Technical
Data Book
DVM S for Euro_ET
(R410A, 50Hz, HP)
2
Nomenclature
Outdoor Unit
Model Name
AM DVM V Inverter
M DVM S Eco
(2) Capacity
(6) Feature 2
x 1/10 HP (3 digits)
A Standard + General Temp.+ Module
H High EER + Low Temp. + Module
G High EER + General Temp. + Module
D Standard + General Temp. + Non-Module
(3) Version
F 2013
H 2014
J 2015 (7) Rating Voltage
K 2016
E 1Ø, 220~240V, 50Hz
M 2017
G 3Ø, 380~415V, 50Hz
N 3Ø, 380~415V, 50/60Hz
3
Features & Benefits
Samsung’s VRF system air conditioners offer instant temperature control, user-friendly installation and advanced
functionality, along with smart power usage. Our flagship VRF-based Samsung DVM S is a highly innovative system
that adopts the new third-generation Samsung Scroll Compressor (SSC) technology with Dual Digital Inverter.
DVM S provides world-class energy efficiency and the most powerful cooling and heating performance available on
the market. This ideal air conditioning system accomodates all variable environments, including large commercial
or residential buildings.
Samsung DVM S offers innovative features to benefit the indoor comfort as well operational coasts of the system
through technological advances such as:
4
Features & Benefits
Smart management
Further improves system’s energy efficiency due to precise indoor
climate control. Web-based remote monitoring and management
system allows quick and easy HVAC control and breakdown alert.
5
Contents
1. Combination Table 7
2. Specification 15
3. Electric Characteristics 99
4. Dimensional Drawing 102
5. Center of Gravity 107
6. Electrical Wiring Diagrams 110
7. Sound Data 112
8. Operation Range 126
9. Piping Diagram 128
10. Installation 137
11. Accessory 173
6
1. Combination Table
Premium Compact
NOTE
••Make sure to use an indoor unit that is compatible with DVM S.
••Indoor units can be connected within the range indicated in following table.
••If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
••Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 × Σ( Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ( Outdoor unit capacity)
※※ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be
assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
※※ Maximum 32 Wall-mount type indoor units with EEV (AM∗∗∗∗NQDEH∗∗∗, AM∗∗∗JNVDKH∗∗∗) can be connected.
••In case of combining modules more than 90HP, please consult the manufacturer when connecting the indoor unit and
deciding on piping length in accordance with design of the building.
7
1. Combination Table
Premium Energy Efficiency
NOTE
••Make sure to use an indoor unit that is compatible with DVM S.
••Indoor units can be connected within the range indicated in following table.
••If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
••Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 × Σ( Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ( Outdoor unit capacity)
※※ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be
assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
※※ Maximum 32 Wall-mount type indoor units with EEV (AM∗∗∗∗NQDEH∗∗∗, AM∗∗∗JNVDKH∗∗∗) can be connected.
••In case of combining modules more than 90HP, please consult the manufacturer when connecting the indoor unit and
deciding on piping length in accordance with design of the building.
8
1. Combination Table
Standard
NOTE
••Make sure to use an indoor unit that is compatible with DVM S.
••Indoor units can be connected within the range indicated in following table.
••If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
••Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 × Σ( Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ( Outdoor unit capacity)
※※ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be
assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
※※ Maximum 32 Wall-mount type indoor units with EEV (AM∗∗∗∗NQDEH∗∗∗, AM∗∗∗JNVDKH∗∗∗) can be connected.
••In case of combining modules more than 90HP, please consult the manufacturer when connecting the indoor unit and
deciding on piping length in accordance with design of the building.
9
1. Combination Table
Indoor Units
Capacity (kW)
Model
1.5 1.7 2.2 2.8 3.2 3.6 4.5 5.6 6.0 7.1 8.2 9.0 11.2 12.8 14.0 16.0
JSF-0
1Way
JSF-1
CST
JSF-2
2Way CST
4Way CST
360 CST
Floor
Standing Unit
4Way CST S
(600X600)
Duct S (MSP)
Slim Duct
MSP Duct
Ceiling
Console
Boracay
Boracay (with
EEV)
AR5000
AR5000 (with
EEV)
10
1. Combination Table
Indoor Units
Capacity (kW)
Model 22.0/ 500 1000
6.0 7.1 8.2 9.0 11.2 12.8 14.0 16.0 18.0 25.0 28.0 32.0 50.0
22.4 CMH CMH
HSP Duct
OAP Duct
Big Duct
PAC
Hydro Unit HE
Hydro Unit HT
ERV Plus
NOTE
••Make sure to use an indoor unit that is compatible with DVM S.
••If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
••Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
※※ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the
indoor unit address was assigned from 64~79, E201 error will occur.
※※ Maximum 32 Wall-mount type indoor units with EEV (AM∗∗∗∗NQDEH∗∗∗, AM∗∗∗JNVDKH∗∗∗) can be connected.
11
1. Combination Table
External Appearance
Premium compact
Capa Capa
Model Name Model Model Name Model
[HP] [HP]
14 AM140JXVHGH/ET
8 AM080JXVHGH/EU 16 AM160JXVHGH/ET
10 AM100JXVHGH/EU 18 AM180JXVHGH/ET
12 AM120JXVHGH/EU 20 AM200JXVHGH/ET
22 AM220JXVHGH/ET
24 AM240KXVGGH/ET
26 AM260KXVGGH/ET 32 AM320KXVGGH1ET
28 AM280KXVGGH/ET 34 AM340KXVGGH1ET
30 AM300KXVAGH/ET
44 AM440KXVGGH1ET
36 AM360KXVGGH1ET
46 AM460KXVGGH1ET
38 AM380KXVGGH1ET
48 AM480KXVGGH1ET
40 AM400KXVGGH1ET
50 AM500KXVGGH1ET
42 AM420KXVGGH1ET
52 AM520KXVGGH1ET
54 AM540KXVGGH1ET
56 AM560KXVGGH1ET 62 AM620KXVGGH1ET
58 AM580KXVGGH1ET 64 AM640KXVGGH1ET
60 AM600KXVGGH1ET
66 AM660KXVGGH1ET
76 AM760KXVGGH1ET
68 AM680KXVGGH1ET
78 AM780KXVGGH1ET
70 AM700KXVGGH1ET
80 AM800KXVGGH1ET
72 AM720KXVGGH1ET
82 AM820KXVGGH1ET
74 AM740KXVGGH1ET
84 AM840KXVGGH1ET
86 AM860KXVGGH1ET
88 AM880KXVGGH1ET
90 AM900KXVGGH1ET
12
1. Combination Table
External Appearance
Capa Capa
Model Name Model Model Name Model
[HP] [HP]
14 AM140JXVHGH/ET
8 AM080JXVHGH/EU
16 AM160JXVHGH/ET
10 AM100JXVHGH/EU
18 AM180JXVHGH/ET
12 AM120JXVHGH/EU
20 AM200JXVHGH/ET
26 AM260KXVGGH2ET
22 AM220KXVGGH2ET
28 AM280KXVGGH2ET
24 AM240KXVGGH2ET
30 AM300KXVAGH2ET
32 AM320KXVGGH2ET
36 AM360KXVGGH2ET 34 AM340KXVGGH2ET
38 AM380KXVGGH2ET
40 AM400KXVGGH2ET
42 AM420KXVGGH2ET
44 AM440KXVGGH2ET 50 AM500KXVGGH2ET
46 AM460KXVGGH2ET
48 AM480KXVGGH2ET
52 AM520KXVGGH2ET
54 AM540KXVGGH2ET 58 AM580KXVGGH2ET
56 AM560KXVGGH2ET
62 AM620KXVGGH2ET
60 AM600KXVGGH2ET 64 AM640KXVGGH2ET
66 AM660KXVGGH2ET
68 AM680KXVGGH2ET
72 AM720KXVGGH2ET
74 AM740KXVGGH2ET 70 AM700KXVGGH2ET
76 AM760KXVGGH2ET
78 AM780KXVGGH2ET
80 AM800KXVGGH2ET
82 AM820KXVGGH2ET 88 AM880KXVGGH2ET
84 AM840KXVGGH2ET 90 AM900KXVGGH2ET
86 AM860KXVGGH2ET
13
1. Combination Table
External Appearance
Standard
Capa Capa
Model Name Model Model Name Model
[HP] [HP]
14 AM140KXVAGH/ET
8 AM080JXVAGH/EU 16 AM160KXVAGH/ET
10 AM100JXVAGH/EU 18 AM180KXVAGH/ET
12 AM120JXVAGH/EU 20 AM200KXVAGH/ET
22 AM220KXVAGH/ET
24 AM240KXVAGH/ET
26 AM260KXVAGH/ET 32 AM320KXVAGH/ET
28 AM280KXVAGH/ET 34 AM340KXVAGH/ET
30 AM300KXVAGH/ET
36 AM360KXVAGH/ET
46 AM460KXVAGH/ET
38 AM380KXVAGH/ET
48 AM480KXVAGH/ET
40 AM400KXVAGH/ET
50 AM500KXVAGH/ET
42 AM420KXVAGH/ET
52 AM520KXVAGH/ET
44 AM440KXVAGH/ET
54 AM540KXVAGH/ET
56 AM560KXVAGH/ET 62 AM620KXVAGH/ET
58 AM580KXVAGH/ET 64 AM640KXVAGH/ET
60 AM600KXVAGH/ET
66 AM660KXVAGH/ET
76 AM760KXVAGH/ET
68 AM680KXVAGH/ET
78 AM780KXVAGH/ET
70 AM700KXVAGH/ET
80 AM800KXVAGH/ET
72 AM720KXVAGH/ET
82 AM820KXVAGH/ET
74 AM740KXVAGH/ET
84 AM840KXVAGH/ET
86 AM860KXVAGH/ET
88 AM880KXVAGH/ET
90 AM900KXVAGH/ET
14
2. Specification
Premium Compact
15
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
16
2. Specification
Premium Compact
17
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
18
2. Specification
Premium Compact
19
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
20
2. Specification
Premium Compact
21
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
22
2. Specification
Premium Compact
23
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
24
2. Specification
Premium Compact
25
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
26
2. Specification
Premium Compact
27
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
28
2. Specification
Premium Compact
29
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
30
2. Specification
Premium Compact
31
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
32
2. Specification
Premium Compact
33
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
34
2. Specification
Premium Compact
35
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
36
2. Specification
Premium Compact
37
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
38
2. Specification
Premium Compact
39
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
40
2. Specification
Premium Compact
41
2. Specification
Premium Compact
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
42
2. Specification
Premium Energy Efficiency
43
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
44
2. Specification
Premium Energy Efficiency
45
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
46
2. Specification
Premium Energy Efficiency
47
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
48
2. Specification
Premium Energy Efficiency
49
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
50
2. Specification
Premium Energy Efficiency
51
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
52
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
54
2. Specification
Premium Energy Efficiency
55
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
56
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
58
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
60
2. Specification
Premium Energy Efficiency
61
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
62
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
64
2. Specification
Premium Energy Efficiency
65
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
66
2. Specification
Premium Energy Efficiency
67
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
68
2. Specification
Premium Energy Efficiency
69
2. Specification
Premium Energy Efficiency
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
70
2. Specification
Standard
71
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
72
2. Specification
Standard
73
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
74
2. Specification
Standard
75
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
76
2. Specification
Standard
77
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
78
2. Specification
Standard
79
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
80
2. Specification
Standard
81
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
82
2. Specification
Standard
83
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
84
2. Specification
Standard
85
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
86
2. Specification
Standard
87
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
88
2. Specification
Standard
89
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
90
2. Specification
Standard
91
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
92
2. Specification
Standard
93
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
94
2. Specification
Standard
95
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
96
2. Specification
Standard
97
2. Specification
Standard
NOTE
•• Specification may be subject to change without prior notice.
•• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
-- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
-- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※※ Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level
-- Reference power : 1pW
-- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
-- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
•• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
98
3. Electric Characteristics
Premium Compact
Capacity Power Supply Voltage Range Running Current [A] Current [A] ODU Fan Motor
Model Min. Max.
HP kW Hz Voltage Cooling Heating MCA MFA kW FLA [A]
(-10%) (+10%)
8 22.4 AM080JXVHGH/EU 50 380-415 342 456 7.4 7.4 18 25 0.83 2.4
10 28.0 AM100JXVHGH/EU 50 380-415 342 456 10 9.4 21.1 32 0.83 2.4
12 33.6 AM120JXVHGH/EU 50 380-415 342 456 12.1 12.1 25 32 0.83 2.4
14 40.0 AM140JXVHGH/ET 50 380-415 342 456 14.3 15.4 25 32 1.24 3.8
16 45.0 AM160JXVHGH/ET 50 380-415 342 456 17.5 17.2 32 40 1.24 3.8
18 50.4 AM180JXVHGH/ET 50 380-415 342 456 17.1 16.9 39.2 50 1.24 3.8
20 56.0 AM200JXVHGH/ET 50 380-415 342 456 20 20.5 42 63 1.24 3.8
22 61.6 AM220JXVHGH/ET 50 380-415 342 456 25.3 25.4 44.6 63 1.24 3.8
24 67.2 AM240KXVGGH/ET 50 380-415 342 456 25.7 24.7 55 63 1.24 3.8
26 72.8 AM260KXVGGH/ET 50 380-415 342 456 27.8 27.4 60 75 1.24 3.8
28 78.6 AM280KXVGGH/ET 50 380-415 342 456 31.5 30.1 67 75 1.24 3.8
30 84.0 AM300KXVAGH/ET 50 380-415 342 456 36.4 33 73 80 1.24 3.8
32 89.6 AM320KXVGGH1ET 50 380-415 342 456 32.1 32.6 67 80 2.07 6.2
34 95.2 AM340KXVGGH1ET 50 380-415 342 456 37.4 37.5 69.6 80 2.07 6.2
36 101.6 AM360KXVGGH1ET 50 380-415 342 456 39.6 40.8 69.6 80 2.48 7.6
38 106.6 AM380KXVGGH1ET 50 380-415 342 456 42.8 42.6 76.6 90 2.48 7.6
40 112.0 AM400KXVGGH1ET 50 380-415 342 456 42.4 42.3 83.8 100 2.48 7.6
42 117.6 AM420KXVGGH1ET 50 380-415 342 456 45.3 45.9 86.6 100 2.48 7.6
44 124.0 AM440KXVGGH1ET 50 380-415 342 456 50.7 48.4 98 125 2.48 7.6
46 129.0 AM460KXVGGH1ET 50 380-415 342 456 53.9 50.2 105 125 2.48 7.6
48 134.4 AM480KXVGGH1ET 50 380-415 342 456 53.5 49.9 112.2 125 2.48 7.6
50 140.0 AM500KXVGGH1ET 50 380-415 342 456 56.4 53.5 115 150 2.48 7.6
52 145.6 AM520KXVGGH1ET 50 380-415 342 456 61.7 58.4 117.6 150 2.48 7.6
54 151.2 AM540KXVGGH1ET 50 380-415 342 456 62.1 57.7 128 150 2.48 7.6
56 156.8 AM560KXVGGH1ET 50 380-415 342 456 64.2 60.4 133 150 2.48 7.6
58 162.6 AM580KXVGGH1ET 50 380-415 342 456 67.9 63.1 140 175 2.48 7.6
60 168.0 AM600KXVGGH1ET 50 380-415 342 456 72.8 66 146 175 2.48 7.6
62 173.6 AM620KXVGGH1ET 50 380-415 342 456 68.5 65.6 140 175 3.31 10
64 179.2 AM640KXVGGH1ET 50 380-415 342 456 73.8 70.5 142.6 175 3.31 10
66 185.6 AM660KXVGGH1ET 50 380-415 342 456 76 73.8 142.6 175 3.72 11.4
68 190.6 AM680KXVGGH1ET 50 380-415 342 456 79.2 75.6 149.6 175 3.72 11.4
70 196.0 AM700KXVGGH1ET 50 380-415 342 456 78.8 75.3 156.8 175 3.72 11.4
72 201.6 AM720KXVGGH1ET 50 380-415 342 456 81.7 78.9 159.6 175 3.72 11.4
74 207.2 AM740KXVGGH1ET 50 380-415 342 456 87 83.8 162.2 200 3.72 11.4
76 212.8 AM760KXVGGH1ET 50 380-415 342 456 87.4 83.1 172.6 200 3.72 11.4
78 218.4 AM780KXVGGH1ET 50 380-415 342 456 89.5 85.8 177.6 200 3.72 11.4
80 224.2 AM800KXVGGH1ET 50 380-415 342 456 93.2 88.5 184.6 225 3.72 11.4
82 229.6 AM820KXVGGH1ET 50 380-415 342 456 98.1 91.4 190.6 225 3.72 11.4
84 235.2 AM840KXVGGH1ET 50 380-415 342 456 98.5 90.7 201 225 3.72 11.4
86 240.8 AM860KXVGGH1ET 50 380-415 342 456 100.6 93.4 206 250 3.72 11.4
88 246.6 AM880KXVGGH1ET 50 380-415 342 456 104.3 96.1 213 250 3.72 11.4
90 252.0 AM900KXVGGH1ET 50 380-415 342 456 109.2 99 219 250 3.72 11.4
NOTE
••MCA : Minimum circuit amperes
••MFA : Maximum fuse amperes
••FLA : Full load amperes
99
3. Electric Characteristics
Premium Energy Efficiency
Capacity Power Supply Voltage Range Running Current [A] Current [A] ODU Fan Motor
Model Min. Max.
HP kW Hz Voltage Cooling Heating MCA MFA kW FLA [A]
(-10%) (+10%)
8 22.4 AM080JXVHGH/EU 50 380-415 342 456 7.4 7.4 18 25 0.83 2.4
10 28.0 AM100JXVHGH/EU 50 380-415 342 456 10 9.4 21.1 32 0.83 2.4
12 33.6 AM120JXVHGH/EU 50 380-415 342 456 12.1 12.1 25 32 0.83 2.4
14 40.0 AM140JXVHGH/ET 50 380-415 342 456 14.3 15.4 25 32 1.24 3.8
16 45.0 AM160JXVHGH/ET 50 380-415 342 456 17.5 17.2 32 40 1.24 3.8
18 50.4 AM180JXVHGH/ET 50 380-415 342 456 17.1 16.9 39.2 50 1.24 3.8
20 56.0 AM200JXVHGH/ET 50 380-415 342 456 20 20.5 42 63 1.24 3.8
22 61.6 AM220KXVGGH2ET 50 380-415 342 456 22.1 21.5 46.1 63 1.66 4.8
24 67.2 AM240KXVGGH2ET 50 380-415 342 456 24.2 24.2 50 63 1.66 4.8
26 72.8 AM260KXVGGH2ET 50 380-415 342 456 24.5 24.3 57.2 63 2.07 6.2
28 78.4 AM280KXVGGH2ET 50 380-415 342 456 27.4 27.9 60 75 2.07 6.2
30 84.0 AM300KXVAGH2ET 50 380-415 342 456 29.2 29 64.2 75 2.07 6.2
32 90.4 AM320KXVGGH2ET 50 380-415 342 456 31.4 32.3 64.2 75 2.48 7.6
34 95.2 AM340KXVGGH2ET 50 380-415 342 456 31.9 31.7 75.2 90 2.9 8.6
36 100.8 AM360KXVGGH2ET 50 380-415 342 456 34.2 33.8 78.4 90 2.48 7.6
38 106.4 AM380KXVGGH2ET 50 380-415 342 456 37.1 37.4 81.2 90 2.48 7.6
40 112.8 AM400KXVGGH2ET 50 380-415 342 456 38.8 39.7 82.2 90 3.31 10
42 118.4 AM420KXVGGH2ET 50 380-415 342 456 41.7 43.3 85 100 3.31 10
44 123.2 AM440KXVGGH2ET 50 380-415 342 456 41.6 41.2 96.4 125 3.31 10
46 128.8 AM460KXVGGH2ET 50 380-415 342 456 44.5 44.8 99.2 125 3.31 10
48 134.4 AM480KXVGGH2ET 50 380-415 342 456 47.4 48.4 102 125 3.31 10
50 140.8 AM500KXVGGH2ET 50 380-415 342 456 48.5 49.2 103.4 125 3.72 11.4
52 145.6 AM520KXVGGH2ET 50 380-415 342 456 52.3 51.7 117.2 150 3.31 10
54 151.2 AM540KXVGGH2ET 50 380-415 342 456 55.2 55.3 120 150 3.31 10
56 156.8 AM560KXVGGH2ET 50 380-415 342 456 57 56.4 124.2 150 3.31 10
58 162.4 AM580KXVGGH2ET 50 380-415 342 456 60.9 59.5 133 150 3.31 10
60 168.0 AM600KXVGGH2ET 50 380-415 342 456 59.9 58.5 133.4 150 3.72 11.4
62 173.6 AM620KXVGGH2ET 50 380-415 342 456 58.7 58.1 135.6 150 4.55 13.8
64 179.2 AM640KXVGGH2ET 50 380-415 342 456 61.6 61.7 138.4 175 4.55 13.8
66 184.8 AM660KXVGGH2ET 50 380-415 342 456 63.4 62.8 142.6 175 4.55 13.8
68 191.2 AM680KXVGGH2ET 50 380-415 342 456 65.6 66.1 142.6 175 4.96 15.2
70 196.0 AM700KXVGGH2ET 50 380-415 342 456 69.4 68.6 156.4 175 4.55 13.8
72 201.6 AM720KXVGGH2ET 50 380-415 342 456 68.4 67.6 156.8 175 4.96 15.2
74 207.2 AM740KXVGGH2ET 50 380-415 342 456 71.3 71.2 159.6 175 4.96 15.2
76 212.8 AM760KXVGGH2ET 50 380-415 342 456 74.2 74.8 162.4 200 4.96 15.2
78 218.4 AM780KXVGGH2ET 50 380-415 342 456 77.1 78.4 165.2 200 4.96 15.2
80 224.0 AM800KXVGGH2ET 50 380-415 342 456 79.1 78.1 177.6 200 4.96 15.2
82 229.6 AM820KXVGGH2ET 50 380-415 342 456 82 81.7 180.4 200 4.96 15.2
84 235.2 AM840KXVGGH2ET 50 380-415 342 456 84.9 85.3 183.2 225 4.96 15.2
86 240.8 AM860KXVGGH2ET 50 380-415 342 456 90.2 90.2 185.8 225 4.96 15.2
88 246.4 AM880KXVGGH2ET 50 380-415 342 456 90.6 89.5 196.2 225 4.96 15.2
90 252.0 AM900KXVGGH2ET 50 380-415 342 456 92.7 92.2 201.2 225 4.96 15.2
NOTE
••MCA : Minimum circuit amperes
••MFA : Maximum fuse amperes
••FLA : Full load amperes
100
3. Electric Characteristics
Standard
Capacity Power Supply Voltage Range Running Current [A] Current [A] ODU Fan Motor
Model Min. Max.
