Ducted INDOOR UNIT


Engineering Manual

High Static Ducted Low Static Ducted


7,500 to 95,900 Btu/h 7,500 to 24,000 Btu/h

Low Static Built In Ducted


7,500 to 24,200 Btu/h
Vertical / Horizontal Air Handler
12,000 to 54,000 Btu/h
Proprietary Data Notice
This document, as well as all reports, illustrations, data, information,
and other materials are the property of LG Electronics U.S.A., Inc., and are
disclosed by LG Electronics U.S.A., Inc. only in confidence.
This document is for design purposes only.

A summary list of safety precautions is on page 3.

For more technical materials such as submittals, catalogs, installation,


owner’s, and service manuals, visit www.lghvac.com.

For continual product development, LG Electronics U.S.A., Inc. reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc.
Table of Contents

Unit Nomenclature.................................................................................. 4 Vertical / Horizontal Air Handler Units......................................... 93-116


Mechanical Specifications............................................................. 94-95
Indoor Unit Overview............................................................................. 5 General Data................................................................................. 96-97
Electrical Data.................................................................................... 98
Controllers Overview............................................................................. 8
External Dimensions.................................................................... 99-100
LATS Overview..................................................................................... 14 Electrical Wiring Diagrams........................................................ 101-102
Refrigerant Flow Diagrams............................................................... 103
High Static Ducted Indoor Units.................................................... 15-52 External Static Pressure and Air Flow.............................................. 104
Mechanical Specifications.................................................................. 16 External Static Pressure Ranges...................................................... 105
General Data................................................................................. 17-19 Heater Capacity Airflow / Static Pressure Drop Factors ������������������ 106
Electrical Data.................................................................................... 19 Acoustic Data............................................................................ 107-110
External Dimensions...................................................................... 21-23 Capacity Tables.......................................................................... 111-115
Electrical Wiring Diagrams............................................................ 24-29 Optional Accessories.........................................................................116
Refrigerant Flow Diagrams............................................................ 30-31
External Static Pressure and Air Flow........................................... 32-33 Application Guidelines................................................................ 117-128
External Static Pressure Ranges................................................... 34-35 Selecting the Best Location........................................................118-119
Acoustic Data................................................................................ 36-41 General Mounting...................................................................... 120-123
Capacity Tables............................................................................. 42-50 General Drain Piping Information.............................................. 124-125
Optional Accessories.......................................................................... 51 Wiring Guidelines...................................................................... 126-127
Wired Remote Controller Location................................................... 128

Introduction
Low Static Ducted Indoor Units..................................................... 53-72
Mechanical Specifications.................................................................. 54 Acronyms............................................................................................ 129
General Data...................................................................................... 55
Electrical Data.................................................................................... 56
External Dimensions........................................................................... 57
Electrical Wiring Diagrams............................................................ 58-61
Refrigerant Flow Diagrams................................................................. 62
External Static Pressure and Air Flow........................................... 63-64
External Static Pressure Ranges........................................................ 65
Acoustic Data..................................................................................... 66
Capacity Tables............................................................................. 69-72

Built In Indoor Units........................................................................ 73-92


Mechanical Specifications.................................................................. 74
General Data...................................................................................... 75
Electrical Data.................................................................................... 76
External Dimensions........................................................................... 77
Electrical Wiring Diagrams............................................................ 78-79
Refrigerant Flow Diagrams................................................................. 80
External Static Pressure and Air Flow........................................... 81-82
External Static Pressure Ranges........................................................ 83
Acoustic Data................................................................................ 84-86
Capacity Tables............................................................................. 87-90
Optional Accessories.......................................................................... 91

TABLE OF sYMBOLS
DANGER This symbol indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
This symbol indicates situations that may result in equipment or property damage accidents only.
This symbol indicates an action should not be completed.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 3
unit nomenclature

ARN U 07 3 TN C 4
Family
ARN = Multi V Indoor Unit
(Refrigerant R410A)

Type
U = DC Inverter Heat Pump
MULTI V Ducted Indoor Unit Engineering Manual

Indoor Unit Nominal Capacity


05 = 5,000 Btu/h 18 = 18,000 Btu/h 42 = 42,000 Btu/h
07 = 7,000 Btu/h 24 = 24,000 Btu/h 48 = 48,000 Btu/h
09 = 9,000 Btu/h 28 = 28,000 Btu/h 54 = 54,000 Btu/h
12 = 12,000 Btu/h 30 = 30,000 Btu/h 76 = 76,000 Btu/h
15 = 15,000 Btu/h 36 = 36,000 Btu/h 96 = 96,000 Btu/h

Electrical Ratings
3 = 208–230V/60Hz/1Ph

Model
B3 = Ducted (low static - bottom return) NJ = Vertical/Horizontal Air Handling Unit TN = 4-Way Ceiling Cassette
B4 = Ducted (low static - bottom return) NK = Vertical/Horizontal Air Handling Unit TP = 4-Way Ceiling Cassette
B8 = Ducted (high static) S8 = Wall Mounted/Mirror (large frame) TQ = 4-Way Ceiling Cassette
BG = Ducted (high static) SE = Wall Mounted/Mirror (small frame) TR = 4-Way Ceiling Cassette
BR = Ducted (high static) SB = Standard Wall Mounted VE = Convertible Surface Mounted
CE = Floor Standing (small frame) SC = Standard Wall Mounted VJ = Ceiling Suspended
CF = Floor Standing (large frame) TT = 1-Way Ceiling Cassette
L1 = Ducted (low static) TU = 1-Way Ceiling Cassette
L2 = Ducted (low static) TL = 2-Way Ceiling Cassette
L3 = Ducted (low static) TM = 4-Way Ceiling Cassette

Feature
A = Basic L = Neo Plasma
C = Plasma Filter R = Mirror and Neo Plasma
G = Low Static U = Uncased

Generation
2 = Second
4 = Fourth
A = Second, Revision A

Due to our policy of continuous product innovation, some specifications may change without notification.
4 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Indoor Unit Overview
Wall-Mounted / Ceiling Cassette

Table 1: Wall-Mounted / Ceiling Cassette Indoor Units.


Nominal Capacity Pipe
Dimensions Air Flow Rate
Btu/h Weight Connections
Unit/Type 1
ARNU***** 2
(W x D x H) (CFM) (lbs.) (inches, O.D.)
(inches) Cooling3 Heating3 (H/M/L4) (Liquid, Vapor)
Wall Mounted–ART COOLTM 073 SER2 7,500 8,500 247/212/141
Mirror 093 SER2 9,600 10,900 282/247/177
36-1/16 x 6-1/2 x 11-1/8 25
123 SER2 12,300 13,600 353/283/212 1/4, 1/2
153 SER2 15,400 17,100 371/283/212
183 S8R2 19,100 21,500 508/459/388
43-9/16 x 7-7/8 x 11-13/16 34
243 S8R2 24,200 27,300 632/508/424 3/8, 5/8
Wall Mounted–Standard 053 SBL4 5,500 6,100 1,120/1,080/1,050
073 SBL4 7,500 8,500 1,190/1,120/1,050
093 SBL4 35-1/4 x 8-15/16 x 11-7/16 9,600 10,900 1,260/1,190/1,050 22
1/4, 1/2
123 SBL4 12,300 13,600 1,420/1,260/1,120
153 SBL4 15,400 17,100 1,550/1,350/1,190
183 SCL4 19,100 21,500 1,120/1,050/980
40-5/16 x 9-7/8 x 12-13/16 31
243 SCL4 24,200 27,300 1,280/1,140/1,000 3/8, 5/8
Ceiling Cassette–One Way 073 TUC4 7,500 8,500 290/258/226
Body: 33-7/8 x 17-3/4 x 6-11/16 Body: 33
093 TUC4 9,600 10,900 325/304/290
Panel: 43-5/16 x 19-3/4 x 1-3/8 Panel: 10 1/4, 1/2

Introduction
123 TUC4 12,300 13,600 353/325/290
183 TTC4 Body: 46-1/2 x 17-3/4 x 6-7/8 19,100 21,500 470/427/385 Body: 42
243 TTC4 Panel: 55-15/16 x 19-3/4 x 1-3/8 24,200 24,200 515/470/406 Panel: 13 3/8, 5/8
Ceiling Cassette–Two Way
183 TLC4 19,100 21,500 459/424/353 1/4, 1/2
Body: 32-11/16 x 21-5/8 x 8-7/8 Body: 49
Panel: 41-5/16 x 25-3/16 x 1-5/8 Panel: 11
243 TLC4 24,200 27,300 601/530/459 3/8, 5/8

Ceiling Cassette–Four Way 053 TRC4 5,500 6,100 265/247/212 Body: 29


(2' x 2') 073 TRC4 Body: 22-7/16 x 22-7/16 x 8-7/16 7,500 8,500 265/247/212 Panel: 7
093 TRC4 Panel: 27-9/16 x 27-9/16 x 7/8 9,600 10,900 283/265/251 Body: 32
1/4, 1/2
123 TRC4 12,300 13,600 307/283/247 Panel: 7
153 TQC4 Body: 22-7/16 x 22-7/16 x 10-3/32 15,400 17,100 388/353/328 Body: 35
183 TQC4 Panel: 27-9/16 x 27-9/16 x 7/8 19,100 21,500 396/388/353 Panel: 7
Ceiling Cassette–Four Way
(3' x 3') 243 TPC4 24,200 27,300 600/530/459
Body: 33-1/16 x 33-1/16 x 8 Body: 48
Panel: 37-3/8 x 37-3/8 x 1-7/16 Panel: 13
283 TPC4 28,000 31,500 671/565/494
Body: 33-1/16 x 33-1/16 x 9-5/8 Body: 54
363 TNC4 36,200 40,600 883/777/706 3/8, 5/8
Panel: 37-3/8 x 37-3/8 x 1-7/16 Panel: 13
423 TMC4 42,000 43,800 1,059/918/812
Body: 33-1/16 x 33-1/16 x 11-5/16 Body: 59
Panel: 37-3/8 x 37-3/8 x 1-7/16 Panel: 13
483 TMC4 48,100 51,200 1,130/953/883
1
All indoor units require 208–230V/60Hz/1Ph and an AWG18-2 communication cable. Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60°
2
Model number shows nominal capacity and frame size designator. F wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
3
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 4
H/M/L = High/Medium/Low
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 5
Indoor Unit Overview
Ducted

Table 2: Ducted Indoor Units.


Nominal Capacity Pipe
Dimensions Air Flow Rate Max.
Btu/h Weight Connections
Unit/Type 1
ARNU***** 2
(W x D x H) (CFM) ESP
(lbs.) (inches, O.D.) (inches)
(inches) Cooling3 Heating3 (H/M/L4) (Liquid, Vapor)
Ducted High Static 073 BGA4 7,500 8,500 441 / 406 / 332
093 BGA4 9,600 10,900 452 / 406 / 332
123 BGA4 12,300 13,600 477 / 427 / 332
153 BGA4 15,400 17,100 487 / 417 / 293
183 BGA4 46-1/2 x 17-3/4 x 11-3/4 19,100 21,500 537/487/417 84 0.62
MULTI V Ducted Indoor Unit Engineering Manual

243 BGA4 24,200 27,300 671/537/487 3/8, 5/8


283 BGA4 28,000 31,500 1,130/1,003/961
363 BGA4 36,200 40,600 1,003/894/770
423 BGA4 42,000 43,800 893/770/622
483 BRA4 48,100 51,200 1,568/1,395/1,183
48-7/16 x 23-3/8 x 15 112 0.78
543 BRA4 54,000 61,400 1,819/1,678/1,395
763 B8A4 76,400 86,000 2,050/1,766/1,766 3/8, 3/4
61-1/2 x 27-1/8 x 18-1/8 192 0.98
963 B8A4 95,900 107,500 2,542/2,260/2,260 3/8, 7/8
Ducted Low Static 073 L1G4 7,500 8,500 270/230/200
27-9/16 x 27-9/16 x 7-1/2 39
093 L1G4 9,600 10,900 320/250/200
123 L2G4 12,300 13,600 360/310/250 1/4, 1/2
0.19
153 L2G4 35-7/16 x 27-9/16 x 7-1/2 15,400 17,100 450/360/310 51
183 L2G4 19,100 21,500 530/450/360
243 L3G4 43-5/16 x 27-9/16 x 7-1/2 24,000 27,300 710/570/430 60 3/8. 5/8
Ducted Low Static - 073 B3G4 7,500 8,500 283/229/194
Built In
093 B3G4 9,600 10,900 318/247/212
32-5/8 x 22-5/8 x 7-1/2 46
123 B3G4 12,300 13,600 353/283/229 1/4, 1/2
0.15
153 B3G4 15,400 17,100 388/353/283
183 B4G4 19,100 21,500 494/424/353
43-5/16 x 22-5/8 x 7-1/2 57
243 B4G4 24,200 27,300 600/530/353 3/8, 5/8
Vertical/Horizontal Air 123 NJA4 12,000 13,500 530/480/380
Handling Unit 1/4, 1/2
183 NJA4 18,000 20,000 580/530/480
117
243 NJA4 18 x 21-1/4 x 48-11/16 24,000 27,000 710/640/480
303 NJA4 30,000 34,000 880/800/630
1.0
363 NJA4 36,000 40,000 990/880/800 121
3/8, 5/8
423 NKA4 42,000 46,000 1,250/1,100/1,000
483 NKA4 25 x 21-1/4 x 55-3/16 48,000 54,000 1,400/1,260/1,000 165
543 NKA4 54,000 60,000 1,475/1,400/1,260
1
All indoor units require 208–230V/60Hz/1Ph and an AWG18-2 communication cable. Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60°
2
Model number shows nominal capacity and frame size designator. F wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
3
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 4
H/M/L = High/Medium/Low
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).

Due to our policy of continuous product innovation, some specifications may change without notification.
6 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Indoor Unit Overview
Surface Mounted / Floor Standing

Table 3: Surface Mounted / Floor Standing Indoor Units.


Nominal Capacity
Btu/h Air Flow Pipe
Dimensions Rate Weight Connections
Unit/Type 1
ARNU**** 2
(W x D x H) (CFM) (lbs.) (inches, O.D.)
(inches) Cooling3 Heating3 (H/M/L4) (Liquid, Vapor)

Ceiling Suspended
183VJA2 19,100 21,500 565/495/424 1/4, 1/2
37-7/16 x 8-11/16 x 25-5/8 55
243VJA2 24,200 27,300 636/565/495 3/8, 5/8

Convertible Surface Mounted


093VEA2 9,600 10,900 268/243/219

35-7/16 x 7-7/8 x 19-5/16 31 1/4, 1/2


123VEA2 12,300 13,600 325/268/244

Floor Standing –Cased


073 CEA4 7,500 8,500 300/265/229

Introduction
093 CEA4 9,600 10,900 335/300/265
42 x 8 x 25 60
123 CEA4 12,300 13,600 371/335/300 1/4, 1/2

153 CEA4 15,400 17,100 406/353/335

183 CFA4 19,100 21,500 565/494/424


52-15/16 x 8 x 25 75
243 CFA4 24,200 27,300 635/565/494 3/8, 5/8

Floor Standing – Uncased


073 CEU4 7,500 8,500 300/265/229

093 CEU4 9,600 10,900 335/300/265


38-1/2 x 7-15/16 x 25-3/16 46
123 CEU4 12,300 13,600 371/335/300 1/4, 1/2

153 CEU4 15,400 17,100 406/353/335

183 CFU4 19,100 21,500 565/494/424


49-7/16 x 7-1/2 x 25-3/16 58
243 CFU4 24,200 27,300 635/565/494 3/8, 5/8
1
All indoor units require 208–230V/60Hz/1Ph and an AWG18-2 communication cable. Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60°
2
Model number shows nominal capacity and frame size designator. F wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
3
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 4
H/M/L = High/Medium/Low
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 7
Controllers Overview
Zone Controllers and Communication Cables

Table 4: Zone Controllers.


Max Wire
Zone Controller Name Model No. Case Color Length Description
(ft)

PQRCVCL0Q Black
Simple Controller with Allows control of indoor unit on/off, operation mode, fan speed,
164
mode selection and temperature setpoint for up to 16 indoor units.
PQRCVCL0QW White

PQRCHCA0Q Black
Simple Controller Allows control of indoor unit on/off, fan speed, and temperature
164
MULTI V Ducted Indoor Unit Engineering Manual

without mode selection setpoint for up to 16 indoor units.


PQRCHCA0QW White
Allows control of indoor unit on/off, operation mode, occupied/
unoccupied temperature setpoints, fan speed, and air flow
direction for up to 16 indoor units. Programmable schedule with 5
LG Premium events per day with control of occupied/unoccupied, on/off,
PREMTA000 Ivory 164
Controller mode, setpoints and fan speed. Advanced functions include
two setpoint autochangeover, minimum difference between
setpoints, setback, timed override, target energy consumption
display, check energy display and master/slave.
Allows control of indoor unit on/off, operation mode, occupied
and unoccupied temperature setpoints, fan speed, and airflow
direction for up to 16 indoor units. Programmable schedule with
LG Programmable
PREMTB10U White 164 5 events per day with control of occupied unoccupied, on/off,
Thermostat
mode, setpoints and fan speed. Advanced functions include two
setpoint autochangeover, minimum difference between setpoints,
setback and timed override.

Allows control of indoor unit on/off, operation mode, fan speed,


Wireless Handheld PQWRHQ0FDB Ivory ----
and temperature setpoint.

Wall-Mounted Remote Allows remote temperature measurement for cassette and


PQRSTA0 Ivory 50
Temperature Sensor ducted units.

Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Tables on pages 12 and 13.

Table 5: Zone Controller Communication Cables.


Communication Cable Name Model No. Wire Length (ft.) Description

Wired Remote Group Required when grouping multiple indoor units with a single
PZCWRCG3 33
Control Cable Assembly zone controller.

Wired Remote/Group Control Increases the distance between a remote controller and an
PZCWRC1 33
Extension Cable indoor unit or between indoor units in a control group.
Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Tables on pages 12 and 13.
Due to our policy of continuous product innovation, some specifications may change without notification.
8 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Controllers Overview
Specialty Application Devices

Table 6: Specialty Application Devices.


Binary
Specialty Application Connect Signals
Name Model No. Application Description
Device to Input/
Output
On/Off, Run Status,
Simple Dry Contact PQDSB1 1/2
Error Status Enables the indoor unit to be
On/Off, Mode, controlled and monitored by third
Dry Contact for
Controller Lock, Power party controls using binary inputs
Economizer, occupied/ PQDSBC1 2/2
Indoor Save, Run Status, and outputs.
unoccupied
Unit Error Status
On/Off, Thermo On/
Enables the indoor unit to be
Dry Contact Unit for Off, Mode, Fan Speed,
PDRYCB300 --- controlled and monitored by a third
24V Thermostat Run Status, Error
party thermostat or controller.
Status
One 25A DPST normally open relay.
Digital Output Comm Used with central controller to control
PQNFP00T0 On/Off 0/1
(DO) Kit Bus third party device manually or by
schedule.
3 Digital Inputs: Dry Contact input only

Introduction
3 Digital Outputs: Max. 2A@30VAC/DC
Third party equipment 4 Analog Outputs: 0 to 10 VDC,
AC
control. Allows system configurable; 0 to 20 mA, configurable
PEXPMB000. Smart IV
I/O Module expansion through --- 4 Universal Inputs individually
ENCXLUS and
Digital and Analog configurable as analog or digital:
ACP IV
inputs and outputs. Analog: Voltage. Current. Thermistor
(NTC, PT, Ni)
Digital for Dry Contact input only
PRARH0 Third party Adds coordinated control of an
Auxiliary Heater Indoor
supplemental heat 0/1 external heater with normal heat
Relay Kit Unit
PRARS0 control pump operations.

Third party Adds coordinated control of an


Auxiliary Two-Stage Indoor
PRARH1 supplemental heat 0/2 external heater with normal heat
Heater Relay Kit Unit
control pump operations.

Monitors total outdoor unit power


Power Distribution Energy 8 Watt
Comm consumption for up to eight systems,
Indicator (PDI) PQNUD1S41 consumption Node
Bus and distributes per indoor unit based
Premium monitoring Meters
on weighted calculation.

Outdoor Multi V Heat Locks outdoor unit into Heat,


Mode Selector Switch PRDSBM ---
Unit Pump Only Cool, or Fan Mode.

Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Tables on pages 12 and 13.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 9
Controllers Overview
Central Controllers

Table 7: Central Controllers (connect to the outdoor unit terminals Internet A, Internet B).
No. of Binary
Devices Systems Devices Comm
Central per Comm per Comm Bus Signals Power,
Name Model No. per Description
Controller Input/ Conn
Controller Bus Bus Ports Output
Monitors / operates indoor units
through a touch screen. Manages
up to 128 devices. Advanced
functions include programmable
schedules, temperature setpoint
range lock, remote controller lock,
PACS4B000. 2 DI / run time limit, manual control and
MULTI V Ducted Indoor Unit Engineering Manual

AC Smart IV 128 16 128 1 24 VAC


ENCXLUS 2 DO scheduling of digital output kit,
peak/demand control, visual floor
plan navigation, web access,
operation and error history log, one
digital input and two digital outputs
for device interlocking and error
e-mail notification.

Provides for scheduling in addition


12 VDC,
AC Ez PQCSZ250S0 32 16 256 1 --- to basic indoor unit control and
ODU
monitoring.

Provides for scheduling, remote


Advanced controller lock, setpoint range limit,
Control web access, peak/demand control,
PACP4B000.
Platform IV 256 16 64 4 10/4 24 VAC PDI integration, and AC Manager
ENCXLUS
(ACP IV) Plus integration advanced
functionality in addition to basic unit
control and monitoring.
Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Tables on pages 12 and 13.

Due to our policy of continuous product innovation, some specifications may change without notification.
10 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Controllers Overview
Integration Solutions

Table 8: Summary Data—Integration Solutions (connect to outdoor unit terminals Internet A, Internet B).
Devices Systems No. of Binary
Devices Comm
Integration per Signals
Name Model No. per per Comm Power Description
Solution Controller Comm Bus Input/
Bus
Bus Ports Output
ACP IV
BACnet® PQNFB17C1 256 16 256 4 24 VAC 10/4 Allow integration of LG equipment
Gateway for control and monitoring by open
protocol BACnet® and LonWorks®
building automation and controls
LonWorks®
PLNWKB100 64 16 64 1 24 VAC 2/2 systems.*
Gateway

Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Tables on pages 12 and 13.
* BACnetTM is a trademark of ASHRAE; LonWorksTM is a trademark of Echlelon Corporation.

Introduction

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 11
Controllers Overview
Options and Features

Table 9: Options and Features.

Wall Wall Mounted—


Mounted— 1-Way 2-Way Ducted High Ducted Low
Feature ART COOL™ 4-Way Cassette
Standard Cassette Cassette Static Static
Mirror
Finish

Nominal Chassis Size (MBh) 5–24 7–24 7–24 18–24 5–18 24–48 7–96 7–24
Air supply outlets 1 1 1 2 4 4 1 1
Airflow direction (left/right) manual auto
Auto airflow direction (up/down) √ √ √ √ √ √
Fan speed (Heating mode) 3 3 4 4 4 4 3 3
MULTI V Ducted Indoor Unit Engineering Manual

Airflow

Fan speed (Cooling mode) 4 4 5 5 5 5 3 3


Fan speed (fan mode) 3 3 4 4 4 4 3 3
Chaos swing (random louver √ √
swing)
Chaos wind (random fan speed) √ √ √ √ √ √
Jet-cool (power cooling) √ √ √ √ √ √
E.S.P. control √ √ √ √ √ √
High ceiling √ √ √ √
Auto-restart after power restore √ √ √ √ √ √ √ √
Hot start √ √ √ √ √ √ √ √
Diagnostics √ √ √ √ √ √ √ √
Auto changeover1 √ √ √ √ √ √ √ √
Auto operation6 √ √ √ √ √ √ √ √
Auto clean (coil dry) √ √
Child lock √ √ √ √ √ √ √ √
Dual thermistor control √ √ √ √ √ √ √ √
Operation

Dual set-point control √ √ √ √ √ √ √ √


Filter life display √ √ √ √ √ √ √ √
Power consumption display √ √ √ √ √ √ √ √
(with PDI)
Forced operation √ √ √ √ √ √
Group control – Requires the
use of one Group control cable √ √ √ √ √ √ √ √
kit (PZCWRCG3) for every
additional indoor unit
Timer (on/off) √ √ √ √ √ √ √ √
Weekly schedule √ √ √ √ √ √ √ √
Test operation mode √ √ √ √ √ √ √ √
Plasma3 √ √ √ √ √ √
Controllers Filter

Washable anti-fungal2 √ √ √ √ √ √ √ √
7-day programmable controller o o o o o o o o
Simple controller w/mode o o o o o o o o
Simple controller w/o mode o o o o o o o o
Wireless controller o o o o o o o4 o4
Condensate lift √ √ √ √ √ √
Ventilation air √ √5 √5 √ √
Casing √ √ √ √ √ √
Others

Standard grille √ √ √ √
Auto elevation grille o
Suction grille
Suction canvas
Aux. heat kit
1
For Heat Recovery systems only. √ = Standard feature
2
Primary washable filters. o = Unit option
3
Secondary plasma filters.
4
Requires 7-day programmable zone controller.
5
Requires ventilation kit PTVK430 or PTVK410+PTVK420 (For TP, TN, TM frames)(Temperature, humidity, and volume limitations apply).
6
Heat Pump systems only.

Due to our policy of continuous product innovation, some specifications may change without notification.
12 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Controllers Overview
Options and Features

Table 10: Options and Features, continued.

Ducted Low Convertible Floor Mount— Floor Mount—


Vert.-Horiz. Vert.-Horiz. Ceiling
Feature Static— Surface
AHU (NJ) AHU (NK) Suspended Cased Uncased
Bottom Return Mount

Nominal Chassis Size (MBh) 7–24 12-36 42-53 18–24 9–12 7–24 7–24
Air supply outlets 1 1 1 1 1 1 1
Airflow direction (left/right) manual manual
Auto airflow direction (up/down) √ √
Fan speed (Heating mode) 3 3 3 3 3 3 3
Airflow

Fan speed (Cooling mode) 3 3 3 4 4 3 3


Fan speed (fan mode) 3 3 3 3 3 3 3
Chaos swing (random louver
swing)
Chaos wind (random fan speed) √ √
Jet-cool (power cooling) √ √
E.S.P. control √ √ √
Auto-restart after power restore √ √ √ √ √ √ √
Hot start √ √ √ √ √ √ √
Diagnostics √ √ √ √ √ √ √
Auto changeover1 √ √ √ √ √ √ √

Introduction
Auto operation6 √ √ √ √ √ √ √
Auto clean (coil dry)
Child lock √ √ √ √ √ √ √
Dual thermistor control √ √ √ √ √ √ √
Operation

Dual set-point control √ √ √ √ √ √ √


Filter life display √ √ √ √ √ √ √
Power consumption display √ √ √ √ √ √ √
(with PDI)
Forced operation √ √
Group control – Requires the
use of one Group control cable √ √ √ √ √ √ √
kit (PZCWRCG3) for every
additional indoor unit
Timer (on/off) √ √ √ √ √ √ √
Weekly schedule √ √ √ √ √ √ √
Test operation mode √ √ √ √ √ √ √
Plasma3 √ √
Controllers Filter

Washable anti-fungal2 √ √ √ √ √
7-day programmable controller o o o o o
Simple controller w/mode o o o o o o o
Simple controller w/o mode o o o o o o o
Wireless controller o4 o o o o o4 o4
Condensate lift √
Ventilation air √
Casing √ √ √
Others

Standard grille
Auto elevation grille
Suction grille o
Suction canvas o
Aux. heat kit √ √
1
For Heat Recovery systems only. √ = Standard feature
2
Primary washable filters. o = Unit option
3
Secondary plasma filters.
4
Requires 7-day programmable zone controller.
5
Requires ventilation kit PTVK430 or PTVK410+PTVK420 (For TP, TN, TM frames)(Temperature, humidity, and volume limitations apply).
6
Heat Pump systems only.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Introduction | 13
LATS Multi V Piping
Design Software

The proper design and installation of the refrigerant piping system


is a critical element of a Multi V system. Multi V Heat Pump systems
require two pipes between components – a liquid line and a vapor
line. Multi V Heat Recovery systems require three pipes between the
outdoor unit and the heat recovery unit – a liquid line, a low-pres-
sure vapor line, and a high-pressure vapor line. A properly designed
refrigerant piping system ensures that refrigerant is delivered to the
indoor unit coils for optimal system performance and capacity.

LG Air Conditioner Technical Solution (LATS) software is a total


design solution for LG Multi V air conditioning systems. This
MULTI V Ducted Indoor Unit Engineering Manual

Windows®-based application assists the design engineer with


specifying and sizing outdoor and indoor units (by calculating
component capacity based on design conditions), laying out the
refrigeration distribution pipe system, checking piping limitations,
calculating refrigerant charge, and generating equipment schedules
and piping diagrams in (.dxf) format for use on CAD building design
drawings.*
* Windows® is a registered mark of Microsoft® Corporation.

To ensure that the refrigerant piping design meets LG’s quality standards, a LATS refrigerant piping design must be provided with
every Multi V order. Following the installation, if any changes or variations to the design are necessary, a new LATS file must be
created and provided to LG prior to system commissioning to ensure the proper pipe size has not changed.

Design Choices
LATS Multi V software is flexible, offering the HVAC system engineer an easy to use Tree mode.

Tree Mode
Using the Tree mode, the engineer can quickly create a one-line schematic drawing of a Multi V system. Integration of the engineered pipe
system into the building drawings is done at a later date by the draftsperson using standard drafting software tools.

• Import building loads from an external file (.xls format).


• System components selected using an easy drag and drop process. Figure 1: Screenshot of LATS Pipe System Design Tool in Tree Mode.
• Automatically analyzes and checks the design complies with most
piping design limitations.
• Sizes refrigerant piping.
• Generates a system engineering report (.xls format).
• Generates an equipment schedule (.xls or .dxf format).
• Generates a system piping diagram (.dxf format).

LATS Report
LATS Multi V software generates a report file (.xls format) containing
project design parameters, cooling and heating design day system
component performance, and capacity data. The report calculates
the system combination ratio, calculates the system refrigerant
charge, and provides detailed bill of material information including a
list of Multi V outdoor units, air handlers, control devices, accesso-
ries, refrigerant pipe sizes segregated by building, by system, by pipe
size, and by pipe segments.

