Type A Comment

Location Observation Remark

Raft Foundation No top reinforcement Consultant to review


between wall

Wall Wall reinforced with BRC A8 To replace all BRC A8


(3.95 kg/m^2) with BRC B6
(3.73 kg/m^2)

Slab

FS 2 215mm thk reinforced with To reduce thickness to


A10 (B) 175mm thick reinforced with
A9 (B)

FS7 165mm thk reinforced with A8 (B) To reduce thickness to 125mm


thick reinforced with A7 (B)

*To add additional 1T12 (T&B) for


crack control
*Additional 3T16 (B) as hidden
strip beam

FS 3 215 mm thk reinforced with To reduce thickness to 115mm


A10 (B) thick reinforced with A7

*To add additional 1T12 (T & B)


for crack control
*Additional 2T12 (B) as hidden
strip beam

FS 5 215mm thk reinforced with A10(B) To reduce to 115mm thick


reinforced with BRC A7 (B)

Cantilever Slab Insufficient Anchorage Length To ensure all top rebars for
cantilever slab is anchored 40 dia.
beyond the supporting beam

Note.

* Only structural element review has been carried out. Structural integrity and robustness is the sole responsibility of the
project consultant

* The above view represent an alternative design proposal within the confine of normal design parameter. The Client
is to seek project consultant's approval prior to the implementation of each recommendation.