STRUCTURAL DESIGN REPORT

PROJECT: SUBSTATIONS@
AL ZAEEM AIR ACADEMY PROJECT LOCATED AL UDEID ZONE B
STATE OF QATAR

0 03.MAY.2018 A.Z M.H F.M.I FOR APPROVAL


Rev. Date By Check App Revision reason for issue description

CLIENT: CONSULTANT: OWNER:


AL BANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP17210

Project: SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID-ZONE B Sheet: Page I


STRUCTURAL DESIGN REPORT DATE: 03.MAY.2018
Project Name: SUBSTATIONS @ AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID-ZONE B

Project No.: GP 17210

Document - Reference No.:

Issue Purpose: FOR APPROVAL

Discipline: STRUCTURAL

Document Type: DESIGN REPORT

Document Title: STRUCTURAL DESIGNREPORT

Number of Pages: 207

Document Revision
Prepared by Reviewed by Approved by
Control No.

Title STRUCTURAL DESIGN ENGINEER LEAD DESIGN ENGINEER GENERAL MANAGER

Name Ahmad Zidan Mustafa Hesenow FAWZI ISMAIL 1

Signature

Company Authentication:

.........................................................
Stamp

CLIENT: CONSULTANT: OWNER:


AL BANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP17210

Project: SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID-ZONE B Sheet: Page II


STRUCTURAL DESIGN REPORT DATE: 03.MAY.2018
CONTENTS

1.0  INTRODUCTION ............................................................................................................................... 1 
2.0  OBJECTIVE ....................................................................................................................................... 1 
3.0  CODES AND REFERENCES ................................................................................................................. 1 
4.0  MATERIAL PROPERTIES ................................................................................................................... 1 
4.1  CONCRETE ............................................................................................................................................... 1 
4.2  REINFORCEMENT ..................................................................................................................................... 1 
4.3  SOIL ......................................................................................................................................................... 1 
5.0  LOADS AND LOAD COMBINATIONS ................................................................................................. 2 
5.1  DEAD AND LIVE LOADS ............................................................................................................................ 2 
5.1.1  AT GROUND:.................................................................................................................................................................. 2 
5.1.2  AT ROOF LEVEL: ............................................................................................................................................................. 2 
5.2  WIND LOAD ............................................................................................................................................. 2 
5.3  SEISMIC LOADS ........................................................................................................................................ 3 
5.4  LOAD COMBINATIONS ............................................................................................................................. 3 
6.0  DESIGN METHODS ........................................................................................................................... 5 
7.0  DESIGN TOOLS ................................................................................................................................. 5 
8.0  STRUCTURAL SYSTEM ...................................................................................................................... 5 
8.1  INTRODUCTION ....................................................................................................................................... 5 
9.0  STRUCTURAL PROFILE ..................................................................................................................... 6 
10.0  DESIGN OF CONCRETE ELEMENTS .................................................................................................... 8 
10.1  FOUNDATION .......................................................................................................................................... 8 
10.1.1  SOIL BEARING CAPACITY CHECK AT SLS .................................................................................................................. 10 
10.1.2  REINFORCMENT DESIGN OF FOUNDATIONS OF SOG 150 mm ............................................................................... 12 
10.1.3  REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 300 mm ....................................................................... 40 
10.1.4  REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 350+500 mm ............................................................... 53 
10.1.5  REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 600 mm ....................................................................... 57 
10.1.6  REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 750 mm ....................................................................... 68 
10.1.7  REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 850 mm ....................................................................... 79 
10.1.8  REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 1000 mm ..................................................................... 84 
10.1.9  REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 1050/1160/1200/1350 mm ........................................ 89 
10.1.10  REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 1500 mm ..................................................................... 94 
10.2  DESIGN OF REINFORCED CONCRETE SLABS ............................................................................................ 99 
10.2.1  RC ROOF FLOOR AT LEVEL +4.65 UPPER DECK (SLAB THK = 250 MM) ................................................................... 99 
10.2.1.1  DEFLECTION CHECK OF RC SLAB AT SLS ........................................................................................................... 119 
10.3  DESIGN OF REINFORCED CONCRETE BEAMS AT ULS ............................................................................. 123 
10.3.1  RC GB 200x600 SS1 ............................................................................................................................................... 123 

CLIENT: CONSULTANT: OWNER:


AL BANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP17210

Project: SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID-ZONE B Sheet: Page III
STRUCTURAL DESIGN REPORT DATE: 03.MAY.2018
10.3.2  RC GB 200x750 SS1 ............................................................................................................................................... 126 
10.3.3  RC GB 200x600 SS2 ............................................................................................................................................... 129 
10.3.4  RC GB 200x750 SS2 ............................................................................................................................................... 132 
10.3.5  RC GB 200x850 SS3 ............................................................................................................................................... 135 
10.3.6  RC GB 200x1200 SS3 ............................................................................................................................................. 138 
10.3.7  RC GB 200x600 SS4 ............................................................................................................................................... 141 
10.3.8  RC GB 200x750 SS4 ............................................................................................................................................... 144 
10.3.9  RC B 200x600 SS1 .................................................................................................................................................. 147 
10.3.10  RC B400x600 SS1................................................................................................................................................... 150 
10.3.11  RC B800x600 SS1................................................................................................................................................... 153 
10.3.12  RC B 200x600 SS2 .................................................................................................................................................. 156 
10.3.13  RC B 400x600 SS2 .................................................................................................................................................. 159 
10.3.14  RC B 800x600 SS2 .................................................................................................................................................. 162 
10.3.15  RC B 200x600 SS3 .................................................................................................................................................. 165 
10.3.16  RC B 400x600 SS3 .................................................................................................................................................. 168 
10.3.17  RC B 800x500 SS3 .................................................................................................................................................. 171 
10.3.18  RC B 800x600 SS3 .................................................................................................................................................. 174 
10.3.19  RC B 800x700 SS3 .................................................................................................................................................. 177 
10.3.20  RC B 200x600 SS4 .................................................................................................................................................. 180 
10.3.21  RC B 400x600 SS4 .................................................................................................................................................. 183 
10.3.22  RC B 800x600 SS4 .................................................................................................................................................. 186 
10.4  DESIGN OF REINFORCED CONCRETE COLUMNS .................................................................................... 189 
10.4.1  RC C 200x600 Design result SS1 ............................................................................................................................ 191 
10.4.2  RC CL 600x600 Design result ................................................................................................................................. 192 
10.4.3  RC C 600x400 Design result .................................................................................................................................. 193 
10.4.4  RC C 200x800 Design result .................................................................................................................................. 194 
10.4.5  RC C 200x600 Design result SS2 ............................................................................................................................ 195 
10.4.6  RC CL 600x600 Design result ................................................................................................................................. 196 
10.4.7  RC C 600x400 Design result .................................................................................................................................. 197 
10.4.8  RC C 200x800 Design result .................................................................................................................................. 198 
10.4.9  RC C 200x600 Design result SS3 ............................................................................................................................ 199 
10.4.10  RC CL 600x600 Design result ................................................................................................................................. 200 
10.4.11  RC C 600x400 Design result .................................................................................................................................. 201 
10.4.12  RC C 200x800 Design result .................................................................................................................................. 202 
10.4.13  RC C 200x600 Design result SS4 ............................................................................................................................ 203 
10.4.14  RC CL 600x600 Design result ................................................................................................................................. 204 
10.4.15  RC C 600x400 Design result .................................................................................................................................. 205 
10.4.16  RC C 200x800 Design result .................................................................................................................................. 206 

11.0  CONCLUSION ............................................................................................................................... 207 

CLIENT: CONSULTANT: OWNER:


AL BANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP17210

Project: SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID-ZONE B Sheet: Page IV


STRUCTURAL DESIGN REPORT DATE: 03.MAY.2018
LIST OF FIGURES
FIGURE 1‐ SS1 ........................................................................................................................................................................................ 6 
FIGURE 2‐ SS2 ........................................................................................................................................................................................ 6 
FIGURE 3‐ SS3 ........................................................................................................................................................................................ 7 
FIGURE 4‐ SS4 ........................................................................................................................................................................................ 7 
FIGURE 5‐ SS1 FOUNDATIONS LAYOUT ........................................................................................................................................................ 8 
FIGURE 6‐ SS2 FOUNDATIONS LAYOUT ........................................................................................................................................................ 8 
FIGURE 7‐ SS3 FOUNDATIONS LAYOUT ........................................................................................................................................................ 9 
FIGURE 8‐ SS4 FOUNDATIONS LAYOUT ........................................................................................................................................................ 9 
FIGURE 9‐SS1 SOIL REACTIONS DUE TO SLS (ENVELOPE) .............................................................................................................................. 10 
FIGURE 10‐SS2 SOIL REACTIONS DUE TO SLS (ENVELOPE) ............................................................................................................................ 10 
FIGURE 11‐SS3 SOIL REACTIONS DUE TO SLS (ENVELOPE) ............................................................................................................................ 11 
FIGURE 12‐SS4 SOIL REACTIONS DUE TO SLS (ENVELOPE) ............................................................................................................................ 11 
FIGURE 13: SS1 SOG 150  LOCATION ....................................................................................................................................................... 12 
FIGURE 14‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 150 ............................................................................................................ 13 
FIGURE 15‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 150 ............................................................................................................ 13 
FIGURE 16‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 150 ...................................................................................................... 14 
FIGURE 17‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 150 ...................................................................................................... 14 
FIGURE 18: SS2 SOG 150  LOCATION ....................................................................................................................................................... 15 
FIGURE 19‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 150 ............................................................................................................ 16 
FIGURE 20‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 150 ............................................................................................................ 16 
FIGURE 21‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 150 ...................................................................................................... 17 
FIGURE 22‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 150 ...................................................................................................... 17 
FIGURE 23: SS3 SOG 150  LOCATION ....................................................................................................................................................... 18 
FIGURE 24‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 150 ............................................................................................................ 19 
FIGURE 25‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 150 ............................................................................................................ 19 
FIGURE 26‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 150 ...................................................................................................... 20 
FIGURE 27‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 150 ...................................................................................................... 20 
FIGURE 28: SS4 SOG 150  LOCATION ....................................................................................................................................................... 21 
FIGURE 29‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 150 ............................................................................................................ 22 
FIGURE 30‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 150 ............................................................................................................ 22 
FIGURE 31‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 150 ...................................................................................................... 23 
FIGURE 32‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 150 ...................................................................................................... 23 
FIGURE 33: SS1 SOG 200  LOCATION ....................................................................................................................................................... 26 
FIGURE 34‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 200 ............................................................................................................ 27 
FIGURE 35‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 200 ............................................................................................................ 27 
FIGURE 36‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 200 ...................................................................................................... 28 
FIGURE 37‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 200 ...................................................................................................... 28 
FIGURE 38: SS2 SOG 200  LOCATION ....................................................................................................................................................... 29 
FIGURE 39‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 200 ............................................................................................................ 30 
FIGURE 40‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 200 ............................................................................................................ 30 
FIGURE 41‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 200 ...................................................................................................... 31 
FIGURE 42‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 200 ...................................................................................................... 31 
FIGURE 43: SS3 SOG 200  LOCATION ....................................................................................................................................................... 32 
FIGURE 44‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 200 ............................................................................................................ 33 
FIGURE 45‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 200 ............................................................................................................ 33 
FIGURE 46‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 200 ...................................................................................................... 34 
FIGURE 47‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 200 ...................................................................................................... 34 
FIGURE 48: SS4 SOG 200  LOCATION ....................................................................................................................................................... 35 
FIGURE 49- TOP REINFORCEMENT IN X DIRECTION AT ULS- SOG 200 ........................................................................................ 36 
FIGURE 50‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 200 ............................................................................................................ 36 
FIGURE 51‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ SOG 200 ...................................................................................................... 37 

