR: CTR: CTR:
CTR: CTR: CTR: CTR: CTR: CTR: CTR: CTR: CTR: CTR: 400-200/1 400-200/1 200-100/1
CTR:
400-200/1 250-125/1 200-100/1 200-100/1 400-200/1 400-200/1 500-250/5-5 500-250/5-5 500-250/5-5 400-200/1 400-200/1

(CTR: 300-150 (CTR: (CTR:400-200/ (CTR:800-400/


/1-1-1) 200-100/1) 1-1-1A) 1-1A)

EPIP1 USV EPIP4 HARIPUR Hill Top EPIP3 Patta Baddi3 EPIP2 B/Wala6 B/Wala3 Ranbaxy B/Wala1 Gridwell

3 MVAR 3 MVAR 3 MVAR 5 MVAR


CAPACITOR BANK CAPACITOR BANK CAPACITOR BANK CAPACITOR BANK
(FUNCTIONAL) (FUNCTIONAL) 10MVAR (NON-FUNCTIONAL)
(NON-FUNCTIONAL) CAPACITOR BANK
LEGEND
Parwanoo Cadbury Baddi-I (FUNCTIONAL) Nalagarh Baddi-II
(17.21 km.) (0.72km.) (3.25 km.) (19.995 km) (3.82 km.)
LIGHTENING ARRESTOR (S/C LINE) (S/C LINE) (S/C LINE)

CIRCUIT BREAKER

CURRENT TRANSFORMER

ISOLATOR WITHOUT
EARTH SWITCH CONDUCTOR/EARTH-WIRE DETAIL

132 kV BUS ZEBRA (54/7/3.18mm)


ISOLATOR WITH
EARTH SWITCH
132 kV LINE PANTHER (30/7/3.00mm)
WAVE TRAP
EARTH-WIRE GSS(7/3.15mm)
DC SYSTEM STATUS
POTENTIAL TRANSFORMER 66 kV BUS ZEBRA (54/7/3.18mm)
BATTERY BANK BATTERY CHARGER
DC VOLTAGE
66 kV LINE POPLAR-I (37/2.88mm) CAPACITY STATUS RATING STATUS
POWER TRANSFORMER
400Ah Boost:2x40A
33kV LINE 220 V Functional Functional
Float:2x40A

CAPACITOR VOLTAGE Boost:2x60A


48 V 400Ah Functional Float:2x60A Functional
TRANSFORMER
SINGLE LINE DIAGRAM OF 132/33/11kV SUB-STATION BASSI
AS ON: 20-01-2016
24
(S/C LINE) (S/C LINE) (S/C LINE) (D/C LINE) (D/C LINE)
[16.94 km] [49.75 km] [32.00 km] [5.25 km] [5.25 km]
CHULLA HAMIRPUR PALAMPUR SHANAN-I SHANAN-II CONDUCTOR/EARTH-WIRE DETAIL

132 kV BUS MOOSE (54/7/3.54mm)

132 kV LINE PANTHER (30/7/3.00mm)

EARTH-WIRE GSS (7/3.15 mm)

33 kV BUS WOLF (30/7/2.59mm)

33 kV LINE WOLF (30/7/2.59mm)

11 kV BUS INDOOR COPPER STRIP


(CTR: (CTR: (CTR: (CTR: (CTR:
500-250/1-1) 400/1) 400/1) 400/1) 400/1)
11 kV LINE ACSR- 6/1/3.35 mm
SF6-CB SF6-CB SF6-CB SF6-CB SF6-CB

LEGEND
SF6-CB
132kV Bus B1 B2
LIGHTENING ARRESTOR
(CTR:400/ (CTR:400/
(PTR: 1A) 1A)
132kV/110V/110V) (PTR: CIRCUIT BREAKER
132kV/110V/110V)
SF6-CB SF6-CB SF6-CB SF6-CB CURRENT TRANSFORMER
SF6-CB
(CTR: 400/1) (CTR: 400/1) (CTR: 400/1) (CTR: 400/1)
(CTR: 400/1) ISOLATOR WITHOUT
EARTH SWITCH

GT1 ISOLATOR WITH


T1 (16 MVA) GT2 GT3 GT4 EARTH SWITCH
(132/33 KV) (3x6.8/7.5 MVA) (3x6.8/7.5 MVA) (3x6.8/7.5 MVA) (3x6.8/7.5 MVA)
(11/132 KV) (11/132 KV) (11/132 KV) (11/132 KV)
TC: ON LOAD
No.of Taps:17 TC:Off LOAD TC:Off LOAD TC:Off LOAD TC:Off LOAD WAVE TRAP
NormalTap:8 No.of Taps:5 No.of Taps:5 No.of Taps:5 No.of Taps:5
NormalTap:3 NormalTap:3 NormalTap:3 NormalTap:3
(CTR: 300/1)
(CTR:1000/ (CTR:1000/ (CTR:1000/ POTENTIAL TRANSFORMER
VCB (CTR:1000/
1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A)
PT
[11kV/110V] PT PT PT POWER TRANSFORMER
[11kV/110V] [11kV/110V] [11kV/110V]
UNIT-I UNIT-II UNIT-III UNIT-IV
(16.667 MW) (16.667 MW) (16.667 MW) (16.667 MW)
33 KV BUS B1 CAPACITOR VOLTAGE
TRANSFORMER

DC SYSTEM STATUS

OCB BATTERY BANK BATTERY CHARGER


VCB VCB VCB DC VOLTAGE
(CTR:150-75/1A)
(CTR:100/1) (CTR:150/1) (CTR:150/1) CAPACITY STATUS RATING STATUS

220 V 750Ah Functional Boost:98A Functional


Float:49A

48 V 400Ah Non- Boost:13A


Functional Float:13A Functional
T1 T2
(2.5 MVA) (2.5 MVA)
(33/11 KV) (33/11 KV)
Makriri GWALI MARANDA
[12.7 km] [43.265 km] [39 KM] TC:ON LOAD TC:ON LOAD
No.of Taps:5 No.of Taps:5
Y NormalTap:2 Y NormalTap:2

(CTR: 200/5) (CTR: 200/5)


PTR VCB PTR VCB
[11kV/110V] [11kV/110V]
11 kV Bus VCB

VCB
VCB VCB
VCB VCB VCB VCB VCB

(CTR:200/5) (CTR:30/5) (CTR:30/5) (CTR:100/5) (CTR:100/5) (CTR:200/5)

11/0.4 kV
400kVA
(PTR:
11kV/110V)
SHANAN BASSI BALAKRUPI TIKKRU Joginder
[5.25km] [0.50km] [10 KM] [6.0km] Nagar
Station Xfmr. [10.426km]

(0.6 MVAR)
CAPACITOR BANK
(Functional)
SINGLE LINE DIAGRAM OF 132/33/11 kV SUB-STATION BATHRI
AS ON: 15-01-2016 25
(45.440 km) (45.440 km) (38.54 km)
KURTHALA-I KURTHALA-II JASSORE
CONDUCTOR/EARTH-WIRE DETAIL LEGEND

132 kV BUS ACSR- ZEBRA(54/7/3.18mm)


LIGHTENING ARRESTOR

132 kV LINE ACSR-PANTHER (30/7/3.00 mm)


CIRCUIT BREAKER
EARTH-WIRE GSS-(7/3.15 mm)
(CTR:500-250/ CURRENT TRANSFORMER
1-1-1-1-1A) ACSR- ZEBRA (54/7/3.18 mm)
33 kV BUS
ISOLATOR WITHOUT
EARTH SWITCH
33kV LINE DOG

11 kV BUS ISOLATOR WITH


(CTR:500-250/ (CTR:500-250/ EARTH SWITCH
1-1-1-1-1A) 1-1-1-1-1A)
11 kV BUS
(CB-SF6) (CB-SF6) (CB-SF6) WAVE TRAP

DC SYSTEM STATUS
POTENTIAL TRANSFORMER
BATTERY BANK BATTERY CHARGER
132kV BUS B1 DC VOLTAGE
CAPACITY STATUS RATING STATUS
POWER TRANSFORMER
PTR: Boost:30A
220 V 200Ah Functional Functional
132kV/110V Float:20A

Boost:60A CAPACITOR VOLTAGE


(CB-SF6) (CB-SF6) 48 V 400Ah Functional Float:60A
Functional
TRANSFORMER
(CTR:150-75/ (CTR:150-75/
1-1-1-1A) 1-1-1-1A)
T1, (25/31.5 MVA)
Y Y T2, (25/31.5 MVA)
(132/33 KV)
(132/33 KV)
TC: ON LOAD TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17
NormalTap:5 NormalTap:5

(CTR:600-300/
(CTR:600-300/
1-1-1-1-1A)
1-1-1-1-1A)
MOCB VCB
PTR:
33kV/110V PTR:
(CTR:600-300/ 33kV/110V
1-1-1-1-1A)
33kV BUS BAR
B1 B2
MOCB

(CTR:150-75/ (CTR:400-200/ (CTR:150-75/ (CTR:400-200/ (CTR:10-5/ (CTR:10-5/ (CTR:600-300/ (CTR:150-75/ (CTR:150-75/


1-1A) 1-1A) (CTR:150-75/ (CTR:150-75/ 1-1A)
1-1A) 1-1A) 1-1A) 1-1A) 1-1A) 1-1A)
1-1A) 1-1A)
MOCB MOCB MOCB MOCB MOCB MOCB MOCB MOCB
MOCB MOCB
MOCB MOCB (CTR:
300-150/1-1)
T1 33/11 kV T2 33/11 kV
1.6 MVA 1.6 MVA
TC:Off LOAD TC:Off LOAD
No.of Taps:5 No.of Taps:5
NormalTap:2 NormalTap:2

(CTR:200-100/ (CTR:200-100/
33/0.4 kV 5-5A) 5-5A)
200 KVA
VCB (CTR:200-100/ VCB
33/0.4 kV
5-5A)
200 KVA Residual
Voltage Xfmr
DALHOUSIE BAKLOH BAIRASUIL KOTI CHAMBA CHAMERA SPARE
[12 KM] [9.00 KM] STAGE-1
PTR: PTR:
ACSR ACSR STN.Xmer VCB VCB 11kV/110V VCB STN.Xmer
11kV/110V
(6/1/4.7mm) (6/1/4.7mm) No.1 No.2
BAKLOH (CTR:100-50/ (CTR:100-50/ (CTR:100-50/
5-5A) Capacitor Bank-1 Capacitor Bank-2
5-5A) 5-5A)
HOSPITAL KAKISE (3.6 MVAR) (3.6 MVAR)
[1.395 KM] [15.520 KM]
[BOTH FUNCTIONAL]
ACSR ACSR
(6/1/2.59mm) (6/1/2.59mm)
(7/3.15mm)
TUNIHATTI [12.56+2.96]KM WSS WSS BATHRI
[37.22 KM] DEVI DEHRA CHOWTRA LOCAL
ACSR
(6/1/2.59mm) NAINIKHAD
(6/1/2.11mm) [35.44 KM]
AAAC ACSR
(7/3.15/2.59mm) (6/1/2.59mm)
[29.42+6.3+1.5]KM (6/1/2.11mm)
[29.2+6.24]KM
SINGLE LINE DIAGRAM OF 132/11 kV SUB-STATION DARLAGHAT 26
AS ON: 05-01-2016
[13.563 km] LEGEND
[22.301 km]
KUNIHAR BAGGA
D/C (CKT-1) D/C (CKT-1)
LIGHTENING ARRESTOR

CIRCUIT BREAKER

CURRENT TRANSFORMER

ISOLATOR WITHOUT
EARTH SWITCH

ISOLATOR WITH
EARTH SWITCH

CTR:500-250/1-1 CTR:500-250/1-1 WAVE TRAP

SF6 (CGL) SF6 (CGL)


POTENTIAL TRANSFORMER

132KV BUS POWER TRANSFORMER

CAPACITOR VOLTAGE
PTR: 132 kV/110 V
TRANSFORMER

SF6 (CGL) SF6 (ABB)

CTR:150-75/1-1-0.577 CONDUCTOR/EARTH-WIRE DETAIL


CTR:500-250/1
132 kV BUS ACSR - ZEBRA (54/7/3.18 mm)
7.5 MVA
132/11 kV
Y
TC: ON LOAD 132 kV LINE ACSR - PANTHER (30/7/3.00 mm)
No.of Taps:17
Y NormalTap:7
EARTH-WIRE GSS - (7/3.15 mm)
CTR:800-400/5-5-5-0.577A
11 kV BUS Indoor Copper Strip

VCB
AMBUJA 11 kV LINE AAA- (7/3.15 mm)
[1.918 km]
11KV BUS PTR: 11 kV/110 V
DC SYSTEM STATUS

VCB VCB VCB VCB VCB BATTERY BANK BATTERY CHARGER


DC VOLTAGE
CTR: CTR: CTR: CTR: CTR: CAPACITY STATUS RATING STATUS
200-100/5-5-5 200-100/5-5-5 200-100/5-5-5 200-100/5-5-5 200-100/5-5-5

220 V 200Ah Functional Boost:50A


Functional
Float:50A
100 kVA
DARLAGHAT/ NAVGAON/ BHARARI GHAT/ DHUNDAN/ 11/0.4 kV 48 V 100Ah Boost:50A Ageing
Functional Float:50A
CHANDA MANGAL/ PARNOO NALAG THALA Y Functional
SUNNI BORDER [11.00 km] [14.00 km] [9.00 km]
[40.00 km] [MULTIPLE [MULTIPLE [MULTIPLE
[MULTIPLE TAPPINGS] TAPPINGS] TAPPINGS] TAPPINGS] S/STN XFMR
SINGLE LINE DIAGRAM OF 132/33/11kV, 2x16 MVA SUB-STATION DEHAN,PALAMPUR
AS ON: 12-01-2016 27
[32.041 km]
BASSI

DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


DC VOLTAGE
CAPACITY STATUS RATING STATUS

Boost:2x40A
220 V 400Ah Functional Functional
LEGEND Float:2x40A

48 V 100Ah Functional Functional


LIGHTENING ARRESTOR
CONDUCTOR/EARTH-WIRE DETAIL
CIRCUIT BREAKER
CTR:500-250/1-1-1 220 kV BUS - KARANKULA (33/5.23 mm)
CURRENT TRANSFORMER
SF6-CB 220 kV LINE ACSR - ZEBRA (54/7/3.18 mm)
ISOLATOR WITHOUT
EARTH SWITCH EARTH-WIRE GSS - (7/3.15 mm)

132 KV BUS
ISOLATOR WITH 66 kV BUS - KARANKULA (33/5.23 mm)
EARTH SWITCH
66 kV LINE ACSR - PANTHER (30/7/3.00 mm)
AAA - (37/2.88 mm)
WAVE TRAP PTR: 132 kV/110 V
SF6 CB SF6 CB Make: BHEL 33 kV BUS ACSR - ZEBRA (54/7/3.18 mm)
Make: ABB Make: ABB
POTENTIAL TRANSFORMER
CTR: CTR: 33 kV LINE - (30/2.59 mm)
150-75/1-1-1-0.577 150-75/1-1-1-0.577
11 kV BUS Indoor Copper Strip
POWER TRANSFORMER
11 kV LINE - (7/4.26 mm)
T-1 T-2
25/31.5MVA Y 25/31.5MVA Y
CAPACITOR VOLTAGE 132/33kV
TRANSFORMER 132/33kV
TC: ON LOAD Y TC: ON LOAD Y
No.of Taps:17 No.of Taps:17
CTR: NormalTap:5 CTR:
NormalTap:5
600-300/1-1-1-0.577 A 600-300/1-1-1-0.577 A
VCB VCB

PTR:33kV/110V PTR:33kV/110V

VCB

CTR:300-150/1A
VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB

400-200/1-1A 400-200/1-1A 400-200/1-1A 400-200/1-1A 150-75/1-1A 400-200/1-1A 300-150/1-1A 400-200/1-1A 400-200/1-1A 150-75/1-1A 400-200/1-1A 300-150/1-1A 400-200/1-1A

10-5/1-1A

OPCL-I OPCL-II ASTHA-II T-2


PATTI Thural KHERA Spare
Maranda-I Baner-II Maranda-II 33/0.4kV Astha-1 Baner-I Bay
Y T-1 Y Y 4 MVA
TC: ON LOAD 33/0.4kV TC: ON LOAD
33kV (2x2.5 MVAR) No.of Taps:17 4 MVA 33/0.4 kV No.of Taps:17
Capacitor Bank NormalTap:7 250 kVA NormalTap:7
STN. XFMR
(NON-FUNCTIONAL)

CTR:800-400/5-5-5-0.577 CTR:800-400/5-5-5-0.577

CTR:
600-300/1-1-1A
PTR:11kV/110V PTR:11kV/110V

VCB
VCB VCB VCB VCB VCB BUS COUPLER VCB
VCB VCB VCB VCB
CTR:300-150/1A
CTR: CTR: CTR: CTR: CTR: CTR: CTR: CTR:
500-250/1-1-1A 250/1-1-1A 250/1-1-1A 250/1-1-1A 250/1-1-1A 250/1-1-1A 250/1-1-1A 250/1-1-1A

SPARE SPARE BHALWANA HPKV SPARE SPARE PALAMPUR KHAIRA


11 KV INCOMER 11 KV INCOMER
NO.-1 NO.-1

11kV (1.2+1.8) MVAR


Capacitor Bank
(FUNCTIONAL)
SINGLE LINE DIAGRAM OF 132/33/11 kV SUB-STATION DEHRA
AS ON: 13-01-2016 28
(D/C LINE) (D/C LINE) (S/C LINE) (D/C LINE) (D/C LINE) (D/C LINE) (D/C LINE)
[60.639 km] [60.639 km] [29.935 km] [43.123 km] [43.123 km] [27.492km] [27.492km] CONDUCTOR/EARTH-WIRE DETAIL
JASSORE-1 JASSORE-2 KANGRA HAMIRPUR-II-2 HAMIRPUR-II-1 AMB-1 AMB-2
132 kV BUS ACSR- ZEBRA(54/7/3.18mm)

132 kV LINE ACSR-PANTHER (30/7/3.00 mm)

EARTH-WIRE GSS-(7/3.15 mm)

33 kV BUS ACSR- ZEBRA (54/7/3.18 mm)

ACSR(6/1/4.72mm)
33kV LINE AAAC(7/4.26mm)

11 kV BUS INDOOR COPPER STRIP

ACSR(6/1/3.35mm)
(CTR: (CTR:500-250/ (CTR:300-150/ (CTR: (CTR: 11kV LINE AAAC(7/4.26mm)
(CTR:500-250/ (CTR:500-250/ 300-150/1-1-1-1-1) 1-1-1-1A) 1-1-1-1-1A) 300-150/1-1-1-1-1) 300-150/1-1-1-1-1)
1-1-1-1A) 1-1-1-1A)
SF6 SF6 SF6 SF6 SF6 SF6 SF6

DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


132 kV DC VOLTAGE
Bus B1
CAPACITY STATUS RATING STATUS
(PTR:
132kV/110V) 220 V 200Ah Boost:30A
Functional Functional
Float:20A

B2 48 V 400Ah Functional Boost:60A


Float:40A Functional

(PTR:
132kV/110V)
SF6
LEGEND
SF6 SF6
(CTR:150-75/ (CTR:150-75/ (CTR:
300-150/1-1-1-1-1)
1-1-1-1-.577A) 1-1-1-1-.577A) LIGHTENING ARRESTOR
T2 (16/20 MVA) T1 (16/20 MVA)
132/33 KV 132/33 KV
CIRCUIT BREAKER
TC: ON LOAD
TC: ON LOAD
No.of Taps:17
No.of Taps:17 NormalTap:5
NormalTap:5 CURRENT TRANSFORMER
(CTR:600-300/ (CTR:600-300/
1-1-1A) 1-1-1A) ISOLATOR WITHOUT
EARTH SWITCH
VCB VCB

ISOLATOR WITH
EARTH SWITCH

33 kV Bus B1
WAVE TRAP

(PTR: (PTR:
33kV/110V) POTENTIAL TRANSFORMER
33kV/110V)

(CTR:150-75/1-1A) (CTR:100-50/1-1-1A) MOCB MOCB VCB


MOCB MOCB MOCB MOCB
(CTR:150-75/ POWER TRANSFORMER
MOCB MOCB (CTR:
(CTR: (CTR: (CTR: 1-1A)
(CTR: (CTR: 150-75/1-1)
(CTR: 400-200/1-1-1A) 150-75/1-1) 400-200/1-1) 150-75/1-1) 150-75/1-1)
10-5/1-1) T1 T2
33/11 kV 33/11 kV CAPACITOR VOLTAGE
4 MVA 4 MVA TRANSFORMER
33/0.4 kV
250kVA TC:Off LOAD TC:Off LOAD
No.of Taps:5 No.of Taps:5
NormalTap:2 NormalTap:2

OCB OCB Cells


(PTR: (PTR:
11kV/110V) 11kV/110V)
Stn. Xfmr Series Series
Haripur Dada-Siba Nadaun Pragpur Kangra Spare Bay Reactor Reactor
(CTR:300-150/ (CTR:300-150/ [14.856km]
[15.050km] [18.750km] [24.170km] [13.150km]
1-1-1A) 1-1-1A) (ACSR) (2*3.6 MVAR Cap. bank)
(ACSR) (AAAC) (ACSR) (AAAC) (FUNCTIONAL)
CT Defective
(CTR:300-150/1-1A)
11 kV Bus

VCB OCB VCB


(CTR:150-250/ OCB OCB OCB VCB (CTR:150-250/
OCB OCB
1-1A) 1-1A)

CTR:(100-50/ CTR:200-100/ CTR:(100-50/ CTR:(100-50/ CTR:(100-50/ CTR:(100-50/


1-1A) 1-1A) 1-1A) 1-1A) 1-1A) 1-1A)

Kundli-har Dhaliara Pragpur Khabli Dehra Gummer


[32.485km] [70.680km] [10.167km] [21.640km] [7.102km] [28.300km]
(ACSR) (ACSR) (ACSR) (ACSR) (ACSR & AAAC)
(3 MVAR) (ACSR) (3 MVAR)
Capacitor Bank-I Capacitor Bank-II
(NON-FUNCTIONAL) (FUNCTIONAL)
SINGLE LINE DIAGRAM OF 132/33/11 KV S/STN, GAGRET 29
AS ON: 21-01-2016 LEGEND

