Sunteți pe pagina 1din 46

Control Systems

EMS98
EMS28 EMS39

EMS324 EMS326 EMS336

EMS339 EMS361 EMS362

EMS363 EMS371 EMS372


EMS815
EMS375 EMS807

EMS827 EMS828 EMS840

EMS854
EMS844 EMS853

EMS855 EMS860
* AMF = Automatic Mains Failure *CT = Current Transformer
* ECU = Engine Controller Unit * GCU = Generator Controller Unit

EMS NO SIZE MANUAL / AMF CTS / SHUNT SINGLE PHASE / MULTI PHASE ECU / GCU
EMS28 100 x 120 x 22mm Manual No No ECU

EMS39 100 x 120 x 22mm Manual No No GCU

EMS98 180 x 126 x 28mm AMF Shunt Multi-Phase GCU

EMS324 96 x 96 x 28mm Manual CT Single Phase GCU

EMS326 100 x 120 x 60mm Manual CTs Multi-Phase GCU

EMS336 100 x 120 x 60mm Manual No Multi-Phase ECU


Fuel
EMS339 100 x 120 x 60mm Manual Shunt Multi-Phase
Optimiser
EMS361 100 x 120 x 60mm Manual CT Single Phase GCU

EMS362 100 x 120 x 60mm Manual Shunt Multi-Phase GCU

EMS363 100 x 120 x 60mm Manual Shunt Single Phase GCU

EMS371 100 x 120 x 60mm Manual CT Single Phase GCU

EMS372 100 x 120 x 60mm AMF Shunt Multi-Phase GCU

EMS375 100 x 120 x 32mm AMF/ATS CTs Multi-Phase GCU

EMS807 100 x 120 x 60mm No No No ECU

EMS815 180 x 126 x 51mm AMF Shunt Multi-Phase GCU

EMS827 180 x 126 x 51mm AMF CTs Multi-Phase GCU

EMS828 180 x 126 x 51mm No No No CCU

EMS840 180 x 126 x 51mm Manual No No GCU

EMS844 100 x 120 x 60mm - CTs Multi-Phase LCC

EMS853 100 x 120 x 60mm Manual CTs Multi-Phase GCU

EMS854 180 x 126 x 51mm AMF Shunt Multi-Phase GCU

EMS855 180 x 126 x 51mm AMF Shunt Multi-Phase GCU

EMS860 180 x 126 x 51mm Manual Shunt Multi-Phase GCU


EMS NO SIZE TYPE FUNCTION

EMS08 - Resistive Sensor Temperature sensor

EMS12 41 x 86 x 40mm Communication Logic to RS232

EMS18 41 x 86 x 40mm Communication Logic to RS485

EMS20 - Communication Logic to Optical

EMS23 41 x 86 x 40mm Communication Logic to Ethernet

EMS24 41 x 86 x 40mm Communication Logic to USB

EMS30 - Communication SNMP Adapter

EMS32 94 x 44.5mm Resistive Sensor Low Water Monitor

EMS34 94 x 44.5mm Resistive Sensor Canopy Temperature Monitor

EMS72 66.6 x 1.6mm Capacitive Sensor Fuel Level Measurement

EMS311 100 x 120 x 30mm Power Meter 3 Phase Power Meter (3V, 3A)

EMS313 100 x 120 x 30mm Power Meter 3 Phase Power Meter (3V, 4A)

EMS314 120 x 100 x 32mm Controller PM-AMF-ATS


Potential Free Outputs / 2
EMS315 66 x 72 x 50mm Relay Module
(For Crank & Fuel Solenoids)
EMS316 41 x 86 x 40mm Multistart Fuel Optimizer

EMS930 111 x 86 x 30mm Input / Output Expansion Module Isolated Inputs / Outputs

EMS931 111 x 86 x 30mm Output Expansion Module Potential Free Outputs / 8


EMS28 ENGINE CONTROLLER UNIT

Key Features
• Operates with energise to run or energise to stop
fuel solenoids
• Simple switch closure initiates the starting sequence
• Manual starting and stopping available from front
panel
• Speed detection directly from Generator, MPU or
alternator output
• Immediate alarm sensing and display
• Display starting and running sequence on display
• External shutdowns for Emergency stop or pump
protection.

PRODUCT SELECTION CHART


Size Manual / AMF ECU / GCU
100 x 120 x 22mm Manual ECU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Engine Temperature
Mounting Hole 92 x 92mm 120°C, 150°C, 200°C
Range
IP rating IP66 front, IP55 rear Oil Pressure Range 500, 750, 1000 KPa
6 V to 32V DC
Supply Voltage Nominal 12V or 24V Input Reference 0V Common
Automotive
Speed Input Battery Volts
0.5-350 Volts 6 to 32 Volts
Sensitivity Measurement
Standby 20ma @27.2 Volts, 20ma
Speed Sensing 50/60Hz AC, MPU, @13.6 Volts
Supply Current
Options Magneto or alternator Running 20ma @27.2 Volts, 20ma
@13.6 Volts
Input Frequency
10Hz – 5KHz Engine Hours 0 – 99999.9 Hours
Range
Speed Display
RPM/Hz Terminations Screw less connection on rear
Options
Displayed 0 - 9999 RPM All features may be adjusted using
Set-up and Adjustment
Frequency Range 0 – 99.9 Hz set-up buttons and LCD menu
EMS39 GENERATOR CONTROLLER UNIT

Key Features
• An integrated Genset controller
• LCD display of engine temperature, oil pressure,
battery volts, speed and Engine Run hours,
provides manual start and stop buttons
• Controls excitation of the battery charging
alternator.
• Scheduler to periodically start the genset to keep
site batteries charged.
• Support outputs to tell the BMS system of the
alarm that caused the genset to be shut down.

PRODUCT SELECTION CHART


Size Manual / AMF ECU / GCU
100 x 120 x 22mm Manual GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Engine Temperature
Mounting Hole 92 x 92mm 120°C, 150°C, 200°C
Range
IP rating IP66 front, IP55 rear Oil Pressure Range 500, 750, 1000 KPa
6 V to 32V DC
Supply Voltage Nominal 12V or 24V Input Reference 0V Common
Automotive
Speed Input Battery Volts
100-350 Volts 6 to 32 Volts
Sensitivity Measurement
Standby 20ma @27.2 Volts, 20ma
Speed Sensing @13.6 Volts
50/60Hz AC Supply Current
Options Running 20ma @27.2 Volts, 20ma
@13.6 Volts
Input Frequency
10Hz – 80Hz Engine Hours 0 – 99999.9 Hours
Range
Speed Display
RPM/Hz Terminations Screw less connection on rear
Options
Displayed 0 – 99.9 Hz All features may be adjusted using
Set-up and Adjustment
Frequency Range 0 – 9999 RPMs set-up buttons and LCD menu
EMS98 GENERATOR CONTROLLER UNIT
Key Features
• Configurable and suitable for single or three phase
gensets.
• The unit controls the starting and stopping of a
genset via a manual start button, an internal auto
mains failure system, an external autostart signal or
the built in scheduler.
• Vital operating parameters are monitored and
displayed.
• If abnormal operation is detected, the unit alarms
and provides genset shutdown
• Control for load transfer contactors is also
provided.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
180 x 126 x 28mm AMF Shunt Multi-Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Controller Overall W 180mm x L 126mm x D 28mm Supply current <100mA
dimensions
Controller Panel W 156mm x H 117mm Standby current <12 mA
Cut out
Controller M4 Plastic Rivets or Screws. 4 AC Voltage inputs 50 – 400V RMS
Mounting Points
Controller IP rating IP65 from the front, IP20 from rear AC Current inputs 0 – 5 Amps RMS. 6X overload 6 Seconds
Interface Module W 81mm x L 151mm x D 55mm AC measurement True RMS (up to 265 Volts)
Dimensions
Interface Module Din Rail AC accuracy better than 2%
Mounting
Interface Module IP 30 DC accuracy 1%
IP Rating
Relative Humidity 95% non-condensing Maximum output 300ma
current
Output protection Short circuit, reverse voltage, load Maximum output 32 Volts DC
dump, relay inductive currents voltage
General protection Reverse voltage, load dump. Operating -10 to +50°C
Temperature
Range
Cranking drop out 0 Volts for 200msec every second Storage -20 to +60°C
protection provided recovery voltage exceeds Temperature
10V.
EMS324 SINGLE PHASE MANUAL GENSET