Due to our policy of continuous product innovation, some specifications may change without notification.
14 | Introduction © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CEILING-CONCEALED
DUCTED
HIGH STATIC
Mechanical Specifications on page 16
General Data on page 17
Electrical Data on page 20
External Dimensions on page 21
Electrical Wiring Diagram on page 24
Refrigerant Flow Diagrams on page 30
External Static Pressure and Air Flow on page 32
External Static Pressure Ranges on page 34
Acoustic Data on page 36
Capacity Tables on page 42
Optional Accessories on page 51
DUCTED High Static
Mechanical Specifications

Casing In Heating mode,


The case is designed to mount concealed above a finished ceiling. the microprocessor
Fan supply air is front horizontal with a dedicated rear horizontal control will activate
return. The unit is manufactured with coated metal. Cold surfaces the indoor unit when
are covered with a coated polystyrene insulating material. The cold indoor room tem-
surface areas of the case are covered externally with sheet insula- perature falls below
tion made of Ethylene Propylene Diene Monomer (M-Class) (EPDM) setpoint temperature
conforming to ASTM Standard D-1418. The case is provided with and signals the
hanger brackets designed to support the unit weight on four corners. outdoor unit to begin heating cycle. The indoor unit fan operation is
Hanger brackets have pre-punched holes designed to accept field delayed until coil pipe temperature reaches 76ºF. Significant airflow
supplied, all-thread rod hangers. is generated when pipe temperature reaches 80°F. In lieu of factory
return air thermistor, screw terminals on the microprocessor circuit
Fan Assembly and Control board accommodate various models of wall-mounted local control-
MULTI V Ducted Indoor Unit Engineering Manual

The unit has Sirocco fans made of high strength ABS GP-2200 lers and/or a wall-mounted remote temperature sensor. The unit
polymeric resin. Fans are directly driven and mounted on a common microprocessor is capable of accepting space temperature readings
shaft. The fan motor is a Brushless Digitally-Controlled (BLDC) concurrently or individually from either:
design with permanently lubricated and sealed ball bearings. The 1. Wall-mounted wired controller(s)
fan motor includes thermal, overcurrent and low RPM protection. 2. Factory mounted return air thermistor or the optional wall-
The fan/motor assembly is mounted on vibration attenuating rubber mounted wired remote temperature sensor
grommets. The fan impeller is statically and dynamically balanced. A single indoor unit has the capability of being controlled by up to
The fan speed is controlled using a microprocessor based, direct two local wired controllers. The microprocessor controls space
digital control algorithm that provides a high fan speed in cooling temperature using the value provided by the temperature sensor
thermal ON and low fan speed in cooling thermal OFF, high fan sensing a space temperature that is farthest away from the tem-
speed in heating thermal ON and fan off in heating thermal OFF. The perature set-point. The microprocessor control provides a cooling or
fan speeds can be field adjusted between low, medium, and high heating mode test cycle that operates the unit for 18 minutes without
speeds and DIP switch settings will allow the fan to run constantly regard to the space temperature. If the system is provided with an
during defrost or oil return modes. Each setting can be field adjusted optional wall-mounted local or central controller, displayed diagnostic
from the factory setting (RPM / ESP) to compensate for additional codes are specific, alpha numeric, and provide the service technician
resistance to airflow caused by field connected ductwork or other with a reason for the code displayed.
airflow restricting devices.
Condensate Lift/Pump
Air Filter The indoor unit is provided with a factory installed and wired conden-
Return air is filtered with a removable, washable filter with antifungal sate lift/pump capable of providing a minimum 27.5 inch lift from the
treatment. MERV 13 filter modules with plenums available. bottom exterior surface of the unit casing. The unit drain pan is pro-
vided with a secondary drain port/plug allowing the pan to be drained
Microprocessor Controls for service. The lift pump comes with a safety switch that will shut off
The unit is provided with an integrated microprocessor-based con- indoor unit if condensate rises too high in the drain pan.
troller. The controller is capable of performing functions necessary
to operate the system without the use of a wall-mounted controller. Condensate Drain Pan
A temperature thermistor is factory-mounted in the return air stream. The condensate drain pan is constructed of HIPS (high impact poly-
All unit operation parameters, excluding the unit operating schedule, styrene resin).
are stored in non-volatile memory resident on the unit microproces-
sor. Operating schedules are stored in select models of the optional, Coil
wall-mounted, local, or central controller. The field supplied commu- The indoor unit coil is constructed with grooved design copper tubes
nication cable between the indoor unit(s) and outdoor unit is to be with slit coil fins, two (2) to three (3) rows, nineteen (19) to twen-
a minimum of 18 AWG, 2-conductor, stranded, and shielded cable ty-one (21) fins per inch.
(RS-485), terminated via screw terminals on the control boards.
The microprocessor control provides the following functions: auto Controls Features
addressing, self-diagnostics, auto restart following power restoration, • Auto changeover • Group control
test run, and will operate the indoor unit using one of five operating
modes: (Heat Recovery only) • External static pressure control
1. Auto Changeover (Heat Recovery only) • Auto operation • Hot start
2. Heating • Auto restart • Self diagnostics
3. Cooling • Child lock • Timer (on / off)
4. Dry • Dual thermistor control • Weekly schedule
5. Fan Only • Dual setpoint control • Fan speed control
For Heat Recovery systems the Auto Changeover setting automati- • Filter life and power consump- • Ventilation (outside air)
cally switches control of the indoor unit between cooling and heating tion display
modes based on space temperature conditions.
For Heat Pump systems, heated or cooled air delivery is dependent • Multiple auxiliary heater
upon outdoor unit operating mode. applications
Due to our policy of continuous product innovation, some specifications may change without notification.
16 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED HIGH STATIC
General Data
BG Units

Table 11: Ducted High Static (BG Frame) Indoor Unit General Data.
Model No. ARNU073BGA4 ARNU093BGA4 ARNU123BGA4 ARNU153BGA4 ARNU183BGA4
Cooling Mode Performance
Capacity (Btu/h) 7,500 9,600 12,300 15,400 19,100
Power Input1 (W) 450 450 450 450 450
Heating Mode Performance
Capacity (Btu/h) 8,500 10,900 13,600 17,100 21,500
Power Input (W) 1
450 450 450 450 450
Entering Mixed Air
Cooling Max. (°F WB) 76 76 76 76 76
Heating Min. (°F DB) 59 59 59 59 59
Unit Data
Refrigerant Type2 R410A R410A R410A R410A R410A
Refrigerant Control EEV EEV EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
35 / 35 / 34 35 / 35 / 34 36 / 35 / 34 37 / 36 / 33 41 / 39 / 37

Ducted High Static


Net Unit Weight (lbs.) 83.8 83.8 83.8 83.8 83.8
Shipping Weight (lbs.) 94.8 94.8 94.8 94.8 94.8
Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
Fan
Type Sirocco Sirocco Sirocco Sirocco Sirocco
Motor 1 1 1 1 1
Housing 2 2 2 2 2
Motor/Drive Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM) 516 / 484 / 434 533 / 484 / 434 586 / 533 / 484 477 / 427 / 318 547 / 470 / 427
Standard Mode
Airflow Rate H/M/L (CFM) 441 / 406 / 332 452 / 406 / 332 477 / 427 / 332 487 / 417 / 293 537 / 487 / 417
High Mode (Factory Set)
External Static Pressure (in. wg) 0.15 0.15 0.15 0.23 0.23
Standard Mode
External Static Pressure (in. wg) 0.23 0.23 0.23 0.31 0.31
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.) 3/8 Flare 3/8 Flare 3/8 Flare 3/8 Flare 3/8 Flare
Vapor Line (in., O.D.) 5/8 Flare 5/8 Flare 5/8 Flare 5/8 Flare 5/8 Flare
Condensate Line (in., I.D.) 1 1 1 1 1
EEV: Electronic Expansion Valve 1
Power Input is rated at high speed.
Power wiring is field supplied and must comply with the applicable local and national codes. 2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
This unit comes with a dry nitrogen charge. R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units. All capacities are net with a combination ratio between
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
95-105%. 4
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet with applicable and national code. Ensure the communication cable is properly grounded at the master
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB). outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor
ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 17
DUCTED HIGH STATIC
General Data
BG Units

Table 12: Ducted High Static (BG Frame) Indoor Unit General Data, continued.
Model No. ARNU243BGA4 ARNU283BGA4 ARNU363BGA4 ARNU423BGA4
Cooling Mode Performance
Capacity (Btu/h) 24,200 28,000 36,200 42,000
Power Input1 (W) 450 450 450 450
Heating Mode Performance
Capacity (Btu/h) 27,300 31,500 40,600 43,800
Power Input (W)1
450 450 450 450
Entering Mixed Air
MULTI V Ducted Indoor Unit Engineering Manual

Cooling Max. (°F WB) 76 76 76 76


Heating Min. (°F DB) 59 59 59 59
Unit Data
Refrigerant Type2 R410A R410A R410A R410A
Refrigerant Control EEV EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
42 / 39 / 37 42 / 41 / 40 44 / 43 / 42 45 / 44 / 44
Net Unit Weight (lbs.) 83.8 83.8 83.8 83.8
Shipping Weight (lbs.) 94.8 94.8 94.8 94.8
Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18 2 x 18
Fan
Type Sirocco Sirocco Sirocco Sirocco
Motor 1 1 1 1
Housing 2 2 2 2
Motor/Drive Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM) 671 / 576 / 547 893 / 770 / 622 1,003 / 894 / 770 1,130 / 1,003 / 961
Standard Mode
Airflow Rate H/M/L (CFM) 671 / 537 / 487 915 / 851 / 770 1,141 / 1,024 / 894 1,218 / 1,141 / 1,084
High Mode (Factory Set)
External Static Pressure (in. wg) 0.23 0.31 0.31 0.31
Standard Mode
External Static Pressure (in. wg) 0.31 0.39 0.39 0.39
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.) 3/8 Flare 3/8 Flare 3/8 Flare 3/8 Flare
Vapor Line (in., O.D.) 5/8 Flare 5/8 Flare 5/8 Flare 5/8 Flare
Condensate Line (in., I.D.) 1 1 1 1
EEV: Electronic Expansion Valve 1
Power Input is rated at high speed.
Power wiring is field supplied and must comply with the applicable local and national codes. 2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
This unit comes with a dry nitrogen charge. R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units. All capacities are net with a combination ratio between
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
95-105%. 4
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet with applicable and national code. Ensure the communication cable is properly grounded at the master
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB). outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor
ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).

Due to our policy of continuous product innovation, some specifications may change without notification.
18 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED HIGH STATIC
General Data
BR and B8 Units

Table 13: Ducted High Static (BR and B8 Frames) Indoor Unit General Data.
Model No. ARNU483BRA4 ARNU543BRA4 ARNU763B8A4 ARNU963B8A4
Cooling Mode Performance
Capacity (Btu/h) 48,100 54,000 76,400 95,900
Power Input1 (W) 450 450 800 800
Heating Mode Performance
Capacity (Btu/h) 51,200 61,400 86,000 107,500
Power Input (W) 1
450 450 800 800
Entering Mixed Air
Cooling Max. (°F WB) 76 76 76 76
Heating Min. (°F DB) 59 59 59 59
Unit Data
Refrigerant Type2 R410A R410A R410A R410A
Refrigerant Control EEV EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
45 / 43 / 41 46 / 45 / 43 50 / 48 / 48 52 / 50 / 50

Ducted High Static


Net Unit Weight (lbs.) 112 112 192 192
Shipping Weight (lbs.) 132 132 222 222
Communication Cable (No. x AWG) 4
2 x 18 2 x 18 2 x 18 2 x 18
Fan
Type Sirocco Sirocco Sirocco Sirocco
Motor 2 2 2 2
Housing 2 2 2 2
Motor/Drive Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM) 1,568 / 1,395 / 1,183 1,819 / 1,678 / 1,395 2,050 / 1,766 / 1,766 2,684 / 2,260 / 2,260
Standard Mode
Airflow Rate H/M/L (CFM) 1,582 / 1,434 / 1,176 1,801 / 1,582 / 1,434 2,260 / 1,766 / 1,766 2,542 / 2,260 / 2,260
High Mode (Factory Set)
External Static Pressure (in. wg) 0.39 0.39 0.59 0.59
Standard Mode
External Static Pressure (in. wg) 0.55 0.55 0.87 0.87
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.) 3/8 Flare 3/8 Flare 3/8 Flare 3/8 Flare
Vapor Line (in., O.D.) 5/8 Flare 5/8 Flare 3/4 Flare 7/8 Flare
Condensate Line (in., I.D.) 1 1 1 1
EEV: Electronic Expansion Valve 1
Power Input is rated at high speed.
Power wiring is field supplied and must comply with the applicable local and national codes. 2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
This unit comes with a dry nitrogen charge. R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units. All capacities are net with a combination ratio between
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
95-105%. 4
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet with applicable and national code. Ensure the communication cable is properly grounded at the master
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB). outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor
ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 19
Ducted High Static
Electrical Data

Table 14: Ducted High Static (BG, BR, and B8 Frames) Indoor Unit Electrical Data.
Power Supply Power Input (W)
Model Voltage Range MCA MOP Rated Amps (A)
Hz Volts Phase Cooling Heating
BG Units
ARNU073BGA4 3.3 2.65 450 450
ARNU093BGA4 3.3 2.65 450 450
ARNU123BGA4 3.3 2.65 450 450
ARNU153BGA4 3.3 2.65 450 450
ARNU183BGA4 208-230 3.3 15 2.65 60 208-230 1 450 450
MULTI V Ducted Indoor Unit Engineering Manual

ARNU243BGA4 3.3 2.65 450 450


ARNU283BGA4 3.3 2.65 450 450
ARNU363BGA4 3.3 2.65 450 450
ARNU423BGA4 3.3 2.65 450 450
BR Units
ARNU483BRA4 4.4 3.5 450 450
208-230 15 60 208-230 1
ARNU543BRA4 4.4 3.5 450 450
B8 Units
ARNU763B8A4 6.5 5.2 800 800
208-230 15 60 208-230 1
ARNU963B8A4 6.5 5.2 800 800
MCA : Minimum Circuit Ampacity. Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
MOP : Maximum Overcurrent Protection. Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.

Due to our policy of continuous product innovation, some specifications may change without notification.
20 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
External Dimensions
BG Units

Figure 2: ARNU073~423BGA4 Dimensions.


13/16

41 4-1/2

Power Supply
8-5/8

Connection

Liquid Pipe
Connection: 3/8 4
48-1/2 1-1/4
2-1/16
15/16 Air Return

2-1/16

6-9/16
1-7/8
5-7/8
8-7/8

1-15/16
ø4
8
2-3/

17-3/4
14

Ducted High Static


3-15/16

5-9/16
4-13/16
8-5/8
3-7/16
1-15/16
22-1/4 Air Supply
3
1-3/16

10-1/4
3-7/16
Gas Pipe Drain Pipe
32-11/16 Connection: 5/8 Connection: 1

46-9/16 4-1/4
7-5/16

6-1/4
11-3/4

4-7/16

9-1/8 9-9/16 9-1/8 9-9/16 9-1/8

Center of Gravity
17-3/4

Unit: inches
Note: All measurements
have a tolerance of ±1/4 in.

46-9/16

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 21
Ducted High Static
External Dimensions
BR Units

Figure 3: ARNU483BRA4, ARNU543BRA4 Dimensions.


43 4-3/4 Power Supply
Connection
1
12

Liquid Pipe
Connection: 3/8
Gas Pipe
Connection: 5/8 3-15/16
MULTI V Ducted Indoor Unit Engineering Manual

50-1/2 3-1/4
4-9/16

2-13/16
48-7/16
1
Air Return

4-13/16
8-3/4
7-3/4
12-1/4

R6
0

3-9/16
23-5/16
/8
2-3

18-3/4

5-11/16
4-13/16
11-7/8
1-1/4

1-15/16 4-5/8 Air Outlet 4-7/16 2-3/16 5-5/16


24-1/2 7-7/16
39-5/8 10-1/4
Drain Pipe
Connection: 1
5-9/16

11-9/16
7
15

6-7/8
7

9-1/2 11 9-1/2 11 8-1/2


39-9/16
23-5/16

Center of Gravity
Unit: inches
Note: All measurements
have a tolerance of ±1/4 in.
48-7/16

Due to our policy of continuous product innovation, some specifications may change without notification.
22 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
External Dimensions
B8 Units

Figure 4: ARNU763B8A4, ARNU963B8A4 Dimensions.

Power
Supply
Connection Gas Pipe
4-9/16 Connection
13/16

55-1/8 76,000: 3/4


96,000: 7/8
17-3/8

2-3/4

4-3/4

7/8
18-1/8 63-7/8 6 3-
5-9/1
61-5/8
Liquid Pipe Drain Pipe

2-1/2
Air Return
Connection: 3/8 Connection: 1

2-3/4
2-1/4
3/4

2-3/8

Ducted High Static


22-7/8
27-1/8
4-1/4

4-7/8
15-11/16

2-5/8
14

32-1/4 Air Supply


2-9/16
1-3/16

44-3/16
12-9/16

11-1/2
18-1/8

8-3/4
6-3/8

11-9/16 12-15/16 12-5/8 12-15/16 4-11/16

Center of Gravity
27-3/8

Unit: inches
Note: All measurements
have a tolerance of ±1/4 in.
61-1/2

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 23
Ducted High Static
Electrical Wiring Diagram
BG Units

Figure 5: ARNU073~423BGA4 Wiring Diagram.


MULTI V Ducted Indoor Unit Engineering Manual

Due to our policy of continuous product innovation, some specifications may change without notification.
24 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Electrical Wiring Diagram
BG Units

Table 15: BG Unit Wiring Diagram Legend.


Terminal Purpose Function
CN-POWER AC Power supply AC Power line
CN-MOTOR1 Fan motor output Motor output of BLDC
RV-VM Sub PCB power supply Power supply connection
CN-FLOAT (BL) Float switch input Float switch sensing
CN-ZONE Zone controller Zone controller connection
CN-EEV EEV Output EEV control output
CN-OPTION Optional PCB EPROM Option PCB connection
CN-DISPLAY Display Display of indoor status
CN-CC Dry contact Dry Contact connection
CN-PTC Auxiliary heater Connection for Auxiliary Heater
CN-PIPE/OUT (RD) Discharge pipe sensor Pipe out thermistor
CN-PIPE/IN (WH) Suction pipe sensor Pipe in thermistor

Ducted High Static


CN-REMO (GN) Wired remote controller Wired remote control connection
CN-ROOM (YL) Room sensor Room air thermistor
CN-D/PUMP Drain pump output AC output for drain pump
CN-485 Communication Connection between indoor and outdoor units

Table 16: BG Unit DIP Switch Settings.


DIP Switch Setting Off On Remarks
SW3 GROUP Master Slave Group Control setting using 7-Day Programmable Controller
Dry Contact Mode Setting
1. Variable: Auto/Manual Mode can be chosen by 7-Day Programmable Controller or
SW4 DRY CONTACT Variable Auto
Wireless Remote Controller (when shipped from factory -> Manual Mode)
2. Auto: For Dry Contact, it is always Auto mode
-OFF: Default (does not operate continuously)
SW5 EXTRA 1 Off On
-ON: Fan operates continuously
COMMUNICATIONS -OFF: 1.2kbps
SW8 Gen. 2 Gen. 4
RATE -ON: 9.6kbps
For Multi V systems, DIP switches 1, 2, 6, and 7 must be set to OFF. These DIP switches are used for other models.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 25
Ducted High Static
Electrical Wiring Diagram
BR Units

Figure 6: ARNU483BRA4, ARNU543BRA4 Wiring Diagram.


MULTI V Ducted Indoor Unit Engineering Manual

Due to our policy of continuous product innovation, some specifications may change without notification.
26 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Electrical Wiring Diagram
BR Units

Table 17: BR Unit Wiring Diagram Legend.


Terminal Purpose Function
CN-POWER AC Power supply AC Power line
CN-MOTOR1 Fan motor output Motor output of BLDC
CN-MOTOR2 Fan motor output Motor output of BLDC
RV-VM Sub PCB power supply Power supply connection
CN-FLOAT (BL) Float switch input Float switch sensing
CN-ZONE Zone controller Zone controller connection
CN-EEV EEV Output EEV control output
CN-OPTION Optional PCB EPROM Option PCB connection
CN-DISPLAY Display Display of indoor status
CN-CC Dry contact Dry Contact connection
CN-PTC Auxiliary heater Connection for Auxiliary Heater
CN-PIPE/OUT (RD) Discharge pipe sensor Pipe out thermistor
CN-PIPE/IN (WH) Suction pipe sensor Pipe in thermistor

Ducted High Static


CN-REMO (GN) Wired remote controller Wired remote control connection
CN-ROOM (YL) Room sensor Room air thermistor
CN-D/PUMP Drain pump output AC output for drain pump
CN-485 Communication Connection between indoor and outdoor units

Table 18: BR Unit DIP Switch Settings.


DIP Switch Setting Off On Remarks
SW3 GROUP Master Slave Group Control setting using 7-Day Programmable Controller
Dry Contact Mode Setting
1. Variable: Auto/Manual Mode can be chosen by 7-Day Programmable Controller or
SW4 DRY CONTACT Variable Auto
Wireless Remote Controller (when shipped from factory -> Manual Mode)
2. Auto: For Dry Contact, it is always Auto mode
-OFF: Default (does not operate continuously)
SW5 EXTRA 1 Off On
-ON: Fan operates continuously
COMMUNICATIONS -OFF: 1.2kbps
SW8 Gen. 2 Gen. 4
RATE -ON: 9.6kbps
For Multi V systems, DIP switches 1, 2, 6, and 7 must be set to OFF. These DIP switches are used for other models.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 27
Ducted High Static
Electrical Wiring Diagram
B8 Units

Figure 7: ARNU763B8A4, ARNU963B8A4 Wiring Diagram.


MULTI V Ducted Indoor Unit Engineering Manual

Due to our policy of continuous product innovation, some specifications may change without notification.
28 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Electrical Wiring Diagram
B8 Units

Table 19: B8 Unit Wiring Diagram Legend.


Terminal Purpose Function
CN-POWER AC Power supply AC Power line
CN-MOTOR1 Fan motor output Motor output of BLDC
CN-MOTOR2 Fan motor output Motor output of BLDC
CN-VM Sub PCB power supply Power supply connection
CN-FLOAT (BL) Float switch input Float switch sensing
CN-ZONE Zone controller Zone controller connection
CN-EEV EEV Output EEV control output
CN-OPTION Optional PCB EPROM Option PCB connection
CN-DISPLAY Display Display of indoor status
CN-CC Dry contact Dry Contact connection
CN-PTC Auxiliary heater Connection for Auxiliary Heater
CN-REMO (GN) Wired remote controller Wired remote control connection
CN-PIPE/OUT (RD) Discharge pipe sensor Pipe out thermistor

Ducted High Static


CN-PIPE/IN (WH) Suction pipe sensor Pipe in thermistor
CN-ROOM (YL) Room sensor Room air thermistor
CN-D/PUMP Drain pump output AC output for drain pump
CN-485 Communication Connection between indoor and outdoor units

Table 20: B8 Unit DIP Switch Settings.


DIP Switch Setting Off On Remarks
SW3 GROUP Master Slave Group Control setting using 7-Day Programmable Controller
Dry Contact Mode Setting
1. Variable: Auto/Manual Mode can be chosen by 7-Day Programmable Controller or
SW4 DRY CONTACT Variable Auto
Wireless Remote Controller (when shipped from factory -> Manual Mode)
2. Auto: For Dry Contact, it is always Auto mode
-OFF: Default (does not operate continuously)
SW5 EXTRA 1 Off On
-ON: Fan operates continuously
COMMUNICATIONS -OFF: 1.2kbps
SW8 Gen. 2 Gen. 4
RATE -ON: 9.6kbps
For Multi V systems, DIP switches 1, 2, 6, and 7 must be set to OFF. These DIP switches are used for other models.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 29
Ducted High Static
Refrigerant Flow Diagram
BG, BR Units

Figure 8: BG, BR Unit Refrigerant Flow Diagram.

Cooling
Heat Exchanger EEV Heating
Filter

TH3 TH2
Sirocco Fan Filter
MULTI V Ducted Indoor Unit Engineering Manual

TH1 lndoor unit

Table 21: BG, BR Unit Refrigerant Pipe Connection Port Diameters.


Model Liquid (inch) Vapor (inch)
BG Units
ARNU073BGA4
ARNU093BGA4
ARNU123BGA4
ARNU153BGA4
ARNU183BGA4 3/8 Flare 5/8 Flare
ARNU243BGA4
ARNU283BGA4
ARNU363BGA4
ARNU423BGA4
BR Units
ARNU483BRA4
3/8 Flare 5/8 Flare
ARNU543BRA4

Table 22: BG, BR Frame Thermistors.


Thermistor Description
TH1 Return air thermistor
TH2 Pipe in thermistor
TH3 Pipe out thermistor

Due to our policy of continuous product innovation, some specifications may change without notification.
30 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Refrigerant Flow Diagram
B8 Units

Figure 9: B8 Unit Refrigerant Flow Diagram.


Cooling
Heat Exchanger EEV Heating
Filter

TH3 TH2
Check
Sirocco Fan Valve
Solenoid Valve
Filter

TH1 lndoor unit

Ducted High Static


Table 23: B8 Unit Refrigerant Pipe Connection Port Diameters.
Model Liquid (inch) Vapor (inch)
ARNU763B8A4 3/8 Flare 3/4 Flare
ARNU963B8A4 3/8 Flare 7/8 Flare

Table 24: B8 Unit Thermistors.


Thermistor Description
TH1 Return air thermistor
TH2 Pipe in thermistor
TH3 Pipe out thermistor

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 31
Ducted High Static
External Static Pressure and Air Flow Tables
BG, BR, B8 Units

Table 25: BG Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0.15 0.19 0.23 0.27 0.31 0.35 0.39 0.47 0.55 0.62
70 - - - - - - - - - -
80 285 141 - - - - - - - -
90 498 427 243 145 - - - - - -
100 672 600 547 388 218 148 - - - -
110 780 755 692 619 494 409 233 - - -
120 925 911 847 769 699 632 515 427 - -
130 1,066 1,059 1,006 951 893 826 769 639 515 399
MULTI V Ducted Indoor Unit Engineering Manual

140 1,281 1,271 1,133 1,073 1,024 968 914 762 628 512
143 1,334 1,324 1,197 1,133 1,084 1,017 960 812 709 593
150 1,465 1,447 1,432 1,271 1,218 1,133 1,063 928 791 642
160 1,500 1,497 1,469 1,349 1,274 1,236 1,221 1,098 946 822

Table 26: BR Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0.19 0.23 0.31 0.39 0.47 0.55 0.59 0.62 0.66 0.70 0.78
91 1,642 1,543 1,349 1,105 819 494 317 130 - - -
96 1,762 1,628 1,518 1,183 1,098 649 483 317 91 - -
101 1,839 1,772 1,691 1,395 1,320 964 889 628 314 215 -
106 1,815 1,808 1,779 1,568 1,522 1,176 1,133 1,020 741 632 293
111 1,892 1,896 1,868 1,762 1,705 1,433 1,419 1,158 1,112 960 618
116 - - - 1,967 1,794 1,582 1,504 1,416 1,327 1,147 974
121 - - - - 1,843 1,794 1,776 1,613 1,575 1,370 1,137
126 - - - - - - 1,921 1,808 1,779 1,624 1,536

Table 27: B8 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0.23 0.35 0.47 0.59 0.71 0.79 0.86 0.90 0.98
60 1,430 - - - - - - - -
65 1,861 - - - - - - - -
70 2,249 1,663 - - - - - - -
75 2,511 2,009 1,578 - - - - - -
80 2,694 2,461 1,949 - - - - - -
85 2,941 2,775 2,380 1,974 - - - - -
91 3,167 3,076 2,786 2,387 1,914 - - - -
95 3,298 3,227 3,040 2,719 2,345 1,787 1,059 - -
100 3,298 3,227 3,118 2,998 2,680 2,454 2,147 1,522 -
105 3,291 3,224 3,118 2,998 2,864 2,733 2,443 2,398 1,811

1. All static pressure air flow rates are listed in CFM.


2. The tables above show the correlation between air flow rates and external static pressure.
3. The tables above show the available external static pressure range.

If the external static pressure of the installed indoor unit is less than the lowest value (as mentioned in the table), the indoor unit components
can fail.
Due to our policy of continuous product innovation, some specifications may change without notification.
32 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
External Static Pressure and Air Flow Charts
BG, BR, B8 Units

Figure 10: BG Unit External Static Pressure and Air Flow Chart.
0.65
P

0.55 ESP
Setting
160
ESP
Setting
0.45 150
ESP ESP
Setting Setting
130 140
ESP
0.35 Setting
120
ESP
Setting
110
0.25 ESP
Setting
100

0.15
100 300 500 700 900 1100 1300 1500
Q (CFM)

Figure 11: BR Unit External Static Pressure and Air Flow Chart.

Ducted High Static


P 0.75
ESP
0.65 ESP Setting
Setting 126
120
0.55 ESP
Setting
ESP 110
0.45 Setting
ESP 100
Setting
0.35 90

0.25

0.15
100 600 1100 1600
Q (CFM)

Figure 12: B8 Unit External Static Pressure and Air Flow Chart.

1
P
0.9
ESP
Setting
0.8 105

0.7
ESP
Setting
0.6 95

0.5 ESP
Setting
0.4 85

ESP
0.3 Setting
75
0.2
1000 1500 2000 2500 3000
Q (CFM)

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 33
Ducted High Static
External Static Pressure Ranges
BG, BR, B8 Units

Table 28: BG Unit External Static Pressure Ranges.


Model Capacity (MBh) Mode Setting Value Standard ESP (in. wg) CFM Min. ESP (in. wg) Max. ESP (in. wg)
High 98 441
High
Mid 95 0.23 406 0.23 0.47
(Factory Set)
Low 92 332
ARNU073BGA4 7.5
High 92 516
Standard Mid 89 0.15 484 0.15 0.31
Low 86 434
High 99 452
High
Mid 95 0.23 406 0.23 0.47
(Factory Set)
Low 92 332
ARNU093BGA4 9.6
MULTI V Ducted Indoor Unit Engineering Manual

High 93 533
Standard Mid 89 0.15 484 0.15 0.31
Low 86 434
High 100 477
High
Mid 96 0.23 427 0.23 0.47
(Factory Set)
Low 93 332
ARNU123BGA4 12.3
High 95 586
Standard Mid 92 0.15 533 0.15 0.31
Low 89 483
High 112 540
High
Mid 100 0.31 219 0.31 0.62
(Factory Set)
Low 95 127
ARNU153BGA4 15.4
High 102 576
Standard Mid 96 0.23 427 0.23 0.39
Low 89 240
High 113 562
High
Mid 110 0.31 494 0.31 0.62
(Factory Set)
Low 100 219
ARNU183BGA4 19.1
High 110 692
Standard Mid 100 0.23 547 0.23 0.39
Low 93 332
High 120 699
High
Mid 113 0.31 562 0.31 0.62
(Factory Set)
Low 100 219
ARNU243BGA4 24.2
High 112 720
Standard Mid 100 0.23 547 0.23 0.39
Low 95 396
High 127 660
High
Mid 120 0.39 516 0.31 0.62
(Factory Set)
Low 113 332
ARNU283BGA4 28.0
High 113 562
Standard Mid 102 0.31 304 0.23 0.39
Low 97 180
High 151 1,084
High
Mid 145 0.39 1,024 0.31 0.55
(Factory Set)
Low 139 894
ARNU363BGA4 36.2
High 138 1,003
Standard Mid 130 0.31 894 0.23 0.39
Low 124 770
High 157 1,218
High
Mid 154 0.39 1,141 0.31 0.47
(Factory Set)
Low 151 1,084
ARNU423BGA4 42.0
High 145 1,130
Standard Mid 138 0.31 1,003 0.31 0.39
Low 134 961
The table above shows the available E.S.P. range.
Due to our policy of continuous product innovation, some specifications may change without notification.
34 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
External Static Pressure Ranges
BG, BR, B8 Units

Table 29: BR Unit External Static Pressure Ranges.


Model Capacity (MBh) Mode Setting Value Standard ESP (in. wg) CFM Min. ESP (in. wg) Max. ESP (in. wg)
High 116 1,582
High
Mid 111 0.55 1,434 0.39 0.78
(Factory Set)
Low 106 1,176
ARNU483BRA4 48.1
High 106 1,568
Standard Mid 102 0.39 1,395 0.27 0.55
Low 95 1,183
High 121 1,801
High
Mid 116 0.55 1,582 0.39 0.78
(Factory Set)
Low 111 1,434
ARNU543BRA4 54.0
High 112 1,819
Standard Mid 108 0.39 1,678 0.27 0.55
Low 102 1,395

Table 30: B8 Unit External Static Pressure Ranges.


Model Capacity (MBh) Mode Setting Value Standard ESP (in. wg) CFM Min. ESP (in. wg) Max. ESP (in. wg)

Ducted High Static


High 102 2,119
High
Mid 98 0.86 1,766 0.47 0.98
(Factory Set)
Low 98 1,766
ARNU763B8A4 76.4
High 86 2,260
Standard Mid 83 0.59 1,766 0.47 0.98
Low 83 1,766
High 105 2,542
High
Mid 102 0.86 2,260 0.47 0.98
(Factory Set)
Low 102 2,260
ARNU963B8A4 95.9
High 94 2,684
Standard Mid 89 0.59 2,260 0.47 0.98
Low 89 2,260
The tables above show the available E.S.P. range.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 35
Ducted High Static
Acoustic Data
Sound Pressure Levels

Figure 13: Sound Pressure Measurement Location. • Measurements are taken 4.9 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of ±3.
DISCHARGE SUCTION • Sound pressure levels are tested in an anechoic chamber under ISO Standard
3745.
DUCT DUCT Operating Conditions:
• Power source: 220V/60 Hz
• Sound level will vary depending on a range of factors including the construc-
3.3 ft.
4.9 ft.