(S/C LINE)
DC SYSTEM STATUS CONDUCTOR/EARTH-WIRE DETAIL [7.952 KM]
AMB LIGHTENING ARRESTOR
BATTERY BANK BATTERY CHARGER
DC VOLTAGE 132 kV BUS ACSR ZEBRA (54/7/3.15 mm)
CAPACITY STATUS CIRCUIT BREAKER
RATING STATUS
Boost:60A 132 kV LINE PANTHER (30/7/3.00mm)
Functional Float:40A Functional CURRENT TRANSFORMER
220 V 400Ah
Boost:60A
EARTH-WIRE OPGW
48 V 400Ah Functional Functional
Float:40A ISOLATOR WITHOUT
EARTH SWITCH
33 kV BUS ACSR ZEBRA (54/7/3.15 mm)

33 kV LINE AAAC (7/4.26mm) ISOLATOR WITH


ACSR (30/7/2.59) EARTH SWITCH

11 kV BUS INDOOR COPPER STRIP


WAVE TRAP
11 kV LINE AAAC (7/4.26mm) (CTR:500-250/1-1-1A)

POTENTIAL TRANSFORMER

POWER TRANSFORMER
132kV BUS BAR

CAPACITOR VOLTAGE
PTR: 132kV/110V TRANSFORMER

SF6 SF6
(CTR:200-100/1-1-1-0.577A)
(CTR:200-100/1-1-1-0.577A)
T1, (25/31.5 MVA) T2, (25/31.5 MVA)
Y (132/11 KV) Y (132/33 KV)
TC: ON LOAD TC: ON LOAD
No.of Taps:17
Y No.of Taps:17 Y NormalTap:5
NormalTap:5

(CTR:2400-1200/1-1-1A)
800-400/1-1-0.577
VCB
VCB
PT:
33/0.11kV

VCB
VCB VCB VCB VCB VCB VCB VCB VCB
(CTR:300-150/
1-1-1A)
(CTR:300-150/ (CTR:300-150/ (CTR:300-150/ (CTR:300-150/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (200-100/1-1-1A)
1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) VCB VCB VCB VCB VCB
11/0.4kV VCB
(CTR:400-200/ (CTR:150-75/ (CTR:400-200/ (CTR:300-150/ (CTR:200-100/
250kVA 1-1-1A)
(CTR:10-5/1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A)

33/0.4KV
SPARE SUPPER MAX INDUSTRY-2 INDUSTRY-1 BHARWAIN SPARE POLYTECHNIC 250kVA
[0.40m] [2.325km] [4.250km] (2x2.5 MVAR)
[4.420km] [2.625km] STN AUX XMER CAPACITOR BANK
(FUNCTIONAL)

STN AUX XMER

GAGRET MBD LUMINOUS SALSAN JEETPUR BEHRI


[1.502km] [0.400m] [1.200km] [0.140m] [3.775km]
(AAAC) (AAAC) (AAAC) (AAAC) (ACSR)
SINGLE LINE DIAGRAM OF 132/33 kV SUB-STATION GAURA, SOLAN (H.P.) AS ON: 07-01-2016 30

[8.58+12.082=20.622km] [51.911+8.58=60.491km]
(S/C) (S/C) SPARE
SOLAN-GAURA GIRI-GAURA SPACE

CONDUCTOR/EARTH-WIRE DETAIL

132 kV BUS ACSR- ZEBRA(54/7/3.18mm)(Twin)

132 kV LINE ACSR-PANTHER (30/7/3.00 mm)

EARTH-WIRE GSS-1. (7/3.15 mm) (upto Tower-148)


2. OPGW (Gaura to solan)

33 kV BUS ACSR- ZEBRA(54/7/3.18mm)(Twin)

ACSR- 6/1/4.72 mm
33 kV LINE AAAC- 7/4.26 mm
(CTR:500-250/1-1-1-1) (CTR:500-250/1-1-1-1)

132kV/110V SF6 SF6

132kV BUS

DC SYSTEM STATUS
BATTERY BANK
(VRLA Type)
BATTERY CHARGER
DC VOLTAGE
CAPACITY STATUS RATING STATUS
SF6
220 V 200Ah Float cum Functional
(CTR: 150-75/1-1-1-1) Functional Boost: 30A

48 V Functional Float cum


400Ah Boost: 60A Functional
T3
(16 MVA)+1TRF BANK
(132/33 KV)
Y TC: ON LOAD
No.of Taps:17
Y NormalTap: 5
LEGEND
(CTR: 600-300/1-1-1-1)
VCB
LIGHTENING ARRESTOR
33kV/110V

CIRCUIT BREAKER

33kV BUS CURRENT TRANSFORMER

ISOLATOR WITHOUT
EARTH SWITCH

VCB
ISOLATOR WITH
(CTR:15-7.5/1-1-1) VCB VCB VCB EARTH SWITCH
(CTR:400-200/1-1-1) (CTR:400-200/1-1-1) (CTR:400-200/1-1-1)
WAVE TRAP
100 kVA
33/0.4 kV
POTENTIAL TRANSFORMER

STATION POWER TRANSFORMER


TRF

SPARE GAURA RAJGARH CAPACITOR VOLTAGE


(Proposed SOLAN) FEEDER NO-II FEEDER NO-III TRANSFORMER
[1.150km] [14.00km]
(ACSR) (AAAC)
SINGLE LINE DIAGRAM OF 132/33/11 kV SUB-STATION AT POANTA
AS ON: 06-01-2016 LEGEND 31

CONDUCTOR/EARTH-WIRE DETAIL DC SYSTEM STATUS (17.517 km) LIGHTENING ARRESTOR


GIRI S/C line
132 kV BUS ACSR- ZEBRA(54/7/3.18mm) BATTERY BANK BATTERY CHARGER
DC VOLTAGE CIRCUIT BREAKER
132 kV LINE ACSR-PANTHER (30/7/3.00 mm) CAPACITY STATUS RATING STATUS
CURRENT TRANSFORMER
EARTH-WIRE GSS-(7/3.15 mm) 220 V 200 Ah Functional
Float:2x20A
Boost:2x40A Functional

33 kV BUS ACSR- ZEBRA (54/7/3.18 mm) ISOLATOR WITHOUT


48 V 200 Ah Float:2x20A PLCC System EARTH SWITCH
Functional Boost:2x40A not working
ACSR- 1. 6/1/4.72 mm
33kV LINE
2. 6/1/3.35 mm
3. 150 mm ISOLATOR WITH
EARTH SWITCH
11 kV BUS INDOOR COPPER STRIP
ACSR- 1. 6/1/4.72mm WAVE TRAP
2. 6/1/3.35mm
11 kV LINE
AAAC- 1. 7/4.26 mm (CTR:300-150/1-1-1)
2. 7/3.81
POTENTIAL TRANSFORMER
SF6 CB
PT: 132kV/110V

POWER TRANSFORMER

132kV BUS

CAPACITOR VOLTAGE
TRANSFORMER

SF6 CB SF6 CB SF6 CB


(ACSR-2) (CTR: 150-75/1) (CTR: 150-75/1-1-1) (CTR: 150-75/1-1-1)
(AAAC-2) [5.311km] Stn Tfr
(AAAC-2) [13.910km] (ACSR-1) T3 T1 T2
Patti (ACSR-2) (AAAC-1) (ACSR-2)
[1.709km] Heerpur (25/31.5 MVA) (25/31.5 MVA) (25/31.5 MVA)
natha [2.08km] [25.762km] [3.426km] [2.54km] (250 kVA)
(132/11 KV) (132/33 KV) (132/33 KV)
R-Gondpur Matarlion Singh V-Industry Bhungarni L-Gondpur Taruwala (33/0.4 KV)
TC: ON LOAD TC: ON LOAD TC: ON LOAD
No.of Taps: 17 No.of Taps: 17 No.of Taps: 17
NormalTap: 5 NormalTap: 5 NormalTap: 5
(CTR:10-5/1)
VCB VCB VCB VCB (CTR:2000-1000/1) (CTR:600-300/0.5771-1-1A) (CTR:600-300/0.5771-1-1A)
VCB VCB VCB
200-100/1 400-200/1 400-200/1 VCB (CB-VCB) (CB-MOCB)
400-200/1 400-200/1 400-200/1 200-100/1 (CB-MOCB)
630mm2 XLPE S/C Cables

VCB

400-200/1
(CTR: 600-300/1-1-1)
33kV BUS BAR

300-150/1-1A
300-150/1-1A

33kV/110V
PT: 33kV/110V
VCB VCB (CB-MOCB) VCB

(CTR:200-100/1-1-1) (CTR:300-150/1-1-1) (CTR:200-100/1-1-1) (CTR:200-100/1-1-1) (CTR:200-100/1-1-1) (CTR:300-150/1-1-1)

2x3.6 MVAR
Capacitor Bank
(Functional)

2x3.6 MVAR CAPACITOR BANK1 2x3.6 MVAR CAPACITOR BANK2


(Non-Functional) (Functional)
Spare Puruwala Badripur CCI/ SAUTAN/ Giri Malwa
[11.323km] [3.055km] Rampur Ghat SHILLAI [24.139km] [10.353km]
(ACSR-2) (ACSR-3) [8.578km] [14.304km] (ACSR-2) (ACSR-2)
(ACSR-1) (ACSR-1 upto SATAUN
ACSR-2 upto SHILLAI)
SINGLE LINE DIAGRAM OF HAMIRPUR-I
AS ON: 12-01-2016 32

LEGEND
[76 km] [49.75 km]
CONDUCTOR/EARTH-WIRE DETAIL
CHOHAL-PSEB BASSI
LIGHTENING ARRESTOR
132 kV BUS ACSR - ZEBRA (54/7/3.18 mm)

CIRCUIT BREAKER 132 kV LINE ACSR - PANTHER (54/7/3.00 mm)

CURRENT TRANSFORMER EARTH-WIRE GSS - (7/3.15 mm)

33 kV BUS ACSR - MOOSE


ISOLATOR WITHOUT
EARTH SWITCH
33 kV LINE ACSR - DOG (6/1/4.72 mm)

ISOLATOR WITH 11 kV BUS


EARTH SWITCH
ACSR (6/1/3.35mm)
11 kV LINE AAAC 1. 7/4.26mm
WAVE TRAP (CTR:500-250/1-1-1A) (CTR: 400/1-1-1-1A) 2. 7/3.81mm

SF6-CB ABCB
POTENTIAL TRANSFORMER
DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


132 kV Bus DC VOLTAGE
POWER TRANSFORMER
CAPACITY STATUS RATING STATUS

220 V Boost:2x40A
200Ah Functional Functional
CAPACITOR VOLTAGE (PTR:132kV/110 V) Float:2x40A
TRANSFORMER
48 V Boost:2x60A
SF6-CB SF6-CB SF6-CB 400Ah Functional Float:2x60A
Functional
ABCB
(CTR: 150/1) (CTR: 150/1)
(CTR:500-250/1-1A) (CTR: 500/1)
T1
T2, (25/31.5 MVA) (25/31.5 MVA)
(13.002 km) (132/33 kV) (132/33 kV)
(20 km) (28.630 km) (19.385 km) (19.395 km)
Tauni Devi Sujanpur Barsar TC: ON LOAD Ladrour Nadaun
Y No.of Taps:17 Y TC: ON LOAD
NormalTap:5 No.of Taps:17
NormalTap:5

(CTR: 600/1) (CTR: 600/1)


(CTR: VCB VCB
(CTR:300/1) (CTR:200/1) 400-200/1A) (CTR:300/1) (CTR:300/1)

VCB VCB VCB VCB OCB

HAMIRPUR(II)-1 HAMIRPUR(II)-2
[4.95 km.] [4.95 km.]
33 kV Bus

(CTR:500-250/5A) OCB
OCB VCB OCB
Connected (CTR:200/1)
(CTR:100/1) (CTR:100/1)
(CTR:400/1)
VCB
TC: Off LOAD (CTR: TC: Off LOAD
No.of Taps:17 33/11 kV ST. Aux. Xmer No.of Taps:17 33/11 kV
300-150/1-1)
NormalTap:5 T2, 5 MVA 33/0.4 kV NormalTap:5 T1 ,5 MVA
100 kVA
(CTR:400/5) (CTR:250/5) Bagana
(26.200 km)
11 kV Bus 11 kV Bus

VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB

Cells

(CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR:
100/1) 200/1) 100/1) 100/1) Series Series 200/1) 200/1) 200/1) 200/1) 200/1) 200/1)
Reactor Reactor

(2*3.6 MVAR Cap. bank)


(FUNCTIONAL)

Ind. Area H/Board Rangus M/wave REC Nalti Hamirpur Kuthera Tikkar Heera Nagar

(ACSR) (AAAC-1) (AAAC-2) (ACSR) (ACSR) (ACSR) (AAAC-1) (ACSR) (AAAC-1) (AAAC-2)
SINGLE LINE DIAGRAM OF 1x25/31.5 MVA,132/33 kV SUB-STATION, JAHOO
AS ON: 11-05-2016 33

(S/C) CONDUCTOR/EARTH-WIRE DETAIL


[65.758 km] (S/C)
HAMIRPUR-II [22.00 km] ACSR- ZEBRA(54/7/3.18mm)
132 kV BUS
(MATTANSIDH) KANGOO

132 kV LINE ACSR-PANTHER (30/7/3.00 mm)

EARTH-WIRE GSS-(7/3.15 mm)

33 kV BUS ACSR- ZEBRA(54/7/3.18mm)

33 kV LINE AAAC- 37/3.53 mm

(CTR:500-250/1-1-1-1-1A) (CTR:500-250/1-1-1-1-1A)

SF6 SF6

132KV BUS B1 LEGEND

LIGHTENING ARRESTOR

CIRCUIT BREAKER
SF6
(CTR:150-75/1-1-1-1-1A)
CURRENT TRANSFORMER
T2
(3x16.67 MVA)
Y (132/33 KV) ISOLATOR WITHOUT
EARTH SWITCH
TC: ON LOAD
Y No.of Taps:17
NormalTap:5
ISOLATOR WITH
EARTH SWITCH
(CTR:600-300/1-1-1-1-1A)

VCB WAVE TRAP

POTENTIAL TRANSFORMER

33KV BUS
POWER TRANSFORMER

PT:
33kV/110V
CAPACITOR VOLTAGE
TRANSFORMER
VCB VCB
VCB
(400-200/1-1-1A) (400-200/1-1-1A) (15-7.5/1-1-1A) DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


DC VOLTAGE
CAPACITY STATUS RATING STATUS

220 V

48 V

Khudla Sarkaghat ST. TR


(33/0.4 kV)
(250 kVA)
SINGLE LINE DIAGRAM OF 132/66/33 kV SUB-STATION AT JUTOGH
AS ON: 18-01-2016 34

CONDUCTOR/EARTH-WIRE DETAIL LEGEND

132 kV BUS ACSR - MOOSE (54/7/3.54 mm)


(S/C LINE) (S/C LINE) LIGHTENING ARRESTOR
(16 km) (15.34 km)
KUNIHAR(Ckt-II) KUNIHAR(Ckt-I) 132 kV LINE ACSR - PANTHER (30/7/3.00 mm)
CIRCUIT BREAKER
EARTH-WIRE GSS - (7/3.15 mm)
CURRENT TRANSFORMER
ACSR - ZEBRA (54/7/3.18 mm)
66 kV BUS
ACSR - WOLF(30/7/2.59 mm) ISOLATOR WITHOUT
EARTH SWITCH
66 kV LINE ACSR - PANTHER (30/7/3.00 mm)
ISOLATOR WITH
33 kV BUS ACSR - ZEBRA (54/7/3.18 mm) EARTH SWITCH

33 kV LINE ACSR - WOLF(30/7/2.59 mm) WAVE TRAP

(CTR:500-250/1-1) (CTR:500-250/1-1) POTENTIAL TRANSFORMER

(CB-SF6) (CB-ABCB)

POWER TRANSFORMER

(CTR:300-150/1-1A)
132kV BUS
CAPACITOR VOLTAGE
B1 B2
(CB-ABCB) TRANSFORMER

DC SYSTEM STATUS

(CB-GCB) (CB-ABCB) (CB-ABCB) (CB-SF6)


BATTERY BANK BATTERY CHARGER
(CTR:150-75/1-1-0.577) (CTR:300-150/1-1-0.577A) (CTR:150-75/1-1-0.577) (CTR:150-75/1-1-0.577) DC VOLTAGE
T2 T1 T3 CAPACITY STATUS RATING STATUS
T4
(3x16.67/21MVA) (3x10.5 MVA) (25/31.5 MVA)
(25/31.5 MVA)
Y (132/66 KV) Y (132/66 KV) Y (132/33 KV) Y (132/33 KV)
Functional
Boost:50A
Functional
220 V 200 Ah Float:30A
TC: ON LOAD TC: OFF LOAD TC: ON LOAD
TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17 Y No.of Taps:17 Y No.of Taps:17
NormalTap:5 NormalTap:5 NormalTap:5 48 V * * * *
NormalTap:5
* Being fed from SLDC System
(CTR:300-150/1-1-0.577) (CTR:600-300/1-1-0.577A) (CTR:600-300/1-1-1-1-1A) (CTR:1200-600/1-1-0.577A)

(CB-SF6) (CB-GCB) PTR: VCB VCB PTR:


33kV/110V 33kV/110V

(CTR:300-150/1-1)
66kV BUS B1 33kV BUS BAR
B1 B2 B2
(CB-SF6)
(CB-VCB)
(CTR:400-200/ (CTR:200-100/ (CTR:200-100/ (CTR:600-300/
(CTR:200-100/1-1A) (CTR:600-300/1-1) 1-1-1A) 1-1A) 1-1A) 1-1-1-1-1A) (CTR:150-300/1A)
(CTR:200-100/ (CTR:400-200/
1-1-1-1-1A) 1-1-1A) VCB VCB VCB
SF6 CB CB-GCB VCB
SF6 CB VCB (Dropout
Fuse)

33/0.4 kV
630 KVA
Y
T1 Residual
(20 MVA) Voltage Xfmr
(66/33 KV)
TC: ON LOAD ST. Aux.
No.of Taps:17 Bharari Dhami Shogi Ashwani Khad Xmer
NormalTap:5 (7.8 km) (13.63 km) (11.5 km) (14.0 km)
Totu Gumma Khalini
Capacitor Bank/ Capacitor Bank/
(1.555 km) (15.49 km) (7.2 km) Series Reactor Series Reactor
(3.6 MVAR) (3.6 MVAR)
[NON-FUNCTIONAL] [NON-FUNCTIONAL]
SINGLE LINE DIAGRAM OF 132/33/11 kV SUB-STATION AT KALA-AMB
AS ON: 06-01-2016 35
CONDUCTOR/EARTH-WIRE DETAIL LEGEND
132 kV BUS ACSR- ZEBRA(54/7/3.18mm)

132 kV LINE ACSR-PANTHER (30/7/3.00 mm) LIGHTENING ARRESTOR


(CTR:200-100/1-1)
Feeder-3 EARTH-WIRE GSS-(7/3.15 mm)
(80 mtr.) (31.960 km) (43.45 mtr.) CIRCUIT BREAKER
[1.954km] GIRI
M/s H.M. Steel M/s J.B. Rolling 33 kV BUS-1 WOLF
(AAAC-1)
(CTR:400-200/1-1)
33 kV BUS-2 ACSR- ZEBRA (54/7/3.18 mm) CURRENT TRANSFORMER
Feeder-7
[1.985km] ACSR 1. 6/1/4.72mm
(AAAC-1) 2. 6/1/3.35mm ISOLATOR WITHOUT
(CTR:400-200/1-1) 33kV LINE AAAC 1. 7/4.26mm EARTH SWITCH
Feeder-6 2. 7/3.81mm
[5.709km]
(ACSR) ACSR (6/1/3.35mm) ISOLATOR WITH
(2x2.5 MVAR) (1.8 MVAR) (1.2 MVAR) AAAC 1. 7/3.81mm EARTH SWITCH
Capacitor Bank Capacitor Bank 11kV LINE 2. 7/3.15mm
Future FUNCTIONAL FUNCTIONAL 3. 7/4.26mm
WAVE TRAP
(CTR:200-100/1-1)
Feeder-2
[69.473km] POTENTIAL TRANSFORMER
(AAAC-1)
(CTR: 150-75/0.577-1-1-1-1) (CTR: 500-250/1-1-1-1) (CTR: 150-75/0.577-1-1-1-1)
(CTR:400-200/1-1)
Feeder-4 SF6-CB SF6-CB
[4.50km]
SF6-CB POWER TRANSFORMER
(AAAC-1)

Incomer
CAPACITOR VOLTAGE
132kV BUS TRANSFORMER

Bus Coupler DC SYSTEM STATUS


NON-FUNCTIONAL
BATTERY BANK BATTERY CHARGER
DC VOLTAGE

Feeder-9 (CTR:200-100/1-1) SF6-CB SF6-CB SF6-CB SF6-CB CAPACITY STATUS RATING STATUS
[1.60km] Boost:2x30A
(AB Cable (CTR: 150-75/0.57-1-1-1) (CTR: 200-100/0.577-1-1-1-1) (CTR: 150-75/0.577-1-1-1-1) (CTR: 150-75/0.577-1-1-1-1) 220 V 200Ah Functional Functional
Float:2x20A
120mm2)
(CTR:400-200/1-1)
48 V 200Ah Functional Boost:2x30A Functional
Feeder-10 Float:2x20A
T3 T(ECE) T2 T1
[5.195km]
(AAAC-1)
(25/31.5 MVA) (25/31.5 MVA) (25/31.5 MVA) (25/31.5 MVA)
(132/33 KV) (132/11 KV) (132/33 KV) (132/33 KV)
(CTR:400-200/1-1) Y Y Y Y ST.Xmer
Feeder-5 TC: ON LOAD TC: ON LOAD
No.of Taps:17
Y TC: ON LOAD TC: ON LOAD
No.of Taps:17
[9.580km] Y NormalTap:5
No.of Taps:17 Y No.of Taps:17 Y NormalTap:5
(AAAC-2&3) NormalTap:5 NormalTap:5

(CTR: 600-300/0.577-1-1-1-1) 250 kVA


(CTR: 600-300/0.577-1-1-1-1) (CTR: 600-300/0.577-1-1-1-1)
Future 33/0.4 kV
VCB-CB VCB-CB VCB-CB
Future 11 kV BUS
33kV/110V (CTR: 10-5/1)
33kV/110V
VCB-CB 33kV/110V
(CTR: 600-300/1-1)
33kV BUS BAR 33kV BUS BAR

