Introduction
This document is designed to instruct the users on how to use the IED order specific files (more
popular known as “option files”), more exactly – how to install them during the new IED insertion and
the Configuration Wizard process or later on with the License Update Tool.
IED insertion if you work offline, follow the steps described in the section titled:
- If you don’t have access to the IED.
IED insertion if you work online, follow the steps described in the section titled:
- If you have access to the IED.
How to run License Update Tool, follow the steps described in the section titled:
- If you already started engineering.
These steps assume that you have access to the order specific files (e.g. 213314930.zip, i.e.
ordernumber.zip)
Step 1
Unzip the file to extract the file “Orderoptions 213314930.xml“from it.
Step 2
Start PCM600 and insert your IED, the IED Configuration Wizard will then start.
Select the Offline option and click Next.
Figure 1
Page | 2
How to use order specific files in PCM600 2.x March 24, 2010
Instructions 1MRG000522
Rev. D
Step 3
Select communication protocol and click Next.
Figure 2
Step 4
Enter the IP address for your IED and click Next.
Figure 3
Page | 3
How to use order specific files in PCM600 2.x March 24, 2010
Instructions 1MRG000522
Rev. D
Step 5
Select the IED version and click Next.
Figure 4
Step 6
Select Browse and navigate to the directory containing the previously unzipped xml file. Select the xml
file, click Open and Next (Fig. 6 and Fig. 7).
Figure 5
Page | 4
How to use order specific files in PCM600 2.x March 24, 2010
Instructions 1MRG000522
Rev. D
Figure 6
Figure 7
Page | 5
How to use order specific files in PCM600 2.x March 24, 2010
Instructions 1MRG000522
Rev. D
Step 7
Confirm the housing options, by clicking Next.
Figure 8
Step 8
Click Finish on the last Configuration Wizard screen, to complete the IED insertion process.
Figure 9
Page | 6
How to use order specific files in PCM600 2.x March 24, 2010
Instructions 1MRG000522
Rev. D
Start PCM600 and insert your IED, the IED Configuration Wizard will then start.
Select the Online option and click Next.
Figure 10
Perform step 3 and 4 described in chapter 2 and then perform a scan on the IED that you are
connected to by clicking Scan and Next.
Figure 11
Perform step 7 and 8 described in chapter 2, to complete the online installation. The order options will
be loaded from the IED.
Page | 7
How to use order specific files in PCM600 2.x March 24, 2010
Instructions 1MRG000522
Rev. D
For offline license update these steps assume that you have access to the order specific files (e.g.
213314930.zip, i.e. ordernumber.zip)
Step 1
For offline license update unzip the file to extract the file “Orderoptions 213314930.xml“from it.
Step 2
Start License Update Tool by right clicking the IED and select “License Update Tool”.
Figure 12
Step 3
Select Yes or No to make a backup or not. It’s recommended to make a backup.
Figure 13
Page | 8
How to use order specific files in PCM600 2.x March 24, 2010
Instructions 1MRG000522
Rev. D
Step 4
Select Online or Offline and click next.
For Offline follow step 5, 6 and 8.
For Online follow step 7 and 8.
Figure 14
Step 5
Select Browse and navigate to the directory containing the previously unzipped xml file. Select the xml
file, click Open and Next.
Figure 15
Page | 9
How to use order specific files in PCM600 2.x March 24, 2010
Instructions 1MRG000522
Rev. D
Step 6
Click Finish on the last License Update Wizard screen, to complete the IED license update process.
Figure 16
Step 7
Click Finish on the last License Update Wizard screen, to complete the IED license update process.
Figure 17
Page | 10
How to use order specific files in PCM600 2.x March 24, 2010
Instructions 1MRG000522
Rev. D
Step 8
After completion a migration report is presented, showing deleted functionality.
Figure 18
Figure 19
If there are any deleted function blocks, you need to check the configuration and make sure that all
variables related to that function block are deleted as well and this will not impact the configuration.
After this, you are ready now to continue using the IED in PCM.
Limitation
If the order option in the IED is updated and a read command is executed, operation will fail. Hence
the order option and the configuration will not match in the IED. To avoid this situation it is
recommended that always execute a write operation from PCM with the new order options in order
to synchronize the configuration and order options both in IED and PCM.