Heating Load Calculation

Floor Ground Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Account
Outdoor 50.00 44.86

Conduction U Net Area(ft) dT (F)


Outer walls 0.37 351.33 23.00
Glass 1.01
Brick 0.42 171.72 11.50
Partition
Glass 1.01
Roof 0.47

Door 0.38 28.92 23.00


Coefficient, Fp Exposed
Floor (Btu/h ft) perimeter, P(ft) dT (F)
0.68 50.36 23.00

Ventilation factor n cfm dT


Qs 1.10 6.00 15.00 23.00
Ql 0.68 6.00 15.00
Total Heating load
TOR
d Calculation

RH(%) w(gr/lb)

50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2973.66
0.00
823.48
0.00
0.00
252.76

Q=Fp*P*dT
787.63
Qs=f*n*cfm*dT
dw Ql=f*n*cfm*dw
2277.00
24.72 1513.05
al Heating load 8627.58
TOR 0.72
Heating Load Calculation

Floor Ground Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Cafeteria Dining Space
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 1175.26 23.00
Glass 1.01 466.45 23.00
Brick 0.42 265.79 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 26.59 11.50
Coefficient, Fp Exposed
Floor (Btu/h ft) perimeter, P(ft) dT (F)
0.68 170.79 23.00

Ventilation factor n cfm dT


Qs 1.10 20.00 15.00 23.00
Ql 0.68 20.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
9947.40
10835.63
1274.60
0.00
0.00
116.20

Q=Fp*P*dT
2671.11
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
7590.00
24.72 5043.49
al Heating load 37478.43
TOR 3.12
Heating Load Calculation

Floor Ground Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Conference Hall
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 397.94 23.00
Glass 1.01 23.00
Brick 0.42 677.41 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 154.61 11.50
Coefficient, Fp Exposed
Floor (Btu/h ft) perimeter, P(ft) dT (F)
0.68 151.88 23.00

Ventilation factor n cfm dT


Qs 1.10 105.00 15.00 23.00
Ql 0.68 105.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
3368.16
0.00
3248.52
0.00
0.00
675.65

Q=Fp*P*dT
2375.40
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
39847.50
24.72 26478.33
al Heating load 75993.57
TOR 6.33
Heating Load Calculation

Floor Ground Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Control Room
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 23.00
Glass 1.01 23.00
Brick 0.42 392.32 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 22.09 11.50
Coefficient, Fp Exposed
Floor (Btu/h ft) perimeter, P(ft) dT (F)
0.68 61.46 23.00

Ventilation factor n cfm dT


Qs 1.10 2.00 15.00 23.00
Ql 0.68 2.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
0.00
0.00
1881.37
0.00
0.00
96.53

Q=Fp*P*dT
961.23
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
759.00
24.72 504.35
al Heating load 4202.49
TOR 0.35
Heating Load Calculation

Floor Ground Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room General Enquiry
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 397.94 23.00
Glass 1.01 142.63 23.00
Brick 0.42 678.00 11.50
Partition
Glass 1.01 54.89 11.50
Roof 0.47
Door 0.38 11.50
Coefficient, Fp Exposed
Floor (Btu/h ft) perimeter, P(ft) dT (F)
0.68 92.97 23.00

Ventilation factor n cfm dT


Qs 1.10 4.00 15.00 23.00
Ql 0.68 4.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
3368.16
3313.29
3251.35
637.55
0.00
0.00

Q=Fp*P*dT
1454.05
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
1518.00
24.72 1008.70
al Heating load 14551.10
TOR 1.21
Heating Load Calculation

Floor Ground Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Office Metal Workshop
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 146.33 23.00
Glass 1.01 279.86 23.00
Brick 0.42 401.40 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 25.11 11.50
Coefficient, Fp Exposed
Floor (Btu/h ft) perimeter, P(ft) dT (F)
0.68 62.49 23.00

Ventilation factor n cfm dT


Qs 1.10 7.00 15.00 23.00
Ql 0.68 7.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
1238.54
6501.15
1924.91
0.00
0.00
109.73