CLIENT: CONSULTANT: OWNER:


AL BANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP17210

Project: SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID-ZONE B Sheet: Page V


STRUCTURAL DESIGN REPORT DATE: 03.MAY.2018
FIGURE 52‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ SOG 200 ...................................................................................................... 37 
FIGURE 53:SS1 THICKENING 300MM LOCATION ......................................................................................................................................... 40 
FIGURE 54‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 300 ................................................................................................................. 41 
FIGURE 55‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 300 ................................................................................................................. 41 
FIGURE 56‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 300 ........................................................................................................... 42 
FIGURE 57‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 300 ........................................................................................................... 42 
FIGURE 58:SS2 THICKENING 300MM LOCATION ......................................................................................................................................... 43 
FIGURE 59‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 300 ................................................................................................................. 44 
FIGURE 60‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 300 ................................................................................................................. 44 
FIGURE 61‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 300 ........................................................................................................... 45 
FIGURE 62‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 300 ........................................................................................................... 45 
FIGURE 63:SS3 THICKENING 300MM LOCATION ......................................................................................................................................... 46 
FIGURE 64‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 300 ................................................................................................................. 47 
FIGURE 65‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 300 ................................................................................................................. 47 
FIGURE 66‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 300 ........................................................................................................... 48 
FIGURE 67‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 300 ........................................................................................................... 48 
FIGURE 68:SS3 THICKENING 300MM LOCATION ............................................................................................................................. 49 
FIGURE 69‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 300 ................................................................................................................. 50 
FIGURE 70‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 300 ................................................................................................................. 50 
FIGURE 71‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 300 ........................................................................................................... 51 
FIGURE 72‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 300 ........................................................................................................... 51 
FIGURE 69‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 350+500 ......................................................................................................... 53 
FIGURE 70‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 350+500 ......................................................................................................... 53 
FIGURE 71‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 350+500 ................................................................................................... 54 
FIGURE 72‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 350+500 ................................................................................................... 54 
FIGURE 73:SS1 THICKENING 600 MM  LOCATION ........................................................................................................................................ 57 
FIGURE 74‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 600 ................................................................................................................. 58 
FIGURE 75‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 600 ................................................................................................................. 58 
FIGURE 76‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 600 ........................................................................................................... 59 
FIGURE 77‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 600 ........................................................................................................... 59 
FIGURE 78:SS2 THICKENING 600 MM  LOCATION ........................................................................................................................................ 60 
FIGURE 79‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 600 ................................................................................................................. 61 
FIGURE 80‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 600 ................................................................................................................. 61 
FIGURE 81‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 600 ........................................................................................................... 62 
FIGURE 82‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 600 ........................................................................................................... 62 
FIGURE 83:SS4 THICKENING 600 MM  LOCATION ........................................................................................................................................ 63 
FIGURE 84‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 600 ................................................................................................................. 64 
FIGURE 85‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 600 ................................................................................................................. 64 
FIGURE 86‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 600 ........................................................................................................... 65 
FIGURE 87‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 600 ........................................................................................................... 65 
FIGURE 88:SS1 THICKENING 750 MM  LOCATION ........................................................................................................................................ 68 
FIGURE 89‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 750 ................................................................................................................. 69 
FIGURE 90‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 750 ................................................................................................................. 69 
FIGURE 91‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 750 ........................................................................................................... 70 
FIGURE 92‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 750 ........................................................................................................... 70 
FIGURE 93:SS2 THICKENING 750 MM  LOCATION ........................................................................................................................................ 71 
FIGURE 94‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 750 ................................................................................................................. 72 
FIGURE 95‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 750 ................................................................................................................. 72 
FIGURE 96‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 750 ........................................................................................................... 73 
FIGURE 97‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 750 ........................................................................................................... 73 
FIGURE 98:SS4 THICKENING 750 MM  LOCATION ........................................................................................................................................ 74 
FIGURE 99‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 750 ................................................................................................................. 75 
FIGURE 100‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 750 ............................................................................................................... 75 
CLIENT: CONSULTANT: OWNER:
AL BANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP17210

Project: SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID-ZONE B Sheet: Page VI


STRUCTURAL DESIGN REPORT DATE: 03.MAY.2018
FIGURE 101‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 750 ......................................................................................................... 76 
FIGURE 102‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 750 ......................................................................................................... 76 
FIGURE 103:SS3 THICKENING 850 MM  LOCATION ...................................................................................................................................... 79 
FIGURE 104‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 850 ............................................................................................................... 80 
FIGURE 105‐ TOP REINFORCEMENT IN Y DIRECTION AT ULS‐ F 850 ............................................................................................................... 80 
FIGURE 106‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 850 ......................................................................................................... 81 
FIGURE 107‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 850 ......................................................................................................... 81 
FIGURE 108:SS3 THICKENING 1000 MM  LOCATION .................................................................................................................................... 84 
FIGURE 109‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 1000 ............................................................................................................. 85 
FIGURE 110- TOP REINFORCEMENT IN Y DIRECTION AT ULS- F 1000 .......................................................................................... 85 
FIGURE 111‐ BOTTOM REINFORCEMENT IN X DIRECTION AT ULS‐ F 1000 ....................................................................................................... 86 
FIGURE 112‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F 1000 ....................................................................................................... 86 
FIGURE 113:SS3 THICKENING 1050/1160/1200/1350 MM  LOCATION ....................................................................................................... 89 
FIGURE 114‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 1050/1160/1200/1350 ................................................................................. 90 
FIGURE 115- TOP REINFORCEMENT IN Y DIRECTION AT ULS- F1050/1160/1200/1350 ............................................................. 90 
FIGURE 116- BOTTOM REINFORCEMENT IN X DIRECTION AT ULS- F1050/1160/1200/1350 ...................................................... 91 
FIGURE 117‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F1050/1160/1200/1350 ........................................................................ 91 
FIGURE 118:SS3 THICKENING 1500 MM  LOCATION .................................................................................................................................... 94 
FIGURE 119‐ TOP REINFORCEMENT IN X DIRECTION AT ULS‐ F 1500 ............................................................................................................. 95 
FIGURE 120- TOP REINFORCEMENT IN Y DIRECTION AT ULS- F1500........................................................................................... 95 
FIGURE 121- BOTTOM REINFORCEMENT IN X DIRECTION AT ULS- F1500 ................................................................................... 96 
FIGURE 122‐ BOTTOM REINFORCEMENT IN Y DIRECTION AT ULS‐ F1500 ...................................................................................................... 96 
FIGURE 123‐ 250 MM RC SLAB OF SS1 ..................................................................................................................................................... 99 
FIGURE 124‐TOP REINFORCEMENT IN X DIRECTION ( ULS ENVELOPE) ........................................................................................................... 100 
FIGURE 125‐TOP REINFORCEMENT IN Y DIRECTION ( ULS ENVELOPE) ........................................................................................................... 100 
FIGURE 126‐BOTTOM REINFORCEMENT IN X DIRECTION ( ULS ENVELOPE) .................................................................................................... 101 
FIGURE 127‐BOTTOM REINFORCEMENT IN Y DIRECTION ( ULS ENVELOPE) .................................................................................................... 101 
FIGURE 128‐ 250 MM RC SLAB OF SS2 ................................................................................................................................................... 104 
FIGURE 129‐TOP REINFORCEMENT IN X DIRECTION ( ULS ENVELOPE) ........................................................................................................... 105 
FIGURE 130‐TOP REINFORCEMENT IN Y DIRECTION ( ULS ENVELOPE) ........................................................................................................... 105 
FIGURE 131‐BOTTOM REINFORCEMENT IN X DIRECTION ( ULS ENVELOPE) .................................................................................................... 106 
FIGURE 132‐BOTTOM REINFORCEMENT IN Y DIRECTION ( ULS ENVELOPE) .................................................................................................... 106 
FIGURE 133‐ 250 MM RC SLAB OF SS3 ................................................................................................................................................... 109 
FIGURE 134‐TOP REINFORCEMENT IN X DIRECTION ( ULS ENVELOPE) ........................................................................................................... 110 
FIGURE 135‐TOP REINFORCEMENT IN Y DIRECTION ( ULS ENVELOPE) ........................................................................................................... 110 
FIGURE 136‐BOTTOM REINFORCEMENT IN X DIRECTION ( ULS ENVELOPE) .................................................................................................... 111 
FIGURE 137‐BOTTOM REINFORCEMENT IN Y DIRECTION ( ULS ENVELOPE) .................................................................................................... 111 
FIGURE 138‐ 250 MM RC SLAB OF SS4 ................................................................................................................................................... 114 
FIGURE 139‐TOP REINFORCEMENT IN X DIRECTION ( ULS ENVELOPE) ........................................................................................................... 115 
FIGURE 140‐TOP REINFORCEMENT IN Y DIRECTION ( ULS ENVELOPE) ........................................................................................................... 115 
FIGURE 141‐BOTTOM REINFORCEMENT IN X DIRECTION ( ULS ENVELOPE) .................................................................................................... 116 
FIGURE 142‐BOTTOM REINFORCEMENT IN Y DIRECTION ( ULS ENVELOPE) .................................................................................................... 116 
FIGURE 143‐ IMMEDIATE DEFLECTION OF RC SLABS 250 MM  (SLS ENVELOPE) .............................................................................................. 119 
FIGURE 144‐ IMMEDIATE DEFLECTION OF RC SLABS 250 MM  (SLS ENVELOPE) .............................................................................................. 120 
FIGURE 145‐ IMMEDIATE DEFLECTION OF RC SLABS 250 MM  (SLS ENVELOPE) .............................................................................................. 121 
FIGURE 146‐ IMMEDIATE DEFLECTION OF RC SLABS 250 MM  (SLS ENVELOPE) .............................................................................................. 122 
FIGURE 147‐ INTERNAL FORCES ENVELOPE AT ULS – GB 200X600 .............................................................................................................. 123 
FIGURE 148‐ INTERNAL FORCES ENVELOPE AT ULS – GB 200X750 .............................................................................................................. 126 
FIGURE 149‐ INTERNAL FORCES ENVELOPE AT ULS – GB 200X600 .............................................................................................................. 129 
FIGURE 150‐ INTERNAL FORCES ENVELOPE AT ULS – GB 200X750 .............................................................................................................. 132 
FIGURE 151‐ INTERNAL FORCES ENVELOPE AT ULS – GB 200X850 .............................................................................................................. 135 
FIGURE 152‐ INTERNAL FORCES ENVELOPE AT ULS – GB 200X1200 ............................................................................................................ 138 
FIGURE 153‐ INTERNAL FORCES ENVELOPE AT ULS – GB 200X600 .............................................................................................................. 141 
CLIENT: CONSULTANT: OWNER:
AL BANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP17210

