SYSTEM NEUTRAL EARTHING

1.0 SYSTEM NEUTRAL EARTHING INTRODUCTION

The purpose of system earthing is to:-

• limit the difference of electric potential between uninsulated conducting


objects in an area
• provide for isolation of faulty equipment and circuits
• limit overvoltage under various conditions

It is standard practice to earth an electrical system for the purpose of limiting the
potential (with respect to the general mass of the earth) of

• current-carrying conductors forming part of the system, and non-current-


carrying metalwork associated with equipment, apparatus, and
• appliances connected to the system.

The former object is normally essential to the proper operation of the system, and
this aspect is generally known as "system earthing".

The latter concerns the safety of human life, of animals and of property, and this
aspect is sometimes known as "equipment earthing" or “safety earthing).

System earthing should normally be provided at one point usually at the source
end at its neutral point and as such System earth refers to intentional connection
of neutral point to earth.

This is necessary because loads may consist of transformers with delta primaries
or delta connected motors and neutral point may not be readily available. Also
for star connected motors/load transformers, earthing at load end may result in
wide variation in fault current depending upon system operating condition and
selective relaying may be difficult.

Also if the supply neutral point is earthed, the phase to earth voltages under
earth fault condition do not rise to high value. Earth fault protection becomes
easy. Hence it is a universal practice to have a neutral earthing at every voltage
level.

The reason for earthing at one point on each system is designed to prevent the
passage of current through the earth under normal conditions and thus to avoid
the risks of electrolysis and interference with communication circuit.

Equipment earthing refers to connection of non-current carrying metallic parts to


earth .It is quite different from neutral earthing. The non current carrying metal
parts include motor body, switchgear structure, transformer core and tank,
sheaths of cables, body of portable equipment etc

1 of 70
SYSTEM NEUTRAL EARTHING

Equipment Earthing ensures safety as the potential of earthed body does not
reach to dangerously high values since it is connected to earth. Secondly the
earth fault current flow through the earthing readily causes operation of fuse or.
an earth fault relay

The term "earthing" is used in this regard whether or not reliance is placed on the
earth itself as a low impedance return path for earth fault current.

The sub-stations, power stations, factories, and electrical installations need


proper body-earthing and neutral-earthing.

The neutral point and bodies of various electrical equipments are connected to
the earthing system,

The earthing system of a sub-station comprises several tens of earth elertrodes


buried deep into the ground The ground electrodes are usually 40 inm diameter,
2 5 rn long GI. Pipes These are connected to Earthing Mesh below ground level

Earthing Mesh can typically be formed by 40 mm dia mild steel rods spaced at 2
rn x 2 m mesh at a depth of 05 m

Earth resistance of Earthing System of a Power Station and sub-station should


be below 0.5 ohm.

Earth resistance of earthing system of residential building may be as high as 2


ohms.

Larger the installation, lower the earth resistance requirement,

With respect to system earthing, the neutral of star connected 3 phase winding of
transformers can be earthed. The neutral of generator can be earthed.

If neutral point is not available, a separate star-delta transformer is arranged Star


points can be earth Sometimes special earthing transformer having zig-zag
winding and neutral point is provided.

A rule to be followed-provide neutral earthing at every voltage level

2 of 70
SYSTEM NEUTRAL EARTHING

Advantages of the System Neutral Earthing


• Elimination of arcing grounds
• Lesser stresses on insulation during earth fault elsewhere.
• Easy earth fault protection.

Disadvantages of the System Neutral Earthing


• Higher earth fault current This disadvantage can be eliminated by providing
reactance earthing or resistance earthing.

In theory, the main power system networks does not have to be earthed and
sometimes arguments are put forward that an unearthed network may be more
reliable.

In some cases this can be true but, in general,unearthed networks can become
unreliable due to over-stressing of the insulation which surrounds cables or lines.

This can arise due to static, induction or intermittent faults.

In the UK & India and most of Europe, the main power networks are earthed.

For example, in the UK & India, the standards and regulations are in place that
are concerned with connection with earth.

This requires that each part of the power network (i.e. each voltage level) be
connected to earth.

In the case of high voltage systems, the earth connection should be as near as
possible to the source of voltage.

There are a number of ways in which the power system can be operated. These
include unearthed, high impedance earthed and low impedance earthed
arrangements.

These different arrangements are described briefly below in subsequent


sections.

3 of 70
SYSTEM NEUTRAL EARTHING

DEFINITION OF SYSTEM EARTHING

Effectively Earthed:

A system earthed through an earthing connection of sufficiently low impedance


(inherent or intentionally added or both) such that ground fault that may occur
cannot build up voltages in excess of limits established for apparatus circuits, or
systems so earthed. The criteria for meeting these requirements are:

• R0 ≤ X1
• X0 ≤ 3X1 The coefficient of earthing (of such systems ≤ 0.8

The earth fault current expected in effectively earthed system is of the same
order of fault current as is available for the three phase short circuit current (it is
typically more than 60% of three phase fault current)

Solidly earthed:

A system earthed through an adequate earth connection in which no impedance


has been inserted intentionally. ( i.e. a solid metallic connection from system
neutral to earth)

Unearthed:

A system, circuit or apparatus without an intentional connection to earth except


through potential indicating or measuring devices or other very high impedance
devices.

Medium Resistance earthed

A system where a resistance is intentionally added into the system earthing


connection such that R0 ≥ 2Xo.

High Resistance earthed

A system where nearly the highest permissible resistance is inserted in the


earthing connection such that Ro ≤ Xco /3

4 of 70
SYSTEM NEUTRAL EARTHING

Reactance Earthed

A system where a reactor is intentionally added into the system earthing


connection such that Xo ≤ 10X1

Coefficient of earthing

Coefficient of earthing is the ratio ELG/ELL, expressed as percentage of the


highest rms line to earth power frequency voltage ELG on a sound phase at a
selected location, during a fault to earth affecting one or more phases, to the line
to line power frequency voltage. ELL which would be obtained at the selected
location, with the fault removed.

Discussion Of Unearthed or insulated system

This does not have a deliberate, formal connection to earth.

There may be some high impedance connections for instrumentation, for


example the coil of a measuring device.

Under normal conditions the capacitance between each phase and earth is
substantially the same.

The effect is to stabilise the system with respect to earth so that, with a three-
phase system, the voltage of each phase to earth is the star voltage of the
system. The neutral point, if any, is then at, or near, earth potential, (see Figure
below).

Ungrounded System Figure-Normal Condition

5 of 70
SYSTEM NEUTRAL EARTHING

Faults on distribution system does occur and cannot be avoided, especially earth
fault.

Refer figure below of Ungrounded System Figure-With Fault On Phase C

From above figures it can be seen that even though the capacitive voltages are
unequal during a single line-to ground fault, the phase-to-phase voltages (VAB,
VAC, and VBC) have not changed in magnitude or phase relationship, and the
system remains in service.

Ground Current in the fault IG is the vector sum of the two currents IA and IB
(which are 90° ahead of their respective voltages VAG and VBG) where IA =
VAG/XCA and IB = VBG/XCB, WHERE XCA and XCB are the system capacitive
reactances calculated from the capacitances of the elements of the distribution
system. (This can be evaluated separately.) This ground current value is used to
determine the maximum ground resistance for high resistance grounding.

If the ground fault is intermittent such as arcing, restriking or vibrating type, then
severe overvoltages can occur.

When the first incident occurs, involving, say a contact between a conductor and
earth, there may be no damage as there is not a complete metallic circuit to
enable current to flow in an unearthed system.

This is different to an earthed system, where a significant current would flow.

At first sight, the unearthed system may appear to be a safer and more reliable
system.

6 of 70
SYSTEM NEUTRAL EARTHING

In reality a current would flow in the unearthed system, returning via capacitive
coupling to the other two phases.

The capacitive current flowing at the fault point is three times the normal
capacitive current to earth from each phase of the whole system.

The damage due to the first fault is likely to be slight, since the total current is still
relatively small.

However, the current could be sufficient to risk electrocution if someone was to


touch the damaged conductor.

