Sunteți pe pagina 1din 11

Failure Analysis of Transmission Line Towers

N. Prasad Rao1; G. M. Samuel Knight2; S. Seetharaman3; N. Lakshmanan4; and Nagesh R. Iyer5

Abstract: Transmission line towers, though designed per code provisions, may fail during mandatory testing required in many countries.
Different types of premature failures that were observed during full-scale testing of transmission line towers at Tower Testing
and Research Station, Structural Engineering Research Centre, Chennai (CSIR-SERC) are studied, and the results are discussed in detail.
The failures are modeled using finite-element software, and the analytical results and the test results are compared with various code pro-
visions. The nonlinear finite-element analysis program NE-Nastran was used to model the elastoplastic behavior of towers. Bracing members
with slenderness ratios above 170 become ineffective, even though they have to carry insignificant forces. Importance of design assumptions
and connection detailing in overall performance of towers were studied. Nonlinear finite-element analysis is useful in understanding the
system behavior and for prediction of the failure pattern and ultimate load. Based on the test results, the importance of studying these failures
is highlighted and significant conclusions were drawn. DOI: 10.1061/(ASCE)CF.1943-5509.0000161. © 2011 American Society of Civil
Engineers.
CE Database subject headings: Electric transmission structures; Electric transmission lines; Nonlinear analysis; Towers; Structural
failures.
Author keywords: Transmission line towers; Nonlinear analysis; Tower testing; Redundants.

Introduction tower members with nominal bolt hole clearance. Steel angle sec-
tions with different grades such as mild, high tensile, and superhigh
The design of mass-produced transmission line (TL) towers is tensile steels are generally used in towers. The load-carrying
based on minimum weight philosophy. The towers are a lattice capacity of the tower not only depends on the individual member
type, consisting of legs, primary, secondary bracings, and cross- capacity, but also on other aspects like joint detailing, framing
arm members. The structural design of the tower is governed eccentricities, force fitting of members, unequal force distribution
by wind loads acting on the conductor, tower body, self-weight
in bolts, and gusset plate connections. Hence, the prototype testing
of the conductor, tower, and other loads caused by icing, line
of TL towers is recommended as essential to verify the design and
deviation, broken wire condition, cascading, erection, maintenance,
detailing. Most of the power transmission tower industries all over
etc. The members in TL towers are generally subjected to tension or
compression forces caused by external loads. Generally the tower is the world have made prototype testing of towers mandatory.
modeled as a pin-jointed space truss. In the analysis, only the leg
and primary bracings are considered, and the redundant members
are not. TL towers are generally analyzed by linear static analysis
Studies on Tower Failures during Prototype Testing
methods. The maximum member forces are arrived at by assuming
Although the existing design methodology for TL towers is serving
that all members are only subjected to axial tension and compres-
the industry well, data from full-scale tests revealed that the behavior
sion forces after analyzing for significant load cases. The final
member sizes are determined based on the effective lengths for of TL towers under complex loading conditions could not be
the compression members and effective area for the tension mem- consistently predicted using present day analytical techniques.
bers. The members are designed based on the prevailing codes of Cross bracing members connected to main legs by one flange of
practice. Bearing type bolted connections are used to connect the each bracing member significantly influences the displacement
within the bracing system. As a result, the intersection joint of
1
Ph.D. Scholar, Structural Engineering Research Centre (CSIR-SERC), tension-compression bracing system, deflects out-of-plane even at
Chennai, India (corresponding author). E-mail: nprao@sercm.org low loads and bending moments are generated (Kemp and Behncke
2
Professor, College of Engineering Guindy, Anna Univ., Chennai, India. 1998).
E-mail: gmsk@annauniv.edu A numerical model for simulating ultimate behavior of lattice
3
Former Director Grade Scientist, Structural Engineering Research steel towers was developed by Lee and McClure (2007). The elastic
Centre (CSIR-SERC), Chennai, India. E-mail: seetha_raman_2000@
yahoo.com
plastic large deformation analysis of a steel lattice tower, using
4
Former Director, Structural Engineering Research Centre finite-element (FE) analysis, was presented and the numerical
(CSIR-SERC), Chennai, India. E-mail: nlaxman@sercm.org results were compared with the full-scale destruction test conducted
5
Director, Structural Engineering Research Centre (CSIR-SERC), on tower section of 10 m height with 8 panels and one cross arm.
Chennai, India. E-mail: nriyer@sercm.org Albermani and Kitipornchai (2009) presented a nonlinear analyti-
Note. This manuscript was submitted on February 4, 2010; approved cal technique accounting for both material and geometric nonli-
on July 27, 2010; published online on July 31, 2010. Discussion period
nearity to predict transmission tower failure. This method was
open until November 1, 2011; separate discussions must be submitted for
individual papers. This paper is part of the Journal of Performance of verified with the results from full-scale tower test conducted on
Constructed Facilities, Vol. 25, No. 3, June 1, 2011. ©ASCE, ISSN a 275 kV D/C transmission tower. The technique showed a good
0887-3828/2011/3-231–240/$25.00. accuracy in terms of failure load and failure mode.

JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES © ASCE / MAY/JUNE 2011 / 231


structural failures, improper detailing, and connection failures. Leg
members often have slenderness ratios in the range of 40–60. In this
range, the compression capacity is nearly equal to the net tension
capacity of the member. The leg members may fail by inelastic
buckling. No specific guideline on secondary bracing and hip brac-
ing patterns are available in the codes of practice. Many failures of
towers are caused by buckling of a compression member, irrespec-
tive of whether they are leg or bracing members. The redundant
members are usually designed with a slenderness ratio that does
not exceed 250.

Present Study

Over 138 full-scale tower tests have been conducted at the Tower
Testing and Research Station, Structural Engineering Research
Fig. 1. Buckling of angle section Centre (CSIR-SERC), and out of this, 32 towers experienced differ-
ent types of premature failures. For the present study, three towers
Design Practice are investigated for their failure during testing (CSIR-SERC 2000,
1997, 2004). The member capacities and member forces at the time
The tower members are usually made of steel equal angle sections. of failure obtained from the conventional pinned truss model are
Fig. 1 shows the cross section of an equal angle member and the given in Table 1. The member capacities were worked out for indi-
main axes. The buckling strength of the member at the weakest axis vidual cases following ASCE 10-97 (ASCE 2000) and IS:802
is considered in the design i.e., VV (ZZ)—axis. This member is (Part1/Sec 2) (IS 1992) specifications. IS:802 specifications are
also restrained by a redundant member connected to a relatively similar to ASCE manual 52 specifications. Hence, the capacity
rigid member at its other end. If a member buckles about its weak- of the member calculated based on IS:802 standard is the same
est axis, the member has to take one of the displaced positions as as that of ASCE 10-97 (ASCE 2000). To study the failure in detail,
shown by dotted lines after buckling. For this, the redundant nonlinear finite-element analysis using NE-Nastran was carried
member has to undergo axial deformation as well as a lateral move- out. Member capacities calculated based on the BS:8100 standard
ment. Redundants are axially stiff and are connected to a relatively are compared with ASCE 10-97 (ASCE 2000) and the test results
rigid member at the other end; the displacement component of main are illustrated in Table 2.
member along the axis of the redundant is prevented. Further, the
redundant has less bending rigidity, so displacement in the lateral Numerical Method
direction cannot be prevented. A redundant in the plane of the brac-
ing connected at an intermediate point, can thus prevent weak axis Nonlinear finite-element (FE) analysis methods are effective for
buckling of the full member, and increase its buckling strength. evaluating the behavior and strength of space frames. NE-Nastran,
If buckling about the weak axis is prevented using a redundant a nonlinear FE analysis program, was used in this study to model
member, then the member has to buckle about major axis, i.e., the elastoplastic behavior of the towers. Four beam column ele-
XX-axis for the same length. This principle is used in the general ments are used to model each angle member of the tower along
design practice of TL towers. the centroid of the angle section for convergence. Although the
beam column element is a line element, the shape of the section
can be defined. The stresses can be obtained from different points
Failure of Transmission Line Towers on the cross section called stress recovery points. The limit load is
reached in the FE analysis when the stress at the maximum stressed
TL towers designed based on code provisions, (for example, see points of the member reaches the yield stress. The nonlinear analy-
ASCE 10-97 (ASCE 2000); BS:8100 [British Standards Institution sis capability of the software accounting for geometric and material
(BSI) 1999]; IS:802 [Bureau of Indian Standards (IS) 1992]), may nonlinearity was used in the analysis to obtain the preultimate
fail during testing for many reasons. The failures that occurred at behavior and the limit loads. The elastic and plastic material proper-
the Tower Testing and Research Station, Chennai, are classified as ties of steel were represented by an elastoplastic bilinear

