Documente Academic
Documente Profesional
Documente Cultură
Introduction
Most induction motors are started directly on line, but when very large
motors are started that way, they cause a disturbance of voltage on the
supply lines due to large starting current surges.
To limit the starting current surge, large induction motors are started at
reduced voltage and then have full supply voltage reconnected when they
run up to near rotated speed.
Two methods used for reduction of starting voltage are: Star delta starting
and Auto transformer starting.
COMPONENT OF STAR-DELTA STARTER
1. 3∅-CONTACTOR
Another advantage is, as the switch operating knob comes at its off position
during tripping, the faulty zone of the electrical circuit can easily be
identified. But in case of fuse, fuse wire should be checked by opening fuse
grip or cutout from fuse base, for confirming the blow of fuse wire.Quick
restoration of supply can not be possible in case of fuse as because fuses
have to be rewirable or replaced for restoring the supply. But in the case of
MCB, quick restoration is possible by just switching on operation.
But during short circuit condition, the current rises suddenly, causing
electromechanical displacement of plunger associated with a tripping coil or
solenoid. The plunger strikes the trip lever causing immediate release of
latch mechanism consequently open the circuit breaker contacts.
An MCB is very simple, easy to use and is not generally repaired. It is just
easier to replace. The trip unit is the main part, responsible for its
proper working. There are two main types of trip mechanism. A bi-
metal provides protection against overload current and an electromagnet
provides protection against short-circuit current.
4. INDICATORS
4. TIMER
The Selec 800SD Star - Delta timer are housed in a compact DIN
rail mount to a socket and are powered from a large choice of AC or
DC power options. Star - Delta timer Selec 800SD has Time
functions for Star - Delta timing etc., are available, adjustable
through the calibrated front control knob. These timers offer many
different timing functions together with accurate, long-term
switching reliability and high current switching contacts. The single
or double pole changeover relay output contacts are isolated from
the supply voltage.
Features
Star Delta
2 Time Ranges
LED status indicator: Star relay ON, Delta relay ON
DIN Rail / Back Panel mount
Finger safe terminals
5. NORMALLY CLOSED (NC) PUSH BUTTON
A Normally Closed (NC) Push Button is a push button that, in its default
state, makes electrical contact with the circuit.
When the button is pressed down, the switch no longer makes electrical
contact and the circuit is now open. Therefore, electricity can no longer flow
to the other part of the circuit to turn or power on the respective part of the
circuit the button was made to switch.
Normally Closed Push buttons are not the most common type of push button
used; Normally Open Push Buttons are. However, they still have widespread
use and application in many devices.
5. NORMALLY OPEN (NO) PUSH BUTTON
A Normally Open (NO) Push Button is a push button that, in its default state,
makes no electrical contact with the circuit. Only when the button is pressed
down does it make electrical contact with the circuit.
When the button is pressed down, the switch makes electrical contact and the
circuit is now closed. Therefore, electricity can now flow to the other part of
the circuit connecting to the push button and make the device turn or power
on the respective part.
Normally Open Push buttons are the most common type of push buttons
used in devices and circuits.
6. NC AUXILIARY CONTACT
7. CONNECTOR
These strip connectors feature tubular screw clamps and wire protectors
which are actuated by a screw. They are available in 2.5, 4 & 6 sq.mm. sizes
and are compact & ideal for small spaces. They can be used as free floating
connectors or as panel mounted terminal blocks. Available in standard 12-
pole strips these can be easily cut into combinations of smaller number of
poles.
Working Principle of Star-Delta Starter
The most basic feature of an Induction motor is its self starting mechanism.
Due to the rotating magnetic field, an emf is induced in the rotor, because of
which current starts flowing in the rotor. As per the Lenz law, the rotor will
start rotating in a direction so as to oppose the flow of electric current and
this gives a torque to the motor. Thus the motor gets self started.
A star delta starter is the most commonly used method for the starting of a 3
phase induction motor. In star delta starting an induction motor is connected
in through a star connection throughout the starting period. Then once the
motor reaches the required speed, the motor is connected in through a delta
connection.
Here, the motor starts with a star connected stator winding, and as when
motor reached about 80% of its full load speed, it begins to run in delta
connected stator winding.
As the winding is star connected, the winding current per phase (IPS) equals
to supply line current (ILS).
As the winding is star connected, the voltage across each phase of the
winding is
Now, let us consider the situation where the motor gets started with delta
connected stator winding from same three phase supply points
Here, ILD = Supply Line Current and, IPD = Winding Current per Phase and
Z = Impedance per phase winding at stand still condition.
