Sunteți pe pagina 1din 5

SEC # 8113010

Size : 3 x 500 mm2 Type : AL/XLPE/STA/PVC


Voltage: 8.7 / 15 (17.5) kV Standard: IEC 60502-2: 2014
Code : AX3-T103-G50-01-00 ELSEWEDY CABLES
Thickness Diameter (Approx.)
Sr. Description
mm mm
1. Aluminum Conductor (Circular Compacted) 26.5
2. Inner Semi-conductor 0.51 (Min.)
3. XLPE Insulation 4.5 (Nom.)
1.02/1.91
4. Outer Semi-conductor (Strippable)
(Min./Max.)
5. Copper Wire Screen 0.67 (Nom.)
6. Copper Tape (Open Helix) 0.1 (Nom.)
7. P.P. Filler
8. Binder Tape
9. PE Bedding 1.64 (Min.)
10. Double Galvanized Steel Tape Armour 0.8 (Nom.)
11. PVC Sheath 3.36 (Min.) 103.9
Drawn by Approved by
Not to Scale
Mr. Usman Eng. Akram M. Abdel Wahab

CR no. 515 C / 2015 – Rev. 0 (Wednesday, August 26, 2015) Technical Department
Saudi Electricity Company
‫الشركة السعودية للكھرباء‬

11-SDMS-03, Rev.02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 01-12-2013

9.0 TECHNICAL DATA SCHEDULE


15 KV TO 36 KV XLPE POWER CABLES
(Sheet 1 of 4)
SEC Inquiry No: C000556027 Item No: 8113010
SEC
SEC VENDOR PROPOSED
DESCRIPTION SPECIFIED
REF VALUES**
VALUES
4.0 DESIGN AND CONSTRUCTION REQUIREMENTS
1. Reference Manufacturing Standard IEC-60502-2 IEC 60502-2:2014
2. Max. Permissible Continuous Conductor Temp (°C) 90 90
3. Maximum Short Circuit Temperature (°C) 250 250
4. Max. Permissible Cont. Temp. of Inner Covering (°C) * 90
5. Max. Permissible Cont. Temp. of Outer Sheath (°C) * 90
U0= 8.7 kV
6. Rated Voltage (kV) 15 kV or 36 kV U=15 kV
Um=17.5 kV
7. Number of Cores 1 or 3 3
8. Conductor Material Cu or Al Aluminum
9. Shape of Conductor Round Round – Compacted
10. Conductor Cross-Section (mm2) As per Inquiry 500 mm2
11. Approximate Diameter of Conductor (mm) * 26.5 mm (Approx.)
12. Number of Strands of Conductor (No) * 61
13. Minimum Thickness of Conductor Shield (mm) * 0.51 mm
14. Insulation Material XLPE XLPE
15. Nominal Thickness of Insulation (mm) As per IEC 4.5 mm
16. Min/Max Thickness of Strippable Semi Conducting
* 1.02 / 1.91 mm
Insulation Shield Material (mm)
17. Diameter Under Insulation Semicon (mm) * 37.1 mm (Approx.)
Number=34
18. No. & Nominal Diameter of Cu Wire Screen (mm) *
Nom. diameter= 0.67 mm
19. Minimum Thickness of Copper Tape and Width (mm) 0.1x15 0.1X15
20. Inner Covering Material PE PE
1.64 mm (Minimum at any
21. Nominal Thickness of Inner Covering (mm) *
point)*
Double Galvanized Steel
22. Armor Type and Thickness (mm) * Tape Armour
Nom. Thickness =0.8 mm
Red, Yellow, Blue
23. Core Identification (Red, Yellow, Blue) Yes
(identifying tapes)
24. Diameter under Inner Covering (mm) * 88.9 mm (Approx.)
25. Filler Material * Non-Hygroscopic filler
26. Outer Sheath Material PVC type ST2 PVC type ST2
27. Diameter under Outer Sheath (mm) * 96.1 mm (Approx.)
3.36 mm (Minimum at
28. Thickness of Outer Sheath (mm) As per IEC
any point)*
* The test of inner covering and outer sheath will be carried out in accordance with IEC 60502-2,
clause 17.5.3.
Saudi Electricity Company
‫الشركة السعودية للكھرباء‬

11-SDMS-03, Rev.02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 01-12-2013