Table 1. Comparison of Member Capacities, Analytical and Test Failure Loads


Failure load
in percentage
Linear analysis force Member capacity
Nonlinear at test failure ASCE 10-97/IS:
Type of tower Test analysis load (kN) 802-1995 (kN) Failure
400 kV D/c 30°–60° deviation 90 104.2 203 276 Portal frame bracing in leg extension at 12 m
800 kV S/c 15° dev. 95 110 16 12 Both members of X brace system BR1
(a) Middle conductor broken condition 13 12 Both members of X brace system BR2
(b) Right conductor broken condition 100 109 1,138 1,249 Girder top chord member TC1
220 kV M/c 15° deviation 100 106.7 1,479 1,726 Leg in 4th panel from ground level
107.5 126.3 Cross bracing in 4th panel
94 111.7 Cross bracing in 3rd panel

232 / JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES © ASCE / MAY/JUNE 2011


Table 2. Code Comparison
Capacity of
Nonlinear analysis force
Member details member in (kN)
at FE model
Type of tower Size ISA (mm) L/r F y N=mm2 failure load (kN) ASCE/IS BS Remarks
400 kV D/c 110 × 110 × 8 100 350 230 276 247 Portal frame bracing in leg
extension No. 4
800 kV S/c (a) 65 × 65 × 4 280 255 26 12 13 BR1
(b) 65 × 65 × 4 280 255 13 12 13 BR2
150 × 150 × 20 63 255 1,221 1,249 1,305 Top chord member TC1
220 kV M/c 150 × 150 × 12 Cruciform 26 255 1,592 1,726 1,628 Leg in 4th panel from ground
100 × 100 × 8 177 255 124 126 107 Cross bracing in 4th panel
100 × 100 × 8 193 255 103 112 95 Cross bracing in 3rd panel

model, with a modulus of elasticity of 2E5 MPa up to yield, 400 kV Double-Circuit DE-Type (30–60°) Dead End
and 2,000 MPa above yield stress. The incremental load and Tower
predictor-corrector iteration under each load increment was used in
The 400 kV double-circuit tower (CSIR-SERC 2000) is designed
the nonlinear range. The isotropic hardening model was used in the
postyield range. Load increments were carried out in 25–30 steps, for use in large line deviation and in dead end locations of heavy ice
until the limit point was reached in the load deformation behavior. zone. The tower is of square configuration with 18 m base width,
The yielding was modeled by the von Mises criterion. Arc-length 6.7 m width at waist level, and 63 m height. The tower configu-
method in conjunction with a modified Newton-Raphson method ration, cross-arm details, secondary bracing pattern, dimensions,
was used to further accelerate convergence of the numerical solu- member sizes, and loads corresponding to the respective failure
tion. By the arc-length scheme, the iterations are forced to converge load case are shown in Fig. 2. Pointed cross arms (conductor sup-
along an arc, thereby often preventing divergence, even when porting points) on left side and box cross arms on right side are
the slope of the load versus the deflection curve decreases to zero used. The tower was tested with 9 m body extension and 12 m
and negative. leg extension. High strength and mild steel angles sections with
yield stress of 350 and 255 MPa are used.
In testing, the transverse horizontal and vertical loads are com-
Towers Studied bined and applied as resultant load at a resultant angle given by
tan1 ðV=HÞ where V is the vertical and H is the horizontal loads.
The towers used for the present study were 400 kV double-circuit, Longitudinal load caused by broken wire conditions is applied as a
and 220 kV multicircuit towers of vertical configuration, and separate horizontal load. Typical steel wire rope arrangement
800 kV single-circuit horizontal configuration towers. (referred as rigging) for load application on the tower is shown

