Engine No.1 AUX ID-DCU-Marine-1.7.1 R:28.8.2009 15.12.2010 1,7
Type Number Name Protection Prot. active
Binary input 1. Remote Start No protection Closed Binary input 2. Remote Stop No protection Closed Binary input 3. Fault Reset No protection Closed Binary input 4. Not Used No protection Closed Binary input 5. Not Used No protection Closed Binary input 6. Not Used No protection Closed Binary input 7. CoolantLowLev Warning Opened Binary input 8. Fuel Leak Warning Opened Binary input 9. Not Used No protection Closed Binary input 10. Not Used No protection Closed Binary input 11. Not Used No protection Closed Binary input 12. Not Used No protection Closed Binary input 13. Not Used No protection Closed Binary input 14. Not Used No protection Closed
Type Number Source Name Inverted
Binary output 1. Starter Starter No Binary output 2. OFF Mode OFF Mode No Binary output 3. In LOC In LOC No Binary output 4. Engine Running Engine Running No Binary output 5. Battery Fail Battery Fail No Binary output 6. Horn Horn No Binary output 7. Overspeed Overspeed No Binary output 8. Start Fail Start Fail No Binary output 9. Not used Not Used No Binary output 10. Alarm Blink Alarm Blink No Binary output 11. Not used Not Used No Binary output 12. Not used Not Used No Binary output 13. Not used Not Used No Binary output 14. Not used Not Used No
Type Number Name Dim Sensor
Analog input 1. Oil Press Bar 4-20mA active Analog input 2. Coolant Press Bar 4-20mA active Analog input 3. Not Used - None Analog input 4. Not Used - None Analog input 5. Coolant Temp °C PT100/°C Analog input 6. Oil Temp °C PT100/°C Analog input 7. Not Used - None Analog input 8. Not Used - None Ser. num. File name Module 01102326 DCU-Marine-AUX-1.7_Malaysia1.aid ID
Prot. block type Delay Function
All the time Standard (0,5s) Remote Start All the time Standard (0,5s) Remote Stop All the time Standard (0,5s) Fault Reset All the time Standard (0,5s) All the time Standard (0,5s) All the time Standard (0,5s) All the time Standard (0,5s) All the time Standard (0,5s) All the time Standard (0,5s) All the time Standard (0,5s) All the time Standard (0,5s) All the time Standard (0,5s) All the time Standard (0,5s) All the time Standard (0,5s)
Resolution Sensor range Protection Active when Block type
0,1 10,0 Wrn+Shutdown Under limit RunOnlyBlkDel1 0,01 10,00 Warning Under limit RunOnlyBlkDel1 1 0 No protection 1 0 No protection 0,1 0,0 Wrn+Shutdown Over limit All the time 0,1 0,0 Warning Over limit All the time 1 0 No protection 1 0 No protection Bargraph 0% Bargraph 100% Function 0,0 10,0 Oil Press 0,00 10,00 0 10 0 200 0,0 200,0 Coolant Temp 0,0 200,0 0 200 0 200 Name Application Firmware ver. Date App. ver. Ser. num. Engine No.1 AUX ID-DCU-Marine-1.7.1 R:28.8.2009 15.12.2010 1,7 01102326
Type Number Name Protection Prot. active Prot. block type
Binary input 1. Not Used No protection Closed All the time Binary input 2. Not Used No protection Closed All the time Binary input 3. Not Used No protection Closed All the time Binary input 4. Not Used No protection Closed All the time Binary input 5. Not Used No protection Closed All the time Binary input 6. EmStop RPU No protection Opened All the time
Type Number Source Name Inverted
Binary output 1. Not used Not Used No Binary output 2. Stop Solenoid Stop Solenoid No Binary output 3. Common Sd Common Sd No Binary output 4. Common Wrn Not Used No File name Module DCU-Marine-AUX-1.7_Malaysia1.aid RPU
Delay Function Standard (0,5s) Standard (0,5s) Standard (0,5s) Standard (0,5s) Standard (0,5s) Standard (0,5s) Emergency Stop