For further improvement the information on the manual is subject to change without prior notice.
NO.: 0010540329
MODELS:
HSU-07CC03 HSU-07CD03 HSU-07CE03 HSU-07HC03 HSU-09CE03
HSU-07HD03 HSU-07HE03 HSU-09CA13 HSU-09CH03 HSU-09CF03
HSU-09CJ03 HSU-09CK03 HSU-09HH03 HSU-09HJ03 HSU-09HE03
HSU-09HK03 HSU-12CA03 HSU-12CA13 HSU-12CB03 HSU-09HF03
HSU-12CB13 HSU-12CC13 HSU-12CD13 HSU-12CE13 HSU-12CH03
HSU-12CF03 HSU-12CG03 HSU-12CI03 HSU-12HR03 HSU-12CL03
HSU-12CM03 HSU-12HA03 HSU-12HC13 HSU-12HD13 HSU-12CP03
HSU-12HI03 HSU-12HJ03 HSU-14C03 HSU-14C13 HSU-12CR03
HSU-14H13 HSU-16C13 HSU-16CC03 HSU-16CD03 HSU-12HN03
HSU-16HC03 HSU-16HD03 HSU-18HA13 HSU-12HP03
HSU-18HC13 HSU-22CA13 HSU-22CB13
HSU-22CC13 HSU-22HA13 HSU-22HC13
HSU-09C03/R1 HSU-09CA03/R1 HSU-09H03/R1
HSU-12CA03/R1 HSU-12C03/R1 HSU-12H03/R1
AS092AMBAA+AU092ABBAA AS052AZMAA+AU052ACMAA
AS184ASMAA+AU184AFMAA AS128AVAAA+AU128ABAAA
AS188ATAAA+AU188AFAAA AS228ATAAA+AU228AFAAA
AS122AYBAA+AU122ABBAA
Content
1. Features
2. function schedule
3. Specifications
4. net dimension for indoor unit
5. net dimension for outdoor unit
6. parts and functions
7. parts and functions for CFC-free type
8. refrigerating cycle diagram
9. program diagram
10. circuit diagram
11. knock-down drawings for indoor unit
12. knock-down drawings for outdoor unit
13. remote controller functions conversion
14. installation and accessory parts
15. installation and accessory parts for CFC -free type
16. maintenance and service
17. easily damaged components list
1
FEATURES
2
FEATURES
Features
1.Comfortable: wide-angle airflow.
The vertical dual-flap and horizontal wide-angle louvers ensure the cool(warm) air reaches
every corner of the room.
4.Quiet operation
Fan With Random-pitched Blades.
Random-pitched blades help reduce operating noise while maintaining a high airflow rate.
5.Energy efficient
The design of inner-grooved copper tube greatly increases the refrigerant contact area
and the efficiency of cooling /heating functions.
6. Convenience
Auto restart and washable panel:
The grille can be removed easily and washed when necessary. Even if the power fails when
the unit is operating,the unit will automatically return to the operating settings in use before
the power failure when power is restored.
3
SPECIFICATIONS
4
SPECIFICATIONS
Specifications:
Type of Indoor unit Cross flow fan Cross flow fan Cross flow fan
fan unit Outdoor unit Axial fan Axial fan Axial fan
Fan Indoor unit r/min 1310/1100/920(H/M/L) 1150/1100/920(H/M/L) 1260/1100/920(H/M/L)
speed Outdoor unit r/min 710 730 710
Air volume m3/h 500 500 500
-3
Moisture removal m3/h 1.5x10 -3 1.5x10 -3
1.5x10
Piping Liquid pipe mm 6.35 6.35 6.35
dimension Gas pipe mm 9.52 9.52 9.52
Piping connection Flare nut Flare nut Flare nut
5
SPECIFICATIONS
Specifications:
6
SPECIFICATIONS
Specifications:
Type of Indoor unit Cross flow fan Cross flow fan Cross flow fan
fan unit Outdoor unit Axial fan Axial fan Axial fan
Fan Indoor unit r/min 1260/1100/920(H/M/L) 1260/1100/920(H/M/L) 1150/1100/920(H/M/L)
speed Outdoor unit r/min 730 730 730
Air volume m3/h 500 500 500
-3
Moisture removal m3/h 1.5x10 -3 1.5x10 -3 1.5x10
Piping Liquid pipe mm 6.35 6.35 6.35
dimension Gas pipe mm 9.52 9.52 9.52
Piping connection Flare nut Flare nut Flare nut
7
SPECIFICATIONS
Specifications:
Model HSU-12CA03
HSU-12C03/R1 HSU-12CM03 HSU-12CA03/R1
Item HSU-12CF03
Cooling capacity BTU/h 12000 12000 12000
Heating capacity BTU/h
Power supply 1PH 220-230V~ 50Hz 1PH 220-230V~ 50Hz 1PH 220-230V~ 50Hz
Power input W 1350 1250 1350
cooling Running current A 6.8 6.0 6.8
EER BTU/(h w) 8.89 9.6 8.89
Power input W
heating Running current A
COP BTU/(h w)
Sound Indoor unit dB(A) 41/38/33(H/M/L) 41/38/33(H/M/L) 41/38/33(H/M/L)
level Outdoor unit dB(A) 49 49 49
950x250x360 998x266x318 998x266x318
Packaging Indoor unit mm
dimensions Outdoor unit mm 920x340x613 920x340x613 920x340x613
Indoor unit kg 11/14(net/gross) 11/14(net/gross) 11/14(net/gross)
weight
Outdoor unit kg 39/44(net/gross) 36/41(net/gross) 36/41(net/gross)
Compressor model RE231VHAH QXR-23(F) RE231VHAH
Overload protector Built-in MRA99122-9201 Built-in
Running capacitor for comp. 30 F/450 VAC 30 F/450 VAC 30 F/450 VAC
Starting method PSC PSC PSC
Refrigerant R407C R22 R407C
Refrigerant charge g 1070 1070 1090
Type of Indoor unit Cross flow fan Cross flow fan Cross flow
fan unit Outdoor unit Axial fan Axial fan Axial fan
Fan Indoor unit r/min 1350/1100/1020(H/M/L) 1260/1100/920(H/M/L) 1260/1100/920(H/M/L)
speed Outdoor unit r/min 760 760 760
3
Air volume m /h 700 700 700
Moisture removal m3/h 1.5x10 -3 1.5x10 -3 1.5x10 -3
Piping Liquid pipe mm 6.35 6.35 6.35
dimension Gas pipe mm 12.7 12.7 12.7
Piping connection Flare nut Flare nut Flare nut
8
SPECIFICATIONS
Specifications:
9
SPECIFICATIONS
Specifications:
10
SPECIFICATIONS
Specifications:
Model HSU-12HC13
Item HSU-14C03 HSU-14C13
HSU-12HD13
11
SPECIFICATIONS
Specifications:
Model HSU-16CC03
Item HSU-14H13 HSU-16C13
HSU-16CD03
12
SPECIFICATIONS
Specifications:
13
SPECIFICATIONS
Specifications:
Model AS184ASMAA
HSU-22CA13 HSU-22HA13 AU184AFMAA
Item HSU-22CB13 HSU-22CC13 HSU-22HC13 (HSU-18CB13)
Cooling capacity BTU/h 22000 22000 18000
Heating capacity BTU/h 22500
Power supply 1PH ,220-230V~ , 60Hz 1PH ,220-230V~ , 60Hz 1PH ,220-230V~, 60Hz
Power input W 2050 2270 1920
cooling Running current A 9.5 11.3 9.0
EER BTU/(h w) 10.73 9.69 9.375
Power input W 2290
heating Running current A 11.5
COP BTU/(h w) 9.82
14
SPECIFICATIONS
Specifications:
15
SPECIFICATIONS
Specifications:
AS188ATAAA
Model AU188AFAAA
Item (HSU-18HC04)
16
FUNCTION
SCHEDULE
17
FUNCTION SCHEDULE
6 Emergency run Over 23 cooling and set 26 , less 23 heating and set 23
When temperature of the heating pipe coil is low. low fan speed
8 Anti-cold wind (heat pump type)
or without airflow
9 Fan speed adjustment Auto, high, middle,low four level fan speeds
13 Anti-freezing of the indoor unit When heating in low ambient temperature to protect system
15 Self trouble shooting Check the system trouble and give an alarm
16 Over current protection (heat pump type) When working in high power to protect system