HP kW Hz Voltage Cooling Heating MCA MFA kW FLA [A]
(-10%) (+10%)
8 22.4 AM080JXVAGH/EU 50 380-415 342 456 8 8.2 18 25 0.83 2.4
10 28.0 AM100JXVAGH/EU 50 380-415 342 456 11 10.7 21.1 32 0.83 2.4
12 33.6 AM120JXVAGH/EU 50 380-415 342 456 13.1 12.9 25 32 0.83 2.4
14 40.0 AM140KXVAGH/ET 50 380-415 342 456 17.5 16.3 25 32 1.24 3.8
16 45.0 AM160KXVAGH/ET 50 380-415 342 456 19.4 18.6 32 40 1.24 3.8
18 50.4 AM180KXVAGH/ET 50 380-415 342 456 20.2 19.1 39.2 50 1.24 3.8
20 56.0 AM200KXVAGH/ET 50 380-415 342 456 22.7 22.3 42 63 1.24 3.8
22 61.6 AM220KXVAGH/ET 50 380-415 342 456 27.8 26.8 44.6 63 1.24 3.8
24 67.2 AM240KXVAGH/ET 50 380-415 342 456 27.4 27.9 55 63 1.24 3.8
26 72.8 AM260KXVAGH/ET 50 380-415 342 456 30.3 28.9 60 75 1.24 3.8
28 78.6 AM280KXVAGH/ET 50 380-415 342 456 33.2 32.4 67 75 1.24 3.8
30 84.0 AM300KXVAGH/ET 50 380-415 342 456 36.4 33 73 80 1.24 3.8
32 89.6 AM320KXVAGH/ET 50 380-415 342 456 38.8 37.5 65.7 80 2.07 6.2
34 95.2 AM340KXVAGH/ET 50 380-415 342 456 40.9 39.7 69.6 80 2.07 6.2
36 101.6 AM360KXVAGH/ET 50 380-415 342 456 45.3 43.1 69.6 80 2.48 7.6
38 106.6 AM380KXVAGH/ET 50 380-415 342 456 47.2 45.4 76.6 90 2.48 7.6
40 112.0 AM400KXVAGH/ET 50 380-415 342 456 48 45.9 83.8 100 2.48 7.6
42 117.6 AM420KXVAGH/ET 50 380-415 342 456 50.5 49.1 86.6 100 2.48 7.6
44 123.2 AM440KXVAGH/ET 50 380-415 342 456 55.6 53.6 89.2 100 2.48 7.6
46 129.0 AM460KXVAGH/ET 50 380-415 342 456 55.8 51.6 105 125 2.48 7.6
48 134.4 AM480KXVAGH/ET 50 380-415 342 456 56.6 52.1 112.2 125 2.48 7.6
50 140.0 AM500KXVAGH/ET 50 380-415 342 456 59.1 55.3 115 150 2.48 7.6
52 145.6 AM520KXVAGH/ET 50 380-415 342 456 64.2 59.8 117.6 150 2.48 7.6
54 151.2 AM540KXVAGH/ET 50 380-415 342 456 63.8 60.9 128 150 2.48 7.6
56 156.8 AM560KXVAGH/ET 50 380-415 342 456 66.7 61.9 133 150 2.48 7.6
58 162.6 AM580KXVAGH/ET 50 380-415 342 456 69.6 65.4 140 175 2.48 7.6
60 168.0 AM600KXVAGH/ET 50 380-415 342 456 72.8 66 146 175 2.48 7.6
62 173.6 AM620KXVAGH/ET 50 380-415 342 456 75.2 70.5 138.7 175 3.31 10
64 179.2 AM640KXVAGH/ET 50 380-415 342 456 77.3 72.7 142.6 175 3.31 10
66 185.6 AM660KXVAGH/ET 50 380-415 342 456 81.7 76.1 142.6 175 3.72 11.4
68 190.6 AM680KXVAGH/ET 50 380-415 342 456 83.6 78.4 149.6 175 3.72 11.4
70 196.0 AM700KXVAGH/ET 50 380-415 342 456 84.4 78.9 156.8 175 3.72 11.4
72 201.6 AM720KXVAGH/ET 50 380-415 342 456 86.9 82.1 159.6 175 3.72 11.4
74 207.2 AM740KXVAGH/ET 50 380-415 342 456 92 86.6 162.2 200 3.72 11.4
76 212.8 AM760KXVAGH/ET 50 380-415 342 456 91.6 87.7 172.6 200 3.72 11.4
78 218.4 AM780KXVAGH/ET 50 380-415 342 456 94.5 88.7 177.6 200 3.72 11.4
80 224.2 AM800KXVAGH/ET 50 380-415 342 456 97.4 92.2 184.6 225 3.72 11.4
82 229.6 AM820KXVAGH/ET 50 380-415 342 456 100.6 92.8 190.6 225 3.72 11.4
84 235.2 AM840KXVAGH/ET 50 380-415 342 456 100.2 93.9 201 225 3.72 11.4
86 240.8 AM860KXVAGH/ET 50 380-415 342 456 103.1 94.9 206 250 3.72 11.4
88 246.6 AM880KXVAGH/ET 50 380-415 342 456 106 98.4 213 250 3.72 11.4
90 252.0 AM900KXVAGH/ET 50 380-415 342 456 109.2 99 219 250 3.72 11.4
NOTE
••MCA : Minimum circuit amperes
••MFA : Maximum fuse amperes
••FLA : Full load amperes
101
4. Dimensional Drawing
Outdoor unit
•• AM080~120JXVHGH
102
4. Dimensional Drawing
Outdoor unit
•• AM080~120JXVAGH
103
4. Dimensional Drawing
Outdoor unit
•• AM140~220JXVHGH
104
4. Dimensional Drawing
Outdoor unit
•• AM140~220KXVAGH
105
4. Dimensional Drawing
Outdoor unit
•• AM240~280KXVGGH, AM240~300KXVAGH
106
5. Center of Gravity
Outdoor unit
•• AM080~120JXVHGH, AM080~120JXVAGH
Units : mm [inches]
[5'-6 3/4"]
1695
A B
761 740
[2’-6”] [2’-5”]
Model A B C
107
5. Center of Gravity
Outdoor unit
•• AM140~220JXVHGH, AM140~220KXVAGH
Units : mm [inches]
[5'-6 3/4"]
1695
A B
761 1150
[2’-6”] [3’-9 1/4”]
Model A B C
108
5. Center of Gravity
Outdoor unit
•• AM240~280KXVGGH, AM240~300KXVAGH
Units : mm [inches]
[5’-10 3/4”]
1795
C
A B
761 1150
[2’-6”] [3’-9 1/4”]
Model A B C
109
6. Electrical Wiring Diagrams
Outdoor unit
INV PBA1 Printed circuit board (inverter1) EEV1 Electronic expansion valve 1 LIQUID(10K) Thermistor (Liquid Tube Temp._10Kohm)
INV PBA2 Printed circuit board (inverter2) EEV2 Electronic expansion valve 2 HOTGAS1 V/V Solenoid valve (Hot Gas Bypass1)
EMI PBA1 Printed circuit board (emi1) EVI-OUT(10K) Thermistor (EVI-out_10kohm) EVI BYPASS V/V Solenoid valve (EVI BYPASS)
EMI PBA2 Printed circuit board (emi2) EVI-IN(10K) Thermistor (EVI-in_10kohm) RETURN V/V Solenoid valve (Accumulator Oil Return)
FAN PBA Printed circuit board (fan motor) SUCTION1(10K) Thermistor (Suction Temp.1_10Kohm) 4WAY V/V Solenoid valve (4 Way valve)
MAIN PBA Printed circuit board (main) SUCTION2(10K) Thermistor (Suction Temp.2_10Kohm) CCH1 Crank Case Heater (Compressor1)
HUB PBA Printed circuit board (hub) SNOW SENSOR SNOW SENSOR CCH2 Crank Case Heater (Compressor2)
COMM PBA Printed circuit board (communication) OIL-COMP1 Oil-Sensor (Compressor1) MAIN COOLING Solenoid valve (Main cooling)
COMP1 Motor (compressor1) OIL-COMP2 Oil-Sensor (Compressor2) HOTGAS2 V/V Solenoid valve (Hot Gas Bypass2)
COMP2 Motor (compressor2) OUT(10K) Thermistor (Ambient Temp._10Kohm) OD EEV V/V Solenoid valve (Outdoor EEV)
FAN1 Motor (fan1) COND(10K) Thermistor (Cond Out Temp._10Kohm) F101 FUSE (Inverter PBA)
FAN2 Motor (fan2) TOP1(200K) Thermistor (Compressor Top 1_200Kohm) 690V/T40A FUSE (EMI PBA)
EVI V/V 1 Solenode valve (EVI1) TOP2(200K) Thermistor (Compressor Top 2_200Kohm) MODE CHANGE Connector (Remote switching cool/heat selector)
EVI V/V 2 Solenode valve (EVI2) DIS1(200K) Thermistor (Discharge Temp.1_200Kohm) EXT CON Connector (Output EXT CON)
EVI EEV Electronic expansion valve (EVI) DIS2(200K) Thermistor (Discharge Temp.2_200Kohm) ERROR/COMP EXT Connector (Output ERROR/COMP EXT CON)
NOTE
•• This wiring diagram applies only to the outdoor unit.
•• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
•• When operating, don’t shortcircuit the protection device (High Pressure switch)
•• For connection wiring indoor-outdoor transmission F1-F2, outdoor_outdoor transmission OF1-OF2, refer to
the installation manual.
•• Protective earth(screw), : connector, : The wire quantity
110
6. Electrical Wiring Diagrams
Outdoor unit
INV PBA1 Printed circuit board (inverter1) EEV1 Electronic expansion valve 1 LIQUID(10K) Thermistor (Liquid Tube Temp._10Kohm)
INV PBA2 Printed circuit board (inverter2) EEV2 Electronic expansion valve 2 HOTGAS1 V/V Solenoid valve (Hot Gas Bypass1)
EMI PBA1 Printed circuit board (emi1) EVI-OUT(10K) Thermistor (EVI-out_10kohm) EVI BYPASS V/V Solenoid valve (EVI BYPASS)
EMI PBA2 Printed circuit board (emi2) EVI-IN(10K) Thermistor (EVI-in_10kohm) RETURN V/V Solenoid valve (Accumulator Oil Return)
FAN PBA Printed circuit board (fan motor) SUCTION1(10K) Thermistor (Suction Temp.1_10Kohm) 4WAY V/V Solenoid valve (4 Way valve)
MAIN PBA Printed circuit board (main) SUCTION2(10K) Thermistor (Suction Temp.2_10Kohm) CCH1 Crank Case Heater (Compressor1)
HUB PBA Printed circuit board (hub) SNOW SENSOR SNOW SENSOR CCH2 Crank Case Heater (Compressor2)
COMM PBA Printed circuit board (communication) OIL-COMP1 Oil-Sensor (Compressor1) MAIN COOLING Solenoid valve (Main cooling)
COMP1 Motor (compressor1) OIL-COMP2 Oil-Sensor (Compressor2) HOTGAS2 V/V Solenoid valve (Hot Gas Bypass2)
COMP2 Motor (compressor2) OUT(10K) Thermistor (Ambient Temp._10Kohm) OD EEV V/V Solenoid valve (Outdoor EEV)
FAN1 Motor (fan1) COND(10K) Thermistor (Cond Out Temp._10Kohm) F101 FUSE (Inverter PBA)
FAN2 Motor (fan2) TOP1(200K) Thermistor (Compressor Top 1_200Kohm) 690V/T56A FUSE (EMI PBA)
EVI V/V 1 Solenode valve (EVI1) TOP2(200K) Thermistor (Compressor Top 2_200Kohm) MODE CHANGE Connector (Remote switching cool/heat selector)
EVI V/V 2 Solenode valve (EVI2) DIS1(200K) Thermistor (Discharge Temp.1_200Kohm) EXT CON Connector (Output EXT CON)
EVI EEV Electronic expansion valve (EVI) DIS2(200K) Thermistor (Discharge Temp.2_200Kohm) ERROR/COMP EXT Connector (Output ERROR/COMP EXT CON)
NOTE
•• This wiring diagram applies only to the outdoor unit.
•• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
•• When operating, don’t shortcircuit the protection device (High Pressure switch)
•• For connection wiring indoor-outdoor transmission F1-F2, outdoor_outdoor transmission OF1-OF2, refer to
the installation manual.