Q=Fp*P*dT
977.34
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
2656.50
24.72 1765.22
al Heating load 15173.40
TOR 1.26
Heating Load Calculation

Floor Ground Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Office wood workshop
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 131.06 23.00
Glass 1.01 84.22 23.00
Brick 0.42 424.82 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 25.11 11.50
Coefficient, Fp Exposed
Floor (Btu/h ft) perimeter, P(ft) dT (F)
0.68 49.34 23.00

Ventilation factor n cfm dT


Qs 1.10 0.00 15.00 23.00
Ql 0.68 0.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
1109.29
1956.43
2037.22
0.00
0.00
109.73

Q=Fp*P*dT
771.68
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
0.00
24.72 0.00
al Heating load 5984.36
TOR 0.50
Heating Load Calculation

Floor Ground Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Seminar Hall
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 246.18 23.00
Glass 1.01 23.00
Brick 0.42 544.87 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 110.43 11.50
Coefficient, Fp Exposed
Floor (Btu/h ft) perimeter, P(ft) dT (F)
0.68 132.05 23.00

Ventilation factor n cfm dT


Qs 1.10 30.00 15.00 23.00
Ql 0.68 30.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2083.67
0.00
2612.92
0.00
0.00
482.58

Q=Fp*P*dT
2065.26
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
11385.00
24.72 7565.24
al Heating load 26194.67
TOR 2.18
Heating Load Calculation

Floor Ground Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Staff Room
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 356.84 23.00
Glass 1.01 296.53 23.00
Brick 0.42 401.89 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 26.59 11.50
Coefficient, Fp Exposed
Floor (Btu/h ft) perimeter, P(ft) dT (F)
0.68 96.42 23.00

Ventilation factor n cfm dT


Qs 1.10 19.00 15.00 23.00
Ql 0.68 19.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
3020.29
6888.39
1927.26
0.00
0.00
116.20

Q=Fp*P*dT
1508.01
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
7210.50
24.72 4791.32
al Heating load 25461.97
TOR 2.12
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Cafeteria Dining space
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 1426.10 23.00
Glass 1.01 677.60 23.00
Brick 0.42 247.70 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
12070.51
15740.65
1187.85
0.00
0.00
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 44790.87
TOR 3.73
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Deputy Director's Room
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 100.14 23.00
Glass 1.01 95.33 23.00
Brick 0.42 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 6.00 15.00 23.00
Ql 0.68 6.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
847.58
2214.52
0.00
0.00
0.00
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
2277.00
24.72 1513.05
al Heating load 6852.15
TOR 0.57
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Director's Room
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 221.04 23.00
Glass 1.01 233.63 23.00
Brick 0.42 224.75 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 5.00 15.00 23.00
Ql 0.68 5.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
1870.88
5427.22
1077.79
0.00
0.00
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
1897.50
24.72 1260.87
al Heating load 11534.27
TOR 0.96
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Lecture Room 1
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 265.65 23.00
Glass 1.01 76.64 23.00
Brick 0.42 174.14 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.47 53.18 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2248.46
1780.35
835.09
0.00
0.00
287.44
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 20943.20
TOR 1.75
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Lecture Room 2
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 247.41 23.00
Glass 1.01 94.87 23.00
Brick 0.42 174.15 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.47 53.18 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2094.08
2203.83
835.14
0.00
0.00
287.44
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 21212.35
TOR 1.77
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Lecture Room 3
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 194.82 23.00
Glass 1.01 143.81 23.00
Brick 0.42 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.47 53.18 11.50