18
NET DIMENSION
FOR
INDOOR UNIT
19
NET DIMENSION FOR INDOOR UNIT
NET DIMENSIONS:
Indoor unit
MODELS: HSU-09C03/R1 HSU-09CA13
795
290
160
Indoor unit
Models: AS052AZMAA HSU-07CC03 HSU-07CD03 HSU-07CE03 HSU-07HC03
HSU-07HD03 HSU-07HE03 HSU-09CA03/R1 HSU-09CH03 HSU-09CJ03
HSU-09CK03 HSU-09H03/R1 HSU-09HH03 HSU-09HJ03 HSU-09HK03
HSU-12CC13 HSU-12CE13 HSU-12HR03 HSU-12HC13 HSU-12HD13 AS092AMBAA
795 182
265
20
NET DIMENSION FOR INDOOR UNIT
NET DIMENSIONS:
MODELS: HSU-12CA13 HSU-12CB03 HSU-12CD13
295
160 880
186
804
21
NET DIMENSION FOR INDOOR UNIT
MODELS:
HSU-12CA03 HSU-12CA03/R1 HSU-12CB13 HSU-12CF03 HSU-12CM03
HSU-12H03/R1 HSU-12HA03 HSU-12HI03 HSU-12HJ03 HSU-14C03 HSU-14C13
HSU-14H13 HSU-16C13 HSU-16CC03 HSU-16CD03 HSU-16HC03
HSU-16HD03 AS124AVMAA AS122AYBAA
938 182
265
MODELS:
AS188ATAAA AS228ASAAA AS184ASMAA HSU-22HC13 HSU-22HA13
HSU-22CC13 HSU-22CB13 HSU-22CA13 HSU-18HC13 HSU-18HA13
330
208
1100
22
NET DIMENSION
FOR
OUTDOOR UNIT
23
NET DIMENSION FOR OUTDOOR UNIT
724
530
281
305
567
723
796
68
140 500 55 67
123
780 62 15
256
845 286
24
NET DIMENSION FOR OUTDOOR UNIT
540
68
140 500 55 67
123
780 62 15
256
845 286
255
540
267.25 500
710
296
727
25
NET DIMENSION FOR OUTDOOR UNIT
288
680
583
810
319.5
26
PARTS
AND
FUNCTIONS
27
PARTS AND FUNCTIONS
Outlet
The air flow direction is adjusted with
the vertical and horizontal louvers
Remote signal receiver
A digital beeping sound is generated when a signal
from the wireless remote controller is received
Inlet grill
For models:
Air filter HSU-18HA13
HSU-22CA13
HSU-22HA13
Vertical flap Power indicator Timer mode indicator Operation mode indicator
Use remote controller to
adjust up and down air flow. Lights up when unit starts. Lights up when Timer Lights up during
operation is selected. compressor running.
(Don't adjust it manually.)
Inlet grill
For models:
HSU-22CB13
Air filter
28
PARTS AND FUNCTIONS
Emergency switch(manual)
Used when remote controller is lost
Air filter or defective .Unit will run temporarily
Power plug
Vertical flap Operation mode indicator Timer mode indicator
Use remote controller to
Power indicator
Lights up during compressor Lights up when Timer operation
adjust up and down air flow. Lights up when unit starts.
running. is selected.
(Don't adjust it manually.)
Emergency switch(manual)
Used when remote controller is lost
Air filter or defective .Unit will run temporarily.
For multi -split type, the power plug is on the outdoor unit.
Emergency switch(manual)
Used when remote controller is lost
or defective .Unit will run temporarily
Air filter
Power plug
Vertical flap Operation mode indicator Timer mode indicator Power indicator
Use remote controller to
Lights up during compressor Lights up when Timer operation Lights up when unit starts.
adjust up and down air flow.
running. is selected.
(Don't adjust it manually.)
29
PARTS AND FUNCTIONS
Emergency switch(manual)
Used when remote controller is lost
or defective .Unit will run temporarily
Vertical flap Power indicator Timer mode indicator Operation mode indicator
Use remote controller to Lights up when unit starts. Lights up when Timer operation Lights up during compressor
adjust up and down air flow. is selected. running .
(Don't adjust it manually.)
Emergency switch(manual)
Used when remote controller is lost
or defective .Unit will run temporarily
Air filter
Remote signal receiver
A beeping sound is generated when
a signal from remote controller is
received.
For models:
HSU-07CE03 HSU-09HJ03 HSU-12CM03 HSU-16CD03 HSU-12CD13
HSU-07HE03 HSU-12CK03 HSU-12HJ03 HSU-16HD03 HSU-12CE13
Inlet grill
Air filter
For models:
HSU-18HC13 HSU-22HC13 HSU-22CC13
30
PARTS AND FUNCTIONS
HSU-12CA03 HSU-09CA13
HSU-12CF03 HSU-12CA13
INLET HSU-12HR03 HSU-12CB13
HSU-12CM03 HSU-12CC13
HSU-12HA03 HSU-12CD13
HSU-12HI03 HSU-12CE13
HSU-12HJ03 HSU-12HC13
HSU-14C03 HSU-12HD13
HSU-16CC03 HSU-14C13
HSU-16CD03 HSU-14H13
HSU-16HC03 HSU-16C13
HSU-16HD03
AU128ABAAA
DRAIN HOSE
OUTLET
Warm air comes out when cooling,
cool air comes out when heating.
2.If the supply cord is damaged, it must be replaced by the manufacturer or its service agent
or a similar qualified person.
3.The type of connecting wire is H05RN-F or H07RN-F.
4.If the fuse on PC board is broken please change it with the type of 50T.3.15A/250V.(for
series 16,18,22)or 50F.2.5A/250V(for series 05, 07,09,10,11,12,14).
5.The distance between the indoor unit and the floor should be more than 1.8m.
6.The wiring method should be in line with the local wiring standard.
7.After installation ,the power plug should be easily reached.
8.The waste battery should be disposed properly.
9.The appliance is not intended for use by young children or infirm persons without supervision.
10.Young children should be supervised to ensure that they do not play with the appliance.
31
PARTS AND FUNCTIONS
For models:
HSU-18HA13 HSU-22CC13
HSU-18HC13 HSU-22HA13
HSU-22CA13 HSU-22HC13
HSU-22CB13
32
PARTS
AND
FUNCTIONS
FOR
CFC-FREE TYPE
33
PARTS AND FUNCTIONS FOR CFC-FREE TYPE
Inlet grill
Outlet
The air flow direction is adjusted with
Remote signal receiver
the vertical and horizontal louvers A digital beeping sound is generated when a signal
from the wireless remote controller is received
Emergency switch(manual)
Used when remote controller is lost
or defective .Unit will run temporarily
Air filter
Power plug
Vertical flap Operation mode indicator Timer mode indicator Power indicator
Use remote controller to
Lights up during compressor Lights up when Timer operation Lights up when unit starts.
adjust up and down air flow.
running. is selected.
(Don't adjust it manually.)
34
PARTS AND FUNCTIONS FOR CFC-FREE TYPE
Emergency switch(manual)
Used when remote controller is lost
or defective .Unit will run temporarily
Vertical flap Power indicator Timer mode indicator Operation mode indicator
Use remote controller to Lights up when unit starts. Lights up when Timer operation Lights up during compressor
adjust up and down air flow. is selected. running .
(Don't adjust it manually.)
Outdoor Unit
DRAIN HOSE
OUTLET
Warm air comes out when cooling,
cool air comes out when heating.
