Documente Academic
Documente Profesional
Documente Cultură
5, May 2019
E-ISSN: 2321-9637
Available online at www.ijrat.org
Abstract: In this paper, power system loss minimization using UPFC placed at optimal location given by
Gravitational Search Algorithm is proposed. Here, the Gravitational Search Algorithm (GSA) optimizes the location
of the UPFC, while the generator outage occurs. The generator outage affects the power flow constraints like power
loss, voltage magnitude, real and reactive power flows. By connecting UPFC at the optimum location power flows
are improved, which causes reduction in power loss. The proposed method is implemented in the
MATLAB/simulink platform. The performance of proposed method is evaluated by comparing power loss under
different conditions i.e. normal condition, generator outage condition and after connecting UPFC at optimal location
which is given ABC algorithm and GSA. The comparison results demonstrate the superiority of the proposed
approach and confirm its potential to find optimal location of UPFC.
2. RECENT RESEARCH WORK: A BRIEF B.Vijay kumar et al have attempted the problem
REVIEW of optimal location of UPFC to minimize power loss
of power system using Artificial Bee Colony
Numbers of related works are available in
algorithm [19]. They were carried out simulation
literature, which are based on enhancing the power
studies on IEEE 30 bus system.
transfer capability of power system. A few of them
During the last decade, continuous and fast
are reviewed here.
improvement of power electronics technology has
Ghamgeen Izat Rashed et al. [13] presented a
made flexible AC transmission systems (FACTS) a
Differential Evolutionary (DE) algorithm for finding
promising concept for power system applications.
the optimal location and the best parameter setting of
With the application of FACTS technology, power
Unified Power Flow Controller (UPFC) for
flow along transmission lines can be more flexibly
minimizing the active and reactive power losses in
controlled. Among a variety of FACTS controllers,
the power system.
UPFC is one of the more interesting and potentially
A novel strategy for optimal placement of PWM
the most versatile. it can provide simultaneous and
based Series Compensator (PWMSC) in huge power
independent control of important power system
systems have been brought in by A. Safari et al. [14].
parameters: line active power flow, line reactive
The proposed approach is based on the Selective
power flow, impedance; and voltage. [20].
Modal Analysis (SMA) and dynamics index to damp
Practically, the optimal location of UPFC tends not
out the inter-area oscillation modes. m. The
by randomly, and the matching methodical
effectiveness of the proposed algorithm is
exploration is not frequently adequate. Several
demonstrated on the 16-machine five-area power
researches have effort to solve the optimal location of
system for various network conditions.
UPFCs with respect to different purposes and
Using Fuzzy logic and Real Coded Genetic
methods. For determining the optimal location, the
Algorithm, an approach for appointment and sizing
operating condition of UPFC must be pre-assigned
of shunt FACTS controller has been suggested by
which can be taken as simultaneously. Some of the
A.R. Phadke et al. [15]. A blurry presentation index
optimization algorithms are introduced to determine
based on distance to encumber node bifurcation,
the location of UPFC such as genetic algorithm,
voltage profile and capacity of shunt FACTS
particle swarm optimization, differential evaluation
controller is suggested. In order to find the most
and etc. but these methods are inferior in terms
efficient location, the suggested method can be
searching ability to give optimal location hence a
applied and optimal size of the shunt FACTS tools.
new heuristic approach is needed to find location of
The suggested strategy has been used on IEEE 14-
UPFC. The proposed method is briefly described in
bus and IEEE 57-bus test systems.
the following section.
