Sunteți pe pagina 1din 18

Battery & Battery Charger Sizing Calculation for

MIRSHARAI EZ 230/33KV NEW GIS SUBSTATION

 Project Name: Design, supply, installation, testing and commissioning of


230/33KV Substation at Mirsharai EZ and extension of 230KV GIS bays at
existing 230/33KV BSRM Substation on turnkey basis..

 Contract No.: PGCB/230KV/MIRSHARAI-BSRM/SS DATED: 26/07/2018

 Substation Name: MIRSHARAI EZ 230/33KV NEW GIS SUBSTATION.

 Contractor: ENERGYPAC ENGINEERING LTD.

 Client: POWER GRID COMPANY of BANGLADESH


CONTENTS

Page No.

1 INTRODUCTION 3

2 DESIGN CRITERIA FOR BATTERY SIZING 3

3 CALCULATION FOR NUMBER OF CELLS 4

4 DESIGN CRITERIA FOR BATTERY CHARGER SIZING 5

5 REFERENCES 5

6 ASSUMPTIONS 5

7 CALCULATION 6-13

i 110V DC LOAD DETAILS 6-7


ii LOAD SUMMARY 7
iii LOAD CYCLE TABLE & GRAPH 8
iv AH SIZING CALCULATION OF BATTERY & BATTERY CHARGER 9-12

8 RESULT 5

9 ANNEXURES:-

i DVR Calculation

ii UPS Sizing

iii K- factor curves (HBL)

iv Temperature correction factor (HBL)


1 INTRODUCTION:
DC Power Supply is the most reliable source of power supply for control, protection
interlock & annunciation requirements both during the AC power failure and in normal
operating conditions.

This document is intended to size the 110V Ni-Cd battery &


battery charger required for 230/33kV Substation at Mirsharai. The
battery is sized in accordance with the IEEE 1115-2000
110V DC Power supply will consist of two number 100% rated battery along
with two number of 100% rated dual float cum boost charger to charge above
batteries.

2 DESIGN CRITERIA FOR BATTERY SIZING:


The duty cycle of battery is selected to be 5 hours. The battery shall be capable
of :

i Two closing operations on all circuit breakers (including future) supplied by


the battery.

ii Two tripping operations on all circuit breakers (including future) supplied by the
battery. Where busbar protection is provided, it shall be assumed that all circuit
breakers in any one busbar protection zone trip simultaneously.

iii Charging of DC motor wound circuit breaker closing springs to enable the closing
operations is considered.

iv Battery can supply load at discharge rate of 10 hours without terminal voltage
drop from rated voltage.

v margin of 10% is considered for de-rating of the battery.

Accordingly, the load cycle is divided into six sections:


The section, corresponding time Ƭ considered load are as follows :

Section Number Time Period Load Considered


Momentary Tripping load +Continuous load +
Section - 1 0-1 min.
Emergency loads + motor
Momentary Closing load +Continuous load +
Section - 2 1-2 min.
Emergency loads
Section - 3 2-60 min. Continuous load +Emergency loads
Section - 4 60 -298 min. Continuous load
Section - 5 298 -299 min Momentary Tripping load+ Continuous load + motor
Section - 6 299 -300 min Momentary Closing load+ Continuous load

The minimum temperature is 4 °C


Design margin of 10% and Ageing Factor of 15% is considered on calculated size.

Page-3
3 CALCULATION FOR NUMBER OF CELLS

Nominal Voltage of the system = 110 V

Maximum Allowable system voltage percentage = +10 %

Maximum allowable system voltage = 121 V

Minimum allowable system voltage = -20 %

Minimum allowable system voltage = 88 V

End cell voltage = 1.1 V

Float charging voltage = 1.4 V

Maximum allowable system voltage


No. of cells (Cell) required =
cell voltage required for float charging

= 121 / 1.4
= 86.4

Minimum No. of cells required = 87.00

No. of cells selected = 92.00

Minimum battery voltage at the end of load cycle = No. of cells x End cell Voltage

= 92×1.1
= 101.2 V
Which is higher than the minimum allowable system voltage

Hence, the number of cells selected as 92 is justified.