35
REFRIGERATING
CYCLE
DIAGRAM
36
REFRIGERATING CYCLE DIAGRAM
comp.
stop valve
capillary tube filter
comp.
capillary tube
stop valve
filter
cooling operation
heating operation
37
PROGRAM
DIAGRAM
38
PROGRAM DIAGRAM
PROGRAM DIAGRAM
INDOOR PROGRAM OUTDOOR PROGRAM
NO. MACHINE MODEL DIAGRAM DIAGRAM
39
PROGRAM DIAGRAM
1.
Start
No
Turn on the unit
Yes
Mode judegement
2.
Auto Auto
No
Air flow in 26 Air flow in >23
No
Yes Yes
No
Yes Yes
No
Yes
Air flow in 23 Air flow in 27
No Yes
40
PROGRAM DIAGRAM
3.
Cool
No Yes
Yes
No Set? first time?
Air flow units start
in SET 6 mins No
No
louver
Yes Set
Yes Auto fan speed: starts
fan
When room speed
comp outdoor temp. temp set
Yes fan stops
pipe sensor +3,high fan; when No
72continue10sec temp set+1 Auto?
room temp
temp set Yes
No +3,middle
fan; when room Auto
temp<temp swing set
Yes set+1,low
After 60 secs unit The indoor
fan;when temp
start. CT >1.9v pipe sensor
sensor off low
continue 3secs temp
fan
protection
will be less
No than 64
then
resume;curre-
Yes nt protection
comp runs for will be less
5mins pipe than 1.7A
sensor -1 then resume
defrosting
temp
protection
No will be more
than 7
41
PROGRAM DIAGRAM
4.
heat
Yes
defrost? In defrosting(see the
defrosting process)
No
Yes
first time?
No
temp set=temp set+4(temp. compensation)
No Yes
first time?
No unit Yes
air flow anti_ col
starts for
in set d wind No
8 mins
anti_cold louver
Yes Yes No starts
wind action
comp outdoor fan
Yes stops 4-way valve No
pipe sensor 72 closes
continue 10secs Auto?
Yes
No
Yes Auto
the pipe sensor set? set
temp. protection swing
Yes will be less than
after unit start 64 ; then No
60 secs CT>1.9v resume; current
continue 3secs protection will
be less than set fan
1.7v then speed
resume
No
auto fan speed:
comp. outdoor when room
fan starts temp<temp. set,high
fan speed;when
temp. set+2 room
temp
temp. set,middle fan
speed;when room
temp.>temp.set+2;
low fan speed
42
PROGRAM DIAGRAM
5.
drying
Yes
Yes first time?
set?
room temp>
temp. set+2? No
No
the same as louver
set fan
auto fan speed: starts
cooling speed
when room temp
temp.set+5,high fan No
temp. set room
temp temp. set+2? speed;when temp. set+3 Auto?
room temp<
comp temp. set+5,middle fan Yes
outdoor fan
stops speed;when temp. set+2
room auto swing set
temp<temp. set+3,low
comp. fan starts for 10
mins and stops for 6 fan speed;when temp.set
min to do drying room
tempemp. set+2,weak
wind runs
protection is intermittently;when
the same as room temp<temp. set in
cooling
3mins waiting,off,over
3mins waiting, weak
wind
note:The fan speed setting, when temp. sensor off or the indoor fan motor runs intermittently, do not
operate manually (compulsory auto run)
43
PROGRAM DIAGRAM
6.
Defrost
Yes
In defrost?
No
No
No No
meet No meet meet meet
condition condition condition condition
A B? C? D?
enter
quit
44
CIRCUIT
DIAGRAM
45
CIRCUIT DIAGRAM
CIRCUIT DIAGRAM
46
D1
VCC RG1 VDD
TSA300J DQ1 VDD AN7805
R6 IN4004 VDD
R52 DB1 C1815 1 Vin Vout 3
T 22K
100
GND
RL1 2 R9 R39 +
1 C1 C7
C22 C2 1 4.7K 10K C3 +
PC2-1 2 25V/2200 F 0.1 F
2
CN12 R5 C5
0.01 F 1A/400V 4.7K
10V/00 F
250V/0.1 F
CN4 C19 VDD MANUAL SW C20
CIRCUIT DIAGRAM
2 1 0.047 F
1 FC1 0.1 F 1
IC1 C18
47C862AN-GC54 0.047 F 2
POWER N INDOOR FAN 1 VDD 64 10K R43
TERMINAL BLOCK 2 63 R46 560 3
3 COMP
SW
62 DQ6
4 SLAV 4
TESTIN
61 R42
5 60 C1815 470
A R44 10K 5
6 59 DQ5
A R49
7 PWRLED 58 10K C1815
B R41 6
8 TIMLED 57 R48 10K 560
B
9 RUNLED 56 R47 10K DQ4
10 55
10K
10K
10K
10K
10K
10K
50/60 C1815 CN10
11 54
12 53 R40
13 REMOV 52
10K
8
VDD
7
6 R27
5 R28
4 R26
3 R25
2 R24
1 R23
14 51 C17
15 50 0.001 F R37 VDD
16 49 1K
IC2 17 VKK
48
MC1413 FANPLS
R22 10K
R19 10K
CX1 18 47 L1
XIN 331K
600M 19 REMOV 46 ROOM TH.
XOUT
20 45
9
RESET 1
11
21
10
44
12
13
14
15
16
VCC DQ3 POWF
47
9012 22 43 2
WADOG + 3
23 42 C16
24 41 50V/4.7 F
LP 25 40 L3 331K
R1 27
R14 CN9
R3 100
5 C11 26 39
0.1 F GND +
27 ROOMTH 38 C15
R50 28 37 1
4 EXTH L2 331K
1OK 29 36 50V/4.7 F 2
INFAN CT
3 VDD 30 35 VDD RA1
10K OUTFAN VAFEF
31 34 A472J CN8
BUZZER VASS R31
2 32 33 R30 HEAT EXECHANGER TH
VSS TEST VDD
C14 1OK R33
1 R15 C8 0.1 f 20K 20K
C12 VDD 0.1 f D3 CT1
R18 220 IN4148
0.1 f 1OK R32
1K DB2
RL1-1 R13
R12 R11 PC2
1K R29 IK
R4 G4A-1A 1K 1K R7
1K 330
IA/400V
PB1 + B 057
C13
VDD VR1
R10 10K
100
16V/470 F
1999.2.H
D1
VDD RG1
AN7805 VDD
R51 TSA3100J TSA3100J DQ1 VDD IN4004
DB1 R6 C1815 VDD 1 3
R52 T 22K Vin Vout
100
F
R9 R39
GND
RL2 2
100
RL1 1 47K C1
C2 1 10K C3 C7
C22 2 R5 25V/2200 F
PC2-1
F
C5
2
CN12 1A/400V 47K 0.1 F
PC1-1 0.01 F 0.1 F
CN6
10V/100
CE1 CN5
C21 CN1 R38 R45
N4 0.01 F 3 10K 1K
CN11 SW1 VDD
3 2 C19
250V/0.1
1 VDD MANUAL SW C20
2 0.047 F 1
IC1 0.1 F
1 FC1 C18
47C862AN-GC54
0.047 F 2
1 64 10K
POWER N INDOOR FAN VDD R43
2 63 R46 560 3
TERMINAL BLOCK COMP 62
3 SW
SLAV DQ0 4
4 TESTTN 61
R44 C1815 470 R42
5 60 10K
6 A 59 5
7 A 58 R49 10K DQ5
B PWRLED 57 C1815 560 R41
8 R48 10K 6
B TIMLED 10K
9 56 R47
RUNLED DQ4
10 50/60 55
54 C1815 CN10
11
* 12 53 R40
13 52 10L
REMOV 51
14 C17 VDD
7
6 R27 10K
5 R28 10K
4 R26 10K
3 R25 10K
2 R24 10K
1 R23 10K
N
VDD
10K
10K
10K
15 50 0.001 F R37
16 49 1K
IC2 17 VKK 48
FANPLS
R22
R20
R19
Mc1413 CX1 18 47 L1
XTN 46
600M 19 REMOV 331K
XOUT 45 ROOM TH.
