Sunteți pe pagina 1din 39

USER MANUAL SLR140

USER MANUAL
OVER CURRENT AND EARTH FAULT RELAY

SLR140

Stelmec Limited | Over Current and Earth Fault Relay 1


USER MANUAL SLR140

PREFACE

 The aim of this handbook is to provide to the user information useful


for the operation of SLR140 relay with the local MMI.

 We advise you to read it carefully, in order to take note of the available


functionalities and to proceed to connection and power of the product
in accordance with the provided recommendations.

 Locally settings, commissioning and real time or event readings are


accessible from keyboard and displayed on the protection display.

 To be fully exploited, the available functions must be parameterized


and consulted with the settings

 Software PC-Protection, provided with the product.

 Before any use, we recommend you to read the safety instructions of


this User’s guide.

Stelmec Limited | Over Current and Earth Fault Relay 2


USER MANUAL SLR140

Contents

1. General......................................................................................................................................... 5
1.1. Safety Instructions......................................................................................................................6
1.2. Relay Features............................................................................................................................7
2. Introduction .................................................................................................................................8
2.1. Application................................................................................................................................ 8
2.2. Main Features............................................................................................................................ 8
3. User Interface...............................................................................................................................9
3.1. General......................................................................................................................................9
3.2. Local Panel................................................................................................................................ 9
3.2.1. Display.................................................................................................................................... 9
3.2.2. Keypad.................................................................................................................................... 9
3.2.3. Indicators............................................................................................................................... 10
4. Local Panel Operation.................................................................................................................. 12
4. 1. Description of Functional Menu............................................................................................... 12
5. Functions..................................................................................................................................... 12
5.1. Principle of the Numerical Protection Technique....................................................................... 12
5.2. Relay Protection Functions........................................................................................................ 13
5.2.1. Non‐Directional Over Current Protection I>, I>> (50/ 51)........................................................ 13
5.2.2. Non‐Directional Earth Fault Protection (50N/ 51N)................................................................ 15
5.2.3. Circuit Breaker Failure Protection (50BF)............................................................................... 16
5.2.4. Self Supervision..................................................................................................................... 17
5.2.5. Auto‐Recloser........................................................................................................................ 17
5.2.6. Cold load pickup.................................................................................................................... 18
5.2.7. Broken Conductor Detection.................................................................................................. 20
5.2.8. Low load Detection.............................................................................................................. ..21
5.2.9. Switch‐on to fault protection ................................................................................................2 1
5.3. Two Different Group Setting.................................................................................................... 22
6.0. Configuration and Parameter Settings..................................................................................... 22
6.1. Principle of Parameter Setting.................................................................................................. 23
6.2. Enabling and Disabling Protection Functions............................................................................ 26
7. Communication........................................................................................................................... 27
7.1. Modbus RS485 Communication................................................................................................ 27
8. Output Response Curves.............................................................................................................. 28

Stelmec Limited | Over Current and Earth Fault Relay 3


USER MANUAL SLR140

8.1. Low Set Characteristics Curves.................................................................................................. 28


8.2. High Set Characteristics............................................................................................................ 31
9.0. Terminal diagram of SLR 140.................................................................................................... 32
9.1. Fixed type: Terminal connection diagram................................................................................. 32
10. Protection Stage....................................................................................................................... 33
10.1. Over Current protection stages............................................................................................... 33
10.2. Earth Fault Current protection stage....................................................................................... 33
10.3. NDR Protection to block the earth fault protection ..................................................... ...........34
10.4. Auto – Recloser protection...................................................................................................... 34
10.5. Cold load pickup..................................................................................................................... 34
10.6. Broken conductor ................................................................................................................... 35
10.7. Low load detection.................................................................................................................. 35
10.8. Switch‐on to fault protection.................................................................................................. 35
11. Technical Data........................................................................................................................... 35
11.1. Auxiliary voltage..................................................................................................................... 35
11.2. Digital input voltage sensing threshold................................................................................... 35
11.3. Current Inputs......................................................................................................................... 36
11.4. Trip Contacts (T1 & T2)............................................................................................................ 36
11.5. Accuracy................................................................................................................................. 36
12. Construction.............................................................................................................................. 37
12.1. Mechanical............................................................................................................................. 37
12.2. Dimensional Drawing............................................................................................................. 37
13. Commissioning.......................................................................................................................... 38
15. Contact Information................................................................................................................... 39

Stelmec Limited | Over Current and Earth Fault Relay 4


USER MANUAL SLR140

1. General

This user manual describes the general function of the combined over current and
earth fault relay SLR140 includes relay operational instructions.

It also includes instructions on parameterization and configuration of the


relay and instructions on changing of settings. And includes detail protection
function descriptions, technical data sheets and case mounting.

Stelmec Limited | Over Current and Earth Fault Relay 5


USER MANUAL SLR140

1.1. Safety Instructions

or user’s safety, we recommend a user to read the following


information/instruction carefully before handling.

