Documente Academic
Documente Profesional
Documente Cultură
Standardisation level
Principles
Functional specification
Technical specification
Product sheet
Procedure
Document Semantics
Governing Superior
Documents:
Standardisation
Control:
Standard
Standardisation Area:
Amendment History
nd
0.2 25/11/08 Michael Briese 2 draft
Disclaimer
" The requirements and guidelines set out in this document shall not apply or be implemented to the extent that they do not meet the requirements
of applicable laws and regulations. In all cases, all applicable legal and regulatory requirements must be met when conducting activities
associated with this document."
Table of contents
Document Semantics .................................................................................................................................................... 2
Glossary of terms........................................................................................................................................................... 5
Introduction..................................................................................................................................................................... 6
Testing Equipment....................................................................................................................................................... 17
Appendixes ................................................................................................................................................................... 27
Glossary of terms
ALARP As low As Reasonably Practical
CoE Centre of Excellence
CMAS Contractor Management Accreditation System
DW Double Wall, term used for secondary containment pipe and UST
D&S Design and Standards
EIT Equipment Integrity Testing
FMC Facilities Management Company
GEMS Global Environmental Management Standards
Pressure Dispensing systems that split the pump from the dispenser, pump
Systems contained within the tank pressurising the dispensing line
NWGLDE National Work Group on Leak Detection Evaluations
PLLD Product Line Leak Detection – Used on Pressure Systems
PLIP Product Loss Investigation Procedure
PMC Project Management Company
PM Project Manager
PTW Permit To Work
SIRA Statistical Inventory Reconciliation Analysis
Siphon Systems which see UST’s connected through common pipe work, a
Systems pump or dispenser/s operating from two or more tanks at the same
time
Suction Dispensing systems that incorporate the pump and liquid meter
Systems within the one dispenser housing, lifting product from the tank
under vacuum
SW Single Wall. Term used for piping and UST that have primary
containment without secondary containment
SFL Safe Fill Level
UPSS Underground Petroleum Storage System
Introduction
EIT (Equipment Integrity Testing) is a technology that’s used to check the physical integrity of UPSS (Underground Petroleum
Storage System). Many service providers exist throughout the world however, this standard identifies with one method that is
preferred based on a criterium for Vacuum testing and a certified detectable leak rate.
The purpose of this Standard is to provide a consistent approach to Shell Project Managers and representatives (FMC and PMC)
across the Shell Retail Networks for the testing of existing underground storage tanks and associated equipment that are at Shell
branded retail locations i.e. Shell has ownership of the UPSS.
This standard identifies with one testing method that is preferred based on the following criteria
Shell’s commitment to HSSE is such that no one undertaking EIT should compromise safety in any way. If there is any doubt as to
whether or not an activity is safe; STOP, assess and determine the appropriate course of action to perform the work safely in
an environmentally sound manner.
This standard is not designed to address any general or specific questions that may apply to a particular job or set of facts.
Contractors that undertake EIT are required to perform all work activities in a safe and environmentally sound manner in compliance
with all laws and regulations, and consistent with this standard.
This document shall be periodically reviewed and modified as appropriate by the Retail Network – Design Standards Engineering
Centre of Excellence (COE).
Annual updates will be published on the Network Engineering Design and Engineering Construction Standards Website.
Pressurisation of Tanks
Pressurisation of tanks and overfilling methods for testing tanks is not preferred under this standard as excessive pressurisation or
overfilling in any form can accelerate loss and can become uncontrollable once a leak occurs i.e. any pressurisation or overfilling of
a tank can cause significant loss associated with tank shell failure impacting the safety of the operator, asset and environment
however; some regulators stipulate methods of testing by pressurisation, check with the D&S CoE before committing to the pressure
testing of UPSS.
Exceptions
The Standard does not set out to reduce or lower any existing standard that may exist, this must be viewed as the minimum criteria
for all Shell owned and branded Retail outlets however, regulatory compliance in all countries must be observed as testing methods
may differ to this standard e.g. pressure testing tanks.
