HiMAP&HiCAM-II
Protection
Relay
Function
Measuring
Function
Event
Record
Function
Communication
Function
Fault Wave
Record
Function
Circuit Breaker
Remote Control
Function
HiMAP Hyundai Intelligent Measuring &
Protection Device
Characteristics M-2
Display M-4
Power Management System HIPMS-Plus M-6
Setting Range M-8
Connection Diagram M-9
Terminal Block Pin Specification M-11
Characteristic Curve M-12
Order Form M-14
View & Dimension M-15
HiMAP Hyundai Intelligent Measuring & Protection Device
Characteristics
HiMAP is designed with a removable case so that HiMAP remotely controls circuit breakers by means of the
the external electric lines can be connected to the command from SCADA Systems and controls the load of
inner part for easy installation and maintenance. power in the computer through RS-485 communication port.
If there is interfacing with another company’s monitoring
system, it is easy to connect both systems because our
Self-diagnosis Function
communication control device provides various interface
HiMAP has a self-diagnosis function set to observe ports and protocols.
any system failures, send an alarm signal, and
display it on the VFD window.
Harmonic Analysis Function
Use of a Digital Filter ▶ Harmonic contents (1st-18th) for three phase current
can be measured. (THD, TDD)
HiMAP uses a digital filter, which prevents any ▶ Harmonic contents for three phase fault wave can be
harmonic effects from the high frequency on the analyzed using HiMAP manager program.
power line.
Vector Diagram
Harmonic Analysis
M-2
HiMAP
Measuring Function
HiMAP has a measuring function as shown in the below table. It displays the value of each measurement on the
VFD window by operating a menu key and then transfers and displays the data on the HIMIX window, which has an
outside digital indicator connected by a communication cable.
Various kinds of measuring values are converted to a primary value by input of a CT/PT ratio and then displayed on
the VFD window.
Communication Function
HiMAP has four communication ports. RS-485 ports transfer all information related to relay operation status,
measuring information, and operation status of circuit breakers. This information is then perceived by HiMAP and
sent to communication control device at the speed of 62.5 K bps, using RS-485 HDLC frame protocol and
MODBUS-RTU protocol.
The communication control device connects a master PC to the Power Management System (HIPMS) at the speed
of 10M bps by Ethernet, TCP/IP. Please refer to the HIPMS manual for details on the monitoring function.
HIMIX communication port transfers kinds of measuring values optional to HIMIX at the speed of 9600 bps.
The external port of HiMAP transfers the fault record from a site to the PC for analysis, changes the relay element
value to a correct one, and is an RS-232C communication port to monitor the status of all kinds of protection relay.
M-3
HiMAP Hyundai Intelligent Measuring & Protection Device
Display
Front View
Internal Case
Display Key
Input Key
Set ACK
M-4
HiMAP
Specification
Item Specification
Current 1A or 5A, Burden: Below 0.1VA/Phase