The following precautions are essential during installation, testing and


commissioning of the relay considering safety of user and proper operation of the
relay:

1. Both system and safety earth shall be connected to appropriate earth terminal of
the relay.
2. The terminals on the rear panel of the relay may carry dangerous voltages,
although the auxiliary voltage is switched off.
3. A live current transformer secondary circuit is short before disconnecting
current input terminal of the relay. Disconnecting a live circuit may cause
dangerous voltages.
4. Any operational measure must be carried out according to the respective
national handling directives and instructions.

Stelmec Limited | Over Current and Earth Fault Relay 6


USER MANUAL SLR140

1.2. Relay Features

The SLR140 is combined non - directional over current and earth fault protection
relay additional with neutral displacement protection.

Protection features

 Three phase over current with two stages (I> & I>>).
 One earth fault with two stage (Io> & Io>>).
 Neutral displacement function
 Block / Unblocking of EF under NDR
 Auto reclosing by selecting number of shots.
 Cold load pickup (CLP), Avoidance of Circuit Breaker tripping due to initial in-
rush currents at turn-on.
 Broken conductor detection.
 Low load condition.
 Switch-on to fault protection.
 Circuit breaker failure protection.
 1 or 2 different groups setting.
 Phase high set instantaneous or definite time over current stage.
 Non directional definite time and inverse time (IDMT) earth fault stage.
 Numerical display for setting values, measured values, recorded fault
values, indications etc.
 Built-in pulse-width-modulated galvanically isolating power unit for a wide
range of auxiliary supply.
 Continuous self-supervision of relay hardware and software for enhanced
system reliability and availability.

Stelmec Limited | Over Current and Earth Fault Relay 7


USER MANUAL SLR140

2. Introduction

This part of the manual describes few applications, main features, protection functions
and contains technical data and also includes operating instructions.

2.1. Application

In the field of power system protection, Stelmec offers Numerical relays which are
enabled with recent technologies. SLR140 relays provide the optimal management to the
electrical network which is based on the reliability, availability and the functionality of
devices used to control & protect the network. The SLR140 relay monitors and protects
the electrical networks against all types of phase to earth and phase to phase short circuits.

2.2. Main Features

Fully digital signal handling with a powerful 16-bit micro controller high measuring
Accuracy on all setting ranges
Easy enabling and disabling of protection functions according to the needs of the
Intended application.
Wide setting ranges for the protection functions.
Easy adaptation of the relay to various substations and alarm systems due
to a flexible signal-grouping matrix in the relay.
Site selectable Unit ID ( 1 to 254)
Site selectable Baud rate ( 9600/18200/38400/57600)
Site selectable reset time delay (0.0 to 20 sec.)
Recording of events and last 999 fault values into an event register, from which data
can be read via keypad or by means of the PC based SLR140 user interface.
Built-in fault recorder for evaluating secondary, as well as Over current and
neutral currents of the protective object.
Auto – Recloser Function.
Neutral displacement control earth fault protection function.

Stelmec Limited | Over Current and Earth Fault Relay 8


USER MANUAL SLR140

3. User Interface

3.1. General

The SLR140 relay can be controlled in two ways:

Locally with the push buttons on the relay front panel.


Locally with a PC connected to the USB port on the relay front panel.
Remote with RS485 network.

3.2. Local Panel

Figure below show the location of the components of the local user interface on the front
panel of the relay.

LCD display
Keypad
LED Indication
USB communication port for PC.

3.2.1. Display

The SLR140 relay provided with clear characteristics 16x2 lines LCD display.

3.2.2. Keypad

Use the keypad and the display to navigate through the menus and to set the required
parameters/values. The keypad comprises the following keys.
Left, Right, Up, Down And Reset Keys.

Stelmec Limited | Over Current and Earth Fault Relay 9


USER MANUAL SLR140

Up/ Down arrow keys are to select functions Increasing/Decreasing.


Left arrow key is used to enable/disable the function.
Right arrow key is used to enter in to the function
Reset key used to clear the fault on the display/exit from the functions
Reset key is used to see the fault records by long pressing

3.2.3. Indicators

The relay front panel holds 9 LED indicators.

Figure 3.2 Relay front panel.

Stelmec Limited | Over Current and Earth Fault Relay 10


USER MANUAL SLR140

Operation Indicators

LED
Explanation Measure/ Remarks
Indicators
AUX LED Lit The Auxiliary Power Switched ON Normal Operating State
START LED One or several signals of the output relay The LED is switched off, when the signal that
Lit matrix have been assigned to output alarm caused output alarm to activate, e.g. The
and the output has been activated by one of START signal resets. The resetting depends on
the signals. the type of configuration. Connected or
Latched.
TRIP LED Lit One or several signals of the output relay The LED is switched off, when the signal that
matrix have been assigned to output Trip and caused output Trip to activate, e.g. The TRIP
the output has been activated by one of the signal resets. The resetting depends on the type
signals. of configuration.
Instantaneous Trip and the output have been activated by Instant LED is glowing; When the Trip is
high set over current (or) high set earth fault. activating by high set over current (or) high set
earth fault.
I> Trip and the output has been activated by low I> LED is glowing; When the Trip is activating
set over current (L1, L2, L3) by low set over current.
Io> Trip and the output have been activated by Io>LED is glowing; When the Trip is activating
earth fault low set by earth fault low set
NDR Trip and the output have been activated by NDR LED is glowing; When the Trip is
the NDR fault activating by NDR fault
IL< This indicates that the Low load condition IL< LED is glowing; When the Trip is
activating by Low load condition
I2/I1 This LED indicate that the Broken Conductor I2/I1 LED is glowing; When the Trip is
condition activating by Broken conductor

Stelmec Limited | Over Current and Earth Fault Relay 11


USER MANUAL SLR140

4. Local Panel Operation

The local panel can be used to read measured values, set parameters and configure
relay functions

4. 1. Description of Functional Menu

The general menu structure is shown in above figure. The menu is based on the user’s
configuration and the options are according to the order code. For example only the
enabled protection stages will appear in the menu.