Sanjeev Kumar et al. [16]. have proposed an
efficient and reliable evolutionary based approach to
solve the optimal power flow (OPF) problems. The 3. UPFC STRUCTURE AND POWER
integration of Fuzzy Systems with Genetic Algorithm FLOW MODEL
(GA) and Particle Swarm Optimization (PSO)
The UPFC consists of two identical inverters, i.e.,
algorithm for optimal setting of OPF problem control
parallel inverter and series inverter, which are
variables. Their approach has been tested on the
connected in parallel and series to power systems
modified IEEE 30-bus test system with objective
through corresponding power transformers. The
function that reflects fuel cost minimization with
different linear and non-linear constraints. The results UPFC is connected between the buses i and j through
have been compared with the results those reported in the series and parallel power transformers [21], the
the literature. structure of the UPFC is described in the Fig. 1. The
B.Vijay kumar et al have attempted the problem parallel inverter can operates either voltage controller
of optimal location of UPFC to improve power or constant reactive power source. It injects constant
system voltage stability using Artificial Bee Colony th
positive or negative reactive power Qi at i bus and
algorithm [17]. They were carried out simulation regulates the voltage of the bus. The series inverter
studies on IEEE 14 bus system. independently controls the active power Pj and
B.Vijay kumar et al have attempted the problem reactive power Qj of the jth bus at associated settings,
of optimal location of UPFC to improve power which distinguishes the UPFC from the STATCOM
system voltage stability using Gravitational search and SSSC. Also the series inverter is used to regulate
algorithm [18]. They were carried out simulation the difference between the ith bus voltage Vi and jth
studies on IEEE 14 bus system. bus voltage Vj. The UPFC installation structure in
543
International Journal of Research in Advent Technology, Vol.7, No.5, May 2019
E-ISSN: 2321-9637
Available online at www.ijrat.org
Pij (t ) Vi
2 (t )
Vkl
2 (t )
G ij
(t )
2Vi Vkl Gij
(t ) (t ) (t )
cos( kl j ) Ploss g k (Vi 2 V j2 2ViV j cos ij )
G
kN E (6)
V j Vkl cos( kl j ) bij (sin kl j )
(t ) (t ) (t ) (t )
ij
Vi V j
(t ) (t )
G ij
(t )
cosij bij
(t )
sin ij Where k= (i,j); NE is the set of numbers net work
(1)
Qij (t ) Vi I ( t ) Vi
(t ) 2 (t )
(bij
(t )
B 2) branches, gk is the conductance of branch k. θij is the
Vi Vkl
(t ) (t )
G ij
(t )
sin( kl i ) bij (cos kl i )
(t )
voltage angle difference between bus i and j.
Vi V j
(t ) (t )
G ij
(t )
sin ij bij
(t )
cosij
3.3. Equality constraints
(2)
In this section explains the power system equality
constraints. Here, the power system generators need
544
International Journal of Research in Advent Technology, Vol.7, No.5, May 2019
E-ISSN: 2321-9637
Available online at www.ijrat.org
to ensure the customers total demand and the inspired by the Newton theory that says: each particle
transmission loss. It is also known as power balance attracts every other particle with a „„gravitational
condition of the power system. The power system force‟‟. The gravitational force between two bodies is
stability condition is affected by the generators directly proportional to the product of their masses
outage, which increase the power loss of the system and inversely proportional to the square of their
and affects the dynamic stability environment. The distance.
required power balance condition can be described in In GSA, each mass (agent) has four
the following equation (7). specifications: its position, its inertial mass, its active
gravitational mass, and its passive gravitational mass.
NG Nl Where inertial mass is measure of an object
PGi PD ( PLj )
i 1 j 1
(7) resistance to changing its state of motion when force
is applied, active gravitational mass is a measure of
the strength of gravitational field due to a particular
Where, PGi is the power generated in the i th bus, object, and passive gravitational mass is measure of
the strength of an object‟s interaction with the
PD is the demand, PLj is the real power loss of the gravitational field. The position of the mass
corresponds to a solution of the problem, and its
j th line. gravitational and inertial masses are determined using
a fitness function.
The inequality constraints are explained in the
following section. 3.6 Determination of Optimum location of UPFC
using GSA
3.4. Inequality Constraints
This section describes about the GSA based
This section describes the inequality constraints of optimum location determination. Initially the IEEE
the power system [24], i.e., voltage, real and reactive standard benchmark system normal power flow is
power and transformer tap positions. These analyzed using the N-R load flow analysis. Then the
constraints should be maintained at the stability limit. generator outage is introduced in the bus system, so
The power stability mainly considers the voltage the system becomes instability. Here, the GSA
stability of every node. , hence bus voltage limits are technique is used to find the most affected location to
mainly considered in the problem. For the stable place the UPFC, i.e., maximum power loss bus. The
operation of power system, bus voltage should be maximum power loss bus is the most suitable
location to connect UPFC.
Vi Vi Normally voltage limit of
min max
Vi
. The steps to find the optimum location are given in
every node may be 0.95 to 1.05 pu. Other Inequality the following section.
constraints are given below
Steps to find the optimum location
Vimin ≤ Vi ≤ Vimax Bus voltage limits (8)
Timin ≤ Ti ≤ Timax Tap position limits (9) Step 1: In the first step, the input agents are
Qimin ≤ Qi ≤ Qimax Reactive power generation (10) randomly generated at N dimensions. Here, the
bus voltage and the line losses are selected as the
Pimin ≤ Pi ≤ Pimax active power generation (11)
agents.
These constraints are satisfied under normal stable
Step 2: Apply load flow solution and then, evaluate
condition. During the generator outage condition, the
the fitness values of the random number of agents.
power flow constraints are affected, which makes Step 3: In the high mass, agents are selected as the
increase in power loss. In these conditions, the power best solutions and the corresponding load flow is
system loss can be minimized by connecting an analyzed.
