HYUNDAI DIGITAL PROTECTION & MEASURING DEVICE

HiMAP&HiCAM-II

Hyundai Intelligent Measuring & Protection Device HiMAP

Hyundai Intelligent Communication & Measuring Device HiCAM-II


HYUNDAI DIGITAL PROTECTION & MEASURING DEVICE

HiMAP is a multifunctional digital protection relay that has a protection function


to protect incoming and feeder lines, the motor and the transformer.
It also has various kinds of measuring functions to check synchronization and a
communication function for the Power Management System (HIPMS) to supervise
operating conditions.

HiCAM-II has integrated as many as 15 analog meters in one body.


The measuring accuracy is below ±0.2-1.0% at rating.
For power monitoring system connection, HiCAM has RS485 communication port,
communication control device (HICM series) and support modbus protocol.
Remote CB On/Off control is possible by the command from power monitoring
system.

Protection
Relay
Function
Measuring
Function
Event
Record
Function

Communication
Function

Fault Wave
Record
Function
Circuit Breaker
Remote Control
Function
HiMAP Hyundai Intelligent Measuring &
Protection Device

Characteristics M-2
Display M-4
Power Management System HIPMS-Plus M-6
Setting Range M-8
Connection Diagram M-9
Terminal Block Pin Specification M-11
Characteristic Curve M-12
Order Form M-14
View & Dimension M-15
HiMAP Hyundai Intelligent Measuring & Protection Device

Characteristics

▶ Excellent operating characteristics using a 32 bit microprocessor.


▶ Easy to operate using an interactive menu system.
▶ Easy to connect monitoring system & local computer using four communication channels.
▶ Increased reliability using a self-diagnostic function.
▶ Designed for operator’s convenience.

Easy Installation and Maintenance Circuit Breaker Remote Control Function

HiMAP is designed with a removable case so that HiMAP remotely controls circuit breakers by means of the
the external electric lines can be connected to the command from SCADA Systems and controls the load of
inner part for easy installation and maintenance. power in the computer through RS-485 communication port.
If there is interfacing with another company’s monitoring
system, it is easy to connect both systems because our
Self-diagnosis Function
communication control device provides various interface
HiMAP has a self-diagnosis function set to observe ports and protocols.
any system failures, send an alarm signal, and
display it on the VFD window.
Harmonic Analysis Function

Use of a Digital Filter ▶ Harmonic contents (1st-18th) for three phase current
can be measured. (THD, TDD)
HiMAP uses a digital filter, which prevents any ▶ Harmonic contents for three phase fault wave can be
harmonic effects from the high frequency on the analyzed using HiMAP manager program.
power line.

Fault / Event Recording Function

HiMAP saves fault events up to 100. Each event


data has a fault phase, pick up ratio, operating time
and fault date.
Also, for the latest fault, HiMAP saves a fault wave
which is 300 cycles with the resolution 36 sampling /
cycle.
This can be transfer to monitoring system by
communication port.

Vector Diagram

Harmonic Analysis

M-2
HiMAP

Protection Relay Function

Model Protection Object Relay Function


•OCR(50/51) •OCGR(50G/51G) •DGR(67G) •DOCR(67)
HiMAP–FI Incoming Feeder •SGR(67G) •OVR(59) •OVGR(64) •DOCGR(67N)
•UVR(27) •PSR(47P/47N) •Trip coil supervision(94) (Option)

•OCR(50) •51LR •THR(49) •NSR(46)


HiMAP–M Motor •NCHR(66) •UCR(37) •OCGR(50G/51G) •DGR(67G)
•SGR(67G) •DFR(87M) •Closing/Trip coil supervision(94)(Option)
•DFR(87T) •OCR(50/51P)✽ •OCR(50/51S)✽
HiMAP-T Transformer •OCGR(50G/51G) •DGR(67G)
•SGR(67G) •Closing/Trip coil supervision(94)(Option)
HiMAP-SC Syncro-Check •SCR(25) •UVR(27)
✽ HiMAP-T Type has 2 OCRs. P means primary and S means secondary.

