Sunteți pe pagina 1din 2

MODBUS REGISTER LIST

Date: Document №: Vers.: Rev.: Sheet / of:


08.02.16. SN080216 -Е -R00 1/2

Rev. Description Date Designed Approved


00 First edition 08.02.16. VS LB

TITLE:
MODBUS REGISTER LIST

EMERGENCY/HARBOUR DIESEL GENERATOR SET


ADB SK355MS-D2876LE201

FOR INFORMATION ONLY


MODBUS REGISTER LIST
Date: Document №: Vers.: Rev.: Sheet / of:
08.02.16. SN080216 -Е -R00 2/2

1. CONTROLLER HARDWARE CONFIGURATION

Interface 2-wire
Protocol Modbus RTU
Reservation No
Cable type Copper (shield twisted pair)
Controller address 1
Operation mode RS485 (direct connection)
Communication speed 57600 bps
Data bits 8
Stop bit 1
Parity check No parity

Controller type ID-DCU-MARINE (ComAp)


Firmware version 2.2 R:12.11.13
Software version 2.2

FOR INFORMATION ONLY


2. DATA TABLE

Modbus Setpoints
Signal description Range Unit Data type
address LL L H HH
1 2 3 4 5 6 7 8 9
40011 Battery voltage 0...40,0 V Integer
40013 Oil pressure 0...10,0 bar Integer
40014 Coolant pressure 0...10,00 bar Integer
40015 Fuel pressure 0...10,00 bar Integer
40017 Coolant temperature 0...200,0 °C Integer
40018 Oil temperature 0...200,0 °C Integer
40106 Engine speed (RPM) 0...3000 2070 RPM Integer
43034- Run hours h Integer
43035 ( 2)
43132 Low oil pressure 0...10,0 1,5 bar Integer
43133 Low coolant pressure 0...10,00 0,20 bar Integer
43134 Low fuel pressure 0...10,00 0,40 bar Integer
43135 High coolant temperature 0...200,0 93,0 °C Integer
43136 High oil temperature 0...200,0 120,0 °C Integer
40001.4 Fuel leakage (high level) X Binary
40001.5 Low coolant level (in expansion tank) X Binary
40001.11 DC Power fault Binary
40001.13 Louver failure (Louver fail to open) Binary
40103.0 Oil pressure too low 0,5 ... 3,0 1,0 bar Binary
40103.1 Coolant temperature too high 70 ... 120 95 °C Binary
40103.5 Local emergency stop Binary
40010.2 Alarm blink (Common alarm) Binary
40010.3 Ready for remote start Binary
40010.5 Engine running Binary
40079.8 Engine controller in EME mode Binary
40079.9 Engine controller in HRB mode Binary
40079.12 Engine in LOCAL mode of operation Binary