5. Functions

The individual protection function of the SLR140 Over current and Earth Fault Relay
can independently of each other be enabled or disabled according to the requirements
of the application.
5.1. Principle of the Numerical Protection Technique

The SLR140 relay is designed using numerical technology. This means that all
signal filtering, protection and control functions are made by digital processing.
The numerical technology used in the relay is primarily based on an adapted fast
Fourier (FFT) analysis, in which case the no of calculations (multiplications &
additions) required to filter the measuring quantity remains reasonable.
By using synchronized sampling of the measured signal (phase or earth fault
current) and a sample rate according to the 2n series, the FFT technique leads to a
solution, which can be realized with just a 8 bit micro-controller without using a
separate DSP (Digital Signal Processor)
The synchronized sampling means an even number of 2n samples per period,
e.g.16 samples/ period. This means that the frequency must be measured and the
no of samples per period must be controlled accordingly, so that the no of samples
per period remains constant should the frequency change.

Stelmec Limited | Over Current and Earth Fault Relay 12


USER MANUAL SLR140

5.2. Relay Protection Functions

The relay having the following protection functions:

Three phase over current protection with (I> & I>>) thresholds.
Earth fault over current protection with (Io> & Io>>) thresholds.
Cold load pickup feature.
Inbuilt Auto recloser
Broken conductor detection
Low load condition.
Switch - on to fault protection
1 or 2 different group setting
50BF circuit breaker failure protection (CBFP) functions by checking of the
dis appearance of the phases and earth fault currents.

Available operation functions:

Measurement of the average, instantaneous or maximum currents, phases


and earth fault current.
Control of the operation of the circuit breaker by monitoring of the closings and
tripping.
Logical selectivity functions available on the phase and earth fault Threshold.
Internal relay NO/NC selectivity function.
The relay controlling following two reset function.
 Hand reset.
 Self reset.

5.2.1. Non-Directional Over Current Protection I>, I>> (50/ 51)

The three phase over current unit comprises adjustable over current stages,
i.e. I>, I>>
Stage I> can be configured for definite time or inverse time operation
characteristic.
Stage I>> have definite time characteristic.

Stelmec Limited | Over Current and Earth Fault Relay 13


USER MANUAL SLR140

Figure 5.2.1 shows the fundamental block diagram of stage I>

Parameters of the Over Current Stages I>, I>> (50/ 51)

Parameter: Value/unit:
Measured value IL A Max. Value of phase currents L1, L2, L3
secondary values.
IL Setting I>, I>> A Setting value in % units
I>, I>> In Setting value as per unit value. setting done in x In
Curves NI, VI, EI, LTI, 3S, Operation character/ inverse time (I>)
1.3S, 0.6S Curve
DT Operation character/ definite time (I>)
t> S Operation time at IDMT (I>)
t>> S Operation time at Definite time (I>>)
k Time multiplier at inverse time (I>)

When the over current exceeds the low-set I> setting value, the over current low-set
element starts and delivers a start signal to the display panel and a group of pre
assigned relay outputs. After a delay time, determined by the inverse time current
characteristics curve selected and the measured current, this over current element
operates and delivers trip signal to the display panel and a group of relay outputs that
are configured to link to the low-set over current tripping.
When the over current exceeds the high-set I>> setting value, the over current high-

Stelmec Limited | Over Current and Earth Fault Relay 14


USER MANUAL SLR140

set element starts and delivers a start signal to the display panel and a group of pre
assigned relay outputs. After a preset time determined by I>> delay, instantaneous
over current element operates and a group of relay outputs that are configured to link
to high-set over current tripping.

The low set stage (I>) of the over current unit can be confirmed for inverse current
characteristics. Seven sets of characteristics curves according to IEC 60255 are available
for the low set stage. i.e. ‘Normal Inverse’ (NI), ‘Very Inverse’ (VI), ‘Extremely Inverse’
(EI), ‘Long Time Inverse’ (LTI), ‘3S’ Curve, ‘1.3S’ Curve and ‘0.6S’ curve.

5.2.2. Non-Directional Earth Fault Protection (50N/ 51N)

One earth fault current unit comprises adjustable earth fault current stages,
i.e. Io>, Io>>
Stage Io> can be configured for definite time or inverse time operation
characteristic.
Stage Io>> have definite time characteristic.

Figure shows the fundamental block diagram of stage Io>.

