The arrangement of conductors of a single phase transmission line is


shown below, where the forward circuit is composed of three solid
wires 2.5 mm in radius and the return circuit of two wires of radius 5 mm
placed symmetrically with respect to the forward circuit.
The mutual GMD between sides A and B is

a. 8.8 m
b. 6.4 m
c. 7.6 m
d. 6.8 m

Not Attem pt Correct Ans. a


Video Solution FAQ? Have any doubt? Solution

Q.2
For some given transmission line the expression for voltage regulation is
given by

. Hence,

a. this must be a 'short' line


b. this may either be a 'medium line' or a 'short line'
c. this expression is true for any line
d. this may either be a 'medium line' or a 'long line'

Not Attem pt Correct Ans. a


Video Solution FAQ? Have any doubt? Solution

Q.3

Determine the insulation resistance of a single core cable of length 5 km


and having conductor radius 12.5 mm, insulation thickness 9 mm and

specific resistance of insulation of 8 × 1012 Ω-m.

a. 108 MΩ
b. 112 MΩ
c. 120 MΩ
d. 138 MΩ

Not Attem pt Correct Ans. d


Video Solution FAQ? Have any doubt? Solution

Q.4

The one line diagram of a system is shown in figure.

The zero sequence network is

a.
b.

c.

d.

Not Attem pt Correct Ans. a


Video Solution FAQ? Have any doubt? Solution

Q.5

In a double line to ground fault on a system, the fault current depended


on

a. Z1 , Z2 , Z0
b. only Z1 , Z2
c. Z2 , Z0
d. Z1 , Z0

Not Attem pt Correct Ans. a


Video Solution FAQ? Have any doubt? Solution

Q.6

Which one of the following types of motors is applicable for equal area
criterion for stability?

a. 3-φ synchronous motor


b. 3-φ induction motor
c. D.C series motor
d. D.C compound motor

Not Attem pt Correct Ans. a


Video Solution FAQ? Have any doubt? Solution

Q.7
In the Merz Price system of protection of alternator, if i1 and i2 are the CT

secondary currents, and nr and no are the number of restraining coils

and operating coils respectively, then the torque-balance equation is

a.

b.

c.

d.

Not Attem pt Correct Ans. c


Video Solution FAQ? Have any doubt? Solution

Q.8

A 25 MVA, 13.2 kV alternator with solid grounded neutral has a


subtransient reactance of 0.25 p.u. The negative and zero sequence
reactances are 0.35 and 0.1 p.u. respectively. A single line to ground fault
occurs at the terminals of an unloaded alternator. The value of fault
current is

a. 4685 A
b. 2376 A
c. 3392 A
d. 3625 A

Not Attem pt Correct Ans. a


Video Solution FAQ? Have any doubt? Solution

Q.9

The transmission line distance protection relay having the property of


being inherently directional is

a. impedance relay
b. MHO relay
c. OHM relay
d. reactance relay

Not Attem pt Correct Ans. b


Video Solution FAQ? Have any doubt? Solution

Q.10
A 400 V, 50 Hz, three phase balanced source supplies power to a star
connected load whose rating is 12√3KVA, 0.8 pf (lag). The rating (in
KVAR) of the delta connected (capacitive) reactive power bank
necessary to bring the pf to unity is ________ .

Not Attem pt Correct Ans. 12.47 (12.30 - 12.60)


Video Solution FAQ? Have any doubt? Solution

Q.11

The maximum demand of a consumer is 2 kW and the corresponding


daily energy consumption is 30 units. The corresponding load factor is
________ %.

Not Attem pt Correct Ans. 62.5 (62.00 - 63.00)


Video Solution FAQ? Have any doubt? Solution

Q.12

A 3-phase, 3-core cable with metal sheet give capacitance of 0.8 μF/km
when two conductors bunched with metal sheath and third conductor
and 0.9 μF/km between bunched conductors and sheath. The
capacitance per phase is ________ μF/km.

Not Attem pt Correct Ans. 1.05 (1.00 - 1.20)


Video Solution FAQ? Have any doubt? Solution

Q.13

A generator feeds power to an infinite bus through a double circuit


transmission line. A three phase fault occurs at the middle point of one
of the lines. The infinite bus voltage is 1 pu, the transient internal voltage
of the generator is 1.1 pu and the equivalent transfer admittance during
fault is 0.8 pu. The 100 MVA generator has an inertia constant of 5
MJ/MVA and it was delivering 1.0 pu power prior of the fault with rotor
power angle of 30°. The system frequency is 50 Hz. The initial
accelerating power (in pu) will be ____________ .

Not Attem pt Correct Ans. 0.56 (0.40 - 0.70)


Video Solution FAQ? Have any doubt? Solution

Q.14

A travelling wave due to lightning with an incident voltage V travels


through the overhead line of surge impedance of 400 Ω and enters a
cable of surge impedance of 40 Ω. The voltage entering the cable at the
junction is __________ V.

