Power factor correction in photovoltaic plants If there is not a photovoltaic plant (PPV = 0):
Annex E
A photovoltaic plant usually supplies only active power, 0
tgϕ 2 = 0.5⋅ 1- = 0.5 cosϕ 2 = 0.9 [E.5]
therefore it is however necessary to draw from the net- P
work the reactive power required for the loads of the
user plant. that is why the power factor controller is set at 0.9 as
If a photovoltaic plant is added to an already existing usually prescribed.
electrical installation, the reactive power drawn by the
network remains the same, whereas the active power In the presence of a photovoltaic plant, active power is
decreases by the quantity supplied by the photovoltaic generated and the power factor regulator shall be set
generator as shown in the following figure: at a value higher than 0.9. In fact, for example, if the
Figure E.1
generated power is half the power drawn by the loads
(PPV = 0.5 · P ), it results:
PPV PN , QN
PV NETWORK 0.5⋅ P
tgϕ 2 = 0.5⋅ 1- = 0.25 cosϕ 2 = 0.97 [E.6]
P
Qc P = PPV + PN In the limit case, when the photovoltaic plant supplies all
Q = Qc + QN the active power required by the loads (PPV=P), the power
factor controller shall be set at a value equal to:
P, Q P
tgϕ 2 = 0.5⋅ 1- =0 cosϕ 2 = 1 [E.7]
P
LOADS
and consequently the capacitor bank shall deliver all the
reactive power required by the loads.
From the point of view of the network, the electrical
installation as a whole (photovoltaic generator and user
plant) shall have, not to incur penalties, an average power
factor equal to 0.9 from which it results:
QN
cos ϕ N ≥ 0.9 tgϕ N ≤ 0.5 ≤ 0.5 [E.1]
PN
from which:
[E.3]
P
Q C ≥ Q - 0.5⋅ ( P - PPV ) = P ⋅ tgϕ1 - 0.5⋅ 1- PV =
P
P ⋅ ( tgϕ1 - tgϕ 2 )
where:
PPV
tgϕ 2 = 0.5⋅ 1- [E.4]
P
Annex F
Harmonics in three-phase systems with Take into consideration the presence in the three-phase
neutral currents of the 3rd harmonic only, in addition to the
Annex F
IL
I N =2.64 ⋅ I1 =2.64 ⋅ =1.98⋅ I L ≈ 200%I L [F.6]
IN 1.33
LOAD LOAD LOAD
As it can be noticed, in the neutral, a current which is
even twice the phase current may flow with the conse-
quent repercussion in the size of the cross section of the
conductor and in the settings of the overload protec-
tions. The ratio between the current in the neutral and in
the phase would increase if also harmonics multiple of
the 3rd one were present. Instead, the assumption that
other harmonics not multiple of the 3rd one are absent
represents a pejorative situation: their presence would
reduce the ratio previously given since such harmonics
would not flow through the neutral being balanced sym-
metrical sets.
Annex F
Figure F.2
Annex F:
• I5 = 0.55 · I1
E1
IL1 • I7 = 0.07 · I1
E2 IL2
the ratio between the neutral current and the phase cur-
rent becomes:
E3 IL3 = 0
I N = I1⋅ 1+ (2 ⋅ 0.88)2 + 0.55 2 + 0.07 2 = 2.1⋅ I1 [F.11]
IN [F.12]
2.1
IN = ⋅ I L =1.46⋅ I L [F.13]
1.44
At first, take into consideration the presence of the 3rd As it can be noticed comparing the formula [F.13] with
harmonic only in addition to the fundamental one. Com- [F.10], also in this case the presence of harmonics not
pared with the previous case, now the current flowing in multiple of the 3rd reduces the ratio between the neutral
the neutral is the square root of the sum of the square of current and the phase current.
the fundamental component plus the square of the sum
of the two 3rd harmonics, that is:
[F.8]
[F.9]
I L1 = I L 2 = I L = I12 + I 32 = I12 ⋅ (1+ 0.88 2 ) =1.33 ⋅ I1
2.02
IN = ⋅ I L =1.52⋅ I L [F.10]
1.33
Glossary
I r.m.s. value of the total current
Glossary
QT5
ABB circuit-breakers for direct current
applications
QT1 QT6
Low voltage selectivity with ABB circuit-breakers Arc-proof low voltage switchgear and controlgear
assemblies
QT2 QT7
MV/LV trasformer substations: theory and exam- Three-phase asynchronous motors
ples of short-circuit calculation Generalities and ABB proposals for the coordina-
tion of protective devices
QT3 QT8
Distribution systems and protection against indi- Power factor correction and harmonic filtering in
rect contact and earth fault electrical plants