KEMPEGOWDA
INTERNATIONAL
CONVEYOR/ OR
L
BUTTERFLY (BFV) ZONE
CONTROL VALVE W/TAMPER UNDERSIDE OF FLOOR SLAB 1065mm x 1193mm PLATFORM AIRPORT BENGALURU
SWITCH H
TEST DRAIN RISER
TERMINAL 2

300mm MAX
THREADED HANGER ROD

25mm MIN
COMBINATION FIRE 25mm MIN TO 152mm MAX HUNG CLG
558mm MAX 25mm V 450mm WIDE x 450mm LONG
STANDPIPE-SPRINKLER
8mm
RISER
UPRIGHT HEAD
BENGALURU, INDIA
PRESSURE GAUGE UPRIGHT HEAD

457mm MIN CLEARANCE


TO OBSTRUCTION
BAFFLE PLATE

100mm-150mm
TO FIRE ALARM SYSTEM TIGHT TO BOTTOM

SEE NOTE
OF CONVEYOR OR
TERMINAL 2
WATERFLOW SWITCH (FS)
PLATFORM

100mm
OWNER
25mm SP SUPPLY

K ESCUTCHEON
INSPECTOR'S TEST VALVE
IS 15105, TABLE 13 (11.3.1.2)

RECOMMENDED WALL HOLE


HORIZONTAL DISTANCE VERTICAL DISTANCE
LESS THAN 200mm - FLAT STEEL Bangalore International
SECTIONAL DRAIN

45mm DIAMETER
50mm DIAMETER
VALVE 201mm TO 400mm -20mm 25mm x 15mm WASHER
RED. TEE
Airport Limited
SIGHT GLASS 401mm TO 600mm 0mm

75mmØ
601mm TO 800mm 30mm
801mm TO 1000mm 60mm Project Head Office
1001mm TO 1200mm 100mm Kempegowda International
NOTE: 1201 TO 1400mm 140mm Airport Bengaluru
1401mm TO 1600mm 190mm
UNION WITH CORROSION-RESISTANT ORIFICE Devanahalli, Bangalore 560 300 India
WHEN OBSTRUCTION (DUCT, PIPES OR CABLE TRAY) 1601 TO 1800mm 260mm

50mm
GIVING FLOW EQUIVALENT TO THE SMALLEST
SPRINKLER ORIFICE IN THE SYSTEM. HORIZONTAL DIMENSION IS OVER 1.2M, ADDITIONAL
SPRINKLERS SHALL BE INSTALLED BENEATH THE LEAD CONSULTANT
GALVANIZED SHEET METAL
OBSTRUCTION.
HEAT COLLECTING BAFFLE
J 450mm WIDE

NOTES: BRASS 30mm


1. TO BE PROVIDED IN EACH VALVE ROOM SERVING THE ADJACENT DRAIN PLUG "O" RING
FIRE ZONE -MAX 4500M². SOM India LLC
2. PRV'S TO BE INSTALLED WHERE PRESSURE EXCEEDS 12.0 BAR (SEE DETAIL #1 THIS SHEET).
3. CONTROL ASSEMBLY TO BE INSTALLED IN CONFORMANCE WITH APPLICABLE CODES 14 Wall Street, New York, NY 10005
AND MANUFACTURER'S REQUIREMENTS.
TYPICAL UPRIGHT SPRINKLER
2 LCA / LCE / LANDSIDE INFRASTRUCTURE

STUP Consultants Pvt Ltd


HORIZONTAL SIDEWALL SPRINKLER HEAD HORIZONTAL SIDEWALL 1004-5. Raheja Chambers

SPRINKLER ZONE FLOOR 3 CONNECTION - BELOW BAGGAGE CONVEYOR 4 SPRINKLER HEAD CONNECTION
Nariman Point, MUM 400-021

1
MEPF ENGINEER
I
CONTROL VALVE ASSEMBLY ARUP LTD.
77 Water Street
New York, NY 10005
BAGGAGE CONSULTANT

BNP Associates
SPRINKLER BRANCH MAIN SPRINKLER BRANCH MAIN
P.O. Box 32746
Abu Dhabi, UAE
INSPECTORS TEST VALVE TO SPRINKLER TO SPRINKLER LIGHTING CONSULTANT
TO SPRINKLER SYSTEM SYSTEM
DUCTWORK OR OTHER SYSTEM MAIN DRIVE VALVE BPI
DUCTWORK OR OTHER
OBSTRUCTION OVER OBSTRUCTION OVER
1200mm IN WIDTH 1.2M IN WIDTH 1" UNION WITH BRASS ORIFICE DISK. 302 5th Ave, 12th FL
H HOLE IN DISK EQUAL TO DIAMETER OF New York, NY 10001
SPRINKLER ORIFICE. LANDSCAPE
PRESSURE
GAUGE Grant Associates
APPROVED HANGER
AND PIPE SUPPORT
22 Milk Street
Bath, UK BA1 1UT
IT / SECURITY / PA / FAS

MBII
MIN 25mm-MAX 300mm 44 Mobile Drive
APPROVED HANGER
Toronto, ON M4A 2P2
AND PIPE SUPPORT SIGNAGE / WAYFINDING
MIN 25mm-MAX 300mm