Project: SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID-ZONE B Sheet: Page VII
STRUCTURAL DESIGN REPORT DATE: 03.MAY.2018
FIGURE 154‐ INTERNAL FORCES ENVELOPE AT ULS – GB 200X750 .............................................................................................................. 144 
FIGURE 155‐ INTERNAL FORCES ENVELOPE AT ULS – B 200X600 ................................................................................................................ 147 
FIGURE 156‐ INTERNAL FORCES ENVELOPE AT ULS – B 400X600 ................................................................................................................ 150 
FIGURE 157‐ INTERNAL FORCES ENVELOPE AT ULS – B 800X600 ................................................................................................................ 153 
FIGURE 158‐ INTERNAL FORCES ENVELOPE AT ULS – B 200X600 ................................................................................................................ 156 
FIGURE 159‐ INTERNAL FORCES ENVELOPE AT ULS – B 400X600 ................................................................................................................ 159 
FIGURE 160‐ INTERNAL FORCES ENVELOPE AT ULS – B 800X600 ................................................................................................................ 162 
FIGURE 161‐ INTERNAL FORCES ENVELOPE AT ULS – B 200X600 ................................................................................................................ 165 
FIGURE 162‐ INTERNAL FORCES ENVELOPE AT ULS – B 400X600 ................................................................................................................ 168 
FIGURE 163‐ INTERNAL FORCES ENVELOPE AT ULS – B 800X500 ................................................................................................................ 171 
FIGURE 164‐ INTERNAL FORCES ENVELOPE AT ULS – B 800X600 ................................................................................................................ 174 
FIGURE 165‐ INTERNAL FORCES ENVELOPE AT ULS – B 800X700 ................................................................................................................ 177 
FIGURE 166‐ INTERNAL FORCES ENVELOPE AT ULS – B 200X600 ................................................................................................................ 180 
FIGURE 167‐ INTERNAL FORCES ENVELOPE AT ULS – B 400X600 ................................................................................................................ 183 
FIGURE 168‐ INTERNAL FORCES ENVELOPE AT ULS – B 800X600 ................................................................................................................ 186 
FIGURE 169‐ SS1 COLUMNS SETTING LAYOUT .......................................................................................................................................... 189 
FIGURE 170‐ SS2 COLUMNS SETTING LAYOUT .......................................................................................................................................... 189 
FIGURE 171‐ SS3 COLUMNS SETTING LAYOUT .......................................................................................................................................... 190 
FIGURE 172‐ SS4 COLUMNS SETTING LAYOUT .......................................................................................................................................... 190 
FIGURE 173‐COLUMNS FORCES ‐ C (200X600) ........................................................................................................................................ 191 
FIGURE 174‐COLUMNS REINFORCEMENT ‐ C (200X600) ........................................................................................................................... 191 
FIGURE 175‐COLUMNS FORCES ‐ CL (600X600) ...................................................................................................................................... 192 
FIGURE 176‐COLUMNS REINFORCEMENT ‐ CL (600X600) .......................................................................................................................... 192 
FIGURE 177‐COLUMNS FORCES ‐ C (600X400) ........................................................................................................................................ 193 
FIGURE 178‐COLUMNS REINFORCEMENT ‐ C (600X400) ........................................................................................................................... 193 
FIGURE 179‐COLUMNS FORCES ‐ C (200X800) ........................................................................................................................................ 194 
FIGURE 180‐COLUMNS REINFORCEMENT ‐ C (200X800) ........................................................................................................................... 194 
FIGURE 181‐COLUMNS FORCES ‐ C (200X600) ........................................................................................................................................ 195 
FIGURE 182‐COLUMNS REINFORCEMENT ‐ C (200X600) ........................................................................................................................... 195 
FIGURE 183‐COLUMNS FORCES ‐ CL (600X600) ...................................................................................................................................... 196 
FIGURE 184‐COLUMNS REINFORCEMENT ‐ CL (600X600) .......................................................................................................................... 196 
FIGURE 185‐COLUMNS FORCES ‐ C (600X400) ........................................................................................................................................ 197 
FIGURE 186‐COLUMNS REINFORCEMENT ‐ C (600X400) ........................................................................................................................... 197 
FIGURE 187‐COLUMNS FORCES ‐ C (200X800) ........................................................................................................................................ 198 
FIGURE 188‐COLUMNS REINFORCEMENT ‐ C (200X800) ........................................................................................................................... 198 
FIGURE 189‐COLUMNS FORCES ‐ C (200X600) ........................................................................................................................................ 199 
FIGURE 190‐COLUMNS REINFORCEMENT ‐ C (200X600) ........................................................................................................................... 199 
FIGURE 191‐COLUMNS FORCES ‐ CL (600X600) ...................................................................................................................................... 200 
FIGURE 192‐COLUMNS REINFORCEMENT ‐ CL (600X600) .......................................................................................................................... 200 
FIGURE 193‐COLUMNS FORCES ‐ C (600X400) ........................................................................................................................................ 201 
FIGURE 194‐COLUMNS REINFORCEMENT ‐ C (600X400) ........................................................................................................................... 201 
FIGURE 195‐COLUMNS FORCES ‐ C (200X800) ........................................................................................................................................ 202 
FIGURE 196‐COLUMNS REINFORCEMENT ‐ C (200X800) ........................................................................................................................... 202 
FIGURE 197‐COLUMNS FORCES ‐ C (200X600) ........................................................................................................................................ 203 
FIGURE 198‐COLUMNS REINFORCEMENT ‐ C (200X600) ........................................................................................................................... 203 
FIGURE 199‐COLUMNS FORCES ‐ CL (600X600) ...................................................................................................................................... 204 
FIGURE 200‐COLUMNS REINFORCEMENT ‐ CL (600X600) .......................................................................................................................... 204 
FIGURE 201‐COLUMNS FORCES ‐ C (600X400) ........................................................................................................................................ 205 
FIGURE 202‐COLUMNS REINFORCEMENT ‐ C (600X400) ........................................................................................................................... 205 
FIGURE 203‐COLUMNS FORCES ‐ C (200X800) ........................................................................................................................................ 206 
FIGURE 204‐COLUMNS REINFORCEMENT ‐ C (200X800) ........................................................................................................................... 206 

CLIENT: CONSULTANT: OWNER:


AL BANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP17210

Project: SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID-ZONE B Sheet: Page VIII
STRUCTURAL DESIGN REPORT DATE: 03.MAY.2018
1.0 INTRODUCTION
MZP W.L.L has been assigned by AL BANDARY ENGINEERING Trading & Contracting to
carry out the design of The Substations , part of AL ZAEEM AIR ACADEMY project
located at AL UDEID ( ZONE-B ) - QATAR.

2.0 OBJECTIVE
This report serves as a structural report to provide the structural analysis and design of
The all Substations , part of AL UDEID ( ZONE-B) Project.

3.0 CODES AND REFERENCES


The following codes shall be adopted in the design and analysis of the project:
 Building Code Requirements for Structural Concrete (ACI 318M-14)
 Qatar Constructions Specifications (QCS 2014)
 American Society Of Civil Engineers (ASCE-7 2010)
 International Building Code (IBC 2012)
 Geotechnical Investigation Report (No.SI 17-050).