Power companies often find that it is time consuming to locate faults on this type
of system. The introduction of an unearthed system into the many system in the
past thus required a change in the Electricity Supply Regulations.

The probability of a second fault is higher than generally thought, as the voltage
across the remaining insulation will be phase to phase level rather than phase to
earth (i.e. an increase of √3 in magnitude). This will stress the phase to earth
insulation and may cause accelerated ageing and breakdown.

A second fault is likely to involve considerable fault energy and damage. It is thus
important to remove the first fault as quickly as possible.

Resonance can cause over-voltages on this type of system.

The system already has a high capacitance and if a phase conductor is


connected to earth via a connection having a high inductance (e.g. an instrument
transformer), then resonance, high circulating currents and over-voltages can
occur.

An intermittent arcing fault which has a high impedance can cause similar high
voltages leading to equipment failure. This is due to a trapped charge effect on
the neutral.

The charge is progressively built up with each subsequent arc and can produce
voltages which can be sufficiently high to overseers insulation by 6 to 7 times (in
theory), of that occurring at normal voltage. In practice, due to weather
conditions, dust etc., the actual voltages measured have been 3 or 4 times the
normal voltage.

If continuity of supply is an important factor for the distribution system, then an


ungrounded system may have some advantages. However, the insulation
applied between each phase conductor and earth is likely to need increasing to
at least the same as that between different phases, in order to deal with single
phase to ground faults, and the trapped charge scenario.

The reasoning behind the prevalence of unearthed systems in many industrial


facilities thus appears to be historical.

7 of 70
SYSTEM NEUTRAL EARTHING

Old practice, especially in American and some European systems was the use of
unearthed neutral system.

This was adopted for process continuity for which the choice was for an
unearthed system that allowed for the controlled shutdown for fault repairs at a
convenient time, and this was of tremendous value to continuous manufacturing
processes by reducing production losses, equipment damage and outages.

Unearthed systems offer no advantage over high-resistance earthed systems in


terms of continuity of service, and have the disadvantages of
• transient over voltages,
• locating the first fault and
• burn downs from a second ground fault.

For these reasons, they are being used less frequently today than high-
resistance earthed systems, and existing unearthed systems are often converted
to high-resistance earthed systems by resistance earthing the neutral.

Discussion Of Earthed systems

If the earth fault is intermittent (arcing, restriking or vibrating), then severe


overvoltages can occur on an unearthed system.

The intermittent fault can cause the system voltage to earth to rise to six or eight
times the phase-to-phase voltage leading to a breakdown of insulation on one of
the unfaulted phases and the development of a phase-to-earth-to-phase fault.

Overvoltages caused by intermittent faults, can be eliminated by earthing the


system neutral through an impedance, which is generally a resistance, which
limits the earth fault current to a value equal to or greater than the capacitive
charging current of the system.

Once the system is resistance earthed, overvoltages are reduced and modern
highly sensitive earth fault protective equipment can identify the faulted feeder on
first fault and trip one or both feeders on the second fault before an arcing burn-
down does serious damage”

The intentional connection of the neutral points of transformers, generators and


rotating machinery to the earth provides a reference point of zero volts. This
protective measure offers many advantages over an unearthed system,
including:
• Reduced magnitude of transient over-voltages
• Simplified ground fault location
• Improved system and equipment fault protection
• Reduced maintenance time and expense
• Greater safety for personnel
• Improved lightning protection
• Reduction in frequency of fault

8 of 70
SYSTEM NEUTRAL EARTHING

An earthed system has at least one conductor or point (usually the neutral or star
point) intentionally connected to earth.

For reasons of cost and practicality, this connection is normally made near the
position where the three individual transformer phase windings are joined, i.e. the
star point or neutral.

This method is adopted if there is a need to connect line to neutral loads to the
system, to prevent the neutral to earth voltage fluctuating with load.

The earth connection reduces the voltage fluctuation and unbalance which would
otherwise occur.

Another advantage is that residual relays can be used to detect faults before they
become phase to phase faults. This can reduce the actual damage caused and
the stresses imposed on other parts of the electrical network.

The type of earthed system is classified according to the type of connection


provided. The main types are:-

Resistors and/or reactors are deliberately inserted in the connection between the
neutral point and earth, normally to limit the fault current to an acceptable level.

The impedance can, in theory, be high enough that little more fault current flows
than in an unearthed situation.

In practice, to avoid excessive transient over-voltages due to resonance with the


system shunt capacitance, inductive earthing needs to allow at least 60% of the 3
phase short circuit capacity to flow for earth faults.

This form of earthing has a lower energy dissipation than resistive earthing.

Arc-suppression coils, also known as Peterson coils or ground fault neutralisers,


can be used as the earth connection. These are tuned reactors which neutralise
the capacitive coupling of the healthy phases, so that fault current is minimal.

Due to the self-clearing nature of this type of earthing it is effective in certain


circumstances on medium voltage overhead systems, for example, those which
are prone to a high number of transient faults,

Resistance earthing is more commonly used, because it can allow the fault
current to be limited and damp transient over-voltages, if the correct value of
resistance is chosen.

In utility distribution systems in various parts of the world, particularly those at 33


kV and 11 kV, it is common to find 750, 1,000 or 1,500 A and in Neutral earth
resistors (NERs) installed in various combinations to limit the earth fault current.

9 of 70
SYSTEM NEUTRAL EARTHING

In systems with rotating machines like generators and motors, it is common to


use NER at the supply source to limit earth fault current to 25 A, 50 A or 75 A to
limit damage to windings and stator core (core tends to melt down for internal
direct EF between winding and core laminations due to winding insulation falire).

In older days liquid filled resistors were used.

In new installations, it is now more common to use ceramic type resistors. These
require less space, have significantly lower maintenance costs and cool down
more quickly than liquid resistors following the passage of fault current.

Most high voltage supply systems, even in the utility, are earthed. Approval has
been given in recent yers to unearthed overhead line systems in certain countries
but these have only been for small 11 kV & 33 kV systems where capacitive
earth fault currents are less than 4 A and circumstances are such that the system
will not be appreciably extended.

There are two broad categories of resistance earthing: low resistance and high
resistance. In both types of earthing, the resistor is connected between the
neutral of the transformer secondary and the earth. These are :--
• Low resistance earth system with EF current limited to high levels of the order
of 1500 A to 2000 A, which in some cases is limited to full load current of the
source supply transformer full load current.
• High resistance earthed system with earth fault current limited to very low
values of:-
• 25 to 70 A, usually used in distribution supply systems with directly
connected generators and motors. The EF current limit in this case is
selected to ensure the machine stator to core earth fault current is within
the machine internal earth fault current for 100 mili-sec, assuming
instantaneous protection is available to clear internal stator earth fault in
the motor/generator
• 5 A usually used for generator with unit transformer that isolates the
generator from the distribution system as far as zero sequence
impedance path is concerned.

10 of 70
SYSTEM NEUTRAL EARTHING

Discussion Of Resistance earthed system

There are two broad categories of resistance grounding: low resistance and high
resistance.

As far as possible generator neutral should be provided with high value NER to
ensure EF current is limited to as low a value as possible, typically 5 to 10 A such
that the resistive component of NER current is greater the connected system
capacitive charging current.

If the EF current contribution is low sensitive EF protection relay settings are


required.

In cases where generator is directly connected to load distribution bus, the


generator NER should be sized to ensure adequate EF current flows to operated
feeder EF relays for prompt fault clearance and circuit isolation. In such cases
the value of source supply generator EF contribution needs to be increase from
a low value of 5 A to the order of 70 A which is the maximum tolerable EF on
machines that can prevent core melting

Both the 5A and 70 A high resistance earthing scheme practiced in the industries
are discussed in the subsequent sections.

Discussion Of Medium Resistance earthing

Medium Resistance earthing usually is adopted for generating systems


connected directly to load distribution switchgear bus, where both motors and
supply generators are connected typically at voltage levels of 6.6 kV / 11 kV.

The medium resistance method has the advantage of immediate and selective
clearing of the earthed circuit but required that the minimum earth fault current be
large enough, usually 400A or more, to positively accurate earth fault relay.