UPFC at optimal location. This can be achieved using Step 4: The best solutions are separated into two
proposed GSA algorithm groups, the first groups have the minimum best
solutions and another group has maximum best
3.5 Gravitational Search Algorithm (GSA) solutions.
Gravitational Search Algorithm (GSA) is one of Step 5: For each best solution groups, the agent‟s
the latest Trajectory based Metaheuristic Algorithm, positions and velocity is modified.
which was first introduced by Rashedi, Nezamabadi Step 6: Run load flow analysis and evaluate the new
and Saied [25, 26] based on the metaphor of agents. Select the best agent from each group.
gravitational interaction between masses. GSA is
545
International Journal of Research in Advent Technology, Vol.7, No.5, May 2019
E-ISSN: 2321-9637
Available online at www.ijrat.org
Step 7: Find the voltage, real and reactive power loss can be minimized by connecting UPFC placed at
flow and power loss. optimal location, which can be determined by the
Step 8: Check the termination criterion. If it is proposed GSA algorithm.
satisfied terminate or else go to step 9.
Step 9: Generate the new agents to generate new
solutions. Go to Step 2.
Once the process is finished, the GSA is ready to
give the optimal location of the UPFC.
Once the termination criterion is attained, the
system is ready to give the optimum location of the
UPFC. The selected location is utilized and the load
flows are analyzed. The proposed method is tested in
the MATLAB platform and the numerical results are
analyzed with various techniques, which are briefly
described in the next section 4.
Power flow
Generator Best location During normal During generator After placing UPFC at
bus no. condition outage condition optimal location given
by GSA
From To
P(MW) Q(MVAR) P(MW) Q(MVAR) P(MW) Q(MVAR)
bus bus
Table 3. Power flow analysis at double generator outage condition with GSA
547
International Journal of Research in Advent Technology, Vol.7, No.5, May 2019
E-ISSN: 2321-9637
Available online at www.ijrat.org
Figure 4. Power loss comparison at single Figure 5. Power loss comparison at double
generator outage generator outage
The power loss comparison at single generator
outage shown in the Figure 4. It shows the Table 2 and Table 4 show effectiveness of
performance of the proposed method, because the proposed method of finding optimal placement of
power loss has been reduced compared to the normal UPFC to reduce power loss in the system. The power
condition and the outage condition. loss comparison at double generator outage is shown
in the Figure 5. It can be observed that the power loss
4.1.2. Double generators outage condition has been reduced as compared to the normal
In this case at a time two generators are given condition and the outage condition. It shows the
outages and corresponding stability is analyzed. performance of the proposed method.
Table 3 shows power flows for normal condition, From the above tabular forms and graphs it is
double generator outage condition and after clear that the proposed method is effectively selects
connecting UPFC whose optimal location is the optimum location of the UPFC as compared to
determined by GSA algorithm. Here, it is observed the other optimization techniques and reduces power
that power flows are improved after connecting the loss in the power system
UPFC.
Table 4 shows power loss at normal condition,
double generator outage condition and after 5. CONCLUSION
connecting UPFC at optimal location which is This paper proposed a heuristic technique based
determined by GSA algorithm. Here, it is observed power loss minimization of the power system using
that by connecting UPFC, power loss of the system is optimal placement of UPFC. Here, optimal location
reduced. Here, it can be observed that power loss is was determined by GSA technique.. The proposed
increased to 14.731MW during double generator heuristic method is tested on IEEE 30 bus system at
outage and it is reduced to 8.531MW after connecting different generator outages. In these conditions, the
UPFC whose location is given by proposed GSA power flows and the power loss are analyzed. The
algorithm. obtained numerical results were compared and the
performances were discussed. From the comparison
results it can be concluded that the proposed heuristic
technique is the well effective technique to determine
optimal location of UPFC in the power system
REFERENCES
[1] P. Ramasubramanian, G. Uma Prasana, and K.
Sumathi, "Optimal Location of FACTS Devices
by Evolutionary Programming Based OPF in
Deregulated Power Systems", British Journal of
Mathematics & Computer Science, Vol.2, No.1,
pp.21-30, 2012
[2] Rakhmad Syafutra Lubis, Sasongko Pramono
Hadi, and Tumiran, "Selection of Suitable
548
International Journal of Research in Advent Technology, Vol.7, No.5, May 2019
E-ISSN: 2321-9637
Available online at www.ijrat.org
Location of the FACTS Devices for Optimal allocation of FACTS in power systems",
Power Flow", International Journal of Electrical International Conference on Power System
& Computer Sciences, Vol.12, No.3, pp.38-49, Technology, 2000
2012 [13] Ghamgeen Izat Rashed, Yuanzhang Sun,
[3] S.Durairaj, and B.Fox, "Optimal Placement of Khalid A. Rashed, and H. I. Shaheen, “Optimal
Facts Devices", International Conference on Location of Unified Power Flow Controller by
Energy & Environment, 2008 Differential Evolution Algorithm Considering
[4] Rahul J. Shimpi, Rajendra P. Desale, Kunal S. Transmission Loss Reduction”, IEEE
Patil, Jaswantsing L. Rajput and Shailesh B. POWECON 2012, pp1-6.