Measuring Function

HiMAP has a measuring function as shown in the below table. It displays the value of each measurement on the
VFD window by operating a menu key and then transfers and displays the data on the HIMIX window, which has an
outside digital indicator connected by a communication cable.
Various kinds of measuring values are converted to a primary value by input of a CT/PT ratio and then displayed on
the VFD window.

Measuring Display Accuracy (%)


Voltage(Vr, Vs, Vt, Vo, Vps, Vns, Vavg, Vomax) 0-999999V ±0.2
Current(Ir, Is, It, Io, Ips, Ins, Iavg, ITHD, ITDD) 0-999999A ±0.2
Real Power 0-99999999 kW ±0.2
Reactive Power 0-99999999 kvar ±0.5
Power

Accumulated Real Energy 0-99999999 kWh ±1.0


Accumulated Reactive Energy 0-99999999 kvarh ±1.0
Power Factor -1.0-1.0 PF ±0.5
Frequency 45-65Hz ±0.01Hz
※ CT/PT ratio will be set by using relay control keys and then displayed via VFD window.
The values will be saved at flash memory even though the power line will be off.

Communication Function

HiMAP has four communication ports. RS-485 ports transfer all information related to relay operation status,
measuring information, and operation status of circuit breakers. This information is then perceived by HiMAP and
sent to communication control device at the speed of 62.5 K bps, using RS-485 HDLC frame protocol and
MODBUS-RTU protocol.
The communication control device connects a master PC to the Power Management System (HIPMS) at the speed
of 10M bps by Ethernet, TCP/IP. Please refer to the HIPMS manual for details on the monitoring function.
HIMIX communication port transfers kinds of measuring values optional to HIMIX at the speed of 9600 bps.
The external port of HiMAP transfers the fault record from a site to the PC for analysis, changes the relay element
value to a correct one, and is an RS-232C communication port to monitor the status of all kinds of protection relay.

Interface with SCADA


Communication Control Device Type of Communication Protocol
HICM-PC(II) Ethernet Modbus / TCP

M-3
HiMAP Hyundai Intelligent Measuring & Protection Device

Display

Front View

Display Window(VFD) Exterior Case

Internal Case

System Status Indicator


CB Status (Normal Operation,
System Fail, Fault)
CB Control

Display Key

Input Key

Select Switch & Led

RS232 Port Movement Key

Set ACK

M-4
HiMAP

Specification

Item Specification
Current 1A or 5A, Burden: Below 0.1VA/Phase
Rating Voltage 110V or 190V, Burden: Below 0.3VA/Phase

Frequency 50Hz or 60Hz

Measuring ±0.2%
Accuracy
Protection Relaying ±2%

Operation Guarantee -10℃ - 55℃


Temperature
Restoration Guarantee -25℃ - 70℃

Circuits-Ground 10 MΩ
Insulation
Between Circuits 5 MΩ
Resistance
Between Contacts 5 MΩ

Voltage Power Frequency AC 60Hz 2000V/1 Min


Withstand Lightning Impulse 1.2/50㎲ 5 kV

Current Circuit Rating Current×3: 3 hours / Rating Current × 20: 2sec


Overland
Voltage Circuit Rating Voltage × 3: 3 hours
Withstand
Control Power Rating Voltage × 1.3: 3 hours
Control Power Interruption Maximum 300 ms
Control Power AC/DC 95V - 250V 50/60Hz, DC 48V
Standards IEC 60255 / KEMC 1120 / IEC 61000-4
Communication Type RS-485 Multi Drop
Protocol HD-BUS / DNP 3.0 / MODBUS
Size 202.5(W) × 156(H) × 251(D)
Weight 4.3kg

I / O Point

Item Point Remark


AI Voltage 4 Default✽
Input AI Current 4 Default✽
DI 5 Default
Default(R1-R7) (21-34)
Output DO 7 31, 32(R6): Remote CB On
33, 34(R7): Remote CB Off
✽ HiMAP-87M(Self-balancing Type) : Current(7CH), Voltage(1CH)
HiMAP-87M(Differential Type) : Current(7CH), Voltage(0CH)
HiMAP-T : Current(7CH), Voltage(1CH)