Key Features
• The unit incorporates key switch initiated
start and stop sequencing.
• Monitors engine and alternator operating
parameters
• LED display to show the operating parameters
of the genset
• Immediate alarm sensing and display
• Automatic shutdown of the genset in event of
damaging conditions.
• The unit monitors oil pressure, fuel level and
engine temperature to provide protection.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
96 x 96 mm (Bezel) x 28 mm Manual CT Single-Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Overall 96 x 96 mm (Bezel) x 28
CT current range 0 - 60A
Dimensions mm behind bezel
IP Rating IP51 front, IP20 rear Overall Accuracy Class 1
Digital Output Open Drain Relay Coil Driver. 300mA
Supply Voltage 8 V to 16V DC
Rating 36VDC max
Operating
-20 to +70°C Input Reference 0V Common
Temperature
Storage Displayed Speed
-20 to +70°C 0 - 1500 RPM
Temperature Range
Relative
95% non-condensing Engine Hours 0 - 99999.9 Hours
Humidity
Standby < 7mA
Supply Current Engine Sensors Type Switch: Close to common on fault
Running = 50mA
AC Voltage
L-N Max 300VRMS Terminations Molex Mini Fit JNR
Range
Environmental Tests: IEC68 Part2
AC Frequency EMC Compliance: EN50081-1, EN50081-2,
40 - 70Hz Testing
Range IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS326 GENERATOR CONTROLLER UNIT

Key Features
• Manual and Autostart initiated start and stop
sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Immediate alarm sensing and display
• Fuel wastage reduction
• Operational cost reduction
• Stop alarm log shows last 50 stops for alarm and
giving time and reason.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
100 x 120 x 60mm Manual CTs Multi-Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 92 x 92mm CT current range 0 – 5A + 25% Overload
IP rating IP55 front, IP20 rear Overall Accuracy Class 1
8 V to 36V DC Open Drain Relay Coil Driver. 300mA
Supply Voltage Digital Output Rating
Nominal Automotive 32VDC max.
Operating
-20 to +70°C Input Reference 0V Common
Temperature
Storage
-20 to +70°C Speed Range 0 – 5000 RPM
Temperature
Relative Humidity 95% non-condensing AC Frequency Range 40 – 70Hz
Standby < 7mA
Supply Current Engine Hours 0 – 99999.9 Hours
Running 50mA
Kilo Watt Hours 0 – 999999.9 KWH Terminations Amp DUAC / Molex Mini Fit JNR
All features may be adjusted using set-
Oil Pressure Range 500, 750, 1000 KPA Set-up and Adjustment up buttons and LCD menu or via a PC
Windows based utility
Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1, EN50081-
AC Voltage Range L-N = 350VRMS. Testing
2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS336 ENGINE CONTROLLER UNIT
Key Features
• Manual and Autostart initiated start and stop
sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Immediate alarm sensing and display
• Status display on the backlight 16 character by 2 line
LCD
• Fuel wastage reduction
• Operational cost reduction
• Stop alarm logs shows last 40 stops for alarm and giving
time and reason.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
100 x 120 x 60mm Manual --- Multi-Phase ECU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 92 x 92mm CT current range 0 – 5A + 25% Overload
IP rating IP55 front, IP20 rear Overall Accuracy Class 1
8 V to 36V DC Open Drain Relay Coil Driver. 300mA
Supply Voltage Digital Output Rating
Nominal Automotive 32VDC max.
Operating
-20 to +70°C Input Reference 0V Common
Temperature
Storage
-20 to +70°C Speed Range 0 – 5000 RPM
Temperature
Relative Humidity 95% non-condensing AC Frequency Range 40 – 70Hz
Standby < 7mA
Supply Current Engine Hours 0 – 99999.9 Hours
Running 50mA
Kilo Watt Hours 0 – 999999.9 KWH Terminations Amp DUAC / Molex Mini Fit JNR
All features may be adjusted using set-
Oil Pressure Range 500, 750, 1000 KPA Set-up and Adjustment up buttons and LCD menu or via a PC
Windows based utility
Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1,
AC Voltage Range L-N = 350VRMS. Testing
EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS339 FUEL OPTIMISER

Key Features
• Fuel consumption reduction by intelligent mains and
battery monitoring.
• Room Temperature monitoring
• Battery Voltage and Symmetry Monitoring and
Display.
• Single and Multi phase mains monitoring and
metering
• Includes communications port for remote monitoring
applications
• Inbuilt data logs provide operating history.
• Stop alarm log shows last 20 stops for alarm and
giving time and reason.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase Others
100 x 120 x 60mm Manual Shunt Multi-Phase Fuel Optimiser

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 155 x 117mm Overall Accuracy Class 1
IP rating IP56 front, IP20 rear Input Reference 0V Common
Supply Voltage 8 V to 36V DC Digital Output Open Drain Relay Coil Driver.
Nominal 12V DC Rating 300mA @ 36VDC max. Short Circuit
Automotive protected
Operating -20 to +70°C Run Hours 0 – 999999.9 Hours
Temperature
Storage -20 to +70°C Mains Run Hours 0 – 999999.9 Hours
Temperature
Relative Humidity 95% non-condensing Battery Run Hours 0 – 999999.9 Hours
Supply Current Standby <10mA DG Run Hours 0 – 999999.9 Hours
Running 70mA
AC Voltage Range L-N = 300VRMS. L-E 300V Canopy EMS08 0-100°C
Temperature Range
AC Frequency 40 – 70Hz Supply Battery Volts 8 to 36 Volts
Range Measurement
BTS Battery 10 to 65V DC Terminations Amp DUAC / Molex Mini Fit JNR
Voltage
Measurement
Set-up and All features may be Testing Environmental Tests: IEC68 Part2
Adjustment adjusted using set-up EMC Compliance: EN50081-1,
buttons and LCD menu or EN50081-2, IEC6100-4-3
via a PC windows based Electrical Safety AS 3100 and AS
utility 3260
EMS361 GENERATOR CONTROLLER UNIT

Key Features
• Custom designed controller for gensets
• Manual and Autostart initiated start and stop sequencing.
• Provides engine and alternator protection by monitoring
their parameters.
• Automatic shutdown of the genset in event of damaging
conditions.
• Immediate alarm sensing and display
• Fuel wastage reduction
• Stop alarm log shows last 40 stops for alarm and giving
time and reason.
• Operational cost reduction