4.0 MATERIAL PROPERTIES


4.1 CONCRETE
Density γ=25 KN/m3
Cubic Compressive strength fcu = 40MPa for slabs and beams.
Cubic Compressive strength fcu = 50MPa for columns, foundations and walls.

4.2 REINFORCEMENT
Carbon Steel Grade 500 - QASCO specification
Min. Tensile Strength Fu = 740 MPa
Min. Yield Strength Fy = 500 MPa
4.3 SOIL
Modulus of Sub-grade Reaction = 48000 KN/m3
Allowable net Bearing Capacity = 190 KN/m2

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 1


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
5.0 LOADS AND LOAD COMBINATIONS
The self-weight of the entire structures will be calculated automatically by the software
according to the material geometry and density. The preliminary load conditions
determined are as follows:
5.1 DEAD AND LIVE LOADS
5.1.1 AT GROUND:
DEAD LOADS:
 Finishes = 2.50 KN/m2.
 Block wall multiple = 18 kN/m3x height x width.
LIVE LOADS:
 Live load = 10.0 KN/m2.
5.1.2 AT ROOF LEVEL:
DEAD LOADS:
 Superimposed Dead Load = 5.0 KN/m2.
LIVE LOADS:
 Live Load (non-accessible roof) = 1.0 KN/m2.
5.2 WIND LOAD
 Risk Category II (see Table 1.5-1 / ASCE 7-10).
 Basic Wind Speed = 38 m/s corresponding to ASCE 7-05. As per ASCE 7-10 and QCS
2014, V = 38/√0.6 = 49 m/s
 Exposure Category C (see section 26.7.3 / ASCE 7-10)
 Topographic Factor = 1
 Directional Factor = 0.85
 Considering all modifiers for all elements as per ACI-318M-2014 clause 6.6.3.1
→ Velocity pressure qz = 0.613 Kz Kd Kzt V2 = 0.613x 0.85x 1.0x 0.99x492/1000 = 1.24 KN/m2

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 2


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
5.3 SEISMIC LOADS
Peak Ground Acceleration (PGA) = 0.04
0.2 Second Spectral Acceleration (g) Ss = 0.09 (As per QCS 2014)
1.0 Second Spectral Acceleration (g) S1 = 0.045 (As per QCS 2014)
Long Time Period TL = 8 sec.
Importance Factor (I) = 1
Site Soil Classification = C
Response modification coefficient (R) = 3
Over strength factor (Ω) = 3
Deflection Amplification Factor (Cd) = 2.5
Considering all modifiers for all elements as per ACI-318M-2014 clause 6.6.3.1

5.4 LOAD COMBINATIONS


The following formulas shows the various load combination according to ASCE 7-2010.
These combinations shall be adopted for the analysis and design of this project.

Table 1- Load Combinations

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 3


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Loading Legend:

1: Self-weight,
2: Floor cover,
3: partitions,
4: Live load,
5: Roof live load,
6: Wind X+,
7: Wind X-,
8:Wind Y+,
9: Wind Y-,
10: Modal
11: Seismic in X direction,
12: Seismic in Y directions

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 4


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
6.0 DESIGN METHODS
The design of structural elements for the proposed project will be based on the Strength
Design Method (Ultimate Strength Method) using different processes. The design
processes that may be used in the design are as follows:
 Manual methods to generate loads
 Manual methods to define the size of structural elements (Columns, Slabs,
Beams, Walls, etc.)
 Finite element methods to design raft, slabs and walls.

7.0 DESIGN TOOLS


1- Autodesk Robot Structural Analysis 2015
2- Excel Spreadsheets For Structural Design
3- S.Concrete
4- Robot Expert 2010

8.0 STRUCTURAL SYSTEM


8.1 INTRODUCTION
The structural system that has to be adopted should be:
1- Able to transfer and distribute the self-weight of the structure to the underlying soil.
2- Able to transfer and distribute the applied loads such as live, superimposed dead
loads to the underlying soil.
3- Able to resist and transfer the lateral loads (wind & seismic load)
4- Economical
5- Constructible
6- Safe
7- Serviceable
8- Aesthetic

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 5


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
9.0 STRUCTURAL PROFILE

Figure 1- SS1

Figure 2- SS2

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 6


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 3- SS3

Figure 4- SS4

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 7


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.0 DESIGN OF CONCRETE ELEMENTS
10.1 FOUNDATION
The foundation comprises of slab on grade 150mm and varies thickening under the
internal columns and external columns.

Figure 5- SS1 Foundations Layout

Figure 6- SS2 Foundations Layout

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 8


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 7- SS3 Foundations Layout

Figure 8- SS4 Foundations Layout

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 9


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.1.1 SOIL BEARING CAPACITY CHECK AT SLS
Figure below illustrates the soil reactions of the foundations.

The maximum soil reactions is found 155.1 KPa. Allowable bearing capacity is 190 KPa.

Figure 9-SS1 Soil Reactions due to SLS (Envelope)

Figure 10-SS2 Soil Reactions due to SLS (Envelope)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 10


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 11-SS3 Soil Reactions due to SLS (Envelope)

Figure 12-SS4 Soil Reactions due to SLS (Envelope)

Maximum soil stress = 181.88 KN/m2 < 190 KN/m2 ,OK

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 11


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.1.2 REINFORCMENT DESIGN OF FOUNDATIONS OF SOG 150 mm
 Figures below show the top and bottom bending reinforcement in both directions X
and Y with reduction of forces for slab on grade.
 The following moments do not cater for minimum required reinforcement which will be
presented at the end of this section.

Figure 13: SS1 SOG 150 location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 12


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 14- Top Reinforcement in X Direction at ULS- SOG 150

Figure 15- Top Reinforcement in Y Direction at ULS- SOG 150

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 13


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 16- Bottom Reinforcement in X Direction at ULS- SOG 150

Figure 17- Bottom Reinforcement in Y Direction at ULS- SOG 150

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 14


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 18: SS2 SOG 150 location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 15


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 19- Top Reinforcement in X Direction at ULS- SOG 150

Figure 20- Top Reinforcement in Y Direction at ULS- SOG 150

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 16


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 21- Bottom Reinforcement in X Direction at ULS- SOG 150

Figure 22- Bottom Reinforcement in Y Direction at ULS- SOG 150

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 17


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 23: SS3 SOG 150 location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 18


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 24- Top Reinforcement in X Direction at ULS- SOG 150

Figure 25- Top Reinforcement in Y Direction at ULS- SOG 150

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 19


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 26- Bottom Reinforcement in X Direction at ULS- SOG 150

Figure 27- Bottom Reinforcement in Y Direction at ULS- SOG 150

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 20


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 28: SS4 SOG 150 location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 21


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 29- Top Reinforcement in X Direction at ULS- SOG 150

Figure 30- Top Reinforcement in Y Direction at ULS- SOG 150

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 22


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 31- Bottom Reinforcement in X Direction at ULS- SOG 150

Figure 32- Bottom Reinforcement in Y Direction at ULS- SOG 150

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 23


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 10
 Average diam. of top reinf. : 10
2. Section:

b = 1000.00 (mm)
h = 150.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 21.82 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 458.36 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.4 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 21.82 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 9.91 (mm)
Internal forces lever arm: L = 105.79 (mm)
Strains in concrete: b = 1.98 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 24


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 10
 Average diam. of top reinf. : 10
2. Section:

b = 1000.00 (mm)
h = 150.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 31.20 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 667.54 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.6 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 31.20 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 14.44 (mm)
Internal forces lever arm: L = 103.86 (mm)
Strains in concrete: b = 3.00 (‰)
in steel: s = 19.86 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 25


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 33: SS1 SOG 200 location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 26


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 34- Top Reinforcement in X Direction at ULS- SOG 200

Figure 35- Top Reinforcement in Y Direction at ULS- SOG 200

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 27


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 36- Bottom Reinforcement in X Direction at ULS- SOG 200

Figure 37- Bottom Reinforcement in Y Direction at ULS- SOG 200

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 28


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 38: SS2 SOG 200 location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 29


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 39- Top Reinforcement in X Direction at ULS- SOG 200

Figure 40- Top Reinforcement in Y Direction at ULS- SOG 200

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 30


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 41- Bottom Reinforcement in X Direction at ULS- SOG 200

Figure 42- Bottom Reinforcement in Y Direction at ULS- SOG 200

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 31


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 43: SS3 SOG 200 location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 32


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 44- Top Reinforcement in X Direction at ULS- SOG 200

Figure 45- Top Reinforcement in Y Direction at ULS- SOG 200

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 33


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 46- Bottom Reinforcement in X Direction at ULS- SOG 200

Figure 47- Bottom Reinforcement in Y Direction at ULS- SOG 200

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 34


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 48: SS4 SOG 200 location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 35


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 49- Top Reinforcement in X Direction at ULS- SOG 200

Figure 50- Top Reinforcement in Y Direction at ULS- SOG 200

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 36


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 51- Bottom Reinforcement in X Direction at ULS- SOG 200

Figure 52- Bottom Reinforcement in Y Direction at ULS- SOG 200

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 37


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 10
 Average diam. of top reinf. : 10
2. Section:

b = 1000.00 (mm)
h = 200.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 16.20 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 297.85 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 16.20 (kN*m)
Load to resistance ratio: 82.1 %
Neutral axis location: c = 6.44 (mm)
Internal forces lever arm: L = 147.26 (mm)
Strains in concrete: b = 0.90 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 38


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 10
 Average diam. of top reinf. : 10
2. Section:

b = 1000.00 (mm)
h = 200.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 16.66 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 297.85 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 16.66 (kN*m)
Load to resistance ratio: 84.4 %
Neutral axis location: c = 6.44 (mm)
Internal forces lever arm: L = 147.26 (mm)
Strains in concrete: b = 0.90 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 39


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.1.3 REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 300 mm

 Figures below show the top and bottom bending reinforcement in both directions X
and Y with reduction of forces above columns for all type of foundations.
 The following moments do not cater for minimum required reinforcement which will be
presented at the end of this section.

