Sunteți pe pagina 1din 11

42 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO.

1, JANUARY 2011

Investigation of the Local Passive Anti-Islanding


Scheme in a Distribution System Embedding a
PMSG-Based Wind Farm
Walid El-Khattam, Member, IEEE, Amirnaser Yazdani, Senior Member, IEEE, Tarlochan S. Sidhu, Fellow, IEEE,
and Ravi Seethapathy, Senior Member, IEEE

Abstract—This paper evaluates the effectiveness of different [7], as a result of the network’s loss of neutral conductor. Thus,
commercial relay functions in a local passive anti-islanding process to circumvent the foregoing scenario, local distribution com-
for a permanent-magnet synchronous generator (PMSG)-based panies (LDCs) attempt to disconnect all distributed generators
wind farm which is interfaced with a radial distribution network.
The results are obtained through a comprehensive set of real-time within the island, by means of various anti-islanding tech-
simulation studies, conducted on a detailed topological model of a niques, once an island forms. The IEEE and other organizations
single-machine equivalent of the PMSG-based wind farm and the have identified anti-islanding standards [8]–[10]. As such, a
network, using three different commercial relays. The paper intro- number of anti-islanding techniques have already been adopted
duces the study set-up and methodology and, additionally, details commercially [5], [6], [11]–[13].
of the mathematical and simulation models of the PMSG-based
wind farm. The models and the methodology presented in this The existing anti-islanding schemes can be broadly classi-
paper can be used, directly or with minor modifications, for many fied as communication-based and local schemes. Communica-
other impact-assessment studies. tion-based schemes, which can be based on a variety of media
Index Terms—Direct-drive distribution system, local passive is- and techniques, are reliable and theoretically have zero (practi-
landing detection, permanent-magnet synchronous generator, pro- cally negligible) non-detection zones. However, they are costly
tection, PWM, relay, wind energy. due to their reliance on point-to-point communications. Local
schemes, however, process the point-of-connection current and
voltage signals of a distributed generator. Thus, they respond
I. INTRODUCTION to excursions of certain derivatives of the measured signals, in
order to detect the formation of an island.

W IND energy is the fastest-growing technology amongst


different distributed generation technologies [1], [2].
Distributed generation can positively or negatively affect the
Local anti-islanding schemes can themselves be divided into
passive and active schemes. Active anti-islanding schemes de-
tect an island by deliberate imposition of disturbances on the
interconnection points [3]. For example, in radial distribution host network, directly through the distributed generators, and
networks, distributed generators can cause bidirectional power are especially convenient to be incorporated in electronically-in-
flows, alter the existing voltage profiles, affect the operation terfaced generators. Thus, they introduce periodic small distur-
and coordination of the existing protection devices such as bances to the network (which is considered their main disadvan-
relays, reclosers [4], etc., and compromise safety. In partic- tage) and detect the formation of islands by local measurements
ular, they can cause energized electric islands within the host [12]. By contrast, passive anti-islanding schemes solely rely on
networks [5], [6]. These islands can form due either to faults local measurements of the point-of-connection voltage/current
causing an upstream feeder breaker to open automatically, or to signals, with no introduction of artificial disturbances. There-
inadvertent opening of the breaker for maintenance operations. fore, passive anti-islanding schemes do not disturb the network
The concern is that a sustained electric island can entail power and thus do not cause power quality problems [7].
quality problems, disturb power restoration during out-of-phase This paper evaluates the suitability of commercial relays
reclosing, and cause severe overvoltage transients due to the and their functions for the local passive anti-islanding process.
islanded feeder capacitance and existing shunt capacitor banks Specifically, a wind farm based on the direct-drive permanent
magnet synchronous generator (PMSG) is considered in this
Manuscript received February 24, 2010; revised May 14, 2010; accepted June paper, as an aggregate of distributed generators interfaced with
05, 2010. Date of publication September 07, 2010; date of current version De-
cember 27, 2010. This work was supported by the Hydro One Network Inc.
a distribution network. Thus, the idea is to equip the wind
Paper no. TPWRD-00134-2010. farm with a commercial relay installed at the point of common
W. El-Khattam, A. Yazdani, and T. S. Sidhu are with the Department of coupling (PCC), and to utilize the built-in functions of the
Electrical and Computer Engineering, The University of Western Ontario,
London, ON, N6A 5B9, Canada (e-mail: walid.elkhattam@uwo.ca; ayaz-
relay for anti islanding. The evaluation is based on real-time
dani@eng.uwo.ca; sidhu@eng.uwo.ca). laboratory tests conducted on three commercial relays with
R. Seethapathy is with Hydro One Networks Inc., Toronto, ON, Canada different functions, in conjunction with a detailed time-domain
(e-mail: ravi.seethapathy@hydroone.com). simulation of the wind farm and a real distribution network.
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. The study reported in this paper identifies the most effective
Digital Object Identifier 10.1109/TPWRD.2010.2061240 relay functions for the local passive anti-islanding process,
0885-8977/$26.00 © 2010 IEEE
EL-KHATTAM et al.: INVESTIGATION OF THE LOCAL PASSIVE ANTI-ISLANDING SCHEME 43

Fig. 1. Signals typically used for local passive anti-islanding process.

along with the test/simulation set up used to obtain the results.