As the winding is delta connected, supply line current (ILD) is root three
times of the winding current per phase (IPD)
As the winding is delta connected, the voltage across each phase of the
winding is
Thus we can say that the starting current from the mains in case of star delta
is one-third of direct switching in the delta. Again, we know that the starting
torque of an induction motor is proportional to the square of the voltage
applied to the winding per phase.
The equation shows that star delta starter reduces the starting torque to one-
third of that produced by DOL starter. The star-delta starter is equivalent to
an autotransformer with a 57.7% tapping. Also, the starting torque of a motor
is directly proportional to the square of the voltage at the windings
T ∝ V2
Star/Delta starters are probably the most common reduced voltage starters.
They are used in an attempt to reduce the start current applied to the motor
during start as a means of reducing the disturbances and interference on the
electrical supply.
The current in star is one third of the current in delta, so this contactor can be
AC3 rated at one third (33%) of the motor rating.
L1, L2 and L3 are the 3-phase line voltages, which are given to primary
contactor. The main motor coils are U, V and W is shown in figure. In star
mode of motor windings, the primary contactor associate the mains to
essential winding terminals U1, V1 and W1.the star contactor shorts the
auxiliary winding terminals U2, V2 and W2 as indicated in figure.
Notwithstanding when the primary contactor is shut supply arrives at
terminals A1, B1, C1 and consequently the motor windings are energized in
star-mode.
The main difference between manual star delta starters and automatic star
delta starters is the automatic switching from Star Connection to Delta
Connection based on predefined time intervals.
A Time Delay Relay is used to obtain the necessary time before switching
from Star to Delta. Depending on the capacity of the motor and its load
conditions, the time delay can be more or less around 10 seconds.
The wiring diagram of an Automatic Star Delta Starter is same as that of the
Semi – Automatic Star Delta Starter. But there is a significant difference in
the control circuit, which is shown in the following image.
First, the ON button is pushed and the contactor S gets energized. This will
close the contact S1 and hence the contactor M will get energized. Since
both the contactors S and M are active, the motor starts rotating in Star
Connection.
When the contactor S is activated, the Time Delay Relay T is also energized.
As a result, the motor windings stay in Star Connection until the time set in
the Time Delay Relay.
After the preset time (say 10 seconds) is up, the contact of Time Delay Relay
i.e. T1 gets opened, resulting in de – energizing of contactor S.
In this Automatic Star Delta Starter, the Delta Connection is established only
after the Star Connection is released. This type of connection is called Open
Circuit Transition.
Automatic Star Delta Starter (Closed Circuit Transition)
The Open Circuit Transition type Automatic Star Delta Starter discussed in
the above section is sufficient for almost all motors but we need a Closed
Circuit Transition type Automatic Star Delta Starter in order to block power
disturbances.
The additional components are a 3 pole contactor and few resistors. The
following image shows the wiring diagram of the Automatic Star Delta
Starter with Closed Circuit Transition.
The main problem with Open Circuit Transition is that the windings of the
motor gets disconnected from the supply for a small duration during the
transition from Star to Delta Connection.
During the startup, the contactors S and M (Star Connection Contactor and
Main Contactor) gets activated and the motor starts rotating. As it gains
speed, the Time Delay Relay Contactor T is energized.
The main difference between the open and closed circuit transitions is that
the Timer Contactor T is connected in parallel to the Delta Contactor D
through the resistors.
After the time delay, the contactor S is deactivated and the contactor D gets
activated. As a result, the windings get connected in Delta Connection.
The following images shows the control circuit for Closed Circuit Transition
type Automatic Star Delta Starter.
When the ON button is pushed, the control relay contactor CR is energized
and the corresponding supplementary contacts CR1 and CR2 will be closed.
As CR2 is closed, the Star Connection contactor S is energized.
Along with the main contactor M, the Timer A gets activated. After a
predefined time, the auxiliary contact of A i.e. A1 is closed, which will
energize the Timer Contactor T and Timer B.
Now, the energizing of the Timer T will result in connecting the resistors in
parallel to the motor windings. The Timer B, which was energized by A1,
operates after a time delay and opens its auxiliary contact B1.
Now, the open B1 will deactivate the S contactor, which will disengage the
Star Connection at the motor windings. As S is de – energized, the contact
S2 is closed and as a result, the Delta contactor is activated. The contactor T
will help the Delta connected windings to stay connected to the supply
through the series resistors.
When a motor is driven by the supply, either at full speed or at part speed,
there is a rotating magnetic field in the stator. This field is rotating at line
frequency. The flux from the stator field induces a current in the rotor and
this in turn results in a rotor magnetic field.