It is expected that Shell Engineers, Shell Representatives, and Tank Testing Contractors are knowledgeable of the local
conditions and contents of this document prior to performing any EIT (Equipment Integrity Test) activities.
The engineering CoE can assist when implementing this standard to a new market.
EIT Criteria
The standard for EIT is set against recognised certified tank-testing methods that have been set against a globally accepted method
for the accreditation of leak detection systems i.e. the NWGLDE.
The National Working Group for Leak Detection Evaluations sets guidelines, monitors the performance and recognises EIT
companies through approved third party certifications, most countries accept this as the globally approved method for evaluating EIT
methods.
The objective of a minimum leak rate criteria is to help set a standard for the detection of leaks, and if present, detectable through
EIT i.e. ‘the test shall result in a conclusive statement whether the UST contains a leak or not.
In this context the term “no leak” means that there is “no leak” above the detection threshold, which implies that under operating
conditions if there is a leak it is equal or lower than 0.37 litres/hour (0.1 US gallon/hour).
The test procedure shall unambiguously state the detection threshold under test conditions and the relation to operating conditions.
The testing method is based on applying under-pressure (vacuum) to the tank and registering Acoustic or Mass signals induced by
air or water ingress into the tank i.e. Leak Tightness Testing shall be carried out by the vacuum test method where the sensing
mechanisms shall be based on a combination of:
A (partial) vacuum is applied so that the pressure on the bottom of the tank is lower than the pressure outside the tank. An acoustic
sensor is used to listen for the tell tale sounds that indicate bubbles in the product filled portion of the tank, a Mass sensor is used to
measure the loss or gain of product within the wetted portion of the tank, these sensors indicate the presence of water ingress or
product loss and are detected through these sensors placed at the within of the tank.
The possibility of line failure associated with product loss or water ingress into tanks being detected before the tank shell is
subjected to testing can change the conditions for the tank test e.g. product drain back from lines or ingress of water can alter the
conditions of the test. Lines must be tested prior to tank shell.
Tanks are to be dipped before testing commences for product and water level. Water should be removed from the tank before
testing commences.
The tank is to be isolated from the sites other UPSS i.e. any manifolded or shared pipe work needs to be isolated from other tank
systems at the time of the test.
* Important Note
1. Using pressure is potentially dangerous; check all associated fittings and valves for max pressure operation, do not
exceed manufactures recommendations for pressure, if in doubt remove or isolate from line.
2. The use of pressurised air is not permitted, Nitrogen pressure only.
3. When testing against spaded lines to tank top insure tank is in free venting condition, pressurisation of lines associated with
tank ullage can bypass causing an over pressurisation of tank shell.
4. The test conditions shall comply with the mode of operation as applicable in the tank station. Special attention is required for
cascaded tanks and interconnecting pipes. In case shut-off valves are present, these may be used to separate the tanks to
allow individual testing however, only when these fittings are pressure rated and confirmed to be suitable for said pressures.
When these are not the case, installation of isolation spades should be considered or isolate tanks from pipe work.
5. The maximum allowable under pressure shall not exceed the limits as dictated by plastic collapse of the tank.
The following table identifies the types of tanks and minimum requirements for testing.
Tanks Test Parameters and Conditions
Steel Single • Vacuum test Ullage only, vacuum must not exceed 126mm Hg (5 inches Hg)
• Tank to be tested with product, minimum level 10% of SFL to Safe Fill Level and free of water
Wall • Vacuum testing to be conducted with two probes where access is available, positioned at opposite ends of tank.
• If using Mass detection probes, tanks are required to be at 75% of SFL.