Page-4
4 DESIGN CRITERIA FOR BATTERY CHARGER SIZING

The battery charger is sized based on two numbers of applications envisaged.

i Under normal float charge conditions (with AC supply available), the battery
charger will cater to the continuous load of the DC system plus trickle charging
of the battery. It shall be possible to switch either charger out of service leaving
the remainder charger & batteries to carry the full DC load requirement & the
same time provide the full battery float charge requirement of the associated
battery.
ii The batteries may require boost charging from time to time, depending upon the
service conditions & other external forces. Under boost charge condition the
charger shall be capable of supplying full boost charge requirement, taking care
not to exceed the maximum permissible battery voltage & simultaneously cater
to the continuous load requirement of the DC system.

The higher of the two ratings (float charging condition & boost charging cond
-itions calculated as above) will be considered for rating the charger

5 REFERENCES
1. Project contract documents & Specification
2. IEEE 1115-2000
3. Mirsharai 230/33KV GIS sld
4. Manufacturer published catalogues of various relays
5. Battery Catalouge

6 ASSUMPTIONS

i The calculation is performed based on published data for HBL NCPP Battery
Technical Manual

ii Total Emergency lighting load is considered 600 W.

iii DC Load details are considered based on our standard 230kV product

7 CALCULATIONS

i 110V DC Load details


ii Load summary
iii Load cycle table & Graph
iv AH Sizing calculation of Battery & Battery Charger

8 RESULTS
i 110V Battery Size Selected 461 AH
ii Charger Selected 92.2 A

Page-5
Table -1

POWER Fire fighting


POWER BATTERY No of Continuous Closing Tripping Emergency
EQUIPMENT LOCATION & NO. NO. CONSUMPTION( Co efficient equipment Motor REMARKS
CONSUMPTION(Watt) VOLTAGE Panels Load Peak peak Lighting
Watt) peak

Emergency Light 30 Control room building 20 600 1 0 0 0 0 0 600

Meter 5 1 20 1 20 0 0 0 0 0
Line feeder Control panel
Indicator 2 8 4 64 1 64 0 0 0 0 0
×(4 nos.)
FBCU(7SJ85) 40 1 160 1 160 0 0 0 0 0

Indicator 2 3 24 1 24 0 0 0 0 0
7SA87 30 1 120 1 120 0 0 0 0 0
7SL87 30 Line feeder Relay panel 1 120 1 120 0 0 0 0 0
4
7SS523 12 ×(4 nos.) 1 48 1 48 0 0 0 0 0
TCS 15 2 120 1 120 0 0 0 0 0
MVAJ 150 4 2400 1 0 0 0 2400 0 0

FBCU(7SJ85) 40 1 80 1 80 0 0 0 0 0
Indicator 2 Transformer Feeder control 8 32 1 32 0 0 0 0 0
2
panel×(2Nos)
Meter 5 1 10 1 10 0 0 0 0 0

Indicator 2 3 12 1 12 0 0 0 0 0
7SA87 30 1 60 1 60 0 0 0 0 0
MVAJ 150 Transformer Feeder Relay 4 110V 1200 1 0 0 0 1200 0 0
2
7SL87 30 panel×(2Nos) 1 60 1 60 0 0 0 0 0
7SS523 12 1 24 1 24 0 0 0 0 0
TCS 15 2 60 1 60 0 0 0 0 0

TCS 15 2 60 1 60 0 0 0 0 0
MVAJ 150 Bus coupler control and relay 2 600 1 0 0 0 600 0 0
Meter 5 1 2 10 1 10 0 0 0 0 0
panel(2 nos)
FBCU(7SJ85) 40 1 80 1 80 0 0 0 0 0
Indicator 2 9 36 1 36 0 0 0 0 0