M-5
HiMAP Hyundai Intelligent Measuring & Protection Device

Power Management System HIPMS-Plus

System Configuration

Remote HIPMS-Plus Station

To Wide and
Enterprise Management Network Local Area Networks
Web Client Mobile Phone
Router (Web Browser) (SMS)
GPS

Maintenance Maintenance
& Operating & Operating
Web Server Multi Server Multi Server

Internet

Redundant Ethernet Network 10/100Mbps(Fiber Optic)

FEP

HICM860S(P) HICM860S(S) HICM860S(P) HICM860S(S) HICM860S(P) HICM860S(S)

Notebook PC

HiMAP-BC RTU(HRC-NET) HiCAM-II

Display Configuration

System Configuration System Detail(1) System Detail(2)

HiMAP Detail RTU Detail Network Status

M-6
HiMAP

Alarm Printer

Report Printer External System


Network

Color Hard Copler

Gateway

HICM860S(P) HICM860S(S) HICM860S(P) HICM860S(S)

HiMAP-F HiMAP HiMIX

Trend Report Setting Report

Alarm Fault Analysis Remote Setting

M-7
HiMAP Hyundai Intelligent Measuring & Protection Device

Setting Range

FI Type

Mode Instant Definite Inverse, Very Inverse, Extremely Inverse


OCR
Current (1-18) × In (0.1A Step) (0.2-2.4) × In (Time Delay) (0.1A Step)
(50/51)
Time Below 0.05sec 0.05-10.0sec (0.01sec Step) 0.05-10.0 Tap (Time Delay) (0.01 Step)
Mode Instant Definite Inverse, Very Inverse, Extremely Inverse
OCGR
Current (0.1-12) × In (0.1A Step) (0.02-1.0) × In (Time Delay) (0.1A Step)
(50G/51G)
Time Below 0.05sec 0.05-10.0sec (0.01sec Step) 0.05-10.0 Tap (Time Delay) (0.01 Step)
Mode - Definite -
UVR
Voltage - (0.2-1.0) × Vn (0.1V Step) -
(27)
Time - 0.1-10.0sec (0.1sec Step) -
Mode - Definite -
POR 47P Voltage - (0.5-1.0) × Vn (0.1V Step) -
Time - 0.1-10.0sec (0.1sec Step) -
Mode - Definite -

NSOVR 47N Voltage - (0.02-0.5) × Vn (0.1V Step) -


Time - 0.1-10.0sec (0.1sec Step) -
Mode - Definite Inverse
OVR
Voltage - (1.1-1.45) × Vn (0.1V Step)
(59)
Time - 0.1-10.0sec (0.1sec Step) 0.05-10.0 Tap (Time Delay) (0.01 Step)
Mode Instant - Inverse
OVGR
Voltage (0.11-0.5) × Vn (0.1V Step)
(64)
Time Below 0.05sec - 0.05-10.0 Tap (Time Delay) (0.01 Step)
Mode Definite
Current (0.04-0.4) × In (0.1A Step)
DGR
Voltage (0.1-0.2) × Vn (0.1V Step)
(67GD)
Time 0.1-10.0sec (0.1sec Step)
Angle 10°- 45°(1°Step)
Mode Definite
Current 1-10 mA (0.1 mA Step)
SGR
Voltage (0.1-0.2) × Vn (0.1V Step)
(67GS)
Time 0.1-10.0sec (0.1sec Step)
Angle 45°-75°(1°Step)
Mode Instant Definite Inverse, Very Inverse, Extremely Inverse
Current - (0.20-2.40) × In (0.01A Step)
DOCR
Voltage - (0.03-1.45) × Vn (0.1V Step)
(67)
Time - 0.05-10.00sec (0.01sec Step) 0.05-10.00 Tap (Time Delay) (0.01 Step)
Angle - Ref. Angle: 0°-359°(1°Step), Op. Angle: ±30°
-90°(1°Step)
Mode Instant Definite Inverse, Very Inverse, Extremely Inverse
Current - (0.05-10.00) × In (0.01A Step)
DOCGR
Voltage - (0.1-0.5) × Vn (0.1V Step)
(67N)
Time - 0.05-10.00sec (0.01sec Step) 0.05-10.0 Tap (Time Delay) (0.01 Step)
Angle - Ref. Angle: 0°-359°(1°Step), Op. Angle: ±10°
-170°(1°Step)
※ - In: Rating Current, Vn: Rating Voltage
- Example HiMAP Setting; In: 5A, OCR: (1-18)×In → 5-90A