High resistance earthing is a method that can be applied to obtain transient over
voltage protection without aiding earthing fault relays to each circuit.

When generators are connected directly to a common distribution bus serving


motor loads and other transformer/cable circuits, the role of NER is two fold
• One to limit EF to levels that can be tolerated by the rotating machines
• Other to ensure EF relays in all the circuits see adequate current for them
to pick up and operate to clear the fault.

In such cases it is recent practice to limit NER EF current to a maximum of 70 A,


which is the tolerable EF limit of motors and generators This allows EF relay pick
up to be in the range of 7A to 21 A which is 10 to 30 % of the EF current, the
range allowed for satisfactory EF protection of equipment.

Assuming 1 % as the lowest setting of numerical relays, the maximum ratio of


CTs in the distribution circuits should be of the order of 700/1A to 2100/1A.

11 of 70
SYSTEM NEUTRAL EARTHING

It is usual to provide core balance CT of 50/1A on outgoing motor feeders which


will ensure that sensitive EF relay connected to CBCT will have a pick up of 2.5A
even if an ordinary numerical EF relay with minimum 5 % EF pick up setting is
used.

CBCTs are useful to ensure EF relay pick up is sensitive enough even though
the EF current is limited to as low a value of 25 to 70 A.

The recent high resistance earthed system practices are shown in figures
attached for different scenarios

In both types of grounding, the resistor is connected between the neutral of the
source generator and/or the source supply transformer secondary and the earth
ground

The objective of the resistance earthing is to limit EF current to a value that can
be considered :-

• Low enough to reduce damage to machines during internal EF. Typical EF to


be limited for generators and motors connected to a common bus would be of
the order of 70 A clearled in instantaneous protection clearance duration of
maximum 100 milli-sec.
• High enough to operate EF relays with adequate sensitivity such as to cover
for a high % of phase to the neutral. winding protection. Typically for 90 %
machine winding protection coverage, the EF relay current pick up should be
10 % of the minimum EF current. The maximum EF current sensitivity should
not be allowed to increase over 30 % of the minimum EF current.

The generator and motor EF current versus withstand time curves for reference
are given in figures below:-

12 of 70
SYSTEM NEUTRAL EARTHING

13 of 70
SYSTEM NEUTRAL EARTHING

Typical Internal Stator Earth Fault Current withstand limit


of generators & motors

Typical External Earth Fault Current withstand limit


of generators & motors (time in second on the x axis)

Time in second

14 of 70
SYSTEM NEUTRAL EARTHING

Discussion Of High resistance earthing.

Generators, especially larger ratings should not be exposed to high EF currents.


The EF should be limited to as low a value as possible. This is not possible for
smaller generators that are directly connected to the distribution system bus as
the generator in this case should contribute enough EF current to operate
distribution feeder earth fault relays for fault clearance and isolation.

However larger generators are usually connected to the distribution system via
their dedicated step up or step down generator transformer that have delta
connected winding on the generator side with star connected winding on the
distribution side where medium resistance earthing with higher EF current
contribution can be followed to satisfy distribution system EF protection
requirements.

The use of Delta-Star unit generator transformer for each generator actually
isolates the generator circuit from the distribution system as far as earth fault on
the distribution system is concerned

Due to isolation of zero sequence circuit between the generator and the
distribution system, the generator earth fault could be limited to as low as value
as possible. This is because generator does not contribute to the external
distribution system EF and hence plays less role in the achievement of fast and
selective earth fault relaying on the external distribution system.

When continuity of operation is desired, downtimes due to dismantling of


generator stator and rotor for factory repairs is not acceptable.

A medium resistance generator earthing with 70 A EF limit is considered to be


too high from this point of view.

In order to improve system integrity by preventing generator outage and


downtime due to core damage on generators, it is important that generator EF
current is limited to low value. For such cases each generator neutral is earthed
through a single phase distribution transformer with a secondary loaded resistor.
The resistor will be sized high to limit the generator EF to as low as value of 5 to
10A such that the resistive component of the generator EF current is greater than
the total capacitive current in the generator circuit to prevent core damage and to
prevent production of high generator circuit transient over voltages in the event of
arcing fault

15 of 70
SYSTEM NEUTRAL EARTHING

Discussion Of Low Resistance Earthing

The practice in the past was to adopt low resistance earthing and this was before
sensitive numerical protection relays were used.

A high earth fault was required to ensure EF protection relays clear the fault but
this practice was a compromise that accepted the fact that internal motor or
generator EF will result in damage to the respective motor/generator.

Concerns of high internal machine stator EF are :-


• Excessive arcing to the machine core burns the stator iron core laminations
at the point of fault and results in core welding.
• Replacement of faulty conductor may not be a very serious matter but
damage to the core cannot be ignored, since the welding of laminations
would result in local overheating.
• The fused metal can sometimes be cut away and replaced, but if severe
damage has occurred, it may be necessary to rebuild the core down to the
fault., which would involve extensive dismantling of the winding.

Low resistance grounding of the neutral limits the ground fault current to a high
level (typically 50 amps or more) in order to operate protective fault clearing
relays and current transformers. These devices are then able to quickly clear the
fault, usually within a few seconds.

The importance of this fast response time is that it:


• Limits damage to equipment,
• Prevents additional faults from occurring,
• Provides safety for personnel,
• Localizes the fault.

The limited fault current and fast response time also prevent overheating and
mechanical stress on conductors.

Note that the circuit must be shut down after the first ground fault.

Low resistance grounding resistors are typically rated 400 amps for 10 seconds,
and are commonly found on medium and high voltage systems

The main drawback of low resistance earthed system is the value of EF that can
be too high resulting in considerable damage to generator/motor core during
internal stator EF. This can result in generator/motor downtime associated with
core damage that would need stator and rotor dismantling leading to costly and
long duration factory repairs

16 of 70
SYSTEM NEUTRAL EARTHING

Solidly earthed system

This is the most common arrangement, particularly at low voltage.

Here the neutral/earth connection is through an adequate connection in which no


impedance has intentionally been added.

.For LV systems the practice is to solidly earth the neutral without any intentional
earthing resistance. The main purpose being to limit voltage above earth at any
point of the LV system for personnel safety reasons.

The disadvantage of this arrangement is that the earth fault current is normally
high, but the system voltages remain suppressed or low under fault conditions

In distribution systems with LV motors, the EF current will be higher than the
values that can be tolerated by the motor. But since motors are of smaller
ratings, this aspect of damage is compromised in favour of personnel safety..

For grid in-feed system voltages above 36 kV, the neutral point of transformers
should be solidly earthed, unless otherwise required by the public utility.

Grid in-feeds with solidly earthed neutral points can result in high earth fault
currents flowing in the general mass of earth in the vicinity of the substation.
They must be designed such that these currents do not result in dangerous step
and touch potentials. Detailed guidance is given in IEEE Standard 80 (IEEE
Guide for Safety in AC Substation Grounding)

Transformer feeders to HV switchboards with a system voltage not exceeding 36


kV may be low resistance earthed within typical industrial or even utility
distribution networks, however, where the distribution network is predominantly
cable, most of any potential earth fault current will flow in cable sheaths.
Standard cable sheath have limited EF current withstand. If standard cables are
to used then transformers iupto 33 kV may be low resistance earthed with EF
current limited to full load current of transformer or maximum of 1200 to 1500 A.

Where cables are procured with additional copper braiding forming sheath with
higher cross sections and able to withstand high EF current then 33 kV systems
can be solidly earthed.

HV & EHV systems > 132 kV are usually solidly earthed

17 of 70
SYSTEM NEUTRAL EARTHING

Earthing Schemes for Multiple Generators

If multiple generators are directly connected to a switchboard and each is


earthed via its own dedicated resistor, then zero sequence harmonic currents
(principally, the third harmonic) may possibly circulate through the neutral-earth
connections of the parallel operating machines. The magnitude of this circulating
current will depend on:
• the difference in magnitude and phase of the triplen harmonic voltages in the
stator voltage waveform of the respective generators operating in parallel (if
the waveforms are not perfectly sinusoidal);
• the magnitude of neutral-earth resistances and of stator reactances (at the
relevant harmonic frequency) of the respective generators.