•• Protective earth(screw), : connector, : The wire quantity
111
7. Sound Data
Summary
NOTE
•• Sound Pressure Level
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
•• Sound Power Level
-- Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level.
-- Reference power : 1pW.
-- Measured according to ISO 3741.
112
7. Sound Data
Summary
Standard
Capacity Sound Pressure dB(A) Sound Power
Model
HP kW Cooling Heating dB(A)
8 22.4 AM080JXVAGH/EU 57 59 77
10 28.0 AM100JXVAGH/EU 58 60 79
12 33.6 AM120JXVAGH/EU 62 64 81
14 40.0 AM140KXVAGH/ET 61 63 81
16 45.0 AM160KXVAGH/ET 63 67 83
18 50.4 AM180KXVAGH/ET 64 67 84
20 56.0 AM200KXVAGH/ET 65 67 87
22 61.6 AM220KXVAGH/ET 65 67 89
24 67.2 AM240KXVAGH/ET 66 69 90
26 72.8 AM260KXVAGH/ET 66 69 90
28 78.6 AM280KXVAGH/ET 69 71 90
30 84.0 AM300KXVAGH/ET 69 71 90
32 89.6 AM320KXVAGH/ET 66 68 89
34 95.2 AM340KXVAGH/ET 67 69 90
36 101.6 AM360KXVAGH/ET 66 68 90
38 106.6 AM380KXVAGH/ET 67 70 90
40 112.0 AM400KXVAGH/ET 68 70 90
42 117.6 AM420KXVAGH/ET 68 70 91
44 123.2 AM440KXVAGH/ET 68 70 92
46 129.0 AM460KXVAGH/ET 70 72 91
48 134.4 AM480KXVAGH/ET 70 72 91
50 140.0 AM500KXVAGH/ET 70 72 92
52 145.6 AM520KXVAGH/ET 70 72 93
54 151.2 AM540KXVAGH/ET 71 73 93
56 156.8 AM560KXVAGH/ET 71 73 93
58 162.6 AM580KXVAGH/ET 72 74 93
60 168.0 AM600KXVAGH/ET 72 74 93
62 173.6 AM620KXVAGH/ET 71 73 93
64 179.2 AM640KXVAGH/ET 71 73 93
66 185.6 AM660KXVAGH/ET 71 73 93
68 190.6 AM680KXVAGH/ET 71 74 93
70 196.0 AM700KXVAGH/ET 71 74 93
72 201.6 AM720KXVAGH/ET 72 74 94
74 207.2 AM740KXVAGH/ET 72 74 94
76 212.8 AM760KXVAGH/ET 72 74 94
78 218.4 AM780KXVAGH/ET 72 74 94
80 224.2 AM800KXVAGH/ET 73 75 94
82 229.6 AM820KXVAGH/ET 73 75 94
84 235.2 AM840KXVAGH/ET 73 75 95
86 240.8 AM860KXVAGH/ET 73 75 95
88 246.6 AM880KXVAGH/ET 74 76 95
90 252.0 AM900KXVAGH/ET 74 76 95
NOTE
•• Sound Pressure Level
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
•• Sound Power Level
-- Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level.
-- Reference power : 1pW.
-- Measured according to ISO 3741.
113
7. Sound Data
Sound Pressure level
Unit: dB(A)
•• NR Curve
1) MAM080JXVHGH/EU
A 080JXVHGH/EU 2) AM100JXVHGH/EU
A M100JXVHGH/EU
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 Cooling NR 80 75
Sound Pressure Level (dB)
3) AM120JXVHGH/EU 4) AM140JXVHGH/ET
AM120JXVHGH/EU AM140JXVHGH/ET
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 Cooling NR 80 75 75 NR 80 75
Sound Pressure Level (dB)
70 NR 75 70 70 NR 75 70
65 NR 70 65 65 Cooling NR 70 65
60 NR 65 60 60 NR 65 60
Silent 1 Silent
Silent 12
55 Silent 2 NR 60 55 55 NR 60 55
50 Silent 3 NR 55 50 50 Silent 3 NR 55 50
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
Hearing NR 25 Hearing NR 25
15 15 15 15
threshold NR 20 threshold NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
114
7. Sound Data
Sound Pressure level
Unit: dB(A)
•• NR Curve
1) AM160JXVHGH/ET 2) AM180JXVHGH/ET
AM160JXVHGH/ET AM180JXVHGH/ET
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
Sound Pressure Level (dB)
3) AM200JXVHGH/ET 4) AM220JXVHGH/ET
AM200JXVHGH/ET AM220JXVHGH/ET
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
Sound Pressure Level (dB)
70 NR 75 70 70 NR 75 70
Cooling Cooling
65 NR 70 65 65 NR 70 65
60 Silent 1 NR 65 60 60 Silent 1 NR 65 60
55 Silent 2 NR 60 55 55 Silent 2 NR 60 55
50 Silent 3 NR 55 50 50 Silent 3 NR 55 50
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
Hearing NR 25 Hearing NR 25
15 15 15 15
threshold NR 20 threshold NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
115
7. Sound Data
Sound Pressure level
Unit: dB(A)
Microphone Model Cooling Silent 1 Silent 2 Silent 3
1m
AM240KXVGGH/ET 69 63 57 49
•• NR Curve
1) AM240KXVGGH/ET 2) AM260KXVGGH/ET
AM240KXVGGH/ET AM260KXVGGH/ET
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 Cooling NR 80 75 75 Cooling NR 80 75
Sound Pressure Level (dB)
3) AM280KXVGGH/ET 4) AM300KXVAGH/ET
AM280KXVGGH/ET AM300KXVAGH/ET
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 Cooling NR 80 75 75 Cooling NR 80 75
Sound Pressure Level (dB)
70 Silent 1 NR 75 70 70 Silent 1 NR 75 70
65 NR 70 65 65 NR 70 65
Silent 2 Silent 2
60 NR 65 60 60 NR 65 60
55 Silent 3 NR 60 55 55 Silent 3 NR 60 55
50 NR 55 50 50 NR 55 50
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
Hearing NR 25 Hearing NR 25
15 15 15 15
threshold NR 20 threshold NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
116
7. Sound Data
Sound Pressure level
Unit: dB(A)
•• NR Curve
1) AM080JXVAGH/EU 2) AM100JXVAGH/EU
AM080JXVAGH/EU AM100JXVAGH/EU
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 Cooling NR 80 75
70 NR 75 70 70 NR 75 70
Sound Pressure Level (dB)
3) AM120JXVAGH/EU 4) AM140KXVAGH/ET
AM120JXVAGH/EU AM140KXVAGH/ET
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 Cooling NR 80 75 75 NR 80 75
70 NR 75 70 70 NR 75 70
Sound Pressure Level (dB)
65 NR 70 65 65 Cooling NR 70 65
60 NR 65 60 60 NR 65 60
Silent 1 Silent
Silent 12
55 Silent 2 NR 60 55 55 NR 60 55
50 Silent 3 NR 55 50 50 Silent 3 NR 55 50
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
Hearing NR 25 Hearing NR 25
15 15 15 15
threshold NR 20 threshold NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
117
7. Sound Data
Sound Pressure level
Unit: dB(A)
•• NR Curve
1) AM160KXVAGH/ET 2) AM180KXVAGH/ET
AM160KXVAGH/ET AM180KXVAGH/ET
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
Sound Pressure Level (dB)
3) AM200KXVAGH/ET 4) AM220KXVAGH/ET
AM200KXVAGH/ET AM220KXVAGH/ET
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
Sound Pressure Level (dB)
70 Cooling NR 75 70 70 Cooling NR 75 70
65 NR 70 65 65 NR 70 65
60 Silent 1 NR 65 60 60 Silent 1 NR 65 60
55 Silent 2 NR 60 55 55 Silent 2 NR 60 55
50 Silent 3 NR 55 50 50 Silent 3 NR 55 50
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
Hearing NR 25 Hearing NR 25
15 15 15 15
threshold NR 20 threshold NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
118
7. Sound Data
Sound Pressure level
Unit: dB(A)
•• NR Curve
1) AM240KXVAGH/ET 2) AM260KXVAGH/ET
AM240KXVAGH/ET AM260KXVAGH/ET
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
Sound Pressure Level (dB)
3) AM280KXVAGH/ET 4) AM300KXVAGH/ET
AM280KXVAGH/ET AM300KXVAGH/ET
90 90 90 90
85 NR 90 85 85 NR 90 85
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 Cooling NR 80 75
Sound Pressure Level (dB)
70 Cooling 70 70 70
Silent 1 NR 75 Silent 1 NR 75
65 NR 70 65 65 NR 70 65
Silent 2 Silent 2
60 NR 65 60 60 NR 65 60
55 Silent 3 NR 60 55 55 Silent 3 NR 60 55
50 NR 55 50 50 NR 55 50
45 NR 50 45 45 NR 50 45
40 40 40 40
NR 45 NR 45
35 35 35 35
NR 40 NR 40
30 30 30 30
NR 35 NR 35
25 25 25 25
NR 30 NR 30
20 20 20 20
Hearing NR 25 Hearing NR 25
15 15 15 15
threshold NR 20 threshold NR 20
10 10 10 10
NR 15 NR 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A-weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
119
7. Sound Data
Sound Power level
Unit: dB(A)
Model Power
AM080JXVHGH/EU 77
AM100JXVHGH/EU 79
AM120JXVHGH/EU 81
AM140JXVHGH/ET 81
1) AM080JXVHGH/EU 2) AM100JXVHGH/EU
AM080JXVHGH/EU AM100JXVHGH/EU
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85
NR 90 80 80
80 80 NR 85
NR 85 75 75
75 NR 80 75 70
NR 80
70
70 70 NR 75
NR 75 65 NR 70 65
65 NR 70 65 60 60
60 60 NR 65
NR 65 55 NR 60 55
55 NR 60 55 50 50
NR 55
50 NR 55 50 45 NR 50 45
45 NR 50 45 40 NR 45
40
40 NR 45
40 35
NR 40
35
35 35 30 30
NR 40 25 NR 35 25
30 30 NR 30
NR 35 20 20
25 25 NR 25
NR 30 15 15
20 20 NR 20
NR 25 10 10
15 15 NR 15
10 NR 20
10 5 5
5 NR 15 5 0 0
125 250 500 1000 2000 4000 8000 A
0 0
125 250 500 1000 2000 4000 8000 A Octave Band Center Frequency(Hz)
Octave Band Center Frequency(Hz)
3) AM120JXVHGH/EU 4) AM140JXVHGH/ET
AM120JXVHGH/EU AM140JXVHGH/ET
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
Sound Power Level (dB)
NR 90 NR 90
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
70 NR 75 70 70 NR 75 70
65 NR 70 65 65 NR 70 65
60 NR 65 60 60 NR 65 60
55 NR 60 55 55 NR 60 55
50 NR 55 50 50 NR 55 50
45 NR 50 45 45 NR 50 45
40 NR 45
40 40 NR 45
40
35 35 35 35
NR 40 NR 40
30 30 30 30
25 NR 35 25 25 NR 35 25
20 NR 30 20 20 NR 30 20
NR 25 NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
5 NR 15 5 5 NR 15 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level.
-- Reference power : 1pW.
-- Measured according to ISO 3741.
120
7. Sound Data
Sound Power level
Unit: dB(A)
Model Power
AM160JXVHGH/ET 82
AM180JXVHGH/ET 85
AM200JXVHGH/ET 86
AM220JXVHGH/ET 88
1) AM160JXVHGH/ET 2) AM180JXVHGH/ET
AM160JXVHGH/ET AM180JXVHGH/ET
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
Sound Power Level (dB)
3) AM200JXVHGH/ET 4) AM220JXVHGH/ET
AM200JXVHGH/ET AM220JXVHGH/ET
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
Sound Power Level (dB)
NR 90 NR 90
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
70 NR 75 70 70 NR 75 70
65 NR 70 65 65 NR 70 65
60 NR 65 60 60 NR 65 60
55 NR 60 55 55 NR 60 55
50 NR 55 50 50 NR 55 50
45 NR 50 45 45 NR 50 45
40 NR 45
40 40 NR 45
40
35 35 35 35
NR 40 NR 40
30 30 30 30
25 NR 35 25 25 NR 35 25
20 NR 30 NR 30
20 20 20
NR 25 NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
5 NR 15 5 5 NR 15 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level.
-- Reference power : 1pW.