M-8
HiMAP

Connection Diagram

HiMAP-FI(3CT, 3PT)

R S T

R1 21
PT / GPT
9 22
10 DISPLAY R2
11 23
12
13 24 Program-
14 mable
R3 25
Relay
CPU 26 Output
15
R4 27
16

28
CB GPT
3rd R5 29

1 30
2 R6
31 Local/
3 Remote
4 50 32
CB On

5 R7 33
CT 6 51 Local/
Remote
34 CB Off
7
8
50G
35
NA
51G 36

37
27 CCS
38
47P Option
39
TCS
R S T DC 24 V
47N 40

1 59 41
2 42
50
3
52a 64 43
44 NA
4
5 52b
51 67G 45
46
CT 6
52
67 47
Remote 48
Vp
67N 60
Vn
7 53 61
DI1
ZCT 8 62 RS485
(Scada)
63
54
DI2 64
65
When using ZCT 59 KEYBOARD Vp
66
(SGR) Vn RS485
67 (HIMIX)
68 Option

P
Control
N
Power

FG

M-9
HiMAP Hyundai Intelligent Measuring & Protection Device

Connection Diagram

HiMAP-FI(2CT, 2PT)

R S T

R1 21
PT × 2
9 22
10 DISPLAY R2
11 23
12
13 24 Program-
14 mable
R3 25
Relay
CPU 26 Output
15
R4 27
16

28
CB
R5 29

1 30
2 R6 31 Local/
3 Remote
CB On
4 50 32
5 R7 33
CT 6 51 Local/
Remote
CB Off
7 34
8
50G
35
NA
51G 36

37
27 CCS

ZCT 38
47P Option
39
TCS
R S T DC 24 V 47N 40

59 41
42
50
52a 64 43
44 NA

52b
51 67G 45
46
47
52
Remote 48
Vp
60
Vn
53 61
DI1
62 RS485
(Scada)
63
54
DI2 64
65
59 KEYBOARD Vp
66
Vn RS485
67 (HIMIX)
68 Option

P
Control
N
Power

FG

M - 10
HiMAP

Terminal Block Pin Specification

HiMAP-FI Type

Control Power Terminal Digital Output Analog Input


P (+) 41 21 R1 22 1 Ia 2
N (-) 42 23 R2 24 3 Ib 4
FG 43 25 R3 26 5 Ic 6
44 27 R4 28 7 Io 8
Communication Terminal N.A.
45 29 R5 30 9 Va 10
60 Vp 46 31 R6(CB On) 32 11 Vb 12
61 Vn 47 33 R7(CB Off) 34 13 Vc 14
62 48 35 N.A. 36 15 Vo 16
63 Vp 37 CCS 38 17 N.A. 18
64 Vn Digital Input 39 TCS 40 19 N.A. 20
65 50 52a
51 52b Terminal No. Description Application
HIMIX Communication 52 Remote 50 CB On Status 52a Fixed
Terminal 51 CB Off Status 52b Fixed
53 D/I 1
66 Vp 52 Remote Input Fixed
54 D/I 2
67 Vn 53 General DI Variable
55
68 N.A. 54 General DI Variable
56
N.A. 21-22 R1
57 23-24 R2
58 Programmable
25-26 R3
Relay Output
59 Common(+24V) 27-28 R4
29-30 R5
31-32 R6(CB On) Fixed
33-34 R7(CB Off) Fixed
35-36 N.A. N.A.
37-38 TCS Fixed
39-40 TCS Fixed