Stelmec Limited | Over Current and Earth Fault Relay 15


USER MANUAL SLR140

Parameters of the Earth Fault Stages Io>, Io>> (50N/ 51N)

Parameter: Value/ Unit:


Measured value Io A Max. Value of phase currents Lo secondary values.
Io>, Io>> A Setting value in % units
Io>, Io>> In Setting value as per unit value. setting done in x In
NI, VI, EI, LTI,
3S, 1.3S, 0.6S Operation character/ inverse time (Io>)
Curves
Io Setting Curve
DT Operation character/ definite time (Io>)
to> S Operation time at IDMT (Io>)
to>> S Operation time at Definite time (Io>>)
k Time multiplier at inverse time (Io>)

When the earth fault current exceeds the low-set Io> setting value, the earth fault
low-set element starts and delivers a start signal to the display panel and a group of
pre assigned relay outputs. After a delay time, determined by the inverse time
current characteristics curve selected and the measured current, this earth-fault
element operates and delivers trip signal to the display panel and a group of relay
outputs that are configured to link to the low-set earth-fault tripping.

When the earth fault current exceeds the high-set Io>> setting value, the earth fault
High-set element starts and delivers a start signal to the display panel and a group of
pre assigned relay outputs. After a preset time determined by Io>> delay,
instantaneous earth fault element operates and a group of relay outputs that are
configured to link to high-set earth fault tripping.

5.2.3. Circuit Breaker Failure Protection (50BF)

The operation of the circuit breaker failure protection is based on the supervision of
the operating time, from the pickup of the configured trip relay to the dropout of the
same relay.

If that time is longer than the operating time of the CBFP stage, the CBFP stage
activates another output relay, which will remain activated, until the primary trip
relay resets.

The CBFP stage functions also in earth fault situations, because its function is merely
based on supervision of the function of the output trip relay .

Stelmec Limited | Over Current and Earth Fault Relay 16


USER MANUAL SLR140

The CBFP blocking signal prevents the CBFP stage from operating, when the
Output relays or any other protection function is operated by forced control.
This protection feature allows the relay to trip the upstream circuit breaker when a
local breaker failure condition is detected.

5.2.4. Self Supervision

The function of the micro controller and the associated circuitry as well as the program
execution is supervised by means of a separate watchdog circuit. Besides
supervising the relay the watchdog circuit attempts to restart the micro controller in a
fault situation. If the restarting fails, the watchdog issues a self-supervision alarm
because of a permanent relay fault.

When the RTC or EPROM fail is detected the Inservice LED is permanent ON and
any assign output relay for Self supervision will be high.

5.2.5. Auto-Recloser

Introduction
In electric power distribution, an auto reclosing is a circuit breaker equipped with a
mechanism that can automatically close the breaker after it has been opened due to a fault.

Auto reclosing are used in coordinated protection schemes for overhead line power
distribution circuits. These circuits are prone to transitory faults such as nearby lightning

Stelmec Limited | Over Current and Earth Fault Relay 17


USER MANUAL SLR140

strikes, wind-borne debris, animals climbing the insulators, and the likes. With a
conventional circuit breaker or fuse, a transient fault would open the breaker or blow the
fuse, disabling the line until a technician could manually close the circuit breaker or
replace the blown fuse. But an auto reclosing will make several pre-programmed attempts
to re-energize the line. If the transient fault has cleared, the auto reclosing circuit breaker
will remain closed and normal operation of the power line will resume. If the fault is
some sort of a permanent fault (downed wires, tree branches lying on the wires, etc.) the
auto reclosing will exhaust its pre-programmed attempts to re-energize the line and
remain tripped off until manually commanded to try again. 90% of faults on overhead
power lines are transient and can be cured by auto reclosing. [3] The result is increased
availability of supply.

Basic Requirements

The Auto-reclosing relay should reclose the breakers whenever it is initiated by


protective relay.
The Auto-reclosing relay shouldn’t reclose the breakers if the initiation occurs
during the reclaim time.
For single pole mode, the AR-Relay should only reclose the Breakers for single
Phase to earth fault.
The AR-Relay should never reclose the breaker if,
 No initiation from protective relay e.g. when the breakers are intentionally
opened by people.
 Any of the breaker is not ready; it’s not switched to active.

5.2.6. Cold load pickup (CLP): Avoidance of Circuit Breaker tripping due to initial in-rush

currents at turn-on.
The relay monitors the status of 'NO' contact of CB and starts cold load time delay, 'CLP
delay'. During this time the relay uses 'CLP I Current setting’, and blocks one or more
stages of over current & earth fault protection function. In result the relay delays the
normal trip function setting for the duration set under 'CLP delay' setting, so as to avoid
CB tripping due to excessive in-rush current occurring upon CB turn-on. Upon
completion of the 'CLP delay' the relay would perform the protection functions as per its
normal OC + EF settings.

Stelmec Limited | Over Current and Earth Fault Relay 18


USER MANUAL SLR140

NOTE: Caution should be exercised while programming the 'CLP delay' and it should
be set at minimum possible value to avoid the persistent fault prevail on the line.
Condition:
As soon as D.I 1 or CB ON is made high, a timer starts and stops as per the set time in
CLP Delay settings.
I1/ I2/ I3/ E Phase current value < CLP I set range value
From the time of D.I.1 or CB ON goes high, if current in all the input is lower than the
CLP set range, then CLP would block the functions such as I>, I>>, Io> and Io>> until
the time delay expires.
If the same current persists after the timer has stopped, then actual fault functions will
take over. After timer has completed, the relay will work in normal mode as usual.
I1/ I2/ I3/E Phase current value > CLP I set range value.
From the time of D.I1 or CB ON goes high, if current in any of the input is higher than
the CLP set range then relay will trip with CLP Fault.