Further, the paper presents the mathematical model and the
steps taken for the development of the PMSG-based wind farm
model. The models and the methodology presented in this
paper can be used, directly or with minor modifications, for
many other impact-assessment studies.

II. COMMERCIAL RELAY FUNCTIONS FOR ANTI-ISLANDING


Fig. 1 illustrates the signals that carry the signature of a dis- Fig. 2. Simplified schematic diagram of the study distribution network.
turbance and are typically processed by relay functions to reveal
the formation of an island. The signals are tested in terms of the
following phenomena. Fig. 3(a) illustrates the LDC’s recommended sequence of
1) Over-/under-voltage (OV/UV) excursions due primarily to events prompted by a fault incident. As shown in Fig. 3(a), the
the reactive-power mismatch between the (aggregates of) fault is assumed to take place at . Then, subject to a max-
generators and loads within the islanded portion of a net- imum average fault detection delay of about 33 ms, the main
work [7]; breaker relay detects the fault, commands the main breaker to
2) Over-/under-frequency (OF/UF) excursions due to the open, and initializes the main recloser timer. Two types of main
real-power mismatch between (the aggregates) of genera- reclosers are assumed in this study to explore the possibility of
tors and loads within the islanded portion of a network [7]; utilizing a fast recloser. The two reclosers are hereafter referred
3) Rates of change of the generators real power output [11] or to as Recloser A and Recloser B, having delays of 1000 ms
frequency (ROCOF) [7], [13]; and and 500 ms respectively, as specified by the LDC. Therefore,
4) Voltage vector phase-angle shift (Vshift) [7], [10]. the distribution network is reconnected to the main grid at
In this paper, a number of relay functions are evaluated in terms ms if Recloser A is installed, or at ms if
of their effectiveness for the local passive anti-islanding pro- Recloser B is in place. On the other hand, the LDC assumes a
cessed, based on the above-mentioned phenomena. maximum of about 50 ms for a typical distributed generator to
drop out, in addition to a maximum of 200 ms for motors to
III. STUDY SYSTEM STRUCTURE AND COMPONENTS disconnect and/or for a fault arc to extinguish. Thus, the wind
Fig. 2 illustrates a simplified single-line schematic diagram farm relay should detect the fault and command the wind farm
of the distribution network under study. The network is real breaker to open before ms for a network with Recloser
and operated by an LDC. Single- and three-phase loads are A, or before ms for a network with Recloser B; these
fed from the feeders and laterals, at various voltage levels. The instants are marked in Fig. 3(a) as the “maximum disturbance
network embeds one main breaker with an automatic recloser, detection time”.
which hereafter is referred to as the main recloser, in addition Fig. 3(a) also indicates a maximum average tripping delay of
to a capacitor bank and a number of fuses along the feeders 133 ms (calculated based on the manufacturer’s datasheets) for
and laterals. Further, the network is assumed to be interfaced the main breaker. It is thus expected that, subsequent to a fault
at the PCC with a wind farm which consists of six 1.67 MW, incident an energized island is formed no later than
PMSG-based, gearless, variable-speed wind-power units. ms. As Fig. 3(a) indicates, this leaves a “maximum permissible
islanding detection time” of 617 ms for a system with Recloser
IV. EVALUATION CRITERIA AND SETUP A, and of 117 ms for a system with Recloser B; detection of
a fault within the maximum permissible disturbance detection
A. Evaluation Criteria time naturally satisfies the maximum permissible islanding de-
The study reported in this paper is based on the assumption tection time requirements.
that the formation of an island is a consequence of the main If the main breaker is inadvertently opened at , an is-
breaker opening, due to either a fault incident or an inadver- land forms in less than about 133 ms, that is, the time taken by
tent operation; we may refer to either scenario as a disturbance. the main breaker to open. As shown in Fig. 3(b), in this case the
Thus, the local passive anti-islanding scheme of the wind-farm main recloser is not even triggered, its time delay does not come
relay is expected to detect the disturbance and disconnect the into the picture, and the maximum permissible disturbance de-
wind farm before the main recloser acts. tection time is the same as the maximum permissible islanding
44 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 1, JANUARY 2011

Fig. 4. Schematic diagram of the test set up used to evaluate the performance
of the relays for the local passive anti-islanding process.

TABLE I
AVAILABLE RELAY FUNCTIONS

Fig. 5. Block illustration of a logic mechanism for the anti-islanding process.

TABLE II
STEADY-STATE PDCS
Fig. 3. Sequence of events due to (a) a fault incident and (b) inadvertent
opening of the main breaker.

detection time. Unlike the faulted operation scenario explained


the RTP from the ComTrade file, played back in real time, am-
earlier, in the inadvertent breaker opening scenario the instant
plified, and concurrently processed by three commercial relays,
at which the wind farm and other distributed generators must be
Relay 1, Relay 2, and Relay 3. Finally, for each operation sce-
dropped out is not constrained by the recloser time, but it is ef-
nario the relay response times are measured and evaluated with
fectively limited by the existing standards or common practices.
respect to the criteria introduced in Section IV-A, to determine
For example, the standard IEEE Std. 1547 requires a maximum
whether or not a particular relay or function would satisfy the
aggregate delay of 2 s for detecting an island and disconnecting
anti-islanding requirements with Recloser A or Recloser B. The
a 10-MW distributed generator [8], [9], whereas the LDC in-
results are discussed in Section VI.
volved in this study recommends that a wind farm be discon-
Table I shows the relay functions of the three relays under test.
nected from the network with a time delay more or less similar
It is to be noted that some relay function can be blocked if the
to those outlined in Fig. 3(a) for a faulted operation scenario.
relay quantities exceed pre-specified limits set within the relay
Therefore, in this paper we consider the maximum disturbance
algorithms. The relay settings have been chosen judiciously to
detection times of 783 (for a system with Recloser A) and 283
achieve desired dependability and security, and are specified in
ms (for a system with Recloser B), for both a faulted operation
Table VIII of Appendix A.
scenario and a inadvertent breaker opening scenario.
Fig. 5 illustrates a diagram of the logic mechanism that com-
bines different relay functions for anti-islanding process and dis-
B. Laboratory Set-Up connection of the wind farm.

