Sunteți pe pagina 1din 118

Calculation Note E1117 KDL

Reference:C:\Einheit.mcd

E1117 KDL

Electrical Protection

Settings Calculation

Related Document: Settings Protection 3-576 846 Rev. B

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
1 / 118
Calculation Note E1117 KDL

Introduction

Settings Overview

For an overview of the protection settings please refer to the following document:
Dwg. No.: 3-576 846, Revision B

DRS-COMPACT Digital Protection Relay

The digital and compact protection system DRS-COMPACT is a multifunctional


protection relay for protection of synchronous machines and transformers. All
components which are necessary for a complete protection system (interposing input
transformers, measuring channels, various matrices, trip and alarm outputs) are
installed in one case.
The signals generated in the plant (current, voltage, binary) are fed via appropriate
interposing transformers and transducers into the system. The further operation is
(except the methods of suppressing and filtering) fully digital. The advantages of this
digital processing are the extensive insensitivity of the system concerning aging,
temperature and also the possibility to reduce complex protection problems to
relative simple algorithms, which can be computed easily. Thereby the
characteristically computed values of the input signals can be used for further
protective functions. The protective functions which are implemented in the relay are
being processed sequentially by the software. In dependence of the working
condition the protection system gives out the equivalent alarm or trip signal.
The signals are being distributed via a software matrix to the trip devices which
corresponds to the tripping scheme. Optical indications signal the alarm and trip of a
protective function.
With the PC the user can read out, display and process further data about the fault
event like alarm protocol and fault recording.
Configuration and setting parameters are being saved in an E2 PROM. Each
modification is being recorded and can be printed out in a reference protocol.

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
2 / 118
Calculation Note E1117 KDL

DRS-WIN Operation Software

The protection relay DRS-COMPACT is operated with WINDOWS based software,


DRS-WIN.

This software provides the following actions:


display and change of all settings: setpoints, output matrix, LED matrix
display of analog measurements
display of analog calculated values
display of digital inputs and outputs
simulation of digital inputs and outputs
display of event recording data
display of fault record
display of protective function status
display of DRS fault status
display and set of DRS system time
editing of plant specific designations

Additional Information

For additional information please refer to the following documents:

ELIN DRS-COMPACT2: Short Technical Description (DIC-018-1)


DRS-COMPACT2A: Technical Data Sheet (GIC-000-A)
ELIN DRS-COMPACT2: Local Operation via Keypad and Display
(DIC-006-1)
DRS-WIN4: Short Manual (SID-401-1)

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
3 / 118
Calculation Note E1117 KDL

CT / VT Ratio
CT Busbar

CT Main Transformer HV

CT at HV side of main transformer

200A
CTMtHvSec  1A CTMtHv  CTMtHv  200
CTMtHvSec

CT Main Transformer Neutral 1

CT at star-point of main transformer

200A
CTMtNSec  1A CTMtN  CTMtN  200
CTMtNSec

CT Main Transformer Neutral 2

CT at star-point of main transformer

400A
CTMtN2Sec  1A CTMtN2  CTMtN2  400
CTMtN2Sec

CT Main Transformer LV

CT at LV side of main transformer

3000A
CTMtLvSec  1A CTMtLv  CTMtLv  3000
CTMtLvSec

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
4 / 118
Calculation Note E1117 KDL

CT Generator Output

CT at output side of generator

3000A
CTGenOutSec  1A CTGenOut  CTGenOut  3000
CTGenOutSec

CT Generator Neutral-End

CT at neutral-end side of generator

3000A
CTGenNeSec  1A CTGenNe  CTGenNe  3000
CTGenNeSec

CT Generator Measure

CT at output side of generator

3000A
CTGenMeaSec  1A CTGenMea  CTGenMea  3000
CTGenMeaSec

CT Auxiliary Transformer HV

CT at HV side of auxiliary transformer

800A
CTAtHvSec  1A CTAtHv  CTAtHv  800
CTAtHvSec

CT Auxiliary Transformer Neutral

CT at star-point of auxiliary transformer

1000A
CTAtNSec  1A CTAtN  CTAtN  1000
CTAtNSec

CT Auxiliary Transformer LV

CT at LV side of auxiliary transformer

500A
CTAtLvSec  1A CTAtLv  CTAtLv  500
CTAtLvSec

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
5 / 118
Calculation Note E1117 KDL

VT Generator Output

VT at output side of generator

11500V
VT GenOutSec  100V VT GenOut  VT GenOut  115
VT GenOutSec

VT Open Delta

VT open-delta-winding at output side of generator

11500V
VT OdSec  100V VT Od  VT Od  115
VTOdSec

VT Generator Neutral

VT at star-point of generator

12000V
VT GenNSec  240V VT GenN  VT GenN  50.00
VT GenNSec

Resistance

Secondary resistance at star-point of generator

RGenNSec  0.266

CT ground

Secondary CT at star-point of generator

250A
CTsecGenNSec  1A CTsecGenN  CTsecGenN  250
CTsecGenNSec

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
6 / 118
Calculation Note E1117 KDL

Generator Data
Nominal apparent power SGenNom  44282kVA

Nominal voltage UGenNom  11.5kV

Nominal current calculated from apparent power and voltage


SGenNom
I GenNom  IGenNom  2223 A
3  UGenNom

Nominal frequency fGenNom  50 Hz

Power factor
cos  0.85  G  acos  cos  G  31.79 deg

Generator nominal impedance in primary value


2
UGenNom
XGprim  XGprim  2.99 
SGenNom

Secondary impedance calculated from primary impedance, CT and VT ratio

CTGenOut
XGsec  XGprim  XGsec  77.91 
VTGenOut

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
7 / 118
Calculation Note E1117 KDL

Generator subtransient reactance in p.U. value xsubtrans  10.6%

Primary impedance calculated from primary nominal generator impedance

XsubtransPrim  xsubtrans  XGprim XsubtransPrim  0.32 

Secondary impedance calculated from secondary nominal generator impedance

XsubtransSec  xsubtrans  XGsec XsubtransSec  8.26 

Generator transient reactance in p.U. value xtrans  15 %

Primary impedance calculated from primary nominal generator impedance

XtransPrim  xtrans  XGprim XtransPrim  0.45 

Secondary impedance calculated from secondary nominal generator impedance

XtransSec  xtrans  XGsec XtransSec  11.69 

Generator synchronous reactance in p.U. value xsynch  160%

Primary impedance calculated from primary nominal generator impedance

XsynchPrim  xsynch  XGprim XsynchPrim  4.78 

Secondary impedance calculated from secondary nominal generator impedance

XsynchSec  xsynch  XGsec XsynchSec  124.66 

Negative phase sequence characteristic NPScharact  30.0s

Continuous negative phase sequence NPScont  15 %

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
8 / 118
Calculation Note E1117 KDL

Main Transformer Data

Nominal HV apparent power SMtHvNom  46000kVA

UMtHvNom  150kV
Nominal HV voltage

Nominal HV current calculated from nominal apparent power and HV voltage


SMtHvNom
I MtHvNom  IMtHvNom  177 A
3  UMtHvNom

Transformer HV nominal impedance in primary value


2
UMtHvNom
XMtHvPrim  XMtHvPrim  489.13 
SMtHvNom

Nominal LV apparent power

SMtLvNom  SMtHvNom SMtLvNom  46000.00 kVA

Nominal LV voltage UMtLvNom  11.5kV

Nominal LV current calculated from nominal apparent power and LV voltage


SMtLvNom
I MtLvNom  IMtLvNom  2309 A
3  UMtLvNom

Transformer LV nominal impedance in primary value


2
UMtLvNom
XMtLvPrim  XMtLvPrim  2.88 
SMtLvNom

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
9 / 118
Calculation Note E1117 KDL

Nominal LV2 apparent power

SMtLv2Nom  6.5MVA SMtLv2Nom  6500.00 kVA

Nominal LV2 voltage UMtLv2Nom  6.6kV

Nominal LV2 current calculated from nominal apparent power and LV voltage
SMtLv2Nom
I MtLv2Nom  IMtLv2Nom  569 A
3  UMtLv2Nom

Transformer LV2 nominal impedance in primary value


2
UMtLv2Nom
XMtLv2Prim  XMtLv2Prim  6.70 
SMtLv2Nom

Transformer impedance in p.U. value z MtBase  10 %

This impedance is based on the following apparent power:

SMtBase  SMtHvNom SMtBase  46000.00 kVA

The transformer impedance based on nominal power

SMtHvNom
z Mt  z MtBase  z Mt  10.00 %
SMtBase

Primary HV impedance calculated from HV nominal impedance

ZMtHvPrim  z Mt  XMtHvPrim ZMtHvPrim  48.91 

Primary LV impedance calculated from LV nominal impedance

ZMtLvPrim  z Mt  XMtLvPrim ZMtLvPrim  0.29 

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
10 / 118
Calculation Note E1117 KDL

The system impedance is considered to be a percentage of the transformer impedance.


This value has to be confirmed by the customer.

Pickup  5%
PkpAngl  80 deg

2
UMtHvNom
ZSysHv  Pickup   exp ( j  PkpAngl )
SMtHvNom ZSysHv  4.25  24.08i 

SMtHvNom
z SysMt  ZSysHv  z SysMt  0.87  4.92i %
2
UMtHvNom

2
UMtLvNom
ZSysLv  Pickup   exp ( j  PkpAngl ) ZSysLv  0.02  0.14i 
SMtLvNom

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
11 / 118
Calculation Note E1117 KDL

Auxiliary Transformer Data


Nominal apparent power SAtHvNom  5000kVA

Nominal HV voltage UAtHvNom  6.6kV

Nominal HV current calculated from nominal apparent power and HV voltage


SAtHvNom
I AtHvNom  IAtHvNom  437 A
3  UAtHvNom

Transformer HV nominal impedance in primary value


2
UAtHvNom
XAtHvPrim  XAtHvPrim  8.71 
SAtHvNom

Nominal LV voltage UAtLvNom  0.42kV

Nominal LV current calculated from nominal apparent power and LV voltage


SAtHvNom
I AtLvNom  IAtLvNom  6873 A
3  UAtLvNom

Transformer LV nominal impedance in primary value


2
UAtLvNom
XAtLvPrim  XAtLvPrim  0.04 
SAtHvNom

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
12 / 118
Calculation Note E1117 KDL

Transformer impedance in p.U. value z AtBase  13.5%

This impedance is based on the following apparent power:

SAtBase  SAtHvNom SAtBase  5000 kVA

The transformer impedance based on nominal power

SAtHvNom
z At  z AtBase  z At  13.50 %
SAtBase

Primary HV impedance calculated from HV nominal impedance


2
UAtHvNom
ZAtHvPrim  z At  ZAtHvPrim  1.18 
SAtBase

Primary LV impedance calculated from LV nominal impedance


2
UAtLvNom
ZAtLvPrim  z At  ZAtLvPrim  0.00 
SAtBase

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
13 / 118
Calculation Note E1117 KDL

General DRS Settings

CT/VT Settings

The CT/VT settings can be edited with DRS-WIN.


Menu: DRS Functions - CT/VT Ratios

CT Ratios

Output CTGenOut  CTGenOutSec  3000.00A

CTGenOutSec  1.00 A

IGenNom  2223.15A

NeutralEnd CTGenNe  CTGenNeSec  3000.00A

CTGenNeSec  1.00 A

IGenNom  2223.15A

Measurement CTGenMea  CTGenMeaSec  3000.00A

CTGenMeaSec  1.00 A

IGenNom  2223.15A

CTsecGenN  CTsecGenNSec
Gen.Neutral  5.00 A
VTGenN

CTsecGenNSec  1.00 A

UGenNom
 9.98 A
2
3  VT GenN  RGenNSec

MT.HV CTMtHv  CTMtHvSec  200.00 A

CTMtHvSec  1.00 A

IMtHvNom  177.05 A

MT.LV CTMtLv  CTMtLvSec  3000.00A

CTMtLvSec  1.00 A

IMtLvNom  2309.40A

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
14 / 118
Calculation Note E1117 KDL

MT.Neutral.1 CTMtN  CTMtNSec  200.00 A

CTMtNSec  1.00 A

IMtHvNom  177.05 A

MT.Neutral.2 CTMtN2  CTMtN2Sec  400.00 A

CTMtN2Sec  1.00 A

IMtHvNom  177.05 A

AT.HV CTAtHv  CTAtHvSec  800.00 A

CTAtHvSec  1.00 A

IAtHvNom  437.39 A

AT.LV CTAtLv  CTAtLvSec  500.00 A

CTAtLvSec  1.00 A

IAtLvNom  6873.22A

AT.Neutral CTAtN  CTAtNSec  1000.00A

CTAtNSec  1.00 A

IAtHvNom  437.39 A

VT Ratios

Output VTGenOut  100V  11500.00 V


100.00 V
UGenNom  11500.00 V

OpenDelta VTOd  100V  11500.00 V


100.00 V
UGenNom  11500.00 V

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
15 / 118
Calculation Note E1117 KDL

Fault Calculation

Short Circuit very close to the generator

The subtransient current is calculated with the generator nominal current and the
subtransient generator reactance as following:
I GenNom
I GenSubTrans  IGenSubTrans  20973 A
xsubtrans

The transient current is calculated with the generator nominal current and the transient
reactance as following:

IGenNom
I GenTrans  IGenTrans  14821 A
xtrans

Short Circuit very close to the HV side of the main transformer

Short Circuit Current calculated with transformer impedance only

I MtHvNom
I MtSc  IMtSc  1771 A
z Mt

Subtransient Current calculated with main transformer impedance and subtransient


generator reactance
IMtHvNom
I MtSubTrans  IMtSubTrans  843 A
SMtHvNom
z Mt  xsubtrans 
SGenNom

IMtHvNom
I MtTrans  IMtTrans  692 A
SMtHvNom
z Mt  xtrans 
SGenNom

Short Circuit very close to the HV side of the auxiliary transformer

Short Circuit Current calculated with transformer impedance only

I AtHvNom
I AtSc  IAtSc  3240 A
z At

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
16 / 118
Calculation Note E1117 KDL

Generator Differential (87G)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Gen. Diff. 3-ph
Pickup Level: 0.05 - 0.60 A in steps of 0.01
Time Delay: no

Operating Principle

Differential protective functions are a selective unit protection system against 2 phase
and 3 phase short circuits inside the protective area which is restricted by the CT's
involved.
Also winding short circuits and two point earth faults if one point is inside the
protective are are detected.
The measuring principle is based on the current vector differential computation within
the protected zone of the relevant sets of CT's.