Fig. 2. Configuration of 400 kV double-circuit DE-type tower and loads

JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES © ASCE / MAY/JUNE 2011 / 233


Fig. 5. Redundant pattern and detail at joint A: (a) during testing;
(b) modified after testing

Fig. 3. Rigging arrangement for load application on tower


(No. 2) and rotation in the bracing-belt joint was observed. The
gusset plate connecting the bracing and the horizontal belt mem-
in Fig. 3. Load sensors are connected at cross-arm tips to measure bers at 15 m height created an eccentricity of 150 mm as shown in
the loads. Angle sensors are used to measure and control the direc- Fig. 5(a) detail A. The horizontal belt member at 15 m height, in
tion of application of loads. The loads are applied simultaneously portal frame was ISA 110 × 110 × 8 mm mild steel angle 14 m
through centralized servo-controlled hydraulic actuators at all load- long made of three segments (Nos. 1, 2, and 3). In this, the middle
ing points. segment (No. 2) was a short member of 1.75 m long. The member
Testing was conducted based on IS:802 Part-III (IS 1978) spec- connections between end segments to middle segment (Nos. 1, 2,
ifications. The test loads are applied in increments of 25, 50, 75, 90, and 3, 2) were through single cover butt joint with bolts arranged in
95, and 100% of the specified loads. At each load increment, the single gauge line. It was presumed that the member rotation might
loads are maintained for a minimum of 2 min. For the final 100% be attributed to the previous fact. Hence, two rows of bolts were
level, the loads are maintained for 5 min. At each load level, the provided and the redundant pattern was also changed as shown in
deflections were measured at top of the tower and waist level in the Fig. 5(b). After modification, the test was continued and the tower
transverse and in the longitudinal directions using a theodolite. withstood 100% load without any distress or rotation at joint A.
The tower was designed for 16 different loading cases. On To study the failure pattern, the entire tower was modeled using
applying loads corresponding to narrow front wind (transverse) beam column elements in NE-Nastran. The failed compression
condition, after reaching 90% load, bracing member (No. 4), at bracing (No. 4), middle segment (No. 2), and some portion in
12 m height in portal frame of body extension part, failed along end segments (Nos. 1 and 3) of horizontal belt at 15 m height
with other members as shown in Fig. 4. The failure was attributed and tension bracings were modeled as plate elements. The eccen-
to a group of members, and the joint may have initiated the failure. tricity at joint A and the interconnection between middle and end
Hence, the failed bracing member (No. 4) in portal frame was segments of horizontal belts (Nos. 1, 2 and 3, 2) were incorporated
strengthened by providing an angle member ISA 130 × 130 × in FE model. Beam element with bolt properties evaluated in the
10 mm against the existing section ISA 110 × 110 × 8 mm during numerical study by Rao and Kalyanaraman (2001) in the joint
prototype testing. model representing the bolted connections between angles in
Testing was continued and once the loads reached 75%, a dis- frames are used to model the bolts. The failure load based on
tress in horizontal belt member in the portal frame at 15 m height nonlinear analysis was 104% of transverse narrow front wind

Fig. 4. Failure of bracing in portal frame

234 / JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES © ASCE / MAY/JUNE 2011


of the member based on ASCE and Indian standards are 20%
higher, and based on British standard, the capacity is 7% higher
than the analytical force.