When the motor is disconnected from the supply (open transition) there is a
spinning rotor within the stator and the rotor has a magnetic field. Due to the
low impedance of the rotor circuit, the time constant is quite long and the
action of the spinning rotor field within the stator is that of a generator which
generates voltage at a frequency determined by the speed of the rotor.
Delta State: The Main and the Delta contactors are closed. The Star
contactor is open. The motor is connected to full line voltage and full power
and torque are available
Merits:
Demerits:
Open transition makes a surge of current and torque at change over which
stuns the system both electrically and mechanically. Electrically, the
outcome of the momentary peaks in current could cause force vacillations or
misfortunes. Mechanically, the expanded torque coming about because of
the current spike could be sufficient to harm system components i.e. snap a
drive shaft.
2. Closed Transition Star/Delta Starter
The auxiliary contactor and resistors are connected across the delta
contactor. In operation, just before the star contactor opens, the auxiliary
contactor closes resulting in current flow via the resistors into the star
connection. Once the star contactor opens, current is able to flow round
through the motor windings to the supply via the resistors. These resistors
are then shorted by the delta contactor.
If the resistance of the resistors is too high, they will not swamp the voltage
generated by the motor and will serve no purpose.
Star State: The Main [KM3] and the Star [KM1] contactors are closed and
the delta [KM2] contactor is open. The motor is connected in star and will
produce one third of DOL torque at one third of DOL current.
Star Transition State: The motor is connected in star and the resistors are
connected across the delta contactor via the aux [KM4] contactor.
Closed Transition State: The Main [KM3] contactor is closed and the Delta
[KM2] and Star [KM1] contactors are open. Current flows through the motor
windings and the transition resistors via KM4.
Delta State: The Main and the Delta contactors are closed. The transition
resistors are shorted out. The Star contactor is open. The motor is connected
to full line voltage and full power and torque are available.
Merit:
It is Important the pause between star contactor switch off and Delta
contactor switch is on correct. This is because Star contactor must be reliably
disconnected before Delta contactor is activated. It is also important that the
switch over pause is not too long.
For 415v Star Connection voltage is effectively reduced to 58% or 240v. The
equivalent of 33% that is obtained with Direct Online (DOL) starting.
If Star connection has sufficient torque to run up to 75% or %80 of full load
speed, then the motor can be connected in Delta mode.
During transition period of switchover the motor must be free running with
little deceleration. While this is happening “Coasting” it may generate a
voltage of its own, and on connection to the supply this voltage can
randomly add to or subtract from the applied line voltage. This is known as
transient current. Only lasting a few milliseconds it causes voltage surges
and spikes. Known as a changeover transient.
SIZE OF EACH PART OF STAR-DELTA STARTER
In the line is the same as just putting the overload before the motor as with a
DOL starter.
In the windings means that the overload is placed after the point where the
wiring to the contactors are split into main and delta. The overload then alw
ays measures the current inside the windings.
The setting of Overload Relay (In Winding) =0.58 X FLC (line current).
There are two contactors that are close during run, often referred to as the
main contractor and the delta contactor. These are AC3 rated at 58% of the
current rating of the motor.
The third contactor is the star contactor and that only carries star current
while the motor is connected in star. The current in star is 1/ √3= (58%) of
the current in delta, so this contactor can be AC3 rated at one third (33%) of
the motor rating.
.
High transmission and current peaks: When starting up pumps and
fans for example, the load torque is low at the beginning of the start
and increases with the square of the speed. When reaching approx. 80-
85 % of the motor rated speed the load torque is equal to the motor
torque and the acceleration ceases. To reach the rated speed, a switch
over to delta position is necessary, and this will very often result in
high transmission and current peaks. In some cases the current peak
can reach a value that is even bigger than for a D.O.L start.
The transition from star to delta transition usually occurs once nominal
speed is reached, but is sometimes performed as low as 50% of
nominal speed which make transient Sparks.
FEATURES OF STAR-DELTA STARTING
Price
Material Unit Total
(p.u.)
Contactor 3 890 2670
Overload Relay 1 950 950
Timer 1 820 820
Push Button 2 60 120
NO+NC 2 40 80
Indicator 2 70 140
TOTAL 7050
COSTING
Price of Material
7050
Labour Cost
705
(10% of Material cost)
Sub Total - 1
7755
Contingencies
233
(3% of Material & Labour cost)
Supervision Charge
(10% of Sub Total cost) 884
Total
(Sub Total + Supervision Charge) 9725
Profit
(20% of Total cost) 1945