The picture below shows the stabilizing of the function with the restraint current which
is computed from the 1st harmonic currents of system 1.

6,0 BIAS=60%

BIAS=50%
Diff. Curr./ Rated Curr..

TRIP
5,0

BIAS=40%
4,0
Set
Diff
BIAS=30%
3,0 0.6
0.5
2,0 0.4
0.3
1,0
0.2 NOTRIP
01

0,0
0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0

Restraint Curr./ RatedCurr.

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
17 / 118
Calculation Note E1117 KDL

Associated CT's

System 1 is connected to the following CT: CT Generator Output

CTsec  CTGenOutSec CTsec  1 A

CTprim  CTGenOut  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

System 2 is connected to the following CT: CT Generator Neutral-End

Nominal Current

Nominal current of the protected device: Generator


I nom  IGenNom
Inom  2223 A
I nom
I nomSec  InomSec  0.74 A
CT

Setting Calculation

Setpoint given as following: Pickup1  10 %

Primary current calculated from relative pickup value and nominal current
I prim  Pickup1  I nom Iprim  222 A

Relay pickup value (secondary current) calculated from primary current and CT ratio.

Iprim
I sec  Isec  0.07 A
CT

High set current is the subtransient generator current

I HighSet  IGenSubTrans IHighSet  20973 A

IHighSet
I HighSetSec  IHighSetSec  6.99 A
CT

Pickup of high set current calculated with nominal current

IHighSet
Pickup2  Pickup2  943.40 %
Inom

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
18 / 118
Calculation Note E1117 KDL

Settings for Stabilizing Characteristic

Bias of Characteristic chosen as following: Bias  45 %

Stabilizing Characteristic (Differential Current - Restrained Current)

The diagram shows the differential current (pickup current) over the restrained
current.

4
I.diff / pU

0
0 1 2 3 4 5 6 7 8
I.restrained / pU

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
19 / 118
Calculation Note E1117 KDL

Explanation to the diagram Differential Current over Restrained Current:

The diagram shows the differential current (pickup current) over the restrained
current. Both values are pU based on generator nominal.

The trip area is above the curve.

The DRS calculates the restrained current as the summation of the absolute value
of both currents of system 1 and system 2.
On this diagram the restrained current is shown in case of same current in system 1
and system 2. Therefore for this diagram the restrained current is the absolute value
of system 1.

The curve consists of 3 areas:

Area 1 is from zero to DRS nominal current which is


CTsec  1.00 A
Based on generator nominal current the first knee point of the curve is
CTprim
 135 % .
Inom
In this area the differential pickup current is constant
I sec  0.07 A
or based on generator nominal current
I prim
 10 %
I nom

Area 2 reaches up to the second knee point which is 3 times DRS nominal current.
3  CTsec  3.00 A .
Based on generator nominal current the second knee point of the curve is
3  CTprim
 405 %
I nom
In this area the differential pickup current increases by 30% which is fixed and not
adjustable.

Area 3 reaches from the second knee point up to the infinite.


The differential current increases by the setting "Bias" which is adjustable between
30% and 60%.
In the actual calculation the setting is
Bias  45 %

DRS Settings
Gen Diff 3-ph (87G)
Operate Value Isec  0.07 A
Bias Bias  45.00 %
High Set OC IHighSetSec  6.99 A
Saturation Detection 5 Per

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
20 / 118
Calculation Note E1117 KDL

Inadvertent Energization (50G/27)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Inadvertent Energization
Operate Value I: 0.10 - 5.00 A in steps of 0.05
Operate Value U: 10 - 120 V in steps of 5.

Operating Principle

Inadvertent Energization is provided to isolate the generator from the system if it is


connected to the system by mistake. Also a short circuit during start of excitation is
detected earlier than with other protections.
The function works with overcurrent detection and overvoltage blocking. The current
setting is below the nominal current. The function is blocked with the voltage level. If
the voltage is higher than the voltage setting, the function is blocked. That means
the function can only trip if the current is higher than the current setting and the
voltage is lower than the voltage setting.

Associated CT

The function is connected to the following CT: CT Generator Neutral-End


CTsec  CTGenNeSec CTsec  1 A

CTprim  CTGenNe  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

Nominal Current

Nominal current of the protected device: Generator


I nom  IGenNom
Inom  2223 A
I nom
I nomSec  InomSec  0.74 A
CT

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec VT sec  100 V

VT prim  VTGenOut  VTsec VT prim  11500 V

VT prim
VT  VT  115
VT sec

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
21 / 118
Calculation Note E1117 KDL

Nominal Voltage

Nominal voltage of the protected device: Generator


Unom  UGenNom
Unom  11500 V
Unom
UnomSec  UnomSec  100.00 V
VT

Setting Calculation for Voltage

Setpoint of voltage given as following: Pickup  60 %

Primary voltage calculated from relative pickup value and nominal voltage

Uprim  Pickup  Unom Uprim  6900 V

Relay pickup level (secondary voltage) calculated from primary voltage and VT ratio
Uprim
Usec  Usec  60.0 V
VT

Setting Calculation for Current

Setpoint of current given as following: Pickup  33.7%

Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom Iprim  749 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

Iprim
I sec  Isec  0.25 A
CT

DRS Settings

Inadvert. Energizing (50G/27)


Operate Value I Isec  0.25 A
Operate Value U Usec  60.00 V
Pickup Delay 0.50 s
Drop-off Delay 3.00 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
22 / 118
Calculation Note E1117 KDL

Generator Overcurrent Voltage Restrained (51V)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Voltage Restrained OC
Operate Value: 0.10 - 5.00 A in steps of 0.05
Nominal Voltage: 70.0 - 140.0 V in steps of 1.00
Time Delay: 0.00 - 30.00 s in steps of 0.05

Operating Principle

Generator overcurrent protection is used to protect the transformer against short


circuits and thermal overload.
Additional it is a backup feature for all other generator protective functions.

This overcurrent function works with a current setting which is dependent on the
actual voltage level. The picture below shows the current setting multiplier over the
actual voltage.

OPERATE VALUE MULTIPLIER

1,0

0,9

0,8

0,7

0,6

0,5

0,4

0,3

0,2

0,1

0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0

PHASE-PHASE VOLTAGE (ACTUAL)

RATED PHASE-PHASE VOLTAGE (SET VALUE)

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
23 / 118
Calculation Note E1117 KDL

Associated CT

The function is connected to the following CT: CT Generator Neutral-End


CTsec  CTGenNeSec CTsec  1 A

CTprim  CTGenNe  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

Nominal Current

Nominal current of the protected device: Generator


I nom  IGenNom
Inom  2223 A
I nom
I nomSec  InomSec  0.74 A
CT

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec VT sec  100 V

VT prim  VTGenOut  VTsec VT prim  11500 V

VT prim
VT  VT  115
VT sec

Nominal Voltage

Nominal voltage of the protected device: Generator


Unom  UGenNom
Unom  11500 V
Unom
UnomSec  UnomSec  100.00 V
VT

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
24 / 118
Calculation Note E1117 KDL

Setting Calculation

Pickup chosen as following: Pickup  121.4%

Operating value (secondary current) calculated from relative pickup value, nominal
current and CT ratio

Inom
I s  Pickup  Is  0.90 A
CT

Time delay chosen as following: TD  6s

The pickup value of 51V has to be compared with the AVR stator current limiter.
The stator current limiter is set to IAvrLimit  105.0 % . The current pickup of function
51V at U51Vmin  90.00 % is calculated to I51Vmin  121.4 % .
This value is higher than the AVR limiter.

Setting Characteristic (Setting - Voltage)

The setting value depends on the voltage level.


The diagram shows the setting value (in pU) in relation to the voltage level
(in percent of the nominal voltage level).

1.4

1.3

1.2

1.1

0.9

0.8
Pickup / pU

0.7

0.6

0.5

0.4

0.3

0.2

0.1

0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3
Voltage / pU

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
25 / 118
Calculation Note E1117 KDL

DRS Settings

Voltage Restraint OC (51V)


Operate Value Is  0.90 A
Nominal Voltage VTsec  100.0 V
Time Delay TD  6.00 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
26 / 118
Calculation Note E1117 KDL

Underimpedance (21G)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Impedance 3-ph.
Pickup Level: 0.1 - 20.0  in steps of 0.1
Time Delay: 0.00 - 30.00 s in steps of 0.05

Operating Principle

Underimpedance protection is used as a backup protection for short circuit protection


in the zone restricted to generator winding up to the main transformer.

The vectors of the phase currents IL1 and IL2 are subtracted for measuring system 1
and the impedance of system 1 is determined using phase to phase voltage UL1L2 .
The same relationship applies to the other two measuring systems with the
corresponding CT and VT inputs.

Associated CT

The function is connected to the following CT: CT Generator Neutral-End


CTsec  CTGenNeSec CTsec  1 A

CTprim  CTGenNe  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec
VT sec  100 V
VT prim  VTGenOut  VTsec
VT prim  11500 V
VT prim
VT 
VT sec VT  115

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
27 / 118
Calculation Note E1117 KDL

Transformer Impedance

Secondary Impedance of Main Transformer measured by this protective function

CT
ZTsec  ZMtLvPrim  ZTsec  7.50 
VT

Relative Impedance of Main Transformer based on Generator Power

SGenNom
z Tgen  z Mt  z Tgen  9.6 %
SMtHvNom

Setting Calculation for Impedance Stage 1 Reach  110%

The stage "Impedance" starts, if both impedance level and current level is above the
setpoint.
Pickup of impedance stage given as following (reach of impedance measuring starting
at neutral-end side of generator)

Relay pickup level (secondary impedance) calculated from relative pickup value and
secondary transformer impedance
Xsec1  Reach  ZTsec Xsec1  8.25 

VT SGenNom
Xpu1  Xsec1   Xpu1  10.6 %
CT U 2
GenNom

TD1  3s
Time delay given as following:

Setting Calculation for Impedance Stage 2 Reach  75 %

The stage "Impedance" starts, if both impedance level and current level is above the
setpoint.
Pickup of impedance stage given as following (reach of impedance measuring starting
at neutral-end side of generator)

Relay pickup level (secondary impedance) calculated from relative pickup value and
secondary transformer impedance
Xsec2  Reach  ZTsec Xsec2  5.63 

VT SGenNom
Xpu2  Xsec2   Xpu2  7.2 %
CT U 2
GenNom

TD2  3s
Time delay given as following:

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
28 / 118
Calculation Note E1117 KDL

Setting Calculation for Current

The stage "Current" starts, if the current level is above the setpoint. Additional this
stage is used for the stage "Impedance".

Pickup of current stage given as following: Pickup  120%

Primary current calculated from relative pickup value and generator nominal current

I prim  Pickup  IGenNom Iprim  2668 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

Iprim
I sec  Isec  0.89 A
CT

DRS Settings

Impedance 3-ph. (21G.1)


Operate Value Xsec1  8.25 
Current Interlock Isec  0.89 A
Time Delay Impedance TD1  3.00 s

Impedance 3-ph. (21G.2)


Operate Value Xsec2  5.63 
Current Interlock Isec  0.89 A
Time Delay Impedance TD2  3.00 s

Can't put exactly the settings values. Settings set as per these pictures above

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
29 / 118
Calculation Note E1117 KDL

Setting Characteristic

The diagram shows the setting value (in pU) as a green circle, the trip is inside.
The red characteristic shows the nominal generator load area
The black line shows the transformer impedance.

