Part: TCD Code

Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0


Page: 96/120
○ Operation CPU
TCD 171[1] Synchronous position trouble Detection
○ Speed CPU
Application Si231

[Meaning] Synchronous position trouble detected [Countermeasures]

*Trouble shooting procedure


Use ERROR LOG TABLE(A42E) on annuciator.
Check information of TCD171 on Trace Data display
[Explanation]
Change 4 Byte to Bit (3rd row, 13rd~16th column) to check.
The trouble will be detected as below cases.
Each Bit shows the reason of the trouble(7~0 Bit is available)
1. In case that the NVRAM data of address 0x0592~3, 0x23D4~5 are differ from
0x55AA value when main power has returned. (TCD 140), it will detect an error 15 .. 7 6 5 4 3 2 1 0
Then, The data in NVRAM is cleared.
Backup SDS Direction Speed - - - Level
RAM Over error in error in 500mm
BRD_Posi_Compen _Request -
error Speed power power
& EF_BRAM_CLEAR SWD_I[VI_UL] SWD_I[VI_DL] failure failure
TCD 171
EF_BRAM_CLEAR
0x8003 0x8004

1. If CP is normal and elevator stops due to power failure,


the elevator goes down to bottom floor with ACD=0B and then
transfer to ACD=27.
2. The speed of emergency stop when main power turned off point is over than 2. If the TCD171 occurs after power off/on and the 7, 5 and 4 Bit
125% of rated speed. is set
1) Check backup battery on DOC-140 is normal.
Limit_v = 1.25 * PGD_F_V_To_Tick * SVD_Contract_Speed / 60 2) If the volt of backup battery is less than 3.0V, replace it.
4. In case that the 6 Bit is set, Check the trouble concerning SDS
BRD_PF_Control.Velocity Refer to TCD150, 151, 157, 158.
> limit_v SWD_I[VI_UL] SWD_I[VI_DL]
5. In case that 0 Bit is set,
1) Refer to POSI OFF(TCD 114).
0x8003 0x8004
2) Check if the elevator is moved by brake opening in power off.

* EF_PF_OVER_V : 0x10
BRD_PF_Control.Dir BRD_PF_Control.Dir
== UP == DN
TCD 171
EF_PF_OVER_V
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0
Page: 97/120
○ Operation CPU
TCD 171[2] Synchronous position trouble Detection
○ Speed CPU
Application Si231

[Meaning] Synchronous position trouble detected [Countermeasures]

[Explanation]

3. When the main power turned off , If the direction information is not STOP,
UP or DOWN, it will detect an error
BRD_PF_Control.Dir BRD_PF_Control.Dir BRD_PF_Control.Dir
== UP == DN == STOP

* EF_PF_DIR : 0x20

SWD_I[VI_UL] SWD_I[VI_DL]
TCD 171
EF_PF_DIR
0x8003 0x8004

4. When TCD 150, 151, 157, 158 are detected.

*check_out : same contact as the before page


* EF_SDS_OS : 0x40

*check_out ERD_SD_OS_Mem TCD 171

EF_SDS_OS
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0
Page: 98/120
○ Operation CPU
TCD 171[3] Synchronous position trouble Detection
○ Speed CPU
Application Si231

[Meaning] Synchronous position trouble detected [Countermeasures]

[Explanation]

5. If the error of rotary encoder is over than 500mm after leveling, it will be
detected.
Coil[SW_GS_
POWER_READY] SWD_I[VI_LDC] Coil[RS_RUNNING] SWD_I[VI_C1ST]

0x8025 0x91B0 0x802A

Coil[AC_OP_MAINT_MODE] TCD 164 TCD 114 TCD 79 TCD 78

0x9030

Coil[AC_OP_FHM_ Coil[AC_OP_ Coil[SW_SS_48V_ Coil[SV_FORCE_


START_MODE] FHM_MODE] DOWN_HOLD] DECEL]
check_out

0x9032 0x9031 0x923C 0x921D

Coil[SW_GS_ Coil[IS_ Coil[IS_


check_out DOOR_ZONE] CUR_V_0] ZONE_500] TCD 171

EF_ZONE500
0x9250 0x91E8 0x9190

* EF_PF_DIR : 0x01
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0
Page: 99/120
○ Operation CPU
TCD 177 Emergency stop occurred frequently Detection Application Si231
○ Speed CPU

[Meaning] It is detected that the failures of high speed running prohibited have [Countermeasures]
occurred 12 times within 10 min
1. Check Error Log Table by A42E, find out the trouble occurred
frequently and perform trouble shooting.
[Explanation]

