DF008

2 3 4 5 6 7 8 9 10 11 12

PROTECTION FUNCTIONS:-
201 202 203 204 205
21
DISTANCE PROTECTION (MAIN-1)
M1
BUS COUPLER 2MBVT1 TRANSFORMER-1 TRANSFORMER-2 220kV DHANORA #1 220kV DHANORA #2
H H
& BUS VT WDG - 1 WDG - 2 WDG - 3 MPCL MPCL 21 DISTANCE PROTECTION (MAIN-2)
220kV 110V 220kV 110V 220kV 110V M2
3 3 3 3 3 3
0.2, 75VA 3P, 10VA 3P, 10VA 27 UNDER VOLTAGE PROTECTION
97 97 97

46 NEGATIVE SEQUENCE PROTECTION


220kV MAIN BUS - 1, 2VT89AE
& TRANSFER BUS, 2VT89A
2000A, 40KA FOR 1 SEC 99 OVERFLUX PROTECTION FOR TRANSFORMER

20289A 20389A 20489A 20589A


2MBVT2 20389AE
WDG - 1 WDG - 2 WDG - 3 20289AE 20489AE 20589AE LBB
LOCAL BREAKER BACKUP PROTECTION
220kV 110V 220kV 110V 220kV 110V
3 3 3 3 3 3 2VT89BE T T
T T
0.2, 75VA 3P, 10VA 3P, 10VA
2VT89B 20189A 20489B 50 INSTANTENEOUS OVERCURRENT RELAY
20189AE 20289B 20389B 20589B
97 97 97
G 50N INSTANTANEOUS EARTH FAULT RELAY G
220kV MAIN BUS - 2,
2000A, 40KA FOR 1 SEC 20252 20352 20452 20552
20289T 51 OVER CURRENT PROTECTION WITH TIME DELAY
20289TE
20289CE 20389CE 20489CE 20589CE
20389T 20489C 20489T 20589C 20589T 51N EARTH FAULT PROTECTION WITH TIME DELAY
20189B 20289C 20389C
20389TE 20489TE 20589TE
20189BE FROM SELECTED
MFM
BUS VT (WDG-1) 202CT P1 204CT1 59 OVER VOLTAGE PROTECTION
P1 CORE - 1 ABT ABT CORE - 1 P1
201CT C264 (BCU)
300/1A FROM SELECTED
800-400/1A ABT ABT
FROM LINE
MAIN CHECK BUS VT (WDG-1) MFM
CORE - 1 A V F PF 79 CL: 0.5,10VA CL: 0.2S,10VA MAIN CHECK VT (WDG-1) 67/ DIRECTIONAL OVER CURRENT &
MFM 67N
1600-800/1A P1 EARTH FAULT PROTECTION

METERING & PROTECTION SAME AS DHANORA LINE-1


ISF<5
_ ISF<5
_
CL: 0.2,10VA MVA MVAR MW 25 FROM LINE 205CT1 5C
ISF<5
_ CORE - 2 C264 (BCU) P1
CORE - 2 C264 (BCU) VT (WDG-2) 79 AUTO RECLOSURE RELAY
300/1A A V F PF 79 MVA MVAR MW 25 800-400/1A P2
203CT 5C A V F PF 79 MVA MVAR MW 25
CORE - 2 CL: 0.2,10VA CL: 0.2,10VA