0.5
Imaginary part of Z / pU

1 0.5 0 0.5 1

0.5

Real part of Z / pU

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
30 / 118
Calculation Note E1117 KDL

Negative Sequence Overcurrent (46G)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Neg.Ph.Sequ.2-st.
Pickup Level 1: 2.0 - 50.0 % in steps of 0.5
Time Delay 1: 0.00 - 30.00 s in steps of 0.05
Pickup Level 2: 2.0 - 50.0 % in steps of 0.5
Time Delay 2: 0.00 - 30.00 s in steps of 0.05

Operating Principle

Two-phase short-circuits, conductor breakage on overhead lines or defective breaker


poles cause high asymmetrical loads on three-phase generators.
An asymmetrical rotating field may be divided into a positive and a negative
component by means of the "symmetrical components" method, where the negative
phase sequence component includes currents with double frequency in the rotor,
causing inadmissible temperature rises in the damper bars.
The unbalance protection system measures this dangerous situation and trips or
isolates the generator whenever an admissible unbalance load value is exceeded.

This function works with definite time characteristic.

Associated CT

The function is connected to the following CT: CT Generator Neutral-End


CTsec  CTGenNeSec CTsec  1 A

CTprim  CTGenNe  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

Nominal Current

Nominal current of the protected device: Generator


I nom  IGenNom
Inom  2223 A
I nom
I nomSec  InomSec  0.74 A
CT

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
31 / 118
Calculation Note E1117 KDL

Compensation Factor

The protection pU system is based on the generator nominal current and the DRS
pU system is based on the CT current. Therefore a compensation factor is used to
convert between these two pu systems:

Inom
CompFact  CompFact  0.74
CTprim

Setting Calculation Stage 1


Pickup46G1  12.1%
Setpoint given as following:

This setpoint must be multiplied with the compensation factor CompFact to


convert to the DRS pU system:

PickupDRS1  Pickup46G1  CompFact PickupDRS1  9.0 %

Time delay given as following:


TD46G1  3s

DRS Settings

Neg Ph Sequ 2-st (46G)


Operate Value St.1 PickupDRS1  8.97 %
Time Delay St.1 TD46G1  3.00 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
32 / 118
Calculation Note E1117 KDL

Negative Sequence Overcurrent Inverse (46Ginv)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Inverse Time Neg.Ph.Sequ.
CT Ratio Comp.: 0.40 - 2.00 in steps of 0.01
Cont. Unbal. Load: 2.0 - 25.0 % in steps of 0,5
Time Constant: 1 - 50 minutes in steps of 1
Neg.Ph.Sequ. Alarm: 5 - 100 % in steps of 1
Neg.Ph.Sequ. Trip: 5 - 100 % in steps of 1

Operating Principle

Two-phase short-circuits, conductor breakage on overhead lines or defective breaker


poles cause high asymmetrical loads on three-phase generators.
An asymmetrical rotating field may be divided into a positive and a negative
component by means of the "symmetrical components" method, where the negative
phase sequence component includes currents with double frequency in the rotor,
causing inadmissible temperature rises in the damper bars.
The unbalance protection system measures this dangerous situation and trips or
isolates the generator whenever an admissible unbalance load value is exceeded.

This function works with inverse time characteristic. the temperature rise of the rotor,
respectively the damper winding itself according to a simplified model is illustrated in
the following formula:

2
 NPS    1  exp  t  
 ( t) =  limit     
 NPScont     

For more details please refer to the DRS function library !

Associated CT

The function is connected to the following CT: CT Generator Neutral-End


CTsec  CTGenNeSec CTsec  1 A

CTprim  CTGenNe  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
33 / 118
Calculation Note E1117 KDL

Nominal Current

Nominal current of the protected device: Generator


I nom  IGenNom
Inom  2223 A
I nom
I nomSec  InomSec  0.74 A
CT

Compensation Factor

The protection pU system is based on the generator nominal current and the DRS
pU system is based on the CT current. Therefore a compensation factor is used to
convert between these two pu systems:

Inom
CompFact  CompFact  0.74
CTprim

Setting Calculation

The time constant for the DRS function is calculated with the negative phase
sequence characteristic NPScharact  30.0 s and the continuous negative
phase sequence NPScont  15.0 % of the generator:

NPScharact
TimeConst  TimeConst  22.22 min
2
NPScont

Chosen value: TimeConst  22 min

The continuous negative phase sequence of the DRS function is chosen lower than the
value of the generator to keep the trip curve below the generator negative sequence
capability curve:

NPScontDRS  15 %

Pickup46GinvAlarm  80 %
The alarm of the function chosen as following:

Pickup46GinvTrip  100%
The trip of the function chosen as following:

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
34 / 118
Calculation Note E1117 KDL

The alarm curve of the DRS follows according the formula:

 2

Alarm ( NPS)  TimeConst  ln  
NPS
 NPS2  NPS 2
 Pickup 
 contDRS 46GinvAlarm 

The trip curve of the DRS follows according the formula:

 2

Trip ( NPS)  TimeConst  ln  NPS 
 NPS2  NPS 2 
 contDRS  Pickup46GinvTrip 

DRS Settings

Inv. Time Neg.Ph.Sequ (46Ginv)


CT Ratio Compensation CompFact  0.74
Continuous Unbalance Load NPScontDRS  15.00 %
Time Constant TimeConst  22 min
Negative Phase Sequence Alarm Pickup46GinvAlarm  80 %
Negative Phase Sequence Trip Pickup46GinvTrip  100 %

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
35 / 118
Calculation Note E1117 KDL

The following diagram shows the negative phase sequence over the time.

The generator negative phase sequence characteristic is shown as a blue curve.


The Alarm stage of the protective function is shown as a cyan curve.
The Trip stage of the protective function is shown as a red curve.
Additional the alarm definite stage (46G.1) is shown in cyan.

The tripping area is above the curves.

0.9

0.8

0.7
Negative Sequence Current / pU

0.6

0.5

0.4

0.3

0.2

0.1

0
0 100 200 300 400 500 600 700 800 900 1000
Time / sec
generator
alarm
trip
definite 1

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
36 / 118
Calculation Note E1117 KDL

Generator Overvoltage (59G)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Voltage 3-ph.2-st.
Pickup Level 1: 2.0 - 200.0 V in steps of 0.2
Time Delay 1: 0.00 - 30.00 sec in steps of 0.05
Pickup Level 2: 2.0 - 200.0 V in steps of 0.2
Time Delay 2: 0.00 - 30.00 sec in steps of 0.05

Operating Principle

Generator overvoltage protection is used to detect dangerous conditions for the


winding and laminated iron insulation.

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec
VT sec  100 V
VT prim  VTGenOut  VTsec
VT prim  11500 V
VT prim
VT 
VT sec VT  115

Nominal Voltage

Nominal voltage of the protected device: Generator


Unom  UGenNom
Unom  11500 V
Unom
UnomSec  UnomSec  100.00 V
VT

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
37 / 118
Calculation Note E1117 KDL

Setting Calculation Stage 1

Setpoint given as following: Pickup59G1  112%

Primary voltage calculated from relative pickup value and nominal voltage

Uprim  Pickup59G1  Unom Uprim  12880 V

Relay pickup level (secondary voltage) calculated from primary voltage and VT
ratio
Uprim
U59G1  U59G1  112.0 V
VT

TD59G1  10 s
Time delay given as following:

Setting Calculation Stage 2


Pickup59G2  120%
Setpoint given as following:

Primary voltage calculated from relative pickup value and nominal voltage

Uprim  Pickup59G2  Unom Uprim  13800 V

Relay pickup level (secondary voltage) calculated from primary voltage and VT ratio

Uprim
U59G2  U59G2  120.0 V
VT

TD59G2  4s
Time delay given as following:

DRS Settings

Voltage 3-ph 2-st (59G)


Operate Value St.1 U59G1  112.0 V
Time Delay St.1 TD59G1  10.00 s
Operate Value St.2 U59G2  120.0 V
Time Delay St.2 TD59G2  4.00 s
Type Overdetection

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
38 / 118
Calculation Note E1117 KDL

Generator Undervoltage (27G)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Voltage 3-ph.2-st.
Pickup Level 1: 2.0 - 200.0 V in steps of 0.2
Time Delay 1: 0.00 - 30.00 sec in steps of 0.05
Pickup Level 2: 2.0 - 200.0 V in steps of 0.2
Time Delay 2: 0.00 - 30.00 sec in steps of 0.05

Operating Principle

Generator undervoltage protection is used to isolate the generator from the system
in case of an undervoltage condition.

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec VT sec  100 V

VT prim  VTGenOut  VTsec VT prim  11500 V

VT prim
VT  VT  115
VT sec

Nominal Voltage

Nominal voltage of the protected device: Generator


Unom  UGenNom
Unom  11500 V
Unom
UnomSec  UnomSec  100.00 V
VT

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
39 / 118
Calculation Note E1117 KDL

Setting Calculation Stage 1

Setpoint given as following: Pickup  90 %

Primary voltage calculated from relative pickup value and nominal voltage

Uprim  Pickup  Unom Uprim  10350 V

Relay pickup level (secondary voltage) calculated from primary voltage and VT ratio

Uprim
Usec1  Usec1  90.0 V
VT

Time delay given as following: TD1  10 s

Setting Calculation Stage 2

Setpoint given as following: Pickup  70 %

Primary voltage calculated from relative pickup value and nominal voltage

Uprim  Pickup  Unom Uprim  8050 V

Relay pickup level (secondary voltage) calculated from primary voltage and VT ratio

Uprim
Usec2  Usec2  70.0 V
VT

Time delay given as following: TD2  3s

DRS Settings

Voltage 3-ph 2-st (27G)


Operate Value St.1 Usec1  90.0 V
Time Delay St.1 TD1  10.00 s
Operate Value St.2 Usec2  70.0 V
Time Delay St.2 TD2  3.00 s
Type Underdetection

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
40 / 118
Calculation Note E1117 KDL

Under - Frequency (81G.u)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Frequency 4-st.
Pickup Level: 10 - 65 Hz in steps of 0.01
Time Delay: 0.00 - 30.00 sec in steps of 0.05

Operating Principle

Underfrequency protection is used to protect gas turbine and generator against low
frequency. Auxiliary drives are protected against overload during low frequency.

Setting Calculation Underfrequency Stage 1

Setpoint given as following: Pickup  98 %

Relay pickup level (frequency) calculated from relative pickup value and generator
nominal frequency

f 1  Pickup  f GenNom f1  49.0 Hz

Time delay given as following:


TD1  10 s

Setting Calculation Underfrequency Stage 2

Setpoint given as following: Pickup  95 %

Relay pickup level (frequency) calculated from relative pickup value and generator
nominal frequency

f 2  Pickup  f GenNom f2  47.5 Hz

Time delay given as following: TD2  4s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
41 / 118
Calculation Note E1117 KDL

DRS Settings

Frequency 4-st (81G.u)


Minimum Voltage Setting 70 V
Maximum Voltage Setting 140 V
Operate Value St.1 f1  49.00 Hz
Type St.1 Underdetection
Time Delay St.1 TD1  10.00 s
Operate Value St.2 f2  47.50 Hz
Type St.2 Underdetection
Time Delay St.2 TD2  4.00 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
42 / 118
Calculation Note E1117 KDL

Over - Frequency (81G.o)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Frequency 4-st.
Pickup Level: 10 - 65 Hz in steps of 0.01
Time Delay: 0.00 - 30.00 sec in steps of 0.05

Operating Principle

Overfrequency protection is used to protect gas turbine and generator against high
frequency and Overspeed.

Setting Calculation Overfrequency Stage 1

Setpoint given as following: Pickup  103%

Relay pickup level (frequency) calculated from relative pickup value and generator
nominal frequency

f 1  Pickup  f GenNom f1  51.5 Hz

Time delay given as following:


TD1  10 s

Setting Calculation Overfrequency Stage 2

Setpoint given as following: Pickup  105%

Relay pickup level (frequency) calculated from relative pickup value and generator
nominal frequency

f 2  Pickup  f GenNom f2  52.5 Hz

Time delay given as following:


TD2  3s

Remark: This function is blocked, when generator is off-line !

Setting Calculation Overfrequency Stage 3

Setpoint given as following: Pickup  105%

Relay pickup level (frequency) calculated from relative pickup value and generator
nominal frequency

f 3  Pickup  f GenNom f3  52.5 Hz

Time delay given as following: TD3  30 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
43 / 118
Calculation Note E1117 KDL

DRS Settings

Frequency 4-st (81G.o)


Minimum Voltage Setting 70 V
Maximum Voltage Setting 140 V
Operate Value St.1 f1  51.50 Hz
Type St.1 Overdetection
Time Delay St.1 TD1  10.00 s
Operate Value St.2 f2  52.50 Hz
Type St.2 Overdetection
Time Delay St.2 TD2  3.00 s
Operate Value St.3 f3  52.50 Hz
Type St.3 Overdetection
Time Delay St.3 TD3  30.00 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
44 / 118
Calculation Note E1117 KDL

Reverse Power (32R)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Rev. Power 3-ph.1-st.
Pickup Level: -5.0 - -0.2 % Pn in steps of 0.1
Time Delay: 0.0 - 180.0 s in steps of 0.1

Operating Principle

Reverse power protection prevents the generator of working as motor.