Figure 53:SS1 Thickening 300mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 40


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 54- Top Reinforcement in X Direction at ULS- F 300

Figure 55- Top Reinforcement in Y Direction at ULS- F 300

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 41


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 56- Bottom Reinforcement in X Direction at ULS- F 300

Figure 57- Bottom Reinforcement in Y Direction at ULS- F 300

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 42


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 58:SS2 Thickening 300mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 43


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 59- Top Reinforcement in X Direction at ULS- F 300

Figure 60- Top Reinforcement in Y Direction at ULS- F 300

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 44


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 61- Bottom Reinforcement in X Direction at ULS- F 300

Figure 62- Bottom Reinforcement in Y Direction at ULS- F 300

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 45


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 63:SS3 Thickening 300mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 46


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 64- Top Reinforcement in X Direction at ULS- F 300

Figure 65- Top Reinforcement in Y Direction at ULS- F 300

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 47


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 66- Bottom Reinforcement in X Direction at ULS- F 300

Figure 67- Bottom Reinforcement in Y Direction at ULS- F 300

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 48


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 68:SS3 Thickening 300mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 49


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 69- Top Reinforcement in X Direction at ULS- F 300

Figure 70- Top Reinforcement in Y Direction at ULS- F 300

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 50


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 71- Bottom Reinforcement in X Direction at ULS- F 300

Figure 72- Bottom Reinforcement in Y Direction at ULS- F 300

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 51


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 10
 Average diam. of top reinf. : 10
2. Section:

b = 1000.00 (mm)
h = 300.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 78.66 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 718.16 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 78.66 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 15.53 (mm)
Internal forces lever arm: L = 243.40 (mm)
Strains in concrete: b = 1.32 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 52


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.1.4 REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 350+500 mm

Figure 73- Top Reinforcement in X Direction at ULS- F 350+500

Figure 74- Top Reinforcement in Y Direction at ULS- F 350+500

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 53


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 75- Bottom Reinforcement in X Direction at ULS- F 350+500

Figure 76- Bottom Reinforcement in Y Direction at ULS- F 350+500

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 54


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 350.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 108.00 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 820.63 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 108.00 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 17.75 (mm)
Internal forces lever arm: L = 292.46 (mm)
Strains in concrete: b = 1.26 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 55


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 350.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 168.00 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1295.89 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.4 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 168.00 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 28.03 (mm)
Internal forces lever arm: L = 288.09 (mm)
Strains in concrete: b = 2.06 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 56


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.1.5 REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 600 mm
 Figures below show the top and bottom bending reinforcement in both directions X
and Y with reduction of forces above columns for all type of foundations.
 The following moments do not cater for minimum required reinforcement which will be
presented at the end of this section.

Figure 77:SS1 Thickening 600 mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 57


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 78- Top Reinforcement in X Direction at ULS- F 600

Figure 79- Top Reinforcement in Y Direction at ULS- F 600

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 58


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 80- Bottom Reinforcement in X Direction at ULS- F 600

Figure 81- Bottom Reinforcement in Y Direction at ULS- F 600

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 59


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 82:SS2 Thickening 600 mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 60


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 83- Top Reinforcement in X Direction at ULS- F 600

Figure 84- Top Reinforcement in Y Direction at ULS- F 600

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 61


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 85- Bottom Reinforcement in X Direction at ULS- F 600

Figure 86- Bottom Reinforcement in Y Direction at ULS- F 600

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 62


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 87:SS4 Thickening 600 mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 63


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 88- Top Reinforcement in X Direction at ULS- F 600

Figure 89- Top Reinforcement in Y Direction at ULS- F 600

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 64


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 90- Bottom Reinforcement in X Direction at ULS- F 600

Figure 91- Bottom Reinforcement in Y Direction at ULS- F 600

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 65


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 600.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 217.00 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 893.56 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 217.00 (kN*m)
Load to resistance ratio: 99.6 %
Neutral axis location: c = 19.32 (mm)
Internal forces lever arm: L = 541.79 (mm)
Strains in concrete: b = 0.73 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 66


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 600.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 204.10 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 893.56 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 204.10 (kN*m)
Load to resistance ratio: 93.7 %
Neutral axis location: c = 19.32 (mm)
Internal forces lever arm: L = 541.79 (mm)
Strains in concrete: b = 0.73 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 67


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.1.6 REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 750 mm
 Figures below show the top and bottom bending reinforcement in both directions X
and Y with reduction of forces above columns for all type of foundations.
 The following moments do not cater for minimum required reinforcement which will be
presented at the end of this section.

Figure 92:SS1 Thickening 750 mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 68


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 93- Top Reinforcement in X Direction at ULS- F 750

Figure 94- Top Reinforcement in Y Direction at ULS- F 750

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 69


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 95- Bottom Reinforcement in X Direction at ULS- F 750

Figure 96- Bottom Reinforcement in Y Direction at ULS- F 750

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 70


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 97:SS2 Thickening 750 mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 71


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 98- Top Reinforcement in X Direction at ULS- F 750

Figure 99- Top Reinforcement in Y Direction at ULS- F 750

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 72


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 100- Bottom Reinforcement in X Direction at ULS- F 750

Figure 101- Bottom Reinforcement in Y Direction at ULS- F 750

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 73


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 102:SS4 Thickening 750 mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 74


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 103- Top Reinforcement in X Direction at ULS- F 750

Figure 104- Top Reinforcement in Y Direction at ULS- F 750

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 75


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 105- Bottom Reinforcement in X Direction at ULS- F 750

Figure 106- Bottom Reinforcement in Y Direction at ULS- F 750

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 76


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16

2. Section:

b = 1000.00 (mm)
h = 750.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 412.10 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1331.53 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 412.10 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 28.80 (mm)
Internal forces lever arm: L = 687.76 (mm)
Strains in concrete: b = 0.86 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 77


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 750.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)
3. Loads:
Factored bending moment: 530.10 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1721.78 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 530.10 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 37.24 (mm)
Internal forces lever arm: L = 684.17 (mm)
Strains in concrete: b = 1.12 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 78


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.1.7 REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 850 mm

 Figures below show the top and bottom bending reinforcement in both directions X
and Y with reduction of forces above columns for all type of foundations.
 The following moments do not cater for minimum required reinforcement which will be
presented at the end of this section.

Figure 107:SS3 Thickening 850 mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 79


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 108- Top Reinforcement in X Direction at ULS- F 850

Figure 109- Top Reinforcement in Y Direction at ULS- F 850

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 80


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 110- Bottom Reinforcement in X Direction at ULS- F 850

Figure 111- Bottom Reinforcement in Y Direction at ULS- F 850

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 81


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 850.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 190.20 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1265.88 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 190.20 (kN*m)
Neutral axis location: c = 27.38 (mm)
Internal forces lever arm: L = 788.37 (mm)
Strains in concrete: b = 0.71 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa) Safety factor: not significant case

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 82


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 850.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 352.90 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1265.88 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 352.90 (kN*m)
Load to resistance ratio: 78.6 %
Neutral axis location: c = 27.38 (mm)
Internal forces lever arm: L = 788.37 (mm)
Strains in concrete: b = 0.71 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 83


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.1.8 REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 1000 mm

Figure 112:SS3 Thickening 1000 mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 84


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 113- Top Reinforcement in X Direction at ULS- F 1000

Figure 114- Top Reinforcement in Y Direction at ULS- F 1000

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 85


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 115- Bottom Reinforcement in X Direction at ULS- F 1000

Figure 116- Bottom Reinforcement in Y Direction at ULS- F 1000

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 86


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 1000.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 92.30 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1489.27 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 92.30 (kN*m)
Neutral axis location: c = 32.21 (mm)
Internal forces lever arm: L = 936.31 (mm)
Strains in concrete: b = 0.70 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa) Safety factor: not significant case

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 87


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 1000.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 160.73 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1489.27 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 160.73 (kN*m)
Neutral axis location: c = 32.21 (mm)
Internal forces lever arm: L = 936.31 (mm)
Strains in concrete: b = 0.70 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa) Safety factor: not significant case

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 88


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.1.9 REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 1050/1160/1200/1350 mm

Figure 117:SS3 Thickening 1050/1160/1200/1350 mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 89


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 118- Top Reinforcement in X Direction at ULS- F 1050/1160/1200/1350

Figure 119- Top Reinforcement in Y Direction at ULS- F1050/1160/1200/1350

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 90


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 120- Bottom Reinforcement in X Direction at ULS- F1050/1160/1200/1350

Figure 121- Bottom Reinforcement in Y Direction at ULS- F1050/1160/1200/1350

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 91


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 1050.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 400.40 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1563.73 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 400.40 (kN*m)
Load to resistance ratio: 57.7 %
Neutral axis location: c = 33.82 (mm)
Internal forces lever arm: L = 985.63 (mm)
Strains in concrete: b = 0.70 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 92


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 1050.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 759.30 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1714.35 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 759.30 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 37.08 (mm)
Internal forces lever arm: L = 984.24 (mm)
Strains in concrete: b = 0.77 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 93


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.1.10 REINFORCMENT DESIGN OF FOUNDATIONS THICKENING 1500 mm

Figure 122:SS3 Thickening 1500 mm location

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 94


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 123- Top Reinforcement in X Direction at ULS- F 1500

Figure 124- Top Reinforcement in Y Direction at ULS- F1500

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 95


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 125- Bottom Reinforcement in X Direction at ULS- F1500

Figure 126- Bottom Reinforcement in Y Direction at ULS- F1500

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 96


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16

2. Section:

b = 1000.00 (mm)
h = 1500.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 242.10 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 2233.90 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 242.10 (kN*m)
Neutral axis location: c = 48.31 (mm)
Internal forces lever arm: L = 1429.47 (mm)
Strains in concrete: b = 0.69 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa) Safety factor: not significant case

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 97


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 1000.00 (mm)
h = 1500.00 (mm)
ds = 50.00 (mm)
d' = 50.00 (mm)

3. Loads:
Factored bending moment: 242.90 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 2233.90 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 242.90 (kN*m)
Neutral axis location: c = 48.31 (mm)
Internal forces lever arm: L = 1429.47 (mm)
Strains in concrete: b = 0.69 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa) Safety factor: not significant case

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 98


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.2 DESIGN OF REINFORCED CONCRETE SLABS
10.2.1 RC ROOF FLOOR AT LEVEL +4.65 UPPER DECK (SLAB THK = 250 MM)

Figures below illustrate the bending moments maps in x and y directions for the reinforced
concrete slabs with thickness 250 mm of substations.