20 RESET
21 44 1
48
CC DQ3 POWF
9
10
11
12
13
14
15
16
43 100 R34
9012 22 WADOG 2
23 42 C16 3
24 41 50V/4.7 F
LP 25 40
R14 C11 39 L3 331K CN9
R3 100
R2 27
R1 27
5 26 GND
0.1 F 27 ROOMTH 38
4 R50 28 37 C15 1
* EX. TH L2 331K
10K 29 CT 36 50V/4.7 F 2
INFAN 35
3 VDD 30 OUTFAN VAFEF VDD RA1
10K 31 VASS 34 A4720
BUZZER 33 CN8
2 32 VSS TEST R31 R30
VDD HEAT EXECHANGER TH.
* C14 10K R33
1 R16 0.1 f 20K 20K
R15 C8 VDD 0.1 f D3
C12
R18 220 220 IN4148 CT1
0.1 f 10K R32 DB2
1K
RL2-2 RL1-1 PC2 R13
R12 R11 PC1
1K 1K 1K R29 1K
R4 DJE-SH-112 G4A-1A R7
1K * 330
1A/400V
F
PB1 * B 057
VDD C13
10L VR1
R10
100
DQ2
16V/470
1999.2.H
CIRCUIT DIAGRAM
TSZ1J405 TSZ2J405 D1
VDD RB1 VDD
DQ1 VDD IN4001 AN7805
F
G11D
RL1 C2 R9
RL2 10K C1 C3 C7
4.7K
10V/100
R5 25V/2200 F
CN1 1A/400V C5 0.1 F
ZE 10K 0.1 F
HC 260/104
CN4
C4 R38 R45
10K 1K SW1 VDD
C19 VDD HANUAL SW C20
450V/2 F 0.047 F 0.1 F
CIRCUIT DIAGRAM
IC1
POWER N C10
(3A) INDOOR FAN TMP47P862VN
TERMINAL BLOCK 0.047 F
FC1 10K R43
VDD R46 560
COMP
SLAV SW 10K R44 DQ6
TESTIH C1915 470 R42
10K R50
A
A R49 10K DQ5
B PWRLED C1815 560 R41
B TIMLED R48 10K
SLO RUNLED R47 10K DQ4
LOW 50/60 C1815 CN10
MID LOOP
HI R40
R27 10K
R28 10K
R26 10K
R25 10K
R24 10K
R23 10K
REMOV C17 10K VDD
22/20
0.001 F
R22 10K
R21 10K
R20 10K
R19 10K
IC2 MC1413 C31 FANPLS VKK R37 220 L1
XIN 331K
6.88H XOUT REMOV ROOM TH.
VDD DQ3 RESET R34 108
POWF
9012 WADOB HI
MID C16
49
LOW 50V/4.7 F
LP
5LO L3 331K CN9
R3 100
R2
R1 27
VDD
C11 GRD
R14 0.1 F ROOMTH C15
10K EX.TH. L2 331K 50V/4.7 F
INFAN CT
OUTFAN VAFEF VDD RA1
BUZZER VASS 5A472J CN8
VSS R31 R30 HEAT EXECHANBER TH.
TEST VDD
18K R33
R15 R16 0.1 f C14 20K 20K
C12 C8 VDD 0.1 f D3 CT
R18 220 220
100P 10K R32 1N4148 DB2
10K
RL2-2 RL1-1 R13
SR1 SR2
DJM-55 JTN15-TMP 1K 1K 1K R29 1K
112DM -F-DC12V R7
F
R17 TR4148
10K C9 FAN PULSE
PST680D
0.1 F R8 KFR-60/A R7=100 R21
C10
50V/4.7 F C6 KAC-20
10K
0.1 F
CN3 KFR-50/C R7=238 R21 R371
1990.02.21.K.
D1
VDD RG1 VDD
TSA3100J DQ1 VDD AN7805
R6 IN4004 VDD 1 3
DB1 C1815 Vin Vout
P52 T 22K
100
F
GND
R9 R39
RL1 1 2 10K C1
47K C3 C7
C22 C2 2 1 25V/2200 F
PC2-1 R5
F
C5 0.1 F
2
1A/400V
F
0.01 F 47K 0.1 F
10V/100
500V/1.2
VDD MANUAL SW C20
250V/0.1
2 1 0.047 F
1 FC1 0.1 F 1
IC1 C18
47C862AN-GC54 0.047 F 2
POWER N INDOOR FAN 1 64 10K
VDD 560 R43 3
TERMINAL BLOCK 2 63 R46
COMP 62
3 SW DQ6
SLAV 61 4
4 TESTIN R42
5 60 C1815 470
A R44 10K
6 59 5
A R40 10K DQ5
7 PWRLED 58
B 57 C1815 560 R41 6
8 R48 10K
B TIMLED 56 10K
9 R47
RUNLED 55 DQ4
10
10K
10K
10K
10K
10K
10K
50/60 C1815 CN10
11 54
12 53
52 R40
13
REMOV 10K
8
7
6 R27
5 R28
4 R26
3 R25
2 R24
1 R23
14 51 C17 VDD
10K
10K
15 50 0.001 F R37 VDD
16 49 43K
IC2 17 VKK 48
FANPLS R36
R19
MC1413
R21
R22 10K
CN1 18 47 18K L1
XIN 46
600M 19 331K
XOUT REMOV 45 ROOM TH.
20
VDD DQ3 RESET 44 1
21
9
10
11
12
13
14
15
16
9012 22 POWF 43 2
WADOG
50
23 42 C16 3
24 41 50V/4.7 F
LP 25 40
R14 L3 331K CN9
5
R1 27
R3 100
C11 26 GND 39
0.1 F 27 ROOMTH 38
4 R50 28 37 C15
EX. TH 331K 1
10K 29 36 L2 50V/47 F 2
3 VDD INFAN CT
10K 30 VAFEF 35 VDD RA1
OUTFAN
31 VASS 34 A4720
2 BUZZER R31 R30 CN8
32 TEST 33
VSS VDD HEAT EXECHANGER TH.
1 C14 10K R33
C12 R15 C8 0.1 f 20K 20K
220 VDD 0.1 F D3
R18 0.1 f CT1
1K 10K R32 IN4148
R13 DB2
RL1-1
R12 R11 PC2
R4 AJM1211 1K 1K 1K R29 1K
R7
1K
649
F
1A/400V
PB1 B 057
VDD C13
R10 10K VR1
100
16V/470
DQ2
VDD 9012 VDD D2 CA1 AC102Z
IN4148
R17
10K FAN PULSE
C9 1 PST600D
0.1 F R8 KF-26G/25G
2 C10
3 C6
10K 50V/4.7 F 0.1 F
CN3
1999.2.H
CIRCUIT DIAGRAM
KNOCK-DOWN
DRAWINGS FOR
INDOOR UNIT
52
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
24 Remote controller
/ Specialized No.
HSU-12C03/R1 HSU-12CG03 HSU-12CI03
NO.
common common restart common
1233071 1233071 1233071 1231261
3300207 0600266 0010400260 0600266
3400078 3400078 3400078
53
4
3
2
1 16
54
15
5
6
23 7
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
14
13 8
9
24
12 11 10
22 21 20 18 17
19
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
Drain pan
47 Remote controller
23. 1431254A
24. 1232077 Flap
\ specialized No.
55
5 6 7 8 9 10 11 12 13
46
45
4 44
3
2
1
43
42
56
41
32
31
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
30
29
24 28
14 15 16 17 18 19 20 21 22 23 24 25 26 27 33 34 35 36 37 38 39 40
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
MODELS:HSU-12CA13
Specialized Specialized
No. No. Parts name No. Parts name
No.