Associated CT

The function is connected to the following CT: CT Generator Neutral-End


CTsec  CTGenNeSec CTsec  1 A

CTprim  CTGenNe  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec VT sec  100 V

VT prim  VTGenOut  VTsec VT prim  11500 V

VT prim
VT  VT  115
VT sec

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
45 / 118
Calculation Note E1117 KDL

Setting Calculation

Pickup  5%
Setpoint given as following:

With the chosen relative pickup value the absolute generator power is calculated

Pprim  Pickup  SGenNom  cos Pprim  1882 kW

The next calculated value gives the nominal absolute protection power which is
based on CT and VT primary data.

PProtnom  3  CTprim  VT  100V PProtnom  59756 kW

With the absolute generator power and the nominal absolute protection power the
relative setpoint for the protection system is calculated.

Pprim
SetpointRelay  SetpointRelay  3.1 %
PProtnom

Time delay given as following: TD  3s

DRS Settings

Rev Power 3-ph 1-st (32R)


Operate Value SetpointRelay  3.1 %
Time Delay TD  3.00 s
Power Direction Direction 1
Phase Rotation Right
CT Error Compensation 0.0 deg

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
46 / 118
Calculation Note E1117 KDL

Low Forward Power (32L)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Dir. Power 3-ph.1-st.
Pickup Level: 2 - 150 % Pn in steps of 1
Time Delay: 0.0 - 600.0 s in steps of 0.1

Operating Principle

Low forward power protection prevents the generator of working as motor.

Associated CT

The function is connected to the following CT: CT Generator Measure


CTsec  CTGenMeaSec CTsec  1 A

CTprim  CTGenMea  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec VT sec  100 V

VT prim  VTGenOut  VTsec VT prim  11500 V

VT prim
VT  VT  115
VT sec

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
47 / 118
Calculation Note E1117 KDL

Setting Calculation

Setpoint given as following: Pickup  3.2%

With the chosen relative pickup value the absolute generator power is calculated

Pprim  Pickup  SGenNom  cos Pprim  1204 kW

The next calculated value gives the nominal absolute protection power which is
based on CT and VT primary data.

PProtnom  3  CTprim  VT  100V PProtnom  59756 kW

With the absolute generator power and the nominal absolute protection power the
relative setpoint for the protection system is calculated.
Pprim
SetpointRelay  SetpointRelay  2.0 %
PProtnom

Time delay given as following:


TD  3s

DRS Settings

Dir. Power 3-ph.1-st. (32L)


Operate Value SetpointRelay  2 %
Time Delay TD  3.0 s
Power Direction Direction 2
Type Overdetection
Phase Rotation Right
CT Error Compensation 0.0 deg

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
48 / 118
Calculation Note E1117 KDL

Overfluxing (24G)
Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Overfluxing
Pickup Level 1: 0.80 - 1.50 pU in steps of 0.01
Time Delay 1: 0.0 - 300.0 s in steps of 0.05
Pickup Level 2: 0.80 - 1.50 pU in steps of 0.01
Time Delay 2: 0.0 - 100.0 s in steps of 0.05

Operating Principle

Electrical Equipment is designed and dimensioned for a maximum magnetic flux


during operation. If this value is exceeded, the equipment may suffer direct or
indirect damage. The increased magnetizing current, with a higher harmonic content,
of a transformer for example, not only causes heating up of the transformer, but also
produces in inadmissible high voltage peaks in the field circuit.

The Overfluxing protection is a single phase system. The supplied voltage signal is
sampled 12 times per cycle. The value and frequency of the signal for each sample
are determined, using the Fourier transformation and subsequently the value V/f is
calculated. This value is then compared with the nominal value Vn /fn and the
saturation value S is derived.

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec VT sec  100 V

VT prim  VTGenOut  VTsec VT prim  11500 V

VT prim
VT  VT  115
VT sec

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
49 / 118
Calculation Note E1117 KDL

Setting Calculation Stage 1

Setpoint of stage 1 given as following: Pickup24G1  107%

Time delay given as following: TD24G1  5s

Setting Calculation Stage 2

Setpoint of stage 2 given as following: Pickup24G2  115%

Time delay given as following: TD24G2  3s

DRS Settings

Overfluxing (24G)
Operate Value St.1 Pickup24G1  1.07
Time Delay St.1 TD24G1  5.00 s
Operate Value St.2 Pickup24G2  1.15
Time Delay St.2 TD24G2  3.00 s
Nominal Voltage VTsec  100.0 V
Nominal Frequency fGenNom  50.0 Hz

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
50 / 118
Calculation Note E1117 KDL

Setting Characteristic

The diagram compares the setting of 59G and 24G (at nominal frequency
f GenNom  50 Hz ).

1 10
3

100
Time / sec

10

1
1 1.05 1.1 1.15 1.2 1.25 1.3 1.35 1.4 1.45
Voltage / pU
59G.1
59G.2
24G.1
24G.2

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
51 / 118
Calculation Note E1117 KDL

Underexcitation (40G)
Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Underexcitation 3-ph.
Quadr. axis react.: 0.50 - 5.00 pU in steps of 0.01
System reactance: 0.00 - 0.20 pU in steps of 0.01
Rotor Angle: 30 - 150 deg in steps of 1
Time Delay: 0.00 - 30.00 s in steps of 0.05

Operating Principle

The underexcitation protection is used to detect failures in the excitation system of


synchronous generators to prevent damage to the equipment and power swings in
the system.
The rotor angle  is calculated with the measured current and voltage and the given
value for quadrature reactance.
This angle is compared with the setpoint.

Active Power (p.u.)

1,0
0,9 0,9
0,9
0,8 0,8
0,8
0,7 0,7
0,7
io n

0,6 0,6 0,6


Tr ip

pe rat

0,5 0,5 0,5


al O

0,4 0,4 0,4


Norm

0,3 0,3 0,3


0,2 0,2 0,2
0,1  0,1 0,1

-1,0 -0,9 -0,8 -0,6 -0,5 -0,4 -0,3 -0,2 -0,1 0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
Reactive Power (p.u.)

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
52 / 118
Calculation Note E1117 KDL

Associated CT

The function is connected to the following CT: CT Generator Neutral-End


CTsec  CTGenNeSec CTsec  1 A

CTprim  CTGenNe  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

Nominal Current

Nominal current of the protected device: Generator


I nom  IGenNom
Inom  2223 A
I nom
I nomSec  InomSec  0.74 A
CT

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec VT sec  100 V

VT prim  VTGenOut  VTsec VT prim  11500 V

VT prim
VT  VT  115
VT sec

Nominal Voltage

Nominal voltage of the protected device: Generator


Unom  UGenNom
Unom  11500 V
Unom
UnomSec  UnomSec  100.00 V
VT

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
53 / 118
Calculation Note E1117 KDL

Setting Calculation

In protection calculation there are two different relative systems (pU systems). One
system is based on generator nominal data, the other is based on protection
nominal data, which is equal to CT and VT primary data. Therefore a
"Compensation factor" is used to convert between these two different systems.

Unom CTprim VTsec


CompFact    CompFact  1.35
VTprim Inom 100V

Stage 1

Setpoint given as following: Pickup  105%

The quadrature reactance is calculated with the pickup level and the synchronous
generator reactance

xq  Pickup  xsynch xq  1.68

The base point in the generator load diagram is calculated with the quadrature
reactance and the generator nominal power
SGenNom
Basepoint  Basepoint  26358 kVAr
xq

The quadrature reactance is converted from generator nominal values to protection


nominal values with the compensation factor

xqProt1  xq  CompFact xqProt1  2.27

The system reactance is calculated from the transformer short circuit impedance.
The result is converted to relative values based on protection nominal data.

xs  0.0000001 xsProt1  xs  CompFact xsProt1  0.00

The rotor angle is measured from the generator load diagram.

 1  85 deg

Time delay given as following: TD1  3s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
54 / 118
Calculation Note E1117 KDL

For comparison the Excitation Limiter of the excitation system is also shown in the
diagram below. Therefore the settings of the excitation is given as following:

Pickupexc  115%

Quadrature and System Reactance from Underexcitation Limiter:

xqExc  Pickupexc  xsynch xqExc  1.84

xsExc  0.000000001

Rotor angle from static Underexcitation Limiter:  ExcStatic  75 deg

Rotor angle from differential Underexcitation Limiter:  ExcDiff  85 deg

The following diagram shows the tripping characteristic of the underexcitation


function in the power (P-Q) plane.
The capability curve (red) is shown only as a circle and does not represent the real
curve.
The underexcitation tripping line is shown in blue on the capacitive area.
The underexcitation Limiter in the excitation system is shown in green.

1.2

0.8
Active Power / pU

0.6

0.4

0.2

1.2 1 0.8 0.6 0.4 0.2 0 0.2 0.4 0.6 0.8 1 1.2
Reactive Power / pU
Capability Curve
Underexcitation Limiter static
Underexcitation Limiter diff
40

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
55 / 118
Calculation Note E1117 KDL

The following diagram shows the tripping characteristic of the underexcitation function in the
impedance (R-X) plane.

0.8

0.6

0.4

0.2

2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
Reactance / pU

0.2

0.4

0.6

0.8

1.2

1.4

1.6

1.8

Resistance / pU
Capability Curve
Underexcitation Limiter static
Underexcitation Limiter diff
40

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
56 / 118
Calculation Note E1117 KDL

DRS Settings

Underexcitation 3-ph (40G)


Quadrature Axis React xqProt1  2.27
System Reactance xsProt1  0.00
Voltage Direction Direction 1
Operate Value St.1  1  85.00 deg
Time Delay St.1 TD1  3.00 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
57 / 118
Calculation Note E1117 KDL

Out of Step (78G)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Out of Step
Base Point (R1): -100.0 - 100.0  in steps of 0.1
Offset (R1-R2): 10.0 - 250.0  in steps of 0.1
Slope: 20.0 - 90.0 deg in steps of 0.1
Imp.Circle Diam.: 10.0 - 500.0  in steps of 0.1
Imp.Circle Cent.: -250.0 - 250.0  in steps of 0.1

Operating Principle
The out of step function is a 3-phase 1-stage relay with blocking at occurrence of
negative phase sequence currents and undervoltage.
It calculates the impedance vector with the positive sequence voltages and currents.
The relay supervises the movement of the vector and by detecting of a trigger
condition a trip will be initiated.

IMPEDANCE DIAGRAM

X [p.u.]
zS
2 xT ADAPT.

xT
p
 
R [p.u.]
-0.5 0.5
x d’
IMP. CIRCLE

BASE
CENTER

POINT
(R1)
IMP. CIRCLE DIAMETER

IMPEDANCE
3 xd’ ADAPTED

CIRCLE

-0.5

OFFSET (R1-R2)

-1.0

VERTICAL BLINDER R2
VERTICAL BLINDER R1

LEGEND
xd’ adapted transient generator reactance
xT adapted transformer reactance
zS adapted external system impedance (line)
 rotor angle (between E p and Uline): 120°/240°
p phase angle (between Ep-Uline and Igenerator)
R1 distance between coordinate zero-point and blinder R1
R1-R2 distance between blinder R1 and blinder R2
[p.u.] refered to RELAY NOM. VALUES/
all imp. set values to be adapted to RELAY NOM. VALUES

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
58 / 118
Calculation Note E1117 KDL

Associated CT

The function is connected to the following CT: CT Generator Output


CTsec  CTGenOutSec CTsec  1 A

CTprim  CTGenOut  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

Nominal Current

Nominal current of the protected device: Generator


I nom  IGenNom
Inom  2223 A
I nom
I nomSec  InomSec  0.74 A
CT

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec VT sec  100 V

VT prim  VTGenOut  VTsec VT prim  11500 V

VT prim
VT  VT  115
VT sec

Nominal Voltage

Nominal voltage of the protected device: Generator


Unom  UGenNom
Unom  11500 V
Unom
UnomSec  UnomSec  100.00 V
VT

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
59 / 118
Calculation Note E1117 KDL

Setting Calculation

The transformer reactance is the short circuit impedance from the main transformer:
SGenNom
xT  z Mt  xT  9.6 %
SMtHvNom

The system impedance is based on main transformer nominal power and must
be adapted to be based on generator nominal power

SGenNom
z SysGen  z SysMt  z SysGen  0.84  4.74i %
SMtHvNom

A compensation factor is used to convert between pU-values and secondary values in


