LOCATION : PPDS-RMHS STANDARD BDV TEST REPORT

TRANSFORMER SL NO: 2043253 PROJECT : NMDC 3.0 MTPY STEEL PLANT (NAGARNAR)
TRANSFORMER RATING: 25/31.5MVA POWER TRANSF0RMER Date:18/08/2019

POWER TRANSFORMER BDV TEST REPORT

NAME PLATE DETAILS:

Sl. No. 2043253 Vector Group Dyn11


MVA 31.5/25 Type of cooling ONAF/ONAN
Make BHEL-JHANSI Frequency 50 Hz
No Load Voltage at HV (KV) 33.0 Temp rise oil 35°C
No Load Voltage at LV (KV) 6.9 Ambient Temp 50°C
Rated current on HV(A) 551.11/437.39 Insulation Level HV 170Kvp,70KVrms
Rated current on LV(A) 2635.73/2091.85 Impedence Voltage 10.0+ 10% Tolerance
OIL MAKE Standard IS:2026 -1977
OIL Type Insulation Class A
OIL Manf Date Insulation Level LV 75Kvp,28KVrms

1. TRANSFOMER OIL BREAK DOWN VOLTAGE TEST:


ELECTRODE GAP : 2.5mm
ELECTRODE TYPE : MUSHROOM
STIRRER : NONE
IEC STANDARD : 60156-95

2. BEFORE OIL FILTERATION :


OIL TEMP : 26ºC
OIL SAMPLE DATE :
OIL SAMPLE TAKEN AT : Bottom- Valve 85( 15NB)
OIL LEVEL AT CONV TANK:

TIME TAKEN FOR


SL NO TEST CYCLE OIL BREAK DOWN VOLTAGE(KV)
TEST(mins)
1 TEST CYCLE-1 5- mins
2 TEST CYCLE-2 2 -mins
3 TEST CYCLE-3 2 -mins
4 TEST CYCLE-4 2 –mins
5 TEST CYCLE-5 2 –mins
6 TSET CYCLE-6 2 –mins
AVERAGE BREAK DOWN VOLTAGE

SIGNATURE: SIGNATURE: SIGNATURE: SIGNATURE:

NAME: NAME: NAME: NAME:


DESIGN: TESTING ENGINEER DESIGN: SITE INCHARGE. DESIGN: DESIGN:
COMPANY: PMPL COMPANY: PMPL COMPANY: NMDC COMPANY: NMDC
LOCATION : PPDS-RMHS STANDARD BDV TEST REPORT
TRANSFORMER SL NO: 2043253 PROJECT : NMDC 3.0 MTPY STEEL PLANT (NAGARNAR)
TRANSFORMER RATING: 25/31.5MVA POWER TRANSF0RMER Date:18/08/2019

1.AFTER OIL FILTERATION :


OIL TEMP : 26ºC
OIL SAMPLE DATE :
OIL SAMPLE TAKEN AT : Bottom- Valve 85( 15NB)
OIL LEVEL AT CONV TANK :
TIME TAKEN FOR
SL NO TEST CYCLE OIL BREAK DOWN VOLTAGE(KV)
TEST(mins)
1 TEST CYCLE-1 5- mins
2 TEST CYCLE-2 2 -mins
3 TEST CYCLE-3 2 -mins
4 TEST CYCLE-4 2 –mins
5 TEST CYCLE-5 2 –mins
6 TSET CYCLE-6 2 –mins
AVERAGE BREAK DOWN VOLTAGE

INSTRUMEN DETAILS:

EQUIPMENT MAKE MODEL/SL.NO RANGE/CAPACITY CALIBRATION


DETAILS VALID DATE
OIL FILTERATION SAPTHAGIRI HUHVR-5KL/154 5KL/5000LPH
MACHINE INDUSTREIES
BDV TEST KIT MEGGER OTS100AF/101725610 0 -100KV

REMARKES: The BDV test is conducted for transformer OIL and found healthy the OIL was fit for
service .