Settings:
System setting ↑ CLP Settings → CLP Range (For Min. % of load/ current setting 10%
to 3200%)
System setting ↑ CLP Settings → CLP Delay ( For setting delay in seconds for the timer
to be active )
System setting ↑ CLP Settings → CLP BLOCK ALL= Yes/ No (If No is selected there
will be option to block individual functions)
System setting ↑ Enable Stages → CLP Enable? = Yes/ No

Stelmec Limited | Over Current and Earth Fault Relay 19


USER MANUAL SLR140

5.2.7. Broken Conductor Detection:

Broken conductors in aerial lines are a type of fault some times very hard to detect in
distribution networks. Traditional approaches to detect broken conductors have been
based on some type of zero current based relaying, but the limitations of such a tradition
are well known. Because of that, in recent years and with the rise of modern
multifunction relays, some hope has been directed towards conventional protection
principles based not on zero currents, but on negative currents.
I1= Positive Phase Sequence
I2= Negative Phase Sequence

If there is any unbalance in the current input/ load and in % is greater than set BC>
range then after the set delay, assigned relay will trip and also LED9 will be glowing.

If there is any unbalance in the current input/ load and in % is greater than set BC>>
range then after the set delay, BC>> fault will occur and assigned relay will trip and also
LED9 & TRIP LED will be glowing.

Settings:
BC> = Alarm
BC>> = Broken Conductor Fault
For BC> setting
System setting ↑ BC> Settings → BC> Range
(For Min. % of load/ current setting 5% to 100%)
System setting ↑ BC>Settings → BC> Delay
( For setting delay in seconds after the fault occurrence to trip relay)
For BC>> setting
System setting ↑ BC>> Settings → BC>> Range (For Min. % of load/ current setting 5%
to 100%)
System setting ↑ BC>> Settings → BC>> Delay
( For setting delay in seconds after the fault occurrence to trip relay)

Stelmec Limited | Over Current and Earth Fault Relay 20


USER MANUAL SLR140

5.2.8. Low Load Condition Detection (IL<)

* D.I 1 or CB ON on X3 should be high


As soon as the current/ Load in all the three CT/ Inputs goes below the set value, the
assigned relay shall trip after set delay time and be latched until the Current/ load
raises above the set value or the D.I1 or CBON is made low.
Settings:
System setting ↑ IL< Settings → IL Range (For Min. % of load/ current setting 5%
to 100%)
System setting ↑ IL< Settings → IL Delay ( For setting delay in seconds after the
fault occurrence to trip relay)
System setting ↑ Enable Stages → IL< Enable? = Yes/ No

5.2.9. Switch on to Fault (SOTF)


As soon as D.I 1 or CB ON on X3 made high, a timer starts and stops as per the set time
in SOTF Delay settings.
From the time of D.I.1 or CB ON goes high, if current in any of the input is higher than the
set Value/ Range, the relay shall trip. After the timer as per the Delay setting has ended and
D.I 1 is still high the function of the relay shall work normally.

Settings:
System setting ↑ SOTF Settings → SOTF Range (For Min. % of load/ current setting
10% to 3200%)

System setting ↑ SOTF Settings → SOTF Delay ( For setting delay in seconds for the
timer to be active )

System setting ↑ Enable Stages → SOTF Enable? = Yes/ No

Stelmec Limited | Over Current and Earth Fault Relay 21


USER MANUAL SLR140

5.3. Two Different Group settings.


Options available are Auto and Manual
Auto Mode: If current/ load is present in all the CT Input or at least any two CT Input,
then Group 1 setting is selected.
If current is present in only one CT input is present or no current input is present, then
Group 2 setting is selected.

Manual Mode: Group selection is based on the user setting through menu.

Settings:
System setting → Group Type = Auto/ Manual
System setting → Group Select = G1/ G2 (For Group selection in Manual mode only)
System setting → Group Disp = G1/ G2 (For changing and viewing the settings of
specific Group)

6. Configuration and Parameter Settings


Default Screen
Primary current:
R :0000 A Y :0000 A
B :0000 A E :0000 A

Secondary current:

R 00.0 A Y 00.0 A
B 00.0 A E 00.0 A

Here the primary and secondary current values can be measure by pressing of
DOWN arrow key.

Available protection stages:


 I>, I>> (IL Setting)
 Io>, Io>> (Io Setting)
 Cold Load Pickup (CLP setting)
 Auto Recloser setting
 Trip circuit supervision (Pre close & Post close)
 DC healthy supervision
 Uo>, Uo>> (NDR setting optional)
 CBFP (CBFP Set)

Stelmec Limited | Over Current and Earth Fault Relay 22


USER MANUAL SLR140

Available other stages:

Digital IP Setting
Digital OP Setting
Enable Stages
Latch relays
Force O/p
Clock
View log

6.1. Principle of Parameter Setting

This example shows how to change the IL Settings. Same as the principle is used to
change other parameters,

 Press the RIGHT key to open the setting level appears on the display.
 Press the UP and DOWN key to change the setting values.
 Press the RIGHT key to return the next submenu.
 Press the UP and DOWN key to change the setting values.
 Press the RESET key to return to the main menu.