Ohm:
2
UGenNom CT
F   F  77.91 
SGenNom VT

The locus is calculated according the drawing above with transient generator reactance
and transformer reactance:

 
z  j  xtrans  xT  z SysGen z  0.008  0.294i

With the result of the locus the two blinders R1 and R2 can be calculated.
The first blinder R1 crosses the real axis at the point calculated below. If the load point
moves over the blinder R1, the function initiates an alarm.

z
xtrans  tan ( 30 deg)
2
R1   R1  0.089
tan ( arg ( z ) ) sin ( arg ( z ) )

The offset shows the distance between the two blinders R1 and R2. If the load point
moves over the blinder R2 within a given time, the function initiates an alarm.

z tan ( 30 deg)
Offset  2   Offset  0.170
2 sin ( arg ( z ) )

The slope of the two blinders is calculated from the angle of the locus:

Slope  arg ( z ) Slope  88.370 deg

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
60 / 118
Calculation Note E1117 KDL

The base point R1 of the first blinder must be converted to a secondary value in ohm
by means of the compensation factor:

R1  8.91 % R1 sec  R1  F R1 sec  6.94 

The offset between the two blinders R1 and R2 must be converted to a secondary
value in ohm by means of the compensation factor:

Offset  16.97 % Offsetsec  Offset  F Offsetsec  13.22 

The slope of the blinders is already calculated and does not need to be converted:

Slope  88.4 deg

The load point must pass the two blinders R1 and R2 inside the impedance circle.
According the drawing above the diameter of the circle is calculated:

ImpCircDia  3  xtrans  2  xT ImpCircDia  0.643

The diameter of the circle must be multiplied with the compensation factor for
secondary values in ohm

ImpCircDia sec  ImpCircDia  F ImpCircDia sec  50.06 

The center of the impedance circle is also calculated according the drawing above:

 ImpCircDia  2  x 
ImpCircCent   T ImpCircCent  0.129
 2 
The center of the circle must be multiplied with the compensation factor for secondary
values in ohm

ImpCircCent sec  ImpCircCent  F ImpCircCent sec  10.03 

The number of slip pulses until a trip is initiated is chosen as following:


SlipPulses  2

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
61 / 118
Calculation Note E1117 KDL

The oscillation frequency of the generator is chosen as following:

fosc  2Hz

The time for the locus to move one cycle is calculated with the oscillation frequency

1
t cycle  tcycle  0.50 s
f osc

The time for the locus to move from R1 to R2 is calculated with the oscillation frequency and
the offset

 Offset 
asin  
1  2 
t R1R2   tR1R2  0.01 s
f osc 

The minimum time for the locus to move from R1 to R2 is calculated with t.R1R2 as
following (valid for the first slip):
Pickup  90 %

t1  Pickup  tR1R2 t1  12.17 ms

The maximum time for one complete slip is calculated with t.cycle as following (valid for
the first slip):
Pickup  200%

T1  Pickup  t cycle T1  1.00 s

The minimum time for the locus to move from R1 to R2 is calculated with t.R1R2 as
following (valid from slip 2 until last trip):
Pickup  80 %

t2  Pickup  tR1R2 t2  10.82 ms

The maximum time for one complete slip is calculated with t.cycle as following (valid
from slip 2 until last trip):
Pickup  200%

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
62 / 118
Calculation Note E1117 KDL

T2  Pickup  t cycle T2  1.00 s

Total time for all slips together is calculated as following:

T3  T1  ( SlipPulses  1)  T2 T3  2.00 s

The maximum negative phase sequence is chosen as following (if the negative phase
sequence is higher, the out-of-step function is blocked):
NPS  10 %

The minimum current value is chosen as following (if the current is below the setting,
the out-of-step function is blocked):

CurrentInterlock  0A

DRS Settings

Out of Step (78G)


Base Point (R1) R1sec  6.94 
Offset (R1-R2) Offsetsec  13.22 
Slope Slope  88.4 deg
Impedance Circle Diameter ImpCircDia sec  50.06 
Impedance Circle Center ImpCircCent sec  10.03 
Slip Pulse Numbers SlipPulses  2
Time Slot t1 t1  0.01 s
Slip Cycle T1 T1  1.00 s
Time Slot t2 t2  0.01 s
Slip Cycle T2 T2  1.00 s
Look-up Time T3 T3  2.00 s
Negative Phase Sequence NPS  10.0 %
Current Interlock CurrentInterlock  0.00 A
Trip instantaneous
Current Direction Direction 1
Phase Rotation Right

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
63 / 118
Calculation Note E1117 KDL

The following diagram shows the impedance circle and the two locus R1 and R2
according calculation above.
The load point must cross the two locus R1 and R2 inside the circle within the given
time. Additional the number of slips must be fulfilled to initiate an alarm and a trip.

1.2

0.8

0.6

0.4

0.2
Reactance / pU

1.2 1 0.8 0.6 0.4 0.2 0 0.2 0.4 0.6 0.8 1 1.2

0.2

0.4

0.6

0.8

1.2

Resistance / pU
Capability Curve
Impedance Circle
R1
R2
Underexcitation Limiter static
Underexcitation Limiter diff
40

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
64 / 118
Calculation Note E1117 KDL

Stator Earth Fault (64G95/51GN)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Current 1-ph.1-st.
Pickup Level: 0.10 - 5.00 A in steps of 0.01
Time Delay: 0.00 - 30.00 sec in steps of 0.05
Associated CT: CT at star-point of generator

Operating Principle

During stator earth fault the current is limited by a resistor in the neutral circuit. The
earth fault current through the generator is measured by the "generator ground CT".
This CT is connected to a single phase Overcurrent function to detect a stator earth
fault.

Setting Calculation

Setpoint given as following: Pickup  5%

In case of an earth fault at the setpoint level, the voltage at the star-point of the
generator is calculated from relative pickup value and the nominal star voltage

UGenNom
UG  Pickup  UG  332 V
3

The voltage at the secondary side of the grounding transformer is calculated from
primary voltage and grounding transformer ratio

UG
UGsec  UGsec  6.6 V
VTGenN

The zero sequence current on the secondary side of the grounding transformer, which
is also the current through the resistor, is calculated from the secondary voltage and
the resistor impedance

UGsec
I groundsec  Igroundsec  25.0 A
RGenNSec

The zero sequence current through the generator is calculated from the secondary
current value and the grounding transformer ratio

I groundsec
I ground  Iground  0.50 A
VTGenN

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
65 / 118
Calculation Note E1117 KDL

Relay pickup level (secondary zero sequence current) calculated from secondary
resistance current and secondary grounding CT ratio

Igroundsec
I Relay  IRelay  0.10 A
CTsecGenN

Time delay given as following: TD  0.2s

DRS Settings

Current 1-ph 1-st (64G95/51GN)


Operate Value IRelay  0.10 A
Time Delay TD  0.20 s
Type Overdetection

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
66 / 118
Calculation Note E1117 KDL

Stator Earth Fault 3rd Harmonics (64G100/27GN)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: STE 3rd Harmonic
Operate Value: 0.2 - 5.0 V in steps of 0.1
Time Delay: 0.00 - 30.00 sec in steps of 0.05
Ratio: 0.20 - 5.00 in steps of 0.05
Associated VT: open delta VT and Star point VT

Operating Principle

The stator earth fault protection is used to detect earth faults in the stator winding by
evaluating the 3rd harmonic in the generator voltage.
The distribution of the 3rd harmonic over neutral and terminal side is taken for the
evaluation of earth faults close to the generator neutral. The 3rd harmonic is
measured in the generator neutral with the star point transformer and on the
generator terminals with the open delta VT.
In case of an earth fault, the 3rd harmonic in the neutral is shorted whereby the
value on the generator terminals is increased by the same value.

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
67 / 118
Calculation Note E1117 KDL

Setting Calculation

The correct settings have to be determined on site during earth fault tests. For this
purpose different measurements of the 3rd harmonic in the generator neutral and
on the generator terminals have to be done in dependence of different generator
loads for the healthy condition and for an earth fault.
There should be a difference between the measured values for the healthy
condition and for the case of an earth fault. The setting of the operate value has to
be chosen to be inside this gap. If this is not possible, also the ratio can be changed
to improve the situation.

Setpoint of chosen as following (must be adapted during commissioning):

Pickup  0.5%

Primary voltage calculated from relative pickup value and VT open-delta nominal
voltage

Uprim  Pickup  VTOd  VT OdSec Uprim  58 V

Relay pickup level (secondary voltage) calculated from primary voltage and VT
open-delta ratio
Uprim
Usec  Usec  0.50 V
VT Od

Time delay given as following: TD  1s

Ratio to adapt the open delta VT and star point VT ratio:


VT Od
Ratio  Ratio  1.33
3 VT GenN

DRS Settings

STE 3rd Harmonic (64G100)


Operate Value Usec  0.5 V
Time Delay TD  1.00 s
Ratio Ratio  1.33

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
68 / 118
Calculation Note E1117 KDL

Cable Earth Fault (64B)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Voltage 1-ph.1-st.
Pickup Level: 2.0 - 200.0 V in steps of 0.2
Time Delay: 0.00 - 30.00 sec in steps of 0.05
Associated VT: open delta VT

Operating Principle

The cable earth fault is detected by an open delta VT.


This signal is connected to a single phase voltage function to detect this kind of fault.

Associated VT

The function is connected to the following VT: VT Open Delta


VT sec  VT OdSec VT sec  100 V

VT prim  VTOd  VT sec VT prim  11500 V

VT prim
VT  VT  115
VT sec

Nominal Voltage

Nominal voltage of the protected device: Generator


Unom  UGenNom
Unom  11500 V
Unom
UnomSec  UnomSec  100.00 V
VT

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
69 / 118
Calculation Note E1117 KDL

Setting Calculation

Setpoint given as following: Pickup  12 %

Primary voltage calculated from relative pickup value and nominal voltage

Uprim  Pickup  Unom Uprim  1380 V

Relay pickup level (secondary voltage) calculated from primary voltage and VT ratio

Uprim
Usec  Usec  12.0 V
VT

Time delay given as following: TD  1s

DRS Settings

Voltage 1-ph 1-st (64B)


Operate Value Usec  12.0 V
Time Delay TD  1.00 s
Type Overdetection

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
70 / 118
Calculation Note E1117 KDL

Breaker Failure (50BF)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Current 3-ph.1-st.
Pickup Level: 0.10 - 5.00 A in steps of 0.01
Time Delay: 0.00 - 30.00 sec in steps of 0.05

Operating Principle
The Breaker Failure Function detects the malfunction of 52G - opening. As a result,
the next breaker (52L) will be tripped. The malfunction is detected by supervision of
the generator current, that means after tripping of the breaker, the current must
decrease to a very low level. The function is realized by an overcurrent function
which is always blocked with the signal "Breaker Failure" and is only active during a
trip of the breaker 52G.

Additional to the current function which works only with current, a digital
signalfunction is added, which starts with the inverted "Breaker Failure" signal and
will stop with the "CB open" feedback from the breaker.

Associated CT

The function is connected to the following CT: CT Generator Neutral-End


CTsec  CTGenNeSec CTsec  1 A

CTprim  CTGenNe  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

Nominal Current

Nominal current of the protected device: Generator


I nom  IGenNom
Inom  2223 A
I nom
I nomSec  InomSec  0.74 A
CT

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
71 / 118
Calculation Note E1117 KDL

Setting Calculation

Setpoint given as following: Pickup  14 %

Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom Iprim  311 A

Relay pickup value (secondary current) calculated from primary current and CT ratio

Iprim
I sec  Isec  0.10 A
CT

Time delay given as following: TD50BF  0.25s

DRS Settings

Current 1-ph 1-st (50BF)


Operate Value Isec  0.10 A
Time Delay TD50BF  0.25 s
Type Overdetection

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
72 / 118
Calculation Note E1117 KDL

Voltage Balance (60)


Relay Characteristic
Relay Type: DRS-COMPACT
Protective Function: Voltage Balance 2
Pickup Level I: 0.10 - 3.00 A in steps of 0.05
Pickup Level U: 5,0 - 100.0 V in steps of 0.5
Time Delay: 0.00 - 30.00 sec in steps of 0.05

Operating Principle
The Voltage Balance Function detects a fault at the voltage transformer or the
connection to the voltage transformer by comparing the three phases of the voltage
inputs.
The function calculates the negative phase sequence voltage and the output will be
active if this level is higher than the selected pickup level.
The function will be blocked if the negative phase sequence of the current input will
exceed the pickup level, to prevent a malfunction during a real short circuit in the
plant.

