Introduction to Power Systems
MVA := MW kVA := kW j := −1
MVAR := MW kVAR := kW
pu := 1
Determine the per unit reactances of the per-phase equivalent circuit using a base of
15 MVA and 66 kV for the primary.
15⋅ MVA
XST := XST⋅ XST = 0.12⋅ pu
10⋅ MVA
X1 :=
(XPS + XPT − XST) X1 = 0.0200⋅ pu
2
X2 :=
(XPS + XST − XPT) X2 = 0.0500⋅ pu
2
X3 :=
(XPT + XST − XPS) X3 = 0.07⋅ pu
2
3.54 An infinite bus, which is a constant voltage source, is connected to the primary of the
three-winding transformer of Problem 3.53. A 7.5 MVA, 13.2 kV synchronous motor with a
subtransient reactance of 0.2 per unit is connected to the transformer secondary. A 5 MW,
2.3 kV three-phase resistive load is connnected to the tertiary. Choosing a base of 66 kV
and 15 MVA in the primary, draw the impedance diagram of the system showing per unit
impedances. Neglect transformer exciting current, phase shifts, and all resistances except
the resistive load.
15⋅ MVA
XSM := XSM⋅ XSM = 0.4⋅ pu
7.5MVA
PD := 5 ⋅ MW QD := 0 ⋅ MVAR
SD := PD + j ⋅ QD SD = 5 ⋅ MVA
A quick review:
⎯ VLN
SD = 3 ⋅ VLN⋅ I VLN = ZD⋅ I I=
ZD
⎯
( ) ( ) ( VLL )
2 2 2
VLN 3 ⋅ VLN 3 ⋅ VLN
SD = 3 ⋅ VLN⋅ ⎯ = ⎯ = ⎯ = ⎯
ZD ZD ZD ZD
Calculate ZD
( VTbase )
2
ZD := ⎯ ZD = 1.058 Ω
SD
2
VTbase
ZTbase := ZTbase = 0.353 Ω
Sbase
ZD
ZD := ZD = 3 ⋅ pu
ZTbase
Source
RS := 0 ⋅ pu XS := 0 ⋅ pu
Transformer
R1 := 0 ⋅ pu X1 = 0.0200⋅ pu Z1 := R1 + j ⋅ X1 Z1 = 0.0200j ⋅ pu
R2 := 0 ⋅ pu X2 = 0.0500⋅ pu Z2 := R2 + j ⋅ X2 Z2 = 0.0500j ⋅ pu
R3 := 0 ⋅ pu X3 = 0.0700⋅ pu Z3 := R3 + j ⋅ X3 Z3 = 0.0700j ⋅ pu
Synchronous Motor
Resistive Load
ZD = 3.00⋅ pu
R2 + jX2 +
RSM + jXSM
RS + jXS R1 + jX1 R3 + jX3 V2
+ + + +
VS V1 V3 ZD ESM
- - - - -
4.1 The Aluminum Electrical Conductor Handbook lists a dc resistance of 0.01552 ohms per 1000ft at 20 degree centigrade and a 60 Hz
resistance of 0.0951 ohm per mile at 50 degree centigrade for the all-aluminum Marigold conductor, which has 61 strands and whose
size is 1113 kcmil. Assuming an increase in resistance of 1.6% for spiraling, calculate and verify the dc resistance. Then calculate
the dc resistance at 50 degree centigrade, and determine the percentage increase due to skin effect.
π 2 3 −7 2 2
cmil := ⋅ mil kcmil := 10 ⋅ cmil kcmil = 5.067 × 10 m kcmil = 0.507 ⋅ mm
4
2
AMarigold := 1113⋅ kcmil AMarigold = 5.64⋅ cm
Ω⋅ cmil −8
ρAL20 := 17.0⋅ ρAL20 = 2.826 × 10 ⋅ Ω⋅ m
ft
ρAL20 Ω
RDC20 := 1.016 ⋅ RDC20 = 0.01552 ⋅ at 20 degrees centigrade Verified!
AMarigold 1000⋅ ft
ρAL50 Ω
RDC50 := 1.016 ⋅ RDC50 = 0.01739 ⋅ at 50 degrees centigrade RDC50⋅ 1000⋅ ft = 0.01739 Ω
AMarigold 1000⋅ ft
Ω Ω RAC50 − RDC50
RAC50 := 0.0951⋅ RAC50 = 0.09510 ⋅ = 3.544 ⋅ %
mi mi RDC50
4.4 One thousand circular mils or 1 kcmil is sometimes designated by the abbreviation MCM. Data for the commercial bare aluminum
electrical conductors lists a 60 Hz resistance of 0.0740 ohm per kilometer at 75 degree centigrade for a 954 MCM All-Aluminum
Conductor.
b) Find the 60 Hz resistance of this conductor in ohms per kilometer at 45 degrees centigrade.
a)
−4 2
AXS := 954 ⋅ kcmil AXS = 4.834 × 10 m
b)
Ω
RAC75 := 0.0740⋅ at 75 degrees centigrade
km
45⋅ C + TAL
RAC45 := RAC75⋅
75⋅ C + TAL
Ω
RAC45 = 0.0667⋅ at 45 degrees centigrade
km