• Isolations within tank chambers are required, where not possible treat as a system test
• Isolate all other equipment
Steel - Double • Tanks with vacuum or brine interstitial monitored space, if tank monitor holding no need to test tank shell. When chasing water ingress or loss associated with
tank, test Pipework associated with ullage independently of a tank or as a system test within the ullage
Wall • Vacuum test Ullage only, vacuum must not exceed 126mm Hg (5 inches Hg)
• Tank to be tested with product, minimum level 10% of SFL to Safe Fill Level and free of water
• Vacuum testing to be conducted with two probes where access is available, positioned at opposite ends of tank
Steel with FRP • If using Mass detection probes tanks are required to be at 75% of SFL
Liner • Monitor interstitial gauge for pressure or liquid level while testing
• Isolations within tank chambers are required, where not possible treat as a system test.
• Isolate all other equipment
FRP Single • Vacuum test Note; vacuum must not exceed 126mm Hg (5 inches Hg)
• Tank to be tested with product, minimum level 10% of SFL to Safe Fill Level and free of water
Wall • If using Mass detection probes tanks are required to be at 75% of SFL.
• Vacuum testing to be conducted with two probes where access is available, positioned at opposite ends of tank. If using Mass probe access via dip tube.
• Isolations within tank chambers are required, where not possible treat as a system test.
• Isolate all other equipment
Tanks with Testing conditions for modified or lined tanks should be checked with the manufactures recommendations for testing e.g. vacuum testing steel tanks with internal FRP
liners can void the warranty of the liner.
after market Your DS CoE can assist when undertaking these tests
linings
FRP Double • Vacuum test Note; vacuum must not exceed 126mm Hg (5 inches Hg)
• *Never apply a vacuum or pressure to the Hydro-guard reservoir and or wet interstitial space as doing so may cause damage to the primary tank. *
Wall • Tanks have interstitial space, brine filled, if brine level holding no test required on tank shell.
• Best results, vacuum test inner tank while monitoring interstitial space level, see manufactures recommendations for testing FRP DW Tanks
• Tank to be tested with product, minimum level 10% of SFL to Safe Fill Level and free of water
• If using Mass detection probes tanks are required to be at 75% of SFL.
• Vacuum testing to be conducted with two probes where access is available, positioned at opposite ends of tank.
Line Testing
Line testing can be conducted independently of the tank or can be conducted as a system test associated with all lines connected to
the tank top.
Independently testing lines through a series of isolations from the tank is required when equipment e.g. dispensers, VR 2 are
showing signs of air ingress or overall performance issues.
Hydrostatic line testing against spaded or isolated fittings is preferred however, in some cases the isolation cannot be conducted as
the fittings are directly buried i.e. without access, in these cases a system test (which includes tank and lines) are tested together.
When failure occurs under a system test, the lines will need to be mechanically isolated from the tank so they can be eliminated
from the test/failures.
The following table identifies the UPSS associated lines and minimum testing requirements.
Pressure Isolation of Pipework within tank chamber required, *Do not test against ball or gate valves; see 1.5 times operating pressure up to
note below. Isolate electrics and tag out. Ensure system is recommissioned before opening and not exceeding 350kpa
Lines Single dispensers. *See additional notes on Electronic and Mechanical Leak Detectors
Wall
Pipe Work All Pipework with secondary containment must have the interstitial open to atmosphere when For steel Pipework up to 250kpa
tested; remove the monitor gauge or primary pressure valve before testing. Fibreglass Pipework 250kpa
with Polyethylene 250kpa
secondary
containment
VR1 * Isolate VR1 at the tank tops, pressurize VR1 circuit across all tanks and ensure tank is free For steel Pipework up to 35kpa
venting. Lower Pressures as tank top adaptors and termination fittings usually untested Fibreglass Pipework 35kpa
components* Polyethylene 35kpa
VR2 This does not include central vac systems or VR2 hanging hardware for dispensers. Isolate all For steel Pipework up to 35kpa
associated equipment and test VR2 loop pipe work separately. Fibreglass Pipework 35kpa
Polyethylene 35kpa
Vent Vents tested as part of the system, this could show up as ullage failure associated with the tank. For steel Pipework up to 35kpa
Any ullage failure found then vents should be isolated retested to eliminate from tank shell failure Fibreglass Pipework 35kpa
Polyethylene 35kpa
Dip Tubes Dips tested as part of the system, this could show up as ullage failure associated with the tank. Any For steel Pipework up to 35kpa
ullage failure found then dips should be stung out at tank top or removed from the tank, tank FRP Pipework up to 35kpa
Dewater retested to eliminate from tank shell failure.