Associated CT

The function is connected to the following CT: CT Generator Neutral-End


CTsec  CTGenNeSec CTsec  1 A

CTprim  CTGenNe  CTsec CTprim  3000 A

CTprim
CT  CT  3000
CTsec

Nominal Current

Nominal current of the protected device: Generator


I nom  IGenNom
Inom  2223 A
I nom
I nomSec  InomSec  0.74 A
CT

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
73 / 118
Calculation Note E1117 KDL

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec VT sec  100 V

VT prim  VTGenOut  VTsec VT prim  11500 V

VT prim
VT  VT  115
VT sec

Nominal Voltage

Nominal voltage of the protected device: Generator


Unom  UGenNom
Unom  11500 V
Unom
UnomSec  UnomSec  100.00 V
VT

Setting Calculation for Voltage

Setpoint of voltage given as following: Pickup  25 %

Primary voltage calculated from relative pickup value and nominal voltage

Uprim  Pickup  Unom Uprim  2875 V

Relay pickup level (secondary voltage) calculated from primary voltage and VT ratio

Uprim
Usec  Usec  25.0 V
VT

The following checks, that the function will become active if one phase is missing.
Therefore the 3 phase system calculated in phasor spelling with 80% voltage

UA  0V  exp ( 0  j )

UGenNom
UB  80 %  exp ( 120deg  j )
3

UGenNom
UC  80 %  exp ( 120deg  j )
3

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
74 / 118
Calculation Note E1117 KDL

The DRS input is the phase-phase voltage

UAB  UA  UB

UBC  UB  UC

UCA  UC  UA

The unity phasor given as following

 2  
a  exp  j
 3 

The negative sequence system calculated as following:

1
Uneg    UAB  a  UBC  a  UCA
2
3  

The negative sequence in absolute and secondary value:

Uneg
Unegsec 
VT Unegsec  26.7 V

The voltage pickup level ( Usec  25.0 V ) must be lower than the calculated
negative sequence value ( Unegsec  26.7 V ).

Setting Calculation for Current

Setpoint of current given as following: Pickup  20.2%

Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom


Iprim  449 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

Iprim
I sec 
CT Isec  0.15 A

Time delay given as following: TD  3s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
75 / 118
Calculation Note E1117 KDL

DRS Settings

Voltage Balance 2 (60)


Operate Value I Isec  0.15 A
Operate Value U Usec  25.0 V
Time Delay TD  3.00 s
Phase Rotation Right

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
76 / 118
Calculation Note E1117 KDL

Block Differential (87B)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Transformer Diff. 3-ph 3-branch
Pickup Level: 0.10 - 0.60 A in steps of 0.01
Time Delay: no

Operating Principle
The connected CT's define the protective range.
The differential protection function is used as selective protection in case of
interwinding faults and in low impedance earthed systems in case of earth faults. The
measuring principle is to form the difference between the CT secondary currents at
either end of the protected zone.
All analog signals of the function are sampled 12 times per cycle. Vector group
compensation is traced digitally, according to the vector group set in the parameter
field. As a result, the currents from all sides of the protected object are available in
the proper phase angle for further processing. Any zero sequence currents that
possibly occur on the protected object are compensated by activating the zero
sequence filter.
The ratio settings "CT ratio compensation" take account of the transformer ratio and
the CT ratio.
The measured values are then added, phase by phase, to the differential current.
The fundamental wave as well as the 2nd harmonic and the 5th harmonic of the
differential current are then calculated, phase by phase.
All current inputs of the differential protection determine the restraint current, phase
by phase. It is the maximum value of the fundamental wave of the currents.
If the tripping condition is met within 24 consecutive samples, the signals "tripping"
and "differential current" in the trip matrix are activated.
The tripping of a phase is blocked whenever the ratio between 2nd harmonic or 5th
harmonic and fundamental wave of the differential current exceeds the values set in
the parameter filed. As a result any false tripping of the differential protection is
prevented when energizing a transformer.
In case of a system disturbance, currents with a higher harmonic contents can also
appear. Whenever the differential current exceeds the value set for parameter
"high-set overcurrent", the harmonic restraint is blocked, phase by phase,
irrespective of the higher harmonic contents; eventually tripping is enabled, phase by
phase. Function output "restraint" indicated the condition of the restraint feature.
The trip output is reset whenever the initiating signal has disappeared during 36
consecutive samples.

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
77 / 118
Calculation Note E1117 KDL

6,0 BIAS=60%

BIAS=50%
Diff. Curr./ Rated Curr..

TRIP
5,0

BIAS=40%
4,0
Set
Diff
BIAS=30%
3,0 0.6
0.5
2,0 0.4
0.3
1,0
0.2 NOTRIP
01

0,0
0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0

Restraint Curr./ RatedCurr.

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
78 / 118
Calculation Note E1117 KDL

Associated CT's

System 1 is connected to the following CT: CT Main Transformer HV

CT1sec  CTMtHvSec
CT1sec  1 A
CT1prim  CTMtHv  CT1sec
CT1prim  200 A
CT1prim
CT1 
CT1sec CT1  200

System 2 is connected to the following CT: CT Main Transformer LV

CT2sec  CTMtLvSec
CT2sec  1 A
CT2prim  CTMtLv  CT2sec
CT2prim  3000 A
CT2prim
CT2 
CT2sec CT2  3000

System 3 is connected to the following CT: CT Auxiliary Transformer HV

CT3sec  CTAtHvSec
CT3sec  1 A
CT3prim  CTAtHv  CT3sec
CT3prim  800 A
CT3prim
CT3 
CT3sec CT3  800

Nominal Current
Nominal current of the protected device: Main Transformer

I nom  IMtHvNom Inom  177 A

I nom
I nomSec  InomSec  0.89 A
CT1

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
79 / 118
Calculation Note E1117 KDL

Nominal Voltage

System 1: Main transformer nominal HV voltage

USys1  UMtHvNom
USys1  150000 V

System 2: Main transformer nominal LV voltage


USys2  UMtLvNom
USys2  11500 V

System 3: Auxiliary transformer nominal HV voltage


USys3  UAtHvNom
USys3  6600 V

Setting Calculation

Setpoint given as following: Pickup  30 %

Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom


Iprim  53 A

Relay pickup level (secondary current) calculated from primary current and CT1 ratio
Iprim
I sec 
CT1 Isec  0.27 A

High Set Overcurrent


The high set overcurrent is equal to the main transformer short circuit current

I High  IMtSc IHigh  1771 A

Relay pickup level (secondary current) calculated from primary current and CT1 ratio

IHigh
I HighSec 
CT1 IHighSec  8.85 A

CT Compensation

The CT compensation is used to compensate the different CT ratio on the inputs of


the protection.

CT2prim USys2
CTcomp21   CTcomp21  1.15
CT1prim USys1

CT3prim USys3
CTcomp31   CTcomp31  0.18
CT1prim USys1

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
80 / 118
Calculation Note E1117 KDL

Settings for Stabilizing Characteristic

Bias of Characteristic chosen as following:


Bias  45 %

Stabilizing Characteristic (Differential Current - Restrained Current)

The diagram shows the differential current (pickup current) over the restrained
current.

4
I.diff / pU

0
0 1 2 3 4 5 6 7 8
I.restrained / pU

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
81 / 118
Calculation Note E1117 KDL

Explanation to the diagram Differential Current over Restrained Current:

The diagram shows the differential current (pickup current) over the restrained
current. Both values are pU based on generator nominal.

The trip area is above the curve.

The DRS calculates the restrained current as the summation of the absolute value
of all currents of system 1 and system 2 (and system 3 if any).

The curve consists of 3 areas:

Area 1 is from zero to DRS nominal current which is


CTsec  1.00 A
Based on generator nominal current the first knee point of the curve is
CT1prim
 113 % .
I nom
In this area the differential pickup current is constant
I sec  0.27 A
or based on transformer nominal current
I prim
 30 %
I nom

Area 2 reaches up to the second knee point which is 3 times DRS nominal current.
3  CT1sec  3.00 A .
Based on generator nominal current the second knee point of the curve is
3  CT1prim
 339 %
I nom
In this area the differential pickup current increases by 30% which is fixed and not
adjustable.

Area 3 reaches from the second knee point up to the infinite.


The differential current increases by the setting "Bias" which is adjustable between
30% and 60%.
In the actual calculation the setting is
Bias  45 %

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
82 / 118
Calculation Note E1117 KDL

DRS Settings
Gen 3.inp.3-ph.-H (87B)
Operate Value Isec  0.27 A
Bias Bias  45.00 %
Vector Group 1-2 0
Vector Group 1-3 0
Zero Sequence Filter System 1 On
Zero Sequence Filter System 2 Off
Zero Sequence Filter System 3 Off
2nd Harmonic 25 %
5th Harmonic 15 %
High Set Overcurrent IHighSec  8.9 A
CT Ratio Compensation 2-1 CTcomp21  1.15
CT Ratio Compensation 3-1 CTcomp31  0.18
Harmonic Bias cross blocking

Impotant Note !
The settings for 2nd Harmonic and 5th Harmonic must be adapted during commissioning.
Several tests (switch on of main transformer) must be done to find out the highest value of
inrush current.
The fault recording feature in DRS-WIN can be used to read out the inrush current and
measure the 2nd and 5th Harmonics. Therefore a not used logic function can be used to
trigger the fault recorder every time the circuit breaker closes.

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
83 / 118
Calculation Note E1117 KDL

Block & Main Transformer Inverse Time Overcurrent (51Binv & 51MTinv)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Inverse Time Overcurrent 3-ph, 2-st
Operating Value St.1: 0.05 - 2.00 A in steps of 0.01
Time Multiplier TMS: 0.05 - 1.00 in steps of 0.05
Operating Value St.2: 1.00 - 31.00 A in steps of 1.00
Time Delay St.2: 0.00 - 31.00 s in steps of 0.05

Operating Principle

Transformer overcurrent protection is used to protect the transformer against short


circuits.
The first stage of this function works with inverse time operating characteristic
according four standard curves: extremely, very, normal and long inverse.
The second stage of this function works with definite time characteristic.

Associated CT

The function is connected to the following CT: CT Main Transformer HV


CTsec  CTMtHvSec
CTsec  1 A
CTprim  CTMtHv  CTsec
CTprim  200 A
CTprim
CT 
CTsec CT  200

Nominal Current

Nominal current of the protected device: Main Transformer

I nom  IMtHvNom Inom  177 A

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
84 / 118
Calculation Note E1117 KDL

Setting Calculation

Characteristic chosen as following:


Characteristic  "Normal Inverse"

Pickup of stage 1 chosen as following:


Pickup  105%
Operating value of stage 1 (secondary current) calculated from relative pickup value,
transformer nominal current and CT ratio
I s1prim  Pickup  I nom
Is1prim  186 A
Is1prim
I s1sec 
CT Is1sec  0.93 A

I s1sec
I s1  Is1  0.93
CTsec

Time multiplier of stage 1 chosen as following:


TMS  0.1s

Operate value of stage 2 chosen equal to subtransient main transformer current:

Pickup  105%

I s2prim  Pickup  I MtSubTrans Is2prim  885 A

Is2prim
I s2sec  Is2sec  4.42 A
CT

I s2sec
I s2  Is2  4.42
CTsec

I s2prim
I s2pU  Is2pU  5.00
I nom

Time delay of stage 2 chosen as following: TD  0.000001s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
85 / 118
Calculation Note E1117 KDL

Trip Characteristic (Time - Current)

Trip characteristic shown on double logarithm scale. The first part is the inverse
curve of stage 1, the second part is the definite characteristic of stage 2.
The x-axis shows the generator current in pU.
The y-axis shows the time delay of the protective function in sec.

1 10
3

100

10
Time / sec

0.1

0.01
1 10 100
Current / pU
inverse
definite.1
definite.2

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
86 / 118
Calculation Note E1117 KDL

DRS Settings

IDMT Overcurrent 3-ph.2-st. (51Binv & 51MTinv)


Operate Value St.1 Ph. ABC Is1  0.93
TMS St.1 Ph. ABC TMS  0.100 s
Characteristic Ph. ABC Characteristic  "Normal Inverse"
Operate Value St.2 Ph. ABC Is2  4.4
Time Delay St.2 Ph. ABC TD  0.00 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
87 / 118
Calculation Note E1117 KDL

Block & Main Transformer Overcurrent Stage 1 and 2 (50B & 50MT)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Current 3-ph.2-st.
Pickup Level 1: 0.10 - 5.00 A in steps of 0.01
Time Delay 1: 0.00 - 30.00 sec in steps of 0.05
Pickup Level 2: 0.10 - 30.00 A in steps of 0.05
Time Delay 2: 0.00 - 30.00 sec in steps of 0.05

Operating Principle

Transformer overcurrent protection is used to protect the transformer against short


circuits.