6.6 ft. tion (acoustic absorption coefficient) of a particular room in which the unit was
installed.
MULTI V Ducted Indoor Unit Engineering Manual

Table 31: Ducted High Static Indoor Unit Sound Pressure Levels.
Sound Pressure Levels dB(A)
Model
High Fan Speed Medium Fan Speed Low Fan Speed
BG Units
ARNU073BGA4 35 35 34
ARNU093BGA4 35 35 34
ARNU123BGA4 36 35 34
ARNU153BGA4 37 36 33
ARNU183BGA4 41 39 37
ARNU243BGA4 42 39 37
ARNU283BGA4 42 41 40
ARNU363BGA4 44 43 42
ARNU423BGA4 45 44 44
BR Units
ARNU483BRA4 45 43 41
ARNU543BRA4 46 45 43
B8 Units
ARNU763B8A4 50 48 48
ARNU963B8A4 52 50 50

Figure 14: ARNU073BGA4, ARNU093BGA4, and ARNU123BGA4 Sound Pressure Level Diagrams.
ARNU073BGA4 ARNU093BGA4 ARNU123BGA4

Due to our policy of continuous product innovation, some specifications may change without notification.
36 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Acoustic Data
Sound Pressure Levels

Figure 15: ARNU153BGA4, ARNU183BGA4, and ARNU243BGA4 Sound Pressure Level Diagrams.
ARNU153BGA4 ARNU183BGA4 ARNU243BGA4

Ducted High Static


Figure 16: ARNU283BGA4, ARNU363BGA4, and ARNU423BGA4 Sound Pressure Level Diagrams.
ARNU283BGA4 ARNU363BGA4 ARNU423BGA4

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 37
Ducted High Static
Acoustic Data
Sound Pressure Levels

Figure 17: ARNU483BRA4, ARNU543BRA4 Sound Pressure Level Diagrams.

ARNU483BRA4 ARNU543BRA4
MULTI V Ducted Indoor Unit Engineering Manual

Figure 18: ARNU763B8A4, ARNU963B8A4 Sound Pressure Level Diagrams.


ARNU763B8A4 ARNU963B8A4

Due to our policy of continuous product innovation, some specifications may change without notification.
38 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Acoustic Data
Sound Power Levels

Table 32: Ducted High Static Indoor Unit Sound Power Levels. • Data is valid under diffuse field conditions.
Sound Power Levels dB(A) • Data is valid under nominal operating conditions.
Model • Sound power level is measured using rated conditions, and tested
High Fan Speed
BG Units in a reverberation room per ISO 3741 standards.
ARNU073BGA4 53 • Sound level will vary depending on a range of factors such as
ARNU093BGA4 54 construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
ARNU123BGA4 55
ARNU153BGA4 56 • Reference acoustic intensity: 0dB = 10E-6μW/m2
ARNU183BGA4 58
ARNU243BGA4 60
ARNU283BGA4 61
ARNU363BGA4 62
ARNU423BGA4 64
BR Units
ARNU483BRA4 62
ARNU543BRA4 65
B8 Units
ARNU763B8A4 70

Ducted High Static


ARNU963B8A4 72

Figure 19: ARNU073BGA4, ARNU093BGA4, and ARNU123BGA4 Sound Power Level Diagrams.
ARNU073BGA4 ARNU093BGA4 ARNU123BGA4

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 39
Ducted High Static
Acoustic Data
Sound Power Levels

Figure 20: ARNU153BGA4, ARNU183BGA4, and ARNU243BGA4 Sound Power Level Diagrams.
ARNU153BGA4 ARNU183BGA4 ARNU243BGA4
MULTI V Ducted Indoor Unit Engineering Manual

Figure 21: ARNU283BGA4, ARNU363BGA4, and ARNU423BGA4 Sound Power Level Diagrams.
ARNU283BGA4 ARNU363BGA4 ARNU423BGA4

Due to our policy of continuous product innovation, some specifications may change without notification.
40 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Acoustic Data
Sound Power Levels

Figure 22: ARNU483BRA4 and ARNU543BRA4 Sound Power Level Diagrams.


ARNU483BRA4 ARNU543BRA4

Ducted High Static


Figure 23: ARNU763B8A4 and ARNU963B8A4 Sound Power Level Diagrams.
ARNU763B8A4 ARNU963B8A4

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 41
Ducted High Static
Cooling Capacity Tables
ARNU073BGA4, ARNU093BGA4, ARNU123BGA4

Table 33: ARNU073BGA4, ARNU093BGA4, ARNU123BGA4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.7 6.2
25 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.7 6.2
30 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.7 6.2
35 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.7 6.2
40 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.7 6.2
45 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.7 6.2
50 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.7 6.2
55 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.7 6.2
60 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.6 6.2
MULTI V Ducted Indoor Unit Engineering Manual

ARNU073BGA4 /
65 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.4 6.1
7.5
70 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.3 6.0
75 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.9 6.2 9.1 5.9
80 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.4 6.3 8.7 6.2 8.8 5.9
85 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.3 6.2 8.4 6.0 8.6 5.6
90 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.2 6.1 8.3 5.9 8.4 5.6
95 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 8.0 6.1 8.2 5.8 8.3 5.5
100 4.9 4.5 6.0 5.2 6.8 5.5 7.5 5.9 7.9 6.0 8.0 5.8 8.2 5.5
105 4.9 4.5 5.7 4.9 6.4 5.3 7.2 5.6 7.3 5.6 7.7 5.6 7.9 5.3
110 4.8 4.4 5.4 4.7 6.0 4.9 6.8 5.3 6.9 5.3 7.3 5.3 7.7 5.2
23 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
25 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
30 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
35 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
40 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
45 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
50 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
55 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.4 8.0
60 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.3 7.9
ARNU093BGA4 /
65 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 12.1 7.8
9.6
70 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 11.9 7.7
75 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.4 8.0 11.6 7.5
80 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.8 8.0 11.1 7.9 11.3 7.4
85 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.6 8.0 10.8 7.6 11.0 7.2
90 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.5 7.8 10.6 7.4 10.8 7.1
95 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.3 7.8 10.5 7.4 10.6 7.0
100 6.3 5.7 7.7 6.6 8.6 7.0 9.6 7.5 10.1 7.7 10.3 7.3 10.5 6.9
105 6.3 5.7 7.3 6.3 8.2 6.7 9.2 7.2 9.4 7.2 9.9 7.1 10.1 6.8
110 6.2 5.6 6.9 5.9 7.7 6.3 8.6 6.7 8.8 6.7 9.4 6.7 9.8 6.6
23 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
25 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
30 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
35 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
40 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
45 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
50 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
55 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.9 10.2
60 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.7 10.2
ARNU123BGA4 /
65 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.5 10.0
12.3
70 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 15.3 9.8
75 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.7 10.2 14.9 9.6
80 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.8 10.3 14.2 10.2 14.5 9.6
85 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.6 10.2 13.8 9.7 14.0 9.2
90 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.4 10.1 13.5 9.6 13.8 9.1
95 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 13.2 10.0 13.4 9.5 13.6 9.0
100 8.1 7.4 9.8 8.5 11.1 9.0 12.3 9.6 12.9 9.8 13.2 9.4 13.4 8.9
105 8.1 7.4 9.3 8.1 10.6 8.7 11.8 9.2 12.0 9.2 12.7 9.1 12.9 8.7
110 7.9 7.1 8.9 7.6 9.8 8.1 11.1 8.7 11.3 8.7 12.0 8.7 12.6 8.4
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
42 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Cooling Capacity Tables
ARNU153BGA4, ARNU183BGA4, ARNU243BGA4

Table 34: ARNU153BGA4, ARNU183BGA4, ARNU243BGA4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6
25 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6
30 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6
35 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6
40 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6
45 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6
50 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6
55 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6
60 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.7 13.5
ARNU153BGA4 /
65 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.4 13.3
15.4
70 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.1 13.1
75 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 18.6 12.8
80 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 17.8 13.5 18.2 12.7
85 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.1 13.6 17.3 12.9 17.6 12.2
90 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 16.8 13.4 16.9 12.7 17.3 12.1
95 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 16.5 13.3 16.8 12.6 17.1 11.9
100 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 16.2 13.1 16.5 12.5 16.8 11.8
105 10.1 9.8 11.7 10.7 13.2 11.5 14.8 12.2 15.1 12.2 15.8 12.1 16.2 11.6

Ducted High Static


110 9.9 9.5 11.1 10.1 12.3 10.7 13.9 11.5 14.2 11.5 15.1 11.5 15.7 11.2
23 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8
25 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8
30 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8
35 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8
40 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8
45 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8
50 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8
55 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8
60 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.4 15.7
ARNU183BGA4 /
65 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.0 15.5
19.1
70 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 23.7 15.2
75 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 23.1 14.9
80 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.1 15.7 22.5 14.8
85 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.2 15.8 21.4 15.1 21.8 14.2
90 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 20.9 15.6 21.0 14.8 21.4 14.1
95 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 20.5 15.5 20.9 14.7 21.2 13.9
100 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 20.1 15.2 20.5 14.6 20.9 13.8
105 12.6 11.4 14.5 12.5 16.4 13.4 18.3 14.2 18.7 14.2 19.7 14.1 20.1 13.5
110 12.3 11.0 13.8 11.8 15.3 12.5 17.2 13.4 17.6 13.4 18.7 13.4 19.5 13.1
23 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0
25 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0
30 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0
35 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0
40 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0
45 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0
50 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0
55 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0
60 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.0 19.9
ARNU243BGA4 /
65 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 30.5 19.6
24.2
70 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 30.0 19.3
75 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 29.2 18.9
80 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.0 19.9 28.5 18.8
85 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 26.8 20.0 27.1 19.1 27.6 18.0
90 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 26.4 19.7 26.6 18.8 27.1 17.8
95 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 25.9 19.6 26.4 18.7 26.8 17.6
100 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 25.4 19.3 25.9 18.5 26.4 17.5
105 15.9 14.4 18.4 15.8 20.8 17.0 23.2 18.0 23.7 18.0 24.9 17.8 25.4 17.1
110 15.5 14.0 17.4 15.0 19.4 15.8 21.8 17.0 22.3 17.0 23.7 17.0 24.7 16.5
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 43
Ducted High Static
Cooling Capacity Tables
ARNU283BGA4, ARNU363BGA4, ARNU423BGA4

Table 35: ARNU283BGA4, ARNU363BGA4, ARNU423BGA4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0
25 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0
30 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0
35 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0
40 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0
45 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0
50 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0
55 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0
60 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 35.8 21.9
MULTI V Ducted Indoor Unit Engineering Manual

ARNU283BGA4 /
65 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 35.3 21.6
28.0
70 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 34.7 21.2
75 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 33.9 20.8
80 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 32.5 21.9 33.0 20.7
85 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.1 22.1 31.4 21.0 31.9 19.9
90 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 30.5 21.7 30.8 20.6 31.4 19.6
95 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 30.0 21.5 30.5 20.5 31.1 19.4
100 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 29.4 21.2 30.0 20.3 30.5 19.2
105 18.5 15.9 21.3 17.4 24.1 18.7 26.9 19.9 27.4 19.9 28.8 19.6 29.4 18.8
110 17.9 15.4 20.2 16.5 22.4 17.4 25.2 18.6 25.8 18.7 27.4 18.7 28.6 18.2
23 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
25 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
30 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
35 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
40 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
45 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
50 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
55 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5
60 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.3 28.3
ARNU363BGA4 /
65 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 45.6 27.9
36.2
70 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 44.9 27.5
75 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 43.8 26.8
80 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 42.0 28.4 42.7 26.7
85 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.2 28.5 40.5 27.1 41.3 25.7
90 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 39.5 28.0 39.8 26.7 40.5 25.3
95 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 38.7 27.9 39.5 26.5 40.2 25.1
100 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 38.0 27.4 38.7 26.3 39.5 24.9
105 23.9 20.6 27.5 22.5 31.1 24.1 34.8 25.7 35.5 25.7 37.3 25.4 38.0 24.3
110 23.2 19.9 26.1 21.3 29.0 22.4 32.6 24.1 33.3 24.1 35.5 24.1 36.9 23.6
23 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
25 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
30 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
35 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
40 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
45 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
50 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0
55 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.1
60 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 53.8 32.9
ARNU423BGA4 /
65 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 52.9 32.4
42.0
70 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 52.1 31.9
75 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 50.8 31.1
80 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 48.7 32.9 49.6 31.0
85 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 46.6 33.1 47.0 31.4 47.9 29.8
90 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 45.8 32.5 46.2 31.0 47.0 29.3
95 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 44.9 32.3 45.8 30.8 46.6 29.1
100 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 44.1 31.8 44.9 30.5 45.8 28.8
105 27.7 23.9 31.9 26.0 36.1 28.0 40.3 29.8 41.2 29.8 43.3 29.4 44.1 28.2
110 26.9 23.1 30.2 24.7 33.6 26.0 37.8 28.0 38.6 28.0 41.2 28.0 42.8 27.4
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
44 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Cooling Capacity Tables
ARNU483BRA4, ARNU543BRA4, ARNU763B8A4

Table 36: ARNU483BRA4, ARNU543BRA4, ARNU763B8A4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3
25 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3
30 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3
35 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3
40 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3
45 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3
50 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3
55 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.4
60 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 61.6 38.1
ARNU483BRA4 /
65 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 60.6 37.6
48.1
70 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 59.6 37.0
75 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 58.2 36.1
80 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 55.8 38.2 56.8 36.0
85 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.4 38.4 53.9 36.5 54.8 34.6
90 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 52.4 37.7 52.9 35.9 53.9 34.0
95 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 51.5 37.5 52.4 35.7 53.4 33.8
100 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 50.5 36.9 51.5 35.4 52.4 33.5
105 31.7 27.7 36.6 30.2 41.4 32.5 46.2 34.6 47.1 34.6 49.5 34.2 50.5 32.7

Ducted High Static


110 30.8 26.9 34.6 28.6 38.5 30.2 43.3 32.5 44.3 32.5 47.1 32.5 49.1 31.8
23 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 69.8 44.7
25 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 69.8 44.7
30 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 69.8 44.7
35 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 69.8 44.7
40 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 69.8 44.7
45 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 69.8 44.7
50 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 69.8 44.7
55 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 69.8 44.7
60 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 69.1 44.5
ARNU543BRA4 /
65 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 68.0 43.8
54.0
70 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 67.1 43.1
75 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 64.4 44.7 65.3 42.1
80 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 60.5 45.2 62.6 44.5 63.7 41.9
85 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 59.9 44.7 60.5 42.6 61.7 40.2
90 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 59.0 44.0 59.4 41.9 60.5 39.8
95 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 57.8 43.8 59.0 41.6 59.9 39.3
100 35.6 32.2 43.2 37.2 48.6 39.5 54.0 42.1 56.7 43.1 57.8 41.2 59.0 39.0
105 35.6 32.2 41.0 35.3 46.4 37.9 51.8 40.2 52.9 40.2 55.6 39.8 56.7 38.1
110 34.7 31.2 38.9 33.4 43.2 35.3 48.6 37.9 49.7 37.9 52.9 37.9 55.1 36.9
23 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8
25 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8
30 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8
35 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8
40 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8
45 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8
50 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8
55 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.9
60 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 97.8 56.5
ARNU763B8A4 /
65 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 96.3 55.7
76.4
70 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 94.7 54.8
75 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 92.4 53.6
80 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 88.6 56.6 90.2 53.3
85 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 84.8 56.9 85.6 54.1 87.1 51.3
90 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 83.3 55.9 84.0 53.3 85.6 50.5
95 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 81.7 55.6 83.3 52.9 84.8 50.1
100 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 80.2 54.8 81.7 52.5 83.3 49.6
105 50.4 41.1 58.1 44.8 65.7 48.1 73.3 51.3 74.9 51.3 78.7 50.7 80.2 48.5
110 48.9 39.8 55.0 42.5 61.1 44.8 68.8 48.1 70.3 48.2 74.9 48.2 77.9 47.1
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 45
Ducted High Static
Cooling Capacity Tables
ARNU963B8A4

Table 37: ARNU963B8A4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3
25 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3
30 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3
35 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3
40 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3
45 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3
50 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3
55 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.4
60 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 122.8 71.0
MULTI V Ducted Indoor Unit Engineering Manual

ARNU963B8A4 /
65 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 120.8 69.9
95.9
70 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 118.9 68.8
75 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 116.0 67.2
80 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 111.2 71.1 113.2 67.0
85 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 106.4 71.4 107.4 67.9 109.3 64.4
90 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 104.5 70.2 105.5 66.9 107.4 63.3
95 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 102.6 69.8 104.5 66.5 106.4 62.9
100 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 100.7 68.8 102.6 65.9 104.5 62.3
105 63.3 51.5 72.9 56.3 82.5 60.4 92.1 64.4 94.0 64.4 98.8 63.6 100.7 60.8
110 61.4 50.0 69.0 53.3 76.7 56.2 86.3 60.4 88.2 60.5 94.0 60.5 97.8 59.1
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
46 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Heating Capacity Tables
ARNU073BGA4, ARNU093BGA4, ARNU123BGA4, ARNU153BGA4

Table 38: ARNU073BGA4, ARNU093BGA4, ARNU123BGA4, ARNU153BGA4 Heating Capacity Table.


Indoor Air Temperature (°F DB)
Outdoor Air Temp. 59 61 64 67 70 73 76 80
Model No. /
Capacity Index TC TC TC TC TC TC TC TC
°F DB °F WB MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 5.7 5.7 5.7 5.7 5.6 5.6 5.6 5.6
0 -0.4 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.8
5.0 4.5 6.6 6.5 6.5 6.5 6.5 6.5 6.5 6.5
10.0 9.0 6.9 6.9 6.9 6.8 6.8 6.8 6.8 6.8
15.0 14.0 7.3 7.3 7.3 7.3 7.3 7.3 7.2 7.1
20.0 19.0 7.7 7.7 7.7 7.7 7.6 7.6 7.4 7.4
25.0 23.0 8.1 8.1 8.1 8.1 8.1 7.9 7.8 7.7
ARNU073BGA4 /
30.0 28.0 8.2 8.2 8.2 8.2 8.2 8.1 7.8 7.6
7.5
35.0 32.0 8.5 8.5 8.5 8.5 8.4 8.2 7.8 7.4
40.0 36.0 8.8 8.8 8.8 8.8 8.5 8.2 7.8 7.4
45.0 41.0 9.2 9.2 9.2 8.9 8.5 8.2 7.8 7.4
47.0 43.0 9.5 9.4 9.4 8.9 8.5 8.2 7.8 7.4
50.0 46.0 10.2 9.8 9.4 8.9 8.5 8.2 7.8 7.4
55.0 51.0 10.4 9.9 9.4 8.9 8.5 8.2 7.8 7.4
60.0 56.0 10.4 9.9 9.4 8.9 8.5 8.2 7.8 7.4
-4 -4.4 7.3 7.3 7.3 7.3 7.2 7.2 7.2 7.2
0 -0.4 7.5 7.5 7.5 7.5 7.5 7.4 7.4 7.4
5.0 4.5 8.5 8.4 8.3 8.3 8.3 8.3 8.3 8.3

Ducted High Static


10.0 9.0 8.8 8.8 8.8 8.7 8.7 8.7 8.7 8.7
15.0 14.0 9.4 9.4 9.4 9.4 9.4 9.4 9.3 9.2
20.0 19.0 9.9 9.9 9.9 9.9 9.7 9.7 9.5 9.4
25.0 23.0 10.4 10.4 10.4 10.4 10.4 10.1 10.0 9.9
ARNU093BGA4 /
30.0 28.0 10.6 10.6 10.6 10.6 10.6 10.4 10.0 9.7
9.6
35.0 32.0 10.9 10.9 10.9 10.9 10.8 10.6 10.0 9.5
40.0 36.0 11.3 11.3 11.3 11.3 10.9 10.6 10.0 9.5
45.0 41.0 11.8 11.8 11.8 11.4 10.9 10.6 10.0 9.5
47.0 43.0 12.2 12.1 12.0 11.4 10.9 10.6 10.0 9.5
50.0 46.0 13.1 12.5 12.0 11.4 10.9 10.6 10.0 9.5
55.0 51.0 13.4 12.6 12.0 11.4 10.9 10.6 10.0 9.5
60.0 56.0 13.4 12.6 12.0 11.4 10.9 10.6 10.0 9.5
-4 -4.4 9.1 9.1 9.1 9.1 9.0 9.0 9.0 9.0
0 -0.4 9.4 9.4 9.4 9.4 9.4 9.2 9.2 9.2
5.0 4.5 10.6 10.5 10.3 10.3 10.3 10.3 10.3 10.3
10.0 9.0 11.0 11.0 11.0 10.9 10.9 10.9 10.9 10.9
15.0 14.0 11.7 11.7 11.7 11.7 11.7 11.7 11.6 11.4
20.0 19.0 12.4 12.4 12.4 12.4 12.1 12.1 11.9 11.8
25.0 23.0 12.9 12.9 12.9 12.9 12.9 12.6 12.5 12.4
ARNU123BGA4 /
30.0 28.0 13.2 13.2 13.2 13.2 13.2 12.9 12.5 12.1
12.3
35.0 32.0 13.6 13.6 13.6 13.6 13.5 13.2 12.5 11.9
40.0 36.0 14.1 14.1 14.1 14.1 13.6 13.2 12.5 11.9
45.0 41.0 14.7 14.7 14.7 14.3 13.6 13.2 12.5 11.9
47.0 43.0 15.2 15.1 15.0 14.3 13.6 13.2 12.5 11.9
50.0 46.0 16.3 15.6 15.0 14.3 13.6 13.2 12.5 11.9
55.0 51.0 16.7 15.8 15.0 14.3 13.6 13.2 12.5 11.9
60.0 56.0 16.7 15.8 15.0 14.3 13.6 13.2 12.5 11.9
-4 -4.4 11.5 11.5 11.5 11.5 11.3 11.3 11.3 11.3
0 -0.4 11.8 11.8 11.8 11.8 11.8 11.6 11.6 11.6
5.0 4.5 13.3 13.2 13.0 13.0 13.0 13.0 13.0 13.0
10.0 9.0 13.9 13.9 13.9 13.7 13.7 13.7 13.7 13.7
15.0 14.0 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.4
20.0 19.0 15.6 15.6 15.6 15.6 15.2 15.2 15.0 14.8
25.0 23.0 16.2 16.2 16.2 16.2 16.2 15.9 15.7 15.6
ARNU153BGA4 /
30.0 28.0 16.6 16.6 16.6 16.6 16.6 16.2 15.7 15.2
15.4
35.0 32.0 17.1 17.1 17.1 17.1 16.9 16.6 15.7 14.9
40.0 36.0 17.8 17.8 17.8 17.8 17.1 16.6 15.7 14.9
45.0 41.0 18.5 18.5 18.5 18.0 17.1 16.6 15.7 14.9
47.0 43.0 19.2 19.0 18.8 18.0 17.1 16.6 15.7 14.9
50.0 46.0 20.6 19.7 18.8 18.0 17.1 16.6 15.7 14.9
55.0 51.0 20.9 19.8 18.8 18.0 17.1 16.6 15.7 14.9
60.0 56.0 20.9 19.8 18.8 18.0 17.1 16.6 15.7 14.9
TC: Total Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 47
Ducted High Static
Heating Capacity Tables
ARNU183BGA4, ARNU243BGA4, ARNU283BGA4, ARNU363BGA4

Table 39: ARNU183BGA4, ARNU243BGA4, ARNU283BGA4, ARNU363BGA4 Heating Capacity Table.


Indoor Air Temperature (°F DB)
Outdoor Air Temp. 59 61 64 67 70 73 76 80
Model No. /
Capacity Index TC TC TC TC TC TC TC TC
°F DB °F WB MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 14.4 14.4 14.4 14.4 14.2 14.2 14.2 14.2
0 -0.4 14.8 14.8 14.8 14.8 14.8 14.6 14.6 14.6
5.0 4.5 16.8 16.6 16.3 16.3 16.3 16.3 16.3 16.3
10.0 9.0 17.4 17.4 17.4 17.2 17.2 17.2 17.2 17.2
15.0 14.0 18.5 18.5 18.5 18.5 18.5 18.5 18.3 18.1
20.0 19.0 19.6 19.6 19.6 19.6 19.1 19.1 18.8 18.5
25.0 23.0 20.4 20.4 20.4 20.4 20.4 20.0 19.8 19.6
ARNU183BGA4 /
30.0 28.0 20.9 20.9 20.9 20.9 20.9 20.4 19.8 19.2
19.1
35.0 32.0 21.5 21.5 21.5 21.5 21.3 20.9 19.8 18.8
MULTI V Ducted Indoor Unit Engineering Manual

40.0 36.0 22.4 22.4 22.4 22.4 21.5 20.9 19.8 18.8
45.0 41.0 23.2 23.2 23.2 22.6 21.5 20.9 19.8 18.8
47.0 43.0 24.1 23.9 23.7 22.6 21.5 20.9 19.8 18.8
50.0 46.0 25.8 24.7 23.7 22.6 21.5 20.9 19.8 18.8
55.0 51.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
60.0 56.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
-4 -4.4 18.3 18.3 18.3 18.3 18.0 18.0 18.0 18.0
0 -0.4 18.8 18.8 18.8 18.8 18.8 18.6 18.6 18.6
5.0 4.5 21.3 21.0 20.7 20.7 20.7 20.7 20.7 20.7
10.0 9.0 22.1 22.1 22.1 21.8 21.8 21.8 21.8 21.8
15.0 14.0 23.5 23.5 23.5 23.5 23.5 23.5 23.2 22.9
20.0 19.0 24.8 24.8 24.8 24.8 24.2 24.2 23.9 23.6
25.0 23.0 25.9 25.9 25.9 25.9 25.9 25.4 25.1 24.8
ARNU243BGA4 /
30.0 28.0 26.5 26.5 26.5 26.5 26.5 25.9 25.1 24.3
24.2
35.0 32.0 27.3 27.3 27.3 27.3 27.0 26.5 25.1 23.8
40.0 36.0 28.4 28.4 28.4 28.4 27.3 26.5 25.1 23.8
45.0 41.0 29.5 29.5 29.5 28.7 27.3 26.5 25.1 23.8
47.0 43.0 30.6 30.3 30.0 28.7 27.3 26.5 25.1 23.8
50.0 46.0 32.8 31.4 30.0 28.7 27.3 26.5 25.1 23.8
55.0 51.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.8
60.0 56.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.8
-4 -4.4 21.1 21.1 21.1 21.1 20.8 20.8 20.8 20.8
0 -0.4 21.7 21.7 21.7 21.7 21.7 21.4 21.4 21.4
5.0 4.5 24.6 24.3 23.9 23.9 23.9 23.9 23.9 23.9
10.0 9.0 25.5 25.5 25.5 25.2 25.2 25.2 25.2 25.2
15.0 14.0 27.1 27.1 27.1 27.1 27.1 27.1 26.8 26.5
20.0 19.0 28.7 28.7 28.7 28.7 28.0 28.0 27.6 27.2
25.0 23.0 29.9 29.9 29.9 29.9 29.9 29.3 29.0 28.7
ARNU283BGA4 /
30.0 28.0 30.6 30.6 30.6 30.6 30.6 29.9 29.0 28.1
28.0
35.0 32.0 31.5 31.5 31.5 31.5 31.2 30.6 29.0 27.5
40.0 36.0 32.8 32.8 32.8 32.8 31.5 30.6 29.0 27.5
45.0 41.0 34.0 34.0 34.0 33.1 31.5 30.6 29.0 27.5
47.0 43.0 35.3 35.0 34.7 33.1 31.5 30.6 29.0 27.5
50.0 46.0 37.9 36.2 34.7 33.1 31.5 30.6 29.0 27.5
55.0 51.0 38.5 36.5 34.7 33.1 31.5 30.6 29.0 27.5
60.0 56.0 38.5 36.5 34.7 33.1 31.5 30.6 29.0 27.5
-4 -4.4 27.2 27.2 27.2 27.2 26.8 26.8 26.8 26.8
0 -0.4 28.0 28.0 28.0 28.0 28.0 27.6 27.6 27.6
5.0 4.5 31.7 31.3 30.9 30.9 30.9 30.9 30.9 30.9
10.0 9.0 32.9 32.9 32.9 32.5 32.5 32.5 32.5 32.5
15.0 14.0 34.9 34.9 34.9 34.9 34.9 34.9 34.5 34.1
20.0 19.0 36.9 36.9 36.9 36.9 36.0 36.0 35.5 35.0
25.0 23.0 38.6 38.6 38.6 38.6 38.6 37.8 37.4 37.0
ARNU363BGA4 /
30.0 28.0 39.4 39.4 39.4 39.4 39.4 38.6 37.4 36.2
36.2
35.0 32.0 40.6 40.6 40.6 40.6 40.2 39.4 37.4 35.4
40.0 36.0 42.2 42.2 42.2 42.2 40.6 39.4 37.4 35.4
45.0 41.0 43.8 43.8 43.8 42.6 40.6 39.4 37.4 35.4
47.0 43.0 45.5 45.1 44.7 42.6 40.6 39.4 37.4 35.4
50.0 46.0 48.8 46.7 44.7 42.6 40.6 39.4 37.4 35.4
55.0 51.0 49.7 47.1 44.7 42.6 40.6 39.4 37.4 35.4
60.0 56.0 49.7 47.1 44.7 42.6 40.6 39.4 37.4 35.4
TC: Total Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
48 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Heating Capacity Tables
ARNU423BGA4, ARNU483BRA4, ARNU543BRA4, ARNU763B8A4

Table 40: ARNU423BGA4, ARNU483BRA4, ARNU543BRA4, ARNU763B8A4 Heating Capacity Table.