1 1432051 Fixing plank 22 1734082 Cushion
2 5002116 Screw 23 1232009 Front panel
3 1734747 Cushion 24 1432049A Front grille
4 1301021 Mounting plate 25 Wiring diagram
Frame of the air purifying
5 1232010 Bottom plate 26 1436882 filter
6 1742063 Cushion 27 2400117 Air purifying filter
7 3000009 motor 28 2239014A Sealed strip
8 0300010 Fan 29 5703011 Spring clip
9 5002118 Screw 30 1742068 Cushion
10 Transformer 31 1742069 Cushion
11 1432052 Electric box 32 5313008 Nut
12 0010400822 PCB 33 2912008 Dustproof cover
13 Power cord 34 5213003 Piping connection
14 4000091 Terminal block 35 5313003 nut
15 0600007 Signal receiver 36 2912007 Dustproof cover
16 5002026 Screw 37 5213005 Piping connection
17 3000008 Swing motor 38 1734078 Heat insulation tube
18 1431054/1431055 Flap 39 0400012 Heat exchanger
19 1432053 Drain pan 40 1436026 Sensor support
20 0900015 Drain hose 41 0300005 Bearing
21 1436029 Connecting rod 42 5002021 screw
43 3400078 Remote controller
57
25 26 27 28 29 30 31 1
58
7
8
32 42
33 41
34
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
35 40
36 39
37
38
24
15 14 13 12 11 10 9
24 23 22 21 20 19 18 17 16
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
58
22
11
15
14
23
20 4
13 1
59
8
5
16 2
6
7
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
21
19
9 17 3
18
12
26
25
10 28 24 27
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
/ / specialized No.
HSU-12CB13
No. HSU-12CA03 HSU-12CE13 HSU-12CF03 HSU-12HA03
AS124AVMAA
restart common common common common common restart
0010800420 0600469 0600469 0600469 0600469 0600698 0010800421
0010400435 0600312 0600321 0600312 0600312 3300338 0010400436
1231135 1231135 1231260 1231259 1231260 1231135 1231135
HSU-12CM03 HSU-16HD03 AS124AYMAA HSU-14C13 HSU-14C03
No. restart common common common common common restart
0010800420 0600469 0600637 0600469 0600469 0600469 0010800420
0010400435 0600312 0600208 0600312 0600312 0600312 0010400435
1231259 1231259 1231259 1231260 1231135 1231135 1231135
HSU-12HJ03 HSU-16CC03 HSU-14H13 HSU-16HC03
No. common restart common common common common restart
0600698 0010800421 0600469 0600637 0600637 0600637 0010800432
3300338 0010400436 0600312 0600208 0600208 0600208 0010400445
1231259 1231259 1231135 1231135 1231135 1231135 1231135
HSU-12H03/R1
HSU-12HI03 HSU-16C13 HSU-12CA03/R1 HSU-16CD03
AS128AYBAA
No. restart common common common common common Restart
0010800432 0600698 0600637 0600469 0600469 0600469 0010800420
0010400445 3300338 0600208 0600312 0600312 0600312 0010400435
1231260 1231260 1231135 1231135 1231135 1231259 1231259
60
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
61
22
11
15
14
23
20 4
13 1
62
5
16 2
6
7
KNOCK-DOWN DRAWINGS FOR INDOORUNIT
21
19
18
9 17 3
12
29
26
27
10 28 24 25
KNOCK-DOWN DRAWINGS FOR INDOOR UNIT
/ Specialized No.
No. HSU-18HA13 HSU-18HC13 HSU-22CA13 AS228ATAAA HSU-22CB13
1231127 1232287 1231127 1231127 1232288
0010400440 0010400440 0010400438 0010400441 0010400438
3400077 3400077 3400078 3400049 3400078
No. HSU-22CC13 HSU-22HA13 HSU-22HC13 AS188ATAAA AS184ASMAA
1232287 1231127 1232287 1231127 1232288
0010400438 0010400440 0010400440 0010400440 0010400438
3400078 3400077 3400077 3400049 3400180
63
11 12 13 14
5 6 7 8 9 10
4
3
2
15
16
17
64
18
19
KNOCK-DOWN DRAWINGS FOR INDOORUNIT
35
36
37
38
39
34 40 41
24 42
33
43
32
31 30 29 28 27 26 25 24 23 22 21 20
KNOCK-DOWN
DRAWINGS
FOR
OUTDOOR UNIT
65
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
HSU-07HC03 HSU-09HH03
No. Parts name HSU-07HD03 HSU-09HK03
HSU-07HE03 HSU-09HJ03
9 ring 1240103
Bottom plate
12 assy. 0100213
Sound insulation
14 cushion 1762577A
66
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
18
17
13
4
19
15
14
10
2
11
16
12
20
3
7
9
5
67
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
68
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
10
Capillary 0500491 0500046
tube assy. 0500490 0500044
11 Screw 5002001 5002001 5002001 5002001
12 Stop valve 2500112 2500020 2500110 2500013
13 Stop valve 2500111 2500019 2500109 2500012
14 Nut 5102004 5102004
Terminal 14401116 1440763 1440116
15
cover 1440763
16 Protector Built-in 3100037 Built in 3100009
17 Nut 5102050 5102050 5102050 5102050
Compress-
18 2000120 2000028 2000121 2000006 2000029
or
Rubber
19 cushion 17521255 1734935 17521255 1734935
20 Cushion 1762172 1762172 1762105 1762105
Suction 2111147
21 pipe 2111348 2111150 21111187
69
8
5 7
4
2 3
1 21
22 9
70
10
26 23
14
24 15
30 27
16
28 25 17
18
19
20
29
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
71
10
7 8
9
5 11
12 13
4 6
2
1 3 14
17
15
18 16
72
19
20
22
31 21
23
24
32 25
26
27
30
28
29
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
HSU-07CC03 HSU-09CH03
No. Parts name HSU-07CD03 AU052ACMAA HSU-09CJ03
HSU-07CE03 HSU-09CK03
1 Front panel 1436312
2 Back frame 1436313
3 Separating 1101210
plate
6 Motor 3000265
7 Motor support 1301227
8 Axial fan 2336029
9 ring 1240103
10 Suction pipe 21111408 21111408 21111406
11 Compressor 2000187 2000209 20000187
Sound insulation
16 cushion 1762575A
Discharge pipe
20 assy. 0500572 21111409 2111407
73
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
18
17
13
4
19
15
14
10
2
11
20
16
12
21
3
7
9
5
74
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
22 Nut 5102050
23 Compressor 2000116
27 Wires 4400509
75
9
7
6
5 11
4
3
12 15 16
1 2
13
76
17
14
18
19
20
26
29 25 21
22
28
23
24
27
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
HSU-18HA13 HSU-22HA13
No. Parts name AU188AFAAA
HSU-18HC13 HSU-22HC13
77
9
7
6
10
5 11
4
3
12 13
1 2
16 15 19
14
78
20
21
17 22
18
30 23
24
25
29
26
27
28
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
HSU-
HSU-14H13 HSU-09H03/R1 HSU-12H03/R1 12HA03 HSU-12HC13 HSU-16HC03
No. Parts name
AU092ABBAA AU122ABBAA HSU-12HI03 HSU-12HD13 HSU-16HD03
HSU-12HJ03
6 Heat
exchanger 0400063 0400008 0400193 0400009 0400009 0400063
13 Terminal
block 4000092
79
7
8
6
9
5
4
3
2 10
11
12 13
80
1
15
16
22
14 17
18
19
20
23
24 21
KNOCK-DOWN DRAWINGS FOR OUTDOOR UNIT
REMOTE
CONTROLLER
FUNCTIONS
CONVERSION
81
REMOTE CONTROLLER FUNCTIONS CONVERSION
82
REMOTE CONTROLLER FUNCTIONS CONVERSION
SWING FAN
Used to set auto fan AUTO Used to select fan speed :
direction. LO.MED.HI.AUTO
C
AM
PM
ON OFF
AM AM
PM PM
MODE
SLEEP
TEMP
Used to select AUTO run ,
ON Used to select sleep
COOL,DRY,HEAT and
SWING OFF FAN mode.
FAN operation.
MODE SLEEP
CLOCK SET SET
CLOCK TIMER
LOCK RESET
Used to confirm Timer
Used to set correct time and Clock settings.
TIMER
HOUR
Used to select
TIMER ON ,TIMER OFF, Used to set clock and
timer setting.