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
100 x 120 x 60mm Manual CTs Single Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 92 x 92mm CT current range 0 – 5A + 25% Overload
IP rating IP55 front, IP20 rear Overall Accuracy Class 1
Supply Voltage 8 V to 36V DC Digital Output Open Drain Relay Coil Driver. 300mA
Nominal Automotive Rating 32VDC max.
Operating -20 to +70°C Input Reference 0V Common
Temperature
Storage -20 to +70°C Speed Range 0 – 5000 RPM
Temperature
Relative Humidity 95% non-condensing AC Frequency Range 40 – 70Hz
Supply Current Standby < 7mA Engine Hours 0 – 99999.9 Hours
Running 50mA
Kilo Watt Hours 0 – 999999.9 KWH Terminations Amp DUAC / Molex Mini Fit JNR
Oil Pressure 500, 750, 1000 KPA Set-up and All features may be adjusted using set-
Range Adjustment up buttons and LCD menu or via a PC
Windows based utility
AC Voltage Range L-N = 350VRMS. Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1, EN50081-
2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS362 GENERATOR CONTROLLER UNIT

Key Features
• Custom designed controller for small gensets
• Manual and Autostart initiated start and stop sequencing.
• Provides engine and alternator protection by monitoring
their parameters.
• Automatic shutdown of the genset in event of damaging
conditions.
• Immediate alarm sensing and display
• Fuel wastage reduction
• Operational cost reduction
• Stop alarm log shows last 40 stops for alarm and giving time
and reason.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
100 x 120 x 60mm Manual Shunt Multi-Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 92 x 92mm CT current range 0 – 5A + 25% Overload
IP rating IP55 front, IP20 Overall Accuracy Class 1
rear
Supply Voltage 8 V to 36V DC Digital Output Open Drain Relay Coil Driver. 300mA
Nominal Rating 32VDC max.
Automotive
Operating -20 to +70°C Input Reference 0V Common
Temperature
Storage Temperature -20 to +70°C Speed Range 0 – 5000 RPM
Relative Humidity 95% non- AC Frequency 40 – 70Hz
condensing Range
Supply Current Standby < 7mA Engine Hours 0 – 99999.9 Hours
Running 50mA
Kilo Watt Hours 0 – 999999.9 KWH Terminations Amp DUAC / Molex Mini Fit JNR
Oil Pressure Range 500, 750, 1000 KPA AC Voltage Range L-N = 350VRMS.
Set-up and Adjustment All features may be Testing Environmental Tests: IEC68 Part2
adjusted using set- EMC Compliance: EN50081-1, EN50081-
up buttons and LCD 2, IEC6100-4-3
menu or via a PC Electrical Safety AS 3100 and AS 3260
Windows based
utility
EMS363 GENERATOR CONTROLLER UNIT

Key Features
• Manual and Autostart initiated start and stop
sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Automatic shutdown of the genset in event of
damaging conditions.
• Immediate alarm sensing and display
• Fuel wastage reduction
• Operational cost reduction

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
100 x 120 x 60mm Manual Shunt Single Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 92 x 92mm Overall Accuracy Class 1
IP rating IP55 front, IP20 rear Digital Output Open Drain Relay Coil Driver. 300mA
Rating 32VDC max.
Supply Voltage 8 V to 36V DC Input Reference 0V Common
Nominal Automotive
Operating -20 to +70°C Speed Range 0 – 5000 RPM
Temperature
Storage -20 to +70°C AC Frequency Range 40 – 70Hz
Temperature
Relative Humidity 95% non-condensing Engine Hours 0 – 99999.9 Hours
Supply Current Standby < 7mA Terminations Amp DUAC / Molex Mini Fit JNR
Running 50mA
CT current range 0 – 5A + 25% Overload Set-up and All features may be adjusted using set-
Adjustment up buttons and LCD menu or via a PC
Windows based utility
AC Voltage Range L-N = 350VRMS. Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1,
EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS371 GENERATOR CONTROLLER UNIT

Key Features
• Custom designed controller for small gensets
• Manual and Autostart initiated start and stop
sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Automatic shutdown of the genset in event of
damaging conditions.
• Immediate alarm sensing and display
• Fuel wastage reduction
• Operational cost reduction
• Stop alarm log shows last 40 stops for alarm and giving
time and reason.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
100 x 120 x 60mm Manual CTs Single Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 92 x 92mm CT current range 0 – 5A + 25% Overload
IP rating IP55 front, IP20 rear Overall Accuracy Class 1
Supply Voltage 8 V to 36V DC Digital Output Open Drain Relay Coil Driver. 300mA
Nominal Automotive Rating 32VDC max.
Operating -20 to +70°C Input Reference 0V Common
Temperature
Storage -20 to +70°C Battery Volts 6 to 40 Volts
Temperature Measurement
Relative Humidity 95% non-condensing AC Frequency Range 40 – 70Hz
Supply Current Standby < 7mA Engine Hours 0 – 99999.9 Hours
Running 50mA
Kilo Watt Hours 0 – 999999.9 KWH Terminations Amp DUAC / Molex Mini Fit JNR
Oil Pressure Range 500, 750, 1000 KPA Set-up and All features may be adjusted using set-
Adjustment up buttons and LCD menu or via a PC
Windows based utility
AC Voltage Range L-N = 350VRMS. Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1,
EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS372 AMF GENERATOR CONTROLLER UNIT

Key Features
• Custom designed controller for gensets
• Manual and Autostart with AMF initiated start and stop
sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Automatic shutdown of the genset in event of
damaging conditions.
• Immediate alarm sensing and display
• Fuel wastage reduction
• Operational cost reduction
• Stop alarm log shows last 40 stops for alarm and giving
time and reason.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
100 x 120 x 60mm AMF Shunt Multi-Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 92 x 92mm CT current range 0 – 5A + 25% Overload
IP rating IP55 front, IP20 rear Overall Accuracy Class 1
Supply Voltage 8 V to 36V DC Digital Output Rating Open Drain Relay Coil Driver. 300mA
Nominal Automotive 32VDC max.
Operating -20 to +70°C Input Reference 0V Common
Temperature
Storage -20 to +70°C Battery Volts 6 to 40 Volts
Temperature Measurement
Relative Humidity 95% non-condensing AC Frequency Range 40 – 70Hz
Supply Current Standby < 7mA Engine Hours 0 – 99999.9 Hours
Running 50mA
Kilo Watt Hours 0 – 999999.9 KWH Terminations Amp DUAC / Molex Mini Fit JNR
Oil Pressure 500, 750, 1000 KPA Set-up and All features may be adjusted using set-
Range Adjustment up buttons and LCD menu or via a PC
Windows based utility
AC Voltage Range L-N = 350VRMS. Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1,
EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS375 POWER METER WITH AMF & ATS