M - 11
HiMAP Hyundai Intelligent Measuring & Protection Device

Characteristic Curve

OCR & OCGR

Inverse | OP LEVEL 0.05-10.0 Very Inverse | OP LEVEL 0.05-10.0

0.01 0.01

DOCR

Extremely Inverse | OP LEVEL 0.05-10.0 DOCR

Op. Current Ref. Volt


Ia Vbc
Ib Vca
0.01
Ic Vab

M - 12
HiMAP

OVR OVGR

Inverse | OP LEVEL 0.05-10.0 Very Inverse | OP LEVEL 0.05-10.0

0.01 0.01

DGR / SGR / DOCGR

DGR SGR

DOCGR

M - 13
HiMAP Hyundai Intelligent Measuring & Protection Device

Order Form

A. Type Selection of HiMAP Please check mark(⋏) into the type required.

HiMAP – ❶ – ❷ ❸ – ❹ (Option)

❶ ❷ ❸ ❹ (option) 4)
Relay Type Ground Fault Type Communication TCS Function
FI Feeder/Incoming C OCGR C RS-485 HDLC T Required
M Motor D DGR / DOCGR X No System Interface X Not Apply
87M Big Motor S SGR M MODBUS-RTU
T Transformer
SY Synchro check
※ Type of 87M (Protection for big motor): ( ) self-balancing type / ( ) differential type

B. System Specification Required Please check mark(⋏) into a parenthesis.


1) Measuring Current (CT) Inputs for OCR: ( ) 5A / ( ) 1A
2) Measuring Zero Phase Current (ZCT) Inputs for GFR: ( ) 5A / ( ) 1A / ( ) 1.5 mA
3) Frequency 3): ( ) 50Hz / ( ) 60Hz
4) Measuring Voltage (line to ground) inputs: ( ) 110V / ( ) 190V / Others ( V)

C. Ground Fault Function Selection


Table 1 (FI)
Item OCR(50/51) OCGR(50/51G) DGR(67G) / SGR(67G) OVR(59) UVR(27) OVGR(64) PSR(47P/47N)
DOCGR(67N)
C ● ● ● ● ● ●
D ● ● ● ● ● ●
S ● ● ● ● ● ●

Table 2 (M)
Item MPR OCGR(50/51G) DGR(67G) / SGR(67G)
DOCGR(67N)
C ● ●
D ● ●
S ● ●

Table 3 (87M)
Item 87M MPR OCGR(50/51G) DGR(67G) / SGR(67G)
DOCGR(67N)
C ● ● ●
D ● ● ●
S ● ● ●

Table 4 (T)
Item DFR OCR P(50/51P) 1) OCR S(50/51S) 2) OCGR(50/51G) DGR(67G) / SGR(67G)
DOCGR(67N)
C ● ● ● ●
D ● ● ● ●
S ● ● ● ●
※ 1) OCR P is transformer primary OCR
2) OCR S is transformer secondary OCR
3) The control voltage of HiMAP is only allow AC / DC 95 - 250V, 50 / 60Hz as a free voltage
4) TCS(Trip Coil Supervision): Circuit breaker coil disconnection check. (option)

Note
Ground fault function shell be selected in accordance with the system ground method.
- OCGR (50G/51G): Effective ground system
- DGR (67G): Resister ground system
- SGR (67G): Floated ground system

M - 14
HiMAP

View & Dimension

Weight 4.3Kg

139
186

Top View Panel Cut-out Dimension


156

33 218

206 251

Front View Side View


138

185

Rear View

M - 15
HiCAM-II Hyundai Intelligent Communication &
Measuring Device

Characteristics C-2
Display C-2
Connection Diagram C-4
Terminal Block Pin Specification C-5
View & Dimension C-6
HiCAM-II Hyundai Intelligent Communication & Measuring Device

Characteristics

Accuracy Compact Size and Display

▶ ±0.2~1.0% at rating ▶ Various indicator and measuring display


▶ Size : 202.5 (W) × 156 (H) × 189 (D)

Voltage / Current Input


Power Management System Connection
▶ CT : 0.1~10 A
▶ PT : 10~380 V ▶ RS485 HD-Bus
▶ Modbus protocol by communication control device
(HICM Series)
Various Measuring

▶ 15 measuring points

Display

Front View

Display Window
Communication Address

Current, Active Power Select Key


% Display

D/I Status LED D/O Status LED

Navigation Key
CB Control Switch/LED

Remote Key

C- 2
HiCAM-II

I / O Point

Item Point Remark


AI Voltage 4 Default
Input AI Current 4 Default
DI 12 Default(41~55)
Default(31~40)
37, 38(D04) : Remote CB On
Output DO 5
39, 40(D05) : Remote CB Off
31~36(D01~D03) use current demand output.