Indoor Air Temperature (°F DB)
Outdoor Air Temp. 59 61 64 67 70 73 76 80
Model No. /
Capacity Index TC TC TC TC TC TC TC TC
°F DB °F WB MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 29.3 29.3 29.3 29.3 28.9 28.9 28.9 28.9
0 -0.4 30.2 30.2 30.2 30.2 30.2 29.8 29.8 29.8
5.0 4.5 34.2 33.7 33.3 33.3 33.3 33.3 33.3 33.3
10.0 9.0 35.5 35.5 35.5 35.0 35.0 35.0 35.0 35.0
15.0 14.0 37.7 37.7 37.7 37.7 37.7 37.7 37.2 36.8
20.0 19.0 39.9 39.9 39.9 39.9 38.9 38.9 38.3 37.8
25.0 23.0 41.6 41.6 41.6 41.6 41.6 40.7 40.3 39.9
ARNU423BGA4 /
30.0 28.0 42.5 42.5 42.5 42.5 42.5 41.6 40.3 39.0
42.0
35.0 32.0 43.8 43.8 43.8 43.8 43.4 42.5 40.3 38.2
40.0 36.0 45.6 45.6 45.6 45.6 43.8 42.5 40.3 38.2
45.0 41.0 47.3 47.3 47.3 46.0 43.8 42.5 40.3 38.2
47.0 43.0 49.1 48.6 48.2 46.0 43.8 42.5 40.3 38.2
50.0 46.0 52.7 50.4 48.2 46.0 43.8 42.5 40.3 38.2
55.0 51.0 53.6 50.8 48.2 46.0 43.8 42.5 40.3 38.2
60.0 56.0 53.6 50.8 48.2 46.0 43.8 42.5 40.3 38.2
-4 -4.4 34.3 34.3 34.3 34.3 33.8 33.8 33.8 33.8
0 -0.4 35.3 35.3 35.3 35.3 35.3 34.8 34.8 34.8
5.0 4.5 39.9 39.4 38.9 38.9 38.9 38.9 38.9 38.9

Ducted High Static


10.0 9.0 41.5 41.5 41.5 41.0 41.0 41.0 41.0 41.0
15.0 14.0 44.0 44.0 44.0 44.0 44.0 44.0 43.5 43.0
20.0 19.0 46.6 46.6 46.6 46.6 45.4 45.4 44.8 44.2
25.0 23.0 48.6 48.6 48.6 48.6 48.6 47.6 47.1 46.6
ARNU483BRA4 /
30.0 28.0 49.7 49.7 49.7 49.7 49.7 48.6 47.1 45.6
48.1
35.0 32.0 51.2 51.2 51.2 51.2 50.7 49.7 47.1 44.7
40.0 36.0 53.2 53.2 53.2 53.2 51.2 49.7 47.1 44.7
45.0 41.0 55.3 55.3 55.3 53.8 51.2 49.7 47.1 44.7
47.0 43.0 57.3 56.8 56.3 53.8 51.2 49.7 47.1 44.7
50.0 46.0 61.6 58.9 56.3 53.8 51.2 49.7 47.1 44.7
55.0 51.0 62.6 59.4 56.3 53.8 51.2 49.7 47.1 44.7
60.0 56.0 62.6 59.4 56.3 53.8 51.2 49.7 47.1 44.7
-4 -4.4 41.1 41.1 41.1 41.1 40.5 40.5 40.5 40.5
0 -0.4 42.4 42.4 42.4 42.4 42.4 41.8 41.8 41.8
5.0 4.5 47.9 47.3 46.7 46.7 46.7 46.7 46.7 46.7
10.0 9.0 49.7 49.7 49.7 49.1 49.1 49.1 49.1 49.1
15.0 14.0 52.8 52.8 52.8 52.8 52.8 52.8 52.2 51.6
20.0 19.0 55.9 55.9 55.9 55.9 54.6 54.6 53.7 53.1
25.0 23.0 58.3 58.3 58.3 58.3 58.3 57.1 56.5 55.9
ARNU543BRA4 /
30.0 28.0 59.6 59.6 59.6 59.6 59.6 58.3 56.5 54.6
54.0
35.0 32.0 61.4 61.4 61.4 61.4 60.8 59.6 56.5 53.7
40.0 36.0 63.9 63.9 63.9 63.9 61.4 59.6 56.5 53.7
45.0 41.0 66.3 66.3 66.3 64.5 61.4 59.6 56.5 53.7
47.0 43.0 68.8 68.2 67.5 64.5 61.4 59.6 56.5 53.7
50.0 46.0 73.7 70.6 67.5 64.5 61.4 59.6 56.5 53.7
55.0 51.0 75.2 71.2 67.5 64.5 61.4 59.6 56.5 53.7
60.0 56.0 75.2 71.2 67.5 64.5 61.4 59.6 56.5 53.7
-4 -4.4 57.6 57.6 57.6 57.6 56.8 56.8 56.8 56.8
0 -0.4 59.3 59.3 59.3 59.3 59.3 58.5 58.5 58.5
5.0 4.5 67.1 66.2 65.4 65.4 65.4 65.4 65.4 65.4
10.0 9.0 69.7 69.7 69.7 68.8 68.8 68.8 68.8 68.8
15.0 14.0 74.0 74.0 74.0 74.0 74.0 74.0 73.1 72.3
20.0 19.0 78.3 78.3 78.3 78.3 76.3 76.3 75.3 74.2
25.0 23.0 81.7 81.7 81.7 81.7 81.7 80.0 79.1 78.3
ARNU763B8A4 /
30.0 28.0 83.4 83.4 83.4 83.4 83.4 81.7 79.1 76.6
76.4
35.0 32.0 86.0 86.0 86.0 86.0 85.1 83.4 79.1 75.0
40.0 36.0 89.4 89.4 89.4 89.4 86.0 83.4 79.1 75.0
45.0 41.0 92.9 92.9 92.9 90.3 86.0 83.4 79.1 75.0
47.0 43.0 96.3 95.5 94.6 90.3 86.0 83.4 79.1 75.0
50.0 46.0 103.4 98.9 94.6 90.3 86.0 83.4 79.1 75.0
55.0 51.0 105.2 99.8 94.6 90.3 86.0 83.4 79.1 75.0
60.0 56.0 105.2 99.8 94.6 90.3 86.0 83.4 79.1 75.0
TC: Total Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 49
Ducted High Static
Heating Capacity Tables
ARNU963B8A4

Table 41: ARNU963B8A4 Heating Capacity Table.


Indoor Air Temperature (°F DB)
Outdoor Air Temp. 59 61 64 67 70 73 76 80
Model No. /
Capacity Index TC TC TC TC TC TC TC TC
°F DB °F WB MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 72.0 72.0 72.0 72.0 71.0 71.0 71.0 71.0
0 -0.4 74.2 74.2 74.2 74.2 74.2 73.1 73.1 73.1
5.0 4.5 83.9 82.8 81.7 81.7 81.7 81.7 81.7 81.7
10.0 9.0 87.1 87.1 87.1 86.0 86.0 86.0 86.0 86.0
15.0 14.0 92.5 92.5 92.5 92.5 92.5 92.5 91.4 90.3
20.0 19.0 97.8 97.8 97.8 97.8 95.4 95.4 94.1 92.7
25.0 23.0 102.1 102.1 102.1 102.1 102.1 100.0 98.9 97.8
ARNU963B8A4 /
30.0 28.0 104.3 104.3 104.3 104.3 104.3 102.1 98.9 95.8
95.9
35.0 32.0 107.5 107.5 107.5 107.5 106.4 104.3 98.9 93.8
MULTI V Ducted Indoor Unit Engineering Manual

40.0 36.0 111.8 111.8 111.8 111.8 107.5 104.3 98.9 93.8
45.0 41.0 116.1 116.1 116.1 112.9 107.5 104.3 98.9 93.8
47.0 43.0 120.4 119.3 118.3 112.9 107.5 104.3 98.9 93.8
50.0 46.0 129.2 123.6 118.3 112.9 107.5 104.3 98.9 93.8
55.0 51.0 131.5 124.7 118.3 112.9 107.5 104.3 98.9 93.8
60.0 56.0 131.5 124.7 118.3 112.9 107.5 104.3 98.9 93.8
TC: Total Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
50 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted High Static
Optional Accessories

Table 42: Optional Accessories for Ducted High Static Indoor Units.
Accessory Model Number
ZFBXBG01A (For 7~42MBh Ducted High Static Indoor Units)
High Efficiency Filter Box ZFBXBR01A (For 48-54MBh Ducted High Static Indoor Units)
ZFBXB801A (For 76-96MBh Ducted High Static Indoor Units)
ZPLMV201A (2VL)
Dynamic V8 Low Profile Air Cleaner
ZPLMV402A (4VL)

ZFLT1301A (4-Pack)
Dynamic V8 VL Replacement Filter Pads
ZFLT1302A (24-Pack)

ZGRLRA01A (Louvered)
Return Air Grille
ZGRLRA02A (Egg Crate)

ZPLMV201A (2VL)
Return Air Plenum
ZPLMV402A (4VL)

Ducted High Static


All accessories are sold separately.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. High Static | 51
MULTI V Ducted Indoor Unit Engineering Manual

Due to our policy of continuous product innovation, some specifications may change without notification.
52 | HIGH STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CEILING-CONCEALED
DUCTED
LOW STATIC
Mechanical Specifications on page 54
General Data on page 55
Electrical Data on page 56
External Dimensions on page 57
Electrical Wiring Diagram on page 58
Refrigerant Flow Diagrams on page 62
External Static Pressure and Air Flow on page 63
External Static Pressure Ranges on page 65
Acoustic Data on page 66
Capacity Tables on page 69
DUCTED LOW Static
Mechanical Specifications

Casing upon outdoor unit oper-


The case is a low profile design with a maximum height of eight ating mode.
inches designed to mount concealed above the finished ceiling. Fan In Heating mode, the
supply air is front horizontal with a rear horizontal field convertible microprocessor control
to a bottom return. The unit is manufactured with coated metal. Cold will activate the indoor
surfaces are covered with a polystyrene insulating material. The unit when indoor room
case is provided with hanger brackets designed to support the unit temperature falls below set-point temperature and signals the
weight on four corners. Hanger brackets have pre-punched holes outdoor unit to begin heating cycle. The indoor unit fan operation is
designed to accept field supplied all-thread rod hangers. delayed until coil pipe temperature reaches 76ºF. Significant airflow
is generated when pipe temperature reaches 80°F. In lieu of factory
Fan Assembly and Control return air thermistor, screw terminals on the microprocessor circuit
The unit has Sirocco fans made of high strength ABS HT-700 board accommodate various models of wall-mounted local control-
MULTI V Ducted Indoor Unit Engineering Manual

polymeric resin. Fans are directly driven and mounted on a common lers and/or a wall-mounted remote temperature sensor. The unit
shaft. The fan motor is a Brushless Digitally-Controlled (BLDC) microprocessor is capable of accepting space temperature readings
design with permanently lubricated and sealed ball bearings. The fan concurrently or individually from either:
motor includes thermal, overcurrent and low RPM protection. The 1. Wall-mounted wired controller(s)
fan/motor assembly is mounted on vibration attenuating rubber grom-
mets. The fan impeller is statically and dynamically balanced. The fan 2. Factory mounted return air thermistor or the optional wall-
speed is controlled using a microprocessor based direct digital con- mounted wired remote temperature sensor.
trol algorithm that provides a high fan speed in cooling thermal ON A single indoor unit has the capability of being controlled by up to
and low fan speed in cooling thermal OFF, high fan speed in heating two local wired controllers. The microprocessor controls space tem-
thermal ON and fan off in heating thermal OFF. The fan speeds can perature using the value provided by the temperature sensor sensing
be field adjusted between low, medium, and high speeds and DIP a space temperature that is farthest away from the temperature
switch settings will allow the fan to run constantly during defrost or set-point. The microprocessor control provides a cooling or heating
oil return modes. Each setting can be field adjusted from the factory mode test cycle that operates the unit for 18 minutes without regard
setting (RPM / ESP) to compensate for resistance to airflow caused to the space temperature. If the system is provided with an optional
by field connected ductwork or other airflow restricting devices. wall-mounted or central controller, displayed diagnostic codes are
specific, alpha numeric, and provide the service technician with a
Air Filter reason for the code displayed.
Return air is filtered with a removable, washable filter with anti-fun-
gal treatment. Condensate Lift/Pump
The indoor unit is provided with a factory installed and wired
Microprocessor Controls condensate lift/pump capable of providing a minimum 27.5 inch lift
The unit is provided with an integrated microprocessor-based con- from the bottom exterior surface of the unit casing. The lift pump
troller. The controller is capable of performing functions necessary comes with a safety switch that will shut off indoor unit if condensate
to operate the system without the use of a wall-mounted controller. rises too high in the drain pan.
A temperature thermistor is factory-mounted in the return air stream.
All unit operation parameters, excluding the unit operating schedule, Condensate Drain Pan
are stored in non-volatile memory resident on the unit microproces- The condensate drain pan is constructed of high impact polystyrene
sor. Operating schedules are stored in select models of the optional, resin (HIPS).
wall-mounted, local, or central controller. The field-supplied commu- Coil
nication cable between the indoor unit(s) and outdoor unit is to be
The indoor unit coil is constructed with grooved design copper tubes
a minimum of 18 AWG, 2 conductor, stranded and shielded cable
with slit coil fins, two (2) to three (3) rows, eighteen (18) to
(RS-485), terminated via screw terminals on the control boards.
twenty-one (21) fins per inch.
The microprocessor control provides the following functions: auto
addressing, self-diagnostics, auto restart following power restoration, Controls Features
test run, and will operate the indoor unit using one of five operating • Auto changeover • Group control
modes: (Heat Recovery only) • External static pressure control
1. Auto Changeover (Heat Recovery only) • Auto operation • Hot start
2. Heating • Auto restart • Self diagnostics
3. Cooling • Child lock • Timer (on / off)
4. Dry • Dual thermistor control • Weekly schedule
5. Fan Only • Dual set-point control • Fan speed control
For Heat Recovery systems the Auto Changeover setting automati- • Filter life and power consump- • Ventilation (outside air)
cally switches control of the indoor unit between cooling and heating tion display
modes based on space temperature conditions. • Multiple auxiliary heater
For Heat Pump systems, heated or cooled air delivery is dependent applications
Due to our policy of continuous product innovation, some specifications may change without notification.
54 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED LOW STATIC
General Data
L1, L2, L3 Units

Table 43: Ducted Low Static (L1, L2, L3 Frames) Indoor Unit General Data.
Model No. ARNU073L1G4 ARNU093L1G4 ARNU123L2G4 ARNU153L2G4 ARNU183L2G4 ARNU243L3G4
Cooling Mode Performance
Capacity (Btu/h) 7,500 9,600 12,300 15,400 19,100 24,000
Power Input1 (W) 40 40 85 85 85 115
Heating Mode Performance
Capacity (Btu/h) 8,500 10,900 13,600 17,100 21,500 27,300
Power Input (W) 1
40 40 85 85 85 115
Entering Mixed Air
Cooling Max. (°F WB) 76 76 76 76 76 76
Heating Min. (°F DB) 59 59 59 59 59 59
Unit Data
Refrigerant Type2 R410A R410A R410A R410A R410A R410A
Refrigerant Control EEV EEV EEV EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
27 / 26 / 23 30 / 26 / 23 31 / 29 / 26 34 / 31 / 29 36 / 34 / 31 39 / 35 / 32

Ducted Low Static


Net Unit Weight (lbs.) 38.6 38.6 50.7 50.7 50.7 59.5
Shipping Weight (lbs.) 47.4 47.4 60.6 60.6 60.6 68.3
Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
Fan
Type Sirocco Sirocco Sirocco Sirocco Sirocco Sirocco
Motor 1 1 2 2 2 2
Housing 2 2 3 3 3 4
Motor/Drive Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM) 270 / 230 / 200 320 / 250 / 200 360 / 310 / 250 450 / 360 / 310 530 / 450 / 360 710 / 570 / 430
Standard Mode
Airflow Rate H/M/L (CFM) 270 / 230 / 200 320 / 250 / 200 360 / 310 / 250 450 / 360 / 310 530 / 450 / 360 710 / 570 / 430
High Mode (Factory Set)
External Static Pressure (in. wg) 0 0 0 0 0 0
Standard Mode
External Static Pressure (in. wg) 0.1 0.1 0.1 0.1 0.1 0.1
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.) 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 3/8 Flare
Vapor Line (in., O.D.) 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 5/8 Flare
Condensate Line (in., I.D.) 1 1 1 1 1 1
EEV: Electronic Expansion Valve 1
Power Input is rated at high speed.
Power wiring is field supplied and must comply with the applicable local and national codes. 2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
This unit comes with a dry nitrogen charge. R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units. All capacities are net with a combination ratio between
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
95-105%. 4
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet with applicable and national code. Ensure the communication cable is properly grounded at the master
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB). outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor
ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 55
DUCTED LOW Static
Electrical Data

Table 44: Ducted Low Static (L1, L2, L3 Frames) Indoor Unit Electrical Data.
Power Supply Power Input (W)
Model Voltage Range MCA MOP Rated Amps (A)
Hz Volts Phase Cooling Heating
L1 Units
ARNU073L1G4 0.5 0.4 40 40
208-230 15 60 208-230 1
ARNU093L1G4 0.5 0.4 40 40
L2 Units
ARNU123L2G4 1.0 0.76 85 85
ARNU153L2G4 208-230 1.0 15 0.76 60 208-230 1 85 85
MULTI V Ducted Indoor Unit Engineering Manual

ARNU183L2G4 1.0 0.76 85 85


L3 Units
ARNU243L3G4 208-2300 1.2 15 0.97 60 208-230 1 115 115
MCA : Minimum Circuit Ampacity. Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
MOP : Maximum Overcurrent Protection. Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.

Due to our policy of continuous product innovation, some specifications may change without notification.
56 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED LOW STATIC
External Dimensions
L1, L2, L3 Units

Figure 24: ARNU073-093L1G4, ARNU123~183L2G4, ARNU243L3G4 Dimensions.

13/16 D
Air Outlet

5-5/16

Ducted Low Static


1-3/8
7-1/2
3-15/16
3-11/16

Vapor Pipe Connection


2-5/8 4-11/16

Liquid Pipe Connection


11-1/2

Drain Pipe Connection


27-9/16
24-3/4
8-11/16

Power Supply Connection

L1 : 14-7/16
L2 : 22-1/16
L3 : 29-3/4 C

Air Inlet
13/16
6-1/16
7-1/2

L1 : 2-15/16
L2 : 3-1/16
L3 : 3-3/16

B
A

A B C D
ARNU073L1G4
30-1/2 27-9/16 28-7/8 26
Center of Gravity ARNU093L1G4
ARNU123L2G4
Unit: inches ARNU153L2G4 38-3/8 35-7/16 36-3/4 33-7/8
Note: All measurements ARNU183L2G4
have a tolerance of ±1/4 in. ARNU243L3G4 46-1/4 43-5/16 44-5/8 41-3/4

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 57
DUCTED LOW Static
Electrical Wiring Diagram
L1 Units

Figure 25: ARNU073L1G4, ARNU093L1G4 Wiring Diagram.


MULTI V Ducted Indoor Unit Engineering Manual

Due to our policy of continuous product innovation, some specifications may change without notification.
58 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Low Static
Electrical Wiring Diagram
L1 Units

Table 45: L1 Unit Wiring Diagram Legend.


Terminal Purpose Function
CN-POWER AC Power supply AC Power line
CN-MOTOR1 Fan motor output Motor output of BLDC
CN-VM Sub PC power supply Power supply connection
CN-FLOAT Float switch input Float switch sensing
CN-ZONE Zone controller Zone controller connection
CN-EEV EEV Output EEV control output
CN-OPTION Optional PCB EPROM Option PCB connection
CN-DISPLAY Display Display of indoor status
CN-CC Dry contact Dry Contact connection
CN-PTC Auxiliary heater Connection for Auxiliary Heater
CN-PIPE/OUT Discharge pipe sensor Pipe out thermistor
CN-LEAK Refrigerant leak detector Refrigerant leak detector connection
CN-PIPE/IN Suction pipe sensor Pipe in thermistor

Ducted Low Static


CN-REMO Wired remote controller Wired remote control connection
CN-ROOM Room sensor Room air thermistor
CN-D/PUMP Drain pump output AC output for drain pump
CN-485 Communication Connection between indoor and outdoor units

Table 46: L1 Unit DIP Switch Settings.


DIP Switch Setting Off On Remarks
SW3 GROUP Master Slave Group Control setting using 7-Day Programmable Controller
Dry Contact Mode Setting
1. Variable: Auto/Manual Mode can be chosen by 7-Day Programmable Controller or
SW4 DRY CONTACT Variable Auto
Wireless Remote Controller (when shipped from factory -> Manual Mode)
2. Auto: For Dry Contact, it is always Auto mode
-OFF: Default (does not operate continuously)
SW5 EXTRA 1 Off On
-ON: Fan operates continuously
COMMUNICATIONS -OFF: 1.2kbps
SW8 Gen. 2 Gen. 4
RATE -ON: 9.6kbps
For Multi V systems, DIP switches 1, 2, 6, and 7 must be set to OFF. These DIP switches are used for other models.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 59
DUCTED LOW Static
Electrical Wiring Diagram
L2, L3 Units

Figure 26: ARNU123L2G4, ARNU153L2G4, ARNU183L2G4, ARNU243L3G4 Wiring Diagram.


MULTI V Ducted Indoor Unit Engineering Manual

Due to our policy of continuous product innovation, some specifications may change without notification.
60 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Low Static
Electrical Wiring Diagram
L2, L3 Units

Table 47: L2, L3 Unit Wiring Diagram Legend.


Terminal Purpose Function
CN-POWER AC Power supply AC Power line
CN-MOTOR1 Fan motor output Motor output of BLDC
CN-MOTOR2 Fan motor output Motor output of BLDC
CN-VM Sub PC power supply Power supply connection
CN-FLOAT Float switch input Float switch sensing
CN-ZONE Zone controller Zone controller connection
CN-EEV EEV Output EEV control output
CN-OPTION Optional PCB EPROM Option PCB connection
CN-DISPLAY Display Display of indoor status
CN-CC Dry contact Dry Contact connection
CN-PTC Auxiliary heater Connection for Auxiliary Heater
CN-PIPE/OUT Discharge pipe sensor Pipe out thermistor
CN-LEAK Refrigerant leak detector Refrigerant leak detector connection

Ducted Low Static


CN-PIPE/IN Suction pipe sensor Pipe in thermistor
CN-REMO Wired remote controller Wired remote control connection
CN-ROOM Room sensor Room air thermistor
CN-D/PUMP Drain pump output AC output for drain pump
CN-485 Communication Connection between indoor and outdoor units

Table 48: L2, L3 Unit DIP Switch Settings.


DIP Switch Setting Off On Remarks
SW3 GROUP Master Slave Group Control setting using 7-Day Programmable Controller
Dry Contact Mode Setting
1. Variable: Auto/Manual Mode can be chosen by 7-Day Programmable Controller or
SW4 DRY CONTACT Variable Auto
Wireless Remote Controller (when shipped from factory -> Manual Mode)
2. Auto: For Dry Contact, it is always Auto mode
-OFF: Default (does not operate continuously)
SW5 EXTRA 1 Off On
-ON: Fan operates continuously
COMMUNICATIONS -OFF: 1.2kbps
SW8 Gen. 2 Gen. 4
RATE -ON: 9.6kbps
For Multi V systems, DIP switches 1, 2, 6, and 7 must be set to OFF. These DIP switches are used for other models.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 61
DUCTED LOW Static
Refrigerant Flow Diagram
L1, L2, L3 Units

Figure 27: L1, L2, L3 Unit Refrigerant Flow Diagram.

Cooling
Heat Exchanger EEV Heating
Filter

TH3 TH2
Sirocco Fan Filter
MULTI V Ducted Indoor Unit Engineering Manual

TH1 lndoor unit

Table 49: L1, L2, L3 Unit Refrigerant Pipe Connection Port Diameters.
Model Liquid (inch) Vapor (inch)
L1 Units
ARNU073L1G4
1/4 Flare 1/2 Flare
ARNU093L1G4
L2 Units
ARNU123L2G4
ARNU153L2G4 1/4 Flare 1/2 Flare
ARNU183L2G4
L3 Units
ARNU243L3G4 3/8 Flare 5/8 Flare

Table 50: L1, L2, L3 Unit Thermistors.


Thermistor Description
TH1 Return air thermistor
TH2 Pipe in thermistor
TH3 Pipe out thermistor

Due to our policy of continuous product innovation, some specifications may change without notification.
62 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED LOW Static
External Static Pressure and Air Flow Tables
L1, L2, L3 Units

Table 51: L1 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0 0.04 0.08 0.11 0.15 0.19
65 178 - - - - -
70 198 171 - - - -
75 219 192 161 - - -
80 240 214 183 - - -
85 262 236 205 170 - -
90 284 258 227 192 - -
95 308 281 251 215 176 -
100 331 305 274 239 199 -
105 356 329 299 263 224 180
110 - 354 324 288 249 205
115 - - 349 314 274 230
120 - - - 340 300 256
125 - - - 367 327 283
130 - - - - 354 310
Table 52: L2 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)

Ducted Low Static


Set Value
0 0.04 0.08 0.11 0.15 0.19
75 230 - - - - -
80 259 237 - - - -
85 290 267 236 - - -
90 320 298 267 229 - -
95 352 329 299 260 - -
100 384 361 331 292 246 -
105 417 394 363 325 279 224
110 450 427 396 358 312 258
115 484 461 430 392 346 292
120 518 495 465 427 380 326
125 553 530 500 461 415 361
130 589 566 536 497 451 397
135 - - 572 534 487 433
Table 53: L3 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0 0.04 0.08 0.11 0.15 0.19
85 360 - - - - -
90 430 392 378 - - -
95 488 436 431 - - -
100 536 484 473 378 - -
105 576 524 507 419 - -
110 612 560 538 454 388 -
115 646 594 568 488 422 -
120 681 629 598 523 456 371
125 719 667 632 561 494 409
130 763 711 672 606 539 453
135 - 765 719 659 592 507
139 - - 745 673 613 540
1. All static pressure air flow rates are listed in CFM.
2. The tables above show the correlation between air flow rates and external static pressure.
3. The tables above show the available external static pressure range.

If the external static pressure of the installed indoor unit is less than the lowest value (as mentioned in the table), the indoor unit components
can fail.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 63
Ducted Low Static
External Static Pressure and Air Flow Charts
L1, L2, L3 Units

Figure 28: L1 Unit External Static Pressure and Air Flow Chart.
0.2
0.18
External Stac Pressure(in-wg)

0.16
ESP
0.14 Setting
120
0.12 ESP
Setting
0.1 110
ESP
0.08 Setting
100
0.06 ESP
Setting
MULTI V Ducted Indoor Unit Engineering Manual

0.04 90
ESP
0.02 Setting
80
0
180.0 230.0 280.0 330.0
Air Flow(cfm)

Figure 29: L2 Unit External Static Pressure and Air Flow Chart.
0.2
0.18
External Stac Pressure(in-wg)

0.16
0.14
ESP
0.12 Setting
130
0.1 ESP
Setting
0.08 ESP 120
0.06 Setting
ESP 110
0.04 ESP Setting
Setting 100
0.02 90
0
200.0 300.0 400.0 500.0 600.0
Air Flow(cfm)

Figure 30: L3 Unit External Static Pressure and Air Flow Chart.
0.2
0.18
External Stac Pressure(in-wg)

0.16
0.14
0.12
0.1
0.08 ESP
Setting
0.06 135
ESP
0.04 Setting
ESP ESP ESP ESP 130
0.02 Setting Setting Setting Setting
90 100 110 120
0
350.0 450.0 550.0 650.0 750.0
Air Flow(cfm))

Due to our policy of continuous product innovation, some specifications may change without notification.
64 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED LOW Static
External Static Pressure Ranges
L1, L2, L3 Units

Table 54: L1 Unit External Static Pressure Ranges.


Model Capacity (MBh) Mode Setting Value Standard ESP (in. wg) CFM Min. ESP (in. wg) Max. ESP (in. wg)
High 100 265
High
Mid 93 0 230 - 0.2
(Factory Set)
Low 86 194
ARNU073L1G4 7.5
High 86 265
Standard Mid 78 0.1 230 - 0.2
Low 69 194
High 113 318
High
Mid 97 0 247 - 0.2
(Factory Set)
Low 86 194
ARNU093L1G4 9.6
High 97 318
Standard Mid 81 0.1 247 0.2
Low 69 194

Table 56: L2 Unit External Static Pressure Ranges.


Model Capacity (MBh) Mode Setting Value Standard ESP (in. wg) CFM Min. ESP (in. wg) Max. ESP (in. wg)
High 105 353

Ducted Low Static


High
Mid 96 0 300 - 0.2
(Factory Set)
Low 89 247
ARNU123L2G4 12.3
High 96 353
Standard Mid 87 0.1 300 - 0.2
Low 78 247
High 119 442
High
Mid 105 0 353 - 0.2
(Factory Set)
Low 96 300
ARNU153L2G4 15.4
High 109 442
Standard Mid 96 0.1 353 - 0.2
Low 87 300
High 131 530
High
Mid 119 0 442 - 0.2
(Factory Set)
Low 105 353
ARNU183L2G4 19.1
High 120 530
Standard Mid 109 0.1 442 - 0.2
Low 96 353

Table 55: L3 Unit External Static Pressure Ranges.


Model Capacity (MBh) Mode Setting Value Standard ESP (in. wg) CFM Min. ESP (in. wg) Max. ESP (in. wg)
High 139 707
High
Mid 118 0 565 - 0.2
(Factory Set)
Low 105 424
ARNU243L3G4 24.0
High 125 707
Standard Mid 102 0.1 565 - 0.2
Low 89 424

The tables above show the available E.S.P. range.


Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 65
Ducted Low Static
Acoustic Data
Sound Pressure Levels

Figure 31: Sound Pressure Measurement Location. • Measurements are taken 4.9 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of ±3.
DISCHARGE SUCTION • Sound pressure levels are tested in an anechoic chamber under ISO Standard
3745.
DUCT DUCT Operating Conditions:
• Power source: 220V/60 Hz
• Sound level will vary depending on a range of factors including the construc-
3.3 ft.
4.9 ft.

6.6 ft. tion (acoustic absorption coefficient) of a particular room in which the unit was
installed.
MULTI V Ducted Indoor Unit Engineering Manual

Table 57: Ducted Low Static Sound Pressure Levels.