Rating Voltage 110V or 190V, Burden: Below 0.3VA/Phase
Measuring ±0.2%
Accuracy
Protection Relaying ±2%
Circuits-Ground 10 MΩ
Insulation
Between Circuits 5 MΩ
Resistance
Between Contacts 5 MΩ
I / O Point
M-5
HiMAP Hyundai Intelligent Measuring & Protection Device
System Configuration
To Wide and
Enterprise Management Network Local Area Networks
Web Client Mobile Phone
Router (Web Browser) (SMS)
GPS
Maintenance Maintenance
& Operating & Operating
Web Server Multi Server Multi Server
Internet
FEP
Notebook PC
Display Configuration
M-6
HiMAP
Alarm Printer
Gateway
M-7
HiMAP Hyundai Intelligent Measuring & Protection Device
Setting Range
FI Type
M-8
HiMAP
Connection Diagram
HiMAP-FI(3CT, 3PT)
R S T
R1 21
PT / GPT
9 22
10 DISPLAY R2
11 23
12
13 24 Program-
14 mable
R3 25
Relay
CPU 26 Output
15
R4 27
16
28
CB GPT
3rd R5 29
1 30
2 R6
31 Local/
3 Remote
4 50 32
CB On
5 R7 33
CT 6 51 Local/
Remote
34 CB Off
7
8
50G
35
NA
51G 36
37
27 CCS
38
47P Option
39
TCS
R S T DC 24 V
47N 40
1 59 41
2 42
50
3
52a 64 43
44 NA
4
5 52b
51 67G 45
46
CT 6
52
67 47
Remote 48
Vp
67N 60
Vn
7 53 61
DI1
ZCT 8 62 RS485
(Scada)
63
54
DI2 64
65
When using ZCT 59 KEYBOARD Vp
66
(SGR) Vn RS485
67 (HIMIX)
68 Option
P
Control
N
Power
FG
M-9
HiMAP Hyundai Intelligent Measuring & Protection Device
Connection Diagram
HiMAP-FI(2CT, 2PT)
R S T
R1 21
PT × 2
9 22
10 DISPLAY R2
11 23
12
13 24 Program-
14 mable
R3 25
Relay
CPU 26 Output
15
R4 27
16
28
CB
R5 29
1 30
2 R6 31 Local/
3 Remote
CB On
4 50 32
5 R7 33
CT 6 51 Local/
Remote
CB Off
7 34
8
50G
35
NA
51G 36
37
27 CCS
ZCT 38
47P Option
39
TCS
R S T DC 24 V 47N 40
59 41
42
50
52a 64 43
44 NA
52b
51 67G 45
46
47
52
Remote 48
Vp
60
Vn
53 61
DI1
62 RS485
(Scada)
63
54
DI2 64
65
59 KEYBOARD Vp
66
Vn RS485
67 (HIMIX)
68 Option
P
Control
N
Power
FG
M - 10
HiMAP
HiMAP-FI Type
M - 11
HiMAP Hyundai Intelligent Measuring & Protection Device
Characteristic Curve
0.01 0.01
DOCR
M - 12
HiMAP
OVR OVGR
0.01 0.01
DGR SGR
DOCGR
M - 13
HiMAP Hyundai Intelligent Measuring & Protection Device
Order Form
A. Type Selection of HiMAP Please check mark(⋏) into the type required.
HiMAP – ❶ – ❷ ❸ – ❹ (Option)
❶ ❷ ❸ ❹ (option) 4)
Relay Type Ground Fault Type Communication TCS Function
FI Feeder/Incoming C OCGR C RS-485 HDLC T Required
M Motor D DGR / DOCGR X No System Interface X Not Apply
87M Big Motor S SGR M MODBUS-RTU
T Transformer
SY Synchro check
※ Type of 87M (Protection for big motor): ( ) self-balancing type / ( ) differential type
Table 2 (M)
Item MPR OCGR(50/51G) DGR(67G) / SGR(67G)
DOCGR(67N)
C ● ●
D ● ●
S ● ●
Table 3 (87M)
Item 87M MPR OCGR(50/51G) DGR(67G) / SGR(67G)
DOCGR(67N)
C ● ● ●
D ● ● ●
S ● ● ●
Table 4 (T)
Item DFR OCR P(50/51P) 1) OCR S(50/51S) 2) OCGR(50/51G) DGR(67G) / SGR(67G)
DOCGR(67N)
C ● ● ● ●
D ● ● ● ●
S ● ● ● ●
※ 1) OCR P is transformer primary OCR
2) OCR S is transformer secondary OCR
3) The control voltage of HiMAP is only allow AC / DC 95 - 250V, 50 / 60Hz as a free voltage
4) TCS(Trip Coil Supervision): Circuit breaker coil disconnection check. (option)
Note
Ground fault function shell be selected in accordance with the system ground method.