Direct Fill
Indirect Fill Preferred isolated from tank via the overfill protection device. If direct buried test with tank. Any For steel Pipework up to 35kpa
ullage failure found then fill should be isolated at tank top or removed from the tank, fill retested to Fibreglass Pipework 35kpa
eliminate from tank shell failure. Polyethylene 35kpa
Typically placed on the submerged pump inside the tank. They constantly monitor the integrity of the pressure piping between the
pump and the nozzles of the vending point.
The system incorporates an electronic or mechanical operated valve. This valve remains in the “open” position because of the
remaining pressure in the pressure piping, after the pump has stopped.
When a leak occurs, fuel will drain from the pressure piping, thus lowering the pressure. The valve no longer retains its open
position but moves into the “test” position or complete shut down of the pressure pump.
Testing of product delivery lines associated with pressure systems fitted with leak detectors should be considered when
A single product delivered through pressure systems often links to other dispensers across the forecourt; isolations will need to be
conducted once all dispensers feeding from the common line are identified, tank testing companies should not test against the leak
detectors or under pump emergency shut off valves.
Line leak detectors are to be tested annually through normal maintenance associated with leak detection devices or constantly
monitored systems. Tank testing companies that are engaged to test Line Leak Detectors will need to be accredited by the
manufacturer and or the distributor of the leak detection equipment. Links to reference documents are within the appendix 1.8
VR2 testing
Tank testing companies that are engaged to test VR2 equipment are required to be accredited by the manufacturer and or the
distributor of said equipment.
As the testing and certification of VR2 equipment is heavily influenced by local regulatory compliance set against the equipments
performance, EIT companies must be aware of the said equipment performance criteria and regulations that govern its use.
Testing Equipment
All equipment to be used within the area designated by the client as exhibiting a higher risk shall be intrinsically safe and the
equipment manufacturers or test authorities proof of compliance shall be available on request.
• The equipment shall NOT be operated outside the operational limits as stated by the equipment manufacturer or
acknowledged test authority.
• The equipment shall be maintained in line with the equipment manufactures specification/recommendations. Prior to
inspection all equipment shall be checked for damage. Any damage that influences the intrinsic safety capability or
functionality of the equipment shall result in denial of that equipment for the test.
• All pressure measuring device(s) shall be bench calibrated using either a reference gauge or incline manometer. Calibration
shall be performed at 20, 50, and 80 percent of full scale. Accuracy shall be within two percent at each of these calibration
points. Calibrations shall be conducted on a frequency not to exceed 90 days.
• The procedure shall include information on the type and brand of equipment
• The procedure shall include a clear description on how to set-up the equipment.
The “hydrophone”
• The “hydrophone” shall be positioned in the liquid phase.
• The hydrophone shall be sensitive for the sound of rising bubbles as a result from air ingress in the liquid phase.
Consequently the hydrophone shall be most sensitive in the range between 4 kHz and 8 kHz. The sensitivity shall allow for a
minimum detection of an induced leak rate of 0.37 litres per hour (0.1 gallon/hour) under practical conditions pertaining noise
levels.
Mass Probes
• Mass detection probes must be positioned at the bottom of the tank, tanks must be at a minimum of 75% SFL before testing
to obtain the best results. Tank bottom must be free of scale and rust a clean surface must be obtained. Location of the probe
can be via direct dip, dewater or fill port preferably with internal tube in place so as to locate probe at tank centre.