Sound Pressure Levels dB(A)
Model
High Fan Speed Medium Fan Speed Low Fan Speed
L1 Units
ARNU073L1G4 27 26 23
ARNU093L1G4 30 26 23
L2 Units
ARNU123L2G4 31 29 26
ARNU153L2G4 34 31 29
ARNU183L2G4 36 34 31
L3 Units
ARNU243L3G4 39 35 32

Figure 32: ARNU073L1G4, ARNU093L1G4, and ARNU123L2G4 Sound Pressure Level Diagrams.
ARNU073L1G4 ARNU093L1G4 ARNU123L2G4

Due to our policy of continuous product innovation, some specifications may change without notification.
66 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Low Static
Acoustic Data
Sound Pressure Levels / Sound Power Levels

Figure 33: ARNU153L2G4, ARNU183L2G4, and ARNU243L3G4 Sound Pressure Level Diagrams.
ARNU153L2G4 ARNU183L2G4 ARNU243L3G4

Ducted Low Static


Sound Power Levels
Table 58: Ducted Low Static Sound Power Levels. • Data is valid under diffuse field conditions.
Model Sound Power Levels dB(A) • Data is valid under nominal operating conditions.
L1 Units • Sound power level is measured using rated conditions, and tested
ARNU073L1G4 48 in a reverberation room per ISO 3741 standards.
ARNU093L1G4 49 • Sound level will vary depending on a range of factors such as
L2 Units construction (acoustic absorption coefficient) of particular area in
ARNU123L2G4 52 which the equipment is installed.
ARNU153L2G4 53 • Reference acoustic intensity: 0dB = 10E-6μW/m2
ARNU183L2G4 54
L3 Units
ARNU243L3G4 58

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 67
Ducted Low Static
Acoustic Data
Sound Power Levels

Figure 34: ARNU073L1G4, ARNU093L1G4, and ARNU123L2G4 Sound Power Level Diagrams.
ARNU073L1G4 ARNU093L1G4 ARNU123L2G4
MULTI V Ducted Indoor Unit Engineering Manual

Figure 35: ARNU153L2G4, ARNU183L2G4, and ARNU243L3G4 Sound Power Level Diagrams.
ARNU153L2G4 ARNU183L2G4 ARNU243L3G4

Due to our policy of continuous product innovation, some specifications may change without notification.
68 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Low Static
Cooling Capacity Tables
ARNU073L1G4, ARNU093L1G4, ARNU123L2G4

Table 59: ARNU073L1G4, ARNU093L1G4, ARNU123L2G4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.7 6.1
25 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.7 6.1
30 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.7 6.1
35 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.7 6.1
40 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.7 6.1
45 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.7 6.1
50 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.7 6.1
55 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.7 6.1
60 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.6 6.1
ARNU073L1G4 /
65 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.4 6.0
7.5
70 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.3 5.9
75 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.9 6.1 9.1 5.8
80 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.4 6.2 8.7 6.1 8.8 5.7
85 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.3 6.1 8.4 5.8 8.6 5.5
90 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.2 6.0 8.3 5.7 8.4 5.5
95 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 8.0 6.0 8.2 5.7 8.3 5.4
100 4.9 4.4 6.0 5.1 6.8 5.4 7.5 5.8 7.9 5.9 8.0 5.6 8.2 5.4
105 4.9 4.4 5.7 4.8 6.4 5.2 7.2 5.5 7.3 5.5 7.7 5.5 7.9 5.2
110 4.8 4.3 5.4 4.6 6.0 4.8 6.8 5.2 6.9 5.2 7.3 5.2 7.7 5.1

Ducted Low Static


23 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6
25 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6
30 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6
35 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6
40 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6
45 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6
50 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6
55 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6
60 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.3 7.6
ARNU093L1G4 /
65 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.1 7.5
9.6
70 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 11.9 7.4
75 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 11.6 7.2
80 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.1 7.6 11.3 7.2
85 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.6 7.6 10.8 7.3 11.0 6.9
90 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.5 7.5 10.6 7.2 10.8 6.8
95 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.3 7.5 10.5 7.1 10.6 6.7
100 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.1 7.4 10.3 7.0 10.5 6.7
105 6.3 5.5 7.3 6.0 8.2 6.5 9.2 6.9 9.4 6.9 9.9 6.8 10.1 6.5
110 6.2 5.3 6.9 5.7 7.7 6.0 8.6 6.5 8.8 6.5 9.4 6.5 9.8 6.3
23 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.9 9.4
25 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.9 9.4
30 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.9 9.4
35 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.9 9.4
40 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.9 9.4
45 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.9 9.4
50 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.9 9.4
55 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.9 9.4
60 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.7 9.4
ARNU123L2G4 /
65 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.5 9.2
12.3
70 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 15.3 9.1
75 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.7 9.4 14.9 8.9
80 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.2 9.4 14.5 8.8
85 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.6 9.4 13.8 9.0 14.0 8.5
90 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.4 9.3 13.5 8.8 13.8 8.4
95 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.2 9.2 13.4 8.8 13.6 8.3
100 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 12.9 9.1 13.2 8.7 13.4 8.2
105 8.1 6.8 9.3 7.4 10.6 8.0 11.8 8.5 12.0 8.5 12.7 8.4 12.9 8.0
110 7.9 6.6 8.9 7.0 9.8 7.4 11.1 8.0 11.3 8.0 12.0 8.0 12.6 7.8
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 69
Ducted Low Static
Cooling Capacity Tables
ARNU153L2G4, ARNU183L2G4, ARNU243L3G4

Table 60: ARNU153L2G4, ARNU183L2G4, ARNU243L3G4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.9 12.0
25 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.9 12.0
30 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.9 12.0
35 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.9 12.0
40 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.9 12.0
45 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.9 12.0
50 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.9 12.0
55 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.9 12.0
60 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.7 11.9
MULTI V Ducted Indoor Unit Engineering Manual

ARNU153L2G4 /
65 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.4 11.7
15.4
70 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 19.1 11.5
75 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 18.4 12.0 18.6 11.3
80 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.3 12.1 17.8 11.9 18.2 11.2
85 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 17.1 12.0 17.3 11.4 17.6 10.8
90 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 16.8 11.8 16.9 11.2 17.3 10.7
95 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 16.5 11.7 16.8 11.2 17.1 10.5
100 10.1 8.6 12.3 10.0 13.9 10.6 15.4 11.3 16.2 11.5 16.5 11.0 16.8 10.5
105 10.1 8.6 11.7 9.4 13.2 10.1 14.8 10.8 15.1 10.8 15.8 10.7 16.2 10.2
110 9.9 8.4 11.1 8.9 12.3 9.4 13.9 10.1 14.2 10.1 15.1 10.1 15.7 9.9
23 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
25 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
30 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
35 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
40 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
45 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
50 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
55 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.7 14.8
60 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.4 14.8
ARNU183L2G4 /
65 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 24.0 14.5
19.1
70 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 23.7 14.3
75 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.8 14.8 23.1 14.0
80 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.4 15.0 22.1 14.8 22.5 13.9
85 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 21.2 14.8 21.4 14.1 21.8 13.4
90 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 20.9 14.6 21.0 13.9 21.4 13.2
95 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 20.5 14.5 20.9 13.8 21.2 13.0
100 12.6 10.7 15.3 12.3 17.2 13.1 19.1 14.0 20.1 14.3 20.5 13.7 20.9 13.0
105 12.6 10.7 14.5 11.7 16.4 12.6 18.3 13.4 18.7 13.4 19.7 13.2 20.1 12.6
110 12.3 10.4 13.8 11.1 15.3 11.7 17.2 12.6 17.6 12.6 18.7 12.6 19.5 12.3
23 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
25 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
30 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
35 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
40 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
45 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
50 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
55 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 31.0 19.4
60 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 30.7 19.3
ARNU243L3G4 /
65 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 30.2 19.0
24.2
70 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 29.8 18.7
75 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 28.6 19.4 29.0 18.3
80 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.9 19.6 27.8 19.3 28.3 18.2
85 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.6 19.4 26.9 18.5 27.4 17.4
90 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 26.2 19.1 26.4 18.2 26.9 17.2
95 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 25.7 19.0 26.2 18.0 26.6 17.0
100 15.8 13.9 19.2 16.1 21.6 17.1 24.0 18.3 25.2 18.7 25.7 17.8 26.2 16.9
105 15.8 13.9 18.2 15.3 20.6 16.4 23.0 17.4 23.5 17.4 24.7 17.2 25.2 16.5
110 15.4 13.5 17.3 14.5 19.2 15.3 21.6 16.4 22.1 16.4 23.5 16.4 24.5 16.0
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
70 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Low Static
Heating Capacity Tables
ARNU073L1G4, ARNU093L1G4, ARNU123L2G4, ARNU153L2G4

Table 61: ARNU073L1G4, ARNU093L1G4, ARNU123L2G4, ARNU153L2G4 Heating Capacity Table.


Indoor Air Temperature (°F DB)
Outdoor Air Temp. 59 61 64 67 70 73 76 80
Model No. /
Capacity Index TC TC TC TC TC TC TC TC
°F DB °F WB MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 5.7 5.7 5.7 5.7 5.6 5.6 5.6 5.6
0 -0.4 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.8
5.0 4.5 6.6 6.5 6.5 6.5 6.5 6.5 6.5 6.5
10.0 9.0 6.9 6.9 6.9 6.8 6.8 6.8 6.8 6.8
15.0 14.0 7.3 7.3 7.3 7.3 7.3 7.3 7.2 7.1
20.0 19.0 7.7 7.7 7.7 7.7 7.6 7.6 7.4 7.4
25.0 23.0 8.1 8.1 8.1 8.1 8.1 7.9 7.8 7.4
ARNU073L1G4 /
30.0 28.0 8.2 8.2 8.2 8.2 8.2 8.1 7.8 7.4
7.5
35.0 32.0 8.5 8.5 8.5 8.5 8.4 8.2 7.8 7.4
40.0 36.0 8.8 8.8 8.8 8.8 8.5 8.2 7.8 7.4
45.0 41.0 9.2 9.2 9.2 8.9 8.5 8.2 7.8 7.4
47.0 43.0 9.5 9.4 9.4 8.9 8.5 8.2 7.8 7.4
50.0 46.0 10.2 9.8 9.4 8.9 8.5 8.2 7.8 7.4
55.0 51.0 10.4 9.9 9.4 8.9 8.5 8.2 7.8 7.4
60.0 56.0 10.4 9.9 9.4 8.9 8.5 8.2 7.8 7.4
-4 -4.4 7.3 7.3 7.3 7.3 7.2 7.2 7.2 7.2
0 -0.4 7.5 7.5 7.5 7.5 7.5 7.4 7.4 7.4
5.0 4.5 8.5 8.4 8.3 8.3 8.3 8.3 8.3 8.3
10.0 9.0 8.8 8.8 8.8 8.7 8.7 8.7 8.7 8.7

Ducted Low Static


15.0 14.0 9.4 9.4 9.4 9.4 9.4 9.4 9.3 9.2
20.0 19.0 9.9 9.9 9.9 9.9 9.7 9.7 9.5 9.4
25.0 23.0 10.4 10.4 10.4 10.4 10.4 10.1 10.0 9.5
ARNU093L1G4 /
30.0 28.0 10.6 10.6 10.6 10.6 10.6 10.4 10.0 9.5
9.6
35.0 32.0 10.9 10.9 10.9 10.9 10.8 10.6 10.0 9.5
40.0 36.0 11.3 11.3 11.3 11.3 10.9 10.6 10.0 9.5
45.0 41.0 11.8 11.8 11.8 11.4 10.9 10.6 10.0 9.5
47.0 43.0 12.2 12.1 12.0 11.4 10.9 10.6 10.0 9.5
50.0 46.0 13.1 12.5 12.0 11.4 10.9 10.6 10.0 9.5
55.0 51.0 13.4 12.6 12.0 11.4 10.9 10.6 10.0 9.5
60.0 56.0 13.4 12.6 12.0 11.4 10.9 10.6 10.0 9.5
-4 -4.4 9.1 9.1 9.1 9.1 9.0 9.0 9.0 9.0
0 -0.4 9.4 9.4 9.4 9.4 9.4 9.2 9.2 9.2
5.0 4.5 10.6 10.5 10.3 10.3 10.3 10.3 10.3 10.3
10.0 9.0 11.0 11.0 11.0 10.9 10.9 10.9 10.9 10.9
15.0 14.0 11.7 11.7 11.7 11.7 11.7 11.7 11.6 11.4
20.0 19.0 12.4 12.4 12.4 12.4 12.1 12.1 11.9 11.8
25.0 23.0 12.9 12.9 12.9 12.9 12.9 12.6 12.5 11.9
ARNU123L2G4 /
30.0 28.0 13.2 13.2 13.2 13.2 13.2 12.9 12.5 11.9
12.3
35.0 32.0 13.6 13.6 13.6 13.6 13.5 13.2 12.5 11.9
40.0 36.0 14.1 14.1 14.1 14.1 13.6 13.2 12.5 11.9
45.0 41.0 14.7 14.7 14.7 14.3 13.6 13.2 12.5 11.9
47.0 43.0 15.2 15.1 15.0 14.3 13.6 13.2 12.5 11.9
50.0 46.0 16.3 15.6 15.0 14.3 13.6 13.2 12.5 11.9
55.0 51.0 16.7 15.8 15.0 14.3 13.6 13.2 12.5 11.9
60.0 56.0 16.7 15.8 15.0 14.3 13.6 13.2 12.5 11.9
-4 -4.4 11.5 11.5 11.5 11.5 11.3 11.3 11.3 11.3
0 -0.4 11.8 11.8 11.8 11.8 11.8 11.6 11.6 11.6
5.0 4.5 13.3 13.2 13.0 13.0 13.0 13.0 13.0 13.0
10.0 9.0 13.9 13.9 13.9 13.7 13.7 13.7 13.7 13.7
15.0 14.0 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.4
20.0 19.0 15.6 15.6 15.6 15.6 15.2 15.2 15.0 14.8
25.0 23.0 16.2 16.2 16.2 16.2 16.2 15.9 15.7 15.0
ARNU153L2G4 /
30.0 28.0 16.6 16.6 16.6 16.6 16.6 16.2 15.7 15.0
15.4
35.0 32.0 17.1 17.1 17.1 17.1 16.9 16.6 15.7 15.0
40.0 36.0 17.8 17.8 17.8 17.8 17.1 16.6 15.7 15.0
45.0 41.0 18.5 18.5 18.5 18.0 17.1 16.6 15.7 15.0
47.0 43.0 19.2 19.0 18.8 18.0 17.1 16.6 15.7 15.0
50.0 46.0 20.5 19.7 18.8 18.0 17.1 16.6 15.7 15.0
55.0 51.0 20.9 19.8 18.8 18.0 17.1 16.6 15.7 15.0
60.0 56.0 20.9 19.8 18.8 18.0 17.1 16.6 15.7 15.0
TC: Total Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Low Static | 71
Ducted Low Static
Heating Capacity Tables
ARNU183L2G4, ARNU243L3G4

Table 62: ARNU183L2G4, ARNU243L3G4 Heating Capacity Table.


Indoor Air Temperature (°F DB)
Outdoor Air Temp. 59 61 64 67 70 73 76 80
Model No. /
Capacity Index TC TC TC TC TC TC TC TC
°F DB °F WB MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 14.4 14.4 14.4 14.4 14.2 14.2 14.2 14.2
0 -0.4 14.8 14.8 14.8 14.8 14.8 14.6 14.6 14.6
5.0 4.5 16.8 16.6 16.3 16.3 16.3 16.3 16.3 16.3
10.0 9.0 17.4 17.4 17.4 17.2 17.2 17.2 17.2 17.2
15.0 14.0 18.5 18.5 18.5 18.5 18.5 18.5 18.3 18.1
20.0 19.0 19.6 19.6 19.6 19.6 19.1 19.1 18.8 18.6
25.0 23.0 20.4 20.4 20.4 20.4 20.4 20.0 19.8 18.8
ARNU183L2G4 /
30.0 28.0 20.9 20.9 20.9 20.9 20.9 20.4 19.8 18.8
19.1
35.0 32.0 21.5 21.5 21.5 21.5 21.3 20.9 19.8 18.8
MULTI V Ducted Indoor Unit Engineering Manual

40.0 36.0 22.4 22.4 22.4 22.4 21.5 20.9 19.8 18.8
45.0 41.0 23.2 23.2 23.2 22.6 21.5 20.9 19.8 18.8
47.0 43.0 24.1 23.9 23.7 22.6 21.5 20.9 19.8 18.8
50.0 46.0 25.8 24.7 23.7 22.6 21.5 20.9 19.8 18.8
55.0 51.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
60.0 56.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
-4 -4.4 18.3 18.3 18.3 18.3 18.0 18.0 18.0 18.0
0 -0.4 18.8 18.8 18.8 18.8 18.8 18.6 18.6 18.6
5.0 4.5 21.3 21.0 20.7 20.7 20.7 20.7 20.7 20.7
10.0 9.0 22.1 22.1 22.1 21.8 21.8 21.8 21.8 21.8
15.0 14.0 23.5 23.5 23.5 23.5 23.5 23.5 23.2 22.9
20.0 19.0 24.8 24.8 24.8 24.8 24.3 24.3 23.9 23.6
25.0 23.0 25.9 25.9 25.9 25.9 25.9 25.4 25.1 23.9
ARNU243L3G4 /
30.0 28.0 26.5 26.5 26.5 26.5 26.5 25.9 25.1 23.9
24.2
35.0 32.0 27.3 27.3 27.3 27.3 27.0 26.5 25.1 23.9
40.0 36.0 28.4 28.4 28.4 28.4 27.3 26.5 25.1 23.9
45.0 41.0 29.5 29.5 29.5 28.7 27.3 26.5 25.1 23.9
47.0 43.0 30.6 30.3 30.0 28.7 27.3 26.5 25.1 23.9
50.0 46.0 32.8 31.4 30.0 28.7 27.3 26.5 25.1 23.9
55.0 51.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.9
60.0 56.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.9
TC: Total Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
72 | Low STATIC © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CEILING-CONCEALED
DUCTED
BUILT IN
Mechanical Specifications on page 74
General Data on page 75
Electrical Data on page 76
External Dimensions on page 77
Electrical Wiring Diagram on page 78
Refrigerant Flow Diagrams on page 80
External Static Pressure and Air Flow on page 81
External Static Pressure Ranges on page 83
Acoustic Data on page 84
Capacity Tables on page 87
Optional Accessories on page 91
DUCTED Built In
Mechanical Specifications

Casing upon outdoor unit


The case is designed to mount concealed above a finished ceiling. operating mode.
Supply air is front horizontal with a dedicated bottom vertical return. In Heating mode, the
The unit is manufactured with coated metal. Cold surfaces are microprocessor control
covered with a coated polystyrene insulating material. The case is will activate the indoor
provided with hanger brackets designed to support the unit weight on unit when indoor room
four corners. Hanger brackets have pre-punched holes designed to temperature falls below
accept field-supplied all-thread rod hangers. set-point tempera-
ture and signals the
Fan Assembly and Control outdoor unit to begin
The unit has Sirocco fans made of high strength ABS HR-2407 the heating cycle. The indoor unit fan operation is delayed until coil
polymeric resin. Fans are directly driven and mounted on a common pipe temperature reaches 76ºF. Significant airflow is generated when
shaft. The fan motor is a Brushless Digitally-Controlled (BLDC) pipe temperature reaches 80°F. In lieu of factory return air therm-
MULTI V Ducted Indoor Unit Engineering Manual

design with permanently lubricated and sealed ball bearings. The istor, screw terminals on the microprocessor circuit board accom-
fan motor includes thermal, overcurrent and low RPM protection. modate various models of wall-mounted local controllers and/or a
The fan/motor assembly is mounted on vibration attenuating rubber wall-mounted remote temperature sensor. The unit microprocessor
grommets. The fan impeller is statically and dynamically balanced. is capable of accepting space temperature readings concurrently or
The fan speed is controlled using a microprocessor based direct individually from either:
digital control algorithm that provides a high fan speed in cooling 1. Wall-mounted wired controller(s)
thermal ON and low fan speed in cooling thermal OFF, high fan 2. Factory mounted return air thermistor or the optional
speed in heating thermal ON and fan off in heating thermal OFF. The wall-mounted wired remote temperature sensor
fan speeds can be field adjusted between low, medium, and high A single indoor unit has the capability of being controlled by up to
speeds and DIP switch settings will allow the fan to run constantly two local wired controllers. The microprocessor controls space tem-
during defrost or oil return modes. Each setting can be field adjusted perature using the value provided by the temperature sensor sensing
from the factory setting (RPM / ESP) to compensate for a limited a space temperature that is farthest away from the temperature
amount of additional resistance to airflow caused by field connected set-point. The microprocessor control provides a cooling or heating
ductwork or other airflow restricting devices. mode test cycle that operates the unit for 18 minutes without regard
to the space temperature. If the system is provided with an optional
Ceiling Grille/Duct Kit wall-mounted local or central controller, displayed diagnostic codes
An optional flush-mounted ceiling return air grille and accordion-style are specific, alpha numeric, and provide the service technician with a
canvas duct kit provides a short-ducted return air solution. reason for the code displayed.

Air Filter Condensate Lift/Pump


Return air is filtered with a removable, washable filter with anti-fun- The indoor unit is provided with a factory installed and wired conden-
gal treatment. sate/lift pump capable of providing a minimum 27.5 inch lift from the
bottom exterior surface of the unit casing. The lift pump comes with a
Microprocessor Controls safety switch that will shut off indoor unit if condensate rises too high
The unit is provided with an integrated microprocessor-based con- in the drain pan.
troller. The controller is capable of performing functions necessary
to operate the system without the use of a wall-mounted controller. Condensate Drain Pan
A temperature thermistor is factory-mounted in the return air stream. The condensate drain pan is constructed of high impact polystyrene
All unit operation parameters, excluding the unit operating schedule, resin (HIPS).
are stored in non-volatile memory resident on the unit microproces-
sor. Operating schedules are stored in select models of the optional, Coil
wall-mounted, local or central controller. The field-supplied commu- The indoor unit coil is constructed with grooved design copper tubes
nication cable between the indoor unit(s) and outdoor unit is to be with slit coil fins, two (2) to three (3) rows, eighteen (18) to
a minimum of 18 AWG, 2 conductor, stranded, and shielded cable twenty-one (21) fins per inch.
(RS-485), terminated via screw terminals on the control boards. The
microprocessor control provides the following functions: auto address- Controls Features
ing, self-diagnostics, auto restart following power restoration, test run, • Auto changeover • Group control
and will operate the indoor unit using one of five operating modes: (Heat Recovery only) • External static pressure control
1. Auto Changeover (Heat Recovery only) • Auto operation • Hot start
2. Heating • Auto restart • Self diagnostics
3. Cooling • Child lock • Timer (on / off)
4. Dry • Dual thermistor control • Weekly schedule
5. Fan Only
• Dual set-point control • Fan speed control
For Heat Recovery systems the Auto Changeover setting
automatically switches control of the indoor unit between cooling and • Filter life and power consump- • Ventilation (outside air)
heating modes based on space temperature conditions. tion display
For Heat Pump systems, heated or cooled air delivery is dependent • Multiple auxiliary heater
applications
Due to our policy of continuous product innovation, some specifications may change without notification.
74 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED Built In
General Data
B3, B4 Units

Table 63: Ducted Built In (B3, B4 Frames) Indoor Unit General Data.
Model No. ARNU073B3G4 ARNU093B3G4 ARNU123B3G4 ARNU153B3G4 ARNU183B4G4 ARNU243B4G4
Cooling Mode Performance
Capacity (Btu/h) 7,500 9,600 12,300 15,400 19,100 24,200
Power Input1 (W) 85 85 85 85 115 115
Heating Mode Performance
Capacity (Btu/h) 8,500 10,900 13,600 17,100 21,500 27,300
Power Input (W) 1
85 85 85 85 115 115
Entering Mixed Air
Cooling Max. (°F WB) 76 76 76 76 76 76
Heating Min. (°F DB) 59 59 59 59 59 59
Unit Data
Refrigerant Type2 R410A R410A R410A R410A R410A R410A
Refrigerant Control EEV EEV EEV EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
33 / 32 / 29 34 / 33 / 32 35 / 34 / 33 41 / 40 / 37 43 / 40 / 37 46 / 43 / 37
Net Unit Weight (lbs.) 46.3 46.3 46.3 46.3 57.3 57.3

Ducted Built In
Shipping Weight (lbs.) 53.3 53.3 53.3 53.3 67.2 67.2
Communication Cable (No. x AWG) 4
2 x 18 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
Fan
Type Sirocco Sirocco Sirocco Sirocco Sirocco Sirocco
Motor 2 2 2 2 2 2
Housing 3 3 3 3 4 4
Motor/Drive Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM) 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353
Standard Mode
Airflow Rate H/M/L (CFM) 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353
High Mode (Factory Set)
External Static Pressure (in. wg) 0 0 0 0 0 0
Standard Mode
External Static Pressure (in. wg) 0.08 0.08 0.08 0.08 0.08 0.08
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.) 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 3/8 Flare
Vapor Line (in., O.D.) 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 5/8 Flare
Condensate Line (in., I.D.) 1 1 1 1 1 1
EEV: Electronic Expansion Valve 1
Power Input is rated at high speed.
Power wiring is field supplied and must comply with the applicable local and national codes. 2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
This unit comes with a dry nitrogen charge. R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units. All capacities are net with a combination ratio between
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
95-105%. 4
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet with applicable and national code. Ensure the communication cable is properly grounded at the master
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB). outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor
ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 75
DUCTED Built In
Electrical Data

Table 64: Ducted Built In (B3, B4 Frames) Indoor Unit Electrical Data.
Power Supply Power Input (W)
Model Voltage Range MCA MOP Rated Amps (A)
Hz Volts Phase Cooling Heating
B3 Units
ARNU073B3G4 1.0 0.76 85 85
ARNU093B3G4 1.0 0.76 85 85
208-230 15 60 208-230 1
ARNU123B3G4 1.0 0.76 85 85
ARNU153B3G4 1.0 0.76 85 85
B4 Units
MULTI V Ducted Indoor Unit Engineering Manual

ARNU183B4G4 1.2 0.97 115 115


208-230 15 60 208-230 1
ARNU243B4G4 1.2 0.97 115 115
MCA : Minimum Circuit Ampacity. Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
MOP : Maximum Overcurrent Protection. Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.

Due to our policy of continuous product innovation, some specifications may change without notification.
76 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED Built In
External Dimensions
B3, B4 Units

Figure 36: ARNU073~153B3G4, ARNU183-243B4G4 Dimensions.


With Suction Grill With Suction Grill With Suction Grill
& Suction Canvas & Suction Canvas

7-1/2
2-3/8
2-1/2
Return Air

1 8-1/2
10-7/8
Liquid
15-1/8
22-5/8

24-5/16
15-1/4
Vapor
Drain

Supply Air
B2

Ducted Built In
A1 With Suction Grill
Power Connection
A2 C2
7-7/16
9-13/16

With Suction Grill

Model A1
ARNU073B3G4
7-1/2
19-11/16 (Max)

ARNU093B3G4
32-5/8
ARNU123B3G4
ARNU153B3G4
C3

Unit: inches
ARNU183B4G4 Note: All measurements
A3 B3 43-5/16
With Suction Grill & Suction Canvas ARNU243B4G4 have a tolerance of ±1/4 in.

Accessory A2 B2 C2 Accessory A3 B3 C3
PBSGB30 35-13/16 14-1/8 2-3/16 PBSC30 32-5/16 10-11/16 1-9/16 to 9-13/16
PBSGB40 46-13/16 14-1/8 2-3/16 PBSC40 43-5/16 10-11/16 1-9/16 to 9-13/16

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 77
DUCTED Built In
Electrical Wiring Diagram
B3, B4 Units

Figure 37: ARNU073~153B3G4, ARNU183-243B4G4 Wiring Diagram.


MULTI V Ducted Indoor Unit Engineering Manual

Due to our policy of continuous product innovation, some specifications may change without notification.
78 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Built In
Electrical Wiring Diagram
B3, B4 Units

Table 65: B3, B4 Unit Wiring Diagram Legend.


Terminal Purpose Function
CN-POWER AC Power supply AC Power line
CN-MOTOR1 Fan motor output Motor output of BLDC
CN-MOTOR2 Fan motor output Motor output of BLDC
CN-VM Sub PC power supply Power supply connection
CN-FLOAT Float switch input Float switch sensing
CN-ZONE Zone controller Zone controller connection
CN-EEV EEV Output EEV control output
CN-OPTION Optional PCB EPROM Option PCB connection
CN-DISPLAY Display Display of indoor status
CN-CC Dry contact Dry Contact connection
CN-PTC Auxiliary heater Connection for Auxiliary Heater
CN-PIPE/OUT Discharge pipe sensor Pipe out thermistor
CN-LEAK Refrigerant leak detector Refrigerant leak detector connection

Ducted Built In
CN-PIPE/IN Suction pipe sensor Pipe in thermistor
CN-REMO Wired remote controller Wired remote control connection
CN-ROOM Room sensor Room air thermistor
CN-D/PUMP Drain pump output AC output for drain pump
CN-485 Communication Connection between indoor and outdoor units

Table 66: B3, B4 Unit DIP Switch Settings.


DIP Switch Setting Off On Remarks
SW3 GROUP Master Slave Group Control setting using 7-Day Programmable Controller
Dry Contact Mode Setting
1. Variable: Auto/Manual Mode can be chosen by 7-Day Programmable Controller or
SW4 DRY CONTACT Variable Auto
Wireless Remote Controller (when shipped from factory -> Manual Mode)
2. Auto: For Dry Contact, it is always Auto mode
-OFF: Default (does not operate continuously)
SW5 EXTRA 1 Off On
-ON: Fan operates continuously
COMMUNICATIONS -OFF: 1.2kbps
SW8 Gen. 2 Gen. 4
RATE -ON: 9.6kbps
For Multi V systems, DIP switches 1, 2, 6, and 7 must be set to OFF. These DIP switches are used for other models.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 79
DUCTED Built In
Refrigerant Flow Diagram
B3, B4 Units

Figure 38: B3, B4 Unit Refrigerant Flow Diagram.

Cooling
Heat Exchanger EEV Heating
Filter

TH3 TH2
Sirocco Fan Filter
MULTI V Ducted Indoor Unit Engineering Manual

TH1 lndoor unit

Table 67: B3, B4 Unit Refrigerant Pipe Connection Port Diameters.


Model Liquid (inch) Vapor (inch)
B3 Units
ARNU073B3G4
ARNU093B3G4
1/4 Flare 1/2 Flare
ARNU123B3G4
ARNU153B3G4
B4 Units
ARNU183B4G4 1/4 Flare 1/2 Flare
ARNU243B4G4 3/8 Flare 5/8 Flare

Table 68: B3, B4 Unit Thermistors.


Thermistor Description
TH1 Return air thermistor
TH2 Pipe in thermistor
TH3 Pipe out thermistor

Due to our policy of continuous product innovation, some specifications may change without notification.
80 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED Built In
External Static Pressure and Air Flow Tables
B3, B4 Units

Table 69: B3 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0 0.04 0.08 0.11 0.15
60 222 107 33 - -
65 234 171 54 - -
70 272 199 77 28 -
75 289 222 99 30 -
80 315 263 175 56 -
85 336 288 209 97 34
90 361 310 240 121 48
95 383 340 287 194 92
100 400 373 319 216 117
105 418 395 353 293 188
110 448 420 367 324 245
115 466 432 408 361 291

Ducted Built In
Table 70: B4 Unit External Static Pressure and Air Flow Table.
Static Pressure (in. wg)
Set Value
0 0.04 0.08 0.11 0.15
75 365 271 125 - -
80 391 310 166 49 -
85 418 354 246 76 -
90 450 380 292 167 44
95 476 429 351 238 96
100 500 468 371 297 129
105 540 499 435 347 219
110 569 522 477 367 294
115 598 561 512 451 351
120 629 597 535 494 383
125 656 630 570 535 458
130 672 656 612 575 516

1. All static pressure air flow rates are listed in CFM.


2. The tables above show the correlation between air flow rates and external static pressure.
3. The tables above show the available external static pressure range.

If the external static pressure of the installed indoor unit is less than the lowest value (as mentioned in the table), the indoor unit components
can fail.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 81
Ducted Built In
External Static Pressure and Air Flow Charts
B3, B4 Units

Figure 39: B3 Unit External Static Pressure and Air Flow Chart.
0.16
0.14
External Stac Pressure(in-wg)

0.12
0.1 ESP
ESP ESP Setting
Setting Setting 110
0.08 ESP 100
Setting 90
80
0.06
ESP
Setting
0.04
MULTI V Ducted Indoor Unit Engineering Manual

70
ESP
0.02 Setting
60
0
30 130 230 330 430
Air Flow(cfm)

Figure 40: B4 Unit External Static Pressure and Air Flow Chart.
0.2
0.18
External Stac Pressure(in-wg)

0.16
0.14
0.12
0.1
0.08 ESP ESP
0.06 ESP Setting Setting
ESP Setting 120 130
0.04 ESP Setting 110
Setting 100
0.02 90

0
200.0 250.0 300.0 350.0 400.0 450.0 500.0 550.0 600.0
Air Flow(cfm)

Due to our policy of continuous product innovation, some specifications may change without notification.
82 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED Built In
External Static Pressure Ranges
B3, B4 Units

Table 71: B3 Unit External Static Pressure Ranges.


Model Capacity (MBh) Mode Setting Value Standard ESP (in. wg) CFM Min. ESP (in. wg) Max. ESP (in. wg)
High 94 283
High
Mid 88 0.08 229 - 0.15
(Factory Set)
Low 83 194
ARNU073B3G4 7.5
High 74 283
Standard Mid 62 0 229 - 0.15
Low 56 194
High 99 318
High
Mid 89 0.08 247 - 0.15
(Factory Set)
Low 85 212
ARNU093B3G4 9.6
High 82 318
Standard Mid 66 0 247 - 0.15
Low 58 212
High 105 353
High
Mid 94 0.08 282 - 0.15
(Factory Set)
Low 88 229
ARNU123B3G4 12.3
High 90 353
Standard Mid 74 0 282 - 0.15
Low 62 229

Ducted Built In
High 110 388
High
Mid 105 0.08 353 - 0.15
(Factory Set)
Low 94 283
ARNU153B3G4 15.4
High 96 388
Standard Mid 90 0 353 - 0.15
Low 74 283

Table 72: B4 Unit External Static Pressure Ranges.


Model Capacity (MBh) Mode Setting Value Standard ESP (in. wg) CFM Min. ESP (in. wg) Max. ESP (in. wg)
High 115 494
High
Mid 103 0.08 424 - 0.15
(Factory Set)
Low 93 353
ARNU183B4G4 19.1
High 100 494
Standard Mid 86 0 424 - 0.15
Low 74 353
High 128 600
High
Mid 118 0.08 530 - 0.15
(Factory Set)
Low 93 353
ARNU243B4G4 24.2
High 116 600
Standard Mid 104 0 530 - 0.15
Low 74 353

The tables above show the available E.S.P. range.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 83
Ducted Built In
Acoustic Data
Sound Pressure Levels

Figure 41: Sound Pressure Measurement Location. • Measurements are taken 4.9 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of ±3.
• Sound pressure levels are tested in an anechoic chamber under ISO Standard
3745.
Ceiling Operating Conditions:
• Power source: 220V/60 Hz
4.9ft
6.6ft
• Sound level will vary depending on a range of factors including the construc-
tion (acoustic absorption coefficient) of a particular room in which the unit was
Microphone
installed.
MULTI V Ducted Indoor Unit Engineering Manual

Table 73: Ducted Built In Indoor Unit Sound Pressure Levels.


