[Meaning] [Countermeasures]
NVRAM is abnormal
1. Check if Backup Battery is normal.
This trouble doesn’t hinder elevator operating. It will be returned to normal after
rescue operation to bottom floor.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0
Page: 86/120
○ Operation CPU
TCD 141 RTC trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
When RTC chip doesn’t operate well, the trouble occurs.
1. Perform ‘RTC set’ by ‘A69E’.
In case that RTC chip is abnormal, the trouble occurs. 3. Replace DOC-140.
This trouble doesn’t hinder elevator operating.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0
Page: 87/120
○ Operation CPU
TCD 145 ER_INV_Door Trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
When Door CPU Watchdog occurs and RETRY signal repeats
two times, but Door CPU is not returned to normal.
1. Check if the Door power Fuse cut on DOJ PCB.
1) FUSE capacity : 3A
2)Check the isolation between Door power line and Earth.
[Explanation]
2. Check if the DMC_CUT1 switch is OFF position.
In case door watch dog signal is off, The operation part will hold 3. Check the voltage between PJ1 mic jack 8 and 17 on the
door CPU retry signal about 300ms and monitor that Door CPU DCD-23X PCB. (AC93V ~ AC121V : Normal)
shall be return to its normal condition.
4. Replace the DCD-23X PCB : When LD4 (SAFE-OK) LED is
But if the door CPU watch dog signal does not return to normal not flickering.
condition within 5seconds, it outputs a new retry signal. And if it
occurs over 2 times, \it will detects an error. 5. Replace the DCD-23X PCB : When LD6 (WDT) LED is OFF.
Even error is detected, the retry signal is outputted repeatedly. 6. Check the voltage between PJ1-14 and PJ3-1 on the
When the watch dog signal is return to normal condition, the error DCD-23X PCB. (DC24V: Normal)
is cleared by automatically.
7. Check the voltage at DRIN-1 on the
DCL-243 PCB. (DC24V : Normal)
1) In case of not DC24V : Check the DR(IN/OUT) wiring.
2) In case of DC24V : Replace DCL-243 PCB.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-0
Page: 88/120
○ Operation CPU
TCD 147 OBS detection Detection Application Si231
○ Speed CPU
[Meaning] [Condition]
The signal of LDC keep off for 20~45 sec. at on position during high
speed operation. (Detecting time is depend on floor height)
This is hold type, so cut safety line and keep elevator inoperable.
[Explanation]
TMC_Start(OBS_
LDC_ON_DETECT_T)
TMC_Check(OBS_LDC_ON_
DETECT_T,FINISH_STATE)
TCD147
SWD_I[VI_LDC] old_LDC_state