Figure 127- 250 mm RC slab of SS1

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 99


STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 128-Top Reinforcement In X Direction ( ULS Envelope)

Figure 129-Top Reinforcement In Y Direction ( ULS Envelope)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 100
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 130-Bottom Reinforcement In X Direction ( ULS Envelope)

Figure 131-Bottom Reinforcement In Y Direction ( ULS Envelope)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 101
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 12
2. Section:

b = 1000.00 (mm)
h = 250.00 (mm)
ds = 35.00 (mm)
d' = 35.00 (mm)

3. Loads:
Factored bending moment: 72.35 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 773.37 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.4 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 72.35 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 16.73 (mm)
Internal forces lever arm: L = 207.89 (mm)
Strains in concrete: b = 1.69 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 102
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 12
2. Section:

b = 1000.00 (mm)
h = 250.00 (mm)
ds = 35.00 (mm)
d' = 35.00 (mm)

3. Loads:
Factored bending moment: 40.53 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 439.77 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 40.53 (kN*m)
Load to resistance ratio: 97.1 %
Neutral axis location: c = 9.51 (mm)
Internal forces lever arm: L = 210.96 (mm)
Strains in concrete: b = 0.93 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 103
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 132- 250 mm RC slab of SS2

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 104
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 133-Top Reinforcement In X Direction ( ULS Envelope)

Figure 134-Top Reinforcement In Y Direction ( ULS Envelope)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 105
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 135-Bottom Reinforcement In X Direction ( ULS Envelope)

Figure 136-Bottom Reinforcement In Y Direction ( ULS Envelope)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 106
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 12
2. Section:

b = 1000.00 (mm)
h = 250.00 (mm)
ds = 35.00 (mm)
d' = 35.00 (mm)

3. Loads:
Factored bending moment: 67.00 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 714.32 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 67.00 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 15.45 (mm)
Internal forces lever arm: L = 208.43 (mm)
Strains in concrete: b = 1.55 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 107
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 12
2. Section:

b = 1000.00 (mm)
h = 250.00 (mm)
ds = 35.00 (mm)
d' = 35.00 (mm)

3. Loads:
Factored bending moment: 44.20 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 466.14 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 44.20 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 10.08 (mm)
Internal forces lever arm: L = 210.72 (mm)
Strains in concrete: b = 0.98 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 108
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 137- 250 mm RC slab of SS3

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 109
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 138-Top Reinforcement In X Direction ( ULS Envelope)

Figure 139-Top Reinforcement In Y Direction ( ULS Envelope)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 110
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 140-Bottom Reinforcement In X Direction ( ULS Envelope)

Figure 141-Bottom Reinforcement In Y Direction ( ULS Envelope)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 111
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 12
2. Section:

b = 1000.00 (mm)
h = 250.00 (mm)
ds = 35.00 (mm)
d' = 35.00 (mm)

3. Loads:
Factored bending moment: 109.10 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1187.98 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.6 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 109.10 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 25.69 (mm)
Internal forces lever arm: L = 204.08 (mm)
Strains in concrete: b = 2.71 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 112
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 12
2. Section:

b = 1000.00 (mm)
h = 250.00 (mm)
ds = 35.00 (mm)
d' = 35.00 (mm)

3. Loads:
Factored bending moment: 59.50 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 632.07 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 59.50 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 13.67 (mm)
Internal forces lever arm: L = 209.19 (mm)
Strains in concrete: b = 1.36 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 113
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 142- 250 mm RC slab of SS4

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 114
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 143-Top Reinforcement In X Direction ( ULS Envelope)

Figure 144-Top Reinforcement In Y Direction ( ULS Envelope)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 115
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 145-Bottom Reinforcement In X Direction ( ULS Envelope)

Figure 146-Bottom Reinforcement In Y Direction ( ULS Envelope)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 116
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 12
2. Section:

b = 1000.00 (mm)
h = 250.00 (mm)
ds = 35.00 (mm)
d' = 35.00 (mm)

3. Loads:
Factored bending moment: 75.94 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 813.18 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.4 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 75.94 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 17.59 (mm)
Internal forces lever arm: L = 207.53 (mm)
Strains in concrete: b = 1.78 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 117
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Element type: slab
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 12
2. Section:

b = 1000.00 (mm)
h = 250.00 (mm)
ds = 35.00 (mm)
d' = 35.00 (mm)
3. Loads:
Factored bending moment: 35.70 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 439.77 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.2 (%)
min = 0.2 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 35.70 (kN*m)
Load to resistance ratio: 85.5 %
Neutral axis location: c = 9.51 (mm)
Internal forces lever arm: L = 210.96 (mm)
Strains in concrete: b = 0.93 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 118
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.2.1.1 DEFLECTION CHECK OF RC SLAB AT SLS

Figure 147- Immediate Deflection of RC slabs 250 mm (SLS Envelope)

Long-term deflection of RC slab can be considered twice the immediate deflection, the long
term deflection of the RC slabs 250 mm is (22.2– 20.1) x 2 = 4.2 mm < allowable L/240 =
4850/240 = 20.2 mm.

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 119
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 148- Immediate Deflection of RC slabs 250 mm (SLS Envelope)

Long-term deflection of RC slab can be considered twice the immediate deflection, the long
term deflection of the RC slabs 250 mm is (23.36– 21.2) x 2 = 4.32 mm < allowable L/240 =
4850/240 = 20.2 mm.

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 120
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 149- Immediate Deflection of RC slabs 250 mm (SLS Envelope)

Long-term deflection of RC slab can be considered twice the immediate deflection, the long
term deflection of the RC slabs 250 mm is (27.6– 24.2) x 2 = 6.8 mm < allowable L/240 =
4400/240 = 18.3 mm.

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 121
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 150- Immediate Deflection of RC slabs 250 mm (SLS Envelope)

Long-term deflection of RC slab can be considered twice the immediate deflection, the long
term deflection of the RC slabs 250 mm is (22.8 – 18.7) x 2 = 8.2 mm < allowable L/240 =
6000/240 = 25 mm.

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 122
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3 DESIGN OF REINFORCED CONCRETE BEAMS AT ULS
10.3.1 RC GB 200x600 SS1
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 151- Internal Forces Envelope at ULS – GB 200x600

Maximum bottom bending moment at ULS Mu = + 33.9 KN.m


Maximum Top bending moment at ULS Mu = -43.1 KN.m
Maximum shear force at ULS Fz =41.9 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 123
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16

2. Section:

b = 200.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 43.10 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 315.65 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 43.10 (kN*m)
Load to resistance ratio: 55.6 %
Neutral axis location: c = 34.13 (mm)
Internal forces lever arm: L = 545.49 (mm)
Strains in concrete: b = 1.30 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 124
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 41.90 (kN)
4. Results :

Reinforcement
Strirrups not required
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 76.87 (kN)
Nominal shear capacity provided by:
concrete = 102.49 (kN)
shear reinforcement = 0.00 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 125
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.2 RC GB 200x750 SS1
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 152- Internal Forces Envelope at ULS – GB 200x750

Maximum bottom bending moment at ULS Mu = +91.8 KN.m


Maximum Top bending moment at ULS Mu = - 108.2 KN.m
Maximum shear force at ULS Fz = 118.4 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 126
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 200.00 (mm)
h = 750.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 108.20 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 400.20 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 108.20 (kN*m)
Load to resistance ratio: 86.9 %
Neutral axis location: c = 43.27 (mm)
Internal forces lever arm: L = 691.61 (mm)
Strains in concrete: b = 1.30 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 127
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 750.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 118.40 (kN)
4. Results :

Reinforcement
Stirrups spacing = 340.00 (mm)
maximum allowable = 347.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 218.49 (kN)
Nominal shear capacity provided by:
concrete = 130.67 (kN)
shear reinforcement = 160.65 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 128
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.3 RC GB 200x600 SS2
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 153- Internal Forces Envelope at ULS – GB 200x600

Maximum bottom bending moment at ULS Mu = +34.2 KN.m


Maximum Top bending moment at ULS Mu = -37.7 KN.m
Maximum shear force at ULS Fz = 55.4 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 129
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 200.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 37.70 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 315.65 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 37.70 (kN*m)
Neutral axis location: c = 34.13 (mm)
Internal forces lever arm: L = 545.49 (mm)
Strains in concrete: b = 1.30 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa) Safety factor: not significant case

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 130
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 55.20 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 195.87 (kN)
Nominal shear capacity provided by:
concrete = 102.49 (kN)
shear reinforcement = 158.67 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 131
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.4 RC GB 200x750 SS2
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 154- Internal Forces Envelope at ULS – GB 200x750

Maximum bottom bending moment at ULS Mu = +99.1 KN.m


Maximum Top bending moment at ULS Mu = -117.7 KN.m
Maximum shear force at ULS Fz = 133.7 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 132
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16

