Documente Academic
Documente Profesional
Documente Cultură
S
UPERCONDUCTING MAGNETIC Power (AEP) [9], [10], to provide reactive power/voltage
0.1 1 10 100 1,000 1 10 100 1,000 10,000 transformers and linked to a dc ca-
pacitor in the dc side. The value of
MWs MWh
the dc link capacitor has been se-
Energy
1
lected as 10 mF in order to obtain
smooth voltage at the StatCom ter-
SMES power and energy requirements for potential electric utility applications. minal bus.
Capacitor Bank
53 MVA Bus D
2
22 AC system equivalent.
StatCom
DC-DC Chopper
Tmva = 80
Terminal Bus
StatCom
DC Capacitor
Tmva = 80
SMES Coil
3
Detailed representation of the StartCom, dc-dc chopper, and SMES coil.
As stated in [12] and [13], a GTO-based inverter con- To generate the gating signals for the inverters, line to
nected to a transmission line acts as an alternating voltage ground voltages are used for the inverter connected to the
source in phase with the line voltage, and, depending on the Y-Y transformer, whereas line-to-line voltages are uti-
voltage produced by the inverter, an operation of inductive lized for the inverter connected to the Y-∆ transformer.
or capacitive mode can be achieved. It has also been empha- This model and control scheme is partly based on the
Power at StatCom
Terminal As shown in Figure 5, the
Hard Limit 1 = Ctrl duty cycle is controlled in two
Porder ways. Three measurements are
Ctrl used in this chopper-SMES con-
SMES Current trol: SMES coil current (CISMES),
ac real power (SPmeas) measured
trigstab
Icharging at the StatCom terminal bus,
and dc voltage (dcvolt) measured
Rate Limited to
Hard Limit 10,000/sec across the dc-link capacitor.
DC Cap. The SMES coil is initially
Voltage
charged with the first control
scheme, and the duty cycle is set
to 0.5 after reaching the desired
stabduty
Case Studies
Gate Signals In order to demonstrate the ef-
to DC-DC Chopper
fectiveness of the StatCom-
SMES combination, several cases
5 are simulated. A three- phase
fault is created at Bus D of Fig-
24 SMES and chopper control. ure 2 to generate dynamic oscil-
lations in each case. The plot 388 388
time step is 0.001 s for all the
figures given in these cases. 384 384
50 50
0 0
−50 −50
−100 −100
3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5
Time (s) Time (s)
100 100
0 0
−100 −100
−200 −200
3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5
Time (s) Time (s)
(a) (b)
7
Real and reactive power responses of the StatCom-SMES.
3.8 3.8
SMES Current (kA)
3.6 3.6
I EEE I NDUSTRY A PPLI CA TI ONS MA GA ZI NE • MA R|A PR 2003 • WWW.I EEE.ORG/I A S
3.5 3.5
3.4 3.4
3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5
Time (s) Time (s)
Average SMES Voltage (kV)
Average SMES Voltage (kV)
30 30
20 20
10 10
0 0
−10 −10
−20 −20
−30 −30
3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5
Time (s) Time (s)
32 32
SMES Current (kA)
DC Voltage (kA)
28.5 28
25 24
21.5 20
18 16
3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5
Time (s) Time (s)
90 90
SMES Energy (MJ)
86 86
82 82
78 78
74 74
70 70
3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5
Time (s) Time (s)
(a) (b)
8
26 SMES operation. (a) StatCom-SMES at Bus B. (b) StatCom-SMES at Bus A.
represent the injected power from the when a 100-MVA load at power factor of
device to the ac system. When compared 0.85 is connected to Bus B. The existence
to no compensation and StatCom-only THE of the load forced the controller to be oper-
cases, shown in Figure 6, both frequency
and voltage oscillations were damped
MODULATION ated closer to its maximum rating. The
performance of the compensator to ac sys-
out faster. OF REAL POWER tem oscillations showed similar results, as
obtained in the previous two cases.
Compensator Located at Bus A CAN HAVE A Again, when the combined compen-
The StatCom-SMES combination is now sator is located at Bus A, it shows better
connected to the ac power system at a bus MORE damping performance.
near the generator bus. The same scenario
drawn in the previous section applies to SIGNIFICANT Reduced Rating in StatCom-SMES
this case. The results are shown in the
fourth column of Figure 6. Compared to INFLUENCE ON While keeping the compensator loca-
tion at Bus B, the performance of
other two cases, StatCom-SMES con-
nected to a bus near the generator shows
DAMPING StatCom-only at full rating is compared
to the performance of StatCom- SMES at
very effective results in damping electro- POWER SWINGS reduced rating. The power rating of the
mechanical transient oscillations caused SMES and StatCom were reduced to half
by a three-phase fault. THAN REACTIVE of their original ratings (80 Mvar,
50-MW peak). The energy level of the
Performance of the POWER ALONE. SMES was kept the same, however, the
StatCom-SMES at Different Locations real power capability of the SMES was
The real and reactive power responses of decreased. The SMES coil was charged
the compensator to oscillations are com- until it reached the desired charging
pared for different locations. Figure 7 compares the StatCom current level, which took twice the time since the termi-
real and reactive power responses for these previous cases nal voltage was lower. A three-phase fault is created at 5.6
(StatCom-SMES at Bus B and StatCom-SMES at Bus A). s for 0.15 s, and the responses of the StatCom-SMES ver-
When the StatCom-SMES is located at Bus B, it provides a sus StatCom-only to the power swings are compared in
voltage support by injecting approximately 50 MVA and Figure 9.
References
[1] W.V. Hassenzahl, “Superconducting magnetic energy storage,”
A.B. Arsoy (aysen@ieee.org) is with Kocaeli University in Izmit
Kocaeli, Turkey. Y. Liu (yilu@vt.edu) is with Virginia Tech in
Proc. IEEE, vol. 71, pp. 1089-1098, Sept. 1983.
Blacksburg, Virginia, USA. P.F. Ribeiro (pribeiro@cal-
[2] Y. Mitani, K. Tsuji, and Y Murakami, “Application of supercon- vin.edu) is with Calvin College in Grand Rapids, Michigan,
ducting magnetic energy storage to improve power system dy- USA. F. Wang (f.wang@ieee.org) is with GE Industrial Sys-
namic performance,” IEEE Trans. Power Syst., vol. 3, pp. tems in Salem, Virginia, USA. This article first appeared in its
28 1418-1425, Nov. 1988. original format at the 2000 IEEE IAS Annual Meeting.