Documente Academic
Documente Profesional
Documente Cultură
In-
In-house-
house-technical training for Electrical Power Engineers
of Davao Light & Power Co., Inc.
1. Electromechanical (Electromagnetic)
2. Static
3. Microprocessor
a) Digital ( analog hybrid)
b) Numeric (Numerical)
Electromechanical
An electromechanical relay converts the
voltages & currents to magnetic & electric
forces & torques that press against spring
tensions in the relay. The tension of the spring
& taps on the electromagnetic coils in the relay
are the main process by which the user sets
such a relay.
Solid State
In a solid state relay, the incoming voltage & current
waveforms are monitored by analog circuits, not
recorded or digitized. The analog values are compared
to settings made by the user via potentiometers in the
relay & in some case, taps on transformers.
In some solid state relays, a simple microprocessor
does some of the relay logic, but the logic is fixed &
simple. In some solid state overcurrent relays, the
incoming AC current is converted in a small signal AC
value, then the AC is fed into a rectifier & filter that
converts the AC to DC value proportionate to the AC
waveform. An op- op-amp & comparator is used to create a
DC that rises when a trip point is reached.
Solid State Relay Logic
Digital
Digital Relays (also known as the analog hybrid)
utilize analog signal measurement techniques to
provide protective trip functions. The role of the
microprocessor in this class of protective relay
was limited to providing some timing, control,
& ancillary logic functions.
Microprocessor
Numerical
A numeric (or numerical) relay digitally samples
the incoming analog signals, converts them to a
binary number, & passes them to a
microprocessor chip where algorithms performs
mathematics to measure the condition of the
power system & to provide the protective (trip)
functions.
Numerical Relay Logic Circuit
Numerical Relay Main Components
Numerical Relay Construction
Numerical Relay Hardware Construction is made of
several subsections:
1. Power Supply
2. Measuring Inputs
3. Input Amplifiers
4. Analog –to
to--Digital (AD)
5. Microcomputer
6. Displays
7. Communications
8. Input/Output (I/O)
9. Enclosure Case
10. Human Machine Interface
Relay Application Design Criteria
The application logic of protective relays divides the power
system into several zones, each requiring its own group of
relays. In all cases the three design criteria are common to
any well designed & efficient protective system.
Since it is impractical to satisfy fully all these design
criteria simultaneously, the necessary compromises must
be evaluated on the basis of comparative risks.
They are:
1) Reliability
2) Speed
3) Simplicity
Reliability
System Reliability consists of two elements:
1) Dependability
2) Security.
Example:
Differential Relays – high speed
Time Overcurrent Relays – low speed
Simplicity
Simplicity in a protective relay system is always
the hallmark of good design. The simplest relay
system, however, is not always the most
economical. Major economies maybe possible
with a complex relay system that uses a
minimum number of circuit breakers.
Simplicity of design improves system reliability –
if only because there are fewer elements that can
malfunction.
Relay Performance Classifications
1) Correct Operation
2) Incorrect Operation
3) No Conclusion
Incorrect Operation & No Conclusion
A. Incorrect Operation - maybe either failure to trip or false tripping.
1) Poor application
2) Incorrect Settings
3) Personnel Error
4) Equipment Failure
equipment that can cause an incorrect operation includes CTs,
VTs, breakers, cable & wiring, relays, channels, or station
batteries.
1) Wound primary type – this has more than one primary turn. The primary and
secondary windings are completely insulated for their respected voltage ratings
and permanently assembled on a laminated iron core.
2) Through or Bar type – this type has the primary & secondary windings
completely insulated and permanently assembled on a laminated iron core.
The primary winding consists of a bar-
bar-type conductor passing through the core
window.
I – Light 16
II – Medium 20
III – Heavy 25
IV - Very Heavy 31
Current Transformer Accuracy Class
(Relaying)
Protective relay performance depends on the accuracy
of the current transformers, not only at load currents,
but also at all fault current levels. The accuracy at high
over currents depends on the cross section of the iron
core and the number of turns in the secondary winding.
The bigger the cross section of the iron core, the more
flux can be developed before saturation. The more the
number of turns, the lower the flux can be developed
before saturation. The more the number of turns, the
lower the flux required to force the secondary current
into the relay. Saturation results in an increase of ratio
error.
ANSI Relay Accuracy Class Designation of CTs
The ANSI relay accuracy class by letter designation and voltage rating.
C…indicates that the transformer ratio can be calculated (10L – earlier type)
T…indicates that the transformer ratio must be determined by test (10H –earlier)
The classification number indicates the secondary terminal voltage that the CT
will deliver to a standard burden at 20 times normal secondary current (100A)
without exceeding a 10% ratio correction.
The standard designated secondary terminal voltages are 10, 20, 50, 100, 200, 400
& 800V.
For instance a ct with a relaying class of C200 means that the % ratio correction
can be calculated & that it does not exceed 10% at any current from 1 to 20 times
the rated secondary current at standard burden of 2 ohms.