Ventilation factor n cfm dT


Qs 1.10 38.00 15.00 23.00
Ql 0.68 38.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
1648.96
3340.71
0.00
0.00
0.00
287.44
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
14421.00
24.72 9582.63
al Heating load 29280.74
TOR 2.44
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Lecture Room 4
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 287.18 23.00
Glass 1.01 71.90 23.00
Brick 0.42 174.15 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.47 53.18 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2430.69
1670.24
835.14
0.00
0.00
287.44
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 21015.37
TOR 1.75
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Lecture Room 5
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 290.06 23.00
Glass 1.01 69.03 23.00
Brick 0.42 174.15 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 53.18 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2455.07
1603.57
835.14
0.00
0.00
232.40
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 20918.03
TOR 1.74
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Leisure Room North
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 302.29 23.00
Glass 1.01 147.21 23.00
Brick 0.42 234.23 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 4.00 15.00 23.00
Ql 0.68 4.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2558.58
3419.69
1123.25
0.00
0.00
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
1518.00
24.72 1008.70
al Heating load 9628.22
TOR 0.80
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Leisure Room South
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 89.34 23.00
Glass 1.01 145.31 23.00
Brick 0.42 470.17 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 4.00 15.00 23.00
Ql 0.68 4.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
756.17
3375.55
2254.70
0.00
0.00
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
1518.00
24.72 1008.70
al Heating load 8913.12
TOR 0.74
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Maker Room North
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 2000.49 23.00
Glass 1.01 907.05 23.00
Brick 0.42 213.40 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 25.11 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
16932.15
21070.77
1023.36
0.00
0.00
109.73
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 54927.87
TOR 4.58
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Maker Room South
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 642.70 23.00
Glass 1.01 700.60 23.00
Brick 0.42 198.90 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 24.99 11.50

Ventilation factor n cfm dT


Qs 1.10 13.00 15.00 23.00
Ql 0.68 13.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
5439.81
16274.94
953.82
0.00
0.00
109.21
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
4933.50
24.72 3278.27
al Heating load 30989.55
TOR 2.58
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Office
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 265.76 23.00
Glass 1.01 66.23 23.00
Brick 0.42 183.52 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 26.59 11.50

Ventilation factor n cfm dT


Qs 1.10 5.00 15.00 23.00
Ql 0.68 5.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2249.39
1538.52
880.07
0.00
0.00
116.20
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
1897.50
24.72 1260.87
al Heating load 7942.56
TOR 0.66
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Auditorium Hall
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 1214.17 23.00
Glass 1.01 23.00
Brick 0.42 3113.49 11.50
Partition
Glass 1.01 11.50
Roof 0.47 5026.00 23.00
Door 0.38 344.74 11.50

Ventilation factor n cfm dT


Qs 1.10 250.00 15.00 23.00
Ql 0.68 250.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
10276.73
0.00
14930.74
0.00
54793.45
1506.51
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
94875.00
24.72 63043.65
al Heating load 239426.09
TOR 19.95
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Training Hall
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 447.17 23.00
Glass 1.01 484.40 23.00
Brick 0.42 501.46 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.47 25.11 11.50

Ventilation factor n cfm dT


Qs 1.10 17.00 15.00 23.00
Ql 0.68 17.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
3784.85
11252.61
2404.75
0.00
0.00
135.72
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
6451.50
24.72 4286.97
al Heating load 28316.40
TOR 2.36
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Cafeteria Dining Space
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 1014.01 23.00
Glass 1.01 438.48 23.00
Brick 0.42 654.45 11.50
Partition
Glass 1.01 11.50
Roof 0.47 1536.57 23.00
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
8582.58
10185.89
3138.41
0.00
16751.69
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 54450.44
TOR 4.54
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Leisure Room North
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 302.30 23.00
Glass 1.01 147.21 23.00
Brick 0.42 234.23 11.50
Partition
Glass 1.01 11.50
Roof 0.47 11.50
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 4.00 15.00 23.00
Ql 0.68 4.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2558.67
3419.69
1123.25
0.00
0.00
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
1518.00
24.72 1008.70
al Heating load 9628.30
TOR 0.80
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Maker Room North
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 2398.26 23.00
Glass 1.01 544.03 23.00
Brick 0.42 215.33 11.50
Partition
Glass 1.01 11.50
Roof 0.47 11.50
Door 0.38 23.62 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
20298.87
12637.82
1032.62
0.00
0.00
103.22
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 49864.39
TOR 4.16
Heating Load Calculation