Fault event

By long pressing (3sec) the RESET key Fault Log menu the following can be read and set:

 This function views the measured values of the phase current and earth fault Current
where the faults are recorded at the moment of last 999 fault tripping with date and
time.

IL> & IL>> Settings

Via the submenus of the IL Setting menu the following can be read and set:

 I> Set, I> delay, I> curve, t> TMS for Low set characteristics.
 I>> Set and t>> delay for high set characteristics.
 Increase/ decrease the settings values are done by UP/ DOWN keys.

Stelmec Limited | Over Current and Earth Fault Relay 23


USER MANUAL SLR140

Io > &Io >>Settings

Via the submenus of the Io Setting menu the following can be read and set:

 Io> Set, Io> delay, Io> curve, to> TMS for Low set characteristics.
 Io>> Set and Io>> delay for high set characteristics.
 Increase/ decrease the settings values are done by UP/ DOWN keys.

NDR Uo> & Uo>> Settings

Via the submenus of the Uo Setting menu the following can be read and set:

 Uo> Set, Uo> delay, Uo> curve(DT only), Uo> TMS for Low set characteristics.
 Uo>> Set and Uo>> delay for high set characteristics.
 Increase/ decrease the settings values are done by UP/ DOWN keys.

Cold load Pickup Settings

Via the submenus of the CLP Setting menu the following can be read and set:

 CLP I> Set, CLP delay, & Blocking function.


 Increase/ decrease the settings values are done by UP/ DOWN keys

Auto Reclose settings

Via the submenus of the Reclose settings menu the following can be read and set:
 Use reclose Yes/ No
 Dead Time 1, Dead Time 2, Dead Time 3, Dead Time 4,
 Reclaim Time.
 Reclose Pulse Time.
 Lockout Reset Time.
 Increase / decrease the settings values are done by UP/ DOWN keys.

Broken conductor BC> & BC>> Settings

Via the submenus of the BC Setting menu the following can be read and set:

 BC> Set, BC> delay for Low set characteristics.


 BC>> Set and BC>> delay for high set characteristics.
 Increase / decrease the settings values are done by UP/ DOWN keys.

Stelmec Limited | Over Current and Earth Fault Relay 24


USER MANUAL SLR140

Low Load Condition IL< Settings

Via the submenus of the IL Setting menu the following can be read and set:

 IL< Set, IL< delay .


 Increase / decrease the settings values are done by UP/ DOWN keys.

Switch -On to fault SOTF Settings

Via the submenus of the SOTF Setting menu the following can be read and set:

 SOTF > Set, SOTF > delay .


 Increase / decrease the settings values are done by UP/ DOWN keys.

Digital IP Set

Via the submenus of the Digital IP Set menu the following can be read and set:
 Trip circuit Enable: Yes/ No, Trip ckt delay for configuration operation delay time.
 DC Healthy Enable: Yes/ No, DC healthy delay for configuration operation delay
time.
Digital OP Set

Via the submenus of the Digital OP Set menu, all the protection function of output relays
RL1, RL2, RL3, RL4, RL5, and RL6 contacts can be open (ON) or close (OFF).
There are 6 relay outputs that can be programmed to respond the relay start signal, trip
signal, or both the start and trip signals indicator.

I> OP Config.
Low set over current output relay configuration.
I>> OP Config.
High set over current output relay configuration.
Io> OP Config.
Low set earth fault current output relay configuration.
Io>> OP Config.

High set earth fault current output relay configuration.


CBFP OP Config.
Circuit Breaker Failure Protection output relay configuration.
Recloser OP Config.
Recloser output relay configuration.
Stelmec Limited | Over Current and Earth Fault Relay 25
USER MANUAL SLR140

Lockout OP Config
Lock out output relay configuration.
DC Healthy OP Config
DC Healthy output relay configuration
Uo> OP Config
Low set NDR output relay configuration
Uo>> OP Config
High set NDR output relay configuration
Alarm OP Config
Alarm output relay configuration
Self Supervision
Self supervision output relay configuration
BC> OP Config
Broken conductor low set output relay configuration
BC>> OP Config
Broken conductor high set output relay configuration
IL< OP Config
Low load output relay configuration
SOTF OP Config
Switch on to fault output relay configuration
Cold Load Pickup
CLP output relay configuration

Force o/p menu:

Via the submenus of the Force output, all the functional test for output relays and LED’s
are done.