• Microphone (hydrophone) should be located within 3 meters of any possible leak source.
Noise signals are recorded so that test data can be reviewed by the test operator or other qualified individuals.
Since the method depends on an audible interpretation of the signal, the test must be conducted under reasonably quiet
conditions.
Vibrations due to heavy traffic, nearby trains, or construction activities could produce sound levels that could compromise the
test.
Earphones
• An earphone shall allow the operator to listen to the received sounds in order to discriminate between leak signals and
background noise. For the acoustic microphone a frequency shift mode shall allow the operator to hear and evaluate the
relevant frequency range. •
• The operator sound system shall allow for easy switching between the microphone and “hydrophone”.
Functionality requirements.
The status of the equipment shall be verified on damage and functionality. The performance of the sensing and measuring
instrument(s) shall be verified at intervals not to exceed 3 months when in use, or immediately following repair and/or modifications.
Functionality test Depending on the type of sensors to be used, functionality and sensitivity demonstration test shall be executed as
described in the test procedure.
• Inspection tags are required to validate and must be attached to the equipment at all times e.g. information should include
date of last inspection
• The tank test company will have a procedure and process for the Verification and recertification of equipment, this should be
made available on request and service records should be kept with the testing equipment on site
• Licensees must abide by the Licensors validation and certification procedures; the Licensor is responsible for ensuring
Licensees are following testing protocols and equipment verifications.
• If mechanical pressure gauges are employed, the maximum incremental graduations of the pressure gauge shall be 10mbar
and the minimum accuracy of the gauge shall be three percent of full scale. The minimum diameter of the pressure gauge
face shall be 4 inches.
• If an electronic pressure-measuring device is used, the full-scale range of the device shall not exceed 0-150mbar with a
minimum accuracy of 0.5 percent of full-scale.
Contractor Requirements
1. The tank-testing contractor shall prepare the required documentation (procedure). The inspection procedure shall control the
set-up, execution and reporting of the testing. The inspection procedure shall include the details on which the client shall
provide information in order to allow proper test preparations, preferably in the form of a detailed service request form, see
example appendix 1.4.
1. The procedure shall be submitted to the client for acceptance.
2. Personnel, which carry out the test, evaluate the data and work out the reporting, shall be trained and have proven
experience in the application of the test method and the inspection procedure. The contractor shall make the personnel
qualification details and an overview of their experiences available to the client. Based on a review of the inspection
procedure, and the personnel qualifications and experience details, the client may require a third party qualification of the
procedure, equipment and personnel.
3. Before each test the client shall provide the service provider with the required details (to be stipulated in the inspection
procedure).
4. The service provider shall review the provided information and will ask for additional information when required. The service
providers will set-up a detailed test plan. Any operational aspect shall be discussed with the client, especially those aspects
that influence availability and safety. Aspects that may lower the detection threshold shall be discussed prior to the test.
5. The test will be carried out according to the inspection procedure and when required a specific test plan.
6. Immediately following completion of a test, a written field report shall be provided to the client. As minimum the field report
shall include concluding statement pertaining leak tightness. When applicable any procedure deviation including their
(anticipated) effect shall be included too.
7. Full reporting shall be provided within 10 working days after testing, or as agreed in the contract.
Personnel requirements
The inspection shall be carried out by personnel who shall:
1. Have received a proven and auditable class room training of minimum 32 hours in the test method, to incorporate as
minimum all influential parameters, equipment features, practical aspects, HSE (Health, Safety and Environment) and data
evaluation.
2. Be trained in the field and have proven experience of a minimum of 3 months and 20 UST tests in the application of the test
method.
3. The contractor shall make the personnel qualification details and an overview of their relevant experiences available to the
client on request.
4. The licensor of the test protocols should ensure that all licensees have a current certification card with a set expiration date.