METERING & PROTECTION SAME AS TRANSFORMER-1


P141
F 1600-800/1A ISF<5
_ P2 ISF<5
_ 87BB BUS DIFFERENTIAL PROTN F
50 50N 51 51N DR
CL: 5P20,10VA CORE - 3 CORE - 3
P642 800-400/1A P444 (MAIN-1) 205CT2 1C
300/1A 203LA
CORE - 3 87T 46 99 DR CL-PS,Vk>1300-650
_ 21 (TARRIF) 87T TRANSFORMER DIFFERENTIAL PROTECTION
CL-PS,Vk>300
_
M1 DR 46 59 27 67 67N PSB DFL SOTF 97
2000/1A Rct <5Ω
_ Rct <10-5Ω
_ 205CVT1
CL-PS,Vk>1000
_ SPARE FROM SELECTED BUS CVT(WDG-2) Im<30-60mA@Vk/2
_ FROM LINE VT (WDG-3) (TARRIF)
Im<30mA@Vk/2
_ SEF STAND-BY EARTH FAULT
Rct <15Ω
_ FROM 33KV SIDE CT(CORE-1)
Im<60mA@Vk/2
_ CORE - 4
P443 (MAIN-2)
CORE - 4 P141(1) 800-400/1A 64R RESTRICTED EARTH FAULT PROTECTION
300/1A 50 50N CL-PS,Vk>1300-650
_ 21 DR 46 59 27 67 67N PSB DFL SOTF
51 51N SEF 64R DR M2 97
CORE - 4 P746 T2 Rct <10-5Ω
_
2000/1A 87 50 CL: 5P20,30VA
BB LBB FROM HV NCT- CORE-1 75/100 MVA Im<30-60mA@Vk/2
_ FROM LINE VT (WDG-4) 97 FUSE FAIL RELAY
CL-PS,Vk>1000
_
FROM HV NCT- CORE-2 ONAN/ONAF
Rct <15Ω
_ CORE - 5 P746
CORE - 5 P746
Im<60mA@Vk/2
_ P2
2000/1A 220/33kV, YNynO 2000/1A
87 50 87 50 205LA DR DISTURBANCE RECORDER
CL-PS,Vk>1000
_ BB LBB Z = 17.5 % CL-PS,Vk>1000
_ BB LBB
Rct<15
_ Ω P2
OLTC ± 8 X 1.25 % Rct <15Ω
_ P2

20152 Im<60mA@Vk/2
_ Im<60mA@Vk/2
_ DFL DISTANCE TO FAULT LOCATION
E 30kV LA E
202LA 205LVT
204CT2
TO P141(1) HV BCT-1 SOTF SWITCH ON TO FAULT
(TARRIF)
TO P141(1) 300/1A CORE - 1
HV CL-PS,Vk>300
_
64R 800-400/1A PSB POWER SWING BLOCK
HV Rct <3Ω
_
CL: 0.2S,20VA
SEF Im<30mA@Vk/2
_
ISF<5
_
T1 25 CHECK SYNCHRONISATION
75/100 MVA 204CVT1
ONAN/ONAF HV NCT(CORE-2) HV NCT(CORE-1) LV NCT(CORE-1) LV NCT(CORE-2) (TARRIF)
220/33kV, YNynO 300/1A 300/1A 300/1A 300/1A WDG - 1
220kV 110V FUNCTIONS IN BCU:-
Z = 17.5 % CL-PS,Vk>300
_ CL-PS,Vk>300
_ CL-PS,Vk>300
_ CL-PS,Vk>300
_
OLTC ± 8 X 1.25 % Rct <3Ω
_ Rct <3Ω
_ Rct <3Ω
_ Rct <3Ω
_ 3 3 FREQUENCY
MW REAL POWER MEASUREMENT F
Im<30mA@Vk/2
_ Im<30mA@Vk/2
_ Im<30mA@Vk/2
_ Im<30mA@Vk/2
_ 0.2, 30VA
MVA ACTIVE POWER MEASUREMENT A CURRENT(R,Y,B)
204LA
MVAR REACTIVE POWER MEASUREMENT PF POWER FACTOR
P141(2) WDG - 1 WDG - 2 WDG - 3 WDG - 4
D LV BCT- 1 204LVT 220kV 110V 220kV 110V 220kV 110V 220kV 110V D
LV LV V VOLTAGE(R,Y,B)
2000/1A SEF 64R 3 3 3 3 3 3 3 3
CL-PS,Vk>2000
_ 0.2, 30VA 0.2, 10VA 3P, 10VA 3P, 10VA
Rct <15Ω
_
Im<60mA@Vk/2
_ 97 97