TIMER ON/OFF
LOCK RESET
Used to lock buttons Used to reset the controller
and LCD display. back to normal condition.
Cautions: Note:
On cooling only unit ,heating mode is not available. The above information is the
After replacing batteries ,press ON/OFF,and display explanation of the displayed
becomes as follows: information therefore varies
Operation mode:AUTO,Temp:No with those displayed in actual
Timer mode:No,Fan speed :AUTO operation.
83
REMOTE CONTROLLER FUNCTIONS CONVERSION
DRY HEAT
COOL
FAN OPERATION
AUTO
SWING PM PM
TEMP.
TEMP
ON
FAN SPEED SWING OFF FAN CLOCK
LO MED MODE SLEEP
CLOCK SET
LOCK
TIMER
TIMER ON
SLEEP
Clock set
When unit is started for the first time and after replacing batteries in remote controller.
clock should be adjusted as follows:
Press CLOCK button ,"AM" or "PM" flashes.
Press or to set correct time. Each press will increase or decrease 1min . If the
button is kept depressed. time will change quickly.
After time setting is confirmed, press SET. "AM"and "PM" stop flashing. while clock
starts working.
Hints
After replacing with new batteries ,remote controller will conduct self-check,displaying
all information on LCD.Then ,it will become normal.
84
REMOTE CONTROLLER FUNCTIONS CONVERSION
Operation
(1)Unit start
Press ON/OFF button,unit starts.
Previous operation status appears on display.
(Not Timer setting)
Power indicator on indoor unit lights up.
AM
LO MED HI AUTO
LOCK RESET
AUTO
(4)Unit stop
Press ON/OFF button.
Only time remains on LCD.
All indicators on indoor unit go out.
Vertical flap closed automatically.
Hints
Remote controller can memorize settings in each operation mode .To run it next
time just select the operation mode and it will start with the previous setting.
No reselecting is needed.(TIMER ON/OFF needs reselecting)
85
REMOTE CONTROLLER FUNCTIONS CONVERSION
Operation
(1)Unit start
Press ON/OFF button,unit starts.
Previous operation status appears on display.(Not Timer setting)
Power indicator on indoor unit lights up.
LO MED HI AUTO
AUTO
Hints
Remote controller can memorize each operation status.When starting it next time,
just press ON/OFF button and unit will run in previous status.
86
REMOTE CONTROLLER FUNCTIONS CONVERSION
Operation
TIMER operation
Set Clock correctly before starting Timer operation(refer to page 92)
You can let unit start or stop automatically at following times:Before you wake up in
the morning,or get back from outside or after you fall asleep at night.
TIMER ON/OFF
(1)After unit start,select your desired operation mode.
Operation mode will be displayed on LCD.
Power indicator on indoor unit lights up.
Just press TIMER button several times until TIMER mode disappears.
Hints
After replacing batteries or a power failure happens,Time setting should be reset.
Remote controller possesses memory function,when use TIMER mode next time,just
press SET button after mode selecting if timer setting is the same as previous one.
87
REMOTE CONTROLLER FUNCTIONS CONVERSION
Operation
TIMER ON-OFF
(1)After unit start,select your desired operation mode
Operation mode will be displayed on LCD.
Power indicator on indoor unit lights up.
ON
Time will be shown on LCD. SWING OFF 1 FAN
lt can be adjusted within 24 hours.
MODE SLEEP
AM refers to morning and PM to afternoon. 3
CLOCK SET
TIMER
6
2 4 5
(4)Time confirming for TIMER ON LOCK RESET
88
REMOTE CONTROLLER FUNCTIONS CONVERSION
Operation
Comfortable SLEEP
Before going to bed at night,you can simply press the
SLEEP button and unit will bring you a sound
sleep in selected mode.
In COOL mode C
PM
LOCK RESET
ln HEAT mode
One hour after SLEEP mode starts,temp.will
become 2 lower than temp.setting. After
running for another 1 hour,temp.decreases
by 2 further. Unit will run for 3 hours at
this temp .then increases another 1 and
SLEEP operation starts SLEEP operation stops
stops automatically 3 hours later.Temp.is
Approx. 6 hrs
lower than temp.setting so that room temp.
won't be too high for your sleeping. 1hr Rises 1
Fig.1
lf the unit is started for the first time,the
compressor will not start running unless Temp.setting Unit stop
and 3 minutes later the compressor starts SLEEP mode starts SLEEP mode stops
89
INSTALLATION
AND
ACCESSORY
PARTS
90
INSTALLATION AND ACCESSORY PARTS
Accessory parts
Number Drawing for the installation of indoor and outdoor units
of
No. Accessory parts articles
B Adhesive tape
4 Drain hose
1
C Saddle(L.S)with screws G
Screw
9 Hexagon wrench 1
tha
n1
0 cm
re
mo
10 Cover 1 mo
re
tha
n1
Arrangement of piping directions 0c
m
E
13 Connecting cable 1
than
60 c
m
more
91
INSTALLATION AND ACCESSORY PARTS
HSU-12CA03 HSU-14C03 HSU-12CA13 HSU-14H13 HSU-16HA13 HSU-22CC13 HSU-12CI03 HSU-07CC03 HSU-07HE03 HSU-09HJ03
HSU-12CF03 HSU-16CC03 HSU-12CB13 HSU-16C13 HSU-16HD13 HSU-22HA13 HSU-07CD03 HSU-09CH03 HSU-09HD03
AU128ABAAA HSU-16CD03 HSU-12CC13 HSU-22CA13 HSU-22HD13 HSU-07CE03 HSU-09CJ03 AU052ACMAA
HSU-12HA03 HSU-16HC03 HSU-12CD13 HSU-22CB13 HSU-07HC03 HSU-09CK03
HSU-12HI03 HSU-16HD03 HSU-12CE13 HSU-07HD03 HSU-09HH03
HSU-12HJ03 HSU-09CA13 HSU-14C13
319.5
281
267
256
583 78 567 78
113.5 113.5
140 500 140
105 500 105
Floor fixing dimensions Floor fixing dimensions Floor fixing dimensions Floor fixing dimensions
of the outdoor unit of the outdoor unit of the outdoor unit of the outdoor unit
(Unit:mm) (Unit:mm) (Unit:mm) (Unit:mm)
Fix the unit to concrete or block with bolts( 10mm)and nuts firmly and horizontally.
Fixing of outdoor unit
When fitting the unit to wall surface,roof or rooftop,fix a supporter surely with nails or
If vibration may affect the house,fix the unit by attaching a vibration-proof mat.
Power Source
Before inserting power plug into receptacle ,check the voltage without fail.The power source is the same as the corresponded name plate.
Install an exclusive branch circuit of the power .
A receptacle shall be set up in a distance where the power cord can be reached.Do not extend the cord by cutting it .
Selection of Pipe
To this unit ,both liquid and gas pipes shall be insulated as
they become low temperature in operation. For series 05, 07,09,10 For series 11,12,14 For series 16,18,22
Use optional parts for piping set or pipes covered with
equivalent insulation material. Liquid pipe( ) 6.35mm(1/4") 6.35mm(1/4") 6.35mm(1/4")
Esp:For HSU-16HC03,HSU-16HD03,HSU-16CD03,
HSU-16CC03,HSU-16C13, gas pipe diameter Gas pipe( ) 9.52mm(3/8") 12.7mm(1/2") 15.88mm(5/8")
is also 12.7mm(1/2").
92
INSTALLATION AND ACCESSORY PARTS
Series 07,09,10,11,12,14
Heat pump model Cooling only model WHT
WHT
1(L)2(N)
BLK
YEL/GRN
1(L)2(N)
WHT
YEL/GRN YEL/GRN WHT BLK
BLK BRN YEL/GRN
BRN BRN BLK RED
RED RED
3 4
RED RED RED
3
BRN
3 4
BRN
1(L)2(N)
4
BLK YEL/GRN
1(L)2(N)
BLK YEL/GRN
WHT YEL/GRN
WHT BLK
WHT BLK WHT YEL/GRN
Indoor unit Outdoor unit
BRN
lndoor unit Outdoor unit
For HSU-16CC03,HSU-16CD03,HSU-16HC03,HSU-16HD03,HSU-16C13,
the above two terminal wiring connection is also suitable.