UPRIGHT SPRINKLER HEAD


G WITH GUARD MSD
MAX 300mm CHECK VALVE
2 Young Place
East Kilbride, GLA G75 0TD
AIRSIDE CONSULTANT

PENDENT SPRINKLER HEAD TO FIRE ALARM


WITH GUARD SYSTEM Ch2m Hill
P.O. Box 360
Dubai, UAE
NOTES: APPROVED INDICATING VALVE
MAX 300mm WITH TAMPER SWITCH
1. SPRINKLER CONTRACTOR SHALL
PROVIDE SPRINKLERS ABOVE AND

TS

TS

TS
BELOW DUCT OR OTHER OBSTRUCTION
OVER 1.2M IN WIDTH. OPTION "A" OPTION "B" FIRE STANDPIPE KEYPLAN
AND SPRINKLER
F RISER
2. SPRINKLER CONTRACTOR SHALL
COORDINATE ALL WORK WITH ALL
OTHER TRADES.
TEST DRAIN
RISER

TYPICAL SPRINKLER HEAD


5 ABOVE AND BELOW DUCTWORK FLOOR LEVEL

E SEE PLANS FOR CONTROL ASSEMBLY LOCATIONS.

VERT. INST. OF SPRINKLER FLR. CONTROL ASSEMBLIES W/CHECK VALVE


6 SEAL & SIGNATURE

NOT FOR
D
CONSTRUCTION
PIPE SHIELD SHIELD
DIAMETER LENGTH THICKNESS
6mm THK STEEL 6mm THK STEEL
ANGULAR BAR ANGULAR BAR UP TO 75Ø 300 18 USSG
BOLTS 50 BOLTS
100Ø 375 16 USSG
HORIZONTAL PIPE 'W' x 'T' 'W' x 'T'
UNISTRUT VERTICAL HORIZONTAL PIPE 125Ø 450 16 USSG FIRE LINE
(VERTICAL SIZE) (VERTICAL SIZE) UNISTRUT VERTICAL
PIPE CLAMP OR PIPE CLAMP OR 150Ø 525 16 USSG
APPROVED EQUAL APPROVED EQUAL
250Ø & LARGER 600 14 USSG
ATTACHED TO SUPPORT FIRE LINE
CONCRETE SLAB 27 APR 2018 DETAIL DESIGN MILESTONE 04
09 MAR 2018 DETAIL DESIGN MILESTONE 03
26 JAN 2018 DETAIL DESIGN MILESTONE 02
FIRE LINE 20 DEC 2017 PROGRESS SET
EXISTING WF 06 NOV 2017 DETAIL DESIGN MILESTONE 01

C STEEL MEMBER CONCRETE ANCHOR 29 SEP 2017 DETAIL DESIGN MILESTONE 01 (DRAFT)

OR TRUSS WEB SAFETY BOLT 01 SEP 2017 PROGRESS SET

ELEVATION SECTION
NO. DATE DESCRIPTION

LONGITUDINAL BRACE
ROD (SIZE INSERT FLEXIBLE SECTION
"C" CLAMP WITH RETAINING STEEL AS REQUIRED) (TYP)
RETAINING CLIP STRAP THREADED ROD DOUBLE NUT FLEXIBLE SECTION
(TYP)
50

CLEVIS HANGER
75 CLEVIS HANGER CLEVIS HANGER
ROD (SIZE
AS REQUIRED) DRAWING TITLE
50

B
VARIABLE

45° BOTTOM OF BEAM


6mm THK
INSULATION
FIRE PROTECTION -
ANGULAR BAR OPTION 1 OPTION 2 OPTION 3
75
U-BOLT W/ NUTS
18 GA. GALVANIZED
STANDARD CONFIGURATION OVER AND UNDER CONFIGURATION NESTED CONFIGURATION DETAILS -
75 & WASHERS
PIPE PIPE
SHEET-METAL SHIELD
NOTES: SHEET 1
HORIZONTAL PIPE 1. PIPE MOVEMENTS DUE TO BRIDGE STRUCTURE 80mm(x), 85mm(y), 30mm(z)
(VERTICAL SIZE) 2. FLEXIBLE EXPANSION JOINTS INDICATED ARE ACCEPTABLE FOR PIPE SIZES UP TO 100mm.
FOR PIPE SIZES LARGER THAN 100mm USE F.M. APPROVED BALL JOINT TYPE EXPANSION JOINTS.
CLEVIS HANGER REQUIRED ON PIPING LARGER THAN 1". SINGLE HORIZONTAL CLEVIS HANGER RUNS
LATERAL BRACE GENERAL PURPOSE HANGERS MAY BE USED ON 1" PIPING ONLY. WITH VAPOUR BARRIER INSULATION
DRAWING NUMBER

7
TYPICAL SEISMIC BRACE COMPONENTS
8
TYPICAL HANGER DETAILS
9
FLEXIBLE EXPANSION FT-7000
JOINTS ON FIRE LINES

© Copyright Skidmore, Owings & Merrill LLP