Key Features
• Manual and Autostart with AMF initiated start and
stop sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Automatic shutdown of the genset in event of
damaging conditions.
• Immediate alarm sensing and display
• Fuel wastage reduction
• Operational cost reduction
• Stop alarm log shows last 10 stops for alarm and giving
time and reason.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
100 x 120 x 32mm AMF/ATS CTs Multi-Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 92 x 92mm General protection Reverse voltage, 120V load dump
IP rating IP66 front, IP20 rear Input Reference 0V DC/Common
Supply Voltage 8 V to 16V DC Generator Voltage 60-300 Volts RMS. Short duration
Nominal 12V Automotive Input Range overload capacity 350V
Operating -10 to +70°C Output OP1 to OP5 Relay Coil Driver Open drain current
Temperature limited 32V 300mA
Storage -20 to +70°C Output protection Short circuit, reverse voltage, load
Temperature dump, inductive relay current
Relative Humidity 95% non-condensing Terminations Amp DUAC / Molex Mini Fit JNR
@50°C
Supply Current Nominal 50mA Set-up and Menu buttons and LCD or by PC with
Adjustment cloning software.
Mains Under Frequency = 40Hz, Environmental Tests IEC68 Part2
Under/Over Over Frequency = 70Hz EMC Compliance EN50081-1, EN50081-2, IEC6100-4-3
Frequency Electrical Safety AS3100,AS3260
Mains Voltage 60-300 Volts RMS. Short Design ISO 9001
Input Range duration overload capacity Manufacturing ISO 9002
350V
EMS807 ENGINE CONTROL UNIT

Key Features
• Manual and Autostart initiated start and stop
sequencing.
• Status display on the backlight graphics LCD
• LEDs indicate various alarms
• The unit can be fitted with an optional RS485 or
RS232 communications port and cab be used with
power meters and AMF/ATS
• integrated all the required engine control
functions in a single package

PRODUCT SELECTION CHART


Size Manual / AMF ECU / GCU
110 x 120 x 60mm No ECU

TECHNICAL SPECIFICATIONS
Overall Dimensions 110 x 100 x 60mm Displayed speed range 0 – 9999 RPM

Mounting Hole 96 x 96 mm Oil Pressure range 500, 750, 1000 KPa


IP rating IP66 front, IP55 rear Engine Hours 0 – 99999.9 Hours

Outputs 3 Amp Contact (24 volt Engine Temperature 120ºC, 200ºC, User Curve
resistive) switching to range
common
Battery Volts 6 to 40 Volts Speed Input Sensitivity 0.5 - 350 Volts Pk
measurement
Speed Frequency 10Hz – 20KHz Canopy Temperature EMS907 supplied unit, User Curve
Range range
Input reference 0 volts common Engine Temperature Switch: close on fault, open on fault
sensor type Resistive (NTC)
Canopy Switch: close on fault, open Supply Current Standby < 7mA
Temperature on fault Running 100mA TBA
sensor type Resistive (NTC)
Fuel Level Sensor Switch close to Fault, open Oil pressure sensor Switch: close on fault, open on fault
type on fault. type Resistive 10 to 180 Ohms (VDO/Datcon)
Resistive 0 to 90 Ohms Resistive 0 to 90 Ohms (Pricol/Datcon)
Resistive 10 to 180 Ohms User Curve
User Curve
Supply Voltage 6 V to 36V DC HET, LOP, Fail to Start, 3 Amp Contact (24 volt resistive) switching
Nominal 12V or 24V Low Fuel outputs to isolated common
Automotive
Con A, Con B NO/NC Isolated 3 Amp with Terminations Amp DUAC / Molex Mini Fit JNR
230V rating
EMS815 AMF AC GENSET CONTROLLER
Key Features
• Manual and Autostart initiated start and stop
sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Automatic shutdown of the genset in event of
damaging conditions.
• Status display on the backlight graphics LCD
• Immediate alarm sensing and display.

TECHNICAL SPECIFICATIONS
Overall 180 x 126 x Oil Pressure Sensor Switch: Close on fault Resistive 10 to 180 Ohms
Dimensions 51mm Type (VDO/Datcon)
Mounting Hole 155 x 117mm Oil Pressure Range 500, 750, 1000 KPa
IP56 front, Engine Temperature
IP rating Switch: Close on fault Resistive (NTC)
IP20 rear Sensor Type
Oil Temperature Standby < 10mA
40ºC-150ºC Supply Current
Range Running 70mA
Battery Volts Engine Temperature
8 to 36 Volts VDO 120ºC, VDO 150ºC, VDO 200ºC
Measurement Range
Operating Canopy Temperature
-20 to +70°C Switch: Close on fault Resistive (NTC)
Temperature Sensor Type
Storage Canopy Temperature
-20 to +70°C EMS08 0-100 ºC
Temperature Range
Relative 95% non-
Oil Temperature Switch: Close on fault Resistive (NTC)
Humidity condensing
AC Frequency
40 – 70Hz Supply Voltage 8 V to 36V DC Nominal Automotive
Range
Switch: Close to fault
AC Voltage L-N = Fuel Level Sensor Resistive 0 to 90 Ohms
Range 350VRMS. Type Resistive 10 to 180 Ohms
Resistive 180 to 10 Ohms
0 – 5A + 25% Set-up and All features may be adjusted using set-up buttons and LCD
CT current range
Overload Adjustment menu or via a PC Windows based utility

Overall Accuracy Class 1 Terminations Amp DUAC / Molex Mini Fit JNR

Environmental Tests: IEC68 Part2


Displayed Speed
0 – 4000 RPM Testing EMC Compliance: EN50081-1, EN50081-2, IEC6100-4-3
Range
Electrical Safety AS 3100 and AS 3260
0 – 99999.9 Open Drain Relay Coil Driver. 300mA 362VDC max.
Engine Hours Digital Output Rating
Hours Short Circuit protected.
Current limited outputs approx. 15mA or less as required
0 – 999999.9
Kilo Watt Hours Analog Input Rating by sensors/
KWH
Short circuit and reverse voltage protected.
Opto-coupler isolated. Whetting current 10mA at 12 V DC.
Input Reference 0V Common Digital Input Rating
DC input protection for +/- 30V DC, Transient Protected.
EMS827 AMF GENERATOR CONTROLLER UNIT

Key Features
• Manual and Autostart with AMF initiated start and
stop sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Automatic shutdown of the genset in event of
damaging conditions.
• Status display on the backlight graphics LCD
• Immediate alarm sensing and display
• Fuel wastage reduction
• Operational cost reduction
• Stop alarm log shows last 50 stops for alarm and
giving time and reason.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
180 x 126 x 51mm AMF CTs Multi-Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 155 x 117mm Overall Class 1
Accuracy
IP rating IP56 front, IP20 rear Digital Output Open Drain Relay Coil Driver. 300mA
Rating 362VDC max
Supply Voltage 8 V to 36V DC Input Reference 0V Common
Nominal Automotive
Operating -20 to +70°C Speed Range 0 – 4000 RPM
Temperature
Storage Temperature -20 to +70°C Engine Hours 0 – 99999.9 Hours
Relative Humidity 95% non-condensing Terminations Amp DUAC / Molex Mini Fit JNR
Supply Current Standby < 10mA Analog Input Current limited outputs 15mA or less as
Running 70mA Rating required by sensors. Short circuit and
reverse voltage protected.
AC Voltage Range L-N = 350VRMS Kilo Watt Hours 0 – 999999.9 KWH
AC Frequency Range 40 – 70Hz Set-up and All features may be adjusted using set-
Adjustment up buttons and LCD menu or via PC
Windows based utility
CT current range 0 – 5A + 25% Overload Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1,
EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS828 COMPRESSOR CONTROLLER

Key Features
• Manual and Remote Start initiated start and
stop sequencing
• Monitors compressor operating parameters
and provides protection
• Status display on the backlight graphics LCD
• LEDs indicate various alarms & warnings
• Automatic shutdown of the compressor
in the event of damaging conditions