Chavan, "Flexible AC Transmission Systems", [14] A.Safari, H.A. Shayanfar and A. Kazemi,
International Journal of Computer Applications, "Optimal location of PWM based series
Vol.1, No.15, pp.54-57, 2010 compensator in a power system", International
[5] P. K. Dash, S. R. Samantaray, and Ganapati Journal of Electrical Power & Energy Systems,
Panda, "Outage Classification and Section Vol.51, pp.127–133, October 2013.
Identification of an Advanced Series- [15] A.R. Phadke, and Manoj Fozdar, K.R. Niazi,
Compensated Transmission Line Using Support "A new multi-objective fuzzy-GA formulation
Vector Machine", IEEE Transaction on Power for optimal placement and sizing of shunt
Delivery, Vol.22, No.1, pp.67-73, January 2007 FACTS controller", International Journal of
[6] H O Bansal, H P Agrawal, S Tiwana, A R Electrical Power & Energy Systems, Vol.40,
Singal and L Shrivastava, "Optimal Location of No.1, pp.46–53, September 2012
FACT Devices to Control Reactive Power", [16] A. Safari, H.A. Shayanfar and A. Kazemi,
International Journal of Engineering Science and "Optimal location of PWM based series
Technology, Vol.2, No.6, pp.1556-1560, 2010 compensator in a power system", International
[7] Xuan Wei, Joe H. Chow, Behruz Fardanesh and Journal of Electrical Power & Energy Systems,
Abdel-Aty Edris, "A Common Modeling Vol.51, pp.127–133, October 2013.
Framework of Voltage-Sourced Converters for [17] B.Vijay kumar “Optimal Location of UPFC
Load Flow, Sensitivity, and Dispatch Analysis", to Improve Power System Voltage Stability
IEEE Transactions On Power Systems, Vol.19, Using Artificial Bee Colony Algorithm”,
No.2, pp.934-941, May 2004 American Journal of Electrical Power and
[8] D. Murali, and M. Rajaram, "Active and Energy Systems 2019; 8(2): 42-49.
Reactive Power Flow Control using FACTS [18] B.Vijay kumar “Improvement of power
Devices", International Journal of Computer system voltage stability by using UPFC placed at
Applications, Vol.9, No.8, pp.45-50, 2010 optimal location given by gravitational search
[9] L. Gyugyi, C.D. Schauder, S.L. Williams, T.R. algorithm” global journal for research analysis,
Rietman, D.R. Torgerson, A. Edris, "The Unified vol.8, issue 5, may 2019.
Power Flow Controller: A New Approach to [19] B.Vijay kumar, “Power System loss
Power Transmission Control", IEEE Trans., Vol. minimization by using UPFC placed at optimal
PWRD-10, No. 2, pp. 1085-1097, April 1995. location given by Artificial Bee Colony
Algorithm” International journal of research in
[10] Jigar S.Sarda, Vibha N.Parmar, Dhaval advent technology,
G.Patel, and Lalit K.Patel, "Genetic Algorithm [20] Gehengouda “ Power Flow Control using UPFC
Approach for Optimal location of FACTS Device”, International Journal Of Control,
devices to improve system loadability and Automation And Systems Vol.3 No.2 April
minimization of losses", International Journal of 2014.
Advanced Research in Electrical, Electronics and [21] A. Rajabi-Ghahnavieh, M. Fotuhi-Firuzabad, M.
Instrumentation Engineering, Vol.1, No.3, Shahidehpour and R. Feuillet, "UPFC for
pp.114-125, 2012 Enhancing Power System Reliability", IEEE
[11] Gerbex, S., Cherkaoui, R., and Germond, Transactions on Power Delivery, Vol.25, No.4,
A.J., "Optimal location of FACTS devices to pp.2881-2890, October 2010.
enhance power system security", IEEE Bologna [22] Wanliang Fang, and H.W. Ngan, "A robust load
Power Tech Conference Proceedings, 2003 flow technique for use in power systems with
[12] Mori, H., and Goto, Y., "A parallel tabu unified power flow controllers", Electric Power
search based method for determining optimal
549
International Journal of Research in Advent Technology, Vol.7, No.5, May 2019
E-ISSN: 2321-9637
Available online at www.ijrat.org
550