VCB-CB

VCB-CB

(CTR:300-150/1-1-1) 300-150/1-1-1

VCB-CB VCB-CB VCB-CB VCB-CB VCB-CB


(CTR:400-200/1-1) (CTR:400-200/1-1) (CTR:400-200/1-1) (CTR:400-200/1-1) (CTR:400-200/1-1) (CTR:400-200/1-1) (CTR:400-200/1-1) (CTR:300-150/1-1) (CTR:200-100/1-1)

(2x3.6 MVAR) (2x3.6 MVAR)


Capacitor Bank Dhaulan Kuan/ M/s Pioneer Embodures Capacitor Bank
Kala-Amb-1 M/s Amba Shakti Parawati Hi Tech Pashupati Pragti/Kala-Amb-2 Sabhu/Ruchira M/s Padmawati
NON-FUNCTIONAL (3.166 km) Nahan (0.79 km) (0.93 km) (0.520 km) through 33kV cable
(1.5 km) (2.72 km) (1.40 km) NON-FUNCTIONAL
CB FAULTY (ACSR-1) (1.00 km)
(ACSR-1) (9.450 km) (AAAC-1) (AAAC-2) (ACSR-2) (ACSR-1) (AAAC-1) CB FAULTY
(ACSR-1) (3-core U/G cable
240 mm)
SINGLE LINE DIAGRAM OF 132/33/11 KV S/STN HPSEBL KANDRORI
AS ON: 11-02-2016 36
LEGEND

LIGHTENING ARRESTOR

CONDUCTOR/EARTH-WIRE DETAIL
CIRCUIT BREAKER
132 kV BUS ZEBRA (54/7/3.18mm)
(24.234 km) CURRENT TRANSFORMER
JASSORE 132 kV LINE ACSR - PANTHER (30/7/3.00 mm)
ISOLATOR WITHOUT
EARTH SWITCH EARTH-WIRE GSS - (7/3.15 mm)

ISOLATOR WITH 33 kV BUS ZEBRA (54/7/3.18mm)


EARTH SWITCH
33 kV LINE
WAVE TRAP

DC SYSTEM STATUS 11 kV BUS


POTENTIAL TRANSFORMER
BATTERY BANK BATTERY CHARGER 11 kV LINE
DC VOLTAGE
CAPACITY STATUS RATING STATUS
(CTR:500-250/1-1-1-1A) POWER TRANSFORMER
220 V Boost:30A
200Ah Functional Float:20A Functional
PTR:
(CB-SF6)
132kV/110V 48 V Boost:60A CAPACITOR VOLTAGE
400Ah Functional Float:60A Functional
TRANSFORMER

132kV BUS B1

(CTR:150-75/ (CTR:150-75/
1-1-1-0.577A) 1-1-1-0.577A) (CTR:150-75/
1-1-1-0.577A)
T1 T2
(16 MVA) (16 MVA) T3
Y Y Y (16 MVA)
(132/33 KV) (132/33 KV)
(132/33 KV)
Y TC: ON LOAD Y TC: ON LOAD Y TC: ON LOAD
No.of Taps:17 No.of Taps:17
NormalTap:5 NormalTap:5 No.of Taps:17
NormalTap:5
(CTR:600-300/ (CTR:600-300/
1-1-1-0.577A) (CTR:600-300/
1-1-1-0.577A) 1-1-1-0.577A)
PTR:
PTR: 33kV/110V
PTR:
33kV/110V
33kV/110V
(CTR: 600-300/
1-1-1-1A)
B1 B2 B3 33kV BUS BAR

(CTR: 600-300/
1-1-1-1A)
VCB
(CTR: (CTR: (CTR:200-100/ (CTR: (CTR: (CTR:200-100/ (CTR:200-100/
(CTR: (CTR:400-200/
400-200/1-1) 150-75/1-1)
(CTR: 1-1-1-.577A) 150-75/1-1A) 150-75/1-1A) 1-1-1A) 1-1-1-1-.577A) 1-1-1-1-.577A)
150-75/1-1) (CB-VCB) 400-200/1-1-1) (CB-VCB) (CB-VCB) (CB-VCB) (CTR:400-200/1-1-1)
(CB-VCB)
(VCB) (CB-VCB) (CB-VCB)
(Dropout
(VCB)
Fuse)
T1 T2
33/11 kV 33/11 kV
Y Y 6.3 MVA
6.3 MVA 33/0.4 kV
Y TC: Off LOAD
TC: Off LOAD Y 250 KVA
No.of Taps:5 Y No.of Taps:5
STN.Xmer
NormalTap:2
NormalTap:2
(CTR:1800-1200/1-1-.577A)
Y
Residual (CTR:1800-1200/1-1-.577A)
(VCB) (VCB) PTR:
Voltage Xfmr
11KV/110v

BADUKHAR THAKURDWARA SURAJPUR ID SOOD KC ALLOY MET INDIA HRA 33kV SAIL
PAPER MILL (Not iin Operation)
Capacitor Bank/ VCB PTR:
Series Reactor B1 B2 11KV/110V
SURAJPUR-1 BAI ATTERIAN-1 BAI ATTERIAN-2
(2x3.6 MVAR) [5.0 km]
[BOTH FUNCTIONAL] (CTR:1800-1200/1-1-.577A) [1.20 km] [1.20 km]
ACSR ACSR ACSR
VCB VCB VCB VCB VCB VCB VCB VCB VCB (6/1/4.72mm) (6/1/4.72mm) (6/1/4.72mm)
PTR: VCB
11KV/110v SURAJPUR-2
(CTR:400-200/ (CTR:200-100/ (CTR:200-100/ (CTR:400-200/ (CTR:400-200/ (CTR:200-100/ (CTR:400-200/ (CTR:200-100/ (CTR:400-200/ (CTR:400-200/ [8.45 km]
1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) ACSR
AIRFORCE DHANGU LODHWAN
(6/1/2.11mm)
AIRFORCE [10.24 km] [7.5 km] [15.25 km]
ACSR ACSR ACSR
[20.32 km]
ACSR (6/1/3.35mm) (6/1/3.35mm) (6/1/3.35mm)
SPARE (6/1/3.35mm)
REY INDORA AGRO BAIN SURAJPUR KANDRORI DAMTAL BAIN DAH
[4.0 km] INDUSTRIES-II [4.0 km] INDUSTRIES-I GANGATH
[4.0 km]
ACSR ACSR ACSR [9.5 km] [9.14 km]
(6/1/3.35mm) (6/1/3.35mm) (6/1/3.35mm) ACSR(6/1/4.72mm) AAAC
(7/3.81mm)
SINGLE LINE DIAGRAM OF 132/33/11 kV SUB-STATION KANGRA LEGEND
AS ON: 15-01-2016
37
LIGHTENING ARRESTOR

[0.135 km] [29.935 km]


PSPCL DEHRA
CIRCUIT BREAKER

CURRENT TRANSFORMER
DC SYSTEM STATUS
BATTERY BANK BATTERY CHARGER ISOLATOR WITHOUT
DC VOLTAGE
EARTH SWITCH
CAPACITY STATUS RATING STATUS
Boost:30A ISOLATOR WITH
220 V 200Ah Functional Functional EARTH SWITCH
Float:30A

48 V 400Ah Boost:60A
Functional Functional
Float:60A WAVE TRAP

(CTR: 600-300/1-1) POTENTIAL TRANSFORMER


(CTR: 500-250/1-1)

SF6 SF6
POWER TRANSFORMER

(CTR: 300-150/1-1-1-1-0.577 A)
132 kV BUS B1 B2 CAPACITOR VOLTAGE
TRANSFORMER
SF6

CONDUCTOR/EARTH-WIRE DETAIL

SF6 SF6 EARTH-WIRE GSS - (7/3.15 mm)


(CTR: 150-75/1-1-1-0.577A) (CTR: 150-75/1-1-1-0.577A)
T1 T2 132 KV BUS ACSR - ZEBRA (54/7/3.18 mm)
(25/31.5 MVA) (25/31.5 MVA)
Y (132/33 KV) Y (132/33 KV)
132 KV LINE ACSR - PANTHER (30/7/3.00 mm)
TC: ON LOAD TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17
NormalTap:7 NormalTap:7 33 KV BUS-1 ACSR - ZEBRA (54/7/3.18 mm)

(CTR: 600-300/1-1-1-0.577) (CTR: 600-300/1-1-1-0.577) 33 KV BUS-2 ACSR - ZEBRA (54/7/3.18 mm)

VCB VCB
33 KV LINE WOLF

(PTR:33kV/110V) VCB 33 kV BUS B2


B1

(CTR: 600-300/1-1-1A) (PTR:33kV/110V)

(PTR:33kV/110V)
(CTR:150-75/ (CTR:400-200/ (CTR:400-200/ (CTR: (CTR:400-200/ (CTR:400-200/
1-1A) 1-1-1-1A) 1-1-1-1A) (CTR:400-200/ (CTR:200-100/ 600-300/1-1-1) 1-1-1A) 1-1-1A)
OCB OCB VCB 1-1-1-.577A) 1-1-1-.577A) (Dropout OCB VCB
(Dropout Fuse) VCB
VCB VCB
Fuse)
T1 T2
33/11 kV 33/11 kV
10 MVA 10 MVA
Y TC: ON LOAD TC: ON LOAD Y
No.of Taps:17 No.of Taps:17
NormalTap:5 NormalTap:5
(CTR: (CTR:
33/0.4 kV 600-300/5-5-0.577A) 600-300/5-5-0.577A) 33/0.4 kV
100 KVA 100 KVA
STN. XFMR STN. XFMR

DEHRA Nagrota SHAHPUR-II Gaj Sidhpur Shahpur-I


[19.594kms] [10.886kms] [18.50kms] [17.260kms] [12.80kms] [18.5kms]

(PTR:11kV/ (CTR: 600-300/5-5-.577A)


110V) 11kV Bus

OCB (PTR:11kV/
OCB OCB OCB OCB OCB OCB OCB OCB OCB VCB VCB 110V)
MOCB OCB

(CTR:50-25/ (CTR:100-50/ (CTR:100-50/ (CTR:100-50/ (CTR:200-100/ (CTR:200-100/ (CTR:100-50/ (CTR:100-50/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/
5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A)

PSEB Mandal Serathana Daultpur Kangra-I Bagli Kangra-II Tiara Rajol Spare Lanj Rajol Exp.
[0.2km] [11.455km] [15.6km] [36.8km] [5.375km] [23.77km] [7.964km] [22.671km] [19.055km] Express [6.05km]
[15.195km]

(1.2+1.8 MVAR)
CAPACITOR BANK
[BOTH FUNCTIONAL]
SINGLE LINE DIAGRAM OF 33/132 kV, 1X50/63 MVA (SINGLE PHASE 16.67/21 MVA POWER TRANSFORMER 3+1) 38
SUB STATION HPSEBL KURTHALA, DISTT. CHAMBA (H.P.)
LEGEND
AS ON: 15-01-2016

LIGHTENING ARRESTOR
CONDUCTOR/EARTH-WIRE DETAIL
(D/C LINE) (D/C LINE)
132 kV BUS ZEBRA (ACSR) CIRCUIT BREAKER
[45.51 km] [45.51 km]
BATHRI-I BATHRI-II FUTURE FUTURE
132 kV LINE PANTHER (ACSR) CURRENT TRANSFORMER

EARTH-WIRE GSS (7/3.15 mm) ISOLATOR WITHOUT


EARTH SWITCH
33 kV BUS-1 TWIN TARANTULA
(ALL ALUMINIUM CONDUCTOR)
ISOLATOR WITH
33 kV BUS-2 TWIN TARANTULA EARTH SWITCH
(ALL ALUMINIUM CONDUCTOR)

33kV LINE WAVE TRAP

POTENTIAL TRANSFORMER

500-250/1-1-1-1-1A 500-250/1-1-1-1-1A
PTR:
SF6 SF6 SF6 SF6 (132kV/110V) POWER TRANSFORMER

Y
CAPACITOR VOLTAGE
Y TRANSFORMER
132 kV BUS

DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


DC VOLTAGE
SF6 SF6
CAPACITY STATUS RATING STATUS
300-150/1-1-1-0.577-1 A 1200-600/1-1-1-1-0.577 A
220 V Boost:60A
T2 (PROPOSED) 400Ah Functional Float:60A Functional
Y (50/63 MVA) Y T1
(132/33 KV) (50/63 MVA) Boost:60A
48 V 400Ah Functional Functional
Y Y (132/33 KV) Float:60A

VCB
PTR:
300-150/1-1-1-1-0.577 A (33 kV/110V)
300-150/1-1-1-1-0.577 A

VCB
33 kV BUS

1200-600
/1-1-1-1-1A
PTR:
(33 kV/110V)

VCB

400-200/1-1-1-1-1 A 400-200/1-1-1-1-1 A 15-7.5/1-1-1A


350-200/1-1-1 A
VCB VCB VCB
ST. Aux. Xmer
33/0.4 kV
250 kVA

FUTURE FUTURE UPPER JOINER TARELLA FUTURE FUTURE


[4.5+3+2=9.5 KM] GINNI GLOBAL
[20 KM] [3.25 KM]
SINGLE LINE DIAGRAM OF 132 kV HEP LARJI 39
[55.83 km.] [55.83 km.] [25 km.] [20 km.] LEGEND
KANGOO(Ckt-I) KANGOO(Ckt-II) BAJAURA MANDI
CONDUCTOR/EARTH-WIRE DETAIL
LIGHTENING ARRESTOR
132 kV BUS
CIRCUIT BREAKER
132 kV LINE
CURRENT TRANSFORMER
EARTH-WIRE
ISOLATOR WITHOUT
33 kV BUS-1 EARTH SWITCH

33 kV BUS-2 ISOLATOR WITH


EARTH SWITCH
(CTR:500/ (CTR:500/ (CTR:500/ (CTR:500/ 33kV LINE
1-1-1-1-1) 1-1-1-1-1) 1-1-1-1-1) 1-1-1-1-1)
WAVE TRAP

PT
132kV/110V POTENTIAL TRANSFORMER
LA

132kV
POWER TRANSFORMER
Bus B1 PT
132kV/110V
LA
CAPACITOR VOLTAGE
Bus B2 TRANSFORMER

(ES) (ES) (ES) (ES) (ES)


(ES)

(CTR:750/1A) (CTR:750/1A) (ES)


(CTR:250/ (CTR:250/ (CTR:250/
(For B/B Prot.) (For B/B Prot.) (CTR: 50/1-1-1-1)
1-1-1-1-1) 1-1-1-1-1) 1-1-1-1-1)
(ES) (ES) (ES) Y (6.3 MVA)
(132/11 KV)
Y GT1 Y GT2 Y GT3
(11/132 KV) (11/132 KV) (52 MVA) Y
(52 MVA) (52 MVA) (11/132 KV)

PTR PTR PTR


[11 kV/110V] [11 kV/110V] [11 kV/110V] 11kV Bus B1
(CTR: 3000/5A) (CTR: 3000/5A) (CTR: 3000/5A)

UNIT-I UNIT-II UNIT-III


(43 MW) (43 MW) (43 MW) 11/0.4 kV,
1 MVA

Spare Stn.Xmer1 Stn.Xmer2 Supply from


Local N.Work
SINGLE LINE DIAGRAM OF 33/132kV, ADJACENT TO 86MW MALANA HEP 40
AS ON: 12-01-2016

(D/C LINE) (D/C LINE)


[24.11 km] [24.11 km]
BAJAURA-Ckt1 BAJAURA-Ckt2
CONDUCTOR/EARTH-WIRE DETAIL

132 kV BUS ACSR-PANTHER (30/7/3.00 mm)


HPSEB LTD.
132 kV LINE ACSR-PANTHER (30/7/3.00 mm)

EARTH-WIRE GSS-(7/3.15 mm)

33 kV BUS ACSR- ZEBRA (54/7/3.18 mm)

33kV LINE AAAC 100M2 (7/4.26 mm)


Al-59

(CTR:600-300/1-1-1-1-1A) (CTR:600-300/1-1-1-1-1A)
PTR:
(132kV/110V)

Y Y LEGEND

Y Y PTR:
(CTR:600-300/1-1-1-1-1A)
132KV Bus B1 (132kV/110V)
LIGHTENING ARRESTOR
B2

CIRCUIT BREAKER

SF6-CB CURRENT TRANSFORMER


(CTR:150-75/1-1-1-.577A)
(CTR:300/1-1-1-1A) (CTR:300/1-1-1-1A) ISOLATOR WITHOUT
T1, (25/31.5 MVA) EARTH SWITCH
Y (132/33 KV)
TC: ON LOAD ISOLATOR WITH
Y No.of Taps:17
GT1 GT2 EARTH SWITCH
NormalTap:5 Y Y
(58 MVA) (58 MVA)
(11/132 KV) (11/132 KV)
(CTR:600-300/1-1-.577A) WAVE TRAP
PTR: VCB
(33kV/110V) POTENTIAL TRANSFORMER
(PTR: (PTR:
11kV/110V] (CTR:3200/5) 11kV/110V] (CTR:3200/5)

33KV BUS POWER TRANSFORMER

43MW 43MW
UNIT-1 UNIT-1 CAPACITOR VOLTAGE
TRANSFORMER
(CTR:400-200/1-1) (CTR:400-200/1-1)
VCB VCB
DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


DC VOLTAGE
CAPACITY STATUS RATING STATUS

220 V 200Ah Boost:30A


Functional Functional
Float:20A

48 V N.A. N.A. N.A. N.A.

TOSS VIRAH
[21.365km] [21.365km]
SINGLE LINE DIAGRAM OF 132/66/33/22 kV SUB-STATION AT MANDI
AS ON: 13-01-2016
41
[35.0 km]
DC SYSTEM STATUS SHANAN (PSEB) [20 km] [60.70 km]
LARJI KANGOO CONDUCTOR/EARTH-WIRE DETAIL LEGEND
BATTERY BANK BATTERY CHARGER
DC VOLTAGE
132 kV BUS ACSR- ZEBRA (54/7/3.18mm)
CAPACITY STATUS LIGHTENING ARRESTOR
RATING STATUS
132 kV LINE ACSR - PANTHER (30/7/3.00 mm)
220 V 200Ah Functional Boost:30A
Float:20A Functional CIRCUIT BREAKER
EARTH-WIRE GSS - (7/3.15 mm)
48 V 400Ah Boost:60A
Functional Functional CURRENT TRANSFORMER
Float:40A
66 kV BUS ACSR-WOLF (30/7/2.59 mm)
ISOLATOR WITHOUT
66 kV LINE ACSR- WOLF(30/7/2.59mm) EARTH SWITCH

(CTR:200-100/ 33 kV BUS ACSR- ZEBRA (54/7/3.18mm) ISOLATOR WITH


1-1-1-0.577) (CTR:500-250/ (CTR:500-250/ EARTH SWITCH
MOCB 1-1-1) 1-1-1) ACSR-DOG(6/1/4.72mm)
33 kV LINE
SF6 SF6 AAAC-100MM2 (7/4.26mm)
66 kV Bus WAVE TRAP
ACSR (6/1/3.55mm)
11 kV LINE ACSR1 (6/1/4.35mm)
AAA (7/4.26mm) POTENTIAL TRANSFORMER
(PTR:66 kV/110 V) 11 kV BUS INDOOR COPPER STRIP
132kV Bus B1
POWER TRANSFORMER
66/33 kV
Y 20 MVA
TC: ON LOAD (PTR:132 kV/110 V)
Y No.of Taps:17 CAPACITOR VOLTAGE
NormalTap:5 Bus B2 TRANSFORMER
(CTR:800-400/
1-1-1-0.577)
SF6
VCB

(CTR:300-150/ SF6 SF6 (FUNCTIONAL)


1-1A) (2*3.6 MVAR Cap. bank)
(CTR:150-75/ (CTR:150-75/
1-1-1-0.577) Series Series
1-1-1-0.577)
Reactor Reactor
33 kV Bus

(PTR:
33 kV/110 V)
T2 (25/31.5 MVA) T1 (16/20 MVA)
Y (132/33 KV) Y (132/33 KV)
VCB TC: ON LOAD TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17
NormalTap:5 NormalTap:5
(CTR:
400-200/1-1) (CTR:600-300/ (CTR:600-300/
1-1-1-0.577) 1-1-1-0.577)
VCB VCB

33 kV Bus Connected
400-200/1-1A VCB (CTR: 300-150/1-1A)

(CTR:600-300/
(PTR: 1-1)
(PTR:
33 kV/110 V) (PTR:
33 kV/110 V)
VCB VCB 33 kV/110 V)
200-100/1-1-1A 200-100/1-1-1A VCB VCB VCB VCB VCB
400-200/1-1A 400-200/1-1A (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/
T2 33/11 kV T1 33/11 kV (CTR:400-200/
1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A)
3.15 MVA 3.15 MVA 1-1-1A)
TC: Off LOAD TC: Off LOAD
No.of Taps:5 No.of Taps:5
NormalTap:2 NormalTap:2
600-300/1-1A 600-300/1-1A

MANDI-I MANDI-II
[3.0km] 600-300/1-1A
[3.0km]
Padhar Sunder-nagar-II Sunder-nagar-I Seiglu Pandoh-I
[23.490 km] Katalila Pandoh-II
[19 km] [25 km] [7.5 km] [10.00 km] [20.689 km] [24.0 km]

VCB VCB VCB VCB

300-150/1-1A 300-150/1-1A 300-150/1-1A 300-150/1-1A

SAULI KHAD DARANG 11KV BARI 11KV KHLIKAR


[12.0km] DHNOG [8.0km] [6.0km]
(ACSR) [22.0km] (AAAC)
(ACSR)
(AAAC)
SINGLE LINE DIAGRAM OF 132/66/33/11 kV SUB-STATION RAKKAR (UNA)
AS ON: 21-01-2016 42
(S/C LINE) (S/C LINE)
TAHLIWALA AMB (15.98 km)
[16.949km] (31.322 km) GOLTHAI

DC SYSTEM STATUS LEGEND CONDUCTOR/EARTH-WIRE DETAIL


BATTERY BANK BATTERY CHARGER
DC VOLTAGE 132 kV BUS ZEBRA (54/7/3.15mm)
LIGHTENING ARRESTOR
CAPACITY STATUS RATING STATUS
132 kV LINE PANTHER (30/7/3.00mm)
Boost:60A
220 V 200Ah Functional Float:40A
Functional
CIRCUIT BREAKER
EARTH-WIRE GSS (7/3.15 mm)
Boost:60A
48 V 400Ah Functional
Float:40A
Functional
CURRENT TRANSFORMER 66 kV BUS PANTHER (30/7/3.00mm)