PRODUCT SELECTION CHART


Size Manual / AMF ECU / GCU
180 x 126 x 51mm No CCU

TECHNICAL SPECIFICATIONS
3A at 230VAC
Overall Dimensions 180 x 126 x 51mm Relay Outputs
5A at 30VDC
Mounting Hole 155 x 117mm Input Reference 0V Common
IP rating IP55 front, IP20 rear Pressure Sensor Type Resistive: 4 – 20mA

Supply Voltage 220 – 260VAC 50-60Hz Pressure Sensor Range 0 – 50.0 Bar

Operating Temperature Sensor


-20 to +70°C Resistive PT100
Temperature Type
Storage
-20 to +70°C Temperature Range 0 – 200ºC
Temperature
Relative Humidity 95% non-condensing CT current range 0 – 5A + 25% Overload
Standby < 10mA
Supply Current Overall Accuracy Class 1
Running 70mA

All features may be adjusted using set-up


AC Voltage Range L-N = 350VRMS. Set-up and Adjustment buttons and LCD menu or via a PC
Windows based utility

Environmental Tests: IEC68 Part2


AC Frequency EMC Compliance: EN50081-1, EN50081-2,
40 – 70Hz Testing
Range IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS840 REMOTE MONITORING SYSTEM

Key Features
• Data logger and communications device
• Intended to monitor on site power sources, including
Mains Power conditions, Diesel Generator
performance, site security, and other critical site
conditions.
• Collected data is automatically transferred to a central
server via GPRS connectivity
• Fitted into an enclosure so it provides a ready to use
solution
• Improves fuel and service management
• Improves network reliability

PRODUCT SELECTION CHART


Size Manual / AMF ECU / GCU
180 x 126 x 51mm Manual GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 155 x 117mm Overall Accuracy Class 1
IP rating IP56 front, IP20 rear Input Reference 0V Common
Supply Voltage 8 V to 36V DC Analog Input Current limited outputs 15mA or less as
Nominal Automotive Rating required by sensors. Short circuit and
reverse voltage protected.
Operating -20 to +70°C Digital Input Opto-coupler isolated.
Temperature Rating Whetting current 10mA at 12V DC
DC input protection for +/- 30V DC
Transient Protected
Storage Temperature -20 to +70°C Terminations Amp DUAC / Molex Mini Fit JNR
Relative Humidity 95% non-condensing Set-up and All features may be adjusted using set-
Adjustment up buttons and LCD menu or via PC
Windows based utility
Supply Current Standby < 10mA Testing Environmental Tests: IEC68 Part2
Running 70mA EMC Compliance: EN50081-1,
EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS844 LINE CONDITIONING CONTROLLER

Key Features
• Supports a transformer with up to 5 taps
• Auto select the best tap to give the correct
output
• Easy configuration for all setup items
• Clear display on the LCD of all measurements
• Auto select best line to line pair based on load
R-B, R-Y and Y-B.

PRODUCT SELECTION CHART


Size CTs / Shunt Single Phase / Multi Phase
100 x 120 x 60mm CTs Multi-Phase

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 92 x 92mm CT current range 0 – 5A + 25% Overload
IP rating IP55 front, IP20 rear Overall Accuracy Class 1
8 V to 36V DC Digital Output Open Drain Relay Coil Driver. 300mA
Supply Voltage
Nominal Automotive Rating 32VDC max.
Operating
-20 to +70°C Input Reference 0V Common
Temperature
Storage
-20 to +70°C Terminations Amp DUAC / Molex Mini Fit JNR
Temperature
AC Frequency
Relative Humidity 95% non-condensing 40 – 70Hz
Range
Standby < 7mA
Supply Current AC Voltage Range L-N = 350VRMS.
Running 50mA
Environmental Tests: IEC68
Part2
All features may be adjusted using set-
EMC Compliance: EN50081- Set-up and
Testing up buttons and LCD menu or via a PC
1, EN50081-2, IEC6100-4-3 Adjustment
Windows based utility
Electrical Safety AS 3100 and
AS 3260
EMS853 GENERATOR CONTROLLER UNIT

Key Features
• Manual and Autostart initiated start and stop
sequencing.
• Status display on the backlight graphics LCD
• LEDs indicate various alarms & warnings
• Automatic shutdown of the genset in event of
damaging conditions.
• The unit also monitors coolant level, fuel level,
canopy temperature and generator loading to
provide even more comprehensive protection.
• Reduces system cost

TECHNICAL SPECIFICATIONS
Overall Oil Pressure Sensor Switch: Close on fault
100 x 120 x 60mm
Dimensions Type Resistive 10 to 180 Ohms
Mounting Hole 92 x 92mm Oil Pressure Range 500, 750, 1000 KPa
Engine Temperature Switch: Close on fault
IP rating IP55 front, IP20 rear
Sensor Type Resistive (NTC)
8 V to 36V DC Engine Temperature
Supply Voltage 120ºC, 150ºC, 200ºC
Nominal Automotive Range
Operating Canopy Temperature Switch: Close on fault
-20 to +70°C
Temperature Sensor Type Resistive (NTC) EMS08 Sensor
Storage Canopy Temperature
-20 to +70°C EMS08 0-100 ºC
Temperature Range
Switch: Close to fault
Relative Fuel Level Sensor Resistive 0 to 90 Ohms
95% non-condensing
Humidity Type Resistive 10 to 180 Ohms
Resistive 180 to 10 Ohms
Standby < 7mA Battery Volts
Supply Current 6 to 40 Volts
Running 50mA Measurement
All features may be adjusted using set-
AC Voltage Set-up and
L-N = 350VRMS. up buttons and LCD menu or via a PC
Range Adjustment
Windows based utility
AC Frequency
40 – 70Hz Terminations Amp DUAC / Molex Mini Fit JNR
Range
Environmental Tests: IEC68 Part2
CT current EMC Compliance: EN50081-1, EN50081-
0 – 5A + 25% Overload Testing
range 2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
Overall Displayed Speed
Class 1 0 – 5000 RPM
Accuracy Range
Digital Output Open Drain Relay Coil Driver.
Engine Hours 0 – 99999.9 Hours
Rating 300mA 32VDC max.
Input Reference 0V Common Kilo Watt Hours 0 – 999999.9 KWH
EMS854 AMF GENERATOR CONTROLLER UNIT

Key Features
• Custom designed controller with AMF functionality
• Manual and Autostart with AMF initiated start and
stop sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Automatic shutdown of the genset in event of
damaging conditions.
• Status display on the backlight graphics LCD
• Immediate alarm sensing and display
• Fuel wastage reduction
• Operational cost reduction

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
180 x 126 x 51mm AMF Shunt Multi-Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 155 x 117mm CT current range 0 – 5A + 25% Overload
IP rating IP55 front, IP20 rear Overall Accuracy Class 1
Supply Voltage 8 V to 36V DC Digital Output Open Drain Relay Coil Driver. 300mA
Nominal Automotive Rating 32VDC max
Operating -20 to +70°C Input Reference 0V Common
Temperature
Storage Temperature -20 to +70°C Speed Range 0 – 5000 RPM
Relative Humidity 95% non-condensing Engine Hours 0 – 99999.9 Hours
Supply Current Standby < 10mA Terminations Amp DUAC / Molex Mini Fit JNR
Running 70mA
AC Voltage Range L-N = 350VRMS Set-up and All features may be adjusted using set-up
Adjustment buttons and LCD menu or via PC
Windows based utility
AC Frequency Range 40 – 70Hz Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1,
EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS855 AMF GENERATOR CONTROLLER UNIT