Sound Pressure Levels dB(A)
Model
High Fan Speed Medium Fan Speed Low Fan Speed
B3 Units
ARNU073B3G4 33 32 29
ARNU093B3G4 34 33 32
ARNU123B3G4 35 34 33
ARNU153B3G4 41 40 37
B4 Units
ARNU183B4G4 43 40 37
ARNU243B4G4 46 43 37

Figure 42: ARNU073B3G4, ARNU093B3G4, and ARNU123B3G4 Sound Pressure Level Diagrams.
ARNU073B3G4 ARNU093B3G4 ARNU123B3G4

Due to our policy of continuous product innovation, some specifications may change without notification.
84 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Built In
Acoustic Data
Sound Pressure Levels / Sound Power Levels

Figure 43: ARNU153B3G4, ARNU183B4G4, and ARNU243B4G4 Sound Pressure Level Diagrams.
ARNU153B3G4 ARNU183B4G4 ARNU243B4G4

Ducted Built In
Sound Power Levels
Table 74: Ducted Built In Indoor Unit Sound Power Levels. • Data is valid under diffuse field conditions.
Model Sound Power Levels dB(A) • Data is valid under nominal operating conditions.
B3 Units • Sound power level is measured using rated conditions, and tested
ARNU073B3G4 53 in a reverberation room per ISO 3741 standards.
ARNU093B3G4 54 • Sound level will vary depending on a range of factors such as
ARNU123B3G4 55 construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
ARNU153B3G4 60
• Reference acoustic intensity: 0dB = 10E-6μW/m2
B4 Units
ARNU183B4G4 61
ARNU243B4G4 62

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 85
Ducted Built In
Acoustic Data
Sound Power Levels

Figure 44: ARNU073B3G4, ARNU093B3G4, and ARNU123B3G4 Sound Power Level Diagrams.
ARNU073B3G4 ARNU093B3G4 ARNU123B3G4
MULTI V Ducted Indoor Unit Engineering Manual

Figure 45: ARNU153B3G4, ARNU183B4G4, and ARNU243B4G4 Sound Power Level Diagrams.
ARNU153B3G4 ARNU183B4G4 ARNU243B4G4

Due to our policy of continuous product innovation, some specifications may change without notification.
86 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Built In
Cooling Capacity Tables
ARNU073B3G4, ARNU093B3G4, ARNU123B3G4

Table 75: ARNU073B3G4, ARNU093B3G4, ARNU123B3G4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8
25 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8
30 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8
35 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8
40 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8
45 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8
50 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8
55 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8
60 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.6 5.8
ARNU073B3G4 /
65 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.5 5.7
7.5
70 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.3 5.6
75 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.1 5.5
80 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.7 5.8 8.9 5.5
85 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.3 5.8 8.4 5.5 8.6 5.2
90 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.2 5.7 8.3 5.5 8.4 5.2
95 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.0 5.7 8.2 5.4 8.3 5.1
100 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 7.9 5.6 8.0 5.4 8.2 5.1
105 5.0 4.2 5.7 4.6 6.5 4.9 7.2 5.3 7.4 5.3 7.7 5.2 7.9 5.0
110 4.8 4.1 5.4 4.3 6.0 4.6 6.8 4.9 6.9 4.9 7.4 4.9 7.7 4.8
23 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4

Ducted Built In
25 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
30 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
35 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
40 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
45 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
50 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4
55 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.5
60 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.3 7.4
ARNU093B3G4 /
65 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.1 7.3
9.6
70 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 11.9 7.2
75 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 11.6 7.0
80 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.1 7.4 11.3 7.0
85 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.7 7.5 10.8 7.1 10.9 6.7
90 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.5 7.3 10.6 7.0 10.8 6.6
95 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.3 7.3 10.5 6.9 10.7 6.6
100 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.1 7.2 10.3 6.9 10.5 6.5
105 6.3 5.4 7.3 5.9 8.3 6.3 9.2 6.7 9.4 6.7 9.9 6.6 10.1 6.3
110 6.1 5.2 6.9 5.6 7.7 5.9 8.6 6.3 8.8 6.3 9.4 6.3 9.8 6.2
23 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
25 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
30 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
35 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
40 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
45 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
50 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5
55 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.6
60 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.7 9.5
ARNU123B3G4 /
65 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.5 9.4
12.3
70 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.3 9.2
75 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 14.9 9.0
80 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.3 9.5 14.5 9.0
85 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.7 9.6 13.8 9.1 14.0 8.6
90 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.4 9.4 13.5 8.9 13.8 8.5
95 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.2 9.3 13.4 8.9 13.7 8.4
100 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 12.9 9.2 13.2 8.8 13.4 8.3
105 8.1 6.9 9.3 7.5 10.6 8.1 11.8 8.6 12.1 8.6 12.7 8.5 12.9 8.1
110 7.9 6.7 8.9 7.1 9.8 7.5 11.1 8.1 11.3 8.1 12.1 8.1 12.5 7.9
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 87
Ducted Built In
Cooling Capacity Tables
ARNU153B3G4, ARNU183B4G4, ARNU243B4G4

Table 76: ARNU153B3G4, ARNU183B4G4, ARNU243B4G4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9
25 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9
30 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9
35 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9
40 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9
45 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9
50 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9
55 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 12.0
60 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.7 11.9
MULTI V Ducted Indoor Unit Engineering Manual

ARNU153B3G4 /
65 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.4 11.7
15.4
70 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.1 11.5
75 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 18.6 11.3
80 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 17.9 11.9 18.2 11.2
85 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.1 12.0 17.2 11.4 17.6 10.8
90 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 16.8 11.7 16.9 11.2 17.2 10.6
95 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 16.5 11.7 16.8 11.1 17.1 10.5
100 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 16.2 11.5 16.5 11.0 16.8 10.4
105 10.2 8.6 11.7 9.4 13.2 10.1 14.8 10.8 15.1 10.8 15.9 10.7 16.2 10.2
110 9.9 8.4 11.1 8.9 12.3 9.4 13.9 10.1 14.2 10.1 15.1 10.1 15.7 9.9
23 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
25 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
30 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
35 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
40 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
45 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
50 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
55 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.6 14.4
60 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.4 14.3
ARNU183B4G4 /
65 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 24.1 14.1
19.1
70 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 23.7 13.9
75 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.7 14.4 23.1 13.6
80 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.4 14.6 22.2 14.4 22.5 13.5
85 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 21.2 14.4 21.4 13.7 21.8 13.0
90 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 20.8 14.2 21.0 13.5 21.4 12.8
95 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 20.4 14.1 20.8 13.4 21.2 12.7
100 12.6 10.4 15.3 12.0 17.2 12.8 19.1 13.6 20.1 13.9 20.4 13.3 20.8 12.6
105 12.6 10.4 14.5 11.4 16.4 12.2 18.3 13.0 18.7 13.0 19.7 12.8 20.1 12.3
110 12.2 10.1 13.8 10.8 15.3 11.4 17.2 12.2 17.6 12.2 18.7 12.2 19.5 11.9
23 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
25 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
30 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
35 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
40 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
45 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
50 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
55 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.2 18.3
60 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 31.0 18.2
ARNU243B4G4 /
65 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 30.5 17.9
24.2
70 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 30.0 17.6
75 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.8 18.3 29.3 17.2
80 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 27.1 18.5 28.1 18.2 28.6 17.1
85 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 26.9 18.3 27.1 17.4 27.6 16.5
90 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 26.4 18.0 26.6 17.1 27.1 16.2
95 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 25.9 17.9 26.4 17.0 26.9 16.1
100 16.0 13.2 19.4 15.2 21.8 16.2 24.2 17.2 25.4 17.6 25.9 16.9 26.4 15.9
105 16.0 13.2 18.4 14.4 20.8 15.5 23.2 16.5 23.7 16.5 24.9 16.3 25.4 15.6
110 15.5 12.8 17.4 13.6 19.4 14.4 21.8 15.5 22.3 15.5 23.7 15.5 24.7 15.1
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
88 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Built In
Heating Capacity Tables
ARNU073B3G4, ARNU093B3G4, ARNU123B3G4, ARNU153B3G4

Table 77: ARNU073B3G4, ARNU093B3G4, ARNU123B3G4, ARNU153B3G4 Heating Capacity Table.


Indoor Air Temperature (°F DB)
Outdoor Air Temp. 59 61 64 67 70 73 76 80
Model No. /
Capacity Index TC TC TC TC TC TC TC TC
°F DB °F WB MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 5.7 5.7 5.7 5.7 5.6 5.6 5.6 5.6
0 -0.4 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.8
5.0 4.5 6.6 6.5 6.5 6.5 6.5 6.5 6.5 6.5
10.0 9.0 6.9 6.9 6.9 6.8 6.8 6.8 6.8 6.8
15.0 14.0 7.3 7.3 7.3 7.3 7.3 7.3 7.2 7.1
20.0 19.0 7.7 7.7 7.7 7.7 7.5 7.5 7.4 7.3
25.0 23.0 8.1 8.1 8.1 8.1 8.1 7.9 7.8 7.7
ARNU073B3G4 /
30.0 28.0 8.2 8.2 8.2 8.2 8.2 8.1 7.8 7.6
7.5
35.0 32.0 8.5 8.5 8.5 8.5 8.4 8.2 7.8 7.4
40.0 36.0 8.8 8.8 8.8 8.8 8.5 8.2 7.8 7.4
45.0 41.0 9.2 9.2 9.2 8.9 8.5 8.2 7.8 7.4
47.0 43.0 9.5 9.4 9.4 8.9 8.5 8.2 7.8 7.4
50.0 46.0 10.2 9.8 9.4 8.9 8.5 8.2 7.8 7.4
55.0 51.0 10.4 9.9 9.4 8.9 8.5 8.2 7.8 7.4
60.0 56.0 10.4 9.9 9.4 8.9 8.5 8.2 7.8 7.4
-4 -4.4 7.3 7.3 7.3 7.3 7.2 7.2 7.2 7.2
0 -0.4 7.5 7.5 7.5 7.5 7.5 7.4 7.4 7.4
5.0 4.5 8.5 8.4 8.3 8.3 8.3 8.3 8.3 8.3
10.0 9.0 8.8 8.8 8.8 8.7 8.7 8.7 8.7 8.7
15.0 14.0 9.4 9.4 9.4 9.4 9.4 9.4 9.3 9.2

Ducted Built In
20.0 19.0 9.9 9.9 9.9 9.9 9.7 9.7 9.5 9.4
25.0 23.0 10.4 10.4 10.4 10.4 10.4 10.1 10.0 9.9
ARNU093B3G4 /
30.0 28.0 10.6 10.6 10.6 10.6 10.6 10.4 10.0 9.7
9.6
35.0 32.0 10.9 10.9 10.9 10.9 10.8 10.6 10.0 9.5
40.0 36.0 11.3 11.3 11.3 11.3 10.9 10.6 10.0 9.5
45.0 41.0 11.8 11.8 11.8 11.4 10.9 10.6 10.0 9.5
47.0 43.0 12.2 12.1 12.0 11.4 10.9 10.6 10.0 9.5
50.0 46.0 13.1 12.5 12.0 11.4 10.9 10.6 10.0 9.5
55.0 51.0 13.3 12.6 12.0 11.4 10.9 10.6 10.0 9.5
60.0 56.0 13.3 12.6 12.0 11.4 10.9 10.6 10.0 9.5
-4 -4.4 9.1 9.1 9.1 9.1 9.0 9.0 9.0 9.0
0 -0.4 9.4 9.4 9.4 9.4 9.4 9.2 9.2 9.2
5.0 4.5 10.6 10.5 10.3 10.3 10.3 10.3 10.3 10.3
10.0 9.0 11.0 11.0 11.0 10.9 10.9 10.9 10.9 10.9
15.0 14.0 11.7 11.7 11.7 11.7 11.7 11.7 11.6 11.4
20.0 19.0 12.4 12.4 12.4 12.4 12.1 12.1 11.9 11.7
25.0 23.0 12.9 12.9 12.9 12.9 12.9 12.6 12.5 12.4
ARNU123B3G4 /
30.0 28.0 13.2 13.2 13.2 13.2 13.2 12.9 12.5 12.1
12.3
35.0 32.0 13.6 13.6 13.6 13.6 13.5 13.2 12.5 11.9
40.0 36.0 14.1 14.1 14.1 14.1 13.6 13.2 12.5 11.9
45.0 41.0 14.7 14.7 14.7 14.3 13.6 13.2 12.5 11.9
47.0 43.0 15.2 15.1 15.0 14.3 13.6 13.2 12.5 11.9
50.0 46.0 16.4 15.6 15.0 14.3 13.6 13.2 12.5 11.9
55.0 51.0 16.6 15.8 15.0 14.3 13.6 13.2 12.5 11.9
60.0 56.0 16.6 15.8 15.0 14.3 13.6 13.2 12.5 11.9
-4 -4.4 11.5 11.5 11.5 11.5 11.3 11.3 11.3 11.3
0 -0.4 11.8 11.8 11.8 11.8 11.8 11.6 11.6 11.6
5.0 4.5 13.3 13.2 13.0 13.0 13.0 13.0 13.0 13.0
10.0 9.0 13.9 13.9 13.9 13.7 13.7 13.7 13.7 13.7
15.0 14.0 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.4
20.0 19.0 15.6 15.6 15.6 15.6 15.2 15.2 15.0 14.8
25.0 23.0 16.2 16.2 16.2 16.2 16.2 15.9 15.7 15.6
ARNU153B3G4 /
30.0 28.0 16.6 16.6 16.6 16.6 16.6 16.2 15.7 15.2
15.4
35.0 32.0 17.1 17.1 17.1 17.1 16.9 16.6 15.7 14.9
40.0 36.0 17.8 17.8 17.8 17.8 17.1 16.6 15.7 14.9
45.0 41.0 18.5 18.5 18.5 18.0 17.1 16.6 15.7 14.9
47.0 43.0 19.2 19.0 18.8 18.0 17.1 16.6 15.7 14.9
50.0 46.0 20.6 19.7 18.8 18.0 17.1 16.6 15.7 14.9
55.0 51.0 20.9 19.8 18.8 18.0 17.1 16.6 15.7 14.9
60.0 56.0 20.9 19.8 18.8 18.0 17.1 16.6 15.7 14.9
TC: Total Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 89
Ducted Built In
Heating Capacity Tables
ARNU183B4G4, ARNU243B4G4

Table 78: ARNU183B4G4, ARNU243B4G4 Heating Capacity Table.


Indoor Air Temperature (°F DB)
Outdoor Air Temp. 59 61 64 67 70 73 76 80
Model No. /
Capacity Index TC TC TC TC TC TC TC TC
°F DB °F WB MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 14.4 14.4 14.4 14.4 14.2 14.2 14.2 14.2
0 -0.4 14.8 14.8 14.8 14.8 14.8 14.6 14.6 14.6
5.0 4.5 16.8 16.6 16.3 16.3 16.3 16.3 16.3 16.3
10.0 9.0 17.4 17.4 17.4 17.2 17.2 17.2 17.2 17.2
15.0 14.0 18.5 18.5 18.5 18.5 18.5 18.5 18.3 18.1
20.0 19.0 19.6 19.6 19.6 19.6 19.1 19.1 18.8 18.5
25.0 23.0 20.4 20.4 20.4 20.4 20.4 20.0 19.8 19.6
ARNU183B4G4 /
30.0 28.0 20.9 20.9 20.9 20.9 20.9 20.4 19.8 19.2
19.1
35.0 32.0 21.5 21.5 21.5 21.5 21.3 20.9 19.8 18.8
MULTI V Ducted Indoor Unit Engineering Manual

40.0 36.0 22.4 22.4 22.4 22.4 21.5 20.9 19.8 18.8
45.0 41.0 23.2 23.2 23.2 22.6 21.5 20.9 19.8 18.8
47.0 43.0 24.1 23.9 23.7 22.6 21.5 20.9 19.8 18.8
50.0 46.0 25.8 24.7 23.7 22.6 21.5 20.9 19.8 18.8
55.0 51.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
60.0 56.0 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8
-4 -4.4 18.3 18.3 18.3 18.3 18.0 18.0 18.0 18.0
0 -0.4 18.8 18.8 18.8 18.8 18.8 18.6 18.6 18.6
5.0 4.5 21.3 21.0 20.7 20.7 20.7 20.7 20.7 20.7
10.0 9.0 22.1 22.1 22.1 21.8 21.8 21.8 21.8 21.8
15.0 14.0 23.5 23.5 23.5 23.5 23.5 23.5 23.2 22.9
20.0 19.0 24.8 24.8 24.8 24.8 24.2 24.2 23.9 23.6
25.0 23.0 25.9 25.9 25.9 25.9 25.9 25.4 25.1 24.8
ARNU243B4G4 /
30.0 28.0 26.5 26.5 26.5 26.5 26.5 25.9 25.1 24.3
24.2
35.0 32.0 27.3 27.3 27.3 27.3 27.0 26.5 25.1 23.8
40.0 36.0 28.4 28.4 28.4 28.4 27.3 26.5 25.1 23.8
45.0 41.0 29.5 29.5 29.5 28.7 27.3 26.5 25.1 23.8
47.0 43.0 30.6 30.3 30.0 28.7 27.3 26.5 25.1 23.8
50.0 46.0 32.8 31.4 30.0 28.7 27.3 26.5 25.1 23.8
55.0 51.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.8
60.0 56.0 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.8
TC: Total Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
90 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ducted Built In
Optional Accessories

Table 79: Optional Accessories for Ducted Built In Indoor Units.


Accessory Model Number
PBSGB30 (For 7~15MBh Ducted Built In Indoor Units [B3 Frames])
Return Air Grille
PBSGB40 (For 18-24MBh Ducted Built In Indoor Units [B4 Frames])
PBSC30 (For 7~15MBh Ducted Built In Indoor Units [B3 Frames])
Return Air Canvas
PBSC40 (For 18-24MBh Ducted Built In Indoor Units [B4 Frames])
All accessories are sold separately.

Ducted Built In

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Built In | 91
MULTI V Ducted Indoor Unit Engineering Manual

Due to our policy of continuous product innovation, some specifications may change without notification.
92 | Built In © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
VERTICAL /
HORIZONTAL
AIR HANDLER
Mechanical Specifications on page 94
General Data on page 96
Electrical Data on page 98
External Dimensions on page 99
Electrical Wiring Diagram on page 101
Refrigerant Flow Diagrams on page 103
External Static Pressure and Air Flow on page 104
External Static Pressure Ranges on page 105
Heater Capacity Airflow / Static Pressure Drop Factors on page 106
Acoustic Data on page 107
Capacity Tables on page 111
Optional Accessories on page 116
Vertical / Horizontal Air Handler
Mechanical Specifications

Casing temperature safety switch, and intercon-


The unit is designed to operate in the vertical up flow configuration necting control wiring harness with a quick
or horizontal left end supply air. Return air opening is on the bottom connect plug for easy connection to the
in the vertical position or right end in the horizontal position. Return air handler control board. Auxiliary heat
air plenum sub-base is to be field-provided. The supply air con- modules are available in nominal capac-
nection is male flange. The unit case is made of 22-gauge coated ities of 5, 10, 15, and 20 kW at 230/60/1.
metal and the external surfaces are finished with a high gloss baked Heating elements are powered from a field
enamel finish. Finish color is “morning fog” (medium beige). Cold provided separate power source. 5 and
surfaces are galvanized steel. The cold surfaces of the case are in- 10 kW modules are powered from a single
ternally insulated with ½ inch foil faced, polystyrene fiber insulation. power wire. The 15 and 20 kW modules
The inside surface of the fan assembly door access panel is treated are powered from two power wires.
with ½ inch polystyrene fiber insulation, encapsulated on both sides, Heating module breakers, fuses, and / or
MULTI V Ducted Indoor Unit Engineering Manual

and sealed along the edges with a reinforced foil-faced covering to disconnects are to be field provided.
prevent deterioration caused by panel removal. All access panels are
provided with gasket seals to minimize air leakage. The unit case is Electric Heat Module Controls
designed to accept an internal, optional, LG electric strip heater. The The electric heat module is capable of operating at full capacity
unit bears the ETL label. Unit breaker, fuses, and / or disconnect are during system defrost and oil return operations. When the air handler
provided by others. is operating in the Cooling, Dry, or Fan Only modes, the electric
heater operation is locked out and unavailable. When the air handler
Fan Assembly and Control is operating in the Heating mode, the heater is field selectable to
The indoor unit has an integral fan assembly consisting of a operate when the room temperature is 2°F lower than set-point or
galvanized steel housing and a forward-curved fan wheel. The direct manually if provided with a start/stop signal from a third-party outside
drive fan/motor assembly is mounted on rubber grommets isolat- source.
ing the rotating assembly from the fan housing. The fan motor is a
Brushless Digitally-Controlled design (BLDC), having permanently Microprocessor Controls
lubricated and sealed ball bearings. The fan motor includes thermal, The unit is equipped with an integrated microprocessor-based
overcurrent and low RPM protection. The fan/motor assembly is controller capable of performing functions necessary to operate the
mounted on vibration attenuating rubber grommets. The fan impeller system without the use of a wall-mounted controller. A temperature
is statically and dynamically balanced. Fan speed is controlled using thermistor is mounted in the return air stream. All unit operating
a microprocessor-based direct digital control algorithm that provides parameters, excluding the operation schedule, are stored in non-vol-
a minimum of a high fan speed in cooling thermal ON and low fan atile memory resident on the unit microprocessor. Operating sched-
speed in cooling thermal OFF, high fan speed in heating thermal ules are stored in select models of the optional wall-mounted local or
ON and fan off in heating thermal OFF. The fan speeds can be field central controller. The field-supplied communication cable between
adjusted between low, medium, and high speeds and DIP switch the indoor unit(s) and outdoor unit is to be a minimum of 18 AWG,
settings will allow the fan to run constantly during defrost or oil return 2 conductor, stranded, and shielded (RS-485). The microprocessor
modes. Each setting can be field adjusted from the factory setting control provides the following functions: auto addressing, self-
(RPM/ESP). The setting provides delivery of the high speed air diagnostics, auto restart following power restoration, and will operate
volume against an external static pressure of up to 1.0 in-wg. the indoor unit using one of the following five operation modes:

Air Filter 1. Auto Changeover (Heat Recovery only)


The unit comes with a filter rack capable of accepting a field- 2. Heating
provided 16” x 20” x 1” (NJ chassis) or 24” x 20” x 1” (NK chassis)
filter cartridge. The filter rack is equipped with guides that keep the 3. Cooling
filter centered in the rack. Filter service access is from the front of 4. Dry
the unit without removing the coil or fan area access panels. Filter 5. Fan Only
access door is provided with thumb screws that can be removed.
For Heat Recovery systems the Auto Changeover setting automati-
Optional Auxiliary Electric Heat Module(s) cally switches control of the indoor unit between cooling and heating
LG optional electric heat modules are designed for field modes based on space temperature conditions.
installation in the reheat position. The electric heat module is For Heat Pump systems, heated or cooled air delivery is dependent
provided with heating elements, contractors, relays, high upon outdoor unit operating mode.

Due to our policy of continuous product innovation, some specifications may change without notification.
94 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Mechanical Specifications

In Heating mode, the microprocessor control does not begin fan Controls Features
operation until coil pipe temperature reaches 76ºF. Significant • Auto changeover (Heat Recovery only)
airflow is generated when pipe temperature reaches 80°F. A field-se- • Auto operation
lectable option maintains fan operation for 30 minutes following
• Auto restart
cooling cycle operations.
• Child lock
• Dual thermistor control
1. Wall-mounted wire controller
• External static pressure control
2. Factory-mounted return air thermistor or the optional wall-
mounted wired remote temperature sensor. • Group control
• Hot start
The microprocessor controls space temperature using the value • Self diagnostics
provided by the temperature sensor sensing a space temperature • Timer (on / off)
that is farthest away from the temperature set-point. A single indoor • Weekly schedule
unit has the capability of being controlled by up to two local wired • Fan speed control
controllers. The microprocessor control provides a cooling or heating

Vertical / Horizontal Air Handler


• Dual set-point control
mode test cycle that operates the unit for 18 minutes without regard
• Filter life and power consumption display
to the space temperature. If the system is provided with an optional
local or central controller, displayed diagnostic codes are specific • Multiple auxiliary heater applications
and provide the service technician with the reason for the code
displayed.

Handling Condensate
The drain pan is designed to work with a gravity building drain sys-
tem. If condensate lifts/pumps are needed, they are to be field-pro-
vided. A secondary drain port plug is provided allowing the pan to be
drained for service. Condensate float safety switch connections are
available on the main control board for connection of a field supplied
float safety switch.

Condensate Drain Pan


The condensate drain pan is constructed of HIPS (high impact
polystyrene resin).

Coil
The indoor unit coil is constructed with grooved design copper tubes
with slit coil fins, 2 to 3 rows, 18 fins per inch.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 95
Vertical / Horizontal Air Handler
General Data
NJ Frames

Table 80: Vertical / Horizontal (NJ Frame) Air Handler Unit General Data.
Model No. ARNU123NJA4 ARNU183NJA4 ARNU243NJA4 ARNU303NJA4 ARNU363NJA4
Cooling Mode Performance
Capacity (Btu/h) 12,000 18,000 24,000 30,000 36,000
Power Input1 (W) 228 228 228 228 228
Heating Mode Performance
Capacity (Btu/h) 13,500 20,000 27,000 34,000 40,000
Power Input (W) 1
228 228 228 228 228
Entering Mixed Air
MULTI V Ducted Indoor Unit Engineering Manual

Cooling Max. (°F WB) 76 76 76 76 76


Heating Min. (°F DB) 59 59 59 59 59
Unit Data
Refrigerant Type2 R410A R410A R410A R410A R410A
Refrigerant Control EEV EEV EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
42 / 41 / 39 42 / 42 / 41 43 / 42 / 41 44 / 43 / 42 45 / 44 / 43
Net Unit Weight (lbs.) 117 117 117 117 121
Shipping Weight (lbs.) 140 140 140 140 144
Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
Fan
Type Sirocco Sirocco Sirocco Sirocco Sirocco
Motor 1 1 1 1 1
Housing 1 1 1 1 1
Motor/Drive Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM) 530 / 480 / 380 580 / 530 / 480 710 / 640 / 480 880 / 800 / 630 990 / 880 / 800
Standard Mode
Airflow Rate H/M/L (CFM) 530 / 480 / 380 580 / 530 / 480 710 / 640 / 480 880 / 800 / 630 990 / 880 / 800
High Mode (Factory Set)
External Static Pressure (in. wg) 0.3 0.3 0.3 0.3 0.3
Standard Mode
External Static Pressure (in. wg) 0.5 0.5 0.5 0.5 0.5
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.) 1/4 Flare 1/4 Flare 3/8 Flare 3/8 Flare 3/8 Flare
Vapor Line (in., O.D.) 1/2 Flare 1/2 Flare 5/8 Flare 5/8 Flare 5/8 Flare
Condensate Line (in., I.D.) 1 1 1 1 1
EEV: Electronic Expansion Valve 1
Power Input is rated at high speed.
Power wiring is field supplied and must comply with the applicable local and national codes. 2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
This unit comes with a dry nitrogen charge. R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units. All capacities are net with a combination ratio between
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
95-105%. 4
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet with applicable and national code. Ensure the communication cable is properly grounded at the master
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB). outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor
ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).

Due to our policy of continuous product innovation, some specifications may change without notification.
96 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
General Data
NK Frames

Table 81: Vertical / Horizontal (NK Frame) Air Handler Unit General Data.
Model No. ARNU423NKA4 ARNU483NKA4 ARNU543NKA4
Cooling Mode Performance
Capacity (Btu/h) 42,000 48,000 54,000
Power Input1 (W) 366 366 366
Heating Mode Performance
Capacity (Btu/h) 46,000 54,000 60,000
Power Input1 (W) 366 366 366
Entering Mixed Air
Cooling Max. (°F WB) 76 76 76
Heating Min. (°F DB) 59 59 59
Unit Data

Vertical / Horizontal Air Handler


Refrigerant Type2 R410A R410A R410A
Refrigerant Control EEV EEV EEV
Sound Pressure dB(A) (H/M/L)
3
46 / 44 / 41 49 / 47 / 41 50 / 49 / 47
Net Unit Weight (lbs.) 165 165 165
Shipping Weight (lbs.) 181 181 181
Communication Cable (No. x AWG) 4
2 x 18 2 x 18 2 x 18
Fan
Type Sirocco Sirocco Sirocco
Motor 1 1 1
Housing 1 1 1
Motor/Drive Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM) 1,250 / 1,100 / 1,000 1,400 / 1,260 / 1,000 1,475 / 1,400 / 1,260
Standard Mode
Airflow Rate H/M/L (CFM) 1,250 / 1,100 / 1,000 1,400 / 1,260 / 1,000 1,475 / 1,400 / 1,260
High Mode (Factory Set)
External Static Pressure (in. wg) 0.3 0.3 0.3
Standard Mode
External Static Pressure (in. wg) 0.5 0.5 0.5
High Mode (Factory Set)
Piping
Liquid Line (in., O.D.) 3/8 Flare 3/8 Flare 3/8 Flare
Vapor Line (in., O.D.) 5/8 Flare 5/8 Flare 5/8 Flare
Condensate Line (in., I.D.) 1 1 1
EEV: Electronic Expansion Valve 1
Power Input is rated at high speed.
Power wiring is field supplied and must comply with the applicable local and national codes. 2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
This unit comes with a dry nitrogen charge. R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608
of CAA.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units. All capacities are net with a combination ratio between
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
95-105%. 4
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet with applicable and national code. Ensure the communication cable is properly grounded at the master
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB). outdoor unit only. Do not ground the ODU-IDU communication cable at any other point.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor
ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 97
Vertical / Horizontal Air Handler
Electrical Data

Table 82: Vertical / Horizontal (NJ, NK Frames) Air Handler Unit Electrical Data.
Power Supply Power Input (W)
Model Voltage Range MCA MOP Rated Amps (A)
Hz Volts Phase Cooling Heating
NJ Frames
ARNU123NJA4 1.4 1.12 228 228
ARNU183NJA4 1.4 1.12 228 228
ARNU243NJA4 208-230 1.4 15 1.12 60 208-230 1 228 228
ARNU303NJA4 1.4 1.12 228 228
ARNU363NJA4 1.4 1.12 228 228
MULTI V Ducted Indoor Unit Engineering Manual

NK Frames
ARNU423NKA4 2.3 1.8 260 260
ARNU483NKA4 208-230 2.3 15 1.8 60 208-230 1 330 330
ARNU543NKA4 2.3 1.8 366 366
MCA : Minimum Circuit Ampacity. Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
MOP : Maximum Overcurrent Protection. Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.

Due to our policy of continuous product innovation, some specifications may change without notification.
98 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
External Dimensions
NJ Frame

Figure 46: ARNU123~363NJA4 Dimensions.


Supply Air
opening

48-11/16

SIDE VIEW
1-5/8 1-9/16 7/8” Wiring
21-1/4 18

Vertical / Horizontal Air Handler


knockouts

1-9/16 1-15/16
2-1/16
18

17

7/8” Wiring
knockouts
2-1/8

12-1/8 1-15/16 1-11/16” Wiring


knockouts Liquid pipe
48-11/16
49-5/16

21-1/4
TOP VIEW
Vapor pipe
2-9/16

Drain connection
for upflow application
1-1/2

Return Air
14-5/16

opening
4-11/16

1-9/16

9-15/16
BOTTOM VIEW Drain connection
for horizontal
application 13
Unit: inches
Note: All measurements FRONT VIEW
have a tolerance of ±1/4 in.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 99
Vertical / Horizontal Air Handler
External Dimensions
NK Frame

Figure 47: ARNU423~543NKA4 Dimensions.


Supply Air
opening

55-3/16
MULTI V Ducted Indoor Unit Engineering Manual

1-5/8 1-9/16 SIDE VIEW


25 7/8” Wiring
21-1/4 knockouts

1-9/16 1-15/16
2-1/16

7/8” Wiring
knockouts
25

24

2-3/16

55-13/16

55-3/16

12-1/8 Liquid pipe


1-11/16” Wiring
21-1/4 knockouts
Vapor pipe
2-9/16

Drain connection
for upflow application
1-1/2
14-1/4

Return Air
opening
1-9/16
4-11/16

Drain connection 16-15/16


for horizontal
application
20
Unit: inches
Note: All measurements FRONT VIEW
have a tolerance of ±1/4 in.