Functional Boost:20A Functional 66 kV LINE


30 V 200Ah Float:15A ISOLATOR WITHOUT WOLF (30/7/2.59mm)
EARTH SWITCH
33 kV BUS (CTR:400-200/1-1)
(CTR:500-250/1-1)
(CTR:500-250/1-1)
ISOLATOR WITH 33 kV LINE AS SHOWN (CB-MOCB)
(CB-SF6) EARTH SWITCH
(CB-SF6)
11 kV BUS INDOOR COPPER STRIP
WAVE TRAP 11 kV LINE AS SHOWN

132kV BUS 66kV BUS B1


POTENTIAL TRANSFORMER
B1 PTR:
PTR: 66kV/110V
132kV/110V
POWER TRANSFORMER
(CB-SF6) (CB-SF6) (CTR:100-50/1-1-1A) (CTR:150-75/1-1-1A)
(CTR:150-75/0.577-1-1-1A) MOCB
(CTR:150-75/0.577-1-1-1A) CAPACITOR VOLTAGE (CB-MOCB) (CB-MOCB)
T2 T1 TRANSFORMER (CTR:400-200/1-1-1A)
(25/31.5 MVA) T1.(10 MVA) T2.(10 MVA)
(25/31.5 MVA) (66/33 KV) T1 66/11 kV
Y (132/33 KV) (132/33 KV) (66/33 KV) Y 20 MVA
TC:Off LOAD
TC: ON LOAD TC:Off LOAD No.of Taps:5 TC:Off LOAD
TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17 No.of Taps:5
Y NormalTap:2 Y Y No.of Taps:5
NormalTap:5 NormalTap:2 NormalTap:2
NormalTap:5

(CTR:300-150/ (CTR:300-150/ (CTR:800-400/


(CTR:1200-600/0.577-1-1-1A) (CTR:600-300/0.577-1-1-1A) 1-1-0.577A) 1-1-0.577A) 0.577-5-5-5A)

VCB VCB (CB-MOCB) (CB-MOCB) VCB

(CTR:600-300/0.577-1-1-1A) (CTR:600-300/1-1)
33kV BUS B1

VCB (CB-SF6)

PTR: (CTR:400-200/ (CTR:200-100/ (CTR:200-100/ (CTR:400-200/ (CTR:400-200/ (CTR:500-250/ (CTR:200-100/ (CTR:400-200/ (CTR:150-75/
(CB-VCB) 1-1A) 1-1A) 1-1A) 1-1A) 1-1A) (CTR:200-100/1-1-1A) 1-1-1A) 1-1A) 1-1A) 1-1A)
33kV/110V/ 400/1A (CTR:200-100/
110V (CTR:300-150/1-1) (CB-VCB) (CB-VCB) (CB-VCB) (CB-VCB) 1-1-1A)
VCB
(CB-VCB) (CB-VCB)

33/0.4 kV
100 KVA
T1 T2
33/0.4 kV
(6.3MVA) (6.3MVA) Y
250 KVA
Y (33/11 KV) (33/11 KV)
TC:Off LOAD TC:Off LOAD
Y No.of Taps:5 Y No.of Taps:5
NormalTap:2 NormalTap:2
WOLF WOLF WOLF DOG ST. Aux.
DOG DOG DOG WOLF
ST. Aux. Xmer
Capacitor Bank/ Capacitor Bank/
Series Reactor Xmer MEHATPUR
Series Reactor TAHLIWALA-I GAGRET BANGANA BARSAR SABER PAPER PTR: PTR: TAHLIWALA-II HAROLI AMB/BASAL
(3.6 MVAR) (3.6 MVAR) [16.00km] [35.20km] [23.289km] 11kV/110V 11kV/110V (CTR:800-400/ [16.433km] [8.368km] [7.750km] [11.122km]
[27.80km] [40.196km]
.577-5-5-5A)
(BOTH FUNCTIONAL) (AAAC-7/4.72mm) (CTR:1200-600/ (CTR:800-400/
.577-5-5-5A) VCB VCB 5-5A)
11KV BUS 11KV BUS

(CTR:800-400/
5-5A)
VCB VCB VCB VCB VCB VCB VCB VCB
VCB VCB VCB VCB
(CTR:250-125/
(CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ 1-1A)
5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A) 5-5A)
5-5A) 5-5A)

SANTOSH SPARE UNA-III UNA-I UNA-I PIRNIGAH SAMOOR UNA-IV M/PUR UNA-II JHALERA
GARH [2.20km] [4.60km] [4.60km] [10.570km] [3.0km] [4.956km] [12.30km] [20.70km]
[7.186km] Cells
(AAAC- (AAAC- (AAAC- (AAAC- (AAAC- (AAAC-
[27.697km] (AAAC- (AAAC- (AAAC-
7/4.72mm) 7/4.72mm) 7/4.72mm 7/4.72mm) 7/4.72mm) 7/4.72mm) 7/4.72mm)
(ACSR- 7/4.72mm) 7/4.72mm)
6/1/3.35mm) &ACSR- Series Series
6/1/3.35mm) Reactor Reactor
(1.8 MVAR) (1.2 MVAR)
(BOTH FUNCTIONAL)
SINGLE LINE DIAGRAM OF 132/66/33 kV SUB-STATION SOLAN
AS ON: 07-01-2016 43

CONDUCTOR/EARTH-WIRE DETAIL
(S/C) (S/C) (S/C) (S/C)
[81.153 km] [65.758 km] [20.00 km] [22.00 km] ACSR- ZEBRA(54/7/3.18mm)
132 kV BUS
GIRI-II GIRI-I KUNIHAR-II KUNIHAR-I

132 kV LINE ACSR-PANTHER (30/7/3.00 mm)

EARTH-WIRE GSS-(7/3.15 mm)

66 kV BUS ZEBRA CONDUCTOR & COPPER HOLLOW


PIPE

66 kV LINE 0.085 sq in (DOTTEREL)


ACSR 12/7/3.00 mm2

33 kV BUS ALUMINIUM FLAT- 75x25 mm

33 kV LINE ACSR 1. ZEBRA(54/7/3.75 mm


2. WOLF (30/7/2.59 mm)
3. DOG(6/1/4.72 mm)
(CTR: 500-250/1-1-1-1) (CTR:500-250/1-1-1-1) (CTR:500-250/1-1-1-1) (CTR:400-250/1-1) AAAC (7/4.26)

SF6 SF6 SF6 SF6

132KV BUS B1(Bus PT not available) LEGEND

LIGHTENING ARRESTOR

CIRCUIT BREAKER
SF6 SF6
(CTR: 250/1-1-1-1) (CTR: 150/1-1-0.577) CURRENT TRANSFORMER
T2 T1
(3x16.67 MVA) (25/31.5 MVA)
Y (132/33 KV) Y (132/66 KV) ISOLATOR WITHOUT
EARTH SWITCH
TC: ON LOAD TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17
NormalTap:5 NormalTap:5
ISOLATOR WITH
EARTH SWITCH
(CTR:1200-600/1-1-1-1-0.577) (CTR:300-150/1-1-0.577)
VCB WAVE TRAP

POTENTIAL TRANSFORMER
ZEBRA TWIN
ZEBRA SINGLE ZEBRA SINGLE 66KV BUS B1
To To Lower
Upper Yard POWER TRANSFORMER
Yard
PT
Connected Connected (66kV/110V) CAPACITOR VOLTAGE
(CTR:600-300/1-1-1) (CTR:600-300/1-1-1) TRANSFORMER
VCB MOCB BOCB
(CTR:300-150 (400-200/
/1-1) 1-1-1)

33KV BUS DC SYSTEM STATUS


33KV BUS
BATTERY BANK BATTERY CHARGER
DC VOLTAGE
PT
PT (33kV/110V) CAPACITY STATUS RATING STATUS
(33kV/ Functional
400Ah Float:2x40A
110V) VCB VCB VCB VCB VCB VCB VCB 220 V Functional Boost:2x60A Boost non-funct
MOCB

(400-200/ (600-300/1-1-1) (400-200/ (400-200/ (150-75/ (400-200/ (300-150/1) 48 V 400Ah Functional 13A Functional
1-1-1) 1-1-1) 1-1-1) 1-1)
1-1-1)
Shimla Parwanoo
(Totu) (18.50 km.)
(25.27 km.)
Solan-I Solan-II
(1.14 km.) Kasauli Rajgarh Sarahan Kandaghat
(1.14 km.) (16.80 km.) (36.00 km.) (32.00 km.) (12.20 km.)
(ACSR-2) (ACSR-2)
(ACSR-3) (ACSR-3/ (AAAC) (AAAC)
AAAC) Cells Cells
ST. TR Series Series
(33/0.4 kV) Reactor Reactor
(250 kVA) TO 33kV KATHED (2x2.5 MVAR)
S/STN (Functional) (Functional)
SINGLE LINE DIAGRAM OF 132/33 KV S/STN TAHLIWALA 44
AS ON: 21-01-2016
LEGEND

(S/C LINE)
UNA
[16.949km] LIGHTENING ARRESTOR
CONDUCTOR/EARTH-WIRE DETAIL
CIRCUIT BREAKER
132 kV BUS ZEBRA (54/7/3.18mm)
CURRENT TRANSFORMER
132 kV LINE PANTHER (30/7/3.00mm)
ISOLATOR WITHOUT
EARTH-WIRE GSS (7/3.15mm) EARTH SWITCH
OPGW:24/1/81.5mm-132kV Line

11 kV BUS INDOOR COPPER STRIP ISOLATOR WITH


EARTH SWITCH
11 kV LINE ACSR(6/1/4.72mm)
AAAC(7/4.26mm)
WAVE TRAP
(CTR:500-250/1-1-1-1-1A)

POTENTIAL TRANSFORMER
SF6

POWER TRANSFORMER
132kV BUS BAR

CAPACITOR VOLTAGE
TRANSFORMER
PTR:
132kV/110V
SF6 SF6
150-75/1-1-1-1-1A 150-75/1-1-1-1-1A
DC SYSTEM STATUS
T1 T2
(25/31.5 MVA) (25/31.5 MVA)
Y (132/33 KV) Y (132/33 KV) DC VOLTAGE
BATTERY BANK BATTERY CHARGER

TC: ON LOAD Y TC: ON LOAD


Y No.of Taps:17 No.of Taps:17
CAPACITY STATUS RATING STATUS
NormalTap:5 NormalTap:5 Boost:30A
220 V 200Ah Functional Functional
Float:20A
600-300/1-1-1-1-1A 600-300/1-1-1-1-1A
PTR: PTR: 400Ah Boost:60A
VCB VCB 48 V Functional Float:40A Functional
33kV/110V 33kV/110V

(CTR: 600-300/1-1-1-1A)
33KV BUS BAR

(CTR:300-150/ (CTR:300-150/ 150-75/1-1A (CTR:400-200/


1-1-1A) 1-1-1A) (CTR:300-150/ 1-1-1A)
VCB VCB 1-1-1A) VCB VCB
VCB
15-7.5/1-1-1A VCB

33/0.4 kV
250 KVA
STN.Xmer FDR-I FDR-II HN STEEL SUKHJEET TAHLIWALA
[2.50km] INDUSTRIES [9.20km]
(ACSR) [0.8km] (AAAC)
(ACSR)
45

66 kV Sub-Stations/
Power Houses
SINGLE LINE DIAGRAM OF 66/33/11 kV SUB-STATION AKANWALI 46
AS ON: 06-01-2016

(D/C LINE) (D/C LINE) (D/C LINE) (D/C LINE) (S/C LINE) (S/C LINE)
[14.507 km] [14.507 km] [10.172 km] [10.172 km] [0.425 km] [2.11 km]
LEGEND
NALAGARH-I NALAGARH-II BADDI-I BADDI-II ALKEM DAVNI
DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER LIGHTENING ARRESTOR


DC VOLTAGE
CAPACITY STATUS RATING STATUS CIRCUIT BREAKER

220 V Boost:2x40A
200Ah Functional
Float:2x40A Functional
CURRENT TRANSFORMER

48 V Boost:2x60A
400Ah Functional Float:2x60A Functional
ISOLATOR WITHOUT
EARTH SWITCH

ISOLATOR WITH
(CTR:500-250/ (CTR:500-250/ (CTR:500-250/ (CTR:500-250/ (CTR:200-100/ (CTR:400-200/ EARTH SWITCH
1-1-1-1A) 1-1-1-1A) 1-1-1-1A) 1-1-1-1A) 1-1-1-1A) 1-1-1-1A)
SF6 SF6 SF6 SF6 SF6 SF6
WAVE TRAP

Main Bus -IIB


66 kV BUS POTENTIAL TRANSFORMER

POWER TRANSFORMER

Main Bus -I
66 kV BUS CAPACITOR VOLTAGE
TRANSFORMER
(PTR:66kV/110V)
CONDUCTOR/EARTH-WIRE DETAIL

Main Bus -IIA 66 kV BUS TWIN ZEBRA (54/7/3.18 mm)


66 kV BUS
SF6 SF6 SF6
66 kV LINE PANTHER (30/7/3.00 mm)
CTR:200-100/ (PTR:66kV/110V) CTR:200-100/ CTR:200-100/
1-1-1-1-0.577A 1-1-1-1-0.577A 1-1-1-1-0.577A EARTH-WIRE GSS - (7/3.15 mm)
SF6
T1 T1 20 MVA T1 20 MVA 33 kV BUS TWIN ZEBRA (54/7/3.18 mm)
20 MVA 66/33 kV 66/33 kV
Y (CTR:500-250/ (CTR:500-250/ Y Y TC: ON LOAD
66/11 kV TC: ON LOAD
TC: ON LOAD 1-1-1-1-1) 1-1-1-1-1) No.of Taps:17 No.of Taps:17 33 kV LINE ACSR - WOLF (30/7/2.59 mm)
Y No.of Taps:17 Y NormalTap:7 Y NormalTap:7
NormalTap:7
CTR:400-200/ CTR:400-200/ 11 kV BUS INDOOR COPPER STRIP
CTR:1200-600/ 1-1-1A 1-1-1A
1-1-0.577A VCB VCB 11 kV LINE ACSR - DOG (6/1/4.72 mm)
VCB

11 kV BUS
33 kV BUS
PTR:
PTR: VCB VCB VCB VCB VCB VCB [33kV/110V]
[11kV/110V]
(CTR:300-150/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/ (CTR:400-200/
1-1-1) 1-1-1) 1-1-1) 1-1-1) 1-1-1) 1-1-1)
VCB VCB VCB VCB VCB
(CTR:15-7.5/ (CTR:200-100/ (CTR:200-100/ (CTR:300-150/ (CTR:200-100/
1-1-1) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A)

Feeder No.4 Feeder No.5 Feeder No.6 Feeder No.8 Feeder No.9 Feeder No.10
(4.00 km.) (6.00 km.) (2.50 km.) (5.50 km.) (25.30 km.) (5.75 km.)
Y

Total 13 Feeders ST. TR


Feeder No.1 Feeder No.2 Feeder No.3 Feeder No.4
(Connected 6 Feeders) 33/0.4 kV
(315 kVA)
SINGLE LINE DIAGRAM OF 66/22 kV SUB-STATION ANDHRA 47
[7.30 km.] AS ON: 18-12-2015
[13.10 km.] Andhra CONDUCTOR/EARTH-WIRE DETAIL
Rohru (Samoli) Stage-II
66 kV BUS-1 WOLF [30/7/2.59 mm]

66 kV LINE

EARTH-WIRE MS FLAT
22 kV 22 kV 22 kV 22 kV
Feeder-I Feeder-II 3 MW Gumma 6 MW Tanganu Proposed
22 kV BUS-1 WOLF [30/7/2.59 mm]

22 kV LINE

11 kV BUS XLPE CABLE

(CTR:400-200/1-1-1 A) (CTR:150-75/1 A)
(CTR: (CTR: (CTR:
200/1-1-1 A) (CTR:400-200/1-1-1 A)
100/1-1-1 A) 150/1-1-1 A)

(PTR: 22kV/110V)
(PTR:
66kV/110V) LEGEND

66 kV Bus B1
LIGHTENING ARRESTOR
22 kV Bus B1

CIRCUIT BREAKER

CURRENT TRANSFORMER

(CTR:75/1 A) (CTR:75/1 A) (CTR: (CTR: 10A)


(CTR: (CTR: 225/1-0.577 A) ISOLATOR WITHOUT
300-150/ 900-450/ EARTH SWITCH
1-1-1-0.577 A) 1-1-1-0.577 A)

GT1 ISOLATOR WITH


GT2 Y Y GT3
EARTH SWITCH
Y (6.67 MVA) Y (6.67 MVA)
Y (6.67 MVA) Stn Transformer
11/66 KV 11/66 KV T1 11/22 KV 315 kVA
TC: ON/Off LOAD 66/22 kV TC: ON/Off LOAD Y 22/0.44 KV WAVE TRAP
TC: ON/Off LOAD
No.of Taps: No.of Taps: (25/31.5 MVA) No.of Taps:
NormalTap: NormalTap: NormalTap:
POTENTIAL TRANSFORMER
PTR PTR
[11 kV/110V] [11 kV/110V] PTR
[11 kV/110V]
POWER TRANSFORMER

UNIT-I UNIT-II UNIT-III


(5.65 MW) (5.65 MW) (5.65 MW) CAPACITOR VOLTAGE
TRANSFORMER

DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


DC VOLTAGE
CAPACITY STATUS RATING STATUS

220 V

48 V
SINGLE LINE DIAGRAM OF 66/22 kV SUB-STATION NAGAN (ANNI)
AS ON: 07-01-2016 48
(S/C LINE) (S/C LINE) LEGEND
[40.304Km.) [17.30Km.)
GUMMA KUMARSAIN
CONDUCTOR/EARTH-WIRE DETAIL
LIGHTENING ARRESTOR
66 kV BUS MOOSE (54/7/3.54mm)
CIRCUIT BREAKER
66 kV LINE WOLF (30/7/2.59mm)
CURRENT TRANSFORMER
EARTH-WIRE GSS-(7/3.15 mm)
ISOLATOR WITHOUT
22 kV BUS COPPER FLAT (75x12mm) EARTH SWITCH

22 kV LINE ACSR- 1. 6/1/4.72mm


2. 6/1/3.35mm ISOLATOR WITH
EARTH SWITCH
(CTR: 400-200/1-1-1-1) (CTR: 400-200/1-1-1-1)
SF6-CB WAVE TRAP
SF6-CB

POTENTIAL TRANSFORMER

66 kV Bus Bar POWER TRANSFORMER

CAPACITOR VOLTAGE
TRANSFORMER

SF6-CB SF6-CB
DC SYSTEM STATUS
(CTR:200-100/1-1-1-1) (CTR:200-100/1-1-1-1)
T2. 10 MVA BATTERY BANK BATTERY CHARGER
T1. 10 MVA
66/22kV XFMR 66/22kV XFMR DC VOLTAGE
TC: ON LOAD
TC: ON LOAD No.of Taps:17 CAPACITY STATUS RATING STATUS
No.of Taps:17 NormalTap:5
NormalTap:5
Functional Boost:30A
220 V 200Ah Functional
Float:30A
(CTR:600-300/1-1) (CTR:600-300/1-1)
48 V N.A. N.A. N.A. N.A.
(CTR:600-300/1-1-1)
22kV Bus

PTR: PTR:
[22kV/110V] [22kV/110V]

(CTR:30-15/1A) (CTR:300-150/1-1) (CTR:300-150/1-1) (CTR:300-150/1-1) (CTR:200-100/1-1) (CTR:200-100/1-1)

22/0.433 kV
[250 kVA]
Y

STN. XFMR
(50mm2 Cable)
ANNI KHANAG SHAWAD BARAD DALASH
[46.047km] [470.912km] [69.207km] [9.00km] [9.750km]
(ACSR-1&2) (ACSR-2) (ACSR-2) (ACSR-2) (ACSR-2)
SINGLE LINE DIAGRAM OF 66/11 kV SUB-STATION BHATOLIKALAN 49
AS ON: 06-01-2016

(S/C LINE) DC SYSTEM STATUS


[2.00km]
BADDI BATTERY BANK BATTERY CHARGER
DC VOLTAGE
CAPACITY STATUS RATING STATUS
Boost:2x20A
220 V 200Ah Functional
Float:2x20A Functional

48 V 200Ah Boost:2x20A
Functional Functional
Float:2x20A

CONDUCTOR/EARTH-WIRE DETAIL

66 kV BUS AAAC TARANTULA (37/5.23mm)

(CTR:400-200/1-1-1-1A) 66 kV LINE PANTHER (30/7/3.00mm)


SF6 CB
EARTH-WIRE GSS (7/3.15mm)

22 kV BUS

66 kV BUS 22 kV LINE

PTR: 66kV/110V

SF6 CB SF6 CB LEGEND


CTR:200-100/1-1-1-1-0.577A CTR:200-100/1-1-1-1-0.577A
LIGHTENING ARRESTOR
T1 T2
Y 20 MVA Y 20 MVA
66/11 kV 66/11 kV CIRCUIT BREAKER
TC: ON LOAD TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17
NormalTap:5 NormalTap:5 CURRENT TRANSFORMER
CTR:1200-600/1-1-.577A CTR:1200-600/1-1-.577A
ISOLATOR WITHOUT
EARTH SWITCH

1200-600/1-1
11KV BUS ISOLATOR WITH
EARTH SWITCH

WAVE TRAP

POTENTIAL TRANSFORMER
11kV/110V 100-50/1-1-1 200/1-1 200/1-1 200/1-1 200/1-1 200/1-1 200/1-1 200/1-1 200/1-1 PTR:
11KV/110v

POWER TRANSFORMER
250 kVA
11/0.4 KV
CAPACITOR VOLTAGE
12 TRANSFORMER
1 2 3 4 9 10 11

ST. Aux.
Xmer
SINGLE LINE DIAGRAM OF 66/11 kV SUB-STATION DAVNI 50
AS ON: 06-01-2016

(S/C LINE) (S/C LINE) (S/C LINE) DC SYSTEM STATUS


[2.110km] [2.391km] [0.60km]
AKANWALI INDORAMA WINSOM BATTERY BANK BATTERY CHARGER
DC VOLTAGE
CAPACITY STATUS RATING STATUS
Boost:2x20A
220 V 200Ah Functional
Float:2x20A Functional