5. The licensor is responsible for the audit which includes checks for the recertification of equipment, personal training and
updates for any regulatory or technology changes. Notification of changes to be forwarded to the DS CoE
6. Be accredited by the local industry standards as applicable
7. Be trained in the Shell PTW system to the minimum level of, Permit Holder
The intention of the minimum service and reporting requirements are to ensure EIT contractors set-up, perform and report in line
with the requirements and intentions as per the technical requirements outlined within their certification and Shells requirements for
servicing and reporting.
Initiated by Shell or its representatives the EIT contractor shall prepare all the required documentation. The documentation shall
control the set-up, execution and the reporting i.e.
1. The documentation shall include the details that Shell or its representatives need to provide in order to allow proper test
preparations, in the form of a Detailed EIT Request Form. See example appendix 1.4
2. The documentation shall be submitted to Shell or its representatives for acceptance.
3. The EIT contractor shall review the provided information and will ask for additional information when required
4. The EIT contractors will set-up a detailed test plan. Any operational aspect shall be discussed with Shell or its
representatives, especially those aspects that influence the availability of the EIT and or require additional safety preparations
for the EIT companies to operate
5. Immediately following completion of a test, a verbal field report shall be provided to the Shell or its representatives
6. Full report is required following the minimum reporting requirements as set out within this document.
EIT companies that meet Shells contractor accreditation; industry standards and testing criteria must have the following minimum
service levels and reporting processes in place
• All associated and certified testing equipment including access capabilities, barricades and signage
• Detailed Service Request Forms
• Online booking, online reporting and confidential customer links. In areas where this is not possible the contractor will provide
written reports.
• Response time to call out, 1 working days or as agreed with Shell or its representatives and or local maintenance contracts
that include minimum call out requirements
• Onsite diagnoses and offsite Quality Assurance capabilities
• Tank tester shall maintain call up log of tightness test failure reports. All confirmed failures must be immediately reported to
Shells Representative to allow immediate removal of relevant product from service
• The Tester shall log the date which the product has been taken from service
• Record retention, minimum 7 years or as per local regulatory compliance
• Record Recovery within 3 working days of request
Undertaking EIT in some cases requires the isolation of associated equipment e.g. product pipe work, dispensers, integrated VR
systems and Vents may require separation from other UPSS onsite.
In most cases the isolations can be conducted from tank access points or tank chambers positioned above the UST however, Any
works associated with the EIT that sees the contractor enter a confined space or is placed in an activity outside of the normal
procedures for EIT, must be reassessed under the PTW system e.g.
1. Work Clearance, mandatory on all sites and renewed every day and identifies high-risk work associated with the testing i.e.
outside the normal scope for testing
2. JHA, is prepared and discussed with Shell or its representatives, EIT technician applies for a Permit to Work
3. PTW, Shell or its representative issues a PTW, EIT technician operates within the agreed work scope and procedure as
outlined by the JHA under permit conditions
Tank construction parameters (e.g. wall thickness, construction material) are not of influence on the detection method however;
associated piping systems can influence the outcome of the total system.
In this case experienced tank installation contractors may be required to isolate system pipe work and prepare the site for testing,
other equipment that may see specialised works prepared prior to testing are;
Appendixes
EIT companies, which are nominated under the NWGLDE as approved and certified but do not meet the above criteria (Vacuum
Testing) must be approved under this standard by the Design Standards team. The DS CoE will assist and provide approval when
alternative tank testing companies are to be used.
Contact
Site
Address
Equipment to be Tested
Specific
Instructions
Within Shell a system to investigate losses associated with the reconciliation of all products stored in UPSS is in use.
PLIP (Product Loss Investigation Procedure) is a step-by-step process that identifies loss associated with SIRA (Statistical Inventory
Reconciliation Analysis) and product reconciliation procedures.
In the advent that SIRA is not used the process for PLIP is still relevant using the local operators reconciliation information.
PLIP A – Product loss investigation undertaken firstly by the site then the Retail Wet Stock Analyst. This involves reconciling all
product movement including deliveries.
