TECHNICAL PROPOSAL
The SecoGear enclosure included the following compartments with its special features to ensure
operation reliability and safety:
Breaker Compartment
Secogear breaker compartment has 6 numbers of interlocking systems to provide safety and prevent
mal-operation. SecoGear is equipped with an automatic grounded metal shutter each for bus and
line/load in front of its primary disconnect bushing. When the breaker is in the test or disconnect
position, the shutter will automatically close and lock to provide the designed IP protection.
Pressure relief is provided to have arc-proof integrity. Breaker position switch are provided within
the drawout mechanism to provide status of breaker position within the compartment. Space heater
is also provided as standard supply.
Cable Compartment
SecoGear cable compartment provides ample space for easy power cable connection. Standard
current Transformers, zero sequence current transformer, voltage transformers, and surge arresters
can be easily installed within the cable c0mpartment.
PAPH-SG18-1100039-R1 Page 8
10th December 2018
Cable entry is designed for bottom entry however any requirement for top entry can be provided
with additional rear compartment.
Reliable interlock between cable compartment door and make-proof Earthing switch is provided.
Position switch of Earthing switch and heater are provided as standard supply.
Standard power cable gland plate is made of stainless steel with its cable supports/clamps.
LV Compartment
LV Compartment is designed as a modular compartment with ample space for secondary component
installation and gasketed door. 3-stacks Swing mounted Terminal Block mounting plate will provide
flexibility for site wiring. Control cable glands 2x4 (Left and Right) and Inter-unit cable through also
provided as standard. Heater current monitor is a smart way to monitor heater operation.
Mimic diagram with its position indicators and high voltage potential indicator are provided in front
of the LV Compartment door.
PAPH-SG18-1100039-R1 Page 9
10th December 2018
Wiring PVC
Rated Voltage 750 V
Control command 1,5 mm 2 - Black
Voltage Transformers 4 mm 2 - Black
Current Transformers 4 mm 2 – Black
Inter Cubicle connection 2,5 mm 2 – Black
Grounding Circuit 2,5 mm 2 – Green Yellow
Frame Material: Steel (2mm thickness), Al-Zn plated
Protection degree: Panel IP 41 / Compartment IP20
Ambient indoor temperature: +40deg. Celsius
Finish color (Coating): RAL 7032 (Light Grey)
Operating Access: Full Front Access
On site Assembly/Service Access: Front and Rear Access – BOTTOM
Environmental conditions.
As specified in IEC 62208 Item 7.1.2.: The air is clean and relative humidity does not exceed 50% at a
maximum temperature of +400C.
Note that in our standard construction, only the panel door is painted. All other steel surfaces
receive a Al-Zn plating that can withstand pollution level class II indoor.
Storage conditions.
Minimum ambient temperature: - 300C.
Maximum ambient temperature: +400C.
PAPH-SG18-1100039-R1 Page 10
10th December 2018
APPENDIX D
BILL OF MATERIAL
PAPH-SG18-1100039-R1 Page 11
10th December 2018
- Additional Cost-Halogen Free LV Wire (set) 1
DC10-25/13.2 25kVA 13.2/0.23kV 1
Line Up Options 1
- Service Truck-One 650mm sevice truck for CB (pc) 1
- Service Truck-One 800mm sevice truck for CB (pc) 1
- Service Trail-One 650mm Sevice Trail for Cable VT (pc) 1
- End cover (pc) 2