48 V 200Ah Boost:2x20A
Functional Functional
Float:2x20A

CONDUCTOR/EARTH-WIRE DETAIL

66 kV BUS AAAC TARANTULA (37/5.23mm)

(CTR:400-200/1-1-1-1A) (CTR:100-50/1-1-1-1A) (CTR:100-50/1-1-1-1A) 66 kV LINE PANTHER (30/7/3.00mm)


SF6 CB SF6 CB SF6 CB
EARTH-WIRE GSS (7/3.15mm)

22 kV BUS

66 kV BUS 22 kV LINE

PTR: 66kV/110V

SF6 CB SF6 CB LEGEND


CTR:200-100/1-1-1-1-0.577A CTR:200-100/1-1-1-1-0.577A
LIGHTENING ARRESTOR
T1 T2
Y 20 MVA Y 20 MVA
66/11 kV 66/11 kV CIRCUIT BREAKER
TC: ON LOAD TC: ON LOAD
Y No.of Taps:17 Y No.of Taps:17
NormalTap:7 NormalTap:7 CURRENT TRANSFORMER
CTR:1200-600/1-1-.577A CTR:1200-600/1-1-.577A
ISOLATOR WITHOUT
EARTH SWITCH

1200-600/1-1
11KV BUS ISOLATOR WITH
EARTH SWITCH

WAVE TRAP

POTENTIAL TRANSFORMER
11kV/110V 100-50/1-1-1 200/1-1 200/1-1 200/1-1 200/1-1 200/1-1 200/1-1 200/1-1 200/1-1 PTR:
11KV/110v

POWER TRANSFORMER
250 kVA
11/0.4 KV
CAPACITOR VOLTAGE
12 TRANSFORMER
1 2 3 4 9 10 11

ST. Aux.
Xmer
SINGLE LINE DIAGRAM OF GHANVI 51
CONDUCTOR/EARTH-WIRE DETAIL

(3.565 km.) (3.565 km.) (20.14 km.) 132 kV BUS


KOTLA(Ckt-II) KOTLA(Ckt-I) NATHPA

132 kV LINE

EARTH-WIRE

33 kV BUS-1

33 kV BUS-2

33kV LINE

Connected Connected Connected


(CTR: 250/1) (CTR: 250/1) (CTR: 250/1)

LEGEND

LIGHTENING ARRESTOR

66 kV Bus B1 Bus B2
CIRCUIT BREAKER

Y Y CURRENT TRANSFORMER
Y Y
Y Y
(PTR: (PTR:
66kV/110V) 66kV/110V) ISOLATOR WITHOUT
EARTH SWITCH

22 kV Bus
ISOLATOR WITH
EARTH SWITCH
GT1 GT2
(13.75 MVA) (13.75 MVA)
11/66 KV 11/66 KV WAVE TRAP
TC: ON/Off LOAD Y TC: ON/Off LOAD Y
No.of Taps:17 No.of Taps:17
NormalTap: NormalTap:
POTENTIAL TRANSFORMER
ST. XFMR-I ST. XFMR-II
22/0.415 kV 22/0.415 kV
Y 500 KVA Y 500 KVA
(PTR: POWER TRANSFORMER
(PTR:
11kV/110V) Connected 11kV/110V) Connected
(CTR:750/5) (CTR:750/5)
To 415 V, AC Kotla(Jeori) To 415 V, AC Kotla(Jeori) CAPACITOR VOLTAGE
Switchgear&UAT Switchgear&UAT TRANSFORMER
Feeder-I Feeder-II
UNIT-I UNIT-II
(11.25 MW) (11.25 MW)

DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


DC VOLTAGE
CAPACITY STATUS RATING STATUS

220 V

48 V
52
SINGLE LINE DIAGRAM OF 66/11 kV SUB-STATION GOLTHAI
AS ON: 21-01-2016

(S/C LINE) (S/C LINE)


UNA BHAKRA PH
(15.98 km.) (1.813 km.) CONDUCTOR/EARTH-WIRE DETAIL

WOLF PANTHER 66 kV BUS MOOSE (54/7/3.53mm)

66 kV LINE PANTHER (30/7/3.00mm)


WOLF (30/7/2.59mm)

EARTH-WIRE GSS (7/2.64mm)

11 kV BUS INDOOR COPPER STRIP


ACSR-1. 6/1/4.72mm
11 kV LINE
2. 6/1/2.59mm

(CTR:500-250/1-1-1) (CTR:500-250/1-1-1)
LEGEND

SF6 SF6
LIGHTENING ARRESTOR

CIRCUIT BREAKER
66 kV Bus Bar B1
CURRENT TRANSFORMER

PTR:[66kV/110V] ISOLATOR WITHOUT


B2 EARTH SWITCH

ISOLATOR WITH
EARTH SWITCH
PTR:[66kV/110V]

WAVE TRAP
SF6

(CTR:200-100/1-1-1-0.577) (CTR:200-100/1-1-1-0.577)
(CTR:500-250/1-1-1) POTENTIAL TRANSFORMER
66/11 kV
Y (6.3 MVA)
TC: ON LOAD
Y No.of Taps:17
POWER TRANSFORMER
NormalTap:5
(CTR:1200-600/0.577-5-5-5A)
VCB CAPACITOR VOLTAGE
TRANSFORMER
11 kV BUS

PANTHER PANTHER
PTR:11kV/110V VCB VCB VCB VCB
SPS IND. SURAJ IND.
[.40km] [.260km]
(CTR:200-100/ (CTR:200-100/ (CTR:400-200/ (CTR:200-100/
DC SYSTEM STATUS 5-5-5A) 5-5-5A) 5-5-5A) 5-5-5A)

BATTERY BANK BATTERY CHARGER


DC VOLTAGE 250 kVA
CAPACITY STATUS RATING STATUS 11/0.4 kV
Y
200Ah Functional Boost:30A Functional BASSI PHASE-II BHAKRA
220 V Float:20A
[9.780km] [2.760km] [10.670km]
St. Xmer (ACSR-1) (ACSR-1) (ACSR-2)
400Ah Functional Boost:40A Functional
48 V
Float:55A
53
SINGLE LINE DIAGRAM OF 66/22 kV SUB-STATION GUMMA
AS ON: 18-01-2016

(S/C LINE) (S/C LINE) (S/C LINE) LEGEND


(42.04 KM.) (15.49 KM.) (21.029 KM.) CONDUCTOR/EARTH-WIRE DETAIL
KUMARSAIN JUTOGH SAINJ
66 kV BUS PANTHER (30/7/3.00mm)
LIGHTENING ARRESTOR

66 kV LINE ZEBRA (54/7/3.18mm)


CIRCUIT BREAKER
EARTH-WIRE GSS-(7/3.15 mm)
CURRENT TRANSFORMER
22 kV BUS WOLF (30/7/2.59mm)
ISOLATOR WITHOUT
22kV LINE DOG (6/1/4.72mm) EARTH SWITCH

ISOLATOR WITH
EARTH SWITCH
(CTR:300-150/1-1A) (CTR:300-150/1-1A) (CTR:300-150/1-1A)

MOCB MOCB MOCB WAVE TRAP

DC SYSTEM STATUS
POTENTIAL TRANSFORMER
BATTERY BANK BATTERY CHARGER
DC VOLTAGE
(CTR:300-150/1-1A)
66 kV BUS CAPACITY STATUS RATING STATUS
POWER TRANSFORMER
MOCB
220 V 200Ah Functional Boost:50A
Functional
Float:30A
CAPACITOR VOLTAGE
48 V N.A. N.A. N.A. N.A. TRANSFORMER

(CTR:100-50/1-1A) (CTR:100-50/1-1A) (CTR:60-30/1-1A)

T1 6.3 MVA T3 6.3 MVA


T2 10 MVA
Y 66/22 kV Y 66/22 kV Y 66/22 kV
TC: ON LOAD TC: ON LOAD
TC: ON LOAD No.of Taps:17
Y No.of Taps:17 Y No.of Taps:17 Y NormalTap:7
NormalTap:7 NormalTap:5 (NON-FUNCTIONAL)
CAPACITOR BANK: 2x2.4 MVAR
(CTR:300-150/1-1A) (CTR:300-150/1-1A) (CTR:300-150/1-1A)

MOCB MOCB MOCB

CTR:150-300/1-1
PT: 22kV/
110V
VCB
(CTR:300-150/1-1A) (CTR:300-150/1-1A)
22 kV BUS

PT: 22kV/ PT: 22kV/


110V 110V

(CTR:50-25/1-1A) (CTR:200-100/ (CTR:200-100/ (CTR:100-50/ (CTR:200-100/ (CTR:100-50/ (CTR:100-50/ (CTR:200-100/ (CTR:100-50/ (CTR:300-150/ (CTR:200-100/ (CTR:200-100/
(CTR:100-50/1-1A)
1-1A) 1-1A) 1-1A) 1-1A) 1-1A) 1-1A) 1-1A) 1-1A) 1-1A) 1-1A) 1-1A)
MOCB MOCB MOCB MOCB MOCB MOCB MOCB MOCB MOCB MOCB MOCB VCB VCB VCB

(CTR:15-7.5/1-1A)

100 KVA
22/0.4 KV

ST. Aux.
Xmer
AIR SUNI DRABLA NO-I GUMMA-I DRABLA-II KADHAR CHAIR GUMMA-II THEOG CHABBA MASHOBRA GUMMA-III GHARGUMMA
(4.900 km) (17.00 km) (1.450 km) (0.600 km) (1.450 km) (11.00 km) (12.900 km) (0.550 km) (18.0 km) (10.5 km) (6.750 km) (0.750 km) (0.900 km)
SINGLE LINE DIAGRAM OF 66/22 kV SUB-STATION HULLI
AS ON: 13-01-2016 54
SAINJ
(9.992 Km.)
(S/C LINE) CONDUCTOR/EARTH-WIRE DETAIL
LEGEND
66 kV BUS ZEBRA (54/7/3.18mm)

LIGHTENING ARRESTOR 66 kV LINE WOLF (30/7/2.59mm)

CIRCUIT BREAKER EARTH-WIRE GSS-(7/3.15 mm)

CURRENT TRANSFORMER 22 kV BUS INDOOR COPPER STRIP

22 kV LINE ACSR: 1. 6/1/4.72mm


ISOLATOR WITHOUT 2. 6/1/3.35mm
EARTH SWITCH 3. 12/7/2.48mm
4. 6/1.409mm
(CTR:300-150/1-1-1-1A)
SF6(66KV, ISOLATOR WITH
2000A) EARTH SWITCH
(P.T.R.: 66kV/110V)
WAVE TRAP
DC SYSTEM STATUS

66 kV Bus Bar POTENTIAL TRANSFORMER BATTERY BANK BATTERY CHARGER


DC VOLTAGE
CAPACITY STATUS RATING STATUS

POWER TRANSFORMER 220 V 200Ah Functional 40A Functional

SF6 SF6 48 V N.A. N.A. N.A. N.A.


CAPACITOR VOLTAGE
(CTR:150-75/1-1-1) (CTR:300-150/1-1-1-1A) TRANSFORMER
66/22 kV,3-Ph, 66/22 kV,3-Ph,
Y 10 MVA,T-2 Y 10 MVA,T-1
TC: ON LOAD
TC: ON LOAD No.of Taps:17
Y No.of Taps:17 Y NormalTap:7
NormalTap:7

(CTR: 400-200/1-1-1-1A) (CTR: 400-200/1-1-1-1A)


(NON-FUNCTIONAL)
SF6 SF6 CAPACITOR BANK [25.3 KV, (2x2.4) = 4.8 MVAR]
(P.T.R.:22kV/110V) (P.T.R.:22kV/110V)

Connected (CTR:
(CTR: 400-200/1-1A) 300-150/1-1)

22 kV Indoor Bus Bar


SF6(22KV, SF6(22KV, SF6(22KV, SF6(22KV, SF6(22KV, SF6(22KV, SF6(22KV,
1250A) 1250A) 1250A) 1250A) 1250A) 1250A) 1250A)

CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR:


(100-50/1-1-1) 200-100/1-1-1) 200-100/1-1-1) 200-100/1-1-1) 200-100/1-1-1) 200-100/1-1-1) 200-100/1-1-1)

250 KVA
22/0.433 kV

STN.XFMR BAGGI PRAGTINAGAR KOTKHAI CHOPAL G/MAHASU THEOG


[32.0km] [3.980km] [11.30km] [50.0km] [9.80km] [12.0km]
(ACSR-1) (ACSR-4) (ACSR-3) (ACSR-1) (ACSR-2) (ACSR-2)
SINGLE LINE DIAGRAM OF 66/22 kV SUB-STATION KUMARSAIN
AS ON: 07-01-2016 LEGEND 55
[17.30Km.) [25.694Km.)
NAGAN FEEDER NOGLI FEEDER
CONDUCTOR/EARTH-WIRE DETAIL
LIGHTENING ARRESTOR
66 kV BUS PANTHER (30/7/3.00mm)
CIRCUIT BREAKER
66 kV LINE WOLF (30/7/2.59mm)
CURRENT TRANSFORMER
EARTH-WIRE GSS-(7/3.15 mm)
ISOLATOR WITHOUT
22 kV BUS WOLF (30/7/2.59mm) EARTH SWITCH

ACSR- 1. 6/1/3.35mm
22 kV LINE 2. 6/1/4.9mm ISOLATOR WITH
AAAC- 7/3.8mm EARTH SWITCH
(CTR: 300-150/1-1-1) (CTR: 300-150/1-1-1)
WAVE TRAP

POTENTIAL TRANSFORMER

66 kV Bus Bar POWER TRANSFORMER

CAPACITOR VOLTAGE
TRANSFORMER

CAPACITOR BANK DC SYSTEM STATUS


(CTR:100-50/1-1-1) 22kV, [2x2.4] MVAR (CTR: 100-50/1-1-0.577)
(FUNCTIONAL) T2. 10 MVA BATTERY BANK BATTERY CHARGER
T1. 6.3 MVA
66/22kV XFMR 66/22kV XFMR DC VOLTAGE
TC: ON LOAD CAPACITY STATUS
TC: ON LOAD No.of Taps:17
RATING STATUS
No.of Taps:17 NormalTap:5
NormalTap:5 Boost:30A
(NON-FUNCTIONAL) (CTR: 100-50 220 V 200Ah Functional Functional
Float:20A
/1-1-1) (CTR:400-200/1-1-1-1)
(CTR:300-150/1-1-1) Boost:30A
48 V 200Ah Functional Functional
Float:20A
(CTR: 300-150/1-1-1)
22kV Bus

PTR: PTR:
[22kV/110V] [22kV/110V]

(CTR:100-50/ (CTR:150-/1-1) (CTR:100-50/ (CTR:100-50/ (CTR:100-50/ (CTR:200-100/1-1A) (CTR:50-25/ (CTR:100-50/ (CTR:180-90/ (CTR:50-25/ (CTR:15-7.5/
1-1) 1-1) 1-1) 1-1) 1-1) 1-1) 1-1) 1-1) 5-5)

STN. XFMR
THANEDHAR ANNI NANKHARI MADHWANI SPARE ADANI NARKANDA KUMARSAIN RAMPUR BARAGAON [63 KVA]
FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER (7 m, 50mm2)
[8.0km] [22.0km] [25.0km] [132.0km]
[76km] [23.8km] [40.0km] [18.0km] [48.0km]
(ACSR-1) (ACSR-1) (ACSR-2) (ACSR-1) (ACSR-1)
(AAAC) (ACSR-1) (ACSR-1) (ACSR-1)
SINGLE LINE DIAGRAM OF 66/33/11 kV SUB-STATION, NALAGARH LEGEND
56
AS ON: 06-01-20116

LIGHTENING ARRESTOR
(ACSR-2) (ACSR-2)
UPERLA UPERLA (ACSR-1)
NANGAL-1 NANGAL-2 AKANWALI CIRCUIT BREAKER
[3.510 km] [3.510 km] [14.507 km]
(ACSR-1) (ACSR-1) CURRENT TRANSFORMER
CONDUCTOR/EARTH-WIRE DETAIL AKANWALI BADDI GPIL
WOLF [14.507 km] [16.739 km] [1.545 km]
ISOLATOR WITHOUT
66 kV BUS TWIN AAAC TARANTULA(37/5.23mm) EARTH SWITCH
POPLAR-II PANTHER PANTHER
ACSR 1.PANTHER (30/7/3.00 mm)
66 kV LINE
2. ZEBRA (54/7/3.18mm) ISOLATOR WITH
POPLAR-II (37/3.05mm) EARTH SWITCH

EARTH-WIRE GSS - (7/3.15 mm)


WAVE TRAP
33 kV BUS SINGLE AAAC TARANTULA(37/5.23mm)

33 kV LINE CTR:500-250 POTENTIAL TRANSFORMER


CTR:1200-600/ CTR:1200-600/ CTR:500-250 CTR:600-300 CTR:500-250
1-1-1-1 1-1-1-1 /1-1-1-1A /1-1-1-1A /1-1-1A /1-1-1-1A
11 kV BUS
MOCB MOCB MOCB MOCB MOCB MOCB
POWER TRANSFORMER
11 kV LINE

CAPACITOR VOLTAGE
TRANSFORMER
CTR:1200-600/ 66 kV BUS
1-1-1-1
PTR:
66kV/110V

CTR:200-100/
CTR:200-100/ 1-1-1-0.577 CTR:200-100/ CTR:200-100/ CTR:200-100/
SPARE SPARE SIDHARTHA MANJHOLI 1-1-1-0.577 1-1-1-0.577 1-1-1-0.577 1-1-1-0.577
MOCB MOCB MOCB
T4 66/33 kV POOJA
T2 66/11 kV B/WALA INDUSTRIAL KHERA-II DABHOTA NALAGARH COTSPIN T1 66/11 kV
T5 66/33 kV (10 MVA) T3 66/33 kV
(20 MVA) (20 MVA) (20 MVA)
(20 MVA) TC: ON LOAD
33/11 kV TC: ON LOAD TC: ON LOAD TC: ON LOAD
TC: ON LOAD No.of Taps:17
No.of Taps:17 No.of Taps:17 No.of Taps:17
3.15 MVA No.of Taps:17 NormalTap:5
NormalTap:5 NormalTap:5 NormalTap:5
NormalTap:5 CTR: CTR: CTR: CTR: CTR: CTR:
300-150/5 300-150/5 600-300/5 300-150/5 300-150/5 300-150/5 CTR:1200-600/
CTR: CTR: CTR: CTR: CTR:400-200/ CTR:1200-600/
100-50/5 200-100/1 100-50/1 300-150/1 CTR:400-200/ 1-1-1-0.577 CTR:400-200/ 1-1-.577A 1-1-.577A
1-1-1-0.577 1-1-1-0.577

PTR:
11kV/110V 11kV/110V

PTR: CTR: CTR: CTR: CTR: CTR: CTR: CTR:


33kV/110V CTR: 300-150/5 200-100/5 300-150/5 300-150/5
300-150/5
400-200/5 300-150/5 300-150/5

33 kV BUS
GODREJ ASIDE G/CLARIDGE PANJAHRA KHERA-I MIDC RAMSHAHAR HIMCHEM
SF6 SF6
CTR: CTR: PTR:
150-75/1-1 150-75/1-1 33kV/110V

CTR: CTR: CTR: CTR: CTR: CTR: DC SYSTEM STATUS


200-100/1-1 100-50/1-1A 300-150/1-1A 100-50/1 100-50/1 CAPACITOR BANK-3 CAPACITOR BANK-4
200-100/1-1 (1.2+1.8 MVAR) BATTERY BANK BATTERY CHARGER (1.2+1.8 MVAR)
Functional DC VOLTAGE
33/0.4 kV Non-Functional
100 kVA CAPACITY STATUS RATING STATUS
(FUNCTIONAL) (NON-FUNCTIONAL)
(2x7.2 MVAR) Boost:50A
220 V 200Ah Functional Functional
Float:50A
Boost:30A
48 V 400Ah Functional Float:30A Functional
SIDHIVINAK SIDDHRTHA MANJHOLI TVS MANJHOLI RAMSHAHAR BAROTIWALA STATION
TRANSFORMER
SINGLE LINE DIAGRAM OF 66/22 kV SUB-STATION NATHPA
AS ON: 05-01-2016
LEGEND 57
(PTR: 66kV/110V)

CONDUCTOR/EARTH-WIRE DETAIL LIGHTENING ARRESTOR

66 kV BUS ZEBRA (54/7/3.75 mm)


66 kV BUS
CIRCUIT BREAKER
66 kV LINE ACSR WOLF (30/7/2.59 mm)
CURRENT TRANSFORMER

EARTH-WIRE GSS-(7/3.15 mm)


ISOLATOR WITHOUT
EARTH SWITCH
22 kV BUS ACSR WOLF (30/7/2.59 mm)
(CTR:100/1) (CTR:200/1)
(CTR: 400-200/1-1-1-1)
66/22 kV 66/22 kV 22 kV LINE ISOLATOR WITH
(20MVA) EARTH SWITCH
(10MVA) Y Y
TC: ON LOAD
TC: Off LOAD T1 No.of Taps:17
T2
No.of Taps:17
NormalTap:5 Y NormalTap:5 Y WAVE TRAP
*OLTC (CTR:100-50/1-1-1-0.577) (CTR:400-200/
Non-functional 1-1-1-.577) POTENTIAL TRANSFORMER
CAPACITOR BANK [2*2.4 MVAR]
(Functional)
(PTR: 22kV/110V)
Connected
(CTR: 300/1) POWER TRANSFORMER
Connected
(CTR:300-150/1-1) Kotla-Ghanvi Ckt-1
22 KV BUS (26.270 km)
CAPACITOR VOLTAGE
22 kV INDOOR SWITCHGEAR TRANSFORMER

DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


DC VOLTAGE
Connected Connected Connected Connected Connected Connected Connected CAPACITY STATUS
(CTR:500-250/1-1)
RATING STATUS
(CTR:400-200/1-1) (CTR:200-100/1) (CTR:15-7.5/5-5) (CTR:400-250/5-5) (CTR:50-25/1-1) (CTR:200-100/1-1)
Connected
(CTR:500-250/1-1) 220 V 200 Ah Functional 20 A Functional

48 V 200 Ah Functional 16 A Functional

NICHAR Karcham JP OLD Katgaon NJPC Old Kinnaur


[5.50 km] (RUKTI 1.5MW+ [14.00km] [19 km] [2.00 km] [14.00km]
DOOR SANCHAR 5MW) TANGLING+SHYANG TONG
[28 km] TO STN. XFMR INCOMING