Due to our policy of continuous product innovation, some specifications may change without notification.
100 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Electrical Wiring Diagram
NJ, NK Frame

Figure 48: ARNU123~363NJA4, ARNU423-543NKA4 Wiring Diagram.

Vertical / Horizontal Air Handler

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 101
Vertical / Horizontal Air Handler
Electrical Wiring Diagram
NJ, NK Frame

Table 83: NJ, NK Frame Wiring Diagram Legend.


Terminal Purpose Function
CN-POWER AC Power supply AC Power line
CN-MOTOR1 Fan motor output Motor output of BLDC
RV-VM Sub PC power supply Power supply connection
CN_OUT Heater Connection for heater
CN-FLOAT Float switch input Float switch sensing
CN-ZONE Zone controller Zone controller connection
CN-EEV EEV Output EEV control output
MULTI V Ducted Indoor Unit Engineering Manual

CN-OPTION Optional PCB EPROM Option PCB connection


CN-DISPLAY Display Display of indoor status
CN-CC Dry contact Dry Contact connection
CN-PIPE/OUT (RD) Discharge pipe sensor Pipe out thermistor
CN-LEAK (VI) Refrigerant leak detector Refrigerant leak detector connection
CN-PIPE/IN (WH) Suction pipe sensor Pipe in thermistor
CN-REMO (GN) Wired remote controller Wired remote control connection
CN-ROOM (YL) Room sensor Room air thermistor
CN-D/PUMP Drain pump output AC output for drain pump
CN-485 Communication Connection between indoor and outdoor units

Table 84: NJ, NK Frame DIP Switch Settings.


DIP Switch Setting Off On Remarks
SW3 GROUP Master Slave Group Control setting using 7-Day Programmable Controller
Dry Contact Mode Setting
1. Variable: Auto/Manual Mode can be chosen by 7-Day Programmable Controller or
SW4 DRY CONTACT Variable Auto
Wireless Remote Controller (when shipped from factory -> Manual Mode)
2. Auto: For Dry Contact, it is always Auto mode
-OFF: Default (does not operate continuously)
SW5 EXTRA 1 Off On
-ON: Fan operates continuously
-ON: Automatic heater operation
SW6 Heater Off On
-OFF: Default (heater manual operation)
COMMUNICATIONS -OFF: 1.2kbps
SW8 Gen. 2 Gen. 4
RATE -ON: 9.6kbps
For Multi V indoor units without electric heaters, DIP switches 1, 2, 6,, and 7 must be set to OFF. These DIP switches are used for other
models.

For Multi V systems with an electric heater, DIP switches 5 and 6 must be set to ON.
• SW 5 ON: Fan operates continuously. During defrost or oil return operation, uninterrupted heating can be attained as a result of continuous
heater and fan operation.
• SW 5 OFF: Fan does not operate continuously. There will be a reduction in heating capacity during defrost or oil return operation.
• SW 6 ON: Automatic heater operation. The heater operates automatically according to heater logic without manual intervention.
• SW 6 OFF: Heater manual operation. Manual operation is required for on/off, but heater operation will follow heater logic.

Due to our policy of continuous product innovation, some specifications may change without notification.
102 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Refrigerant Flow Diagram
NJ, NK Frames

Figure 49: NJ, NK Frame Refrigerant Flow Diagram.

Sirroco Fan

Cooling
Heat Exchanger EEV Heating
Filter
TH3 TH2
TH1 Filter

Vertical / Horizontal Air Handler


lndoor unit

Table 85: NJ, NK Frame Refrigerant Pipe Connection Port Diameters.


Model Liquid (inch) Vapor (inch)
NJ Frames
ARNU123NJA4
1/4 Flare 1/2 Flare
ARNU183NJA4
ARNU243NJA4
ARNU303NJA4 3/8 Flare 5/8 Flare
ARNU363NJA4
NK Frames
ARNU423NKA4
ARNU483NKA4 3/8 Flare 5/8 Flare
ARNU543NKA4

Table 86: NJ, NK Frame Thermistors.


Thermistor Description
TH1 Return air thermistor
TH2 Pipe in thermistor
TH3 Pipe out thermistor

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 103
Vertical / Horizontal Air Handler
External Static Pressure and Air Flow Charts
NJ, NK Frames

Figure 50: NJ Frame External Static Pressure and Air Flow Chart.

0.7 (in wg)


0.6 (in wg)
100 0.5 (in wg)

0.4 (in wg)


90 0.3 (in wg)

0.2 (in wg)


ESP @ Pressure
MULTI V Ducted Indoor Unit Engineering Manual

80 0.1 (in wg)

70

60

50
350 550 750 950
CFM

Figure 51: NK Frame External Static Pressure and Air Flow Chart.

120
0.8 (in wg)
0.7 (in wg)
110
0.6 (in wg)
100
0.5 (in wg)
0.4 (in wg)
ESP @ Pressure

90
0.3 (in wg)
0.2 (in wg)
80
0.1 (in wg)

70

60

50
900 1000 1100 1200 1300 1400 1500
CFM

Due to our policy of continuous product innovation, some specifications may change without notification.
104 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
External Static Pressure and Air Flow
NJ, NK Frames

Table 87: NJ Frame External Static Pressure and Air Flow Table.
Model No. / Flow Rate Static Pressure (in. WG)
Capacity (MBh) Mode CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
High 530 **53 58 66 72 82 84 92 *92 *92 *92
ARNU123NJA / 12 Mid 480 **53 56 64 70 79 83 92 *92 *92 *92
Low 380 **53 54 62 69 77 83 92 *92 *92 *92
High 580 **53 60 68 74 84 85 95 *95 *95 *95
ARNU183NJA4 / 18 Mid 530 **53 58 66 72 82 84 92 *92 *92 *92
Low 480 **53 55 64 70 79 83 92 *92 *92 *92
High 710 56 67 74 78 87 94 98 *98 *98 *98
ARNU243NJA4 / 24 Mid 640 53 65 70 75 85 91 96 *96 *96 *96
Low 480 **53 55 64 70 79 84 92 *92 *92 *92
High 880 65 72 80 85 92 98 103 *103 *103 *103

Vertical / Horizontal Air Handler


ARNU303NJA4 / 30 Mid 800 62 69 77 82 90 96 101 *101 *101 *101
Low 640 53 65 70 75 85 91 96 *96 *96 *96
High 990 80 85 90 95 100 103 *103 *103 *103 *103
ARNU363NJA4 / 36 Mid 880 65 72 80 85 92 98 103 *103 *103 *103
Low 800 62 69 77 82 90 96 101 *101 *101 *101

Table 88: NK Frame External Static Pressure and Air Flow Table.
Model No. / Flow Rate Static Pressure (in. WG)
Capacity (MBh) Mode CFM 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
High 1,260 67 75 80 87 90 98 102 110 *115 *115
ARNU423NKA4 / 42 Mid 1,100 61 67 75 80 87 92 100 108 110 115
Low 1,000 56 65 72 77 84 90 98 105 108 115
High 1,400 74 79 84 91 96 102 110 115 *115 *115
ARNU483NKA4 / 48 Mid 1,260 67 75 80 87 90 98 102 110 115 *115
Low 1,000 56 65 72 77 84 90 98 105 108 115
High 1,475 77 82 87 93 98 105 113 115 *115 *115
ARNU543NKA4 / 54 Mid 1,400 74 79 84 91 96 102 110 113 *115 *115
Low 1,260 67 75 80 87 90 98 102 110 115 *115
* Flow rate (CFM) decreases by 3% per 0.1 in. WG. Minimum airflow rates are listed in CFM. Factory Default is high static pressure.
** Fan external static pressure is at minimum value. If the flow rate (CFM) is increased by 400 CFM/ton from 1.5 tons to High static pressure is 0.5 in wg.
2.5 tons of capacity, then ESP value should be increased by 4.
Low static pressure is 0.3 in wg.
If the flow rate (CFM) is increased by 400 CFM/ton from 3.0 tons to
4.5 tons of capacity, then The ESP value should be increased by 5. Vertical Air Handling Units are UL Listed up to 0.5 in wg external
static pressure, including air filter, set coil, and largest kW size
heater, unless otherwise noted.

If the ESP is set incorrectly, the air conditioning may malfunction.

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 105
Vertical / Horizontal Air Handler
Heater Capacity Airflow / Static Pressure Drop Factors

Table 89: Minimum Airflow by Heater Capacity.


Heater Capacity (kW)
Capacity (MBh [tons])
5 10 15 20
12 (1.0) 380 Not available Not available Not available
18 (1.5) 380 Not available Not available Not available
24 (2.0) 480 480 Not available Not available
30 (2.5) 630 630 Not available Not available
36 (3.0) 780 780 Not available Not available
42 (3.5) 1,000 1,000 1,000 1,000
48 (4.0) 1,000 1,000 1,000 1,000
54 (4.5) 1,300 1,300 1,300 1,300
MULTI V Ducted Indoor Unit Engineering Manual

Airflow rates in the table above are listed in CFM. Flow rate (CFM) is decreased by 3% per 0.1 in wg from 0.8 in wg to 1.0 in wg.
Vertical Air Handling Units are UL Listed up to 0.5 in wg external static pressure, including air filter, set
coil, and largest kW size heater, unless otherwise noted.

Do not operate with less than the minimum airflow. If an airflow is Do not operate with less than the minimum airflow. If an airflow is
used below the minimum, there is a risk of fire, which may lead to used below the minimum, there is a risk of damage to the product.
physical injury or death.
Table 90: Electric Heater Static Pressure Drop Factors.
Heater Capacity (kW) Static Pressure Drop (in. wg)
0 0
5 -0.01
10 -0.02
15 -0.04
20 -0.06
in wg = inch water gauge If the ESP setting value is inappropriate, the provided safety device will turn the heater off according to
If the electric heater has been installed, then the ESP value has to be set. the airflow.
For every increase in static pressure by 0.01 in wg, the ESP value should be increased by 1.

Table 91: Air Filter Static Pressure Drop Factors.


Capacity (MBh(tons)) Flow Rate (CFM) Static Pressure Drop (in wg)
High (480) -0.02
12 (1.0) Middle (380) -0.01
Low (380) -0.01
High(530) -0.02
18 (1.5) Middle(480) -0.02
Low(380) -0.01
High(710) -0.04
24 (2.0) Middle(640) -0.03
Low(480) -0.02
High(880) -0.05
30 (2.5) Middle(800) -0.05
Low(630) -0.03
High(990) -0.07
36 (3.0) Middle(880) -0.05
Low(800) -0.05
High(1250) -0.11
42 (3.5) Middle(1100) -0.09
Low(1000) -0.07
High(1400) -0.14
48 (4.0) Middle(1260) -0.11
Low(1000) -0.07
High(1475) -0.18
54 (4.5) Middle(1400) -0.16
Low(1260) -0.12
If the air filter has been installed, the ESP value has to be set. For every increase in static pressure by 0.01 in. wg, the ESP value should be increased by 1.

Due to our policy of continuous product innovation, some specifications may change without notification.
106 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Acoustic Data
Sound Pressure Levels

Figure 52: Sound Pressure Measurement Location. • Measurements are taken 3.3 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of ±3.
Microphone • Sound pressure levels are tested in an anechoic chamber under ISO Standard
3745.
Operating Conditions:
• Power source: 220V/60 Hz
• Sound level will vary depending on a range of factors including the construc-
3.3ft

tion (acoustic absorption coefficient) of a particular room in which the unit was
installed.

3.3ft

Vertical / Horizontal Air Handler


Table 92: Vertical / Horizontal Air Handler Unit Sound Pressure Levels.
Sound Pressure Levels dB(A)
Model
High Fan Speed Medium Fan Speed Low Fan Speed
NJ Frames
ARNU123NJA4 42 41 39
ARNU183NJA4 42 42 41
ARNU243NJA4 43 42 41
ARNU303NJA4 44 43 42
ARNU363NJA4 45 44 43
NK Frames
ARNU423NKA4 46 44 41
ARNU483NKA4 49 47 41
ARNU543NKA4 50 49 47

Figure 53: ARNU123NJA4, ARNU183NJA4, and ARNU243NJA4 Sound Pressure Level Diagrams.
ARNU123NJA4 ARNU183NJA4 ARNU243NJA4

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 107
Vertical / Horizontal Air Handler
Acoustic Data
Sound Pressure Levels

Figure 54: ARNU303NJA4, ARNU363NJA4, and ARNU423NKA4 Sound Pressure Level Diagrams.
ARNU303NJA4 ARNU363NJA4 ARNU423NKA4
MULTI V Ducted Indoor Unit Engineering Manual

Figure 55: ARNU483NKA4 and ARNU543NKA4 Sound Pressure Level Diagrams.


ARNU483NKA4 ARNU543NKA4

Due to our policy of continuous product innovation, some specifications may change without notification.
108 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Acoustic Data
Sound Power Levels

Sound Power Levels


Table 93: Vertical / Horizontal Air Handler Unit Sound Power Levels. • Data is valid under diffuse field conditions.
Sound Power Levels dB(A) • Data is valid under nominal operating conditions.
Model • Sound power level is measured using rated conditions, and tested
High Fan Speed
NJ Frames in a reverberation room per ISO 3741 standards.
ARNU123NJA4 59 • Sound level will vary depending on a range of factors such as
ARNU183NJA4 59 construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
ARNU243NJA4 60
• Reference acoustic intensity: 0dB = 10E-6μW/m2
ARNU303NJA4 60
ARNU363NJA4 61
NK Frames
ARNU423NKA4 61
ARNU483NKA4 62

Vertical / Horizontal Air Handler


ARNU543NKA4 63

Figure 56: ARNU123NJA4, ARNU183NJA4, and ARNU243NJA4 Sound Power Level Diagrams.
ARNU123NJA4 ARNU183NJA4 ARNU243NJA4

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 109
Vertical / Horizontal Air Handler
Acoustic Data
Sound Power Levels

Figure 57: ARNU303NJA4, ARNU363NJA4, and ARNU423NKA4 Sound Power Level Diagrams.
ARNU303NJA4 ARNU363NJA4 ARNU423NKA4
MULTI V Ducted Indoor Unit Engineering Manual

Figure 58: ARNU483NKA4 and ARNU543NKA4 Sound Power Level Diagrams.


ARNU483NKA4 ARNU543NKA4

Due to our policy of continuous product innovation, some specifications may change without notification.
110 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Cooling Capacity Tables
ARNU123NJA4, ARNU183NJA4, ARNU243NJA4

Table 94: ARNU123NJA4, ARNU183NJA4, ARNU243NJA4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 15.5 10.9
25 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 15.5 10.9
30 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 15.5 10.9
35 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 15.5 10.9
40 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 15.5 10.9
45 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 15.5 10.9
50 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 15.5 10.9
55 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 15.5 10.9
60 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 15.4 10.8
ARNU123NJA4 /
65 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 15.1 10.6
12.0
70 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 14.9 10.5
75 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 14.3 10.9 14.5 10.2
80 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.5 11 13.9 10.8 14.2 10.2

Vertical / Horizontal Air Handler


85 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.3 10.9 13.5 10.4 13.7 9.8
90 7.9 7.8 9.6 9 10.8 9.6 12 10.2 13.1 10.7 13.2 10.2 13.5 9.7
95 7.9 7.8 9.6 9 10.8 9.6 12 10.2 12.9 10.6 13.1 10.1 13.3 9.6
100 7.9 7.8 9.6 9 10.8 9.6 12 10.2 12.6 10.5 12.9 10 13.1 9.5
105 7.9 7.8 9.1 8.6 10.3 9.2 11.5 9.8 11.8 9.8 12.4 9.7 12.6 9.3
110 7.7 7.6 8.7 8.1 9.6 8.6 10.8 9.2 11.1 9.2 11.8 9.2 12.3 9
23 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 23.2 13.6
25 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 23.2 13.6
30 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 23.2 13.6
35 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 23.2 13.6
40 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 23.2 13.6
45 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 23.2 13.6
50 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 23.2 13.6
55 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 23.2 13.6
60 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 23 13.5
ARNU183NJA4 /
65 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 22.7 13.3
18.0
70 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 22.3 13.1
75 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 21.4 13.6 21.8 12.8
80 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20.2 13.7 20.9 13.5 21.2 12.7
85 11.9 9.8 14.4 11.3 16.2 12 18 12.8 20 13.6 20.2 12.9 20.5 12.3
90 11.9 9.8 14.4 11.3 16.2 12 18 12.8 19.6 13.4 19.8 12.7 20.2 12.1
95 11.9 9.8 14.4 11.3 16.2 12 18 12.8 19.3 13.3 19.6 12.7 20 12
100 11.9 9.8 14.4 11.3 16.2 12 18 12.8 18.9 13.1 19.3 12.5 19.6 11.9
105 11.9 9.8 13.7 10.7 15.5 11.5 17.3 12.3 17.6 12.3 18.5 12.1 18.9 11.6
110 11.5 9.5 13 10.1 14.4 10.7 16.2 11.5 16.6 11.5 17.6 11.5 18.4 11.2
23 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 31 18.9
25 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 31 18.9
30 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 31 18.9
35 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 31 18.9
40 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 31 18.9
45 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 31 18.9
50 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 31 18.9
55 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 31 18.9
60 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 30.7 18.8
ARNU243NJA4 /
65 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 30.2 18.5
24.0
70 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 29.8 18.2
75 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 28.6 18.9 29 17.8
80 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.9 19.1 27.8 18.8 28.3 17.7
85 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.6 18.9 26.9 18 27.4 17
90 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 26.2 18.6 26.4 17.7 26.9 16.8
95 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 25.7 18.5 26.2 17.6 26.6 16.6
100 15.8 13.6 19.2 15.7 21.6 16.7 24 17.8 25.2 18.2 25.7 17.4 26.2 16.5
105 15.8 13.6 18.2 14.9 20.6 16 23 17 23.5 17 24.7 16.8 25.2 16.1
110 15.4 13.2 17.3 14.1 19.2 14.9 21.6 16 22.1 16 23.5 16 24.5 15.6
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 111
Vertical / Horizontal Air Handler
Cooling Capacity Tables
ARNU303NJA4, ARNU363NJA4, ARNU423NKA4

Table 95: ARNU303NJA4, ARNU363NJA4, ARNU423NKA4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 38.8 22.9
25 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 38.8 22.9
30 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 38.8 22.9
35 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 38.8 22.9
40 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 38.8 22.9
45 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 38.8 22.9
50 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 38.8 22.9
55 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 38.8 22.9
60 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 38.4 22.8
MULTI V Ducted Indoor Unit Engineering Manual

ARNU303NJA4 /
65 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 37.8 22.4
30.0
70 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 37.3 22.1
75 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 35.8 22.9 36.3 21.6
80 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.6 23.2 34.8 22.8 35.4 21.5
85 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 33.3 22.9 33.6 21.8 34.3 20.6
90 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 32.8 22.6 33.0 21.5 33.6 20.4
95 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 32.1 22.4 32.8 21.3 33.3 20.1
100 19.8 16.5 24.0 19.0 27.0 20.2 30.0 21.6 31.5 22.1 32.1 21.1 32.8 20.0
105 19.8 16.5 22.8 18.1 25.8 19.4 28.8 20.6 29.4 20.6 30.9 20.4 31.5 19.5
110 19.3 16.0 21.6 17.1 24.0 18.1 27.0 19.4 27.6 19.4 29.4 19.4 30.6 18.9
23 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
25 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
30 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
35 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
40 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
45 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
50 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.5
55 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.4 27.6
60 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 46.1 27.4
ARNU363NJA4 /
65 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 45.4 27.0
36.0
70 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 44.6 26.6
75 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 42.8 27.6 43.6 26.0
80 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.3 27.8 41.8 27.4 42.5 25.9
85 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 40.0 27.6 40.3 26.2 41.0 24.8
90 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 39.2 27.1 39.6 25.8 40.3 24.5
95 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 38.5 27.0 39.2 25.7 40.0 24.3
100 23.8 19.9 28.8 22.9 32.4 24.4 36.0 25.9 37.8 26.5 38.5 25.4 39.2 24.1
105 23.8 19.9 27.4 21.7 31.0 23.3 34.6 24.9 35.3 24.9 37.1 24.6 37.8 23.5
110 23.0 19.3 25.9 20.6 28.8 21.7 32.4 23.3 33.1 23.3 35.3 23.4 36.7 22.8
23 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
25 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
30 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
35 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
40 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
45 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
50 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.1
55 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 54.2 32.2
60 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 53.8 32.0
ARNU42NKA4 /
65 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 52.9 31.5
42.0
70 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 52.1 31.0
75 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 50.0 32.2 50.8 30.3
80 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 47.0 32.5 48.7 32.0 49.6 30.2
85 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 46.6 32.2 47.0 30.6 47.9 29.0
90 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 45.8 31.6 46.2 30.1 47.0 28.5
95 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 44.9 31.4 45.8 29.9 46.6 28.3
100 27.7 23.2 33.6 26.7 37.8 28.5 42.0 30.2 44.1 31.0 44.9 29.7 45.8 28.1
105 27.7 23.2 31.9 25.3 36.1 27.2 40.3 29.0 41.2 29.0 43.3 28.6 44.1 27.4
110 26.9 22.5 30.2 24.0 33.6 25.3 37.8 27.2 38.6 27.2 41.2 27.3 42.8 26.6
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
112 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Cooling Capacity Tables
ARNU483NKA4, ARNU543NKA4

Table 96: ARNU483NKA4, ARNU543NKA4 Cooling Capacity Table.


Indoor Air Temperature (°F DB / WB)
Outdoor 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76
Model No. / Air
Capacity Index (°FTemp. TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
DB) MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 61.9 35.2
25 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 61.9 35.2
30 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 61.9 35.2
35 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 61.9 35.2
40 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 61.9 35.2
45 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 61.9 35.2
50 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 61.9 35.2
55 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 61.9 35.2
60 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 61.4 35.0
ARNU483NKA4 /
65 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 60.5 34.5
48.0
70 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 59.5 34.0
75 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 57.1 35.3 58.1 33.2
80 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.8 35.6 55.7 35.1 56.6 33.0

Vertical / Horizontal Air Handler


85 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 53.3 35.2 53.8 33.5 54.7 31.7
90 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 52.3 34.6 52.8 33.0 53.8 31.3
95 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 51.4 34.4 52.3 32.8 53.3 31.0
100 31.7 25.4 38.4 29.2 43.2 31.2 48.0 33.1 50.4 33.9 51.4 32.5 52.3 30.7
105 31.7 25.4 36.5 27.8 41.3 29.8 46.1 31.8 47.0 31.8 49.4 31.4 50.4 30.0
110 30.7 24.7 34.6 26.3 38.4 27.7 43.2 29.8 44.2 29.8 47.0 29.9 49.0 29.2
23 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 69.7 39.6
25 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 69.7 39.6
30 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 69.7 39.6
35 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 69.7 39.6
40 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 69.7 39.6
45 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 69.7 39.6
50 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 69.7 39.6
55 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 69.7 39.6
60 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 69.1 39.4
ARNU543NKA4 /
65 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 68.0 38.8
54.0
70 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 67.0 38.2
75 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 64.3 39.7 65.3 37.3
80 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 60.5 40.0 62.6 39.4 63.7 37.2
85 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 59.9 39.7 60.5 37.7 61.6 35.7
90 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 58.9 38.9 59.4 37.1 60.5 35.2
95 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 57.8 38.7 58.9 36.9 59.9 34.9
100 35.6 28.6 43.2 32.9 48.6 35.1 54.0 37.3 56.7 38.2 57.8 36.6 58.9 34.6
105 35.6 28.6 41.0 31.2 46.4 33.5 51.8 35.8 52.9 35.7 55.6 35.3 56.7 33.8
110 34.6 27.7 38.9 29.6 43.2 31.2 48.6 33.5 49.7 33.6 52.9 33.6 55.1 32.8
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 113
Vertical / Horizontal Air Handler
Heating Capacity Tables
ARNU123NJA4, ARNU183NJA4, ARNU243NJA4, ARNU303NJA4

Table 97: ARNU073B3G4, ARNU093B3G4, ARNU123B3G4, ARNU153B3G4 Heating Capacity Table.


Indoor Air Temperature (°F DB)
Outdoor Air Temp. 59 61 64 67 70 73 76 80
Model No. /
Capacity Index TC TC TC TC TC TC TC TC
°F DB °F WB MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 9 9 9 9 8.9 8.9 8.9 8.9
0 -0.4 9.3 9.3 9.3 9.3 9.3 9.2 9.2 9.2
5.0 4.5 10.5 10.4 10.3 10.3 10.3 10.3 10.3 10.3
10.0 9.0 10.9 10.9 10.9 10.8 10.8 10.8 10.8 10.8
15.0 14.0 11.6 11.6 11.6 11.6 11.6 11.6 11.5 11.3
20.0 19.0 12.3 12.3 12.3 12.3 12 12 11.8 11.7
25.0 23.0 12.8 12.8 12.8 12.8 12.8 12.6 12.4 12.3
ARNU123NJA4 /
30.0 28.0 13.1 13.1 13.1 13.1 13.1 12.8 12.4 12
12.0
35.0 32.0 13.5 13.5 13.5 13.5 13.4 13.1 12.4 11.8
MULTI V Ducted Indoor Unit Engineering Manual

40.0 36.0 14 14 14 14 13.5 13.1 12.4 11.8


45.0 41.0 14.6 14.6 14.6 14.2 13.5 13.1 12.4 11.8
47.0 43.0 15.1 15 14.9 14.2 13.5 13.1 12.4 11.8
50.0 46.0 16.2 15.5 14.9 14.2 13.5 13.1 12.4 11.8
55.0 51.0 16.5 15.7 14.9 14.2 13.5 13.1 12.4 11.8
60.0 56.0 16.5 15.7 14.9 14.2 13.5 13.1 12.4 11.8
-4 -4.4 13.4 13.4 13.4 13.4 13.2 13.2 13.2 13.2
0 -0.4 13.8 13.8 13.8 13.8 13.8 13.6 13.6 13.6
5.0 4.5 15.6 15.4 15.2 15.2 15.2 15.2 15.2 15.2
10.0 9.0 16.2 16.2 16.2 16 16 16 16 16
15.0 14.0 17.2 17.2 17.2 17.2 17.2 17.2 17 16.8
20.0 19.0 18.2 18.2 18.2 18.2 17.8 17.8 17.5 17.3
25.0 23.0 19 19 19 19 19 18.6 18.4 18.2
ARNU183NJA4 /
30.0 28.0 19.4 19.4 19.4 19.4 19.4 19 18.4 17.8
18.0
35.0 32.0 20 20 20 20 19.8 19.4 18.4 17.5
40.0 36.0 20.8 20.8 20.8 20.8 20 19.4 18.4 17.5
45.0 41.0 21.6 21.6 21.6 21 20 19.4 18.4 17.5
47.0 43.0 22.4 22.2 22 21 20 19.4 18.4 17.5
50.0 46.0 24 23 22 21 20 19.4 18.4 17.5
55.0 51.0 24.5 23.2 22 21 20 19.4 18.4 17.5
60.0 56.0 24.5 23.2 22 21 20 19.4 18.4 17.5
-4 -4.4 18.1 18.1 18.1 18.1 17.8 17.8 17.8 17.8
0 -0.4 18.6 18.6 18.6 18.6 18.6 18.4 18.4 18.4
5.0 4.5 21.1 20.8 20.5 20.5 20.5 20.5 20.5 20.5
10.0 9.0 21.9 21.9 21.9 21.6 21.6 21.6 21.6 21.6
15.0 14.0 23.2 23.2 23.2 23.2 23.2 23.2 23 22.7
20.0 19.0 24.6 24.6 24.6 24.6 24 24 23.6 23.3
25.0 23.0 25.7 25.7 25.7 25.7 25.7 25.1 24.8 24.6
ARNU243NJA4 /
30.0 28.0 26.2 26.2 26.2 26.2 26.2 25.7 24.8 24.1
24.0
35.0 32.0 27 27 27 27 26.7 26.2 24.8 23.6
40.0 36.0 28.1 28.1 28.1 28.1 27 26.2 24.8 23.6
45.0 41.0 29.2 29.2 29.2 28.4 27 26.2 24.8 23.6
47.0 43.0 30.2 30 29.7 28.4 27 26.2 24.8 23.6
50.0 46.0 32.5 31.1 29.7 28.4 27 26.2 24.8 23.6
55.0 51.0 33 31.3 29.7 28.4 27 26.2 24.8 23.6
60.0 56.0 33 31.3 29.7 28.4 27 26.2 24.8 23.6
-4 -4.4 22.8 22.8 22.8 22.8 22.4 22.4 22.4 22.4
0 -0.4 23.5 23.5 23.5 23.5 23.5 23.1 23.1 23.1
5.0 4.5 26.5 26.2 25.8 25.8 25.8 25.8 25.8 25.8
10.0 9.0 27.5 27.5 27.5 27.2 27.2 27.2 27.2 27.2
15.0 14.0 29.2 29.2 29.2 29.2 29.2 29.2 28.9 28.6
20.0 19.0 30.9 30.9 30.9 30.9 30.2 30.2 29.8 29.3
25.0 23.0 32.3 32.3 32.3 32.3 32.3 31.6 31.3 30.9
ARNU303NJA4 /
30.0 28.0 33.0 33.0 33.0 33.0 33.0 32.3 31.3 30.3
30.0
35.0 32.0 34.0 34.0 34.0 34.0 33.7 33.0 31.3 29.7
40.0 36.0 35.4 35.4 35.4 35.4 34.0 33.0 31.3 29.7
45.0 41.0 36.7 36.7 36.7 35.7 34.0 33.0 31.3 29.7
47.0 43.0 38.1 37.7 37.4 35.7 34.0 33.0 31.3 29.7
50.0 46.0 40.9 39.1 37.4 35.7 34.0 33.0 31.3 29.7
55.0 51.0 41.6 39.4 37.4 35.7 34.0 33.0 31.3 29.7
60.0 56.0 41.6 39.4 37.4 35.7 34.0 33.0 31.3 29.7
TC: Total Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
114 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Vertical / Horizontal Air Handler
Heating Capacity Tables
ARNU363NJA4, ARNU423NKA4, ARNU483NKA4, ARNU543NKA4

Table 98: ARNU363NJA4, ARNU423NKA4, ARNU483NKA4, ARNU542NKA4 Heating Capacity Table.