800 kV Single-Circuit Horizontal Configuration


Tower

The 800 kV single-circuit medium line deviation tower (CSIR-


SERC 1997) was 44 m high, square based, and with horizontal con-
figuration. The width of the tower reduces from 17.25 m at ground
level to 11.25 m at waist level. The configuration, dimensions,
member sizes, and loads applied on the tower are shown in Fig. 8.
The girder was 24 m wide with 6.5-m- and 8.85-m-long cross arms
on left and right side, respectively. Mild steel material of yield
stress 255 MPa was used for all the members. The tower was
designed for 30 different loading conditions.
Fig. 6. Deformed view of members in portal frame: FE analysis
In testing, the transverse horizontal and vertical loads are com-
bined and applied as resultant load at a resultant angle. Longitudi-
nal load owing to broken wire condition is applied as a separate
condition. The nonlinear analysis failure and stress patterns are horizontal load. The test was conducted based on IS: 802 Part-III
shown in Figs. 6 and 7. FE analysis predicts out-of-plane buckling (IS 1978) specifications. The deflection measurements were taken
of bracing member (No. 4) and rotation of middle segment (No. 2) at each load level in the transverse and in the longitudinal directions
about joint A similar to the test failure pattern. The stress pattern in at top of the tower. Failure occurred during middle conductor
the bracing member (No. 4) shows that the member was not fully broken and right conductor broken condition tests. Studies are
yielded. The FE analysis shows that the failure of bracing member conducted on these two failures.
(No. 4) was caused not only by force in that member, but also by
rotation of the joint as well. Force in the bracing member (No. 4) Middle Conductor Broken Condition Test
predicted from nonlinear analysis is compared with its capacity cal- During middle conductor broken condition test, X-bracing mem-
culated based on ASCE, IS, and BS codes in Table 2. The capacity bers BR1 in inner K- frame in the longitudinal face above hinge

Fig. 7. Stress pattern in failed bracing member: FE analysis

JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES © ASCE / MAY/JUNE 2011 / 235


at 25 m level failed at 95%. Both the members of the X-bracing
system shown in View C, Fig. 8, buckled in the out-of-plane mode
over its full length. Further, a group of members in the triangle
portion have also failed. The main member forming the triangular
portion above the waist level TP1 and the transverse face X-bracing
BR2 above this triangular portion at 15 m height have also failed as
shown in Fig. 9. Both X-bracings BR1 and BR2 consist of ISA
65 × 65 × 4 mm section. The main member TP1 in triangular
portion consists of double angle of ISA 150 × 150 × 12 mm
connected back to back. The tower was analyzed with linear
and nonlinear analysis methods.
The entire tower was modeled using beam column elements in
NE-Nastran. The nonlinear analysis predicted the failure load as
110% of the middle conductor broken condition loads. The FE
analysis failure pattern is shown in Fig. 10. The capacity of the
bracing member determined, assuming tension-compression brac-
ing system based on the Indian standard, was 25% higher than the
forces calculated using linear analysis.
Both members of the X-bracing system in BR1 and BR2 are
subjected to compressive forces. Whenever both members of
the X-bracing system are in compression, the ASCE standard sug-
gests, that members shall be designed for full length about its major
axis, since the joint at crossover point may not offer the required Fig. 9. Failure in middle conductor broken condition
restraint to the compression member. Based on this, the slenderness
ratio was increased by 26% and the capacity of the member was
reduced by 38% compared with the capacity based on the tension- caused in-plane buckling of the main member TP1 in the triangular
compression system. The force in the X-bracing member BR2 portion.
predicted by nonlinear analysis is 8% higher than its capacity The theoretical capacity of the main member calculated on the
calculated, based on the assumption that there is no restraint from assumption of major axis buckling is 1.77 times that of the force
the joint at the crossover point against out-of-plane buckling. calculated based on test failure load. Capacity of this member about
The main member of triangular portion above waist level TP1 its weak axis is 5.5% higher than that of the force obtained from test
was designed for out-of-plane buckling about its major axis by failure load. This clearly shows that the redundant member R1 has
providing a redundant member R1 at its midlength in elevation. not offered the required restraint to the main member in changing
One end of the redundant member was connected to member its buckling mode from a weak axis to a major axis.
TP1 at its midlength and the other end to the crossover point of As a remedial measure, members in the X-bracing system BR1
X-bracing system BR2. Since BR2 members failed, the redundant and BR2 are changed to ISA 75x75x5 mm and the tower was tested
member R1 connected at a crossover point also deformed, and to its full capacity.