Key Features
• Manual and Autostart AMF initiated start and stop
sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Automatic shutdown of the genset in event of
damaging conditions.
• Status display on the backlight graphics LCD
• Immediate alarm sensing and display
• Fuel wastage reduction
• Operational cost reduction
• Stop alarm log shows last 50 stops for alarm and
giving time and reason.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
180 x 126 x 51mm AMF Shunt Multi-Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 155 x 117mm Overall Accuracy Class 1
IP rating IP56 front, IP20 rear Digital Output Rating Open Drain Relay Coil Driver.
300mA 362VDC max
Supply Voltage 8 V to 36V DC Input Reference 0V Common
Nominal Automotive
Operating -20 to +70°C Speed Range 0 – 4000 RPM
Temperature
Storage Temperature -20 to +70°C Engine Hours 0 – 99999.9 Hours
Relative Humidity 95% non-condensing Terminations Amp DUAC / Molex Mini Fit JNR
Supply Current Standby < 10mA Analog Input Rating Current limited outputs 15mA or
Running 70mA less as required by sensors. Short
circuit and reverse voltage
protected.
AC Voltage Range L-N = 350VRMS Kilo Watt Hours 0 – 999999.9 KWH
AC Frequency Range 40 – 70Hz Set-up and All features may be adjusted using
Adjustment set-up buttons and LCD menu or
via PC Windows based utility
CT current range 0 – 5A + 25% Overload Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1,
EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS
3260
EMS860 GENERATOR CONTROLLER UNIT
Key Features
• Manual and Autostart initiated start and stop
sequencing.
• Provides engine and alternator protection by
monitoring their parameters.
• Automatic shutdown of the genset in event of
damaging conditions.
• Status display on the backlight graphics LCD
• Immediate alarm sensing and display
• Fuel wastage reduction
• Operational cost reduction
• Stop alarm log shows last 50 stops for alarm and
giving time and reason.

PRODUCT SELECTION CHART


Size Manual / AMF CTs / Shunt Single Phase / Multi Phase ECU / GCU
180 x 126 x 51mm Manual Shunt Multi-Phase GCU

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole 155 x 117mm Kilo Watt Hours 0 – 999999.9 KWH
IP rating IP56 front, IP20 rear CT current range 0 – 5A + 25% Overload
Supply Voltage 8 V to 36V DC Overall Accuracy Class 1
Nominal Automotive
Operating -20 to +70°C Digital Output Rating Open Drain Relay Coil Driver.
Temperature 300mA 362VDC max. Short circuit
protected.
Storage Temperature -20 to +70°C Input Reference 0V Common
Relative Humidity 95% non-condensing Speed Range 0 – 4000 RPM
Supply Current Standby < 10mA Engine Hours 0 – 99999.9 Hours
Running 70mA
AC Voltage Range L-N = 350VRMS Terminations Amp DUAC / Molex Mini Fit JNR
AC Frequency Range 40 – 70Hz Set-up and All features may be adjusted using
Adjustment set-up buttons and LCD menu or
via PC Windows based utility
Oil Pressure Range 500, 750, 1000 KPa Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1,
EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS
3260
EMS12 LOGIC TO RS232 MODULE

Key Features
• Provides conversion from logic level to RS232.
• Outgoing communications are indicated by an LED
• Din rail mounting ( 72mm form )

TECHNICAL SPECIFICATIONS
Features Specification
Overall Dimensions 41mm(W) x 86mm(H) x 40mm(D)
Mounting Din Rail 72mm Series. 32mm rail.
IP rating IP30
Storage Temperature -20 to +85°C
Relative Humidity 95% non condensing
Operating Temperature -20 to +60°C
Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1, EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS18 LOGIC TO RS485 ISOLATED MODULE

Key Features
• Provides conversion from logic level to opto isolated RS485.
• Outgoing communications are indicated by an LED
• Optically isolated for long haul applications
• 12/24V DC power supply
• Din rail mounting ( 72mm form )

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Size 41mm(W) x 86mm(H) x Fan Out Maximum : 32
40mm(D)
Mounting Din Rail 72mm Series. 32mm Bit Rate Maximum : 57600 BPS
Hole rail.
IP rating IP30 Isolation 1KV between primary and secondary
circuits
Storage -20°C to 85°C Common Mode -7DC to +12 VDC(Across the network)
Temperature Voltage Range
Relative 95% non-condensing Short Circuit Protected
Humidity Protection
Operating -20°C to +60°C Supply Current Standby : 5mA@12V DC power
Temperature supply
Maximum : 250mA Depending on Fan
out
Supply 9.3V to 36V DC, Nominal Testing Environmental Test: IEC68 Part2
Voltage 12V/24V Automotive EMS Compliance: EN50081-1,
EN50081-2, IEC61000-4-3
Electrical safety AS 3100 and AS 3260
EMS20 LOGIC TO OPTICAL MODULE

Key Features
• Provides conversation from logic level to fibre optic
• 12/24 DC power supply
• Outgoing communication indicates by red LED
• Immune to electrical noise
• No common ground required

TECHNICAL SPECIFICATIONS
Features Specification
Overall Dimensions 41mm(W) x 86mm(H) x 40mm(D)
Mounting Din Rail 72mm Series. 32mm rail.
IP rating IP30
Storage Temperature -20 to +85°C
Relative Humidity 95% non-condensing
Operating Temperature -20 to +60°C
Common Connection Point to Point (P2P)
Bit Rate 57600 BPS
Supply Current Standby : 5mA@12V DC
Maximum : 60mA@48m
Supply Voltage 9.3V to 36V DC
Nominal 12V/24V Automotive
Short Circuit Protection Protected
Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1, EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS23 LOGIC TO ETHERNET ISOLATED MODULE

Key Features
• Provides conversion from logic level to isolated Ethernet.
• Outgoing communications are indicated by an LED
• Optically isolated for long haul applications
• 12/24V DC power supply
• Din rail mounting ( 72mm form )

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Size 41mm(W) x 86mm(H) x Fan Out Maximum : 32
40mm(D)
Mounting Din Rail 72mm Series. 32mm rail. Bit Rate Maximum : 57600 BPS
Hole
IP rating IP30 Isolation 1KV between primary and secondary
circuits
Storage -20°C to 85°C Common Mode -7DC to +12 VDC(Across the network)
Temperature Voltage Range
Relative 95% non-condensing Short Circuit Protected
Humidity Protection
Operating -20°C to +60°C Supply Current Standby : 5mA@12V DC power
Temperature supply
Maximum : 250mA Depending on Fan
out
Supply 9.3V to 36V DC, Nominal Testing Environmental Test: IEC68 Part2
Voltage 12V/24V Automotive EMS Compliance: EN50081-1, EN50081-
2, IEC61000-4-3
Electrical safety AS 3100 and AS 3260
EMS24 LOGIC TO USB ISOLATED MODULE

Key Features
• Provides conversion from logic level to isolated USB.
• Outgoing communications are indicated by an LED
• Optically isolated for long haul applications
• 12/24V DC power supply
• Din rail mounting ( 72mm form )

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Size 41mm(W) x 86mm(H) x Fan Out Maximum : 32
40mm(D)
Mounting Din Rail 72mm Series. 32mm rail. Bit Rate Maximum : 57600 BPS
Hole
IP rating IP30 Isolation 1KV between primary and secondary
circuits
Storage -20°C to 85°C Common Mode -7DC to +12 VDC(Across the network)
Temperature Voltage Range
Relative 95% non-condensing Short Circuit Protected
Humidity Protection
Operating -20°C to +60°C Supply Current Standby : 5mA@12V DC power
Temperature supply
Maximum : 250mA Depending on Fan
out
Supply 9.3V to 36V DC, Nominal Testing Environmental Test: IEC68 Part2
Voltage 12V/24V Automotive EMS Compliance: EN50081-1, EN50081-
2, IEC61000-4-3
Electrical safety AS 3100 and AS 3260
EMS30 SNMP ADAPTER

Key Features
• Outgoing communications are indicated by an LED
• Optically isolated for long haul applications.
• 12/24V DC power supply.
• Din rail mounting. (72mm form)
• Provides Isolated RS485.
• Ethernet LAN accessible with TCP/IP Address.