Fig. 4 illustrates a simplified diagram of the laboratory set up C. Pre-Disturbance Steady-State Conditions (PDCs)
used for the study reported in this paper. First, a detailed model The results in this paper are obtained for three pre-disturbance
of the network, embedding a single-machine equivalent of the steady-state conditions (PDCs) which each correspond to a pen-
wind-farm, is simulated in the PSCAD/EMTDC software envi- etration level of the wind farm, as shown in Table II. The pene-
ronment under different disturbed conditions. Then, the result of tration level is defined as the ratio of the real and reactive powers
each simulation case is saved in the form of a ComTrade file and delivered by the wind farm to their counterparts demanded by
delivered to the Real-Time Player (RTP). The PCC three-phase the network loads including the power losses. With reference to
voltage and the wind farm current signals are then retrieved by Table II, the worst-case PDC in terms of islanding detection is
EL-KHATTAM et al.: INVESTIGATION OF THE LOCAL PASSIVE ANTI-ISLANDING SCHEME 45

TABLE III
RELAY OPERATING TIMES FOR FAULTS AT LOCATION F1

A blank cell indicates a correct nontripping.

that of II, i.e., the penetration level of 100%, where the wind V. SIMULATION MODEL
farm real and reactive powers closely match their counterparts To enable the studies reported in this paper, a detailed sim-
demanded by the network. ulation model of the distribution network, its components, and
the wind farm is developed in the PSCAD/EMTDC software
environment [14]. The feeders are represented by equivalent
D. Disturbance Incidents sections, and the voltage-/frequency-dependent P/Q model is
adopted for the loads. The wind farm is represented by a 10-MW
The disturbances that the network is subjected to are due to
equivalent single-machine model which includes all details of
either faults or inadvertent opening of the main breaker; each
the power electronics, switching scheme, and controls, to en-
disturbed operating case is preceded by one of the PDCs intro-
able the inclusion of dynamic interactions with the network,
duced in Table II.
harmonics, potential resonance phenomena, etc. The single-ma-
As fault incidents, single-phase to ground, double-phase to
chine modeling of the wind farm is necessary to permit the con-
ground, and three-phase to ground (permanent or self-clearing)
duction of simulations within reasonable time periods, which
faults are imposed on the network of Fig. 2, at either the location
would have been too lengthy if all six wind-power units of the
F1 or F2. The two locations are strategically chosen in the up-
wind farm had been concurrently simulated in their full detail.
stream and downstream sides of the wind farm. The simulation
The model development and components are presented in Ap-
is set up in such a way that the main breaker opens (fuse-saving
pendix B.
scheme) and creates an island, 100 ms after the fault inception
moment. This time delay is assumed to consist of a 30-ms fault VI. STUDY RESULTS AND ANALYSIS
detection time and a 70-ms tripping time, which are deliberately
chosen to be less than the respective maximum average values A. Performance of Relay Functions During Faults
of 33 ms and 133 ms [Fig. 3(a)]. The fault can be permanent To obtain the results, 36 faulted operation scenarios have
or self clearing (temporary). For a permanent fault, the main been simulated; the scenarios correspond to different PDCs, as
breaker is kept open for the rest of the simulation period to let well as various faults of different types and locations (see Sec-
the island establish. However, for a self-clearing fault, the fault tions IV-C and IV-D). Tables III and IV indicate the response
is held in place for 120 ms, that is, the fault is cleared 20 ms after times of each relay. It is observed that Relays 1 and 3 are able
the opening of the main breaker and formation of the island. to detect all disturbance incidents, irrespective of the recloser
To simulate an inadvertent breaker opening scenario, the main type, with time delays less than the maximum permissible
breaker is opened and kept so for the entire simulation period. disturbance detection times introduced in Section IV.A (783
46 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 1, JANUARY 2011

TABLE IV
RELAY OPERATING TIMES FOR FAULTS AT LOCATION F2

A blank cell indicates a correct nontripping.