Busbar protection central


7SS522 12 1 1 12 1 12 0 0 0 0 0
unit

TCS 15 2 60 1 60 0 0 0 0 0
Indicator 2 4 16 1 16 0 0 0 0 0
Meter 2 1 4 1 4 0 0 0 0 0
Bus section CRP 2
FBCU(7SJ85) 40 2 160 1 160 0 0 0 0 0
7SS523 12 2 48 1 48 0 0 0 0 0
MVAJ 150 2 600 1 0 0 0 600 0 0

Disconnector 5 DISCONNECTOR 24 120 0.5 60 0 0 0 0 0

GCB Drive
10 10 100 0.5 50 0 0 0 0 0
Box(132KV)

Fire Fighting
200 2 400 0.5 200 0 0 0 0 0
equipments

UPS for SAS 1500 1 1500 1 1500 0 0 0 0 0

Total power For ten feeders 3310 0 0 4800 0 600


Table-2
POWER
POWER Continuous Tripping Motor(DS & Emergency
EQUIPMENT LOCATION & NO. NO. CONSUMPTION( Co efficient Closing Peak Motor(CB) REMARKS
CONSUMPTION Load peak DS/ES) Lighting
Watt)
Tripping
526 24 12624 1 0 12624
coil
230kV CB Single Pole 4Nos.
closing
526 12 6312 1 0 6312
coil
8000 14700
Tripping
526 12 6312 1 0 6312
coil
230kV CB Gang operated 6nos
closing
526 6 3156 1 0 3156
coil
0 9468 18936 8000 14700 0
Simultaneity of feeders 1 0.5 1 0.5 0.3 1
Power for all 10 feeders 0 4734 18936 4000 4410 0

Summation of table 1 & 2


Closing Tripping Emergency
Continuous Load Motor
Peak peak Lighting
Table 1 3310 0 4800 600 0
Table 2 0 4734 18936 0 8410
Total Power 3310 4734 23736 600 8410
Total Current 30.09 43.04 215.78 5.45 76.45455
LOAD CYCLE TABLE & GRAPH

Period (min) Duration LOAD DESCRIPTION LOAD(A)

0--1 1 min Momentary tripping load+continuous load+emergency load+Motor (215.78+30.09+5.45+76.45)= 327.77 A


1--2 1 min Momentary closing load+continuous load+emergency load (43.04+30.09+5.45) = 78.58 A
2--60 58 min continuous load+emergency load (30.09+5.45) = 35.54 A
60--298 238 min continuous load (30.09) = 30.09 A
298--299 1 min Momentary tripping load+continuous load+Motor (215.78+30.09+76.45) = 322.32 A
299--300 1 min Momentary closing load+continuous load (43.04+30.09) = 73.13 A

LOAD
345.00
340.00
335.00
330.00
325.00
320.00
315.00
310.00
305.00
300.00
295.00
290.00
285.00
280.00
275.00
270.00
265.00
260.00
255.00
250.00
245.00
240.00
235.00
230.00
225.00
220.00
215.00
210.00
205.00
200.00
CURRENT(AMPERE)

195.00
190.00
185.00
180.00
175.00
170.00
165.00
160.00 LOAD
155.00
150.00
145.00
140.00
135.00
130.00
125.00
120.00
115.00
110.00
105.00
100.00
95.00
90.00
85.00
80.00
75.00
70.00
65.00
60.00
55.00
50.00
45.00
40.00
35.00
30.00
25.00
20.00
15.00
10.00
5.00
0.00
0
6
12
18
24
30
36
42
48
54
60
66
72
78
84
90
96
102
108
114
120
126
132
138
144
150
156
162
168
174
180
186
192
198
204
210
216
222
228
234
240
246
252
258
264
270
276
282
288
294
300
TIME(MINUTE)
Nominal Temperature 45 Nominal Cell Cell Mfg: Cell Type:
Voltage
Lowest 20ᵒC HBL Nickel Cadmium
1.2V
Highest 45