-- Measured according to ISO 3741.
121
7. Sound Data
Sound Power level
Unit: dB(A)
Model Power
AM240KXVGGH/ET 90
AM260KXVGGH/ET 90
AM280KXVGGH/ET 90
AM300KXVAGH/ET 90
1) AM240KXVGGH/ET 2) AM260KXVGGH/ET
AM240KXVGGH/ET
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
Sound Power Level (dB)
3) AM280KXVGGH/ET 4) AM300KXVAGH/ET
AM280KXVGGH/ET AM300KXVAGH/ET
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
Sound Power Level (dB)
NR 90 NR 90
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
70 NR 75 70 70 NR 75 70
65 NR 70 65 65 NR 70 65
60 NR 65 60 60 NR 65 60
55 NR 60 55 55 NR 60 55
50 NR 55 50 50 NR 55 50
45 NR 50 45 45 NR 50 45
40 NR 45
40 40 NR 45
40
35 35 35 35
NR 40 NR 40
30 30 30 30
25 NR 35 25 25 NR 35 25
20 NR 30 NR 30
20 20 20
NR 25 NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
5 NR 15 5 5 NR 15 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level.
-- Reference power : 1pW.
-- Measured according to ISO 3741.
122
7. Sound Data
Sound Power level
Unit: dB(A)
Model Power
AM080JXVAGH/EU 77
AM100JXVAGH/EU 79
AM120JXVAGH/EU 81
AM140KXVAGH/ET 81
1) AM080JXVAGH/EU 2) AM100JXVAGH/EU
AM080JXVAGH/EU AM100JXVAGH/EU
110 110
105 105 110 110
100 100 105 105
95 95 100 100
95 95
90 90 90 90
85 85
Sound Power Level (dB)
NR 90 85 85
Sound Power Level (dB)
NR 90
80 NR 85 80 80 80
NR 85
75 NR 80 75 75 75
70 70 NR 80
NR 75 70 NR 75 70
65 NR 70 65 65 65
NR 70
60 NR 65 60 60 NR 65 60
55 NR 60 55 55 NR 60 55
50 NR 55 50 50 NR 55 50
45 45 45 NR 50 45
NR 50
40 40 40 NR 45
40
NR 45 35 35
35 35 NR 40
NR 40 30 30
30 30 NR 35
25 NR 35
25 25 25
NR 30 20 NR 30 20
20 20 NR 25
NR 25 15 15
15 15 NR 20
NR 20 10 10
10 10 5 NR 15 5
5 NR 15 5 0 0
0 0 125 250 500 1000 2000 4000 8000 A
125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz)
Octave Band Center Frequency(Hz)
3) AM120JXVAGH/EU 4) AM140KXVAGH/ET
AM120JXVAGH/EU AM140KXVAGH/ET
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
Sound Power Level (dB)
NR 90 NR 90
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
70 NR 75 70 70 NR 75 70
65 NR 70 65 65 NR 70 65
60 NR 65 60 60 NR 65 60
55 NR 60 55 55 NR 60 55
50 NR 55 50 50 NR 55 50
45 NR 50 45 45 NR 50 45
40 NR 45
40 40 NR 45
40
35 35 35 35
NR 40 NR 40
30 30 30 30
25 NR 35 25 25 NR 35 25
20 NR 30 NR 30
20 20 20
NR 25 NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
5 NR 15 5 5 NR 15 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level.
-- Reference power : 1pW.
-- Measured according to ISO 3741.
123
7. Sound Data
Sound Power level
Unit: dB(A)
Model Power
AM160KXVAGH/ET 83
AM180KXVAGH/ET 84
AM200KXVAGH/ET 87
AM220KXVAGH/ET 89
1) AM160KXVAGH/ET 2) AM180KXVAGH/ET
AM160KXVAGH/ET AM180KXVAGH/ET
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
Sound Power Level (dB)
3) AM200KXVAGH/ET 4) AM220KXVAGH/ET
AM200KXVAGH/ET AM220KXVAGH/ET
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
Sound Power Level (dB)
NR 90 NR 90
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
70 NR 75 70 70 NR 75 70
65 NR 70 65 65 NR 70 65
60 NR 65 60 60 NR 65 60
55 NR 60 55 55 NR 60 55
50 NR 55 50 50 NR 55 50
45 NR 50 45 45 NR 50 45
40 NR 45
40 40 NR 45
40
35 35 35 35
NR 40 NR 40
30 30 30 30
25 NR 35 25 25 NR 35 25
20 NR 30 NR 30
20 20 20
NR 25 NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
5 NR 15 5 5 NR 15 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level.
-- Reference power : 1pW.
-- Measured according to ISO 3741.
124
7. Sound Data
Sound Power level
Unit: dB(A)
Model Power
AM240KXVAGH/ET 90
AM260KXVAGH/ET 90
AM280KXVAGH/ET 90
AM300KXVAGH/ET 90
1) AM240KXVAGH/ET 2) AM260KXVAGH/ET
AM240KXVAGH/ET AM260KXVAGH/ET
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
Sound Power Level (dB)
3) AM280KXVAGH/ET 4) AM300KXVAGH/ET
AM280KXVAGH/ET AM300KXVAGH/ET
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
Sound Power Level (dB)
NR 90 NR 90
80 NR 85 80 80 NR 85 80
75 NR 80 75 75 NR 80 75
70 NR 75 70 70 NR 75 70
65 NR 70 65 65 NR 70 65
60 NR 65 60 60 NR 65 60
55 NR 60 55 55 NR 60 55
50 NR 55 50 50 NR 55 50
45 NR 50 45 45 NR 50 45
40 NR 45
40 40 NR 45
40
35 35 35 35
NR 40 NR 40
30 30 30 30
25 NR 35 25 25 NR 35 25
20 NR 30 NR 30
20 20 20
NR 25 NR 25
15 15 15 15
NR 20 NR 20
10 10 10 10
5 NR 15 5 5 NR 15 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound power level is an absolute value that a sound source generates.
-- dBA = A-weighted sound power level.
-- Reference power : 1pW.
-- Measured according to ISO 3741.
125
8. Operation Range
Cooling Heating
55 30
48 24
45
20
35
10
25
Continuous
Warming
Outdoor(˚CDB)
Outdoor(˚CDB)
Operation Range Continuous
15 0 Up
Operation Operation Range
Range
5
-10
-5
“Expand Operational
Temperature Range” Option -20
-15
-25
-25 -30
10 15 20 25 27 30 5 10 15 20 25 27 30
Indoor(˚CWB) Indoor(˚CWB)
126
8. Operation Range
Defrosting correction factor
The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while
the defrosting operation is in progress.
The capacity values, which take these factors into account, in other words, the integrated heating capacity values,
can be calculated as follows :
Formula : A = B × C
Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrating correction factor for frost accumulation (kW) = C
Outdoor temperature (°C, DB/WB) -10/-10.4 -8/-8.5 -6/-6.5 -4/-4.6 -2/-2.7 0/-0.7 2/1.2 5/4.1 7/6
Capacity coefficient 0.99 0.98 0.96 0.95 0.91 0.88 0.86 0.91 1.00
On heating operation, frost can be formed on heat exchanger according to outdoor temperature.
(Frost on heat exchanger results in decreasing the performance.)
To remove frost on heat exchanger of outdoor unit, defrost operation is carried out periodically.
During defrost operation, capacity of outdoor unit may decrease.
The decrement is not considered to the individual capacity tables.
This figure shows an effect of intelligence defrost operation
It is actually the frost occurrence section from 0 ℃ or less.
Since the outdoor temperature over 0 ℃, the heating performance is the same before and after applying intelligence
defrost operation
In outdoor conditions below 0 ℃, frost conditions reflect the actual entering the defrost opration because heating
performance is improved
127
9. Piping Diagram
Outdoor unit
Ball Valve -
Outdoor Fan Motor Gas pipe (BV_G)
(OFM)
Thermistor-
Ambient
(T_A)
Thermistor-
CondOut
(T_CO)
Thermistor -
Suction pipe (T_S)
Pressure
Switch-
High1
(PW_H1) Thermistor-
Thermistor- Discharge Electronic
Compressor pipe1 Pressure Expansion
Top1 (T_D1) Sensor - Accumulator Valve - EVI
(T_CT1) Low (AC) (E_EVI)
(PS_L)
Compressor
(COMP) IPM Cooler
(IPMC)
Solenoid Thermistor -
Valve - Liquid pipe
EVI (T_L)
(V_EVI) Solenoid Valve -
Accumulator oil Return
(V_AR)
Ball Valve -
Liquid pipe (BV_L)
128
9. Piping Diagram
Outdoor unit
(2) AM140JXVHGH
Ball Valve -
OutdoorFanMotor1 OutdoorFanMotor2 Gas pipe (BV_G)
(OFM1) (OFM2)
Thermistor -
Ambient
(T_A)
Thermistor -
Cond Out
(T_CO)
Thermistor -
Suction pipe (T_S)
Pressure
Switch-
High1
(PW_H1) Thermistor-
Thermistor- Discharge Electronic
Compressor pipe1 Expansion
Top1 (T_D1) Accumulator Valve - EVI
(T_CT1) (AC) (E_EVI)
Pressure
Sensor -
Compressor Low
(COMP) (PS_L) IPM Cooler
(IPMC)
Solenoid Thermistor -
Valve - Liquid pipe
EVI (T_L)
(V_EVI) Solenoid Valve -
Accumulator oil Return
(V_AR)
Ball Valve -
Liquid pipe (BV_L)
129
9. Piping Diagram
Outdoor unit
(3) AM160~220JXVHGH
Ball Valve -
OutdoorFanMotor1 OutdoorFanMotor2 Gas pipe (BV_G)
(OFM1) (OFM2)
Thermistor-
Ambient
(T_A)
Thermistor-
CondOut
(T_CO)
Thermistor -
Suction pipe (T_S)
Thermistor -
Liquid pipe
Solenoid (T_L)
Valve - Solenoid Valve -
EVI 1 (V_EVI2)
Accumulator oil Return
(V_EVI1) (V_AR)
Ball Valve -
Liquid pipe (BV_L)
130
9. Piping Diagram
Outdoor unit
OutdoorFanMotor1 OutdoorFanMotor2
(OFM1) (OFM2) Check Valve - Ball Valve -
EEV Bypass 1 Gas pipe (BV_G)
(CV_EB1)
Thermistor-
Ambient Electronic
(T_A) Reservoir ExpansionValve-
Main1(E_M1)
Thermistor - (RE)
Cond In (T_CI)
Thermistor-
CondOut
(T_CO)
Check Valve -
EEV Bypass 2
(CV_EB2)
Compressor 1 Electronic
(COMP1) (COMP2) Expansion
Valve - EVI
(E_EVI)
Thermistor -
Liquid pipe
Solenoid (T_L)
Valve - Solenoid Valve -
EVI 1 (V_EVI2)
Accumulator oil Return
(V_EVI1) (V_AR)
Ball Valve -
Liquid pipe (BV_L)
131
9. Piping Diagram
Outdoor unit
(5) AM140~180KXVAGH
Ball Valve -
OutdoorFanMotor1 OutdoorFanMotor2 Gas pipe (BV_G)
(OFM1) (OFM2)
Thermistor -
Ambient
(T_A)
Thermistor -
Cond Out
(T_CO)
Thermistor- Electronic
Thermistor- Discharge Expansion
Compressor pipe1 Accumulator Valve - EVI
Top1 (T_D1) (AC) (E_EVI)
(T_CT1)
Solenoid Thermistor -
Valve - Liquid pipe
EVI (T_L)
(V_EVI) Solenoid Valve -
Accumulator oil Return
(V_AR)
Ball Valve -
Liquid pipe (BV_L)
132
9. Piping Diagram
Outdoor unit
(6) AM200~220KXVAGH
Ball Valve -
OutdoorFanMotor1 OutdoorFanMotor2 Gas pipe (BV_G)
(OFM1) (OFM2)
Thermistor-
Ambient
(T_A)
Thermistor-
CondOut
(T_CO)
Compressor 1 Electronic
(COMP1) (COMP2) Expansion
Valve - EVI
(E_EVI)
Thermistor -
Liquid pipe
Solenoid (T_L)
Valve - Solenoid Valve -
EVI 1 (V_EVI2)
Accumulator oil Return
(V_EVI1) (V_AR)
Ball Valve -
Liquid pipe (BV_L)
133
9. Piping Diagram
Outdoor unit
(7) AM240~260KXVAGH
OutdoorFanMotor1 OutdoorFanMotor2
(OFM1) (OFM2) Check Valve - Ball Valve -
EEV Bypass 1 Gas pipe (BV_G)
(CV_EB1)
Thermistor-
Ambient Electronic
(T_A) ExpansionValve-
Main1(E_M1)
Thermistor -
Cond In (T_CI)
Thermistor-
CondOut
(T_CO)
Check Valve -
EEV Bypass 2
(CV_EB2)
Compressor 1 Electronic
(COMP1) (COMP2) Expansion
Valve - EVI
(E_EVI)
Thermistor -
Liquid pipe
Solenoid (T_L)
Valve - Solenoid Valve -
EVI 1 (V_EVI2)
Accumulator oil Return
(V_EVI1) (V_AR)
Ball Valve -
Liquid pipe (BV_L)
134
High Temperature & Pressure Gas
High Temperature & Pressure Liquid
Low Temperature & Pressure Gas
Low Temperature & Pressure Liquid
Ball Valve -