Daily Reconciliation
This is undertaken by the Site operator on a daily basis. If they are unable to reconcile fuel then a PLIP A is initiated
If the site can not identify the reason for the loss, or the loss is attributed to equipment issues the PLIP A is escalated to a PLIP B.
PLIP B – On site product loss investigation involving checking all equipment and system components.
The PLIP B is the on site investigation and EIT that needs to be carried out to determine the source of failure associated with the
product loss.
The PLIP B is undertaken by the Retail Field Engineer, L2 FMC or PMC, the Engineer remains responsible for its completion.
If testing the system indicates the system is tight and there is no explanation for the losses, then the Wet Stock Analyst is advised
and monitoring of the site continues.
PLIP C - The investigation undertaken once it has been determined that product has been lost to the environment.
The PLIP C procedure is the engineering and environmental activities undertaken once a loss of containment in conjunction with a
loss of product has been identified.
Engineering activities relate to taking action to prevent any more loss from the underground systems and rectification of leaking
equipment.
Environmental activities relate to identifying the effects of a loss, development of a remedial action plan and then the implementation
of that plan. The specific procedures follow by the Environment Services team are not identified in this document and links to these
are given.
Once the implementation has commenced the PLIP C procedure is complete and the ongoing remedial works are identified as an
environmental project.
When initiating an EIT the reasons for testing can differ, once the problem is identified pin pointing and directing the tank test
company to the specific issue helps in setting the scope for the test. The more information around the history of the system will
make the diagnoses clearer and help in making a decision for the end result i.e. repair and re-commissioning.
Breakdown
Equipment PLLD alarms (slow pumping), Interstitial Monitors (low brine level alarm)
Alarms
Equipment When conducting repairs or replacement that requires cutting or removing pipe work, man
ways, threaded couplings, change out of STP’s or of the primary tank connections.
Replacement
and repairs
Water Ingress High water alarm ATG, or detected water onsite dipping. Water detected through dispensers
customer complaints
Filtration Slow Pumping, continuous cleaning of filters. Ethanol products should check particulate levels
in fuel sample see Ethanol Conversion Guidelines
issues
Product Onsite or offsite PSH, Close system and test, check reconciliation of product
Engage PLIP C procedure
Outside
Containment
Regulatory Formal request local regulator for EIT
Request
Environmental Compliance test as per local conditions to operate.
Compliance
Regulatory compliance and periodic EIT are not reasons for system closure unless they are directly related to ongoing complaints
and issues with the operating system, a decision to close should be discussed with all parties concerned, if in doubt close the
system and test.
Note; Indirect and Direct Fill lines are considered as part of the wetted tank area and need to be isolated along with the tank until
repaired.
Failure with pipe work associated with ullage will not require tanks to be pumped out however, pending the type of failure i.e.
particularly with Vent/VR systems could see water ingress via pipe work into the tank which would cause tanks to be closed.
In some countries where VR1 and 2 systems form part of the vapour monitoring tanks will need to be closed, local regulatory
conditions for UPSS should be checked.
The following table is a guide for actions associated with failure types. Note that in some countries continuing to operate any part of
the system with a known failure is prohibited until repairs and re-certification.
Pressure Line
Suction Line
Vent
VR 1
VR 2
• D&S CoE
Shell Design Standards EIT Reference Documents
• OG.04.20065 - Recommended selection of leak detection methods for Underground Storage Tanks (UST’s) as to be applied by
SRI
• PLIP Procedures
https://sww-knowledge.shell.com/knowhow/livelink.exe/Open/96261290
• NWGLDE
The, National Work Group on Leak Detection Evaluations
• Leak Detectors
http://www.franklinfueling.com/service/pdfs/sps/400439001.pdf
http://www.franklinfueling.com/service/pdfs/sps/TB002r0504.pdf
http://www.veeder.com/page/Mechanical_Line_Leak_Detection