(1) (2) (3) (4) (5) (6) (8)


Period Load(Amperes) Change in Load Duration of Period Time to End of Capacity Rating Required Section
(Amperes) (Minutes) section(Minutes) Factor (kt) Size(3)×(6)
=Rated Amp Hrs
Section 1-First 1 Period(s) Only-if A2 is greater than A1. Go to section 2
1 A1 A1-A0 M1 t=M1
327.77 327.77 1.00 1.00 0.67 219.61
Total 219.61

(1) (2) (3) (4) (5) (6) (8)


Period Load(Amperes) Change in Load Duration of Period Time to End of Capacity Rating Required Section
(Amperes) (Minutes) section(Minutes) Factor (kt) Size(3)×(6)
=Rated Amp Hrs
Section 2-First 2 Period(s) Only-if A3 is greater than A2. Go to section 3
1 A1 A1-A0 M1 t=M1+M2
327.77 327.77 1.00 2.00 0.72 235.99
2 A2 A2-A1 M2 t=M2
78.58 -249.19 1.00 1.00 0.67 -166.96
Total 69.04

(1) (2) (3) (4) (5) (6) (8)


Period Load(Amperes) Change in Load Duration of Period Time to End of Capacity Rating Required Section
(Amperes) (Minutes) section(Minutes) Factor (kt) Size(3)×(6)
=Rated Amp Hrs
Section 3-First 3 Period(s) Only-if A4 is greater than A3. Go to section 4
1 A1 A1-A0 M1 t=M1+M2+M3
327.77 327.77 1.00 60.00 1.7 557.21
2 A2 A2-A1 M2 t=M2+M3
78.58 -249.19 1.00 59.00 1.68 -418.64
3 A3 A3-A2 M3 t=M3
35.54 -43.04 58.00 58.00 1.67 -71.88
Total 66.69
(1) (2) (3) (4) (5) (6) (8)
Period Load(Amperes) Change in Load Duration of Period Time to End of Capacity Rating Required Section
(Amperes) (Minutes) section(Minutes) Factor (kt) Size(3)×(6)
=Rated Amp Hrs
Section 4-First 4 Period(s) Only-if A5 is greater than A4. Go to section 5
1 A1 A1-A0 M1 t=M1+M2+M3+M4
327.77 327.77 1.00 298.00 5.15 1688.02
2 A2 A2-A1 M2 t=M2+M3+M4
78.58 -249.19 1.00 297.00 5.14 -1280.84
3 A3 A3-A2 M3 t=M3+M4
35.54 -43.04 58.00 296.00 5.13 -220.80
4 A4 A4-A3 M4 t=M4
30.09 -5.45 238.00 238.00 4.15 -22.6175
Total 163.77

(1) (2) (3) (4) (5) (6) (8)


Period Load(Amperes) Change in Load Duration of Period Time to End of Capacity Rating Required Section
(Amperes) (Minutes) section(Minutes) Factor (kt) Size(3)×(6)
=Rated Amp Hrs
Section 5-First 5 Period(s) Only-if A6 is greater than A5. Go to section 6
1 A1 A1-A0 M1 t=M1+M2+M3+M4+M5
327.77 327.77 1.00 299.00 5.16 1691.29
2 A2 A2-A1 M2 t=M2+M3+M4+M5
78.58 -249.19 1.00 298.00 5.15 -1283.33
3 A3 A3-A2 M3 t=M3+M4+M5
35.54 -43.04 58.00 297.00 5.14 -221.23
4 A4 A4-A3 M4 t=M4+M5
30.09 -5.45 238.00 239.00 4.19 -22.8355
5 A5 A5-A4 M5 t=M5
322.32 292.23 1.00 1.00 0.67 195.7941
Total 359.70