OutdoorFanMotor1 OutdoorFanMotor2
Cooling System
Gas pipe (BV_G)
(OFM1) (OFM2) COOL
Thermistor- FAN ON
Ambient
•• 20HP with indoor units
(T_A)
Thermistor-
CondOut
(T_CO)
Thermistor - OFF
Liquid pipe
Solenoid (T_L) FAN OFF
Valve - Solenoid Valve -
EVI 1 (V_EVI2)
Accumulator oil Return
(V_EVI1) (V_AR)
Ball Valve -
Liquid pipe (BV_L)
135
136
High Temperature & Pressure Gas
High Temperature & Pressure Liquid
Low Temperature & Pressure Gas
Low Temperature & Pressure Liquid
Ball Valve -
OutdoorFanMotor1 OutdoorFanMotor2 Gas pipe (BV_G)
Heating System
(T_A)
Thermistor-
CondOut
(T_CO)
Thermistor - OFF
Liquid pipe
Solenoid (T_L) FAN OFF
Valve - Solenoid Valve -
EVI 1 (V_EVI2)
Accumulator oil Return
(V_EVI1) (V_AR)
Ball Valve -
Liquid pipe (BV_L)
10. Installation
Electrical wiring work
•• When installing outdoor units in module, select the power supply cable according to the sum of outdoor unit
capacity. (Refer to the table for each model)
•• Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 66 / CENELEC: H07RN-F)
Ex.) AM500✴XVA✴✴
•• This device is intended for the connection to a power supply system with a maximum permissible system
NOTE impedance shown in the table (on the left page) at the interface point (power service box) of the user’s supply.
•• The user must ensure that this device is connected only to a power supply system which fulfills the requirement
above. If necessary, the user can ask the public power supply company for the system impedance at the interface
point.
•• This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal
to Ssc(*2) at the interface point between the user’s supply and the public system. It is the responsibility of the
installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).
[Ssc (*2)]
137
10. Installation
Electrical wiring work
138
10. Installation
Electrical wiring work
•• Main power and the ground cable must be withdrawn through the knock-out hole on the bottom-right or right
side of the cabinet.
•• Withdraw the communication cable from the designated knock-out hole on the bottom-right side of the front part.
•• Install the power and communication cable using separate cable protection tube.
•• Fix a protection tube to the knock-out hole on the outdoor unit by using a CD connector or bushing. Make sure to
use insulating bushing.
Protection
tube
139
10. Installation
Electrical wiring work
ELCB
or
MCCB+
ELB
Communication cable
Power·ground cable
140
10. Installation
Electrical wiring work
Main unit
Sub unit
Protection
tube
141
10. Installation
Space requirement for installation
ffSpace requirement was decided based on following conditions; Cooling mode, outdoor temperature of 35 °C.
Larger space is required if the outdoor temperature is higher than 35 °C or if the place is heated easily by quantity
of solar radiation.
ffWhen you secure installation space, consider path for people and the direction of the wind.
ffSecure installation space as shown in the below illustration, considering ventilation and the service space.
ffIf the installation space is narrow, installer or other worker may get injured during work and may also cause
problem to the product.
ffIf you install multiple number of outdoor units in one space, make sure to secure enough ventilation space if
there’s any walls around the product that may disturb the air flow. If enough ventilation space is not secured,
product may malfunction.
ffYou may install the outdoor units with 20mm of space between the product, but product’s performance may
decrease depending on the installation environment.
Single installation
(Unit : mm)
Over 100 (S2)
Over 300
Front side
Height of the wall is
Front side Over 100
unlimited
Over 500 (S1)
142
10. Installation
Space requirement for installation
Module installation
Over 300
Over 300
(S2)
Height of
Over 200
the wall is
Over 100
Over 500
Front side Over 400 Front Over 400
(S1)
side
Over 100
Over 500
Front side
Over 600
Over 100
Over 100 Over 100
Over 500
Front side
<Case 3>
200
h2
Over200
Over
Grille/louver
Grille/louver
1500
Front side
500
Suction air
0
50
S1+h1/2 S2+h2/2 Ex.) Mechanical room ver
O
r5 00
Ove
143
10. Installation
Base construction and installation of the outdoor unit
ffConstruct the drainage ditch with reinforced concretes and make sure that water-proofing work is done.
ffFor smooth draining of defrost water, make sure to apply 1/50 slope.
ffConstruct a drainage around the outdoor unit to prevent the defrost water (from the outdoor unit) from
stagnating, overflowing or freezing near the installation space.
ffWhen the outdoor unit is installed on the roof, check the strength and waterproof status of the roof.
(Unit : mm)
°
60
80
960
760
80 80
X
X’
100
150 100
50
100
<X-X’ SECTION>
°
°
60
60
80
80
80
80 80
80 80 80
144
10. Installation
Base construction and installation of the outdoor unit
(Unit : mm)
Classification DVM S Small Type DVM S Large A Type DVM S Large B type
A 940 1,350 1,350
B 740 1,150 1,150
ffAnchor specification
b
c
❇❇ Use the anchor bolts and nuts that is zinc plated or made of STS material.
a
Regular anchor bolts or nuts may get damaged by corrosion.
Block the part. (When withdrawing the pipe from the front side)
Liquid side pipe
After installing the anti-vibration frame, untighten the fixing part on the top and bottom part of the frame.
XX
145
10. Installation
Wind/snow prevention duct
ffIt is necessary to install a discharge guide duct(field supply) to direct exhaust from the fan horizontally, when it is
difficult to provide a minimum space of 2m between the air outlet and a nearby obstacle.
Discharged air
Grille/louver
Suction air
ffIn cold regions with lots of snowfall, install a snow prevention duct, as a sufficient countermeasure, to prevent
snow from accumulating on the outdoor unit. When the snow prevention duct is not installed, frost may
accumulate on the heat exchanger and heating operation may not work normally.
ffAir outlet of the duct should not be directed to the enclosed space.
Cautions regarding on installing the frame and selecting the base ground
CAUTION
• Height (h) of the frame and the base ground should be higher than the "heaviest expected snowfall".
• Area of the frame and the base ground should not be larger than the are of the outdoor unit. Snow may
accumulate if the area of the frame or the base ground is larger.
146
10. Installation
Wind/snow prevention duct
ff In windy regions such as near sea shores, protection wall or wind protection duct must be installed for normal
operation of the outdoor unit. (Refer to the illustration of the snow prevention duct, for installing the wind protection
duct.)
ffInstall the wind prevention duct with the consideration of major wind direction. If the direction of the discharge
part is same as major direction of the wind, it could cause product’s performance decrease.
Cautions regarding on installing the frame and selecting the base ground
• The base ground must be solid and the outdoor unit must be fixed with anchor bolts.
CAUTION
• Make sure to install outdoor unit in a place strong enough to withstand its weight. If the place cannot
withstand the weight of the outdoor unit, outdoor unit may fall and cause personal injury.
• When installing on a rooftop subject to strong wind, countermeasures must be taken to prevent the unit from falling down.
• Use a frame that is resistant to corrosion.
560 (22.05) 880 (34.65) 560 (22.05) 871 (34.29) (Unit : mm)
782 (30.79)
532 (20.94)
668 (26.30)
1210 (47.64)
1318 (51.89)
2300 (90.55)
612 (24.09)
127 (5.00) 593 (23.35)
2271 (89.41)
1632 (64.25)
1150 (45.28)
1134 (44.65)
980 (38.58)
965 (37.99)
108 (4.25)
2000 (78.74)
180 (7.09)
180 (7.09)
<AM080/100/120✴XV✴✴>
560 (22.05) 1295 (50.98) 560 (22.05) 871 (34.29)
1197 (47.13)
532 (20.94)
668 (26.30)
1210 (47.64)
1318 (51.89)
2300 (90.55)
612 (24.09)
127 (5) 593 (23.35)
2271 (89.41)
1632 (64.25)
1150 (45.28)
1134 (44.65)
980 (38.58)
965 (37.99)
108 (4.25)
2415 (95.08)
180 (7.09)
180 (7.09)
<AM140/160/180/200/220✴XV✴✴>
560 (22.05) 1295 (50.98) 560 (22.05) 871 (34.29)
1192 (46.93)
532(20.94)
668 (26.30)
1252 (49.29)
1315 (51.77)
2400 (94.49)
2371(93.35)
640 (25.20)
552 (21.73)
1732 (68.19)
1255 (49.41)
1255(49.41)
1080(42.52)
1080 (42.52)
550(21.65)
(7.09)
180
180
406(15.98)
<AM240/260/280/300✴XV✴✴>
147
10. Installation
Refrigerant pipe installation
ffThe length of refrigerant pipe should be as short as possible and the height difference between an indoor and
outdoor unit should be minimized.
ffPiping work must be done within allowable piping length, height difference, and the allowable length after
branching.
ffThe pressure of the R-410A is high. Use only certified refrigerant pipe and follow the installation method.
ffAfter installing the pipes, calculate the total length of the pipe to check if additional refrigerant is needed. When
you need to charge the additional refrigerant, make sure to use R-410A refrigerant.
ffUse clean refrigerant pipe and there shouldn’t be any harmful ion, oxide, dust, iron content or moisture inside
pipe.
ffUse tools and accessories that fit on R-410A only.
148
10. Installation
Refrigerant pipe installation
ffInstall the refrigerant pipe according to main pipe size of each outdoor unit capacity.
ffWhen the pipe length (including elbow) between an outdoor unit and the farthest indoor unit exceeds 90m, you
must increase the size of the pipe (main pipe) by one grade which connects between the outdoor unit to the first
branch joint.
ffFor H/R model, When the pipe length (including elbow) between an outdoor unit and the farthest indoor unit
exceeds 90m, you must increase the size of the liquid pipe by one grade among the pipes(main pipe) which
connects between the outdoor unit to the first branch joint.