Consequently, harmonic current can circulate in the neutral resistors of dissimilar


machines operating in parallel, and also between identical machines operating in
parallel if the harmonic voltage is sufficiently large and/or the electrical loading of
the identical generators is sufficiently different.

If the sustained circulating current is such as to exceed the thermal rating of the
resistor, then the current may be reduced by increasing the ohmic value of the
resistor by adopting high resistance earthing for each generator.

A common bus connected earthing transformer (ET) for bus medium resistance
earthing will be required for schemes with multiple generators where each
generator is high resistance earthed). This may be done to ensure the resultant
earth fault current is at least 3 to 10 times the setting current of any earth fault
relay on the relevant HV system.

Various generator specification and standards states the maximum acceptable


harmonic voltages in the stator voltage waveform of synchronous generators.

Where generators of dissimilar ratings, characteristics or loadings are to be


operated in parallel so as to give rise to circulating currents in the above-
mentioned earthing resistors that would exceed the thermal rating of the
resistors, then the HV system shall be earthed via one earthing resistor only.
Each generator shall then be provided with a suitable switching device, i.e.,
remotely operated circuit breaker or latched contactor) to facilitate connection of
any machine to the single earthing resistor. During normal operation, only one
generator shall be connected to the resistor. If the generator so connected is
tripped for any reason, an alarm is required to prompt manual intervention to
close the neutral earth switching device of one of the other operating generators
to facilitate earthing of the system.

Where generators are connected to the main switchboard via individual


generator step-up transformers, each generator neutral point shall be individually
earthed through a single phase distribution transformer with a secondary resistor.
The resistor shall be rated to limit the generator earth fault current to 10 A, or to
3 x Ico where Ico is the per-phase capacitive charging current, whichever is the
greater.( In this respect the per-phase capacitive current is that due to the
generator stator windings, generator transformer LV winding, and generator main
cable/connections).

18 of 70
SYSTEM NEUTRAL EARTHING

Each earthing transformer and resistor shall be rated to withstand the respective
earth fault currents for a duration of not less than 10 s. Longer withstand times
may be required,depending on the earthfault protection system applied.

Common Star Delta Earthing Transformer Details

The earthing of a medium voltage network neutral or the protection of generator


can be carried out using a common zig zag earthing transformer or a star-delta
earthing transformer (also called homopolar generator) associated with a
medium value NER connected on the low voltage end.

This so called homopolar generator is a three phase transformer with two


windings and free flux (generally). This transformer has a primary winding
(medium voltage) which is star connected with its neutral connected to the earth.
The secondary is delta connected on a resistor.

During normal operation, the voltage across the terminals of the secondary is
zero and no current flows through the resistor.

When a fault arises on a phase, neutral point’s displacement on the primary


makes appear an homopolar voltage on the terminals of the secondary (see
diagrams ) :the current flows through the resistor.

Normal operation Earth fault Condition

The value chosen for this resistor, and characteristics of the transformer
(inductive & resistive drops), determines the earth fault current at the medium
voltage. In the event of a less severe fault, the neutral displacement is less and
the fault current in the low and medium voltage end are lees in proportional to the
neutral displacement.

19 of 70
SYSTEM NEUTRAL EARTHING

20 of 70
SYSTEM NEUTRAL EARTHING

Various GENERATOR Earthing Schemes Adopted In Practical Industrial


Sytems

The are shown individually in SLDs in subsequent pages

• Medium resistance system for industrial distribution system


predominated by motor loads with source supply generator directly
connected to the same distribution switchgear bus

Requirement For NER Selection In Above Scheme

• Generator is directly connected to the distribution system and


hence its EF current contribution should be high enough to
operate EF relays so as to clear and isolate faults on the
distribution feeders, but at the same time the EF current
should be low enough to prevent motor/generator core
damage due to internal stator earth faults in them.

21 of 70
SYSTEM NEUTRAL EARTHING

• Medium resistance system with common bus earthing with high


resistance used for generator earthing in a industrial distribution
system predominated by motor loads with source supply generator
directly connected to the same distribution switchgear bus

Requirement For Common RT With Medium NER Selection In


Above Scheme

• Generator is directly connected to the distribution system and


hence its EF current contribution should be high enough to
operate EF relays so as to clear and isolate faults on the
distribution feeders, but at the same time the EF current
should be low enough to prevent motor/generator core
damage due to internal stator earth faults in them.

Requirement For Individual High NER Selection For Each


Generator In Above Scheme
• Generator could be unearthed in the above scheme under
normal system operation, but a high NER is selected for each
generator to ensure generator will not be unearthed during its
start up when the generator circuit CB will be open. The value
of EF from generator is low as it does not add to the common
earthing transfer NER EF contribution limited to medium EF
current value required for reasons cited above.

22 of 70
SYSTEM NEUTRAL EARTHING

• Low To Medium resistance system with MULTIPLE GENERATORS


with only one generator neutral circuit switched on to common NER
connected to common neutral earth switchgear or otherwise

23 of 70
SYSTEM NEUTRAL EARTHING

Classification of systems based on types of system earthing and based on


protection in case of indirect contact

Dangerous touch voltages must be prevented from occurring or persisting in the


event of a fault (fault to frame).The limit values for touch voltages are:-
• 50 V ac
• 120 V dc

The earthing systems are classified internationally as:-


• TN System classified further as:-
o TN-S System
o TN-C System
o TN-C-S System
• TT System
• IT System
• Other systems as per IS 3043

General applications of these earthing systems used internationally and in in


India are as follows:
Basic Types Internationally Accepted

TN-S Internationally Accepted Systems With Separate 240 V Single phase domestic /
Neutral & Protective conductors throughout the commercial supply
system
TN-C Internationally Accepted Systems With Combined ‘----------------------------
Neutral & Protective conductors throughout the
system
TN-C-S Combination of international TN-S & TN-C in 415 V Three phase domestic /
different parts of the system commercial supply
TT 415 V three phase industrial
supply
IT TT System in which all exposed conductive parts 415 V three phase industrial
are connected to earth electrode which is systems where process
electrically independent of the source earth. Single continuity is of more impotanc
Phase TT system not followed in India
Indian Types As Per IS 3043

INDIAN TN-S Same as International TN-S system above but with 415 V Three phase domestic /
an independent earth electrode within the commercial supply
downstream load centre consumer’s premises is
required in this system
INDIAN TN-C Same as International TN-C system above but with 415 V Three phase domestic /
an independent earth electrode within the 3 phase commercial supply
downstream load centre consumer’s premises is
required in this system
T-TN-S The consumer’s installation, a TN-S system For bulk supply at 6.6 kV & 11 kV
receiving power at a captive substation through a
delta connected transformer primary

Each of the systems configurations are shown in diagrams in subsequent pages.

24 of 70
SYSTEM NEUTRAL EARTHING

• TN-S System is one in which the neutral and protective earthing system
are separate

TN-S as Per IS 3043 (Same As International One)

Indian TN-S as per IS 3043

25 of 70
SYSTEM NEUTRAL EARTHING

• TN-C System is one in which the neutral and protective earthing system
are combined

Indian TN-C as per IS 3043 (same as international TN-C)

26 of 70
SYSTEM NEUTRAL EARTHING

• TN-C-S System is one in which combination of both TN-S & TN-C are
adopted in different parts of the system

TN-C-S as per IS 3043

27 of 70
SYSTEM NEUTRAL EARTHING

• TT System in which all exposed conductive parts are connected to


earth electrode which is electrically independent of the source earth.
Single Phase TT system not followed in India

TT System as per IS 3043

28 of 70
SYSTEM NEUTRAL EARTHING

• IT System in which all exposed conductive parts are connected to


earth electrode with source is isolated from earth or may be earthed
through high impedance.