4R/PH.-1/C-630 SQ. mm XLPE Cu. CABLE(TYP)


4R/PH.-1/C-630 SQ. mm XLPE Cu. CABLE(TYP)
30kV LA
TO 33KV SWITCHGEAR I/C-2
TO 33KV SWITCHGEAR I/C-1
LEGEND :-
MAIN OUTDOOR EQUIPMENTS
MOTOR OPTD ISOLATOR
M WITH INTEGRAL MAIN SL.No DESCRIPTION QTY.
EARTH SWITCH

MOTOR OPTD 1 75/100 MVA (ONAN/ONAF) 220/33kV 3 PHASE POWER TRANSFORMER WITH BUSHING CTS 2 NOS
C POWER TRANSFORMER HIGH SPEED C
M EARTH SWITCH
WITH BUSHING CT 2 245kV, 2000A, 40KA, FOR 1 SEC. 3P,SF6 CIRCUIT BREAKER, 5 NOS CONDUCTOR DETAILS
220KV
SL.No. SYSTEM PARAMETER
SF6 / 33kV CABLE PLUG SYSTEM 3 245kV, 800A, 40KA, FOR 1 SEC. 5 -CORE, 1 -Ph C.T. (800-400/1/1/1/1. 2000/1A) FOR LINE BAY 6 NOS CONDUCTOR
IN CABLE TERMINATION (3 POLE)
CH400 STANDS FOR
4
SL.No. SYSTEM PARAMETER FOR 33kV GIS SL.No DESCRIPTION
400 SQ.mm CU CABLE 1.0 MINIMUM CLEARANCES ADOPTED (mm) : 245 kV, 300A, 40KA, FOR 1 SEC. 5 -CORE, 1 -Ph C.T. (300/1/1/1/1. 2000/1A) FOR TRAFO. BAY 6 NOS
220 kV
CIRCUIT BREAKER
5 245kV, 1600A, 40KA, FOR 1 SEC. 4 -CORE, 1 -Ph CT. (1600-800/1/1, 2000/1/1A) FOR B/C BAY 3 NOS
i. PHASE TO PHASE 2100 1. MAIN SYSTEM 3PH, 3WIRE, AC 50+/-, 5% Hz 1 MAIN BUS I CUM TRANSFER BUS TWIN MOOSE ACSR
T EMVT 2 NOS. SEC. WDG. 6 245 kV, 800A, 40KA, FOR 1 SEC. 1 -CORE, 1 -Ph MPCL TARRIF METERING CT. (800-400/1A) 6 NOS
TANDEM ISOLATOR 2. RATED OPERATION VOLTAGE 33kV 2 MAIN BUS II TWIN MOOSE ACSR
ii. PHASE TO EARTH 2100
7 245 kV, 1 -P1h BUS CVT , WITH 3 SECONDARIES (220/ 3)/0.11/ 3/0.11/ 3/0.11/ 3 kV 6 NOS
JACK BUS / EQUIPMENT CONNECTION FOR SINGLE MOOSE ACSR / 3.5" IPS
CAPACITIVE VOL. iii. SECTIONAL CLEARANCE 4500 3. RATED CURRENT 2500A 3
8 245 kV, 1 -Ph LINE CVT , WITH 4 SECONDARIES (220/ 3)/0.11/ 3/0.11/ 3/0.11/ 3/0.11/ 3 kV LINE BAY AL. TUBE - (EH TYPE)
DETECTING SYSTEM 6 NOS
ISOLATOR WITH
ONE E/S SOLIDLY JACK BUS / EQUIPMENT CONNECTION FOR SINGLE MOOSE ACSR / 3.5" IPS
2.0 SYSTEM NEUTRAL EARTHING 9 245 kV, 1 -Ph MPCL TARRIF METERING CVT , WITH 1 SECONDARIY (220/ 3)/0.11/ 3kV) 6 NOS 4. RATED INSULATION VOLTAGE 36kV 4
EARTHED TRANSFORMER BAY AL. TUBE - (EH TYPE)