Associated CT

The function is connected to the following CT: CT Main Transformer HV


CTsec  CTMtHvSec
CTsec  1 A
CTprim  CTMtHv  CTsec
CTprim  200 A
CTprim
CT 
CTsec CT  200

Nominal Current

Nominal current of the protected device: Main Transformer

I nom  IMtHvNom
Inom  177 A

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
88 / 118
Calculation Note E1117 KDL

Setting Calculation Stage 1

Setpoint given as following: Pickup50MT1  120%

Primary current calculated from relative pickup value and nominal current

I prim  Pickup50MT1  Inom


Iprim  212 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

I prim
I sec1 
CT Isec1  1.06 A

Time delay given as following:


TD50MT1  6sec

Setting Calculation Stage 2

Setpoint given as following: Pickup50MT2  200%

Primary current calculated from relative pickup value and nominal current

I prim  Pickup50MT2  Inom


Iprim  354 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

I prim
I sec2 
CT Isec2  1.77 A

Time delay given as following:


TD50MT2  1s

DRS Settings

Current 3-ph.2-st. (50B & 50MT)


Operate Value St.1 Isec1  1.06 A
Time Delay St.1 TD50MT1  6.00 s
Operate Value St.2 Isec2  1.77 A
Time Delay St.2 TD50MT2  1.00 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
89 / 118
Calculation Note E1117 KDL

Main Transformer Neutral Overcurrent 1 (51MT.N.1)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Current 1-ph.2-st.
Pickup Level: 0.10 - 5.00 A in steps of 0.01
Time Delay: 0.00 - 30.00 sec in steps of 0.05
Pickup Level 2: 0.10 - 30.00 A in steps of 0.05
Time Delay 2: 0.00 - 30.00 sec in steps of 0.05

Operating Principle

Transformer neutral overcurrent protection is used to protect the solidly grounded


transformer against earth fault. The neutral sequence current is detected with a CT
in the neutral of the HV side of the transformer. A single phase overcurrent function
is connected to this CT.

Associated CT

The function is connected to the following CT: CT Main Transformer HV Neutral 1


CTsec  CTMtNSec
CTsec  1 A
CTprim  CTMtN  CTsec
CTprim  200 A
CTprim
CT 
CTsec CT  200

Nominal Current
Nominal current of the protected device: Main Transformer

I nom  IMtHvNom
Inom  177 A

Setting Calculation Stage 1

Setpoint given as following:


Pickup  30 %
Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom


Iprim  53 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

I prim
I sec1 
CT Isec1  0.27 A

Time delay given as following: TD1  4s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
90 / 118
Calculation Note E1117 KDL

Setting Calculation Stage 2

Setpoint given as following:


Pickup  30 %

Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom Iprim  53 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

I prim
I sec2  Isec2  0.27 A
CT

Time delay given as following: TD2  0.50s

DRS Settings

Current 3-ph.2-st. (51MT.N.1)


Operate Value St.1 Isec1  0.27 A
Time Delay St.1 TD1  4.00 s
Operate Value St.2 Isec2  0.27 A
Time Delay St.2 TD2  0.50 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
91 / 118
Calculation Note E1117 KDL

Main Transformer Neutral Overcurrent 2 (51MT.N.2)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Current 1-ph.2-st.
Pickup Level: 0.10 - 5.00 A in steps of 0.01
Time Delay: 0.00 - 30.00 sec in steps of 0.05
Pickup Level 2: 0.10 - 30.00 A in steps of 0.05
Time Delay 2: 0.00 - 30.00 sec in steps of 0.05

Operating Principle

Transformer neutral overcurrent protection is used to protect the solidly grounded


transformer against earth fault. The neutral sequence current is detected with a CT
in the neutral of the HV side of the transformer. A single phase overcurrent function
is connected to this CT.

Associated CT

The function is connected to the following CT: CT Main Transformer HV Neutral 2


CTsec  CTMtN2Sec
CTsec  1 A
CTprim  CTMtN2  CTsec
CTprim  400 A
CTprim
CT 
CTsec CT  400

Nominal Current
Nominal current of the protected device: Main Transformer

I nom  IMtHvNom
Inom  177 A

Setting Calculation Stage 1

Setpoint given as following:


Pickup  30 %
Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom


Iprim  53 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

I prim
I sec1 
CT Isec1  0.13 A

Time delay given as following: TD1  4s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
92 / 118
Calculation Note E1117 KDL

Setting Calculation Stage 2

Setpoint given as following:


Pickup  30 %

Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom Iprim  53 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

I prim
I sec2  Isec2  0.13 A
CT

Time delay given as following: TD2  0.50s

DRS Settings

Current 3-ph.2-st. (51MT.N.2)


Operate Value St.1 Isec1  0.13 A
Time Delay St.1 TD1  4.00 s
Operate Value St.2 Isec2  0.13 A
Time Delay St.2 TD2  0.50 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
93 / 118
Calculation Note E1117 KDL

Main Transformer Restricted Earth Fault (64T.REF)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Transformer Diff. 3-ph 2-branch
Pickup Level: 0.10 - 0.60 A in steps of 0.01
Time Delay: no
Associated CT: Transformer HV CT (zero sequence system) and
Transformer neutral CT

Operating Principle

Transformer restricted earth fault protection detects an earth fault within the
protection range and is stable against faults outside this range. The function is
connected to the zero sequence system of the main transformer HV CT and the main
transformer neutral CT. These CT's cover the protection range. The protective
function is realized with a transformer differential function. The advantage is the bias
of this function, to make 64T.REF stable against errors of the CT 's.

The analog signals of the function are sampled 12 times per cycle. The
corresponding vectors (value and phase) for 1st harmonic (nominal frequency) are
calculated with Fourier analysis. For each sample the differential signals are
calculated for each phase and checked whether the setting value has been
exceeded.
If during 11 consecutive samples (0.9 cycles) the values are above the setting the trip
output in the trip matrix is active.
If during 36 consecutive samples (3 cycles) the initiating conditions are no longer
fulfilled the trip output in the trip matrix will reset.
Associated CT's

System 1 is connected to the following CT: CT Main Transformer HV

CT1sec  CTMtHvSec
CT1sec  1 A
CT1prim  CTMtHv  CTsec
CT1prim  200 A
CT1prim
CT1 
CT1sec CT1  200

System 2 is connected to the following CT: CT Main Transformer Neutral

CT2sec  CTMtNSec
CT2sec  1 A
CT2prim  CTMtN  CTsec
CT2prim  200 A
CT2prim
CT2 
CT2sec CT2  200

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
94 / 118
Calculation Note E1117 KDL

Nominal Voltage

System 1: Main transformer nominal HV voltage

USys1  UMtHvNom
USys1  150000 V

System 2: same voltage as System 1


USys2  USys1
USys2  150000 V

Setting Calculation

Setpoint given as following:


Pickup  30 %
Primary current calculated from relative pickup value and nominal HV current

I prim  Pickup  Inom


Iprim  53 A

Relay pickup level (secondary current) calculated from primary current and CT1 ratio

Iprim
I sec 
CT1 Isec  0.27 A

High Set Overcurrent

The high set overcurrent is equal to the main transformer short circuit current

I High  IMtSc
IHigh  1771 A

Relay pickup level (secondary current) calculated from primary current and CT1 ratio

IHigh
I HighSec 
CT1 IHighSec  8.85 A

CT Compensation

The CT compensation is used to compensate the different CT ratio on the inputs of


the protection.

CT2prim USys2
CTcomp21   CTcomp21  1.00
CT1prim USys1

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
95 / 118
Calculation Note E1117 KDL

Settings for Stabilizing Characteristic

Slope of Characteristic chosen as following:


Slope  45 %

DRS Settings
Gen 2.inp.3-ph.-H (64MT.REF)
Operate Value Isec  0.27 A
Bias Slope  45.00 %
Vector Group 1-2 0
Zero Sequence Filter System 1 Off
Zero Sequence Filter System 2 Off
2nd Harmonic 25 %
5th Harmonic 15 %
High Set Overcurrent IHighSec  8.9 A
CT Ratio Compensation 2-1 CTcomp21  1.00
Harmonic Bias phase blocking

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
96 / 118
Calculation Note E1117 KDL

Main Transformer Overfluxing (24T)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Overfluxing
Pickup Level 1: 0.80 - 1.50 pU in steps of 0.01
Time Delay 1: 0.0 - 300.0 s in steps of 0.05
Pickup Level 2: 0.80 - 1.50 pU in steps of 0.01
Time Delay 2: 0.0 - 100.0 s in steps of 0.05

Operating Principle

Electrical Equipment is designed and dimensioned for a maximum magnetic flux


during operation. If this value is exceeded, the equipment may suffer direct or
indirect damage. The increased magnetizing current, with a higher harmonic content,
of a transformer for example, not only causes heating up of the transformer, but also
produces in inadmissible high voltage peaks in the field circuit.

The Overfluxing protection is a single phase system. The supplied voltage signal is
sampled 12 times per cycle. The value and frequency of the signal for each sample
are determined, using the Fourier transformation and subsequently the value V/f is
calculated. This value is then compared with the nominal value Vn /fn and the
saturation value S is derived.

Associated VT

The function is connected to the following VT: VT Generator Output


VT sec  VT GenOutSec VT sec  100 V

VT prim  VTGenOut  VTsec VT prim  11500 V

VT prim
VT  VT  115
VT sec

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
97 / 118
Calculation Note E1117 KDL

Setting Calculation Stage 1

Setpoint of stage 1 given as following: Pickup24G1  107%

Time delay given as following: TD24G1  5s

Setting Calculation Stage 2

Setpoint of stage 2 given as following: Pickup24G2  115%

Time delay given as following: TD24G2  3s

DRS Settings

Overfluxing (24T)
Operate Value St.1 Pickup24G1  1.07
Time Delay St.1 TD24G1  5.00 s
Operate Value St.2 Pickup24G2  1.15
Time Delay St.2 TD24G2  3.00 s
Nominal Voltage VTsec  100.0 V
Nominal Frequency fGenNom  50.0 Hz

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
98 / 118
Calculation Note E1117 KDL

Setting Characteristic

The diagram compares the setting of 59G and 24G (at nominal frequency
f GenNom  50 Hz ).

1 10
3

100
Time / sec

10

1
1 1.05 1.1 1.15 1.2 1.25 1.3 1.35 1.4 1.45
Voltage / pU
59G.1
59G.2
24G.1
24G.2

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
99 / 118
Not Used
Calculation Note E1117 KDL
AT protections cover by ABB

Auxiliary Transformer Differential (87AT)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Transformer Diff. 3-ph 3-branch
Pickup Level: 0.10 - 0.60 A in steps of 0.01
Time Delay: no

Operating Principle
The connected CT's define the protective range.
The differential protection function is used as selective protection in case of
interwinding faults and in low impedance earthed systems in case of earth faults. The
measuring principle is to form the difference between the CT secondary currents at
either end of the protected zone.
All analog signals of the function are sampled 12 times per cycle. Vector group
compensation is traced digitally, according to the vector group set in the parameter
field. As a result, the currents from all sides of the protected object are available in
the proper phase angle for further processing. Any zero sequence currents that
possibly occur on the protected object are compensated by activating the zero
sequence filter.
The ratio settings "CT ratio compensation" take account of the transformer ratio and
the CT ratio.
The measured values are then added, phase by phase, to the differential current.
The fundamental wave as well as the 2nd harmonic and the 5th harmonic of the
differential current are then calculated, phase by phase.
All current inputs of the differential protection determine the restraint current, phase
by phase. It is the maximum value of the fundamental wave of the currents.
If the tripping condition is met within 24 consecutive samples, the signals "tripping"
and "differential current" in the trip matrix are activated.
The tripping of a phase is blocked whenever the ratio between 2nd harmonic or 5th
harmonic and fundamental wave of the differential current exceeds the values set in
the parameter filed. As a result any false tripping of the differential protection is
prevented when energizing a transformer.
In case of a system disturbance, currents with a higher harmonic contents can also
appear. Whenever the differential current exceeds the value set for parameter
"high-set overcurrent", the harmonic restraint is blocked, phase by phase,
irrespective of the higher harmonic contents; eventually tripping is enabled, phase by
phase. Function output "restraint" indicated the condition of the restraint feature.
The trip output is reset whenever the initiating signal has disappeared during 36
consecutive samples.

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
100 / 118
Not Used
Calculation Note E1117 KDL
AT protections cover by ABB

6,0 BIAS=60%

BIAS=50%
Diff. Curr./ Rated Curr..

TRIP
5,0

BIAS=40%
4,0
Set
Diff
BIAS=30%
3,0 0.6
0.5
2,0 0.4
0.3
1,0
0.2 NOTRIP
01

0,0
0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0

Restraint Curr./ RatedCurr.