Fig. 8. Configuration of 800 kV single-circuit tower and loads

236 / JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES © ASCE / MAY/JUNE 2011


Fig. 10. FE model failure: middle conductor broken condition

Right Conductor Broken Condition Test as 102%. The FE model failure pattern is shown in Fig. 12. The FE
model with plate elements shows that the stress in some portion of
When the applied loads corresponded to right conductor broken
the top chord member has exceeded the yield stress.
condition test, at 100% load, the top chord member of the The capacity of the member TC1 was assumed as concentrically
girder TC1, near the right cross-arm and girder junction failed, loaded, and was 9.7% more than the member analytical force.
as shown in Fig. 11. The failed top chord member was ISA In reality, one end of the member is connected to inner leg of
150 × 150 × 20 mm. The forces calculated using linear and non- earth wire peak through a gusset plate introducing eccentricity
linear analysis are the same in this member. and the other end is concentrically loaded because it is continuous.
The finite-element model with beam column elements predicted The slenderness ratio of the member with a concentric load on one
the failure load as 109% of right conductor broken condition loads. end and normal framing eccentricity on the other end increased by
In the beam column model, the stresses in the failed top chord 22% and the capacity reduced by 7.3%. This capacity was closer to
member exceeded the yield stress. To check the stress distribution the member force obtained from test failure load. As a remedial
in the top chord member, both flanges of the member were modeled measure, the redundant pattern in the top plan of the girder was
with plate shell elements. The failure pattern is same as that of modified to reduce the slenderness ratio of the top chord member.
model with beam column elements and the failure load is predicted The nonlinear finite-element analysis showed significant varia-
tion in the member forces and was considerably higher than the
conventional linear elastic analysis forces. The nonlinear analysis
forces were 5–13% higher in leg members and 10–20% higher in
bracing members. Leg and bracing members near the hinge portion
were subjected to maximum force. In the girder, the force variation
in the elevation bracings and bottom plan members was 6%. Little
variation was observed in the top and bottom chord members.

220 kV Multicircuit Tower

The 220 kV multicircuit tower (CSIR-SERC 2004) was designed


for carrying 12 conductors, six on each side, and for use in small
line deviation up to 15°. The tower with square base of 12.4 m at
ground level tapered to a width of 2.5 m at 49 m height. From
49–60 m height, the width of 2.5 m is kept constant. A K-braced
pattern was used for the bottom two panels, and X-bracing for all
other panels were provided. Two angles in the form of cruciform
sections were used for leg members from ground to 47 m height.
Tower configuration, cross-arm details, secondary bracing pattern,
dimensions, member sizes, and loads corresponding to failure
loading conditions are shown in Fig. 13. All members were made
of mild steel. The tower was designed for normal loading condition,
earth wire along with one conductor broken condition and simul-
Fig. 11. Top chord failure in right conductor broken condition
taneous breaking of two conductor conditions.

JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES © ASCE / MAY/JUNE 2011 / 237


Fig. 12. FE model failure and stress pattern: right conductor broken condition

Fig. 13. Configuration of 220 kV multicircuit tower and loads

In testing, transverse horizontal and vertical loads are combined 100%, the X-bracing members in the third and fourth panels
and applied as resultant load at a resultant angle. Wind loads on the and leg member in the fourth panel above 12 m from ground level
tower body were combined with the conductor loads at their respec- buckled as shown in Fig. 14.
tive heights, and the wind on the tower body below waist level was The bracing member in the fourth panel buckled at its major
combined and applied at 6 and 18 m levels. The testing was con- axis. Both members of the cross bracing in third panel deflected
ducted based on IS:802 Part-III (IS 1978) specifications. In the out-of-plane. The X-bracing members in the failed panels are long
earth wire and top conductor broken condition test, the tower members with slenderness ratio above 160. The capacity of the
was subjected to transverse and vertical loads at all conductors failed bracing members calculated based on ASCE and Indian stan-
and at earth wire point, in addition to longitudinal load at earth wire dards are 19.4 and 17.5% higher than the forces predicted from the
and right top conductor point. When the tower was loaded up to conventional linear static analysis using truss elements.

238 / JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES © ASCE / MAY/JUNE 2011


Fig. 15. FE model failure: all beam elements: plate and beam elements

Bracing forces in the third and fourth panels obtained from non-
linear analysis are 4–8% more than the forces that were predicted
from linear analysis. Thus, the margin of safety of X-bracings in the
third and fourth panels reduces to 14 and 8%, respectively, calcu-
lated by nonlinear analysis. Once the bracing member in the fourth
panel failed, the leg member in that panel and the bracing member
in third panel also failed. As a remedial measure, the sizes of the
bracing members are increased. The forces predicted from nonlin-
ear analysis are higher—3–10% for bracing members, and 2–4%
for leg members, compared with the forces predicted from the lin-
ear elastic analysis. The experimental deflection was 50% higher
compared with the analytical deflection in the transverse and in
Fig. 14. Failure of leg and braces in panel 3 and panel 4 the longitudinal directions. This additional deformation might have
increased the member forces.

The nonlinear analysis with all members of the tower modeled


using beam column elements predicts the failure load as 107% of Comparison of Tower Capacities
ground wire and top conductor broken condition. The analysis fail-
The member capacities calculated based on BS, ASCE, and Indian
ure pattern of the bracing shown in Fig. 15 coincides with the test
standards are given in Table 2. The ASCE and Indian standards
failure pattern. To check the stress distribution in the leg and brac-
overestimated the load-carrying capacity of single angle bracing
ing member’s cross section, the failed leg and bracing members members by 10–20% for all slenderness ratios.
were modeled using plate elements. The failure pattern of the The bracing member capacities calculated based on British stan-
FE model using plate elements is same as that of the model with dard is closer to experimental values. Causality may be attributed to
beam column elements and predicts the failure load as 105%. The the full width of the angle section instead of the flat width and a
FE model shows that the stresses in some portion of the leg cross reduction factor accounting for member imperfection used in the
section have reached yield stress. design strength calculations.

Fig. 16. Comparison of load capacities for leg members

JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES © ASCE / MAY/JUNE 2011 / 239


Fig. 17. Comparison of load capacities for bracing members

The capacity of cruciform section made of two angles and 4. In the 800 kV horizontal configuration tower, the cross bracing
the capacity of a compound member consisting of pair of angles in the longitudinal face of inner K-frame above the hinge por-
connected back to back at intervals in the form of a T section tion and also the cross bracing above the triangular portion in
and designed for major axis buckling, calculated based on British the transverse face failed, because both the members of cross
standards, is closer to the test results, compared with the capacity bracing system were subjected to compression, and this was
calculated based on American standard. This may be attributable to not accounted for in the design. If both members of cross bra-
the consideration of possible additional deformation caused by cing system are subjected to compression, then there will be no
shear. The capacity of cruciform sections calculated based on lateral restraint from crossover point. Out-of-plane buckling
ASCE standards is 16–20% more than the experimental values. over full length of the member should be considered. The main
Figs. 16 and 17 show the comparison of failure loads for leg and member forming the triangular portion above the waist level
bracing members calculated based on different standards, FE analy- that was made of two angles connected back-to-back failed
sis, and experiments. It shows that the member capacity predicted because of inadequate restraint from the redundant member.
by ASCE standards is always higher than the experimental values 5. All redundant members shall be checked based on British stan-
for all the slenderness ratios of the members. Nonlinear FE analysis dard provisions or it shall be designed for 2.5% of the axial
results are 7–14% more than the test results. force in the main member as recommended in the Indian
standard.