6.2. Enabling and Disabling Protection Functions


Enable Stages

Via the submenus of the Enable Stages menu, all the protection functions can be enabled
(ON) or disabled (OFF)

I> Yes / No
Over current low set stage (I>)
I>> Yes / No
Over current high set stage (I>>)
Io> Yes / No
Earth fault current low set stages (Io>)
Stelmec Limited | Over Current and Earth Fault Relay 26
USER MANUAL SLR140

Io>> Yes / No
Earth fault current high set stages (Io>>)
Uo> Yes / No
NDR low set stage (Uo>)
Uo>> Yes / No
NDR high set stage (Uo>>)
BC> Yes / No
Broken conductor low set stage ( BC>)
BC>> Yes / No
Broken conductor high set stage ( BC>>)
IL< Yes / No
Low load condition stage ( IL<)
SOTF > Yes / No
Switch on to fault stage
Cold load Pickup > Yes / No
Cold load pickup stage

Scaling

Via the submenus of the Scaling menu, the primary and secondary current ratings are
read and set, where the primary current setting having maximum 2000A as well as the
secondary current setting having 1A or 5A

System Setting

Via the submenus of the System setting menu the following can be read and set:

 Setting of date & time.


 RS485 Module configurations Port enables Protocol, and Device ID/Unit ID & Baud
rate selection.

7. Communication

The PC Port is used for on – site parameterization of the relay, for downloading of a
program and for reading relay parameters to a PC. For connection to a PC, one USB port
is available on the front panel of the relay.

7.1. Modbus RS485 Communication

The interface popularly known as RS-485 is an electrical specification for multipoint


systems that use balanced lines. RS-485 is similar to RS-422, but RS-422 allows just one
driver with multiple receivers whereas RS-485 supports multiple drivers and receivers.
Stelmec Limited | Over Current and Earth Fault Relay 27
USER MANUAL SLR140

RS-485 is actually a physical layer specification which allows multiple nodes to be


connected to a differential 2-wire bus. Unlike RS-232 which can be full duplex (transmit
and receive at the same time), RS-485 exchanges must be half duplex. This means there
must be rules about who can talk and when.

RS485 is the most versatile communication standard in the standard series defined by the
EIA, as it performs well on all four points. That is why RS485 is currently a widely used
communication interface in data acquisition and control applications where multiple
nodes communicate with each other.

8. Output Response Curves

8.1. Low Set Characteristics Curves

The inverse definite minimum time (IDMT) characteristics curve in SLR140 with IEC
60255 having seven selectable curves which are following:

8.1.1. Normal Inverse Curve

Stelmec Limited | Over Current and Earth Fault Relay 28


USER MANUAL SLR140

8.1.2. Very Inverse Curve

8.1.3. Extremely Inverse Curve

Stelmec Limited | Over Current and Earth Fault Relay 29


USER MANUAL SLR140

8.1.4. Long Time Inverse Curve

8.1.5. ‘1.3S’ Curve

Stelmec Limited | Over Current and Earth Fault Relay 30


USER MANUAL SLR140

8.1.6. ‘3S’ Curve

8.1.7. ‘0.6S’ Curve

8.2. High Set Characteristics

The high-set is selectable between definite time and instantaneous tripping characteristics.

Stelmec Limited | Over Current and Earth Fault Relay 31


USER MANUAL SLR140

9. Terminal Diagram of SLR140 : 3 O/C and 1 E/F with AR , CLP, SOTF,


Broken conductor along with Two Group Setting.
Terminal DRG. No.: S14CW10005
9.1. Fixed type: Terminal connection diagram

Stelmec Limited | Over Current and Earth Fault Relay 32


USER MANUAL SLR140

10. Protection Stages


10.1. Over Current Protection Stages

A. Over Current Stage I> (50)


Current Setting Range 2% – 400% (step 1%)
Definite Time Characteristic
Operating Time 0.05 – 200.0 S (step 0.01S)
Inverse Time Characteristic
8 Characteristic Curve Sets EI,VI,NI,LTI,3.0 S, 1.3S, 0.6S,
DT
Time Multiplier (TMS) 0.01 – 2.0 in step of 0.005
Resetting Time <60 ms
Resetting Ratio 0.97
Inaccuracy
Operating Time Definite Time ±5% or ±50 ms
Operating Time Inverse Time ±5% or at least ±50 ms

B. Over Current Stage I>> (51)


Current Setting Range 5% – 4000% (step 1%)
Definite Time Characteristic
Operating Time 0.01 – 20.0 S (step 0.01 S)
Resetting Time <60 ms
Resetting Ratio 0.97
Inaccuracy
Starting ±5% of set value
Operating Time ±5% or ±50 ms

10.2. Earth Fault Current Protection

A. Earth Fault Current Stage Io> (50N)


Current Setting Range 2% – 400% (step 1%)
Definite Time Characteristic
Operating Time 0.05 – 200.0 S (step 0.01S)
Inverse Time Characteristic
7Characteristic Curve Sets EI,VI, NI, LTI, 1.3Sec, 3.0Sec,
0.6s, DT
Time Multiplier (TMS) 0.01 – 2.0 in step of 0.005
Resetting Time <60 ms
Resetting Ratio 0.97
Inaccuracy
Starting ±5% of set value

Operating Time Definite Time ±5% or ±50 ms


Operating Time Inverse Time ±5% or at least ±50 ms

Stelmec Limited | Over Current and Earth Fault Relay 33


USER MANUAL SLR140

B. Earth Fault Current Stage Io>> (51N)

Current Setting Range 5% – 2000% (step 1%)