For HSU-07CC03,HSU-07CD03,HSU-07CE03,HSU-07HC03,HSU-07HD03,HSU-07HE03,
HSU-09CH03,HSU-09CJ03,HSU-09CK03,HSU-09HH03, HSU-09HJ03,HSU-09HK03,
AS052AZMAA, AU052ACMAA
YEL/GRN RED
4
RED
3
RED
3 4
RED
3 4
BLK BLK
BLK
2(N) 1(L)
2(N) 1(L)
1(L)2(N)
1(L)2(N)
WHT WHT
BLK
BLK
Series 16,18,22
Heat pump model Cooling only model
YEL/GRN
YEL/GRN GRY WHT YEL/GRN WHT
WHT
BRN BLK WHT
1 2 3
GRY BLK
1 2 3
BRN BRN
RED RED
RED RED BRN
BRN
4 5
4 5
YEL/GRN YEL/GRN
93
INSTALLATION AND ACCESSORY PARTS
Outdoor Unit
1 lnstallation of Outdoor Unit
lnstall according to Drawing for the installation of indoor and outdoor units
2 Connection of Pipes
Apply refrigerant oil on half union and flare nut.
To bend a pipe,give the roundness as large as possible not to crush the pipe.
Connecting the pipe of gas side first makes working easier.
Be careful that foreign matters,such as wastes of sands,etc.shall not enter the pipe.
3 Connection
Use the same method on indoor unit.Loosen
the screws on terminal block and insert the Terminal block
plugs fully into terminal block,then tighten the
screws.
Insert the cable according to terminal number
Make a loop
in the same manner as the indoor unit.
If wiring is not correct,proper operation can
not be carried out and controller may be da-
maged.
Fix the cord with a clamp.
4 Attaching Drain-Elbow
lf the drain-elbow is used, please attach it as figure.
Note:Only for heat pump unit.
Drain hose
94
INSTALLATION AND ACCESSORY PARTS
Correct lncorrect
3 On Drainage
Please install the drain hose so as to be downward slope without fail.
Please don't do the drainage as shown below.
Less than 5 cm
lt becomes high midway. The end is immersed lt waves. The gap with the ground There is the bad smell
in water. is too small. from a ditch.
Please pour water in the drain pan of the indoor unit,and confirm that drainage is
carried out surely to outdoor.
ln case that the attached drain hose is in a room,please apply heat insulation
to it without fail.
Gas leaks from pipe connecting? ls drainage securely carried out? ls the lamp normally lightening?
Heat insulation of pipe connecting? ls the earth line securely connected? Are cooling and heating(when
Are the connecting wirings of indoor ls the indoor unit securely fixed? in heatpump)performed normally?
and outdoor firmly inserted to the ls power source voltage abided by ls the operation of room temperature
terminal block? the code? regulator normal?
ls the connecting wiring of indoor ls there any noise?
and outdoor firmly fixed?
95
INSTALLATION AND ACCESSORY PARTS
Indoor Unit
1 Fitting of the Mounting Plate and Positioning of the Wall Hole
When the mounting plate is first fixed
1 Carry out,based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the
wall,then temporarily fasten the plate with one steel nail.
2 Make sure once more the proper level of the plate,by hanging a thread with a weight from the central top
of the plate,then fasten securely the plate with the attachment steel nail.
3 Find the wall hole location A using a measuring tape. Amm Bmm
HSU-09CA13 180
HSU-12CA13 210
HSU-12CG03 160
HSU-12CI03
96
INSTALLATION AND ACCESSORY PARTS
Piping
Heat insulation
material
Pipe supporting
plate
lndoor/outdoor electric cord and drain hose must be bound with refrigerant piping by protecting tape.
97
INSTALLATION AND ACCESSORY PARTS
Gas Side
9.52mm(3/8")
5 Purging Method Liquid Side (
6.35mm(1/4")
12.70mm(1/2"))
98
INSTALLATION
AND
ACCESSORY
PARTS
FOR
CFC-FREE TYPE
99
INSTALLATION AND ACCESSORY PARTS FOR CFC-FREE TYPE
7465789
A
lnstallation Manual of Room Air Conditioner
Read this manual before installation
goprufre
Explain sufficiently the operating means to the user according to this manual.
TUV Rheiniand Sicherhelt
Accessory parts
Number
No. Accessory parts of
articles Drawing for the installation of indoor and outdoor units
more than 5 cm
1 Remote controller 1 The appearance is different by models.
These models adopt CFC free refrigerant R407C
mo
2 R-03 dry battery
2 Optional parts for piping re th
an
10
cm
Mark Parts name
3 1 A Non-adhesive tape G
Mounting plate B Adhesive tape
C Saddle(L.S)with screws
4 1 Connecting electric cable mo
Drain hose D for indoor and outdoor
re
tha
n1
0c
E Drain hose m
4X50
5 Steel nail,cement
8
F Heat insulation material
G Piping hole cover F
6 1
Attention must be paid to
Main pipes H Putty A
the rising up of drain hose
8 Drain-elbow
1 About1.8m About2.5m
C
m
9 Hexagon wrench 1
tha
n 10
c
re
mo
10 Cover 1
mo
re
tha
n1
11 Cushion
4 Arrangement of piping directions 0c
m
Rear left D
12 Plastic clamp 1 Left Rear mo
right re
tha
Right n1
13 Connecting cable 1
Below
5c
m
E
14 Pipe supporting plate 1
than
60 c
m
more
HSU-09C03/R1
256
HSU-09H03/R1
HSU-12H03/R1
Floor fixing dimensions of the outdoor
unit (Unit:mm)
Fix the unit to concrete or block with bolts( 10mm)and nuts firmly and horizontally.
Fixing of outdoor unit When fitting the unit to wall surface, roof or rooftop fix a supporter surely with nails or wires in consideration of earthquake and strong wind.
If vibration may affect the house,fix the unit by attaching a vibration-proof mat.
100
Outdoor Unit 1 Power Source lnstallation
The power source must be exclusively used for air conditioner.(Over 10A)
ln the case of installing an air conditioner in a moist place,please install an
Gas Side
9.52mm(3/8') earth leakage breaker.
5 Purging Method:To use vacuum pump Liquid Side ( 12.70mm(1/2")
For installation in other places,use a circuit breaker as far as possible.
6.35mm(1/4")
1
101
2-way valve
The standard pipe length is 5m.If it is over 5m, the function of the unit will be affected.If the pipe Open the valve rod for the 2-way valve to and angle of 3-way valve
has to be lengthened, the refrigerant should be entirely discharged; after vacunmizing charge anticlockwise 90 degree.
Service port
After 6 seconds later, close the 2-way valve and male Open
the total refrigerant R407C once only, according to 16g/m. 90 90 4 90 for 6 sec.
the inspection of gas leakage.
3 Connection If it does not stop gas leakage, Less than 5 cm
102
1 Stick a paper pattern on the wall horizontally YEL/GRN WHT BLK
2 Position by using the pattern then remove YEL/GRN
lndoor/outdoor electric cable and drain hose must be bound with refrigerant piping BLK
1(L) 2(N)
RED
3 4
Cut away,with a nipper,the lid for piping according to the piping direction and then BLK YEL/GRN
bend the pipe according to the position of wall hole.When bending,be careful not
1(L) 2(N)
Fix to side bar and lintel a mounting bar, Which is separately sold,and then fasten BRN
4 Connecting the lndoor/Outdoor Electric Cable YEL/GRN RED
the plate to the fixed mounting bar.
3
RED
3 4
Refer to the previous article," When the mounting plate is first fixed ",for the BRN
4
2 Making a Hole on the Wall and Fitting the Piping Hole Cover Remove terminal cover at right bottom corner of indoor unit,then
WHT WHT BLK YEL/GRN
Make a hole of 60mm in diameter, take off wiring cover by removing its screws.