TECHNICAL SPECIFICATIONS
Features Specifications
Overall Dimensions 102 x 86 x 50mm
Mounting Din Rail 72mm Series. 32mm rail.
IP rating IP30
Storage Temperature -20 to +85°C
Relative Humidity 95% non-condensing
Operating Temperature -20 to +60°C
Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1, EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
Supply Voltage 9.3 V to 36V DC, Nominal 12V/ 24V Automotive
Supply Current Standby: 20mA@12V DC power supply
Maximum: 500mA Depending on Fanout.
Bit Rate Maximum; 57600 BPS
Isolation 1KV between primary and secondary circuits.
Common Mode Voltage Range -7DC to +12VDC (Across the RS485 network)
Short Circuit Protection Protected
EMS32 LOW WATER MONITOR

Key Features
• Operating Voltage 12v to 16v
• IP20
• Attack delay of max 5 sec(Sensitive to bubbles)

TECHNICAL SPECIFICATIONS
Features Specifications
Size 94mm x 44.5mm
Weight 45g
Case Flange case
Operating Temperature -20C to 180C
Resistance Resist dust, water, heat
EMS34 CANOPY TEMPERATURE MONITOR

Key Features
• Operating Voltage 12v to 16v
• IP20
• Attack delay of max 40

TECHNICAL SPECIFICATIONS
Features Specifications
Size 94mm x 44.5mm
Weight 45g
Case Flange case
Operating Temperature -20C to 180C
Resistance Resist dust, water, heat
EMS72 FUEL PROBE

Key Features
• 12V/24V DC power supply
• EMS72V1 provides both and isolated RS485 for
communication and 4-20mA output

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Overall size 66.6 mm(D) x 1.6 mm (W) Operating -20 to +60°C
Temperature
Mounting Mechanical Assembly Supply Current Standby: 5mA@12V DC power supply
Maximum: 250mA Depending on Fan out
IP rating IP30 Fan Out Maximum: 32
Storage -20 to +85°C Bit Rate Maximum: 57600 BPS
Temperature
Relative 95% non-condensing Isolation 1KV between primary and secondary
Humidity circuits
Supply 9.3V to 36V DC, Nominal 12V/24V Common -7DC to +12VDC (Across the network)
Voltage Automotive Mode Voltage
Range
Testing Environmental Tests: IEC68 Part2 Short Circuit Protected
EMC Compliance: EN50081-1, Protection
EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS311 POWER METER

Key Features
• Measures True RMS Volts, Current, and Frequency with
better than class 1 accuracy
• Measures apparent power, active power, reactive power,
power factor and Kilowatt hours.
• Fitted with a loading gauge and load shed output.
• Fitted with a Gen OK output indicating voltage and
frequency is within specification.
• Uses standard 5 amp CTs for current sensing.
• May be set to use 1 CT for balanced loads.
• Includes Earth Leakage detection system and engine
shutdown alarm output.
• Powered off the system battery (12 or 24 volt DC).

TECHNICAL SPECIFICATIONS
Features Specifications
Overall Dimensions 100 x 120 x 30mm
Mounting Hole 92 x 92 mm
IP rating IP55 front, IP20 rear
Supply Voltage 8 V to 36V DC
Nominal 12V or 24V Automotive
Supply Current Standby 17mA
Running 50mA
Input AC voltage (max) 600V AC Line to Line
Short duration conditions to 700V
CT range 1 – 2000
Input AC Current (max) 5 Amps, 6.25 x overload for 2 seconds
Maximum allowable Current 6553 Amps
Overall Accuracy Better than Class 1
Input Frequency Range 40 – 70Hz
Output Rating Open Drain Relay Coil Driver. 300mA 32VDC max.
Set-up and Adjustment All features may be adjusted using set-up buttons and LCD menu or via a
PC Windows based utility.
Terminations Screw Terminals.
Operating Temperature -20 to +70°C
Storage Temperature -20 to +70°C
Relative Humidity 95% non-condensing
Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1, EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS313 POWER METER

Key Features
• Measures True RMS Volts, Current, and Frequency with
better than class 1 accuracy
• Measures Active power and Kilowatt hours.
• Fitted with a loading gauge.
• Fitted with a Gen OK output indicating voltage and
frequency is within specification.
• Uses standard 5 amp CTs for current sensing.
• May be set to use 1 CT for balanced loads.
• Powered off the system battery (12 or 24 volt DC).
• Powers down to very low current draw when genset AC is
not present.
• Companion product to the EMS907 ECU and EMS924
AMF/ATS.
• Includes communications port for remote monitoring
applications.

TECHNICAL SPECIFICATIONS
Features Specifications
Overall Dimensions 100 x 120 x 30mm
Mounting Hole 92 x 92 mm
IP rating IP55 front, IP20 rear
Supply Voltage 8 V to 36V DC
Nominal 12V or 24V Automotive
Supply Current Standby 17mA
Running 50mA
Input AC voltage (max) 600V AC Line to Line
Short duration conditions to 700V
CT range 1 – 2000
Input AC Current (max) 5 Amps, 6.25 x overload for 2 seconds
Maximum allowable Current 6553 Amps
Overall Accuracy Better than Class 1
Input Frequency Range 40 – 70Hz
Output Rating Open Drain Relay Coil Driver. 300mA 32VDC max.
Set-up and Adjustment All features may be adjusted using set-up buttons and LCD menu or via a
PC Windows based utility.
Terminations Screw Terminals.
Operating Temperature -20 to +70°C
Storage Temperature -20 to +70°C
Relative Humidity 95% non-condensing
Testing Environmental Tests: IEC68 Part2
EMC Compliance: EN50081-1, EN50081-2, IEC6100-4-3
Electrical Safety AS 3100 and AS 3260
EMS314 PM-AMF-ATS

Key Features
• Integrated solution for Telecom DG sets
• Dual Power Meter for DG and Mains
• Single or three phase operation
• Integrated AMF function
• Integrated ATS controller
• Measures true RMS Volts, Current, and Frequency.
Class 1 accuracy
• Includes KW and KWH meters
• Includes Loading Gauge and Overload Protection
• Uses standard 5 amp CTs for current sensing. May be
set to use 1 CT for balanced loads
• Designed to be a companion to the EMS907V1 Engine
Controller