- OCGR (50G/51G): Effective ground system
- DGR (67G): Resister ground system
- SGR (67G): Floated ground system
M - 14
HiMAP
Weight 4.3Kg
139
186
33 218
206 251
185
Rear View
M - 15
HiCAM-II Hyundai Intelligent Communication &
Measuring Device
Characteristics C-2
Display C-2
Connection Diagram C-4
Terminal Block Pin Specification C-5
View & Dimension C-6
HiCAM-II Hyundai Intelligent Communication & Measuring Device
Characteristics
▶ 15 measuring points
Display
Front View
Display Window
Communication Address
Navigation Key
CB Control Switch/LED
Remote Key
C- 2
HiCAM-II
I / O Point
Specification
Item Specification
Current 1 A or 5 A(0.1 A~10 A), Burden : Below 0.1 VA / Phase
Rating Voltage 110 V or 190 V(10 V~380 V), Burden : Below 0.3 VA / Phase
Frequency 50 Hz or 60 Hz
Accuracy Measuring ±0.2 %
Operation Guarantee -10 ℃ ~ 55 ℃
Temperature
Restoration Guarantee -25 ℃ ~ 70 ℃
Circuit-Ground 10 ㏁
Insulation
Between Circuits 5㏁
Resistance
Between Contacts 5㏁
Voltage Power Frequency AC 60 Hz 2,000V/1 Min
Withstand Lightning Impulse 1.2/50 ㎲ 5 kV
Current Circuit Rating Current×3 : 3 hours / Rating Current×20 : 1 sec
Overland
Voltage Circuit Rating Voltage×3 : 3 hours
Withstand
Control Power Rating Voltage×1.3 : 3 hours
Control Power AC 85 ~ 264 V (50 / 60 Hz), DC 90 ~ 120 V
Power Consumption 18 VA, AC 220 V
Communication Type RS–485 / Multi Drop
Protocol HD-BUS / Modbus
Standards KEMC1110, IEC1036
Size 202.5 (W)×156 (H)×189 (D)
Weight 1.5 Kg
Measuring
C- 3
HiCAM-II Hyundai Intelligent Communication & Measuring Device
Connection Diagram
3P 4W 3PT_3CT 3P 3W 2PT_2CT
RS T N 45/50/55 41 42 43 44 46 47 48 49 51 52 53 54 RS T 45/50/55 41 42 43 44 46 47 48 49 51 52 53 54
PT/GPT 9 PT 9
10 10
11 11
12 DI 12 DI
13 13
14 14
Vp Vp
66 66
Vn 67 Vn 67
15 15
16 68 16 68
69 69
GPT 70 70
AI COMM. AI COMM.
1 1
2 2
3 3
L L
4 4
N N
5 5
DO FG DO FG
CT 6 CT 6
AD/DC AD/DC
7 95~250V 7 95~250V
8 R5 R4 R3 R2 R1 50/60Hz 8 R5 R4 R3 R2 R1 50/60Hz
40 39 38 37 36 35 34 33 32 31 40 39 38 37 36 35 34 33 32 31
3P 3W 3PT_3CT 3P 3W 2PT_3CT
RS T 45/50/55 41 42 43 44 46 47 48 49 51 52 53 54 RS T 45/50/55 41 42 43 44 46 47 48 49 51 52 53 54
PT 9 PT 9
10 10
11 11
12 DI 12 DI
13 13
14 14
Vp Vp
66 66
Vn 67 Vn 67
15 15
16 68 16 68
69 69
70 70
AI COMM. AI COMM.
1 1
2 2
3 3
L L
4 4
N N
5 5
DO FG DO FG
CT 6 CT 6
AD/DC AD/DC
7 95~250V 7 95~250V
8 R5 R4 R3 R2 R1 50/60Hz 8 R5 R4 R3 R2 R1 50/60Hz
40 39 38 37 36 35 34 33 32 31 40 39 38 37 36 35 34 33 32 31
C- 4
HiCAM-II
Control Power Terminal Digital Input Digital Output Terminal No. Description Application
L (+) 41 52a 31 R1(+) 31~32 R1
N (-) 42 52b 32 R1(-) 33~34 R2 Variable
FG FG 43 Remote 33 R2(+) 35~36 R3
44 DI 1 34 R2(-) 37~38 R4(Remote On) Fixed
Terminal 45 Common(+24V) 35 R3(+) 39~40 R5(Remote Off) Fixed
56 46 DI 2 36 R3(-) 41 CB On Status 52a
57 47 DI 3 37 R4(CB On) 42 CB Off Status 52b Fixed
58 48 DI 4 38 R4(CB On) 43 Remote Input
59 49 DI 5 39 R5(CB Off) 44 General DI Variable
60 50 Common(+24V) 40 R5(CB Off) 45 Common HiCAM Self Power +24V
N.A.
61 51 DI 6 46 General DI
62 52 DI 7 Analog Input 47 General DI
63 Variable
53 DI 8 1 Ia 2 48 General DI
64 54 DI 9 3 Ib 4 49 General DI
65 55 Common(+24V) 5 Ic 6 50 Common HiCAM Self Power +24V
Io 51 General DI
7 8
Communication 52 General DI
9 Vab 10
Terminal Variable
Vbc 53 General DI
Vp 11 12
66
Vca 54 General DI
Vn 13 14
67
Vo 55 Common HiCAM Self Power +24V
Vp 15 16
68
Vn 17 N.A. 18
69
N.A. 19 N.A. 20
70
C- 5
HiCAM-II Hyundai Intelligent Communication & Measuring Device
Weight 1.5Kg
186
139
33 141 15
206
156
185
138
Rear View
C- 6