Indoor Air Temperature (°F DB)
Outdoor Air Temp. 59 61 64 67 70 73 76 80
Model No. /
Capacity Index TC TC TC TC TC TC TC TC
°F DB °F WB MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 26.8 26.8 26.8 26.8 26.4 26.4 26.4 26.4
0 -0.4 27.6 27.6 27.6 27.6 27.6 27.2 27.2 27.2
5.0 4.5 31.2 30.8 30.4 30.4 30.4 30.4 30.4 30.4
10.0 9.0 32.4 32.4 32.4 32.0 32.0 32.0 32.0 32.0
15.0 14.0 34.4 34.4 34.4 34.4 34.4 34.4 34.0 33.6
20.0 19.0 36.4 36.4 36.4 36.4 35.5 35.5 35.0 34.5
25.0 23.0 38.0 38.0 38.0 38.0 38.0 37.2 36.8 36.4
ARNU363NJA4 /
30.0 28.0 38.8 38.8 38.8 38.8 38.8 38.0 36.8 35.6
36.0
35.0 32.0 40.0 40.0 40.0 40.0 39.6 38.8 36.8 34.9
40.0 36.0 41.6 41.6 41.6 41.6 40.0 38.8 36.8 34.9
45.0 41.0 43.2 43.2 43.2 42.0 40.0 38.8 36.8 34.9
47.0 43.0 44.8 44.4 44.0 42.0 40.0 38.8 36.8 34.9
50.0 46.0 48.1 46.0 44.0 42.0 40.0 38.8 36.8 34.9

Vertical / Horizontal Air Handler


55.0 51.0 48.9 46.4 44.0 42.0 40.0 38.8 36.8 34.9
60.0 56.0 48.9 46.4 44.0 42.0 40.0 38.8 36.8 34.9
-4 -4.4 30.8 30.8 30.8 30.8 30.4 30.4 30.4 30.4
0 -0.4 31.7 31.7 31.7 31.7 31.7 31.3 31.3 31.3
5.0 4.5 35.9 35.4 35.0 35.0 35.0 35.0 35.0 35.0
10.0 9.0 37.3 37.3 37.3 36.8 36.8 36.8 36.8 36.8
15.0 14.0 39.6 39.6 39.6 39.6 39.6 39.6 39.1 38.6
20.0 19.0 41.9 41.9 41.9 41.9 40.8 40.8 40.3 39.7
25.0 23.0 43.7 43.7 43.7 43.7 43.7 42.8 42.3 41.9
ARNU42NKA4 /
30.0 28.0 44.6 44.6 44.6 44.6 44.6 43.7 42.3 41.0
42.0
35.0 32.0 46.0 46.0 46.0 46.0 45.5 44.6 42.3 40.1
40.0 36.0 47.8 47.8 47.8 47.8 46.0 44.6 42.3 40.1
45.0 41.0 49.7 49.7 49.7 48.3 46.0 44.6 42.3 40.1
47.0 43.0 51.5 51.1 50.6 48.3 46.0 44.6 42.3 40.1
50.0 46.0 55.3 52.9 50.6 48.3 46.0 44.6 42.3 40.1
55.0 51.0 56.3 53.4 50.6 48.3 46.0 44.6 42.3 40.1
60.0 56.0 56.3 53.4 50.6 48.3 46.0 44.6 42.3 40.1
-4 -4.4 36.2 36.2 36.2 36.2 35.6 35.6 35.6 35.6
0 -0.4 37.3 37.3 37.3 37.3 37.3 36.7 36.7 36.7
5.0 4.5 42.1 41.6 41.0 41.0 41.0 41.0 41.0 41.0
10.0 9.0 43.7 43.7 43.7 43.2 43.2 43.2 43.2 43.2
15.0 14.0 46.4 46.4 46.4 46.4 46.4 46.4 45.9 45.4
20.0 19.0 49.1 49.1 49.1 49.1 47.9 47.9 47.3 46.6
25.0 23.0 51.3 51.3 51.3 51.3 51.3 50.2 49.7 49.1
ARNU483NKA4 /
30.0 28.0 52.4 52.4 52.4 52.4 52.4 51.3 49.7 48.1
48.0
35.0 32.0 54.0 54.0 54.0 54.0 53.5 52.4 49.7 47.1
40.0 36.0 56.2 56.2 56.2 56.2 54.0 52.4 49.7 47.1
45.0 41.0 58.3 58.3 58.3 56.7 54.0 52.4 49.7 47.1
47.0 43.0 60.5 59.9 59.4 56.7 54.0 52.4 49.7 47.1
50.0 46.0 64.9 62.1 59.4 56.7 54.0 52.4 49.7 47.1
55.0 51.0 66.1 62.6 59.4 56.7 54.0 52.4 49.7 47.1
60.0 56.0 66.1 62.6 59.4 56.7 54.0 52.4 49.7 47.1
-4 -4.4 40.2 40.2 40.2 40.2 39.6 39.6 39.6 39.6
0 -0.4 41.4 41.4 41.4 41.4 41.4 40.8 40.8 40.8
5.0 4.5 46.8 46.2 45.6 45.6 45.6 45.6 45.6 45.6
10.0 9.0 48.6 48.6 48.6 48.0 48.0 48.0 48.0 48.0
15.0 14.0 51.6 51.6 51.6 51.6 51.6 51.6 51.0 50.4
20.0 19.0 54.6 54.6 54.6 54.6 53.3 53.3 52.5 51.8
25.0 23.0 57.0 57.0 57.0 57.0 57.0 55.8 55.2 54.6
ARNU543NKA4 /
30.0 28.0 58.2 58.2 58.2 58.2 58.2 57.0 55.2 53.5
54.0
35.0 32.0 60.0 60.0 60.0 60.0 59.4 58.2 55.2 52.4
40.0 36.0 62.4 62.4 62.4 62.4 60.0 58.2 55.2 52.4
45.0 41.0 64.8 64.8 64.8 63.0 60.0 58.2 55.2 52.4
47.0 43.0 67.2 66.6 66.0 63.0 60.0 58.2 55.2 52.4
50.0 46.0 72.1 69.0 66.0 63.0 60.0 58.2 55.2 52.4
55.0 51.0 73.4 69.6 66.0 63.0 60.0 58.2 55.2 52.4
60.0 56.0 73.4 69.6 66.0 63.0 60.0 58.2 55.2 52.4
TC: Total Capacity (MBh).

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. VAH | 115
Vertical / Horizontal Air Handler
Optional Accessories

Table 99: Optional Accessories for Vertical / Horizontal Air Handler Units.
Accessory Model Number
5kW Electric Heater ANEH053B1
10kW Electric Heater ANEH103B2
15kW Electric Heater ANEH153B2
20kW Electric Heater ANEH203B2
All accessories are sold separately.

Figure 59: Electric Heater.


MULTI V Ducted Indoor Unit Engineering Manual

Example: 5kW Capacity Heater


Bracket
Bi metal

Heater Coil
Terminal Block

Relay

Heater Cable

Image shown above may vary depending on model capacity.

Table 100: Electric Heater Capacities.


Model Number / Heater Capacity
Indoor Unit Model No. / Capacity (MBh)
ANEH053B1 (5kW) ANEH103B2 (10kW) ANEH153B2 (15kW) ANEH203B2 (20kW)
ARNU123NJA4 (12) X Not available Not available Not available
ARNU183NJA4 (18) X Not available Not available Not available
ARNU243NJA4 (24) X X Not available Not available
ARNU303NJA4 (30) X X Not available Not available
ARNU363NJA4 (36) X X Not available Not available
ARNU423NKA4 (42) X X X X
ARNU483NKA4 (48) X X X X
ARNU543NKA4 (54) X X X X

For additional information, refer to the Electric Heater Manual.

Due to our policy of continuous product innovation, some specifications may change without notification.
116 | VAH © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
APPLICATION
GUIDELINES
Selecting the Best Location on page 118
General Mounting - High, Low, and Built In Ducted Units
on page 120
General Mounting - Vertical / Horizontal Air Handling Units
on page 122
General Drain Piping Information on page 124
Wiring Guidelines on page 126
Wired Controller Location on page 128
Acronyms on page 129
Application Guidelines
Selecting the Best Location

Selecting the Best Location Figure 60: Selecting the Best Location / Minimum Clearance Require-
ments (for High Static, Low Static, Built In Ducted Units).
Do’s
• Place the unit where air circulation will not be blocked. Service access
23-5/8 x 23-5/8
• Place the unit where drainage can be obtained easily and to mini-
mize the length of the condensate drain piping. Control box

• Place the unit where noise prevention is taken into consideration.


• Place the unit in a location that can support a load four times the
indoor unit weight, and where the indoor unit can be level.
• Ensure there is sufficient maintenance space.
MULTI V Ducted Indoor Unit Engineering Manual

39-3/8
• Locate the indoor unit in a location where it can be easily connect- 23-5/8 23-5/8
ed to the outdoor unit / heat recovery unit.

Don’ts
• Avoid installing the unit near high-frequency generators.
• Do not install the unit near a doorway.
• The unit should not be installed near a heat or steam source, or Minumim 13/16 for High and Low Static Ducted Units
where considerable amounts of oil, iron powder, or flour are used. Unit: inch
(These materials may generate condensate, cause a reduction in
heat exchanger efficiency, or the drain pump to malfunction. If this Figure 61: Minimum Clearances for Vertical / Horizontal Air Handler Units.
is a potential problem, install a ventilation fan large enough to vent
out these materials.) Minimum 14 inches

The unit should not be installed where sulfuric acid and flammable
or corrosive gases are generated, vented into, or stored. There is
risk of fire, explosion, and physical injury or death. Front

The unit may be damaged, may malfunction, and / or will


not operate as designed if installed in any of the conditions Rear
listed. 0 inches
0 inches* 0 inches*
More than
23-5/8 inches
If the unit is installed near a body of water, the installation parts are
at risk of corroding. Appropriate anti-corrosion methods should be *When using top panel access holes
taken for the unit and all installation parts. Minimum 14 inches for power wiring / communications cable

Installing in an Area Exposed to Unconditioned Air


Figure 62: Installing Near a Heat or Steam Source.
In some installation applications, areas (floors, walls) in some rooms
may be exposed to unconditioned air (room may be above or next to Indoor Unit
an unheated garage or storeroom). To countermeasure:

• Verify that carpet is or will be installed (carpet may increase the


temperature by three [3] degrees).
Include enough Install a ventilation fan
distance with sufficient capacity
• Add insulation between the floor joists.
Heat or steam source

• Install radiant heat or another type of heating system to the floor.

Due to our policy of continuous product innovation, some specifications may change without notification.
118 | Guidelines © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Application Guidelines
Selecting the Best Location

Figure 63: Service Clearances for High Static Ducted Units. Figure 64: Service Clearances for Low Static and Built In Ducted Units.

Service access
23-5/8 x 23-5/8
Control box
B (Minimum)
A (Minimum)

A
Unit: inch

Application Guidelines
Figure 65: Minimum Clearances for Built In Ducted Units with
Accessories.
Ceiling

Service Space
Minimum 7-5/8

A
With Return Air Grille

Table 101: Service Clearance Dimensions For High Static, Low Static, and
Minimum 7-5/8

Built In Ducted Units.


Dimensions (inches)
With Return Air Grille and Frame
Return Air Canvas Duct Kit A B
High Static Ducted
BG 23-5/8 23-5/8
BR 23-5/8 23-5/8

Refer to Return Air Grille and Return Air Canvas Installation B8 23-5/8 23-5/8
Manual for detail installation of built in ducted units. Low Static Ducted
Unit: inch L1 31-1/2 31-1/2
L2 31-1/2 39-3/8
L3 31-1/2 47-1/4
Built In Ducted
B3 23-5/8 35-7/16
B4 23-5/8 43-5/16

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 119
Application Guidelines
General Mounting - High, Low, and Built In Ducted Units

General Mounting - High, Low, and Built In Ducted Units


• The ceiling should be strong and solid enough to protect the indoor • Apply a filter accessory at the air return opening.
unit from vibration. • Install the unit with a slope towards the drainage point to ensure
• Refer to dimensions table below for each indoor unit type. condensate drains easily.
• Apply a joint-canvas between the unit and duct to absorb unneces-
sary vibration.
Figure 66: High Static Ducted BG, BR Frame Bolt Locations. Figure 67: High Static Ducted B8 Frame Bolt Locations.
A A
B B K L
F J
MULTI V Ducted Indoor Unit Engineering Manual

C
E

EC
D

G
F

GD
I

H
H Drainage Point I
Table 102: High Static Ducted BG, BR, B8 Frame Suspension Bolt Positions
Dimensions (inches)
Frame
A B C D E F G H I J K L
BG 48-9/16 46-9/16 13-5/8 1-3/4 17-3/4 1-3/16 3-5/8 32-11/16 7-5/16 - - -
BR 50-7/16 48-7/16 18-13/16 2-1/4 23-1/4 1-3/16 4-11/16 39-5/8 11-9/16 - -
B8 63-7/8 61-5/8 22-7/8 11-1/2 27-3/8 55-1/8 18-1/8 44-3/16 66-3/16 15-3/8 17-9/16 5/8

Table 103: Low Static L1, L2, L3 Suspension Bolt Positions. Figure 68: Low Static Ducted Bolt Locations.
Dimension (inches) E
Frame
A B C D E F G H I J G
L1 28-7/8 30-7/16 24-3/4 27-9/16 1-7/16 7-1/2 13/16 26 6-1/8 27-9/16
L2 36-3/4 38-5/16 24-3/4 27-9/16 1-7/16 7-1/2 13/16 33-7/8 6-1/8 35-7/16
L3 44-5/8 46-3/16 24-3/4 27-9/16 1-7/16 7-1/2 13/16 41-3/4 6-1/8 43-5/16 D C

J
A
B
F
I

H Drain
Hole
Due to our policy of continuous product innovation, some specifications may change without notification.
120 | Guidelines © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Application Guidelines
General Mounting - High, Low, and Built In Ducted Units

Table 104: Built In Ducted Suspension Bolt Positions. Figure 69: Built In Ducted Bolt Locations.
Dimensions (inches) B
Frame A
A B C D E F G H I J
B3 33-7/16 35-7/16 15 22-5/8 3-11/16 7-1/2 7/8 31-5/16 6-7/16 32-3/8
J
B4 44-7/16 46-1/2 15 22-5/8 3-11/16 7-1/2 7/8 41-15/16 6-7/16 43-5/16

D
C
E
G
General Mounting Procedure

F
I
1. Select and mark the areas where the hanging bolts should be placed.

Application Guidelines
2. Drill the holes.
H
3. Install the unit horizontally using a level gauge.
Drainage point

Do not damage power wiring during installation. There is risk of electric shock, Figure 70: Drilling Holes for the Hanging Bolts.
which may result in physical injury or death.

Do not damage power wiring during installation. There is a risk of equipment


malfunction, which may result in property damage.
Figure 71: Hanging Bolt Installation.
Hanging bolt
(W3/8 or M10)
Nut
Flat washer for M10
(W3/8 or M10)
(accessory)
Spring washer
(M10)

Flat washer for M10 Figure 72: Old Versus New Building Hanging Bolt Installation.
(accessory) Old Building New Building
Nut
(W3/8 or M10)
The following parts are field Included with the indoor unit:
supplied: • Flat washer - M10
• Hanging bolt - W-3/8″ or 1/2″
• Nut - W-3/8″ or M10 1 Set Anchor
• Spring washer - M10 2 Plate Washer
3 Spring Washer
The threaded rod hangers (bolts) and hardware must be secure- 4 Nut
ly tightened to prevent the unit from falling from its installation 5 Hanging Bolts
location. There is a risk of personal injury from falling equip-
ment.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 121
Application Guidelines
General Mounting - Vertical / Horizontal Air Handler Units

General Mounting - Vertical / Horizontal Air Handler Units


Vertical / horizontal air handler units can be installed either in an upflow or a horizontal-left position.
General Guidelines
• Support platforms should be sturdy enough to support the air handler unit plus any accessories including filter boxes. The size of the
support should be bigger than the air handler unit; the unit itself should be placed at the center of the support.
• Vibration isolators (field-supplied) must be installed between the air handler unit and the support(s).
• Upflow installation has to be applied if a return plenum and a supply duct are present.
• Secure the plenum to support adapters and duct work.
• To prevent air leaks, seal all ducts following local codes.
• Follow all relevant building codes in installations in which an external condensate pan may be necessary. Supports for air handler units
MULTI V Ducted Indoor Unit Engineering Manual

should be located in or above the external condensate pan.

Specific Guidelines for Horizontal-Left Installation


• Units should not be installed where the access panels face up or down, nor where filter access is obstructed.
• If the air handler unit is suspended, use angled steel brackets with threaded rods as support.
• To ensure proper condensate drainage, the air handler unit must be installed so it is within 1/8″ level of its length and width.

Figure 73: Upflow Installation. Figure 74: Horizontal-Left Installation.


More than 3/8 inch Field-Supplied
Field-Supplied threaded rod Return Plenum
Supply Duct
Field-Supplied
Supply Duct

More than 1-1/2


inch X 1-1/2 inch angle B
A
Recommended
length more than 26
inch with 2 inch C
clearance on both Suspension Support Locations
Field-Supplied sides of unit
Return Plenum Table 105: Horizontal-Left Installation Dimensions.
Dimensions (inches)
Model No. Capacity (Btu/h)
A B C
NJ Frames
ARNU123NJA2 12,000
ARNU183NJA2 18,000
ARNU243NJA2 24,000 4 23 41-3/8
ARNU303NJA2 30,000
ARNU363NJA2 36,000
NK Frames
ARNU423NKA2 42,000
ARNU483NKA2 48,000 4 29 48
ARNU543NKA2 54,000
Due to our policy of continuous product innovation, some specifications may change without notification.
122 | Guidelines © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Application Guidelines
General Mounting - Vertical / Horizontal Air Handler Units

Duct Work For Vertical / Horizontal Air Handler Units Figure 75: Attaching Ducts to the Vertical / Horizontal Air Handler Unit.
• Use at least ten (10) M4-25L screws when attaching the supply
duct to the vertical-horizontal air handler unit.

• To prevent vibration transmission, install flexible connectors be-


tween the supply duct and the vertical-horizontal air handler unit.
If an electrical heater is included, the flexible connector must be
constructed from a heat-resistant material.

• When routed through unconditioned spaces, ducts must be insulat-


ed and covered with vapor barriers.

• Internal acoustical insulation lining may be necessary for a metal


duct system if it does not have a 90° elbow and ten (10) feet of At least ten (10) screws
main duct to the first branch takeoff. (M4-25L)

• Fibrous ducts could be used as a substitute if built and installed


in accordance with the most recent edition of the Sheet Metal and

Application Guidelines
Air Conditioning Contractors’ National Association (SMACNA)
Construction Standard.

• Fibrous ducts and acoustical linings must follow National Fire


Protection Association (NFPA) Standards 90A or 90B as tested by
UL Standard 181 for Class 1 ducts.

• Seal around the ducts to prevent air leaks.


More than
1 inch

At least six (6) screws (M-4-25L)

Table 106: Vertical / Horizontal Air Handler Unit Duct Connection Figure 76: Vertical / Horizontal Air Handler Unit Duct Connection
Dimensions Table. Dimensions Diagram.
Dimensions (inches)
Model No. A B C
D E F G H
Height Width Depth
NJ Frames Front
ARNU123NJA2
48-5/8 18 21-1/4 1-9/16 17-1/2 20 17 12-1/8
ARNU183NJA2
Refrigerant Pipe Right Side
ARNU243NJA2 Connections
Drain
Connections
ARNU303NJA2 48-5/8 18 21-1/4 1-9/16 17-1/2 20 17 12-1/8 for Upflow
ARNU363NJA2 Installation
Drain Connections
NK Frames for Horizontal-Left
ARNU423NKA2 Installation

ARNU483NKA2 48-5/8 25 21-1/4 1-9/16 24-1/2 20 24 12-1/8


ARNU543NKA2 Air Filter Cover

Bottom

Top

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 123
APPLICATION GUIDELINES
General Drain Piping Information

General Drain Piping Information Figure 77: High Static, Low Static, Built In Ducted Indoor Unit Drain
Pump to Drain Piping System.
All ducted indoor units generate water during cooling operation,
therefore, how to properly handle this condensation must be Hanger distance
considered. High Static, Low Static, and Built In Ducted indoor Max. 3.3~4.9 feet
units include factory-installed drain pumps; Vertical / Horizontal Air 11-13/16 inches Hanger Bracket
Handler units have a gravity drain. Depending on the location of the
indoor unit, condensation can be drained directly to the outside of PVC Elbow
1/50~1/100
slope
the building, or a common indoor unit drainage piping system can be Metal PVC Piping
installed. clamp

Vertical / Horizontal Air Handler Unit Drain Information Drain pump Flexible drain hose
MULTI V Ducted Indoor Unit Engineering Manual

• Avoid blocking filter access panel when connecting the condensate Insulation
drain lines.
• An additional external condensate line should run from the unit into Figure 78: Vertical / Horizontal Air Handler Unit Drain Piping System.
the pan. Drain for Upflow Installations Drain for Horizontal-Left Installations
• The entire condensate line should be drained from the external
condensate pan. Horizontal-Left
Drain Access Hole
• Point the drain hose downward for easy drain flow.
• Do not use pipe joint connection or PVC/CPVC for the unit drain Air Filter Cover

line connection. Use Teflon® tape.

Supplementary drain
with proper trap. (Field-
supplied kit can be used.)

Main drain along with suitable trap.


A field-supplied external condensate pan should be installed under- (A field-supplied trap with sufficient depth can be used. Standard-sized traps
neath the entire vertical / horizontal air handler unit. If not, damage are not sufficient. Refer to the U-Trap Specifications figure for the recommended
condensate trap.)
may result due to condensate overflow.
Figure 79: Vertical / Horizontal Air Handler Unit U-Trap Specifications.
• Install the U-Trap to prevent leaks
caused by blocking the intake air filter.
Table 107: Indoor Unit Drainage Specifications.
Applied U-Trap Dimensions
Drain Pipe Dia.
Indoor Unit Drain Type (ID, in.) A ≥ 2-9/16 inch
BG, BR, B8 Frame B ≥ 2C 3/4 inch
High Static Ducted 27-1/2 in. Lift
C ≥ 2 x SP connector
SP = External Pressure B
L1, L2, L3 Frame Drain Pump, Ø1 (in. WG)
Low Static Ducted C
Factory Installed Ex) External Pressure
B3, B4 Frame Built In Ducted = 0.4 in. WG U-Trap
A ≥ 2-9/16 inches A
NJ, NK Frame Vertical / Horizontal B ≥ 1-7/12 inches
Gravity Ø1 C ≥ 13/16 inches
Air Handler Unit

Figure 80: Flexible Drain Hose Connection.

Flexible Drain Hose


Ducted indoor units and vertical / horizontal air handler units include a factory-
provided flexible drain hose (with one or two clamps) to connect the indoor unit
to the drain piping / drain piping system.

Clamp the Flexible Drain Hose Connection


Due to our policy of continuous product innovation, some specifications may change without notification.
124 | Guidelines © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Application Guidelines
General Drain Piping Information

Drain Piping Figure 81: Drain Piping Slope.


• Drain piping must have down slope (1/50 to 1/100).
Upward
• Any holes through the ceilings, walls, etc., must be large enough to Pipe clamp
routing
accommodate the drain piping and insulation. not allowed
• To prevent reversal flow, do not provide up and down slope.
Indoor unit
• For High Static, Low Static, and Built In Ducted Units, the outside
diameter of the drain connection on the indoor unit is 1-1/4 inches.
• For Vertical / Horizontal Air Handling Units, use PVC with a 3/4”
male pipe thread fitting for the condensate pan. Maintenance
• For High Static, Low Static, and Built In Ducted Units, the drain drain port
piping material is polyvinyl chloride pipe (1 inch).

Drain Leak Test Figure 82: Properly Insulating the Drainage Piping.
A leak test should be performed 24 hours after the drainage system
has been installed.

Drain Pipe Insulation

Application Guidelines
To prevent condensate from forming on the drain piping, field-
supplied 5/16 inch thick polyethylene insulation should be properly
installed.

Ensure the indoor unit, refrigerant piping, drain piping, and power wiring /
communication cables are properly supported with anchor bolts and clamp Insulation Insulation Properly Fitting Insulation
hangers positioned at 3.3 to 4.9 foot intervals. Not Required Requir ed

Common Indoor Unit Drainage System Figure 83: Example of a Common Indoor Unit Drainage System.
It is usual work practice to connect individual 45° to 60° Angle 45° to 60° angle for protection against overflow
indoor unit drain pipes to one common indoor unit
drainage system.
45° to 60° Angle
The diameter of the common vertical drain pipe
should be as large as necessary. The diameter of 45° to 60° Angle Position the vent
down to prevent
the horizontal pipe should be the same or larger Common horizontal drain pipe debris from entering
1/50
than the vertical drain pipe. To avoid property to 1
/100 the system
damage in the event of the primary drain becom- Slop
e
ing clogged, and to optimize drain system perfor-
mance, it may be prudent to install a secondary
drain line.
27-1/2 in.
(Maximum pump
Common
Design the drain system to plan for winter opera- lift distance
vertical
[depends on indoor
tion (condensate line may freeze up if condensate unit type]). drain pipe
does not properly drain away). Drain all gener-
ated condensate from the external condensate
Include trap
pan to an appropriate area. Install a trap in the at the end.
condensate lines as near to the indoor unit coil as
possible. To prevent overflow, the outlet of each
trap should be positioned below its connection to • It is recommended that a dedicated drain pipe be installed for the air conditioning
the condensate pan. All traps should be primed, system. If the indoor unit drainage system is shared with a rainwater drain, waste
insulated, and leak tested. water, or any other type of building drain system, back flow, leaks, ice may form,
or noxious odors may infiltrate the air conditioning system.
• Install a trap if the drain access to the outside faces an undesirable location (i.e.,
sewer), otherwise, noxious odors may infiltrate the air conditioning system.
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 125
Application Guidelines
Wiring Guidelines

General Power Wiring / Communications Cable Guidelines


• Follow manufacturer’s circuit diagrams displayed on the inside of the control box cover.
• Have a separate power supply for the indoor units.
• Provide a circuit breaker switch between the power source and the indoor unit.
• Confirm power source specifications.
• Confirm that the electrical capacity is sufficient.
• Starting current must be maintained ±10 percent of the rated current marked on the name plate.
• Confirm wiring / cable thickness specifications:
• Power wiring is field supplied. Wire size is selected based on the larger MCA value, and must comply with the applicable local and
national codes.
MULTI V Ducted Indoor Unit Engineering Manual

• Communication cable must be a minimum of 18 AWG, two-conductor, stranded, shielded, and must comply with the applicable local
and national codes. Ensure the communication cable is properly grounded at the master outdoor unit only. Do not ground the ODU-IDU
communication cable at any other point.
• It is recommended that a circuit breaker is installed, especially if conditions could become wet or moist.
• Include a disconnect in the power wiring system. Add an air gap contact separation of at least 1/8 inch in each active (phase) conductor.
• Any openings where the field wiring enters the cabinet must be completely sealed.

• Terminal screws may loosen during transport. Properly tighten the terminal connections during installation or risk electric shock,
physical injury or death.
• Loose wiring may cause the wires to burnout or the terminal to overheat and catch fire. There is a risk of electric shock, physical
injury or death.

• Terminal screws may loosen during transport. Properly tighten the terminal connections during installation or risk equipment
malfunction or property damage.
• Loose wiring may cause unit malfunction, the wires to burnout or the terminal to overheat and catch fire. There is a risk of equip-
ment malfunction or property damage.
A voltage drop may cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.

Power Wiring and Communications Cable Connections


1. Insert the power wiring / communications cable Figure 84: Location of Power Wiring / Communications Cable Terminals in the High Static
from the outdoor unit or heat recovery unit and Low Static Ducted Indoor Units.
(Heat Recovery systems only) using the desig- BG, BR, B8 Frame Terminals
nated path in the indoor unit.

2. Connect each wire to its appropriate terminal


L(L1) N(L2)
A B Lock nut
on the indoor unit control board. Verify that the
color and terminal numbers from the outdoor Conduit Conduit
mounting
unit or heat recovery unit (Heat Recovery sys- Power Supply Communications
plate

tems only) wiring match the color and terminal High Voltage
(208/230V)
numbers on the indoor unit.

3. Secure the power wiring / communications


cable.

Due to our policy of continuous product innovation, some specifications may change without notification.
126 | Guidelines © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Application Guidelines
Wiring Guidelines

Figure 85: Location of Power Wiring / Communications Cable Terminals in the Built In Ducted Indoor Unit.

B3, B4 Frame Terminals

L(L1) N(L2) YL RD BK
3(A) 4(B)
Lock nut

Power Supply Communications


Conduit High Voltage
(208/230V)

Figure 86: Location of Power Wiring / Communications Cable Terminals in the Vertical / Horizontal Air Handler Unit.

Application Guidelines
Power Wiring Through
Optional Access Hole

Communication Cable Through


Optional Access Hole

Figure 87: Terminal Block in the High Static (BG, BR, B8 Frame) Ducted Indoor Unit.
Outdoor Unit Terminal Block
Indoor Unit Terminal Block
SODU IDU INTERNET DRY1 DRY2 GND 12V
L(L1) N(L2) YL RD BK A B B A - - B A - - - -

Power Input Ground Wired Controller


208-230V /
60 Hz / 1 Phase

Figure 88: Terminal Block in the Low Static (L1, L2, L2 Frame) Ducted Indoor Unit.
Outdoor Unit Terminal Block
Indoor Unit Terminal Block SODU IDU INTERNET DRY1 DRY2 GND 12V
L(L1) N(L2) 3(A) 4(B) B A - - B A - - - -

Ground Power Input


208-230V /
60 Hz / 1 Phase

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 127
Application Guidelines
Wiring Guidelines / Wired Controller Placement

Figure 89: Terminal Block in the Built In Ducted Indoor Units.


Outdoor Unit Terminal Block
Indoor Unit Terminal Block
SODU IDU INTERNET DRY1 DRY2 GND 12V
L(L1) N(L2) YL RD BK A B B A - - B A - - - -

Ground Power Input Wired Controller


208-230V /
60 Hz / 1 Phase
MULTI V Ducted Indoor Unit Engineering Manual

Figure 90: Terminal Block in the Vertical / Horizontal Air Handler Units.

Indoor Unit Terminal Block Outdoor Unit Terminal Block


SODU IDU INTERNET DRY1 DRY2 GND 12V
L(L1) N(L2) 3(A) 4(B)
B A - - B A - - - -

Ground Power Input


208-230V /
60 Hz / 1 Phase

Wired Controller Placement Figure 91: Proper Location for the Wired Controller.
Wired controllers include a sensor to detect room temperature. To
maintain comfort levels in the conditioned space, the wired control-
ler must be installed in a location away from direct sunlight, high
humidity, and where it could be directly exposed to cold air. Control-
ler must be installed four (4) to five (5) feet above the floor where its
LED display can be read easily, in an area with good air circulation, YES
and where it can detect an average room temperature.
TEMP

Remote Controlle r

NO
TEMP

Remote Controlle r

Do not install the wired controller near or in:


• Drafts or dead spots behind doors and in corners

• Hot or cold air from ducts NO


4 to 5 feet
Rem
ot e
Cont
roller
TEMP

above the floor


• Radiant heat from the sun or appliances
NO
• Concealed pipes and chimneys

• An area where temperatures are uncontrolled, such as an outside


wall

Due to our policy of continuous product innovation, some specifications may change without notification.
128 | Guidelines © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Acronyms

Table 108: AcronymTable.


ABS Acrylonitrile Butadiene Styrene IDU Indoor Unit
AC Air Conditioner/Alternate Current kW Kilowatts
ACP Advanced Control Platform in Aq inches water
AHU Air Handling Unit ISO International Standards Organization
ASHRAE American Society of Heating, Refrigeration, and Air Conditioning LATS LG Air Conditioning Technical Solution software
ASTM American Society for Testing and Materials LED Light Emitting Diode
AWG American Wire Gauge LEED Leadership in Energy and Environmental Design
AWHP Air-to-Air Water Heat Pump MBh Thousands BTUs per hour
BLDC Brushless Digitally-Controlled MCA Minimum Circuit Ampacity
BTL BACnet® Testing Laboratories mm Millimeter
Btu/h British Thermal Unit per Hour MOP Maximum Overcurrent Protection
CAA Clean Air Act OD Outside Diameter
CFM Cubic Feet per Minute ODU Outdoor Unit
CFR Code of Federal Regulations PI Power Input
DB Dry Bulb PTAC Packaged Terminal Air Conditioner
dB(A) Decibels with “A” frequency weighting SHC Sensible Heat Capacity

Application Guidelines
DPST Double-Pole Single Throw SMACNA Sheet Metal & Air Conditioning Contractors’ National Association
DX Direct expansion RPM Revolutions per Minute
EEV Electric Expansion valve TC Total Capacity
EPDM Ethylene Propylene Diene M-Class Rubber USD United States Dollar
EMF Electromagnetic Field UL Underwriters Laboratories
ESP External Static Pressure V Voltage
ETL Electric Testing Laboratories VAV Variable Air Volume
GND Ground VRF Variable Refrigerant Flow
H/M/L High/Medium/Low W Watts
HVAC Heating, Ventilating and Air Conditioning WB Wet Bulb
Hz Hertz wg Water Gauge
ID Inside Diameter

Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp. Guidelines | 129
LG Electronics U.S.A., Inc. LG Electronics Commercial Products Support
Commercial Air Conditioning Division 1-888-865-3026 USA
11405 Old Roswell Road Follow the prompts for commercial A/C products. EM-MultiV-Ducted-IndoorUnits-02-15
Alpharetta, Georgia 30009 Supersedes: EM-MultiV-Ducted-IndoorUnits-01-15
www.lg-vrf.com Supersedes: EM-MultiV-IndoorUnits-07-14

S-ar putea să vă placă și