IT System as per IS 3043

29 of 70
SYSTEM NEUTRAL EARTHING

• Indian TN-S system as per IS 3043

• Indian T-TN-S system as per IS 3043

30 of 70
SYSTEM NEUTRAL EARTHING

RECOMMENDED PRACTICE

• It is necessary to provide system neutral earthing at each voltage level except


where a certain voltage level is intentionally kept unearthed.

• Recommended type of earthing for various systems is given in Table I.

• Recommended generator earthing applications are given in Table II.

• Location of earthing connection:- Earthing should normally be provided at


the source end. This is necessary because loads may consist of
transformers with delta primaries or delta connected motors and neutral point
may not be readily available. Also earthing at load end may result in wide
variation in fault current depending upon system operating condition and
selective relaying may be difficult.

• Generator earthing:- The maximum stress which a generator is normally


designed to withstand is that associated with the currents of a three phase
fault at the machine terminals. Because of relatively low zero sequence
impedance inherent in most synchronous machines, a solid line to earth fault
at machine terminals results in a machine winding current higher than three
phase fault current. Therefore some impedance in the generator neutral
earthing is necessary.

• Multiple power source:- When there are two or more major bus sections,
each bus section should have at least one earthed neutral point.

When there are two or more generators at one station, only one neutral
earthing resistor is some times used.

Each power source is then connected to the resistor through a neutral bus
and neutral switching equipment (preferably breakers) it is desirable in such
cases to operate with only one generator neutral breaker closed at a time to
eliminate any circulating harmonic or zero sequence currents.

In the case of multiple transformers all neutral isolating devices may be


normally closed because presence of delta connected windings (which are
nearly always present on at least one side of each transformer) minimizes
circulation of harmonic current between transformers.

• Zig-Zag earthing transformer:- Where one machine only is tied to a bus


with feeders requiring a permanent system earthing, generator neutral
earthing of any type is usually inadequate. Here removal of the generator
from service for any reason also removes the only earthing point. This also
may be the case with several machines on the bus where, for most economic
scheduling of generation or other reasons, all the generators on that bus may
at some time be shut down. In such cases an earthing transformer should be
provided on the generator bus. Either a zig zag or wye-delta transformer may
be used. For a given short time current rating, the zig-zag earthing
transformer is somewhat lower in cost and more frequently used. As an

31 of 70
SYSTEM NEUTRAL EARTHING

alternative, a more readily available start/delta transformer of adequate rating


(probably in stock) may be used.

• Parallel operation of Transformer:- When an earthed star/star transformer


with delta tertiary is operated in parallel with similar transformers with neutrals
unearthed, the rating of the tertiary of the former should be checked for being
adequate to carry zero sequence current under fault condition. The usual
33% rating of the tertiary winding may not be adequate.

• Merits and demerits of various earthing systems

EARTHING MERITS DEMERITS


TYPE
Solid earthing Fast relaying More damage at the point of
fault
No over voltage
Low resistance Graded protection Overvoltage on healthy
earthing possible. phases
Less damage at the point Higher cost
of fault.
High resistance No damage to the High overvoltages on healthy
earthing equipment phases
Continuity of supply Graded protection not
possible with fault possible
hanging in the system
Protection system is costly
:

32 of 70
SYSTEM NEUTRAL EARTHING

• Comparative Performance For Various Conditions Using Different


Earthing Methods

Characteristics Ungrounded Solid Low High


Grounded Resistance Resistance
Grounded Grounded

Immunity To Transient Voltages Worst Good Good Best

Ease Of Ground Fault Protection Worst Good Better Best

Equipment Protected Against Arc Fault


Worst Poor Better Best
Damage

Safety To Personnel Worst Better Good Best

Service Reliability Worst Good Better Best

Maintenance Cost Worst Good Better Best

Continued Production After First Ground


Better Poor Poor Best
Fault

Ease of Locating First Ground Fault Worst Good Better Best

Relay Co-ordination Not Possible Good Better Best


73% Increase in Voltage Stress Under L-G
Poor Best Good Poor
Fault Conditions
Not Not
Two Voltage Levels on the Same System Not Possible Best
Possible Possible

Reduction in Frequency of Faults Worst Better Good Best

First High Ground Fault Current Flows Over


Worst Better Good Best
Grounding Circuit

Potential Flashover To Ground Poor Worst Good Best

• Expected earth fault currents:- The typical level of available earth fault
current that can be expected from various types of system earthing are as
follows:

Solidly earthed, effectively Same order of fault current as is available for


earthed, earthed for serving the three phase short circuit current (more than
line to neutral loads 60% of three phase fault current)
Reactance earthed Nearly as high as the three phase short circuit
current (25% to 60% of 3 phase fault current)
Low resistance earthed 25A to 70 to 100 amperes depending on value
of resistance.
Medium resistance earthed 200 A to several thousand amperes
High resistance earthed Upto 10A level ( current though resistor more
than system charging current)

33 of 70
SYSTEM NEUTRAL EARTHING

The medium resistance method has the advantage of immediate and


selective clearing of the earthed circuit but require that the minimum earth
fault current be large enough, usually 400A or more, to positively accurate
earth fault relay.
High resistance earthing is a method that can be applied to obtain transient
over voltage protection without aiding earthing fault relays to each circuit.

• Criteria for limiting transient over voltages:- In resistance earthed


systems, the resistor earth fault current should be at least equal to, but
preferably greater than the charging current of the system.

In reactance earthed system the ratio Xo/X1 ≤ 10 where Xo is the zero


sequence inductive reactance of the system including that of the neutral
reactor.

Where a combination of earthing transformer and neutral earthing resistor is


used, the earthing transformer impedance should be low relative to the
neutral resistance. Ro / Xo ≥ 2, where Ro and Xo are inclusive of neutral
resistor and earthing transformer.

• Arrestor Application:- Arrester application discussed below is only to bring


out arrester ratings required with adoption of different methods of system
neutral earthing. ……..

The minimum required arrester rating is the maximum operating voltage


times coefficient of earthing, which is 80% for effectively earthed systems,
and more than 80% for non-effectively earthed or unearthed systems. The
earth fault current in this case is more than 60% of three phase fault current.

Systems, which employ some form of resistance system earthing, are non-
effectively earthed systems having coefficient of earthing of 100% for arrester
application purposes.

Many high voltage systems may exhibit coefficients of earthing as low as


70% and certain multi earthed distribution systems may even slightly less.

It may not be practicable to provide an earthing transformer of the size and


impedance necessary to give an Xo/Xl ratio of 3 or less. However, if the
generator neutral is also earthed by means of a suitable reactor, the earthed
neutral type (80%) of arrester may be applied at the machine terminals.

34 of 70
SYSTEM NEUTRAL EARTHING

EQUIPMENT SIZING

HIGH RESISTANCE EARTHING (TRANFORMER / RESISTOR


COMBINATION)
• EARTHING TRANSFORMER/ET)
• VOLTAGE = VLL
• IMPEDANCE (Xep) = (Xo / X1) ( VLL KV)2
---------------------------------
3 PHASE FAULT MVA
• CURRENT (Ie) = 3E / X1 + X2 +X0 + 3 Xep
(E = VLG Xep = REACTANCE OF EARTH RETURN PATH)
• DURATION = 10 SEC OR 60 SEC OR CONTINUOUS (FOR HIGH
RESISTANCE EARTH ONLY)
• EARTHING RESISTOR
R= 706
-------
CN2

C = CAPACITANCE TO EARTH IN µF / PH
N = TRANSFORMATION RATIO OF ET
• VOLTAGE = TRANFORMER SEC VOLTAGE
• TIME = 10 SEC OR 60 SEC

MEDIUM RESISTANCE EARTHING


R= VPH
---------
FAULT CURRENT
FAULT CURRENT IS GENERALLY LIMITED TO 200 TO 1000 A.
DURATION = 10 SEC OR 60 SEC.