22 kV INDOOR SWITCHGEAR 22 kV INDOOR SWITCHGEAR

(CTR: (CTR: (CTR:


200-100/1-1A) (CTR: (CTR: (CTR: (CTR: (CTR:
200-100/1-1) 200-100/1-1A) 300-150/1-1A)
1200-600/1-1A) 600-300/1-1A) 300-150/1-1A) 600/1A)

BAP INCOMER BAP 1 22kV INCOMER


BAP 2 NEW JP REGENT SHP
[19 km] [19 km] FROM OUTDOOR BUS PANVI SHP NOGLI FEEDER
[5.0 km] [3.0 km] [4.5 km] [7 km]
SINGLE LINE DIAGRAM OF 66/22 kV SUB-STATION NOGLI
AS ON: 02-12-2014 58
LEGEND
[34.41 km] [25.69 km] [24.71 km]
SAMAULI(ROHRU) JOGNI (IPP)
KUMARSAIN JEORI
CONDUCTOR/EARTH-WIRE DETAIL LIGHTENING ARRESTOR

66 kV BUS
CIRCUIT BREAKER

66 kV LINE CURRENT TRANSFORMER

EARTH-WIRE GSS-(7/3.15 mm)


ISOLATOR WITHOUT
EARTH SWITCH
22 kV BUS

ISOLATOR WITH
22 kV LINE EARTH SWITCH
Connected Connected Connected CTR:
(CTR: 300/1) (CTR: 300/1) (CTR: 300/1) 400-200/1-1-1-1 WAVE TRAP

POTENTIAL TRANSFORMER

66 kV Bus POWER TRANSFORMER

Unit-I Unit-II Unit-III Unit-IV Unit-V Unit-VI CAPACITOR VOLTAGE


TRANSFORMER

T1
(10 MVA)
(66/22 KV)

CAPACITOR BANK T-2 T-3 T-4 T-5


22kV, [2x2.4] MVAR (300 kVA) (300 kVA) (1250 kVA) (1250 kVA)
(0.4/22 KV) (0.4/22 KV) (0.4/22 KV) (0.4/22 KV)

22kV BUS

CTR: CTR: CTR: CTR: CTR: CTR: CTR: CTR: CTR:


200-100/1 200-100/1 100-50/1 60-30/5 60-30/1 180-90/1 100-50/1 200-100/1 60-30/1

OLD RAMPUR JAKAT KHANA DANSA TAKLECH THANEDHAR KUMARSAIN RAMPUR NIRMAND BAHLI
59
SINGLE LINE DIAGRAM OF 66/11 kV SUB-STATION PARWANOO
AS ON: 07-01-2016

LEGEND

(S/C) (S/C)
SOLAN BAROTIWALA LIGHTENING ARRESTOR
(18.50 km.) (17.213 km.)
(S/C)
CIRCUIT BREAKER
PINJORE
AAAC (8.230 km.)
DOTTEREL
CURRENT TRANSFORMER
DOTTEREL
ISOLATOR WITHOUT
EARTH SWITCH
DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER ISOLATOR WITH


DC VOLTAGE EARTH SWITCH
CAPACITY STATUS RATING STATUS
WAVE TRAP
220 V 200Ah Functional Float:20A Functional (CTR: (CTR:
Boost:30A (CTR:200-150-75/1-1-1) 300-150/1-1) 300-150/1-1)
48 V Non- Float:20A Non- SF6 MOCB MOCB POTENTIAL TRANSFORMER
200Ah
Functional Boost:30A Functional

POWER TRANSFORMER

66 kV Bus Bar
CAPACITOR VOLTAGE
TRANSFORMER

PTR:[66kV/110V]
CONDUCTOR/EARTH-WIRE DETAIL

SF6 SF6 66 kV BUS ACSR - PANTHER (30/7/3.00 mm)


(CTR:200-100/1-1-1) (CTR:200-100/1-1-1) AAAC- 37/2.88mm
66 kV LINE DOTTEREL ACSR 12/7/3.08 mm
T-2 66/11 kV T-1 66/11 kV
Y (20 MVA) Y (20 MVA) GSS - (7/3.15 mm)
EARTH-WIRE
TC: ON LOAD (from YARD) TC: ON LOAD (from YARD) OPGW on Solan feeder
Y No.of Taps: 17 Y No.of Taps: 17
NormalTap: 5
11 kV BUS INDOOR COPPER STRIP
NormalTap: 5
ACSR -1.DOG (6/1/4.72 mm)
(CTR:1200-600/5-5) (CTR:1200-600/5-5) 2. 6/1/2.11 mm
VCB VCB 11 kV LINE AAAC- 1. 7/4.26 mm
(CTR:
1200-600/5-5) 2. 7/3.81 mm
PTR: PTR:
11kV/110V 11 kV BUS 11kV/110V

VCB
VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB

(CTR:200-100 300-150/1-1 300-150/1-1 CTR:25/1 (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR: (CTR:
(CTR:200-100 400-200/5-5) 400-200/5-5) 400-200/5-5) 400-200/5-5) 400-200/5-5) 400-200/5-5) 400-200/5-5) 400-200/5-5) 400-200/5-5) 200-100/5-5)
/1-1A) 200-100/1-1) 250-125/1-1) 250-125/1-1)
/1-1A)

100 kVA
11/0.4 kV
Y
KHADEEN SPARE PARWANOO-4 PARWANOO-2 PARWANOO-3 PARWANOO-5
(2 MVAR) (2 MVAR) WATER SUPPLY KASAULI COSMO GABRIAL SPARE PARWANOO-1 SPARE
[3.50 km] [4.00km] (2 MVAR) (2 MVAR)
Cap Bank-3 Cap Bank-4 (1.3 km.) (34.8 km.) (11.885 km.) (2.65 km.) (8.5 km.) (1.2 km.) (4.1 km.) (2.3 km.) Cap Bank-1
(ACSR-DOG) St. Xmer (ACSR-2) (ACSR-1) Cap Bank-2
Non- Non- (ACSR-2) (ACSR-DOG) UPTO NARIYAL (AAAC 1/ (ACSR-DOG) (ACSR-1) (AAAC 1) Functional
Functional
Functional Functional (ACSR-DOG) AAAC 2)
SINGLE LINE DIAGRAM OF 66/11 kV SUB-STATION SAINJ 60
AS ON: 20-01-2016

(S/C LINE) (S/C LINE)


(21.029 KM.) (9.992 KM.)
CONDUCTOR/EARTH-WIRE DETAIL
GUMMA HULLI

66 kV BUS ZEBRA (54/7/3.18mm)

66 kV LINE WOLF(30/7/3.00mm)

EARTH-WIRE GSS-(7/3.15 mm)

22 kV BUS INDOOR COPPER STRIP

ACSR 6/1/3.35mm
22 kV LINE AAAC 1. 7/3.18mm
2. 7/3.15mm

11 kV BUS INDOOR COPPER STRIP


(CTR:600-300/1A) (CTR:300-150/1A)

SF6 11 kV LINE ACSR 6/1/3.35mm


SF6

LEGEND

66 kV BUS
LIGHTENING ARRESTOR

PTR: 66kV/110V CIRCUIT BREAKER

CTR:100-50/1 CURRENT TRANSFORMER

(AAAC-2) (ACSR) (AAAC-1) (ACSR) SF6 SF6 ISOLATOR WITHOUT


[3.70km] [27.0km] [12.0km] [150km] EARTH SWITCH
6.3 MVA (CTR:100-50/1-1A (CTR:100-50/1-1A
ADANI DEHA LELLU PULBHAL 66/22 kV
T2 6.3 MVA
TC: ON LOAD T1 6.3 MVA ISOLATOR WITH
No.of Taps:17 66/11 kV 66/11 kV EARTH SWITCH
NormalTap:8 Y Y TC: ON LOAD
CTR:75/1 TC: ON LOAD
CTR:75/1 CTR:75/1 No.of Taps:17 No.of Taps:17
CTR:75/1 Y NormalTap:8 Y NormalTap:8 WAVE TRAP
VCB
VCB VCB VCB VCB
CTR:100-50/ (CTR:200-100/0.577-1-1-1A) (CTR:200-100/0.577-1-1-1A) POTENTIAL TRANSFORMER
.577-1-1-1A
VCB VCB

POWER TRANSFORMER

VCB CAPACITOR VOLTAGE


TRANSFORMER

DC SYSTEM STATUS
VCB VCB VCB VCB VCB
BATTERY BANK BATTERY CHARGER
DC VOLTAGE
CTR:200-100/1 CTR:200-100/1 CTR:25/1 CTR:200-100/1 CTR:200-100/1 CAPACITY STATUS RATING STATUS

220 V Boost:40A Functional


200Ah Functional Float:24A
100 KVA
48 V N.A. N.A. N.A. N.A.
22/0.4 KV

IPH STAGE-I IPH STAGE-I IPH STAGE-II IPH STAGE-II


[2.22km] [4.00km] [10.22km] [12.0km]
ST. Aux.
Xmer
SINGLE LINE DIAGRAM OF 66/11 kV SUB-STATION TERRACE 61

AS ON: 13-01-2016
CONDUCTOR/EARTH-WIRE DETAIL

(S /C LINE) 66 kV BUS ZEBRA (54/7/3.18mm)


(6.4 km)
Pong Feeder 66 kV LINE WOLF (30/7/2.59mm)

EARTH-WIRE GSS-(7/3.15 mm)

11 kV BUS INDOOR COPPER STRIP


ACSR: 6/1/4.72mm
11 kV LINE AAAC:1. 7/4.26mm
2. 7/3.15mm
XLPE Cable: 120mm2

DC SYSTEM STATUS
LEGEND
BATTERY BANK BATTERY CHARGER
DC VOLTAGE
LIGHTENING ARRESTOR
(CTR: 300-150/1-1-1A) CAPACITY STATUS RATING STATUS
SF6 Boost:30A
220 V 200Ah Functional Float:20A Functional CIRCUIT BREAKER

200Ah Boost:30A
48 V Functional Float:20A Functional CURRENT TRANSFORMER

ISOLATOR WITHOUT
66 kV Bus Bar EARTH SWITCH
PTR:.
[66kV/110V]
ISOLATOR WITH
EARTH SWITCH

MOCB SF6 WAVE TRAP

(CTR: 200-100/1-1-1-.577A) (CTR: 200-100/1-1-1-.577A)


T-1 66/11 kV T-2 66/11 kV POTENTIAL TRANSFORMER
Y (10 MVA) (10 MVA) Y
TC: Off LOAD TC: Off LOAD
Y No.of Taps:5 No.of Taps:5 Y
NormalTap:2 NormalTap:2
POWER TRANSFORMER
PTR: (CTR:1200-600/1-1-1-.577A) PTR:
11kV/110V (CTR:1200-600/1-1-1-.577A)
11kV/110V
VCB VCB
CAPACITOR VOLTAGE
(CTR:1200-600/1-1-1-.577A) TRANSFORMER
11 kV BUS

VCB

VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB

(CTR:100-50/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:100-50/ (CTR:100-50/ (CTR:100-50/ (CTR:200-100/ (CTR:200-100/ (CTR:200-100/ (CTR:100-50/
1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A) 1-1-1A)

100 kVA
11/0.4 kV
Y
Goyal Sri Ganesh Kasba Ind. Area Spare Spare Premier Spare Ind. Area DV Steel Seul Khad
Furnance Furnance Kotla Phase-1 Alcobev Phase-2 [0.390km] [13.981km]
St. Xmer [0.240km] [0.120km] [29.388km] [3.520km] [0.265km] [2.615km] (AAAC-1) (ACSR)
(AAAC-1) (ACSR) (AAAC-2) (XLPE) (AAAC-1)
(AAAC-1)
SINGLE LINE DIAGRAM OF 66/22 kV SUB-STATION SMOLI
AS ON: 07-01-2016 62

[34.408 km] [13.10 km]


NOGLI ANDHRA (CHIRGAON)
S/C LINE S/C LINE
CONDUCTOR/EARTH-WIRE DETAIL LEGEND

66 kV BUS PANTHER(30/7/3.00mm)
LIGHTENING ARRESTOR

66 kV LINE WOLF (30/7/2.59mm)


CIRCUIT BREAKER
EARTH-WIRE GSS-(7/3.15 mm)
CURRENT TRANSFORMER
22 kV BUS PANTHER(30/7/3.00mm)
ISOLATOR WITHOUT
ACSR (6/1/4.72mm) EARTH SWITCH
22 kV LINE AAAC (7/3.81mm)

ISOLATOR WITH
EARTH SWITCH

Connected Connected
(CTR: 300-150/1-1A) (CTR: 300-150/1-1A) WAVE TRAP

POTENTIAL TRANSFORMER
66 KV, B1

POWER TRANSFORMER

Connected (ACSR) (ACSR) Connected


(CTR: 200-100/1-1) CAPACITOR VOLTAGE
(CTR:150-75/1-1) [15.0km] [15.0km] TRANSFORMER
Chirgaon-1 Chirgaon-2

16 MVA 10 MVA
Y 66/22 kV 66/22 kV DC SYSTEM STATUS
TC: ON LOAD TC: ON LOAD
No.of Taps:17 No.of Taps:17 BATTERY BANK BATTERY CHARGER
NormalTap:5 NormalTap:5 DC VOLTAGE
Connected CAPACITY STATUS RATING STATUS
(CTR: 200-100/1-1A) (CTR: 200-100/1-1A)
(NON-FUNCTIONAL) Boost:30A
CAPACITOR BANK [(2x2.4) = 4.8 MVAR] 220 V 200Ah Functional Functional
Connected Float:20A
(CTR: 900-450/1-1-1) (CTR: 600-300/1-1)
48 V Boost:15A Functional
200Ah Functional
Float:10A
(CTR:
300-150/1-1)

Connected Connected
(CTR: (CTR: (CTR:200-100/1-1A) (CTR:300-150/1-1A)
(CTR:200-100/1-1A)
400-200/1-1-1) 400-200/1-1-1)

100 KVA
22kV/0.4kV

STN.XFMR
Rohru-1 Rohru-2 Spare SWARA KUDDU MASLIHED
[2.64km] [2.64km] [26.5km] [12.0km]
(AAAC) (AAAC) (ACSR) (ACSR)
SINGLE LINE DIAGRAM OF 66/15/11 kV SUB-STATION AT TOTU (SHIMLA) 63
AS ON: 18-01-2016

(S/C LINE) (D/C LINE) CONDUCTOR/EARTH-WIRE DETAIL


(25.27KM.) (1.555KM.)
SOLAN JUTOGH 66 kV BUS PANTHER (30/7/3.00mm)

66 kV LINE AAAC-UPAS (37/3.53mm)

EARTH-WIRE

33 kV BUS

11kV LINE ACSR-DOG(6/1/4.26mm)

66 kV BUS

DC SYSTEM STATUS

BATTERY BANK BATTERY CHARGER


OCB DC VOLTAGE
CAPACITY STATUS RATING STATUS
(CTR:400-200/1-1-1A)
Functional Boost:60A
OCB 220 V 200Ah Float:40A
Functional
T4
Y 6.3 MVA
66/11 kV 48 V N.A. N.A. N.A. N.A.
T3 T2
Y TC:Off LOAD Y 6.3 MVA Y 6.3 MVA
ISOLATOR No.of Taps:5
NormalTap:2 66/11 kV 66/11 kV
Y TC:Off LOAD Y TC:Off LOAD LEGEND
PTR: 11kV/110V No.of Taps:5 No.of Taps:5
CTR:
NormalTap:2 NormalTap:2

AUTO-REC LIGHTENING ARRESTOR

T1
Y 20 MVA INCOMING (A/R) CIRCUIT BREAKER
66/11 kV
Y CHAKKAR (A/R) CURRENT TRANSFORMER
TC: ON LOAD
No.of Taps:17
NormalTap:5 TARADEVI (A/R)
ISOLATOR WITHOUT
(CTR:1200-600/ EARTH SWITCH
1-1A)
VCB
(CTR:1200-600/ ISOLATOR WITH
VCB 1-1A) EARTH SWITCH
11 kV BUS
WAVE TRAP

POTENTIAL TRANSFORMER
(CTR:300-150/ (CTR:300-150/ (CTR:300-150/ (CTR:300-150/ (CTR:300-150/ (CTR:300-150/ (CTR:300-150/ (CTR:300-150/ (CTR:300-150/
1A) 1A) 1A) 1A) 1A) 1A) 1A) 1A) 1A)

POWER TRANSFORMER

CAPACITOR VOLTAGE
STP M.E.S. JUTOGH DHAMI C/PLANT TARADEVI BANUTI CHAKKAR SUMMER HILL STN AUXILIARY TRANSFORMER
(GADOG) [54.0km] [18.0km] [1.0km] [40.0km] [45.0km] [6.50km] [2.360km]
[3.0km]
64
PROPOSED OFC ROUTING DIAGRAM OF HPSEBL ABOVE 66kV( INCLUDING EXISTING & OFC PROPOSED UNDER PRIORITY LINKS &
ADDITIONAL COMMUNICATION REQUIREMENT)
2.00 km.
Naptha Bhaba(E) 13.10 km.
Proposed SAMOLI ANDRA(E)
Proposed
(OPGW) Proposed
39.00 km. (OPGW)
(OPGW) Proposed PLCC
Proposed 20.140 km. Baspa (E) Wangtoo
34.41 km. (OPGW)
(OPGW) Kashang
Proposed
Proposed
3.565 km. (OPGW) PLCC
Ghanvi (E) Jeori(E) 24.71km. (OPGW) NOGLI 25.69km.
Proposed Ksain
Proposed 42.04km.
(OPGW)
PGCIL Proposed (OPGW)
1.55 km. (OPGW) 15.490 km. GUMMA 21.29km. Sainj 9.992km.
HULLI
Totu Existing Proposed Proposed
Proposed
(ADSS) (OPGW) (OPGW) (OPGW)
6.0 km. 20.000 km.
Kumar House JUTOGH(E) Maliana KALA AMB(E)
32.00 km. Proposed
Palampur (E) Jhakri
Bassi(E) Darlaghat (E) 15.34km. (OPGW) Proposed 31.96km.
Proposed Kunihar(E) (OPGW)
(OPGW) Proposed
Proposed (OPGW)
13.563 km. Proposed 47.64km.
180km.
Kurthala (OPGW) 20.00 km. 63.99 km.(OPGW) Under Central
Proposed 15.00 km. Existing SOLAN(E) GIRI(E) 16.39km. PONTA
(OPGW) PGCIL Existing Proposed Sector
(OPGW) 18.5 km. Existing
45.42 km. Proposed (OPGW) (OPGW)
PGCIL Existing (OPGW) Abdullapur
(OPGW)
(OPGW)
Bathri Kangra(E)
26.03km. PARWANOO
36.00 km. Bagha (E) PGCIL Existing
Chullah Gaura
39 km. Proposed 16.205km. (OPGW)
30 km. Proposed BAROTIWALA (E)
(OPGW) (OPGW) Proposed Sonepat
(OPGW)
Hamirpur-I(E) Proposed Kangoo(E)
42.139 km. 3.250 km. PGCIL Existing 27.0 km.
(OPGW)
Existing (OPGW)
Proposed Existing
60 km. (OPGW)
Jassore(E) Dehra(E) (OPGW) (OPGW)
PGCIL Existing
Proposed
(OPGW)
(OPGW) 17.0 km. 3.50km.
Jahoo Mandhala BADDI(E) Nalagarh U/Nangal (E)
24.234 km. Proposed 4.90km. 53.00 km. 8.0 km. PGCIL Existing HPSEB PGCIL Existing
(OPGW) 6.40 km.
Proposed Existing Existing (OPGW) (OPGW) PGCIL Existing
(OPGW) (OPGW) (OPGW) (OPGW)
28 km.
Hmpr-II(E)
Ratti 10.301km. Existing Nalagarh
Kandrori (OPGW) PGCIL
43 km. Proposed
Existing Akkanwali
Proposed (OPGW) Proposed
(OPGW) Proposed
(OPGW) (OPGW)
Tahliwal
17.0 km.
Rakkar
31.3km.
Amb
Larji (E) (OPGW)
Mandi(E) ROW AGREEMENT SIGNED WITH PGCIL
20.00 km.
Pandoh
Existing
(OPGW)
ON 26.07.2010 FOR LAYING OF OPGW ON
15.980 km. Proposed
Proposed
(OPGW)
21.00 km. HPSEB HT/EHT LINES (PG-9 CP-303)
7.80 km. Proposed
(OPGW) (OPGW)
JUTOGH
Bajura(E) Legends
Golthai Gagret
1.55 km.
22 kV
25.27 km.
33 kV TOTU SOLAN
66 kV
132 kV 22.00 km.
220 kV 26.03 km.
BAROTIWALA KUNIHAR
33 kV S.Stn.
66 kV S.Stn. 3.250 km.
17.00 km.
132 kV S.Stn. BADDI NALAGRAH

220 kV S.Stn. 3.510 km.