4C 4 CORE CURRENT TRANSFORMER
10 245 kV, 2000A, 40KA, FOR 1 SEC. 3-POLE ISOLATORS WITH 1E/S (MECHANICALLY GANG). 16 NOS JACK BUS / EQUIPMENT CONNECTION FOR TWIN MOOSE ACSR / 3.5" IPS
3.0 HIGHEST SYSTEM VOLTAGE 245KV (r.m.s) 5. DRY FREQ. WITHSTAND VOLTAGE (r.m.s) 70KV 5
5 CORE CURRENT TRANSFORMER BUS COUPLER BAY AL. TUBE - (EH TYPE)
5C
BUS CVT WITH 11 245 kV, 2000A, 40KA, FOR 1 SEC. 3-POLE TANDEM ISOLATORS(MECHANICALLY GANG). 4 NOS
B 460KV (r.m.s) 6. RATED IMPULSE VOLTAGE (PEAK) 170KV B
3 SECONDARIES 3 CORE CURRENT TRANSFORMER 4.0 POWER FREQ. WITHSTAND VOLTAGE
3C
12 198kV, 7 KJ/kV, GAPLESS 1-Ph, LIGHTNING ARRESTER 12 NOS CLIENT:
LINE CVT WITH 1C 1 CORE CURRENT TRANSFORMER 5.0 LIGHTNING IMPULSE WITHSTAND VOLTAGE ±1050 kvp 7 SYSTEM FAULT LEVEL 40kA FOR 1SEC.
BHARAT OMAN REFINERIES LIMITED.
13 30kV, 5 KJ/kV, GAPLESS 1-Ph, LIGHTNING ARRESTER 6 NOS
4 SECONDARIES BINA, MADHYA PRADESH
SURGE ARRESTOR 6.0 SYSTEM FAULT LEVEL 40KA FOR 1 SEC 14 315kVA, 33/0.433kV, AUX. TRANSFORMER 1 NOS 8. DESIGN AMBIENT TEMP. 40°C
DEVELOPMENT CONSULTANTS PVT. LTD.
CONSULTING ENGINEERS
KOLKATA MUMBAI CHENNAI NEW DELHI
Name
PROJECT:
5427PK095-BIN- E - SYD - SYS-0401-SL 220/33kV KEY SINGLE LINE DIAGRAM 1. 33KV PSLD AND 33KV CT/CVT SIZING CALCULATION SHALL BE
Date BINA REFINERY PROJECT
Sign.
SUBMITTED SEPARATELY.
7703-71-60-A1-0101 (REV-E) MAIN SINGLE LINE DIAGRAM -220/33KV SYSTEM Name SUBSTATION 220/33kV SUB-STATION AT BINA
Date
Sign. 1. CEP/WBSETCL/Sub-Stn/Package-19 /SUPPLY / 2013-14 / 27 dated 30.11.13
Name 2. CEP/WBSETCL/Sub-Stn/Package-19/Erection (E)/2013-14/28 dated 30.11.13
CONTRACT No.
Date
TITLE: A
Sign.
A
Name
Date PROTECTION & METERING SINGLE LINE DIAGRAM (220KV SIDE)
Sign.
Name
0 Date ALSTOM T&D INDIA LTD. DRAWING No. TOTAL SH.
FORMERLY AREVA T&D INDIA LTD. SH.No. REV.
Sign. A1 DLF IT PARK, PREMISES NO.-8 1
ELE. CIVIL MECH. GRID
REFERENCE NO. DESCRIPTION NOTES REV.No. DESCRIPTION DATE DRAWN REVIEW APPROVED STATUS MAJOR ARTERIAL ROAD TOWER-C, 5427PK095-BIN- E - SYD - SYS-0451-SL SCALE 1 OF 1 0
CHECKED 8TH FLOOR, KOLKATA- 700 156. NTS