TECHNICAL SPECIFICATIONS
Overall Dimensions 120 x 100 x 32mm
Mounting Hole 92 x 92 mm. Mounted using 4x M4 x 6mm plastic rivets
IP rating IP66 front, IP20 rear
Supply Voltage 6 V to 36V DC. Nominal 12V or 24V Automotive
Supply Current Nominal 50mA
General protection Reverse voltage, 120V load dump
Drop out protection 0 Volts for 200ms every second provided recovery exceeds 5V
Input reference 0V DC/Common
Mains Voltage Input Range 60-300 Volts RMS. Short duration overload capability 350V
Generator Voltage Input Range 60-300 Volts RMS. Short duration overload capability 350V
Mains Under/Over Frequency Under Frequency = 40Hz, Over Frequency =70 Hz
Mains Contactor output Relay Coil Driver Open drain current limited 32V 300mA
Genset Contactor output Relay Coil Driver Open drain current limited 32V 300mA
Alarm/Hooter output Relay Coil Driver Open drain current limited 32V 300mA
Run DG output Relay Coil Driver Open drain current limited 32V 300mA
Load Shed output Relay Coil Driver Open drain current limited 32V 300mA
Output protection Short circuit, reverse voltage, load dump, inductive relay currents
Set-up and Adjustment Menu buttons and LCD Messages or by Pc with cloning software
Terminations Screw connections on rear. Recommended wire size 0.75mm
Operating Temperature -10 to +70°C
Storage Temperature -20 to +70°C
Relative Humidity 95% non-condensing @ 50°C
Environmental Tests. IEC68 Part2
EMC Compliance. EN50081-1, EN50081-2, IEC6100-4-3
Electrical Safety: AS3100, AS3260
Design. ISO 9001
Manufacturing. ISO 9002
EMS315 RELAY MODULE

Key Features
• Reduces wiring and installation cost by
integrating high power relays in a single din rail
mounted package.
• May be powered from 12 or 24 volts.
• Works over the full automotive voltage range
with no adverse effects.
• Requires no setup or jumpers for voltage setting.
• Status indicated with easy to view LEDs
• Outputs turned on using switch to ground or
open collector outputs.
• Heavy duty barrier terminals for output wiring
• Screw terminals for input wiring

TECHNICAL SPECIFICATIONS
Features Specifications
Overall Dimensions 66 x 72 x 50mm
Operating Voltage 12 or 24 Volts Automotive
Nominal Operating Current 130 ma
Maximum operating voltage 40 volts
Minimum operating voltage 8 volts
Relay drop out voltage 4 Volts
Maximum switch current 70 Amps
EMS316 MULTISTART

Key Features
• LVM Input for mains AC status
• Isolated battery voltage monitoring from 10 to 60 Volts
• Genset starting and stopping on AMF, Aircon Status,
low String battery
• LED icons for AMF running status, Aircon status and
battery status
• Output to control the Genset Run request
• Fitted with serial port for communications
• Fully configurable through the DIP Switches.
• Din rail mounted for easy installation
• 12V DC powered with low standby and operating
current

TECHNICAL SPECIFICATIONS
Features Specifications
Size 41mm(W) x 86mm(H) x 40mm(D)
Mounting Hole Din Rail 72mm Series. 32mm rail.
IP rating IP30
Supply Voltage 8v to 16V
Short Circuit Protection Protected (Reverse Polarity Protection)
Supply Current Standby : 5mA@12V DC power supply
Maximum : 120mA Depending on Fan out
Testing Environmental Test: IEC68 Part2
EMS Compliance: EN50081-1, EN50081-2, IEC61000-4-3
Electrical safety AS 3100 and AS 3260
EMS930 I/O EXPANSION MODULE

Key Features
• An addressable Input and Output Expansion
module used with various EMS Controllers
• Two communication port connectors one of which
connects to the controller and the other to allow
connection to a BMS or PC
• 8 potential free outputs, supporting No / NC
connections.
• 8 Opto isolated digital inputs
• LEDs indicate the status of all the inputs, outputs,
power supply and Opto-communication

PRODUCT SELECTION CHART


Size I/O Expansion Module Function
111(L) x 86(H) x 30(D)mm I/O Expansion Module Relay Input / Output

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole Din Rail 72mm Series. 32mm rail Relative 95% non-condensing
Humidity
IP rating IP30 Input Whetting 10mA @ Vin=12V (Vin-3V) < (12V)
Voltage
Supply Voltage 9.5 V to 36V DC, Nominal 12V / 24V Input Reference 0 Volt
Automotive
Operating -20 to +60°C I/O function Set- IO assignments are contained
Temperature up and within the Master controller
Adjustment
Storage -20 to +85°C Terminations Strip length: 6-7 mm
Temperature Wire range: 24-12 AWG,0.5 to
2.5mm²
Supply Current Standby <9mA@12V DC power Testing Environmental Tests: IEC68 Part2
supply <13mA@24V DC power EMC Compliance: EN50081-1,
supply EN50081-2, IEC6100-4-3
Full Function 500mA Depending on Electrical Safety AS 3100 and AS
I/O activations. 3260
EMS931 OUTPUT EXPANSION MODULE

Key Features
• An addressable Output Expansion module
used with various EMS Controllers
• Two communication port connectors one of
which connects to the controller and the
other to allow connection to a BMS or PC
• 8 potential free contact outputs, supporting
No / NC connections.
• LEDs indicate the status of all the outputs,
power supply and Opto-communication

PRODUCT SELECTION CHART


Size I/O Expansion Module Function
111(L) x 86(H) x 30(D)mm Output Expansion Module Relay Output

TECHNICAL SPECIFICATIONS
Features Specification Features Specification
Mounting Hole Din Rail 72mm Series. 32mm Relative Humidity 95% non-condensing
rail
IP rating IP30 Input Reference 0 Volt
Supply Voltage 9.5 V to 36V DC, Nominal I/O function Set-up and IO assignments are contained
12V / 24V Automative Adjustment within the Master controller
Operating -20 to +60°C Terminations Strip length: 6-7 mm
Temperature Wire range: 24-12 AWG,0.5 to
2.5mm²
Supply Current Standby <9mA@12V DC Testing Environmental Tests: IEC68 Part2
power supply EMC Compliance: EN50081-1,
<13mA@24V DC power EN50081-2, IEC6100-4-3
supply Electrical Safety AS 3100 and AS
Full Function 500mA 3260
Depending on I/O
activations.0
Storage -20 to +85°C
Temperature
BASIC WIRING AND INSTALLATION TIPS

* EMS controllers are designed with rivets for the enclosures, which allows for effortless
mounting of the device onto the control panel.

Rivet

* Knowing the DG is bound to undergo a lot of vibrations, EMS controllers are designed with mass
termination type connectors.

Connector
ELECTRONIC MONITORING SOLUTIONZ LTD.
Address: 5C, Westech Place, Kelston, Auckland 0602 New Zealand
Tel: +64 9818 4726
Fax: +64 9818 4726
Global Marketing: marketing@ems.gen.nz
Technical Support: techsupport@ems.gen.nz
Website: www.ems.gen.nz

TRAK ENTERPRISES.
Address: 3C, 2nd Floor, Symphony C, Range hill Road, Pune INDIA
Tel: +91 0 20 2556 1566
Email: trakent@vsnl.net / virdi@trak.ems.gen.nz
Technical Support: techsupport@ems.gen.nz
Website: www.ems.gen.nz

We also provide consultation for players in Genset market around the world to help provide
the optimal solution.

S-ar putea să vă placă și