REACTANCE EARTHING

REACTANCE Xn = X1 – X0
3
X1 = GENERATOR POSITIVE SEQUENCE SUB TRANSIENT
REACTANCE
X0 = GENERATOR ZERO SEQUENCE REACTANCE

35 of 70
SYSTEM NEUTRAL EARTHING

THERMAL CURRENT RATING


3E
Ie = ------------------------------------------------------
X1 + X2 + Xo + 3 (X n + X ep )
NOTE 1.
FOR X1 OF GENERATORS AND SYNCHRONOUS MOTORS USE
TRANSIENT REACTANCE FOR X2 OF GENERATORS,
SYNCHRONOUS AND INDUCTION MOTORS USE SUB
TRANSIENT REACTANCE ( X1, X2, X0 ETC REFER TO - SOURCE
TO POINT TO FAULT REACTANCE)
TIME - 10 SECONDS
60 SECONDS

36 of 70
SYSTEM NEUTRAL EARTHING

TABLE I
Sl. System Recommended Method of Ref. Remarks
# Earthing Fig
1 Industrial Plants
a) Up to 415V Solidly Earthed 1 Earth connector should be of
adequate capacity
b) Above 415V up to Medium Resistance 2 Limit Earth fault current to
11kV Earthed largest feeder current &
permit tripping of circuit.
c) Above 11kV Solidly earthed Earth Connector should be of
adequate capacity
2 Auxiliary Systems of i) Medium Resistance 2 Resistance to limit earth fault
Power Plants Earthed current to transformer full
load current & permit tripping
of circuits.
ii) High Resistance 3 When continued operation
Earthed (until it is convenient to locate
and correct the fault) is
desired.
3 Synchronous
Generators
a) Unit System i) High Resistance 3 Current limited to 1.5 times
Earthed capacitive charging current
(usually distribution
transformer and secondary
resistor)
b) Several machines ii) Reactor Earthed 4 Earth fault current to be
and/or feeders on limited to 25% -60% of three
the bus phase fault current to prevent
serious transient over voltages
( XO ≤ 10X1 ) and permit
selective relaying.
4 Transmission System a) Effectively earthed 1
b) Earth fault neutralizer 3 When it is desired to limit the
earth fault current and to
reduce switching surges to
safe values.

37 of 70
SYSTEM NEUTRAL EARTHING

TABLE II
Isolated
Neutral
NGT + and
Solid Reactor Resistor Remarks
NGR Zig-
Zag
NGT
LV BUS SM P S P NS Note 1 With CEIG
NO LV
MM P S P NS Note 2 Approval
FEEDER
LV BUS SM P NS P NS Note 1
WITH
FEEDER MM P P P NS Note 2
SM NS P P NS NS
HV BUS P
NO HV (With
FEEDER MM NS P NS NS
Neutral
Bus)
SM NS P P NS S* If
HV BUS
P sufficient
WITH
(With cable
HV MM NS P NS S*
Neutral capacitance
FEEDER
Bus) is available
P (For P (For
UNIT utility utility
NS P NS
SYSTEM Generators Generators
only) only)

NOTE1 FOR FAULT LEVEL GREATER THAN 40 KA FOR EXISTING SYSTEMS


NOTE 2 FOR FAULT LEVEL GREATER THAN 70 KA FOR NEW SYSTEMS
S - SATISFACTORY
P- PREFERRED
NS- NOT SUITABLE
SM - SINGLE MACHINE
MM - MULTIPLE MACHINES

38 of 70
SYSTEM NEUTRAL EARTHING

39 of 70
SYSTEM NEUTRAL EARTHING

40 of 70
SYSTEM NEUTRAL EARTHING

Figure 5

41 of 70
SYSTEM NEUTRAL EARTHING

Calculation of industrial distribution supply system Medium NER

Basis Of Calculation

• Compared to isolated neutral and distribution transformer (high resistance)


methods of grounding, the medium resistance grounding for the plant, say
typically 6.6 kV.auxiliary electrical system has the advantages of lower
transient over-voltages, and more reliable protective relaying.

• The Supply transformer secondary 6.6 kV neutral or supply source generator


6.6 kV neutral should thus be medium resistance earthed in order to limit 6.6
kV system earth faults (EF) to low values such as to restrict excessive
damage to 6.6 kV equipment (especially to rotating machines like 6.6 kV
motors due to core melt down possibility in case of higher earth faults)
bearing in mind the fact that earth faults are not too low to result in non
operation of earth fault protection (because of lower earth fault currents
expected as compared to low resistance earthing).

• In the medium resistance 6.6 kV system earthing method, the earth fault
current should be limited to a value that can be reliably detected
instantaneously and cleared immediately by all 6.6 kV circuits whilst at the
same time ensuring their respective EF relay setting is not below the
expected charging capacitance current of the system.

• It has been observed that with the addition of even small resistance at the
neutral, the line to neutral voltage during line to ground fault rises to line to
line voltage. But the transient over voltages can be kept to lower side if the
magnitude of the resistive component of earth fault current is increased such
that the resistive loss during EF is greater than capacitance loss in the
system during the fault.

42 of 70
SYSTEM NEUTRAL EARTHING

• With respect to above note the following aspects for 6.6 kV system NGR :-

o The 6.6 kV incomer transformer circuit EF relay setting should not


exceed 30 % of the EF current and the outgoing motor/transformer 6.6 kV
EF relay setting minimum sensitivity should be 10 % of the EF current.
o Any 6.6 kV circuit EF relay setting should not be lower than the system
capacitive charging current which for a system with 9 transformers, 2
motors and 1 km of 6.6 kV cables is not expected to be greater than 3 to
5 A at 6.6 kV (assuming 1 A for 1 km of 6.6 kV cables, 0.1 A for two 6.6
kV motors and total of 1 A for transformer capacitance charging current
for 9 transformers including other margins. For Thumb Rule Values Refer
Appendix attached).
o Say the largest incoming 6.6 kV circuit CT ratio will be 2000/1A,
Assuming a 1.00 % setting available for numerical earth fault relays at
least 67 A earth fault current contribution will be required for satisfactory
operation of the earth fault protection connected to the largest incoming
feeder 2000/1 A CT. This ensures the largest incomer feeder EF setting is
very well below 30 % of the total EF current for achieving the desired EF
sensitivity. (Note for 2000/1A CT, its respective feeder EF relay setting
can be set to 20 A (1.0 % of 2000 A) which is 30 % of the total EF Current
expected of 67 A.
• For outgoing circuits with lower CT ratings, better EF sensitivity (10 % of EF
current) can be achieved with 67 A EF current.
• While selecting the value of ground fault current, it has been observed that
with 67 Amps 6.6 kV ground fault current, fast and sensitive earth fault
protection can be provided without mal-operation due to capacitive current
charging effect
• Also 67 A EF current is safely within the tolerable value of generators and
motors for internal stator EF.
• The earthing resistor will be of the heavy duty, non inductive, rustless,
oxidation resistant, jointless and unbreakable stainless steel grid type. The
resistor willl be housed in a vermin proof, water proof & weather proof
protected metal clad enclosure suitable for outdoor installation.
• Since any circuit EF relay will isolate the feeder within a few seconds on the
occurrence of ground fault, a time of say 10 seconds may be taken for the
NGR short time rating, the 6.6 kV neutral earthing resistor should be capable
of carrying rated 67 A earth fault current for a period of at least 10 seconds
without damage to itself or its enclosure. The earthing resistor will be
complete with supporting insulator/structure and insulated for 7.2kV above
earth for 6.6 kV resistor.

43 of 70
SYSTEM NEUTRAL EARTHING

Calculation of industrial distribution supply system Medium NER

Rated MVA of HV Transfo. = 20.00 MVA


Voltage Ratio of HV Transfo. = 33kV / 6.9 kV kV
NGR connected to Winding (kV) = 6.6 kV
Vector Group of HV Transfo = Dyn1
NER Current rating = 67 A
( As per Basis Discussed In this sizing report)
System Rated Voltage = 7.2 kV
Hence
Resistance value of NER = 6.6 / 1.732 / 67
= 56.873 Ohm
NER Current rating = 67 A
NER Rated Maximum Voltage = 7.2 kV
NER Nominal Voltage 6.6 kV
0
NER Design Ambient Temperature = 55 C
Resistance value of NER = 56.873 Ohm
Material of Construction Stainless Steel (SEE Note Below)
Temperature rise 250 °C over ambient temp 50°C
Degree of protection = IP - 55
Location of installation = Outdoor
Note:- The earthing resistor shall be of the heavy duty, non inductive, rustless,
oxidation resistant, jointless and unbreakable stainless steel grid type. The resistor
willl be housed in a vermin proof, water proof & weather proof protected metal clad
enclosure suitable for outdoor installation.