It is hold type, prohibit operation by R5SC after opening door at door zone

Coil[EM_EO_ Coil[AC_OP_
old_fast_run_cut FAST_RUN_CUT] MAINT_MODE] +1 E_Stop_Count[9]

0x90F4 0x9030

+1 E_Stop_10M_Count

E_Stop_10M_Count >= 12
TCD 177

Coil[EM_EO_FAST_RUN_CUT] old_fast_run_cut

0x90F4
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0
Page: 100/120
○ Operation CPU
TCD 178 Safety drive occurred frequently Detection Application Si231
○ Speed CPU

[Meaning] Detected that rescue running have occurred more than 6 times [Countermeasures]
within 10 min.
1. Search the reason for stopping out of door zone.
2. If stopping during running, refer to the error log table,
3. When below-stopping or over-stopping during leveling occurs
[Explanation]
verify whether parameter setting for the control of leveling is
It is hold type, prohibit operation by R5SCafter opening door at door zone light. (Pgc_Gain → ADDR:0x0212)

Coil[SW_FS_SAFETY_DRIVE_DETECT] tmp

0x92A8

old_safety_drive tmp Coil[AC_OP_MAINT_MODE]


+1 S_Drv_Count[9]

0x9030

+1 S_Drv_10M_Count

tmp old_safety_drive

Coil[SW_GS_IS_STOP] SWD_I[VI_LDC]
TCD 178

S_Drv_10M_Count >= 6 0x925D 0x8025


Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0
Page: 101/120
○ Operation CPU
TCD 182 Operation over duty trouble Detection Application Si231
○ Speed CPU

[Meaning] Count number of brake opening, if it is 180 times in 1 hour. [Countermeasures]

Stop at door zone with door opened for 10 min., and return
normal operation automatically.
[Explanation]

Stop elevator in order to protect brake coil for 10 min..

[Condition]
Stand by 10 min. after door open at door zone.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0
Page: 102/120
○ Operation CPU
TCD 184 SDS forced deceleration occurred frequently Detection Application Si231
○ Speed CPU

[Meaning] Forced deceleration occurs 3 times in series. [Countermeasures]

1. Check if Slow Down S/W works normally.


2. Check if assembly condition of Slow Down S/W is correct.
[Explanation]
Installation
Elevator lands at top or bottom floor by forced deceleration in case that the distance 60 m/min 90 m/min 105 m/min
distance
between landing level & SDS roller is farther than installation distance when SDS is
activated. SD1U(D) 1000 mm 1400 mm 1800 mm
If above condition occurs 3 times, high speed operation is cut with door opened at SD2U(D) x 2000 mm 2700 mm
door zone, TCD184 is appeared and system holds the trouble.
3. If the allowance is 50mm higher, adjust Slow Down S/W again.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0
Page: 103/120
○ Operation CPU
TCD 188 OLS trouble Detection Application Si231
○ Speed CPU

[Meaning] OLS is abnormal [Countermeasures]


In case that OLS is activated for 1080 msec even though CLS & CDS is
1. Check if Door PCB (DCD-23X) is normal.
activated, the trouble is detected.
2. Check CDS(13rd column), CLS(14th), & OLS(15th) of 3rd row
on annunciator. (If Bit is 1, switch is activated)
[Explanation] 3. Check the volt CA-07 on DOC-140, Y2-03 on DOM PCB, &
PJ1-13 on door PCB.
SWD_I[VI_CDS] Coil[DC_F_CLS] SWD_I[VI_DOLS] SWD_I[VI_RDMC] ERD_Door_Err If OLS is activated : 0V
If OLS is not activated: 24V
0x802B 0x90B5 0x802D 0x8060
4. Check if wiring & connecting is correct.
Coil[AC_OP_ Coil[SW_SS_48V_ Coil[SW_GS_ 5. If LED of OLS reed switch is lighted but OLS is out of position
MAINT_MODE] DOWN_HOLD] POWER_READY] Coil[DC_DCPU] TCD97 for activation, replace reed switch.

Coil[AC_OP_FIRE_ Coil[AC_OP_ Coil[SW_SV_


FIGHTING_MODE] FIRE_MODE] 1ST_FIRE] check_out

Coil[AC_OP_ Coil[SW_SV_
FIREMAN_MODE] 2ND_FIRE]

check_out 1080 msec


TMC_Start(OLS_
ERROR_DETECT_T)

TMC_Check(OLS_ERROR_
DETECT_T,FINISH_STATE) Coil[SW_GS_DOOR_ZONE]
TCD 188
0x9250

SWD_I[VI_CDS] SWD_I[VI_DOLS] TCD97


R TCD 188

0x802B 0x802D