Definite Time Characteristic
Operating Time 0.01 – 20.0 S (step 0.01S)
Resetting Time <60 ms
Resetting Ratio 0.97
Inaccuracy
Starting ±5% of set value

Operating Time Definite Time ±5% or ±50 ms

10.3. NDR Protection to block the earth fault protection

Uo > Range 4V to 88V (step 1V)


Uo > DELAY 0.05S to 200S (step 0.01S)
Uo > CURVE DT
Uo > TMS 0.01 to 2 (step 0.005)
Uo >> RANGE 10V to 110V (step 1V)
Uo >> DELAY 0.05S to 3 S (step 0.01S)

10.4. Auto – Recloser Protection

Dead time 0.0S to 500S (step 0.1S)


Dead time 0.0S to 500S (step 0.1S)
Dead time 0.0S to 500S (step 0.1S)
Dead time 0.0S to 500S (step 0.1S)
Close Pulse time 0.2S to 1S (step 0.1S)
Reclaim Time 0.0S to 500 S (step 1S)
Lockout 0.0S to 500S (step 1S)
Reclose Shots UPTO 4 – (5 Trips)

10.5. Cold load Pickup

Current Setting Range CLP I> 10% – 3200% (step 1%)


Delay 0.01S to 20S (step 0.01S)
Blocking Function ALL,I>,I>>,EF>,EF>>

Stelmec Limited | Over Current and Earth Fault Relay 34


USER MANUAL SLR140

10.6. Broken Conductor

BC Range BC> 5% – 100% (step 1%)


BC> Delay 0.01S to 99.99S (step 0.01S)
BC Range BC>> 5% – 100% (step 1%)
BC>> Delay 0.01S to 99.99S (step 0.01S)

10.7. Low Load Detection

Low load Range IL< 5% – 100% (step 1%)


IL< Delay 0.01S to 99.99S (step 0.01S)

10.8. Switch-on to Fault

SOTF Range 10% – 3200% (step 1%)


SOTF Delay 0.01S to 99.99S (step 0.01S)

11. Technical Data


11.1. Auxiliary voltage

Supply Voltage 18~135V AC/DC or 85~2650 V AC/ DC


Supply Frequency 50Hz
VA Rating 3 VA Typical
Typical Burden 8W (For Non-Operating Relay)
Maximum Burden <12 W (For Operating Relay)
Power Of Withstand 20ms

11.2. Digital Input voltage sensing threshold

Rated Aux. Supply Voltage 24/ 30 / 48 / 110 / 220V DC

Sensing Threshold Less than 50% of the rated aux. supply


Current drain Less than 2 mA

Stelmec Limited | Over Current and Earth Fault Relay 35


USER MANUAL SLR140

11.3. Current Inputs

CT Inputs Phase 1A/5A Characteristics


Range Of Measurement 0.03 In to 24 In
Burden At In <0.2 VA @ 5A CT & <0.1 VA @ 1A CT
Permanent Thermal Withstand 3 In
1 Sec Thermal Withstand 100 In
Dynamic Withstand (1/2 Cycle) 250 In

Earth-fault CT Input1A/5A Characteristics


Range Of Measurement 0.03 In to 24 In
Burden At In <0.2 VA @ 5A CT & <0.1 VA @ 1A CT
Permanent Thermal Withstand 3 In
1 Sec Thermal Withstand 100 In

11.3. Trip Contacts (T1 & T2)

Number Of Contacts 2 Making Contacts


Rated Voltage 250V AC
Continuous Carry 15A
Max. Making Current 30A
Breaking Capacity, AC 2000 W/VA
Breaking Capacity, DC (L/R = 40ms) 50W
Contact Material AgNi 90/ 10

11.4. Accuracy

Protection Thresholds : ±5%


Time Delay : ± 5 % with a Minimum of 50 ms
Measurements : ±5%

Stelmec Limited | Over Current and Earth Fault Relay 36


USER MANUAL SLR140

12. Construction
12.1. Mechanical

Mounting : Panel Mounting


Front Panel (WxHxD) : 135 mm x 181mm x 182mm
Approximate Weight : 1.75 kg.

12.2. Dimensional Drawing

Stelmec Limited | Over Current and Earth Fault Relay 37


USER MANUAL SLR140

13. Commissioning

Before the commissioning of the relay, it is necessary to check that the following:

 The current transformer’s secondary rated current in conformity with the


rating mentioned on the relay label.
 Wiring is in conformity with the connection diagram.
 Auxiliary supply should be match with the auxiliary supply range of the relay
label
 Tripping circuit is OK

Revision History:

Rev. No. with Date Brief description of Revision


R0 First release
R1 Unit ID
10/04/2016 Baud rate selection
Reset Delay
Low load detection
Broken conductor detection
Switch on to Fault
Cold load Pickup

Stelmec Limited | Over Current and Earth Fault Relay 38


USER MANUAL SLR140

15. Contact Information

STELMEC LIMITED

MUMBAI INDIA.

TEL: +91-250-6519997 /
6454150.
E-mail:
relay@stelmec.com
Visit Us At:
www.stelmec.com

Stelmec Limited | Over Current and Earth Fault Relay 39

S-ar putea să vă placă și