Floor Second Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Maker Room S
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 1180.27 23.00
Glass 1.01 699.17 23.00
Brick 0.42 201.34 11.50
Partition
Glass 1.01 11.50
Roof 0.47 2106.28 23.00
Door 0.38 23.62 11.50

Ventilation factor n cfm dT


Qs 1.10 15.00 15.00 23.00
Ql 0.68 15.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
9989.81
16241.72
965.53
0.00
22962.66
103.22
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
5692.50
24.72 3782.62
al Heating load 59738.05
TOR 4.98
Heating Load Calculation

Floor Second Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Leisure Room South
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 110.72 23.00
Glass 1.01 123.93 23.00
Brick 0.42 480.07 11.50
Partition
Glass 1.01 11.50
Roof 0.47 300.85 23.00
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 3.00 15.00 23.00
Ql 0.68 3.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
937.13
2878.89
2302.18
0.00
3279.87
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
1138.50
24.72 756.52
al Heating load 11293.09
TOR 0.94
Heating Load Calculation

Floor Third Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Maker Room
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 1606.29 23.00
Glass 1.01 779.03 23.00
Brick 0.42 473.66 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 23.63 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
13595.64
18096.87
2271.44
0.00
0.00
103.26
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 49859.07
TOR 4.15
Heating Load Calculation

Floor Third Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Leisure Room
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 267.26 23.00
Glass 1.01 182.24 23.00
Brick 0.42 234.23 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 4.00 15.00 23.00
Ql 0.68 4.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2262.09
4233.44
1123.25
0.00
0.00
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
1518.00
24.72 1008.70
al Heating load 10145.47
TOR 0.85
Heating Load Calculation

Floor Fourth Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Maker Room
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 1606.29 23.00
Glass 1.01 779.03 23.00
Brick 0.42 473.66 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 23.63 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
13595.64
18096.87
2271.44
0.00
0.00
103.26
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 49859.07
TOR 4.15
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Leisure Room
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 267.26 23.00
Glass 1.01 182.24 23.00
Brick 0.42 234.23 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 4.00 15.00 23.00
Ql 0.68 4.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2262.09
4233.44
1123.25
0.00
0.00
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
1518.00
24.72 1008.70
al Heating load 10145.47
TOR 0.85
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Maker Room
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 1606.29 23.00
Glass 1.01 779.03 23.00
Brick 0.42 473.66 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 23.63 11.50

Ventilation factor n cfm dT


Qs 1.10 25.00 15.00 23.00
Ql 0.68 25.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
13595.64
18096.87
2271.44
0.00
0.00
103.26
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
9487.50
24.72 6304.37
al Heating load 49859.07
TOR 4.15
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Leisure Room
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 267.26 23.00
Glass 1.01 182.24 23.00
Brick 0.42 234.23 11.50
Partition
Glass 1.01 11.50
Roof 0.47
Door 0.38 11.50

Ventilation factor n cfm dT


Qs 1.10 4.00 15.00 23.00
Ql 0.68 4.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
2262.09
4233.44
1123.25
0.00
0.00
0.00
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
1518.00
24.72 1008.70
al Heating load 10145.47
TOR 0.85
Heating Load Calculation

Floor First Condition DBT(F) WBT(F)


Indoor 73.00 60.89
Room Researcher's Library
Outdoor 50.00 44.86

Conduction U Net Area(sq.ft) dT (F)


Outer walls 0.37 1283.48 23.00
Glass 1.01 940.91 23.00
Brick 0.42 935.78 11.50
Partition
Glass 1.01 11.50
Roof 0.47 2563.32 23.00
Door 0.38 22.22 11.50