2. Section:

b = 200.00 (mm)
h = 750.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 117.70 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 400.20 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 117.70 (kN*m)
Load to resistance ratio: 94.5 %
Neutral axis location: c = 43.27 (mm)
Internal forces lever arm: L = 691.61 (mm)
Strains in concrete: b = 1.30 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 133
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 750.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 133.70 (kN)
4. Results :

Reinforcement
Stirrups spacing = 340.00 (mm)
maximum allowable = 347.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 218.49 (kN)
Nominal shear capacity provided by:
concrete = 130.67 (kN)
shear reinforcement = 160.65 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 134
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.5 RC GB 200x850 SS3
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 155- Internal Forces Envelope at ULS – GB 200x850

Maximum bottom bending moment at ULS Mu = +65.3 KN.m


Maximum Top bending moment at ULS Mu = -135.1 KN.m
Maximum shear force at ULS Fz = 89.6 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 135
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 200.00 (mm)
h = 850.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 135.10 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 456.56 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 135.10 (kN*m)
Load to resistance ratio: 83.3 %
Neutral axis location: c = 49.37 (mm)
Internal forces lever arm: L = 789.02 (mm)
Strains in concrete: b = 1.30 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 136
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 850.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 89.64 (kN)
4. Results :

Reinforcement
Stirrups spacing = 390.00 (mm)
maximum allowable = 397.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 232.24 (kN)
Nominal shear capacity provided by:
concrete = 149.46 (kN)
shear reinforcement = 160.20 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 137
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.6 RC GB 200x1200 SS3
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 156- Internal Forces Envelope at ULS – GB 200x1200

Maximum bottom bending moment at ULS Mu = +193.2 KN.m


Maximum Top bending moment at ULS Mu = - 184.35 KN.m
Maximum shear force at ULS Fz = 166 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 138
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 200.00 (mm)
h = 1200.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 193.20 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 653.84 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 193.20 (kN*m)
Load to resistance ratio: 58.1 %
Neutral axis location: c = 70.70 (mm)
Internal forces lever arm: L = 1129.95 (mm)
Strains in concrete: b = 1.30 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 139
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 1200.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 166.00 (kN)
4. Results :

Reinforcement
Stirrups spacing = 570.00 (mm)
maximum allowable = 572.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 279.79 (kN)
Nominal shear capacity provided by:
concrete = 215.22 (kN)
shear reinforcement = 157.83 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 140
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.7 RC GB 200x600 SS4
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 157- Internal Forces Envelope at ULS – GB 200x600

Maximum bottom bending moment at ULS Mu = +79.7 KN.m


Maximum Top bending moment at ULS Mu = -79.4 KN.m
Maximum shear force at ULS Fz = 132.86 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 141
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 200.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 79.70 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 325.44 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 79.70 (kN*m)
Load to resistance ratio: 99.8 %
Neutral axis location: c = 35.19 (mm)
Internal forces lever arm: L = 545.04 (mm)
Strains in concrete: b = 1.34 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 142
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 132.86 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 195.87 (kN)
Nominal shear capacity provided by:
concrete = 102.49 (kN)
shear reinforcement = 158.67 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 143
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.8 RC GB 200x750 SS4
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 158- Internal Forces Envelope at ULS – GB 200x750

Maximum bottom bending moment at ULS Mu = +70.4 KN.m


Maximum Top bending moment at ULS Mu = - 90.3 KN.m
Maximum shear force at ULS Fz = 152.3 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 144
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 200.00 (mm)
h = 750.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 90.30 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 400.20 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 90.30 (kN*m)
Load to resistance ratio: 72.5 %
Neutral axis location: c = 43.27 (mm)
Internal forces lever arm: L = 691.61 (mm)
Strains in concrete: b = 1.30 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 145
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 750.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 152.30 (kN)
4. Results :

Reinforcement
Stirrups spacing = 340.00 (mm)
maximum allowable = 347.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 218.49 (kN)
Nominal shear capacity provided by:
concrete = 130.67 (kN)
shear reinforcement = 160.65 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 146
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.9 RC B 200x600 SS1
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 159- Internal Forces Envelope at ULS – B 200x600

Maximum bottom bending moment at ULS Mu = + 88.4 KN.m


Maximum Top bending moment at ULS Mu = - 136.45 KN.m
Maximum shear force at ULS Fz = 178.7 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 147
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 200.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 136.50 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 569.04 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.5 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 136.50 (kN*m)
Load to resistance ratio: 99.9 %
Neutral axis location: c = 61.53 (mm)
Internal forces lever arm: L = 533.85 (mm)
Strains in concrete: b = 2.47 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 148
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 178.70 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 195.87 (kN)
Nominal shear capacity provided by:
concrete = 102.49 (kN)
shear reinforcement = 158.67 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 149
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.10 RC B400x600 SS1
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 160- Internal Forces Envelope at ULS – B 400x600

Maximum bottom bending moment at ULS Mu = +74.66 KN.m


Maximum Top bending moment at ULS Mu = -459.8 KN.m
Maximum shear force at ULS Fz = 234.9 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 150
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 400.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 459.80 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1986.53 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.9 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 459.80 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 107.40 (mm)
Internal forces lever arm: L = 514.35 (mm)
Strains in concrete: b = 3.00 (‰)
in steel: s = 12.64 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 151
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 400.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 234.90 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 52.25 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 272.73 (kN)
Nominal shear capacity provided by:
concrete = 204.97 (kN)
shear reinforcement = 158.67 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 152
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.11 RC B800x600 SS1
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 161- Internal Forces Envelope at ULS – B 800x600

Maximum bottom bending moment at ULS Mu = +592.9 KN.m


Maximum Top bending moment at ULS Mu = - 886.7 KN.m
Maximum shear force at ULS Fz = 442.65 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 153
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16

2. Section:

b = 800.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 886.74 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 3817.85 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.9 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 886.74 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 103.21 (mm)
Internal forces lever arm: L = 516.14 (mm)
Strains in concrete: b = 3.00 (‰)
in steel: s = 13.28 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 154
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 8 /shear area: 628.32 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 800.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 442.65 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 783.48 (kN)
Nominal shear capacity provided by:
concrete = 409.95 (kN)
shear reinforcement = 634.69 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 155
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.12 RC B 200x600 SS2
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 162- Internal Forces Envelope at ULS – B 200x600

Maximum bottom bending moment at ULS Mu = +50.4 KN.m


Maximum Top bending moment at ULS Mu = - 118 KN.m
Maximum shear force at ULS Fz = 151.7 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 156
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16

2. Section:

b = 200.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 118.00 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 487.78 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.4 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 118.00 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 52.74 (mm)
Internal forces lever arm: L = 537.58 (mm)
Strains in concrete: b = 2.08 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 157
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 151.70 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 195.87 (kN)
Nominal shear capacity provided by:
concrete = 102.49 (kN)
shear reinforcement = 158.67 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 158
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.13 RC B 400x600 SS2
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 163- Internal Forces Envelope at ULS – B 400x600

Maximum bottom bending moment at ULS Mu = +108.96 KN.m


Maximum Top bending moment at ULS Mu = - 448.58 KN.m
Maximum shear force at ULS Fz =191 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 159
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16

2. Section:

b = 400.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 448.60 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1933.56 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.9 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 448.60 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 104.54 (mm)
Internal forces lever arm: L = 515.57 (mm)
Strains in concrete: b = 3.00 (‰)
in steel: s = 13.07 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 160
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 4 /shear area: 314.16 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 400.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 191.00 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 391.74 (kN)
Nominal shear capacity provided by:
concrete = 204.97 (kN)
shear reinforcement = 317.34 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 161
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.14 RC B 800x600 SS2
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 164- Internal Forces Envelope at ULS – B 800x600

Maximum bottom bending moment at ULS Mu = + 593.5 KN.m


Maximum Top bending moment at ULS Mu = - 752.7 KN.m
Maximum shear force at ULS Fz = 676.62 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 162
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 800.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 752.70 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 3196.53 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.7 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 752.70 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 86.41 (mm)
Internal forces lever arm: L = 523.27 (mm)
Strains in concrete: b = 3.00 (‰)
in steel: s = 16.44 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 163
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 8 /shear area: 628.32 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 800.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 676.60 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 783.48 (kN)
Nominal shear capacity provided by:
concrete = 409.95 (kN)
shear reinforcement = 634.69 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 164
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.15 RC B 200x600 SS3
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 165- Internal Forces Envelope at ULS – B 200x600

Maximum bottom bending moment at ULS Mu = +86.2 KN.m


Maximum Top bending moment at ULS Mu = - 148.12 KN.m
Maximum shear force at ULS Fz = 184.2 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 165
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 200.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 148.12 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 619.25 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.6 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 148.12 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 66.96 (mm)
Internal forces lever arm: L = 531.54 (mm)
Strains in concrete: b = 2.72 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 166
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 184.20 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 195.87 (kN)
Nominal shear capacity provided by:
concrete = 102.49 (kN)
shear reinforcement = 158.67 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 167
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.16 RC B 400x600 SS3
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 166- Internal Forces Envelope at ULS – B 400x600

Maximum bottom bending moment at ULS Mu = +72.79 KN.m


Maximum Top bending moment at ULS Mu = - 525.4 KN.m
Maximum shear force at ULS Fz = 275.4 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 168
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 400.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 525.40 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 2302.44 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 1.0 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 525.40 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 124.48 (mm)
Internal forces lever arm: L = 507.09 (mm)
Strains in concrete: b = 3.00 (‰)
in steel: s = 10.50 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 169
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 4 /shear area: 314.16 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 400.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 275.40 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 391.74 (kN)
Nominal shear capacity provided by:
concrete = 204.97 (kN)
shear reinforcement = 317.34 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 170
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.17 RC B 800x500 SS3
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 167- Internal Forces Envelope at ULS – B 800x500