H/P
33.6 kW 40.0 kW 61.6 kW Ex.) 135.2 kW
Pipe size (mm)
Capacity (kW) No.
Liquid pipe Gas pipe
(D) 33.6 kW (1) Ø 12.70 Ø 28.58
73.6 kW (2) Ø 19.05 Ø 34.92
(1) (2) (3) 135.2 kW (3) Ø 19.05 Ø 41.28
(C) (E)
(A)
(B)
149
10. Installation
Refrigerant pipe installation
Outdoor unit capacity (kW) *Maximum pipe length within 90m *Maximum pipe length over 90m
(Cooling) Liquid pipe (mm) gas pipe (mm) Liquid pipe (mm) gas pipe (mm)
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1)
If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2)
If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3)
If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
150
10. Installation
Refrigerant pipe installation
Branch pipe length within 45m Branch pipe length between 45~90m
Indoor unit capacity (kW)
Liquid pipe (mm) Gas pipe (mm) Liquid pipe (mm) Gas pipe (mm)
Note1)
If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2)
If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3)
If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
Size of the pipe between the branch joint and the indoor unit
Make a selection according to outdoor unit capacity.
151
10. Installation
Refrigerant pipe installation
(D)
Branch joint
ffBranch joint between outdoor units (C)
Classification Outdoor unit capacity (kW) Model name of the branch joint
40.0 kW and below MXJ-YA2512M
40.1 kW ~ 45.0 kW MXJ-YA2812M
45.1 kW ~ 67.2 kW MXJ-YA2815M
Y-joint (D)
67.3 kW ~ 95.2 kW MXJ-YA3419M
95.3 kW ~ 135.2 kW MXJ-YA4119M
Over 135.2 kW MXJ-YA4422M
152
10. Installation
Refrigerant pipe installation
2) Distribution header
153
10. Installation
Refrigerant pipe installation
H/R
33.6 kW 40.0 kW 61.6 kW Ex.) 135.2 kW
Pipe size (mm)
Capacity (kW) No. Low pressure High pressure
Liquid pipe
(D) gas pipe gas pipe
33.6 kW (1) Ø 12.70 Ø 28.58 Ø 19.05
(1) (2) (3)
(C) 73.6 kW (2) Ø 19.05 Ø 34.92 Ø 28.58
(E)
(A) 135.2 kW (3) Ø 19.05 Ø 41.28 Ø 34.92
(B)
(F)
Outdoor unit capacity *Maximum pipe length within 90m *Maximum pipe length over 90m
(kW) Liquid pipe Low pressure High pressure Liquid pipe Low pressure High pressure
(Cooling) (mm) gas pipe (mm) gas pipe (mm) (mm) gas pipe (mm) gas pipe (mm)
22.4 kW Ø 19.05 Ø 15.88 Ø 19.05 Ø 15.88
Ø 9.52 Ø 12.70
22.5 kW ~ 28.1 kW Ø 22.22 Ø 22.22
Ø 19.05 Ø 19.05
28.2 kW ~ 33.6 kW
33.7 kW ~ 40.0 kW Ø 12.70 Ø 15.88
40.1 kW ~ 45.0 kW Ø 22.22 Ø 22.22
Ø 28.58 Ø 28.58
45.1 kW ~ 50.4 kW
50.5 kW ~ 56.0 kW
Ø 15.88 Ø 19.05
56.1 kW ~ 63.3 kW
Ø 28.58 Ø 28.58
63.4 kW ~ 70.3 kW
Ø 34.92 Ø 34.92
70.4 kW ~ 98.4 kW
98.5 kW ~ 135.2 kW Ø 19.05 Ø 22.22
Ø 41.28 Ø 34.92 Ø 41.28 Ø 34.92
135.3 kW ~ 169.0 kW
169.1 kW ~ 252.0 kW Ø 22.22 Ø 53.98 Ø 53.98 Ø 25.40 note1) Ø 53.98 Ø 53.98
*Maximum pipe length : The pipe legth between an outdoor unit and the farthest indoor unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
❇❇ For HR model, only increase the size of the liquid pipe If pipe length exceeds 90m
❇❇ For the case that the diameter of the default pipe of an outdoor unit does not match that of the pipe installed on
the site, a socket is provided by default together with the outdoor unit.
154
10. Installation
Refrigerant pipe installation
H/R
Size of the pipe between the branch joint and the indoor unit
Make a selection according to outdoor unit capacity.
Pipe size (O.D. mm)
Indoor unit capacity (kW)
Liquid pipe Gas pipe
6.0 kW and below Ø 6.35 Ø 12.70
6.1 kW ~ 16.0 kW Ø 9.52 Ø 15.88
16.1 kW ~ 23.0 kW Ø 9.52 Ø 19.05
Over 23.0 kW Ø 9.52 Ø 22.22
155
10. Installation
Refrigerant pipe installation
H/R
33.6 kW 39.2 kW 44.8 kW Branch joint
ffBranch joint between outdoor units (C)
Classification Model name Specification (kW)
(D)
Liquid/Low pressure Y-joint MXJ-TA3419M 135.2 kW and below
(C) MXJ-TA4122M Over 135.2 kW
(1) (2) (3)
(C) MXJ-TA3100M 135.2 kW and below
(E) High pressure Y-joint (C)
MXJ-TA3800M Over 135.2 kW
(A)
(B)
ffFirst branch joint (D)
Make a selection according to outdoor unit capacity.
(F)
Outdoor unit capacity Model name of the
Classification
(kW) branch joint
40.0 kW and below MXJ-YA2512M
40.1 kW ~ 45.0 kW MXJ-YA2812M
Liquid/Low 45.1 kW ~ 67.2 kW MXJ-YA2815M
pressure Y-joint (D) 67.3 kW ~ 95.2 kW MXJ-YA3419M
95.3 kW ~ 135.2 kW MXJ-YA4119M
Over 135.2 kW MXJ-YA4422M
22.4 kW MXJ-YA1500M
High pressure 22.5 kW ~ 67.2 kW MXJ-YA2500M
Y-joint (D) 67.3 kW ~ 135.2 kW MXJ-YA3100M
Over 135.2 kW MXJ-YA3800M
156
10. Installation
Refrigerant pipe installation
Additional refrigerant
H/P H/R
3.6 kW
7.1 kW
7.1 kW
157
10. Installation
Refrigerant pipe installation
Size of liquid pipe Ø 6.35 Ø 9.52 Ø 12.70 Ø 15.88 Ø 19.05 Ø 22.22 Ø 25.40 Ø 28.58
Additional amount (kg/m) 0.02 0.06 0.125 0.18 0.27 0.35 0.53 0.65
--For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter regardless
of the pipe size.
158
10. Installation
Refrigerant pipe installation
ffAmount of additional refrigerant for each indoor unit (ⓑ)
(Unit : kg)
Capacity(kW) 500 1000
1 .5 1 .7 2 .2 2 .8 3 .2 3 .6 4 .5 5 .6 6 7 .1 8 .2 9 9.3 11 .2 12 .8 14 16 18 22 22 .4 28 32 50
Model CMH CMH
Slim1way cassette (JSF)
(AM∗∗∗FN1DE∗∗) 0 .25 0 .25 0 .25 0 .32 0 .32
(AM∗∗∗JN1DE∗∗)
Interior1way cassette
0 .15 0 .15
(AM∗∗∗HN1DE∗∗)
2way cassette
0 .31 0 .47
(AM∗∗∗FN2DE∗∗)
4Way Casette S
0 .45 0 .45 0 .45 0 .45 0 .57 0 .69 0 .69
(AM∗∗∗FN4DE∗∗)
360 Casette
0 .45 0 .45 0 .45 0 .45 0 .69 0 .69 0 .69
(AM∗∗∗KN4DE∗∗)
FloorStanding Unit
0 .22 0 .32 0 .32
(AM∗∗∗∗NFDE∗∗)
ERV plus (AM∗∗∗FNKDE∗∗) 0 .11 0 .36
4way cassette S (600 ⅹ 600)
0 .29 0 .29 0 .29 0 .29 0 .37 0 .37 0 .37
(AM∗∗∗FNNDE∗∗)
Duct S (AM∗∗∗HNMPK∗/∗) 0 .22 0 .22 0 .22 0 .22 0 .31 0 .38 0 .38 0 .38
Duct S (AM∗∗∗HNMPK∗9∗) 0 .31 0 .31 0 .38 0 .38 0 .38
Duct S (AM∗∗∗HNHPK∗/∗) 0 .38 0 .38 0 .38
Slim duct (AM∗∗∗FNLDE∗∗) 0 .17 0 .17 0 .17 0 .26 0 .35 0 .35 0 .45 0 .42 0 .42 0 .62 0 .62
Slim duct (with drain pump)
0 .35 0 .35 0 .45 0 .42 0 .42 0 .62 0 .62
(AM∗∗∗KNLDE∗∗)
MSP duct
0 .24 0 .24 0 .24 0 .28 0 .28 0 .28 0 .32 0 .54 0 .68 0 .68 0 .91
(AM∗∗∗∗NMDE∗∗)
MSPduct (with drain pump)
0 .24 0 .24 0 .24 0 .28 0 .28 0 .28 0 .32 0 .54 0 .68 0 .68 0 .91
(AM∗∗∗KNMDE∗∗)
Home Duct (AM∗∗∗KNLDEH) 0.13 0.13 0.13 0.17
Ceiling (AM∗∗∗FNCDE∗∗ /
0 .39 0 .39 0 .56 0 .95
AM∗∗∗JNCDK∗∗)
Console (AM∗∗∗∗NJDE∗∗) 0 .16 0 .27 0 .27 0 .27 0 .27
Neo forte (AM∗∗∗FNTDE∗∗) 0 .24 0 .24 0 .24 0 .24 0 .36 0 .36
Neo forte (with EEV)
0 .34 0 .34 0 .34 0 .34 0 .51 0 .51 0 .51
(AM∗∗∗FNQDE∗∗)
AR5000 (AM∗∗∗JNADK∗∗) 0 .16 0 .16 0 .19 0 .25 0 .25 0 .52 0 .52 0 .52
AR5000 (with EEV)
0 .22 0 .22 0 .25 0 .34 0 .34 0 .71 0 .71 0 .71
(AM∗∗∗JNVDK∗∗)
New Boracay
0.24 0.24 0.32 0.32 0.49 0.49 0.49
(AM∗∗∗KNTDE∗∗)
New Boracay (with EEV)
0.24 0.24 0.32 0.32 0.49 0.49 0.49
(AM∗∗∗KNQDE∗∗)
MAX 4 (with EEV)
0.49
(AM∗∗∗MNQDE∗∗)
HSP duct (AM∗∗∗FNHDE∗∗) 0 .68 0 .68 0 .68 1 .18 1 .18
OAP duct (AM∗∗∗JNEPE∗∗) 0 .68 1 .18 1 .18
Big duct (AM∗∗∗JNHFK∗∗) 1 .15 1 .15
Hydro Unit HE
0.6 0.7 1.2
(AM∗∗∗FNBD∗∗)
Hydro Unit HT
0.6 note1)
(AM∗∗∗FNBF∗∗)
MCU (MCU-S∗NE∗∗N) 0.5
ffIf AHU kit is included among the indoor units, you must add 0.063kg of refrigerant for every 1kW of the AHU
capacity increase.
Note1)
In case the capacity conjunction of the Hydro Unit HT exceeds 50 % among the total indoor unit, please don’t put
the additional refrigerant.
159
10. Installation
Refrigerant pipe installation
160
10. Installation
Refrigerant pipe installation
• For pipes larger than Ø 19.05, drawn type (C1220T-1/2H or C1220T-H) type copper pipe must be used. If a
annealed type (C1220T-O) copper pipe is used, pipe may break due to its low pressure resistance and cause
CAUTION
personal injury.