Specification

Item Specification
Current 1 A or 5 A(0.1 A~10 A), Burden : Below 0.1 VA / Phase
Rating Voltage 110 V or 190 V(10 V~380 V), Burden : Below 0.3 VA / Phase
Frequency 50 Hz or 60 Hz
Accuracy Measuring ±0.2 %
Operation Guarantee -10 ℃ ~ 55 ℃
Temperature
Restoration Guarantee -25 ℃ ~ 70 ℃
Circuit-Ground 10 ㏁
Insulation
Between Circuits 5㏁
Resistance
Between Contacts 5㏁
Voltage Power Frequency AC 60 Hz 2,000V/1 Min
Withstand Lightning Impulse 1.2/50 ㎲ 5 kV
Current Circuit Rating Current×3 : 3 hours / Rating Current×20 : 1 sec
Overland
Voltage Circuit Rating Voltage×3 : 3 hours
Withstand
Control Power Rating Voltage×1.3 : 3 hours
Control Power AC 85 ~ 264 V (50 / 60 Hz), DC 90 ~ 120 V
Power Consumption 18 VA, AC 220 V
Communication Type RS–485 / Multi Drop
Protocol HD-BUS / Modbus
Standards KEMC1110, IEC1036
Size 202.5 (W)×156 (H)×189 (D)
Weight 1.5 Kg

Measuring

Measuring Display Accuracy Remark


Voltage 0~999999 V ±0.2% Line to Line Voltage
Current 0~999999 A ±0.2% Phase Current
Real Power 0~99999999 kW ±0.2%
Reactive Power 0~99999999 kvar ±0.5%
Apparent Power 0~99999999 kVA ±1.0%
Accumulated Real Energy 0~99999999 kWh ±1.0%
Accumulated Reactive Energy 0~99999999 kvarh ±1.0%
Power Factor -1.0~1.0 PF ±0.5%
Frequency 45~65 Hz ±0.01 Hz
Reverse Real Power 0~999999 kW ±0.5% (-) Sign
Reverse 0~999999 kWh ±1.0% (-) Sign

C- 3
HiCAM-II Hyundai Intelligent Communication & Measuring Device

Connection Diagram

3P 4W 3PT_3CT 3P 3W 2PT_2CT

RS T N 45/50/55 41 42 43 44 46 47 48 49 51 52 53 54 RS T 45/50/55 41 42 43 44 46 47 48 49 51 52 53 54

PT/GPT 9 PT 9
10 10
11 11
12 DI 12 DI
13 13
14 14
Vp Vp
66 66
Vn 67 Vn 67
15 15
16 68 16 68
69 69
GPT 70 70
AI COMM. AI COMM.
1 1
2 2
3 3
L L
4 4
N N
5 5
DO FG DO FG
CT 6 CT 6
AD/DC AD/DC
7 95~250V 7 95~250V
8 R5 R4 R3 R2 R1 50/60Hz 8 R5 R4 R3 R2 R1 50/60Hz

40 39 38 37 36 35 34 33 32 31 40 39 38 37 36 35 34 33 32 31

Remote CB On : 37, 38 Terminal Remote CB On : 37, 38 Terminal


Remote CB Off : 39, 40 Terminal Remote CB Off : 39, 40 Terminal

3P 3W 3PT_3CT 3P 3W 2PT_3CT

RS T 45/50/55 41 42 43 44 46 47 48 49 51 52 53 54 RS T 45/50/55 41 42 43 44 46 47 48 49 51 52 53 54

PT 9 PT 9
10 10
11 11
12 DI 12 DI
13 13
14 14
Vp Vp
66 66
Vn 67 Vn 67
15 15
16 68 16 68
69 69
70 70
AI COMM. AI COMM.
1 1
2 2
3 3
L L
4 4
N N
5 5
DO FG DO FG
CT 6 CT 6
AD/DC AD/DC
7 95~250V 7 95~250V
8 R5 R4 R3 R2 R1 50/60Hz 8 R5 R4 R3 R2 R1 50/60Hz