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
101 / 118
Not Used
Calculation Note E1117 KDL
AT protections cover by ABB

Associated CT's

System 1 is connected to the following CT: CT Auxiliary Transformer HV

CT1sec  CTAtHvSec
CT1sec  1 A
CT1prim  CTAtHv  CT1sec
CT1prim  800 A
CT1prim
CT1 
CT1sec CT1  800

System 2 is connected to the following CT: CT Auxiliary Transformer LV

CT2sec  CTAtLvSec
CT2sec  1 A
CT2prim  CTAtLv  CT2sec
CT2prim  500 A
CT2prim
CT2 
CT2sec CT2  500

Nominal Current
Nominal current of the protected device: Auxiliary Transformer

I nom  IAtHvNom Inom  437 A

I nom
I nomSec  InomSec  0.55 A
CT1

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
102 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Nominal Voltage
System 1: Auxiliary transformer nominal HV voltage

USys1  UAtHvNom
USys1  6600 V

System 2: Auxiliary transformer nominal LV voltage


USys2  UAtLvNom
USys2  420 V

Setting Calculation

Setpoint given as following: Pickup  25 %

Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom


Iprim  109 A

Relay pickup level (secondary current) calculated from primary current and CT1 ratio
Iprim
I sec 
CT1 Isec  0.14 A

High Set Overcurrent


The high set overcurrent is equal to the main transformer short circuit current

I High  IMtSc IHigh  1771 A

Relay pickup level (secondary current) calculated from primary current and CT1 ratio

IHigh
I HighSec 
CT1 IHighSec  2.21 A

CT Compensation

The CT compensation is used to compensate the different CT ratio on the inputs of


the protection.

CT2prim USys2
CTcomp21   CTcomp21  0.04
CT1prim USys1

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
103 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Settings for Stabilizing Characteristic

Bias of Characteristic chosen as following:


Bias  45 %

Stabilizing Characteristic (Differential Current - Restrained Current)

The diagram shows the differential current (pickup current) over the restrained
current.

4
I.diff / pU

0
0 1 2 3 4 5 6 7 8
I.restrained / pU

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
104 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Explanation to the diagram Differential Current over Restrained Current:

The diagram shows the differential current (pickup current) over the restrained
current. Both values are pU based on generator nominal.

The trip area is above the curve.

The DRS calculates the restrained current as the summation of the absolute value
of all currents of system 1 and system 2 (and system 3 if any).

The curve consists of 3 areas:

Area 1 is from zero to DRS nominal current which is


CTsec  1.00 A
Based on generator nominal current the first knee point of the curve is
CT1prim
 183 % .
I nom
In this area the differential pickup current is constant
I sec  0.14 A
or based on transformer nominal current
I prim
 25 %
I nom

Area 2 reaches up to the second knee point which is 3 times DRS nominal current.
3  CT1sec  3.00 A .
Based on generator nominal current the second knee point of the curve is
3  CT1prim
 549 %
I nom
In this area the differential pickup current increases by 30% which is fixed and not
adjustable.

Area 3 reaches from the second knee point up to the infinite.


The differential current increases by the setting "Bias" which is adjustable between
30% and 60%.
In the actual calculation the setting is
Bias  45 %

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
105 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

DRS Settings
Gen 3.inp.3-ph.-H (87AT)
Operate Value Isec  0.14 A
Bias Bias  45.00 %
Vector Group 1-2 0
Vector Group 1-3 0
Zero Sequence Filter System 1 On
Zero Sequence Filter System 2 Off
Zero Sequence Filter System 3 Off
2nd Harmonic 25 %
5th Harmonic 15 %
High Set Overcurrent IHighSec  2.2 A
CT Ratio Compensation 2-1 CTcomp21  0.04
Harmonic Bias cross blocking

Impotant Note !
The settings for 2nd Harmonic and 5th Harmonic must be adapted during commissioning.
Several tests (switch on of main transformer) must be done to find out the highest value of
inrush current.
The fault recording feature in DRS-WIN can be used to read out the inrush current and
measure the 2nd and 5th Harmonics. Therefore a not used logic function can be used to
trigger the fault recorder every time the circuit breaker closes.

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
106 / 118
Not Used
Calculation Note E1117 KDL
AT protections cover by ABB

Auxiliary Transformer Inverse Time Overcurrent (51ATinv)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Inverse Time Overcurrent 3-ph, 2-st
Operating Value St.1: 0.05 - 2.00 A in steps of 0.01
Time Multiplier TMS: 0.05 - 1.00 in steps of 0.05
Operating Value St.2: 1.00 - 31.00 A in steps of 1.00
Time Delay St.2: 0.00 - 31.00 s in steps of 0.05

Operating Principle

Transformer overcurrent protection is used to protect the transformer against short


circuits.
The first stage of this function works with inverse time operating characteristic
according four standard curves: extremely, very, normal and long inverse.
The second stage of this function works with definite time characteristic.

Associated CT

The function is connected to the following CT: CT Auxiliary Transformer HV


CTsec  CTAtHvSec
CTsec  1 A
CTprim  CTAtHv  CTsec
CTprim  800 A
CTprim
CT 
CTsec CT  800

Nominal Current

Nominal current of the protected device: Auxiliary Transformer

I nom  IAtHvNom Inom  437 A

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
107 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Setting Calculation

Characteristic chosen as following:


Characteristic  "Normal Inverse"

Pickup of stage 1 chosen as following:


Pickup  105%
Operating value of stage 1 (secondary current) calculated from relative pickup value,
transformer nominal current and CT ratio
I s1prim  Pickup  I nom
Is1prim  459 A
Is1prim
I s1sec 
CT Is1sec  0.57 A

I s1sec
I s1  Is1  0.57
CTsec

Time multiplier of stage 1 chosen as following:


TMS  0.1s

Operate value of stage 2 chosen equal to subtransient main transformer current:

Pickup  105%

I s2prim  Pickup  I MtSubTrans Is2prim  885 A

Is2prim
I s2sec  Is2sec  1.11 A
CT

I s2sec
I s2  Is2  1.11
CTsec

I s2prim
I s2pU  Is2pU  2.02
I nom

Time delay of stage 2 chosen as following: TD  0.000001s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
108 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Trip Characteristic (Time - Current)

Trip characteristic shown on double logarithm scale. The first part is the inverse
curve of stage 1, the second part is the definite characteristic of stage 2.
The x-axis shows the generator current in pU.
The y-axis shows the time delay of the protective function in sec.

1 10
3

100

10
Time / sec

0.1

0.01
1 10 100
Current / pU
inverse
definite.1
definite.2

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
109 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

DRS Settings

IDMT Overcurrent 3-ph.2-st. (51ATinv)


Operate Value St.1 Ph. ABC Is1  0.57
TMS St.1 Ph. ABC TMS  0.100 s
Characteristic Ph. ABC Characteristic  "Normal Inverse"
Operate Value St.2 Ph. ABC Is2  1.1
Time Delay St.2 Ph. ABC TD  0.00 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
110 / 118
Not Used
Calculation Note E1117 KDL
AT protections cover by ABB

Auxiliary Transformer Overcurrent Stage 1 and 2 (50AT)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Current 3-ph.2-st.
Pickup Level 1: 0.10 - 5.00 A in steps of 0.01
Time Delay 1: 0.00 - 30.00 sec in steps of 0.05
Pickup Level 2: 0.10 - 30.00 A in steps of 0.05
Time Delay 2: 0.00 - 30.00 sec in steps of 0.05

Operating Principle

Transformer overcurrent protection is used to protect the transformer against short


circuits.

Associated CT

The function is connected to the following CT: CT Auxiliary Transformer HV


CTsec  CTAtHvSec
CTsec  1 A
CTprim  CTAtHv  CTsec
CTprim  800 A
CTprim
CT 
CTsec CT  800

Nominal Current

Nominal current of the protected device: Auxiliary Transformer

I nom  IAtHvNom
Inom  437 A

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
111 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Setting Calculation Stage 1

Setpoint given as following: Pickup50AT1  120%

Primary current calculated from relative pickup value and nominal current

I prim  Pickup50MT1  Inom


Iprim  525 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

I prim
I sec1 
CT Isec1  0.66 A

Time delay given as following:


TD50AT1  6sec

Setting Calculation Stage 2

Setpoint given as following: Pickup50AT2  200%

Primary current calculated from relative pickup value and nominal current

I prim  Pickup50MT2  Inom


Iprim  875 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

I prim
I sec2 
CT Isec2  1.09 A

Time delay given as following:


TD50AT2  1s

DRS Settings

Current 3-ph.2-st. (50AT)


Operate Value St.1 Isec1  0.66 A
Time Delay St.1 TD50MT1  6.00 s
Operate Value St.2 Isec2  1.09 A
Time Delay St.2 TD50MT2  1.00 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
112 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Auxliary Transformer Neutral Overcurrent (51AT.N)

Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Current 1-ph.2-st.
Pickup Level: 0.10 - 5.00 A in steps of 0.01
Time Delay: 0.00 - 30.00 sec in steps of 0.05
Pickup Level 2: 0.10 - 30.00 A in steps of 0.05
Time Delay 2: 0.00 - 30.00 sec in steps of 0.05

Operating Principle

Transformer neutral overcurrent protection is used to protect the solidly grounded


transformer against earth fault. The neutral sequence current is detected with a CT
in the neutral of the HV side of the transformer. A single phase overcurrent function
is connected to this CT.

Associated CT

The function is connected to the following CT: CT Auxliary Transformer HV Neutral


CTsec  CTAtNSec
CTsec  1 A
CTprim  CTAtN  CTsec
CTprim  1000 A
CTprim
CT 
CTsec CT  1000

Nominal Current
Nominal current of the protected device: Auxliary Transformer

I nom  IAtHvNom
Inom  437 A

Setting Calculation Stage 1

Setpoint given as following:


Pickup  30 %
Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom


Iprim  131 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

I prim
I sec1 
CT Isec1  0.13 A

Time delay given as following: TD1  4s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
113 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Setting Calculation Stage 2

Setpoint given as following:


Pickup  30 %

Primary current calculated from relative pickup value and nominal current

I prim  Pickup  Inom Iprim  131 A

Relay pickup level (secondary current) calculated from primary current and CT ratio

I prim
I sec2  Isec2  0.13 A
CT

Time delay given as following: TD2  0.50s

DRS Settings

Current 3-ph.2-st. (51AT.N)


Operate Value St.1 Isec1  0.13 A
Time Delay St.1 TD1  4.00 s
Operate Value St.2 Isec2  0.13 A
Time Delay St.2 TD2  0.50 s

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
114 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Breaker Opening Too Long (94GB)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Logic 2
Time Delay: 0.00 - 999.00 s in steps of 0.01 s

Operating Principle

The Logic function is primarily an OR gate of the four function inputs (In 1 to In 4).
Every function input is an AND gate of all selected inputs respectively outputs in the
selection mask.
Every input respectively output may be inverted by a the invert mask.
The function output is an OR function of all four function inputs and may be used directly
or inverted (if selected) with the parameterized time delay as input for the LED matrix or
the output matrix.,
The function output will be feed back to the binary inputs as per selected in the feedback
mask.

Specification

The Breaker Opening Too Long function is the logical part of the breaker failure function.
Both trip relays of the circuit breaker 52G.1 and 52G.2 are supervised and are the input
of the logic function called 52G.tripped.
If the breaker is tripped by any device the function is started. If the breaker opens the
function gets the feedback called 52G.open. If this input gets active within the
supervision time delay the function falls back without action. If the input does not get
active because the breaker did not open, after the time delay the function trips the next
breaker(s).
Logic 2
BI.01: 52G.open IN 1
NOT “94GB“
BI.05: 52G.tripped AND

IN 2

AND
Trip Matrix

OR
IN 3 Feedback

AND

IN 4

AND

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
115 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Setting Calculation

The time delay is chosen to be the same as the function 50BF

TD  TD50BF TD  0.25 s

DRS Settings
Logic 2 (94GB)
In 1 Select BI 01: 52G.open
BI 05: 52G tripped
In 1 Invert BI 01: 52G.open
Time Delay TD  0.25 s
Function output normal

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
116 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Excitation Trip (94Exc)


Relay Characteristic

Relay Type: DRS-COMPACT


Protective Function: Logic 2
Time Delay: 0.00 - 999.00 s in steps of 0.01 s

Operating Principle

The Logic function is primarily an OR gate of the four function inputs (In 1 to In 4).
Every function input is an AND gate of all selected inputs respectively outputs in the
selection mask.
Every input respectively output may be inverted by a the invert mask.
The function output is an OR function of all four function inputs and may be used directly
or inverted (if selected) with the parameterized time delay as input for the LED matrix or
the output matrix.,
The function output will be feed back to the binary inputs as per selected in the feedback
mask.

Specification

The Excitation Trip function is a logical function which trips the generator breaker and the
field breaker in case of an excitation fault.
This functions works as a backup to the function of the excitation system
The input of the logic function is connected to the excitation trip signal which comes from
the excitation system. After a time delay the trips are issued.

Logic 2
BI.02: Excitation.Trip IN 1
“94Exc“
AND

IN 2

AND
Trip Matrix

OR
IN 3 Feedback

AND

IN 4

AND

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
117 / 118
Not Used
Calculation Note E1117
AT protections KDL
cover by ABB

Setting Calculation

The time delay is chosen to be as following TD  0sec

DRS Settings

Logic 2 (94Exc)
In 1 Select BI 02: Excitation.Trip
Time Delay TD  0.00 s
Function output normal

ANDRITZ HYDRO - PRT / Proschek 27.04.2012 Doc. No.: 3-576 850


3576850B_CalculationNote_Prt.mcd Rev.: B
118 / 118

S-ar putea să vă placă și