(1) (2) (3) (4) (5) (6) (8)


Period Load(Amperes) Change in Load Duration of Period Time to End of Capacity Rating Required Section
(Amperes) (Minutes) section(Minutes) Factor (kt) Size(3)×(6)
=Rated Amp Hrs
Section 6-First 6 Period(s) Only-if A7 is greater than A6. Go to section 7
1 A1 A1-A0 M1 t=M1+M2+M3+M4+M5+M6
327.77 327.77 1.00 300.00 5.17 1694.57
2 A2 A2-A1 M2 t=M2+M3+M4+M5+M6
78.58 -249.19 1.00 299.00 5.16 -1285.82
3 A3 A3-A2 M3 t=M3+M4+M5+M6
35.54 -43.04 58.00 298.00 5.15 -221.66
4 A4 A4-A3 M4 t=M4+M5+M6
30.09 -5.45 238.00 240.00 4.2 -22.89
5 A5 A5-A4 M5 t=M5+M6
322.32 292.23 1.00 2.00 0.72 210.4056
6 A6 A6-A5 M6 t=M6
73.13 -249.19 1.00 1.00 0.67 -166.96
Total 207.65
Maximum section size = 359.7 AH

Required size = Maximum section size x Design margin x Temperature correction


factor x Aging factor

Battery size calculated = 455.0205 AH

Battery size selected = 461 AH

Standing DC loading for Protection, Control, Indications and alarms = (230kV line feeder control
and relay panel load + 230/33KV transformer feeder control and relay panel load + 230KV Bus
coupler control and relay panel load + Busbar protection central unit panel load + Bus section
control and relay panel load)

= (244 + 432 + 122 + 216 + 186 + 12 + 288) Watts [ values were taken from Table 1]

= 1500 Watts

= 13.63636364 Amp.

Battery size selected = 461 AH

Battery can backup the above mentioned load upto (461 / 13.636363) = 33.8 Hours

Which Fulfills PGCB’s requirement.

Page-11
FLOAT CUM BOOST CHARGER SIZING CALCULATION

SELECTED BATTERY SIZE = 461 AH


DC Nominal Voltage = 110 V
A) FLOAT CHARGER RATING
Float Charger Rating = (Continuous load current + Float charging current)
Continuous Load Current = 30.09 A
Float Charging Current = 2 mA per AH rating of battery
= 0.92 A
Float Charger Rating Calculated = 31.01 A
Design Margin = 10%
Rating of Battery Charger = 34.11 A

B) BOOST CHARGER RATING


Boost Charger Rating = 20% of AH Rating of battery
Boost Charger Rating Calculated = 92.2 A
Battery Charger Rating Selected = 92.2 A

RESULT

No. of Battery Cells = 92 Nos.

AH Capacity = 461 AH.

Boost Charger rating = 92.2A at 110V DC

Page-12
ANNEXURE-1
DVR Calculation
Number of Boost Voltage Total Boost Nominal Load % of Max Max load Required Voltage Voltage Drop at
No of Diode
Cell Per cell Voltage Voltage Voltage Voltage Drop At DVR Single Diode
110VDC
92 1.53 140.76 110 5 115.5 25.26 0.8 31.58
ANNEXURE-2

Local Station- UPS

Sr.No Equipment Description Power Req No of Unit Actual


Consumption
1 HMI PC 300 3 900
2 Disturbance Recorder 100 1 100
3 Ethernet Switches 40 6 240
4 TFT Monitors 60 3 180
5 Laser Color Printer 190 2 380
6 GPS Time Sync Equipment 15 1 15
7 Gateway 15 2 30
TOTAL 1845 W

Power Factor = 0.8

KVA Requirement = 2.30625 kVA

Considering 85% Efficiency


And avg. diversity factor = 1273.05 W
Of 0.6 of UPS

Hence, Load on battery(W) = 1280 W

S-ar putea să vă placă și