Not Attem pt Correct Ans. 0.18 (0.05 - 0.30)


Video Solution FAQ? Have any doubt? Solution

Q.15

In the reactance diagram shown below, the fault current if the


impedance of fault is negligible is –jx p.u.. The value of x = _________.

Not Attem pt Correct Ans. 11.5 (11.00 - 12.00)


Video Solution FAQ? Have any doubt? Solution

Q.16

The ohmic value of impedance to be connected in the neutral to ground


circuit of a 2000 KVA transformer with earth fault relay set to 40%, with
respect to 400 V side is ________ Ω.

Not Attem pt Correct Ans. 0.20 (0.01 - 0.40)


Video Solution FAQ? Have any doubt? Solution

Q.17

A single phase 8 MVA, 33/11 kV transformer has equivalent impedance


referred to LV side as (1 + j9)Ω. Choosing transformer rating as the base
values, the per unit equivalent impedance referred to the HV side is

a. 0.5∠56.4° p.u
b. 0.4∠63.2° p.u
c. 0.6∠83.6° p.u
d. 0.5∠42.6° p.u

Not Attem pt Correct Ans. c


Video Solution FAQ? Have any doubt? Solution

Q.18

In the system shown below, the Zbus of the network is


If line L2 between the buses 1 and 2 is removed, then the modified Zbus is

a.

b.

c.

d.

Not Attem pt Correct Ans. b


Video Solution FAQ? Have any doubt? Solution

Q.19

Two 11 kV, 3-phase, 5 MVA generator having subtransient reactance of


3% and 2% respectively operate in parallel. Suppose the power loaded
through a 11/220 kV, 10 MVA transformer has % equivalent reactance of
4%. The fault current of generator 1 if a three phase fault occurs at H.T.
side of the transformer is

a. 3.28 KA
b. 4.92 KA
c. 8.2 KA
d. 5.66 KA

Not Attem pt Correct Ans. a


Video Solution FAQ? Have any doubt? Solution
Q.20

Alternators 10 MVA, 11 kV having 8% reactance and transformer 15


MVA, 11/33 kV having 10% reactance are connected to bus as shown
below and the bus is connected to grid through reactor.

What is the value of reactor reactance if fault occurs on feeder and


current to be limited to CB rating of 500 MVA. (Take 15 MVA as base)

a. 0.041 pu
b. 0.045 pu
c. 0.128 pu
d. 0.09 pu

Not Attem pt Correct Ans. a


Video Solution FAQ? Have any doubt? Solution

Q.21

The generalized circuit constants of a 3-phase, medium length


transmission line are

A = D = 0.936 + J 0.016 = 0.936 ∠ 0.98ο

B = 33.5 + J 138 = 142.0 ∠ 76.4ο Ω

C = ( -5.18 + J 914 ) × 10-6 ℧


If the load at the receiving end is 50 MW at 220 kV with a power factor of
0.9 lagging, then magnitude of line to line sending end voltage should be

a. 133.2 kV
b. 220.0 kV
c. 230.7 kV
d. 246.3 kV

Not Attem pt Correct Ans. c


Video Solution FAQ? Have any doubt? Solution

Q.22

Three faults stimulated on a power system give the following result:


If,3–φ = 1700 A;

If,LL = 1500 A;
If, SLG = 2000 A

The base values at the fault location are : 100 MVA, 11 kV. The p.u. values
of all sequence impedances are

a. Z1 = 2.24 Ω; Z2 = 3.20 Ω; Z0 = 2.196 Ω


b. Z1 = 3.735 Ω; Z2 = 3.59 Ω; Z0 = 2.196 Ω
c. Z1 = 4.30 Ω; Z2 = 3.59 Ω; Z0 = 2.20 Ω
d. Z1 = 3.735 Ω; Z2 = 4.24 Ω; Z0 = 2.196 Ω

Not Attem pt Correct Ans. b


Video Solution FAQ? Have any doubt? Solution

Q.23

A synchronous generator is rated 645 MVA, 24 kV, 0.9 p.f. lagging. It has
a synchronous reactance of 1.2 Ω. The generator is feeding full load at
0.9 p.f. lagging at rated voltage. The excitation emf (Ef) line to line and

power angle δ are respectively

a. 27.25 kV and 27.33°


b. 47.86 kV and 37.33°
c. 42.55 kV and 27.33°
d. 34.56 kV and 37.33°

Not Attem pt Correct Ans. b


Video Solution FAQ? Have any doubt? Solution

Q.24

Two generators rated 150 MW and 300 MW are operating in parallel. The
droop characteristic of their governors are 3% and 4% respectively. The
speed changes are set so that the generators operated at 50Hz share
the full load of 450 MW in the ratio of their rating. If the load is reduced to
300 MW. The new frequency and generator output assuming free
governor action is

a. 50.4 Hz and PG1 = 100 MW, PG2 = 200 MW


b. 50.6 Hz and PG1 = 90 MW, PG2 = 210 MW
c. 40.9 Hz and PG1 = 80 MW, PG2 = 220 MW
d. 51.6 Hz and PG1 = 70 MW, PG2 = 230 MW