9.0 TECHNICAL DATA SCHEDULE


15 KV TO 36 KV XLPE POWER CABLES
(Sheet 2 of 4)
SEC Inquiry No: C000556027 Item No: 8113010
SEC SEC SPECIFIED VENDOR PROPOSED
REF
DESCRIPTION VALUES VALUES**
15 kV – Red
29. Color of Outer Sheath Red
36 kV – Black
Yes (please refer to
30. Marking Embossed as Specified Yes
below note)
31. Overall Diameter of the Cable (mm) * 103.9 mm (Approx.)
32. Net Weight of Conductor (Kg/Km) * 3942 (-/+)2%
33. Conductor DC Resistance at 20°C (Ohms/Km) * 0.0605
34. Conductor AC Resistance at 90ºC (Ohms/Km) * 0.0817
35. Inductance (mH/Km) * 0.283
36. Capacitance (uF/Km) * 0.5
37. Inductive Reactance (Ohms/Km) * 0.107
38. Capacitive Reactance (Ohms/Km) * 5305.2
39. Conductor Impedance at 90º C (Ohms/Km) R + jX 0.0817 + j 0.107
40. Positive sequence impedance (Ohms/Km) R1 + jXL1 0.0817 + j 0.107
41. Zero sequence impedance (Ohms/Km) R0 + jXL0 1.6884 + J 0.0542
42. Positive sequence charging admittance (S/km) J B1 -J 5.9038
43. Zero sequence charging admittance (S/km) J B0 -J 0.019
44. Zero Sequence Impedance Assuming all Current
in Screens:
R (Ohms / Km) * 1.6884
X (Ohms / Km) * 0.0542
45. Charging Current (Amps/Km) * 1.64
46. Earth Fault Capacitive Current (Amps/Km) * 1.64
47. Short Circuit Rating of Cable based on Maximum
Conductor Operating Temperature (1 Second)
- Conductor (KA) * 46.9
- Screen (KA) * 5.2
48. Conductor Temperature before Short Circuit (0 C) * 90
49. Conductor Temperature at the end of Short Circuit (0C) * 250
0
50. Screen Temperature before Short Circuit ( C) * 80
51. Screen Temperature at the end of Short Circuit (o C) * 250
21 for 15 kV
52. System Short Circuit for one Second (kA)
25 for 36 kV
53. Permissible load in Amps under Maximum Service
* 407**
Conditions given in this Specification (Amp)

** When laid under the following conditions:


Soil Resistivity 2.0 °C.m/W
Burial Depth 0.5 Mt.
Ground Temperature 40 °C
Type of bonding Both ends
Saudi Electricity Company
‫الشركة السعودية للكھرباء‬

11-SDMS-03, Rev.02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 01-12-2013

9.0 TECHNICAL DATA SCHEDULE


15 KV TO 36 KV XLPE POWER CABLES
(Sheet 3 of 4)
SEC Inquiry No: C000556027 Item No: 8113010

SEC SEC SPECIFIED VENDOR PROPOSED


REF
DESCRIPTION VALUES VALUES**
54. Maximum pulling Tension (kN) * 20
55. Maximum side wall press (kN/m) * 12.82
1.56 (Minimum
56. Maximum Bending Radius (m) *
Bending Radius)
57. Meets Strippability requirement of AEIC CS-8 Yes Yes
58. Maximum partial discharge at 1.5 times rated
Yes Yes
voltage, 10 PC
59. Meets Spark Test requirement for jacket Yes Yes
60. Meets all Test requirements of IEC-60502-2 Yes Yes
6.0 PACKING AND SHIPPING
1. Drum Type Returnable Non-Returnable
2. Length of Cable (m) As per Inquiry 500 m (-/+)5%
3. Dimensions (m) * 3.2 m
4. Gross Weight (Kg) * 7265 (Approx.)
5. Net Weight (Kg) * 6125 (Approx.)
6. Marking as per the Specification Yes Yes
8.0 SUBMITTALS
1. All submittals as per the Specification Yes

Note:
1. Drum dimension is not for measure, it is for information only.

2. Cable marking will be in two lines as follows;

ELSEWEDY CABLES KSA 3X500 MM2 8.7/15 kV AL/XLPE/STA/PVC PROPERTY OF


SAUDI ELECTRICITY COMPANY Manufacturing Year

‫ملكية‬ XLPE ‫معزول‬ ‫كابل الومنيوم‬ ‫ كف‬١٥ /٨,٧ ٢‫ مم‬٥٠٠X٣ ‫السويدى للكابالت السعودية‬
‫سنة الصنع بالھجرى‬ ‫الشركة السعودية للكھرباء‬

Note: (*) - Values to be provided/proposed by the Vendor.


(**) - Please provide explanations for deviations, if any.
Saudi Electricity Company
‫الشركة السعودية للكھرباء‬

11-SDMS-03, Rev.02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 01-12-2013

9.0 TECHNICAL DATA SCHEDULE


15 KV TO 36 KV XLPE POWER CABLES
(Sheet 4 of 4)
SEC Inquiry No: C000556027 Item No: 8113010

A) Additional Technical Information or Features Specified by SEC.

B) Additional Supplementary Data or Features Proposed by Bidder/Vendor/Supplier.

C) Other Particulars to be filled-up by the Bidder/Vendor/Supplier.

D) List of Deviations and Clauses to which exception is taken by the


Bidder/Vendor/Supplier.
(Use separate sheet, if necessary).

Manufacturer of
DESCRIPTION Vendor/Supplier
Material/Equipment
Name of Company ELSEWEDY CABLES Co.Ltd

FACTOURY :P.O. BOX 31670 YANBU


Location and Office Address
51000 KSA

Name and Signature of Authorized ENG. AKRAM M. ABDEL WAHAB


Representative with Date 26/08/2015

Official Seal / Stamp