44 of 70
SYSTEM NEUTRAL EARTHING

Generator High Resistance Earthing Transformer & NER Calculation


Basis Of Design
• In order to protect stator core from damage during internal stator earth fault,
it is necessary to limit stator earth fault to as low a value that is
practicable.
• Generators connected to the distribution system, through unit
generator transformer dedicated to each generator, can be treated as
an isolated system which is not influenced by the earthing
requirements of the distribution system which in this case is
established through tdistribution side transformer medium earthing
resistance.
• The industry wide practice for such generators is to use a 11 kV
neutral earthing transformer suitably rated with secondary winding
designed for 240 V or so and loaded with a resistor of a value which
when referred to the primary will pass a low earth fault current of say 5
to 10 A.
• The Neutral earthing resistor connected shall be of low ohmic value of
rugged construction while still presenting a high equivalent value in the
generator 11 kV neutral circuit
• The Neutral resistor shall be incorporated to prevent the production of
high transient over voltages (TOVs) in the event of an arcing earth fault
which it does by discharging the bound charge in the circuit
capacitance.
• To prevent transient over voltages, it is necessary to ensure the
equivalent resistance in the stator circuit should not exceed the
impedance at system frequency of the total summated capacitances of
the three phases of the generator circuit.
• In this respect the resistive component of stator EF current should not
be less than (not < than) the residual capacitance current ( 3.Ico ) in
the generator 11 kV circuit upto generator unit tranformer.
• For Selecting Earthing Transformer, it is necessary to ensure it never
becomes saturated otherwie a very undesirable condition of ferro-
resonance may occur.. In this respect it is usual to select transformer
havinng a primary winding with knee-point voltage (Vk) = to 1.3 x
generator rated line voltage of 11000 V (11 kV)

45 of 70
SYSTEM NEUTRAL EARTHING

Generator High Resistance Earthing Transformer & NER Calculation

Selection Of EF Current Limit


Generator Data
Generator Rating = 50 MW
Rated Gen kV 11 kV
Maximum Overvoltage 14.3 kV

Generator Transformer Data


Ratio 11/132 kV

Total Capcitance Per Phase


Micro-Farad
Gemerator 0.22 Typical
Micro-Farad
Generator Connections 0.001 Typical
Micro-Farad
Generator-Transformer 11 kV 0.006 Typical
Micro-Farad
11 kV Cable 100 m 0.0003 Typical
Micro-Farad
Surge Suppressor Capacitance 0.25 Typical
Micro-Farad
Total 0.4773 Typical
(3.C) Micro-
TOTAL RESIDUAL CAPACITANCE 1.4319 Farad

TOTAL RESIDUAL CAPACITIVE IMPEDANCE 2222.99 Ohm


(10^6 ) / (3.w.C)

Neutral Earthing Resistor


The Effective Resistance Should Be Made Equal To Residual Capacitive
Impedance (2222.99 Ohm calculated above) To Ensure TOV Is Controlled
Then Resistive Component Of EF 2.8569 A

The Actual Fault Current Will Contain Equal Resistive & Capacitive Components &
The Net EF Current Will Be Sqrt (Ir^2+Ic^2)
4.04026 A

46 of 70
SYSTEM NEUTRAL EARTHING

Generator High Resistance Earthing Transformer & NER Calculation

Neutral Earthing Distribution Transformer (Neutral ET or N ET) & NER Sizing


N ET
Transfo Primary Vk (Knee Point Voltage) 15.000 kV
Applied kV On N ET During EF 6.351 kV
Applied kV On N ET During EF With Field
Forcing 8.256 kV

Increase in Neutral EF Current 3.714 A

Maximum N ET Loading Under Above Condition 55.709 kVA

Considering 30 sec duty, the N ET Can Have 6 9.285 kVA


Times Short Term 30 Sec Overload Withstand
With kVA Considered Based On Maximun EF
Amp & Knee Point kV
10.000 kVA

N ET Secondary Rating
Consider Secondary Knee Point Of 240.000 V
Maximum Secondary Current 232.123 A

N ET Secondary Loading Resistor

Equivalent Neutral Primary Resistor 2222.99 Ohm

Actual Secondary Loading Resisor Based on 15 0.56909 Ohm


kV / 250 V N ET

N ET Secondary Amp 41.6667 A

Type N ET Cu Loss 310 Watt


Type N ET Resistance Due Cu Loss 0.17856 Ohm

Therefore N ET Secondary Loading Resistor


0.39053 Ohm
Rated N ET Secondary Resistor Ampere For 30 232.123 A (For 30 Sec)
Seconds
,(1.3*2.857*11000/240)

47 of 70
SYSTEM NEUTRAL EARTHING

Generator High Resistance Earthing Transformer & NER Calculation

Generator High Resistance Neutral Earthing Transformer Reactance


Calculation

Typical % X Of N ET 4 %
Typical X pu Of N ET 0.04 PU
N ET Rating (Base kVA) 10 kVA
N ET Rating (Base MVA) 0.01 MVA
Base kV 0.25 kV
X Base 6.25 Ohm
N ET X in Ohm 0.25 Ohm
N ET R in Ohm AS Calculated Above 0.17856 Ohm
(This Should
X/R Ratio Of N ET 1.40009 Not Exceed 2)

Summary Of Requirements
N ET Rating 10 kVA
N ET Ratio ,15000V/240V
N ET Secondary Loaded Resistor 0.39053 Ohm
N ET Secondary Loaded Resistor 30 Second A For 30
Current Rating 232.123 Second
N ET X/R Ratio 1.4 (Not > 2.)

48 of 70
SYSTEM NEUTRAL EARTHING

APPENDIX EXPALAINING NEUTRAL INVERSION OR FERRORESONANCE

49 of 70
SYSTEM NEUTRAL EARTHING

50 of 70
SYSTEM NEUTRAL EARTHING

APPENDIX FOR TYPICAL EARTHING TRANSFORMER SIZING

TYPICAL NGR CALCULATION METHODOLGY

51 of 70
SYSTEM NEUTRAL EARTHING

52 of 70
SYSTEM NEUTRAL EARTHING

53 of 70
SYSTEM NEUTRAL EARTHING

APPENDIX GIVING GUIDELINE FOR SIZING OF COMMON BUS


CONNECTED MEDIUM RESISTANCE EARTHING

1.0 CALCULATION OF MEDIUM RESISTANCE EARTHIMG

The selection of NER EF contribution should be such that the EF current


is as low as possible in the range between 50 A to 400 A for protecting
the large HV motor or generator from stator core melting damage. Lower
the figure the better in this respect.

Higher figure is better for EF relay operation.

One has to check with machine supplier if their supplied


motors/generators can tolerate the higher EF in 400 A range provided
protection is provided to clear the machine EF instantaneously.

In the main the EF current and EF relay setting should be selected to


ensure:-

• There is sufficient EF current to flow in the feeder (all outgoing and


incoming circuits) for satisfactory EF relay operation.

In this respect the EF relay current setting should be of the order of 10


to 30 % (lower the better as it gives better % winding EF coverage) of
the EF current contributed through the respective circuit. That is EF
current to EF relay current pick up setting ratio is 3.33 to 5 or more.

• The minimum EF setting is not very sensitive to cause nuisance


tripping of healthy feeder due to system transients or capacitive
charging currents during fault on other feeders

The net capacitive charging current (3 ICO) is calculated from the zero
sequence capacitive charging current of surge suppressors,
transformers (usually very small), all cables and motors connected to
the system at which point the NER sizing needs to be carried out)-
For calculation of 3 ICO , see Appendix attached here, which is based
on references included in typical NER Vendor catalogues.