ms for a system with Recloser A and 283 ms for a system rent injection capability, as explained in Appendix B. This
with Recloser B). More importantly, the two relays detect the property is further highlighted in Fig. 6 which illustrates
disturbance in less than 50 ms which, taking into account a the PCC voltage and wind farm current contribution, for
maximum tripping time of 50 ms for the wind farm breaker [see a fault at the main substation bus (location F1, Fig. 2). It
Fig. 3(a)], means that the wind farm is dropped out even before is noted that, prior to the fault inception at s, the
the main breaker opens at 100 ms, i.e., before an island forms. wind farm has been delivering an output power of about
The only exception to this is one case for Relay 3 where the 0.315 p.u.; subsequent to the fault, the PCC voltage drops
disturbance is detected in 64.1 ms after the fault inception. The to about 0.1 p.u., but the wind farm current remains limited
results further indicate that, in 66.7% of the cases the response to about 0.67 p.u.
time of Relay 2 is such that the relay can be employed for a • Relays 1 and 3 are able to detect all disturbance incidents
system with Recloser A. On the other hand, Relay 2 is able to through their OV/UV functions. However, Relay 2 detects
detect only 63.9% of the disturbance incidents based on the re- only 63.9% of the incidents through its OV/UV function.
quirements of a system with Recloser B. In 33.3% of the cases, This is due to the relay ineffectiveness in tracking the net-
Relay 2 is unable to detect a disturbance incident, irrespective work frequency, which results in the blockage of the relay
of the criterion adopted. The failure can be attributed to the OV/UV functions.
inability of the relay to track frequency excursions caused by • Relay 1 is able through its Vshift function to detect 19.4%
the disturbances, which, in turn, has resulted in the blockage of of the total fault disturbance incidents. These incidents
both the frequency and voltage functions of the relay. correspond to the concurrent imposition of three-phase to
The analysis of the results reported in Tables III and IV indi- ground faults at both locations F1 and F2. The reason for
cates the following. missing the rest of the incidents is either the small ampli-
• Relays 1 and 3 correctly do not detect any over-current phe- tudes of the voltage excursions or the failure of the relay
nomena (OI function is not available in Relay 2), since the frequency tracking scheme required for the Vshift func-
wind-power units constituting the wind farm are power- tion. According to the manufacturer, the Vshift function in
electronically controlled and thus of a limited fault cur- Relay 1 performs only if both a voltage excursion is of an
EL-KHATTAM et al.: INVESTIGATION OF THE LOCAL PASSIVE ANTI-ISLANDING SCHEME 47

TABLE V
INADVERTENT MAIN BREAKER OPENING CASE: RELAY OPERATING TIMES

Fig. 6. PCC voltage waveform and the wind farm current waveform, for a three-
phase fault taking place at F1, in Fig. 2.

adequately large magnitude and the frequency can be prop-


erly tracked. It should be noted that the Vshift function in
Relay 1 measures the time interval between two consecu-
tive voltage zero crossings, and then compares the result
of one cycle with that of the next cycle using a specific
number of samples. This requires the network frequency to observed that all the three relays detect the inadvertent main
be within a pre-specified range to be tracked by the relay breaker opening in less than 283 ms. Therefore, they are suit-
and to enable the Vshift function. In cases where the fre- able for anti-islanding application under the inadvertent breaker
quency has been tracked, the Vshift function has failed due opening, irrespective of the recloser type. The performance of
to small magnitudes of the voltage excursions. The Vshift the relays functions can be summarized as follows.
function is not embedded in Relay 2 or Relay 3. • All three relays detect the disturbances through their
• The OF/UF function of Relay 1 is activated by all fault dis- OV/UV functions, except in two cases: for the PDC I,
turbance incidents. However, Relays 2 and 3 are able to Relay 1 takes a long time, while Relay 2 does not detect
only detect 63.9% of the disturbances through their OF/UF any voltage excursion; this is believed to be due to the fact
functions. The reason is that the frequency variation rates that the network steady-state voltage is 1.05 p.u.
turn out to be beyond the relays measurement capabilities. • Relay 1 does not detect any disturbance through its Vshift
For the relays under study, the OF/UF function is accom- function. The reason is that the voltage excursions are
panied by a delta voltage supervisory scheme, which com- smaller than the relay pre-specified thresholds. Vshift
pares the maximum of the sampled values of two consec- function is not embedded in Relay 2 or Relay 3.
utive windows of equal lengths, as specified by the manu- • Except in two cases, all three relays are able to detect the
facturer; if the delta voltage is greater than the pre-speci- disturbances through their OF/UF and ROCOF functions.
fied value, the OF/UF function of the relay is blocked for In the two cases, Relay 2 is not able to detect any distur-
the corresponding cycle. This provision is necessary to sta- bance due to the fact that the rates of frequency variations
bilize the frequency function under transients, for example turn out to be outside of the pre-specified range.
during a tripping process or at the beginning of a fault inci-
dent. For a number of simulation case studies, the voltage C. Relay Selection Criteria
variation exceeds the permissible range and leads to the
blockage of the OF/UF function. To select the fastest relay function and/or relay, the “cor-
• Through their ROCOF functions, Relays 1, 2, and 3 are rect-operation index”, , the “fail-to-operate index”, , and
able to detect, respectively, 88.9%, 52.8%, and 38.9% of the “relay dependability index” are defined as shown in (1)–(3),
the fault incidents. It should be pointed out that the ROCOF at the bottom of the next page [15], where signifies the number
function requires a minimum of 100 ms, including the cal- of combinations of relay functions. The last index, i.e., (3), rep-
culation time for ROCOF, the time for filtering, and the resents the fact that, even though only one relay function may
time for the output contact operation. Also, if the ROCOF suffice to detect disturbance incidents, a combination of more
is higher than the limits sets by the relay frequency tracking relay functions typically translates into a higher relay depend-
algorithm, the function does not operate, as is the case for ability.
the results reported here. Tables VI and VII include the values of , and relay
dependability index, based on the maximum permissible distur-
bance detection times of 783 ms (for a system with Recloser A)
B. Performance of Relay Functions Under Inadvertent
and 283 ms (for a system with Recloser B). The results clearly
Breaker Opening
indicate that Relays 1 and 3 perform considerably better than
In addition to faulted operation, the relay functions have also Relay 2, in terms of the overall detection of the disturbances.
been evaluated under inadvertent opening of the main breaker. It is also noted that Relay 1 exhibits a superior performance as
The tests have been performed for all the three PDCs speci- compared with Relay 3, in terms of the relay functions and relay
fied in Table II, and the results are reported in Table V. It is dependability.
48 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 1, JANUARY 2011