Conclusions
References
It is possible to predict the probable load-carrying capacity of a
tower, deficiencies in the design, and instability in the structure us- Albermani, F., and Kitipornchai, S. (2009). “Failure analysis of transmis-
ing FE nonlinear analysis. Nonlinear analysis should be carried out sion towers.” Eng. Failure Anal., 16(6), 1922–1928.
for slender, tall towers, and for horizontal configuration towers with ASCE. (2000). “Design of latticed steel transmission structures.”
all redundant members included, since force variation is significant. ASCE 10-97, Reston, VA.
Based on the experimental, analytical, and theoretical investigation British Standards Institution (BSI). (1999). “Lattice towers and masts:
carried out on two 220 kV and 400 kV vertical configuration towers Part 3 code of practice for strength assessment of members of lattice
and one 800 kV horizontal configuration tower, the following con- towers and masts.” BS:8100-3:1999, London.
Bureau of Indian Standards (IS) (1978). “Code of practice for use of
clusions are drawn for incorporation in future designs of towers:
structural steel in over head transmission line towers—Testing.” IS:802
1. Bracing members with slenderness ratios above 170 become (Part III), New Delhi, India.
ineffective, even though they carry only small forces. Bureau of Indian Standards (IS) (1992). “Code of practice for use of struc-
2. Nonlinear FE analysis of TL towers leads to increased member tural steel in over head transmission line towers—Permissible stresses.”
forces. In horizontal configuration towers, the forces in the leg IS:802 (Part 1/Sec 2), New Delhi, India.
members increased by 5–8%, and the forces in bracing mem- Kemp, A. R., and Behncke, R. H. (1998). “Behavior of cross bracing in
bers increased by 10–20% compared with conventional linear latticed towers.” J. Struct. Eng., 124(4), 360–367.
static analysis. In the case of multicircuit tower, the nonlinear Lee, P. S., and McClure, G. (2007). “Elastoplastic large deformation analy-
analysis forces in the bracing members have increased by 10%. sis of a lattice steel tower structure and comparison with full scale tests.”
3. In the 400 kV dead-end-type tower, the bracing member in the J. Constr. Steel Res., 63, 709–717.
portal frame of the leg extension failed because of the eccen- Rao, N. P., and Kalyanaraman, V. (2001). “Nonlinear behavior of lattice
panel of angle tower.” J. Constr. Steel Res., 57, 1337–1357.
tricity in the horizontal belt and bracing intersection, which
Structural Engineering Research Centre (CSIR-SERC). (1997). “800 kV
was not accounted in the design. When long belt members S/C, ‘B30’ type tower.” Rep. No. 1030 41, Chennai, India.
are divided into three or more segments from the view point Structural Engineering Research Centre (CSIR-SERC). (2000). “400 kV
of fabrication, it should be proportionate in length and inter- D/C type-DE (30–60°) dead end tower.” Rep. No. 1051 41, Chennai,
connected with bolts in multiple gauge lines instead of single India.
gauge line, to avoid rotation of the joint at belt and bracing Structural Engineering Research Centre (CSIR-SERC). (2004). “220 kV
intersection point. M/C ‘PC-30’ type tower.” Rep. No. 1098 41, Chennai, India.

240 / JOURNAL OF PERFORMANCE OF CONSTRUCTED FACILITIES © ASCE / MAY/JUNE 2011


Copyright of Journal of Performance of Constructed Facilities is the property of American Society of Civil
Engineers and its content may not be copied or emailed to multiple sites or posted to a listserv without the
copyright holder's express written permission. However, users may print, download, or email articles for
individual use.

S-ar putea să vă placă și