Ventilation factor n cfm dT


Qs 1.10 45.00 15.00 23.00
Ql 0.68 45.00 15.00
Total Heating load
TOR
Calculation

RH(%) w(gr/lb)
50.00 60.64
67.25 35.92

Q= U*A*dT
(BTU/hr)
10863.37
21857.34
4487.53
0.00
27945.31
97.10
Qs=f*n*cfm*dT,
dw Ql=f*n*cfm*dw
17077.50
24.72 11347.86
al Heating load 93676.02
TOR 7.81
Floor Area No. of Heating Load
Floor Room
(sq.ft) People Calculation(TOR)
General Enquiry 327.87 4 1.21
Conference hall 1349.69 105 6.33
Control room 209.25 2 0.35
Seminar hall 1024.40 30 2.18
Office (Wood Workshop) 142.84 5 0.50
Ground
Account 157.48 6 0.72
Staff room 543.58 19 2.12
Cafeteria Dining Space 1357.44 20 3.12
Office( Metal Workshop) 248.97 7 1.26
Total 5361.50 17.81

Training Hall 629.26 17 2.36


Office 133.26 5 0.66
Director's Room 277.92 5 0.96
Deputy Director's Room 217.65 6 0.57
Cafeteria Dining Space 1935.78 25 3.73
Leisure Room(north) 277.60 4 0.80
Maker Space (north) 2883.54 25 4.58
Lecture Room1 409.89 25 1.75
First
Lecture Room 2 409.89 25 1.77
Lecture Room 3 489.44 38 2.44
Lecture Room 4 432.17 25 1.75
Lecture Room 5 432.17 25 1.74
Maker Space South 1102.12 13 2.58
Leisure Room (south) 303.97 4 0.74
Auditorium 5025.14 250 19.95
Total 14959.80 46.39

Cafeteria Dining Space 1536.66 25 4.54


Maker Room North 2883.54 25 4.16
Leisure Room(north) 277.60 4 0.80
Second
Maker Room South 2106.93 15 4.98
Leisure Room (south) 300.85 3 0.94
Total 7105.58 15.41

Leisure Room 277.60 4 0.85


Third Maker Space 2883.54 25 4.15
Total 3161.15 5.00
Leisure Room 277.60 4 0.85
Fourth Maker Space 2883.54 25 4.15
Total 3161.15 5.00

Leisure Room 277.60 4 0.85


Fifth Maker space 2883.54 25 4.15
Total 3161.15 5.00

Sixth Researcher's Library 2563.32 45 7.81

Grand Total 39473.64 102.42


Heating Load
Calculation(KW)

22.27
1.23
7.68
1.75
2.53
7.46
10.98
4.45
62.62

8.30
2.33
3.38
2.01
13.13
2.82
16.10
6.14
6.22
8.58
6.16
6.13
9.08
2.61
70.17
163.15

15.96
14.61
2.82
17.51
3.31
54.21

2.97
14.61
17.59
2.97
14.61
17.59

2.97
14.61
17.59
0.00
27.45

360.19
Floor Area No. of
Floor Room
(sq.ft) People
Cafeteria Dining Space 1536.66 25
Maker Room North 2883.54 25
Leisure Room(north) 277.60 4
Second
Maker Room South 2106.93 15
Leisure Room (south) 300.85 3
Total

Leisure Room 277.60 4


Third Maker Space 2883.54 25
Total

Leisure Room 277.60 4


Fourth Maker Space 2883.54 25
Total

Leisure Room 277.60 4


Fifth Maker space 2883.54 25
Total

Sixth Researcher's Library 2563.32 45

Grand
Total
HeatingLoad Calculation(TOR)
4.54
4.16
0.80
4.98
0.94
15.41

0.85
4.15
5.00

0.85
4.15
5.00

0.85
4.15
5.00

7.81

102.42
Heating Load
Floor
ToR KW
Ground 17.81 62.62
First 46.39 163.15
Second 15.41 54.21
Third 5.00 17.59
Fourth 5.00 17.59
Fifth 5.00 17.59
Sixth 7.81 27.45
TOTAL 102.42 360.19
Heating Load
180
160
140
120

Load (KW)
100
80
60
40
20
0
Ground Fi rst Second Thi rd Fou
Floor
Heating Load
50.00
45.00
Heating Load 40.00
35.00
30.00
25.00
20.00
15.00
10.00
5.00
0.00
Ground Fi rst Second Thi rd Fourth Fifth

Second Thi rd Fourth Fifth Si xth


Floor
ting Load

Thi rd Fourth Fifth Si xth