TABLE VI waveforms were recorded, played back in real time, and fed to
RELAYS PERFORMANCE INDICES three commercially available relays. The conclusions are as fol-
lows.
• The over-/under-voltage function can be relied upon as a
fast and relatively reliable indicator of an islanding inci-
dent. However, the voltage-shift function turns out to be
ineffective in the islanding detection process.
• Both the over-/under-frequency and rate-of-change-of-fre-
quency functions are reliable for an anti-islanding process.
However, they are rather slow and can be blocked if the
relay is unable to track the frequency, calling for better al-
gorithms in terms of the speed of response and frequency
tracking capability.

APPENDIX A
RELAY SETTINGS
The relay settings are reported in Table VIII.
TABLE VII
RELAYS DEPENDABILITY (%) BASED ON NUMBER OF OPERATING FUNCTIONS

APPENDIX B
SIMULATION MODEL DEVELOPMENT

A. Circuit and Controls of the Wind System


Fig. 7 illustrates a simplified schematic diagram of the
PMSG-based wind system. The wind system consists of a
wind turbine that is directly coupled to a multi-pole PMSG,
an ac-dc-ac power-electronic converter, and the interface
transformer . The ac-dc-ac converter, in turn, consists of
a rotor-side converter (RSC) and a grid-side converter (GSC).
The RSC and GSC are three-phase voltage-sourced converters
that are connected in parallel from their dc-side terminals to a
dc-link capacitor, , and controlled based on the pulsewidth
modulation (PWM) switching strategy. The ac-side terminals
of the RSC are connected to the PMSG stator, whereas those of
the GSC are interfaced with the low-voltage side of via a
three-phase LC filter. The high-voltage side of is connected
VII. CONCLUSION to the distribution network (see Fig. 2) and is defined as the
This paper evaluated the effectiveness of different relay func- PCC. The filter mitigates the current switching harmonics
tions and their combination in an anti-islanding process for a injected by the GSC into the network. The per-phase series
PMSG-based direct-drive wind farm interfaced with a radial dis- inductance and shunt capacitance of the filter are denoted by
tribution network. The results were obtained through detailed and , respectively. signifies the parasitic resistance of
time-domain simulation studies conducted for a real distribu- the inductor and also embeds the impact of the GSC conduc-
tion network and a single-machine equivalent of a hypothetical tion power loss. The wind system delivers the real and reactive
wind farm, in the PSCAD/EMTDC software environment. The power and to the network, at the PCC, which are referred

(1)

(2)

(3)
EL-KHATTAM et al.: INVESTIGATION OF THE LOCAL PASSIVE ANTI-ISLANDING SCHEME 49

TABLE VIII where , and signify the turbine power, the PMSG
RELAYS SETTINGS airgap power, and the PMSG developed torque, respectively.
The damping factor represents the impact of friction and
windage, and is the drive-train inertia constant in s. is
formulated as

(B.3)

where is the air density, is the turbine radius, is the wind


speed, is the base power, is the turbine power ef-
ficiency, is the tip-speed-ratio, is the tur-
bine angular speed, and is the turbine pitch angle. It should
be noted that the turbine and PMSG shaft speeds are related
through , where is the PMSG number of pole
pairs. However, as in (B.1) and (B.2), is equal to, and can
be replaced by, . Based on (B.1), variable-speed operation of
the wind system is enabled by controlling through the RSC,
as explained next.
PMSG Torque Control: The mathematical model of the
PMSG in its rotor field coordinate system is given by [16]–[18]
Fig. 7. Simplified schematic of the PMSG-based wind system representing a
10-MW wind farm.
(B.4)