Not Attem pt Correct Ans. b


Video Solution FAQ? Have any doubt? Solution

Q.25

A single phase ring distributor ABC is fed at A. The loads at B and C are
30 A at 0.8 p.f lagging and 20 A at 0.6 p.f lagging respectively both
expressed with reference to voltage at A. The impedances of the section
AB, BC and CA are (1.5 + j1.5), (2 + j 2.5) and (2 + j 3) ohms respectively.
The current in section BC is

a. 1.14 ∠80.9° A
b. 1.12 ∠80.9° A
c. 1.21 ∠–80.9° A
d. 1.15 ∠–80.9° A

Not Attem pt Correct Ans. d


Video Solution FAQ? Have any doubt? Solution

Q.26

In a string of three identical units, the capacitance from each joint is


12.5% of the capacitance of each unit. The voltage across any unit should
not exceeds 11 kV. The voltage across the top most unit is V 1 = _______

kV.

Not Attem pt Correct Ans. 7.91 (7.60 - 8.00)


Video Solution FAQ? Have any doubt? Solution

Q.27

A 50 Hz, 4 pole turbo generator rated 20 MVA, 13.2 kV has an inertia


constant of H = 9 MW-sec/MVA. The acceleration of the generator if the
input less the rotational losses is 25000 HP and the electric power

developed is 15000 kW is _________ elec. degrees/s2 .

Not Attem pt Correct Ans. 182.49 (182.00 - 183.00)


Video Solution FAQ? Have any doubt? Solution

Q.28

A 200 MVA alternator operates on full load at a frequency of 50 Hz. The


load is added to system of 40 MW. Due to time lag in governor system,
the steam valve begins to open after 0.5 second. The change in
frequency that occurs in this time is __________ Hz. (Given, H = 5
MJ/MVA of generator capacity.)

Not Attem pt Correct Ans. -0.50 (-0.30 - -0.70)


Video Solution FAQ? Have any doubt? Solution

Q.29

A 11 kV, 20 MVA star connected alternator has a reactance 4 Ω per


phase and negligible resistance. Merz price protection is used for
protection of winding. The neutral grounding resistance is 7 Ω. If only
85% of the winding is remain protected, the relay setting is _________ %.

Not Attem pt Correct Ans. 12.91 (12.60 - 13.10)


Video Solution FAQ? Have any doubt? Solution

Q.30

An alternator rated at 10 KV protected by the balanced circulating


current system has its neutral grounded through a resistance of 10 Ω.
The protective relay is set to operate when there is an out of balance
current of 1.8 amp in the pilot wires, which are connected to secondary
windings of 1000/5 ratio current transformers. The percentage winding
which remains unprotected is __________ %.

Not Attem pt Correct Ans. 62.36 (62.00 - 62.60)


Video Solution FAQ? Have any doubt? Solution

Q.31

A SLG fault occurs at Bus-2 at the far end of the line. The various
parameters of the system are:
Gen - G: 3-phase, 50 MVA, 33 kV,
X1 = X2 = 0.2 p.u; X0 = 0.1 p.u

33 kV line: X1 = X2 = 10 Ω; X0 = 20 Ω.

The fault current magnitude if the generator neutral is solidly grounded


and fault impedance is zero is ________ A.

Not Attem pt Correct Ans. 1122.33 (1121.00 - 1124.00)


Video Solution FAQ? Have any doubt? Solution

Q.32

In a 220 kV, 50 Hz system the reactance and suceptance upto location of

circuit breaker is 12 Ω and 15 × 10–6 S respectively. A resistance of 500


Ω is connected across the contacts of the circuit breaker. The natural
frequency of oscillation is _________ kHz.

Not Attem pt Correct Ans. 3.72 (3.00 - 4.00)


Video Solution FAQ? Have any doubt? Solution

Q.33

A 11 kV, 3-phase, 50 Hz under ground line, 7 km long uses three single


core cables. Each cable has a core diameter 2.5 c.m. and the radial
thickness of insulation is 1 c.m. The relative permittivity of the dielectric
is 3.5. The maximum electrostatic stress is _________ MV/m.

Not Attem pt Correct Ans. 1.22 (1.05 - 1.40)


Video Solution FAQ? Have any doubt? Solution