E-EXISTING RTU NALAGARH
3.569 km.
UPERLA NANGAL
400 kV S.Stn.
65

Detail of Proposed/Existing OPGW Network of HPSEBL

S.No. Name of Line Total Voltage Existing (ULDC- Laid by ES Existing Laid by OPGW OPGW Proposed Total OPGW Remarks
OPGW Level (kV) I) (Kms) Wing (Kms) PGCIL Telecom as Proposed under Additional Proposed
(Existing+ per agreement under Priority Communication (Kms)
Proposed) Links Requirement
(Kms)

Part-I Part-II
1 Amb - Dehra 28 132 28 28
2 Dehra - Hamirpur II 43 132 43 43
3 Chullah - Bassi 15 132 15 15
4 Hamirpur II - Chullah 36 132 36 36
5 Jassore - Dehra 60 132 60 60
6 Pandoh - Mandi 20 132 20 20
7 Larji - Bajura 21 132 21 21
8 Jassore - Bathri 39 132 39 39
9 Amb-Gagret 7.80 132 7.80 7.80
10 Rakkar-Golthai 15.98 132 15.98 15.98
11 Kangoo - Ratti-Pandoh -Larji 53 132 53 53
12 Dehra-Kangra 29.93 132 29.93 29.93
13 Bhaba-Nathpa 2.000 220 2.000 2.000
14 Nathpa-Ghanvi 20.140 66 20.140 20.140
15 Ghanvi-Jeori 3.565 66 3.565 3.565
16 Jeori-Nogli 24.710 66 24.710 24.710
17 Nogli-Samoli 34.410 66 34.410 34.410
18 Samoli-Andhra 13.100 66 13.100 13.100
19 Nogli-Kumarsain 25.690 66 25.690 25.690
20 Kumarsain-Guuma 42.040 66 42.040 42.040
21 Gumma-Sainj 21.290 66 21.290 21.290
22 Sainj-Hulli 9.992 66 9.992 9.992
23 Gumma-Jutogh 15.490 66 15.490 15.490
24 Jutogh-Totu 1.550 66 1.55 To be Laid by PGCIL
25 Totu-Solan 25.270 66 25.27
26 Solan-Kunihar 22.000 66 22
27 Kunihar-Barotiwala 26.030 66 26.03
28 Barotiwala-Baddi 3.250 66 3.25
29 Baddi-Nalagarh 17.000 66 17
30 Baddi-Akhanwali 10.301 66 10.301
31 Nalagarh-Uperala Nangal 3.510 66 3.51
32 Uperala Nangal-Nalagarh PGCIL 3.569 220 3.569 63.990 63.990
33 Solan-Giri 63.990 132 31.960 31.960
34 Giri-KalaAmb 31.960 132 16.390 16.390
35 Giri-Poanta 16.390 132 16.205 16.205
36 Kangoo-Bagga 16.205 132 13.563 13.563
37 Bagga-Darlaghat 13.563 132 32.000 32.000
38 Bassi-Palampur 32.000 132 24.234 24.234
39 Jassore-Kandrori 24.234 132 20.000 20.000
40 Jutogh-Maliana 20.000 132 45.42 45.42
41 Bathri-Kurathala 45.42 132
42 Jutogh-Kunihar 15.340 132 15.340
43 Kunihar-Kangoo 47.640 132 47.640
44 Kangoo-Hamirpur 42.139 132 42.139
45 Rakkar - Amb 31.3 132 31.3
46 Una-Tahliwal 17 132 17
47 LILO Kangoo-Hamirpur to Jahu 6.4 132 6.4
48 Uperala Nangal-Baddi 27 220 27
49 Baddi-Mandhala 8 220 8
50 Hamirpur I - Hamirpur II 5 132 5
51 Solan-Parwanoo 18.5 18.5
52 Jutogh-Kumar House 6 11 6 ADSS already laid by PGCIL
Total 1181.698 105.119 100.001 102.179 29.500 368.710 476.189 844.899

1 Bhaba-Kashang 39 220 39 Proposed by HPPCL

Note: 39 Km Bhaba-Kashang line has been included in proposed OPGW network as per the request of HPPCL. The expenditure on this account shall be born by HPPCL.
66

List of HPSEBL Sub-Stations/Power Houses where Optical line terminal Equipment are installed and proposed to be installed.

Name of Sub-Stations/ Terminal Equipment Name of Sub-Stations/ Terminal Equipment


S. No. Sr. No.
Power Houses Installed Proposed Power Houses Installed Proposed
220 kV Sub-Stations/Power Houses 132 kV Sub-Stations/Power Houses
STM-1 Add/Drop Multiplexer
1 Jassore Sub-Station Proposed under Priority links 22 Solan Sub-Station (Proposed under Telecom
Nnetwork of PGCIL)
Proposed under Additional
2 Giri Power House 23 Barotiwala Sub-Station ……..do…….
communication requirement
3 Jeori Sub-Station ……..do……. 24 Tahiwal Sub-Station Proposed by ES Wing
4 Bhaba Power House ……..do……. 25 Jahu Sub-Station ……..do…….
5 Kashang Power House ……..do……. 26 Mandhala Sub-Station ……..do…….
STM-4 installed
6 Hamirpur II Sub-Station 27 Fathepur Sub-Station To be provided by ES Wing
under Central sector
7 Kangoo Sub-Station ……..do……. 28 Hamirpur-I Sub-Station To be proposed by HPSEBL
8 Kunihar Sub-Station ……..do……. 66 kV Sub-Stations/Power Houses
STM-1 Add/Drop Multiplexer
Proposed under Additional
9 Uperala Nangal Sub-Station (Proposed under Telecom 1 Nathpa Sub-Station
communication requirement
Nnetwork of PGCIL)
10 Baddi Sub-Station ……..do……. 2 Ghanvi Power House ……..do…….
132 kV Sub-Stations/Power Houses 3 Nogli Power House ……..do…….
1 Amb Sub-Station Proposed under Priority links 4 Samoli Sub-Station ……..do…….
2 Dehra Sub-Station ……..do……. 5 Andhra Power House ……..do…….
3 Chullah Power House ……..do……. 6 Kumarsain Sub-Station ……..do…….
4 Bassi Power house ……..do……. 7 Gumma Sub-Station ……..do…….
5 Bijni (Mandi) Sub-Station ……..do……. 8 Sainj Sub-Station ……..do…….
6 Larji Power House ……..do……. 9 Hulli Sub-Station ……..do…….
STM-1 Add/Drop Multiplexer
7 Bajura Sub-Station ……..do……. 10 Totu Sub-Station (Proposed under Telecom
Nnetwork of PGCIL)
8 Bathri Sub-Station ……..do……. 11 Nalagarh Sub-Station ……..do…….
9 Gagret Sub-Station ……..do……. 12 Parwanoo Sub-Station ……..do…….
10 Rakkar Sub-Station ……..do……. 13 Malpur sub-Station To be provided by ES Wing
11 Golthai Sub-Station ……..do……. 14 Akhanwali Sub-Station Existing (ABB)
12 Kangra Sub-Station ……..do…….
Proposed under Additional
13 Kala-Amb Sub-Station
communication requirement
14 Poanta Sub-Station ……..do…….
15 Bagga Sub-Station ……..do…….
16 Darlaghat Sub-Station ……..do…….
17 Palampur Sub-Station ……..do…….
18 Kandrori Sub-Station ……..do…….
19 Maliana Sub-Station ……..do…….
20 Kurathala Sub-Station ……..do…….
STM-16 installed
21 Jutogh Sub-Station
under Central sector
EXISTING PLCC SYSTEM OF HPSEBL 67
KURTHALA
132 kV

KANDRORI 264/268 kHZ BAIRASUIL THIEN DAM BHABA 352/340 GHANVI


kHZ
ABB ETI 21 BATHARI BPL66kV
51
180/188 kHZ
68,61 92 99,84 BPL

252/232
kHZ
BPL66kV

332/336 kHZ 252/260 kHZ BPL 132 kV


ABB 132 kV

PALAMPUR SANSAPUR PONG 81,98 277/285


666 kHZ
424/450 160/148 kHZ BPL66kV
220 kV
kHZ BPL 340/348 kHZ BPL 220 kV
85,95 86,97 66 kV
430/412 &
476/468 kHZ
420/428 kHZ 220 kV WSI 220kV
JASSURE
43 24

KANGRA KOTLA SUNGRA


83,93 TAHLIWAL BHAKHRA
PGCIL 280/356 kHZ 352/364 kHZ ABB
ABB ET1-21
120/116 kHZ ABB ET1-21 220 kV 132 kV ET1-21 132 kV
136/128 kHZ ABB ET1-21 220 kV 87,96
324/328 kHZ ABB ET1-21
132 kV
152/148 kHZ ABB 300/304 kHZ
ET1-21 220 kV ABB ET1-21
132 kV 308/300 kHZ 128/120 kHZ 312/320 312/3200
H/PUR ABB ETL42 BPL kHZ kHZ
89 NEW BPL66kV BPL,66 KV
222 H/PUR OLD 777 80
SHANAN BASSI 292/296 kHZ
440/444 kHZ ABB ET1-21 NOGLI ANDHRA
284/288 kHZ 132 kV 200/220 kHZ
270/295 346/364 ABB 132 kV
kHZ kHZ ABB 132 kV 336/308 kHZ ABB ET1-42
BPL 132 kV ABB 132 kV ABB ET1-21 66kV
90 41

396/4000
AMB
372/376 kHZ 244/248 kHZ
CHULLAH ABB 132 kV DEHRA kHZ , ABB RAKKER, UNA GOLTHAI
ET1-21 204/156 &
180/100
132 kV 132 kV kHz BPL 82 25,888 356/352 238/230
kHZ kHZ
91 ABB,66 KV BPL,66 KV
BIJNI 256/264 kHZ 432/442 &
ABB ET1-21 200/208 kHZ GAGRET
204/246 kHZ BPL 132 kV BPL 220 kV
66 kV 360/368
kHZ
BPL 66kV
999
128/136 &
144/152 kHZ
340/3336 kHZ
RAURI WSI 220 kV
272/268 & ROHRU
ET1-21 ABB 324/320 kHZ
132 kV 39 23,57
ABB 132 kV 45 22,56
BAJOURA 33
196/368 LARJI KANGOO 220 kV KUNIHAR JUTOGH GUMMA KUMARSAIN
kHZ BPL 132 kV D/C 340/348kHZ
9505
132 kV 360/368 & BPL 66 kV
30 472/468 kHZ
BPL 132 kV 312/320kHZ
456/412 & BPL 66 kV
420/400 kHZ
228/360 kHZ BPL 132 kV
BPL 9505
392/388, 445/480
428/424 kHZ ABB 132 kV
SAINJ 372/368 kHz kHZ 132 kV
132 kV BPL 66 kV
240/220 kHZ 296/292 kHZ 64,65 49
ABB 132 kV ABB 132 kV TOTU
448/456 kHZ
BPL 132 kV BAGGA KULHAL RISHIKESH
KOTKHAI
72 52,60
USEB USEB

338/384 & 132 kV


464/450 kHZ
ABB 132 kV
GAURA
MALANA MPCL DEHAR
37 DARLAGHAT 555,27
220 kV 46,67
34 SOLAN MAJRI
288/296 188/180
180/188 & 368/196 kHZ kHZ BPL kHZ BPL
404/400 ABB 132kV 467.5/430
kHz ETL42 132kV kHZ 132 kV 114/105
kHZ ABB 220 kV
DAVNI AKKANWALI
66 kV
388/384 & 364/372 360/364 & 480/476
kHZ ABB 132 kV kHZ ABB 132 kV
66 kV
380/472 & KHODRI
312/320 352/304
kHz ETL42 kHZ BPL 340/348 418/456
kHZ BPL 324/328
132kV kHZ BPL & 396/400
66 kV 48 132 kV 42,62
336/316 & 35 31,73 kHZ ABB 43,68
256/212 132 kV
36,75 kHz ETL42 230/238 140/148 356/376
38 NALAGARH
kHz ETL42 kHZ BPL kHZ BPL kHZ BPL
66 kV 66 kV 132 kV
420/428 BADDI
PANCHKULA
kHz BPL
HVPNL
40,76
BAROTIWALA PARWANOO ABDULAPUR KALA AMB PAONTA (GONDPUR)
344/372 420/428 248/272 220/228
kHz ETL42 HVPNL
kHz ETL42 kHz ETL42 kHz Alstom
S.No. REFERENCES ELEMENT S.No. REFERENCES ELEMENT
296/364 4. UNDER PLCC SUBDIVISION, HPSEBL, SUNDERNAGAR
kHz ETL42 1. PLCC TERMINAL
5. UNDER PLCC SUBDIVISION, HPSEBL, JOGINDERNAGAR
480/488 & 2. EPBAX EXCHANGE
468/444 6. UNDER PLCC SUBDIVISION, HPSEBL, SHIMLA
PGCIL kHz ETL42 3. 66/132/220 KV SUBSTATION
7. UNDER PLCC SUBDIVISION, HPSEBL, SOLAN
400 kV BHATOLI KALAN
U/NANGAL MANDHALA 8. INTERSTATE PLCC LINKS
220 kV 220 kV 66 kV
68

STATUS REPORT OF EXISTING PLCC EQUIPMENT AS ON 28.02.2015


Total No. of channels
in station
No. of Carrier Status of Link Outdoor Equipment 48 V DC System
Station Link detail Make & Model Remarks
Links Frequency Ch. Covered No. of Total Ch.
above channels in station
Healthy Faulty CVT Wave Trap LMU Battery Charger Battery Bank
Kangoo (1) 1 132 kV Kangoo-Mattansidh(1) 256/264 kHz ABB ETI-21 (S/C) Yes -- Good Good Good Healthy Not Healthy
2 132 kV Kangoo-Mattansidh (2) 328/332 kHz ABB ETI-21 (S/C) Yes -- Good Good Good 30 PLCC links which are not
3 132 kV Kangoo-Bijni 272/268 kHz ABB ETI-21 (S/C) Yes -- Good Good Good functional have out lived its
4 132 kV Kangoo-Bajaura (1) 424/428 kHz ABB ETI-21 (S/C) Yes -- Good Good Good life, obsolete in the market.
5 132 kV Kangoo-Bajaura (2) 164/160 kHz ABB ETL-41(S/C) Yes -- Good Good Good The firms have refused to
6 132 kV Kangoo-Bajaura(3) 260/232 kHz ABB ETL-41 (S/C) Yes -- Good Good Good repair these proprietary
7 132 kV Kangoo-Bagga 444/452 kHz ABB ETL-42 (T/C) Yes -- Good Good Good faulty fixed frequency
8 132 kV Kangoo-Darlagahat BPL-6515 R2 (T/C) -- Yes -- -- -- dependent and other
9 132 kV Kangoo-Dehar (1) 460/464 kHz ABB ETI-21 (S/C) Yes -- Good Good Good modules of these links.
10 132 kV Kangoo-Dehar(2) 384/368 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
11 132 kV Kangoo-Dehar(3) BPL-6515 R2 (T/C) -- Yes Good Good Faulty
12 132 kV Kangoo-Larji (1) 476/204 kHz BPL-9505 V3 (T/C) Yes -- Good Good Good
13 132 kV Kangoo-Larji (2) 320/324 kHz BPL-9505 V3 (T/C) Yes -- Good Good Good
14 132 kV Kangoo-Larji (3) ABB ETI-21 (S/C) 0 19 19 Yes -- Good Good Good
Dehar HEP (2) Covered in Kangoo (1) 4 0 4 Good Good Good Healthy Not Healthy
Bijni (3) 15 132 kV Bijni-Shanan HEP 264/204 kHz BPL-9505 V3 (T/C) Yes -- Good Good Good
Not Healthy Not Healthy
16 132 kV Bijni-Larji HEP 336/340 kHz ABB ETI-21 (S/C) 1 3 4 Yes -- Good Good Good
188/364 kHz(Ch-1)
Larji HEP (4) 17 132 kV Larji- Bajaura 182/365 kHz(Ch-2) BPL-9505 V3 (T/C) 5 2 7 Yes -- Good Good Faulty Not Healthy Not Healthy
Bajaura (5) 18 132 kV Bajaura-Malana (1) 236/292 kHz ABB ETL-41 (S/C) Yes -- Good Good Good
Healthy Not Healthy
19 132 kV Bajaura-Malana (2) 224/220 kHz ABB ETL-41 (S/C) 5 2 7 Yes -- Good Good Good
Malana HEP(6) Covered in Bajaura (5) 2 0 2 Good Good Good Healthy Healthy
Bagga (7) 20 132 kV Bagga-Darlaghat 468/472 kHz ABB ETI-21 (S/C) 2 1 3 Yes -- Good Good Good Healthy Healthy
Golthai (8) 21 66 kV Golthai-Rakkar 220/200 kHz ABB ETL-42 (T/C) 2 2 4 Yes -- Good Good Good Healthy Not Healthy
Rakkar(9) 22 132 kV Rakkar-Amb 336/308 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
Not Healthy Not Healthy
23 132 kV Rakkar-Tahliwal 300/308 kHz ABB ETL-42 (T/C) 2 3 5 Yes -- Good Good Good
Amb(10) 24 132 kV Amb-Dehra(1) 296/292 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
25 132 kV Amb-Dehra(2) 400/396 kHz ABB ETI-21 (S/C) -- Yes Good Good Good
Healthy Healthy
26 132 kV Amb-Gagret (1) 204/156 kHz BPL-9505 V3 (T/C) -- Yes Good Good Good
27 132 kV Amb-Gagret (2) 100/180 kHz BPL-9505 V3 (T/C) 1 6 7 -- Yes Good Good Good
Bassi HEP(11) 28 132 kV Bassi-Shanan HEP BPL-9505 V3 (T/C) -- Yes Good Good Good
29 132 kV Bassi-Anu(1) BPL-9505 V3 (T/C) Yes -- Good Good Good
Not Healthy Not Healthy
30 132 kV Bassi-Anu(2) PUNCOM-PL9500 (T/C) Yes -- Good Good Good
31 132 kV Bassi-Palampur ABB ETI-21 (S/C) 0 7 7 Yes -- Good Good Good
Shanan HEP(12) Covered in Bijni(3) & Bassi(11) 4 0 4
Palampur(13) Covered in Bassi (11) 1 0 1 Healthy Not Healthy
Kangra (14) 32 132 kV Kangra-Dehra (1) ABB ETI-21 (S/C) Yes -- Good Good Good
33 132 kV Kangra-Dehra (2) ABB ETI-21 (S/C) Yes -- Good Good Good Healthy Healthy
34 132 kV Kangra-Dehra (3) PUNCOM-PL9500(S/C) 0 3 3 -- Yes Good Good Good
Dehra (15) 35 132 kV Dehra-Amb ABB ETI-21 (S/C) Yes -- Good Good Good
36 132 kV Dehra-Mattansidh (1) ABB ETI-21 (S/C) Yes -- Good Good Good
37 132 kV Dehra-Mattansidh (2) ABB ETI-21 (S/C) Yes -- Good Good Good
38 132 kV Dehra-Mattansidh (3) PUNCOM-PL9500(S/C) Yes -- Good Good Good Healthy Healthy
39 132 kV Dehra-Mattansidh (4) PUNCOM-PL9500(S/C) Yes -- Good Good Good
40 132 kV Dehra-Jassore (1) HBB ETI-22 (T/C) Yes -- Good Good Good
41 132 kV Dehra-Jassore (2) PUNCOM-PL9500(S/C) 3 8 11 Yes -- Good Good Good
Mattansidh (16) 42 132 kV Mattansidh-Anu (1) ABB ETI-21 (S/C) Yes -- Good Good Good
43 132 kV Mattansidh-Anu (2) ABB ETI-21 (S/C) Yes -- Good Good Good Healthy Healthy
44 132 kV Mattansidh-Anu (3) PUNCOM-PL9500(T/C) 6 4 10 Yes -- Good Good Good
Jassore(17) 45 132 kV Jassore-Bathri BPL-6515 R2 (T/C) -- Yes Good Good Faulty
46 220 kV Jassore-Bairasuil BPL-6515 R2 (T/C) -- Yes Good Good Faulty
47 220 kV Jassore-Pong BPL-6515 R2 (T/C) -- Yes Good Good Faulty
Healthy Not Healthy
48 220 kV Jassore-ThinDam(1) PUNCOM-PL9500(S/C) -- Yes Good Good Good
49 220 kV Jassore-ThinDam(2) PUNCOM-PL9500(S/C) Yes -- Good Good Good
50 132 kV Jassore-Kandrori ABB ETI-21 (S/C) 3 9 12 Yes -- Good Good Good
Bathri (18) Covered in Jassore(17) 2 0 2
Kandrori (19) Covered in Jassore(17) 1 0 1
69