to as the “wind system real power” and “wind system reactive (B.5)
power”, respectively.
Fig. 7 also includes simplified block diagrams of the con- (B.6)
trollers of the RSC and GSC. The function of the RSC and its
associated control scheme is to regulate the PMSG stator cur- where is the base frequency, and , and are the
rent (and thus the electrical torque), for the ultimate goals of PMSG -axis inductance, -axis inductance, and rotor flux
variable-speed operation and maximum power-point tracking magnitude. The abovementioned model does not consider any
(MPPT). As Fig. 7 indicates, the control is exercised in the damper windings for the PMSG.
PMSG rotor field coordinate system which is synchronized to As (B.6) suggests, can be controlled by a combination of
the machine rotor angle . On the other hand, the GSC and and . However, is typically a small value. More-
its control scheme regulate the dc-link voltage, that is, . The over, simultaneous control of and introduces nonlinearity
GSC also enables the control of the wind system reactive power in the control process. Therefore, only is used to dynam-
. The control of the GSC is carried out in a dq reference ically control , while is regulated at zero. This strategy
frame that is synchronized to the filter output voltage, i.e., , also results in the lowest machine current for a given torque. The
through a phase-locked loop (PLL). aforementioned control objectives are achieved through the two
following control laws:
B. Mathematical Model and Controls of Wind System
In what follows, the per-unit (p.u.) version and the base value
of a variable (or parameter) are represented by and , re- (B.7)
spectively. Moreover, the - and -axis components of a per-unit
three-phase variable are denoted by and , respec-
tively.
Drive-Train: The electromechanical system of the wind (B.8)
system of Fig. 7 consists of a mechanical subsystem and an
where and are, respectively, the - and -axis compo-
electrical subsystem. The former is the wind turbine while the
nents of the PMSG stator terminal voltage to be reproduced by
latter is represented by the PMSG. The two subsystems are
the RSC. The two signals are first normalized to the dc-link
related by
voltage, i.e., , transformed to the frame using the rotor
angle , and fed to the PWM scheme of the RSC. Assuming an
(B.1) adequately large PWM switching frequency, one has
and . The signals and are the reference com-
mands for and , respectively, . In (B.7) and
(B.2) (B.8), the terms inside the square brackets represent two corre-
sponding proportional-integral (PI) compensators whose gains
50 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 1, JANUARY 2011

are and (for ), and and (for ); the other in turn, render and proportional to, and thus controllable
terms are introduced to eliminate the dynamic coupling between by, respectively, and , as
and .
Assuming that , based on (B.6) is calculated (B.12)
as (B.13)

(B.9) The wind system reactive power is the resultant of and the
reactive power delivered by , as

where the torque reference command is determined through (B.14)


the MPPT strategy, as explained next.
Maximum Power-Point Tracking: For a given in In most cases, it can be assumed that .
(B.3) is a decreasing function of . Therefore, under normal op- Dynamics of and are described by
erating conditions, is kept to a small value, near zero, to enable
the maximum possible turbine power; at excessively high wind (B.15)
speeds, a pitch-angle control mechanism (not discussed in this
paper) automatically increases to limit the PMSG power and (B.16)
speed. Regardless, for a given peaks for a unique
tip-speed-ratio which is denoted by . Thus, to maximize the and can be independently controlled through the two fol-
turbine power at every wind speed, an MPPT strategy should, lowing control laws:
directly or indirectly, keep constant and equal to . One
way to achieve this goal is to force the turbine torque to change
in proportion to the square of the turbine speed [19]. In view of
(B.1), this is equivalent in changing the PMSG electrical torque (B.17)
in proportion to the square of the turbine speed, that is

(B.10)
(B.18)
where the proportionality constant depends on the turbine
parameters and characteristics. is then delivered to the where and are, respectively, the desired - and -axis
PMSG torque-control scheme and imposed on the PMSG. components of the GSC ac-side terminal voltage to be synthe-
The approximation in (B.10) is plausible since and thus sized by PWM. The two signals are normalized to , trans-
change relatively slowly due to the drive-train inertia. formed to the frame using the angle provided by the PLL,
Moreover, the PMSG torque-control scheme can be made and fed to the PWM scheme of the GSC. It can be assumed that
remarkably fast through proper selection of the controller and , if the PWM switching frequency is
parameters , and . sufficiently large. and are the reference commands for
It can be shown that the MPPT process results in the turbine and , respectively. The terms inside the square brackets rep-
power being proportional to the cube of the wind speed, that is resent two corresponding PI compensators whose gains are
and (for ), and and (for ); the other terms are in-
(B.11) troduced to eliminate the dynamic coupling between and ,
and to mitigate the impact of PCC voltage disturbances on
DC-Link Voltage Regulation and Grid-Side Reactive-Power and . To protect the GSC against external faults, and are
Control: The grid-side control of the wind system effectively bound to upper limits that may themselves be functions of the
boils down to the control of the power components and turbine pre-disturbance power, based on a pre-determined pro-
(shown in Fig. 7). The former control is used to regulate the file. The bounds, however, guarantee that the short-circuit cur-
dc-link voltage ; in this process, the wind system real power rent of the PMSG-based wind system at its rated power output
is a by-product, as will become evident shortly. The latter is limited to 1.2–1.5 p.u.
control, however, determines the wind system reactive power The dc-link voltage dynamics are described by the following
which affects the power factor that the wind system ex- power balance equation, ignoring the power losses and the en-
hibits to the network. Thus, can be regulated to a constant ergy exchanged with the interface reactor :
value, or alternatively it can be controlled through a closed-loop
mechanism to regulate the PCC voltage magnitude, if the grid
is non-stiff. In this paper, the former option has been exercised.
and are independently controlled based on a current-con-
trol strategy [20]. The control is exercised in a frame whose (B.19)
-axis is aligned with the space vector corresponding to the
voltage , by means of the PLL [21]. Thus, and where is the PMSG stator terminal power and, based on
, where is the magnitude of . These properties, (B.12), is expressed in terms of . Equation (B.19) represents
EL-KHATTAM et al.: INVESTIGATION OF THE LOCAL PASSIVE ANTI-ISLANDING SCHEME 51

a control plant for which is the output, is the disturbance TABLE IX


input, and is the control input. On the other hand, tracks WIND SYSTEM TURBINE AND PMSG PARAMETERS
. Therefore, can be regulated by , for example, based on
the following control law:

(B.20)

where is the reference command for the dc-link voltage.


is an estimate of , included in the controller as a feed-forward TABLE X
WIND SYSTEM BASE VALUES
signal, to enhance the performance of the dc-link voltage regu-
lation process. This estimate can be obtained using a variety of
techniques. In this paper, it is assumed that , where
is calculated from (B.6). The terms inside the square brackets
define a PI compensator whose gains are and .
In steady-state and quasi-steady regimes: 1) the PMSG/tur-
bine speed excursions and 2) the dc-link voltage fluctuations
can be ignored. Therefore, based on (B.2) and (B.19), one finds
and . On the other hand, ignoring the PMSG TABLE XI
WIND SYSTEM PARAMETERS
and power-electronic converter power losses, we have
and . Thus, based on (B.11), we have

(B.21)

Equation (B.21) indicates that the wind system real power is


not a directly controllable variable, but a function of (the cube
of) the wind speed. Thus, to create each PDC (Section IV-C,
Table II) the wind speed is set in the simulation model to an
appropriate value, based on (B.21).

C. Simulation Model of Wind System The wind system and controller parameters are presented in
Tables IX to XI. Care should be taken in interpreting the PMSG
The parameters of the wind system of Fig. 7 have been parameters; the PMSG is assumed to be a 10.6-MVA, 1.2-kV,
scaled such that the wind system represents a 10-MW wind 9.24-Hz, 120-pole machine. However, its per-unit parameters
farm. Thus, a detailed switched model of the wind system unit are expressed in terms of the base voltage and frequency of, re-
is developed in the PSCAD/EMTDC software environment. In spectively, 1.551 kV and 377 rad/s, corresponding to a 1.9 kV
the model, the RSC and the GSC both are pulsewidth modu- (rms, L-L), 60-Hz wind system. It should also be noted that, un-
lated with the switching frequency of 3060 (51 60) Hz, their like the conventional three-phase systems where the line-to-neu-
PWM carrier signals are synchronized to the angle and, to tral rms voltage is taken as the base voltage, for the wind system
allow the maximum utilization of the dc-link voltage [22], their the line-to-neutral peak voltage represents the base voltage. As
PWM modulating signals are augmented with the respective such, the base current is represented by the peak value of the
third-order harmonics. The PMSG model has been realized by rated ac current of the wind system.
dependent current sources, integrators, multipliers, and adders,
based on (B.4)–(B.6). The turbine is modeled by a FORTRAN
code, based on parameters and analytical equations presented REFERENCES
in [23]. The wind system controllers include (B.7)–(B.8), [1] C. Abbey, F. Katiraei, C. Brothers, L. Dignard-Bailey, and G. Joos,
“Integration of distributed generation and wind energy in Canada,” in
(B.9)–(B.10), (B.17)–(B.18), and (B.20), whose parameters are Proc. IEEE Power Eng. Soc. General Meet., Jun. 2006.
calculated in such a way that: [2] T. Ackermann, Wind Power in Power Systems. New York: Wiley,
• the transfer functions and are 2005.
[3] W. El-Khattam and M. M. A. Salama, “Distributed generation tech-
of the first order, with a time constant of 1.0 ms; nologies, definitions and benefits,” Elect. Power Syst. Res. J., vol. 71,
• the transfer functions and are of no. 2, pp. 119–128, Oct. 2004.
the first order, with a time constant of 1.0 ms; [4] R. A. Walling, R. Saint, R. C. Dugan, J. Burke, and L. A. Kojovic,
“Summary of distributed resources impact on power delivery systems,”
• the transfer function has a closed-loop IEEE Trans. Power Del., vol. 23, no. 3, pp. 1636–1644, Jul. 2008.
bandwidth of about 550 rad/s and a phase margin of about [5] W. Xu, K. Mauch, and S. Martel, An Assessment of DG Islanding
53 degrees; and Detection Methods and Issues for Canada CANMET Energy Tech-
nology Centre—Varennes, Natural Resources Canada, Rep. # CETC-
• the wind-power unit generates its rated power at the wind Varennes 2004-074 (TR), Jul. 2004 [Online]. Available: http://cetc-
speed of m/s. varennes.nrcan.gc.ca/en/er_re/inter_red/p_p.html?2004-074
52 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 1, JANUARY 2011