Maximum bottom bending moment at ULS Mu = +276.1 KN.m


Maximum Top bending moment at ULS Mu = - 223.6 KN.m
Maximum shear force at ULS Fz = 185.94 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 171
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 800.00 (mm)
h = 500.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 276.10 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1382.56 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.4 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 276.10 (kN*m)
Load to resistance ratio: 99.9 %
Neutral axis location: c = 37.37 (mm)
Internal forces lever arm: L = 444.12 (mm)
Strains in concrete: b = 1.77 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 172
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 8 /shear area: 628.32 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 800.00 (mm)
h = 500.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 185.94 (kN)
4. Results :

Reinforcement
Stirrups spacing = 220.00 (mm)
maximum allowable = 222.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 728.20 (kN)
Nominal shear capacity provided by:
concrete = 334.79 (kN)
shear reinforcement = 636.14 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 173
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.18 RC B 800x600 SS3
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 168- Internal Forces Envelope at ULS – B 800x600

Maximum bottom bending moment at ULS Mu = +315.9 KN.m


Maximum Top bending moment at ULS Mu = -26 KN.m
Maximum shear force at ULS Fz = 159.89 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 174
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16

2. Section:

b = 800.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 315.90 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1287.58 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.3 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 315.90 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 34.81 (mm)
Internal forces lever arm: L = 545.21 (mm)
Strains in concrete: b = 1.33 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 175
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 8 /shear area: 628.32 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 800.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 159.89 (kN)
4. Results :

Reinforcement
Strirrups not required
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 307.46 (kN)
Nominal shear capacity provided by:
concrete = 409.95 (kN)
shear reinforcement = 0.00 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 176
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.19 RC B 800x700 SS3
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 169- Internal Forces Envelope at ULS – B 800x700

Maximum bottom bending moment at ULS Mu = +894.1 KN.m


Maximum Top bending moment at ULS Mu = -604.7 KN.m
Maximum shear force at ULS Fz =350.4 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 177
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 800.00 (mm)
h = 700.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 894.10 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 3187.28 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.6 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 894.10 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 86.16 (mm)
Internal forces lever arm: L = 623.38 (mm)
Strains in concrete: b = 3.00 (‰)
in steel: s = 19.98 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 178
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 8 /shear area: 628.32 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 800.00 (mm)
h = 700.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 350.40 (kN)
4. Results :

Reinforcement
Stirrups spacing = 320.00 (mm)
maximum allowable = 322.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 839.10 (kN)
Nominal shear capacity provided by:
concrete = 485.10 (kN)
shear reinforcement = 633.69 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 179
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.20 RC B 200x600 SS4
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 170- Internal Forces Envelope at ULS – B 200x600

Maximum bottom bending moment at ULS Mu = + 71.1 KN.m


Maximum Top bending moment at ULS Mu = - 142.4 KN.m
Maximum shear force at ULS Fz = 186.4 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 180
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16

2. Section:

b = 200.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 142.40 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 594.04 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.5 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 142.40 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 64.23 (mm)
Internal forces lever arm: L = 532.70 (mm)
Strains in concrete: b = 2.59 (‰)
in steel: s = 20.00 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 181
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 2 /shear area: 157.08 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 200.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 186.40 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 195.87 (kN)
Nominal shear capacity provided by:
concrete = 102.49 (kN)
shear reinforcement = 158.67 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 182
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.21 RC B 400x600 SS4

Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 171- Internal Forces Envelope at ULS – B 400x600

Maximum bottom bending moment at ULS Mu = + 54.2 KN.m


Maximum Top bending moment at ULS Mu = -423.2 KN.m
Maximum shear force at ULS Fz = 164.6 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 183
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16

2. Section:

b = 400.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 423.20 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 1814.45 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.8 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 423.20 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 98.10 (mm)
Internal forces lever arm: L = 518.31 (mm)
Strains in concrete: b = 3.00 (‰)
in steel: s = 14.13 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 184
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 4 /shear area: 314.16 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 400.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 164.60 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 391.74 (kN)
Nominal shear capacity provided by:
concrete = 204.97 (kN)
shear reinforcement = 317.34 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 185
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.3.22 RC B 800x600 SS4
Figures below show the results of internal force envelope diagrams at ultimate limit
state of reinforced concrete beams at Transportation Unit.

Figure 172- Internal Forces Envelope at ULS – B 800x600

Maximum bottom bending moment at ULS Mu = +560.4 KN.m


Maximum Top bending moment at ULS Mu = -810.65 KN.m
Maximum shear force at ULS Fz = 384 KN

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 186
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for simple bending

Concrete: fc' = 32.0 (MPa) Reinforcing steel: fy = 500.0 (MPa)


1 = 0.85
 Code: ACI 318-02
 Average diam. of bottom reinf.: 16
 Average diam. of top reinf. : 16
2. Section:

b = 800.00 (mm)
h = 600.00 (mm)
ds = 40.00 (mm)
d' = 40.00 (mm)

3. Loads:
Factored bending moment: 810.65 (kN*m)
Strength reduction factor  0.90

4. Results:
Reinforcement:
Theoretical area: As = 3462.88 (mm2) A's = 0.00 (mm2)
Reinforcement ratio:  = 0.8 (%)
min = 0.3 (%)
max = 1.9 (%)
Case analysis:
O
Case N 1: ULS My= 810.65 (kN*m)
Load to resistance ratio: 100.0 %
Neutral axis location: c = 93.61 (mm)
Internal forces lever arm: L = 520.21 (mm)
Strains in concrete: b = 3.00 (‰)
in steel: s = 14.95 (‰)
Stresses in steel: tensioned s = 500.0 (MPa)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 187
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Section design for shear forces

Concrete: normal concrete fc' = 32.0 (MPa)


Stirrups: yield strength fy = 500.0 (MPa)
size 10 /one leg area: 78.54 (mm2)/
number of legs 8 /shear area: 628.32 (mm2)/
stirrup angle 90.0 deg

 Code: ACI 318-02


 Type of element BEAM

2. Section :

b = 800.00 (mm)
h = 600.00 (mm)
d = 40.00 (mm)
3. Data:

Applied loads:
shear force: 384.00 (kN)
4. Results :

Reinforcement
Stirrups spacing = 270.00 (mm)
maximum allowable = 272.74 (mm)
minimum effective = 104.50 (mm)
Section resistance:
Strength reduction factor  = 0.75
Effective shear strength = 783.48 (kN)
Nominal shear capacity provided by:
concrete = 409.95 (kN)
shear reinforcement = 634.69 (kN)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 188
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4 DESIGN OF REINFORCED CONCRETE COLUMNS

Figures below show the various sizes of columns were conducted by S-Concrete.

Figure 173- SS1 Columns Setting Layout

Figure 174- SS2 Columns Setting Layout

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 189
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
Figure 175- SS3 Columns Setting Layout

Figure 176- SS4 Columns Setting Layout

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 190
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.1 RC C 200x600 Design result SS1

Figure 177-Columns Forces - C (200x600)

Figure 178-Columns Reinforcement - C (200x600)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 191
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.2 RC CL 600x600 Design result

Figure 179-Columns Forces - CL (600x600)

Figure 180-Columns Reinforcement - CL (600x600)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 192
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.3 RC C 600x400 Design result

Figure 181-Columns Forces - C (600x400)

Figure 182-Columns Reinforcement - C (600x400)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 193
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.4 RC C 200x800 Design result

Figure 183-Columns Forces - C (200x800)

Figure 184-Columns Reinforcement - C (200x800)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 194
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.5 RC C 200x600 Design result SS2

Figure 185-Columns Forces - C (200x600)

Figure 186-Columns Reinforcement - C (200x600)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 195
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.6 RC CL 600x600 Design result

Figure 187-Columns Forces - CL (600x600)

Figure 188-Columns Reinforcement - CL (600x600)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 196
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.7 RC C 600x400 Design result

Figure 189-Columns Forces - C (600x400)

Figure 190-Columns Reinforcement - C (600x400)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 197
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.8 RC C 200x800 Design result

Figure 191-Columns Forces - C (200x800)

Figure 192-Columns Reinforcement - C (200x800)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 198
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.9 RC C 200x600 Design result SS3

Figure 193-Columns Forces - C (200x600)

Figure 194-Columns Reinforcement - C (200x600)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 199
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.10 RC CL 600x600 Design result

Figure 195-Columns Forces - CL (600x600)

Figure 196-Columns Reinforcement - CL (600x600)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 200
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.11 RC C 600x400 Design result

Figure 197-Columns Forces - C (600x400)

Figure 198-Columns Reinforcement - C (600x400)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 201
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.12 RC C 200x800 Design result

Figure 199-Columns Forces - C (200x800)

Figure 200-Columns Reinforcement - C (200x800)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 202
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.13 RC C 200x600 Design result SS4

Figure 201-Columns Forces - C (200x600)

Figure 202-Columns Reinforcement - C (200x600)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 203
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.14 RC CL 600x600 Design result

Figure 203-Columns Forces - CL (600x600)

Figure 204-Columns Reinforcement - CL (600x600)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 204
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.15 RC C 600x400 Design result

Figure 205-Columns Forces - C (600x400)

Figure 206-Columns Reinforcement - C (600x400)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 205
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
10.4.16 RC C 200x800 Design result

Figure 207-Columns Forces - C (200x800)

Figure 208-Columns Reinforcement - C (200x800)

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 206
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018
11.0 CONCLUSION
The concrete elements of the structure have been found to be satisfactory for the
given set of loading conditions.

CLIENT: CONSULTANT: OWNER:


ALBANDARY ENGINEERING TRADING & MZ & PARTNERS W.L.L QATAR ARMED FORCES
CONTRACTING W.L.L
STRUCTURAL CONSULTANT: REPORT NUMBER: MZP PROJECT NO.:
MZ & PARTNERS W.L.L SS STR: GP 17210

Project SUBSTATIONS - AL ZAEEM AIR ACADEMY PROJECT AT AL UDEID Sheet: Page 207
STRUCTURAL DESIGN REPORT DATE: MAY.03.2018