40 39 38 37 36 35 34 33 32 31 40 39 38 37 36 35 34 33 32 31

Remote CB On : 37, 38 Terminal Remote CB On : 37, 38 Terminal


Remote CB Off : 39, 40 Terminal Remote CB Off : 39, 40 Terminal

C- 4
HiCAM-II

Terminal Block Pin Specification

Control Power Terminal Digital Input Digital Output Terminal No. Description Application
L (+) 41 52a 31 R1(+) 31~32 R1
N (-) 42 52b 32 R1(-) 33~34 R2 Variable
FG FG 43 Remote 33 R2(+) 35~36 R3
44 DI 1 34 R2(-) 37~38 R4(Remote On) Fixed
Terminal 45 Common(+24V) 35 R3(+) 39~40 R5(Remote Off) Fixed
56 46 DI 2 36 R3(-) 41 CB On Status 52a
57 47 DI 3 37 R4(CB On) 42 CB Off Status 52b Fixed
58 48 DI 4 38 R4(CB On) 43 Remote Input
59 49 DI 5 39 R5(CB Off) 44 General DI Variable
60 50 Common(+24V) 40 R5(CB Off) 45 Common HiCAM Self Power +24V
N.A.
61 51 DI 6 46 General DI
62 52 DI 7 Analog Input 47 General DI
63 Variable
53 DI 8 1 Ia 2 48 General DI
64 54 DI 9 3 Ib 4 49 General DI
65 55 Common(+24V) 5 Ic 6 50 Common HiCAM Self Power +24V
Io 51 General DI
7 8
Communication 52 General DI
9 Vab 10
Terminal Variable
Vbc 53 General DI
Vp 11 12
66
Vca 54 General DI
Vn 13 14
67
Vo 55 Common HiCAM Self Power +24V
Vp 15 16
68
Vn 17 N.A. 18
69
N.A. 19 N.A. 20
70

C- 5
HiCAM-II Hyundai Intelligent Communication & Measuring Device

View & Dimension

Weight 1.5Kg

186

139

Panel Cut-out Dimension


Top View
189

33 141 15
206
156

Front View Side View

185
138

Rear View

C- 6
HHIS-WC-SE-B11-04, 2009.12 Designed by MERMONT

Head Office 1, Jeonha-dong, Dong-gu, Ulsan, Korea


Tel: 82-52-202-8101~8 Fax: 82-52-202-8100
Seoul 140-2, Gye-dong, Jongno-gu, Seoul, Korea
(Sales & Marketing) Tel: 82-2-746-7579, 7523 Fax: 82-2-746-7648
Orlando 3452 Lake Lynda Drive, Suite 170, Orlando, Florida 32817, U.S.A.
Tel: 1-407-249-7350 Fax: 1-407-275-4940
New Jersey 300 Sylvan Avenue, Englewood Cliffs, NJ 07632, U.S.A.
Tel: 1-201-816-0286 Fax: 1-201-816-4083
London 2nd Floor, The Triangle, 5-17 Hammersmith Grove, London, W6 0LG, UK
Tel: 44-20-8741-0501 Fax: 44-20-8741-5620
Tokyo 8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo, 100-0006, Japan
Tel: 81-3-3212-2076, 3215-7159 Fax: 81-3-3211-2093
Osaka I-Room 5th Fl. Nagahori-Plaza Bldg. 2-4-8, Minami Senba, Chuo-Ku, Osaka, 542-0081, Japan
Tel: 81-6-6261-5766, 5767 Fax: 81-6-6261-5818
Dubai Level 2, Unit 205, Emaar Square-Bldg.4 Sheikh Zayed Road, P.O.Box 252458, Dubai, U.A.E.
Tel: 971-4-425-7995 Fax: 971-4-425-7996
Sofia 1271, Sofia 41, Rojen Blvd., Bulgaria
Tel: 359-2-803-3200 Fax: 359-2-803-3203
Yangzhong No. 9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, China
Tel: 86-511-8842-0666, 0212 Fax: 86-511-8842-0668, 0231

S-ar putea să vă placă și