15 VA Class 5 P 20
15 VA – continuous VA
Class 5 – Accuracy class
P -- Protection class
20 -- Accuracy limit factor
CT Accuracy Equivalents
IEC ANSI
5P20 @ 25 VA C--100
C
5P20 @ 50 VA C-200
C-
5P20 @ 100 VA C-400
C-
5P20 @ 200 VA C-800
C-
Choosing Current Transformer for Relaying Use
To be sure that the CTs do not saturate, the relay class rating
of the CT should be twice the voltage necessary to drive the
maximum fault current thru the connected burden.
For example, assume a bus with 24 KA fault current and a CT
rated 600:5A. Divide the 24KA by the ratio 120, to determine
the secondary current, 200A, under maximum fault
conditions.
If the secondary burden is 0.53 ohms, the voltage required is
200 x 0.53 =106 V. A CT with relay class rating of C200 or
T200 or higher accuracy should be chosen for this application.
Choosing CT
Where low ratio CTs are needed on a system with a high
available fault current, it may be difficult to find with a
necessary relay class rating.
W 12.5 0.10
X 25.0 0.70
M 35.0 0.20
Y 75.0 0.85
Z 200 0.85
ZZ 400 0.85
VT ANSI ACCURACY CLASS
Accuracy Limits of Correction Limits of Power Factor
Class Factor & Transformer Lagging of Load
Min Max
0.3 0.997 1.003 0.6 – 1.0
0.6 0.994 1.006 0.6 – 1.0
1.2 0.988 1.012 0.6 – 1.0
1 2 L--G
L 1.25/8hr
2 2 L-L
L- -
3 1 L-G
L- 25 -161kv, 1.74/1min
230
230--750kv, 1.40/1min
4A 1 L--G
L 1.25/8hr
4B 1 L-L
L- -
5 1 L-G
L- 1.40/1 min
Coupling Capacitor VT
It is a voltage transformer tapped across part of
a capacitor unit connected from the conductor
to ground.
It is widely used at the system voltages of 115KV
& above.
It is suitable for Power Line Carrier Coupling.
CCVT
System Neutral Grounding
Primary Purposes of System Grounding
1.732 x Vf
Line--Line Fault
Line If line-
line-line = -------------------- x Base I
Z1 + Z2
3 x Vf
Single--line
Single line--to
to--Grd If slgd = ---------------------- x Base I
Z1+Z2+Z0+Zn
Relay Classification According to
Operating Time Characteristics
1. Instantaneous Relays – are those with no intentional
time delay. Operating maybe ½ cycle or less.
2. Definite – time Relays – those with a preset time that
is not dependent on the magnitude of the actuating
current or voltage once pick-
pick-up value is exceeded.
3. Inverse time delay relays – those whose operating time
is long for small values of actuating current (or voltage)
and becomes progressively less for increasingly higher
values of current.
Types of Overcurrent Relay Curves
Inverse Relay Curve – Least Steep
Assume that the 7SJ relay should trip on sustained current at 500
amps minimum and 3000 amps in 1 second. The CT ratio is 600:5 A.
13.5
t = ________ . Tp
(I/
(I/Ip
Ip)) – 1
13.5
t = ________ . Tp
(25/4.16) – 1
t = 2.7
@ t = 1 sec Tp=1/2.7
Tp=1/2.7
Iop 0.1
% slope = ------------ x 100 = ------- x 100 = 2%
Ir (smaller) 4.9
From fig. 8
To determine if the relay will operate during
external fault, apply these values to the percent
slope equation:
Iop 1
% slope = ------------- x 100 = --------- x 100 = 2%
Ir (smaller) 49
Iop = 50 – 10 = 40 A
40
% slope = ------ x 100% = 400%
10
a) Overvoltage Relays
b) Undervoltage Relays
Overvoltage Relay (59)
Overvoltage relay - is a relay that functions on a given value of
overvoltage. It is calibrated on increasing voltage
to close a set of normally open contacts at a
specified voltage.
a) Inverse time
b) Definite time
c) Instantaneous
Inverse Time Overvoltage Relay
Voltage Relaying
3-phase Voltage Relaying
Undervoltage Relay (27)
Undervoltage Relay – is a relay that functions on a given value of undervoltage.
It is calibrated on decreasing voltage to close a set of
contacts at a specified voltage.
They are mostly used as bus undervoltage protection either, to alarm or trip
voltage sensitive loads, such as induction motors whenever the line voltage drops
below the calibrated setting.
They are also used for Source Transfer Scheme, where it will initiate transfer &
when desired, retransfer of a load from its normal source to a standby or
emergency power source.
The relay must be reset before the any of the breakers can be
reenergized. The manual reset prevents reclosing the breakers
before the fault is cleared.
AC Reclosing Relay (79)
Is a relay that controls the automatic reclosing
& locking out of an ac-
ac-circuit interrupter.
Distance Relay (21)
It is a relay that functions when the circuit
admittance, impedance or reactance increases or
decreases beyond predetermined limits.
For line protection, it measures the impedance on
the distance from the relay location to the point of
fault.
Types of Distance Relays
Reactance type – measures the reactive component of system
complex impedance. They are inherently non-
non-directional.
Operation is practically unaffected by arc resistance, but may
operate on load current.