Outdoor side Indoor unit Outdoor unit
slightly descending to outside the wall lndoor side
lnstall piping hole cover and seal it Wall hole
When connecting the cable after installing the indoor unit
off with putty after installation. Thickness
of wall 1.lnsert from outside the room cable into left side of the
B mm
wall hole, in which the pipe has already existed.
2.Pull out the cable on the front side,and connect the cable making a loop.
Paper Pattern for Indoor Unit Installation Leave at Least 50mm between the
Please use this sheet to site the unit top of the unit and the ceiling
750
375
21 19 30 90 90 30 19 21
548
74.5
13
96
115.5
142
180
103
207.4
244
237
27
46.5
30
48
INSTALLATION AND ACCESSORY PARTS FOR CFC-FREE TYPE
214
139
501
HSU-09CA03/R1 HSU-09H03/R1 HSU-12CA03/R1 HSU-12H03/R1
Paper Pattern for Indoor Unit Installation Leave at Least 50mm between the
Please use this sheet to site the unit top of the unit and the ceiling
140
66 140 140 66
R30
100 100
70
240
225
104
155
0 145 145
R3
40
70
90 30 30 90
300
680
INSTALLATION AND ACCESSORY PARTS FOR CFC-FREE TYPE
HSU-09C03/R1
Paper Pattern for Indoor Unit Installation Leave at Least 50mm between the
Please use this sheet to site the unit top of the unit and the ceiling
Datum line
105
Outline of Indoor Unit
Emm Emm
Piping Hole
Piping Hole
(For rear Piping)
(For rear Left Piping)
Diameter of Piping Hole Diameter of Piping Hole
60mm 60mm
60 60
mm mm
40mm
40mm
INSTALLATION AND ACCESSORY PARTS FOR CFC-FREE TYPE
Model A B C D E
106
MAINTENANCE AND SERVICE
(7) In heating starting operation, the outdoor unit starts but the indoor unit does not run. This is
cold prevention function in heating operation. Only when the temperature of indoor unit can Reaches
Certain degree, it can start. (Normally this needs several minutes.)
4 maintenance:
(1)Do not pour water on indoor unit, electric or technical problems will occur.
(2)Be sure to pull out power plug before cleaning. Never pull the electric cable.
(3)Do not block the inlet or outlet.
(4)Do not use for other purpose, such as food preservation, animal breeding.
(5)Use soft cloth to clean unit casing, for serious stains. Use with water wiring the water
out of the cloth before wiping. Wipe off the cleaners, as these will damage the coating.
Also hot water over 40 may cause discoloring or deformation.
(6)Do not use water to clean remote controller, instead to wipe it with a place of dry cloth.
Do not use glass cleaner or a chemical cloth.
(7)As heating exchenger of outdoor is exposed in open air, dust may accumulate a time goes by,
which will reduce its performance. Clean it periodically with vacuum cleaner or water,
but do not use steel brush.
5 service
10.5.1 Unit does not work
(1) Cause: power supply
Remedy :
Check the power receptacle if it is broken or poor contact , repair it.
Check the indoor or outdoor cable if wrongly connected (refer to wiring diagram),correct
the wrong wring .
(2)Cause:Fuse blown out
Remedy:
Confirm if fuse is blown out . Replace the bad fuse, including the power supply fuse and
fuse on control circuit.
(3)Cause:voltage too low
Remedy:
Voltage is 15% lower than the rating (1PH,187V).Find out the cause. If voltage is too low,
voltage regulator is needed .
(4)Cause:improper temperature setting
Remedy:
Make sure if there are some loosen parts, and if sensor is moved out of place. Check the
relevant contact. Using multimeter if there is poor contact. Refer to wiring diagram.
(5)Cause:starting relay fails
Remedy:
Normally the starting relay of voltage type is in normal close status. Check it with a
multimeter, and replace it if it fails.
Overload protector should, under contact temperature, in contact status. Or it is detective
and need be replaced.
(6)Cause:compressor burnt
Remedy:
Terminal R.S.C. represent run, start, and common terminal respectively.
The sin of resistance of starting winding and running winding equals the total winding.
Namely, Rst = Rcs +Rcr , measure with a multimeter, if there are short circuit, break, or
ground leakage due to casing contact. Replace the compressor of the same specifications
and brand.
(7)Cause compressor got stuck
Remedy:
If the winding of the compressor is ok, try to strike the compressor casing with either a
rubber hammer keeps on and off.
6 Air conditioner keep on and off
108
MAINTENANCE AND SERVICE
109
MAINTENANCE AND SERVICE
Remedy:
Using piping correctly. Do not exceed the specified pipe length.
(3)Inner leakage of the 4 - way valve causing malfunction.
Remedy:
Check the 4 - way valve and replace it if it is defective.
(4)Clogged capillary tube causing high suction temperature.
Remedy :
Clean capillary tubes or replace it.
(5)Cause:clogged strainer , causing high suction temperature.
Remedy:
Replace: capillary tube assy
(6)Cause:high running current
Remedy:
After measuring the current with a clamp meter, check power supply voltage to find out
the causes for abnormal power supply.
(7)Cause:overload because of too much Freon.
Remedy:
Discharge and suction pressure have rised to activate protector.
(8)Cause:compressor does not run properly, rotor got stuck.
Remedy:
Replace compressor after confirmation.
(9)Cause:OLP (protector relay) itself is detective.
Remedy:
Check the contact with a Multimeter, if it is closed when there is no overheat. in case it
is not closed, replace with a new OLR.
9 water leakage on air conditioner:
(1)Cause:drain hose joint is not tight.
Remedy:
Fix the joint again and bind it tightly with tape.
(2)Cause:condense hose is bent or pressed.
Remedy:
Check the drain hose and arrange it correctly. Replace if broken.
(3)Cause:too much dirt in drain pan, clogging drain hose.
Remedy:
Clean the drain pan and drain hole.
(4)Cause:indoor unit is install titled
Remedy:
Correct its installation position.
10 the split unit does not make cooling run after installation:
(1)Cause:gas leakage during pipe connection.
Remedy:
Open the heat insulation for leakage's detect. Add refrigerant after fixing.
(2)Cause:there are damages or crashes to the gas and liquid pipe or indoor and
outdoor unit connecting pipe.
Remedy:
Replaced the damaged part of piping , then charge refrigerant after pressure testing and
pumping down.
(3)Cause:wrong wiring
Remedy:
Inspect the wiring according to the wiring diagram. Repair the control line if there is
any problem.
(4)Cause:compressor burnt (because of wrong wiring) .
110
MAINTENANCE AND SERVICE
COOL ON HEAT
1 1
temp.Setting Temp.Setting +3
(3)Defrost operation
During HEAT operation, 4 - way valve is energized, when it is reenergize, defrost
111
MAINTENANCE AND SERVICE
operation will begin, indoor unit and outdoor unit fan stop, while comp. Is still running.
After 10minutes, HEAT operation resumes with the 4 -way valve energized. Outdoor fan
starts running, but the indoor fan does not work until evaporator warms up.
(4) Frost - prevention for evaporator during COOL and DEFROST operation . If indoor
heat exchanger temp . Stays below 0 for 5 minutes , comp. And outdoor fan will stop.
(5) When comp. Stops only after 3 minutes can it be restarted.
(6) Computer detects the indoor unit temp. From its temp. Sensor , while the curent
transformer (CT) monitors the comp. Current to protect it against overheat and over
current. As a result the proper operation of the unit is ensured.
Prevention against over current
when CT detects high current on compressor.It will first stop outdoor fan then resume the
fan operation when current become normal. Should the current keeps rising, both the
compressor and the outdoor fan will be stopped.
prevention agaist overload in heat operation
During heat operation, if indoor unit temperature sensor detects high temperature, it will
first stop the outdoor fan then resume the fan operation when the temperature becomes normal.
If the temperature keeps rising, both the compressor and the outdoor fan will be stopped.
Comp. and outdoor fan operation.
Compressor and outdoor fan stop abnormally
112
MAINTENANCE AND SERVICE
113