[6] Assessment of Islanded Operation of Distribution Networks and Mea- [22] J. A. Houldsworth and D. A. Grant, “The use of harmonic distortion
sures for Protection 2001 [Online]. Available: http://www.berr.gov.uk/ to increase the output voltage of a three-phase PWM inverter,” IEEE
files/file 15099.pdf, Ecconnect, DTI/Pub URN 01/1119, DTI Trans. Ind. Appl., vol. IA-20, no. 5, pp. 1224–1228, Sep./Oct. 1984.
[7] A. Dysko, C. Booth, O. Anaya-Lara, and G. M. Burt, “Reducing unnec- [23] J. G. Slootweg, H. Polinder, and W. L. Kling, “Representing wind tur-
essary disconnection of renewable generation from the power system,” bine electrical generating systems in fundamental frequency simula-
IET Renew. Power Gener., vol. 1, no. 1, pp. 41–48, Mar. 2007. tions,” IEEE Trans. Energy Convers., vol. 18, no. 4, pp. 516–524, Dec.
[8] IEEE Standard for Interconnecting Distributed Resources with Electric 2003.
Power Systems, IEEE Standard 1547, Jul. 2003.
[9] IEEE Standard Conformance Test Procedures for Equipment Intercon- Walid El-Khattam (S’00–M’06) received the Bachelor’s and Master’s degrees
necting Distributed Resources with Electric Power Systems, IEEE Stan- in electrical engineering from Ain Shams University, Cairo, Egypt, in 1991 and
dard 1547.1, Jul. 2005. 1996, respectively, and the Ph.D. degrees in electrical engineering from the Uni-
[10] B. Kroposki, S. Englebretson, C. Pink, J. Daley, R. Siciliano, and D. versity of Waterloo, Waterloo, ON, Canada in 2005.
Hinton, Validation of IEEE P1547.1 Interconnection Test Procedures: Since 2007, he has been an Assistant Professor in the Department of Elec-
ASCO 7000 Soft Load Transfer System National Renewable Energy trical Power and Machines, Ain Shams University. He was previously with the
Laboratory, Golden, CO, NREL/TP-560-34870, Sept. 2003 [Online]. University of Western Ontario (UWO), London, ON, Canada as Postdoctoral
Available: http://www.nrel.gov/docs/fy04osti/34870.pdf Fellow. His area of research is distributed generation performance, planning,
[11] M. A. Redfern, O. Usta, and G. Fielding, “Protection against loss of and protection, power distribution systems, and probabilistic analysis of power
utility grid supply for a dispersed storage and generation unit,” IEEE systems.
Trans. Power Del., vol. 8, no. 3, pp. 948–954, Jul. 1993.
[12] J. E. Kim and J. S. Hwang, “Islanding detection method of distributed
generation units connected to power distribution system,” in Proc.
IEEE PowerCon 2000—Int. Conf. Power System Technology, Dec. Amirnaser Yazdani (M’05–SM’09) received the Ph.D. degree in electrical en-
2000, vol. 2, pp. 643–647.
gineering, from the University of Toronto, Toronto, ON, Canada, in 2005.
[13] W. Freitas, X. Wilsun, C. M. Affonso, and H. Zhenyu, “Comparative He was with Digital Predictive Systems (DPS) Inc., Mississauga, ON, active
analysis between ROCOF and vector surge relays for distributed gen-
in design and simulation of high-power electronic converters for wind energy
eration applications,” IEEE Trans. Power Del., vol. 20, no. 2, pt. 2, pp. systems. Presently, he is an Assistant Professor with the University of Western
1315–1324, Apr. 2005.
Ontario (UWO), London, ON, Canada. His research interests include dynamic
[14] PSCAD/EMTDC v. 4.2 Manitoba HVDC Research Centre. Win- modeling and control of switching power converters, distributed generation, and
nipeg, MB, Canada.
microgrids.
[15] F. C. Chan, “Performance assessment and control of power system re-
laying,” IEEE Trans. Power Del., vol. 4, no. 2, pp. 986–994, Apr. 1989.
[16] S. Morimoto, Y. Takeda, T. Hirasa, and K. Taniguchi, “Expansion of
operating limits for permanent magnet motor by current vector control
considering inverter capacity,” IEEE Trans. Ind. Appl., vol. 26, no. 5, Tarlochan S. Sidhu (M’90–SM’94–F’04) received the Ph.D. degree from the
pp. 866–871, Sep./Oct. 1990. University of Saskatchewan, Saskatoon, SK, Canada, in 1989.
[17] P. C. Krause, O. Wasynczuk, and S. D. Sudhoff, Analysis of Electric He is currently the Chair of the Department of Electrical and Computer Engi-
Machinery. New York: IEEE Press, 1995. neering, a Professor, and the Hydro One Chair in Power Systems Engineering at
[18] A. Yazdani and R. Iravani, “A neutral point clamped converter system the University of Western Ontario (UWO), London, ON. His areas of research
for direct drive variable speed wind power unit,” IEEE Trans. Energy interest are power system protection, monitoring, and control.
Convers., vol. 21, no. 2, pp. 596–607, Jun. 2006. Dr. Sidhu is a Fellow of the Institution of Engineers (India) and the Institution
[19] R. Datta and V. T. Ranganathan, “Variable-speed wind-power genera- of Electrical Engineers (U.K). He is also a Registered Professional Engineer in
tion using doubly fed wound rotor induction machine—A comparison the Province of Ontario and a Chartered Engineer in the U.K.
with alternative schemes,” IEEE Trans. Energy Convers., vol. 17, no.
3, pp. 414–421, Sep. 2002.
[20] C. Schauder and H. Mehta, “Vector analysis and control of advanced
static VAR compensators,” IEE Proc.—Gener., Transmiss., Distrib., Ravi Seethapathy (M’76–SM’09) is currently Manager—Distributed Genera-
vol. 140, no. 4, pp. 299–306, Jul. 1993. tion, and Advanced Grid Development, Hydro One Networks Inc., Toronto, ON,
[21] S. Chung, “A phase tracking system for three phase utility interface Canada He sits on several T&D/DG committees at the PES/IEEE and CIGRE.
inverters,” IEEE Trans. Power Electron., vol. 15, no. 3, pp. 431–438, Dr. Seethapathy is a Registered Professional Engineer in the Province of
May 2000. Ontario.

S-ar putea să vă placă și