Kunihar (20) 51 220 kV Kunihar-Kotla (1) 144/152 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
52 220 kV Kunihar-Kotla (2) 128/136 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
53 220 kV Kunihar-Bhaba (1) 444/432 kHz ABB ETL-42 (T/C) Yes --
Only in Red phase Good
54 220 kV Kunihar-Bhaba (2) 200/208 kHz ABB ETL-42 (T/C) Yes --
55 132 kV Kunihar-Solan (1) 288/296 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
56 132 kV Kunihar-Solan (2) 372/364 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
57 132 kV Kunihar-Solan (3) 384/388 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
58 220 kV Kunihar-Baddi (1) 196/368 kHz ABB ETL-42 (T/C) Yes -- Healthy Healthy
Only in Red phase Good
59 220 kV Kunihar-Baddi (2) 440/448 kHz ABB ETL-42 (T/C) Yes --
60 132 kV Kunihar-Barotiwala 304/352 kHz ABB ETI-22 (T/C) Yes -- Good Only in Red phaGood
61 132 kV Kunihar-Darlaghat (1) 300/308 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
62 132 kV Kunihar-Darlaghat (2) 236/276 kHz BPL-6515 T2 (T/C) -- Yes Good Good Faulty
63 132 kV Kunihar-Jutogh (1) 160/152 kHz BPL-6515 R2 (T/C) -- Yes Good Good Faulty
64 132 kV Kunihar-Jutogh (2) 420/400 kHz BPL-6515 R2 (T/C) -- Yes Not provided Faulty
65 220 kV Kunihar-Panchkulla 180/188 kHz ABB ETI-22 (T/C) 0 27 27 -- Yes Not Provided
Jutogh(21) 66 66 kV Jutogh-Gumma 312/320 kHz BPL-6515 R2 (T/C) 4 2 6 -- Yes Good Good Faulty Healthy Healthy
Darlaghat(22) covered in Kunihar(21)& Bagga(7) 4 0 4
Gumma (23) 67 66 kV Gumma-Huli (1) 392/388 kHz BPL-6515 R1 (S/C) -- Yes Good Good Faulty
68 66 kV Gumma-Huli (2) 368/372 kHz BPL-6515 R1 (S/C) -- Yes Good Good Faulty Not Healthy Not Healthy
69 66 kV Gumma-Kumarsain 340/348 kHz BPL-6515 R2 (T/C) 2 4 6 -- Yes Good Good Faulty
Kumarsain(24) 70 66 kV Kumarsain-Nogli 360/368 kHz BPL-6515 R2 (T/C) 2 2 4 -- Yes Not Provided Faulty Healthy Not Healthy
Huli (26) Covered in Gumma(23) 2 0 2
Nogli (27) 71 66 kV Nogli-Kotla (1) 312/320 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
72 66 kV Nogli-Kotla (2) 384/400 kHz ABB ETI-22 (T/C) Yes -- Good Good Good
Not Healthy Not Healthy
73 66 kV Nogli-Samauli (1) 436/412 kHz ABB ETL-42 (T/C) Yes --
Only in Red Phase Good
74 66 kV Nogli-Samauli (2) 356/312 kHz ABB ETI-21 (S/C) 2 7 9 Yes --
Kotla(28) 75 220 kV Kotla-Bhaba 468/476 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
76 220 kV Kotla-Ghanvi (1) 364/368 kHz ABB ETL-41 (S/C) Yes -- Good Good Good Healthy Not healthy
77 220 kV Kotla-Ghanvi (2) 252/232 kHz BPL-9505 V3 (T/C) 8 6 14 -- Yes Good Good Good
Ghanvi (29) 78 66 kV Ghanvi-Nathpa 360/368 kHz BPL-6515 R2 (T/C) 4 2 6 -- Yes Good Good Faulty Healthy Not Healthy
Bhaba(30) Covered in Kotla(28) & Kunihar(20) 6 0 6
Nathpa(31) Covered in Ghanvi(29) 2 0 2
Samoli (32) 79 66 kV Samauli-Andhra (1) 236/228 kHz ABB ETL-42 (T/C) Yes -- Good Good Good Not Healthy Not Healthy
80 66 kV Samauli-Andhra (2) 400/396 kHz ABB ETI-21 (S/C) 3 3 6 Yes -- Good Good Good Not Healthy Not Healthy
Andhra HEP(33) Covered in Samoli (32) 3 0 3
Solan (34) 81 132 kV Solan-Giri (1) 180/188 kHz BPL-6515 R2 (T/C) -- Yes Good Good Faulty
82 132 kV Solan-Giri (2) 464/460 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
Healthy Healthy
83 132 kV Solan-Giri (3) 480/476 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
84 66 kV Solan-Parwanoo 340/348 kHz BPL-6515 R2 (T/C) 4 6 10 -- Yes Good Good Faulty
Parwanoo(35) 85 66 kV Parwanoo-Barotiwala 140/148 kHz BPL-6515 R2 (T/C) 2 2 4 -- Yes Good Good Faulty Healthy Healthy
Barotiwala(36) 86 66 kV Barotiwala-Baddi 230/238 kHz BPL-6515 R2 (T/C) 4 2 6 -- Yes Good Good Faulty Healthy Healthy
Baddi(37) 87 66 kV Baddi-Nalagarh (1) 420/428 kHz BPL-6515 R2 (T/C) -- Yes Good Good Faulty
88 66 kV Baddi-Nalagarh (2) 240/280 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
89 220 kV Baddi-Panchkulla 404/400 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
90 220 kV Baddi-U.Nangal 420/428 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
Healthy Healthy
91 220 kV Baddi-Mandhala 248/272 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
92 66 kV Baddi-Akanwali (1) 316/336 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
93 66 kV Baddi-Akanwali (2) 212/256 kHz ABB ETL-42 (T/C) 6 13 19 Yes -- Good Good Good
Akanwali(38) 94 66 kV Akanwali-Davni (1) 472/380 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
Healthy Healthy
95 66 kV Akanwali-Davni (2) 320/312 kHz ABB ETL-42 (T/C) 4 4 8 Yes -- Good Good Good
Davni(39) Covered in Akanwali (39)
Nalagarh(40) 96 66 kV Nalagarh-U.Nangal 344/372 kHz ABB ETL-42 (T/C) 4 2 6 Yes -- Good Good Good Healthy Healthy
U.Nangal (41) 97 220 kV U.Nangal-Reru (PGCIL)(1) 480/488 kHz ABB ETL-42 (T/C) Yes -- Good Good Good
98 220 kV U.Nangal-Reru (PGCIL)(2) 468/444 kHz ABB ETL-42 (T/C) Yes -- Good Good Good Healthy Healthy
99 220 kV U.Nangal-Mandhala ABB ETL-42 (T/C) 4 6 10 Yes -- Good Good Good
Mandhala (42) Covered in U.Nangal(41)&Baddi(37)
Giri(43) 100 132 kV Giri-KalaAmb(1) 324/328 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
101 132 kV Giri-KalaAmb(2) 396/400 kHz ABB ETI-21 (S/C) Yes -- Good Good Good
102 132 kV Giri-Poanta 356/376 kHz BPL-6515 R2 (T/C) -- Yes Good Good Faulty
Healthy Healthy
103 132 kV Giri-Abdullapur 4118/456 kHz BPL-6515 R2 (T/C) -- Yes Good Good Faulty
104 220 kV Giri-Khodri (1) 114/106 kHz HBB ETI-22 (T/C) Yes -- Only on one phase Good
105 220 kV Giri-Khodri (2) 308/316 kHz ABB ETL-42 (T/C) 4 10 14 Yes -- Good Good Good
KalaAmb(44) Covered in Giri(43)
Poanta (45) Covered in Giri(43)
Gagret(46) Covered in Amb(10)
Tahliwal(47) Covered in Rakkar(9)
Sansarpur Terr.(48) 106 66 kV Terrace-Pong BPL-6515 R2 (T/C) 0 2 2 -- Yes Faulty Faulty Faulty Not Healthy Not Healthy
Anu(49) Covered in Bassi(11)&Mattansidh(16)
Total 106 169 76 30
S/C: Single Channel Cabinets
T/C: Twin Channel Cabinets
70

Detail of EPABX under PLCC Division, HPSEBL Sunder-Nagar


Exchange Description Exchange Description
Name of Sub-Station/ Name of Sub-Station/
S.No. Capacity Used Capacity/Description S.No. Capacity Used Capacity/Description
Power House Make/Model (ID) Power House Make/Model (ID)
Trunks Subscribers Trunks Subscribers Trunks Subscribers Trunks Subscribers
I) 220kV Sub-Stations/Power Houses II) 132 kV Sub-Stations/Power Houses
Uperla Nangal Control Room-20 1 Amb BPL MDX-50 (080) 2 12 Rakkar Control Room-20
Kunihar-2 Dehra Carrier-22
Akhanwali-2 2 Bagga BPL MDX-50 (060) 2 12 Darlaghat Control Room-20
1 Baddi BPL MDX-50 (040) 10 20 Panchkula-2 Kangoo Carrier-22
Nalagarh-2 Kangoo Control Room-20
Mandhala 3 Bajaura BPL MDX-50 (030) 3 12 Larji Carrier-24
Barotiwala Malana
Matrix Kunihar Control Room-20 Kunihar 20
2 Bhabha 2 48
Eternity (051) Kotla Carrier-22 4 Barotiwala BPL MDX-50 (035) 3 12 Parwanoo
Solan-2 Control Room-20 Baddi
Matrix Kala Amb Carrier-22 Hamirpur 25
3 Giri-Nagar 10 20
Eternity (027) Goandpur (Poanta) 5 Bassi Matrix Eternity (064) 3 20 Shanan
Khodri Dehan
Hamirpur-I-2 Control Room-44 6 Bathri
4 Hamirpur-II BPL MDX-50 (022) 6 20 Kangoo-2 Kunihar 37
Dehra-2 7 Darlaghat Matrix Eternity (037) 3 46 Kangoo
Dehra 25 Bagga
Kandrori 8 Dehan(Palampur)
5 Jassore BPL MDX-50 (057) 4 12
Bathri Hamirpur-I 20
RSD (Thein) Hamirpur-II
Nogli 48 Jassore
9 Dehra BPL MDX-50 (063) 6 20
Kunihar Amb
6 Jeori (Kotla) Matrix Eternity (043) 4 48
Samoli Kangra-I
Andhra Kangra-II
Kangoo-Hamirpur Control Room-20 10 Gagret
Kangoo-Bijni Carrier-22 11 Gaura
7 Kangoo BPL MDX-50 (033) 5 12 Kangoo-Larji Solan-3 20
Kangoo-Bajaura Kala Amb-2
Kangoo-Bagga 12 Gondpur(Poanta Sahib) Matrix Eternity (027) 9 20 Khodri-2
Shimla 22 Gondpur
Kangoo 22 Abdullapur
Dehra PH Anu-I 22
Darlaghart 22 13 Hamirpur-I BPL MDX-50 (053) 3 4 Anu-II
Bajaura Bassi PH
8 Kunihar Matrix Eternity (039) 11 48 Solan 20 14 Jutogh Nelco 45 EPABX not in function
Giri 24 15 Kala-Amb BPL MDX-50 (042) 2 12 Poanta Sahib-2 20
Bhabha 16 Kandrori
Barotiwala 17 Kangra
Baddi 18 Kurthala
Kotla Kangoo Control Room-23
9 Mandhala 19 Larji BPL MDX-50 (023) 3 20 Bajaura Carrier-20
Rehru-2 20 Bijni
Baddi 20 Malana BPL MDX-50 (072) 1 12 Bajaura Control Room-20
10 Uperla Nangal Matrix Eternity (038) 5 20
Mandhala
Nalagarh
71

Exchange Description
Name of Sub-Station/
S.No. Capacity Used Capacity/Description
Power House Make/Model (ID)
Trunks Subscribers Trunks Subscribers
II) 132 kV Sub-Stations/Power Houses
Kangoo Control Room-20
21 Mandi (Bijni) BPL MDX-50 (047) 3 8 Shanan Carrier-22
Larji
Golthai Carrier-20
22 Rakkar (Una) BPL-MDX-50 (082) 2 24
Amb
Kunihar-3 20
23 Solan Matrix Eternity (034) 7 20 Poanta Sahib-3
Parwanoo
24 Tahliwala
III) 66 kV Sub-Stations/Power Houses
1 Akanwali
Samoli
2 Andhra BPL-1997 MDX-50 (026) 2 4
Nogli
3 Ani (Nagan)
4 Batoli Kalan
5 Davni
6 Ghanvi - - - EPABX not in function
Bhakhra Carrier-20
7 Golthai BPL MDX-50 (083) 2 20
Rakkar
8 Gumma BPL-1997 MDX-50 (22) 4 4 EPABX not in function
9 Khotkhai (Hulli)
10 Kumarsain
Baddi-2 20
11 Nalagarh Matrix Eternity (036) 3 20
Uperla Nangal-1
12 Nathpa Nelco - - EPABX not in function
Kotla 20
13 Nogli BPL-1997 MDX-50 (20) 2 4
Andhra
14 Parwanoo
15 Sainj
16 Sansarpur Terrace
Andhra 20
17 Smoli (Rohru) BPL-1997 MDX-50 (028) 2 4
Nogli
18 Totu
72

MDF No-1 MDF No-4 MDF No-7

Card Type eZ32 Card Type EMTL Card Type EMTL


Phy Add 2-0-0 2-0-1 2-0-2 2-0-3 2-0-4 2-0-5 2-0-6 2-0-7 2-0-8 2-0-9 Phy Add 0-3-1 0-3-1 0-3-1 0-3-1 0-3-2 0-3-2 0-3-2 0-3-2 Phy Add 0-8-1 0-8-1 0-8-1 0-8-1 0-8-2 0-8-2 0-8-2 0-8-2
Ext No 21770001 21770002 21770003 21770004 21770005 21770006 21770007 21770008 21770009 21770010 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type EMTL
Phy Add 2-0-10 2-0-11 2-0-12 2-0-13 2-0-14 2-0-15 2-0-16 2-0-17 2-0-18 2-0-19 Phy Add 0-3-3 0-3-3 0-3-3 0-3-3 0-3-4 0-3-4 0-3-4 0-3-4 Phy Add 0-8-3 0-8-3 0-8-3 0-8-3 0-8-4 0-8-4 0-8-4 0-8-4
Ext No 21770011 21770012 21770013 21770014 21770015 21770016 21770017 21770018 21770019 21770020 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type EMTL
Phy Add 2-0-20 2-0-21 2-0-22 2-0-23 2-0-24 2-0-25 2-0-26 2-0-27 2-0-28 2-0-29 Phy Add 0-3-5 0-3-5 0-3-5 0-3-5 0-12-0 0-12-0 0-12-0 0-12-0 Phy Add 0-8-5 0-8-5 0-8-5 0-8-5 0-9-0 0-9-0 0-9-0 0-9-0
Ext No 21770021 21770022 21770023 21770024 21770025 21770026 21770027 21770028 21770029 21770030 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type EMTL
Phy Add 2-0-30 2-0-31 2-1-0 2-1-1 2-1-2 2-1-3 2-1-4 2-1-5 2-1-6 2-1-7 Phy Add 0-12-1 0-12-1 0-12-1 0-12-1 0-12-2 0-12-2 0-12-2 0-12-2 Phy Add 0-9-1 0-9-1 0-9-1 0-9-1 0-9-2 0-9-2 0-9-2 0-9-2
Ext No 21770031 21770032 21770033 21770034 21770035 21770036 21770037 21770038 21770039 21770040 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type EMTL
Phy Add 2-1-8 2-1-9 2-1-10 2-1-11 2-1-12 2-1-13 2-1-14 2-1-15 2-1-16 2-1-17 Phy Add 0-12-3 0-12-3 0-12-3 0-12-3 0-12-4 0-12-4 0-12-4 0-12-4 Phy Add 0-9-3 0-9-3 0-9-3 0-9-3 0-9-4 0-9-4 0-9-4 0-9-4
Ext No 21770041 21770042 21770043 21770044 21770045 21770046 21770047 21770048 21770049 21770050 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type EMTL
Phy Add 2-1-18 2-1-19 2-1-20 2-1-21 2-1-22 2-1-23 2-1-24 2-1-25 2-1-26 2-1-27 Phy Add 0-12-5 0-12-5 0-12-5 0-12-5 0-14-0 0-14-0 0-14-0 0-14-0 Phy Add 0-9-5 0-9-5 0-9-5 0-9-5 0-11-0 0-11-0 0-11-0 0-11-0
Ext No 21770051 21770052 21770053 21770054 21770055 21770056 21770057 21770058 21770059 21770060 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type EMTL
Phy Add 2-1-28 2-1-29 2-1-30 2-1-31 2-2-0 2-2-1 2-2-2 2-2-3 2-2-4 2-2-5 Phy Add 0-14-1 0-14-1 0-14-1 0-14-1 0-14-2 0-14-2 0-14-2 0-14-2 Phy Add 0-11-1 0-11-1 0-11-1 0-11-1 0-11-2 0-11-2 0-11-2 0-11-2
Ext No 21770061 21770062 21770063 21770064 21770065 21770066 21770067 21770068 21770069 21770070 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type NDDI
Phy Add 2-2-6 2-2-7 2-2-8 2-2-9 2-2-10 2-2-11 2-2-12 2-2-13 2-2-14 2-2-15 Phy Add 0-14-3 0-14-3 0-14-3 0-14-3 0-14-4 0-14-4 0-14-4 0-14-4 Phy Add 0-0-0 0-0-1 0-0-2 0-0-3 0-0-4 0-0-5 0-0-6 0-0-7 0-19-0 0-19-1
Ext No 21770071 21770072 21770073 21770074 21770075 21770076 21770077 21770078 21770079 21770080 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type NDDI
Phy Add 2-2-16 2-2-17 2-2-18 2-2-19 2-2-20 2-2-21 2-2-22 2-2-23 2-2-24 2-2-25 Phy Add 0-14-5 0-14-5 0-14-5 0-14-5 0-16-0 0-16-0 0-16-0 0-16-0 Phy Add 0-19-2 0-19-3
Ext No 21770081 21770082 21770083 21770084 21770085 21770086 21770087 21770088 21770089 21770090 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
❿ Phy Add 2-2-26 2-2-27 2-2-28 2-2-29 2-2-30 2-2-31 2-4-0 2-4-1 2-4-2 2-4-3 ❿ Phy Add 0-16-1 0-16-1 0-16-1 0-16-1 0-16-2 0-16-2 0-16-2 0-16-2 ❿ Phy Add
Ext No 21770091 21770092 21770093 21770094 21770095 21770096 21770097 21770098 21770099 21770100 Ext No Ext No

MDF No-2 MDF No-5 MDF No-8

Card Type eZ32 Card Type EMTL Card Type


Phy Add 2-4-4 2-4-5 2-4-6 2-4-7 2-4-8 2-4-9 2-4-10 2-4-11 2-4-12 2-4-13 Phy Add 0-16-3 0-16-3 0-16-3 0-16-3 0-16-4 0-16-4 0-16-4 0-16-4 Phy Add
Ext No 21770101 21770102 21770103 21770104 21770105 21770106 21770107 21770108 21770109 21770110 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-4-14 2-4-15 2-4-16 2-4-17 2-4-18 2-4-19 2-4-20 2-4-21 2-4-22 2-4-23 Phy Add 0-16-5 0-16-5 0-16-5 0-16-5 0-18-0 0-18-0 0-18-0 0-18-0 Phy Add
Ext No 21770111 21770112 21770113 21770114 21770115 21770116 21770117 21770118 21770119 21770120 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-4-24 2-4-25 2-4-26 2-4-27 2-4-28 2-4-29 2-4-30 2-4-31 2-8-0 2-8-1 Phy Add 0-18-1 0-18-1 0-18-1 0-18-1 0-18-2 0-18-2 0-18-2 0-18-2 Phy Add
Ext No 21770121 21770122 21770123 21770124 21770125 21770126 21770127 21770128 21770129 21770130 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-8-2 2-8-3 2-8-4 2-8-5 2-8-6 2-8-7 2-8-8 2-8-9 2-8-10 2-8-11 Phy Add 0-18-3 0-18-3 0-18-3 0-18-3 0-18-4 0-18-4 0-18-4 0-18-4 Phy Add
Ext No 21770131 21770132 21770133 21770134 21770135 21770136 21770137 21770138 21770139 21770140 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-8-12 2-8-13 2-8-14 2-8-15 2-8-16 2-8-17 2-8-18 2-8-19 2-8-20 2-8-21 Phy Add 0-18-5 0-18-5 0-18-5 0-18-5 0-23-0 0-23-0 0-23-0 0-23-0 Phy Add
Ext No 21770141 21770142 21770143 21770144 21770145 21770146 21770147 21770148 21770149 21770150 Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-8-22 2-8-23 2-8-24 2-8-25 2-8-26 2-8-27 2-8-28 2-8-29 2-8-30 2-8-31 Phy Add 0-23-1 0-23-1 0-23-1 0-23-1 0-23-2 0-23-2 0-23-2 0-23-2 Phy Add
Ext No Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-12-0 2-12-1 2-12-2 2-12-3 2-12-4 2-12-5 2-12-6 2-12-7 2-12-8 2-12-9 Phy Add 0-23-3 0-23-3 0-23-3 0-23-3 0-23-4 0-23-4 0-23-4 0-23-4 Phy Add
Ext No Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-12-10 2-12-11 2-12-12 2-12-13 2-12-14 2-12-15 2-12-16 2-12-17 2-12-18 2-12-19 Phy Add 0-23-5 0-23-5 0-23-5 0-23-5 0-25-0 0-25-0 0-25-0 0-25-0 Phy Add
Ext No Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-12-20 2-12-21 2-12-22 2-12-23 2-12-24 2-12-25 2-12-26 2-12-27 2-12-28 2-12-29 Phy Add 0-25-1 0-25-1 0-25-1 0-25-1 0-25-2 0-25-2 0-25-2 0-25-2 Phy Add
Ext No Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
❿ Phy Add 2-12-30 2-12-31 2-3-0 2-3-1 2-3-2 2-3-3 2-3-4 2-3-5 2-3-6 2-3-7 ❿ Phy Add 0-25-3 0-25-3 0-25-3 0-25-3 0-25-4 0-25-4 0-25-4 0-25-4 ❿ Phy Add
Ext No Ext No Ext No

MDF No-3 MDF No-6 MDF No-9

Card Type eZ32 Card Type EMTL Card Type


Phy Add 2-3-8 2-3-9 2-3-10 2-3-11 2-3-12 2-3-13 2-3-14 2-3-15 2-3-16 2-3-17 Phy Add 0-25-5 0-25-5 0-25-5 0-25-5 0-27-0 0-27-0 0-27-0 0-27-0 Phy Add
Ext No Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-3-18 2-3-19 2-3-20 2-3-21 2-3-22 2-3-23 2-3-24 2-3-25 2-3-26 2-3-27 Phy Add 0-27-1 0-27-1 0-27-1 0-27-1 0-27-2 0-27-2 0-27-2 0-27-2 Phy Add
Ext No Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-3-28 2-3-29 2-3-30 2-3-31 2-5-0 2-5-1 2-5-2 2-5-3 2-5-4 2-5-5 Phy Add 0-27-3 0-27-3 0-27-3 0-27-3 0-27-4 0-27-4 0-27-4 0-27-4 Phy Add
Ext No Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-5-6 2-5-7 2-5-8 2-5-9 2-5-10 2-5-11 2-5-12 2-5-13 2-5-14 2-5-15 Phy Add 0-27-5 0-27-5 0-27-5 0-27-5 0-2-0 0-2-0 0-2-0 0-2-0 Phy Add
Ext No Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-5-16 2-5-17 2-5-18 2-5-19 2-5-20 2-5-21 2-5-22 2-5-23 2-5-24 2-5-25 Phy Add 0-2-1 0-2-1 0-2-1 0-2-1 0-2-2 0-2-2 0-2-2 0-2-2 Phy Add
Ext No Ext No Ext No
Card Type eZ32 Card Type EMTL Card Type
Phy Add 2-5-26 2-5-27 2-5-28 2-5-29 2-5-30 2-5-31 Phy Add 0-2-3 0-2-3 0-2-3 0-2-3 0-2-4 0-2-4 0-2-4 0-2-4 Phy Add
Ext No Ext No Ext No
Card Type EMTL Card Type EMTL Card Type
Phy Add 0-1-0 0-1-0 0-1-0 0-1-0 Phy Add 0-2-5 0-2-5 0-2-5 0-2-5 0-4-0 0-4-0 0-4-0 0-4-0 Phy Add
Ext No Ext No Ext No
Card Type EMTL Card Type EMTL Card Type
Phy Add 0-1-1 0-1-1 0-1-1 0-1-1 0-1-2 0-1-2 0-1-2 0-1-2 Phy Add 0-4-1 0-4-1 0-4-1 0-4-1 0-4-2 0-4-2 0-4-2 0-4-2 Phy Add
Ext No Ext No Ext No
Card Type EMTL Card Type EMTL Card Type
Phy Add 0-1-3 0-1-3 0-1-3 0-1-3 0-1-4 0-1-4 0-1-4 0-1-4 Phy Add 0-4-3 0-4-3 0-4-3 0-4-3 0-4-4 0-4-4 0-4-4 0-4-4 Phy Add
Ext No Ext No Ext No
Card Type EMTL Card Type EMTL Card Type
❿ Phy Add 0-1-5 0-1-5 0-1-5 0-1-5 0-3-0 0-3-0 0-3-0 0-3-0 ❿ Phy Add 0-4-5 0-4-5 0-4-5 0-4-5 0-8-0 0-8-0 0-8-0 0-8-0 ❿ Phy Add
Ext No Ext No Ext No

S-ar putea să vă placă și