2.0 CALCULATION OF NER CURRENT WITH CHECK ON CT


REQUIREMENTS FOR SATISFACTORY EF RELAY OPERATION
WITHOUT HEALTHY CIRCUIT NUISANCE TRIPPING

2.1. Work out Minimum EF current through incomer and through


outgoing circuit.

Minimum EF is based on expected worst generation or minimum


source circuit configuration. One has to arrive at a credible
minimum source configuration and not be unrealistically
pessimistic.

Say this is Iefc_min

54 of 70
SYSTEM NEUTRAL EARTHING

2.2. Work out the system capacitance charging current

This is based on capacitance of connected cable, generator,


surge suppressor, motor, transformer winding and inter winding
capacitance. Say this is Isys_cap.

2.3. Work out Minimum EF Relay Current Pick up Setting

Multiply Isys_cap. by 1.5 for safe margin to work out minimum EF


current setting that one should consider in any of the incoming or
outgoing feeder. Prefer one sets it higher than 1.5 x Isys_cap.

Say minimum EF is worked out as Imin-ef-setg > or = 1.5 x


Isys_cap.

For proper operation of relay, the relay EF current pick up setting


should be > 10 to 30 % of the minimum EF current expected to
flow through the relay (this will be different in the incomer source
switchgear CT and will be total EF current in the outgoing circuit).

This means Imin-ef-setg > 0.1 to 0.3 x Iefc_min

Or Iefc_min > Imin-ef-setg / 0.3 or Imin-ef-setg / 0.1

Or Iefc_min > 3.33 to 10 x Imin-ef-setg ;


say. 5.00 x Imin-ef-setg as an average

2.4. Work out Optimum EF Current Contribution

For better margin SELECT a SCHEME where minimum EF


Current follows the equation below:-

Iefc_min > 5.00 x Imin-ef-setg > 5 x 1.5 x Isys_cap.

This is to be tested for each incomer and outgoing

THE NER sizing based on fault contribution required for


satisfactory EF relay operation should be based on the above.

2.5. Check On CT Primary Current Suitability & Decide Need For


CBCT

The CT primary current for such a scheme should be such that the
relay can be set at 10 % to 20 % current setting in terms of CT
current.

Most relays will have minimum 10 % EF setting, new relays have


lower setting.

55 of 70
SYSTEM NEUTRAL EARTHING

For 10 % EF current setting available in most relays the maximum


CT primary current allowed can be worked out as

Ict_prim x 0.10 should be less than between 10 to 30 % of the


minimum EF current i.e , 0.1 to 0.3x Iefc_min

Work out CT primary current above which CBCT is a must to a


achieve desired setting and sensitivity.

3.0 EXAMPLE

• From Step 2.2 Find Isys_cap

Let us take a 6.6 kV system for which this guide is initiated where system
capacity is of the order of 30 MVA capacity.
o 1 A / km of all cables at 6.6 kV. Say 20 cables average 100 m i.e 2
km. Works out to be 2 A of charging current for 6.6 kV cables
o 2 A per generator surge capacitor. Works out to be 8 A of
charging current for 4 direct generators
o Direct connected Motor/Generator capacitance charging Amp =
0.05 * HP/RPM. For 15000 HP at average 1500 RPM, This works
out to be 0.05*15000/1500 = 0.5 A of charging current for 6.6 kV
motors
o Transformer capacitance charging Amp = 0.1 per transformer. For
15 transformer this works out to be 15*0.1 = 1.5 A of charging
current for 6.6 kV transformers

The total works out to be (2+8+0.5+1.5) = 12 A

The system capacity is 30 MVA So This Works Out To Be 0.5 A per 1.0
MVA as the system capacitive charging current. The net capacitive
charging current would then be 0.5 x 30 = 15 A (actually this should be
worked out byt adding all cable lengths and transformers etc).

This 15 A was worked out just for this example.


So Isys_cap. = 15 A

• From Step 2.3 Find Imin-ef-setg

Imin-ef-setg > 1.5 x Isys_cap. > 1.5*15 > 22.5 A

Say Imin-ef-setg = 25 A.

• From Step 2.4 Find Iefc_min

Iefc_min > 5.00 x Imin-ef-setg > 5 x 1.5 x Isys_cap.


Iefc_min > 5.00 x 25 A > 125 A. say 125 A to 150a

So select NER with this contribution say 125 A in this case

56 of 70
SYSTEM NEUTRAL EARTHING

• From Step 2.5 Find Ict_prim To Check CBCT requirement

Assuming Relay Can Be Set At 10 % (i.e < 20 % ) EF current pick up


setting. The Requirement is:-
o Ict_prim x 0.10 < 20 to 30 % of the minimum EF current of
Iefc_min

Ict_prim_max < 0.3* Iefc_min / 0.10 < 0.3*125/0.1 < 375 A

If Ict_prim_max < 0.2* Iefc_min / 0.10 < 0.2*125/0.1 < 250 A

CT ratio should not be > 375 A assuming lowest EF relay sensitivity is OK


and assuming relay has a 10 % setting available in its range.

Where ever circuit CT ratio exceeds above in this particular case, one
needs to use Core balance CT with either 50 or 100 or whatever as
primary CBCT Ampere

For Circuits with CT primary > 375 A In The Case Being Studied, Let us
Take A CBCT of 50 A. Then EF Setting > Imin-ef-setg > 1.5 x Isys_cap.
> 1.5*15 > 22.5 A = 25 A

With 50 A CBCT. EF setting should be 50 % to ensure setting is greater


than 25 A.

With 50 % setting the current setting is 25 A. The EF current is 125 A.

The Ratio of EFC to EF setting = 125/25 = 5 times (Which is OK)

If a CBCT of 100 A is selected then above equation is something like


this given below

For Circuits with CT primary > 375 A In The Case Being Studies, Let us
Take A CBCT of 100 A. Then EF Setting > Imin-ef-setg > 1.5 x Isys_cap.
> 1.5*15 > 22.5 A = 25 A

With 100 A CBCT. EF setting should be 25 % to ensure setting is greater


than 25 A.

With 25 % setting the current setting is 25 A. The EF current is 125 A.

The Ratio of EFC to EF setting = 125/25 = 5 times (Which is OK)

57 of 70
SYSTEM NEUTRAL EARTHING

4.0 EXAMPLE-NER SIZING

Let in this case a bus earthing transformer be considered

Say 6.6kV/110 V transformer be seleted with resistor in broken delta


which offers a techno-economically cost effective option.

NER is calculated here as follows:-

o Earthing Transformer (ET) voltage ratio = 6600/110 =60


o For EF current of 125 A, ET primary phase current =125/3=41.67
A
o The ET secondary current for above will be 41.67*60 =2500 A.
o The Voltage across the resistor =√3 x sec voltage = =√3 x 110 =
190.53 V
o Required NER ohm on broken delta will be 190.53/2500 = 0.076
Ohm

NER current rating will be high.

Alternative is to use Star-Closed Delta transformer with 6.6 kV neutral


connected NER of size = 6600/1.732/125 =30.4 Ohm

The NER should have 10 sec withstand rating at 125 A current, but
should have continuous rating for less than its relay setting current which
in this case is 20 % of he 125 A NER rating (i.e continuoua rating of 30 A
or so).

58 of 70
SYSTEM NEUTRAL EARTHING

59 of 70
SYSTEM NEUTRAL EARTHING

60 of 70
SYSTEM NEUTRAL EARTHING

61 of 70
SYSTEM NEUTRAL EARTHING

62 of 70
SYSTEM NEUTRAL EARTHING

63 of 70
SYSTEM NEUTRAL EARTHING

64 of 70
SYSTEM NEUTRAL EARTHING

APPENDIX GIVING RULE OF THUMB CALCULATION OF SYSTEM


CAPACITIVE CHARGING CURRENT

65 of 70
SYSTEM NEUTRAL EARTHING

66 of 70
SYSTEM NEUTRAL EARTHING

67 of 70
SYSTEM NEUTRAL EARTHING

68 of 70
SYSTEM NEUTRAL EARTHING

69 of 70
SYSTEM NEUTRAL EARTHING

70 of 70