161
10. Installation
Additional refrigerant
200 ~
300 mm
When the piping length
1 m or less
between outdoor unit
and the branch joint Over 2 m Over 2 m
exceeds 2m, install a
vertical trap as show in
the figure.
162
10. Installation
Refrigerant pipe installation
H/P
1. Using Y-joint
H/R
Using Y-joint
MCU
MCU
MCU
MCU
MCU
MCU
Note 1)
163
10. Installation
Refrigerant pipe installation
H/P
164
10. Installation
Refrigerant pipe installation
Outdoor unit 10 m or
Pipe length x ≤ 10 m, y ≤ 10 m, z ≤ 10 m
~ Outdoor less
unit (Module Equivalent 13 m or
installation) x ≤ 13 m, y ≤ 13 m, z ≤ 13 m
length less
165
10. Installation
Refrigerant pipe installation
Note 2) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110m, (If the height
difference is over 40m, contact your local dealer for more information.)
but when the indoor unit is located at lower level than outdoor unit, allowable height difference is 110m
(If the height difference is over 50m, need to decide whether to install PDM kit or not.)
Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A
166
10. Installation
Refrigerant pipe installation
H/R
MCU MCU
Installing with
MCU only H1
H2
H3
l
MCU n o p q
Installing with H4
H1 MCU MCU
H2
H3
167
10. Installation
Refrigerant pipe installation
168
10. Installation
Refrigerant pipe installation
Note 1) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110m, (If the height
difference is over 40m, contact your local dealer for more information.) but when the indoor unit is located at
lower level than outdoor unit, allowable height difference is 110m (If the height difference is over 50m, need to
decide whether to install PDM kit or not.)
Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A
Note 2) Required condition
Classification Condition Example
45 m ≤ b+h+k, l+m+q, l+r ≤ 90 m : Size of the
First branch joint ~
branch liquid and low pressure gas pipes (b,
Farthest Indoor unit
l, m) must be increased by 1 grade.
If the size of pipe (main pipe), between
the first branch joint and the outdoor unit, r
extended pipe
H4
MCU ~
c+d, c+e, c+f, g, h+i, h+j, h+k, n, o, p, q, r ≤ 45 m
Each indoor unit
Difference between the distance of the outdoor unit to the farthest
indoor unit and nearest indoor unit ≤ 45 (a+b+h+k) - (a+b+c+d) ≤ 45
Note 3) For indoor units to which no MCU is connected, be sure to set their options to “Cooling only indoor unit,” and then
connect them to a low pressure gas pipe and a liquid pipe. Be sure to combine the cooling only indoor units so
that their total capacity becomes 50% or less of the total capacity of all indoor units.
Note 4) In case of connecting more than one indoor unit in one MCU Port, the below indoor units can not be combined.
ERV plus (AM∗∗∗FNKDE∗∗), OAP duct(AM∗∗∗JNEPE∗∗), Hydro Unit HE(AM∗∗∗FNBD∗∗), Hydro Unit
HT(AM∗∗∗FNBF∗∗), AHU kit (MXD-K∗∗∗AN, MCM-D∗∗∗N)
Note 5) In case of connecting two MCU ports with Y-joint, the indoor units can not be combined to more than one.
169
10. Installation
Refrigerant pipe installation
MCU specification
Exterior of MCU
Number of
connectable indoor Up to 8 units Up to 8 units Up to 8 units Up to 8 units
units at one port
The maximum
capacity of the
16 kW 16 kW 16 kW 16 kW
connectable indoor
units at one port
The maximum
capacity of the
61.6 kW 61.6 kW 32.0 kW 16 kW
connectable indoor
units
Internal EEV Not included
• Indoor units without internal EEV(AM∗∗∗∗NTDE∗, AM∗∗∗∗NADE∗) can not be connected directly to the
CAUTION MCU.
• Please connect these indoor units using EEV kit(MEV-E∗∗SA, MXD-E∗∗K∗∗∗A).
170
10. Installation
Refrigerant pipe installation
Example installing
(Each port
connection)
Example installing
(MCU series MCU MCU
connection)
Under 16.0 kW indoor unit : Don’t use Y-connector This unit is only
16.0 kW ~ 28.0 kW indoor unit : Use Y-connector at the Gas & Liquid line connectable for one
If you want to continuous cooling operation under -5 ℃, set outdoor ‘Expand port under 16 Kw
operational temperature range for cooling operation (HR only)’, and use
Y-connector on 5.0 ~ 16 kW indoor unit This unit is
In case of using Y-connector, it is only connectable for port combination at below impossible to
Connectable port combination for Y-connector : A + B port, C + D port, E + F port connect MCU to
Non-connectable port combination for Y-connector : B + C port, D + E port, non- MCU in series.
Installing indoor
units continuous port
Set Dip Switch option for using Y-connector
S/W Option S/W Option S/W Option S/W Option
ON ON ON ON
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Default Combination of A+B port Combination of C+D port Combination of E+F port
171
10. Installation
Refrigerant pipe installation
Protect with
wet towel when
welding
70 mm
❇❇ When installing MCU, use the pattern sheet for installation that is provided with the product.
❇❇ When welding the gas pipes, protect the product with the flame-proof sheet.
❇❇ When connecting the MCU with outdoor units, default direction is set in the MCU.
If installing opposite direction, weld the enclosed copper cap in each high pressure, low pressure and liquid pipes.
172
11. Accessory
Controller
Wireless Remote
AR-KH00E 360 CST Only DVM, CAC
Controller
Wired Remote
MWR-WE11N DVM, CAC
Controller
Wired Remote
Controller MWR-SH00N DVM, CAC
- Simple Type
Wired Remote
Controller
MWR-SH10N DVM, CAC
- Touch Simple
Type
Wired Remote
MWR-WW00N EHS Only EHS
Controller
Master controller +
Zone Controller MWR-ZS00N DVM, CAC
Damper controller
173
11. Accessory
Controller
Touch Centralized
MCM-A300N DVM, CAC
Controller
ERV Interface
MIM-N10 DVM, CAC
Module
Lonworks
MIM-B18BN DVM, CAC
Gateway
External Contact
MIM-B14 DVM, CAC
Interface Module
Gate Way
MTFC (Multi
Tenant Function MCM-C210N DVM
Controller)
SIM (Signal
MIM-B12N DVM, CAC
Interface Module)
PIM (Pulse
MIM-B16N DVM, CAC
Interface Module)
174
11. Accessory
Controller
Installation /Test
S-Converter MIM-C02N DVM, CAC
run Solution
External Room
MRW-TA DVM, CAC
Sensor
Operation Mode
MCM-C200 DVM
Selection Switch
Others
FCU Interface
MIM-F10N CHILLER Only CHILLER
Module
NOTE
• In case you want more information about the accessories, please refer to the control and accessories TDB on
pvi.Samsung.com site.
175
11. Accessory
Controller & Control Accessory Compatibility
NASA Non-NASA
Item Remark
(DVM S) (DVM +3/+4)
Wireless Remote Controller MR-EH00 MR-EH00 DVM, CAC
Wireless Remote Controller AR-KH00E AR-KH00E DVM, CAC (360 CST)
Wired Remote Controller MWR-WE11N MWR-WE10 DVM, CAC
Wired Remote Controller
MWR-SH00N MWR-SH00 DVM, CAC
- Simple Type
Wired Remote Controller
MWR-SH10N - DVM, CAC
Individual - Touch Simple Type
Control System
ERV Wired Remote Controller MWR-VH12N - DVM, CAC (ERV)
Wired Remote Controller MWR-WW00N MWR-WW00 EHS
Receiver KIT MRK-A10N - DVM, CAC
Zone Controller MWR-ZS00N MWR-ZS00 DVM, CAC
Zone Controller MWR-ZS10N MWR-ZS10 DVM, CAC
Zone Controller MRW-TS MRW-TS DVM, CAC
Onoff Controller MCM-A202DN MCM-A202D DVM, CAC
Touch Centralized Controller MCM-A300N - DVM, CAC
Centralized
WIFI KIT MIM-H03N MIM-H03 DVM, CAC
Control System
Interface Module MIM-N01 MIM-N01 DVM, CAC
ERV Interface Module MIM-N10 MIM-N10 DVM, CAC
Integrated DMS2.5 MIM-D01AN MIM-D00A DVM, CAC
management
System S-NET3 MST-P3P MST-P3P DVM, CAC
NOTE
• In case you want more information about the accessories, please refer to the control and accessories TDB on
pvi.Samsung.com site.
176
11. Accessory
Piping
NOTE
• In case you want more information about the accessories, please refer to the control and accessories TDB on
pvi.Samsung.com site.
177
11. Accessory
Indoor unit
Motion detect
MCR-SMA 4Way Cassette S (600x600)
Sensor
178
11. Accessory
Indoor unit
External room
MRW-TA Casssette, Wall-mount, Ceiling, Duct, Console
sensor
NOTE
• In case you want more information about the accessories, please refer to the control and accessories TDB on
pvi.Samsung.com site.
179
11. Accessory
Indoor unit's Accessory Compatibility
OAP
1way MSP Duct
Floor Standing
Duct
Mini 4way
Slim duct
B-Ceiling
HSP Duct
ERV Plus
Big Duct
Console
Ceiling
Duct-S
4way
2way
AHU
RAC
PAC
360
Product Model Remark
8,10HP
MSP-0
MSP-S
MSP-2
MSP-1
JSF-0
JSF-2
JSF-1
5HP
PC4NUDMAN Ceiling O
PC4NBDMAN Ceiling (Black) O
PC4NUNMAN Open O
PC4NBNMAN Open (Black) O
PC4NUSKAN Waffle O
PC4NBSKAN Waffle (Black) O
PC4NUSKEN Classic O
Panel PC4SUSMAN Waffle O
PC4SUSMEN Classic O
PC1NUSMAN Stripe O
PC1NUPMAN Z-Slide O
PC1MWSKAN O
PC1NWSMAN Fluid O
PC1BWSMAN O
PC2NUSMEN Stripe O
MDP-N047SNC0D - O
MDP-N047SNC1D - O O
MDP-M075SGU1D - O O
MDP-M075SGU2D - O
DRAIN
PUMP MDP-M075SGU3D - O
MDP-E075SEE3D - O
External, All
MDP-G075SP O O
Capacities
MDP-G075SQ Internal O O
S-Plasma MSD-CAN1 - O O
Ion KIT MSD-EAN1 - O
Motion -
detect MCR-SMA O
Sensor
ERV CO2 -
MOS-C1 O
Sensor
MEV-E**SA 1 Indoor O
EEV KITS
MXD-E**K***A 2,3 Indoor O
6 ports,
MCU-S6NEK2N O O O O O O O O O O O O O O O O O O O O O O O
max 61.6kW
4 ports,
MCU-S4NEK3N O O O O O O O O O O O O O O O O O O O O O O O
max 61.6kW
MCU-KIT
2 ports,
MCU-S2NEK2N O O O O O O O O O O O O O O O O O O O O O O O
max 32.0kW
1 port,
MCU-S1NEK1N O O O O O O O O O O O O O O O O O O O O O O O
max 16.0kW
MXD-K025AN only for 2.5Hp's AHU O
MXD-K050AN only for 5Hp's AHU O
MXD-K075AN only for 7.5Hp's AHU O
AHU-KIT
MXD-K100AN only for 10Hp's AHU O
only for 10~40Hp's
MCM-D201N O
AHU
NOTE
• In case you want to know more information the accessories, please refer to the control and accessories TDB on
pvi.samsung.com site
180
2016. 12
Ver.1.0
Samsung Electronics Co., LTD.
B2B PM / SE
Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677
Website : www.samsung.com, http://btsp.samsunggsbn.com Email : airconditioner@samsung.com
Images and data in this book may subject to change without prior notice.