CONCRETE MIX DESIGN & CONTROL REPORT

Lab.Ref.No Type B -T004 W/C 0.43 Number of sample 6 Date 8.08.2019


Project Port Sector Rehabilitation Project (II), Package 4A Slump 150-200 Admixture 0.7
Concrete Class Class B - 24 Mpa Dmax 20mm Size of sample 15*30
AGGREGATE GRADATION AGGREGATES MIX Slump Temprature
o
Gradation Material Weight(Kg) Time cm C
100
37.5 100 100 100 SIEVE FINE COARSE MIX
Cement 330 1 min. 19 25.6
20 97 90 100 C-33 C-33 Water 142 30 min 10 29.4
80 5.0 41 40 60 mm Fine Aggregate 0-
759
5 mm
mm

For 1 m3
0.6 20 13 23
Coarse
0.2 1 0 5 50 mm 100 100
60 Aggregate 5-19 1145
25 mm 100 100 100.0 mm
% Passing

19 mm 100 94.5 96.7 Admixture 2.310


40 9.5 mm 100 43.7 TOTAL 2378
4.75 mm 98.1 3.4 41.3
2.36 mm 91.3 1.2
20
1.18 mm 69.8 0.9
0.600 mm 48.6 0.8 19.9
0 0.300 mm 11.5 0.7 CORRECTED WEIGHT OF MIX
0.1 1 10 100

Sieve Size (mm) 0.150 mm 1.7 0.6 1.0 Material 1000L 35L
0.075 mm 1.0 0.5 Cement 330 11.550
MIX CALCULATIONS FOR 1 m3 OF CONCRETE Water 158.2 5.535

MATERIAL CALCULATIONS Volume S.S.D GRAVITY WEIGHT % Mix 40.0 60 F.A.1 0 - 5 752 26.303
330 Dosage C.A.1 5 - 19 1136 39.766
CEMENT V = 104.8 3.150 330
3.150 Sp.Gr.of cement MATERİAL 0-5 5 19 Admixture 2.310 0.081
Water Moisture correction
WATER = 0.43 142 1 142
Cem. Moisture % 0.54 0.10
Total
AIR 2% 20.0 Absorbsion % 1.52 0.870 Water TOTAL 2378.1 83.2
Additive 2 1.06 2.310 -0.98 -0.77 0.00 -16.3
Vb= Total volume of cement+ water + air + addtv 268.8 REMARKS :Admixture Sika viscocrete F180G
STRENGTH ( N/ mm2)
Aggregate Aggr. volume Va = 1000 - Vb 731.2
F.A1

0-5 Volume = Va x FA1 % = 40 292.5 2.595 759 7 Day 28 Day Air content:%4.5
Sample No

1
C.A1

5 19 Volume = Va x CA1 % = 60 438.7 2.610 1145 Density : 2337


2
Total 1,000 2378 3

Avg.

AL FAYHA-QC ENGINEER CE QA/QC ENGINEER ENGINEER/EMPLOYER